IR 05000206/1986036

From kanterella
Jump to navigation Jump to search
Insp Repts 50-206/86-36,50-361/86-24 & 50-362/86-23 on 860628-0815.No Violations or Deviations Noted.Major Areas Inspected:Operational Safety Verification,Monthly Surveillance & Maint,Esf Sys,Refueling & Independent Insp
ML13323B186
Person / Time
Site: San Onofre  
Issue date: 09/03/1986
From: Dangelo A, Huey F, Johnson P, Stewart J, Tang R, Tatum J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To:
Shared Package
ML13323B185 List:
References
50-206-86-36, 50-361-86-24, 50-362-86-23, NUDOCS 8609190257
Download: ML13323B186 (15)


Text

U.S. NUCLEAR REGULATORY COMMISSION

REGION V

Report N /86-36, 50-361/86-24, 50-362/86-23 Docket N,

50-361, 50-362 License N DPR-1, NPF-10, NPF-15 Licensee:

Southern California Edison. Company P. 0. Box. 800,' 2244 Walnut Grove Avenue Rosemead, California 92770 Facility Name: San Onofre Units 1, 2 and. 3 Inspectionat: 4San Onofre, San Cleimnte,California Inspection -coilducted: Unit.1. July 26 'through'August 15,. 1986 Unit :2/3 June 28 through August 15, 1986 Inspectors: ey, Senior. Resident-.

Date Signed Inspe r, Units 1, 2 'and 3 P. S art, Resident Inspector Date Signed-c-A. D An lo Resident Inspector Date Signed r tu, Resident Inspector Date Signed R. C T g, Resident Inspector Date Signed Approved B,

P. H. J nson, Chief Date Signed Reacto Projects Section 3 Inspection Summary Inspection on July 26 through August 15, 1986 (Report No. 50-206/86-36) and June. 28, through August. 15; 1986 (Report No. 50-361/86-24 and 50-362/86-23.)

Areas Inspected: Routine resident --inspection of Unit 1 Operations. Program including the following areas:

operational safety verification, evaluation of plant trips and events, -monthly surveillance 'activities monthly maintenance activties, engineered-safety feature system walkdown, refueling activities, independent inspection, 'and licensee events report'review. Inspection Procedures 30703.,.61726, 62703, 71707, 71710, :71711., 92701, 93702, 93701,

.,62700; 82301, 'and 90712 were covere Results:

Of the areas examined, no violations or deviations were identifie PDR ADOCK 05000206 G

PDR

DETAILS Psons Contacted Southern California Edion Compan H. Ray, Vice President, Site Manager G. Morgan, Station Mrager

  • M. Wharton,' Deputy Station Manager D Schone, Quality,Assurance Manager D. Stoneciplier, 'Quality'Control Manager R. Krieger,' Operations 'Manager D. Shull, Maintenance Manager J. Reilly, Techilcal Manager P Knapp, Health Physics Manager B. Ziritl;' Compliance>Manager D, Peacor, Emergency, 'Preparedfiess Manager P. Eller,'Security'Manager J.'Reeder, Operations 'Superintendent, Unit 1 H. Merten, Maintenance Manager, Unit T. Mackey, Compliance' Supervisor C. Couser, Compliance. Enginee San Diego,Gas;&' Electric Compan R. Erickson, San Diego Gas ectric
  • Denotes those attending the exit imeeting on August 15, 198 The inspectors also contacted other licensee employees during the course-of the inspection, including operations shift superintendents, control

'room'supervisors", control room operators QA and QC engineers, compliance engineers, maintenarice craftsmen, and health physics engineers and technician Operational Safety Verif icatioi (Units 2/3)..

The' inspectots.perfornied :severalplant-tours and verified the operability of selected emergency sytms, reviewed the tag o t'log

'and verified proper'return'to service of affected'components.. Partiedlar attention was given to housekeeping, ekainitiation'. for potential fire hazards, fluid leaks,';

xcessive'vibratioii, and verification.thdt maintenance requests, had beeA initiated-in need of iaittenanc On July 9 'and. 10, 1986, theinspector observed'the Un it 2/3 pre.-shift briefing. "On July 16, th ns ector obseervedthe control room turnover between'the swing'and grav yard shift;' Brief ings by the outgoing staff'

appeared to be detail d and informativ z Nod-deviatios or violations were identifie.

Evaluation of Plant Trips, and Events Unit 1 (Period.June.28 to July 26,.1986 Covered in Inspection Report 86-35)

On July 26, 1986, Unit 1 reentered Mode1 after completing repairs to the turbine generator voltage regulator and the turbine speed control system.; Unit I was synchronized to the grid at 1843 on July 26, 198 Emergency Feedwater Actuation Signal (EFAS) on July 29, 1986 At 1935, with Unit 1 at 76% power, 'the main steam flow signal to the steam generator level control system momentarily.failed. This failure.resulted in a rapid reduction in steam generator level and the initiation of an EFAS.y The reactor operators took manual control of the feedwater system and reduced turbine load to approximately 63% power during the transient. The operators stabilized the water level in the steam generators and returned the steam generator feed control system (FCS) to automatic at 2005 with reactor power.at 65%. The licensee initiated troubleshooting 'of main steam pressure transmitter'(PT) 459,-suspected as the possible cause for the loss-of the main steam'flow signa Unusual Event 'on'July 30, 1986 At 0104 on July 30,1986, with 'reactor power at 65%, the main steam flow signals to the FCS failed low and the reactor operators took manual control of the FC It was determined that PT-459'(which provides steam density compensation' for the calculation of stea flow) had -failed low and this'caused all three steam/feedwater fl6w mismatch trips in the' reactor protection system 'to become inoperable. 'At 0104, the licensee entered Technical Specification (TS) action statement 3.0.3 due-to the loss-of the reactor.

protection system trip function. At 0201, the shutdown required by TS 3.0.3 was initiated and at 0203, an.Unusual Event was declared by the licensee. At 0350, the repair of PT-459 had been completed and."

the steam/feedwater flow mismatch-protection function had been restored. At 0350, the Unusual'Event was-terminated with the, reactor power at 30%. The licensee initiated an increase.in power at 0515 to continue Power Physics Testing following the refueling' and modification outag Power Reductions due to Condenser-Saltwater Leaks on July 30 and 31, 1986 At "1341 on July 30, 1986, a reactor power reduction was' made to repair a salt water leak in the number 2 water box. Three leaking tubes were repaired

'A loss of vacuum occurred durihg the power reduction which further reduced-power (temporarily) to 20%.

At.1100 on July 31, 1986, a reactor power reduction was initiated to enter Mode 2 for the purpose of repairing condenser saltwater

leakage. Repairs weremade to the number 2 condenser waterbox tube sheet. epox Steam Generator Wide Range Leve Transmittir Repair -

Mode 2 Entry on August..2, 1986 At 2200 on August 1, 1986, a reactor power reduction was initiated to enter Mode 2 so.that a' containment entry could-be madeto repair the "C" steam generator wide range level.trarsinitter. Repair of the transmitter was required by the plant Technical.Specifications (the transmitter is :part of the emergency-feedwater system instrumentation).. 'The'unit'was synchron'ied to the grid-at 2202 on August 2, 198 Reactor Trip on August 5, 1986 At 0245 on August.5, 1986, with reactor power at 87%, the reactor tripped as a 'result of a.turbine-load rejectio This load rejection occurred 'due to a failure in the"turbine. govern6' control

system.causing the turbine -control valves to close. The. licensee conducted an investigation, with the assistance of a Westihghouse turbine engideer,-and was unable to' determine the cause of'the f ailure."

Ground on a Safety Injection Valie Control System Return 'to Mode' 3 on Aftgust '5, 1986 At '23,02 on Augus t 5, 1986, the reacto,was' returned to Mode 3 from Mode',2 as a precatitionary measure;while troubleshooting a 125 V DC ground on the'. controi system for' safety injection system control valve FCV1112.- Theteactor.had revious lyentered Mode 2 and had achieved'c i-,caliyt 2151'(about one 'horearlier).

Power Reduction Due to Safety Injectioh Recirculation Valve CV-875B Faifur 'on August 8, 1986:.

At 1936 on Augfitst 8,- 1986, with reactor power-ai50%, a power reduction was initiated when safety injection-recirculation valve, CV-875B, mechanically failed open. The valve shaft separated'from the operator which allowed feedwater system pressure to force the valve ope 'As a result, feedwater flow was redirected to.the refueling water storage tank.(RWST)

since the feedwater pump also functions as the safety injection-pump. The repair of the valve'

required securing the west feedwater pump because the valve is unisolable frbm the discharge of the-pum Reactor power was reduced'toapproximately 20% in order to' initiate repair of CV-875 Containment Sump Level Increase While Recirculating the Refueling Water Storage Tank -

Mode 2 Entry on August 9, 1986

'

On August 9, 1986, at 0453, the. unit entered Mode 2 so that licensee personnel 'could investigate containment conditions when it was noted that 'the containment sump level increased. while, recirculating the RWST. The licensee determined that the-sump level increase was du to leakage past containment spray header isolation valve CV-114 with the spray heade presurized. This occurred while'recirculating the RWST. w ater with a refueling water.pum The amount of RWST'water which leaked in6 containment was approximately 1500 gallons over a one.houi perio The licensee's" inspecti dh and cleanu did not'

identify a'.n dama ge and the unit was returned to. Mode 1 at. 2302 on August 9,.198 Unit"2 Reactor Trip o ly 1986 (Unit 2)

At 1408 on July 7,11986, while at 49% power the reactor tripped after 12 days of cntinuous operatio The. contributing.causes to the-reactor trip and.the.circumstances-surrounding it' are summarized belo At approximately 1008 on July 7 1986, control element assembly (CEA)

No. 55 dropped to the bottom ofthe core. *Investigations revealed that 2.jof 3.silicon'controlled tectifiers (SCRs) in the control element drive mechanism cdntrolsystem (CEDMCS) for this CEA failed due. to an increase in temperature in'the CEDMCS room. The temperature increased from the normal:, 70 F to 850 F. due to a failure of':the air conditioning units in the rpo The temperature surrounding the SCRs inside the CEDMCS-cabinets was estimated to be 130 0 (These SCRs, recive power from the.CEA drive motor generator set, via the reactor trip'breaker.itchgear which converts AC, power to DC power for the magnetic coils in the.CEDM.) CEA No-.55 could not' be'recovered and -at 1018 -a power. reduction was hiiitiated per Technical Specification 3/4..1.3. - At'1208, power was 'further reduced to 49%"due'to high azimuthal' power',tilt (Technical Specification 3/4.2.3). jAt,1408, after the failed SCRs associated with.CEA No. 55 were replaced,. CEA No. 49'dropped into the core. This 6ccurred before CEA No.55 was returned'to service. As soon as.CEA.No. 49 dropped, -the reactor tripped on low departure from nucleate boiling ratio" (DNBR)

and. high 'local power density due to the additional penalty factor' generated byr the'.core protection 'calculators (CPCs).

It was later determined that the upper and lower Hall Effect -sensors (sensors formontoring currentsuplied.to 'the CEDM gripper coils for, CEA No.' 49.had failed. These sensors were later replace Duri'ng efforts to start up the reactor on July 10, unrelated problems were encountered with the automatic.sequentia withdrawal of the CEA The" problems were attributed toa defective control switch in thecontrol circuit, which'was correcte No' additional problems were identified and the reactor was. taken.critical'at 1250'

on July..

'

From. the time the first CEA dropped (No. 55),the licensee took appropriate actions to recover the rod and' to commence power reduction 'as required by.the. Technical Specifications. For post trip fllowup action, the licensee performed CEA'grooming (coil traces of the CEDM) of all CEAs which identified minor pr6blems'in some CEDM Thse'problems were promptly corrected by the, license During the recent Unit 2 Cycle 3 refueling outage, the licensee replaced CEA timer cards with automatic-CEDM timing modules (ACTMs)

in the CEDMCS of all 91 CEAs.i The Hall Effect sensors mentioned above are part of the ACTM The intehy in using this ACTM design was.to improve CEDM-perfornince and minimize inadvertent rod drop The licensee is currently working with the vendbr, Combustio Engineering, to explore ways of '.liminatihg possible ACTM. software and hardware problems.

Reactor Trip on July 14, 1986 (Unit 2)

On July 14, 1986, at 0858,'the unititripped from 100% power while the licensee was conducting reactor plant'protection system (RPPS)

.l6gic matrix functional testing associated with the containment isolation actuationsignal'(CIAS).' The-licensee had completed functional testing.,of trip-path 1 and was..testing trip'path.2, when a CIAS was received on trip, path 1. The "two out of four logic" for

..containment isolation was satisified whith caused the main steam isolation valves (MSIVs) and the main feedwater isolation valves (MFIVs,).to shut. -This.resulted in a CPC auxiliary reactor trip on high pressurizer pressure. When the' licensee tried to reset-the CIAS, one.relay did not reset initially but.did reset whil troubleshooting. The licensee examined the relay, found that-the contacts were slightly pitted, and concluded that this had caused the failure. The-relay cntacts.were subsequently refurbished without.performance'of any failure testing. As a result, the failure-mechanism 'could not be demonstrated.. The relay ihvolved was a Potter. and Brumfield.KR3DH 'relay with. twin silver-cadmium oxide contacts rated'for 20.amps at 120 volts AC, 60 Hertz (resistive).

Reactor Trip onAugust 12,.186...(Unit 2)

On August 12, 1986, at 1330, 'the reactor tripped, from 100% powe Prior to the'event, main steam isolation 'signal (MSIS)._logic matrix testing in the reactor' plant protection system (RPPS) 'was"being conducted. Licensee personnel had :reset trip.path 3' after completion-of..,testing 'and had just'commenced testing.of trip, path 4 when a trip signal was received 'on-trip path 3..-This satisfied'the MSIS logic and'the-main steam isolation valves. (MSIVs) shu As a result of the loss of the secondary heat sink,' the CPCs trippedthe reactor on high pressurizer pressure.,The licensee conducted'.

subsequent testing of the RPPS, -but the root.ause forthe MSIS could not be identified.. A similarprobm wasenounteredduring the previous'RPPS surveillance testiAg that. was conducted'on-July 14', 1986 (see previous paragraph). -The 'unit was returned to service-,.

on August 14, 1986'.

Transients Due to CEA Drops (Unit 2)

On July.25,-1986, at 1603, power was reduced to' 87% when CEA' 83 dropped into the' core. The CEA, a-shutdowri CEA, was later recovered and unit power was returned to 98% at 230 on the same da Unit power:was.held at 98%-for a scheduled moderator temperature coefficient surveillance.' Prior to the CEA drop, a "CEDMCS Timer

Failure" alarm was received in the control room. As a result, the licensee commenced troubleshooting in the CEDMCS room to determine the cause of this alarm. During the troubleshooting, the RESET button was depressed,while CEA 83 was on the upper gripper. At this time, CEA 83 droppe It was noted that depressing the RESET button should clear-the logic circuitry but should not cause any CEA movement. The ACTM card for CEA 83 was tested and reinstalled since no. problems 'ould, be,foun The licensee considered this a

"non-reproducible failure mechanism."-,

On July.29, 1986, at 2259,'unit power was reduced to 82% when CEA 44 dropped into the core. The CEA was recovered.and unit.power'.was returned to 100%. at 0420 on July 30, 1986. The CEA drop apparently occurred while the licensee was responding to a."CEDMCS*Timer, Failure" alarm'in the control.room. Abnormal voltage was indicated in the CEDMCS room for CEAs 44, 45., and 46-which are all regulating CEAs in subgroup 1 All three-CEAs were on the upper gripper at the.time. The licensee concluded that.the Hall Effect sensors on these.CEAs were faulty, which'was possibly due to' excessive heat n

'the CEDMCS cabinet.- These sensors were replaced and.CEA44. was'.

recovere On July 31, 1986, at 1050,.unit power was 'reduced to 70%/ when CEA 45 dropped into the core.. CEA 45 was withdrawn at 1240 after.the licensee replaced t he -ACTM card with the old CEA timer card. !Unit power was then restored to 100% at 1600 that day. ' The licensee concluded that the CEA drop had.been caused by higher than normal'

resistanceacross the fuse which supplies 'power to the l6gid =for subgroup 1 This caused an excessive voltage drop across the Hall Effect sensors in the.ACTM card and resulted in the CEA drop. The fuse was replaced but a.low voltage condition was still -indicate The licensee.installed a temporary jumper from a spate fuse and plans to further investigate the problem during next outag From. July31 until' theend of the reporting period '(August 15), Unit 2 did not experience any more CEA.dr6p Unit 3'.

Reactor Trip on July 26, 1986 (Unit 3)

On:July 26, 1986, the reactor was manually tripped from 77% power when the main.feedwater pumps automatically tripped due to loss of

'suction pressure. The licensee had reduced reactor.power to 80% so'

that one quadrant of the main condenser could.be isolated for cleaning. While in this configuration, a saltwater'leak developed in' another quadrant of the condenser. The system automatically started to. ddimp this condensate" and. add -clean makeup wate Since the rate of automatic' ondensate make-up was less than the dump rate, suction pressure dropped and' the -feedwater pumps tripped. The saltwater 'leak was repaired and the unit was returned to service on July' 27, 198 * 7 Miscellaneous Load Reductions (Unit 3)

At 2000, on July 28, 1986, reactor :Power was reduced to 18% in order to make repairs to the'hydrailic dump valve associated with main feedwater block' val ve 3HV-4051. Repairs were completed on uly 29, 198 On August 5, 1986, power was reduced to 80% in order to isolate and clean the 'iorth east condenser waterbox. While operating in this configuration, a,saltwater leak developed in the north west condenser.: In this case., reactor operators were cognizant of the situation, due to a.similar occurrence on July 16, 1986 (paragraph 3c), and reactor power was reduced'. to 62% to prevent the main feedwater'.pumps 'from-tripping on low suction pressure until the north east quadrant could be returned to servic Unit power was restored to, 100% on August 7, 198 No 'violations or devations were identifie.

MonthlySurveillaice Activities D'ay Su'rveillance on Remote Instrumentation (Unit 2)

During this inspection period, 'the inspector observed, portions of the remote. shutdown instrumentation 31-day surveillance required by Unit 2 Technical Specification 4.3.3:5' As observed, the surveillancewas conducted in-accordance with procedure S023-3-3.28 TCN6-13*. Day Surveillance on Auxiliary Feedwater System (Unit 2)

The inspector observed portions 'f;the auxiliary feedwater system valve'posit'ion verification which is conducted every 31 day The purpose of this surveillance is'to'demonstrate the operability of the auxiliary feedwater system as required by Technical Specifications 4.7.1.2.1.a.2.* and'4.7.i..2.1. The surveillance, as observed, was performed in ac'cordance with procedure SO 23-3-3:16, TCN 6-12.

c.-

Shiftly'Surveillance (Units 2 and 3)

The inspector observed portions of the shiftlTy surveillance '(channel check).conducted'on certain liquid and gaseous effluent area radiation monitors for Units' 2 and 3. These area monitors are required to be 'tested by the Technical Specifications. The surveillance, as observed, was conducted in accordance with procedure S023-3-3.21 and thd tested monitors were 'demonstrated operabl Weekly Surveillance (Unit 3)'

The inspector observed portions of the Unit 3 eekly surveillance conducted by the licensee. This surveillance included verification

,,of borated water source availability (Technical.Specification

4.1.2.8,:a.2 and 4.5.a.1), -verification of fire water storage tank volume, (Technicaf Specification 4.7.8.1..a),

and source check of radiation monitors'(Technical Specification 4.3.38 Table 4.3-8 and 4.3.3.9 Table 4.3-9).

The potrtions observed were performed in accordance with protedure SO3-3-5.27, TCN 2-1 f No violations or deviations were identifie.

Monthly Maintenance Activities Motor'Driven.Auxiliary Feedwater Pump (2P141) (Unit' 2)

The licensee identified oil leaks on the motor bearings and packing leaks on the inboard pump bearings of motor driven auxiliary feedwater pump (AFWP) 2P141. These problems were corrected by the licensee during this inspection period. The inspector observed the final adjustmentof the pump packings.by maintenance personnel as'

part of the effort to return the pump to service. Both operations and quality control personnel were present during this effor Drain Valve S21305MR422 (Unit 2)

The inspector observed part of the licensee's effort to repair valve S21305MR422 which is a drain valve located in the' discharge path of AFWP 2P141. The licensee had identified a water leak through the valve seat. The inspector observed that maintenance personnel followed the requirements specified in Station Maintenance P'rocedure S0123-1-6.12 and the instructions detailed in the Maintenance Order (MO 86031056000). The inspector also noted that, the QC holdpoint was properly maintaine Steam Driven Auxiliary Feedwater Pump Check Valve (Units 2 and'3.)

As discussed previously in report 50-361/86-19 paragraph 5b, th licensee conducted inspections of check valves 1301-MU-003 and 1301-MU-005 on Unit 2,'and check valve 1301-MU-003 on Unit 3.' These-check valves are in the steam supply piping to the steam driven auxiliary feedwater pump, and each one is supplied by a separate steam heade After the check valves were inspected and -repaired on Unit 2, the licensee discovered that check valve 1301-U-005 was making a loud rattling noise. The licensee disassembled HU-005 to determine the cause for-the noise, and found that a dowel pin, which is used to stake the hinge pin, had been.sheared of The dowell pin was

'replaced, but it did not' correct the rattling noise. The licensee believes that the noise is due-tob,,a resonant condition, and has closed valve :2HV-8201,to isolate steam to HU-005, Valve 21V-8201 will automatically open upon receipt of an emergency feedwater actuation signal (EFAS)., and the 'system remained operable. The licensee plans to correct the resonant condition during. the next'

Unit 2 outag During this report period, the licensee inspected check valve 1301-MU-005, which completes-the check valve inspection for the Unit-3 steam'driven auxiliary feedwater;.pum The hinge pins were found to be degraded, and they were repiaced with hinge pins that have a stellite inlay for the wearing'surfac The inspector observed portions of these maintenance activities, and found that they were conducted in accordance with the approved

. procedure No violations or deviations were identifie.

Engineered-Safety FeatureWalkdown.(Unit':2).Boric Acid Flowpath/Emergency Boration/Charging Sytem During the inspection period, the inspector performed walkdowns of the Unit 2 boric acid flowpath and the emergency boration portion of the charging system.. The. system was found.tojbe in the.alignment required by Technical Specifications (Sections 3.1.2.2,3.1.2.4, 3.1.2.6, 3.1.2.8)

and Station.Procedur'e'(S023-3-3.1) as applicable to the current operating mode, (Mode 1). ',In addition, all required ESF locks for the. manual valves were found.t6 bi in place and properly locked.

Cleanliness' and -housekeeping of the boric-acid flowpaths and surrounding areas was 'also inspected. The condition of the boric acid makeup (BAMU)

tank room was less tha-f satisfactory;. The inspector noticed large chunks of boric acid'crystals around the BAMU tanks and on the tank outlet Valves., In addition, unused paper clips, piping insulation clamps, heat trace, Iinsulationmaterial, and other debris were scattered around 'the tanks and.tank -leie'l transmitter,(LT) 206 The inspector noted that no one was working 'in the room at the time.. These conditions were,

,idehtified to the licensee for resolutio While checking the' position of charging header isolation.valves S2/208MU091 and S2/208MU084 in the 30 foot elevation penetration area ("the Jailhouse"), the inspector noticed water dripping'from an overhead valve. In addition, approximately 1-cubic meter of water had accumulated on the floor 'of the room. due to leakage'. from various other vilve The valve drip, that' was the source of concern, came fromthe cap of valve S2/208MR163 which is the vent valve from-the 2 inch line between (downstream of)'.the charging' pump.and'charging headerisolation valve S2/208MU091. The -inspector noted that deficiency tag had been hung on the leaking valve but no bag had beenplaced below the valve to catch the leaking water. The 'HP foreman, upon finding'this, immediately.placed a plastic.bag. around"the valve to catch the leakage and modified the HP sign outside the :room to require lab coats to be worn. Previously,.only boots and gloves were required. The-inspector also informed the plant operator of the -condition in the roo No violations' or deviations were identifie @ 7.Refueling Activities During this inspection period, refue ing activities we re civites wre corpleted'and ower-physics acceptance testing was accomplished forUnit 1on Au tis 12, 198 No violations -or deviations were identified.

Independent Inspection Allegatioi.Concerriing Valve 3HCV-6459 (RV-86-A-007)

(1) Characterization An allegation was, received which stated that the.,'ar box

'casing for valve 3HCV-6459 was dropped.and cracked while the valve was undergaiig repairs. The allege w-conce thelvaike ger~ o.+/-

lee.was '~ocrned 'tha the crajkedgear casing may have been repaired with.metal putty and then painted over so the crack would not be notice (2) Implied.Significance to Design, Construction or Operation The cracked 'gear casing could possibly render the valve inoperable when called upon to functio (3) Assessiient of Safety Significance Valve 3HCV-6459 is loc'ated 'in the A train of the' saltwater cooling system (SWC), and is used to backflush component cooling water (CCW) heat exchanger E-00 The valve is manually 'operated and'serves its safety function in.the closed position. Since the. yalve is normally clos'ed'and'the gear box does not, have to fuinction-to'satisfy the safety requirement, the gear box is not safety relate The inspector examined the gear, box on' 3HCV-6459a evi'denc of

'dicusedths and found no evidence of-damage. The'irspector discussed this allegation with the licensee, and the licensee conducted 'a search through their'.nonconformance reports (NCRs) and found that a similar valve, 3HCV-6458, had a cracked gear casing. 3HCV-6458 is used t6 backflushCCW heat exchanger E-002. The inspector examined the valve and reviewed the NCR (3F-0078). The gear box casing was cracked, but the safety function 'of the valve was not affected. and the deficient conditiohad been properly identified anddispositioned by the license ) Staff Position The coacked gearbox casing on valve'3HCV-6458 does not impair the safety function of the valve. This allegation is close (5) ActionReqoired None.'

.~Design Chanrge-RevieQ'

During %the Unit 2 refuel ng oufage the licensee replaced. the exist ig reactor; coolant pump (RCP)

seals with a newly designed 'seal p

ed b

Bi aiillanett Company The n wly designed seals appeaied' to be finctioiing as aiticipated with the exception that the' ontole bleejd-off temperature f RCP-3fwas approximately 1800F, which is ab6ut300F higher than fo the bther pump The design called for10 oF to 140F Seeral, reactor trips occurred after the design chainge was completed and the seails functioned'as requ d

The inspector bmpleted areview 'of desigh chane package (DCP) 6025 )SM whic imif mentd the RCP seal replacement, an veri that t change was conducted in accordance with the N licensee sprocedures'.'

violatibns 6r dfviations were identified,Review of Licensee Eyent Reports Thef101owing Licensee Event Reprts LERs were closed on the basi of in-office review.:

(Closed Licen ee Event Report 8-1; Rev., Further Jnfo rmation onFeedwater Hammer Eveit

'

This item indicated that further inforniation on the feedwater'hammer event woul'd be.provided to the NRC: 'It is closed based on the receiit" of tflis.ri ormation' as part.of the SONGS Unit 1 Restart Progra nit 2 (Closed Licensee Event Report 8-77, C6ntrol Room Isolation System Actuation ;Due to 'Error The 1 censee reported, -that a Control Roori Isolai6n System (CRIS)

actuation occirred as a -result of the "failure of an instrumentation and cohtrdl technician -to fully depress the CRIS reset 'switch as required by the surveillance procedur he was usin The licensee, indicated thatfor corrective action adsign age woul db cmpleted to install-A keyIlock switch: fo the bypass finction and spring loaded.switch for the reset faictioii to minimize the'

6ssibility' of futther CRIS actuations, - Based on this Proposed design

'change, this item is close (Closed) Licensee Event Report 85-01,.Missed Fire Watch This report indicated that a routine roving fire.watch missed a tour of 'an electrical tunnel which-was-.required by Technical Specifications The licensee reported that the cause of the event was.inadequate prior planning of a security computer 6utage, and *a failure-of personnel-to implement a revised accessnrotigfor'the firewatch. The licensee indicated that the corrective actions taken, to prevent recurrence of this event, included authorization of firewatches tb enter vital areas during contingencies when security officers are notavailable..Based on the licensee.'s corrective actions, this item i's close (Closed) Licensee Event Report,86-03, Control Room Isolation System Actuation The licensee reported that one trairi'ofthe CRIS actuated 'as' result of the failure of 'a capacitor in a-radiation monitor power supply. The power supply was repaired'as corrective action. Based on this corrective-action, this item is close (Closed) Licensee Event Report 86-08, 'Containment Audible Monitor Inoperable During Mode 6 This report indicated that the'source rangeneutron flux monitor'

audible'speaker,-located in containment, failed prior to entry into Mode 6. However, the reactor was takeh 'into. Mode' 6' contrary to Technical Specification Limiting Condition for Operation 3.0.4. The cause of this event was reported to be'the lack of explicit procedural requirements' to sufficiently ensure that all 'Mode 6 surveillances were performed.prior to entering the Mode. The licenseeindicated that corrective actions were performed to revise the Mode 6 entry controlling procedure to explicitly require review of each surveillance requirement (for completio)' prior to the-Mode entry, Basedon these'corrective actions,, this item is. close (Closed) Licensee Event Report' 86-09', Turbine Driven Auxiliary Feedwater Pump Steam Supply Check Valve Damage This report, which was supplied for information only, gave an update on status of the, turbine driven i

feedwater.pump steam supply check valves which had received substantial damage due to steam erosion. The licensee reported that, for corrective actioh; a

.design.change wa-mleetdfor the affected check valves. Thi.

'change incorporated the use of stellite sleeves in the hinge pin

.'t:

seating s'urface for the valves.' These sleeves were added to ensure that excessive wear does not develop between-.refuein outages at which 'time they can be inspected for wear. -,Based on this design, change, this' item is closed'.

13' (Closed) Licensee Event Report 86-11, Spurious Containment Purge Isolation System Actuation This report indicated that a Containment Purge H atio System (CPIS)-actuation ocurred as a result of a signal from an area radiation monito The-cause of the area radiation.monitor alarm was the result of spurious electrical noise. The'-licensee implemented-corrective 'actions to..reduce'the p6ssibility-of spurious CPIS actuations as indicated in LER 85-5 These 'orrective.actions consisated of replacing the" detector and ensuring its.proper grounding. Since this is the first CPIS -since-implementation of these 'corrective actions, this item -fs" closed'.. (Closed) Licensee Event Report 86-15, Reactor Trip'Due to Shotted Capacitor in a IE Inverter'

The licensee rep6rted that a.reactor trip occurred as a result of the failure of.a capacitor in a vital inverter while another vital inverter was out of service for testing.. This resulted in'two control element -assemblycalculators (CEAC's) being inoperable at the same tim The licehsee indicated that the possibility of the failure of a capacitor resulting':in inoperability of.6ne CEAC with

.the 6ther CEAC out of service is very remote -Due to the fact that this'is an isolated occurrence, this item is closed h. '(Closed) Licensee Event Report 86 2, Spurious Fuel.Handling

.

  • '

Isolation SystemActuation

'The'licensee reported that a spurious fuel handling isolation system (FHIS) actuation occurred when an airborne monitor alarmed as a result of random electrical noise. The-licensee-also indicated that corrective.action (replacement of the detector and verification of proper grounding) had been taken to minimize the possibility o further spurious actuation Based bn this corrective action, this item is close Unit 3 (Closed) Licensee'Event Report 86-05-, Turbine 'Trip, Reactor Trip Due to Voltage Spike -on Non-lE Instrument Bus

'

This -item was.submitted to report that a turbine -trip - reactor trip occurred as 'a result of a voltage transient on one phase of' the-,

non-1E uninterruptible power supply inverter. -This inverter supplies power to two auxiliary relays 'associated'with the contro element, drive mechanism undervoltage relays in the turbine trip circuitry. For corrective action, the licensee indicated that a design change-, sin ilar to that implemented inUnit 2, as performed in Unit 3.- The design change rearrang d"the auxilary relays.so that a single. phase voltage transient-will not cAuse a turbine tri Based on this design chahge, this item. is closed.'.'

1. 4 (Closed) Licensee'Event Report '86709, Turbine Driven Auxil ary Feedwater Pump Steam. Supply CheckValve Damage This report, which-was supplied for information only, gave an update on status of. the-turbine driven, auxiliary feedwater pump steami supply check valves which had received substantial damage due to steam. erosion. -This item is 'similar to LER 86-09 for Unit 2. The same design chahge.used in Unit 2 was implemented for the affected check: valves in. Unit This change incorporated the use of stellite sleeves in the hinge pin'seating surface for the valve These sleeves were added to ensure that excessive wear does not develop between refueling outages at which time.they can be inspected for wear. -Based on this design. change, this item'is close No violations or deviations were-identifie :

Exit Meeting

On August '15, 1986, an exit meeting was conducted with the licensee representatives identified in Paragraph 1. The inspectors summarized the inspection scope and findings 'as-described in this report.