LER 80-028/03L-0:on 800926,w/unit at 100% Power,Reduction in Svc Water Pressure to Charging Pumps Experienced.Caused by Missing Valve Disk for Check Valve 2-SW-112.Valve Replaced
ML18139A767
Person / Time
Site: Surry Dominion icon.png
Issue date: 10/24/1980
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML18139A766 List:
References
LER-80-028-03L-01, LER-80-28-3L-1, NUDOCS 8010280512
Download: ML18139A767 (2)


Text

- - -=~--~-----~------_ -*--------

{7-77)

NRC FORM *366 e eu. S. NUCLEAR REGULATORY COMMISSION LICENSEE EVENT REPORT CONTROL BLOCK: ... \ _.....____._ _.__..___.__l G (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATION)

~8 7

Iv I A I s IP Is I 214101 o Io 1- Io Io Io Io Io 1- lo Io 101 4 I 1 I 1 I 1 I 1 IG)I I 10 9 LICENSEE CODE 15 LICENSE NUMBER 25 26 LICENSE TYPE :JO 57 CAT 58 CON'T

[IE]

7 8

~~~~~ W© 60 I61o I s I oDOCKET I o INUMBERo I 2 I s I 1 6810!69 oI 21EVENT2 IDATE 6 I sI oI© I I I I I 74 75 1 O 2 4 8 O REPORT DATE I 8010 EVENT DESCRIPTION AND PROBABLE CONSEQUENCES@

I On September 26, 1980, with the unit at 100% power, a reduction in service water

~\pressure to the charging prnnps was experienced. Investigation indicated a missing (Iill check valve disk for 2-SW-113, on the discharge of 2-SW-P-lOA. If the pump had not been!

C£:II) isolated, a reduction in cooling water flow would have occurred. This is contrary to

[§JI] I T.S.3.3.A.8.b and is reportable per T.S.6.6.2.b.(2). The temporary modification

~ \ (missing disk) was not documented. This is contrary to T.S.6.4.D and is reportable

~ I per T.S.6.6.2.b(3). The health and safety of the public were not affected.

7 8 9 80 SYSTEM CAUSE CAUSE COMP. VALVE 1, v, E, x ,e CODE CODE SUB CODE COMPONENT CODE SUBCOOE SUSCODE

~8 Is !wl@ w@ LLJ@ , v I Al w@ w@

7 9 10 11 12 13 18 19 20 SEQUENTIAL OCCURRENCE REPORT REVISION c:;-., LER/RO CVENT YEAR REPORT NO. CODE TYPE NO.

\!.:..I REPORT NUMBER I

21 8/ o j 22 L=.J 23 I 01 21 Bl 2" 26 27 I28o l 329I L!:.J 30 l:::J 31 w

32 ACTION FUTURE EFFECT SHUTDOWN (.:;:;\ ATTACHMENT NPR0-4 PRIME COMP. COMPONENT TAKEN ACTlON ON ?LANT METHOD HOURS ~ SUBMITTED FORM :;us. SUPPLIER MANUFACTURER LfJ@Li.J@

33 34 W@)

35 l:Ll 36 10 10 10 10 37 40 I L!.l@-

41 W§ 42 W@

43 44 PI 3 I O I 5 I@

47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS @

\ The cause of the event was a missing valve disk for 2-SW-113. The "A"** pump was

[IID I isoJ ated thereby allowing the "B" pump to perform its intended function. The check CIII] I valve, 2-SW-113, was subsequently replaced.

[ill]

7 8 9 80 FACILITY

@ METHOD OF r::;::;-.

STATUS  % POWER OTHER STATUS DISCOVERY DISCOVERY DESCRIPTION ~

~W !, lo la I~~'--=~~--~ lA.J~I. .____O~p~e~r~a=t~o~r=--O~b.::...::.s~e~rv...;..;;;a~t~i~o~n;...________;

8 9 10 12 1"3 44 45 46 80 ACTIVITY CONTENT Q.

RELEASED OF RELEASE AMOUNT OF ACTIVITY ~ _LOCATION OF RELEASE @)

~ ~@ ~@ I.....___N_A_ _ _ ____. NA 8 9 10 11 44 45 80 PERSONNEL EXPOSURES r.;;:;"\

NUMBER A TYPE DE5CRIPT10N ~

CCEJ I O I O I O lL2J@

8 9 11 12 NA 1--3------------------------------------8....JO PERSONNEL INJURIES Q NUMBER DESCRIPTION~

~8 Io Io Io I~1 2 - - - - - - - - - - -NA 9 11 ... -------------------------------'80 LOSS OF OR DAMAGE TO FACILITY TYPE DESCRIPTION G

\:::;J i==ma 7 u.J@ ~ 1 0 ~ - - - - - - - - - - - -NA- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - "

9 90 PUBLICITY Q..

ISSUEDQ DESCRIPTlON ~ NRC USE ONLY "'

l2IIJ8 L R ! ~ ~ - - - - - - - - - - N _ A_ _ _ _ _ _ _ _ _ _- - - J 9 10 68 II II 69 I IIII I I I I~

80 ;

8 OJ 02 8 0 ~ff OF PREPARER _ _ _ _J_._L_._W_i_ls_o_n_ _ _ _ _ __ PHONE:_.;.(_80_4_)_3_5_7-_3_1_8_4_ _ __

0 a.

e e ATTACHMENT 1 SURRY POWER STATION, UNIT 2 DOCKET NO: 50-281 REPORT NO: 80-028/031-0 EVENT DATE: 09-26-80 TITLE OF REPORT: INOPERABLE CHECK V~VE 2-SW-113

1. Description of Event:

On September 26, 1980, with the unit operating a steady state power level of 100%, a reduction in service water pressure to the charging pumps was experienced. This reduced pressure .condition existed only when 2-SW-P-lOB was operating. Subsequent troubleshooting indicated that the discharge check valve, 2-SW-113, on the non-operating redundant pump (2-SW-P-lOA) was open. This is contrary to Technical Specification 3.3.A.8.b and is re-portable .per Technical Specification 6. 6. 2. b (2).. While investigating the event, it became apparent that 2-SW-P-lOB may have been operated in .degraded mode without prcrper administrative*measures in place. Specifically, the internals for check valve 2-SW-113.,were removed and documentation o.f this temporary modification was not performed. This is contrary to Technical Specification 6.4.D and is repo*rtable per Technical Specification 6.6.2.b(3).

When this modification was performed,. cannot be determined. However, both pumps were proven operable, utilizing PT-18.8, on September 6, 1980.

2. Probable Consequences and Status of Redundant Equipment:

The charging pump service water pumps supply cooling water to the charging pump intermediate seal and lube oil coolers. With the "A" pump's discharge isolated, 2-SW-P-lOB was operable and was performing its intended function.

Therefore, the health and safety of the public were not affected.

3. Cause of Occurrence:

The cause of the event was a missing valve disk for 2-SW-113. Investigation revealed that the valve disk was removed during a previous maintenance activity.

Documentation of the previous maintenance was not performed.

4. Immediate Corrective Action:

The immediate corrective action was to close the discharge valve for pump "A".

This allowed 2-SW-P-lOB to function as designed. A maintenance request was issued to repair 2-SW-113.

5. Subsequent Corrective Action:

Check valve 2-SW-113 was replaced and tested.

6.
  • Actions Taken To Prevent Reccurrence:

Operation and maintenance personnel have been reinstructed in the proper *method of performance of work on Safety-Related systems.

7. Generic Implications:

None