A05951, Suppls Response to Violations Noted in Insp Rept 50-213/86-17,per 860903 Mgt Meeting.Info Consisting of Review of Actual Tank Levels & Annunciator Response Procedures for Tank Low Level Alarms Forwarded on 860908-12

From kanterella
Jump to navigation Jump to search
Suppls Response to Violations Noted in Insp Rept 50-213/86-17,per 860903 Mgt Meeting.Info Consisting of Review of Actual Tank Levels & Annunciator Response Procedures for Tank Low Level Alarms Forwarded on 860908-12
ML20215D306
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 09/26/1986
From: Opeka J, Sears C
CONNECTICUT YANKEE ATOMIC POWER CO.
To: Ebneter S
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
A05951, A5951, NUDOCS 8610140076
Download: ML20215D306 (2)


Text

- _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ ._ _ _ _ _ . _

s CONNECTICUT YANKEE ATOMIC POWER COMPANY B E R L I N, CONNECTICUT P.O. BOX 270 HARTFORD CONNECTICUT e6141-o270 TELEPHONE 203 4 8s-s000 September 26, 1986 Docket No. 50-213 A05951 Mr. Stewart D. Ebneter, Director Division of Reactor Safety U.S. Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, Pennslyvania 19406 Gentlemen:

Haddam Neck Plant Supplementary Information Regarding I&E Inspection No. 50-213/86-17 At the September 3, 1986 management meeting concerning this inspection, additional information concerning item 86-17-03 was requested by the Staff regarding administrative controls which were in place at the time of the inspection to control quantities of water in various tanks.

A packet of information consisting of a review of actual tank levels and annunciator response procedures for tank low level alarms was transmitted to you via the Resident Inspector on September 8 and 12, 1986. The purpose of this letter is to formalize and summarize that response.

This information showed that, although there is no requirement to maintain 180,000 gallons (minimum) of water inventory total in the three tanks in question (demineralized water storage tank, primary water storage tank, recycle primary water storage tank),

actual tank levels are substantially above the 180,000 gallon level, since it is normal practice to keep those tanks full.

8610140076 860926 "-

PDR ADOCK 05000213 G PDR

\Q te e \

= _ _ _ - = = _ _ = - -

s To formalize control of this level, however, Connecticut Yankee Atomic Power Company (CYAPCO) will, by October 31, 1986, increase the low level alarm setpoint on the recycle primary water storage tank, and revise the associated annunciator response procedure, to ensure that the total water inventory at the low level alarm for all three tanks is greater than 180,000 gallons when the plant is in modes 1, 2 or 3.

We trust you will find this additional information satisfies your request. We are available to discuss this information with you at your convenience.

Very truly yours, CONNECTICUT YANKEE ATOMIC POWER COMPANY a .b J. F. Ope ka Senior Vice President By: C. F. Sears Vice President cc: C. I. Grimes i l