Forwards Summary of Long Term Emergency Diesel Generator Loading Under post-accident Conditions.Long Term Emergency Diesel Generator Loads for All Accident Conditions within 2,000 H Rating of 3,000 Kw
ML20154L599
Person / Time
Site: Crystal River Duke Energy icon.png
Issue date: 09/15/1988
From: Widell R
FLORIDA POWER CORP.
To: Varga S
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
3F0988-11, 3F988-11, NUDOCS 8809260228
Download: ML20154L599 (6)


Text

--

cCOe s.*e,

, 9064 e@O 300*

  • ;Lr a
  • Florida Power C OR POR A7 ION September 15, 1988 3F0988-11 W nnant Control Desk U. S. Nuclear Regulatory Comnission Washington, D.C. 20555 Attention: S. A. Varga

Subject:

Crystal River Unit 3 Docket No. 50-302 Operating Li nse No. DPR-72 Lorg ' Ibm Emergency Diesel Generator loading

Dear Sir:

In a letter dated July 22,1988 (3F0788-18), Florida Power Corporation (FFC) described a study shich had been initiated to evaluate long tem emergency diesel generator loading under post accident m nditions. 'Ihe study was undertaken as a result of NRC concerns that the evaluated loads for the first 30 minutes of sane accident scenarios may not be bounding for the loryjer term.

'Ihe study has been ccrpleted and a sumary is attached. As the summary shows, the long tem emergency diesel generator loads for all accident conditions are within the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> rating of 3000 kw. 'Ihis is true for the existing plant configuration as well as for the configuration to be inplemented durirq the next refueling outage.

Should there be any questions, please contact this office.

Sincerely,

/

s r r, I j

Rolf C. Wide 1 Director Nuclear Operations Site Support 0809260228 880915 PDR ADOCK 05000302 PNV Attachment p xc: Dr. J. Nelson Grace Regional AdminisJrator, Rcgion II Mr. Peter Holmes-Ray /

Senior Resident Inspector Post Office Box 219

  • Telephone (904) 795 3802 A Flonda Progress Company l$

. I DIE 9EL GGEIUGIR "A" & "B" 7 Df0f EXIBUD IDME 2e Emert3erry Diesel Generator (EDG) loadig subnittal of February 29, 1988 covemd the auttnatic loading for the first 30 minutes. mis subnittal represents the loading frun 30 minutes to seven days.

Tables 1 and 2 of this @=ent tabulate the "A" EDG 30 minute to seven day extended time loads including both the autcmatically applied loads and the manually awlied loads with "B" EDG failure. Se loads runain within the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> 3000 W rating of the diesel generator for both existing conditions and after the installation of the Refuel VII rodifications.

Tables 3 ani 4 of this document tabulate the "B" EDG 30 minute to seven day extended time loads including both the automatically awlied loads and the manually awlied loads with "A" EDG failure. W e loads remain within the 2000 hour0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br /> 3000 W rating of the diesel generator for both existing conditions and after the installation of the Refuel VII modifications.

Failura of the steam driven Emergency Feedvater Punp (EFP-2) results in sharing of loads between "A" and "B" EDG's. Werefore, the "B" ED3 failure will bound all scemrios for the "A" EDG loadirq projected for seven days. Before the Refuel VII modifications the maxim.nn "A" EDG loading with "B" IIG failure is 2924 W and occurs during steam line break outside the Reactor Buildirq. After the Refuel VII modifications the maxinum "A" EDG loadirs with "B" ED3 failure is 2879 m and occurs during the 0.07 sq. ft. and 0.04 sq. ft. Intamediate Break LOCAs.

%e failure of motor driven Emergency Foodvater PLmp (EFP-1) does not affect the loading of "B" ED3 because EFP-2 is steam driven. Worofore, the "A" ED3 failure will bound all s narios for the "B" ED3 loadim projected for seven days. Before the Refuel VII modifications the maximum "B" EDG loading with "A" EDG failure is 2939 W and occurs during the 0.07 sq. ft. and 0.04 sq. ft.

Intermediate Break IDCAs. After the Refuel VII modificaticos the maxinza "B" EDG loading with "A" EDG failure is 2895 W and occurs during the 0.07 sq. ft.

and 0.04 sq. ft. Intemodiate Break IDCAs.

20 time interval tabulaticos provide approximate timim when the load charges occur.

\

l l

l EM-3A IDADING WI'IH EDG-3B FAIIIJRE WrIH PIANNED )CDIFICATICNS INSTAIIED TABLE 1 Iarge Break IDCA - 14.4 Sq.-Ft.

Time After Break 30m lh id id - 7d

'Ibtal Power (kW) 2726.4 2319.4 2360.4 2180.4 Int. Break IDCA - 0.5 Sq.-Ft.

Time After Break 30m lh Id 1d - 7d Total Power (kW) 2726.4 2319.4 2360.4 2180.4 Int. Break IDCA - 0.07 Sq.-Ft.

Time After Break 30m lh 3h id id - 7d

'Ibtal Power (kw) 2879.4 2654.4 2790.1 2180.4 2180.4 Int. Break IDCA - 0.04 Sq.-Ft.

Time After Break 30m 33m lh 3h Id id - 7d

'Ibtal Power (kw) 2682.4 2879.4 2654.4 275,0.1 2180.4 2180.4 Small Break IDCA - 0.01 Sq.-Ft.

Time After Break 30m lh 10.5h id id - 7d Total Power (kw) 2705.9 2457.4 2610.1 2180.4 2180.4 Steam Line Break Inside RB Time After Break 30m lh id id - 7d

'Ibtal Power (kw) 2718.4 2876.4 2180.4 2180.4 Steam Line Break Outside RB Time After Break 30m lh id id - 7d

'Ibtal Power (kw) 2784.4 2876.4 2180.4 2180.4 Feedwater Line Break Inside RB Time After Break 30m lh id 1d - 7d Total Power (kw) 2718.4 2876.4 2180.4 2180.4 OISG Tube Rupturo Time After Break 30m lh id id - 7d

'Ibtal Power (kW) 2783.4 2876.4 2180.4 2180.4

ED3-3A IDADING WITH EDG-3B FAIIURE HU:SENT PIRfr CCHFIGURATICH TABLE 2 Iarge Break IOCA - 14.4 Sq.-Ft.

Time After Break 30m lh id id - 7d Total Power (kW) 2726.4 2319.4 2360.4 2180.4 Int. Break IDCA - 0.5 Sq.-Ft. 30m lh id 1d - 7d -

Ibtal PtnAT (kw) 2726.4 2319.4 2360.4 2180.4 Int. Break IDCA - 0.07 Sq.-Ft.

Time After Break 30m lh 3h id id - 7d Ltal Power (kw) 2584.4 2794.4 2790.1 2180.4 2180.4 Int. Break IDCA - 0.04 Sq.-Ft.

Time After Break 30m 33m lh 3h Id Id - 7d Total Power (kw) 2822.4 2584.4 2794.4 2790.1 2180.4 2180.4 Small Break IOCA - 0.01 Sq. Ft.

Time After Break 30m lh 10.5h Id id - 7d TM.31 Power (kW) 2845.9 2597.4 2610.1 2180.4 2180.4 Steam Line Break Inside RB Time After Break 30m lh id id - 7d ibtal Power (kW) 2858.4 2532.4 2180.4 2180.4 Steam Line Break Outside RB Time After Break 30m lh id 1d - 7d

'Ibtal Nwer (kW) 2924.4 2532.4 2180.4 2180.4 Feodwater Idne Break Inside RB Time After Break 30m lh id Id - 7d Ibtal Power (kw) 2858.4 2532.4 2180.4 2180.4 oIsa wbe Rupture -

Time After Break 30m lh id 1d - 7d Ibtal Power (kw) 2923.4 2532.4 2180.4 2180.4 1

1 I

i

EDG-3B IDADING WI'IH EIn-3A FAIIURE WI'IE PIANNED EIFICATICtB INSTAIJ.ED TABIE 3 Iarge Break IDCA - 14.4 Sq.-Ft.

Time After Bmak 30m lh id 1d - 7d Total Power (kw) 2830.8 2423.8 2464.8 2284.8 Int. Break IDCA - 0.5 Sq.-Ft.

Time After Break 30m lh id id - 7d Total Power (kw) 2830.8 2423.8 2464.8 2284.8 Int. Break IDCA - 0.07 Sq.-Ft.

Time After Break 30m lh 3h Id ld - 7d

'Ibtal R:wer (kW) 2548.8 2758.8 2894.5 2284.8 2284.8 Int. Break IDCA - 0.04 Sq.-Ft.

Time After Lreak 30m 33m lh 3h Id id - 7d

'Ibtal Ptwar (kv) 2351.8 2548.8 2758.8 2894.5 2284.8 2284.8 Small Break IDCA - 0.01 Sq.-Ft.

Time After Break 30m lh 10.5h id ld - 7d Total Power (kw) 2351.8 2561.8 2714.5 2284.8 2284.8 Ste a Line Break Inside RB Time After Break 30m lh id id - 7d Ibtal Power (kw) 2286.8 2496.8 2284.8 2284.8

.l Steam Line Break Outsids RB Time After Break 30m lh id ld - 7d

'Ibtal Power (W) 2286.8 2496.8 2284.8 2284.8 Foodwater Line Break Inside RB Time After Bmak 30m lh Id 1d - 7d i 'Ibtal Power (kW) 2286.8 2496.8 2284.8 2284.8 OIEG 7bbe Rupturo Time After Break 30m lh id id - 7d

'Ibtal Ibwer (kw) 2491.8 2636.8 2284.8 2284.8 i

. .-e EIG-3B IDADING WI'IH EDG-3A FAllDRE MtESDff PIANT CCNFIGURATICH TABIE 4 Iarge Break IDCA - 14.4 Sq.-Ft.

Time After Break 30m lh Id id - 7d

'Ibtal Power (kw) 2870.9 2463.9 2504.9 2324.9 i

Int. Btmak IDCA - 0.5 Sq.-Ft.

Time After Break 30m lh Id ld - 7d

'Ibtal Power (kw) 2070.9 2463.9 2504.9 2324.9 9

Int. Break IDCA - 0.07 Sq.-Ft.

Time Aftar Break 3tha lh 3h id id - 7d -

'Iotal Power (kW) 2728.9 2938.9 2934.6 2324.9 2324.9 Int. Btsak IDCA - 0.04 Sq.-Ft.

Time After Break ' 30m 33m lh 3h Id 1d - 7d

'Ibtal Power (kw) 2531.9 2728.9 2938.9 2934.6 2324.9 2324.9 Small Break IDCA - 0.01 Sq.-Ft.

Time After Break 30m lh 10.5h id Id - 7d Total Power (kW) 2531.9 2741.9 2754.6 2324.9 2324.9 Steam Line Break Inside RB Time After Break 30m lh id 1d - 7d

'Ibtal Power (kW) 2466.9 2676.9 2324.9 2324.9 Steam Line Break Outside RB Time After Break 30m lh Id ld - 7d

'Ibtal Power (kw) 2466.9 2676.9 2324.9 2324.9 Foodwater Line Break Inside RB Timo After Break 30m lh id id - 7d

'Ibtal Power (kW) 2466.9 2676.9 2324.9 2324.9 1

OISG 'Ibbe Rupturc Time After Break 30m lh id ld - 7d

'Ibtal Power (kW) 2531.9 2676.9 2324.9 2324.9 4

l J