A04500, Provides Addl Info to Amend Proposed Tech Specs on Flammable Liquid Control for Control Room,Per 850724 Telcon.Definition of Suitable Containers Consistent w/820716 Submittal & Section 2.2 of SER Issued W/Exemptions from 10CFR50,App R

From kanterella
Jump to navigation Jump to search
Provides Addl Info to Amend Proposed Tech Specs on Flammable Liquid Control for Control Room,Per 850724 Telcon.Definition of Suitable Containers Consistent w/820716 Submittal & Section 2.2 of SER Issued W/Exemptions from 10CFR50,App R
ML20133H123
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 08/01/1985
From: Opeka J
CONNECTICUT YANKEE ATOMIC POWER CO.
To: Zwolinski J
Office of Nuclear Reactor Regulation
References
A04500, A4500, B11475, NUDOCS 8508090199
Download: ML20133H123 (2)


Text

.

CONNECTICUT YANKEE ATOMIC POWER COMPANY B E R L I N. CONNECTICUT P O. BOX 270 HARTFORD. CONNECTICUT 06141-0270 TELEPHONE 203-665-5000 August 1,1985 Docket No. 50-213 Bil475 A04500 Director of Nuclear Reactor Regulation Attn: Mr. John A. Zwolinski, Chief Operating Reactors Branch #5 U. S. Nuclear Regulatory Commission Washington, D.C. 20555 Gentlemen:

Haddam Neck Plant Additional Information on Proposed Technical Specification for Flammable Liquids Control Pursuant to the telephone discussion of July 24,1935 between Northeast Utilities and the NRC Staff, Connecticut Yankee Atomic Power Company is amending its proposed Technical Sppcification on Flammable Liquids Control for the Haddam Neck Control Room.W The alternate wording agreed to is attached and includes a definition for " suitable" containers. The definition of the word " suitable" i consistent with our previous submittal discussing flammable liquid containers U (J and is consistent with Section-2.2 of the Safety Evaluation Report (3) issued with the exemptions from 10CFR50, Appendix R.

Very truly yours, CONNECTICUT YANKEE ATOMIC POWER COMPANY

3. F. OpeKa b ht_.LJ Senior Vice President Attachment (1) 3. F. Opeka letter to 3. A. Zwolinski, dated July 10, 1985,

Subject:

Haddam Neck Plant, Proposed Revisions to Technical Specifications, Flammable Liquids Control.

(2) W. G. Counsil letter to D. G. Eisenhut, dated July 16, 1982,

Subject:

Haddam Neck Plant, Additional Information Supporting Exemption Request from Appendix R.

(3) 3. A. Zwolinski letter to W. G. Counsit, dated November 14, 1984,

Subject:

f Exemption from Requirements of Appendix R to 10CFR50, Section Ill.G and accompanying Safety Evaluation Report.

L(Oh g

8508090199 B50801 PDR ADOCK 05000213 p PDR

3 a.,,-

H. FLAMMABLE LIQUIDS CONTROLS Flammable liquids in _ volumes grea.er than 1 pint shall be restricted from the control room except under the following conditions:

1. Written permission is obtained from the Supervising Control Operator or Shift Supervisor, and
2. The flammable liquid is contained in a suitable
  • container not to exceed one quart in volume, and
3. A dedicated fire watch is assigned to the activity.
  • A suitable container is non-spillable and has a flame arrestor in the nozzle, i