MONTHYEARML0507603362005-03-12012 March 2005 February 2005 Monthly Operating Report for Watts Bar Nuclear Plant ML0504503612005-02-0808 February 2005 January 2005 Monthly Operating Report for Watts Bar ML0502101552005-01-14014 January 2005 December 2004 Monthly Operating Report for Watts Bar Nuclear Plant, Unit 1 ML0435501362004-12-14014 December 2004 November 2004 Monthly Operating Report for Watts Bar Nuclear Plant ML0432005472004-11-10010 November 2004 October 2004 Monthly Operating Report for Watts Bar Nuclear Plant ML0429504722004-10-15015 October 2004 September 2004 Monthly Operating Report for Watts Bar Nuclear Plant, Unit 1 ML0425904872004-09-0909 September 2004 August 2004 Monthly Operating Report for Watts Bar Nuclear Plant ML0423202812004-08-16016 August 2004 July 2004 Monthly Operating Report for Watts Bar Unit 1 ML0419706292004-07-13013 July 2004 June 2004 Monthly Operating Report for Watts Bar Nuclear Plant (WBN) Unit 1 ML0413902412004-05-13013 May 2004 April 2004 Monthly Operating Report for Watts Bar Nuclear Plant ML0411103702004-04-15015 April 2004 March 2004 Monthly Operating Report for Watts Bar ML0407505152004-03-11011 March 2004 February 2004 Monthly Operating Report for Watts Bar Nuclear Plant ML0404902322004-02-12012 February 2004 January 2004 Monthly Operating Report for Watts Bar, Units 1 ML0402204842004-01-14014 January 2004 December 2003 Monthly Operating Report for Watts Bar, Unit 1 ML0335102802003-12-12012 December 2003 November 2003 Monthly Operating Report for Watts Bar Unit 1 ML0332302352003-11-14014 November 2003 October 2003 Monthly Operating Report for Watts Bar, Unit 1 ML0329400272003-10-14014 October 2003 September 2003 Monthly Operating Report for Watts Bar Nuclear Plant, Unit 1 ML0326604252003-09-15015 September 2003 August 2003 Monthly Operating Report for Watts Bar Unit 1 ML0323005332003-08-15015 August 2003 July 2003 Monthly Operating Report for Watts Bar ML0320201132003-07-15015 July 2003 June 2003 Monthly Operating Report for Watts Bar Nuclear Plant ML0316710252003-06-12012 June 2003 May 2003 Monthly Operating Report for Watts Bar ML0313500962003-05-12012 May 2003 April 2003 Monthly Operating Report for Watts Bar Nuclear Plant ML0310701052003-04-14014 April 2003 March 2003 Monthly Operating Report for Watts Bar Nuclear Plant ML0307900142003-03-14014 March 2003 February 2003 Monthly Operating Report for Watts Bar Nuclear Plant ML0304400782003-02-10010 February 2003 January 2003 Monthly Operating Report for Watts Bar Nuclear Plant ML0301701562003-01-14014 January 2003 December 2002 Monthly Operating Report for Watts Bar Nuclear Plant ML0234603572002-12-10010 December 2002 November 2002 Monthly Operating Report for Watts Bar ML0232402492002-11-15015 November 2002 October 2002 Monthly Operating Report for Watts Bar Unit 1 ML0229100172002-10-15015 October 2002 September 2002 Monthly Operating Report for Watts Bar ML0226102012002-09-13013 September 2002 August 2002 Monthly Operating Report for Watts Bar ML0223404212002-08-15015 August 2002 July 2002 Monthly Operating Report for Watts Bar ML0219801632002-07-12012 July 2002 June 2002 Monthly Operating Report for Watts Bar ML0217006882002-06-12012 June 2002 May 2002 Monthly Operating Report for Watts Bar ML0214803422002-05-10010 May 2002 April 2002 Monthly Operating Report for Watts Bar, Unit 1 ML0211306322002-04-12012 April 2002 March 2002 Monthly Operating Report for Watts Bar Nuclear Plant ML0208702582002-03-14014 March 2002 February 2002 Monthly Operating Report for Watts Bar Nuclear Plant, Unit 1 ML0206402052002-02-14014 February 2002 January 2002 Monthly Operating Report for Watts Bar Nuclear Plant, Unit 1 ML0201802172002-01-15015 January 2002 December 2001 Monthly Operating Report for Watts Bar Nuclear Plant 2005-03-12
[Table view] |
Text
Tennessee Valley Authority, Post Office Box 2000, Spnng City, Tennessee 37381-2000 10 CFR 50.4 OCT 1 5 2002 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Gentlemen:
In the Matter of ) Docket Nos. 50-390 Tennessee Valley Authority WATTS BAR NUCLEAR PLANT (WBN) - SEPTEMBER 2002 MONTHLY OPERATING REPORT Enclosed is the September 2002 Monthly Operating Report as required by WBN Technical Specification Section 5.9.4. If you have any questions concerning this matter, please call me at (423) 365-1824.
Sincerely, ace Manager, Site Licensing and Industry Affairs Enclosure cc: See page 2 PFriledon recycled paper
U.S. Nuclear Regulatory Commission Page 2 OCT 1 5 2002 cc (Enclosure):
NRC Resident Inspector Watts Bar Nuclear Plant 1260 Nuclear Plant Road Spring City, Tennessee 37381 Mr. L. Mark Padovan, Senior Project Manager U.S. Nuclear Regulatory Commission MS 08G9 One White Flint North 11555 Rockville Pike Rockville, Maryland 20852-2738 U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth St., SW, Suite 23T85 Atlanta, Georgia 30303
ENCLOSURE TENNESSEE VALLEY AUTHORITY WATTS BAR NUCLEAR PLANT (WBN)
MONTHLY OPERATING REPORT SEPTEMBER 2002 UNIT 1 DOCKET NUMBER 50-390 LICENSE NUMBER NPF-90
OPERATING DATA REPORT Docket No. 50-390 Unit Name: WBN Unit I Date: October 3, 2002 Completed By: D. K. Flournoy Telephone: (423) 365-3803 Reporting Period: September 2002
- 1. Design Electrical Rating (MWe-Net): 1155
- 2. Maximum Dependable Capacity (MWe-Net): 1125 Month Year-to-Date Cumulative
- 3. Number of Hours 720 5857.64 50956.5 Reactor was Critical
- 4. Hours Generator 720 5790.62 50691.2 On-Line
- 5. Unit Reserve 0.0 0.0 0.0 Shutdown Hours
- 6. Net Electrical Energy Generated 811209 6521624 55908340 (MWh)
E-1
UNIT SHUTDOWNS DOCKET NO: 50-390 UNIT NAME: WBN-1 DATE: October 3, 2002 COMPLETED BY: D. K. Floumoy TELEPHONE: (423) 365-3803 REPORT PERIOD: September 2002 Cause and Corrective Action to Prevent Recurrence 2 3 Method 4Instructions for Preparation of
'F: Forced Reason:
S: Scheduled A-Equipment Failure (Explain) 1-Manual Data Entry sheets for Licensee B-Maintenance or Test 2-Manual Trip/Scram Event Report (LER)
C-Refueling 3-Automatic Trip/Scram (NUREG - 1022)
D-Regulatory Restriction 4-Continuation Outage E-Operator Training / License Examination 5-Other (Explain)
F-Administrative G-Operational Error (Explain)
H- Other (Explain)
Summary: WBN Unit 1 operated at or near 100% power during September 2002 Although there was no power reduction, WBN did declare a Notice of Unusual Event on September 27, 2002, due to a Loss of Offsite Power caused by a fire at the Watts Bar Hydro Plant (LER 390/2002-005). There were no challenges to the pressurizer power operated relief valves or pressurizer safety valves during the month.
E-2