Requests Addl Exemptions from Listed 10CFR50,App R Requirements,Per 831228 Ltr,Explaining Significant Deviation in Interpretation Provided in Generic Ltr 83-33. Justification Will Be Submitted by 840131
ML18089A489
Person / Time
Site: Salem  PSEG icon.png
Issue date: 01/13/1984
From: Liden E
Public Service Enterprise Group
To: Varga S
Office of Nuclear Reactor Regulation
References
GL-83-33, NUDOCS 8401200185
Download: ML18089A489 (4)


Text

e CPS~G Public Service Electric and Gas Company P.O. Box 236 Hancocks Bridge, New Jersey 08038 Nuclear Department January 13, 198fy Director of Nuclear Reactor Regulation

u. s. Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, MD 20014 Attention: Mr. Steven Varga, Chief Operating Reactors Branch 1 Division of Licensing Gentlemen:

REQUEST FOR EXEMPTIONS FROM 10 CFR 50, APPENDIX R SALEM GENERATING STATION NO. 1 AND 2 UNITS DOCKET NOS. 50-272 AND 50-311 This letter requests additional exemptions from 10CFR50 Appendix R for Salem Generating Station Units 1 and 2. As explained in our letter to you dated December 28, 1983, staff interpretation of 10CFR50 Appendix R provided in Generic Letter 83-33 represents significant deviation from the definitions used by PSE&G. This plant specific definition was developed following the criteria used by NRR in their evaluation of Salem Generating Station's fire protection program. To comply with the redefinition, PSE&G will need additional modification and/or exemptions from Appendix R. Our letter dated December 28, 1983 provided you with a description of the deviations and a list of fire areas where exemptions were requested to clarify our conformance to Appendix R criteria. While developing appropriate references and detailed justification for these exemptions, we have identified additional areas where similar exemptions from Appendix R are needed. Attached is a list of these exemption requests.

These exemptions will not compromise the safe shutdown capability of Salem Generating Station in the event of a fire.

The types of exemptions requested are similar to those previously granted for Salem and other licensees.

I. s4012001esa4oir3------'1 PDR ADOCK 05000272  :

F PDR The Energy People 95-2168 (SOM) 11-82

u. S. Nuclear Regulatory Commission 1/13/83 A detailed justification for these exemptions will be submitted to you by January 31, 1984.

Sincerely, E. A. Liden Manager - Nuclear Licensing and Regulation cc: Mr. Donald C. Fischer Licensing Project Manager Mr. James Linville Senior Resident Inspector

ATTACHMENT SALEM GENERATING STATION UNITS NO. 1 AND 2 REQUESTS FOR EXEMPTION FROM 10CFR50 APPENDIX R

1. Electrical Penetration (El.100)

An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2a to the extent that the emergency door leading to the Inboard Mech. Pen. area does not constitute a 3-hour rated barrier.

2. Upper Electrical Penetration (El.100)

An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2c to the extent that the installed fire detection system is not area wide.

3. Aux. Bldg. Relay Rm (El.100)

An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2a to the extent that a non-rated fire door is installed in the 3-hour rated barrier.

4. Aux. Bldg. (El.84) PlF/P2F An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2b to the extent that the separation between charging pumps is not 20 feet.
5. Aux. Bldg. (El.84) PlF/P2F An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2c to the extent that the component cooling heat exchanger cubicle does not constitute a 1-hour rated barrier.
6. Aux. Bldg. (El.84) PlF/P2F An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2a to the extent that the unrated fire doors do not constitute a 3-hour rated barrier.
7. Aux. Bldg. (El.64) PlB/P2B An exemption is requested from the explicit requirements of 10CFR50 Appendix R Section III.G.2a to the extent that the unrated fire doors do not constitute a 3-hour rated barrier.