IR 05000311/1978056

From kanterella
Jump to navigation Jump to search
IE Insp Rept 50-311/78-56 on 781220-22.No Noncompliance Noted.Major Areas Inspected:Insp of New Fuel Receipt,Insp & Storage & Preparations for Initial Fuel Loading
ML18078A918
Person / Time
Site: Salem PSEG icon.png
Issue date: 01/11/1979
From: Caphton D, Kalman G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML18078A917 List:
References
50-311-78-56, NUDOCS 7903070163
Download: ML18078A918 (5)


Text

U.S. NUCLEAR REGULATORY COMMISSION OFFICE OF INSPECTION ANO ENFORCEMENT Report N /78-56 Docket N "'-=--=="-'-'----

C PPR-53 Region I License N SNM-1831 Priority -------

Category ~-"-----

Licensee:

Public Service Electric and Gas Comoany 80 Park Place Newark, New Jersey 07101 Facility Name:

Salem Nuclear Generating Station, Unit 2 Inspection at:

Hancocks Bridge, New Jersey Inspection conducted:

December 20-22, 1978 Inspectors:

Approved by:

f.'~ ~M

~ a!meactorinSpector n, Chief, Nuclear Support No. 1, RO&NS Branch Inspection Summary:

date signed date signed date signed 1/11/79 date? sfgned Inspection on December 20-22, 1978 (Report No. 50-311/78-56)

Areas Inspected:

Routine, unannounced inspection of new fuel receipt, inspection and storage, and preparations for initial fuel loadin The inspection involved 25 inspector-hours on site by one NRC.regional based inspecto Results:

No items of noncompliance were identified during the conduct of this inspection.

Region I Form 1 2 (Rev. April 77)

7903070103

.....

DETAILS Persons Contacted J. Harrick, Engineer B. James, Westinghouse Senior Surveillance Engineer, Nuclear Fuel Division

  • D. Lyons, QA Specialist
  • H. Midura, Plant Manager
  • L. Norrholm, Resident NRC Inspector J. Nichols, Reactor Engineer
  • E. Roscioli, Senior Reactor Staff Supervisor W. Schell, Engineer
  • R. Silverio, Assistant to Manager
  • J. Stillman, Station QA Engineer
  • W. Treston, QA Engineer In addition to the above, other licensee and contractor personnel were contacted during the course of the inspectio * denotes those present at th~ exit intervie Fuel Receipt Scope The fuel receipt procedure and fuel handling equipment certi-fication documents were reviewed and checked for consistency with applicable standard Fuel vendor shipping documentation for the first 118 fuel assemblies was reviewe The receipt and handling of one shipment of 12 fuel assemblies was observe Documents Reviewed (l)

I-2, Revision 0, Refueling Instructions (sections thru 2. 7).

(2)

Westinghouse Fuel Shipping Notices and Bills of Ladin (3)

Whiting Corporation Load Test Report for the 5 and 110 Ton Fuel Handling Building Cranes, dated October 12, 197 (4)

SUP 17.3, Revision 0, Fuel Handling Tools and Fixtures, Fuel Handling Building, with completed checkoff sheet *

3 Findings No items of noncompliance were identified during the course of the inspectio The licensee 1s documentation of mechanical and electrical inspections for the fuel handling building cranes could not be located prior to completion of the in-spection and will be reviewed during a subsequent inspectio This item is unresolved (311/78-56-01). Fuel Insoection Scope Inspection records for the first 118 fuel assemblies were r~viewed, fuel inspection activities were witnessed, and licensee and vendor fuel inspection personnel were interviewe Documents Reviewed (1)

Fuel Receipt and Inspection Records (Westinghouse Form 54991).

(2)

Westinghouse Quality Release Document Findings No items of noncompliance were identifie.

Fuel Storage Scooe The fuel handling building was inspected against the criteria outlined in the Special Nuclear Material License and the FSA The inspector verified by independent measurement that spacing of the new fuel assemblies in the new fuel storage area and the spent fuel pool was consistent with license requirement Fuel status boards were checked for accuracy against actual fuel location The requirements delineated by 10 CFR 70 were discussed and licensee personnel acknowledged under-standing of their responsibilitie * Findings The licensee's application for the Special Nuclear Material License identified the fuel handling building fire protection equipment to include 11 *** sufficient numbers of portable C02 fire exti ngui she rs...

11 and 11... there is a Fi re and Smoke Detection System

  • The inspection of the fuel handling facility revealed that a total of two C02 fire extinguishers were available in the building and the fire detection system was located only in the skimmer pump room, a compartment segregated from most other areas of the fuel handling buildin The enclosed truck bay had neither a fire detection system nor a fire extinguishe The inspector questioned whether the intent of the license requirements pertaining to fire protection was fulfilled by the existing syste The licensee agreed to reevaluate the fuel handling building fire protection require-ments and, if appropriate, to augment the existing syste This area will be reexamined during a subsequent inspection (311/78-56-02). Initial Fuel Loading Procedure Review Scope The final version of the initial fuel loading procedure was not available at the time of the inspectio An informal review was conducted of a draft copy of the procedure with emphasis on procedure content and compatibility with applicable standard Documents Reviewed (1)

SUP 60, Initial Core Loading, Unit No. (2)

Appendix A, Initial Core Loading Sequenc (3) Appendix B, Reactor System Sampling Prior to Core Loadin \\

(4) Appendix c, Primary Source Installatio (5)

Appendix D, Tests to be Performed Prior to Initial Core Loadin (6) Appendix E, Preparation of Inverse Count Rat *

5 Findings The draft Core Loading Procedure was discussed with the licensee 1s reactor engineering staff. The completed version of the procedure will be reviewed during a subsequent inspectio.

Unresolved Items Unresolved items are matters about which more information is required in order to ascertain whether they are acceptable items, items of noncompliance, or deviation An unresolved item was disclosed during the inspection and is discussed in Paragraph.

Exit Interview The inspector met with licensee representatives (see Detail 1 for attendees) at the conclusion of the inspection on December 22, 197 The inspector summarized the scope and findings of the inspection at that time.