ML20031B238
ML20031B238 | |
Person / Time | |
---|---|
Site: | Browns Ferry |
Issue date: | 09/22/1981 |
From: | Stello V NRC OFFICE OF INSPECTION & ENFORCEMENT (IE) |
To: | |
Shared Package | |
ML20031B237 | List: |
References | |
EA-81-083, EA-81-83, NUDOCS 8110010067 | |
Download: ML20031B238 (1) | |
Similar Documents at Browns Ferry | |
---|---|
Category:NOTICE OF VIOLATION OF A REGULATION
MONTHYEARML20129D2931996-07-19019 July 1996
[Table view]Notice of Violation from Insp on 960617-20.Violation Noted: During Test,Two Members of Security Force Failed to Detect Firearm Visible on x-ray & Take Action to Neutralize Possibility of Threat After Identifying Part of Firearm ML20205C6581996-02-14014 February 1996 Notice of Violation from Secretary of Labor Decision & Order .Violation Noted:On 930202 & 04,SWEC,discriminated Against D Harrison for Engaging in Protected Activities ML20244C4181989-04-10010 April 1989 Notice of Violation from Insp on 881208-31.Violations Noted: Prior to 881223,licensee Failed to Properly Establish Administrative Procedure for Control of Equipment ML20245J0501989-02-0202 February 1989 Notice of Violation from Insp on 881001-31.Violation Noted: Reactor Bldg & Refueling Floor Ventilation Radiation Monitor Calibr & Functional Test Not Performed on 881017 ML20195B2311988-10-25025 October 1988 Notice of Violation from Insp on 880701-31.Violation Noted:Failure to Generically Review Condition Adverse to Quality Repts SQN 871347,SQP 871003,SQP 871066 & Sqt 871304 within 70 Days of Initiation of Repts ML20154R8101988-09-22022 September 1988 Notice of Violation from Insp on 880612-30.Violation Noted: Condition Adverse to Quality Rept Not Generated During Conduct of Special Test 88-09, Diesel Generator Governor & Voltage Regulator Calibr on 880621 ML20155A9381988-09-19019 September 1988 Notice of Violation from Insp on 880711-15.Violation Noted: Licensee Line Mgt Became Aware That Four Temporarily Promoted Shift Engineers Did Not Meet Above Stds & Did Not Adequately Disposition Issue ML20154K8891988-09-12012 September 1988 Notice of Violation from Insp on 880501-0611.Violation Noted:Three Fire Brigade Members Who Entered Drywell for Fire Fighting Operations Not Qualified & Q-list Equipment Data Package (Sys 1) Not in Compliance W/Nuclear QA Manual ML20155J0411988-06-0303 June 1988 Notice of Violation from Insp on 880401-30.Violation Noted: Administrative Procedure PMP 0602.01 Found to Be Inadequate Due to Lack of Any Requirement or Guidance on Use of Draft Info in Preparation of Licensing Submittals ML20154P5641988-05-20020 May 1988 Notice of Violation from Insp on 880301-31.Violations Noted: Failure to Adhere to Tech Spec Administrative Controls Involving Plant Operations Review Committee Activities & Failure to Provide Required Retraining in Areas of Qa/Qc ML20151V2791988-04-20020 April 1988 Notice of Violation from Insp on 880314-21.Violations Noted: Loose Rivets Found on Refueling Floor within Control Zone & Accountability Records Did Not Identify Crews or Parts Missing on Ultrasonic Scanner Used in Vessel ML20150E5261988-03-24024 March 1988 Notice of Violation from Insp on 880101-31.Violation Noted: Activities Affecting Quality Not Being Accomplished Per Documented Procedures & Drawings in That Insp of One QC Accepted Pipe Support Revealed Deviations from Requirements ML20150B9291988-02-26026 February 1988 Notice of Violation from Insp on 871201-31.Violation Noted: Test Performed on Standby Gas Treatment Sys Train B on 871125 Did Not Comply W/Ansi N510-1975 ML20236W0991987-12-0303 December 1987 Notice of Violation from Insp on 871001-30.Violations Noted: Failure to Properly Control Measuring & Test Equipment & to Indicate Operating Status of Component Important to Safety Such That Inadvertent Operation Prevented ML20236B5121987-10-16016 October 1987 Notice of Violation from Insp on 870921-25.Violation Noted: Failure to Comply W/Disposal Site Conditions by Shipping Radwaste Drum W/Free Liquid ML20238E3311987-09-0202 September 1987 Notice of Violation from Insp on 870701-31.Violation Noted: Licensee Failure to Follow Site Director Std Procedure 23.2 Requirements in Maintaining Complete & Current Accountability Records of Site Byproduct Matl ML20236M0001987-08-0505 August 1987 Notice of Violation from Insp on 870601-30.Violation Noted:Failure to Properly Disposition Significant Condition Adverse to Quality Re 870303 Failure of Emergency Diesel Room Fire Dampers ML20215K2911987-06-15015 June 1987 Notice of Violation from Insp on 870301-0430 ML20213A5801987-04-14014 April 1987 Notice of Violation from Insp on 870209-13 & 17-20 ML20206F2071987-04-0808 April 1987 Notice of Violation from Insps on 870201-28 ML20206D3441987-03-30030 March 1987 Notice of Violation from Insp on 870224-27 ML20207U0161987-03-0404 March 1987 Notice of Violation from Insp on 861101-1231 ML20211A6191987-02-0505 February 1987 Notice of Violation from Insp on 861001-31 ML20210U6271987-02-0505 February 1987 Notice of Violation from Insp on 870105-09 ML20213A3931987-01-28028 January 1987 Notice of Violation from Insp on 860211-0523.Violation Noted:Failure to Complete Corrective Actions Re Maintaining Separation Between Safety Div I & II Circuits ML20213A3271987-01-28028 January 1987 Notice of Violations from Insps on 860211-0523.Violations Noted:Failure to Rept or Correct Condition Described in Nonconformance Rept SQNCEB8409 & Internal Procedures for SQNCEB8409 Failed to Meet Design Procedures ML20207L7591987-01-0202 January 1987 Notice of Violation from Insp on 861015-17 ML20210U0081986-09-29029 September 1986 Notice of Violation from Insp on 860728-0801 ML20205M1331986-04-0808 April 1986 Notice of Violation from Insp on 860310-12 ML20127B2811985-05-14014 May 1985 Notice of Violation from Insp on 850422-26 ML20127B4781985-05-13013 May 1985 Notice of Violation from Insp on 850401-04 ML20127F4931985-04-26026 April 1985 Notice of Violation from Insp on 850401-04 ML20127K7451985-04-24024 April 1985 Notice of Violation from Insp on 850226-0325 ML20062J9481982-07-0101 July 1982 Notice of Violation from Insp on 820526-0625 ML20058H5131982-06-0909 June 1982 Notice of Violation from Insp on 820503-04 ML20058B9031982-06-0404 June 1982 Notice of Violation from Insp on 820512-19 ML20062K0001982-06-0303 June 1982 Notice of Violation from Insp on 820426-0525 ML20054K2651982-05-17017 May 1982 Notice of Violation from Insp on 820326-0425 ML20054K2291982-04-29029 April 1982 Notice of Violation from Insp on 820322-26 & 29-31 ML20053E0191982-04-15015 April 1982 Notice of Violation from Insp on 820226-0325 ML20054D9231982-02-23023 February 1982 Notice of Violation from Insp on 820126-29 ML20050Q9311982-01-21021 January 1982 Notice of Violation from Insp on 811126-1225 ML20041F7731982-01-12012 January 1982 Notice of Violation from Insp on 811130-1204 ML20039B5981981-11-0505 November 1981 Notice of Violation from Emergency Preparedness Appraisal on 810713-24 ML20032D2951981-09-28028 September 1981 Notice of Violation from Insp on 810727-0825 ML20031B2381981-09-22022 September 1981 Notice of Violation for Failure to Meet Requirement That Prompt Public Notification Sys Be Installed by 810701 1996-07-19 Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS MONTHYEARIR 05000259/19990051999-10-0101 October 1999
[Table view]Insp Repts 50-259/99-05,50-260/99-05 & 50-296/99-05 on 990725-0904.No Violations Noted.Major Areas Inspected: Operations,Maintenance,Engineering & Plant Support PNO-II-97-014, on 970305,Unit 3 Experienced Loss of Offsite Power & Declared Notification of Unusual Event.Unit 2 Operating at 100 Percent During Event & Unaffected.Unit 1 in Long Term Shutdown Condition & Also Unaffected1997-03-0505 March 1997 PNO-II-97-014:on 970305,Unit 3 Experienced Loss of Offsite Power & Declared Notification of Unusual Event.Unit 2 Operating at 100 Percent During Event & Unaffected.Unit 1 in Long Term Shutdown Condition & Also Unaffected ML20138M0061997-01-13013 January 1997 EN-97-003:notice of Order Prohibiting Involvement in NRC- Licensed Activities (Effective Immediately) Issued to Jr Byrum.Action Based on NRC Investigation & Testimony Before DOL IR 05000260/19960991996-10-16016 October 1996 SALP Repts 50-260/96-99 & 50-296/96-99 for Period 950319- 960907 ML20129D2931996-07-19019 July 1996 Notice of Violation from Insp on 960617-20.Violation Noted: During Test,Two Members of Security Force Failed to Detect Firearm Visible on x-ray & Take Action to Neutralize Possibility of Threat After Identifying Part of Firearm IR 05000259/19960071996-07-19019 July 1996 Partially Withheld Insp Repts 50-259/96-07,50-260/96-07 & 50-296/96-07 on 960617-21 (Ref 10CFR73.21(c)(2)).Violations Noted.Major Areas Inspected:Aspects of Security Program for Power Reactors,Including Detection & Assessment Aids ML20205C6581996-02-14014 February 1996 Notice of Violation from Secretary of Labor Decision & Order .Violation Noted:On 930202 & 04,SWEC,discriminated Against D Harrison for Engaging in Protected Activities IR 05000259/19930371993-11-0303 November 1993 Partially Withheld Insp Repts 50-259/93-37,50-260/93-37 & 50-296/93-37 on 931004-08.Noncited Violation Identified. Major Areas Inspected:Security Program Plans,Alarm Station & Communication,Access Controls & Personnel IR 05000259/19930091993-05-26026 May 1993 Partially Withheld Insp Repts 50-259/93-09,50-260/93-09 & 50-296/93-09 on 930426-30 (Ref 10CFR73.21).Violation Noted But Not Cited.Major Areas Inspected:Physical Security Program for Power Reactors IR 05000259/19930061993-03-18018 March 1993 Insp Repts 50-259/93-06,50-260/93-06 & 50-296/93-06 on 930222-26.Non-cited Violations Noted.Major Areas Inspected: Mgt Support,Physical Barriers,Protected & Vital Areas,Access Control & Security Communications.Partially Withheld PNO-II-91-039, on 910625,licensee Mgt Completed Third Mgt Assessment After Completion of HPCI & RCIC Quick Start Testing1991-06-26026 June 1991 PNO-II-91-039:on 910625,licensee Mgt Completed Third Mgt Assessment After Completion of HPCI & RCIC Quick Start Testing IR 05000259/19910141991-04-22022 April 1991 Insp Repts 50-259/91-14,50-260/91-14 & 50-296/91-14 on 910325-29.No Violations Noted.Major Areas Inspected:Valve Operators,Level Switches,Temp Elements,Level Transmitters, Flow Switches,Terminal Blocks & Junction Boxes IR 05000259/19910121991-04-16016 April 1991 Insp Repts 50-259/91-12,50-260/91-12 & 50-296/91-12 on 910315-20.No Violations Noted.Major Areas Inspected:Test Procedures,Test Preparation,Test Performance & Test Results of Primary Containment Integrated Leak Rate Test IR 05000259/19910021991-03-18018 March 1991 Insp Repts 50-259/91-02,50-260/91-02 & 50-296/91-02 on 910119-0215.Non-cited Violations Noted.Major Areas Inspected:Surveillance,Maint,Operational Safety,Mods,Post Mod Testing,Esfs Walkdown,Standby Liquid Control & Mgt IR 05000259/19900221990-12-10010 December 1990 Insp Repts 50-259/90-22,50-260/90-22 & 50-296/90-22 on 900625-29.No Violations Noted.Major Areas Inspected:Followup of BFN Implementation of EQ Program to Comply W/Requirements of 10CFR50.49 IR 05000259/19900201990-08-13013 August 1990 Insp Repts 50-259/90-20,50-260/90-20 & 50-296/90-20 on 900625-29 & 0709-13.No Violations or Deviations Noted.Major Areas Inspected:Corrective Action Program Implementation & Quality Verification Activities IR 05000266/19900121990-06-0808 June 1990 Enforcement Conference Repts 50-266/90-12 & 50-301/90-12 on 900525.Violations Noted.Major Areas Discussed:Licensee Apparent Recurrent High Radiation Area Barrier Violations & Weaknesses in Radiation Protection Program IR 05000259/19900121990-04-24024 April 1990 Partially Withheld Insp Repts 50-259/90-12,50-260/90-12 & 50-296/90-12 on 900404 (Ref 10CFR2.790(d) & 73.21). Violations Noted.Major Areas Inspected:Personnel Access Control & Safeguards Contingency Plan Implementation IR 05000259/19900041990-03-0808 March 1990 Partially Withheld Insp Repts 50-259/90-04,50-260/90-04 & 50-296/90-04 (Ref 10CFR2.790(d) & 73.21).No Violations or Deviations Noted.Major Areas Inspected:Physical Security Program for Power Reactors,Including Mgt Support & Audits IR 05000269/19890391990-02-22022 February 1990 Insp Repts 50-269/89-39,50-270/89-39 & 50-287/89-39 on 891212-15 & 18-20.No Violations or Deviations Noted.Major Areas inspected:post-refueling Startup Tests of Unit 3 & Core Performance Surveillances on Units 1 & 2 IR 05000260/19890621990-02-13013 February 1990 Insp Rept 50-260/89-62 on 891109-1213.No Violations Noted. Major Areas Inspected:Design of CRD Housing Lateral Restraint,Design of Restraint Beam Assembly & Calculation of Equivalent Spring Constant K1 & K2 IR 05000260/19890421990-02-13013 February 1990 Insp Rept 50-260/89-42 on 891106-10.Major Areas Inspected: Responses to Open Items in Rept 50-260/89-32,util Final Resolution of Control Rod Drive Housing Upgrade Program & Potential Buckling of Reactor Vessel Skirt Support IR 05000260/19890591990-02-0606 February 1990 Insp Rept 50-260/89-59 on 891204-08.Open Items Noted Re Ampacity Calculations,Proper Cable Separation & Spec for Installation of Instrument Sense Lines.Major Areas Inspected:Electrical Issues in Nuclear Performance Plan IR 05000260/19890361989-09-21021 September 1989 Insp Rept 50-260/89-36 on 890828-0901.No Violations Noted. Major Areas Inspected:Small Bore Piping & Instrument Tubing Program IR 05000260/19890301989-09-18018 September 1989 Insp Rept 50-260/89-30 on 890313-24.No Violations Noted. Major Areas Inspected:Essential Design Calculations Under Civil Calculation Review Program IR 05000260/19890311989-07-13013 July 1989 Insp Rept 50-260/89-31 on 890426-0628.Open Issues Noted. Major Areas Inspected:Design Calculations for Seismic Design Program,Including Generation & Transfer of Seismic Loads & Impact Evaluation of Primary Sys IR 05000260/19880391989-06-17017 June 1989 Insp Rept 50-260/88-39 on 881219-22.Six Out of Eight Open Items Reviewed Closed.Major Areas Inspected:Techniques, Procedures & Criteria Used for Generating New Amplified Response Spectra (Ars) & Util Responses to Open Items IR 05000260/19890211989-06-14014 June 1989 Insp Rept 50-260/89-21 on 890123-24.Two of Three Items Reviewed During Insp Considered Closed.Major Areas Inspected:Responses to Three Open Items Identified in Insp Rept 50-260/88-38,including CSG-14,CSG-23 & CSG-26 IR 05000260/19890151989-05-17017 May 1989 Insp Rept 50-260/89-15 on 890123-0203.Open Item Noted Re Calculations Associated W/Ie Bulletins 79-14 & 79-02 on safety-related Piping.Major Areas Inspected:Design Criteria Documents & Calculations for safety-related Piping IR 05000259/19890061989-05-0303 May 1989 Insp Repts 50-259/89-06,50-260/89-06 & 50-296/89-06 on 890130-0203 & 0214-0310.Violations & Deviations Noted.Major Areas Inspected:Adequacy of Testing,Calibr,Maint & Configuration Control of safety-related Instrumentation ML20244C4181989-04-10010 April 1989 Notice of Violation from Insp on 881208-31.Violations Noted: Prior to 881223,licensee Failed to Properly Establish Administrative Procedure for Control of Equipment IR 05000259/19880361989-04-0707 April 1989 Insp Repts 50-259/88-36,50-260/88-36 & 50-296/88-36 on 81208-31.Violations Noted.Major Areas Inspected:Plant Operations,Mgt Control Over Plant Activities & Work Control Process to Determine Readiness for Fuel Load ML20247G6941989-03-23023 March 1989 PNO-ADSP-89-001:on 890317,GE-supplied Cables in Nuclear Instrumentation Sys Found Deteriorated W/Rubber Insulation Brittle & Cracked W/Portions of Conductor Exposed.Ge Has Obtained Sample Cable for Further Analysis IR 05000259/19880351989-03-17017 March 1989 Insp Repts 50-259/88-35,50-260/88-35 & 50-296/88-35 on 881201-31.No Violations or Deviations Noted.Unresolved Items Noted Re Surveillance Testing & Missed Surveillance.Major Areas Inspected:Ros,Nrc Bulletins & Open Items IR 05000259/19890011989-03-0909 March 1989 Partially Withheld Insp Repts 50-259/89-01,50-260/89-01 & 50-296/89-01 on 890109-10.No Violations Noted.Major Areas Inspected:Corrective Actions to Notice of Violation & Program for Control & Accounting of SNM IR 05000259/19880331989-02-13013 February 1989 Insp Repts 50-259/88-33,50-260/88-33 & 50-296/88-33 on 881101-30.Violation Noted.Major Areas Inspected:Operational Safety Verification,Mods,Surveillance Observations,Sys Return to Svc,Status of 10CFR21 Repts & ROs IR 05000259/19880271989-02-13013 February 1989 Insp Repts 50-259/88-27,50-260/88-27 & 50-296/88-27 on 880823-890106.No Violations or Deviations Noted.Major Areas Inspected:Seismic Qualifications,Cleanliness Controls,Fire Protection,Surveillance Testing & Instrumentation ML20245J0501989-02-0202 February 1989 Notice of Violation from Insp on 881001-31.Violation Noted: Reactor Bldg & Refueling Floor Ventilation Radiation Monitor Calibr & Functional Test Not Performed on 881017 IR 05000259/19880321989-02-0101 February 1989 Corrected Insp Repts 50-259/88-32,50-260/88-32 & 50-296/88-32 on 881001-31.Violations Noted.Major Areas Inspected:Operational Safety Verification,Surveillance Observation,Mods,Sys Return to Svc & ROs ML20195B2311988-10-25025 October 1988 Notice of Violation from Insp on 880701-31.Violation Noted:Failure to Generically Review Condition Adverse to Quality Repts SQN 871347,SQP 871003,SQP 871066 & Sqt 871304 within 70 Days of Initiation of Repts IR 05000259/19880311988-10-24024 October 1988 Insp Repts 50-259/88-31,50-260/88-31 & 50-296/88-31 on 880719-22 & 0907-08.No Violations or Deviations Noted.Major Areas Inspected:Plant Regulatory Performance Improvement Program Action Item Implementation IR 05000259/19880211988-10-21021 October 1988 Insp Repts 50-259/88-21,50-260/88-21 & 50-296-88-21 on 880701-31.Violation & Unresolved Items Noted.Major Areas Inspected:Operational Safety,Maint Observations,Surveillance Testing Observations & Restart Test Program ML20195B2371988-10-21021 October 1988 Insp Repts 50-259/88-21,50-260/88-21 & 50-296-88-21 on 880701-31.Violation & Unresolved Items Noted.Major Areas Inspected:Operational Safety,Maint Observations,Surveillance Testing Observations & Restart Test Program IR 05000259/19880291988-09-28028 September 1988 Partially Withheld Insp Repts 50-259/88-29,50-260/88-29 & 50-296/88-29 on 880912-16 (Ref 10CFR2.790 & 73.21). Violations Noted in Area of Key Control.Major Areas Inspected:Security Organization,Records & Repts ML20154R8101988-09-22022 September 1988 Notice of Violation from Insp on 880612-30.Violation Noted: Condition Adverse to Quality Rept Not Generated During Conduct of Special Test 88-09, Diesel Generator Governor & Voltage Regulator Calibr on 880621 IR 05000259/19880261988-09-20020 September 1988 Insp Repts 50-259/88-26,50-260/88-26 & 50-296/88-26 on 880829-0902.No Violations or Deviations Noted.Major Areas Inspected:Emergency Preparedness,Including Programmatic Elements of Emergency Detection & Classification & Training ML20155A9381988-09-19019 September 1988 Notice of Violation from Insp on 880711-15.Violation Noted: Licensee Line Mgt Became Aware That Four Temporarily Promoted Shift Engineers Did Not Meet Above Stds & Did Not Adequately Disposition Issue ML20155A9561988-09-19019 September 1988 Insp Repts 50-259/88-22 & 50-260/88-22 & 50-296/88-22 on 880711-15.Violations Noted.Major Areas Inspected:Assessment of New Employee Concern IR 05000259/19880221988-09-19019 September 1988 Insp Repts 50-259/88-22 & 50-260/88-22 & 50-296/88-22 on 880711-15.Violations Noted.Major Areas Inspected:Assessment of New Employee Concern ML20154R8211988-09-15015 September 1988 Insp Repts 50-259/88-18,50-260/88-18 & 50-296/88-18 on 880612-30.Violations Noted.Major Areas Inspected:Operational Safety,Maint Observation,Independent Audits & Restart Test Program 1999-10-01 |
Text
p
=
1
.. O yj APPENDIX NOTICE OF VIOLATION Tennessee Valley Authority Docket Nos. 50-259 Browns Ferry Nuclear Power Plant 50-260 50-296 License Nos. DPR-33 DPR-52 DPR-68 EA 81-83 As a result of the July 27, 1981 submittal from Tennessee Valley Authority in response to the July 1,1981 NRC request for information on emergency planning and in accordance with Interim Enforcement Policy, 45 FR 66754 (October 7, 1980),
the following violation was identified:
10 CFR 50.54(s)(2) and Section IV.D.3 of Appendix E, require that by July 1, 1981, each nuclear power reactor licensee demonstrate that administrative and physical means have been established for alerting and providing prompt instructions to the public within the plume exposure pathway of the Emergency Planning Zone ~within about 15 minutes.
Contrary to the above, Tennessee Valley Authority was unable to demonstrate that means had been established for alerting and promptly providing public instruction within the plume exposure pathway of the Emergency Planning Zone within about 15 minutes.
This is a Severity Level IV violation.
(Supplement I)
Pursuant to the provisions of 10 CFR 2.201, Tennessee Valley Authority is hereby required to submit to this office within 30 days of the date of this Notice, a written statement or explanation in reply, including:
(1) admissico or denial of the alleged item of noncompliance; (2) the reasons for the item of noncompliance if admitted; (3) the corrective steps which have been taken and results achieved; (4) corrective steps which will be taken to avoid further items of noncompliance; and (5) the date when full compliance will be achieved.
Under the authority of Section 182 of the Atomic Energy Act of 1954, as amended, 42 U.S.C 2232, this response shall be submitted under oath or affirmation.
The responses directed by this Notice are not subject to the clearance procedures of the Office of Managment and Budget as required by the Paperwork Reduction Act of 1980, PL 96-511.
FOR THE NUCLEAR REGULATORY COMMISSION
/
(
Vic Stello, Jr., Director Office of Inspection and Enforcement Dated at Bethesda, Maryland this 22ndday of September 1981
~