ML18093B025

From kanterella
Jump to navigation Jump to search
1 to Updated Safety Analysis Report, Penetration Seal Data, M-663-00017A, Rev W06, B8-148 to B13-25
ML18093B025
Person / Time
Site: Wolf Creek 
Issue date: 03/08/2018
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 M-663-00017A, Rev W06
Download: ML18093B025 (166)


Text

M-663-00017A, Revision WOl Penetration Seal Data Appendix:

B8 Penetration #:

P133S0810 Penetration Type:

RB-5A Fire Area (Side 1 ): A-25 Fire Area (Side 2):

A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

5"

2. Opening Size:

24"0 11. Gap between pen:

N/A

3. Penetrants :

(1) 10.. P

12. Barrier Type:

F

4. Sealant Type:

HOSE/HOLE. Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1:

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

13" **

Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C1311. ** Sealant depth determ ined by inspection report.

Sketch:

FA: A-25 Slde1 4 ~

CrY)

. b **

~

I I

(l'fl>)

P133S0810

. [)..

. ~ {)..

I Q_:

. rJ, **.

p..,

  • 1 I *. (}

I FA: A-1 Side 2 R

Steel

M-663-00017A Revision WOl Penetration Seal Data Appendix:

88 Photos:

P13350810 Fire Area A-25 (Side 1)

Fire Area A-25 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-000I?A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

Fire Area (Side 1)

A-25 No issues within heat affected zone Fire Area (Side 2)

A-1 No issues within Heat Affected Zone Side 1 Photo Sketch P133S0810 Side2Photo Page B8-150 ofBS-180 Appendix:

B8 Review Distances (Rel-.ca MaJ.0001TA. ~-7.2.3-f I 10" Pipe L1 &L2 Temp. R1 Radius R2Radlus Dist. (ft)

(Of)

(in)

(in) 0.5 1697 4.5 5.8 1

1497 3.6 4.9 1.5 1321 2.8 4.1 2

1167 2.1 3.5 2.5 1032 1.5 2.8 3

914 1

2.3 3.5 810 0.5 1.8 4

719 0.1 1A 4.5 639 Contact 1.1 5

569 0.8 5.5 508 0.5 6

454 0.2 6.5 406 0

7 365 Contact sketch r quir

M-663-00017 A, Revision WOl Page 88-151 of B - 1 0 Penetration Seal Data Appendix:

BB Penetration #:

P133S0820 Penetration Type:

RB-5A Fire Area (Side 1): A-25 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

2. Opening Size:

24"0

3. Penetrants:

(1) 10"P

4. Sealant Type:

HOSE/HOLE, Ceramic Fiber

5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Ace/Rei):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth:

Assumed Per Detail Walkdown Comments:

Slab thi ckness determined by Drawing C-1C1311 Sketch:

FA; A*2.5 Side 1 P133S0820

10. Annular Gap (smallest):

6"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

FA: A-1 Slde2 R

Steel

M-663-000 17 A, Revision WO l Page B -152 of88-l 0 Penetration Seal Data Appendix:

88 Photos:

P133S0820 Fire Area A-25 (Side 1)

Fire Area A-25 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-000 17~ Revision WOl Penetration Seal Data Heat Affected Zone Review:

P133S0820 Fire Area (Side 1)

A-25 No issues within Heat Affected Zone Fire Area (Side 2)

A-1 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page 88-153 of 88-180 Appendix:

B8 Review Distances

(~ce

~17A.

figu117.2.3-1) 10* Pipe L1 &l2 Temp. R1 Radius R2 Radius Dist. (ft)

(*F)

(In)

(in) 0.5 1697 4.5 5:8 1

1497 3.6 4.9 1.5 1321 2.8 4.1 2

1167 2.1 3.5 2.5 "1032 1.5 2.8 3

914 1

! 2..3 3.5 810 0.5 1.8 4

719 0.1 1.4 4.5 639 Contact 1.1 5

569

<0.8 5.5 508 0:5 6

454 0.2 6.5 406 0

7

' 365 I

Contact I

I No sketch requir

M-663-00017A Revision WOl Penetration Seal Data Appendix:

B8 Penetration #:

P134S0864 Penetration Type:

RB-5A Fire Area (Side 1 ): A-24 Fire Area (Side 2):

A-1 Loc./Eiev.:

2000'-0" M-OX Dwg: M-1 X1341

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

2"

2. Opening Size:

10" D 11. Gap between pen:

N/A

3. Penetrants:

(1) 4"P

12. Barrier Type:

F R

4. Sealant Type:

HOSE/HOLE, Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No*

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

14-1/2" **

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C1311.

  • Pipe not insulated locally at seal penetration. ** Sealant depth determined by inspection report.

Sketch :

FA: A-24 Side1 P134S0864

_ *, I

  • : 0*

' o *A *.:.;

  • V'*
  • ..y..- 0.

~6 '.: I

"' Cit

  • FA: A-1 Side 2

M-663-000I ?A, Revision WOl Penetration Seal Data Appendix:

B8 Photos:

P134S0864 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P134S0864 Fire Area (Side 1)

A-24 No issues within Heat Affected Zone Fire Area (Side 2)

A-1 No issues wilhln Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page 88-156 of BS-180 Appendix:

B8 Review Distances IR:IIIIRnCI t.Wlfl3.00017A..... 1.U.1 )

4*Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) rFl (In)

(In) 0.5 1625 4.2

'5.5 1

1374 3

4.4 1.5 1163 2.1 3.4 2

987 1.3 2.6 2.5 839 0.6 2

  • 3 715 0.1 1.4 3.5 610 Contact 0.9 4

523 0.6 4.5 450 02 5

389 Contact No sketch requir

M-663-0001 7A, Revision WOl Penetration Seal Data Appendix:

88 Penetration #:

P134S0865 Penetration Type:

RB-5A Fire Area (Side 1): A-24 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1341

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

2"

2. Opening Size:

10" D 11. Gap between pen:

N/A

3. Penetrants:

(1) 4"P

12. Barrier Type:

F

4. Sealant Type:

HDSE/HDLE, Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

14"..,.

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C1311. ** Sealant depth determined by inspection report Sketch:

'I> ; *.

, D*

    • I

. (...

. a o. v*

r r;::....,.

~

  • P13-4S0865 "A * * *

~* ** p '

!>*. ~

~

    • ('... !

0 b

I p

FA:. A*1 Side 2 R

Steel

M -663-0001 7 A Revision WO I Penetration Seal Data Appendix:

B8 Photos:

P13450865 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A. Revision WOI Penetration Seal Data Heat Affected Zone Review:

P134S0865 Fire Area (Side 1}

A-24 No Issues within Haat Affected Zone Fire Area {Side 2)

A-1 No Issues within Heat Affected Zone Side 1 Photo Side2 Photo Sketch Page 88-159 ofB8-180 Appendix:

B8 1Review Distances

(-.nc.~17A.f9n1~1)

.... Pipe L1 &L2 Temp. R1 Radius R2Radlua Dist. (ft) rFJ (In)

(In) 0.5 1625

4.2 5.5 11 1374 3

4.4 1.5 1163 2.1 3.4 2

987 1.3 2.6 2:5 839 0.6 2

3 715 0.1 1.4 3.5 610 Contact 0.9 4

'523 0.6 4.5 450 I 0.2 5

389 Contact No sketch required

M-663-000 17 A, Revision WO I Penetration Seal Data Appendix:

B8 Penetration #:

P134S0875 Penetration Type:

RB-5A Fire Area (Side 1 ): A-24 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M*OX Dwg: M-1X1341

1. Barrier Thickness:

12"

2. Opening Size:

18"0

3. Penetrants:

(1) 10"P

4. Sealant Type:

HOSE/HOLE, Ceramic Fiber

5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition {Acc/Rej):

Accept

9. Sealant Depth:

Assumed Per Detail Walkdown Comments:

Slab thickness based on drawing C-1 C 1311.

Sketch:

/:2,

P134S0875

10. Annular Gap (smallest):

2"

11. Gapbetweenpen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

BANl> (TiP)

(>

  • /)
  • Q' *

. b 0 '.

0.. ~

BooT(T~)

FA: A*1 S1d412 R

Steel

M-663-000 !7A, Revision WOJ Penetration Seal Data Appendix:

B8 Photos:

P134S0875 Fire Area A-24 (Side 1)

Fire Area A-24

{Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P134S0875 Fire Area (Side 1)

A-24 No issues within Heat Affected Zone Fire Area (Side 2)

A-1 No issues within Heat Affected Zone Side1 Photo Side2Photo Sketch Page B8-l62 of 88-180 Appendix:

B8 Review Distances (R8fer'er~Qo ~1 7A. r~g~N7.2.3-1 )

10" Pipe L1 & L2 Temp. R1 RadiU$ R2 Radius Dist. (ft) ffl (in)

(In) 0.5 1697 4.5 5.8 1

1497 3.6 4.9 1.5 1321 2.8 4.1 2

1167 2.1 3.5 2.5 1032 1.5 2.8 3

914 1

2.3 3.5 810 0.5 1.8 4

719 0.1

' 1.4 4.5 639 Contact 1.1 5

569 011 5.5 508 0.5 6

454 0.2 6.5 406 0

7 365 Contact I

No sketch requir d.

M-663-00017A Revision WOI Penetration Seal Data Appendix:

B8 Penetration #:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:

P134S0911 RB-5A 12" 12"0 (1) 4""P Fire Area (Side 1): A-24 Fire Area (Side 2): A-1 M-OX Dwg: M-1X1341

10. Annular Gap (smallest):

3" 11. Gap between pen:

N/A

12. Barrier Type:

F

4. Sealant Type:

HOSE/HOLE, Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

13-1/2"..

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C1311. ** Sealant depth determined by inspection report.

Sketch:

FA: A-24 Sldo 1 P134S0911 FA: A-1 Side2 R

Steel

M-663-00017A, Revision WO I Page B -164 ofB8-l 0 Penetration Seal Data Appendix:

B8 Photos:

P13450911 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A Revision WOl Page 88-165 of B - L80 Penetration Seal Data Appendix:

88 Heat Affected Zone Review:

P13450911 Fire Area (Side 1)

A-24 Review Distances (Reference M-66~17A Fog...., 7 2.3-1 )

No issues within Heat Affected Zone 4" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 05 1625 4.2 5.5 1

1374 3

4.4 Fire Area (Side 2)

A-1 1.5 1163 2.1 3.4 No issues within Heat Affected Zone 2

987 1.3 2.6 2.5 839 0.6 2

3 715 0.1 1.4 3.5 610 Contact 0.9 4

523 0.6 4.5 450 0.2 5

389 Contact Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch No sketch required.

M-663-00017 A, Revision WOI Page 88-166 of B -J 0 Penetration Seal Data Appendix:

88 Penetration #:

P134S0912 Penetration Type:

RB-5A Fire Area (Side 1):

A-24 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1341

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

3"

2. Opening Size:

14"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 4""P

12. Barrier Type:

F R

4. Sealant Type:

HDSE/HDLE, Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

13-1/2" **

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C 1311. ** Sealant depth determined by inspection report.

Sketch:

FA: A-24 Side 1 P134S0912 FA:A-1 Stde2

M-663-000l?A, Revision WOl Page 88-167 ofB8-180 p,enetration Seal Data Appendix:

88 Photos:

P13450912 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOJ Penetration Seal Data Heat Affected Zone Review:

P134S0912 Fire Area (Side 1)

A-24 No Issues within Heat Affected Zone Fire Area (Side 2)

A-1 No Issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page B8-168 of B8-180 Appendix:

88 Review Distances

~

M-663-0001TA. f'O,ft7U1 )

4"Pfpe L1 &l2 Temp. R1 Radius R2 Radius Dlat. (ft) rF)

(In)

(In) 0.5 1625 4.2

]5.5 1

1374 3

] 4.4 1.5 1163 2.1 J 3.4

. 2 987 1.3 2.6 2.5 839 0.6 2

3 715 0.1 1.4 3.5 610 Contact 0.9 4

523

().6 4.5 450 0.2 5

389 Contact No sketch required.

M-663-00017A, Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:

P134S0918 RB-SA 12" 10"0 (1) 4"P Page 88-I 69 of 8 8-I 0 Appendix:

B8 Fire Area (Side 1 ): A-24 Fire Area (Side 2):

A-1 M-OX Dwg: M-1X1341

10. Annular Gap (smallest):

1-1 /2" 11. Gap between pen:

N/A

12. Barrier Type:

F R

4. Sealant Type:

HDSE/HDLE, Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Ace/Rei):

Accept Jeff Suter

9. Sealant Depth:

15"....

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C131 1. *' Sealant depth determined by inspection report.

Sketch:

FA: A*24 Sida1

( c!fZ"Afl'l I(

r::.see*N

,-or~~

P134S0918 FA. A*1 SJde2

M-663-000 17A, Revision WOI Penetration Seal Data Appendix:

B8 Photos:

P134S0918 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P13450918 Fire Area (Side 1)

A-24 No issues within Heat Affected Zone Fire Area (Side 2)

A-1 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page B8-17l ofBS-1 80 Appendix:

88 Review Distances

~~~17A. Flgura 7.2.l-1) 4"Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1625 4.2 5.5 1

1374 3

4.4 1.5 1163 2.1 3.4 2

987 1.3 2.6 12.5 839 0.6 2

3 715 0.1 1.4 3.5 610 Contact 0.9 4

-523 0.6 4.5 450 0.2 5

389 Contact I

I No sketch required.

M-663-00017A, Revision WOl Penetration Seal Data Appendix:

B8 Penetration #:

P134S0919 Penetration Type:

RB-5A Fire Area (Side 1 ): A-24 Fire Area (Side 2):

A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1 X1341

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

5"

2. Opening Size:

10"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 4"P

12. Barrier Type:

F

4. Sealant Type:

HOSE/HOLE, Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Ace/Rei):

Accept Jeff Suter

9. Sealant Depth:

14" **

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C1311... Sealant depth determined by inspection report.

Sketch:

FA; A-24 Slde1 C< **,,., <

  • . 011, ~!--,.:~__::J+...:...:._,..,.._- :~ N b ( T't v

~Lsa *~ /

I!'J~

  • t?>oo T (ToP £.t ~lit)

. *

  • t;j ; -~

V1t0 F1 :1),

v.

P134S0919 Soot (rtP)

FA: A*1 Slde2 R

Steel

M-663-00017A, Revision WO I Penetration Seal Data Appendix:

B8 Photos:

P134S0919 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P134S0919 Fire Area (Side 1)

A-24 No Issues within Heat Affected Zone Fire Area (Side 2)

A-1 No issues within Heat Affecte~ Zone Side 1 Photo Side2Photo Sketch Page B&-1 74 ofBS-180 Appendix:

88 Review Distances (Relenlnoi~17A.FJQ~n 7.2.3-1) 4"Pipe L1&l2 Temp. R1 Radius R2 Radius Dist. (ft)

(*f)

(in)

(in) 0.5 1625 4.2 5.5 1

1374 3

  • 4.4 1.5 1163 2.1 3.4 2

987 1.3 2.6 2.5

~ 839 I o.s 2

3

! 715 I 0.1 1.4 3.5

[610

  • Contact 0:9 4

523 0.6 4.5 1450 0.2 5

389 Contact No sketch require

  • M-663-0001 7A Revision WOI Penetration Seal Data Appendix:

B8 Penetration #:

Penetration Type:

Loc./Eiev.:

2034'-11

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:

P141W1854 RB-SA 36" 26"D (1) 18"P Fire Area (Side 1):

A-8 Fire Area (Side 2): A-9 M-OX Dwg: M-1X 1918

10. Annular Gap (smallest):

2"

11. Gap between pen:

N/A

12. Barrier Type:

F

4. Sealant Type:

HDSE/HDLE, Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

41 "..

Reviewed By:

Walkdown Comments:

Barrier thickness based on C-1 C1311. ** Sealant depth determined from inspection report.

Sketch:

FA: A..S Side 1 P141W1854 FA: A-9 Slde2 R

Steel

M-663-000 !7A, Revision WOI Page B8-176 of B -I 0 Penetration Seal Data Appendix:

B8 Photos:

P141W1854 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-9 (Side 2)

Fire Area A-9 (Side 2)

M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P141W1854 Fire Area (Side 1)

A-8 No issues within Heat Affected Zone Fire Area (Side 2)

A-9 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page 88-177 of 88-180 Appendix:

B8 Review Distances (Rere..,.,.M-663-000lTA. FlgUre7.2.3-1 )

18" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

Jin)

(In) 0.5 1741 4.7 6

1 1576 3.9 5.3 1.5 1426 3.3 4.6 2

1292 2.7 4

2.5 1171 2.1 3.5 3

1062 1.6 3

3.5 964 1.2 2.5 4

875 0.8 2.1 4.5 795 0.4 1.8 5

724 0.1 1.5 5.5 659 Contact 1.2 6

600 0.9 6.5 548 0.7 7

501 0.5 7.5 458 0.3 8

419 0.1 8.5 385 Contact No sketch required.

M-663-00017A, Revision WOl Penetration Seal Data Appendix:

88 Penetration #:

P141W1980 Penetration Type:

RB-SA Fire Area (Side 1 ):

A-16 Fire Area {Side 2): A-9 Loc./Eiev.: 2028'-6" M-OX Dwg: M-OX1920

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

2"

2. Opening Size:

26"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 18"P

12. Barrier Type:

F

4. Sealant Type:

HDSE/HDLE, Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth:

Assumed per detail Walkdown Comments:

Barrier thickness based on C-OC1411.

Sketch:

FA: A-16 Side 1 P141W1980

14. Pipe Insulated:

No Jeff Suter Prepared By:

Wayne Aregood Reviewed By:

\\?,. J ( I FA: A-9 Slde2 R

Steel

M-663-00017A, Revision WOI Penetration Seal Data Appendix:

B8 Photos:

P141W1980 Fire Area A-16 (Side 1 )

Fire Area A-16 (Side 1 )

Fire Area A-9 (Side 2)

Fire Area A-9 (Side 2)

M-663-00017A. Revision WOl Penetration Seal Data Heat Affected Zone Review:

P141W1980 Fire Area {Side 1)

A-16 No issues within Heat Affected Zone Fire Area {Side 2)

A*9 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page 88-180 of 88-J 80 Appendix; 88 Review Distances (Ra'-Ce ~17A. flglft7.2.3*1

)

18" Pipe L1 &L2 Temp. R1 Radius R2 Radius Oist. (ft) rF)

{In}

(In}_

0.5 1741 4.7 6

1 1576 3.9 5.3 1.5 1426 3.3 4.6 2

1292 2.7 4

2.5 1171 2.1 3.5 3

1062 1.6 3

3.5 964 1.2 2.5 4

875 0.8 2.1 4.5 795 0.4 1.8 5

724 0.1 1.5 5.5 659 Contact 1.2 6

600 0.9 6.5 548 0.(

7 501 0.5 7.5 458 0.3 8

419 l 0.1 8.5 385 Contact No sketch requir

i

,~'a-~

W&~tl.F CREEK

~/NUCLEAR OPERATING CORPORATION M-663-00017 A 9 Fire Protection Evaluation For Page 1 Penetrant Size Exceeding Typical Detail RB-1 or RB-8 Limitation Rev. No.

Prepared By Date Reviewed By Date W01

~~*

Jeff Suter

"-~/.dkf--

Wayne S Aregood 08/22/05 08/22/05

M-663-00017 A Attachment B9 Revision W01 Table of Contents Page 2 of 7 Revision Log................................................................................................................................... 3 1.0 Purpose............................................................................................................................... 4 2.0 Scope.................................................................................................................................. 4

3. 0 References.......................................................................................................................... 4 4.0 Evaluation........................................................................................................................... 5 5.0 Conclusions......................................................................................................................... 7 Appendix 89, Penetration Seal Data...................................................... (15 Total Pages)

M-663-000 17 A 9 Revision WO 1 Revision Reason for Revision WO 1 Original Issue Page 3 of 7 Revision Log

M-663-00017A Attachment B9 Revision WO 1 1.0 Purpose Page 4 of?

1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M-663-000 17 A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017. In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations -Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

M-663-00017 A Attachment B9 Revision W01 Page 5 of 7 5.0 Evaluation 5.1 Assessment of Condition to Design Requirements The penetration openings identified in Table I contain a pipe penetrant that exceeds the size limitation directly bounded by typical detail RB-1 or RB-8 from M-663-00017.

RB-1 is sealed with Radflex between silicone impregnated fiberglass boots. RB-8 is also a Radflex seal, were interference does not allow the installation of boot on one or both barrier sides. In this case a minimum 1-1/2" depth of Silicone Foam is utilized as a "plug" on the barrier side containing the interference. For both seal details, the maximum penetrant size is 1 0" in diameter. The topside boot for RB-1 may be omitted in floor/ceiling orientations.

Figures 1 and 2 depict typical RB-1 and RB-8 details, respectively.

TABLE I Penetrations with Penetrant Size Exceeding Detail RB-1 or RB-8 Limitations Penetration Communicating Typical Pipe Barrier Radflex Comments I Number Fire Areas Detail Penetrant Thickness Seal Disposition Side 1 Side 2 Diameter Depth P121S0277 A-1 A-4 RB-1 14" 19" *

> 19" See 5.2 P121S0278 A-1 A-4 RB-1 14" 19" *

> 19" See 5.2 P122S0347 A-1 A-2 RB-1 12" 22" *

> 22" See 5.2 P134W2053 A-8 A-24 RB-8 12" 36"

> 36" See 5.2 P142W1933 A-16 A-10 RB-8 18" 36"

> 36" See 5.2

  • Barrier thickness is based on top of slab to recessed portion of corrugated metal deck.

PENETRANT BAND CLAMP STEEL SLEEVE

<TYP.l

<OPTIONAL>

INVERTED BOOT ADHESIVE SEAL

<TYP.)

FLOOR WALL CONFIGURATION CONFIGURATION Figure 1, Typical Detail RB-1 (Reference M-663-00017)

M-663-00017A 9 Revision WO 1 lt<VERlW !lOOT IT'fP.I FLOOR OR 'WALL CONFIGURATION Figure 2, Typical Detail RB-8 (Reference M-663-00017) 5.2 Evaluation of Condition Page 6 of?

Radflex has been utilized in boundaries providing fire and radiation protection where mechanical penetrant movement is likely. To satisfy radiation attenuation requirements, Radflex has typically been installed to the full depth of the barrier.

The tested configurations bounding typical details RB-1 and RB-8 contained a 12" depth of Radflex within the barrier plane (Radflex was also present in boots beyond the barrier plane).

The Table I penetrations are provided with seal depths within the barrier plane that are at least 19". Consistent with the tested configurations, additional Radflex material is also present in the boots beyond the barrier plane.

Radflex has a density (150 lb/fn comparable to concrete, with excellent fire test performance regarding material char and thermal transmission to the unexposed side seal surface.

Considering this, and the substantial seal material depth increase over the tested configurations, there is reasonable assurance that penetrant thermal insult will not impact the fire resistive performance of the Table I penetrations. Therefore, the Table I penetrations are considered 3-hour F and T rated.

Conservatively, the heat affected zone for each of the Table I penetrations was reviewed in accordance wth the criteria and methodology of established in M 663-00017 A Section 7.2.3 for non-T rated penetrations.

The review, documented in Appendix 89, identified that no exposed insitu combustibles or PFSSD circuits are located within the heat affected zone for the Table I penetrations.

This further substantiates the acceptability of the Table I penetration seal configurations.

M-663-00017 A 9 Revision W01 5.3 Post Fire Safe Shutdown Impact Page 7 of 7 There is no impact to PFSSD systems or components as a result of this evaluation. The Table I penetrations are considered 3-hour F and T rated.

Additionally, as a conservative measure, comprehensive walkdown reviews for each of these penetrations revealed that no exposed insitu combustibles or PFSSD circuits are present within the heat affected zone for the Table I penetrations.

6.0 Conclusions Based on the above discussions, the Table I penetration seals are considered 3-hour F and T rated, consistent with regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements.

M-663-00017A Revision WOl Page 89-1 of 8 9 Penetration Seal Data Appendix:

B9 Penetration #:

P12150277 Penetration Type:

RB-1 Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-4 Loc./Eiev.:

1988'-0" M-OX Dwg: M-OX1211

1. Barrier Thickness:

19"

10. Annular Gap (smallest):

6"

2. Opening Size:

30" D

11. Gap between pen:

N/A

3. Penetrants:

(1) 14"P

12. Barrier Type:

F R

W

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NJA Prepared By:

8. Boot Condition (Acc!Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC1211.

Insulation appears to transition through seal area. Penetrant appears to be concentrically positioned and annulus is equal all the way around.

Sketch:

~f=;=~~~~r~R P121S02n

M-663-00017A, Revision WOJ Page 8 9-2 of 89-15 Penetration Seal Data Appendix:

89 Photos:

P12150277 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1) y Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-000l?A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P121S0277 Fire Area (Side 1)

A-1 No issues within Heat Affected Zone Fire Area (Side 2)

A-4 No issues within Heat Affected zone Side 1 Photo Side2 Photo Sketch Page B9-3 ofB9-15 Appendix:

B9 Review Distances (IWonoce ~17A.

Fl9'ft 7~3-1 I 14* Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist (ft)

(Of)

(In) 1in) 0.5 I 1721 4.6 5.9 1

1539 3.8 5.1 1.5 1377 3

4.4 2

1233 2.4 3,8 2.5 11 05 1.8 3.2 3

991 1.3 12.7 3.5 889 0.9 12.2 4

?99.

0.4 11.8 4.5 719 0.1 1.4 5

647

! Contact 1.1 5.5 583 I

0.. 8 6

527 I

0.6 6.5 477 0.3 7

432 0.1 7.5 392 Contact I

II No sketch requir d.

M-663-00017A Revision WOJ Page 89-4 of 89 Penetration Seal Data Appendix:

B9 Penetration #:

P121S0278 Penetration Type:

RB-1 Fire Area (Side 1):

A-1 Fire Area (Side 2):

A-4 Loc./Eiev.:

1988'-0" M-OX Dwg: M-OX1211

1. Barrier Thickness:

19"

10. Annular Gap (smallest):

2"

2. Opening Size:

22"0 11. Gap between pen:

N/A

3. Penetrants :

(1) 14"P

12. Barrier Type:

F R

W

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC12 11.

Sketch:

FA: A-1 SIDE 1 FA: A~

SIDE2 P121SOi78

M-663-00017A, Revision WOJ Page 89-5 of 89-15 Penetration Seal Data Appendix:

89 Photos:

P12150278 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P121S0278 Fire Area {Side 1)

A-1 No issues within Heat Affected Zone Fire Area (Side 2)

A-4

1. 4U3F1N, 1-112" Cond.: Not within Heat Affected Zone.

Side 1 Photo Side 2 Photo Sketch FA: A-t 5de1

  • c..
  • * *,...,T * :-

"* b

  • c.* '
  • * ~*- *.

Page 89-6 of B9-t 5 Appendix:

89 Review Distances (1Werenct~17A. f9Me 1.2.3-1)

L1 &l2 Oist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 7

7.5

+

  • ~

4&

  • n o

.a.....

. ~ ~. **

t 14" Pipe Temp. R1 Radius rt=>

(in) 1721 4.6 1539 3.8 1377 3

1233 2.4 1105 1.8 991 1.3 889 0.9 799 0.4 719 0.1 647 Contact 583 527 477 432 392 FA:M SJde2 R2 Radius (In) 5.9 5.1 4.4 3.8 3.2 2.7 2.2 1.8 1.4 1.1 0.8 0.6 0.3 0.1 Contact

M-663-00017A Revision WOI Page 89-7 of 8 9 Penetration Seal Data Appendix:

B9 Penetration #:

P122S0347 Penetration Type:

RB-1 Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-2 Loc./Eiev.:

1988'-0" M-OX Dwg: M-OX1221

1. Barrier Thickness:

22"

10. Annular Gap (smallest):

1"

2. Opening Size:

16"0 11. Gap between pen:

N/A

3. Penetrants:

(1 ) 12"P

12. Barrier Type:

F R

W

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC 1211.

Sketch:

FA: A-1 SIDE 1 I

M-663-00017A, Revision WOl Page 89-of 89-15 Penetration Seal Data Appendix:

89 Photos:

P122S0347 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-2 (Side 2)

Fire Area A-2 (Side 2)

M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P122S0347 Fire Area (Side 1)

A-1 No issues within Heat Affected Zone Fire Area (Side 2)

A-2 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch No sketch r Page 89-9 ofB9-15 Appendix:

89 Review 1Distances

(~foi.663-17A,FogLn 7.2.3-1

)

12*p~

L1 & L2 Temp. R1 Radius R2Radius Dist. (ft)

(OF)

(In)

{in) 0.5 1712 4.6 5.9 1

~524 3.7 5.1 1.5

~ 357 3

4.3 2

1209 2.3 3.'6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5 860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact

1.3 5

618 1

5.5 555 0.7 6

499 0.4 6.5 450 0.2 7

406 0

7.5 368 Contact

M-663-00017A, Revision WOI Pag B9-JOofB9-I-Penetration Seal Data Appendix:

B9 Penetration#:

P134W2053 Penetration Type:

RB-8 Fire Area (Side 1): A-8 Fire Area (Side 2): A-24 Loc./Eiev.: 2012'-3" M-OX Dwg: M-1 X1921

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

2"

2. Opening Size:

18"0

11. Gap between pen :

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F w

4. Sealant Type:

Radflex/foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

N/A

14. Pipe Insulated:

No

6. Damming Side 2:

N/A Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Wayne Aregood

9. Sealant Depth:

34" H Reviewed By:

Walkdown Comments:

Barrier thickness determined by Drawing C-OC 1341 (wsa). ** Sealant depth determined by inspection report.

Sketch:

Fk A-3 Slde1 P13AW2053 F

  • A*24 Slde2

M-663-000J ?A, Revision WOI Pag 89-11 of89-15 Penetration Seal Data Appendix:

89 Photos:

P134W2053 Fire Area A-8 (Side 1 )

Fire Area A-8 (Side 1)

Fire Area A-24 (Side 2)

Fire Area A-24 (Side 2)

M-663-00017A, Revision WOJ Penetration Seal Data Heat Affected Zone Review:

P134W2053 Fire Area (Side 1)

A-8

1. 2" Concl. 5U3A 1T, utility power. not within Heat Affected Zone
2. Two (2) 112" lighting conduit, nol within Heat Affected Zone Fire Area (Side 2)

A-24 No Issues within Heat Affected Zona Side 1 Photo Sketch fA:,..

Side1 Side2Photo Page B9-12 of B9-15 Appendix:

B9 Review Distances (Rtfelwloe M-U3-000i7A. ~

7.2.3*1 )

L1 &L2 Dlst. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 7

7.5 12R Pipe Temp. R1 Radius rFl (in) 1712 4.6 1524 3.7 1.357 3

1209 2.3 1078 1.7 962 1.2 860 0.7 769 0.3 689 Con tad.

618 555 499 450 406 368 FA: A*2A

    • z R2 RadiUI (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1.7 u

1 0.7 0.4 0.2 0

Contact I

I I

I I

M-663-00017A, Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2035'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P142W1933 R8-8 36" 24"0 (1) 18"P Foam/Radflex N/A

6. Damming Side 2:

N/A

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth:

36.5" Radflex Walkdown Comments:

Pag B9-13 of B9-I -

Appendix:

B9 Fire Area (Side 1 ):

A-16 Fire Area (Side 2): A-10 M-OX Dwg: M-1X1919

10. Annular Gap (smallest):

1-1/2" 11. Gap between pen:

N/A

12. Barrier Type:

F R

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Yes Jeff Suter Prepared By:

Wayne Aregood Reviewed By:

Barrier thickness based on drawing C-1 C 1421. 1-1/2" foam damming per original inspection record and 2 sleeve extension will produce a 36-1/2" radrlex seal (wsa ). Sleeve extender per FCR 1-881-091.

Sketch:

FA: A-16 Side 1 P142W19l3

M-663-00017A, Revision WOI Page 8 9-14 ofB9-15 Penetration Seal Data Appendix:

B9 Photos:

P142W1933 Fire Area A-16 (Side 1)

Fire Area A-16 (Side 1)

Fire Area A-10 (Side 2)

Fire Area A-10 (Side 2)

M-663-000l?A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P142W1933 Fire Area (Side 1)

A-16 No Issues within Heat Affected Zone Fire Area (Side 2)

A-1 0 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page B9-J5 ofB9-15 Appendix:

'89

!Review Distances (Refelw1ce M-663-00017A. f9lre 7.2.3-1 1 18" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist (ft)

J"F)

(in)

(in) 0.5 1741 4.7 6

1 1576 3.9 5.3 1.5 1426 3.3 4.6 2

1292 2.7 4

2.5 1171 2.1 3.5 3

1062 1.6 3

3.5 964 1.2 2.5 4

875 0.8 2.1 4.5 795 0.4 1.8 5

724 0.1 1.5 5.5 659 Contact 1.. 2 6

600 0.9 6.5 548 0.7 7

501 0.5 7.5 458 0.3 8

419 0.1 8.5 385 Contact No sketch requ*r

Page 1 i~

1;:2

\\

CREEK wr~*t.F

~~~~**

-.\\r /NUCLEAR OPERATING CORPORATION M-663-00017 A 10 Fire Protection Evaluation For Penetration Openings With Steel Plates Rev. No.

Prepared By Date Reviewed By Date W01

~~~ 08/20/05 ~~

08/20/05 Wayne S Aregood Jeff Suter

M-663-00017 A Attachment B 1 0 Revision WO 1 Table of Contents Page 2 of?

Revision Log................................................................................................................................... 3 1.0 Purpose............................................................................................................................... 4 2.0 Scope.................................................................................................................................. 4 3.0 References.......................................................................................................................... 4 4.0 Evaluation........................................................................................................................... 5 5.0 Conclusions......................................................................................................................... 7 Appendix 810-1, Penetration Seal Data..................................................... (6 Total Pages)

M-663-00017 A Attachment B 1 0 Revision W01 Revision Reason for Revision W01 Original Issue Page 3 of?

Revision Log

M-663-00017A Attachment B 1 0 Revision W01 1.0 Purpose Page 4 of?

1.1 The purpose of this document is to evaluate existing penetration seals that are not directly b'ounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M663-00017A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M663-00017.

In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April24, 1986 3.2 NRC Information Notice 88-04, "Inadequate Qualification and Documentation of Fire Barrier Penetration Seals".

3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 Underwriters Laboratory Fire Resistance Directory (UL System CAJ0010), 2002 Edition 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

M-663-00017 A Attachment B 1 0 Revision WO 1 Page 5 of7 5.0 Evaluation Penetration Number P134W2653 P141S1034 5.1 Assessment of Condition to Design Requirements Each penetration opening identified in Table I was sealed with a typical detail from M-663-00017, with all or part of the annulus opening sealed on at least one barrier side by a welded steel plate. The steel plate protection ensures that that the opening portion protected by steel will not allow the passage of flame or hose stream comparable to UL System CAJ001 0. This UL system, reveals that a minimum 0.057" (16 gauge) thick steel plate on one barrier side provides a :>

hour Fire (F) rated seal. In all cases, the steel plate thickness for the Table I penetrations exceed 0.057". Also, the plates are physically attached (welded) to sleeves/penetrant such that fire exposure would not distort the plate protective closure. However, there is no direct testing demonstrating a Temperature (T) rating for the steel plates.

Therefore, further review is required to assess acceptability.

Additionally, the penetrant size for P141S1034 exceeds that allowed by assigned typical detail M-1. This issue is addressed within this evaluation, since the heat affected zone review for the steel plate effectively bounds the review necessary for the large pipe penetrant.

Table I identifies penetrations with steel enclosure plates. Penetration inspection results are documented in Appendix B 10.

TABLE I Penetrations with Steel Closure Plates Communicating Typical Primary Penetrant Steel Plate Fire Areas Detail Opening Size Exposed Comments/Disposition:

Side 1 Side 2 Size Area A-6 T-2 FB-1 10" (1) 3/4" p 50 in 2

FB-1 seal with multiple (1)1/2"P penetrants and the secondary annulus gap sealed with steel plates on both sides of the barrier.

See paragraph 5.2.

A-16 A-8 M-1 24" 18" p 198 in 2

M-1 seal with a large bore pipe penetrant and the topside annulus sealed with closure plate. Bottom side damming found acceptable. See paragraph 5.2.

M-663-00017 A Attachment B 1 0 Revision W01 5.2 Evaluation of Condition Page 6 of?

Penetration P134W2653 is a wall seal that is contains two separate penetration sleeves with end plates welded to the embedded sleeve and to the penetration sleeve. This design creates a secondary annular gap that is closed by a welded

%" steel plate on both sides of the barrier. The primary penetration sleeve is sealed in accordance with the limitations of the FB-1 typical detail, and is bounded.

Therefore, this evaluation mly applies to the secondary annulus enclosure plates that are integral to the barrier and directly affect T rating requirements.

Penetration P141 S 1034 is a floor seal that is constructed with a single sleeve.

The topside of the sleeve is closed with a Yz" steel plate, welded from the pipe penetrant to the sleeve, thus establishing a pipe restraint at this location. This design creates a single annulus gap that is also sealed with an M 1 (Silicone Foam with bottom side damming) typical detail. Additional Silicone Foam fill could not be determined from the original inspection documents. Therefore, the sealant depth is assumed to be the minimum required 6". Because the annulus is sealed with at least 6" of RTV Foam with 1" damming board on the bottom side, it is reasonable to conclude that the topside steel plate will enhance the F rating performance of the installed M 1 detail. However, the penetration is not considered T rated due to the large unbounded penetrant size.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix 810, were conducted for each penetration of concern.

This review was completed in accordance with the criteria and review methodology established in M663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that no exposed insitu combustibles or PFSSD circuits are located within the heat affected zone.

Each of the penetrations satisfies the review criteria of M-663-00017 where T rating requirements are not met.

Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation. The Table I penetrations are 3-hour F rated. The comprehensive walkdown review for each of these penetrations revealed that no exposed insitu combustibles or PFSSD circuits are regatively affected by the non T rated penetrations.

M-663-00017 A 10 Revision W01 6.0 Conclusions Page 7 of?

Based on the above discussions, it is reasonable to conclude that the Table I penetration seals are acceptable as 3-hour F rated and will perform their intended function, regardless of not achieving a T rating.

The penetration seals satisfy regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements, to prevent spread of fire from one fire area to another. It has also been determined through this evaluation that the lack of a T rating will not affect the plant's ability to achieve and maintain PFSSD.

M -663-00017 A, Revision WO I Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2007'-6"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P134W2653 FB-1 24" 6"D (1)3/4""P. (1)1/2"P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept Page 8 I 0-1 of 8 I 0-6 Appendix:

B10 Fire Area (Side 1): A-6 Fire Area (Side 2):

T-2 M-OX Dwg: M-1X1950

10. Annular Gap (smallest):

1" 11. Gap between pen:

1/2"

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Sleeve annulus is sealed with welded 1/4" plate (from wall sleeve to penetrant sleeve) both sides. Internal sleeve space configuration is unknown.

Sketch:

FA:,t,.(;

Sl<ltl 1 4!' (ryf}_ : (>

J,

. !?.* -., "

Q

  • . a:

A,

Q Q

~

~

t?.

l.>

FA: T*2 Slde 2

M-663-00017A Revision WOl Penetration Seal Data Photos:

P134W2653 Fire Area A-6 (Side 1)

Fire Area T-2 (Side 2)

Page l 0-2 of B I 0-6 Appendix:

810 Fire Area A-6 (Side 1)

~

,.t'~

a*

'1

  • ~~.
  • ~~....

.~.

?

/ /

~'

(.

t

,r Fire Area T-2 (Side 2)

M-663-0001 7A, Revision WOJ Penetration Sea'l Data Heat Affected Zone Review:

P134W2653 Fire Area (Side 1)

No Issues with Heat Affected Zone Fire Area (Side 2)

T -2 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page Bl0-3 ofBI0-6 Appendix:

810 Review Distances (RefeNnce M-663-00017A. F9R 7..2.3-1) 1/2" & 3/4" P~s

_12" Pipe Data Usedl l1 &L2 Temp. R1 Radius R2 Radius Dlst. (ft)

("F)

(in)

(inl 0.5 1557 3.9 5.2 1

1262 2.5 3.9 1.5 1026 1.5 2.8 2

836 0.6 2.0 2.5 684 Contact 1.3 3

562 0.7 3.5 '

465 0.3 4

386 Contact No sketch r quir

M-663-00017A, Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2026'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P141S1034 M-1 20" 24"0

{1) 18"P Foam Page 8 1 0-4 of 8 I 0-6 Appendix:

B10 Fire Area (Side 1 ): A-1 6 Fire Area (Side 2): A-8 M*OXDwg: M-1 X1411

10. Annular Gap (smallest):

1/4"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Steel plate welded to sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush with barrier Jeff Suter

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth:

6" Reviewed By:

Walkdown Comments:

Slab thickness based on C-OC1411. Top side of penetration is covered with a welded steel plate Foam depth is assumed to be the 6" minimum allowed for a mechanical detail. Original Inspection Record documents 6" blind seal depth due to welded steel anchor plate (wsa).

Sketch:

FA: A*16 Side1 P141S1034 1*e.,~<! (, ""'

t.

FA: Ml Side 2

M-663-00017A Revision WOI Page BJ 0-5 of B I 0-6 Penetration Seal Data Appendix:

810 Photos:

P14151034 Fire Area A-16 (Side 1 )

Fire Area A-16 (Side 1)

Fire Area A-8 (Side 2)

Fire Area A-8 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P14151034 Fire Area (Side 1)

A-16 No issues within Heat Affected Zone Fire Area (Side 2)

A-8 No issues within Heat Affected Zone Side 1 Photo Side2Photo Sketch No sketch r Page BI0-6 ofBl0-6 Appendix:

810 Review Distances (Ref-M-663-00017A. Fi9UN 7.2.3-11 I

18" Pipe I L1 & L2 Temp. R1 Radius R2 Radius

' Dist. (ft)

("F)

(in)

(in) 0.5 1741 4.7 6

1 1576 3.9 5.3 1.5 1426 3.3 4.6 2

1292 2.7 4

2.5 1171 2.1

, 3.5 3

1062 1.6

.3 3.5 964 1.2 2.5 4

875 0.8 2.1 4.5 795 OA 1.8 5

724 0.1 1.5 5.5 659 Contact 12 6

600 0.9 6.5 548 0.7 7

l 5o1 0.5 7.5 458 0.3 8

419 0.1 8.5 385 Contact

Rev. No.

W01 W~rl.F CREEK

\\r. NUCLEAR OPERATING CORPORATION M-663-00017 A Attachment B 11 Fire Protection Evaluation For Penetrations Interfacing With Seismic Gap Seals Prepared By Date Reviewed By A-~~~

08/19/05

~~*

Wayne S Aregood Jeff Suter Page 1 Date 08/19/05

M-663-00017A Attachment B 11 Revision WO 1 Table of Contents Page 2 of 7 Revision Log................................................................................................................................... 3 1.0 Purpose............................................................................................................................... 4 2.0 Scope.................................................................................................................................. 4

3. 0 References.......................................................................................................................... 4 4.0 Evaluation........................................................................................................................... 5 5.0 Conclusions......................................................................................................................... 7 Appendix B 11, Penetration Seal Data...................................................... ( 12 Total Pages)

M-663-00017A 11 Revision WO 1 Revision Reason for Revision W01 Original Issue Page 3 of?

Revision Log

M-663-000 17 A Attachment B 11 Revision WO 1 1.0 Purpose Page 4 of?

1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M663-00017, or the penetration seal configuration is unique enough to potentially affect performance of the penetration seal. This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M663-00017A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M663-00017.

In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, "Inadequate Qualification and Documentation of Fire Barrier Penetration Seals".

3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 RER 2004-002, Reportability Review for PIR 2004-0234 3.7 PIR 2004-0234, Potential Unrated Seismic Gap Seal Design Detail 5 from C-1029.

4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

M-663-00017 A Attachment B 11 Revision WO 1 Page 5 of 7 4.2 It is assumed that the entire Table I penetration seal and seismic gap interfaces were installed with similar vertically positioned ceramic fiberboard separators as found in the seismic gap between Penetration Seals P621S0179 and P621S0180. These seismic gap interfaces were examined internally during the seismic gap interface exploratory effort conducted in response to seismic gap seal continuity concerns documented in References 3.6 and 3.7. The intrusive inspections revealed vertically positioned ceramic fiberboard separators between the seismic gap seal and the Silicone Foam seal.

This is an acceptable assumption based on installation techniques and practices that would necessitate the use of ceramic fiberboard to ensure containment of sealant material during initial Silicone Foam seal installation.

5.0 Evaluation 5.1 Assessment of Condition to Design Requirements Penetration Number P621S0179 P621S0180 P631S0119 Each penetration opening identified in Table I was sealed with an approved M-663-00017 typical detail. The seal interfaces with a fire rated seismic gap seal detail S~2. Each penetration seal type is independently bounded by the referenced typical detail. However, the Silicone Foam seal interface with a fire rated seismic gap seal is not directly bounded by testing. Refer to Appendix 811 for relevant Table I penetration seal data.

TABLE I Penetration Seal and Seismic Gap Interfaces Communicating Typical Penetrating Fire Areas Detail Items Comment/Disposition:

Side 1 Side2 F-4 F-2 E-2A Conduits:

9" Silicone Foam with top cap and two (1) 1'1:." Cond.

separate bottom side damming boards.

(2) 2" Cond.

Vertical ceramic fiber damming board (1) 3" Cond.

positioned on both sides separating seal from seismic gap design. Seismic gap and Silicone Foam interface was intrusively inspected in response to Ref 3.6 and 3.7.

F-4 F-3 M-6A Spare 9" Silicone Foam with top cap and two separate bottom side damming boards.

Vertical ceramic fiber damming board positioned on both sides separating seal from seismic gap design. Seismic gap and Silicone Foam interface was intrusively inspected in response to Ref 3.6 and 3.7.

F-7 F-4 E-2A Conduits:

9" Silicone Foam with top cap and two (3) 2" Cond.

separate bottom side damming boards.

(1) 3" Cond.

Vertical ceramic fiber damming board positioned on both sides separating seal from seismic gap design.

M-663-00017A Attachment B 11 Revision WO 1 Page 6 of?

Penetration Communicating Typical Penetrating Number Fire Areas Detail Items Comment/Disposition:

Side 1 Side2 P631S0120 F-7 F-4 E-2A Conduits:

9" Silicone Foam with top cap and two (1) 1'h" Cond.

separate bottom side damming boards.

(1) 3" Cond.

Vertical ceramic fiber damming board positioned on both sides separating seal from seismic gap design.

P641S0051 F-1 F-7 E-2A Conduits:

9" Silicone Foam with bottom side (1) 1 'h" Cond.

damming board. Vertical ceramic fiber (1) 3" Cond.

damming board positioned on both sides separating seal from seismic gap design.

P641S0052 F-1 F-6 E-2A Conduits:

9" Silicone Foam with bottom side (1) 1 'h" Cond.

damming board. Vertical ceramic fiber (2) 2" Cond.

damming board positioned on both sides (1) 3" Cond.

separating seal from seismic gap design.

5.2 Evaluation of Condition The penetrations identified in Table I have unique design conditions where floor block-outs are incorporated within the seismic expansion gap of the Fuel Building to Auxiliary building interface.

These common penetration and seismic gap openings were sealed with a fire rated detail in accordance with M-663-00017.

Ceramic fiberboard was vertically positioned on the sides of the blackout opening interface with the seismic gap in order to contain the Silicone Foam during seal installation.

The existence of the added vertical ceramic fiberboard was confirmed during the seismic gap inspection and rework effort as discussed in Section 4.2. The vertically positioned ceramic fiberboard serves the following two significant functions:

It prevents the Silicone Foam from spilling or expanding into the seismic gap air space between the topside ceramic fiber fill, and the bottom side backing rod and Dymeric Caulk.

It separates the two designs (sealant materials) during fire exposure minimizing impact of performance characteristics (material char and/or consumption) from one another.

Placement of the vertical ceramic fiberboards along the sides of the opening provides a basis for an acceptable 3-hour fire rated configuration for both the penetration seal and seismic gap interfaces. The ceramic fiberboard is inert and does not change in physical characteristics when subjected to direct flame impingement.

It will maintain the interface and sealant stability for both configurations during fire exposure.

The primary seismic gap sealant (compressed ceramic fiber) tightly abuts the vertical ceramic fiberboard, thus establishing physical separation between both primary and secondary sealants that will minimize consumption of either penetration sealant (Silicone Foam) or seismic gap design (Dymeric compounds).

Both these designs utilize fire resistant and compressible materials as the primary sealant and are both 3-hour fire rated. The addition of the vertical ceramic fiberboards between the seismic gap detail and the penetration seal material ensures that both designs will

M-663-00017 A Attachment B11 Revision WO 1 Page 7 of?

perform independent of each other during fire exposure and_ plant environments such as building moments.

Additionally, ceramic fiberboard (damming) *is typically used at WCNOC for penetration seal damming and has been extensively tested as part of penetration seal assemblies in accordance with ASTM E119 time and temperature curves with consistent and acceptable results.

Based on the above discussions, it is reasonable to conclude that both seal designs remain bounded and the addition of the vertical damming board ensures that the interface will not experience any negative interactions during fire exposure or plant environments such as building moments.

Therefore, the seismic gap and penetration seal interfaces with ceramic fiberboard are acceptable.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation. The penetration seal and seismic gap interfaces identified in Table I will perform their intended function for a 3-hour duration.

6.0 Conclusions Based on the above discussions, it is reasonable to conclude that the Table I penetration seals are 3-hour F and T rated, which satisfies regulatory requirements and commitments, as well as WCNOC Fire Protection Program requirements to prevent spread of fire from one fire area to another.

M-663-000 17 A Revision WO 1 Page 8 11-I of 8 I I -12 Penetration Seal Data Appendix:

B11 Penetration #:

P621S0179 Penetration Type:

E-2A Fire Area (Side 1 ):

F-4 Fire Area (Side 2): F-2 Loc./Eiev.:

2025'-0"'

M-OX Dwg: M-OX6211

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

2"

2. Opening Size:

12"X3'-0"

11. Gap between pen:

2"

3. Penetrants:

(4) ER

12. BarrierType:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Concrete*

5. Damming Side1 :

Top Cap/Flush

14. Pipe Insulated:

N/A

6. Damming Side 2:

Not Attached Wayne Aregood

7. Damming Continuity (Ace/Rei):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9" Reviewed By:

Walkdown Comments:

  • Seismic Gap Detail interface. Changed OTY of penetrants from "(3) ER" to "(4) ER". There are two individual bottom side damming boards installed, one is friction fitted within the opening and the other is seen in the bottom side photo. This was confirmed during the Seismic Gap destructive examination effort.

Sketch:

FA! F-4 Slde1 FA! F*%.

Slde:Z

M-663-00017A Revision WOl Page B I 1-2 of B I 1-12 Penetration Seal Data Appendix:

811 Photos:

P62150179 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1) 11 Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017A, Re ision WOl Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2025'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:

P621S0180 M-6A 10" 12"X3'-0" SPARE Foam Top Cap Flush Page B 11-3 of B I 1-12 Appendix:

B11 Fire Area (Side 1 ):

F-4 Fire Area (Side 2):

F-3 M-OX Dwg: M-OX6211

10. Annular Gap (smallest):

N/A 11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Concrete *

14. Pipe Insulated:

N/A

6. Damming Side 2:
  • Flush w/Q-Deck Valley Wayne Aregood
7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Ace/Rei):

N/A Jeff Suter

9. Sealant Depth:

9" Reviewed By:

Walkdown Comments:

  • Seismic Gap Detail interface. There are two individual bottom side damming installed, one is friction fitted within the opening and the other is seen in the bottom side photo. This was confirmed during the Seismic Gap destructive examination effort.

Sketch:

FA: F-4 Side 1 P621S0180 l:lA mtntNii ---.

~*)

FA: F-3 Slde2

M-663-00017 A Revision WOJ Page B 11 -4 of B I 1-12 Penetration Seal Data Appendix:

811 Photos:

P621S0180 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1) 17 Fire Area F-3 (Side 2)

Fire Area F-3 (Side 2)

M -663-000 17 A, Revision WO I Page 8 I 1-5 of 8 I 1-12 Penetration Seal Data Appendix:

B 11 Penetration #:

P631S0119 Penetration Type:

E-2A Fire Area (Side 1 ):

F-7 Fire Area (Side 2): F-4 Loc.!Eiev.: 2046'-6" M-OXDwg: M-1X6311

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

2"

2. Opening Size:

12"X 2'-6" 11. Gap between pen:

1-1/2"

3. Penetrants :

(4)ER

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:
  • Concrete
5. Damming Side1 :

Foam w/Top cap flush

14. Pipe Insulated:

NIA

6. Damming Side 2:
  • Flush w/Q-Deck Wayne Aregood
7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9" Reviewed By:

Walkdown Comments:

Seismic Gap Detail interface. There are two individual bottom side damming installed, one is friction fitted within the opening and the other is seen in the bottom side photo. This was confirmed during the Seismic Gap destructive examination effort.

Sketch:

P631S0119 f t

~~~q~~q~~ r r FA: F-A Sld&2

Page B I 1-6 of B I 1-J 2 Penetration Seal Data Appendix:

811 Photos:

P631S0119 Fire Area F-7 (Side 1)

Fire Area F-7 (Side 1)

Fire Area F-4 (Side 2)

Fire Area F-4 (Side 2)

M -663-000 17 A, Revision WO I Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2046'-6"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P631S0120 E-2A 10" 12"X2'-0" (2)ER Foam Page B I 1-7 of B I 1-12 Appendix:

B1 1 Fire Area (Side 1 ): F-7 Fire Area (Side 2): F-4 M-OX Dwg: M-1X6311

10. Annular Gap (smallest):

3" 11. Gap between pen:

3"

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
  • concrete
5. Damming Side1:

Foam w/Top cap nush

14. Pipe Insulated:

N/A

6. Damming Side 2:
  • Flush w/Q-Deck Wayne Aregood
7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9" Reviewed By:

Walkdown Comments:

  • Seismic Gap Detail interface. There are two individual bottom side damming installed, one is friction fitted within the opening and the other is seen in the bottom side photo. This was confirmed during the Seismic Gap destructive examination effort.

Sketch :

FA:. F*7 Sid& 1 P631S012D FA: F-4 Side2

M-663-000 I 7 A Revision WO I Page B 11-8 of 8 I I -12 Penetration Seal Data Appendix:

811 Photos:

P631S0120 Fire Area F-7 (Side 1)

Fire Area F-7 (Side 1)

Fire Area F-4 (Side 2)

Fire Area F-4 (Side 2)

M-663-00017A Revision WOJ Page 8 I 1-9 of B 1 I -12 Penetration Seal Data Appendix:

B11 Penetration #:

P641S0051 Penetration Type:

E-2A Fire Area (Side 1):

F-1 Fire Area (Side 2): F-7 Loc./Eiev.: 2064'-0" M-OX Dwg: M-OX6411

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

3"

2. Opening Size:

1 0-518"X3'-6"

11. Gap between pen:

15"

3. Penetrants:

(2)ER

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Concrete

5. Damming Side1 :

Foam flush w/Siab

14. Pipe Insulated:

N/A

6. Damming Side 2:

Flush w/Q-Deck Valley Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9" Reviewed By:

Walkdown Comments:

  • Seismic Gap Detail interface. There are two individual bottom side damming installed, one is friction fitted within the opening and the other is seen in the bottom side photo. This was confirmed during the Seismic Gap destructive examination effort.

Sketch:

FA: f*1 Side 1

~T~Il ~-2.

C"T'fP) ~

!iiiOcn>

r-SU l'\\.A""'\\111l'UJ ~

f'O"P.n'\\ (T'Cz\\

fA: F-7 Side 2

M-663-000l7A, Revision WOJ Page B I 1-1 0 of B I 1-12 Penetration Seal Data Appendix:

8 11 Photos:

P641S0051 Fire Area F-1 (Side 1)

Fire Area F-1 (Side 1)

Fire Area F-7 (Side 2)

Fire Area F-7 (Side 2)

M-663-00017A Revision WO l Page Bil -l I ofB J 1-12 Penetration Seal Data Appendix:

811 Penetration #:

P641S0052 Penetration Type:

E-2A Fire Area (Side 1): F-1 Fire Area (Side 2):

F-6 Loc./Eiev.:

2064'-0" M-OX Dwg: M-OX6411

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :
6. Damming Side 2:

1 0" 12"X3'-0" (4)ER Foam Foam Flush w/slab Foam Flush w/Q-Deck Valley

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

NIA

9. Sealant Depth:

9" Walkdown Comments:

10. Annular Gap (smallest):

4" 11. Gap between pen:

2"

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

NIA Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Concrete Seismic Gap Detail interface. There are two individual bottom side damming installed, one is friction fitted within the opening and the other is seen in the bottom side photo. This was confirmed during the Seismic Gap destructive examination effort.

Sketch:

FA. F-1 Side 1 i>trTAIL sq--z. ----.

l'fP. ScJr~

ltli5S FA: F-6 Slde2

M-663-000 17 A Revision WO I Page BJ 1-12 ofBII-12 Penetration Seal Data Appendix:

B11 Photos:

P641S0052 Fire Area F-1 (Side 1)

Fire Area F-1 (Side 1)

Fire Area F-6 (Side 2)

Fire Area F-6 (Side 2)

Rev. No.

W01

~

j'l.._

W rl.F CREEK

~lr. NUCLEAR OPERATING CORPORATION M-663-00017 A 12 Fire Protection Evaluation For Penetration Openings Crediting Calcium Silica and Fiberglass Piping Insulation Prepared By Date Reviewed By

~

.v.t ct:kf-08/20/05

~~*

Wayne S Aregood Jeff Suter Page 1 Date 08/20/05

M-663-000 17 A Attachment B 12 Revision W01 Table of Contents Page 2 of 11 Revision Log................................................................................................................................... 3 1.0 Purpose............................................................................................................................... 4 2.0 Scope.................................................................................................................................. 4 3.0 References.......................................................................................................................... 4 4.0 Evaluation........................................................................................................................... 5 5.0 Conclusions....................................................................................................................... 11 Appendix 812, Penetration Seal Data................................................... (24 Total Pages)

M-663-00017 A Attachment B 12 Revision W01 Revision Reason for Revision W01 Original Issue Page 3 of 11 Revision Log

M-663-000 17 A Attachment B 12 Revision WO 1 1.0 Purpose Page 4 of 11 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 The Table I and II Penetration Seals in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M663-00017A for a cross-reference list of penetrations within Table I and II that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M663-00017.

In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations -Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 M-663-00111, Promatec Penetration Closure Heat Transfer Report, Rev. 3 3.7 CTP-1001, (M-663-00082) Fire Qualification Test on Silicone Foam Floor Penetration Seals, Rev. W01 3.8 AP 10-102, Control Of Combustible Materials, Rev. 9 3.9 AP 10-104, Breach Authorization, Rev. 19 3.10 Bruin Plastics Company Inc., Material Safety Data Sheet for VRP 1862 9X12, Yellow Standard Herculite Vinyl Laminated Fabric or Vinyl Coated Mesh Polyester Scrim

M-663-00017A Attachment B 12 Revision WO 1 Page 5 of 11 3.11 M-162C, Specification for Non-metallic Thermal Insulation for Piping and Equipment Located In Auxiliary Building, Control Building, Diesel Generator Building, Fuel Building, and Radwaste Building For The Wolf Creek Generating Station, Rev. 19 3.12 DDCN M-162C-19-1 0,

Subject:

Pipe Insulation Control to Ensure Penetration Seal Fire Resistance Rating Maintained 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

5.0 Evaluation 5.1 Assessment of Condition to Design Requirements Penetration Number P133S0799:

with a single 12" pipe penetrant P134S0860:

with a single 12" pipe penetrant Initial typical detail assignment for the penetrations identified in Tables I and II resulted in a condition where at least one M663-00017 typical detail critical parameter was not satisfied for each penetration seal.

In these cases, the nonconforming parameter was penetrant size. Due to the lack of industry testing, penetration seals identified in Tables I and II require further evaluation to determine actual fire rating and to document the basis for that assigned rating.

Refer to Appendix B 12 for relevant penetration seal data.

TABLE I Radflex Penetrations Crediting Insulation Communicating Fire Areas Typical Barrier Sealant Comments/Disposition Side 1 Side 2 Detail Thickness Depth (Inches)

A-25 A-1 RB-1 12" Assumed 1;1, thick (X) Calcium Silica Per Pipe Insulation provides Detail additional protection from direct flame impingement and provides basis for "F" Rating.

(Ref. M-162C, D-8)

A-24 A-1 RB-1 12" Assumed 2" thick (X) Calcium Silica Per Pipe Insulation provides additional protection from Detail direct flame impingement and provides basis for "F" Rating.

(Ref. M-162C, D-8)

M-663-00017 A 12 Revision W01 Penetration Number P114W0423:

with a single 8" pipe penetrant P125W2432:

with a single 8" pipe penetrant P125W2434:

with a single 8" pipe penetrant P13250683:

with a single 24" pipe penetrant P13250684:

with a single 24" pipe penetrant P132W1433:

with a single 8" pipe penetrant Page 6 of 11 TABLE II Silicone RTV Foam Penetrations Crediting Insulation Communicating Fire Areas Typical Barrier Sealant Comments/Disposition Side 1 Side 2 Detail Thickness Depth (Inches)

A-1 A-6 M-1 12" Assumed 1 ;!,thick (AS) Fiberglass Per Pipe Insulation provides additional protection from Detail direct flame impngement on both sides of the barrier and provides basis for "F" Rating.

(M-162C, D-19c)

A-1 A-33 M-1 24" Assumed 1 ;!,thick (AS) Fiberglass Per Pipe Insulation provides additional protection from Detail direct flame impingement on the A-1 side of the barrier and provides basis for "F" Rating.

(M-162C, D-19j)

A-6 A-33 M-1 24" Assumed 1 ;!,thick (AS) Fiberglass Per Pipe Insulation provides additional protection from Detail direct flame impingement on the A-6 side of the barrier and provides basis for "F" Rating.

(M-162C, D-19c)

A-8 A-1 M-6A 10" 11" 1 ;!,thick (AS) Fiberglass Pipe Insulation provides additional protection from direct flame impingement on both sides of the barrier and provides basis for "F" Rating.

(M-162C, D-19j)

A-8 A-1 M-1 10" Assumed 1 Y:!' thick (AS) Fiberglass Per Pipe Insulation provides additional protection from Detail direct flame impingement on both sides of the barrier and provides basis for "F" Rating.

(M-162C, D-19f)

A-8 CC-1 M-1 24" Assumed 1 ;!,thick (X) Calcium Silica Per Pipe Insulation provides additional protection from Detail direct flame impingement on both sides of the barrier and provides basis for "F" Rating.

(Ref. M-162C, D-17)

M-663-000 17 A Attachment B 12 Revision W01 Page 7 of 11 5.2 Evaluation of Condition 5.2.1 Radflex Penetrations (Table I)

Radflex seal designs with pipe penetrants greater than 2" have not been specifically fire tested in accordance with ASTM 5-119.

M663-00017, RB-1 Detail evaluated penetrant size and concluded that 1 0" pipe penetrant with or without pipe insulation is 3-hour fire (F) and temperature (T) rated. This determination was based on the comparison of Radflex material performance to Silicone RTV Foam, with a resulting conclusion that that Radflex is superior to Silicone RTV Foam when subjected to fire exposure.

It is important to note that this evaluated conclusion was based on bare pipe exposure, which is considered more severe than pipe protected with Calcium Silica type insulation.

Table I penetration seals have a single 12" pipe penetrant that is slightly larger than that evaluated in M-663-00017, Detail RB-1.

Therefore, further review is required to assess acceptability.

Field inspection and review of the penetrations identified in Table I revealed that each penetration seal incorporates Calcium Silica pipe insulation.

The Calcium Silica piping insulation was initially installed due to high system temperatures and the potential to degrade the sealant material after prolonged system temperature exposures. It is concluded that F rating requirements can be satisfied if the Calcium Silica pipe insulation is credited for providing added protection from the effects of conductive and radiant thermal propagation to the unexposed side of the barrier.

Pipe penetrants that utilize Calcium Silica are continuously protected through and on both sides of the barrier, thus significantly reducing thermal insult during fire exposure to the installed penetrants.

M663-00111 demonstrated that insulating pipe penetrants through the seal material would significantly reduce thermal exposure to the seal material, thus preserving seal characteristics for prolong system temperature exposures.

This report documented a significant drop in interface temperatures as a result of installed piping insulation. The actual drop varies depending on postulated system temperatures and insulation thickness, but in all cases the reported temperature drop is significant.

This thermal benefit logic can be applied to fire exposure when considering that the pipe penetrants being evaluated are only slightly larger than that previously evaluated in M-663-00017, Detail RB-1.

Furthermore, Calcium Silica type insulation is not consumed during fire exposure, as demonstrated in fire test CTP-1 001, Penetration 5.1. This fire test contained a 4" pipe penetrant that was insulated with 1" thick Calcium Silica through a 6" Silicone RTV Foam seal with 1" bottom side damming. Considering that Silicone RTV Foam has a greater char rate, it is consumed more rapidly than Radflex.

Therefore, direct flame

M-663-00017 A Attachment B12 Revision WO 1 Page 8 of 11 impingement to the test article would be more severe than that expected for the Table I pipe penetrations sealed with Radflex (RB-1).

This coupled with the fact that the Radflex penetration seal designs have greater sealant depths and insulation thickness, the slightly larger pipe sizes than that qualified in M-663-00017, Detail RB-1 are considered inconsequential. Based on these constructive attributes, it is reasonable to conclude that the penetration seals identified in Table I would resist the affects of fire exposure and prevent the passage of flame to unexposed side of the barrier for a 3-hour duration. Therefore, Table I penetration seals are considered 3-hour F rated.

Due to the larger pipe sizes, Table I penetration seals are not qualified for a 3-hour T rating. In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix B12-1, were conducted for each penetration of concern. This review was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that no exposed insitu combustibles or PFSSD circuits are located within the Heat Affected Zone (HAZ) for penetration P133S0799. Therefore, the penetration satisfies the review criteria of M-663-00017 where T rating requirements are not met.

P134S0860 has radiation shielding directly affixed to the insulation within the HAZ to provide added protection from radiological exposure. This shielding has combustible components and further assessment is required to ensure that a fire in Fire Area A-1 would not transmit sufficient conductive or radiant heat to ignite the shielding in Fire Area A-24.

Section 7.2.3 and Table 7.2.3-1 of M663-00017A has compared pipe sizes and unexposed side penetrant exposure temperatures.

The comparison demonstrates that a 10" un-insulated pipe through a 12" Silicone RTV Foam seal will yield a temperature of 455°F on the unexposed side of the test slab (on the penetrant, 6" above the slab). As discussed above, the slightly larger pipe insulated with Calcium Silica type insulation will adequately compensate for the diameter differential. It is also apparent that an equal depth of Radflex verses Silicone RTV Foam is a superior seal configuration with regard to fire exposure performance.

In addition, it is reasonable to conclude regarding penetrant temperature performance, that the presence of Calcium Silica insulation will also provide additional thermal margin to resist conductive and radiant energy propagation through the barrier to the radiation shielding affixed to the penetrant insulation.

The unexposed side insulation is not directly exposed to the fire and will provide at least equivalent protection to that of the exposed side of the barrier, thus providing even more thermal margin than that indicated in Table 7.2.3-1.

The lead shielding is comprised of Standard "Herculite" (Polyvinyl Chloride [PVC] Nylon laminate) with a fibrous reinforcement weave to provide strength. The PVC/Nylon laminate material is the combustible element of the shielding, which has a 600°F auto-ignition temperature, as identified by the manufactures data (Bruin Plastics). Based on the above

M-663-00017 A Attachment B 12 Revision WO 1 Page 9 of 11 discussions, it is reasonable to conclude that the auto-ignition temperature of the radiation shielding will not be reached resulting from a fire in Fire Area A 1. This conclusion is primarily based on the presence of the Calcium Silica insulation, through and on both sides of the barrier penetration seal and the fact that the installed Radflex will perform better than that of Foam, as evaluated in M-663-00017 A.

Therefore, the presence of radiation shielding within the HAZ of penetration seal P134S0860 is acceptable and its ability to prevent the passage of flame will not be impacted by the lack ofT rating.

5.2.2 Silicone RTV Foam Penetrations (Table II)

The Table II penetration openings contain insulated pipe penetrants that are sealed with Silicone RTV Foam and Ceramic Fiber damming.

Penetration P132W1433 is insulated with Calcium Silica through the seal and completely encompasses the barrier opening on both barrier sides.

As discussed in Section 5.2.1 above, this insulation material has been demonstrated by industry testing to improve unexposed side penetration seal performance. The insulation provides protection of the seal from direct flame impingement and a reduction in thermal conduction though the penetrant. This protection ensures the 3-hour F rated performance of this seal.

The remaining Table II penetrations are insulated with fiberglass type insulation on at least one side of the barrier. The Fiberglass Anti-Sweat insulation appears to abut or stop at the penetration seal material and is primarily used for piping with less than 200°F system temperatures. As with Calcium Silica insulation, the Fiberglass Anti-Sweat insulation also provides protection from direct flame impingement and it is reasonable to conclude that substantial benefit is achieved by crediting this non-combustible insulation type material. For the purpose of this evaluation, one sided insulation protection is the more severe and bounds two sided insulation protection.

Pipe penetrants that utilize Fiberglass Anti-Sweat type insulation (AS) provide added shielding from direct flame impingement resulting lower temperature exposure to the penetrant, thus lowering heat transmission to the unexposed barrier side of the barrier. Although, not specifically tested to ASTM E119 requirements, fiberglass type insulation is non-combustible and is not readily consumed during fire exposures.

The fiberglass element of the insulation is anticipated to remain intact for a 3-hour fire duration.

Specific temperature performance is not a critical attribute for this insulation type because it does not transition through the barrier/seal opening nor does it contribute to the physical barrier separating fire areas.

The pipe insulation is a molded, heavy density, one-piece insulation made from inorganic glass fibers bonded with a thermosetting resin.

The insulation is produced in three-foot lengths either with or without a jacket and is typically installed, cut to length, as needed. The jacket is a white-Kraft paper bonded to aluminum foil Uacket) and reinforced with fiberglass

M-663-0001.7 A Attachment B12 Revision W01 Page 10 of 11 fibers. This vapor seal material and the adhesive used to bond the vapor seal to the jacketing has been determined combustible and is evaluated herein.

The vapor barrier and associated adhesive amounts have been determined to be an insignificant quantity of Class "A" combustible that is located on the inner surface of the jacketing. When tested in accordance with ASTM E-84, NFPA 255 and UL 723 as plain insulation or on a composite basis (insulation, jacket and adhesive), the pipe insulation does not exceed:

  • 25 Flame spread
  • 50 fuel contribution
  • 50 smoke development Because the vapor seal and associated adhesive contribute an insignificant quantity of combustible and the fiberglass insulation element would not be consumed during fire exposure, it is reasonable to conclude that the remaining fiberglass would provide thermal benefit to the penetrant on the unexposed side of the barrier.

Although, it can be expected that the insulation jacket, vapor barrier and adhesive would be consumed rapidly during an ASTM E119 fire on the exposed barrier side, the remaining fiberglass element of the composite insulation unit would not be dislodged due to the stainless steel banding used to secure the composite insulation unit to the pipe. It is important to understand that this insulation is regarded as an enhancement that will impede radiant energy from passing through the penetrant, damming and sealant to the unexposed side of the barrier. This additional protection (insulation) is credited to slow the char rate of the internal sealant material by impeding thermal propagation to the unexposed side of the barrier, thus yielding improved thermal performance on the unexposed side of the barrier.

On the unexposed barrier side the vapor barrier and adhesive are protected from fire propagation by the compressive sheet metal outer jacket, which will not be physically affected on the cold side.

Based on the protective attributes provided by the Fiberglass Anti-Sweat pipe insulation, it is reasonable to conclude that the penetration seals identified in Table II would resist the affects of fire exposure and prevent the passage of flame to unexposed side of the barrier for a 3-hour duration. Therefore, Table II penetration seals are considered :>hour F rated.

Due to the larger pipe sizes, Table II penetration seals are not qualified for a :>hour T rating.

In effort to evaluate fire area impact, feld walk-downs and comprehensive assessment reviews, documented in Appendix B 12-1, were conducted for each penetration of concern. This review was completed in accordance with the criteria and review methodology established in M663-00017A Section 7.2.3 for non-T rated penetrations. The review identified that no exposed in situ combustibles or PFSSD circuits are located within the Heat Affected Zone. Therefore,

M-663-000 17 A Attachment B 12 Revision WO 1 Page 11 of 11 the Table II penetrations satisfy the review criteria of M-663-000 17 where T rating requirements are not met.

Procedure AP 1 0-1 04 and Specification M-162C have been revised to provide insulation control for the Table I and II penetrations and associated pipe lines.

This was necessary in order to identify the fire protection significance of the insulation and define the fire protection compensatory measures if insulation is removed.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation. The Table I and II penetration seals are evaluated as 3-hour F rated.

The comprehensive walkdown review for each of these penetrations revealed that no exposed insitu combustibles or PFSSD circuits are negatively affected by the non-T rated penetrations.

A segment of insulated pipe directly above penetration P134S0860 is covered with radiation shielding that is directly affixed to the pipe insulation.

This radiation shielding contains combustible PVC plastic material that is within AP 10-102 limitations. The above evaluation determined that the presence of the shielding does not to impact the seal's ability to maintain its intended design function. Therefore, PFSSD circuits are not negatively affected by the non-T rated penetrations.

6.0 Conclusions Based on the above discussions, it is reasonable to conclude that the Table I and II penetration seals are acceptable as 3-hour F rated and will perform their intended design function, regardless of not achieving a T rating. In all cases, the installed piping insulation on either side of the barrier will improve radiant performance regardless of pipe sizes. By crediting the piping insulation radiant improvement (T) will be achieved by lowering thermal transmission through the barrier, thus improving the F rating performance of the penetration seals.

The penetration seals satisfy regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements, to prevent spread of fire from one fire area to another. It has also been determined through this evaluation that the lack of a T rating will not affect the plant's ability to achieve and maintain PFSSD.

M-663-00017 A, Revision WOl Page Bl2-l ofB12-24 Penetration Seal Data Appendix:

812 Penetration #:

P114W0423 Penetration Type:

M-1 Fire Area (Side 1): A-1 Fire Area (Side 2): A-6 Loc./Eiev.:

1986'-6" M-OX Dwg: M-1X0360

1. Barrier Thickness:

12" Nominal

10. Annular Gap (smallest):

Unknown

2. Opening Size:

14"D

11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F

4. Sealant Type:

Assumed Per Detail

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Unknown

14. Pipe Insulated:

Yes

6. Damming Side 2:

Unknown Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

Assumed 6" Reviewed By:

Walkdown Comments:

QC documentation identifies that seal depth is 6". Insulation completely covering seal surfaces, seal specifics can not be verified (See Drawing M-13EF06; Essential Service Water [EF] Line Number 099-HBC-8", 95F Design Temp, 1-1/2" thick, Classification "AS" [Anti-Sweat] Fiberglass Type Insulation)

Sketch:

I I a

1 I.

I J I.

I I

~.~/'..

ti

'I

M -663-00017 A, Revision WO 1 Penetration Seal Data Photos:

P114W0423 Fire Area A-1 (Side 1)

Fire Area A-6 (Side 2)

Fire Area A-1 (Side 1)

Fire Area A-6 (Side 2)

Page Bl2-2 ofB12-24 Appendix:

812

M-663-000I?A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P114W0423 Fire Area (Side 1)

A-1 1 1-1/2" Conduit 5J1259, Not within Heat Affected Zone

2. 3.4" Conduit for emergency Light A-14, not within Heat Affected Zone Fire Area (Side 2)

A-6

1. 1-1/2" Conduit 5J 1259, Not within Heat Affected Zone
2. 3.4" Conduit for emergency Light A-14, not within Heat Affected Zone Side 1 Photo Side 2 Photo No photo required.

No photo required.

Sketch Page Bl2-3 ofB12-24 Appendix:

812 Review Distances (Reference M-663-00017A, Figure 7.2.3-1) 8" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

{of)

(in)

(in) 0.5 1677 4.4 5.8 11 1463 3.4 4.8 1.5 1277 2.6 3.9 2

1116 1.9 3.2 2.5 976 1.2 2.6 3

855 0.7 2

3.5 750 0.2 1.6 4

659 Contact 1.2 4.5 581 0.8 5

512 0.5 5.5 453 0.2 6

402 0

6.5 358 Contact

M-663-00017A Revision WOl Page 8 12-4 of 8 12-24 Penetration Seal Data Appendix:

B12 Penetration #:

P125W2432 Penetration Type:

M-1 Fire Area (Side 1 ):

A-1 Fire Area (Side 2):

A-33 Loc./Eiev.: 1993'-6" M-OX Dwg: M-1X1932

1. Barrier Thickness:

24"

10. Annular Gap (smallest):

1"

2. Opening Size:

14"0

11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

A F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :
  • Unknown
14. Pipe Insulated:
  • No
6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

NJA Jeff Suter

9. Sealant Depth:
  • Assumed 6" Reviewed By:

Walkdown Comments:

Barrier thickness based on drawing C-1 C 1151. ' Side 1 is completely covered w/insulation.

  • Side 2, pipe is not insulated, side 1 is insulated. QC documentation identifies that seal depth is 6".

Sketch:

FA: A-1 Side1 rN:SUL.A TtdrJ (Tvp)

P125W2432

  • o t).

I 0

Q FA: A-33 Sde2

M-663-00017A Revision WOJ PageB12-ofBI2-24 Penetration Seal Data Appendix:

812 Photos:

P125W2432 Fire Area A-1 (Side 1 )

Fire Area A-1 (Side 1 )

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P125W2432 Fire Area (Side 1)

A-1

1. No issues within Heat Affecte<l Zone Fire Area (Side 2)

A-33

2. 1 1/2" conduit (not identified) within Heat Affected Zone. Conduit is Plant utility, 110 Volt, No Problem.

Side 1 Photo Sketch FA:.A-1 S*1 Side 2 Photo Page 812-6 ofB12-24 Appendix:

812 Review Distances (RefMnc:e M-663-00017A. F'IJift 7..2.3-1 )

L1 &l2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 B"Pipe Temp.

("F) 1677 1403 1277 1116 976 855 750 659 581 512 453 402 358 FA:~

'*2 R1 Radius (in) 4.4 3.4 2.6 1.9 1.2 0.7 0.2 Contact R2Radlus (in) 5.8 4.8 3.9 3.2 2.6 2

1.6 1.2 0.8 0.5 0.2 0

Contact

M-663-000I?A Revision WOJ Page Bl 2-7 ofB12-24 Penetration Seal Data Appendix:

B12 Penetration #:

P125W2434 Penetration Type:

M-1 Fire Area (Side 1): A-6 Fire Area (Side 2): A-33 Loc./Eiev.:

1990'-1" M*OX Dwg: M-1X1932

1. Barrier Thickness:

24"

10. Annular Gap (smallest):

1/4"

2. Opening Size:

14"0 11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

A F

w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Flush

14. Pipe Insulated:

No'

6. Damming Side 2:
  • Unknown Wayne Aregood
7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:
  • Assumed 6" Reviewed By:

Walkdown Comments:

Barrier thickness based on 1 C-1151.

  • Side 1 is completely covered w/insulation.
  • Side 2, pipe is not insulated, side 1 is insulated. OC documentation identifies that seal depth is 6".

Sketch:

FA: A-6 S!de1 JIISULII iJOII/

P125W2434

~-+--- A~ 54-1 mt<b c..'

P- **,

t:o~~

FA: A-33 Side 2

M-663-00017A, Revision WOl Page 8 12-of 8 12-24 Penetration Seal Data Appendix:

812 Photos:

P125W2434 Fire Area A-6 (Side 1)

Fire Area A-6 (Side 1)

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2)

M-663-000 17 A. Revision WO 1 Penetration Seal Data Heat Affected Zone Review:

P1.25W2434 Fire Area (Side 1)

A-8

1. No issues within Heat Affected Zone Fire Area (Side 2)

A-33

2. 6" Cable Tray 182F02, not within Heat Affected Zone Side 1 Photo Side2Photo Sketch Page 812-9 ofB12-24 Appendix:

812 Review Distances

!Ref8r1nce M.663-00017A. r90 1.2.~1 )

a* Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

(OF)

(in)

(In) 0.5 1677 4.4 5.8 1

1463 3.4 4.8 1.5 1277 126 3.9 2

1116 1.9 3.2 2.5 976 1.2 2.6

.3 855 0.7 2

3.5 750 0.2 1.6

  • 4 659 Contact 1.2

.4.5 581 0.8 5

512 0.5

. 5.5 453 0.2 6

402 0

6.5 358 Contact I

I

M-663-00017A Revision WOL Penetration Seal Data Penetration#:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P132S0683 M-6A 1 0" 30"D (1 )24"P Foam Page B 12-1 0 of B 12-24 Appendix:

B12 Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 M-OX Dwg: M-1X1321

10. Annular Gap (smallest):

1"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Assumed per detail

14. Pipe Insulated:

Yes

6. Damming Side 2:

Recessed 4" Jeff Suter

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth :

11'"

Reviewed By:

Walkdown Comments:

Top side seal is enclosed within support insulation. Insulation abuts damming board on bottom side. Slab thickness determined by Drawing C-1 C1311 (wsa).

  • 11" foam depth based on installation QC documentation (WSA). (See Drawing M-13EF02; Essential Service Water Supply [EF] Line Number 076-HBC-24", 95F Design Temp. 1-1/2" thick, Classification "AS" [Anti-Sweat] Fiberglass Type Insulation)

Sketch:

FA: A.S s da 1 P1US0883 FA! A-t SicM2

Page 8 12-11 ofBI2-24 Penetration Seal Data Appendix:

812 Photos:

P13250683 Fire Area A-8 (Side 1}

Fire Area A-8 (Side 1 )

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P132S0683 Fire Area (Side 1)

A-8 No issues within Heat Affected Zone Fire Area (Side 2)

A-1 No Issues within Heat Affected Zone Side 1 Photo Side2Photo oto Sketch Page B12-12ofBJ2-24 Appendix:

812 Review Distances

< Ra~an~nce~17A.fi!IIJIW7-U-1 24~ P_ipe_

L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) rt=)

{In)

(in) 0.5 1763 4.8 6.1 1

1615 4.1 5.5 1.5 1480 3~5 4.9 2

1357 3

4.3 2.5 11244 2.5 3.8 3

1141 2

3.J 3.5 11048 1.6 2.9 4

~ 962 1.2 2.5 4.5 884 0.8 2.2 5

813 0.5 1.9 5.5 748 0.2 1.6 6

1689 Contact 1.3 6.5 635 1.1 7

585 0.8 7.5 540 0.6 8

499 0.4 8.5 462 0.3 9

427 0.1 9.5 396 Contact No sketch requir

M-663-00017A Revision WOI PageBI2-J3 ofBI2-24 Penetration Seal Data Appendix:

B12 Penetration #:

P132S0684 Penetration Type:

M-1 Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

lndeterminant

2. Opening Size:

30"D 11. Gap between pen:

N/A

3. Penetrants:

(1)24"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Assumed per detail

14. Pipe Insulated:

Yes

6. Damming Side 2:

Assumed per detail Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth:

Assumed per detail Reviewed By:

Walkdown Comments:

Insulation covers opening on both barrier sides. Slab thickness determined by Drawing C-1 C1311 (wsa) (See Drawing M-13EF03; Essential Service Water Return (EF] Line Number 080-HBC-24", 11 OF Design Temp, 1-1/2" thick, Classification "AS" [Anti-Sweat] Fiberglass Type Insulation)

Sketch:

I~**""

~c~.... A FA: A-1 Side2

M-663-00017A Revision WOI Page 812-14 ofBI2-24 Penetration Seal Data Appendix:

B12 Photos:

P132S0684 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-0001 7 A, Revision WOl Page 8 12-1 ofBJ 2-24 Penetration Seal Data Appendix:

812 Heat Affected Zone Review:

P132S0684 Fire Area (Side 1)

A-8 Review Distances (Reference M-663.()()()17A, F>gure 7.2.3-1 )

No issues within Heat Affected Zone 24" Pipe L 1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

(*F)

(in)

(in) 0.5 1763 4.8 6.1 1

161 5 4.1 5.5 Fire Area (Side 2)

A-1 1.5 1480 3.5 4.9 No issues within Heat Affected Zone 2

1357 3

4.3 2.5 1244 2.5 3.8 3

1141 2

3.3 3.5 1048 1.6 2.9 4

962 1.2 2.5 4.5 884 0.8 2.2 5

813 0.5 1.9 Side 1 Photo Side 2 Photo 5.5 748 0.2 1.6 6

689 Contact 1.3 6.5 635 1.1 7

585 0.8 7.5 540 0.6 8

499 0.4 No photo required.

No photo required.

85 462 0.3 9

427 0.1 9.5 396 Contact J

Sketch I

No sketch required.

M-663-00017A Re ision WOI Page 12-1 6 of B 12-24 Penetration Seal Data Appendix:

B12 Penetration#:

P132W1433 Penetration Type:

M-1 Fire Area (Side 1): A-8 Fire Area (Side 2):

CC-1 Loc./Eiev.: 2013'-0 3 M-OX Dwg: M-1X1904

1. Barrier Thickness:

24"

10. Annular Gap (smallest):

Unknown

2. Opening Size:

16"0

11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

A F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Unknown

14. Pipe Insulated:

Yes

6. Damming Side 2:

Unknown Wayne Aregood

7. Damming Continuity (Acc/Rej):

Unknown Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

QC documentation identifies a 6" seal depth. Insulation completely covers seal configuration. (WSA) (See Drawing M-13GB04: Central Chilled Water Supply [GB) Line Number 008-HBD-8", 44F Design Temp, 2" thick, Classification "X" Calcium Silica Type Insulation)

Sketch:

FA: A-8 Sida1 P132W1433

  • o.
b.

., 0 I

  • t:.

v I

D

/,)

  • J I. ** ~*

~

/l.

~.

I I>- *,

  • ol I
  • * /:J.

' I>

FA: CC*J Side 2

M-663-000J7A,Revi ion WOI Page B 12-17 of812-24 Penetration Seal Data Appendix:

8 12 Photos:

P132W1433 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area CC-1 (Side 2)

Fire Area CC-1 (Side 2)

M*663*000 17 A, Revision WO l Penetration Seal Data Heat Affected Zone Review:

P132W1433 Fire Area (Side 1)

A-8

1. 4" conduit, not within Heat Affected Zone Fire Area (Side 2)

CC-1

2. 1* nitrogen line, not within Heat Affected Zone. Insulation thickness Included in dimensional distance.

Side 1 Photo Sketch FA: A-I Sllle1 Side 2 Photo Page Bl2-18 of B12-24 Appendix:

1812 Review Distances (Rer-tMI63-00017.&. Fogon 7.2.~1 )

L1 & L2 DisL (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5

'6 16.5 s* Pipe Temp. R1 Radius rFI (in) 1677 4.4 1463 3.4 12n 2.6 1116 1.9 976 1.2 855 0.7 750 0.2 659 Contact 581 512 453 i 402 I

I 358 FA: CC.1 Side 2 R2 Radius (in) 5.8 4.8

3.9 3.2

.. 2.6 2

1.6 I ~.2 o;s 0.5 0.2 0

Contacl

M -663-00017 A Revision WO 1 Page 812-19 of812-24 Penetration Seal Data Appendix:

B12 Penetration #:

P133S0799 Penetration Type:

RB-1 Fire Area (Side 1): A-25 Fire Area (Side 2):

A-1 Loc./Eiev.:

2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

4"

2. Opening Size:

24"D 11. Gapbetweenpen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F R

4. Sealant Type:

Ra dflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Unknown

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept

  • Jeff Suter
9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

  • Boot for bottom side only. top side enclosed. Insulation appears to transition through the sealant zone. (WSA)

(See Drawing M-1 3EJ02; Residual Heat Removal Train 8 [EJ] Line Number 009-ECB-1 2", 350F Design Temp, 2" thick. Classification "X" Calcium Silicate Type Insulation)

Sketch:

FA: A*15 Slde1 P133S07a9 L

  • a I

l I

I '

!,;)

'd.*

FA:A-1 Side 2

M-663-00017A, Revision WOl Page 8 12-20 of 8 12-24 Penetration Seal Data Appendix:

812 Photos:

P133S0799 Fire Area A-25 (Side 1)

Fire Area A-25 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A. Revision WOl Penetration Seal Data Heat Affected Zone Review:

P13350799 fire Area (Side 1)

A-25 No issues within Heat Affected Zone Fire Area (Side 2}

A-1 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page 8 12-2 1 ofB1 2-24 Appendix:

B 12 Review Distances

('Ref- ~17A.

Figura 7.2.3-, 1 12* Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F)

(in)

(in) 0.5 1712 4.6 5.9 1

1524

3.7 5.1 1.5 1357 3

4.3 2

1209

, 2.3 3.6 2.5 1078 1.7 3.1 3

962

. 1.2 2.5 3.5 860 0.7 2.1 4

769 I o.3 1.7 4.5 689 I Contact 1.3 5

618 I

1 5.5 555 I

0.7 6

499 I

0.4 6.5_

i 450 0.2 7

406 I

0 7.5 368 i

Contact I

No sketch required.

M-663-00017 A, Rev ision WO I Page B 12-22 of B 12-24 Penetration Seal Data Appendix:

B12 Penetration #:

P134S0860 Penetration Type:

RB-1 Fire Area (Side 1): A-24 Fire Area (Side 2):

A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1341

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

4"

2. Opening Size:

24"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F R

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:
  • Unknown
14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):
  • Accept Jeff Suter
9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C 1311.

  • Top side seal is covered with support insulation and shielding, obscuring inspection attributes. Insulation appears to transition through the sealant via bottom side examination.

Sketch:

FA: A*24 Slde1 Sli~:t..O*

IN-/..--r4 ~,..--Surrt~~:T INS ti'Ttu; PI..Acu ~~

r-J. __ I __ -,/

C'o~~ BooT ~~st\\.

,"\\I I~~-

-~_Q_ 1 I 1

011 1 1 111 tl I I ~_d-

.il_

10!-

'b"

  • o*

t-..

".. *.. ~~.,1 t'

~ :... *:

~

p.

~.

I P134SOII60 coot c~P)

FA; A-1 Slde2

M-663-00017A, Revision WOI Page B 12-23 of B 12-24 Penetration Seal Data Appendix:

812 Photos:

P134S0860 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P134S0860 Fire Area (Side 1)

A-24

1. lead shielding (PVC coated) on pipe Fire Area (Side 2)

A-1 No Issues within Heat Affected Zone Side 1 Photo Side2Photo qui Sketch Page 812-24 ofBJ2-24 Appendix; 812 Review Distances (IWerenol ~17A, f9n 7.2.~1)

I L1 & L2 12" Pipe Temp. R1 Radius R2 Radius Dist. (ft)

(OF)

(in)

(in) 0.5 1712 4.6 5.9 1

1524 3.7 5.1 11.5 1357 3

4.3 2

1209 2.3 3.6 2.5 1078 1.7 3.1 3

962 1.2 2.5 3.5

'860 0.7 2.1 4

769 0.3 1.7 4.5 689 Contact 1.3 5

618 1

5.5 555

().7 6

499 0.4 6.5 450 0.2 7

406 0

7.5 368 1 Contact I

Rev. No.

W01 W02

,d-'a W~~t.F CREEK

  • -~.r./NUCLEAR OPERATING CORPORATION M-663-00017A 13 Fire Protection Evaluation For Penetration Openings with Unique Bounding Attributes (PIR 2005-2384)

Prepared By Date Reviewed By

~~~ 9/9/05

--&1'~

Wayne S Aregood Jeff Suter

~~~ 1/11/06

--&1'~

Wayne S Aregood Jeff Suter Page 1 Date 9/9/05 01/11/06

M-663-000 17 A 13 Revision W02 Table of Contents Page 2 of 19 Revision Log................................................................................................................................. 3 1.0 Purpose............................................................................................................................. 4 2.0 Scope..................................-.............................................................................................. 4 3.0 References........................................................................................................................ 4 4.0 Evaluation......................................................................................................................... 5 5.0 Conclusions..................................................................................................................... 19 Appendix 813, Penetration Seal Data...................................................... (88 Total Pages)

M-663-000 17 A 13 Revision W02 Revision Reason for Revision W01 Original Issue Revision Log W02 Changed seal requirements for Penetration P142W1932 Page 3 of 19

M-663-000 17 A Attachment B 13 Revision W02 1.0 Purpose Page 4 of 19 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M-663-00017A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-000 17. In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 M-663-00111, Promatec Penetration Closure Heat Transfer Report, Rev. 3 3.7 CTP-1001, (M-663-00082) Fire Qualification Test on Silicone Foam Floor Penetration Seals, Rev. W01 3.8 CTP-1002, (M-663-00083), Fire Qualification Test on Silicone Foam Floor Penetration Seals 3.9 CTP-1020 & 1021 (M-663-00060), Fire Qualification Test on Penetration Seals 3.10 CTP-1022 (M-663-00121), Fire Qualification Test on Penetration Seals

M-663-000 17 A Attachment B 13 Revision W02 Page 5 of 19 3.11 TR-187 (M-663-00154), Fire and Hose Stream Test of a 8" thick specimen of

  1. TC0-026 Ceramic Blanket used as a penetration seal material in a 12" diameter sleeve penetrated by bare pipe, insulated pipe, and copper, monel, and stainless steel instrument tubing 3.12 PIR 2005-2384, Unbounded Penetration Seals requiring additional design to enhance seal performance.

3.13 Work Order 05-275799, Thirty-one Penetration Seals Requiring Field Work 3.14 Work Order 03-256183, Cable Addition for Penetration P371W0948 3.15 M-162C, Specification for Non-metallic Thermal Insulation for Piping and Equipment Located In Auxiliary Building, Control Building, Diesel Generator Building, Fuel Building, and Radwaste Building For The Wolf Creek Generating Station, Rev. 19 3.16 DDCN M-162C-19-1 0,

Subject:

Pipe Insulation Control to Ensure Penetration Seal Fire Resistance Rating Maintained 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

5.0 Evaluation 5.1 Assessment of Condition to Design Requirements 5.1.1 Initial typical detail assignment for the Table I penetrations resulted in a condition where at least one M-663-000 17 typical detail critical parameter was not satisfied for each penetration seal.

The issues associated with these penetrations are generically identified below, while the Table I "Problem" column characterizes the applicable issue(s) to the respective penetration.

5.1.1.1 5.1.1.2 Penetrant size exceeds the typical detail limitations such that the seal could not be reasonably qualified as 3-hour fire (F) rated due to seal material type and/or depth.

Penetrant size exceeds the typical detail limitations.

The penetration seal can be qualified by evaluation as 3-hour F rated due to seal material type and depth.

However, the penetration is not directly qualified as 3-hour temperature (T) rated, and field inspection has determined that combustible materials are located within the M-663-000 17 A defined heat affected zone. This presents the potential for auto-ignition of

M-663-00017 A Attachment B 13 Revision W02 5.1.1.3 Page 6 of 19 combustible materials on the unexposed barrier side, when considering a 3-hour ASTM E-119 fire intensity.

Penetrant design lateral movement exceeds typical detail limitation. For these penetrations the primary seal material (ceramic fiber) may lose resilience, if subjected to significant lateral movement compressing the ceramic fiber.

This creates the potential for a through hole opening within the ceramic fiber seal.

Due to the presence of a silicone impregnated boot on both barrier sides, intrusive inspection was deemed necessary to determine if identified design movements had affected seal continuity.

Each of the Table I penetrations required field work to address the issues identified above. This was initially identified in PIR 2005-2384, with field work conducted in accordance with Work Order 05-275799.

The Table I "Resolution" column identifies the field work activity conducted for each penetration. Appendix B 13 contains the penetration walkdown data that was utilized to assess the adequacy of the initial in plant configuration for the Table I penetrations.

TABLE I Penetration Seal Field Work Resolution Penetration Communicating Typical Problem Eva I.

Fire Areas Resolution No.

Side 1 Side2 Detail Section Section P112W1377 A-1 C-1 M-6A 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area C-1) and evaluate for F-Ratinq only.

P112W1379 A-1 C-1 M-6A 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area C-1) and evaluate for F-Rating only. Eliminate combustible storage area on A-1 side that is within the heat affected zone for the penetrant.

P113W0421 A-1 A-5 M-1 5.1.1.1 Add foam to satisfy M-6A and this 5.2.1 penetration will be bounded.

P121S0284 A-1 A-4 RB-5A 5.1.1.2 Wrap penetration at floor up 18" (min.)

5.2.6 with 3" (min.) ceramic fiber blanket.

Encapsulate exposed ceramic fiber with a stainless steel sheet metal cover. Notch around interferences as necessary.

Secure sheet metal cover with stainless steel banding.

P121S0285 A-1 A-4 RB-5A 5.1.1.2 Wrap penetration at floor up 18" (min.)

5.2.6 with 3" (min.) ceramic fiber blanket.

Encapsulate exposed ceramic fiber with a stainless steel sheet metal cover. Notch around interferences as necessary.

Secure sheet metal cover with stainless steel banding.

P121S0287 A-1 A-4 RB-5A 5.1.1.2 Wrap penetration at floor up 18" (min.)

5.2.6 with 3" (min.) ceramic fiber blanket.

Encapsulate exposed ceramic fiber with a stainless steel sheet metal cover. Notch around interferences as necessary.

Secure sheet metal cover with stainless steel banding.

M-663-00017 A Attachment B 13 Revision W02 Penetration Communicating Fire Areas No.

Side 1 Side 2 P132W1845 A-8 A-3 P133S0762 A-8 A-1 P133S0784 A-25 A-1 P133S0788 A-25 A-1 P133W2037 A-8 A-25 P133W2042 A-8 A-25 P134S0877 A-24 A-1 P134W2054 A-8 A-24 P141S1015 A-16 A-8 P141S1023 A-16 A-8 P141W1907 A-16 A-26 P141W1908 A-16 A-26 P141W1913 A-16 A-26 Typical Problem Detail Section M-6A 5.1.1.1 FB-1 5.1.1.3 RM-5.1.1.2 1A/A-7 RB-5A 5.1.1.2 M-1 5.1.1.1 M-1 5.1.1.1 RB-5A 5.1.1.2 M-1 5.1.1.1 M-6A 5.1.1.1 M-6A 5.1.1.1 M-1 5.1.1.1 M-1 5.1.1.1 M-1 5.1.1.1 Page 7 of 19 Eva I.

Resolution Section

1) Locally remove insulation to expose 5.2.5 seal damming and to provide sufficient room to allow damming attachment on A-8 side.
2) Mechanically attach per A-5 Detail, two layers of ceramic fiber damming to the barrier surface on each A-8 side.

Perform intrusive inspection to verify 5.2.7 penetrant movement has not affected seal continuity.

Remove Armaflex from A-25 (Top Side) 5.2.4 for a distance of at least 7' -6" from penetration and replace with noncombustible Anti-sweat insulation, if required.

Remove Armaflex from A-25 (Top Side) 5.2.2 for a distance of at least 7'-6" from penetration and replace with noncombustible Anti-sweat insulation, if required.

Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area A-25) and evaluate for F-and T ratir19_.

Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area A-25) and evaluate for F-Ratir19_ only.

Remove Armaflex from A-24 (Top Side) 5.2.2 for a distance of at least 7'-6" from penetration and replace with noncombustible Anti-sweat insulation, if required.

Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area A-8) and evaluate for F-Rating only.

1) Add full depth ceramic fiber to sleeve 5.2.5 on topside (Fire Area A-16) and evaluate for F-Rating only.
2) Remove Armaflex (Top Side) for a distance of at least 4' on the 4" pipe connected to the main pipe and locally remove Armaflex from the 4" pipe with air gap for a minimum distance of to 12" from closest contact point, both directions and replace with noncombustible Anti-sweat insulation, if required.

Add full depth ceramic fiber to sleeve on 5.2.5 topside (Fire Area A-16) and evaluate for F-Rating only.

Add ceramic fiber to sleeve in Fire Area 5.2.5 A-26 and mechanically attach a single layer of ceramic fiber board to barrier on A-26 side. Evaluate for F-Rating only.

Add ceramic fiber to sleeve in Fire Area 5.2.5 A-26 and mechanically attach a single layer of ceramic fiber board to barrier on A-26 side. Evaluate for F-Ratingonly.

Add foam to satisfy M-6A, which will 5.2.1 bound penetration.

M-663-00017 A Attachment B 13 Revision W02 Page 8 of 19 Penetration No.

P142S1083 P142S1086 P142W1932 P143W2514 P143W2515 P145S0952 P145S0954 P152W1421 P311W0841 P311W0842 P311W0845 P611W0206 Communicating Typical Problem Eva I.

Fire Areas Resolution Side 1 Side 2 Detail Section Section A-16 A-3 M-1 5.1.1.1 Add ceramic fiber flush with sleeve on the 5.2.5 topside (Fire Area A-16) and evaluate as F-Rated only.

A-16 A-3 FB-1 5.1.1.2 Remove Armaflex (Top Side) for a 5.2.3 distance of at least 12" from closest point (Both Directions) of main penetrating pipe and replace with noncombustible Anti-Sweat insulation, if required.

A-16 A-10 M-6A 5.1.1.1 Remove existing silicone foam seal and 5.2.9 damming from the 2026' Corridor (A-16) side and add full depth ceramic fiber to the penetration from the A-16 side.

Evaluate for F-RatinQ only.

A-16 A-5 M-1 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area A-16) and mechanically attach at least one layer of ceramic fiber board to barrier on A-16 side. Evaluate for F-RatinQ only.

A-16 A-5 M-6A 5.1.1.1 Mechanically attach at least one layer of 5.2.5 ceramic fiber board to barrier on A-16 side. Evaluate for F-Rating only.

A-23 A-15 FB-1 5.1.1.3 Perform intrusive inspection to verify 5.2.7 penetrant movement has not affected seal continuity.

A-23 A-15 FB-1 5.1.1.3 Perform intrusive inspection to verify 5.2.7 penetrant movement has not affected seal continuity.

A-19 CC-1 M-1 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area CC-1) and evaluate for F-RatinQ only.

C-1 CC-1 M-6A 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area CC-1) and evaluate for F-Rating only.

C-1 CC-1 M-6A 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area CC-1) and evaluate for F-Rating only.

C-1 CC-1 M-6A 5.1.1.1 Add full depth ceramic fiber to recessed 5.2.5 side of seal (Fire Area CC-1) and evaluate for F-Rating only.

F-2 F-3 M-1 5.1.1.1 Add ceramic fiber to recessed side of 5.2.5 penetration (Fire Area F-2) and mechanically attach a single layer of ceramic fiber board to barrier on F-2 side.

Evaluate for F-Rating only.

5.1.2 Work Order 03-256183 identified that during installation of additional cables through penetration P371 W0948 it was noted that the gap tolerances for installing foam per CNT -MC-905 could not be obtained between the new cables and the cable tray sleeve. The resulting seal configuration observed in the field is not directly bounded by typical detail E-2A from M-663-000 17.

M-663-000 17 A Attachment B 13 Revision W02 Page 9 of 19 5.2 Evaluation of Condition 5.2.1 Silicone Foam Added - Bounding to M-6A Detail The Table I penetration seals referring to this section have a penetrant size that exceeds the M-1 typical detail bounding limitation. The addition of RTV Silicone Foam material to a minimum 9" depth between 1" thick ceramic fiber damming results in penetration attributes that are bounded by the limiting parameters of typical detail M-6A from M-663-00017.

Therefore, no further evaluation is required.

5.2.2 RB-5A Detail with Armaflex Removed from HAZ The HDSE/HDLE annular reduction seals for the Table I penetrations referring to this section are bounded by the limitations of typical detail RM-1A, which allows up to an 18" pipe penetrant for an HDSE/HDLE seal. The unbounded portion necessitating evaluation is the penetrant size in relation to the annular gap sealed with ceramic fiber and a silicone impregnated boot.

Figure 1 reflects the RB-5A typical detail seal configuration.

INVERTED BOOT ITYP.l HOSE/HOLE fULL BARRIER DEPTH (12"" MIN.I 1"' MAX. ANNULUS AROUND PIPE. DIMENSION DETERMINED

~~:::...._---;SY MAX. TRANSVERSE PIPE

.*. ' MOVEMENT.

METAL SLEEVE If APPLICABLE FLOOR OR WALL CONFIGURATION FIGURE 1 Typical Detail RB-SA (Reference M-663-00017)

These penetrations are considered 3-hour F rated based on the successful performance of Penetration 1 from fire test CTP-1 022. The tested configuration was comprised of a 1 0" opening containing a 2" diameter pipe penetrant. The opening was sealed with a 12" depth of HOLE leaving a 1" annulus around the pipe penetrant.

Silicone impregnated boots filled with a 3" ceramic fiber depth were then installed beyond the barrier plane on both penetration sides. This presented a seal configuration consistent with Figure 1 above.

M-663-000 17 A Attachment B 13 Revision W02 Page 10 of 19 Industry fire testing reveals that the exposed side boot is sacrificial and will be consumed when directly subjected to an ASTM E-119 fire. The loss of this boot will result in the loss of the exposed side ceramic fiber due to gravity, since the only structural support provided for the material beyond the barrier plane is that presented by the boot.

However, the unexposed side boot with ceramic fiber fill will remain in tact, and adequately prevent fire propagation via the small annular gap between the pipe penetrant and the HDSE/HDLE sidewall. This ceramic fiber and boot configuration will not be charred or consumed during the fire exposure.

The ceramic fiber will be maintained in position by the unexposed side boot, which is not determinately impacted, because it is not subjected to direct flame impingement.

Considering the performance of Penetration 1 from CTP-1 022 and the and the non-ablative material properties of ceramic fiber, penetrant size will not impact seal F rating. However, fire testing does not directly bound a T rating for penetrants larger than 2" diameter.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix B 13, were conducted for each penetration of concern. This review was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that once the combustible Armaflex is removed from the heat affected zone, no other exposed insitu combustibles or PFSSD circuits are located within the HAZ. Each of the penetrations satisfy the review criteria of M-663-00017 where T rating requirements are not met.

Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

5.2.3 FB-1 Detail with Armaflex Removed from HAZ Penetration P142S 1086 contains a pipe penetrant (24" diameter) that exceeds the size limitation directly bounded by typical detail FB-1 from M-663-00017. The FB-1 detail, which is comprised of a 12" ceramic fiber depth between silicone impregnated fiberglass boots, directly qualifies a seal with up to a 6" diameter penetrant as 3-hour fire F and T rated.

Penetration P 14281 086 is considered 3-hour F rated based on the successful performance of the following fire tested configurations, which

M-663-00017 A Attachment B 13 Revision W02 Page 11 of 19 demonstrate that a minimum 8" depth of ceramic fiber will prevent the passage of flame and hose stream to the unexposed barrier side.

TR-187-12" diameter opening containing a 2" bare and insulted pipe and three Yz" diameter tube penetrants. The penetration was sealed with an 8" depth of ceramic fiber blanket.

CTP-1002 Penetration 6 - 12" diameter opening containing a 6" bare pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

CTP-1 002 Penetration 1 0 - 12" diameter opening containing a 6" insulated pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

CTP-1 020 Penetration 1 - 6" diameter opening containing a 2" bare pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

CTP-1021 Penetration 1 - 10" diameter opening containing a 2" bare pipe penetrant. The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

Ceramic fiber is an inert material comprised of compressed refractory fibers. It is not charred or consumed during fire exposure. The material will not be negatively affected by heat transmission through the penetrating item. Therefore, penetrant size is not a concern regarding capability of a ceramic fiber seal to prevent flame and hose stream passage to the unexposed side. However, penetrant size is a concern regarding unexposed side temperature development.

Based on a comparison to the fire tested configurations bounding detail FB-1, penetration P142S1086 is not considered T rated.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix B 13, were conducted for penetration P142S 1086. This review was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

M-663-000 17 A Attachment B 13 Revision W02 Page 12 of 19 The review identified that once the combustible Armaflex insulation is removed from the heat affected zone, no other exposed insitu combustibles or PFSSD circuits are located within the HAZ.

The penetration satisfies the review criteria of M-663-00017 where T rating requirements are not met. Therefore, the penetration is acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

5.2.4 RM-1A /A-7 Detail with Armaflex Removed from HAZ Penetration P133S0784 is an HSDE/HDLE annular reduction seal with the annular gap between the pipe and high density elastomer sealed with ceramic fiber.

The pipe penetrant is 14" diameter. The HOSE/HOLE portion of the seal is bounded by the limitations of typical detail RM-1A, which allows up to an 18" pipe penetrant for an HDSE/HDLE seal. The unbounded portion necessitating evaluation is the penetrant size in relation to the annular gap sealed with ceramic fiber. Ceramic fiber seal detail A-7 qualifies up to a 2" pipe penetrant as 3-hour F and T rated.

This penetration is considered 3-hour F rated based on the discussion provided in Section 5.2.3 for a ceramic fiber sealed penetration.

However, the penetration is not considered T rated based on the large penetrant size.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix B 13, were conducted for penetration P133S0784. This review was completed in accordance with the criteria and review methodology established in M-663-00017 A Section 7.2.3 for non-T rated penetrations.

The review identified that once the combustible Armaflex insulation is removed from the heat affected zone, no other exposed insitu combustibles or PFSSD circuits are located within the HAZ.

The penetration satisfies the review criteria of M-663-00017 where T rating requirements are not met. Therefore, the penetration is acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

M-663-00017 A Attachment B 13 Revision W02 Page 13 of 19 5.2.5 Ceramic Fiber Added to Silicone Foam Seal Each of the Table I penetrations referring to this section contain a large penetrant size that is not directly bounded by detail M-1 or M-6A. The primary seal material (Silicone Foam) for these penetrations chars during fire exposure, with the char rate typically accelerating as the penetrant size increases.

This is the case due to the increased thermal mass presented by a large diameter penetrant. Considering an ASTM E-119 3-hour fire exposure, the thermal mass of a penetrant larger than that bounded by fire testing could potentially contribute to an increased seal char rate and ultimately present a seal failure mode.

To address this concern, seal performance was enhanced by adding ceramic fiber materials to the existing seal configuration to ensure a 3-hour F rating capability. The recessed area of existing penetration seals were either filled with compressed ceramic fiber and/or additional ceramic fiberboards were added to one or both sides of the barrier penetration seal, depending on in-plant configuration.

Ceramic fiber is an inert material comprised of compressed refractory fibers. It is not charred or consumed during fire exposure.

The material will not be negatively affected by heat transmission through the penetrating item. The addition of the ceramic fiber optimizes the capability of the penetration seal to resist the affects of Silicone Foam consumption and thermal propagation (conduction and radiant energy) along the large penetrant. Therefore, ensuring that the seal will prevent the passage of flame for a 3-hour duration. However, due to the large penetrant size, these penetrations are not considered T rated.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix B 13, were conducted for each penetration of concern. This review was completed in accordance with the criteria and review methodology established in M-663-000 17 A Section 7.2.3 for non-T rated penetrations.

The review identified that once the combustible Armaflex is removed from the heat affected zone (where required by Table 1), no other exposed insitu combustibles or PFSSD circuits are affected within the HAZ. Each of the penetrations satisfies the review criteria of M-663-00017 where T rating requirements are not met.

Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

M-663-000 17 A 13 Revision W02 Page 14 of 19 5.2.6 Thermal Protective Jacket added to RB-5A Details The Table I penetration seals referring to this section have penetrant sizes exceeding the bounding limitations of the assigned typical detail.

These RB-5A penetrations are 3-hour F rated based on the discussion provided in Section 5.2.2. However, the penetrations are not considered T rated based on the penetrant size exceeding the limitations of the typical detail. Typical detail RB-5A bounds up to a 2" diameter pipe as 3-hour F and T rated, while the penetrations of concern each contain a 4" diameter steel pipe penetrant.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix B 13, were conducted for each penetration of concern. This review was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

The HAZ review identified that combustible Armaflex anti-sweat insulation is provided on the pipe within the heat affected zone on the bottom side of each penetration.

No other exposed insitu combustibles or PFSSD circuits are located within the HAZ. In all cases, the pipe penetrating the barrier opening is protected with fiberglass insulation on the topside and the bottom side is protected with Armaflex insulation.

No insulation transitions through the seal. It has been determined that Armaflex anti-sweat insulation is combustible and should be removed from the pipe on the unexposed side of the barrier for a sufficient distance that will eliminate auto-ignition concerns. However, since the location is within a radiological and/or contaminated area along the ceiling in areas that are difficult to access, an alternative measure was chosen.

This involved protecting the topside penetration seal configuration with a thermal protective jacket to lower unexposed side temperatures on the bottom side in effort to prevent potential auto-ignition of the Armaflex type insulation.

This thermal protective jacket is constructed by wrapping the penetration sleeve, boot and existing pipe insulation with 3" thick ceramic fiber blanket for a distance of 18" from the floor interface. The ceramic fiber is then encapsulated with a 20-gage stainless steel cover, banded in place to prevent dislodgement during potential hose stream activities.

As necessary, the jacket design was locally notched at interferences to eliminate system interaction.

See Figure 2 for the thermal protective jacket design.

M-663-000 17 A Attachment B13 Revision W02 Page 15 of 19 Ceramic fiber is the primary insulating component of the thermal jacket design. Ceramic fiber has been tested and qualified through penetration and seismic gap seal testing programs. Ceramic fiber products are inert and will remain in place for the entire 3-hour qualification period with no material consumption. The resulting installation, as shown in Figure 2, will provide an additional 18" x 3" thick thermal protective barrier along the pipe penetrant to enable lowering of unexposed side temperatures, which will prevent auto-ignition of the Armaflex that is present on the bottom side of the penetration.

The thermal jacket design is installed over existing insulation, thus providing added protection from radiant and conductive energy that could develop from fire exposure on the topside of the barrier. The end result protective configuration provides a cumulative seal depth of approximately 37". The bounding fire tested seal depth was 12" of HOLE between boots containing a 3" depth of ceramic fiber.

Pipe penetrants that utilize fiberglass insulation are protected up to the ceramic filled boot that is part of the installed penetration seal design, thus significantly reducing thermal insult during fire exposure to the installed penetrants.

M-663-00111 demonstrated that insulating pipe penetrants through the seal material would significantly reduce thermal exposure to the seal material and penetrant. This report documented a significant drop in interface temperatures as a result of installed piping insulation.

The actual drop varies depending on postulated system temperatures and insulation thickness, but in all cases the reported temperature drop is significant.

This thermal benefit logic can be applied to fire exposure when considering that the pipe penetrants being evaluated are only slightly larger than that previously evaluated in M-663-00017, Detail RB-5A.

Therefore, direct flame impingement to the test article would be more severe than that expected for the Table I pipe penetrations protected with ceramic fiber thermal jacketing. Based on the construction attributes of the existing insulation and thermal jacketing, it is reasonable to conclude that the penetration seals identified in Table I would resist the affects of fire exposure and prevent conductive and radiant energy exposure to unexposed side of the barrier for a 3-hour duration. Therefore, Table I penetration seals referencing this section are 3-hour F rated and will prevent the auto-ignition of Armaflex type insulation on the unexposed side of the barrier.

Structurally, the addition of the insulating jacket will not affect the seismic qualification, system performance, or the performance of any SSCs in proximity to the seals. The insulating jacket design is self-supporting to the floor, compressible, and will move with any system moment as with the current insulation material installed on the pipes.

Based on the above discussions and considering the installed 37" (approximate) seal design and the pipe penetrant size in relation to that bounded by testing, it is reasonable to conclude that the additional thermal jacket design will provide the additional protection necessary to

M-663-000 17 A Attachment B 13 Revision W02 Page 16 of 19 prevent potential auto-ignition of the unexposed side Armaflex present on the pipe penetrant.

Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

CERAMC fiBER BLAN-<Er --

WI STAN...ES5 STEEL SI*EAHiNC SHT. MErAL (20 GA. MN 1

£M9EIJ I

~" lt.IIN.I FIGURE 2 Thermal Protective Jacket 5.2.7 Penetrations with Lateral Movement Exceeding Typical Detail Penetration seals referring to this section have design penetrant movement that exceeds the bounding limitations of the installed seal configuration. The movement specifically evaluated and inspected were lateral movements that could potentially compress the ceramic fiber within the penetration opening during system operational cycles.

Because significant lateral movement is a worse case scenario these penetrations could not be evaluated acceptable in accordance with Attachment B4.

M-663-000 17 A Attachment B 13 Revision W02 Page 17 of 19 Therefore, intrusive examination was performed to assess the internal ceramic fiber condition.

This inspection revealed that no through-hole opening was present and therefore, these ceramic fiber details (FB-1) are fully bounded in accordance with the penetration attributes. Considering that the plant has been operating for 20 years and has experienced numerous system cycles, it is reasonable to conclude that these booted penetrations have been subjected to the typical system movement that will be seen through the life of the plant. Therefore, no further evaluation is required.

5.2.8 Penetration P371W0948 Penetration P371W0948 is a cable tray blackout through a 12" thick concrete wall. The current seal configuration is not directly bounded by assigned deta'il E-2A. The actual seal configuration is 1 0" Silicone Foam with 1" ceramic fiber damming flush with the barrier plane on both sides with the exception of the cable chase side, where in isolated areas of cable congestion at the top of the blackout, damming continuity is not maintained due to substantial cable fill. At these locations, Silicone Foam is present in lieu of ceramic fiber damming. The resulting overall seal depth for the penetration is maintained at 12".

This configuration provides an acceptable seal based on comparison to the requirements of typical details E-2A and E-18. E-2A requires a 9" Silicone Foam depth between 1" ceramic fiber damming, while E-18 requires a 12" Silicone Foam depth and no damming. The penetration of concern contains a minimum 10" Silicone Foam depth with isolated areas providing a 12" foam depth. Industry fire testing has demonstrated that a 1" ceramic fiber depth provides superior fire resistive performance to that provided by a 1" Silicone Foam depth. Considering this, the penetration seal configuration for P371W0948 is at least equivalent to detail E-18, as Silicone Foam depth is either 12" per the detail requirements or an equal thickness of ceramic fiber damming is substituted for Silicone Foam, where the foam depth is 10". Therefore, the penetration is considered 3-hour F and T rated.

5.2.9 Penetration P142W1932 Penetration P142W1932 contains a large penetrant size that is not directly bounded by detail M-6A.

As discussed in Section 5.2.5, the primary seal material (Silicone Foam) chars during fire exposure, with the char rate typically accelerating as the penetrant size increases.

To address this concern, the Silicone Foam seal will be removed and a full barrier (36") thick ceramic fiber seal will be installed.

This seal configuration was necessary, as it was not cost effective or ALARA wise to add ceramic fiber to the recessed side of the existing seal in the 'A' RHR Heat Exchanger Room (A-10), where the penetration is located 30 feet from the floor. The seal work will be conducted in the 2026' Corridor 1408 (A-16) where the seal is readily accessible.

This action will

M-663-000 17 A 13 Revision W02 Page 18 of 19 necessitate original seal removal, since it is installed flush with the barrier plane on the A-16 side.

Ceramic fiber is an inert material comprised of compressed refractory fibers. It is not charred or consumed during fire exposure. The material will not be negatively affected by heat transmission through the penetrating item. Therefore, penetrant size is not a concern regarding capability of a ceramic fiber seal to prevent flame and hose stream passage to the unexposed side, as the material depth and penetration annulus are well within the bounding limitations of typical ceramic fiber seal detail A-7 from M-663-000 17. However, penetrant size is a concern regarding unexposed side temperature development.

Therefore, penetration P142W1932 is considered F but not T rated.

M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F

  • rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipment/circuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, a field walkdown and comprehensive assessment review, documented in Appendix 813, was conducted for the penetration of concern. This review was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that no exposed insitu combustibles or PFSSD circuits are affected within the HAZ. The penetration satisfies the review criteria of M-663-00017 where T rating requirements are not met.

Therefore, P142W1932 is acceptable, as this evaluation demonstrates reasonable assurance that the penetration seal does not present a negative impact to PFSSD capability.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation. The Table I penetrations are evaluated as 3-hour F rated or are 3-hour F and T rated where stated. The comprehensive walkdown review for each of the non-T rate penetration seals revealed that no exposed insitu combustibles outside what was evaluated existed, and no PFSSD circuits are negatively affected by the non-T rated penetrations.

Therefore, no PFSSD circuits are negatively affected by the non-T rated penetrations

M-663-000 17 A 13 Revision W02 6.0 Conclusions Page 19 of 19 Based on the above discussions, it is reasonable to conclude that the Table I penetration seals that were not bounded to T rating requirements are acceptable as 3-hour F rated and will perform their intended design function. The additional modification made to these penetrations significantly enhance the seal performance, ensuring that regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements to prevent spread of fire from one fire area to another are satisfied. It has also been determined through this evaluation that the lack of a T rating will not affect the plant's ability to achieve and maintain PFSSD.

M-663-00017A Revision WOJ Page 813-1 ofBI3-Penetration Seal Data Appendix:

B13 Penetration #:

P112W1377 Penetration Type:

M-6A Fire Area (Side 1): A-1 Fire Area (Side 2): C-1 Loc.!Eiev.:

1979'-6" M-OX Dwg: M-1X1902

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

2"

2. Opening Size:

42"0

11. Gap between pen:

N/A

3. Penetrants:

(1)30"P

12. Barrier Type:

A F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Flush

14. Pipe Insulated:

Yes

6. Damming Side 2:

25"recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth :

9" Reviewed By:

Walkdown Comments:

Insulation abuts damming, does not transition through seal zone.

Sketch:

M-663-00017A, Revision WOl Page B\\3-2 ofBJ3-8 Penetration Seal Data Appendix:

813 Photos:

P112W1377 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-000I?A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P112W1377 Fire Area (Side 1)

A-1 t 1-1/2" Cond. 5J3022, not within Heal Affected Zone.

Fire Area (Side 2)

C-1

2. 4" Cond. 4U1 F1A. not with Heat Affected Zone
3. 3/4" Cond. 4J301 8, not within Heat Affected Zone
4. 1" Cond. 6J1A10, not within Heat Affected Zone Side 1 Photo Side2Photo Sketch p *.. *-
  • IS
  • f!/- **.,... - A.

Page B 13-3 of B 13-88 Appendix:

813 Review Distances (Rolftltwlce ~17A.

FQUIW 7.2.3-1 I 30" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft)

("F) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 6

6.5 7

1706 1513 1342 1 1192 11059 942

, 839 748 668 597 535 480 432 389 FA:C.1 llde2 (In)

(in) 4.5 5.9 3.7 5

2.9 4.2 2.2 3.6 1.6 3

1.1 2.4 0.6 2

0.2 1.6 Contact 1.2 0.9 0.6 0.4 0.1 Contact

M-663-000 17 A Revision WO I Page B 13-4 of B 13-Penetration Seal Data Appendix:

B13 Penetration #:

P112W1379 Penetration Type:

M-6A Fire Area (Side 1 ):

A-1 Fire Area (Side 2):

C-1 Loc./Eiev.:

1979'-6" M-OX Dwg: M-1X1902

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

1 1/2"

2. Opening Size:

42"0

11. Gap between pen:

N/A

3. Penetrants:

(1)30"P

12. Barrier Type:

A F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Flush

14. Pipe Insulated:

Yes

6. Damming Side 2:

24"recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Insulation abuts damming, does not transition through seal zone.

Sketch:

M-663-00017A, Revision WOI Page B 13-5 of 8 13-Penetration Seal Data Appendix:

813 Photos:

P112W1379 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P112W1379 Fire Area (Side 1)

A-1

1. Secunty communications cable, not within Heat Affected Zone
2. Combustible Material Storage Area directly adjacent and under penetration seal.

Fire Area {Side 2)

C-1

2. 314"11ghting conduit, not within Heat Affected Zone Side 1 Photo Sketch FA: A-t Slde1 Side 2 Photo Page B 13-6 of B 13-88 Appendix:

B13 Review Distances (Rafenwloe Moll6).()0()17A. F"9ft 7 U1 I L1 & L2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

5.5 16 6.5 7

30" Pipe Temp. R1 Radius

("F)

(in) 1706 4.5 1513 3.7 1342 12.9 1192 2.2 1059

1.6 J 942 1.1

]839 0.6 748 0.2 I 668 Contact 1_597 535 480 432 389 FA:C.1 llde2 R2 Radius (in) 5.9 5

4.2 3.6 3

24 2

1.6 1.2 0.9 0.6 1*0.4 I 0:1 1 Contact I

M-663-000 17 A, Revision WO 1 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

1983'-10

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :
6. Damming Side 2:

P113W0421 M-1 12" Nominal 12"0 (1)8"P Foam Flush 2-1 /2" Recess

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth :

7 -1 /2" Walkdown Comments:

Sketch:

Page 8 !3-7 of BI3-Appendix:

B13 Fire Area (Side 1): A-1 M-OX Dwg: M-1 X0360 Fire Area (Side 2): A-5

10. Annular Gap (smallest):

3/4" 11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Steel

M-663-00017A, Revision WOI Penetration Seal Data Appendix:

813 Photos:

P113W0421 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-5 (Side 2)

Fire Area A-5 (Side 2)

M-663-000l?A Revision WOJ Page B 13-9 of B 13-8 Penetration Seal Data Appendix:

B13 Penetration #:

P121S0284 Penetration Type:

RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2):

A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1211

1. Barrier Thickness:

19"

10. Annular Gap (smallest):

2"

2. Opening Size:

8"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 4"P

12. Barrier Type:

F R

W

4. Sealant Type:

HDSE/HDLE, Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1; Boot
14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC1211.

Pipe is insulated in A-1 and covered with Armaflex in A-4, this is not considered insulated for the purpose of heat exposure_

Sketch:

FA: A-1 SIDE 1 FA: A-4~~~~~

SlDE2 s" 0 t!rttJ

_j P121SQ2.84

M-663-00017A Revision WOI Page 813-10 of BJ3-8 Penetration Seal Data Appendix:

813 Photos:

P121S0284 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P121S0284 Fire Area (Side1)

A-1 No Issues within Heat Affected Zone Fire Area (Side 2)

A-4

1. Armaftex on pipe.: Additional Evaluation Required.

Side1 Photo Sketch FA:A-i Sktei Side2 Photo Page 813-11 ofB13-88 Appendix:

813 Review Distances (FWartnoe~17A.Fua7.2.3-l l

L1 & L2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

A

  • t l.

~

  • "it *j A

. -. ~.

4" Pipe Temp.

m 1625 1374 1163 987 839 715 610 523 450 389 FA: A-4 81de2 R1 Radius (In) 42 3

2.1 1.3 0.6 0.1 Contact R2 Radius (in}

5.5 4.4 3.4 2.6 2

1.4 0.9 0.6 l o.2 Contact

M-663-00017A Revision WOl Page 8 13-1 2 of B 13-8 Penetration Seal Data Appendix:

B13 Penetration #:

P121S0285 Penetration Type:

RB-SA Fire Area (Side 1 ):

A-1 Fire Area (Side 2): A-4 Loc./Elev.: 1988'-0" M*OX Dwg: M-OX1211

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

19" 8"0 (1) 4"P HDSE/HDLE, Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth :

Assumed Per Detail Walkdown Comments:

Slab thickness determined from drawing C-OC 121 1.

Sketch:

FA: A-1 SIDE 1

- ~CT\\OfJ" FA: A-4 SIDE2

10. Annular Gap (smallest):

1-1/2"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

-n.

_l P121S028S R

W Steel

M-663-00017A Revision WOI Penetration Seal Data Appendix:

813 Photos:

P121S0285 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1 )

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-000J7A, Revision WOI Penetration Seal Data Heat Affected Zone Review:

P121S0285 Fire Area (Side 1}

A-1 No issues within Heat Affected Zone Fire Area (Side 2)

A-4

1. Armaftex on pipe: Addition evaluation Required Side 1 Photo Sketch FA:A-1 Slde1 Side2Photo p oto, Page 8 13-14 of BJ3-88 Appendix:

813 Review Distances (Reference ~17A.

Fi91n 7 ~1 I 4*P1pe L1 & L2 Temp. R1 Radius R2Radlus Dist. (ft)

("F)

(In)

(In) 0.5 1625 4.2 5.5 1

1374 3

4.4 1.5 1163 2.1 3.4 2

987 1.3 2.6 2.5 839 0.6 2

3 715 0.1 1.4 3.5 610 Contact 0.9 4

523 0.6 4.5 450 0.2 5

389 Contact I

I

Page B 13-15 of B 13-Penetration Seal Data Appendix:

B13 Penetration #:

P121S0287 Penetration Type:

RB-5A Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Elev.:

1988'-0" M-OX Dwg: M-OX1211

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

22" 8"0 (1)4"P HDSEIHDLE, Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth :

Assumed Per Detail Walkdown Comments:

Slab thickness determined from drawing C-OC 1211.

Anti-sweat on bottom side is not considered insulation.

Sketch:

FA; A-1 SIDE 1

10. Annular Gap (smallest):

1"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

r P121S0287 R

W Steel

M-663-00017 A Revision WOl Page B 13-1 6 of B 13-8 Penetration Seal Data Appendix:

813 Photos:

P12150287 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017A. Revision WOI Penetration Seal Data Heat Affected Zone Review:

Fire Area (Side 1)

A-1 No issues within Heat Affected Zone Fire Area (Side 2)

A-4 1 Atmaflex on pipe.: Additional Evaluation Required

2. Unscheduled conduit (Detection), not an issue.

P12150287 Side1 Photo Side2Photo Sketch FA: A-1 lld*1 pho

. p. -

  • 0....

I I) '*

~

  • I r.

Page Bl3-17 ofBl3*88 Appendix:

813 Review Distances (Relonrn:a t.+663-00017A.F"0117.2.~1)

L1 &L2 Oist. (ft 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

0..

~ R.

4RPi Temp. R1 Radius 2.1 987 1.3 839 10.6 715 0.1 610 Contact 523 450 389 FA: M Side2 R2 Radius 4.4 3.4 2.6 2

1.4 0.9 0.6 02 I Contact

M-663-000J7A Revision WOJ Page B 13-18 of B 13-Penetration Seal Data Appendix:

813 Penetration #:

P132W1845 Penetration Type:

M-6A Fire Area (Side 1): A-8 Fire Area (Side 2): A-3 Loc./Eiev.: 2013'-9" M-OX Dwg: M-1X191 8

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

3"

2. Opening Size:

30"0

11. Gap between pen:

N/A

3. Penetrants:

(1)24"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

1/4" recessed

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):
  • Accept Prepared By:
8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9-3/4" Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing 1-C01321.

  • Partially exposed, acceptance applies to exposed surfaces only. Changed Detail from M-1 to M-6a based on actual seal depth.

Sketch:

FA: A-8 Sde1

..

  • o*

~

0 I>.

  • FA: A-3 P132W1845 s d 2

M -663-000 17 A, Revision WO l Page B 13-19 of B I -

Penetration Seal Data Appendix:

813 Photos:

P132W1845 Fire Area A-8 (Side 1}

Fire Area A-8 (Side 1}

Fire Area A-3 (Side 2}

Fire Area A-3 (Side 2)

M-663-000J7A, Revision WOI Penetration Seal Data

  • Heat Affected Zone Review:

P132W1845 Fire Area (Side 1)

A-8 No issues within Heat Affected Zone I

Fire Area (Side 2)

A-3 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch Page 813-20 of 813-88 Appendix:

813 Review Distances (RefaaiCI M-663-00017,6,. f""IQin 7.2.3-1 l 24" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dlsl (ft)

(*F)

(in)

(In) 0.5 1763 4.8 6.1 1

1615 4.1

. 5.5 1.5 1480 3.5

. 4.9 2

1357 3

4.3 2.5 1244 2.5 3.8 3

1141 2

3.3 3.5 1048 1.6 2.9 4

962 1.2 2.5 4.5 884 10.8 2.2 5

813 0.5 1.9 5.5 748 1 0.2 1.6 6

689 I Contact 1.3 6.5 635 u

7 585 0.8 7.5 540 0.6 8

499 0.4 8.5 462 0.3 9

427

().1 9.5 396 Contact No sketch requir

M-663-000 17 A, Revision WO I Page B 13-21 of 8 13-Penetration Seal Data Appendix:

B13 Penetration #:

P133S0762 Penetration Type:

FB-1 Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

3/4"

2. Opening Size:

8"0 11. Gap between pen:

N/A

3. Penetrants :

(1)2"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

N/A

14. Pipe Insulated:

Yes

6. Damming Side 2:

N/A Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

14" **

Reviewed By:

Walkdown Comments:

Current Boot condition is acceptable and shows no degradation from excessive moments. There is evidence of previous repair on the top side. However, it physically appears to be quite old. Label ordered. Slab thickness determined by Drawing C-1 C1311. **sealant depth determined by inspection report.

Sketch:

FA: A-8 SIDE 1 FA: A-1 SIDE2 P133S0762

M-663-00017A Revision WOI Page B 13-22 of 8 13-Penetration Seal Data Appendix:

B13 Photos:

P133S0762 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A Revision WOl Page B 13-23 of B 13-Penetration Seal Data Appendix:

813 Penetration #:

P13350784 Penetration Type:

RM-1AIA-7 Fire Area (Side 1):

A-25 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

2-1 /2"

2. Opening Size:

20"0

11. Gap between pen :

N/A

3. Penetrants:

(1) 14"P

12. Barrier Type:

F R

4. Sealant Type:

HDSE/HDLE

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

HOLE flush w/sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

14-1/2" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C 1311. Top side HOLE flush with sleeve end. Bottom side pipe is insulated. top side has Armaflex. Slab thickness determined by Drawing C-1 C 1311. Sealant depth determined from inspection document and observation of seal material within sleeve.

Sketch:

FA: A-U S de 1

<~f'/'cLI 1' NStltA/J a~

P133S0784

'(> -

() '

1 bt.t/ rl bSE I

fA. A-1 Side2

M-663-00017A Revision WOl Page B 13-24 of B 13-Penetration Seal Data Appendix:

813 Photos:

P133S0784 Fire Area A-25 (Side 1)

Fire Area A-25 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Heat Affected Zone Review:

P133'S0784 Fire Area (Side 1)

A-25 1 Almaftex on pipe: Additional Evaluation Required Fire Area (Side 2)

A-1 No issues within Heat Affected Zone Side 1 Photo Side 2 Photo Sketch FA: A-215 Slde1

~~lf4x Page B13-25 ofB13-88 Appendix:

613 Review Distances (Ref-M$3-00017A. r'!IIA 72.3-1l L1 & L2 Dist. (ft) 0.5 1

1.5 2

2.5 3

3.5 4

4.5 5

~ - 5 6

6.5

  • 7 17.5 1.4* Pipe Temp. R1 Radius rf)

(in) 1721 4.6 1539 3.8 1377 3

1233 2.4 1105 1.8 991 1.3 889 0:9 799 0.4 719 D.1 647 Contact 583 527 477 I

432 392 FA:A-1 Slde2 R2 Radius (in) 5.9 5.1 4.4 3.8

~.2 12.7 2.2 1.8 1.4 1.1 0.8 0.6 0.3 10.1 Contact