r** ,.,

i.. ....,

PS~G Public Service Electric and Gas Company 80 Park Plaza Newark, N.J. 07101 Phone 201/430-7000 April 9, Mr. Boyce H. Grier Director of USNRC Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 81-29/03L Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 81-29/03L. This report is required within thirty (30) days of the occurrence.

Sincerely yours,

/4WJM'tf" R. A. Uderitz General Manager -

Nuclear Production CC: Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies)

% 2ll01 13~0°!1 ~ 8C

Report Number:

e 81-29/03L Report Date: April 9, 1981 Occurrence Date: 3/14/81 Facility: Salem Generating Station - Unit 1 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Diesel Generator Inoperable (lA)

Erratic Governor Control CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 - Rx Power 100% - Unit Load 1130 MW DESCRIPTION OF OCCURRENCE:

During normal operation, while performing Surveillance Test SP(O) 4.8.1.1.2, Diesel Generator lA was declared inoperable because erratic governor control prevented the raising of the generator load to > 1400 KW as required by the surveillance test. Action Statement 3.8~1.l.b was entered at 0210 hours0.00243 days <br />0.0583 hours <br />3.472222e-4 weeks <br />7.9905e-5 months <br />.

Investigation revealed that the governor oil system was approximately one quart low. Oil was added, the system vented and a satisfactory surveillance test completed. The Action Statement was terminated at 1048 hours0.0121 days <br />0.291 hours <br />0.00173 weeks <br />3.98764e-4 months <br />.

This occurrence constituted operation in a degraded mode IAW Technical Specification 6.9.1.9.b.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Procedure Inadequacy ANALYSIS OF OCCURRENCE:

No procedure currently exists which directs the operators to check the governor oil sump level on a routine basis.

CORRECTIVE ACTION:

Inspection Orders IO 100733 (Unit 1) and IO 100734 (Unit 2) have been issued which require operating personnel to check the governor oil sump levels on all diesel generators monthly.

FAILURE DATA:

Not Applicable Prepared By W. J. Steele Station SORC Meeting No. 81-26