ML18093B027

From kanterella
Jump to navigation Jump to search
1 to Updated Safety Analysis Report, Structural Steel Fireproofing Data, M-663-00017A, Rev W06, G1A-64 to G1A-162
ML18093B027
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 03/08/2018
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 M-663-00017A, Rev W06
Download: ML18093B027 (60)


Text

M-663-00017 A. Revision W03 Page G1A-64 of G1A-162 St,ructural Steel Fireproofing Data Appendix G1A Room-Elevation:

1316-2000 Building:

Auxiliary Fire Area:

==

Description:==

Valve Compartment Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/R

  • Member Size:

N/R Comments:

Fireproofed steel within this room is miscellaneous steel not primary building steel Room Sketch:

Thermal Short #2 (TS2) 1Data N/A N/A N/A No Columns No sketch required.

Thermal Short #1 Sketch No sketch required.

A-08

M-663-00017A, Revision W03 Page G1A-65 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

1317-2000 Building:

Auxiliary Fire Area:

A-08

==

Description:==

Seal Water Heat Exch Rm Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

Comments:

N/A N/R N/R Fireproofed steel within this room is miscellaneous steel not primary building steel N/A N/A N/A No Columns Room Sketch:

No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1319-2000 Building:

Demineralizer Compartments Typical of 8 Thermal Short #1 (TS1) Data N/A N/A N/A No Exposed Steel Room Sketch:

Page G1A-66 of G1A-162 Appendix G1A Auxiliary Fire Area:

A-08 Thermal Short #2 (TS2) Data N/A N/A N/A No Exposed Steel No sketch required.

Thermal Short #1 Sketch No sketch required.

i

M-663-00017 A, Revision W03 Page G1A-67 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

1321-2000 Building:

Auxiliary Fire Area:

A-08

==

Description:==

Exit Vestibule Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

Comments:

C-OS1 431 Beam 15 X 50 Beam is embedded or supported by underlying Wall, Thermal Short Review not required.

Room Sketch:

N/A N/A N/A No Columns EU!.v. zooo'

(~~)----~----------~~r-t===~~

bOO~

I Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Page G1A-68 of G1A-162 Structural Steel Fireproofing Data Appendix G1A 1321-2000 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 Thermal Short #2 Sketch No sketch required.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1309-2000 Building:

Residual Heat Removal Heat Exch Rm B Thermal Short #1 (TS1) Data N/A Beam N/R No Thermal Short Issues Room Sketch:

Page G1A-69 of G1A-162 Appendix G1A Auxiliary Fire Area:

A-09 Thermal Short #2 (TS2) Data N/A N/A N/A No Columns No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Page G1A-70 ofG1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

1310-2000 BUilding:

Auxiliary Fire Area:

A-10

==

Description:==

Residual Heat Removal Heat Exch Rm A Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

N/A Beam N/R N/A N/A N/A Comments:

No Thermal Short Issues No Columns Room Sketch:

No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Page G1A-71 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

1335-2000 Building:

Auxiliary Fire Area:

A-11

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS1441 N/A Member Type:

N/R N/A Member Size:

N/R N/A Comments:

No Issues No Columns Room Sketch:

No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1336-2000 Building:

Electrical Chase Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this Room Room Sketch:

Page G1A-72 of G1A-162 Appendix G1A Auxiliary Fire Area:

A-12 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this Room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1411-2026 Building:

Main Feedwater Rm No. 1 Thermal Short #1 (TS1) Data C-1S1452 N/R N/R Steel within this room is not protected and is considered Misc. to support floor grating. Steel failure can not impact redundant Train Room Sketch :

- Room Layout

'ioT£"£1.@

2 o ~"""1'- 7~*

Page G1A-73 of G1A-1 62 Appendix G1A Auxiliary Fire Area :

A-23 Thermal Short #2 (TS2) Data C-1S1001 N/R N/R Steel within this room is not protected and is considered Misc. to support floor grating. Steel failure can not impact redundant Train TI-l as ~"Te ll L J.S folol'" ;>~oTt:Y.TtJl>.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1412-2026 Building:

Main Feedwater Rm No. 2 Thermal Short #1 (TS1) Data C-151452 N/R N/R Steel within this room is not protected and is considered Misc. to support floor grating. Steel failure can not impact redundant Train Room Sketch:

Jj'"'.(lfl

""t.fi/TfT

~

Page G1A-74 of G1A-162 Appendix G1A Auxiliary Fire Area:

A-23 Thermal Short #2 (TS2) Data C-1 5 1001 N/R N/R Steel within this room is not protected and is considered Misc. to support floor grating. Steel failure can not impact redundant Train 111..

N ~

  • o

~--~--r---------~~~----r-------~

I b 0

4

-, ~

(J p

Tt~tS STl:"t£/.. IS Ndr f>.r:~nen:D AI Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

1415-2026 Building:

I & C Hot Shop Thermal Short #1 (TS1) Data N/A N/A N/A No Steel Within Room. Steel above is reviewed in Room 1405 Room Sketch:

Page G1A-75 of G1A-1 62 Appendix G1A Auxiliary Fire Area:

A-26 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel Within Room. Steel above is reviewed in Room 1405 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Page G1A-76 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

==

Description:==

Drawing:

Member Type :

Member Size:

Comments:

1413-2026 Building:

Auxiliary Shutdown Panel Room Thermal Short #1 (TS1) Data N/A N/A N/A No Steel Within Room Auxiliary Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel Within Room Room Sketch:

No sketch required.

Thermal Short #1 Sketch

~------------~--------------------------~

No sketch required.

A-28

M-663-00017A, Revision W03 Page G1A-77 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3104-1974 Building:

Control Fire Area:

C-01

==

Description:==

Control, Stair No. C-2, South Access Control to Aux Building Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

Comments:

C-OS3211 N/A N/A Stairwell, See Room 3105 for Details, No Fire Proofing In this Room. See 31 05 for Barrier issue.

Room Sketch:

N/A N/A N/A No Columns No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Page G1A-78 of G1A-1 62 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3106-1974 Building:

Control Fire Area:

C-02

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-0532 11 N/A Member Type:

Beam N/A Member Size:

12 X 27 N/A Comments:

No Columns Room Sketch:

( t


1@;

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Page G1A-79 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3105-1974 Building:

Control Fire Area:

C-03

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-053211 N/A Member Type:

Beam N/A Member Size:

18 X 45 N/A Comments:

Beam supported by underlying wall.

No Columns Room Sketch:

ca I-Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3206-1984 Building:

==

Description:==

Corridor Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

Page G1A-80 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-05 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3212-1984 Building:

Women's Locker Room Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

~

Page G1A-81 ofG1A-162 Appendix G1 A Control Fire Area:

C-05 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type :

Member Size:

Comments:

3213-1984 Building:

Women's Toilet Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-82 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-05 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data

' Room-Elevation:

3214-1984 Building:

==

Description:==

Hall Thermal Short 11 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

Page G1A-83 of G1A-162 Appendix G1A Control Fire Area; C-05 Thermal Short t2 {TS2} Data N/A N/A N/A No Steel within this room o sketch requ*r Thermal Short #1 Sketch o sketch re

M-663-00017A, Revision W03 Structural Stee,l Fireproofing Data Building:

==

Description:==

Men's Shower Room Thermal Short #1 (TS1) Data Drawing:

NIA Member Type:

N/A Member Size:

N/A Comments:

No Steel within this toom Room Sketch:

Page G1A-84 ofG1A-162 Appendix G1A Control Fire Area:

C-05 Thermal Short #2 (TS2) Data N/A NfA N/A No Steel within this room o sketch requir d.

o sketch r

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3216-1984 Building:

==

Description:==

Drying Room Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

Page G1A-85 ofG1A-162 Appendix G1 A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-05 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3217-1984 Building:

Men's Toilet Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

~

Page G1A-86 ofG1A-162 Appendix G1A Control Fire Area:

C-05 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketc required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3218-1984 Building:

==

Description:==

H.P. office Area Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

Page G1A-87 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-05 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3219-1984 Building:

H.P. office Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-88 of G1A-162 Appendix G1A Control Fire Area:

C-05 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3220-1984 Building:

==

Description:==

Sign In/Out Area Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

Page G1A-89 of G1A-1 62 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-05 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Page G1A-90 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3221-1984 Building:

Vestibule No. 1 Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Control Fire Area :

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room Room Sketch :

~----------~~------------------------~

No sketch required.

~--~----------------------------------~

Thermal Short #1 Sketch

~--------------------------------------~

No sketch required.

C-05

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3222-1984 Building:

H.P. office Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-91 of G1A-162 Appendix G1A Control Fire Area:

C-05 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3223-1984 Building:

==

Description:==

Janitors Closet Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No steel, concrete ceiling Room Sketch:

Page G1A-92 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No steel, concrete ceiling C-05 No sketch required.

Thermal Short #1 Sketch l

No sketch required.

M-663-00017 A, Revision W03 Page G1A-93 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3224-1984 Building:

Vestibule No. 2 Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room Room Sketch:

~------------------------------~---------------------------------------~

No sketch required.

Thermal Short #1 Sketch

~

No sketch required.

C-05

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room -Elevation:

3201-1984 Building:

==

Description:==

Control, Stair C-1 Thermal Short #1 (TS1) Data Drawing:

C-083311 Member Type:

Beam Member Size:

N/R Comments:

Room Sketch:

ELt:V. 1984 1

Dooe.

~2011 Thermal Short #1 Sketch Page G1A-94 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Columns No sketch required.

M-663-00017 A, Revision W03 Page G1A-95 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3201-2000 Building:

Control Fire Area:

C-06

==

Description:==

Control, Stair C-1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

Comments:

C-OS3411 Beam N/R Beam is supported by underlying wall N/A N/A N/A No Columns Room Sketch:

r=~~~~~~--- N l<:l.EY* lD00 1

IIJ.T.S.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation :

3201-2016 Building:

==

Description:==

Control, Stair C-1 Thermal Short #1 (TS1) Data Drawing:

C-083511 Member Type:

Beam Member Size:

N/R Comments:

Beam is supported by underlying wall.

Room Sketch :

3Z.OI

£t.EV. ZO!t..

Thermal Short #1 Sketch Page G1A-96 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Columns N ~

IOQ No sketch required.

M-663-00017A, Revision W03 Page G1A-97 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3201-2032 Building:

Control Fire Area:

C-06

==

Description:==

Control, Stair C-1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS3611 Member Type:

Beam Member Size:

14 X 30 Comments:

Beam is supported by underling wall Room Sketch:

N/A N/A N/A No Columns

/ ~

~------------~---~?

~

£ t.£ '/1 1/w Zt1 3 Z

)JTS Thermal Short #1 Sketch I

No sketch required.

M-663-00017A, Revision W03 Page G1A-98 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3201-2047 Building:

Control Fire Area:

C-06

==

Description:==

Control, Stair C-1 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

Comments:

C-183711 Beam 36 X 150 Beam is supported by underlying wall.

N/A N/A N/A No Columns Room Sketch:

ElE.V. Z047'

( IJT!,)

I.,..,..-;.,..

i.

.---..::1)1.1:;__.....,-


@)...

-~~

~r-tft;tt"1t~

- i>>"~

wn~z7 I---rf~~Sf~~~flfJ-

_"'J"~

. J~...,b

- 473007 Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3201-2073 Building:

==

Description:==

Control, Stair C-1 Thermal Short #1 (TS1) Data Drawing:

C-153811 Member Type:

Beam Member Size:

33 X 118 Comments:

Beam Is supported by underlying wall.

Room Sketch:

Thermal Short #1 Sketch Page G1A-99 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Columns No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room -Eievatio n:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3202-1984 Building:

Controlled H.P. Tool & lnst. Storage Room Thermal Short #1 (TS1 ) Data N/A N/A N/A No Steel within this room Room Sketch:

r---

Page G1A-100 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

I Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3203-1984 Building:

Hot Janitors Closet Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-101 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3204-1984 Building:

Corridor No. 1 Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-102 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3205-1984 Building:

H.P. Area Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-103 of G1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-000 17 A. Revision W03 Structural Steel Fireproofing Data Room -Eievatio n:

==

Description:==

Drawing:

Member Type :

Member Size:

Comments:

3207-1984 Building:

Exit Monitor Area Thermal Short #1 (TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-104 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-06 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A. Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3208-1984 Building:

Laundry Room Thermal Short #1 {TS1) Data N/A N/A N/A No Steel within this room Room Sketch:

Page G1A-105 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-06 No sketch required.

Thermal Short #1 Sketch No sketch required.

i

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3209-1984 Building:

==

Description:==

Decon Area Thermal Short #1 (TS1) Data Drawing :

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

Page G1A-106 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room C-06 No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Page G1A-107 of G1A-1 62 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3210-1984 Building:

Control Fire Area:

C-06

==

Description:==

Decon Shower Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

N/A N/A Member Type:

N/A N/A Member Size:

N/A N/A Comments:

No Steel within this room No Steel within this room Room Sketch:

r---

No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3211-1984 Building:

==

Description:==

H.P. Area Thermal Short #1 (TS1) Data Drawing:

N/A Member Type:

N/A Member Size:

N/A Comments:

No Steel within this room Room Sketch:

o sketc Page G1A-108ofG1A-162 Appendix G1A Control Fire Area:

C-06 Thermal Short #2 (TS2) Data N/A N/A N/A No Steel within this room requ1r o sketch requir

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

3230-1984 Building:

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Drawing:

C-08331 1 Member Type:

Beam Member Size:

12 X 27 Comments:

Room Sketch:

.. N 0-

0. * *
  • .;).

., b o * **

Cl r.,~..

Thermal Short #1 Sketch b

0 Page G1A-109 of G1A-162 Appendix G1A Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Columns

.. -I 24m 1110 /ITTACtfrvto-11!;

T !NO :!> I t>e: D ~7l:(.T/IiJ

': f a*"

LJ C-07

M-663-00017A, Revision W03 Page G1A-11 0 of G1A-162 Structural Steel Fireproofing Data Appendix G1A 3230-1984 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 No photo required.

Thermal Short #2 Sketch No sketch required.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room -Elevation:

3229-1984 Building:

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Drawing:

C-OS3311 Member Type:

Beam Member Size:

36 X 160 Comments:

Beam is supported by underlying wall.

Room Sketch:

Thermal Short #1 Sketch Page G1A-111 ofG1A-162 Appendix G1A Control Fire Area:

C-08 Thermal Short #2 (TS2) Data N/A N/A No Columns No sketch required.

M-663-00017 A, Revision W03 Page G1A-112 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3305-2000 Building:

Control Fire Area:

C-1 1

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-083411 N/A Member Type :

Beam N/A Member Size:

36 X 150 N/A Comments:

Beam is supported by underlying wall.

No Columns Room Sketch:

~

To? !'4>10. t..l15K:

f4

~o-:" <00111. C.u ~Ill..,

C..\\4 18'70

<ASU!Ti'A1S G.4 ~" 10 c lo.l TlttS ~,,.,

0~ CH"' c.A'a!

\\.lOT AFI'ec.TC:b

(.JlMO BT

-Tik:l~

~~err

{.,(SA.?o 0~

1'\\ liZ.

c..ca, 10 153-Dz. I t..J't S7D 1 330~ 1 C.u ~H70 A.

~

c..J t T7o 33o51 rv Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation :

3306-2000 Building:

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Drawing:

C-OS3411 Member Type:

Beam Member Size:

12 X 27 Comments:

Room Sketch:

~ - -

5ll1881-a<~4\\llat-

~ N I J~'-1 5JiiiSI-S"C8A51-1S I

5 C8Q8l-5"J" Il(61 -

5"Uo!:ll>8t -

fL£V. zoc:o' 5JjJ<.8\\-

~TS Thermal Short #1 Sketch

. ~

Page G1A-1 13 of G1A-1 62 Appendix G1A Control Fire Area:

C-12 Thermal Short #2 (TS2) Data N/A N/A N/A No Columns

--~

-~

- Ll

-r'l

--c-J j');ot l

--LJ

M-663-00017A, Revision W03 Page G1A-114 of G1A-162 Structural Steel Fireproofing Data Appendix G1A 3306-2000 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 Thermal Short #2 Sketch No sketch required.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Structural Steel Fireproofing Data Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3403-2016 Building:

Non-Vital Swgr & Xfmr Rm No. 1 Thermal Short #1 (TS1) Data C-OS3511 Beam 14 X 30 Room Sketch:

Thermal Short #1 Sketch I

Page G1A-115 of G1A-162 Appendix G1A Control Fire Area:

C-15 Thermal Short #2 (TS2) Data C-OS3001 Column 14 X 370 No Thermal Shorts, column is bounded by testing.

/..).

M-663-00017A, Revision W03 Page G1A-116 of G1A-162 Structural Steel Fireproofing Data Appendix G1A 3403-2016 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 Thermal Short #2 Sketch No sketch required.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

No photo required.

M-663-00017A, Revision W03 Page G1A-117 ofG1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3418-2016 Building:

Control Fire Area:

C-17

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-053511 N/A Member Type:

Beam N/A Member Size:

12 X 27 N/A Comments:

No Columns Room Sketch:

Q¥l] __ _

Thermal Short #1 Sketch u

' u '

1 4

~

i ~ '~*., C I

41

M-663-00017A, Revision W03 Page G1A-118 of G1A-162 Structural Steel Fireproofing Data Appendix G1A 3418-2016 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 Thermal Short #2 Sketch No sketch required.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

No photo required.

M-663-00017 A, Revision W03 Page G1A-119 ofG1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

3419-2016 Building:

Control Fire Area:

C-18

==

Description:==

Electrical Chase Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-OS3511 N/A Member Type:

Beam N/A Member Size:

12 X 27 N/A Comments:

No Columns Room Sketch:

~

-.N

@-f I

I I3*Mt 1 ~4,... 1 f'"~

WIUti DoD~ 311.,1 I

~

b.,..~

3olto'13 I

Thermal Short #1 Sketch VII! W Lt>OK.IN.ti W~~~

  • 'i" 7)/J:;

A S5VAIVP.

M-663-00017A, Revision W03 Page G1A-120 of G1A-162 Structural Steel Fireproofing Data Appendix G1A 3419-2016 Thermal Short #1 Photo 1 Thermal Short #1 Photo 2 Thermal Short #2 Sketch No sketch required.

Thermal Short #2 Photo 1 Thermal Short #2 Photo 2 No photo required.

No photo required.

M-663-00017 A, Revision W03 Page G1A-121 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

C019-2016 Building:

Control Fire Area:

C-19

==

Description:==

Cable Chase@ CA-C3, 2016-0 to 2032-0 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

Member Type:

Member Size:

Comments:

C-083511 N/R N/R No Steel Attachments N/A N/A N/A No Columns Room Sketch:

No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017 A, Revision W03 Page G1A-122 of G1A-162 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

C020-2016 Building:

Control Fire Area:

C-20

==

Description:==

Cable Chase@ CA-C6, 2016-0 to 2032-0 Thermal Short #1 (TS1) Data Thermal Short #2 (TS2) Data Drawing:

C-083511 N/A Member Type:

Beam N/A Member Size:

N/R N/A Comments:

Unistrut only No Columns Room Sketch:

No sketch required.

Thermal Short #1 Sketch No sketch required.

M-663-00017A, Revision W03 Page G1A-123 of G1A-1 62 Structural Steel Fireproofing Data Appendix G1A Room-Elevation:

==

Description:==

Drawing:

Member Type:

Member Size:

Comments:

3505-2032 Building:

Electrical Chase Thermal Short #1 (TS1) Data C-08361 1 Beam 36 X 230 HAZ Only, Beam supported by underlying wall Control Fire Area:

Thermal Short #2 (TS2) Data N/A N/A N/A No Columns Room Sketch:

l35o'l A

..------- Y.IDS"I -----, --~ 11...113'-

f.ii..GVF+ 71D&.J 2,o~'2...

Nt5 Thermal Short #1 Sketch V

NO 7J'e"~n7/lt.. S4'ai?1

/~S.<Jc:""S.

~

[

J J r

1 I

I

!W~>'~

No sketch required.

C-23