Category:CORRESPONDENCE-LETTERS
MONTHYEARML17355A4601999-10-26026 October 1999 Forwards Revised Epips,Including Revs to 0-EPIP-1102, 0-EPIP-1212,0-EPIP-20110,0-EPIP-20111,0-EPIP-20132, 0-EPIP-20133 & 0-EPIP-20201,per 10CFR50.54(q) & 10CFR50, App E.Epip 0-EPIP-20107,has Been Deleted ML17355A4301999-10-0808 October 1999 Forwards Rev 16 of Updated Fsar.Info Accurately Reflects Plant Changes Made Since Previous Submittal.Rev Incorporates Changes Completed Between 971015 & 990408.Summary of Accuracy Review Changes & Instructions,Included ML17355A4461999-10-0404 October 1999 Notifies NRC of Change in Commitment to Perform Periodic Testing of Critical Welds & Parts on Special Lifting Devices IAW NUREG-0612.Use of Ae Technology Will Provide Same Level of Testing Quality as Did NDE Methods Noted in ANSI Std L-99-208, Forwards Changes,Tests & Experiments Made as Allowed by 10CFR50.59 for Period Covering 971014-990408. Summary of PORV Actuations & Results of Plants SG Tube Insp,Which Occurred During That Time Included1999-10-0404 October 1999 Forwards Changes,Tests & Experiments Made as Allowed by 10CFR50.59 for Period Covering 971014-990408. Summary of PORV Actuations & Results of Plants SG Tube Insp,Which Occurred During That Time Included ML17355A4291999-10-0404 October 1999 Forwards Response to NRC Telcon Questions Re License Amend Request Dtd 990727,proposing Amend on one-time Basis to Modify TS 3.8.1.1 & TS 3.4.3 & 3.5.2 to Extend Allowed Outage Time for EDG from 72 H to 7 Days ML20212M1601999-09-28028 September 1999 Refers to 990908 Engineering Meeting Conducted at NRC Region II to Discuss Engineering Issues at Lucie & Turkey Point Facilities.List of Attendees & Copy of Presentation Handout Encl ML17355A4251999-09-22022 September 1999 Forwards NRC Form 536 in Response to NRC Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams, Issued 990820 ML17355A4111999-09-0909 September 1999 Informs That Thermo-Lag Upgrades for Fire Zones 47,54,113, 114,115,116,118,119,120 & 143 Completed on 990726,per GL 92-08 ML17355A4131999-09-0707 September 1999 Forwards Revised Relief Request 20 Re Requirement to Perform Exams as Required by IWL-2524 & IWL-2525,Table IWL-2500-1 for Exempt Tendon Insp,Per Recent Discussions with NRC ML17355A4141999-09-0202 September 1999 Documents That Util Has No Concerns or Challenges Related to site-specific Written Exam Administered at Plant on 990830 ML17355A4041999-08-23023 August 1999 Forwards Info to Support Assessment of Potential Risks Associated with Proposed Civil Aircraft Operations at Former Homestead Air Force Base to FP&L Turkey Point Nuclear Facility Units 3 & 4 ML17355A4071999-08-23023 August 1999 Informs That FPL Has Completed Review of Info Listed in Reactor Vessel Integrity Database,Version 2 & Found Listed Discrepancies,Re Closure of GL 92-01,rev 1,suppl 1, Reactor Vessel Structural Integrity. ML17355A4061999-08-23023 August 1999 Forwards Semiannual FFD Performance Rept for Period of Jan- June 1999,for Turkey Point Units 3 & 4.List of Events Reported & Summary of Mgt Actions Taken,Included ML17355A4001999-08-20020 August 1999 Informs That on 990722,util Determined Blind Specimen Submitted to Smithkline Beecham Clinical Labs on 990721,was Reported Back with Unsatisfactory Results.Attachment 1 Is Summary of Investigation of Unsatisfactory Performance ML17355A3941999-07-27027 July 1999 Submits Response to NRC AL 99-02, Operating Reactor Licensing Action Estimates, for FY00 & FY01 ML17355A3871999-07-16016 July 1999 Provides Supplement to FP&L Response to NRC Request for Info Re Y2K Readiness at Nuclear Power Plants ML17355A3851999-07-14014 July 1999 Informs That Pages Missing from 1998 Annual Radiological Environ Operating Rept, Contain Info Unrelated to ODCM- Specified Sampling & Were Not Included as Part of Rept ML17355A3711999-07-0606 July 1999 Forwards Revised EPIPs 0-EPIP-20201, Maintaining Emergency Preparedness - Radiological Emergency Plan Training & 0-EPIP-20126, Off-Site Dose Calculations. with Summary of Changes ML17355A3591999-06-30030 June 1999 Forwards Turkey Point,Unit 4 ISI Rept. Listed Repts Are Encl.No Eddy Current Exams Scheduled for Unit 4 Steam Generators ML17355A3661999-06-30030 June 1999 Forwards Florida Power & Light Topical QA Rept, Dtd June 1999.Encl I Includes Summary of Changes Made to Topical QA Rept Since 1998 ML17355A3571999-06-28028 June 1999 Informs That Util Voluntarily Reporting Facility Readiness as Outlined in Suppl 1 to GL 98-01.Encl Is Y2K Readiness Disclosure for Units 3 & 4,reporting Status of Facility Y2K Readiness ML17355A3521999-06-18018 June 1999 Forwards Response to NRC 990415 RAI Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves. ML17355A3491999-06-0404 June 1999 Forwards Summary of Corrective Actions Implemented by FPL Re GL 96-06, Assurance of Equipment Operability & Containment Integrity During Design Basis Accident Conditions. ML17355A3441999-05-27027 May 1999 Modifies FPLs Consent to Confirmatory Order to Reflect Resolution of Four Issues Identified as Pending in L-99-031 ML17355A3451999-05-24024 May 1999 Requests Waiver of 520 Hours (13 Wks) Required Parallel Watchstanding in Control Room Prior to License Application Submittal for W Conley ML17355A2921999-04-22022 April 1999 Forwards Rev 35 to Turkey Point EP & Revised EPIP 0-EPIP-20101, Duties of EC, Per Requirements of 10CFR50, App E & 10CFR50.54(q).Summary of Changes,Encl.Implementation Date for Both Documents Was 990330 ML20205M0431999-04-13013 April 1999 Eighth Partial Response to FOIA Request for Records.App Q & R Records Encl & Being Made Available in PDR ML17355A2891999-04-0909 April 1999 Forwards Relief Request 20, Exempt Tendon Insp, Requesting Relief from ASME Section XI Code,1992 Edition,Paragraph IWL-2521.1(c) Which Requires That Each Exempted Tendon Be Examined IAW IWL-2524 & IWL-2525.Approval Needed by 991001 ML17355A2861999-04-0505 April 1999 Forwards COLR for Turkey Point Unit 4,Cycle 18,IAW TS 6.9.1.7 ML17336A0681999-04-0101 April 1999 Expresses Support for FP&L Request for Waiver of Applicable Review Fees Upon FP&L Submittal of an Application for License Renewal for Turkey Point Units 3 & 4 ML17355A2751999-03-25025 March 1999 Informs NRC & Staff of Fp&Ls Plans to Submit License Renewal Application for Turkey Point Units 3 & 4 by End of Dec 2000 ML17355A2641999-03-19019 March 1999 Requests Changes to FPL Official Service List for Turkey Point,Units 3 & 4.Add s Franzone & Remove G Hollinger from All Correspondence ML17355A2651999-03-19019 March 1999 Forwards Annual Radioactive Effluent Release Rept for Jan-Dec 1998 & Rev 7 to ODCM for Gaseous & Liquid Effluents from Turkey Point,Units 3 & 4. ML17355A2621999-03-16016 March 1999 Forwards Special Rept as Result of Turkey Point Unit 3 End-of-Cycle 16 ISI of SG Tubes.Rept Summarizes Results of SG Tube ISI ML17355A2631999-03-12012 March 1999 Forwards FPL Decommissioning Fund Status Repts for St Lucie, Units 1 & 2 & Turkey Point,Units 3 & 4.Rept for St Lucie, Unit 2 Provides Status of Decommissioning Funds for All Three Owners of That Unit ML20204C6991999-03-10010 March 1999 Requests Amend to Turkey Point PSP to Modify Requirement to Post Security Officers to Provide Continuous Observation of Entire PA Perimeter in Event of Security Computer Failure. Change to Security Force Staffing Level Also Requested ML17355A2451999-03-0909 March 1999 Submits Info on FPL Current Levels of Nuclear Property Insurance,Per 10CFR50.54(w)(3) ML17355A2501999-03-0808 March 1999 Informs That Licensee Reviewed NRC 990228 Ltr Issuing Exemption Requested Re Fire Rating of Raceway Fire Barriers in Open Turbine Bldg.Tabulated Summary of Util Comments & Marked Copy of NRC Ltr & SER Encl ML17355A2441999-03-0101 March 1999 Provides Update to Util Written Notices,Dtd 961120 & 970627 of Claim Involving Alleged Bodily Injury Arising Out of or in Connection with Use of Radioactive Matl at Units 3 & 4 ML17355A2431999-02-25025 February 1999 Informs That FPL Does Not Have Any Candidates from Turkey Point Scheduled to Participate in 990407,Generic Fundamentals Examination (GFE) ML17355A2301999-02-18018 February 1999 Forwards Semiannual Fitness for Duty Performance Data for Period of 980701-981231 for Turkey Point Units 3 & 4 ML17355A2361999-02-18018 February 1999 Forwards Tabulation of 1998 Occupational Exposure Data for Turkey Point,Units 3 & 4,per TS 6.9.1.2.a.Reactor Coolant Specific Activity Limits of 100/E-bar Mci Per Gram of Gross Radioactivity Were Not Exceeded During 1998 L-99-042, Forwards Rev 13 to Turkey Point Physical Security Plan,Per 10CFR50.54(p).Util Determined That Rev Does Not Decrease Safeguards Effectiveness of Plan.Encl Withheld,Per 10CFR2.790(a)(3)1999-02-18018 February 1999 Forwards Rev 13 to Turkey Point Physical Security Plan,Per 10CFR50.54(p).Util Determined That Rev Does Not Decrease Safeguards Effectiveness of Plan.Encl Withheld,Per 10CFR2.790(a)(3) ML17355A2341999-02-18018 February 1999 Provides Response to RAI Re GL 97-01, Degradation of Crdm/ CEDM Nozzle & Other Vessel Closure Head Penetrations. ML17355A2231999-02-0808 February 1999 Informs That Util Will Comply with Commitment with Respect to Units 3 & 4,in Response to Ja Zwolinski 990129 Ltr.Util Also Agrees to Incorporate Commitment Into Confirmatory Order Modifying License Effective Immediately Upon Issuance ML17355A2031999-01-29029 January 1999 Forwards Rev 3 to Turkey Point Nuclear Plant Recovery Plan. Rev Does Not Decrease Effectiveness of Plan ML17355A2171999-01-20020 January 1999 Forwards Listed ISI Repts for Turkey Point Unit 3,in Accordance with Provisions of ASME Code,Section XI ML17354B2241999-01-0606 January 1999 Forwards Annual 10CFR50.46 Rept Re Changes To,Or Errors Discovered in ECCS Evaluation Models,Or in Application of Such Models That Effect Peak Clad Temp Calculation ML17354B2081998-12-15015 December 1998 Informs That Fpl,In Cooperation with State of Fl & County Emergency Response Agencies,Will Conduct Exercise of Turkey Point Radiological Emergency Plan on 990210.Scenario Package Forwarded to Emergency Preparedness Section Chief,Region II ML17354B2091998-12-15015 December 1998 Forwards Price Anderson Guarantees Annual Financial Rept,Per 10CFR140.21.Exhibit 1 Submitted to Satisfy Annual Financial Reporting Requirement of 10CFR50.71(b) 1999-09-09
[Table view] Category:INCOMING CORRESPONDENCE
MONTHYEARML17355A4601999-10-26026 October 1999 Forwards Revised Epips,Including Revs to 0-EPIP-1102, 0-EPIP-1212,0-EPIP-20110,0-EPIP-20111,0-EPIP-20132, 0-EPIP-20133 & 0-EPIP-20201,per 10CFR50.54(q) & 10CFR50, App E.Epip 0-EPIP-20107,has Been Deleted ML17355A4301999-10-0808 October 1999 Forwards Rev 16 of Updated Fsar.Info Accurately Reflects Plant Changes Made Since Previous Submittal.Rev Incorporates Changes Completed Between 971015 & 990408.Summary of Accuracy Review Changes & Instructions,Included ML17355A4461999-10-0404 October 1999 Notifies NRC of Change in Commitment to Perform Periodic Testing of Critical Welds & Parts on Special Lifting Devices IAW NUREG-0612.Use of Ae Technology Will Provide Same Level of Testing Quality as Did NDE Methods Noted in ANSI Std L-99-208, Forwards Changes,Tests & Experiments Made as Allowed by 10CFR50.59 for Period Covering 971014-990408. Summary of PORV Actuations & Results of Plants SG Tube Insp,Which Occurred During That Time Included1999-10-0404 October 1999 Forwards Changes,Tests & Experiments Made as Allowed by 10CFR50.59 for Period Covering 971014-990408. Summary of PORV Actuations & Results of Plants SG Tube Insp,Which Occurred During That Time Included ML17355A4291999-10-0404 October 1999 Forwards Response to NRC Telcon Questions Re License Amend Request Dtd 990727,proposing Amend on one-time Basis to Modify TS 3.8.1.1 & TS 3.4.3 & 3.5.2 to Extend Allowed Outage Time for EDG from 72 H to 7 Days ML17355A4251999-09-22022 September 1999 Forwards NRC Form 536 in Response to NRC Administrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams, Issued 990820 ML17355A4111999-09-0909 September 1999 Informs That Thermo-Lag Upgrades for Fire Zones 47,54,113, 114,115,116,118,119,120 & 143 Completed on 990726,per GL 92-08 ML17355A4131999-09-0707 September 1999 Forwards Revised Relief Request 20 Re Requirement to Perform Exams as Required by IWL-2524 & IWL-2525,Table IWL-2500-1 for Exempt Tendon Insp,Per Recent Discussions with NRC ML17355A4141999-09-0202 September 1999 Documents That Util Has No Concerns or Challenges Related to site-specific Written Exam Administered at Plant on 990830 ML17355A4041999-08-23023 August 1999 Forwards Info to Support Assessment of Potential Risks Associated with Proposed Civil Aircraft Operations at Former Homestead Air Force Base to FP&L Turkey Point Nuclear Facility Units 3 & 4 ML17355A4071999-08-23023 August 1999 Informs That FPL Has Completed Review of Info Listed in Reactor Vessel Integrity Database,Version 2 & Found Listed Discrepancies,Re Closure of GL 92-01,rev 1,suppl 1, Reactor Vessel Structural Integrity. ML17355A4061999-08-23023 August 1999 Forwards Semiannual FFD Performance Rept for Period of Jan- June 1999,for Turkey Point Units 3 & 4.List of Events Reported & Summary of Mgt Actions Taken,Included ML17355A4001999-08-20020 August 1999 Informs That on 990722,util Determined Blind Specimen Submitted to Smithkline Beecham Clinical Labs on 990721,was Reported Back with Unsatisfactory Results.Attachment 1 Is Summary of Investigation of Unsatisfactory Performance ML17355A3941999-07-27027 July 1999 Submits Response to NRC AL 99-02, Operating Reactor Licensing Action Estimates, for FY00 & FY01 ML17355A3871999-07-16016 July 1999 Provides Supplement to FP&L Response to NRC Request for Info Re Y2K Readiness at Nuclear Power Plants ML17355A3851999-07-14014 July 1999 Informs That Pages Missing from 1998 Annual Radiological Environ Operating Rept, Contain Info Unrelated to ODCM- Specified Sampling & Were Not Included as Part of Rept ML17355A3711999-07-0606 July 1999 Forwards Revised EPIPs 0-EPIP-20201, Maintaining Emergency Preparedness - Radiological Emergency Plan Training & 0-EPIP-20126, Off-Site Dose Calculations. with Summary of Changes ML17355A3591999-06-30030 June 1999 Forwards Turkey Point,Unit 4 ISI Rept. Listed Repts Are Encl.No Eddy Current Exams Scheduled for Unit 4 Steam Generators ML17355A3661999-06-30030 June 1999 Forwards Florida Power & Light Topical QA Rept, Dtd June 1999.Encl I Includes Summary of Changes Made to Topical QA Rept Since 1998 ML17355A3571999-06-28028 June 1999 Informs That Util Voluntarily Reporting Facility Readiness as Outlined in Suppl 1 to GL 98-01.Encl Is Y2K Readiness Disclosure for Units 3 & 4,reporting Status of Facility Y2K Readiness ML17355A3521999-06-18018 June 1999 Forwards Response to NRC 990415 RAI Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves. ML17355A3491999-06-0404 June 1999 Forwards Summary of Corrective Actions Implemented by FPL Re GL 96-06, Assurance of Equipment Operability & Containment Integrity During Design Basis Accident Conditions. ML17355A3441999-05-27027 May 1999 Modifies FPLs Consent to Confirmatory Order to Reflect Resolution of Four Issues Identified as Pending in L-99-031 ML17355A3451999-05-24024 May 1999 Requests Waiver of 520 Hours (13 Wks) Required Parallel Watchstanding in Control Room Prior to License Application Submittal for W Conley ML17355A2921999-04-22022 April 1999 Forwards Rev 35 to Turkey Point EP & Revised EPIP 0-EPIP-20101, Duties of EC, Per Requirements of 10CFR50, App E & 10CFR50.54(q).Summary of Changes,Encl.Implementation Date for Both Documents Was 990330 ML17355A2891999-04-0909 April 1999 Forwards Relief Request 20, Exempt Tendon Insp, Requesting Relief from ASME Section XI Code,1992 Edition,Paragraph IWL-2521.1(c) Which Requires That Each Exempted Tendon Be Examined IAW IWL-2524 & IWL-2525.Approval Needed by 991001 ML17355A2861999-04-0505 April 1999 Forwards COLR for Turkey Point Unit 4,Cycle 18,IAW TS 6.9.1.7 ML17336A0681999-04-0101 April 1999 Expresses Support for FP&L Request for Waiver of Applicable Review Fees Upon FP&L Submittal of an Application for License Renewal for Turkey Point Units 3 & 4 ML17355A2751999-03-25025 March 1999 Informs NRC & Staff of Fp&Ls Plans to Submit License Renewal Application for Turkey Point Units 3 & 4 by End of Dec 2000 ML17355A2641999-03-19019 March 1999 Requests Changes to FPL Official Service List for Turkey Point,Units 3 & 4.Add s Franzone & Remove G Hollinger from All Correspondence ML17355A2651999-03-19019 March 1999 Forwards Annual Radioactive Effluent Release Rept for Jan-Dec 1998 & Rev 7 to ODCM for Gaseous & Liquid Effluents from Turkey Point,Units 3 & 4. ML17355A2621999-03-16016 March 1999 Forwards Special Rept as Result of Turkey Point Unit 3 End-of-Cycle 16 ISI of SG Tubes.Rept Summarizes Results of SG Tube ISI ML17355A2631999-03-12012 March 1999 Forwards FPL Decommissioning Fund Status Repts for St Lucie, Units 1 & 2 & Turkey Point,Units 3 & 4.Rept for St Lucie, Unit 2 Provides Status of Decommissioning Funds for All Three Owners of That Unit ML20204C6991999-03-10010 March 1999 Requests Amend to Turkey Point PSP to Modify Requirement to Post Security Officers to Provide Continuous Observation of Entire PA Perimeter in Event of Security Computer Failure. Change to Security Force Staffing Level Also Requested ML17355A2451999-03-0909 March 1999 Submits Info on FPL Current Levels of Nuclear Property Insurance,Per 10CFR50.54(w)(3) ML17355A2501999-03-0808 March 1999 Informs That Licensee Reviewed NRC 990228 Ltr Issuing Exemption Requested Re Fire Rating of Raceway Fire Barriers in Open Turbine Bldg.Tabulated Summary of Util Comments & Marked Copy of NRC Ltr & SER Encl ML17355A2441999-03-0101 March 1999 Provides Update to Util Written Notices,Dtd 961120 & 970627 of Claim Involving Alleged Bodily Injury Arising Out of or in Connection with Use of Radioactive Matl at Units 3 & 4 ML17355A2431999-02-25025 February 1999 Informs That FPL Does Not Have Any Candidates from Turkey Point Scheduled to Participate in 990407,Generic Fundamentals Examination (GFE) ML17355A2341999-02-18018 February 1999 Provides Response to RAI Re GL 97-01, Degradation of Crdm/ CEDM Nozzle & Other Vessel Closure Head Penetrations. L-99-042, Forwards Rev 13 to Turkey Point Physical Security Plan,Per 10CFR50.54(p).Util Determined That Rev Does Not Decrease Safeguards Effectiveness of Plan.Encl Withheld,Per 10CFR2.790(a)(3)1999-02-18018 February 1999 Forwards Rev 13 to Turkey Point Physical Security Plan,Per 10CFR50.54(p).Util Determined That Rev Does Not Decrease Safeguards Effectiveness of Plan.Encl Withheld,Per 10CFR2.790(a)(3) ML17355A2361999-02-18018 February 1999 Forwards Tabulation of 1998 Occupational Exposure Data for Turkey Point,Units 3 & 4,per TS 6.9.1.2.a.Reactor Coolant Specific Activity Limits of 100/E-bar Mci Per Gram of Gross Radioactivity Were Not Exceeded During 1998 ML17355A2301999-02-18018 February 1999 Forwards Semiannual Fitness for Duty Performance Data for Period of 980701-981231 for Turkey Point Units 3 & 4 ML17355A2231999-02-0808 February 1999 Informs That Util Will Comply with Commitment with Respect to Units 3 & 4,in Response to Ja Zwolinski 990129 Ltr.Util Also Agrees to Incorporate Commitment Into Confirmatory Order Modifying License Effective Immediately Upon Issuance ML17355A2031999-01-29029 January 1999 Forwards Rev 3 to Turkey Point Nuclear Plant Recovery Plan. Rev Does Not Decrease Effectiveness of Plan ML17355A2171999-01-20020 January 1999 Forwards Listed ISI Repts for Turkey Point Unit 3,in Accordance with Provisions of ASME Code,Section XI ML17354B2241999-01-0606 January 1999 Forwards Annual 10CFR50.46 Rept Re Changes To,Or Errors Discovered in ECCS Evaluation Models,Or in Application of Such Models That Effect Peak Clad Temp Calculation ML17354B2081998-12-15015 December 1998 Informs That Fpl,In Cooperation with State of Fl & County Emergency Response Agencies,Will Conduct Exercise of Turkey Point Radiological Emergency Plan on 990210.Scenario Package Forwarded to Emergency Preparedness Section Chief,Region II ML17354B2091998-12-15015 December 1998 Forwards Price Anderson Guarantees Annual Financial Rept,Per 10CFR140.21.Exhibit 1 Submitted to Satisfy Annual Financial Reporting Requirement of 10CFR50.71(b) ML17354B2061998-12-0909 December 1998 Informs That Request for Exemption Specified in Section II.B.3 Will Not Be Needed Re Fire Rating of Raceway Fire Barriers in Open Turbine Bldg ML17354B1981998-11-25025 November 1998 Forwards Scope & Objective for 1999 Plant Annual Emergency Preparedness Exercise.Objectives Developed in Conjunction with State & Local Govts.Exercise Scheduled for 990210 1999-09-09
[Table view] Category:RESEARCH INSTITUTION/LABORATORY TO NRC
MONTHYEARML17348A2431990-04-0505 April 1990 Submits Results of Comparisons of Heat Rate Measurements in Reg Guide 3.54 W/Measurements Predicted by ORIGEN-S/SAS2. Cover Pages from Technical Repts Encl ML20138G8311985-10-11011 October 1985 Informs That Bnwl Employee DB Jarrell Will Assist in Support of NRC Maint & Surveillance Program,Phase I ML20136G1941985-06-25025 June 1985 Submits List of Battelle Participants Supporting NRC Maint & Surveillance Program,Phase I ML20069P2701982-10-19019 October 1982 Discusses Summary of ACRS Reactor Operations Subcommittee 820929 Meeting Re Turkey Point Cold Overpressure Incident. Tech Specs Do Not Properly Address Situations in Which Availability of Certain Sys More Vital to Safe Operation ML17341A2051981-06-0808 June 1981 Forwards Containment Leakage Rate Testing, Technical Evaluation Rept ML17340A6411980-12-12012 December 1980 Submits Info in Response to 801126 & 1202 Telcons Re Potential Drop of Steam Generator & Subsequent Release of Radioactive Matl.Release of Radioactivity Would Be Less than 10%.Forwards Article on Deposits in Primary Sys ML19344A8161980-03-27027 March 1980 Forwards Requests for Addl Info to Complete Evaluation of Reactor Bldg Crane to NUREG-0554 Requirements ML17339A5011980-01-22022 January 1980 Forwards Final Inputs for 6-month Period Re Util Fire Protection Review.Recommends Acceptance of Plans for Fire Detection Sys & Proposal for Screen Wash Pump as Backup. Mod Necessary on Water Suppression Sys ML17338A3441978-12-0606 December 1978 Discusses Fire Protection in Operating Nuclear Power Stations,In Particular Providing Analysis of Facilities' Ser.Proposed Fire Protection Mod Increases Level of Protection Against Fire Hazards ML17338A3461978-09-21021 September 1978 Requests Addl Info Re Fire Protec at Subj Facils.Info Concerns Water Supply,Cable Protec,Yard Hydrants,Smoke Venting Equip & Smoke Removal.Documentation Re Info Sought Encl 1990-04-05
[Table view] |
Text
REGULATORY I HMATION DISTRIBUTION SYST (RIDS)
ACCESSION NBR: 8001300333 DOC ~ DATE ~ 80/01/22 NOTARIZED: NU DOCKET Planti t 3i Florida. l ower and *Light 05000250 AU [H ~ AAMh PIALCgH,h,
'U FACED:50 250 Tur key Po>nt
'"'"50 251urkey Point Pl anti I HUR AFPILlATIOtl Oni On'i t 4i 8'lor'ida Power and L"ight Brookhaven Natatorial Laboratory G
C 05ooo251 APL'l&~ NAME HEC/PiEHT" Af FELIAt'10A FEAGUSONrR,LE Plant Systems Branch SUBJECT; Forwards final inputs for six month period re util fire protection'eview, Recommends acceptance'f pl'ans tot fire detection sys 4 proposa) for screen wash pump as backups Mod n'ecessary on water suppression sys.
DISTRIBUTION CODE: AOOeS COPIES RECEIVED:LTR ENCL L SIZE~ g i'IlCE: Fir e Protect ion Information lAfter Issuance o7 OP Cfc ~ ~ )
N QTES TES ~
REG IP I EN l COPIES REGIP IEN l COPIES 10 CUOPNAI~K PNGL ID CUOh/NAME LllA ENCL' AG'l ION: 05 BC bg8 +/
IN'I'EHNAL; 0 1 1 02 NRC PDR 09 Ie'2 2 2 1'i 'i'APKOO-AUX IL SYS BH 14 PLAA'i SYS UH i9 RAMH'A'GR" i i 20 AUHAAARK<H'0 i
OELD i 0 KXTEHNAL: 03 LPDR 1 NSIC 1 -1 16 P ACAS 16 TOTAL NUMBER OF COPIES REQUIRED; LT'lR 37 ENCL 36
0 tr g e a l I (
l 9
g I
o W II lI I
tp.'g
OIjo~0 BROOKHAVEN NATIONALLABORATORY ASSOCIATED UNIVERSITIES, INC.
Upton, New York 11973 Department of Nuclear Energy (516) 345- 2144 January 22, 1980 Nr. Robert L. Ferguson Plant Systems Branch U.S. Nuclear Regulatory Commission Washington, D.C. 20555 RE: Turkey Point Nuclear Power Plant, Fire Protection Review Items 3.1.1, 3.1.2, 3.1.6, 3.1.7, and 3.1.15
Dear Bob:
Attached hereto are the final Brookhaven National Laboratory inputs scheduled for this 6 month period:
3.1.1 Fire Detection System 3.1.2 Fire Water Supplies 3.1.6 Water Suppression System 3.1.7 Foam Suppression 3.1.15 Hydrogen Supply Lines Respectfully yours, Robert E. Hall, Group Leader Reactor Engineering Analysis REH:EAN:sd attachment cc.: R. Cerbone wo/enc.
W. Kato E. f)acDougall V. Panciera wo/enc.
E. Sylvester Woo(,
gh
~ ~
e
TURKEY POINT Fire Protection Review Item 3.1.1 Fire Detection S stem The SER states early warning automatic fire detection systems will be provided in the switchgear rooms and in the charging pump rooms.
The licensee's submittal with a cover letter dated December 20, 1979 provided design details for asterisked items 3.1.1(4) and 3.1.1(5) as noted in the SER.
The information is in the form of layout drawings and manufacturers equipment descriptions. The areas addressed by this submittal are the diesel generator rooms and the switchgear rooms.
The majority of fire detection heads are of the ionization high voltage type.
A flame detector will be installed in the diesel generator room and a heat de-tector in the diesel day tank room. The diesel generator rooms are zoned on a single zone with remote lamps at a zone control panel. The remote lamps divide the diesel generator building into two mirror images with a diesel generator and its associated day tank on a single remote lamp. The zone con-trol panel is located between the Rod Control Drive Rooms.
The switchgear rooms are divided by elevation and division. Each switchgear room associated with a unit (either Unit 3 or 4) has its own zone. The zone is then divided into three remote lamp annunciation at the zone panel.
On drawing 5177-100-E-12, the plan view shows detector 16-1 and 16-6 as DFS-10 Pyrotronics flame detectors while the electrical systematic at the top of the page labels these detectors as DTF136P Pyrotronics Thermal detectors. The flame detector should be installed in the diesel generator room.
Based on the above review and comment, we recommend that the preliminary plans and equipment be accepted. Any significant changes in the preliminary sub-mittal should be reviewed and approval obtained.
Item 3.2.2 Fire Hater Su l 3.2.3 The SER dated Harch 21, 1979, Item No. 3.1.2 "Fir e Water Supply" requires the licensee to provide an analysis of the fire water demand at the plant. This analysis would demonstrate the adequacy of the screen wash pumps to provide adequate back-up to the fire pumps. The SER also required, if the analysis proved favorable, that the spool piece connection between the screen wash pump and the fire protection system be permanent.
An analysis submitted under cover letter dated May 21, 1979 is inadequate. No substantiating calculations have been submitted to verify numbers given.
A revisit to the plant in October, 1979 verified that the curb would prevent oil from entering the condensate pit and the heat from the postulated fire would not actuate spri nklers in the pit. Also duri ng our visit various deluge
ZP systems for the hydrogen seal oil unit, for the auxiliary transformer and for the main transformer were noted in the area where a common fire could create the maximum fire water demand. All these deluge systems have to be taken into consideration when calculating the fire water demand because they could be set off by a common fire. With the addition of these deluge systems to the fire water demand, the screen wash pump rated at 1680 gpm at 84.4 psi cannot meet this requirement.
The plant's proposal to use the screen wash pump as a backup to the fire pumps is unacceptable. If the pumps could meet the demand, the connection between the screen wash system and fire protection system would have to be permanent.
Based upon the above review, the evaluation documented in the May 21, 1979 letter and the proposed modification documented in the October 8, 1979 letter are unacceptable. Please refer to Section 3.2.3 (Fire Water Supply).
3.1.6 Water Su ression S stems The SER states that fixed automatic water spray protection will be provided for the door and ventilation openings of the switchgear rooms which face main and auxiliary transformers.
The licensee submittal dated October 8, 1979 provided design details for asterisked item 3.1.6 "Water Suppression Systems" as noted in the SER. The areas addressed by this submittal are the water curtains for Unit 3 Switchgear Room Door and Vent and for Unit 4 Switchgear Door and Vent.
Two sidewall heads protect the louvered opening while one head protects the door opening. The basic design criteria appears adequate but we recommend that the following changes be made.
- 1. Minimum pipe size should be 1 inch.
- 2. No bushings should be used.
- 3. Heat collectors should be provided on sprinkler heads.
- 4. A waterflow switch should be provided on feed with annunciation in the control room.
- 5. The feed for these sprinkler heads should be independent of the feeds for the deluge systems.
Based upon the above review, the general criteria is'cceptable but we recom-mend that the design be modified as indicated above. Overall approval is based on the acceptance of these modifications.
3.1.7 Foam Su r'essi on The SER states that portable foam suppression equipment will be provided and that a means will be provided for introducing foam from a portable foam system into the diesel generator rooms and diesel fuel oil day tank rooms.
The licensee under cover letter dated October 8, 1979, submitted the design details for the implementation of SER item 3.1.7 "Foam Suppression." The SER requires the utility to provide access for introducing foam into the diesel generator rooms and diesel generator day tank rooms without opening doors to expose fire brigade personnel to a fire atmosphere.
U The design consists of two (2) four-inch sleeves through the wall and one four-inch opening in the door for each diesel generator room. The location of openings appear to be placed to provide complete coverage of the diesel generator area. We recommend that the utility confirm that the penetrations are of sufficient size to accommodate the portable foam equipment purchased by the plant.
The drawings submitted do not show the penetrations into the diesel day tank room. We recommend that final approval for 3.1.7 "Foam Sppression" be with-held until the penetrations for the diesel day tank room have been submitted and reviewed.
3.1.15 H dro en Su 1 Lines The SER states that the use of the hydrogen supply lines in the auxiliary building corridor will be discontinued and new lines will be provided for use outside of this area.
The licensee submittal, with a cover letter dated October 8, 1979, provided design criteria for asterisked item 3.1.15 concerning the rerouting of the hydrogen supply line. Presently this supply line is routed through the auxiliary building corridor thus exposing safety related equi pment.
The licensee has indicated that the existing supply line will be removed and the new hydrogen line will run on the roof of the Auxiliary Building to a point near the Units 3 and 4 volume control tanks. At this point the lines will penetrate the roof and be routed to the respective tanks.
Based on the review of the above criteria, the rerouting of the hydrogen sup-ply line outside the Auxiliary Building corridor is acceptable.