ML20247G694

From kanterella
Jump to navigation Jump to search
PNO-ADSP-89-001:on 890317,GE-supplied Cables in Nuclear Instrumentation Sys Found Deteriorated W/Rubber Insulation Brittle & Cracked W/Portions of Conductor Exposed.Ge Has Obtained Sample Cable for Further Analysis
ML20247G694
Person / Time
Site: Browns Ferry  Tennessee Valley Authority icon.png
Issue date: 03/23/1989
From: Bearden W
Office of Nuclear Reactor Regulation
To:
References
PNO-ADSP-89-001, PNO-ADSP-89-1, NUDOCS 8904040297
Download: ML20247G694 (1)


Text

_ _ - _ _ _ _ _ . ._

l

. March 23, 1989 PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL. OCCURRENCE PNO-ADSP-89-01

.This preliminary notification constitutes EARLY notice of events of POSSIBLE safety or i public interest significance. The information is as initially received without verifi-L cation or evaluation, and is basically all that is known by ADSP staff on this date.

FACILITY: Tennessee Valley Authority Licensee Emergency Classification:

Browns Ferry Unit 2 Notification of Unusual Event Docket Nos. 50-259, 50-260 and 50-296 Alert Soddy Daisy, Tennessee Site Area Emergency General Emergency

_ X _Not Applicable

SUBJECT:

DETERIORATED NUCLEAR INSTRUMENTATION CABLES AT BROWNS FERRY

(

  • The licensee identified on March 17, 1989, that various cables in the Nuclear Instrumentation System had become deteriorated in that the rubber insulation is brittle and cracked with portions of the conductor exposed. The problem was identified in General Electric supplied power cables with Buna-S rubber insulation which are used in the Source.

Intermediate, and Average Power Range Instrumentation Systems at Browns Ferry. These cables are being replaced with properly qualified cable. The same type of cable may have been used on other Browns Ferry, General Electric supplied nuclear steam supply system components. Based on preliminary information recieved by TVA from General Electric on March 21, 1989, 17 other BWRs built between the late 1960s and 1971 also have this type cable. According to GE no prior problems with this type cable have been identified. GE has obtained a sample of the cable for further analysis to identify the reason for the deterioration and will be providing information to INP0 on the issue. A manual search of records at Browns Ferry is in progress to determine if any other components are affected.

This PN is being issued for information purposes only.

This information is current as if 11:00 p.m. CST on March 22.

Contact:

W. C. Bearden - 205-729-6196 DISTRIBUTION OWFN MNBB H-St. NL Mail: ADM:DMB O Chairman Zech XEUU ACRS RES D0T: Trans only Commissioner Roberts ARM PDR Commissioner Carr 0GC Commissioner Rogers NRC Ops Ctr Commissioner Curtiss INP0 SECY NMSS NSAC CA NRR OGC OIA Regional Offices GPA 01 RI Resident Office PA SLITP EDO DE Licensee:

Reactor Licensees) e S9040 9' 890323 pg _nse-e9-oot y aM ,

(

- _ _ _ -