ML18093B021

From kanterella
Jump to navigation Jump to search
1 to Updated Safety Analysis Report, Penetration Seal Data, M-663-00017A, Rev W06, B6-3 to B7-79
ML18093B021
Person / Time
Site: Wolf Creek 
Issue date: 03/08/2018
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 M-663-00017A, Rev W06
Download: ML18093B021 (109)


Text

M-663-00017A, Revision WOl Page B6-3 ofB6-24 Penetration Seal Data Appendix:

86 Heat Affected Zone Review:

P13150491 Fire Area (Side 1)

A-8 Review Distances (Refe<enee ~1 7-'. FQ~n7.2.3-1 I No issues within Heat Affected Zone 12" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1712 4.6 5.9 1

1524 3.1 5.1 Fire Area (Side 2)

A-1 1.5 1357 3

4.3 No issues within Heat Affectea Zone 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 J 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 I

1 Side 1 Photo Side2Photo 5.5 555 0.7 6

499 I

0.4 6.5 1 450 0.2 7

406 0

7.5 368 Contact

' No photo required.

No photo required.

I li Sketch No sketch required.

~

M-663-00017A, Revision WOI Page B -4 of 86-24 Penetration Seal Data Appendix:

B6 Penetration#:

P133S0780 Penetration Type:

M-6A Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

2"

2. Opening Size:

18"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush wffloor

14. Pipe Insulated:

No

6. Damming Side 2:

2"recessed

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth:

9" Walkdown Comments:

Slab thickness determined by Drawing C-1 C1311 Sketch:

FA:. A*1 SIDE2 Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

M-663-0001 7A, Revi ion WOJ Page 8 6-5 of 86-24 Penetration Seal Data Appendix :

86 Photos:

P133S0780 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Page B6-6 of 86-24 Penetration Seal Data Appendix:

B6 Heat Affected Zone Review:

P133S0780 Fire Area (Side 1)

A-8 Review Distances (RefeA1!101 ~17A.

FigUre 72.).~)

, No Issues within Heat Affected Zone 12~ Pipe l1&L2 Temp. R1 Radius R2 Radius Oist. (ft)

("F)

(in)

(in) 05 1712 4-.6 5.9 1

1524 3.7 5.1 Fire Area (Side 2)

A-1 1.5 1357 3

4.3 No issues within Heat Affected Zone 2

1209 2.3 3.6 2.5 1078 1.7 3.1 I

3 962 1.2 2.5 3.5 860 0.7 2.1 I

4

769 0.3 1.7 I

i 4.5 1689 Contac!

1.3 5

618

' 1 Side 1 Photo Side 2 Photo 5.5 555 i 0.7 6

499 I o.4 6.5 450

! 02 7

406 lo 7.5 368 1 Contact No photo required.

No photo required.

I Sketch No sketch required.

l

M-663-000l?A, Revision WOl Page 86-7 ofB6-24 Penetration Seal Data Appendix:

86 Penetration #:

P133S0781 Penetration Type:

M-6A Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.:

2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

2"

2. Opening Size:

18"0 11. Gap between pen:

N/ A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

N/A

14. Pipe Insulated:

No

6. Damming Side 2:

2-1 /2" recess Wayne Aregood

7. Damming Continuity (Ace/Rei):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

12-1/2" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C1311. Changed from M-1 to M-6A based on sealant depth.

Sketch:

FA: A-8 1

M-663-00017A Revision WOI Page 86-8 of 86-24 Penetration Seal Data Appendix:

86 Photos:

P133S0781 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1 )

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Page B6-9 ofB6-24 Penetration Seal Data Appendix:

B6 Heat Affected Zone Review:

P133S0781 Fire Area (Side 1)

A-8 Review Distances (Refe!81'101 M-U3-00017A. F'll\\ft 7.2.3-1 )

No issues within Heat Affected Zone 12ft Pipe l1&L2 Temp. R1 Radius R2 Radius Dist.l_f!}_

("F) iin)

(in) 05 1712 4.6 5.9 1

1524 3.7 5.1 Fire Area (Side 2)

A-1 1.5 1357 3

4.3 No issues within Heat Affected Zone 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 I 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1..3 5

618 1

Side 1 Photo Side 2 Photo 5.5 555 0.7 6

499 0.4 6.5 450 0.2 7

406 0

7.5 368 Contact No photo required.

No photo required.

Sketch No sketch required.

l

M-663-00017A Revision WOl Page 86-J 0 of 86-24 Penetration Seal Data Appendix:

B6 Penetration #:

P141W2487 Penetration Type:

M-6A Fire Area (Side 1): A-16 Fire Area (Side 2):

A-26 Loc./Eiev.: 2042'-11 M-OX Dwg: M-1X1938

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

18"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Flush

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Jeff Suter

7. Damming Continuity (Ace/Rei):

Accept Prepared By:

8. Boot Condition (Ace/Rei):

N/A Wayne Aregood

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Changed detail to M-6A based on field inspection.

Sketch:

P141W2487 FA; A-26 Sld*2

M-663-00017A, Revision WOI Page 86-1 I of 86-24 Penetration Seal Data Appendix:

86 Photos:

P141W2487 Fire Area A-16 (Side 1)

Fire Area A-16 (Side 1)

Fire Area A-26 (Side 2)

Fire Area A-26 (Side 2)

M-663-000l?A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P141W2487 Fire Area (Side 1)

A-16

1. 1" Cond., (no 10): Not within Heat Affected Zone Fire Area {Side 2)

A-26

2. 3" Cond. 4U3B2X, Not within Heat Affected Zone.

Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch Sklll:h FA: A-11 1 llde1

  • ~

Page B6-12 ofB6-24 Appendix:

B6 Review Distances (Raferancl foMiS3.00017 A, FlgU'It 7.2.3.1 )

12* Pipe l1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1712 4.6 5.9 1

1524 3.7 5.1 1.5 1357 3

4.3 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962

! 1.2 2.5 3.5 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3

-5 618 1

5.5 555 0.7 6

499 0.4 6.5 450 0.2 7

406 0

7.5 368 Contact r

I

M-663-000 17 A, Revision WO I Page 86-J3 of B6-24 Penetration Seal Data Appendix:

86 Penetration #:

P14251079 Penetration Type:

M-6A Fire Area (Side 1): A-16 Fire Area (Side 2):

A-8 Loc./Eiev.: 2026'-0" M-OX Dwg: M-1X1421

1. Barrier Thickness:

20"

10. Annular Gap (smallest):

1-3/4"

2. Opening Size:

18"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

N/A

14. Pipe Insulated:

No

6. Damming Side 2:

Recessed 8" Jeff Suter

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth:

15-1/2" Reviewed By:

Walkdown Comments:

Slab thickness based on C-OC1411. Damming recessed on bottom side approximately 8" based on observation from the floor. Detail changed to M-6A.

Sketch:

I c.~ ( '1i>)

0 P142S1079

M-663-00017A Revision WOl Pa2.e 86-14 of B6-24 Penetration Seal Data Appendix:

86 Photos:

P142S1079 Fire Area A-16 (Side 1)

Fire Area A-16 (Side 1)

Fire Area A-8 (Side 2)

Fire Area A-8 (Side 2)

M-663-00017A, Re ision WOI Page B6-15 ofB6-24 Penetration Seal Data Appendix:

B6 Heat Affected Zone Review:

P14251079 Fire Area (Side 1)

A-16 Review Distances (Referlnc:e t.4-663-00017A. FCilR 7.2.).1 }

No Issues within Heal Affected Zone 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(oF)

(in)

(in) 0.5 1712 4.6 5.9 I

1 1524 3.7 5.1 Fire Area (Side 2)

A-8 1.5 1357 3

14.3 2

1209 2.3 3.6 No issues within Heat Affected Zone 2.5 1078 1.7 3.1 3

962 12 2.5 3.5 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 1

Side 1 Photo Side2 Photo 5.5 555 0.7 6

499 0.4 6.5 450 0.2 7

406 0

7.5 368 Contact No photo required.

No photo required.

Sketch No sketch required.

I

M-663-0001 7A, Revision WOI Page 86-1 of 86-24 Penetration Seal Data Appendix:

B6 Penetration #:

P151S1196 Penetration Type:

M-6A Fire Area (Side 1): A-20 Fire Area (Side 2): A-26 Loc./Eiev.: 204 7'-6" M-OX Dwg: M-1X1511

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

1/8"

2. Opening Size:

16"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

N/A

14. Pipe Insulated:

No

6. Damming Side 2:

Ceramic fiber flush with barrier pia Jeff Suter

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth:

12" Reviewed By:

Walkdown Comments:

Slab thickness based on M-1X 1511. Change Detail to M-6A based on field inspection Sketch:

FA: A-20 Side 1 c+

?

~J (T.,p-)

I,.

,..,.(.

- I>

~

ex....-.

\\1~)

FA: A-26 P151S1198 Slde2

M-663-0001 7A Revision WOI Page 86-17 of 86-24 Penetration Seal Data Appendix:

86 Photos:

P151S1196 Fire Area A-20 (Side 1)

Fire Area A-20 (Side 1 )

Fire Area A-26 (Side 2)

Fire Area A-26 (Side 2)

M-663-00017~ Revision WOl Page 86-J 8 of 86-24 Penetration Seal Data Appendix:

B6 Heat Affected Zone Review:

P15151196 Fire Area (Side 1)

A-20 Review Distances

~~17A.~12.3-l)

No issues within Heat Affected Zone 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("~

(in)

(in) 0.5 1712 14.6 5.9 1

1524 3.7 5.1 Fire Area (Side 2)

A-26 1.~

1357 3

4.3 No Issues within Heat Affected Zone 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 0.7

2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 1

Side 1 Photo Side2 Photo 5.5 555 0.7 6

499 0.4

.6.5 450 0.2 7

406 0

7.5 368 Contact No photo required.

No photo required.

Sketch No sketch required.

J

M-663-000 17 A, Revision WO I Page B6-I 9 of 86-24 Penetration Seal Data Appendix:

B6 Penetration #:

P153W2557 Penetration Type:

M-6A Fire Area (Side 1): A-19 Fire Area (Side 2): A-20 Loc./Eiev.: 2063'- 9 M-OX Dwg: M-OX1946

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

1/2"

2. Opening Size:

16"D

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

1/2" recessed

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9-1/2" Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing C-1 C1521. Need new labels. incorrectly labeled in Plant. Changed Detail from M-1 to M-6A based on actual seal depth.

Sketch:

FA; A-111 Side 1 P1S3W2S57 l>

FA: A- 0 SkM2

-663-00017A, Revision WOI Page 8 6-20 of B6-24 Penetration Seal Data Appendix:

86 Photos:

P153W2557 Fire Area A-19 (Side 1)

Fire Area A-19 (Side 1 )

Fire Area A-20 (Side 2)

Fire Area A-20 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P153W2557 Fire Area (Side 1)

A-19 1 No issues within Heat Affected Zone

  • Fire Area (Side 2)

A-20

1. Pipe Strut; No Issue Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch FA: A-11 Side 1 Page 86-21 ofB6-24 Appendix:

86 Review Distances

(~

M-663-00017A. f'On72.~1)

L1 & L2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

ls.s 7

7.5 12" Pipe Temp. R1 Radius

("F)

(in) 1712 4.6 1524 3.7 1357

. ~

1209 2.3 1078 1.7 962 1.2 860 0.7 769 0.3 689 Contact 618 555 499 450 406 368 FA: A-20 Skle2 R2 Radius (in)

! 5.9 5.1 4.3 3.6 3.1 2,5 2.1 1.7 -

1.3 1

0.7 0.4 0.2 0

Contact

M-663-00017A, Revision WOI Page 86-22 of B6-24 Penetration Seal Data Appendix:

B6 Penetration#:

P621S0161 Penetration Type:

M-6A Fire Area (Side 1 ): F-4 Fire Area (Side 2): F-2 Loc./Eiev.: 2026'-0" M-OX Dwg: M-OX6211

1. Barrier Thickness:

10"

2. Opening Size:

16"0

3. Penetrants:

(1) 12"P

4. Sealant Type:

Foam

5. Damming Side1:

Foam 2" above slab

6. Damming Side 2:

Flush w/ Q-Deck Valley

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Ace/Rei):

NIA

9. Sealant Depth:

11" Walkdown Comments:

Changed Detail from M-1 to M-6A based on actual foam depth.

Sketch:

Se.C.Tlo~ A P62150161

10. Annular Gap (smallest):

1-1/4"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

FA: f*2 Slde2 w

Steel

M-663-00017A, Revision WO I Page B6-23 ofB6-24 Penetration Seal Data Appendix:

86 Photos:

P621S0161 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1)

Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017A, Revision WOI Penetration Seal Oata Heat Affected Zone Review:

P621S0161 Fire Area (Side 1)

F-4 No Issues within Heat Affected Zone Fire Area (Side 2)

F-2

1. 4U6030 2" Cond.: Within Heat Affected Zone. Further review determined that this condl,lit is not PFSSD. Set-route oontrol is necessary, Side 1 Photo Side2Photo No photo required.

Sketch FA: F...

Sldt1

  • u. *

~ -

  • l>,** ~ * *
  • .*.'- u. *,.

t

  • JL

. 6.*.

  • g~

Page 86-24 of 86~24 Appendix:

B6 Review Distances

!Rel--=s M-663-00017.0.. fi!)Yte 1.2.~1 )

L1 &l2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 7

7.5 12" Pipe Temp. R1 Radius J"F)

(in) 1712 4.6

_!524 3.7

_!357 3

1209 2.3 1078 1.7 962 1.2 860 0.7 769 0.3 689 Contact 618 555 499 450 406 368 I

fA: F-2 Sld-.2 R2 Radius (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1.7 1.3 1

0.7 0.4 0.2 0

Contact

Page 1 i a W{~rt.F CREEK

........:.\\,/NUCLEAR OPERATING CORPORATION M-663-00017A 7 Fire Protection Evaluation For Penetrant Size Exceeding Typical Detail FB-1 Limitation Rev.

Prepared By Date Reviewed By Date No.

W01

-&I~ 08/19/05

~~dkf2--

08/19/05 Jeff Suter Wayne S Aregood W04

~(/~/'-

12/14/11

-&I~ 12/15/2011 Don Garbe Jeff Suter

M-663-000 17 A 7 Revision W04 Table of Contents Page 2 of 8 Revision Log................................................................................................................................. 3 1.0 Purpose............................................................................................................................. 4 2.0 Scope................................................................................................................................ 4 3.0 References........................................................................................................................ 4 4.0 Evaluation......................................................................................................................... 5 5.0 Conclusions....................................................................................................................... 8 Appendix 87, Penetration Seal Data.................................................... (89 Total Pages)

M-663-00017 A Attachment B7 Revision W04 Revision Reason for Revision W01 Original Issue Page 3 of 8 Revision Log W04 Included new penetrations P135S0943 and P145S1019 added by C.P. 012957.

M-663-00017 A Attachment B7 Revision W04 1.0 Purpose Page 4 of 8 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M-663-00017 A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017. In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details 3.6 TR-187 (M-663-00154), Fire and Hose Stream Test of a 8" thick specimen of

  1. TC0-026 Ceramic Blanket used as a penetration seal material in a 12" diameter sleeve penetrated by bare pipe, insulated pipe, and copper, monel, and stainless steel instrument tubing 3.7 CTP-1002, (M-663-00083), Fire Qualification Test on Silicone Foam Floor Penetration Seals 3.8 CTP-1020 & 1021 (M-663-00060), Fire Qualification Test on Penetration Seals 3.9 Change Package 012957, Install Turbine Driven Auxiliary Feedwater Pump Standby Tanks, Rev. 0

M-663-00017 A Attachment B7 Revision W04 Page 5 of 8 3.10 WIP-M-1X1352-002-A-1, Auxiliary Bldg.- Area 5 Penetration Closure Plan EL.

2013'-6", EL. 2026'-0", EL. 2090'-0", Rev. 0 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

5.0 Evaluation 5.1 Assessment of Condition to Design Requirements The penetration openings identified in Table I contain a pipe penetrant that exceeds the size limitation directly bounded by typical detail FB-1 from M-663-00017. The FB-1 detail, which is comprised of a 12" ceramic fiber depth between silicone impregnated fiberglass boots, directly qualifies a seal with up to a 6" diameter penetrant as 3-hour fire (F) and temperature (T) rated.

TABLE I Penetrations with Penetrant Size Exceeding Detail FB-1 Limitations Penetration Communicating Pipe Penetrant Number Fire Areas Diameter Comments/ Disposition Side 1 Side2 P112W1378 A-1 C-1 30" See 5.2 P112W1380 A-1 C-1 30" See 5.2 P121S0271 A-1 A-4 12" See 5.2 P131S0492 A-8 A-1 24" See 5.2 P132S0682 A-8 A-1 24" See 5.2 P132S0739 A-8 A-1 8"

See 5.2 P132W1844 A-8 A-3 24" See 5.2 P135S0232 A-15 A-33 10" See 5.2 P135S0233 A-15 A-33 8"

See 5.2 P141S1014 A-16 A-8 24" See 5.2 P141W2486 A-16 A-26 12" See 5.2 P143W1488 A-5 F-4 12" See 5.2 P143W1489 A-5 F-4 12" See 5.2 P152W2585 A-19 A-22 10" See 5.2 P152W2617 A-19 A-22 8"

See 5.2 P311W0839 C-1 CC-1 30" See 5.2

M-663-00017 A Page 6 of 8 Attachment B7 Revision W04 Penetration Communicating Pipe Penetrant Fire Areas Comments/ Disposition Number Side 1 Side2 Diameter P321S0085 C-6 C-1 8"

See 5.2 P321S0086 C-6 C-1 8"

See 5.2 P321S0123 C-6 C-1 8"

See 5.2 P611W0082 F-1 F-2 8"

See 5.2 P611W0197 F-2 F-3 12" See 5.2 P621S0153 F-5 F-3 10" See 5.2 P621S0156 F-4 F-3 12" See 5.2 P621S0157 F-4 F-2 12" See 5.2 P621S0162 F-4 F-2 12" See 5.2 P621W0009 F-4 F-5 12" See 5.2 P621W0017 F-5 F-4 12" See 5.2 P621W0221 A-5 F-4 12" See 5.2 P621W0224 A-5 F-4 12" See 5.2 P135S0943 A-15 A-33 10" See 5.2 P145S1019 A-23 A-15 8"

See 5.2 5.2 Evaluation of Condition The Table I penetrations are considered 3-hour F rated based on the successful performance of the following fire tested configurations, which demonstrate that a minimum 8" depth of ceramic fiber will prevent the passage of flame and hose stream to the unexposed barrier side.

TR-187 - 12" diameter opening containing a 2" bare and insulted pipe and three W' diameter tube penetrants. The penetration was sealed with an 8" depth of ceramic fiber blanket.

CTP-1002 Penetration 6-12" diameter opening containing a 6" bare pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

CTP-1 002 Penetration 10 -

12" diameter opening containing a 6" insulated pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

CTP-1020 Penetration 1 - 6" diameter opening containing a 2" bare pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

M-663-000 17 A 7 Revision W04 Page 7 of 8 CTP-1021 Penetration 1 - 10" diameter opening containing a 2" bare pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

Ceramic fiber is an inert material comprised of compressed refractory fibers. It is not charred or consumed during fire exposure.

The material will not be negatively affected by heat transmission through the penetrating item.

Therefore, penetrant size is not a concern regarding capability of a ceramic fiber seal to prevent flame and hose stream passage to the unexposed side.

However, penetrant size is a concern regarding unexposed side temperature development. Based on a comparison to the fire tested configurations bounding detail FB-1, the Table I penetrations are not considered T rated.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipmenUcircuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix 87, were conducted for each penetration of concern. For penetrations P135S0943 and P145S1019 the design location for the penetrations, as identified on M-1X1352, were reviewed and assessed in relation to the current field configuration. The review for the Table 1 penetrations was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that no exposed insitu combustibles or PFSSD circuits are located within the heat affected zone.

Each of the penetrations satisfies the review criteria of M-663-00017 where T rating requirements are not met.

Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation. The Table I penetrations are 3-hour F rated. The comprehensive walkdown review for each of these penetrations revealed that no exposed insitu combustibles or PFSSD circuits are negatively affected by the non T rated penetrations.

M-663-000 17 A 7 Revision W04 6.0 Conclusions Page 8 of 8 Based on the above discussions, it is reasonable to conclude that the Table I penetration seals are acceptable as 3-hour F rated and will perform their intended function, regardless of not achieving a T rating.

The penetration seals satisfy regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements, to prevent spread of fire from one fire area to another. It has also been determined through this evaluation that the lack of a T rating will not affect the plant's ability to achieve and maintain PFSSD.

M-663-00017 A, Revision W04 Pa e 87-1 of 87-89 Penetration Seal Data Appendix:

87 Penetration #:

P112W1378 Penetration Type:

FB-1 Fire Area (Side 1):

A-1 Fire Area (Side 2): C-1 Loc./Eiev.:

1979'-6" M-OX Dwg: M-1X1902

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

3"

2. Opening Size:

42"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 30"P

12. Barrier Type:

A F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth :

Assumed Per Detail Reviewed By:

Walkdown Comments:

Insulation abuts boot, does not transi tion through seal zone. Insulation removed, no longer insulated.

Sketch :

M-663-000 17 A, Revision W04 Pa e B?-2 of B?-89 Penetration Seal Data Appendix:

B7 Photos:

P112W1378 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data

  • Heat Affected Zone Review:

P112W1378

  • Fire Area (Side 1)

A-1 No issues within Heat Affected Zone Fire Area (Side 2)

C-1 No Issues within Heat Affected Zone Side 1 Photo Side2Photo No photo required.

Sketch Pa e 87-3 of 87-89 Appendix:

87 Review Distances

~~ ~17A.Fjgute 7.2.3-1) 30" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1706 14.5 5.9 1

1513 3.7 5

1.5 1342 2.9 4.2 2

1192 12.2 3.6 2.5 1059 1.6 3

3 942 1.1 2.4 3.5 839 0.6 2

14 748

' 0.2 1.6

' 4.5 668 Contact 1..2

's 597 0.9 5.5 535 0.6 6

480 I

0.4 6.5 432 0.1 7

389 I

Contact No sketch required.

M-663-00017 A, Revision W04 Penetration Seal Data Penetration#:

P112W1380 Penetration Type:

FB-1 Loc./Eiev.: 1979'-6"

1. Barrier Thickness:

36"

2. Opening Size:

42"0

3. Penetrants:

(1 l 30"P

4. Sealant Type:

Ceramic Fiber

5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

NIA

8. Boot Condition (Acc/Rej):

Accept Pa e 87-4 of 87-89 Appendix:

B7 Fire Area (Side 1 ):

A-1 M-OX Dwg: M-1X1902 Fire Area (Side 2): C-1

10. Annular Gap (smallest):

3" 11. Gap between pen:

N/A

12. Barrier Type :

A F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Steel

9. Sealant Depth :

Assumed Per Detail Reviewed By:

Walkdown Comments:

Sketch:

M-663-00017 A, Revision W04 Pa e 87-5 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P112W1380 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-000 17 A, Rev1s1on W04 Page 87-6 of 87-89 Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P112W1380 Fire Area (Side 1)

A-1 Review Distances

~11!81te~17A.Fogtn7..2.3-1)

1. No issues within Heat Affected Zone 30" Pipe L1 & L2 Temp. R1 Radius R2 Radius Oist. (ft)

(oF)

(in)

(in) 0.5 1706 4.5 5.9 1

1513 3.7 5

Fire Area (Side 2)

C-1 1.5 1342 2.9 4.2 No Issues within Heat Affected Zone 2

1192 2.2 3.6 2.5 1059 1.6 3

3 942 1.1 2.4 3.5 839 0.6 2

4 748 0.2 1.6 4.5 66B Contact 1.2 Side 1 Photo Side2 Photo 5

597 1 0.9 5.5 535 0.6 6

480 I

0.4 6.5 432 10.1 7

389 Contact No photo required. I No photo required.

Sketch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-7 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P121S0271 Penetration Type:

FB-1 Fire Area (Side 1): A-1 Fire Area (Side 2):

A-4 LocJEiev.:

1988'-0" M-OX Dwg: M-OX12 11

1. Barrier Thickness:

22"

10. Annular Gap (smallest):

1/2"

2. Opening Size:

16" D

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F R

W

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Ace/Rei):

NJA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC1211.

Sketch:

FA: A-1 SIDE 1 FA: A-4 SIDE2 P121 S0271

M-663-00017 A, Revision W04 Pa e 87-8 of 87-89 Penetration Seal Data Appendix:

B7 Photos:

P12150271 Fire Area A-1 (Side 1 )

Fire Area A-1 (Side 1)

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017A, Rev1s1on W04 Page 67-9 of 67-89 Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P12150271 Fire Area (Side 1)

A-1 Review Distances (Reference ~17A figure 7 2.3-1)

No issues within Heat Affected Zone.

12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(*f)

(in)

(in) 0.5 1712 4.6 5.9 I

1 1524 3.7 5.1 Fire Area (Side 2)

A-4 1.5 1357 3

4,3 No issues within Heat Affected Zone.

2 1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 1

Side 1 Photo Side2Photo 5.5 555 0.7 6

499 0.4 6.5 450 0.2 7

406 0

7.5 368 Conta.ct No photo required.

No photo required. I

  • -------------------~

' Sketch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-10 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P131S0492 Penetration Type:

FB-1 Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1 X1311

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

2"

2. Opening Size:

30"D

11. Gap between pen:

N/A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on C-1 C 1311.

Sketch :

FA: A-8 Side 1 sec.no"-1 A 1>1 31~92

~..

, o.

\\0" AN (N eJ rscn..-r~.u-"fiO tJ

-+=--_,_.

(rtP)

FA: A*1 Side 2

M-663-00017 A, Revision W04 Pa e 87-11 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P131S0492 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M 663 00017A R..

W04

..1 eVISIOn p age 8712 fB7 89 0

Penetration Seal Data Appendix: 87 Heat Affected Zone Review:

P13150492 Fire Area (Side 1)

A-8 Review Distances (Aa~eten<;e ~17A, FIQift 1.2.3-1 )

No Issues within Heat Affected Zone I

24" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(*F)

(in)

(in) 0.5 11763 4.8 6.1 1

1615 4.1 5.5 Fire Area {Side 2)

A-1 1.5 1480 3.5 4.9 2

1357 3

4.3 No Issues witrun Heat Affected Zone 2,5 3.8 2.5 1244 3

1141 2

3.3 3.5 1048 1.6 2.9 4

962 1.2 2.5 4.5 884 0.8 22 5

813 0.5 1.9 Side 1 Photo Side 2Photo 5,5 748 I o.2 1.6 6

689 I Contact 1.3 If 6.5 635 I

1.1 7

1585 I

0.8 I'

7.5 1540 0.6 8

499 0.4 No photo required.

No photo required.

8.5 462 0.3 I*

9 427 0.1 II 9.5 396 Contact I

II Sketch No sketch required.

' I I

I I

M-663-00017 A, Revision W04 Pa eB7-13ofB7-89 Penetration Seal Data Appendix:

B7 Penetration #:

P13250682 Penetration Type:

FB-1 Fire Area (Side 1 ): A-8 Fire Area (Side 2):

A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

2"

2. Opening Size:

30"D 11. Gap between pen:

N/A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Wayne Aregood

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C 1311 (wsa )

Sketch:

FA: A-4 Slde1 P1J2S0682 FA: A-1 Sid* 2

M-663-00017 A, Revision W04 Pa e 87-14 of 87-89 Penetration Seal Data Appendix:

B7 Photos:

P132S0682 Fire Area A-8 (Side 1 )

Fire Area A-8 (Side 1 )

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M 663 00017A R p

B7 15 f87 89 W04 eVISIOn age -

0 Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P13250682 Fire Area (Side 1)

A-8 Review Distances (Refetenc:e~17A.FIQin7.2.3-11 No issues within Heat Affected Zone I

24" Pipe L1 &U Temp. R1 Radius R2 Radius Dist. (ft)

(OF)

(in)

(in) 0.5 1763 4.8 6.1 1

1615 4.1 5.5 Fire Area (Side 2)

A-1 11.5 1480 3.5 4.9 No issues within Heat Affected Zone 2

1-357 3

14.3 2.5 1244 2.5 3.8 3

1141 2

3.3 3.5 1048 1.6 2.9 4

962 1.2 2.5 4.5 884 0.8 2.2 5

813 0.5 1.9 I

Side 1 Photo Side2 Photo 5.5 748 0.2 i 1.6 I

6 689 Contact 1.3 6.5 635 1.1 I

7 585 0.8 7.5 540 0.6 8

499 0.4 No photo required.

No photo required.

8.5 462 0.3 9

427 0.1 9.5 396 Contact J

Sketch I

No sketch required.

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P132S0739 FB-1 12" 16"0 (1) 8"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept Pa e 87-16 of 87-89 Appendix:

B7 Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 M-OX Dwg: M-1 X1321

10. Annular Gap (smallest):

3" 11. Gap between pen:

NfA

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on C-1 C 131 1.

Sketch:

FA: A-3 Slde 1 P132S0739

  • C).. ~

~

D..

I "...

. 6.

  • I tl. a OA

("T'ol?)

FA: A*1 Side 2

M-663-000 17 A, Revision W04 Pa e 87-17 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P132S0739 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1 )

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, ReVISIOn W04 Page 87-18 ofB7-89 Penetration Seal Data Appendix:

B7 Heat Affected Zone Review:

P132S0739 Fire Area (Side 1)

A-8 Review Distances

~M-663-00017A F~g..,.7.2.3-1 )

No issues within Heat Affected Zone

&"Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(*F)

(in)

(in) 0.5 1677 4.4 5.8 1

1463 3.4 4.8 Fire Area (Side 2)

A-1 1.5 1277 2.6 3.9 No Issue$ within Heat Affected Zone 2

1116 1.9 3.2 2.5 976

. 1.2 2.6 3

855 0.7 2

3.5 750

t0.2 1.6 4

659 Contact 1.2 4.5 581 0.8 5

512 0.5 Side 1 Photo Side2Photo 5.5 453 0.2 6

402 0

6.5 358 Contact No photo required.

o photo required.

Sketch No sketch requ1re

M-663-00017 A, Revision W04 Pa e 87-19 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P132W1844 Penetration Type:

FB-1 Fire Area (Side 1): A-8 Fire Area (Side 2):

A-3 Loc./Eiev.: 2013'-9" M-OX Dwg: M-1X1918

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

3"

2. Opening Size:

30"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):
  • Accept Jeff Suter
9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing 1-CO 1321. Insulation encapsulated, assumed OK.

Sketch:

FA; A-8 Side 1 p

- ~....... -

  • . * * * ~ * 'c:i:

D.**

  • ~. *.. *

.. *. fl.

. *o....... '

'~ - *

  • Q I
  • V

\\...-.-

  • .. ***o."

J

'o l /} I

o., S.q'lr;J#AI I

D eJiiJ~~1itiiJ

.D.

  • P13.2W1844 FA: A-3 Slde2 Steel

M-663-00017 A, Revision W04 Pa e 87-20 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P132W1844 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1 )

Fire Area A-3 (Side 2)

Fire Area A-3 (Side 2)

M 663 00017A R ev1s1on W04 p aoe B 21 f 87 89 7-0 Penetrati.on Seal Data Appendix:

87 Heat Affected Zone Review:

P132W1844 Fire Area (Side 1)

A-8 Review Distances (Refwence ~f7A. F~g~.n~ 7.2.3-1 1 No Issues within Heat Affected Zone 24" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1763 4.8 6.1 1

1615 4.1 5.5 Fire Area (Side 2)

A-3 1.5 1480 3.5 4.9 No issues within Heat Affected Zone 2

1357 3

4:3 2.5 1244 2.5 3.8 3

1141 2

3.3 3.5 1048 1.6 2.9 4

962 1.2 2.5 4.5 884 0.8 2.2 5

813 0.5 1.9 Side 1 Photo Side 2 Photo 5.5 748 0.2 1.6 6

689 Contact 1.3 6.5 635 1.1 7

585 0.8 7.5 540 0.6 8

499 0.4 No photo required.

No photo required.

8.5 462 0.3 9

427 0.1 9.5 396 Contact J

Sketch No sketch required.

l

M-663-00017 A, Revision W04 Pa e 87-22 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P135S0232 Penetration Type:

FB-1 Fire Area (Side 1): A-15 Fire Area (Side 2): A-33 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1151

1. Barrier Thickness:

16"

10. Annular Gap (smallest):

1 1/2"

2. Opening Size:

16"D 11. Gap between pen:

N/A

3. Penetrants:

(1) 10"P

12. BarrierType:

A F

w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth :

Assumed Per Detail Reviewed By:

Walkdown Comments:

Underside of slab has Q-Decking, effective barrier thickness is measured from corrugated valley.

Sketch:

FA:. A-15 SIDE 1

~ ~

FA.: A-33 SIOE2

M-663-00017 A, Revision W04 Pa e 87-23 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P135S0232 Fire Area A-15 (Side 1)

Fire Area A-15 (Side 1)

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2)

M 663 00017A R eVISIOn W04 p ag_e 87 24 f B7 89 0

Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P13550232 Fire Area (Side 1)

A*15 Review Distances

{Re!erenoa M-663-0001 7A. Figure 7.2.3-1 )

No issues within Heat Affected Zone 10R Pipe L1 &l2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1697 4.5 5.8 I

I 1

1497 i 3.6 4.9 I

Fire Area (Side 2)

A-33 1.5 1321

[ 2.8 4.1 I

No Issues within Heat Affected Zone 2

1167

2.1 3.5 2.5 1032 hs 2.8 I

3 914 1

2.3 3.5 810 0.5 1.8 4

719 0.1 1.4 4.5 639 Contact 1.1 5

569 0.8 Side 1 Photo Side 2 Photo 5.5 508 o.5 6

454 0.2 I

6.5 406 0

I 7

365 Contact No photo required.

No photo required.

Sketch No sketch required.

I I

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:

P135S0233 FB-1 16" 14"0 (1) S"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

NIA

8. Boot Condition (Ace/Rei):

Accept Pa e 87-25 of 87-89 Appendix:

B7 Fire Area (Side 1): A-15 Fire Area (Side 2): A-33 M-OXDwg: M-1X1151

10. Annular Gap (smallest):

1" 11. Gap between pen:

N/A

12. Barrier Type:

A F

w

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Underside of slab has Q-Decking, effective barrier thickness is measured from corrugated valley.

Sketch:

FA: A-15 SIOE1

M-663-00017 A, Revision W04 Pa e 87-26 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P135S0233 Fire Area A-15 (Side 1 )

Fire Area A-15 (Side 1)

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2)

M 663 00017A R..

W04 eVISIOn p age B7 27 f 87 89 0

Penetration Seal Data Appendix: 87 Heat Affected Zone Review:

P13550233 Fire Area (Side 1)

A-15 Review Distances (Rsfen!nc:e~17A. Flgtn 7.2.3-1)

No issues within Heat Affected Zone 8" Pipe L1 & l2 Temp. R1 Radius R2 Radius Dlst. {ft)

(OF}

(inJ (in) 0.5 1677 4.4 5.8 11 1463 3.4 4.8 Fire Area (Side 2)

A-33 1.5 12n 2.6 3.9 No issues within Heat Affected Zone 2

1i16 1.9 3.2 I

2.5 976 1.2 2.6 3

855 0.7 2

3.5 750 0.2 1.6 4

659 Con tad 1.2 4.5 581 0.8 5

512 0.5 Side 1 Photo Side2Photo 5.5 453 02 6

402 0

6.5 358 Contael No photo required.

No photo required.

I Sketch No sketch required.

I I

I

M-663-00017 A, Revision W04 Pa e 87-28 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P135S0943 Penetration Type:

FB-1 Fire Area (Side 1): A-15 Fire Area (Side 2): A-33 Loc./Eiev.: 2013'-6" M-OX Dwg:

M-1X1352

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

Not Reviewed

2. Opening Size:

14"0

11. Gap between pen:

Not Reviewed

3. Penetrants:

(1) 10" p

12. Barrier Type:

A F

P w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

NIA

14. Pipe Insulated:

No

6. Damming Side 2:

NIA Jeff Suter

7. Damming Continuity (Ace/Rei): NIA Prepared By:
8. Boot Condition (Acc/Rej):

Not Reviewed Don Garbe

9. Sealant Depth:

Not Reviewed Reviewed By:

Walkdown Comments:

The walkdown review was based on design location of the penetration, as identified on Sketch:

FA. A-IS

'Srtlt. I T..

I>

CER ~-.. r<. \\'l:BE~

n~~u.~~)

M-1X1352

M-663-00017 A, Revision W04 Pa e 87-29 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P141S1014 Penetration Type:

FB-1 Fire Area (Side 1): A-16 Fire Area (Side 2): A-8 Loc./Eiev.:

2026'-0" M-OX Dwg: M-1X1411

1. Barrier Thickness:

20"

10. Annular Gap (smallest):

2-1 /4"

2. Opening Size:

30"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Wayne Aregood

9. Sealant Depth:

Assumed per detail Reviewed By:

Walkdown Comments:

Slab thickness based on C-OC1 411.

Sketch:

FA: A-18 Side 1 P141S1014

.a.. IJ'

~~~~-----+4-*L_~_~ t

',P FA: A-8 Slde2

M-663-00017 A, Revision W04 Pa e B?-30 of B?-89 Penetration Seal Data Appendix:

87 Photos:

P141S1014 Fire Area A-16 (Side 1)

Fire Area A-16 (Side 1)

Fire Area A-8 (Side 2}

Fire Area A-8 (Side 2)

M 663 00017A R..

W04 eVJSJOn p age 67 31 fB7 89 0

Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P14151014 Fire Area (Side 1)

A-16 Review Distances 1~

~17A. FogiQ 7.2.3-1)

No issues within Heat Affected Zone 24" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1763 4.8 6.1 1

1615 4.1 5.5 Fire Area (Side 2)

A-8 1.5 1480 3.5 4.9 No issues within Heat Affected Zone 2

1357 3

4.3 2,5 1244 2.5 3.8 3

11141 2

3.3 3.5 1048 1.6 2.9 4

962 1.2 2.5 4.5 884 0.8 2.2 5

813 0.5 1.9 I

Side 1 Photo Side2Photo 5.5 748 0.2 1.6 6

689 Contact 1.3 6.5 635 1.1 7_

585 0.8 7.5 540 0.6 8

499 0.4 I No photo required.

No photo required.

8.5 462 0.3 I

9 427 0.1 I

9.5 396 Contact Sketch No sketch required.

I I

I I

I

M-663-00017 A, Revision W04 Pa e 87-32 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P141W2486 Penetration Type:

FB-1 Fire Area (Side 1): A-16 Fire Area (Side 2):

A-26 Loc./Eiev.:

2042'-11 M-OX Dwg: M-1X1 938

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

2"

2. Opening Size:

18"D 11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Wayne Aregood

9. Sealant Depth :

Assumed per detail Reviewed By:

Walkdown Comments:

Sketch:

FA: A*16 Skle1 P141W2486 Co~ (... )

(: 1 FA: A*26 Sid 2

M-663-00017 A, Revision W04 Pa e 87-33 of 87-89 Penetration Seal Data Appendix:

B7 Photos:

P141W2486 Fire Area A-16 (Side 1 )

Fire Area A-16 (Side 1)

Fire Area A-26 (Side 2)

Fire Area A-26 (Side 2)

M-663-000 17 A, Rev1s1on W04 PaQe 87-34 of 67-89 Penetration Seal Data Appendix:

87

. Heat Affected Zone Review:

P141W2486 Fire Area (Side 1)

A-1 6 No Issues within Heat Affected Zone Fire Area (Side 2)

A-26 No Issues within Heat Affected Zone Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-35 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P143W1488 Penetration Type:

FB-1 Fire Area (Side 1 ): A-5 Fire Area (Side 2): F-4 Loc./Eiev.: 2043'-0" M-OX Dwg: M-OX1907

1. Barrier Thickness:

48" *

10. Annular Gap (smallest):

2-1/2"

2. Opening Size:

18"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. BarrierType:

A F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

48"*

Reviewed By:

Walkdown Comments:

  • This wall is located on the East side of the Aux. Bldg and interfaces with the Fuel Bldg, indirectly. Each building is independent with a seismic gap between them, resulting in a 48" wall thickness. The corresponding Fuel Bldg Pen.

No. is P621W0224. Queri ed (LB) QC that was involved with this seal during construction. QC indicated this seal is full depth ceramic fiber and is a separate seal from P621W0224.

Sketch:

FA: A..S Side 1 P143W14811 o:.

,-.,o**, *.,*t>*

c.e llAII'I,,

F l ~li.l'r -:y,)

FA: F-4 Skte2

M-663-00017 A, Revision W04 Pa e 87-36 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P143W1488 Fire Area A-5 (Side 1)

Fire Area A-5 (Side 1)

Fire Area F-4 (Side 2)

Fire Area F-4 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected Zone Review:

P143W1488 Fire Area (Side 1)

A-5

1. 5U5A96, 24~ Cable Tray, Not within Heat Affected Zone

, Fire Area (Side 2)

F-4

  • 2. 5U5P01, 24" Cable Tray, Not within Heat Affected Zone. Seismic Gap, No issues.

Side 1 Photo Side 2 Photo No photo required.

No photo required.

1 Sketch

~HIT~~

c~,T'(

.,.,.~ Mf ~

Pfll CIJM*T't' Pa e 87-37 of 87-89 Appendix:

87 Review Distances

~ RefartflCOI M-U3-<<JJ 17A fllura 7 ~-~ 11 1r Pipe L1 & L2 Temp. R1 Radius R2 Radius Oist. (ft)

(*f)

(in.

(in) 0.5 1712

\\ 4.6

'5.9 1

1524 3.7 5.1 1.5 1357 3

4.3 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 0.7 2.1 4

769 0.'3 1.7 4.5 689 Contact 1.3 5

618 1

5.5 555 0_7 6

499 0.4 6.5 450 0.2 7

406 I

0 7.5 368 Contact

M-663-00017 A, Revision W04 Pa e 87-38 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P143W1489 Penetration Type:

FB-1 Fire Area (Side 1): A-5 Fire Area (Side 2):

F-4 Loc./Eiev.: 2043'-0" M-OX Dwg: M-OX1907

1. Barrier Thickness:

48" *

10. Annular Gap (smallest):

2"

2. Opening Size:

18"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

A F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

48".

Reviewed By:

Walkdown Comments:

  • This wall is located on the East side of the Aux. Bldg and interfaces with the Fuel Bldg, indirectly. Each building is independent with a seismic gap between them, resulting in a 48" wall thickness. The corresponding Fuel Bldg Pen.

No. is P621W0221. Queried (LB) QC that was involved with this seal during construction. QC indicated this seal is full depth ceramic fiber and is a separate seal from P621W022 1.

Sketch:

FA: A-5 Slct.1 P621W0221

\\)....

Sde2

M-663-00017 A, Revision W04 Pa e 87-39 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P143W1489 Fire Area A-5 (Side 1)

Fire Area A-5 (Side 1)

Fire Area F-4 (Side 2)

Fire Area F-4 (Side 2)

M-663-00017A, Revision W04 Penetration Seal Data Heat Affected Zone Review:

P143W1489 Fire Area (Side 1)

A-5

1. 5U485Q, 1" Cond.: Not within Heat Affected Zone
2. 5J1W28, 3" Cond.: Not within Heat Affected Zone
3. 5U-5A1L, 1-112" Cond.: Not within Heat Affected Zone
4. 5J1W3L. 1-1/2" Cond.: Not within Heat Affected Zone
5. 5U5A96, 24" Cable Tray: Not within Heat Affected Zone I Fire Area (Side 2)

F-4 See P621W0221 for Detail, No issues within Heat Affected Zone.

Side 1 Photo Side2Photo No photo required.

Sketch Pa e 87-40 of 67-89 Appendix:

87 Review Distances (R4feteoo8~1714.F~ 7.2.3-1.

12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(.F)

(in)

(in) 0.5 1712 4.6 5.9 1

1524 3.7 5.1 1.5 1357 3

4.'3 2

1209 2.3 3.6 2.5 1078 1.7 3J 3

962 1.2 2.5 3.5 860 0.7 2.1 4

.769 0.3 1.7 4.5 689 Contact 1.3 5

618

~

5.5 555 0.7 6

499 I

0.4 6.5 450 0.2 7

406 0

7.5 368 Contact I

I

M-663-00017 A, Revision W04 Pa e 87-41 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P145S1019 Penetration Type:

FB-1 Fire Area (Side 1): A-23 Fire Area (Side 2): A-15 Loc./Eiev.: 2026'-0" M-OX Dwg:

M-1 X1352

1. Barrier Thickness:

24"

10. Annular Gap (smallest):

Not Reviewed

2. Opening Size:

12"D 11. Gap between pen:

Not Reviewed

3. Penetrants:

(1) 8" p

12. Barrier Type:

F P

R W

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

N/A

14. Pipe Insulated:

No

6. Damming Side 2:

N/A Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Not Reviewed Don Garbe

9. Sealant Depth:

Not Reviewed Reviewed By:

Walkdown Comments:

The walkdown review was based on design location of the penetration, as identified on Sketch:

fA *.4-:<.)

'5l:i7E I

? 14SSIC2>1"1 u~ s"P CEIIII ~Z<. FJ: SER J)JSoLA~ ~?.)

M-1X1352

M-663-00017 A, Revision W04 Pa e B7 -42 of B7 -89 Penetration Seal Data Appendix:

B7 Penetration #:

P152W2585 Penetration Type:

FB-1 Fire Area (Side 1): A-1 9 Fire Area (Side 2): A-22 Loc./Eiev.: 2064'-1 1 M-OX Dwg: M-OX1947

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

1"

2. Opening Size:

14"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 10"P

12. Barrier Type:

A F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

B. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing C-1 C1521.

Sketch:

P152W2S8S FA: A-.22 s dl2

M-663-00017 A, Revision W04 Pa e 87-43 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P152W2585 Fire Area A-19 (Side 1 }

Fire Area A-19 (Side 1)

Fire Area A-22 (Side 2}

Fire Area A-22 (Side 2}

M-663-00017 A, Revisjon W04

~ Page 87-44 of 87-89 Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P152W2585 Fire Area (Side 1)

A-19 Review Distances I

{Ref8renat ~17A.

FJgUN 7.2.~1 )

No issues within Heat Affected Zone 10M Pipe L1 &l2 Temp. R1 Radius R2 Radius I Dist. (ft)

("F)

(in)

(in) 0.5 1697 4.5 5.8 1

1497 3.6 4.9 Fire Area (Side 2)

A-22 1.5 1321 2.8 4.1 No Issues within Heat Affected Zone 2

1167 2.1 3.5 2.5 1032 1.5 2.8 3

914 1

2.3 3.5 810 0.5 1.8 4

719 0.1 1.4 4.5 639 Contact 1.1 5

569 0.8 Side 1 Photo Side2Photo 5.5 508 0.5 6

454 02 6.5 406 0

-~

II 7

365 Contact

~

No photo required.

Sketch No sketch required.

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2064'-11

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P152W2617 FB-1 1 0-1/2" 12"D (1) B"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept Pa e B?-45 of B?-89 Appendix:

B7 Fire Area (Side 1): A-19 Fire Area (Side 2): A-22 M-OX Dwg: M-1X1948

10. Annular Gap (smallest):

0" 11. Gap between pen:

N/A

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Barrier thickness based on drawing C-1C1521. A-22 (side 2) concrete chipped away to allow boot attachment.

Sketch:

FA: A-19 Slde1 P152W2:617

' /). #.

t2."---

- C)*

C>,

0 f

I),

D.

F

  • A*22 Side2

M-663-00017 A, Revision W04 Pa e 87-46 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P152W2617 Fire Area A-19 (Side 1 )

Fire Area A-19 (Side 1)

Fire Area A-22 (Side 2)

Fire Area A-22 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Heat Affected Zone Review:

P152W2617 Fire Area (Side 1)

A-19 No Issues within Heat Affected Zone

,fire Area (Side 2)

A-22

1. 1-1/2" Cond. 5J1262 (seismic Monitor) within Heat Affected Zone. Further review determined that this conduit is not PFSSD. Set-route control Is necessary.
2. 1-1/2" Cond. 1J3A18, not within Heat Affected Zone Side 1 Photo Side2Photo No photo required.

Sketch Pa e 87-47 of 87-89 Appendix:

B7 Review Distances (Raferwloo M-663000171>.. Flgln 7.2.3-1 )

8" Pipe l1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

Jin)

(in}

0.5 1677 4.4 5.8 1

1463 3.4 4.8 1.5 12n 2.6 3.'9 2

1116 1.9 32 2.5 976 1.2 2.6 3

855 0.7 2

3.5 750 0.2 1.6 4

659 Contact 12 4.5 581 0.8 5

512 0.5 5.5 453 0.2 6

402 0

6.5 358 Contac1

M-663-00017 A Revision W04 Pa e 87-48 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P311W0839 Penetration Type:

FB-1 Fire Area (Side 1): C-1 Fire Area (Side 2): CC-1 Loc./Eiev.:

1976'-0" M-OX Dwg: M-1X3901

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

2"

2. Opening Size:

36"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 30"P

12. Barrier Type:

A F

w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Barrier thickness determined by Drawing C-1 C3111.

Sketch:

FA: C-1 Slde1 Pl11W0839

  • ci,...... "
  • a t:>-

I>

D

/J -o

' V '

l 0 I

-* />.

(). - -.

FA: CC-1 Side2

M-663-00017 A, Revision W04 Pa e 87-49 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P311W0839 Fire Area C-1 (Side 1)

Fire Area C-1 (Side 1 )

Fire Area CC-1 (Side 2)

Fire Area CC-1 (Side 2)

M-663-000 17 A, Revision W04 Penetration Seal Data Heat Affected Zone Review:

P311W0839 Fire Area (Side 1)

1. H/2* Cond. 5J1A1W: Not within Heat Affected Zone.

Fire Area (Side 2)

CC-1

1. No issues within Heat Affected Zone.

Side 1 Photo Side 2 Photo No photo required.

No photo required.

1 Sketch FA:c::-1 lld*1 Pa e 87-50 of B7 -89 Appendix:

87 Review Distances

{Refl!l'flllt.8 M-li63-00017A, ~

7.2,).1 )

L1 & L2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 16 6.5 7

30* Pipe Temp. R1 Radius

(*F)

(in) 1706 4.5 1513 3.7 1342 2.9 1192 2.2 1059 1.6 942 1.1 839 0.6 1748 0.2 668 Contact 597 535 480 432 389 FA: CC.1

~a R2 Radius (in) 5.9 5

4.2 3.6 3

24 2

1.6 12 0.9 o.s OA 0.1 Contact

M-663-00017 A, Revision W04 Pa e 87-51 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P32150085 Penetration Type:

FB-1 Fire Area (Side 1): C-6 Fire Area (Side 2): C-1 Loc./Eiev.:

1984'-0" M-OXDwg: M-1X3211

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1"

2. Opening Size:

12"D

11. Gap between pen:

N/A

3. Penetrants:

(1) 8"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:
  • Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C3211.

  • 12" min Ceramic Fiber required by Detail. Pipes are not insulated locally at boot and pipe interface.

Sketch:

FA! C.(!

Side 1 Pl21S0085 F

  • C*1 Sde2

M-663-00017 A, Revision W04 Pa e 87-52 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P321S0085 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017 A. Revtston W04 Penetration Seal Data Heat Affected Zone Review:

P321S0085 Fire Area (Side 1)

C-6 No issues within Heat Affected Zone Fire Area (Side 2)

C-1 No Issues within Heat Affected Zone Side 1 Photo Side 2 Photo No photo required.

No photo required.

I!

Sketch Page 87-53 of 87-89 Appendix:

87 Review Distances (ReWenc:a ~17A, f'9R 7 2.3-1 )

8"Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ftl

(:E)_

(i'!l (in) 0.5 1677 4.4 I 5.8 1

1463 3.4 4.8 1.5 1217

2.6 3.9 2

1116 1.9 3.2 2.5 976 1.2 2.6 3

855 i 0.7 2

3.5 750 0.2 1.6 4

659 Contact 12 4.5 581 0.8 5

512 0.5 5.5 453 02 6

402 0

6.5 358 Contact No sketch required~

M-663-00017 A, Revision W04 Pa e 87-54 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P321S0086 Penetration Type:

FB-1 Fire Area (Side 1 ): C-6 Fire Area (Side 2): C-1 Loc./Elev.:

1984'-0" M-OX Dwg: M-1X3211

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

12"D

11. Gap between pen:

N/A

3. Penetrants:

(1) 8"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:
  • Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1C3211.

  • 12" min Ceramic Fiber required by Detail. Pipes are not insulated locally at boot and pipe interface.

Sketch:

FA: C-6 Sde 1 P321S0086

M-663-000 17 A, Revision W04 Pa e 87-55 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P321S0086 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017 A, Rev1s1on W04 Penetration Seal Data Heat Affected Zone Review:

P321S0086 Fire Area (Side 1)

C-6 No issues within Heat Affected Zone Fire Area (Side 2) c-1 No Issues within Heat Affected Zone Side 1 Photo Side2 Photo No photo required.

No photo required.

Sketch Page 87-56 ofB7-89 Appendix:

B7 Review Distances (Ral-t.U$3.00011A.F"9R7.2.3-1) 8" Pipe L 1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(°F)

(in)

(in) 0.5 11677 4.4 5.8 1

3A 4B 1463 1.5 1277 2.6 3.9 2

1116 1.9 3.2 2.5 976 1.2 2.6 3

855 0.7 2

3.5 750 0.2 LS 4

659 Conlact 1.2 4.5 581 0.8 5

512 0.5 5.5 453 I

02 6

402 0

6.5 358 Con lac!

No sketch required.

M-663-00017 A, Revision W04 Pa e 87-57 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P32150123 Penetration Type:

FB-1 Fire Area (Side 1): C-6 Fire Area (Side 2): C-1 Loc./Eiev.: 1984'-0" M-OX Dwg: M-1X32 11

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

12"D 11. Gap between pen :

N/A

3. Penetrants:

(1) 8"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Ace/Rei):

N/A Prepared By:

8. Boot Condition (Ace/Rei):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C3211.

Sketch:

FA: C*6 Sidtl1 P321S0123 z*

FA: C-1 Side 2

M-663-00017 A, Revision W04 Pa e 87-58 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P32150123 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1 )

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M 663 00017A R evJsJon W04 p age 87 59 f 87 89 0

Penetration Seal Data Appendix:

87 Heat Affected Zone Review:

P32150123 Fire Area (Side 1)

C-6 Review Distances (fWereoceM-(;63-000H

~7.2.3-1)

No issues within Heat Affected Zone an Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F) linJ (in) 0.5 1677 4.4 5.8 1

1463 3.4 4.8 Fire Area (Side 2)

C-1 1.5 12n 2.6 3.~

No issues within Heat Affected Zone 2

1116 1.9 3.2 12.5 976 1.2 2.6 3

855 0.7 2

3.5 750 0.2 1.6 4

659 Contact 1.2 4.5 581 0.8 5

512 0.5 Side 1 Photo Side 2 Photo 5.5 453 0.2 6

402 0

6.5 358 Contact No photo required.

No photo required.

Sketch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-60 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P611W0082 Penetration Type:

FB-1 Fire Area (Side 1): F-1 Fire Area (Side 2):

F-2 Loc./Eiev.: 2012'-10 M*OX Dwg: M-1X6906

1. Barrier Thickness:

24"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

12"D 11. Gapbetweenpen:

N/A

3. Penetrants:

(1) a**p

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing C-1C6111 Sketch:

FA; F*1 Side1 e,ooT C*rm P611W0082

.- -b'

/' SANb (r'lP)

FA: F-2 Side2

M-663-00017 A, Revision W04 Pa e 87-61 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P611W0082 Fire Area F-1 (Side 1)

Fire Area F-1 (Side 1)

Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Heat Affected Zone Review:

P611W0082 Fire Area (Side 1)

F-1

1. 1* Pipe, lnspectorTestfor FP: No issues within Heat Affected Zone.

Fire Area (Side 2)

F-2

2. 5U6015, 3/4* Cond. for thermostat.: No issue Side 1 Photo Side2 Photo No photo required.

Sketch Pa e 87-62 of 87-89 Appendix:

B7 Review Distances (Rafe.oance ~

TA. f9he 1.2.3-1)

B" Pipe L1 & L2 Temp. R1 Radius R2 Radius Oist. (ft)

(*F)

(in)

(in) 0.5 1677 A.4 15.8 1

1463 13.4 4.8 1.5 1277 12.6 3.9 2

1116 11.9 3.2 2.5 976

! 1.2 2.6 3

855 I o.1 2

3.5 750 10.2 1.6 4

659 Contact 1.2 4.5 581 0.8 5

512 0.5 5.5 453 0.2 6

402 0

6.5 358 Contact

M-663-00017 A. Revision W04 Pa e 87-63 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P611W0197 Penetration Type:

FB-1 Fire Area (Side 1 ): F-2 Fire Area (Side 2):

F-3 Loc./Eiev.: 2019'-0" M-OX Dwg: M-1X6906

1. Barrier Thickness:

12"

2. Opening Size:

16"0

3. Penetrants:

(1) 12"P

4. Sealant Type:

Ceramic Fiber

5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth:

Assumed Per Detail Walkdown Comments:

Wall thickness determined by Drawing C-1 C6111.

Sketch:

FA: F*2 Side 1 P611W0197

10. Annular Gap (smallest):

1-1/4"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

' /)

r>

p ll '

/J'.,p.

tr..

'.b..

FA: F-3 Slde2 Steel

M-663-00017 A, Revision W04 Pa e 87-64 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P611W0197 Fire Area F-2 (Side 1)

Fire Area F-2 (Side 1)

Fire Area F-3 (Side 2)

Fire Area F-3 (Side 2)

M-663-00017A Revision W04 Penetration Seal Data Heat Affected Zone Review:

P611W0197 Fire Area (Side 1)

F-2

1. 5U5W1G, 1-112" Cond.: Additional Review is required. Further review determined that this conduit is not PFSSD. Set-route control is necessary.

Fire Area (Side 2)

F-3 No issues within Heal Affected Zone Side 1 Photo No photo required.

Sketch FA: f~

llde1 Side2 Photo Pa e 87-65 of 87-89 Appendix:

87 Review Distances (Rehlrwrlc:e ~7A.

Fq.ft 7.2.3-1 1 L1 & L2 Dlst (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 7

7.5 12" Pipe Temp. R1 Radius

("F)

(in)

. 1712 4.6 1524 3.7 1357 3

1209 2.3 1078 1.7 962 1.2 860 0.7 769 0.3 689 Contact 618 555 499 450 406 368 FA: f.J lkteZ R2 Radius (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1.7 1.3 1

0.7 0.4 0.2 0

Contact

M-663-00017 A, Revision W04 Pa e 87-66 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P621 50153 Penetration Type:

FB-1 Fire Area (Side 1): F-5 Fire Area (Side 2):

F-3 loc./Eiev.: 2026'-0" M-OX Dwg: M-OX6211

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

1"

2. Opening Size:

14"0

11. Gap between pen:

N/A

3. Penetrants:

(1)10"P

12. Barrier Type:

F w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Sketch:

FA; F..S Skkl 1 SE£.. rloll A PS21S0153 FA: F.J Slde2

M-663-00017 A, Revision W04 Pa e 87-67 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P62150153 Fire Area F-5 (Side 1)

Fire Area F-5 (Side 1)

Fire Area F-3 (Side 2)

Fire Area F-3 (Side 2)

M-663-00017A Revision W04 Page 87-68 of 87-89 Penetration Seal Data Appendix:

67 Heat Affected Zone Review:

P62150153 Fire Area (Side 1)

F-5 Review Distances (Refefence ~17A.I"i;de 7.2.3-1 )

No issues within Heat Affected Zone 10" Pipe l1&L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(In)

(in) 0.5 11697 4.5 5.8 I Fire Area (Side 2) 1 1497 3.6 4,9 F-3 1.5 1321 2.8 4.1

  • No Issues within Heat Affected Zone 2

1167 2.1 13.5 2.5 1032 1.5 12.8 3

914 1

12.3 3.5 810 0.5 1.8 4

719 0.1 1.4 4.5 639 Contact 1.1 5

569 0.8 Side 1 Photo Side2 Photo 5.5 508 0.5 6

454 0.2 6.5 406 0

7 365 Contact No photo required.

No photo required.

Sketch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-69 of 87-89 Penetration Seal Data Appendix:

B7 Penetration #:

P621S0156 Penetration Type:

FB-1 Fire Area (Side 1): F-4 Fire Area (Side 2): F-3 Loc./Eiev.:

2026'-0" M-OX Dwg: M-OX6211

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

1"

2. Opening Size:

16"D

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Sketch:

FA: F-4 Slde1,--- --~

I I

St::CIIOl-l A P621S0156 ll 10" It"

_j FA: F.J Slde2

M-663-00017 A, Revision W04 Pa e 87-70 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P621S0156 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1)

Fire Area F-3 (Side 2)

Fire Area F-3 (Side 2)

M 663 00017A R 8VISJOn W04 p age 87 71 f87 89 0

Penetration Seal Data Appendix:

87 Heat Affected Zone ~Review:

P621S0156 Fire Area (Side 1)

F-4 Review Distances j

~~~W>ce Mo663-00017A, F'9ft 7.2.3-1 I No Issues within Heat Affected Zone 12" Pipe l1&L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1712 4.6 5.9 1

1524 3.7 5.1 Fire Area (Side 2)

F-3 1.5 1357 3

4.3 No Issues within Heat Affected ZQne 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 1

Side 1 Photo Side2Photo 5.5 555 0.7 6

499 0.4 6.5 450 0.2 I

7 406 0

7.5 368 Contact 1 ~ No photo required.

No photo required.

Sketch No sketch

  • ed.

requ1

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2026'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:

P62150157 FB-1 1 0" 16"0 (1)12"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

NIA

8. Boot Condition (Acc/Rej):

Accept Pa e 87-72 of 87-89 Appendix:

B7 Fire Area (Side 1):

F-4 Fire Area (Side 2): F-2 M-OX Dwg: M-OX6211

10. Annular Gap (smallest):

1/4"

11. Gap between pen:

N/A

12. BarrierType:

F w

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness ( 12") determined by C-1 C6211.

Sketch:

FA: F_.

Side 1

,o* l't

  • E t-*~._*.

or.-H.

' 1---------4-__.f....;-~ _j 2.

FA: F-3 Side 2

M-663-00017A, Revision W04 Pa e 87-73 of 87-89 Penetration Seal Data Appendix:

B7 Photos:

P621S0157 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1)

Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected Zone Review:

P62150157 Fire Area (Side 1)

F-4 No issues within Heat Affected Zone Fire Area (Side 2)

F-2

1. 1/2" unscheduled Cond.: Not within Heat Affected Zone.

Side 1 Photo No photo required.

Sketch FA: F..,

Side2Photo Pa e 87-74 of 87-89 Appendix:

87

'Review Distances (Refenlnc:e Ma3-00017A. F'!llft 7 2.3-1 )

12'" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1712 4.6 5,9 1

1524 3.7 5.1 1.5 1357 3

4.3 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 1

5.5 555 0.7 6

499 0.4 6.5 450 0.2 7

406 lo 7.5 368 Contact

M-663-00017 A, Revision W04 Pa e 87-75 of 87-89 Penetration Seal Data Appendix:

87 Penetration#:

P621S0162 Penetration Type:

FB-1 Fire Area (Side 1): F-4 Fire Area (Side 2): F-2 Loc./Eiev.: 2026'-0" M-OX Dwg: M-OX6211

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

1-1/4"

2. Opening Size:

16"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Sketch:

FA:. F-<1 Slcte 1 Stc.T'Iot-1 A P621S0162 FA: F*2 Slde2

M-663-00017 A, Revision W04 Pa e 87-76 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P62150162 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1 )

Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected.Zone Review:

P621S0162

  • Fire Area (Side 1)

F-4 No issues within Heat Affected Zone Fire Area {Side 2)

F-2

1. 4U6030, 2" Cond.: Not within Heat Affected Zone Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch FA: P:-4 81de 1 I

l Pa e 87-77 of B7 -89 Appendix:

87 Review Distances

(~

IU6J.<l0017A.!"ogLft7.2.J.1) 12" Pipe l1 & l2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 7

7.5 1712 4.6 1524 3.7 1357 3

1209 2.3 11078 1.7

962 1.2

\\ 860 0.7

\\ 769 I o.3

\\ 689 Contact

\\ 618 555 499 450 406 368

  • I

. l FA: F.a SlcN2 (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1J 1.. 3 1

0.7 0.4 0.2 0

Contact

M-663-000 17 A, Revision W04 Pa e 87-78 of 87-89 Penetration Seal Data Appendix:

87 Penetration #:

P621W0009 Penetration Type:

FB-1 Fire Area (Side 1 ):

F-4 Fire Area (Side 2): F-5 Loc./Eiev.:

2041 '-6" M-OX Dwg: M-OX6908

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

12" 16"0 (1) 12"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej);

Accept

9. Sealant Depth:

Assumed Per Detail Walkdown Comments:

Wall thickness (12") determined by C-1C6211.

Sketch:

FA: F....

Slda 1 P621W0009

  • ~.
10. Annular Gap (smallest):

3/4" 11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

b,

0 I>..

FA: F-5 Sdo2 Steel

M-663-00017 A, Revision W04 Pa e 87-79 of 87-89 Penetration Seal Data Appendix:

87 Photos:

P621W0009 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1)

Fire Area F-5 (Side 2)

Fire Area F-5 (Side 2)