|
---|
Category:LICENSEE EVENT REPORT (SEE ALSO AO
MONTHYEARML20024J2601994-10-0404 October 1994 LER 94-006-00:on 940913,automatic Reactor/Turbine Trip Occurred on Over Power Differential Temperature.Caused by Equipment Failure.Replaced Relay & Evaluated Failure Rate of Types of relays.W/941004 Ltr ML20029D1011994-04-20020 April 1994 LER 93-003-01:on 930925,reactor Tripped Due to Inadvertent Closure of Msiv.Caused by Inadequate Checking.Corrective Actions:Cros Throttled CA Flow & Entered Procedure EP/2/A/5000/01.W/940420 Ltr ML20046D5871993-08-17017 August 1993 LER 93-008-00:on 930718,reactor Tripped & Auxiliary Feedwater Sys Automatic Start Due to low-low-level in SG 1A. Developed General Troubleshooting procedure.W/930817 Ltr ML20045H2421993-07-12012 July 1993 LER 93-006-00:on 930612,automatic Reactor Trip Initiated by intermediate-range Channel N35 Hi Flux Reactor Trip Bistable.Caused by Blown Fuse in Channel.Entire Drawer Replaced & Channel Placed Back in svc.W/930712 Ltr ML20024G9751991-05-0909 May 1991 LER 91-004-00:on 910410,tech Spec Violation Occurred Re Containment Valve Injection Water Sys Being Inoperable. Caused by Inapropriate Action.Maint Staff Instructed Supervisors & Technicians of Correcting cause.W/910509 Ltr ML20024G7371991-04-18018 April 1991 LER 91-006-00:on 910323,nuclear Svc Water Valves Left W/O Emergency Power Supply.Caused by Inappropriate Action Due to Misreading of Operator Aid Computer (Oac) Graphics.Oac Graphics Training Will Be provided.W/910418 Ltr ML20029A3311991-02-12012 February 1991 LER 91-002-00:on 910113,reactor Exceeded 5% Power Level W/ RHR Sys Pump 1A Inoperable Due to Closed Suction Valve. Caused by Inappropriate Action & Procedural Deficiency. Incident Discussed W/Involved personnel.W/910212 Ltr ML20044B1761990-07-10010 July 1990 LER 90-013-00:on 900611,approx 5,000 Gallons of RCS Water Inadvertently Transferred to Refueling Water Storage Tank. Caused by Inappropriate Action.Proper Sys Parameters Restored & Analysis of Event performed.W/900709 Ltr ML20043G6441990-06-14014 June 1990 LER 90-008-00:on 900430,high Pressure CO2 Discharge Occurred on Auxiliary Feedwater Fire Protection Sys.Caused by Const/ Installation Deficiency in Solenoids.Solenoids Orientation Verified to Be Installed correctly.W/900614 Ltr ML20043C8951990-05-29029 May 1990 LER 89-010-01:on 880314,auxiliary Feedwater Pump 2A Discharge to Steam Generator 2A Isolation Failed to Completely Close.Caused by Design Deficiency.Mods to Actuator Torque Switch Setting increased.W/900524 Ltr ML20042G6301990-05-0909 May 1990 LER 90-025-00:on 900409,unexpected ESFs Actuation Occurred During Performance of Incore Thermocouple Testing.Caused by Deficient Procedure.Procedure Revised & Reviewed W/Personnel Lessons Learned from event.W/900503 Ltr ML20043A9271990-05-0303 May 1990 LER 89-030-01:on 890726,Tech Spec Violation Occurred Due to Shipment of Two Liners of Secondary Bead & Powdex Resin Mixture.On 891215,same Tech Spec Violation Occurred.Caused by Mgt Deficiency.Shipments suspended.W/900503 Ltr ML20042F4721990-05-0303 May 1990 LER 90-015-00:on 900402,Tech Spec 3.0.3 Entered When Both Trains of Containment Valve Injection Water Sys Rendered Inoperable.Caused by Supervisor Incorrectly Denoting Valve Position.Valves 1RN-493 & 494 closed.W/900430 Ltr ML20042F4741990-05-0303 May 1990 LER 90-006-00:on 900321,discovered That Nuclear Svc Water Sys Assured Makeup Source to Containment Valve Injection Water Sys Surge Chamber 2A Would Not Provide Adequate Flow. Caused by Clogged pipe.W/900430 Ltr ML20042E3141990-04-0303 April 1990 LER 90-002-01:on 900103,containment Air Return Fan Failed to Start During Test & Breaker FO1A in Motor Control Ctr Opened.Caused by Inappropriate Action.Measures Taken to Ensure Positions of Breakers verified.W/900409 Ltr ML20012C6881990-03-15015 March 1990 LER 90-011-00:on 900215,discovered That Control Room Doors Were More Difficult to Open than Normal.Ventilation Sys Found to Be Incapable of Maintaining Positive Pressure. Caused by Design Deficiency.Walls sealed.W/900315 Ltr ML20012C6901990-03-15015 March 1990 LER 90-005-01:on 900126,Tech Spec 3.0,3 Entered Due to More than One Power Range Nuclear Instrumentation Channel Exceeding 5% Deviation.Caused by Mgt Deficiency.Operations Procedure revised.W/900314 Ltr ML20012C3741990-03-13013 March 1990 LER 90-012-00:on 900127,central Alarm Station Operator Noted That Controlled Access Door Not Closed.Caused by Inappropriate Action Taken Which Was Unauthorized.Personnel Counseled on Importance of Sys operability.W/900313 Ltr ML20012C5091990-03-13013 March 1990 LER 90-009-00:on 900212,containment Purge Sys Heaters Not Being Verified to Be Running During Monthly Surveillance as Required by Tech Specs.Caused by Defective Procedures,Due to Incomplete Info.Procedures revised.W/900313 Ltr ML20012C5111990-03-12012 March 1990 LER 90-007-01:on 891108,discovered That Transmission Procedures Used to Perform Undervoltage Relay Tests Revealed That Test Acceptance Criteria Did Not Agree W/Tech Specs & Relays Not Being Adjusted as required.W/900316 Ltr ML20012B8121990-03-0909 March 1990 LER 90-008-00:on 900203,discovered That Insulation Removed from Main Steam Auxiliary Equipment Piping to Auxiliary Feedwater Pump Turbine.Caused by Design Oversight Due to Unanticipated Interaction of sys.W/900309 Ltr ML20012C4961990-03-0707 March 1990 LER 90-010-00:on 900205,discovered That Standby Shutdown Facility Wide Range RCS Temp Indications Had Not Been Subj to Monthly Channel Check as Required by Tech Spec 4.7.13.6. Caused by Defective procedure.W/900307 Ltr ML20012A1781990-02-27027 February 1990 LER 90-005-00:on 900126,Tech Spec 3.0.3 Entered Due to Inoperable Power Range Nuclear Instrumentation (Prni) During Unit Shutdown.Caused by Mgt Deficiency.Action Developed to Better Anticipate & Carry Out Prni calibr.W/900227 Ltr ML20006E8231990-02-14014 February 1990 LER 90-004-00:on 900104,contact Carrier Screws in nonsafety- Related Breaker Found Loose & in Bottom of Motor Control Ctr Cubicle.Caused by Mfg Deficiency.Loose Screws Secured. Part 21 related.W/900215 Ltr ML20006D4861990-02-0707 February 1990 LER 90-001-00:on 900105,unexpected Auxiliary Feedwater Automatic Startup Occurred During Periodic Cabinet Test. Caused by Procedure Deficiency.Procedures to Be Revised to Prevent recurrence.W/900207 Ltr ML20011E2281990-02-0202 February 1990 LER 90-002-00:on 900103,containment Air Return Fan 1B Failed to Start During Quarterly Test & Breaker F01A in Motor Control Ctr Discovered Open.Caused by Inappropriate Operator Action.Lockout Breakers closed.W/900202 Ltr ML20011E3951990-02-0202 February 1990 LER 90-001-00:on 891116,potential Concern Identified W/ Pressurizer Safety Valve Blowdown Being Greater than Assumed in Safety Analyses.Caused by Functional Design Deficiency. Also Reportable Per Part 21.W/900202 Ltr ML19354E0191990-01-19019 January 1990 LER 89-020-01:on 891118,Tech Spec 3.0.3 Entered & 5-month Auxiliary Bldg Ventilation Sys Inoperability Occurred as Result of Low Filter Exhaust Flow Condition on 891111.Caused by Design Oversight.Duct Will Be cleaned.W/900119 Ltr ML19354E0931990-01-18018 January 1990 LER 89-025-01:on 890922,power Lost to Condenser Circulating Water Cooling Tower Fans Due to Deenergization of 13.8 Kv Auxiliary Switchgear.Caused by Weather Conditions.Reactor Power Reduced to Maintain Condenser vacuum.W/900119 Ltr ML19354E0201990-01-18018 January 1990 LER 89-016-01:on 890913,generator 1B Power Circuit Breaker Opened,Causing Unit Runback to 54% Power & Failure of Generator Breaker Air Pressure Gauge.Caused by Equipment Failure.Pneumatic Gauge replaced.W/900117 Ltr ML19354D8261990-01-15015 January 1990 LER 89-029-00:on 891213,determined That Max Actuator Torque Switch Setting Insufficient to Overcome Friction Force Due to Age Hardening of Elastomeric Seat Matl on Bif/General Signal Corp Valve.Also Reported Per Part 21.W/900112 Ltr ML20005G4261990-01-12012 January 1990 LER 89-013-00:on 890726,two Carbon Steel Liners,Containing Mixture of Powdex & Bead Resins,Shipped to Barnwell,Sc,In Violation of Process Control Program.Caused by Mgt Deficiency.Shipment suspended.W/900112 Ltr ML20005G3061990-01-0909 January 1990 LER 89-020-00:on 890921,abnormal Degradation of Steel Containment Vessels Observed.Caused by Corrosion by Standing Water in Annulus Areas.Steel Containment Vessels Will Be Recoated During Next Refueling outage.W/900109 Ltr ML20005E4021989-12-29029 December 1989 LER 89-028-00:on 891204,steam Generator 1D Power Operated Relief Valve Did Not Close on Train a Main Steam Isolation Signal During Valve Inservice Test.Caused by Failed Fuse. Fuse replaced.W/891229 Ltr ML20011D3321989-12-20020 December 1989 LER 89-021-00:on 890821,hydrogen Skimmer Fan 2A Declared Inoperable in Order to Replace Breaker,In Response to NRC Bulletin 88-010.On 890825,breaker Tripped & Power Reduction Resumed.Caused by Inappropriate action.W/891222 Ltr ML20011D3351989-12-20020 December 1989 LER 89-027-00:on 891120,chemical & Vol Control Sys Centrifugal Charging Pump 1B Declared Inoperable Due to Inability to Maintain Sufficient Charging Flow.Cause Not determined.Power-range Detector replaced.W/891222 Ltr ML20011D2321989-12-18018 December 1989 LER 89-020-00:on 891111,low Filtered Exhaust Flow Discovered by Control Room Operators During Observation of Indications. Caused by Design Oversight Re Interaction of Sys/Components. Clothes Dryer Filters to Be modified.W/891218 Ltr ML19332E7201989-12-0606 December 1989 LER 89-023-01:on 890915,Tech Spec 3.0.3 Entered as Result of Both Trains of Control Room Area Ventilation Sys Being Inoperable.Caused by Equipment Malfunctions.Control Room & Area Pressurization Flow Rates revised.W/891120 Ltr ML19324B1141989-10-20020 October 1989 LER 89-024-00:on 890920,safety Review Group Staff Member Identified Committed Fire Door S102A as Possibly Inadequate. Caused by Design Deficiency.Fire Watch Established & Door repaired.W/891019 Ltr ML19324B4091989-10-20020 October 1989 LER 89-025-00:on 890922,13.8 Kv Auxiliary Switchgear Deenergized Resulting in Loss of Power to Condenser Circulating Water Cooling Tower Fans.Power Reduction Due to Hurricane Hugo.W/891019 Ltr ML19325C6381989-10-11011 October 1989 LER 89-023-00:on 890915,Tech Spec 3.0.3 Entered Due to Both Trains of Control Room Area Ventilation Sys Being Inoperable.Caused by Defective pre-operational Testing Procedure.Train a Control Room Damper adjusted.W/891011 Ltr ML19325C6401989-10-11011 October 1989 LER 89-016-00:on 890913,four Channels of Power Range Instrumentation Showed Greater than 5% Allowable Mismatch Between Rated Thermal Power & Nuclear Power.Caused by Equipment Failure.Pneumatic Gauge replaced.W/891011 Ltr ML19325C6441989-10-11011 October 1989 LER 89-019-00:on 890912,capability of Switches 2CA-15A & 2CA-18B Disabled Rendering Feedwater Pumps 2A & 2B Inoperable.Caused by Defective Procedure & Inappropriate Actions.Procedure Revised & Update issued.W/891011 Ltr ML19325C1961989-10-0404 October 1989 LER 89-026-00:on 890823,tested Breaker Replaced W/Traceable Breaker in Response to Bulletin 88-010.Breaker Tripped. Caused by Mfg Deficiency.Work Request Written.Item Reportable Per Part 21.W/891003 Ltr ML19327B6071989-09-20020 September 1989 LER 89-025-00:on 890922,auxiliary Switchgear Deenergized, Resulting in Loss of Power to Condenser Circulating Water Cooling Tower Fans.Caused by Inoperable power-range Instrumentation Due to Hurricane Hugo.W/890920 Ltr ML17303B1821986-12-30030 December 1986 LER 86-058-01:on 861111 & 18,overtemp Delta T Reactor Trip Occurred on Increasing Reactor Coolant Temp Rate.Caused by Spike on Potentiometer.Valve Realigned & Unit Returned to Previous status.W/861230 Ltr 1994-04-20
[Table view] Category:RO)
MONTHYEARML20024J2601994-10-0404 October 1994 LER 94-006-00:on 940913,automatic Reactor/Turbine Trip Occurred on Over Power Differential Temperature.Caused by Equipment Failure.Replaced Relay & Evaluated Failure Rate of Types of relays.W/941004 Ltr ML20029D1011994-04-20020 April 1994 LER 93-003-01:on 930925,reactor Tripped Due to Inadvertent Closure of Msiv.Caused by Inadequate Checking.Corrective Actions:Cros Throttled CA Flow & Entered Procedure EP/2/A/5000/01.W/940420 Ltr ML20046D5871993-08-17017 August 1993 LER 93-008-00:on 930718,reactor Tripped & Auxiliary Feedwater Sys Automatic Start Due to low-low-level in SG 1A. Developed General Troubleshooting procedure.W/930817 Ltr ML20045H2421993-07-12012 July 1993 LER 93-006-00:on 930612,automatic Reactor Trip Initiated by intermediate-range Channel N35 Hi Flux Reactor Trip Bistable.Caused by Blown Fuse in Channel.Entire Drawer Replaced & Channel Placed Back in svc.W/930712 Ltr ML20024G9751991-05-0909 May 1991 LER 91-004-00:on 910410,tech Spec Violation Occurred Re Containment Valve Injection Water Sys Being Inoperable. Caused by Inapropriate Action.Maint Staff Instructed Supervisors & Technicians of Correcting cause.W/910509 Ltr ML20024G7371991-04-18018 April 1991 LER 91-006-00:on 910323,nuclear Svc Water Valves Left W/O Emergency Power Supply.Caused by Inappropriate Action Due to Misreading of Operator Aid Computer (Oac) Graphics.Oac Graphics Training Will Be provided.W/910418 Ltr ML20029A3311991-02-12012 February 1991 LER 91-002-00:on 910113,reactor Exceeded 5% Power Level W/ RHR Sys Pump 1A Inoperable Due to Closed Suction Valve. Caused by Inappropriate Action & Procedural Deficiency. Incident Discussed W/Involved personnel.W/910212 Ltr ML20044B1761990-07-10010 July 1990 LER 90-013-00:on 900611,approx 5,000 Gallons of RCS Water Inadvertently Transferred to Refueling Water Storage Tank. Caused by Inappropriate Action.Proper Sys Parameters Restored & Analysis of Event performed.W/900709 Ltr ML20043G6441990-06-14014 June 1990 LER 90-008-00:on 900430,high Pressure CO2 Discharge Occurred on Auxiliary Feedwater Fire Protection Sys.Caused by Const/ Installation Deficiency in Solenoids.Solenoids Orientation Verified to Be Installed correctly.W/900614 Ltr ML20043C8951990-05-29029 May 1990 LER 89-010-01:on 880314,auxiliary Feedwater Pump 2A Discharge to Steam Generator 2A Isolation Failed to Completely Close.Caused by Design Deficiency.Mods to Actuator Torque Switch Setting increased.W/900524 Ltr ML20042G6301990-05-0909 May 1990 LER 90-025-00:on 900409,unexpected ESFs Actuation Occurred During Performance of Incore Thermocouple Testing.Caused by Deficient Procedure.Procedure Revised & Reviewed W/Personnel Lessons Learned from event.W/900503 Ltr ML20043A9271990-05-0303 May 1990 LER 89-030-01:on 890726,Tech Spec Violation Occurred Due to Shipment of Two Liners of Secondary Bead & Powdex Resin Mixture.On 891215,same Tech Spec Violation Occurred.Caused by Mgt Deficiency.Shipments suspended.W/900503 Ltr ML20042F4721990-05-0303 May 1990 LER 90-015-00:on 900402,Tech Spec 3.0.3 Entered When Both Trains of Containment Valve Injection Water Sys Rendered Inoperable.Caused by Supervisor Incorrectly Denoting Valve Position.Valves 1RN-493 & 494 closed.W/900430 Ltr ML20042F4741990-05-0303 May 1990 LER 90-006-00:on 900321,discovered That Nuclear Svc Water Sys Assured Makeup Source to Containment Valve Injection Water Sys Surge Chamber 2A Would Not Provide Adequate Flow. Caused by Clogged pipe.W/900430 Ltr ML20042E3141990-04-0303 April 1990 LER 90-002-01:on 900103,containment Air Return Fan Failed to Start During Test & Breaker FO1A in Motor Control Ctr Opened.Caused by Inappropriate Action.Measures Taken to Ensure Positions of Breakers verified.W/900409 Ltr ML20012C6881990-03-15015 March 1990 LER 90-011-00:on 900215,discovered That Control Room Doors Were More Difficult to Open than Normal.Ventilation Sys Found to Be Incapable of Maintaining Positive Pressure. Caused by Design Deficiency.Walls sealed.W/900315 Ltr ML20012C6901990-03-15015 March 1990 LER 90-005-01:on 900126,Tech Spec 3.0,3 Entered Due to More than One Power Range Nuclear Instrumentation Channel Exceeding 5% Deviation.Caused by Mgt Deficiency.Operations Procedure revised.W/900314 Ltr ML20012C3741990-03-13013 March 1990 LER 90-012-00:on 900127,central Alarm Station Operator Noted That Controlled Access Door Not Closed.Caused by Inappropriate Action Taken Which Was Unauthorized.Personnel Counseled on Importance of Sys operability.W/900313 Ltr ML20012C5091990-03-13013 March 1990 LER 90-009-00:on 900212,containment Purge Sys Heaters Not Being Verified to Be Running During Monthly Surveillance as Required by Tech Specs.Caused by Defective Procedures,Due to Incomplete Info.Procedures revised.W/900313 Ltr ML20012C5111990-03-12012 March 1990 LER 90-007-01:on 891108,discovered That Transmission Procedures Used to Perform Undervoltage Relay Tests Revealed That Test Acceptance Criteria Did Not Agree W/Tech Specs & Relays Not Being Adjusted as required.W/900316 Ltr ML20012B8121990-03-0909 March 1990 LER 90-008-00:on 900203,discovered That Insulation Removed from Main Steam Auxiliary Equipment Piping to Auxiliary Feedwater Pump Turbine.Caused by Design Oversight Due to Unanticipated Interaction of sys.W/900309 Ltr ML20012C4961990-03-0707 March 1990 LER 90-010-00:on 900205,discovered That Standby Shutdown Facility Wide Range RCS Temp Indications Had Not Been Subj to Monthly Channel Check as Required by Tech Spec 4.7.13.6. Caused by Defective procedure.W/900307 Ltr ML20012A1781990-02-27027 February 1990 LER 90-005-00:on 900126,Tech Spec 3.0.3 Entered Due to Inoperable Power Range Nuclear Instrumentation (Prni) During Unit Shutdown.Caused by Mgt Deficiency.Action Developed to Better Anticipate & Carry Out Prni calibr.W/900227 Ltr ML20006E8231990-02-14014 February 1990 LER 90-004-00:on 900104,contact Carrier Screws in nonsafety- Related Breaker Found Loose & in Bottom of Motor Control Ctr Cubicle.Caused by Mfg Deficiency.Loose Screws Secured. Part 21 related.W/900215 Ltr ML20006D4861990-02-0707 February 1990 LER 90-001-00:on 900105,unexpected Auxiliary Feedwater Automatic Startup Occurred During Periodic Cabinet Test. Caused by Procedure Deficiency.Procedures to Be Revised to Prevent recurrence.W/900207 Ltr ML20011E2281990-02-0202 February 1990 LER 90-002-00:on 900103,containment Air Return Fan 1B Failed to Start During Quarterly Test & Breaker F01A in Motor Control Ctr Discovered Open.Caused by Inappropriate Operator Action.Lockout Breakers closed.W/900202 Ltr ML20011E3951990-02-0202 February 1990 LER 90-001-00:on 891116,potential Concern Identified W/ Pressurizer Safety Valve Blowdown Being Greater than Assumed in Safety Analyses.Caused by Functional Design Deficiency. Also Reportable Per Part 21.W/900202 Ltr ML19354E0191990-01-19019 January 1990 LER 89-020-01:on 891118,Tech Spec 3.0.3 Entered & 5-month Auxiliary Bldg Ventilation Sys Inoperability Occurred as Result of Low Filter Exhaust Flow Condition on 891111.Caused by Design Oversight.Duct Will Be cleaned.W/900119 Ltr ML19354E0931990-01-18018 January 1990 LER 89-025-01:on 890922,power Lost to Condenser Circulating Water Cooling Tower Fans Due to Deenergization of 13.8 Kv Auxiliary Switchgear.Caused by Weather Conditions.Reactor Power Reduced to Maintain Condenser vacuum.W/900119 Ltr ML19354E0201990-01-18018 January 1990 LER 89-016-01:on 890913,generator 1B Power Circuit Breaker Opened,Causing Unit Runback to 54% Power & Failure of Generator Breaker Air Pressure Gauge.Caused by Equipment Failure.Pneumatic Gauge replaced.W/900117 Ltr ML19354D8261990-01-15015 January 1990 LER 89-029-00:on 891213,determined That Max Actuator Torque Switch Setting Insufficient to Overcome Friction Force Due to Age Hardening of Elastomeric Seat Matl on Bif/General Signal Corp Valve.Also Reported Per Part 21.W/900112 Ltr ML20005G4261990-01-12012 January 1990 LER 89-013-00:on 890726,two Carbon Steel Liners,Containing Mixture of Powdex & Bead Resins,Shipped to Barnwell,Sc,In Violation of Process Control Program.Caused by Mgt Deficiency.Shipment suspended.W/900112 Ltr ML20005G3061990-01-0909 January 1990 LER 89-020-00:on 890921,abnormal Degradation of Steel Containment Vessels Observed.Caused by Corrosion by Standing Water in Annulus Areas.Steel Containment Vessels Will Be Recoated During Next Refueling outage.W/900109 Ltr ML20005E4021989-12-29029 December 1989 LER 89-028-00:on 891204,steam Generator 1D Power Operated Relief Valve Did Not Close on Train a Main Steam Isolation Signal During Valve Inservice Test.Caused by Failed Fuse. Fuse replaced.W/891229 Ltr ML20011D3321989-12-20020 December 1989 LER 89-021-00:on 890821,hydrogen Skimmer Fan 2A Declared Inoperable in Order to Replace Breaker,In Response to NRC Bulletin 88-010.On 890825,breaker Tripped & Power Reduction Resumed.Caused by Inappropriate action.W/891222 Ltr ML20011D3351989-12-20020 December 1989 LER 89-027-00:on 891120,chemical & Vol Control Sys Centrifugal Charging Pump 1B Declared Inoperable Due to Inability to Maintain Sufficient Charging Flow.Cause Not determined.Power-range Detector replaced.W/891222 Ltr ML20011D2321989-12-18018 December 1989 LER 89-020-00:on 891111,low Filtered Exhaust Flow Discovered by Control Room Operators During Observation of Indications. Caused by Design Oversight Re Interaction of Sys/Components. Clothes Dryer Filters to Be modified.W/891218 Ltr ML19332E7201989-12-0606 December 1989 LER 89-023-01:on 890915,Tech Spec 3.0.3 Entered as Result of Both Trains of Control Room Area Ventilation Sys Being Inoperable.Caused by Equipment Malfunctions.Control Room & Area Pressurization Flow Rates revised.W/891120 Ltr ML19324B1141989-10-20020 October 1989 LER 89-024-00:on 890920,safety Review Group Staff Member Identified Committed Fire Door S102A as Possibly Inadequate. Caused by Design Deficiency.Fire Watch Established & Door repaired.W/891019 Ltr ML19324B4091989-10-20020 October 1989 LER 89-025-00:on 890922,13.8 Kv Auxiliary Switchgear Deenergized Resulting in Loss of Power to Condenser Circulating Water Cooling Tower Fans.Power Reduction Due to Hurricane Hugo.W/891019 Ltr ML19325C6381989-10-11011 October 1989 LER 89-023-00:on 890915,Tech Spec 3.0.3 Entered Due to Both Trains of Control Room Area Ventilation Sys Being Inoperable.Caused by Defective pre-operational Testing Procedure.Train a Control Room Damper adjusted.W/891011 Ltr ML19325C6401989-10-11011 October 1989 LER 89-016-00:on 890913,four Channels of Power Range Instrumentation Showed Greater than 5% Allowable Mismatch Between Rated Thermal Power & Nuclear Power.Caused by Equipment Failure.Pneumatic Gauge replaced.W/891011 Ltr ML19325C6441989-10-11011 October 1989 LER 89-019-00:on 890912,capability of Switches 2CA-15A & 2CA-18B Disabled Rendering Feedwater Pumps 2A & 2B Inoperable.Caused by Defective Procedure & Inappropriate Actions.Procedure Revised & Update issued.W/891011 Ltr ML19325C1961989-10-0404 October 1989 LER 89-026-00:on 890823,tested Breaker Replaced W/Traceable Breaker in Response to Bulletin 88-010.Breaker Tripped. Caused by Mfg Deficiency.Work Request Written.Item Reportable Per Part 21.W/891003 Ltr ML19327B6071989-09-20020 September 1989 LER 89-025-00:on 890922,auxiliary Switchgear Deenergized, Resulting in Loss of Power to Condenser Circulating Water Cooling Tower Fans.Caused by Inoperable power-range Instrumentation Due to Hurricane Hugo.W/890920 Ltr ML17303B1821986-12-30030 December 1986 LER 86-058-01:on 861111 & 18,overtemp Delta T Reactor Trip Occurred on Increasing Reactor Coolant Temp Rate.Caused by Spike on Potentiometer.Valve Realigned & Unit Returned to Previous status.W/861230 Ltr 1994-04-20
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20217H0201999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Catawba Nuclear Station,Units 1 & 2 ML20216E5401999-09-0707 September 1999 Special Rept:On 990826,discovered That Meteorological Sys Upper Wind Speed Cup Set Broken,Causing Upper Wind Channel to Be Inoperable.Cup Set Replaced & Channel Restored to Operable Status on 990826 ML20212B4711999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Catawba Nuclear Station,Units 1 & 2 ML20217H0321999-08-31031 August 1999 Revised Monthly Operating Rept for Aug 1999 for Catawba Nuclear Station,Units 1 & 2 ML20211B1281999-08-31031 August 1999 Dynamic Rod Worth Measurement Using Casmo/Simulate ML20211A9791999-08-20020 August 1999 Safety Evaluation Granting Licensee Request for Approval of Proposed Relief from Volumetric Exam Requirements of ASME B&PV Code,Section Xi,For Plant,Unit 2 ML20211F3441999-08-17017 August 1999 Updated non-proprietary Page 2-4 of TR DPC-NE-2009 ML20211C1291999-08-17017 August 1999 ISI Rept Unit 1 Catawba 1999 RFO 11 ML20210R1051999-08-0606 August 1999 Special Rept:On 990628,cathodic Protection Sys Was Declared Inoperable After Sys Did Not Pass Acceptance Criteria of Bimonthly Surveillance.Work Request 98085802 Was Initiated & Connections on Well Anode Were Cleaned or Replaced ML20210S2891999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Catawba Nuclear Station,Units 1 & 2 ML20212B4871999-07-31031 July 1999 Revised Monthly Operating Rept for July 1999 for Catawba Nuclear Station,Units 1 & 2 ML20209E4361999-07-0909 July 1999 SER Agreeing with Licensee General Interpretation of TS LCO 3.0.6,but Finds No Technical Basis or Guidance That Snubbers Could Be Treated as Exception to General Interpretation ML20196K6631999-07-0707 July 1999 Safety Evaluation Supporting Licensee 990520 Position Re Inoperable Snubbers ML20210S2951999-06-30030 June 1999 Revised Monthly Operating Rept for June 1999 for Catawba Nuclear Station,Units 1 & 2 ML20209H4501999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Catawba Nuclear Station,Units 1 & 2 ML20209H4561999-05-31031 May 1999 Revised Monthly Operating Rept for May 1999 for Catawba Nuclear Station,Units 1 & 2 ML20206T4771999-05-31031 May 1999 Rev 3 to UFSAR Chapter 15 Sys Transient Analysis Methodology ML20196L1881999-05-31031 May 1999 Non-proprietary Rev 1 to DPC-NE-3004, Mass & Energy Release & Containment Response Methodology ML20196A0001999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Catawba Nuclear Station,Units 1 & 2 ML20206P5201999-05-14014 May 1999 Safety Evaluation Accepting GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves ML20206N8391999-05-0404 May 1999 Rev 16 to CNEI-0400-24, Catawba Unit 1 Cycle 12 Colr ML20206R1811999-04-30030 April 1999 Monthly Operating Repts for Apr 1999 for Catawba Nuclear Station,Units 1 & 2 ML20196A0041999-04-30030 April 1999 Revised Monthly Operating Repts for Apr 1999 for Catawba Nuclear Station,Units 1 & 2 ML20206N8261999-04-22022 April 1999 Rev 15 to CNEI-0400-24, Catawba Unit 1 Cycle 12 Colr. Page 145 of 270 of Incoming Submittal Not Included ML20205S5551999-04-21021 April 1999 Safety Evaluation Accepting Response to GL 96-06, Assurance of Equipment Operability & Containment Integrity During Design Basis Accident Conditions ML20205N3651999-04-12012 April 1999 Safety Evaluation Accepting IPE of External Events Submittal ML18016A9011999-04-12012 April 1999 Part 21 Rept Re Defect in Component of DSRV-16-4,Enterprise DG Sys.Caused by Potential Problem with Connecting Rod Assemblies Built Since 1986,that Have Been Converted to Use Prestressed Fasteners.Affected Rods Should Be Inspected ML20206R1931999-03-31031 March 1999 Revised Monthly Operating Repts for Apr 1999 for Catawba Nuclear Station,Units 1 & 2 ML20205P9521999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Catawba Nuclear Station,Units 1 & 2 ML20205P9561999-02-28028 February 1999 Revised Monthly Operating Repts for Feb 1999 for Catawba Nuclear Station,Units 1 & 2 ML20204C9111999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Catawba Nuclear Station,Units 1 & 2 ML20203A2581999-02-0505 February 1999 Safety Evaluation of TR DPC-NE-3002-A,Rev 2, UFSAR Chapter 15 Sys Transient Analysis Methodology. Rept Acceptable. Staff Requests Duke Energy Corp to Publish Accepted Version of TR within 3 Months of Receipt of SE ML20204C9161999-01-31031 January 1999 Revised Monthly Operating Repts for Jan 1999 for Catawba Nuclear Station,Units 1 & 2 ML20199K8711999-01-13013 January 1999 Inservice Insp Rept for Unit 2 Catawba 1998 Refueling Outage 9 ML20199E3071998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Catawba Nuclear Station,Units 1 & 2 ML20216F9931998-12-31031 December 1998 Piedmont Municipal Power Agency 1998 Annual Rept ML20205E9441998-12-31031 December 1998 1998 10CFR50.59 Rept for Catawba Nuclear Station,Units 1 & 2, Containing Brief Description of Changes,Tests & Experiments,Including Summary of Ses.With ML20206P2081998-12-31031 December 1998 Special Rept:On 981218,inoperability of Meteorological Monitoring Instrumentation Channels,Was Observed.Caused by Data Logger Overloading Circuit.Replaced & Repaired Temp Signal Processor ML20203A4101998-12-22022 December 1998 Rev 16 to CNEI-0400-25, Catawba Unit 2 Cycle 10 Colr ML20203A4041998-12-22022 December 1998 Rev 14 to CNEI-0400-24, Catawba Unit 1 Cycle 11 Colr ML20198B1341998-12-14014 December 1998 Revised Special Rept:On 980505,discovered That Certain Fire Barriers Appeared to Be Degraded.Caused by Removal of Firestop Damming Boards.Hourly Fire Watches Established in Affected Areas ML20196J8351998-12-0808 December 1998 Safety Evaluation Granting Relief Request Re Relief Valves in Diesel Generator Fuel Oil Sys ML20199E3221998-11-30030 November 1998 Revised MOR for Nov 1998 for Catawba Nuclear Station,Units 1 & 2 Re Personnel Exposure ML20198E3151998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Catawba Nuclear Station,Units 1 & 2 ML20196C0251998-11-27027 November 1998 SER Accepting Clarification on Calibration Tolerances on Trip Setpoints for Catawba Nuclear Station ML20196A6881998-11-25025 November 1998 Safety Evaluation Granting Relief Request 98-02 Re Limited Exam for Three Welds ML20196D4041998-11-19019 November 1998 Rev 1 to Special Rept:On 980618,determined That Method Used to Calibrate Wind Speed Instrumentation Loops of Meteorological Monitoring Instrumentation Sys Does Not Meet TS Definition for Channel Calibration.Procedure Revised ML20195E5521998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Catawba Nuclear Station,Units 1 & 2 ML20198E3261998-10-31031 October 1998 Revised Monthly Operating Repts for Oct 1998 for Catawba Nuclear Station,Units 1 & 2 ML20154M7661998-10-12012 October 1998 LER 98-S01-00:on 980913,terminated Vendor Employee Entered Protected Area.Caused by Computer Interface Malfunction. Security Retained Vendor Employee Badge to Prevent Further Access & Computer Malfunction Was Repaired.With 1999-09-07
[Table view] |
Text
~
-G .f ,
I- :
"* y,gy,,,, l U'q , J> . Duke her Comparty .
y Curau ha Nuclear Station
'PO Bar:36
> Clour. S C :9710
. 6 .- .;
e ,
- ' DUKE POWER s'}l' October.19, 1989 u
~
Document Control Desk '
.U. S. Nuclear Regulatory Commission'
. Washington, D. C. 20555-p
Subject:
- Catawba Nuclear Station ,
- a. . ~ ,
Docket No..50-413-W ' .LER 413/89-24 ,
Gentlemen:
.. Attached is Licensca Event Report 413/89-24, concerning Technical-
~
Specification violation for inoperable fire door due to latch failure ,
- and inadequate policy regarding controlled access fire doors. ;
This event'was considered to be of no significance with respect to the, health and safety of the public. .
.Very truly'you:5 .
Tian.n B. o- .'
Tony B. Owen ' !
Station Manager keb\LER-NRC.TBO-1 xc: Mr. S. D. Ebneter American Nuclear Insurers
. Regional Administrator, Region II c/o Dottie Sherman, ANI Library U.~S. Nuclear Regulator Commission The Exchange, Suite 245 101 Marietta Street, NW, Suite 2900 270 Farmington Avenue ,
l O Atlanta, GA 30323 Farmington, CT 06032
.M & M Nuclear Consultants Mr. K. Jabbour 1221 Avenues of the Americas U. S. Nuclear Regulatory Commission New York, NY 10020 Office of Nuclear Reactor Regulation Washington, D. C. 20555 INPO Records Center Suite 1500 Mr. W. T. Orders 1100 circle 75 Parkway NRC Resident Inspector Atlanta, GA 30339 Catawba Nuclear Station
. koha3 a b ,. ~- - , - __, .. .. m-.e
- ~ - . . . . . . . . .. . .. . . r samt Po,,,, asp u s. kuCttaa kniut.r.The commisasoN I M '
' (M!vtD OMS 6:G. ainoatos LICENSEE EVENT REPORT (LER) ""'8''*
l
[ PamnT =A= m ooCm T Nuuna m ..v o, Catawba Nuclear Station, Unit 1 015 l o l o l 0 l 4l 1 3 1loFl0l4
'" Technical Specification Violation For Inoperable Fire Door Due to Latch Fai;.ure ,
-and Inadequate Policy Regarding Controlled Access Fire Doors ,
SVg.,T paf t its Lgn NyMagM iti REPOaY DAYS (Yi OTHt R F ACILITill iNv0LviD ici MO :Ta Day vtan vaan "LWy ',' 6 ",*/,*y voNTu cav vaan eacsiv, naves DocntY Nuvetaisi i N/A o15tol0log g ;
~ ~
i 0l9 2 l0 8 9 8l 9 0l2l4 0 !O 1l0 2l0 8l 9 0 is to 1 0 ioi l l
,,,,a,,,,, Ti.n ofif...u irno,unu.NTTo,E noui..W.a.o,ioe,.i ,C . .. .. . .,nu "o * *
- 1 n ami ro .osi.. so.n imi i n Yuni n .o i.imm so ni.im so.ni.uan.i n.Tu.i noi 01 49 1 n .oiiumm so ni.im
.o n..wi. .
_ g,w,t gs. g,;,.g,,,,,,
, y _
. .inna x .o ni.imni
.o n..n.n..in., u.. ,
- g. so aost inn so.ni.mm so.ni.wi. nsi to .osi.in n., to T36.il28t 4 i to T31.H2ns8 LICENBEE CONTACT POR TMit LER titi N1ME YtLErm0NS NUMBIR l R.M. Glover, Compliance Manager 81013 813 111-l 312131 6 COMPLETE ONE LiNE Pom (AC COMP 0htNT f A LURE OtsClitetD IN TMit fitPORT H31
( CIU58 Svlftv CouPONENT Ma%AC n{p0mf o pa NI Cault sv8Ttu CovPONINT "')'g AC m .0mia pn
'5 I I I I I l l' I 1 1 I I I I 5
I l l l l l l 1 I I l l l I SuP9tEMENTAL fitPORT E XPICTED i,41 MONTH DAY vtAR >
] vts ,,,,.. . txPactro svewssio= oa rs, 7 so l l l ,
t u u A CT w,, ,. i m . . . . ,.. .,.., ,,,. .. . . .. ... ,, ...., n . ,
On, September 20, 1989, at 1530 hours0.0177 days <br />0.425 hours <br />0.00253 weeks <br />5.82165e-4 months <br />, with Units 1 and 2 in Mode 1, Power Operation, a Catawba Safety Review Group staff member en route to the Diesel Generator Rooms identified Committed Fire Door S102A as being a possibly inadequate fire boundary door. This door is equipped with a manual latchbolt l
(which was found broken), a key operated lock, and a Controlled Access Door (CAD) mechanism which is actuated by a security badge access key. A fire watch was established, pending a Design Engineering (DE) operability evaluation. On September 21, DE determined that the CAD mechanism for this door was inadequate as a fire protection latching device. Door S102A was repaired on October 4, and the fire watch was terminated. The latch is known to have been in a failed condition between April 27, 1988 and September 20, 1989, with no fire watch posted, thereby violating Technical Specifications. This incident is attributed to a design deficiency, for the selection of a door not capable of withstanding frequent use, resulting in a failed latch, and to an inadequate policy regarding Controlled Access Fire Doors, resulting in the belief that the CAD mechanism would meet the intent of Technical Specifications when a fire door latch was failed. Corrective actions included establishment of a fire watch and repairing the door, and will include a policy statement from DE.
w *
, <,w m v.s. evetsu cuutuoa, ca inio.
N UCENSEE EVENT REP 3RT (LER) TEXT CONTINUATION mroveo ows ~o sin-co.
EXPlht&: $/31/5 F ACILITY ,,AME lli DOCLET NUM$th 6.) ggn gygggn (g) PAgg (3l vsaa " MW. 3*.O
' C:t:yba Nuclear Station, Unit 1 015l0l010l li a lo I- nl > l 6 -
0 10 0l2 oF 0 l4 3en ., w. wwe wamamm BACKGROUND
, Technical . Specification 3.7.11, fire Barrier Penetrations, states that all sealing devices (including fire doors) in fire rated assembly penetrations (EIIS: PEN] shall be operable at all times, or within one hour establish a continuor.s fire watch on at least one side of the penetrition, or verify the
.! operability of fire detectors [EIIS:XT] on at least one side of the penetration
- and establish an hourly fire watch patrol. Surveillar:e Requirement 4.7.11.2 states that fire doors shall be verified operable by inspecting the' closing
,~
mechanism and latches at least once per six months. This surveillance is met by the performance of PT/0/A/4200/48, Periodic Inspection of Fire Barriers and
, Related Structures. National Fire Code, Volume 4, NPFA80, requires that fire
- doors be equipped with both latching (paragraph 2-8.2.3) and closing (paragraph ,
j 2-8,5.2) devices.
NRC Committ'ed Fire Door $102A is located on the 554 foot elevation of the
!.. Auxiliary Building [EIIS:VF], coordinates AA-54. It is frequently used, providing access from the Servi e Building [EIIS:MF] to the Battery [EIIS:BTRY) -
Room. Corridor and the Diesel Generator [EIIS: GEN] Rooms. It is equipped with a i key operated dead bolt lock, a manual lever actuated latch bolt, and a -
Controlled Access Door (CAD) mechanism, which is actuated by a security badge access key. The door was manufactured by R.V. Harty Company, Inc., and its selection was based on an estimated use frequency.
EVENT DESCR!pTION On September 28, 1987, NRC Committed Fire Door S102A successfully latched during the performance'of PT/0/A/4200/48.
~
, On April 27, 1988, Door S102A failed to latch during the performance of l PT/0/A/4200/48. A fire watch was not established, due to the belief that as L long as the CAD mechanism was operable, the door was operable per Technical ll Specification 3.7.11. On April 29, 1988, Priority 3 Work Request 5368 MNT was written to repair the latch.
1 On July 7, 1988, Station Problem Report (SPR) No. CNPR03510 was initiated by Maintenance Engineering Services (MES) due to the latch bolt on Door S102A not working properly, due to worn internals. The SpR stated that the R.V. Harty Company had gone out of business, and that replacement parts were not available. ,
Possible resolutions provided were to either fabricate new internals, or to L
l replace the door (as well as other R.V. Harty doors in the plant).
l l On November 2, 1988, SPR No. CNPR03830 was initiated to replace Door $102A with Door AX300A, which was the entrance door to the Unit 2 Upper Head Injection (UHI) Building. Work Request 5368 MNT was voided, on November 11, 1988, since Door S102A was to be replaced (however, this replacement was not performed and no repair was done).
l
..a e m.m.m m
, yr -
~
~
3, w% >
- i- ;
esas poem asea . Ua NUCLEIP. C 51ULAT0*v COMMCION L
j P. LICENR3 EVENT REPORT (LER) TEXT CONTINUATION u*aovto oMe No. mo.co.
EXPit.t&; $/31/5
- PACILITY SpAM4 418 DOCKET NUMDth (2) LER NUM64 A 18) peg @
vs*a " $!@.
"'s*.W j l[
q
.C;cawba Nuclear Station, Unit 1 1
o l5 l0 lo j 9 l gl3 l9 p jo - nj 9l g -
g lg O l3 oF 0 l4 l
. a.c , m ni
[. i m , -
~
4 On May 25, 1989, Door S102A again failed to latch during the performance of ;
PT/0/A/4200/48. The door was thought to be operable, due to the operability of 1 4
the CAD mechanism. ,
~
On. June 20, 1989, Prior.ity 4 Work Request 1428 MES was written to !
fabricate / replace the needed parts on Door S102A, .
On Septe:nber 20, 1989, at 1530 hours0.0177 days <br />0.425 hours <br />0.00253 weeks <br />5.82165e-4 months <br />, with Units 1 and 2 in Mode 1, Power Operation, a Catawba Safety Review Group staff member en route to the Diesel ;
Generator Rooms identified Committed Fire Door S102A as being a possibly [
' inadequate fire boundary door. The manual lever actuated latch bolt was found ,
to be broken. The Fire Protection' Console Operator was notified, and a fire r watch was established by Security, pending a Design Engineering (DE) operability '
evaluation.. On September 21, DE determined that the CAD mechanism for this door was inadequate as a-latching device for fire protection purposes. Door S102A was repaired under Work Reg'ue w 142S MES, and the fire watch was subsequently terminated, on October 4.
CONCLUSION This incident is attributed to a design deficiency, due to the selection of a door having a latch bolt mechanism not capable of withstanding the frequent use encountered at the location of Door S102A. This selection was based on an t estimated use frequency which was lower than the actual frequency of use, and '
resulted in the eventual material failure of the latch bolt mechanism. The corrective action for worn internals on the R.V. Harty doors will be to fabricate new internals for each door. This has been successfully performed for Doors S303A, the 'iingle Point A: cess door, and for Door S102A.
This . incident is also attributed to an inadequate policy regarding the Technical Specification operability of CAD operated fire doors with inoperable latch bolts. This policy appeared to be reinforced by a July 27, 1988 memorandum from DE' to MES, which stated that the requirement of closure and latching for two other fire doors had been met because the doors were CAD doors. This memorandum, however, was in reference only to the closure ability of the doors. ;
This policy was reflected in the Fire Door Inspections procedure, PT/0/A/4400/01H, in which fire door surveillances are performed. This procedure states that if CAD alarm capability is not degraded, that a fire watch need not be established. The latch is known to have been in a failed condition between April 27, 1988 and September 20, 1989, with no fire watch posted, thereby violating Technical Specification 3.7.11.
According to DE, the CAD device does not meet the requirement for a fire door latching device since a fire near the door could damage the CAD circuitry.
De-energization of the CAD mechanism would fail the CAD latch open, as a safety
' feature, rendering it inoperable as a fire barrier. As a corrective action, DE will provide a written policy regarding the role of the CAD device in NRC
"~mwn" +m me: m?-
v
, 3 enG Poem atta . U 5. NUCLEM KEIUL1T0aY Co.MISEtch UCENSEE EVENT CEPORT (LER) TEXT CONTINUATION Amovro ous no me.om 4m; Em m exmntswa oocuvaum ia m unwu in m ... m
catawba Nuclear Station, Unit 1 018101010 ) a ll I1 9lo -
nl9lA -
O l0 0 13 oF O !4 asxten . w. -w wc w anso,nn '
On May 25, 1989, Door S102A again failed to latch during the performance of ;
PT/0/A/4200/48. The door was thought to be operable, due to the operability of the CAD mechanism. ,
On June 20, 1989, Priority 4 Work Request 1428 MES was written to
-fabricate /repir.ce the needed parts on Door S102A.
6 On September 20, 1989, at 1530 hours0.0177 days <br />0.425 hours <br />0.00253 weeks <br />5.82165e-4 months <br />, with Units 1 and 2 in Mode 1, Power Operation, a Catawba Safety Review Group staff member en route to the Diesel Generator Rooms identified Committed Fire Door S102A as being a possibly
, ~
inadequate fire boundary door. The manual lever actuated latch bolt was found to be broken. The Fire Protection Console Operator was notified, and a fire watch was established by Security, pending a Design Engineering (DE) operability evaluation. On September 21, DE determined that the CAD mechanism'for this door was inadequate as a latching device for fire protection purposes. Door S102A was repaired under Work Requ'est 1428 MES,'and the fire watch was subsequently terminated, on October 4.
CONCLUSION This incident is attributed to a design deficiency, due to the selection of a door having a latch bolt mechanism not capabic of withstanding the frequent use encountered at the location of Door S102A. This selection was based on an estimated use frequency which was lower than the actual frequency of use, and resulted in the eventual material failure of the latch bolt mechanism. The
' corrective action for worn internals on the R.V. Harty doors will be to fabricate new internals for each door. This has been successfully performed for Doors 5303A, the Single Point Access door, and for Door 5102A. -
This incident is also attributed to an inadequate policy regarding the Technical Specification operability of CAD operated fire doors with inoperable latch bolts. This policy appeared to be reinforced by a July 27, 1988 memorandum from DE to MES, which stated that the requirement of closure and latching for two other fire doors had been met because the doors were CAD doors. This memorandum, however, was in reference only to the closure ability of the doors.
This policy was reflected in the Fire Door Inspections procedure, PT/0/A/4400/01H, in which fire door surveillances are performed. This procedure
'j states that if CAD alarm capability is not degraded, that a fire watch need not be established. The latch is known to have been in a failed condition between April 27, 1988 and September 20, 1989, with no fire watch posted, thereby violating Technical Specification 3.7.11.
According to DE, the CAD device does not meet the requirement for a fire door 1atching device since a fire near the door could damage the CAD circuitry.
De-energization of the CAD mechanism would fail the CAD latch open, as a safety feature, rendering it inoperable as a fire barrier. As a corrective action, DE will provide a written policy regarding the role of the CAD device in NRC
.s w wr
p- _.
3 l
f- l If4C Dessa M W.S. t*uCLtM C.BOULafony comuseslow
]
r LICENSEE EVENT REPORT (LEM) TEXT CONTINUATION u*aovie oue wo. mo-mo.
y 8xPints:St3lle
( Sagetify somes gia DocneT Isunseth tan gge gouggm tel PAGE tal p n aa -
" W .P. "tTJ.f Catawba Nuclear Station, Unit 1~
0 5to o ol li l 3 alo -
nl Ia -
010 Ol4 0F 0 l4 '
fort n- .
- e =c %=sr., nn Committed Fire Doors. In addition, PT/0/A/4400/01H will be changed to reflect '
f
! this policy. A letter has been sent to Security teams, stating that if a door i
latch is broken, then either a fire watch must be established, or the door must P beLlocked. ,
P Door problems at Catawba are considered to be a recurring problem. A task force
- . has been formed to investigate and resolve' door closure problems, including High
- . Fadiation doors and fire doors. ;
L CORRECTIVE ACTION-I SUBSEQUENT ,
E A fire watch was established at Door S102A.
.1) ,
- 2) Door S102A was repaired under Work Request 1428 MES, and the fire r watch was terminated.
- 3) MES is in the process of replacing the worn internals of R.V. Harty .
doors.
. 4) A letter was sent to Security teams, stating that when a door latch is broken, either the door must be locked or a fire watch established.
~5) A task force ef Station personnel has been formed to discuss and resolve door problems. L PLANNED.
- 1) Guidance will be provided regarding the role of the CAD mechanism in satisfying the operability requirements for NRC Committed Fire Doors.
12 l 2) PT/0/A/4400/01H, Fire Door Inspections, will be revised to reflect the determination that the CAD mechanism cannot be used to establish fire o door operability when a latch is inoperable. ,
SAFETY ANALYSIS Although the CAD mechanism was not an acceptable latching device for Door S102A, .
it would have provided immediate notification to Security if the door was open.
If a fire had occurred, the fire detectors in the Battery Room Corridor would
.have sounded, and the Fire Brigade would have responded to extinguish the fire.
In the event that the detectors did not alarm, and the CAD mechanism failed.
Security personnel would have responded to an " illegal unlock" alarm, discovered the fire, and could have secured the door using the key operated dead bolt lock, if desired. The health and safety of the public were not affected by this incident.
m . , . m .m . m 4. .. - a