IR 05000275/2021012
| ML21207A199 | |
| Person / Time | |
|---|---|
| Site: | Diablo Canyon |
| Issue date: | 07/28/2021 |
| From: | Nick Taylor NRC/RGN-IV/DRS/EB-2 |
| To: | Welsch J Pacific Gas & Electric Co |
| References | |
| IR 2021012 | |
| Download: ML21207A199 (9) | |
Text
July 28, 2021
SUBJECT:
DIABLO CANYON POWER PLANT, UNITS 1 AND 2 - TEMPORARY INSTRUCTION 2515/194 REPORT 05000275/2021012 AND 05000323/2021012
Dear Mr. Welsch:
On June 15, 2021, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Diablo Canyon Power Plant, Units 1 and 2 and discussed the results of this inspection with Ms.
Paula Gerfen and other members of your staff. The results of this inspection are documented in the enclosed report.
No findings or violations of more than minor significance were identified during this inspection.
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely, Nicholas H. Taylor, Chief Engineering Branch 2 Division of Reactor Safety
Docket Nos. 05000275 and 05000323 License Nos. DPR-80 and DPR-82
Enclosure:
As stated
Inspection Report
Docket Numbers:
05000275 and 05000323
License Numbers:
Report Numbers:
05000275/2021012 and 05000323/2021012
Enterprise Identifier: I-2021-012-0010
Licensee:
Pacific Gas and Electric Company
Facility:
Diablo Canyon Power Plant, Units 1 and 2
Location:
Avila Beach, CA
Inspection Dates:
June 07, 2021 to June 11, 2021
Inspectors:
S. Graves, Senior Reactor Inspector
D. Loveless, Senior Reactor Analyst
Approved By:
Nicholas H. Taylor, Chief
Engineering Branch 2
Division of Reactor Safety
Enclosure
SUMMARY
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a Temporary Instruction 2515/194 at Diablo Canyon Power Plant,
Units 1 and 2, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.
List of Findings and Violations
No findings or violations of more than minor significance were identified.
Additional Tracking Items
None.
INSPECTION SCOPES
Inspections were conducted using the appropriate portions of the Temporary Instruction (TI) in effect at the beginning of the inspection unless otherwise noted. Currently approved Inspection Procedures (IPs) with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html.
Samples were declared complete when the TI requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards. Starting on March 20, 2020, in response to the National Emergency declared by the President of the United States on the public health risks of the coronavirus (COVID-19),inspectors were directed to begin telework. In addition, regional baseline inspections were evaluated to determine if all or a portion of the objectives and requirements stated in the IP could be performed remotely. If the inspections could be performed remotely, they were conducted per the applicable IP. In some cases, portions of an IP were completed remotely and on site. The inspections documented below met the objectives and requirements for completion of this TI.
OTHER ACTIVITIES
- TEMPORARY INSTRUCTIONS, INFREQUENT AND ABNORMAL
2515/194 - Inspection of the Licensees Implementation of Industry Initiative Associated With the Open Phase Condition Design Vulnerabilities In Electric Power Systems (NRC Bulletin 2012-01)
The inspectors reviewed the licensees implementation of Revision 3 to the Nuclear Energy Institute Industry Initiative on Open Phase Condition, (ADAMS Accession No. ML19163A176)dated June 6, 2019. This review included the licensee's application of risk screening techniques to determine that the risk associated with an open phase condition (OPC) event is significantly reduced through the implementation of detection circuits and the use of operator manual actions in lieu of automatic trip functions. The inspectors also reviewed the updates to the DCPP licensing basis to reflect the need to protect against open phase conditions.
Inspection of the Licensees Implementation of Industry Initiative Associated With the Open Phase Condition Design Vulnerabilities In Electric Power Systems (NRC Bulletin 2012-01) (1 Sample)
- (1) Inspection of the Licensees Implementation of Industry Initiative Associated With the Open Phase Condition Design Vulnerabilities In Electric Power Systems (NRC Bulletin 2012-01) (1 Sample)
Pacific Gas and Electric Company (PG&E) had selected the open phase detection system designed and manufactured by Power System Sentinel Technologies, LLC, (PSSTech) as the design vendor for Diablo Canyon Power Plant (DCPP). The licensee had installed dual-channel open phase detection systems on the 500-kV main transformer banks for both Unit 1 and 2, as well as on the Standby Startup 230-kV transformers for both units. In total, the licensee installed eight PSSTech open phase detection systems on four transformers.
During normal operation each unit generates and delivers power to the 500-kV transmission system via the main transformer banks. Each transformer bank has three single-phase transformers connected in a grounded-Wye primary and Delta secondary configuration. Each units main generator also provides power to the unit auxiliary loads through two auxiliary transformers (Delta configured primary windings). During periods in which the main generator is offline, such as outages, the unit main transformers can be manually realigned in a backfeed configuration. This configuration can also be used to provide offsite power to the unit if the preferred offsite source is unavailable. The licensee identified that this backfeed configuration was susceptible to open phase conditions and installed open phase detection using the common neutral connection to mitigate this condition.
The licensee also installed open phase detection systems on each units Standby Startup transformers. Each unit has a 230-kV/12-kV transformer (SUT11, SUT21) connected in a grounded-Wye/Delta configuration. These transformers are part of the preferred offsite power supply and during off-normal conditions supply offsite power to the units startup and vital loads.
As part of the licensee's implementation of Revision 3 to the open phase initiative, the licensee used contractor services to model and evaluate the effects of open phase conditions (OPCs) on the DCPP electrical distribution system and ESF/PRA-credited loads. The inspectors reviewed the contractor's report and assumptions, and discussed the distribution system behavior under various open-phase scenarios with licensee staff, including the use of existing 51N neutral overcurrent relaying and pilot wire differential protection relaying as protective elements in the licensee's OPC mitigating strategy. The inspectors noted that the 4.16-kV ESF motor circuit breaker protective relays did not use a seal-in function for overcurrent trips, allowing the motors to be reset and restarted from both the local control and the control room. The circuit breakers have an anti-pump feature which prevents the circuit breakers from immediately reclosing onto a fault.
INSPECTION RESULTS
Observation: Temporary Instruction 2515/194-03.01 - Voluntary Industry Initiative 2515/194 Based on discussions with DCPP staff, review of design and testing documentation, and walkdowns of installed equipment, the inspectors had reasonable assurance that PG&E is appropriately implementing the voluntary industry initiative at DCPP. The inspectors verified the following criteria:
Detection, Alarms and General Criteria
1. [03.01(a)(1)] Open phase conditions are detected and alarmed in the control room.
2. [03.01(a)(2)] In scenarios where automatic detection may not be possible due to very
low or no load conditions, or when transformers are in a standby mode, automatic detection will occur as soon as loads are transferred to the standby source.
Additionally, where automatic detection is not reliable, PG&E has established monitoring requirements on a per shift basis, to look for evidence of an open phase condition.
3. [03.01(a)(4)] No Class 1E circuits were being replaced with non-Class 1E circuits in
this design.
4. [03.01(a)(5)] The Final Safety Analysis Report was updated to discuss the design
features and analyses related to the effects of any open phase condition design vulnerability.
5. [03.01(a)(6)] The open phase condition detection and alarm components are
maintained in accordance with PG&E procedures or maintenance program, and periodic tests, calibrations setpoint verifications or inspections (as applicable) have been established. The open phase equipment is covered under the licensees maintenance rule requirements.
Use of Risk-Informed Evaluation Method
1. [03.01(c)(1)] The plant configuration matched the changes made to the probabilistic
risk assessment model to address an open phase condition, and the logic of the probabilistic risk assessment model changes is sound.
2. [03.01(c)(2)] The procedures which validate that the open phase condition alarm would
identify the proper indication to validate the open phase conditions at all possible locations.
3. [03.01(c)(3)] Observations associated with procedure(s) and operator actions required
to respond to an open phase condition alarm and potential equipment trip match the Human Reliability
Analysis.
4. [03.01(c)(4)] Assumptions listed in the NEI 19-02 Appendix A evaluation and the
sensitivity analyses listed in Section 5 of the evaluation were verified.
5. [03.01(c)(5)] Assumptions, procedures, operator actions, and PG&E analyses specified
above are consistent with the plant-specific design and licensing basis, including:
a. Initiating events considered in the analysis b. Boundary conditions specified in Attachment 1 of the NEI Voluntary Industry Initiative, Revision 3 c. Operating procedures for steps taken to recover equipment from the effects of open phase conditions (or use of alternate equipment) was appropriate.
d. Where recovery was assumed in the probabilistic risk assessment analysis for tripped electric equipment, restoration of the equipment was based on analyses that demonstrate that automatic isolation trips did not result in equipment damage
No findings or exceptions were identified.
EXIT MEETINGS AND DEBRIEFS
The inspectors verified no proprietary information was retained or documented in this report.
- On June 15, 2021, the inspectors presented the Exit Meeting inspection results to Ms.
Paula Gerfen, Site Vice President, and other members of the licensee staff.
DOCUMENTS REVIEWED
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
2515/194
Calculations20-064
Diablo Canyon Power Plant Open Phase Analysis (Zachry)
PRA 19-07
Risk Impacts of the Open Phase Condition at DCPP
PRA 19-07
Risk Impacts of the Open Phase Condition at DCPP
Corrective Action
Documents
SAPN
50304396, 51073848, 51080145, 51091117, 51091286,
51094821, 51102249, 51110258, 51118174, 51118204,
51122198, 51122347
Corrective Action
Documents
Resulting from
Inspection
SAPN
51122198
Drawings
437530, Sheet 1
Electrical Single Line Meter & Relay Diagram 12KV Start-Up
System
437531, Sheet 1
Electrical Single Line Meter and Relay Diagram 12KV
System
437532, Sheet 1
Unit 1 Electrical Single Line Meter & Relay Diagram 4160
Volt System
437595, Sheet 1
Electrical Schematic Diagram Charging Pumps No. 11 & 12
437618, Sheet 1
Electrical Schematic Diagram Stand By Start-Up Transformer
No. 11 And Associated Circuit Breakers
437619, Sheet 1
Electrical Schematic Diagram StandBy Start-Up Transformer
No. 11 And Associated Circuit Breakers
500790, Sheet 1
Electrical Schematic Diagram Main Annunciator Windows
PK2013 - PK2025
500808, sheet 1
Electrical Arrangement of Main Annunciator Window
501140, Sheet 1
Electrical Schematic Diagram Main Annunciator Windows
PK2013 - PK2025
2110, Sheet 1
Electrical Single Line Diagram 500/230/25/12/4.16KV
Systems
57554, Sheet 1
Electrical Cable Tray and Conduit Layout Plan Below Elev.
140' - 0" Area "A"
57568, Sheet 1
Electrical Cable Tray and Conduit Layout Plan Below Elev.
107' - 0" Area "A"
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Miscellaneous
230kV Open Phase Simulator Scenario
NA
DCP 1000025547
REV 0
ATTACHMENT 8
UFSAR Change Request - Section 8. 2. 3. 2. 2. 4, Operation
During Severe Grid Disturbances Analysis
Procedures
AR PK20-19
Unit 1 Annunciator Response 230 KV Open Phase
AR PK20-19
Unit 2 Annunciator Response 230 KV Open Phase
AR PK20-24
Unit 1 Annunciator Response 230 KV SWYD
AR PK20-24
Unit 2 Annunciator Response 230 KV SWYD
EOP ECA-0.3
Unit 1 Restore 4kV Buses
MP E-50.46ST
SUT Open Phase Detection Relay Maintenance and Testing
MP E-50.46ST.1
SUT Open Phase Detection Relay Data Acquisition
MP E-
50.46TGM.2
Main Bank Transformer (MBT) Open Phase Detection Relay
Channel Reference
OP J-2:XII
Unit 2 230kV Open Phase Protection System Operation
OP J-2:XII
Unit 1 230kV Open Phase Protection System Operation
Self-Assessments
Temporary Instruction (TI) 2515/194 Open Phase Condition
Design Vulnerabilities in Electric Power Systems Inspection
Date June 8, 2021 SAPN 51105830