U. S. NUCLEAR REGULATORY COMMISSION

REGION V

Report No /86-20, 50-361/86-17, 50-362/86-1 Docket No, 507361, 50-362 License No DPR-13, NPF-10, NPF-15 Licensee:

Southern California Edison Company P. 0. Box 800, 2244 Walnut Grove Avenue Rosemead, California 91770 Facility Name:

San Onofre Units 1, 2 and 3 Inspection at:

San Onofre, San Clemente, California Inspection Conducted: May 5-9, 1986 Inspectors.:

P. P. Narbut, Proj ct.Inspection Dat Sgned P. Phelan, Reactor Inspector D

Signed A. To h, React r Inspector Date Signed Approved by:

P. H. Jo on, Chief Dt'Sge Date Signed Reactor ojects Section 3 Inspection Summary Inspection on May 5-9, 1986 (Report Nos. 50-206/86-20, 50-361/86-17, 50-362/86-17)

Areas Inspected: Unannounced regional inspection of.licensee activities in the areas of post trip review, onsite review committee, offsite review committee,.battery surveillance, diesel generator (TDI) Part 21 reports, and site procedure generation. Inspection procedures 30703, 40700, 40701, 92700, 36100, 51051, 51053, 51055, 42700, and'93702 were utilize Results:

Of the areas inspected, no-violations or deviations were identifie PD PDR, ADOCK4 050020 0 ~

~

~

D

_~~~-------

-

DETAILS Persons Contacted Southern California Edison Company

  • H. E. Morgan, Station Manager
  • M. Wharton, Deputy Station Manager
  • R. W. Krieger, Operations Manager
  • D. Shull, Maintenance Manager J. Reilly, Techhical Manager
  • W. G. Zint1, Compliance Manager
  • J. Reeder, Operations Superintendent, Unit 1
  • R. N. Santosuosso, Instrument and Control Supervisor
  • C. A. Couser, Compliance Engineer
  • B. Katz, Manager, Operations and Maintenance Support
  • K. A. Slagle,'Manager, Material and Administrative Services
  • W. M. Lazear, QA Supervisor T. Herring, STA Supervisor J. F. Grosshart, QA Engineer S. W. McMahan, Manager, Maintenance Engineering and'Services B. L. McGee, Supervisor, Site Procedures Group M. E. Freedman, Compliance Engineer G. T. Gibson, Compliance Supervisor F. Briggs, Supervisor, Station Technical J. Rudolph, NSSS Superintendent H. 'Merten, Assistant Maintenance Manager,.Unit 1 J. Mangum, Maintenance Engineer, UnitL B. Mair, Maintenance Field Engineer D. Sheriton, Maintenance Manager, Unit 1 D. Mentoya, Electrician M. Manely, Electrician Apprentice A. Schramm, Supervisor of Coordination W. McGhee, Coordination Supervisor D. Ziebell, Operations Procedures Group Supervisor T. Mackey, Compliance Supervisor L. Falcan, Supervisory Procedure Writer A. Melville, CDM Center Supervisor N. Bloom, Supervisor, Maintenance Procedures & Administrative Engineering
  • Denotes those individuals attending exit meeting of May 9, 198.

Onsite Review Committee, Units 1 and 2/3 The inspector examined the activities of the licensee's Onsite Review Committee to verify that the licensee's program meets regulatory requirements and to determine if the safety related responsibilities are being adequately me The committee's responsibilities are defined in the facility license technical specifications section 6.5 which include a prescribedmeeting frequency and quorum. The committee's responsibilities include investigation of all violations of technical specifications, review of all reportable events, review of operations, and review of judgements concerning prolonged operation with equipment in bypass or trip. The Technical Specifications also require the'committee's decisions to be in writing and written minutes of each meeting to be maintaine Procedures The inspector reviewed the licensee's procedure for the onsite committee;'Site General Order SO123 GCO-1, Revision 0, dated April

.24,'1985., entitled "Organization and Responsibilities of.the Onsite Review Committee."

The pr6cedure wa's fouid to acceptably implement the technical

.:specification'requirements. Theprocedure had strengths in that it provided a workidng definition for the term-"potential nuclear safety hazard.',and provided a standard agenda form which ensures all topics required by technical specifications are covered in the monthly or special imeeting The procedure contained one apparent error in that paragraph IV. onlyjrequired the Chairman and four members to establish a quorum; whereas the technical specification for Unit 1 required the Chairman and five.members. The Licensee' explained, and the inspector verified, that the quorum requirement in the technical specification had been changed in November 1985 and that the technical specification quorum requirements had been met at meetings held since that.time. Additionally, a revised superseding procedure was prepared and was in the approval process. The new procedur reflects the current requirements for a quorum. Based on the above, no violation of NRC requirements occurred and no further followup is deemed appropriat Records The inspector examined a.sample of the Onsite Review Committee (OSRC) meeting minutes. The minutes reviewed covered the period from September 1985 to March.1986 for Units 1, 2 and 3. The inspector noted that quorum requirements were met, that the required reviews were performed, that special meetings for appropriate topics were held (above and beyond the 'minimum requirements of the Technical Specifications) and that appropriate exp.lanatory information was included as attachments to.the minute Observation The inspector attended a special meeting of the OSRC held on May 8, 1986 to review the procedure and the engineering/safety evaluation for a special evolution pertaining to dewatering the lower refueling cavity of Unit 1. The evolution involved transferring highly contaminated water with suspended solids from the containment refueling cavity to a 'spent fuel pool cavity through a temporary transfer system designed for the evolutio The inspector observed that the information presented to the OSRC was detailed, that the questioning by the committee members was pertinent and detailed, and that the conduct of the meeting was formal and in accordance with procedures. There appeared to be a healthy exchange of views and no reluctance to explore alternate idea Other Areas a

Check Valve Noise The November 21, 1985 water hammer event at Unit 1 and the resultant investigative actions pointed out an apparently improper evaluation of an abnormal condition by the license In June 1985, prior to the November 21, 1985 event, the licensee became aware of and evaluated a rapping noise in the vicinity of the subsequently failed check valves. The licensee's followup investigation and actions in response to this noise were determined to be inappropriate and were the subject of a proposed violation as discussed in inspection report 50-206/86-0 o OSRC Review of NRC Violations Review'of the OSRC minutes showed that the San Onofre OSRC formally addressed NRC violations cited against Technical Specifications as. required. The review also showed that the OSRC does not formally review NRC violations cited against 10 I

CFR Appendix B criteria. Although this does not violate the specific wording of-the administrative requirements of the Technical Specifications (section 6), the omission of these reviews appeared to be unnecessarily narro The licensee pointed out that the knowledge of such non-technical specification violations was common and that the review of the adequacy of corrective actions was performed by the higher levels of management so that, in short, such violations did not suffer from lack of attention. At the exit interview licensee management stated that the inspectors comment would be considered. This item will be followed up in the normal course of periodic inspections in this are o OSRC Changes as a Result of the Event The licensee described actions taken to strengthen the safety review process in their April 8, 1986 letter to the NRC. In regards to the OSRC, the licensee has entered into contract with an independent, operations-experienced consultant to provide oversight of the OSRCand to report to corporate management any issues of concern either technical or procedura II

4 Conclusion The activities of the OSRC were found to meet regulatory requirements and appeared to be acceptably conducte. "Offsite Review Committee, Units 1 and 2/3 The inspector examined the activities of the offsite review committee for San Onofre, the Nuclear Safety Group (NSG), to verify that the licensee's program meets.regulatory requirements.,

The NSG responsibilities are defined in Section 6.5 of the facility operating licensee Technical Specifications which contains other specific requirements regarding the quorum, required records, meeting frequency and audit The inspector examined the licensee's procedure for the NSG, E&C 40-9-21

"Nuclear Safety Group Review Evaluation and Audit Responsibilities for SONGS."

The inspector discussed the conduct of NSG responsibilities and reviewedrecords of meetings and issue reviews with the NSG Supervisor at the licensee's corporate office The inspector noted that the NSG audits which are required to be

"performed under the cognizance of the NSG" (per Technical Specifications),were perfdrmed by the onsite QA group. The scheduling and.review of those audits; findings, and corrective actions are reviewed by the NSG (and therefore are under the cognizance of the NSG).

The inspector noted that, although the requirements of the Technical Specification were formally fulfilled, the desirable direct involvement of the NSG as independent oversight.of actual site conditions and practices appeared'to be los The licensee demonstrated that.NSG-members were, in fact, involved in a direct oversight through a surveillance program. The NSG surveillance program, which isbeyond the requirements of the Technical Specifications, was reviewed by the inspector. The NSG had conducted eleven surveillances in the period from March 1.985 to March 1986. The surveillances were generally multiple week efforts, which went into great depth and included direct observation of the conduct of work and operations as well as technical evaluations. At the exit interview,' the inspector noted that, although the NSG surveillance program was an extensive effort, it was not required or described by a utility procedure. Licensee management noted the inspector's'comment for consideration. The activities of the NSG will be examined in the future scheduled inspection In regards to the NSG involvement in the review of the OSRC findings on check valve noise, the licensee letter of April 8, 1986 stated that the NSG reviewers would be instructed on the need' for an insightful questioning approach. Anyfurther response to this question will be addressed by the licensee response to the proposed violation described in inspection report 50-206/86-07 regarding the inadequate investigation of check valve nois Conclusion:

The activities of.the NSG meet regulatory requirements and appear to be acceptably conducte..

Abnormal Condition and Post-Trip Reviews The inspector examined the licensee's system for dealing with abnormal conditions and post-trip reviews. These areas have come under increasing attention not only as a result of the November 21, 1985 water hammer event at San Onofre but also as a result of the February 1983 event at Salem. Pursuant to the.1983 event the NRC issued Generic Letter 83-28 dated July 8, 1983 which required licensees to.respond to certain. generic concerns, one of which was the area of post-trip revie The generic letter responses were initially reviewed and review guidelines were issued by the NR The guidelines basically required that the licensee develop systematic safety assessment.procedures that ensure certain specific criteria are met prior to restart from a tri Those restart criteria were, in summary, that the root cause and sequence of events are understood, that near term corrective actions.have been taken, that major safety systems are determined to have responded properly, and that a potential safety concern had not been-identifie The guidelines further stated that, if any of the.criteria were not met,

-then an independent assessment of the event should be performed by an independent body such as the OSRC. The guidelines specify the responsibility and authorities of personnel who perform the review and require, in short, management involvement {at the Shift Supervisor level)

and STA involvement. The guidelines also.require the licensee.to is'sue procedures.to: implement the post-trip review requirements and to submit information regarding its post-trip review program and procedure On May 8 and,9, 1985 the NRCissued letters to San Onofre stating that the licensee'.s programs for post-trip review had been reviewed and found acceptable for Units,2/3,and Unit 1, respectivel The licensee's currenf'procedures for post-trip review were reviewed by the inspector,. The.procedure is S0123-0-25 revision 0, "Trip/Transient Review" issied November 22,.198 The procedure was found to'ieet the review guidelines discussed earlier

in this section.. It was noted, in -discussion with licensee management, that SCE has also incorporated the suggestions. of industry groups such as INPO into.their post-trip review process. The.inspector noted that the post-trip review procedure ;was well laid-out and had a-specific comprehensive multipage form 'for use in the post-trip review proces The procedure covers all'points-raised in the review guidelines and includes other very useful vitems
such as a requirement to interview every person involved and to reco'rd their answers.. It also requires that an entry be made suggesting straining additions from any lessons learned from the.even The post-trip review.process and the recording of post-trip review information is.ordinarily done on-shift by shift personnel and data is recorded by:hand on the forms provided in the procedure. The inspector reviewed several post-trip review forms for previous reactor trips. The

infoimation provided was found to be terse but indicated a review of the proper questions had been done and judgements mad The licensee has supplemented thepost trip review process with a second analysis of events called the "Station Incident Report". This is a study of the same events done in a more studied and complete fashion by offshift personnel and supervision and serves as a second studied analysis of the event, the corrective actions, and a hazards evalutio The process is described by the licensee's procedure, SO123-V-2.27

"Station Incident Report (SIR)" Revision The SIR serves as the permanent record of.the description and cause of the event and corrective actions to prevent recurrence. The SIR is the document forwarded to the. OSRC for their monthly formal review of unit operations and event The inspector examined a number of SIR's and found the documents to be clearly written and comprehensive. 'The SIRs include sections which describe the event, the equipment and personnel behavior, reportability actions, cause analysis, similar incidents and proposed corrective action (including procedure, training, and equipment aspects).

The' SIR also includes.a formal safety evaluation. Actions identified in the SIR are numbered and tracked by the licensee's computerized action item tracking syste It-was further noted by the inspector that the major organizational units at the site had :their own.documented policies for conducting and'

recording of results of investigations. For example, the maintenance group has a procedure (S0123-G-4) which is used to examine maintenance errors and record.causes and corrective actions. These-corollary investigations.were found'to be included with'the SIRs when applicabl Based on the above the inspector concluded that the licensee's established program for post-trip and abnormal condition reviews met regulatory requirements and was generally strong in terms of procedural adequacy and detail. However, an inspection conducted by the re'sident inspectors pursuant to the April 13, 1985 premature criticality event at Unit 3 identified the failure to properly document the post-trip review information required by procedures (Report No. 50-362/86-1; pending).

The licensee's actions to -resolve the identified procedural compliance problem will be followed pursuant to the Unit 3 report. Additionally, as was discussed in paragraph 2 of this-report, the licensee's action in following up the abnormal condition of check valve noise in June of 1985 was found to be unacceptable as documented in the proposed violation in inspection report 50-206/86-0 Subsequent to these matters, senior regional management visited the reactor site during the week of May 19,.198 Interviews were conducted with managementand. workingolevel individuals to assess attitudes towards the goals of safety andexcellenc The interviewed SCE staff appeared to have a positive attitude"toward ensuring that operations are conducted properly and safel Conclusion The licensee's program for abnormal condition and post.trip reviews meets regulatory requirements and appears to be acceptably defined in procedures...A weakness in implementation was identified in report,.

50-362/86-11 and will be followed pursuant to that repor.

Procedures Development Program Inspection Objective An NRC Incident Investigation Team (IIT) identified several' items relating to. the November 2b 1985 water hammer incident,.which appered to involvedweaknesses in various plant procedures. The licensee issued~antinvestigationI report regarding the event, and addressed planned corrective actions for the specific weaknesse In Section 6-5.2 of that report, the licensee described a self-assessment of the program for development and improvement of procedures', along with plans for improvement of the procedures development program 'itself. The licensee also expressed an opinion that the program has, inigeneral, effectively provided technically correct documents of acceptable quality. The licensee'stated that the plant operating instructiohs were based upon ANSI-N18.7 and INPO-document The objective of this inspection was to clarify the licensee reference to INPO criteria and to determine the extent to which recent humah facto'rs recommendations had been 'adopted in the SONGS procedures generation proces Inspection Scope During this inspection, the inspector' reviewed the elements and basis for generation and changes to procedures, to assess implementation of'criteria of-ANSI-N18.7 and the degree of adoption of INPO recommendations.issued between.1983-1985:

The inspector interviewed personnel and examined samples of procedures in the categories of operating instructions, alar response procedures, abnormal operating procedures, and maintenance procedures. The inspector examined the following procedures,.'

instructions and writers guides which are used by the licensee to generate operations, maintenance and surveillance instructions:

S01-14-24 Operations Procedure Group SO1-14-42 Responsible Use of Procedures S0123-0-20 Use of Procedures 80123-0-34 Distribution and Acknowledgement of Information S0123-0-35 Review of Operational Occurrences S0123-0-40 Operations Procedure Group Organization and Methods

S0123-VI-Documents, Authors Guide to the Preparation of Site Orders, Procedures and Instructions S0123-VI-Documents, Review and Approval Process for Site Orders, Procedures and Instructions S0123-VI-1.0.1 Documents - Temporary Change.Notices (TCNs)

Preparation, Review, Approval, Incorporation and Distribution NGS-D-017 Independent Verification (Site Order)

SO1-VI-1. Unit 1 Emergency Operating Instructions Preparation, Revision, Validation S0123-PF-1 Site Orders, Procedures, Instructions and Forms Linked. Program S01-14-31 Temporary Facility Modifications SO123-VI-1-02 Annual/Biennial Review of Site Orders, Proceduresand Instructions S0123-V-1.03 Methods of Handling Invalid Steps/Sections S0123-VI-19.0 Implementation of Overtime Restrictions SO123-VI-Guidelines for Completing the Unreviewed Safety Question and Environment Evaluatio MPG-00 Maintenahee Procedures Writer's Guide QAP-N5.02 Coordination, Review and Approval by Quality Assurance Organization of Southern California Edison (SCE) Station Procedures 50124-0-25 Post Trip/Transient Review Findings and Observations (1) Organization: A Site Procedures Group (SPG) issued procedure guidance applicable to Units #1/2/3 and coordinated interdisciplinary review of procedure The site quality assurance organization performs final review of new and revised procedures, including disposition of interdisciplinary review comments, and provides final approval of the procedure. The Unit #1. operations organization includes an Operations Procedures Group (OPG), staffed with personnel holding reactor operator licenses, who originate and review plant operations procedures, i.e., Operating Instructions (01), Alarm Response Procedures (ARP), Abnormal Operating Instructions (AOI), and Emergency Operating Instructions (EOI). The Unit #1 Maintenance Procedure Group (MPG) also includes a procedures preparation group, that originates maintenance and surveillance procedures. The Unit #2/3 organization's procedures work is also directed by the SPG,.but differs from the Unit #1 activitie (2) Writer Guides:

The SPG issued Site Procedure S0123-VI-1.0 and 1.0.4 which provide guidelines for-format and content of the various types of plant operating/maintenance procedures. The document includes human factors/style considerations of NRC and INPO documents dating up to 1982; however, more recent INPO recommendations issued between 1983-1985 have not been incorporated, nor evaluated by SPG for incorporation, and were not available at the SPG offices. The SPG supervisor stated that there was no policy for SPG to obtain such documents, evaluate and incorporate results into revisions of the writers guide, nor.require upgrading of existing procedures to revised writer's guide.,instruction The SPG document attempts to provide both.general and specific guidelines and yet recognize the autonomy of the Unit #1 and Unit #2/3 plants in different detailed-approaches to procedures generation. The SPG thus does not appear to function as a strong.driving force for uniformity at the -site and continuing upgrade of procedure The PG (Unit #1) issued plant procedureSO1-14-24 which provides guidelines for format and content of plant operating department ptdcedures. The document both references the SPG writer's guide and provides additional requirements and

simplifying detail for procedure writers; it is a 73-page document -i.ssued in April 198 The document addresses

'Preparation, research, work flow-path definition, format and

.tyle consistent with many human factors recommendations of NRC and INPO guidelines. Some such recommendations have not been addressed, such as Annuiciator Procedures (ref INPO-85-003) are not required to'define methods to verify the alarm nor verify that expected automatic actions have in fact occurred. It appeared that INPO recommendations issued between 1983-1985 ha not been incorporated nor evaluated by OPG for incorporation, nor werethey available at the OPG offices. However, extensive SCE work has been done to upgrade Emergency Operating Instructions in accordance with Westinghouse Owners Group, NRC and INPO guidance, and the responsible coordinator for that work was in close proximity to OPG and maintained a significant reference library, including many but not all relevant guidance document The OPG supervisor stated that there was no policy for OPG to obtain such documents, evaluate and incorporate results into revision of the OPG writer's guide, nor require upgrading of existing procedures to upgraded writer's guide instruction He stated that an upgrade of an operating procedure may occur when it came up for annual/biennial review; he would then decide if that procedure should be left as is or revised; only in the event of revision would he expect the document to be recast into the format/style of the latest revision of the writer's guide. The.OPG thus does not appear to function as a

strong driving force for continuing upgrade of procedures to increasing standards of adequacy.*

The maintenance procedures group (MPG) (Unit #1) issued a procedures writer's guide MPG-001 which provides guidelines for fo'rmat and content ofsmaintenance 'andsurveillance procedures The document includes human factors/style considerationsof NRC and INPO documents dating through 1985, including those of to ientify The INPO documents were not available at the MPG office,-however, the MPG supervisor stated that the current writer's guide reflected results of an evaluation of an INPO report which had been routed thrugh'rthe MPG for information; (he could not retrieve any specific documentation of the review to identify the specific documents considered).

The MPG supervisor stated that there was no policy for MPG to obtain suchPdocuments, evaluate and incorporate results into revision of the.writer's guide, nor required upgrading of existing procedures to revised writers guide instruction The MPG thus appeared to function autonomouisly to upgrade existing procedures to increasing standards of performance, dependent uepon management adhoceinitiativ This MPG appeared successful in upgrading the procedures writer's guide to be current with newer industry recommendation The operations department had, in 1985, conducted a major'

effort to upgrade'.Emergency Operating Instructions.(EOI's), and had provided a writer s guide to NRC'via an April 12, 1985 letter.- The described procedure generation, verification.-an validationprocssesappead to be reflected in EOI's reviewed 0by,.the nspecto (3) Procedure Preparation:- The OPG and M PG files contain 'a

"Procedure Hi story File and a Next Revision File" for each procedure, in addition to the groups each haing the FSAR, the TechnicalSpecificaions-and other-references availabl The maintenance department also implements a reus-o-assac

's yqtedm were any'-employee may~ask-for consideration of action, in4cluding mino, /maj'or ~changes to procedures.- The forms are logged/tracked/re50olv d,-, and keyed to the next revision file where, applicabld.._The 'SPG and OPG writer's guides caution aga'it"removing any 'information: from history file These provisionsassure retention/availability of inforainuo whic-h prior procedure revisions were based, and are required to

- be referred.to

,by.proc edure writers during the procedure

'revision,.proces~s

'It also assures that knowledge of'prior, commitments to NRC (and others) is retained so as to avo id inadvertent deletion of procedure provisions previou'sly recognized as important:

The SPG, OPG, and MP.G writer's guides each include requirements to identify and define requirements to. conductand document indepen'dent verification of activitie s conducted outside the control-.room which are important to safety, and a small sampling of procedures indicated -that this 'element has been

included at appropriate poiit The guides also stress the importance of using the "active" versus "passive" sense in

.'instructional step; defining'interfaces with other procedures, and defining responsibilities and principal lead for activities involving more than one individual or organization. (These elements were in question in NRC Inspection Report 86-04, Paragraph.7-6, relating to air lock procedures. *The licensee subsequently determined the problem to be absence of a governing-procedure as opposed to inadequacy of an existing procedure.)

The MPG and OPG writer's guides include requirements for peer review prior to issuance to SPG for interdisciplinary formal review. Instructions for review/approval of procedures include checklists for reviewers of procedures, as does the Quality Assurance Department review/approval instruction. The check lists address format, style, logic, accuracy and walkdown The SPG/OPG guides.include requirements to conduct and document a walkdown of the various types of procedures prior to approval. The MPG writer's guide provides for walkdown/field-checks.prior to approvalor during first-us The OPG guide and related operating/administrative procedures require that plant transients analyses include interview of personnel to determine adequacy of procedures used and recommended improvements, with documentation of recommendations on a tracking system which assures followup via the Next Revision File during annual/bienniel reviews or more promptl The procedures controlling temporary modifications of facilities include specific checklist items to determine plant procedure changes required and associated training and accomplishment of these items prior to activation of the modification. Provisions for prompt procedure changes via Temporary Procedure Change Notices (TCNs) are include The process for interim changes to procedures (TCNs) appears consistent with ANSI-18.7 and Technical Specification requirements, including level of approval, time limits for expiration of non-permanent changes and final approvals of permanent change The TCN process allows substitution of corrected pages and full reissuance of procedures constrained by the requirement that the "intent" of the procedure is not altered; the administrative procedures appear to provide reasonable guidance/amplification of the term "intent".

The TCN process provides for prompt issuance of changes under circumstances of immediate operator nee Management has clearly expressed expectations regarding use of plant procedures. The, instruction S01-14-42, "Responsible Use of Procedures"," incorporates-guidance as to the specific responsibilities of personnel who review the data in procedures/checklists that have been applied by plant staff, including responsibility to obtain resolution of "comments" and

check for return of the system to its proper configuratio For procedures implementation in progress at shift change, the instruction requires users to reverify prerequisites and precautions. Instructions are included to controlstransfer of data from field copies-to the record copy of procedures during implementation. The instruction includes provisions for procedure users to request (Instruction Resolution-Request-IRR)

action on errors, additions or inadequacies in procedure. The IRR is forwarded to the procedure writer group and filed in the History.File and Next Revision.File for the procedure. A separate procedure (SO123-VI-1.0.3) provided instructions for procedure users who fidd invalid (cannot, should not, or need not be performed as written) steps or sections in a procedure due to various circumstaces. Alternative annotations and approvadl levels.are designated, and instructions for review proided for the.designated approval authority.. Provisions are included for obtaining and documenting telephone approvals/disapprovals,.and for initiating a formal Temporary (Procedure) Change Notice (TCN).

The instructi ns for review and approval of procedures provides for a transmittal cover sheet with checklist entries required for checking against process drawings (P&IDs), verification against 'actual plant conditions, and disposition of existing temporary-'faclity-modification/temporary-change notices. A separate instruction is provided for evaluating procedures

.against requirements.of 10 CFR 50.59;"pointed examples are included to assist the reviewer, in addition to designation and training of specific.personnel authorized to perform such reviews. Examples are illustrated via reference to actual experiences -at operating power plant (4) Procedures Developed:

The procedures currently in place for plant operations and maintenance appear to encompass the areas described in Appendix A of Regulatory Guide 1.33. The format, content and-style of these procedures generally appear to conform to that specified in the applicable SCE writer's guide In some cases, the current revision of the procedure

.dates to early 1984 and the procedure has not yet been subjected to.biennial review and upgrade to the latest revisions of the writer's guides. Some procedures have not fully implemented the style and certain human factors aspects of the current writer's guides. Examples involve Operating Instructions (01) and Abnormal-Operating Instructions (AOI).

(For the following aspects'the inspector identified specific procedure examples to the SCE Compliance and QA representatives):

(a) NOTES that include action/step type instructions; (b) CAUTIONS that include action/step type instructions; (c) REFERENCES which do not identify specific parts of applicable Technical Specifications;

(d) REFERENCES that include Technical Specifications, appropriate to specific steps of a procedure, but not identified at those steps; and (e) STEPS in procedures which do not involve operator actions, but which may be appropriate as highlighted NOTES or CAUTION Procedures for response to annunciators do include:

a replicate of each actual annunciator plate, set point for annunciator activation, initiating device identification, plant mode applicability, probable physical causes/of activation, recommended operator actions, and technical references (e.g.,

Technical Specifications, drawings, interfacing procedures).

Additionally, general procedures' have been implemented for response to annunciators, addressing operator actions for multiple alarms, and compensatory actions for unreliable, spurious, or inoperable annunciator The alarm procedures (and the writer's guide) do no incorporate identification of the preferred instruments/methods to verify alarm validity, nor do they require and identify for verification the automatic actions expected to occur; as

. recommended by INPO-85-003. The plant superintendent stated his intent to evaluate resources to upgrade the Abnormal Operating Instructions to.incorporate these industry guideline ( Conclusions'

SCE management has demonstrated a commitment to increasing standards of adequacy for plant procedures, through organization, staffing, and policy support resulting in technically experienced staff trained for and dedicated to preparation and revision of procedure However, management has apparently not been aware of the extent to which theSCE.staff has and has not incorporated developing industry recommendations into the program. This may be attributed to the absence of formal expression of management expectations and absence of associated feedback of status, such as evaluation and action on INPO guidance issued since 198 In the absence of such management expression, individual organizational elements have addressed such criteria non-uniformly and incompletely in SCE writer's guide Additionally, the Site Procedures Group (SPG), which organizationally is the focal point for all site procedures, has no taken the lead to address this aspect either site wide or plant specifi At the exit meeting, SCE representatives stated that SCE would evaluate the inspectors' findings and take action if appropriat No violations or deviations were identified. The licensee's evaluation of this area will be reviewed during a future inspection (Followup Item

50-206/86-20-01).

14 Transamerica DeLaval, Inc., (TDI) Diesel Generators The inspector held discussions with supervisors and cognizant engineer responsible for, and reviewed documentation associated with, the installation, inspection, testing, and design adequacy for the TDI diesel generators (DSRV 20) installed at San Onofre Unit The licensee is a member of the TDI owner's group and as such is implementing the owner's group recommendations. The recommendations are in the form of two distinct phases:

Phase I: is the resolution of 16 core issues intended to serve as the bases for the licensing of plants during the period prior to the completion of Phase I Phase II: is the design'review/quality revalidation (DR/QR) of a large set of.important engine components to assure that their design and manufacture are adequat Unit 1 has preseritly completed Phase I of.the owner's group recommendation hase II recommendations are complete for the number one diesel and should be complete for the number two diesel by June 13, 198 TDI has issued several 10, CFR 21 Potential Defect Reports for the Unit 1 diesel generators: Below is a comprehensive list identifying the item, problem, SCE'scorrective action and status:

NRC Open TDI

'Part 21 SCE Corrective Item N I.D. No. Issue' Date Problem Action Status

  • 86-20-02 102 9/19/80-Dowel counter Inspected and Closed bore in link found zero rod-may be too clearance as shallow,.

require *86-20-03 103

12/16/80 Potential turbo-Drip lubrication Closed charger lube oil system was system defec installe P 111 5/13/82 Capscrews holding Inspected Closed the starting air capscrews and valve assembly verify proper are too lon lengt *86-20-04 112 6/23/82 Improper material Coupling was Closed used in the manufactured by coupling drive Faulk, which is assembly exempt from manufactured by subject 10 CFR 2 Koppers Co., In P 114 7/20/83 High pressure Line was Closed fuel line inspected using possibly subject a fiberoptic to ruptur borescope, no draw seams were foun P 117 9/21/83 Potential problem Line was Closed with the engine inspected for mounted fuel oil support and lin observed during operation. No deficiencies note P 118 10/11/83 Potential problem Subject cables Closed with the engine were replaced...

mounted with properly electrical rated cable cable (90Co).

86-06-P 119 11/16/83 Linear Inspected 25%

Closed indications in of piston the Engine Piston assemblies as Skirt Casting recommende Found no indication P 120 1/9/84 Possible loose Both DGs were Closed hubs on the inspected. Drive

overspeed coupling on DG 1 governor and was tight,.DG 2's fuel transfer was loose and pump driv subsequently, repaire P 121 2/15/84 Problem with Revised DG test Closed turbo-charger procedure as thrust bearing recommended. Will lubrication run auxKiliary L.O'.

during fast pump prior to fast start star P

>

123 7/

Possible surface Inspection Closed imperfctionindicated,.that with valve all springs were springs, satisfactor *86-20-05

.124 1/13 8 Potential Fuel inspection Closed problem with equipment-is high. pressure inspected on fuel injection refueling pumps, delivery-interval, and

.

valve holde sent to vender every five year *86-20-06

---

3/10/86 Elastomer liner Due to system Closed on foot valve of design, no L.O..system corrective disintegrated, action was require Note: Asterisked items have had NRC tracking numbers assigned with this repor The licensee has taken effective and timely measures to address the many concerns associated with the TDI emergency diesel generator No violations or deviations were identifie.

Station Batteries The inspector reviewed procedures which implemented the technical specification required surveillances,for the 125-volt safety related batteries associated with Unit 1. The inspector verified that procedures exist for each part,of technical specification section 4.4.D and that the maintenance procedures for the 125-volt batteries contained the required acceptance criteria where necessary and as noted in the battery technical manual. Battery maintenance-and surveillance'records for 1984-1986 period were reviewed for completeness and proper performance. The inspector witnessed the-performance of a weekly battery surveillance on the number one battery and made observations as to the thoroughness and adherence to.the procedure displayed by the technical personnel performing the tas Based on the review of the above procedures and documents and physical inspection of the batteries, the inspector noted the following items:

.a..'

During a tour of the number one battery room, the inspector noted electrolyte seeping from the cover seam of several cell Two patches of bubbled paint on the floor were observed (indicative of

.leaking electrolyte).

The-northeast end of the battery rack was corroded due to electrolyte reacting with the rack covering. In all, eleven examples of leaking electrolyte were observed. This condition was brought to the attention of the Unit 1 maintenance superviso The inspector was informed that this was an identified-conditio The licensee initially identified this concern, NCR SO1-P-5226, in May of 1985, and at that time proposed applying a vendor recommended adhesive to the cover seam as a corrective action.. The vendor performed a pressure test, MO 85052752000, of 1.0 p.s.i. to verify soundness of all cells.. Approximately half of the cells failed this test. However, to date, no final corrective action has been initiate The batteries have successfully passed the required surveillances, most recently the 18 month load duty cycle test which demonstrates their ability to provide the current time profile required for accident conditions. However, the licensee stated and NRC technical

personnel concur that the leaking condition should not affect the functionality of the battery. The licensee's corrective action will be examined in a future inspectio (Followup Item 50-206/86-20-07) In reviewing the completed procedure SO1-PE-82-193-1, Rev. 0; completed July 24, 1984, one concern was identified.. The procedure was used for th6 preoperational test of the new number one batteries ability to satisfy.' the service load and overall capacity design requirements. To obtain a common reference paint, the temperature of the. battery must be accounted for when determining the discharge rat IEEE 450-1980, Maintenance, Testing and Replacement of Large Lead Storage Batteries (referenced in the procedure), Sectioii reads, "Note that etestdischarge current is equal to the rated dichrgcrrent dvided.by K, whefe K is the discharge current correction factor for theihiLial electrolyte temperature."

"Initially, cell temperatuie was 829F. which corresponds to aK factor of 0.972, '.The tst was run with a discharge current of 1240

+20, -0 amps.' With the.tellteimperature correction, it would have

<been 1275 +20,

-0 amps.. As the discharge rate is increased, th batteries capacity is decrease The minimum final acceptance criteria,f6r this' test s.105 volts or greater. The recorded final voltage was 105.2 volts. Had the cell temperature correction factor been d'pplied, thereby increasing the discharge rate,' the final voltage may have decreased'beldw the acceptance criteria limit. A temperature correction factor was applied to the test, but only to the formula for computing bittery capacity, not for the discharge rat As the test procedure appears to be in conflict with the-accepted industrial standards for the capacity testing of large lead storage batteries, this item is unresolved and will be examined further in a future inspection (Unresolved Item 50-206/86-20-08).- However, this condition does not impact on the batteries ability to satisfy the required emergency design loads. This was demonstrated by the

,successful completion-of the recent 18 month battery load profile tes.

Unresolved Items Unresolved items are matters about which more information is required in order to ascertain whether they are acceptable items, items of noncompliance, or deviations. An unresolved item disclosed during this inspection is discussed in Paragraph 7 of this repor.

Exit Meeting The inspectors met with licensee management representatives denoted in paragraph 1 on May 9', 1986. The scope of the inspection and the inspectors' findings as noted in this report were discussed.