ML18093B023

From kanterella
Revision as of 01:08, 29 June 2018 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Wolf Creek Generating Station Revision 31 to Updated Safety Analysis Report, Penetration Seal Data, M-663-00017A, Rev W06, B7-80 to B8-147
ML18093B023
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 03/08/2018
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 M-663-00017A, Rev W06
Download: ML18093B023 (165)


Text

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected Zone Review: P621W0009 Fire Area (Side 1) F-4 No issues within Heat Affected Zone Fire Area (Side 2) F-5 1. 314" Cond.: Not wlthin Heat Affected Zone. Side 1 Photo Side 2 Photo No photo required. No photo required.

Sketch FA: F-4 S1ft1

  • Pa. e 87-80 of 87-89 Appendix: 87 Review Distances (Rafenm T.2.3-l) 12" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) (.F) (in} (in) 0.5 1712 4,6 5.9 , 1524 3.7 5.1 1.5 1357 3 4.3 2 1209 2.3 3.6 2.5 1078 1.7 3,1 3 962 1.2 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 5.5 555 0.7 6 499 0-4 6.5 450 0.2 7 406 0 75 368 Coolact -...... ---1--o--.:=.....-

FA: F-1 8Jdt 2 I M-663-00017 A, Revision W04 Pa e 87-81 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P621W0017 Penetration Type: FB-1 Fire Area (Side 1): F-5 Fire Area (Side 2): F-4 Loc./Eiev.: 2041'-6" M-OX Dwg: M-OX6908 1. Barrier Thickness
2. Opening Size: 3. Penetrants:
4. Sealant Type: 5. Damming Side1: 12" 16"0 (1) 12"P Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

NIA 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed per detail Walkdown Comments:

Wall thickness ( 12") determined by C-1 C6211. Sketch: FA: F--5 Sldo 1 P621W0017 10. Annular Gap (smallest)

1-1/2" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete:
14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: C> ' -. -(/ -ll' *" : t>' *, * *
  • I ;... , ,* b u * ' .. FA: F-4 Si6e2 Steel M-663-00017 A, Revision W04 Pa e B7 -82 of B7 -89 Penetration Seal Data Appendix: 87 Photos: P621W0017 Fire Area F-5 (Side 1) Fire Area F-5 (Side 1) Fire Area F-4 (Side 2) Fire Area F-4 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected Zone Review: P621W0017 Fire Area (Side 1) F-5 1. 1/2" unscheduled Cond.: Not within Heat Affected Zone Fire Area (Side 2) F-4 2. 5U5P1J, 1-1/2" Cond.: Not within Heat Affected Zone 3. 6U5Z1 B, 2" Cond.: Not within Heat Affected Zone. Side 1 Photo No photo required. Sketch FA: f.l lcle1 Side 2 Photo Pa e 87-83 of 67-89 Appendix: B7 Review Distances 7A.flgure7

.2.3-1) 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Oist. (ft) ("F) _lin} (in) 0.5 1712 14.6 5.9 1 1524 '3.7 5.1 --1.5 1357 3 4.3 2 1209 2.3 3.16 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 5.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 0 7._5 368 Contact t 81de2 M-663-000 17 A, Revision W04 Pa e 87-84 of 87-89 Penetration Seal Data Appendix: B7 Penetration

  1. P621W0221 Penetration Type: FB-1 Fire Area (Side 1 ): A-5 Fire Area (Side 2): F-4 Loc./Eiev

.: 2043'-0" M-OX Dwg: M-OX6901

1. Barrier Thickness:
  • 48" 10. Annular Gap (smallest):

2" 2. Opening Size: 18"0 11. Gap between pen: N/A 3. Penetrants:

(1) 12"P 12. Barrier Type: A F 4. Sealant Type: Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated

No 6. Damming Side 2: Boot* Wayne Aregood 7. Damming Continuity (Acc/Rej): NJA Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: 48" Reviewed By: Walkdown Comments:

  • This wall is located on the west side of the Fuel Bldg a11d interfaces with the Aux Bldg. Each building is independent with a seismic gap between them, resulting in a 48" wall thickness. The correspond ing Aux Bldg Pen. No. is P143W1489. Queried (LB) QC that was involved with this seal during construction. QC indicated this seal is full depth ceramic fiber and is a separate seal from P143W1489. Sketch: FA: A*5 Sida1 P621W0221 u . " .. Slde2 M-663-00017 A, Revision W04 Pa e 87-85 of 87-89 Penetration Seal Data Appendix: 87 Photos: P621W0221 Fire Area A-5 (Side 1) Fire Area A-5 (Side 1 ) Fire Area F-4 (Side 2) Fire Area F-4 (Side 2)

7 A, Revision W04 Penetration Seal Data Heat Affected Zone Review: P621W0221 Fire Area (Side 1) A-5 See P621 W1489 for Details, No issues within Heat Affected Zone. Fire Area (Side 2) F-4 1. 112* Unscheduled Cond.

StaUon): No within Heat Affected Zor19. 2. 5U5P01, 24" Cable Tray, Not within Heat Affected Zone Side 1 Photo Side2Photo No photo required No photo required.

Sketch Pa e 87-86 of 87-89 Appendix: 87 Review Distances (Refa!llnCe M-663<00017A.

Figure 1' .2.3-1) Pipe L1 &l2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1712 4.6 5_9 1 1524 3.7 1 5.1 1.5 1357 3 14.3 2 1209 2.3 1 -3.6 2.5 1078 1.7 3.1 3 962 12 2.5 3.5 860 I 0.7 2."1 4 769 (l_J 1.7 4.5 689 Contact 1.3 Is 618 1 5.5 555 0.7 6 499 0.4 6.5 450 02 7 406 0 7.5 368 Contac_t M-663-000 17 A, Revision W04 Pa e 87-87 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P621W0224 Penetration Type: FB-1 Fire Area (Side 1): A-5 Fire Area (Side 2): F-4 Loc./Eiev.: 2043'-0" M-OX Dwg: M-OX6901
1. Barrier Thickness
48"
  • 10. Annular Gap (smallest

): 2-1/2" 2. Opening Size: 18"0 11. Gap between pen: N/A 3. Penetrants

(1) 12"P 12. Barrier Type: A F 4. Sealant Type: Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated: No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): NIA Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth: 48"* Reviewed By: Walkdown Comments:
  • This wall is located on the west side of the Fuel Bldg and interfaces with the Aux Bldg. Each building is independent with a seismic gap between them, resulting in a 48" wall thickness

. The corresponding Aux Bldg Pen. No. is P143W1488

. Queried (LB) QC that was involved with this seal during construction

. QC indicated this seal is full depth ceramic fiber and is a separate seal from P143W1488.

Sketch: FA: Ao9 Side1 P143W14811 1 I s 1*91\tc..

. " ....... P ...

  • I b *,. ' .. ' t) t (.C llA'I'IIC.

(..TVn FA: F-4 Slde2 M-663-000 17 A, Revision W04 Pa e 87-88 of 87-89 Penetration Seal Data Appendix: 87 Photos: P621W0224 Fire Area A-5 (Side 1) Fire Area A-5 (Side 1) Fire Area F-4 (Side 2) Fire Area F-4 (Side 2)

M-663-000

17A, W04 Penetration Seal Data Heat Affected Zone Rev.iew: P621W0224 Fire Area (Side 1) A-5 1. 5U5A96, 24" Cable Tray, Not within Heat Affected Zone. Fire Area (Side 2) F-4 2. 5U5P01, 24" Cable Tray, Not within Heat Affected Zone 3. 1fT Unscheduled Cond. (Pull Station),

Not within Heat Affected Zone Side 1 Photo Side 2 Photo No photo required. No photo required. Sketch FA: A-45 '*' '"

.

-Nof A\. HeJrs r.J Pa. e 87-89 of 87-89 Appendix: 87 Review Distances (Ref 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1712 4.6 5.9 1 1524 3.7 5.1 1.5 1357 3 4.3 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 9.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 15.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 0 7.5 368 Contact + +

Page 1 I I i I 6. *.

CREEK

-\f NUCLEAR OPERATING CORPORATION M-663-00017 A Attachment 88 ' Fire Protection Evaluation For Penetrant Size Exceeding Typical Detail RB-SA Limitation I I Rev. No. Prepared By Date Reviewed By Date W01 08/19/05 08/19/05 I Jeff Suter Wayne S Aregood I '

M-663-00017 A Attachment 88 Revision WO 1 Table of Contents Page 2 of 8 Revision Log ...................................................................................................................................

3 1.0 Purpose ...............................................................................................................................

4 2.0 Scope ..................................................................................................................................

4 3.0 References

..........................................................................................................................

4 4.0 Evaluation

...........................................................................................................................

5 5.0 Conclusions

.........................................................................................................................

8 Appendix 88, Penetration Seal Data ....................................................

(180 Total Pages)

M-663-000 17 A Attachment B8 Revision W01 Revision Reason for Revision W01 Original Issue Page 3 of 8 Revision Log M-663-00017 A Attachment B8 Revision WO 1 1.0 Purpose Page 4 of 8 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04.

This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10. 2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1. 2.2 Refer to Section 7.0 of M-663-00017 A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017.

In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 CTP-1022 (M-663-00121),

Fire Qualification Test on Penetration Seals 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

M-663-00017 A Attachment 88 Revision W01 5.0 Evaluation 5.1 Assessment of Condition to Design Requirements Page 5 of 8 The penetration openings identified in Table I contain a pipe penetrant that exceeds the size limitation directly bounded by typical detail RB-5A from M-663-00017. Figure 1 depicts detail RB-5A, which is an annular reduction seal. The primary opening is sealed with full barrier depth HOSE/HOLE, leaving a small annular gap (1" maximum) between the penetrant and HOSE/HOLE to accommodate penetrant movement.

The gap is sealed on both barrier sides with a minimum 3" depth of ceramic fiber within a silicone impregnated fiberglass boot. Typical detail RB-5A directly qualifies a seal with up to a 2" diameter penetrant as 3-hour F and T rated. The HOSE/HOLE annular reduction seals for the Table I penetrations are bounded by the limitations of typical detail RM-1A, which allows up to an 18" pipe penetrant for an HOSE/HOLE seal. The unbounded portion necessitating evaluation is the penetrant size in relation to the annular gap sealed with ceramic fiber and a silicone impregnated boot. TABLE I Penetrations with Penetrant Size Exceeding Detail RB-5A Limitations Penetration Communicating Pipe Penetrant Fire Areas Comments' Disposition Number Side 1 Side 2 Diameter P111W1584 A-1 A-4 2-1/2" See 5.2 P121S0257 A-1 A-4 8" See 5.2 P121S0258 A-1 A-4 8" See 5.2 P121S0263 A-1 A-4 6" See 5.2 P121S0266 A-1 A-4 4" See 5.2 P121S0267 A-1 A-4 4" See 5.2 P121S0268 A-1 A-4 6" See 5.2 P121S0273 A-1 A-4 6" See 5.2 P121S0274 A-1 A-4 6" See 5.2 P121S0275 A-1 A-4 10" See 5.2 P121S0279 A-1 A-4 12" See 5.2 P121S0280 A-1 A-4 4" See 5.2 P121S0281 A-1 A-4 8" See 5.2 P121S0283 A-1 A-4 4" See 5.2 P121W1781 A-1 RW-1 6" See 5.2 P121W1782 A-1 RW-1 3" See 5.2 P122S0327 A-1 A-2 10" See 5.2 P122S0331 A-1 A-2 3" See 5.2 P122S0338 A-1 A-2 4" See 5.2 P122S0339 A-1 A-2 14" See 5.2 P122S0340 A-1 A-2 14" See 5.2 P122S0349 A-1 A-2 12" See 5.2 P122S0350 A-1 A-2 4" See 5.2 P122S0351 A-1 A-2 4" See 5.2 P122S0357 A-1 A-2 8" See 5.2 M-663-00017 A Attachment 88 Revision W01 Penetration Number P122S0367 I P122S0373 P131S0513 P131S0522 P131S0525

P131S0526 P131S0529 P131S0530 S0697 P132S0698 P132S0699 P132S070 P132S0710 P132S0713 P132S0722 P132S0723 P133S0769 P133S0771 P133S0793 P133S0800 P133S0801

P133S0802 P133S0810 P133S0820

P134S0864 0875 P134S0911 P134S0912 P134S0918 P134S0919 P141W1854 P141W1980 Communicating Fire Areas Side 1 Side 2 A-1 A-2 A-1 A-2 A-8 A-1 A-8 A-1 A-8 A-1 A-9 A-1 A-9 A-1 A-9 A-1 A-9 A-1 A-10 A-1 A-10 A-1 A-8 A-1 IA-8 A-1 A-8 A-1 A-8 A-1 A-8 -1 A-8 A-1 A-8 A-1 A-25 A-1 A-25 A-1 A-25 A-1 A-25 A-25 A-1 A-25 A-1 A-25 A-1 A-25 A-1 A-24 A-1 A-24 A-1 A-24 A-1 A-24 A-1 A-24 A-1 A-24 A-1 A-24 A-1 A-8 A-9 A-16 A-9 Page 6 of8 Pipe Penetrant Comments/

Disposition Diameter 8" See 5.2 4" See 5.2 3" See 5.2 3" See 5.2 3" See 5.2 10" See 5.2 10" See 5.2 10" If 8" 5.2 8" 5.2 10" 5.2 (1) 3", (1) 3/4" See 5.2 (1) 3", (1) 3/4" See 5.2 6" See 5.2 3" See 5.2 3" See 5.2 3" See 5.2 4" See 5.2 6" See 5.2 6" See 5.2 4" See 5.2 4" See 5.2 4" See 5.2 6" See 5.2 10" See 5.2 10" See 5.2 4" See 5.2 4" See 5.2 10" See 5.2 I 4" See 5.2 4" See 5.2 4" See 5.2 4" See 5.2 18" See 5.2 18" See 5.2 M-663-000 17 A Attachment 88 Revision WO 1 "'YERlEO BOOT fTYP I FIP.E OR ltiSVRUMHIT iUSt Page 7 of 8 1* MAX. Am<I.A..US MOUND I'J'l'!,

iJ(lEIM!'IED 6'1' Mol,}:, TR ... "'S*'ERSE PI"E Fll.l. 511/M:I(F!

!)[JDili m" MIN.I FLOOR OR WALL CONfiGUR/.l,TION 5.2 Evaluation of Condition Figure 1, Typical Detail RB-5A (Reference M-663-00017)

The Table I penetrations are considered 3-hour F rated based on the successful performance of Penetration 1 from fire test CTP-1022.

The tested configuration was comprised of a 1 0" opening containing a 2" diameter pipe penetrant.

The opening was sealed with a 12" depth of HOLE leaving a 1" annulus around the pipe penetrant.

Silicone impregnated boots filled with a 3" ceramic fiber depth were then installed beyond the barrier plane on both penetration sides. This presented a seal configuration consistent with Figure 1 above. Industry fire testing reveals that the exposed side boot is sacrificial and will be consumed when directly subjected to an ASTM E-119 fire. The loss of this boot will result in the loss of the exposed side ceramic fiber due to gravity, since the only structural support provided for the material beyond the barrier plane is that presented by the boot. However, the unexposed side boot with ceramic fiber fill will remain in tact, and adequately prevent fire propagation via the small annular gap between the pipe penetrant and the HOSE/HOLE sidewall.

This ceramic fiber and boot configuration will not be charred or consumed during the fire exposure.

The ceramic fiber will be maintained in position by the unexposed side boot, which is not determinately

impacted, because it is not subjected to direct flame impingement.

Considering the performance of Penetration 1 from CTP-1022 and the and the non-ablative material properties of ceramic fiber, penetrant size will not impact seal F rating. However, a T rating for penetrants larger than 2" diameter is not directly bounded by fire testing.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates M-663-00017 A Attachment 88 Revision WO 1 Page 8 of 8 that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment

reviews, documented in Appendix 88, were conducted for each penetration of concern. This review was completed in accordance with the criteria and review methodology established in M663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that no exposed insitu combustibles or PFSSD circuits are located within the heat affected zone. Each of the penetrations satisfies the review criteria of M-663-00017 where T rating requirements are not met. Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation.

The Table I penetrations are 3-hour F rated. The comprehensive walkdown review for each of these penetrations revealed that no exposed insitu combustibles or PFSSD circuits are negatively affected by the non T rated penetrations.

6.0 Conclusions Based on the above discussions, it is reasonable to conclude that the Table I penetration seals are acceptable as 3-hour F rated and will perform their intended

function, regardless of not achieving a T rating. The penetration seals satisfy regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements, to prevent spread of fire from one fire area to another.

It has also been determined through this evaluation that the lack of a T rating will not affect the plant's ability to achieve and maintain PFSSD.

M-663-00017A, Revision WOl PenetraUon Seal Data Penetration

  1. P111W1584 Penetration Type: RB-5A Loc./Eiev.:

1981'.()"

1. BarrierThickness
24" 2. Opening Size: 8"0 3. Penetrants
(1) 2-1/2"P Page 88-1 of 88-180 Appendix: B8 Fire Area (Side 1): A-1 M-OX Owg: M-1X1910 Fire Area (Side 2): A-4 10. Annular Gap (smallest): 2* 11. Gap between pen: N/A 12. Bar:rierType
f R W 4. Sealant Type
HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot filled w/ceramic fiber 14. Pipe Insulated:

No 6. Damming Side 2: Not inspected Wayne Aregood 7. Damming Continuity (Acc!Rej):

N/A Prepared By: 8. Boot Condition (AcciRej):

Accept Jeff Suter 9. Sealant Depth: 29" ** Reviewed By: Walkdown Comments: 1 )-Physical manipulation of boot material confirmed boot is filled w/ceramic fiber. ,.,. Sealant depth determined by installation inspection report. Sketch: FA:A-1 Slde1 P111W1 .. .. b.. .. A '

  • C) * ., * ** * ** * * . 4 * *
  • p .. * * * ., A' I * * ' . . . . . FA:A-4 Slde2 M-663-00017A, Revision WOI Page B8-2 of 1 80 Pen,etration Seal Data Appendix: B8 Photos: P111W1584 Fire Area A-1 (Side 1) Fire Ar;ea A-1 (Side 1) Fire Area A-4 (Side 2) Rre Area A-4 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P111W1584 Fire Area (Side 1) A-1 1. Pull Box for conduit 5J1C2K. 3*: Not within Heat Affected Zone. Pull box is 3-112" away from plpe. Fire Area (Side 2) A-4 2. Pull Box not within Heat Affected Zone. Pull Box is 3-112* away from pipe. Could not visuany identify the conduit entering the Pull Box because I could not climb or use a ladder due to contamination area. However same circuit as in Side 1. Side 1 Photo Side2Photo No photo required.

Sketch Page 88-3 of 88-180 Appendix: 88 Review Distances (Refentnatt,4.;663.0(1017-'.

fiQIA 2*112" Pipe L1 &L2 Temp. R1 Radius R2 Radius Oist._lft)

("F) (in) (in) 0.5 1593 14 5.4 ' J 1321 2.8 4.1 1.5 1097 1.8 3.1 2 . 914 1 2.J 2.5 763 0.3 1.6 3 639 Con tad . 1.1 3.5 537 0.6 4 454 0.2 4.5 385 Contact M-663-0001 7A, Revision WOJ Page 88-4 ofB -I 0 Penetration Seal Data Appendix: B8 Penetration#:

P121S0257 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 LocJEiev.:

1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness

19" 10. Annular Gap (smallest)
1" 2. Opening Size: 12"0 11. Gap between pen: N/A 3. Penetrants
(1) B"P 12. Barrier Type: F R W 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete:

Steel 5. Damming Side1: Boot 14. Pipe Insulated

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej)
N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Slab Thickness determined from drawing C-OC1211 Sketch: FA: A-1 SloE 1 P121S0257 M-663-00017 A, Revision WO I Penetration Seal Data Appendix: 88 Photos: P12150257 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P12150257 Fire Area (Side 1) A-1 No Issues within Heat Affected Zone Fire Area (Side 2) A-4 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch I Page B8-6 of 88-180 Appendix: B8 ,Review Distances (RefenlrlC8 M-6"63-00017A.

f9l'8 7.2.3-11 L1 &L2 Temp. R1 Radius R2 Radius Dist.J.f!t rt=l (In) (In) 0.5 1677 4.4 5.8 1 1463 3.4 4.8 1.5 1277 2.6 3.9 2 1116 1.9 3.2 2.5 ,976 1.2 2.(; 3 855 0.7 2 3_5 750 0.2 1.6 4 659 Contact 1.2 j4.5 581 0.8 5 512 0.5 5.5 453 0.2 6 1402 0 6..5 358 Contact No sketch requir

  • M-663-000I?A, Revision WOI Penetration Seal Data Appendix: B8 Penetration
  1. P121S0258 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.
1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness
22" 2. Opening Size: 14"0 3. Penetrants
(1) 8"P 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)
N/A 8. Boot Condition (Acc/Rej)
Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab Thickness determined from drawing C-OC 1211 Sketch: FA: A-1 SIDE 1 fA: A-4 SIDE2 5' fr<<) 10. Annular Gap (smallest)
2 1/2" 11. Gap between pen: N/A 12. Barrier Type: F R W 13. Opening Sleeved or Concrete: Steel 14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: P121S0258 M-663-00017A

, Revision WOl Page 88-8 of 8 -I 0 Penetration Seal Data Appendix: B8 Photos: P121S0258 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • M-663-00017A. Revision WOl Penetration Seal Data Heat Affected Zone Review: P121S0258 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-4 1. 4U3F5F, 2" Cond.: Measured, not within Heat Affected Zone. 2. 4U3F1H, 1-112" Cond.: Measured, not within Heat Affected Zone. 3. 4U3F1J, 1-112" Cond.: Measured, not within Heat Affected Zone. Side 1 Photo Side2Photo requi Sketch Page 88-9 of 88-J 80 Appendix: 88 Review Distances M-663-<<Xl17A.

Flllft 1.2.3-1 ) 8"Pipe L1 & l2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (In) (in) 0.5 1sn 4.4 )5.8 1 1463 3.4 ,4.8 1.5 12n 2.6 3.9 2 1116 1.9 3.2 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 6.59 1 Contact 1.2 4.5 581 0.8 5 512 0.5 '5.5 453 0.2 6 402 0 6.5 )358 Contact FA: A-1 Slde1 Nl I

!/t!llf M-663-00017A

, Revision WOI Penetration Seal Data Appendix: 88 Penetration

  1. P121S0263 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc.!Eiev.: 1988'-0" M-OX Dwg: M-OX 1211 1. Barrier Thickness
2. Opening Size: 3. Penetrants: 4. Sealant Type: 5. Damming Side1: 19" 12" D (1) 6"P HDSE/HDLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): NIA 8. Boot Condition (Acc/Rej)
Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined by drawing C-OC 1211 Sketch: FA: A*1 SIDE 1 10. Annular Gap (smallest):

2 1/2" 11. Gap between pen: N/A 12. Barrier Type: F R W 13. Opening Sleeved or Concrete:

Steel 14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By:

M-663-00017A, Revision WOl Penetration Seal Data Appendix: 88 Photos: P121S0263 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) y Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P121S0263 Fire Area (Side 1) A-1 No Issues within Heat Affected Zone. Fire Area (Side 2) A-4 No Issues within Heat Affected Zone. Side 1 Photo Side2Photo u Sketch Page B8-12 of 88-180 Appendix: B8 Review Distances F9n 7.2.3-1) &*Pipe L1 &L2 Temp. R1 Radius R2 Radius Dlst. (ft) rt=> [In} (in}_ '0.5 1659 4.3 5.7 1 1431 3.3 4.6 1.5 1236 2.4 3.8 2 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 *Contact 1.3 4 608 0.9 4.5 531 0!6 5 464 0.3 5.5 408 0 6 359 Contact I I No sketch require
  • M-663-00017A, Revi ion WOl Penetration Seal Data Appendix: B8 Penetration
  1. P121S0266 Penetration Type: RB-5A Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness
22" 2. Opening Size: 14" D 3. Penetrants
(1) 4"P 4. Sealant Type: HDSE/HDLE

, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Ace/Rei): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: FA: A-1 SIDE 1 10. Annular Gap (smallest)

4 1/2" 11. Gap between pen: N/A 12. Barrier Type: F R W 13. Opening Sleeved or Concrete: Steel 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By:

M-663-000 17 A, Revision WO l Penetration Seal Data Appendix: 68 Photos: P121S0266 Fire Area A-1 (Side 1 ) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P121.S0266 Fire Area (Side 1) A-1 No issues within Heat Affected Zone : Fire Area (Side 2) A-4 , No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page B8-15 of B8-I 80 Appendix: B8 Review Distances 4" Pipe L1 & L2 Temp. R1 Radius R2 Radiua Oist. (ft) ("F) _{I'!} (in) 0.5 1625 4.2 5.5 1 1374 3 4.4 1.5 1163 2.1 3.4 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 1.4 3.5 610 Contact 0.9 4 1523 0.6 4.5 1450 0.2 5 389 Contact I I o sketch requir M-663-00017A

, Revision WOl Penetration Seal Data Appendix:

B8 Penetration

  1. P121S0267 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.
1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness
22" 2. Opening Size: 14" D 3. Penetrants: (1) 4'"P 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab lhickness determined by drawing C-OC1211 Sketch: FA: A-1 SIDE 1 FA: A-4 SIOE2 10. Annular Gap (smallest)
3" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M-663-000l?A, Revision WOJ Page B8-l 7 of B -I 0 Penetration Seal Data Appendix: B8 Photos: P121S0267 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)
  • *
  • M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review: P12150267 Fire Area (Side 1) A-1 No Issues within Heat Affected Zone Fire Area (Side 2) A-4 1, 6U1020: 314" Cond.: Measured, not within Heat Affected Zone, OKI Side1 Photo Sketch FkA-1 Slde1 .. Side 2 Photo . ' . , . * ... Page B8-J8 ofB8-180 Appendix: B8 Review Distances (Reference FiguRI7.2.3.1

) L1 & L2 Dist. (ft) 0.5 1 1.5 2 3.5 4 4.5 5 * . .: . .. . .. . -o* ' -4"Pipe Temp. R1 Radius R2 Radius ("F) (in) (in) 1625 4.2 5.5 1374 .3 4.4 1163 2.1 3.4 987 1.3 2.6 839 0.6 2 715 0.1 1.4 610 Contact 0:9 523 0!6 450 02 389 Contact M-663-000I?A

, Revision WOl Penetration Seal Data Appendix: B8 Penetration#:

P121S0268 Penetration Type: RB-5A Loc./Eiev.:

1988'-0" Fire Area (Side 1 ): A-1 M-OX Dwg: M-OX1211 Fire Area (Side 2): A-4 1. Barrier Thickness:

2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 22" 18" D (1) 6"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej)

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab Thickness determined by drawing C-OC1211 Sketch: 10. Annular Gap (smallest)
4" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M-663-000I?A Revision WOl Penetration Seal Data Appendix: 88 Photos: P121S0268 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review: P121S0.268 Fire Area {Side 1} A-1 No Issues within Heat Affected Zone. Fire Area (Side 2) A-4 No issues within Heat Affected Zone. Side 1 Photo Side 2 Photo Sketch Page B8-21 of B8-l80 Appendix: B8 Review Distances &"Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) c*F) (in) (in} 0.5 1659 4.3 5.7 1 1431 3.3 4.6 1.5 1236 2.4 3.8 2 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 0.9 4.5 531 0.6 5 464 0.3 5.5 408 0 6 359 Contact No sketch requir d .

M-663-00017A, Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P121S0273 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OXDwg:

M-OX1211 1. Barrier Thickness

22" 2. Opening Size: 18" D 3. Penetrants
(1) 6"P 4. Sealant Type: HDSE/HDLE

, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Ace/Rei):

N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: FA: A-1 SIOE1 10. Annular Gap (smallest)

5" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M-663-00017A

,Revision WOI Page B8-23 of B -I 0 Penetration Seal Data Appendix: 88 Photos: P121S0273 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • Revision WOI 1 Penetration Seal Data Heat Affected Zone Review: P121S0273 Fire Area {Side 1) No Issues within Heat Affected Zone. Fire Area (Side 2) A-4 No issues within Heat Affected Zone. Side 1 Photo Side2Photo Sketch Appendix: .88 Review Distances &"Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) (OF) (in) (in) 0.5 1659 4.3 5.7 -1 1431 3.3 4.6 1.5 1236 2.4 2 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 0.9 4.5 531 0.6 5 464 0.3 5.5 408 0 6 359 Contact I No sketch requir d .

M-663-00017 A Revision WOl Penetration Seal Data Appendix: B8 Penetration

  1. P121S0274 Penetration Type: RB-SA Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-4 Loc.!Eiev.: 1988'-0" M-OX Dwg: M-OX1211
1. Barrier Thickness
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 22" 18" D (1) 6"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): NIA 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC 1211. Sketch: FA! A-1 SIDE 1 FA: A-4 Scg SIDE2 10. Annular Gap (smallest)
2" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: P121So274 R W Steel M-663-00017A Revision WOI Page B8-26 of 8 -I 0 Penetration Seal Data Appendix: 88 Photos: P121S0274 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) y ' Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

M-663-000J7A

, Revision WOI PageB -27 ofB -180 Penetration Seal Data Appendix: B8 Heat Affected Zone Review: P121S0274 Fire Area (Side 1) A-1 Review Distances (Reference M-S63-00017A

, FIQUTa 7.2.3-1) No issues within Heat Affected Zone. 6" Pipe L 1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1659 4.3 5.7 1 1431 3.3 4.6 Fire Area (Side 2) A-4 1.5 1236 2.4 3.8 2 No Issues within Heat Affected Zone. 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 0.9 4.5 531 0.6 5 464 0.3 Side 1 Photo Side 2 Photo 5.5 408 0 6 359 Contact No photo required.

No photo required. Sketch No sketch required.

M-663-00017A, Revision WOJ Penetration Seal Data Appendix:

B8 Penetration

  1. P121S0275 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness
19" 10. Annular Gap (smallest)
1-1/2" 2. Opening Size: 24" D 11. Gap between pen: N/A 3. Penetrants:

(1) 10"P 12. Barrier Type: F R W 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 13. Opening Sleeved or Concrete:

Steel 5. Damming Side1: Boot 14. Pipe Insulated:

Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

NIA Prepared By: 8. Boot Condition (Acc/Rej)

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Slab thickness determined from drawing C-OC1211. Sketch: FA: A.-1 SIDE.: 1 SIDE: 2 P121S0275 M-663-000 17 A Revision WO I Page 88-29 of 8 -180 Penetration Seal Data Appendix:

88 Photos: P121S0275 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P12150275 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-4 1. 4U1038, 1" Cond.: Not within Heat Affected Zone Side 1 Photo Sketch FA:A-1 Sld*1 ' . .. . . ./j . . Side2 Photo Page B8-30 ofBS-180 Appendix: B8 Review Distances 10* Pipe L1 &L2 Temp. R1 Radius R2Radius Oist. (ft) ("F) (in) (in) 0.5 1697 4.5 5.8 1 1497 3.6 4.9 1.5 1321 2.8 4.1 2 1167 2.1 3,5 2.5 1032 1.5 2.8 3 914 1 2.3 3.5 810 0.5 1.8 4 719 0.1 1.4 4.5 639 Contact u 5 569 0.8 5.5 508 0.5 6 454 0.2 .. 6.5 1406 I 0 7 365 I Contact I UA '7fl'l Vll tv,

' FA:M SkleZ M-663-00017A

, Revision WOI Penetration Seal Data Appendix: B8 Penetration

  1. P121S0279 Penetration Type: RB-SA Loc./Eiev .: 1988' -0" Fire Area (Side 1 ): A-1 M-OX Dwg: M-OX1211 Fire Area (Side 2): A-4 1. Barrier Thickness
22" 2. Opening Size: 20" D 3. Penetrants
4. Sealant Type: 5. Damming Side1: (1) 12"P HDSE/HDLE. Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: 10. Annular Gap (smallest

): 1" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: P121S0279 R W Steel M-663-00017A, Revision WOI Penetration Seal Data Appendix: 88 Photos: P121S0279 Fire Area A-1 (Side 1 ) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)
  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P121S0279 Fire Area (Side 1) A-1 2. 1-112" Stainless Steel Pipe. no issue Fire Area (Side 2) A-4 1. 4U3F5G, 2" Cond., measured not within Heat Affected Zone. Side 1 Photo Sketch fA: A-1 S6de1 t ... Side2Photo Page B8-33 ofBS-180 Appendix: B8 Review Distances (Rdrence M-663o000 17A.

7 .2.)-1 ) 12* Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) rF) (In) (in) 0.5 1712 4.6 15.9 1 1524 3.7 '5.1 1.5 1357 .3 *4.3 2 1209 ; 2.3 3.6 2.5 1078 '1.7 3.1 3 962 1.2 2.5 3,5 860 0.7 2.1 4 769 0.3 1.7 14.5 589 Contact 1.3 IS 618 1 5.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 0 7.5 368 Contact I I M-663-00017A

, R vision WOI Penetration Seal Data Appendix: B8 Penetration

  1. P121S0280 Penetration Type: RB-5A Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 22" 10" D (1) 4"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC 1211. Sketch: 10. Annular Gap (smallest)
3" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M-663-00017A

, Revision WOJ Penetration Seal Data Appendix:

88 Photos: P121S0280 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1 ) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

M-663-00017A Revision WOI Page B -36 of B -I 0 Penetration Seal Data Appendix: 88 Heat Affected Zone Review: P121S0280 Fire Area (Side 1) A-1 Review Distances (Reference M-663-00017A.

Fogure 7 2.3-1 1 No issues within Heat Affected Zone. 4" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (OF) (in) (in) 0.5 1625 4.2 5.5 1 1374 3 4.4 Fire Area (Side 2) A-4 1.5 1163 2.1 3.4 No issues within Heat Affected Zone. 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 1.4 3.5 610 Contact 0.9 4 523 0.6 4.5 450 0.2 5 389 Contact Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch No sketch required.

M-663-00017A

, Revision WOI Page B8-37 of B -I 0 Penetration Seal Data Appendix: B8 Penetration

  1. P121S0281 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1211 1. Barrier Thickness:

22" 10. Annular Gap (smallest)

1" 2. Opening Size: 14" 0 11. Gap between pen: N/A 3. Penetrants
(1) 8"P 12. Barrier Type: F R W 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Slab thickness determined from drawing C-OC1211. Sketch:

M-663-00017 A, Revision WOJ Penetration Seal Data Appendix:

B8 Photos: P121S0281 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1 ) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

  • *
  • Revision WOl Penetration Seal Data Heat Affected Zone Review: P121S0281 Fire Area (Side 1) No issues within Heat Affected Zone Fire Area (Side 2) A-4 1. 4U3F1F, 1-112" Cond.: Within Heat Affected Zone, further review determined that this conduit Is not designated required for PFSSD. Set-route control is necessary

. 2. 4U3F1G, 1-112* Cond.: Not within Heat Affected Zone. 3. 4U3F5G, 2" Cond.: Not within Heat Affected Zone. 4. 4U3F04, 12 Cable Tray: This Cable Tray is PFSSD, but it Is not within Heat Affected Zone. No Set-route control necessary

. Side 1 Photo Side 2Photo Sketch Skftdt FA: A-1 Sldt1 4 ..... ,

  • IIJ , . .. . .... ... .. . , 0. * , Page B8-39 ofB8-180 Appendix: 88 Review Distances (RefwenceM-663-00017A.f"'IIIJIII7.2.3-1) a* Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) (Of) (In) Jin) 0.5 1677 4.4 5.8 1 1463 3.4 4.8 1.5 1277 2.6 3.9 2 1116 1.9 3.2 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 12 4.5 581 0.8 5 512 0.5 5.5 453 0.2 6 402 0 6.5 358 Contact M-663-00017A, Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P121S0283 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX 1211 1. Barrier Thickness:
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 22" 8" D (1) 4"P HDSE/HDLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)
N/A 8. Boot Condition (Acc/Rej)
Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments:

Slab thickness determined from drawing C-OC 1211. Sketch: FA: A-1 SIOE1 10. Annular Gap (smallest):

1-1/2" 11. Gap between pen: N/A 12. Barrier Type: F R W 13. Opening Sleeved or Concrete: Steel 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: P121S02B3 M-663-000I?A, Revision WOI Penetration Seal Data Appendix: B8 Photos: P121S0283 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-4 (Side 2) Fire Area A-4 (Side 2)

M-663-000 17 A. Revision WO 1 Penetration Seal Data

  • Heat Affected Zone Review: P121S0283 Fire Area (Side 1) A-1 No issues within Heat Affected Zone. Fire Area (Side 2) A-4 No issues within Heat Affected Zone. Side 1 Photo Side2Photo
  • Sketch No sketch re
  • Page B8-42 of BS-180 Appendix:

B8 Review Distances F"IQIR 1 .. 2.3*1) 4"Pipe L1 & L2 Temp. R1 Radius R2Radlus Dist. (ft) ("F) (In) (in) 0.5 1625 4.2 5.5 1 1374 3 4.4 1.5 1163 2.1 3.4 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 1.4 3.5 610 Contact 0.9 4 523 0.6 4.5 450 0.2 5 389 Contact

  • M-663-00017A Revision WOJ Penetration Seal Data Penetration
  1. Penetration Type: Loc./Eiev.: 1989'-2 1 1. Barrier Thickness
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: P121W1781 RB-5A 36" 8"0 (1) 6"P HDSE/HDLE Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej):

Accept Appendix:

B8 Fire Area (Side 1): A-1 Fire Area (Side 2): RW-1 M-OX Dwg: M-OX1916 10. Annular Gap (smallest):

1/2" 11. Gap between pen: N/A 12. Barrier Type: F R W 13. Opening Sleeved or Concrete: Steel 14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments: Sketch:

M-663-00017A, Revision WOl Page B8-44 of B -I 0 Penetration Seal Data Appendix: B8 Photos: P121W1781 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area RW-1 (Side 2) Fire Area RW-1 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P121W1781 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) RW-1 No Issues within Heat Affected Zone Side 1 Photo Side2 Photo p 0 Sketch Page B8-4S of B8-180 Appendix: B8 Review Distances

{Reference Figure T.2.l-1) s* Pipe L1 &L2 Temp. R1 Radius R2 Radius DlsL (ft) ("F) (In) (in) 0.5 1659 4.3 5.7 1 1431 3.3 4.6 1.5 1236 2.4 3.8 2 1069 1.7 3 2.5 925 1 2,4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 0.9 4.5 531 0.6 5 464 0.3 5.5 408 0 6 359 Contact o sketch requir d .

M -663-00017 A, Revision WO 1 Penetration Seal Data Penetration

  1. Penetration Type: loc./Eiev.
1993'-6"
1. Barrier Thickness:
2. Opening Size: 3. Penetrants
P121W1782 RB-5A 36" 6"0 (1) 3"P Appendix:

B8 Fire Area (Side 1): A-1 Fire Area (Side 2): RW-1 M-OX Dwg: M-OX1916 10. Annular Gap (smallest)

1" 11. Gap between pen: N/A 12. Barrier Type: F R W 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments: Sketch: I f P121W1782 M-663-00017A, Revision WOl Penetration Seal Data Appendix: B8 Photos: P121W1782 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area RW-1 (Side 2) Fire Area RW-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data

  • Heat Affected Zone Review: P121W1782 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Sjde 2) RW-1 No Issues within Heat Affected Zone Side 1 Photo Side 2 Photo
  • Sketch o sketch r
  • Page 88-48 of B8-l80 Appendix: B8 Review Distances (Refe!lii!081U&J.00011A.

FOn 7.2.3-, ) 3* Pipe L1 & L2 Temp. R1 Radius R2 Radius Dlst._lft)_

rF> . (in) (in) 0.5 1607 14.1 5.4 11 1344 2.9 4.3 1.5 1126 ' 1.9 3.3 2 945 1.1 2.5 2.5 795 0.4 1.8 3 671 Contact 1.2 3.5 568 0.8 4 483 0.4 4.5 412 0.1 5 354 Contact

  • I I M-663-00017A

, Revision WOl Penetration Seal Data Appendix:

B8 Penetration

  1. P122S0327 Penetration Type: RB-5A Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221
1. Barrier Thickness
19" 10. Annular Gap (smallest):

6" 2. Opening Size: 24"0 11. Gap between pen: N/A 3. Penetrants

(1) 10"P 12. Barrier Type: F R W 4. Sealant Type: HDSE/HDLE. Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated: Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): NIA Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Slab thickness determined From drawing C-OC1211. Insulation appears to transition through seal material.

Sketch:

M-663-000 17 A, Revision WO 1 Page B8-50 ofB -l 0 Penetration Seal Data Appendix: 88 Photos: P122S0327 Fire Area A-1 (Side 1} Fire Area A-1 (Side 1) Fire Area A-2 (Side 2} Fire Area A-2 (Side 2}

M-663-00017A, Revision WOl

  • Penetration Seal Data Heat Affected Zone Review: P122S0327 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 1-1/2" Cond. 4J1080, not within Heat Affected Zone 2. 1-1/2" Cond. 1 UJ1071, not within Heal Affected Zone 3. 1*1/2" Cond. 1U1048, not within Heat Affected Zone Side 1 Photo Side2 Photo
  • Sketch
  • Page B8-51 of 88-180 Appendix: B8 Review Distances (l'!.eferanc.IMifl3.00017 A. F'lll'ft T .U.1 )

L1 & L2 Temp. R1 Radius R2Radius Dist.j_ft)

_rn_ _11n). (in) 0.5 1697 4.5 5,8 1 1497 .J.6 4.9 1.5 1321 2.8 4.1 .2 1167 2.1 3.5 2.5 1:032 1.5 2.8 3 914 1 2..3 3.5 810 0.5 LB 4 719 0.1 1.4 --4.5 639 Cootacl 1.1 s 569 I 0.8 5.5 508 0.5 js 454 0.2 ' 65 406 0 -7 365 Contact M-663-00017A

, Revision WOI Page 88-52 of B -I 0 Penetration Seal Data Appendix:

B8 Penetration

  1. P122S0331 Penetration Type: RB-5A Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-2 Loc./Eiev

.: 1988'-0" M-OX Dwg: M-OX1221

1. Barrier Thickness
19" 2. Opening Size: 10"0 3. Penetrants:

(1) 3"P 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: FA: A-1 SIDE 1 FA: A-2 SIDE2 10. Annular Gap (smallest)

3" 11. Gap between pen: N/ A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: P122SOl31 R W Steel M -663-00017 A, Revision WO I Page 88-53 of 8 -I 0 Penetration Seal Data Appendix: 88 Photos: P12250331 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1 ) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)
  • *
  • Revision WOl Penetration Seal Data Heat Affected Zone Review: P122S0331 Fire Area (Side 1) A-1 . No issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 1J1037, 1/2" Cond.: Not within Heat Affected Zone. 2. 1 B2E02, 6" Cable Tray: Not within Heat Affected Zone Side 1 Photo Side2Photo Sketch FA: A-1 Page 88-54 ofB8-180 Appendix: B8 Review Distances 7.2.3-1) L1 & L2 i Dist. (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 3* Pipe Temp. R1 Radius COf) (in) -_1607 . 4.1 1344 2.9 1126 1.9 945 1.1 795 0.4 671 Contact 568 483 412 I -I 354 FA: A-a Slde2 R2 Radius (In) 5.4 4.3 3.3 2.5 1.8 1.2 0.8 1oA *0.1 C{)nlact M-663-000 17 A Revision WO I Penetration Seal Data Appendix: B8 Penetration#:

P122S0338 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221

1. Barrier Thickness
19" 2. Opening Size: 8"0 3. Penetrants
(1) 4"P 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC 1211. Sketch: FA: A-1 Slde1 P122S0338

10. Annular Gap (smallest)
1-1/2" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: FA: A-2 Side 2 R W Steel M-663-000 17 A, Revision WO I Penetration Seal Data Appendix: B8 Photos: P122S0338 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)
  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P12250338 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-2 1 Cond, Fire Protection Detection

, not within Heat Affected Zone Side 1 Photo Sketch FA: A-1 SkJe1 I ' Side2 Photo uired

  • NO ....

.,. * *

  • lb 4 .. b * ..,o.v, -Page 88-57 of 88-180 Appendix: B8 Review Distances 4* Pipe L1&L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 1625 4.2 1374 3 1163 2.1 987 1.3 839 0.6 715 0.1 610 COntact 523 450 389 .-T" --+ T I + *
  • FA: A.Z std*2 (In) 5.5 4.4 3.4 2.6 2 1.4 0.9 0.6 0.2 Contact M -663-00017 A, Revision WO 1 Page B8-58 of B -I 0 Penetration Seal Data Appendix: B8 Penetration
  1. P122S0339 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221 1. Barrier Thickness
19" 10. Annular Gap (smallest)
5" 2. Opening Size: 30"0 11. Gap between pen: N/A 3. Penetrants
(1) 14"P 12. Barrier Type: F R W 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

NIA Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Slab thickness determined from drawing C-OC1211. Sketch:

M-663-00017A Revision WOI Page B8-59 of B -I 0 Penetration Seal Data Appendix: B8 Photos: P122S0339 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)

  • *
  • M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review: P122S0339 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-2 No Issues within Heat Affected Zone Side 1 Photo Side2Photo oto Sketch Page B8-60 of B8-180 Appendix: B8 Review Distances (Refe!ente fl!l" 7.2.3-1 ) 14"Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (In) (in) 0.5 1721 4!6 5.9 1 1539 3.8 5.1 I 1377 l3 4.4 1233 2.4 3.8 2.5 ' 1105 1.8 3.2 '3 991 1.3 2.7 3.5 889 0.9 2.2 4 799 0.4 1.8 4.5 719 0.1 1.4 5 647 Contact 1.1 5.5 583 0.8 6 527 0.6 6.5 477 0.3 7 432 0.1 7.5 392 Contact No sketch requir
  • M-663-00017A Revision WOI Page 88-61 of 8 -180 Penetration Seal Data Appendix: B8 Penetration
  1. P122S0340 Penetration Type: RB-5A Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221 1. Barrier Thickness
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 19" 22"0 (1) 14"P HDSE/HDLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Ace/Rei): NJA 8. Boot Condition (Acc/Rej)
Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: 10. Annular Gap (smallest):

2" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: 24' P122$0340 R W Steel M-663-00017A

, Revision WOl Penetration Seal Data Appendix: B8 Photos: P122S0340 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)

  • *
  • M-663.00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P122S0340 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 1-1/2" Cond 1 U3C1 K. not within Heat Affected Zone Side 1 Photo Sketch requi PA:A-1 Slde1 Side2Photo . . . Page B8-63 of B8-180 Appendix: B8 Review Distances T .2.3-1 ) 14* Pipe L1 & L2 Temp. R1 Radius R2 Radius Disl (ft) rF) (In) (in) 0.5 1721 4.6 5.9 1 1539 3.8 5.1 1.5 13n 3 4.4 2 1233 2.4 3.8 2.5 1105 1.8 3.2 3 991 1.3 2.7 3.5 889 0.9 2.2 4 799 0.4 1.8 4.5 0.1 1.4 5 I 647 Contact 1.1 5.5 583 0.8 6 527 0.6 6.5 477 0.3 7 432 0.1 7.5 392 Contact I I I 1 M-663-00017A

, Revision WOI Penetration Seal Data Appendix: B8 Penetration

  1. P122S0349 Penetration Type: RB-5A Loc./Eiev

.: 1988'-0" Fire Area (Side 1): A-1 M-OX Dwg: M-OX1221 Fire Area (Side 2): A-2 1. Barrier Thickness

2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 19" 20"0 (1) 12"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: 10. Annular Gap (smallest)

3" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M-663-00017A

, Revision WOI Penetration Seal Data Appendix: 88 Photos: P122S0349 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)

  • *
  • Revision WOI Penetration Seal Data Heat Affected Zone Review: P122S0349 Fire Area (Side 1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 1 U3C07, 12* Cable Tray: Portions of the Cable Tray Is within the Heat Affected Zona, further raview determined that this Cable Tray is Not PFSSD. Set-route control Is necessary
2. 1U3C1 R. 2" Cond.: Not within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page B8-66 ofB8-180 Appendix: IB8 Review Distances (Raferenc:a M-fi63.00017A.

FlglQ 7.2.3-1) 12-Pipe L1 & L2 Temp. R1 Radius R2 Radius Disljftl_

m li'!l (in) 0.5 1712 4.6 5.9 1 1524 3.7 5.1 1.5 1357 3 4.3 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 61'8 I 1 5.5 555 0.7 6 499 I 0.4 6.5 450 0.2 7 406 0 7.5 368 Contact M-663-00017A

, Revision WOl Penetration Seal Data Appendix:

B8 Penetration

  1. P12250350 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221 1. Barrier Thickness
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 19" 12"0 (1)4"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Ace/Rei): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC1211. Sketch: FA: A-1 Sldt1 ' 11 ,.. Q-M.C I I) . I p. . . 10. Annular Gap (smallest): 2-1/2" 11. Gap between pen: N/ A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: FA; A-2 Side 2 R W Steel M-663-00017A

, Revision WOI Penetration Seal Data Appendix: B8 Photos: P12250350 Fire Area A-1 (Side 1} Fire Area A-1 (Side 1 ) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2}

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P122S0350 Fire Area (Side1) A-1 No issues within Heat Affected Zone Fire Area (Side 2) A-2 No issues within Heal Affected Zone Side 1 Photo Side2 Photo Sketch Page 88-69 of B8-1 80 Appendix: :88 Review Distances (Ra!Mnoe 1.4-fl63.00017A.

FlgLI'II L1 & L2 Temp. R1 Radius R2 Radius Dist. (ftl _rn_

(In) 0.5 1625 4.2 5.5 1 1374 3 4.4 1.5 1163 2.1 3.4 2 987 1.3 2.6 2.5 839 0.6 2 -3 715 0.1 1.4 3.5 1610 1 Contact 0.9 4 1523 0.6 4.5 450 0.2 5 389 Contact No sketch requir M-663-00017A

, Revision WOJ Page88-70ofB

-1 0 Penetration Seal Data Appendix: 88 Penetration

  1. P122S0351 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221
1. Barrier Thickness
19" 10. Annular Gap (smallest)
4" 2. Opening Size: 12"0 11. Gap between pen: N/A 3. Penetrants:

(1) 4"P 12. Barrier Type: F R W 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej)
NIA Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Slab thickness determined from drawing C-OC1211. Sketch:

M -663-00017 A Revision WO I Penetration Seal Data Appendix: B8 Photos: P122S0351 Fire Area A-1 (Side 1 ) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2}

M-663-000 17 A, Revision WO 1 Penetration Seal Data Heat Affected Zone Review: Fire Area (Side 1) No Issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 1U3C1C. 1-112" Cond .. Not within Heat Affected Zone 2. 1U3C10. 1*112" Cones Not wilhill Heal Affected Zone 3. 1U3C1P. 1*112" Cond .. Not Mlh*n Heal Affected Zona 4 1U3C1N. 1*112" Cond Not within Heal Affected Zone P122S0351 Side 1 Photo Side 2 Photo Sketch FA:A-1 llde1

  • 0 * * * * *
  • Page 88-72 ofBS-180 Appendix:

88 Review Distances IU63-00017A.

..... 1.2 ' 4* Pipe L1 & L2 Temp. R1 R.dlus R2 Radius Dial (ft) ("F) (In) (In) 0.5 1625 4.2 5.5 1 1374 3 4.4 1.5 1163 2.1 3.4 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 1.4 3.5 610 Coolact 0.9 4 523 0.6 4.5 450 0.2 5 389 Contact M-663-000I7A

, Revision WOl Page 88-73 ofB -1 0 Penetration Seal Data Appendix:

88 Penetration

  1. P122S0357 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221 1. Barrier Thickness
2. Opening Size: 3. Penetrants: 4. Sealant Type: 5. Damming Side1: 19" 16"D (1) 8"P HDSE/HDLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): NIA 8. Boot Condition (Acc/Rej)
Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC 1211. Sketch: 10. Annular Gap (smallest)
1" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M -663-00017 A, Revision WO I Penetration Seal Data Appendix: 88 Photos: P122S0357 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)
  • *
  • M-663-0001 7A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P122S0357 Fire Area (Side 1) No issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 112" Detection Cond., not an issue or within HAZ Side 1 Photo Side2 Photo Sketch Page BS-75 ofB8-180 Appendix: B8 Review Distances F'ogu'8 7.:U.1 )

L1 & L2 Temp. R1 Radius R2 Radius Dis tift) ("F) (in) (in} 0.5 167.7 4.4 5.8 1 1463 3.4 4.8 1.5 12n 2.6 3.9 2 1116 1.9 '3.2 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 0.5 js.s 453 0.2 6 402 0 6.5 358 Contact No sketch requir d .

M-663-000 17 A, Revision WO I Penetration Seal Data Appendix: 88 Penetration

  1. P122S0367 Penetration Type: RB-SA Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221
1. Barrier Thickness
25" 2. Opening Size: 16"0 3. Penetrants
(1) a**p 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined from drawing C-OC 1211. Sketch: FA: A-1 SIDE 1 FA: A-2-SIDE2 10. Annular Gap (smallest)

2" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: R W Steel M -663-00017 A Revision WO I Penetration Seal Data Appendix: 88 Photos: P122S0367 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)

M-663-00017A, Revision WOl Page B -7 of B -1 0 Penetration Seal Data Appendix: 88 Heat Affected Zone Review: P122S0367 Fire Area (Side 1) A-1 Review Distances (ReferenC<! M-663-00017A

. F19ure 7 2.3-1 ) No issues within Heat Affected Zone 8" Pipe l1 & l2 Temp. R1 Radius R2 Radius Dist. (ft) (oF) (in) (in) 0.5 1677 4.4 5.8 1 1463 3.4 4.8 Fire Area (Side 2) A-2 1.5 1277 2.6 3.9 No issues within Heat Affected Zone 2 1116 1.9 3.2 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 0.5 Side 1 Photo Side 2 Photo 5.5 453 0.2 6 402 0 6.5 358 Contact No photo required. No photo required. Sketch No sketch requ1red.

M-663-000 17 A Revision WO 1 Page 88-79 of B -1 0 Penetration Seal Data Appendix: B8 Penetration

  1. P122S0373 Penetration Type: RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-2 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1221 1. Barrier Thickness
2. Opening Size: 3. Penetrants
19" 10"0 (1) 4"P 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

NIA 8. Boot Condition (Acc/Rej)

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments:

Slab thickness determined from drawing C-OC1211. Sketch: FA: A-1 Side1 P122S0373 b * ---10. Annular Gap (smallest)

2" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete:
14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: * *
  • I> . ' FA:A-2 Side2 R W Steel M-663-00017 A Revision WOl Penetration Seal Data Appendix: 88 Photos: P122S0373 Fire Area A-1 (Side 1) Fire Area A-1 (Side 1) Fire Area A-2 (Side 2) Fire Area A-2 (Side 2)
  • *
  • M-663-00017A.

Revision WOl Penetration Seal Data Heat Affected Zone Review: P12250373 Fire Area (Side 1) A-1 : No issues within Heat Affected Zone Fire Area (Side 2) A-2 1. 1J1037, 1/2" Cones.: No issues within Heat Affected Zone 2. 1U1363, 1* Cond.: No issues within Heat Affected Zone 3. 1U1318, 112" Cond.: No issues within Heat Affected Zone ** 1J1039, 112" Cond.: No Issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page B8..SI ofB8-180 AppendiJt: B8 Review Distances 4" Pipe L1 & L2 Temp. R1 Radius R2Radlua Oist. (ft) ("F) (in) (In) 0.5 1625 4.2 5.5 1 1374 3 4_4 1.5 1163 2.1 3.4 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 I 1.4 3.5 610 *Contact 0.9 4 523 0.6 4.5 450 0.2 5 389 Contact M-663-000I?A

, Revision WOl Penetration Seal Data Appendix:

B8 Penetration

  1. P131S0513 Penetration Type: RB-SA Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc.fEiev.
2000'-0" M-OX Dwg: M-1X1311 1. Barrier Thickness
20" 10. Annular Gap (smallest)
2 2. Opening Size: 1 O"D 11. Gap between pen: N/A 3. Penetrants
(1) 3"P 12. Barrier Type: F 4. Sealant Type: HOSE/HOLE

, Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: 21" ** Reviewed By: Walkdown Comments: Slab thickness based on C-1 C 1311. ** Sealant Depth determined from inspection report. Sketch: FA: Ml Side1 P131S0513 4 ("Nf') b (ru) -.. *' _ .. ,r::J, t> * .. ... \ .. FA: A-1 Side2 R Steel M-663-00017A

, Revision WOl Penetration Seal Data Appendix:

B8 Photos: P131 50513 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-000J?A, Revision WOJ Penetration Seal Data Heat Affected Zone Review: P131S0513 Fire Area (Side 1) A-8 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page 88*84 of 88-180 Appendix: 88 Review Distances (Ral!llencl M-663-00017A.

Fog&n 7.2.3-1) 3" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1607 4.1 5.4 1 1344 2.9 4.3 1.5 1126 i 1.9 3.3 2 945 11.1 2.5 2.5 795 0.4 1.8 I 671 Contact 1.2 568 0.8 4 483 0.4 -4.5 412 0.1 5 354 Contact No sketch requir d .

M-663-000I?A Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P131S0522 Penetration Type: RB-5A Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc.!Eiev.
2000'-0" M-OX Dwg: M-1X1311 1. Barrier Thickness
2. Opening Size: 3. Penetrants:
4. Sealant Type: 5. Damming Side1: 20" 10"0 (1) 3"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej}: Accept 9. Sealant Depth: 20' ... Walkdown Comments: 10. Annular Gap (smallest)
3" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: Slab thickness based on C-1 C 1311 ... Sealant depth determined by inspection report. Sketch: FA: A-8 Slde1 P131S0522
t>': .-,*o*. *
  • t>
  • f * ... * ' tl' -* , *** f , , *. v-. II .. . . .. 0 .-*** t -: .. * () *.. ,. '()I *** *_C.' .. # * # .. .. .---(r*tr) P.' . -p-; I l?: , ...... P .. ..., .._I>. D ': _:. :-. ,,. . a Q .-*** eo-:. -. r G . B-Wb (m) FA: A-1 Slde2 R Steel M-663-00017A, Revision WOl Penetration Seal Data Appendix: 88 Photos: P13150522 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P13150522 Fire Area (Side 1) A-8 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No Issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page B8-87 ofB8-1'80 Appendix: B8 Review Distances 1

L1 & L2 Temp. R1 Radius R2Radlus rF> _{inl (in) 0,5 1607 4,1 5.4 11 1344 2.9 4.3 1.5 1126 1.9 3.3 I 2 945 1.1 2.5 2.5 795 0,4 1.8 3 671 Contact 1.2 3.5 568 0.8 .. 4 483 0.4 4.5 412 0.1 5 354 Contact No sketch requir

  • M-663-00017A

, Revision WOI Penetration Seal Data Appendix:

88 Penetration

  1. Penetration Type: Loc./Eiev.: 2000'-0"
1. Barrier Thickness
2. Opening Size: 3. Penetrants:

P131S0525 RB-5A 20" 10"0 (1) 3"P Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 M-OX Dwg: M-1X1311

10. Annular Gap (smallest)
3" 11. Gap between pen: N/A 12. Barrier Type: F 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 14. Pipe Insulated
No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej)
Accept Jeff Suter 9. Sealant Depth: 22-1/2" .. Reviewed By: Walkdown Comments:

Slab thickness based on C-1 C 1311. ** Sealant depth determined by inspection report. Sketch: FA: Slde1 P131S0525

  • i>** *1>-. \ ., 0 : .
  • I) . * * *
  • 0 . b* * .. y . . '-II I -I *
  • P. '. 9 f>>: FA: A-1 S de2 R Steel M-663-00017A Revi ion WOI Penetration Seal Data Appendix: 88 Photos: P131S0525 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-000J7A. Revision WOl Penetration Seal Data Heat Affected Zone Review: P131S0525 Fire Area (Side 1) A-8 No issues within Heat Affected Zone I Fire Area (Side 2) A-1 No Issues within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page BS-90 ofB8-180 Appendix: B8 Review Distances 3* Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (Of) (in) (in) 0.5 1607 4.1 5.4 u 1344 2.9 4.3 1.5 1126 1-9 3.3 2 945 1.1 2.5 2.5 795 0.4 1.8 3 671 Contact 1.2 3.5 568 0.8 4 483 0.4 4.5 412 Q_1 5 354 Contact I No sketch requir
  • M-663-00017A, Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. Penetration Type: Loc./Eiev.: 2000'-0" 1. Barrier Thickness
2. Opening Size: 3. Penetrants
P131S0526 RB-SA 20" 18"0 (1) 10"P Fire Area (Side 1): A-9 Fire Area (Side 2): A-1 M-OXDwg: M-1X1311
10. Annular Gap (smallest)
1" 11. Gap between pen: N/A 12. Barrier Type: F 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 14. Pipe Insulated: Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej)
Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments: R Steel Slab thickness based on C-1 C1311. Insulation appears to go through the sealant from the bottom side. However, the top side insulation terminates just above the boot. Therefore

, the insulation will be assumed not to go through the seal. Sketch: FA:A-9 Sldo1 P131S052ti

  • J .. ' /) t:> I . ' ., F
  • A-1 Sldo2 M -663-00017 A, Revision WO 1 Penetration Seal Data Appendix:

88 Photos: P13150526 Fire Area A-9 (Side 1) Fire Area A-9 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review: P131S0526 Fire Area (Side 1) A-9 No issues within Heat Affected Zone I Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page B8-93 of 88-180 Appendix: B8 Review Distances (ReletM<:e M-663-0001 71>., fQin 7.2.3-1 ) 10" Pipe L1 & L2 Temp. R1 Radius R2Radius Dist. (ft) ("F) (In) 1in) 0.5 1697 4.5 5,8 1 1497 3.6 4.9 1.5 1321 2.8 4.1 2 1167 2.1 3.5 2.5 1032 1.5 2.8 3 914 1 2.3 3.5 I 810 0.5 1.8 4 719 0.1 1.4 4.5 639 Contact 1.1 5 569 0.8 5.5 508 0.5 6 454 0.2 6.5 406 0 7 365 Contact No sketch requir d .

M-663-000 17 A Revision WO I Penetration Seal Data Appendix; 88 Penetration

  1. P131S0529 Penetration Type: RB-SA Fire Area (Side 1 ): A-9 Fire Area (Side 2); A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1311 1. Barrier Thickness
20" 10. Annular Gap (smallest)
3" 2. Opening Size; 24"0 11. Gap between pen: N/A 3. Penetrants
(1) 10"P 12. Barrier Type: F 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete; 5. Damming Side1: Boot 14. Pipe Insulated: Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth; 20-1/2"** Reviewed By; Walkdown Comments: Slab thickness based on C-1 C 1311. ** Sealant depth determined by inspection report. Sketch: FA: A-9 Skte1 P131S0529

-.,. , . . -' p . tJ ** .. . * ... 0 . I>' . Q . . ,..

(l1f'l 'I> ..* I>J ... (:> II Q ' \ .

  • I) I .. F
  • A-1 Slde2 R Steel M-663-00017A, Revision WOI Penetration Seal Data Appendix: B8 Photos: P13150529 Fire Area A-9 (Side 1) Fire Area A-9 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-000 17 A, Revision WO 1 Penetration Seal Data Heat Affected Zone Review: P13150529 Fire Area (Side 1) A*9 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page 88-96 of 88-I 80 Appendix: B8 Review Distances (Reference f"tQift 7.2.3--1

) 10" Pipe l1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1697 4.5 5.8 1 I 1497 3.6 4.9 1.5 11321 2.8 4.1 2 1167 2.1 3.5 2.5 1032 1.5 2.8 3 914 1 1 2.3 3.5 810 0.5 11.8 4 719 0.1 1.4 4.5 639 Con tad 1 1.1 5 569 0.8 5.5 508 0.5 6 454 i0.2 6.5 406 0 7 365 Contact No sketch requir d .

M-663-00017A Revision WOl Penetration Seal Data Penetration

  1. Penetration Type: Loc./Eiev.: 2000'-0" 1. Barrier Thickness
2. Opening Size: 3. Penetrants
P131S0530 RB-5A 20" 24"0 (1) 10 .. P Appendix:

88 Fire Area (Side 1): A-9 Fire Area (Side 2): A-1 M-OXDwg: M-1X1311 10. Annular Gap (smallest): 6" 11. Gap between pen: N/ A 12. Barrier Type: F R 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated: *Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth: 23" ** Reviewed By: Walkdown Comments: Slab thickness based on C-1 C1311. *From the bottom side examination, it appears that the insulation transitions through the seal area ... Sealant depth determined by inspection report. Sketch: FA: A*9 Slcte1 P131S0530

,---.........

,._ ... -,

I -1 eooT (TiP) p .... b 1 v* ' 'ol*c..' FA; A*1 Sid 2 M-663-00017A, Revision WOI Penetration Seal Data Appendix: B8 Photos: P131S0530 Fire Area A-9 (Side 1) Fire Area A-9 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P131S0530 Fire Area (Side 1) A-9 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page BS-99 of BS-180 Appendix: B8 Review'Distances (Ralernla M-683.ooo17 A filin 7.2.3-1 l 10" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F} {in) (In} 0.5 '1697 4.5 5.8 1 t497 3.6 4.9 L5 1321 2.8 4.1 2 1167 2.1 .3.5 2.5 W32 1.5 2.8 3 914 1 12.3 3.5 810 0.5 11.8 4 719 0.1 11.4 4.5 639 Contact u 5 569 0.8 5.5 508 i 0.5 ' 6 454 {).2 6.5 406 -o 7 365 Contact No sketch requir l M-663-00017A

, Revision WOJ Page 88-100 ofB -I 0 Penetration Seal Data Appendix:

B8 Penetration

  1. P131S0531 Penetration Type: RB-SA Fire Area (Side 1): A-9 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1311 1. Barrier Thickness
20" 10. Annular Gap (smallest):

1" estimated

2. Opening Size: 16"0 11. Gap between pen: N/A 3. Penetrants:

{1) 8"P 12. Barrier Type: F R 4. Sealant Type: HOSE/HOLE.

Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

  • Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): NIA Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth: 22-1/2" ** Reviewed By: Walkdown Comments:

Slab thickness based on C-1 C1311.

  • It appears that the insulation transitions through the seal area. Appears to have an FB-6 on top side. Can not absolutely verify due to contaminated area. ** Sealant depth determined by inspectio n report. Sketch: FA: A*9 Side 1 P131S0531

.

  • If> FA: A*1 Side2

-663-000 17 A, Revision WO 1 Penetration Seal Data Appendix:

88 Photos: P131 50531 Fire Area A-9 (Side 1) Fire Area A-9 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-000 17 A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P131S0531 Fire Area (Side 1) A-9 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone 1 Side 1 Photo Side2 Photo Sketch Page B8-I 02 of B8-180 Appendix: 88 Review Distances Figure 7.2.3-1) -s-Pipe L1 & L2 Temp. R1 Radius R2Radius Dist. (ft) (OF) (in) (in) 0.5 1677 4.4 5.6 1 1463 3.4 4.8 Q.5 1277 2.6 3.9 2 1116 1.9 3.2 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 I 0.5 5.5 453 0.2 6 402 0 6.5 I 358 Contaol I No sketch required

.

M-663-00017A Revision WOl Penetration Seal Data Appendix:

B8 Penetration#:

P132S0697 Penetration Type: RB-5A Fire Area (Side 1 ): A-1 0 Fire Area (Side 2): A-1 Loc./Eiev.

2000'-0" M-OX Dwg: M-1X1321 1. Barrier Thickness
2. Opening Size: 3. Penetrants
20" 18"0 (1) 8"P 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness based on C-1 C1311. Sketch: FA: A-10 Slde1 .... (N!') '0. * : .:? ** I

  • t\ -..
  • y*<::J \ b* .._. I * : /} t * ., I I b. * ' P132S0697
10. Annular Gap (smallest):

4" 11. Gapbetweenpen

N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: *o: , . . .... P. iJ ,' o' . . , *'
  • D.*" " I> . , FA: A-1 Slde2 R Steel M-663-00017A Revision WOI Page 88-104 ofB -I 0 Penetration Seal Data Appendix: B8 Photos: P132S0697 Fire Area A-1 0 (Side 1) Fire Area A-1 0 (Side 1 ) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review: P132S0697 Fire Area (Side 1) A-10 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page BS-105 ofBS-180 Appendix: B8 Review 'Distances (Rerelroct f\4.663.00017A.

Fig.Jnt 7 l a* Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (In) (in) 0.5 1677 14.4 '5.8 j1 1463 3.4 4.8 1.5 1277 2.6 3.9 2 1116 1.9 3.2 2.'5 976 1,2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 0.5 5.5 453 0.2 6 402 0 6.5 358 Contact No sketch requir

  • M-663-00017A

, Revision WOI Penetration Seal Data Appendix:

88 Penetration

  1. P132S0698 Penetration Type: RB-5A Fire Area (Side 1): A-10 Fire Area (Side 2): A-1 Loc./Eiev

.: 2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness
20" 10. Annular Gap (smallest)
1" 2. Opening Size: 18"0 11. Gap between pen: N/A 3. Penetrants
(1) WP 12. Barrier Type: F R 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: 21-1/2" ** Reviewed By: Walkdown Comments: Slab thickness based on C-1 C 1311. Due to the offset that is present on the bottom side, it is not likely the insulation transition through the seal. However the pipe is insulated on both sides of the seal. Sealant depth determined by inspection report. Sketch: FA: A-10 Side1 P132S0698

  • L>. * '*
  • f/ I . t>. /) C> . . . IHSUt.II/ICN

{rrr) . -* I ' 0 *e;;,-. . . ... ... * <>

  • b' .. ,. ..... FA: A-1 Side 2.

M-663-00017A, Revision WOl Page 88-107 of 88-I 0 Penetration Seal Data Appendix: 88 Photos: P132S0698 Fire Area A-1 0 (Side 1 ) Fire Area A-1 0 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A,Revi ion WOI Penetration Seal Data Heat Affected Zone Review: P13250698 Fire Area (Side 1) A-10 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page B8-l 08 of B8-180 Appendix: 88 Review Distances 10" Pipe L1 & L2 Temp. R1 Radius R2 Radius Disl(ft}

{-.=) jlnj_ (In) 0.5 1697 4.5 5.8 1 1497 3.6 4.9 1.5 1321 2.8 4.1 2 1167 2.1 3.5 2.5 1032 1.5 2.8 3 914 1 2.3 3.5 810 0.5 1.8 4 719 0.1 1.4 4.5 639 Contact 1.1 5 569 0.8 5.5 508 0.5 6 454 0.2 6.5 406 0 7 365 Contact No sketch required

.

M-663-000I?A

, Revision WOJ Page B -109 ofB8-180 Penetration Seal Data Appendix:

B8 Penetration

  1. P132S0699 Penetration Type: RB-SA Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc.IElev.:

2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness
26" 10. Annular Gap (smallest):

1/2" 2. Opening Size: 8"0 11. Gap between pen: 1/4" 3. Penetrants

(1) 3"P, (1) 3/4"P 12. Barrier Type: F R 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)
N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness based on C-1C1311. Sketch: FA: A-8 Slde1 R1\l.rfCb

('!"'(')

P132S0699 SfC..t\0 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By:

'l TOMT\Id ' ... ' . -. . FA: A-1 Sldo 2 M-663-00017A Revision WOI Penetration Seal Data Appendix: B8 Photos: P132S0699 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1 ) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: Fire Area (Side 1) A-8 1. 1-112" System Drain Pipe, No issues Fire Area (Side 2) No issues within Heat Affected Zone Side 1 Photo Sketch FA: A-1 81de1 P132S0699 Side2 Photo Page 88-111 of 88-180 Appendix: B8 Review Distances L1 &L2 Dist. (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 s 3R Pipe Temp. R1 Radius lin) 1607 4:1 1344 2.9 1126 1.9 945 1.1 795 0.4 671 'Contact 568 483 ' 412 354 FA:A-1 sade2 R2 Radius (in) 5.4 4.3 3.3 2.5 I *1.8 1.2 0.8 <0.4 0.1 Contact M-663-00017A,Revision WOI Penetration Seal Data Appendix: B8 Penetration
  1. Penetration Type: Loc./Elev.
2000'-0"
1. Barrier Thickness
2. Opening Size: 3. Penetrants
P132S0700 RB-5A 26" 8"0 (1) 3"P, (1) 3/4"P Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 M-OX Dwg: M-1X1321 10. Annular Gap (smallest)
1/4" 11. Gap between pen: 1/2" 12. Barrier Type: F 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 6. Damming Side 2: boot 7. Damming Continuity (Acc/Rej):

NIA 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments:

Slab thickness based on C-1 C1311. Sketch: FA: ,__, Sld4t 1 P132S0700

14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: .. : t:: *1>'*-* t **

  • "' '!::>' : 6; A : , *.'
  • FA:A-1 Slde 2 R Steel M-663-00017A Revision WOJ Penetration Seal Data Appendix:

B8 Photos: P132S0700 Fire Area A-8 (Side 1) Fire Area A-8 {Side 1) Fire Area A-1 {Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: Fire Area (Side 1) A-8 1. 1-1/2" System Drain Pipe, No issue Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Sketch FA: A-1 Side 1 P13250700 Side 2 Photo Page B8-ll4 ofBS-180 Appendix: B8 Review Distances (R1111111nce M-663-00017.A.

Flgule 7.2.3-1 ) L1&L2 Dist. (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 3* Pipe Temp. R1 Radius ("F) (in) 1607 4.1 1344 2.9 1126 ,1.9 945 1.1 795 0.4 671 Contact 568 483 412 354 FA:A-1 Side2 R2 Radius (in) 5.4 14.3 i 3.3 2.5 1.8 1.2 0.8 0.4 0.1 Contact M-663-00017A Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P132S0704 Penetration Type: RB-SA Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321
1. Barrier Thickness:
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 20" 10"0 (1) 6P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej):

N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness based on C-1 C1311. Top side in VCT Room Sketch: FA: A.S Slda 1 P132S0704

  • r:J, 10. Annular Gap (smallest)
1/4" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: 'n. I ... * />' . PI -f!l. {) ** u'. . , d. -. v *.l.f> FA:A-1 Sde2 R Steel M-663-00017A, Revision WOJ Penetration Seal Data Appendix: B8 Photos: P13250704 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A.

Revision WOl Penetration Seal Data Heat Affected Zone Review: P132S0704 Fire Area (Side 1) A-8 No Issues within Heat Affected Zone Fire Area {Side 2) A-1 No Issues within Heat Affected Zone Side 1 Photo Side2Photo Uifi Sketch Page 88-117 of88-l80 Appendix: 88 Review Distances (Rat..,.,.

FoguM7.2.

3-1 I s* Pipe L1 & L2 Temp. R1 Radius R2 Radius Dlst. (ft) ("F) (in) (in) 0.5 1659 4.3 5.7 1 11431 3.3 4.6 1.5 1236 2.4 3.8 2 ' 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 I 0.9 4.5 531 I 0.6 5 464 I 0.3 5.5 408 0 6 359 Contact No sketch required

.

M-663-000I?A

, Revision WOJ Penetration Seal Data Appendix:

B8 Penetration

  1. P132S0710 Penetration Type: RB-SA Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.
2000'-0" M-OX Dwg: M-1X1321
1. Barrier Thickness:

26" 8"0 10. Annular Gap (smallest)

1-1/4" 2. Opening Size: 3. Penetrants:

(1) 3"P 4. Sealant Type: HOSE/HOLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)

NIA 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments:

Slab thickness based on C-1 C 1311. Sketch: FA: A-8 Slde 1 "P_. -: ij .** . : -'d\ ............. * ...

  • J *
  • t> ..... * .a * -'?' . ... ,. ...,.. . .. c:1. . ' . . . 11. Gap between pen: N/A 12. BarrierType
F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: Yes Wayne Aregood Prepared By: Jeff Suter Reviewed By: I
  • p ,.., .o . <1 . ("t'i ) P132S0710 FA: A-1 Sdt2 R Steel M-663-000I7A,Revision WOI Penetration Seal Data Appendix: 88 Photos: P13250710 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P132S0710 Fire Area (Side 1) A-8 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Slde2 Photo Sketch Page 88-120 ofB8-180 Appendix: 88 Review Distances (Relenlooa M-66J.00017A.

F9" 7.2.3-11 3R Pipe L1&L2 Temp. R1 Radius R2Radius Dist. (ft) ("F) (in) fin) 0.5 1607 4.1 ISA 1 '1344 2.9 4.3 1.5 1126 1.9 3.3 2 945 1.1 2.5 2.5 795 0.4 1.8 3 671 Contact 1.2 13.5 *568 0.8 4 483 0.4 4.5 412 5 354 Contact No sketch required

.

M-663-00017A

, Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P132S0713 Penetration Type: RB-5A Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321 1. Barrier Thickness
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 26" 10"0 {1) 3"P HDSE/HDLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: 28" ** Walkdown Comments: 10. Annular Gap (smallest)
3" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: Slab thickness based on C-1 C 1311 ... Sealant depth determined from inspection report. Sketch: FA: A-8 Side 1 P132S0713

,' I; ,I '.*

  • p **
  • r I I 'D . * ' 1> ** ¢ I * * .* "t;:J" *
  • 0 * . '()* -* . . FA:A-1 Side 2 R Steel M-663-00017A, Revision WOI Page 88-122 ofB -I 0 Penetration Seal Data Appendix: B8 Photos: P132S0713 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P132S0713 Fire Area (Side 1) A-8 No issues within Heat Affected Zone Fire Anta (Side 2) No issues within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page B8-I 23 of 88-I 80 Appendix: 88 Review Distances 3*pipe L1 & L2 Temp. R1 Radha R2Rad .... Dlst. (ft) rF1 (lnj (i'!}_ 0.5 1607 4.1 5.4 1 1344 2.9 4.3 1.5 1126 1.9 3.3 2 945 1.1 2.5 2.5 795 0.4 t .8 3 671 Contact 1.2 3.5 568 0.8 4 483 0.4 4.5 412 0.1 5 354 Contact No sketch required

.

M-663-00017A Revision WOJ Penetration Seal Data Appendix:

B8 Penetration

  1. P13250722 Penetration Type: RB-5A Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.:

2000'-0" M-OX Dwg: M-1X1321 1. Barrier Thickness

2. Opening Size: 3. Penetrants:

32" 10"0 (1) 3"P 4. Sealant Type: HDSE/HDLE

, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)

N/A 8. Boot Condition (Acc/Rej)
N/A 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness based on C-1C1311. Sketch: FA: A-8 Side 1 P132.S0722 . -. .dl /) .. '. PI . . ' t I> ' i> -*
  • AI' * . ": . fl . . .. . . 10. Annular Gap (smallest)
3" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: ... -, * <2 I . :. .*. ' b -. '. ....
  • t:>. '0' * # \. IJ ... FA: A-1 Slda2 R Steel M-663-00017A,Revision WOl Penetration Seal Data Appendix: 88 Photos: P132S0722 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

M-663-000 17 A, Revision WO I Penetration Seal Data Heat Affected Zone Review: Fire Area (Side 1) A-8 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo No photo required.

Sketch P132S0722 No photo required.

Page 88-126 ofB -I 0 Appendix: B8 Review Distances (Rtiference F.gure 7.2.3-1 ) 3" Pipe No sketch required M-663-00017A Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P132S0723 Penetration Type: RB-5A Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.
2000'-0" M-OX Dwg: M-1X1321
1. Barrier Thickness
32" 10. Annular Gap (smallest)
3-1/2" 2. Opening Size: 12"0 11. Gap between pen: N/A 3. Penetrants
(1) 4,.P 12. Barrier Type: F 4. Sealant Type: HDSE/HDLE.

Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: 35" ** Reviewed By: Walkdown Comments: Slab thickness based on C-1 C 1311. **Sealant depth determined by inspection report. Sketch: FA: A-8 Side1 P1:U$0723 D 0 * -.. p .: :;, ** ., toll . . . .

  • I "I> p, :'*:t>_.* ,.,.,-...
  • / J), *
  • J * * .. "
  • I
  • FA: A-1 Side 2 R Steel M-663-000l?A, Revision WOI Penetration Seal Data Appendix:

B8 Photos: P13250723 Fire Area A-8 (Side 1) Fire Area A-8 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A.

Revision WOl Penetration Seal Data Heat Affected Zone Review: P13250723 Fire Area (Side 1) A-8 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issun within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page BS-129 ofBS-180 Appendix: B8 Review Distances (IWMnol f"VUM 7.2.ao1 I 4* Pipe L1 & l2 Temp. R1 Radius R2 Radius Dlst. (ft) ("F) (In) (in) 0.5 1625 4.2 5.5 1 1374 3 4.4 1.5 1163 2.1 !3.4 --. 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 1.4 3.5 610 Contact 0.9 4 523 i0.6 I :*s 450 0.2 389 Contact No sketch required

.

M-663-00017A Revision WOl Penetration Seal Data Appendix: B8 Penetration

  1. P133S0769 Penetration Type: RB-5A Fire Area (Side 1 ): A-25 Fire Area (Side 2): A-1 Loc./Elev.: 2000'-0" M-OX Dwg: M-OX1331
1. Barrier Thickness
2. Opening Size: 3. Penetrants:
4. Sealant Type: 5. Damming Side1: 12" 12"D (1) 6"P HDSE/HDLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej)
Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined by Drawing C-1C1311 Sketch: FA! .0.*25 Sld 1 P133SOT89
10. Annular Gap (smallest)
1" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: ' .IJ ** 01 . . _-, i). t> ** C> FA:A-1 Slde2 R Steel M-663-00017A Revision WOI Penetration Seal Data Appendix: 88 Photos: P13350769 Fire Area A-25 (Side 1} Fire Area A-25 (Side 1) Fire Area A-1 (Side 2} Fire Area A-1 (Side 2)

M-663-00017A

, Revision WOJ Page B _,.., 2 of B -I 0 Penetration Seal Data Appendix:

B8 Heat Affected Zone Review: P133S0769 Fire Area (Side 1) A-25 Review Distances (Reference M-663-000HA.

F19ure 7.2.3-1) No Issues within Heat Affected Zone 6" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (*f) (in) (in) 0.5 1659 4.3 5.7 1 1431 3.3 4.6 Fire Area (Side 2) A-1 1.5 1236 2.4 3.8 No issues within Heat Affected Zone 2 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 0.9 4.5 531 0.6 5 464 0.3 Side 1 Photo Side 2 Photo 5.5 408 0 6 359 Contact No photo required.

No photo required.

Sketch No sketch required.

M-663-00017A

, Revision WOI Penetration Seal Data Appendix: B8 Penetration

  1. P133S0771 Penetration Type: RB-5A Fire Area (Side 1 ): A-25 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331
1. Barrier Thickness
12" 10. Annular Gap (smallest)
2-112" 2. Opening Size: 12"0 3. Penetrants: (1) 6'"P 4. Sealant Type: HDSE/HDLE, Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)
N/A 8. Boot Condition (Acc/Rej):

Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments:

Slab thickness determined by Drawing C-1C1311 Sketch: FA: A-2$ Side 1 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete:

14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By:
  • f.j -* * * . ,* o .. .
  • 1:> * -. , 0 **. . .

R Steel M-663-000 17A, Revision WOI Penetration Seal Data Appendix: B8 Photos: P13350771 Fire Area A-25 (Side 1) Fire Area A-25 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • Revision WOl Penetration Seal Data Heat Affected Zone Review: P133S0771 Fire Area (Side 1) A-25 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page 88-135 ofB8-180 Appendix: B8 Review Distances (Relat'IIIICII M-663-0001 7A. f'oguw7.2.3-1 , 6R Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) (OF) (in) (in) 0.5 1659 4.3 5.7 1 1431 3.3 4.6 1.5 1236 2.4 3.8 2 1069 1.7 3 2.5 925 1 2.4 3 803 0.5 1.8 3.5 698 Contact 1.3 4 608 0.9 4.5 531 0.6 5 464 0.3 5.5 408 0 6 1 359 Contac*t No sketch required

.

M-663-00017A

, Revision WOI Page B -136 of 88-1 0 Penetration Seal Data Appendix:

B8 Penetration

  1. P133S0793 Penetration Type: RB-5A Fire Area (Side 1): A-25 Fire Area (Side 2): A-1 Loc./Eiev

.: 2000'-0" M-OX Dwg: M-OX1331 1. Barrier Thickness

12" 2. Opening Size: 14"0 3. Penetrants
(1) 4 .. P 4. Sealant Type: HOSE/HOLE. Ceramic Fiber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity

{Acc/Rej): N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments: Slab thickness determined by Drawing C-1 C1311 Sketch: FA; A-2.5 Slde1 P133S0793 l1 * ' * '(!, *** *I)

  • I 10. Annular Gap (smallest

): 4" 11. Gap between pen: N/ A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: FA: A-1 Slde2 R Steel M-663-00017A

, Revision WOI Page -137 of 88-1 0 Penetration Seal Data Appendix:

B8 Photos: P133S0793 Fire Area A-25 (Side 1) Fire Area A-25 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P133S0793 Fire Area (Side 1) A-25 No issues within Heat Affected Zone Fire Area (Side 2) A-1 1. 112" Ughting Cond. Within Heat Affected Zone, not an Issue. Side 1 Photo Sketch FA: A-:21 II>> t . . . . . ' Side2Photo Page 88-138 ofB8-180 Appendix: 88 Review Distances (AIInnct f9n 7 L1 & L2 Dist (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 .. -4" Pipe Temp. R1 Radius ("F) (in) 1625 4.2 1374 3 1163 2.1 987 1.3 839 0.6 715 0.1 610 Contact 523 450 389 I ' . FA:A-1 8Jde2 R2 Radius (In) 5.5 4.4 3.4 2.6 2 L4 0.9 0.6 0.2 Contact I M-663-00017A

, Revision WOI Penetration Seal Data Appendix:

B8 Penetration

  1. P13350800 Penetration Type: RB-SA Fire Area (Side 1 ): A-25 Fire Area (Side 2): A-1 Loc./Eiev.:

2000'-0" M-OXDwg:

M-OX1331

1. Barrier Thickness
12" 10. Annular Gap (smallest):

2-112 2. Opening Size: 14"0 11. Gap between pen: N/A 3. Penetrants:

(1) 4"P 12. Barrier Type: F 4. Sealant Type: HOSE/HOLE

, Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 14. Pipe Insulated

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

NIA Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth: 13-1/2" .. Reviewed By: Walkdown Comments:

Slab thickness determined by Drawing C-1 C1311. **Sealant depth determined by inspection report. Sketch: FA: Ar25 Side 1 FA: A-1 Slde2 R Steel M-663-00017A

, Revision WOI Penetration Seal Data Appendix: B8 Photos: P133S0800 Fire Area A-25 (Side 1) Fire Area A-25 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

M-663-0001 7A Revision WOI Page 88-141 ofB -I 0 Penetration Seal Data Appendix: B8 Heat Affected Zone Review: P133S0800 Fire Area (Side 1) A-25 Review Distances

!Reference M-Q63-00017A.

Figure 72.3-1) No issues within Heat Affected Zone 4" Pipe l1 & l2 Temp. R1 Radius R2 Radius Dist. (ft) (*F) (in) (in) 0.5 1625 4.2 5.5 1 1374 3 4.4 Fire Area (Side 2) A-1 1.5 1163 2.1 3.4 No issues within heat affected zone 2 987 1.3 2.6 2.5 839 0.6 2 3 715 0.1 1.4 3.5 610 Contact 0.9 4 523 0.6 4.5 450 0.2 5 389 Contact Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch No sketch required.

M-663-00017A

, Revision WOI Page 88-142 ofB -1 0 Penetration Seal Data Appendix: B8 Penetration

  1. P133S0801 Penetration Type: RB-5A Fire Area (Side 1): A-25 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331
1. Barrier Thickness:
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 12" 8"0 (1) 4"P HOSE/HOLE, Ceramic Fiber Boot 6. Damming Side 2: Boot 7. Damming Continuity (Acc/Rej)
N/A 8. Boot Condition (AccJRej):

Accept 9. Sealant Depth: 14-1/4" ** Walkdown Comments: 10. Annular Gap (smallest)

1" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insulated
No Wayne Aregood Prepared By: Jeff Suter Reviewed By: Slab thickness determined by Drawing C-1 C1311. ** Sealant depth determined by inspection report. Sketch: FA: A*25 Side1 P133S0801 4 ., ( l'(P) c.: . .. .t' . "* D, 1 . . D . Q* \ ' , Q* '6 * . * () ., I Q I . .v J *p .* . ... . * :j,
  • J :-"" . C> ' Q ' 'f ,I 1>.' FA: A-1 Side 2 R Steel M-663-0001 7A, Revision W01 Penetration Seal Data Appendix: 88 Photos: P13350801 Fire Area A-25 (Side 1) Fire Area A-25 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)
  • *
  • M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P13350801 Fire Area (Side 1) A-25 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side 2 !Photo Sketch Page 88-144 ofB8-180 Appendix:

88 Review Distances 4*Ptpe L1&L2 Temp. R1 Radlu1 R2 Radlue Dill. (ft) ("F) (In) (In) 0.5 1625 4.2 I 5.5 1 1374 3 4.4 ]1.5 1163 12.1 3.4 2 987 1.3 2.6 2.5 839 0.6 2 3 1715 0.1 1.4 3.5 610 Contact 0.9 4 523 0.6 4.5 450 0.2 5 389 Contact No sketch requ*r

  • M-663-00017A

, Revision WOI Page B -145 of 88-1 0 Penetration Seal Data Appendix:

B8 Penetration

  1. P133S0802 Penetration Type: RB-5A Fire Area (Side 1): A-25 Fire Area (Side 2): A-1 Loc./Eiev

.: 2000'-0" M-OX Dwg: M-OX1331 1. Barrier Thickness

12" 10"0 10. Annular Gap (smallest)
1-112" 2. Opening Size: 11. Gap between pen: N/A 3. Penetrants
(1) 6 .. P 12. Barrier Type: F 4. Sealant Type: HOSE/HOLE. Ceramic Fiber 13. Opening Sleeved or Concrete: 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: 15" ** Reviewed By: Walkdown Comments: Slab thickness determined by Drawing C-1 C 1311. ** Sealant depth determined by inspection report. Sketch: A-2!1 Side1 P133S0802

,, -'o. *r:t . r .. ' t>, . v. 'Booc (n'l' 't> .. ,. 0 . . ' . Ll *.1\ * * -(;-1 *o

  • o' * ...L. .... FA: A-1 Sid 2 R Steel M-663-00017A

, Revision WOJ Page B8-146 of B -I 0 Penetration Seal Data Appendix: B8 Photos: P13350802 Fire Area A-25 (Side 1) Fire Area A-25 (Side 1) Fire Area A-1 (Side 2) Fire Area A-1 (Side 2)

  • *
  • M-663-000l?A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P133S0802 Fire Area (Side 1) A-25 No issues within Heat Affected Zone Fire Area (Side 2) A-1 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page 88-147 ofB8-180 Appendix: B8 Review Distances (Relarance fM!63.<<l0 17A. Figl.q 7

) s* Pipe L1 &L2 Temp. R1 Radius R2Radius Dist. (ft) (Of) (in) (in) IQ.S 1659 4.3 5.7 1 1431 3.3 4.6 1.5 1236 2.4 13.8 2 1069 1.7 ]3 2.5 925 1 2.4 13 803 0.5 1.8 3.5 698 Contact 1.3 14 608 0.9 14.5 531 0.6 's 464 0.3 5.5 408 0 6 359 Contact No sketch required

.