Responds to Violations Noted in Insp Repts 50-335/86-02 & 50-389/86-01.Corrective Actions:Operating Personnel Instructed to Shut Auxiliary Bldg Doors When Found Open
ML17308A213
Person / Time
Site: Saint Lucie  NextEra Energy icon.png
Issue date: 04/07/1986
From: Woody C
FLORIDA POWER & LIGHT CO.
To: Grace J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
L-86-154, NUDOCS 8604210155
Download: ML17308A213 (4)


Text

~l l~

P.O. BOW 029100 MIAMI, FL 33102 FLORIDA POW R & LIGHt COXIPANY I

7 )986 L-86-150 Dr. 3. IVelson Grace Regional Administrator, Region II U. S. IVuclear Regulatory Commission 101 Marietta Street IV.W., Suite 2900 Atlanta, Georgia 30323

Dear Dr. Grace:

Re: St. Lucie Units 1 and 2 Docket IVos. 50-335 and 50-389 Ins ection Re ort 86-02/01 Florida. Power R Light Company has reviewed the subject inspection report, and a response is attached.

There is no proprietary information in the report.

Very truly yours, C. O. Wo Group e President IVuclear Energy COW/PLP:de Attachment cc: Harold F. Reis PNS-LI-86-111 t 8bO+ 101>5 Pop OQCH, 0>

00~~

pg Ll:1 PEOPLE... SERVING PE. > ~

~ <

ATTACHMENT St. Lucie Units 1 and 2 Docket Nos. 50-335 and 50-389 lns ection Re ort 86-02/Ol Finding:

Final Safety Analysis Report (FSAR) paragraphs 9.0, air conditioning, heating, cooling and ventilation system, and 9.0.3.1, Reactor Auxiliary Building (RAB) ventilation systems, state the 'design criteria/objectives for these systems as follows:

a. provide air flow areas of low potential radioactivity to areas of progressively higher potential radioactivity (with exterior doors closed),
b. assure that the ventilation system operation during normal operation does not cause an annual offsite release of gaseous radioactivity from the plant to exceed limits allowed by 10 CFR 50, Appendix I,
c. ventilation air exhausted from potentially contaminated areas is filtered for the removal of particulates as required to satisfy 10 CFR 50, Appendix I, and
d. air exhausted from the shield building annulus, fuel handling building and reactor auxiliary building (main ventilation system) is first filtered, and then discharged to the environment through vent stacks in order to facilitate an overall measurement of gaseous releases and to prevent potential contamination of ventilation air intakes.

Contrary to the above, on November 15, 1985, these FSAR design criteria/objectives could not be met in that several RAB exterior doors were blocked open and the RAB ventilation lineup was improper, i.e., building pressure was positive with air flow from inside to outside.

Response

1. FPL has instru'cted the operating personnel to shut doors when found open.

Management personnel have been directed to take steps to ensure their personnel are aware of the need to maintain the Reactor Auxiliary Building (RAB) door closed.

2. FPL considered that the subject finding was caused by inattention to detail by all site personnel regarding the maintenance of the RAB doors in the proper position. FPL has determined that the increased attention given this area should preclude recurrence.
3. FPL has instructed Guard Force Personnel to close RAB outside doors during routine security checks or notify the Operating Shift Supervisor if unable to close door.