IR 05000206/1986038

From kanterella
Jump to navigation Jump to search
Insp Repts 50-206/86-38,50-361/86-28 & 50-362/86-27 on 860902-05.No Violations or Deviations Noted.Major Areas Inspected:Previous Insp Findings,Tmi Items & Tdi Emergency Diesel Generator 10CFR21 Followup
ML13323B206
Person / Time
Site: San Onofre  
Issue date: 09/18/1986
From: Richards S, Willett D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
To:
Shared Package
ML13323B205 List:
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-1.C.1, TASK-1.D.2, TASK-2.F.2, TASK-TM 50-206-86-38, 50-361-86-28, 50-362-86-27, NUDOCS 8610150292
Download: ML13323B206 (4)


Text

U. S. NUCLEAR REGULATORY COMMISSION

REGION V

Report No /86-38, 50-361/86-28 and 50-362/86-27 Docket No, 50-361 and 50-362 License No DPR-13, NPF-10 and NPFel5 Licensee:

Southern California Edison Company 2244 WalhutiGrove Avenue Rosemead, California. 91770 Facility-Name: San Onofre Nuclear Generating Staton-Units 1,2 aa Inspection at: San Onofre, San Clemente, Californ ia Inspection Conducted:..

September 2-5, 1986 Inspector:

5T2 dennis Will

, Reactor Inspector Date Signed Approved By:

2_

Stuart Richards, Chief Date Signed Engineering Section Summary:

Inspection on September2-5, 1986 (Report Nos.. 50-206/86-38, 50-361/

86-28 and 50-362/86-27)

Areas Inspected:. Routine, unannounced safety inspection of Ticensee action on previous inspectiohfindings,TMI (NUREG-0737)Items, TDI Emergency Diesel Generator 10. CFR Part 21. ifollow-u NRC inspection modules 37702, 30703,

.36100, 94702 and.25565 were covered'during this inspectio Results:

Of the..areas inspected, no violations or deviations were identi fie oi 0292 0923 PDR ADOCK 05000206 i

PDR

DETAILS Persons Contacted Licensee Personnel

  1. M.'A. Wharton Deputy Station Manager
    1. C.A. Couser, Compliance Engineer
  1. J. McKinnon, Quality Assurance Engineer
  1. D.L. Johnson, Engineer, HVAC
  1. W.G. Zihtl, Manager, Compliance
  1. J.A. Mangum, Maintenance Engineer
  1. N. Maringas, ISEG Freedman, Compliance Engineer J. L. Beal, Corporate EQ Engineer Licensin R.L.. Phelps, Corporate EQ Engineer, Safety/Licensing M.J. Speer, Compliance Engineer K. Meddings, Compliance Enginee I.Jones, Training Engineer J. Ibarra,, Corporate HUman Factors'Engineer, Licensing The inspectors also held discussions with other licensee and contract personhel during this inspection. These included plant staff engineers technicians,. administrative assistants and quality assurance personne #Denotes those present during the entrance meeting on September 5,; 1986 Follow-up of unresolved open iteris'Unit 1 (closed):

The Control Room Ventilation Systei was demonstrated to be within design values and,independent-of the Technical Support Center (TSC,) prior to the restart of: the uni b. 86-25-02 (closed): Adocumentationreview of,nontonformances (NCR S01-P-2570, NCR S01-P-2691) and their clos ut (CWO 4006-70, MO 85071243000), did not identify any frconsistencies or improprieties in theresolution and disposition of these nonconformances.. CFR Part 21 Repofts for Trahsamerica DeLaival Inc. (TDI) Diesel Generator The inspector reviewed dotumentation associ'ated with the inspection, testing and maintenance of.the TDI diesel's and discussed the status of the owners group recommendations with the cognizant-engineer and owners group representatiy Phase II of the,owners'group recommendatiohs has now been completed for both Unit 1 TDI diesels (# 1 and 2).

The two Part 21 reports which are currently open for the 'TDI diesels are:

a. TDI #132, November 6, 1986, Problem: Intake and Exhaust spring fa lu e potential

Resolution:

Replace with qualified springs Schedule: Four to six months as parts are available b. TDI # 136, 'Ju y 2, 1986 Problem: Insufficient torquing to connecting rod boltin Res6lution: Torque per new TDI' procedures (pending)

Schedule: -indeterminate 4. Outstanding TMI (NUREG-0737) Issues Units 2 and' Item I.D.2 SPDS (closed): -The SPOS function is performed by the Critical Function Monitoring System (CFMS).and the Qualified Safety Parameter Display System (QSPDS) which 'contains those parameters that are seismically qualified. The 'CFMS and QSPDS have been tested and.verif'ed at Units 2 and 3. These systems have been modeled on the plant. specifi& simulator and are being used by licensee personnel during trainin Item II-..F.2 (closed):

This item was partially closed-out in IR#

5O-361/85 13.,.Now that the Heated Junction Thermocouple installation has been completed, instrumentation for detection of inadequate core coolingis-completed. The.Subcooli ng Margin Monitor (SMM) has, been'removed from the vertical control boards. This was the result of 'a humaIn factors engineering study which concluded that it was redundant to the SMM available on the seismically qualified QSPDS. The procedure review 'for inadequate core cooling was completed durYihg.th'e.i6ose-out of TMI item I.C.1 in.this repor Item I.C.1 (closed):

This item was partially closed out in IR#

50- 361/86-13.'The inspector reviewed the 'system description for. CFMS and QSPDS (SD-S023-820). and the following Emergency Operating Instructions (EOLS):

5023-12-4

"Steam Generator Jube Rupture" 5'S023-12-81 Functiona. Recov ery"

'

S023-12- "Steam Line Bre ak" These'emergency procedures uti ize the SPDS (CFMS & QSPDS) to detect inadequate core. cooling and 'to provide. information pertinent' to the emergenc. Follow-up of Violations Regarding Environmental Qualification (EQ)

A team inspection reviewing the environmental qualification program at the San Onofre units-1, 2; and 3 identified five noncompliances in their inspection report (50-206/85-30, 50-361/85-29, 50-362/85-28) that were later issued as violations. This report also identified that "no generic documentation deficiencies were found."

Corrective action identified in the. licensee's May 9, 1986 response t the Notice of, Violat.ion issued'by Region V NRC on April 2, 1986 was reviewed.by the inspector and. closed as follows:

a. GaliteCabfe (losed): 'The' licensee contacted the manufacturer and verified the simiTarity betweenthe Galite and Prestol-ite process

.

for applying insulation material. to conductor Firewall EP Cable (closed):. The licensee obtained an additional test report supporting the conclusion that Firewal EP cable is qualified for use at San Onofre Unit c. Target Rock Sol.enoid'Valves(closed)." The licensee revised the alified-life calculations for nine valves, based on a fication of valve energization status, following the EQ team inspectio Rockbestos-Firewall III Cable(closed):

The licensee obtained test data for Rockbestos Firewall III cable. This data supports the conclusion that Firewall III cable is qualified for use.at San Onofre units 1, 2., and e. Honeywell Transducer (closed):

The licensee maintains that the qualification package.was in errorwhen it specified a steam environment. The NRC maintains that the package was in error because the equipment was qualified by-analysis instead of type testin which would have been required if it was subject to a steam environment as indicated. The licensee agrees that type testing would have been required if the equipment was subject to a steam.:

environment. The equipment is qualified, no further action is require.

Exit Interview The inspection team met with representatives (denoted'in paragraph 1)on September*5, 1986. The~scope-andfindings of the inspection, which were discussed during this meeting are summarized -s set forth in paragraphs 1 through 5 of this report.