Forwards Application for Amend to License DPR-59,revising Tech Spec 4.11.B.2, Crescent Area Ventilation to Require Calibr of Existing Temp Indicator Controllers or New Temp Control Switches
ML19354E034
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 01/16/1990
From: Brons J
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML19354E035 List:
References
JPN-90-011, JPN-90-11, NUDOCS 9001250273
Download: ML19354E034 (2)


Text

,

123 Main street c i~ White Plains,feewWk 10301 914 681S240

.- j M NmW&hr seaa c.are -

4# Authority lt%*c!2*"'  !

January 16, 1990 -l JPN-90-011 U. S. Nuclear Regulatory Commission Attn.: Document Control Desk-  ;

Mall Station P1137 Washington, D.C. 20555 j

SUBJECT:

James A. FitzPatrick Nuclear Power Plant Docket No. 50-333 Proposed Change to the Technical  !

Specifications Regarding Crescent Area i Unit Coolers improvement (JPTS-89-032) i

REFERENCE:

1. NYPA Letter JAFP-89-0284, W. Fernandez to U.S. NRC,  !

dated April 12,1989, responding to violations regarding the inoperability of the Crescent Area Unit Coolers.

{

Dear Sir; i This application for an amendment to the James A. FitzPatrick Technical  !

Specifications revises the crescent area cooler surveillance requirements to reflect the modifications to each coolor's control instrumentation. The change revises Specification l 4.11.B.2, " Crescent Area Ventilation," on page 239, to require calibration of the existing temperature indicator controllers or the new temperature control switches.

The crescent area coolers are being modified during and following the March 1990 - '

refueling outage to reduce the potential for silt accumulation (Reference 1). The existing configuration, in which temperature indicator controllers modulate temperature control valves in the service water system, will be eliminated. The new configuration will regulate crescent area air temperature by cycling the cooler fans. Temperature control switches

  • will be installed to turn the cooler fans on and off.

These modifications to crescent area coolers will be completed September 30,1990.

The Authority had originally intended to complete all cooler modifications by June,1990 (Reference 1); however, due to the upcoming refueling outage and the unavailability of laboratory testing facilities, the schedule has been extended. Laboratory testing is required for calibrating the custom flowmeters which are being installed on the coolers.

The coolers are scheduled to be modified one at a time consistent with the ou' of service provisions of Specification 3.11.B of the FitzPatrick Technical Specificatiotd. NRC staff approval of this change is requested by April,1990 to allow a phased implementation of the cooler modifications.

9001250273 900116 PDR ADOCK 05000333 I P PDC h t

I (

t

l(: : (

. -t f

Enclosed for filing is the signed original of a document entitled " Application for Amendment to Operating Ucense," with Attachments I and ll thereto, comprising a statement of the proposed change to the Technical Specifications and the associated Safety Evaluation. ,

in accordance with 10 CFR 50.91, a copy of this application and the associated ,

attachments are being provided to the designated New York State official.  ;

,i- Should you or your staff have any questions regarding the proposed changes, please contact Mrs. S. M. Toth of my staff.

1 Ve truly yours, Ihn .Brons

  • Executive Vice President

/

Nuclear Generation N.]

cc: U. S. Nuclear Regulatory Commission -

475 Allendale Road King of Prussia, PA 19406 Office of the Resident Inspector U. S. Nuclear Regulatory Commission P. O. Box 136 Lycoming, NY 13093 Mr. David E. LaBarge Project Directorate I 1 Division of Reactor Projects- 1/11 U. S. Nuclear Regulatory Commission Mail Step 14 B2 I. Washington, DC 20555 Ms. Donna Ross New York State Energy Office >