ML21168A162
| ML21168A162 | |
| Person / Time | |
|---|---|
| Site: | Wolf Creek (NPF-042) |
| Issue date: | 06/07/2021 |
| From: | Wolf Creek |
| To: | Office of Nuclear Reactor Regulation |
| Shared Package | |
| ML21168A142 | List:
|
| References | |
| WO 21-0011 | |
| Download: ML21168A162 (21) | |
Text
FORM APF-05D-001-02, REV. 12 CALCULATION CHANGE NOTICE CCN NO.
XX-E-013 Base Calc No.
- 004 Rev No.
Page 1 CN006 Sequence No.
CALCULATION TITLE - From CALCULATION TITLE field in EIS:
Post-Fire Safe Shutdown (PFSSD) Analysis COMPUTER CODE:
VERSION:
Administrative?
YES NO ASSOCIATED ENGINEERING CHANGE #:
012513 REGULATORY REVIEWS:
Attached Attached to:
Not Applicable Evaluation #
CP 012513 N/A Only if Administrative USAR STATEMENT:
Requires a change to the USAR:
Does NOT require a change to the USAR ANY DOCUMENTS IMPACTED?
YES If yes, enter: SWO #, or Condition Report #, if applicable.
NO Status:
COMMITTED FINAL VOID SUPERSEDED ORIG DigsigOrg 2.8, 0.7 NA-Vendor Calculation Printed Name NA Signature QUALIFICATION REQUIRED:
Date ES9280479 ORIG Printed Name Signature QUALIFICATION REQUIRED:
Date ES9280479 VERF DigsigVer 2.8, 0.7 William M. Wilkins Printed Name Signature QUALIFICATION REQUIRED:
02/24/2020 Date ES9280479 VERF Printed Name Signature QUALIFICATION REQUIRED:
Date ES9280479 APP DigsigApp 2.8, 0.7 Jeff Suter Printed Name Signature 02/26/2020 Date APP Printed Name Signature Date DigsigCert 3.5 1.75 Vendor supplied document - WCNOC PE Stamping is not required per WCNOC-162 Rev. 05, Section 8.1.13.
DigsigCert 3.5 1.75 RPE Certification (For ASME Section III Stress Reports/Design Reports, refer to AP 05D-001 for qualification requirements)
CALCULATION SUBJECT (Statement Of Problem) - Enter this in SUBJECT field in EIS:
CP 012513 XNB02 replacement impact to revise relay designations for transformer protection features. Additionally, discussion of load tap changer feature of new transformer included with clarification it is not PFSSD.
FORM APF-05D-001-02, REV. 12 CALCULATION DATABASE INPUT CCN NO.
XX-E-013 Base Calc No.
- 004 Rev No.
Page 2 CN006 Sequence No.
Link new systems to the calculation/CCN in EIS.
Systems Affected:
NB, MA Develop relationships between interdependent calculations in EIS.
Additional Calculations Providing Input to this calculation:
None Additional Calculations Impacted by this calculation:
None Develop relationships between the calculation/CCN and controlled reference documents in EIS.
Additional Controlled Documents Inputs to this calculation:
None Additional Controlled Documents Impacted by this calculation:
None The reference documents listed below are those that cannot be linked to the calculation/CCN and shall be entered in the INDUSTRY REFERENCE field in EIS, e.g., ASME Codes, ANSI Standards, letters, etc.
Additional Other Reference Documents:
CP 012513, Enercon Calc. WCN-025-CALC-019 Link new components to the calculation/CCN in EIS.
Additional Components:
None REFER TO DESKTOP GUIDE FOR PROCESSING CALCULATIONS IN EIS
FORM APF-05D-001-02, REV. 12 ATTACHMENT 1 CCN NO.
XX-E-013 Base Calc No.
- 004 Rev No.
Page 3 CN006 Sequence No CCN Page No.
Calc.
Page Affected DVR/SCRN/
Other CCN Page No.
Calc.
Page Affected
/DVR/SCRN
/Other CCN Page No.
Calc.
Page Affected
/DVR/SCRN
/Other CCN Page No.
Calc.
Page Affected
/DVR/SCRN
/Other 1-3 None 4(Att.
1)
Appendix 1; p63 Appendix 2; p8 Appendix 4; p17,24 OAR None
FORM APF-05D-001-02, REV. 12 ATTACHMENT 1 CCN NO.
XX-E-013 Base Calc No.
- 004 Rev No.
Page 4 CN006 Sequence No Vendor calculation WCN-025-CALC-019, Rev 1
Page 1 of 8 Note 1: For non-safety-related calculation, design verification can be substituted by review.
CALCULATION COVER SHEET CALC NO.
WCN-025-CALC-019 REV. 1 PAGE NO.
1 of 8
Title:
UPDATE TO WCNOC CALCULATION XX-E-013, PFSSD ANALYSIS Client:
WCNOC Project Identifier:
WCN-025 Item Cover Sheet Items Yes No 1
Does this calculation contain any open assumptions, including preliminary information, that require confirmation? (If YES, identify the assumptions.)
2 Does this calculation serve as an Alternate Calculation? (If YES, identify the design verified calculation.)
Design Verified Calculation No.
3 Does this calculation supersede an existing Calculation? (If YES, identify the design verified calculation.)
Superseded Calculation No.
Scope of Revision:
Revised Sec. 5.0 and Appendix A to address DCP 12513 90% Comments.
Revision Impact on Results:
This calculation documents the changes for the replacement of transformer XNB02.
Study Calculation Final Calculation Safety-Related Non-Safety-Related (Print Name and Sign)
Originator:
Alex Wurtz Date:
2//2020 Design Verifier1 (Reviewer if NSR): Stacey Graybeal Date:
2//2020 Approver: Austin Tran Date:
2//2020 Alex Wurtz Digitally signed by Alex Wurtz Date: 2020.02.20 13:47:40
-06'00' Digitally signed by Stacey Graybeal Date: 2020.02.20 14:09:35
-06'00' Digitally signed by Austin Tran DN: cn=Austin Tran, ou=Enercon Services, Inc., email=atran@enercon.com, c=US Date: 2020.02.20 14:13:33 -06'00' Digitally signed by Austin Tran DN: cn=Austin Tran, ou=Enercon Services, Inc.,
email=atran@enercon.co m, c=US Date: 2020.02.20 14:14:22
-06'00'
Page 2 of 8 CALCULATION REVISION STATUS SHEET CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
2 of 8 CALCULATION REVISION STATUS REVISION 0
1 DATE 01/30/2019 2//2020 DESCRIPTION Initial Issue Revised Sec. 5.0 and Appendix A to address DCP 12513 90% Comments.
PAGE REVISION STATUS PAGE NO.
3,6-8 1,2,4,5 REVISION 0
1 PAGE NO.
REVISION APPENDIX/ATTACHMENT REVISION STATUS APPENDIX NO.
A NO. OF PAGES 4
REVISION NO.
1 ATTACHMENT NO.
NO. OF PAGES REVISION NO.
Page 3 of 8 TA/BLE OF CONTENTS CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
3 of 8 Section Page No.
1.0 Purpose and Scope
4 2.0 Summary of Results and Conclusions 4
3.0 References 5
4.0 Assumptions 5
5.0 Design Inputs 6
6.0 Methodology 7
7.0 Calculations 8
8.0 Computer Software 8
List of Appendices
- of Pages A
- Markup Updates to XX-E-013 4
UPDATE TO WCNOC CALCULATION XX-E-013, PFSSD ANALYSIS CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
4 of 8 CSP 3.03 Attachment E Page 4 of 8 Revision 2
1.0 Purpose and Scope
Wolf Creek is performing a systematic replacement of their large oil-filled transformers to address aging concerns and to implement design improvements in support of long term station operation.
ESF Transformer XNB02 is to be replaced prior to the replacement of ESF transformer XNB01.
DCP 012513 is replacing XNB02 and the new transformer will have a Load Tap Changer (LTC) to control the voltage supplied to 4.16kV bus NB02 even if the 13.8 kV input voltage level changes. The DCP is also replacing/deleting relays in the PA201 13.8kV switchgear panel and the relays are addressed by XX-E-013. The purpose of this calculation is to document the impact on Wolf Creek calculation XX-E-013 due to these changes.
This calculation is non-safety related per the ENERCON requirements. The Wolf Creek update will be considered special scope per the site requirements.
2.0 Summary of Results and Conclusions Wolf Creek calculation XX-E-013 does not have any computations. It is a document used to identify the components required to support the Post Fire Safe Shutdown (PFSSD) functions. Based on the results of this calculation the addition of the LTC controls will not impact the PFSSD function of XNB02. Two overcurrent relays (287/T2 Phase B and Phase C) are removed from the calculation (287/T2 Phase A is replaced with one new relay to monitor all three phases). Also, components 263-1/T2, 263X-1/T2, 263-2/T2 and 263X-2/T2 are removed from the calculation (no longer required for the sudden pressure alarm/trip function). New fault pressure trip relays 263FP K4A and 263FP K4B are added because they provide a trip input for breaker NB00209 (XNB02 input breaker to NB02). Cable 16NBK16AA supplies 125VDC to the sudden pressure monitor that contains the two relays at
UPDATE TO WCNOC CALCULATION XX-E-013, PFSSD ANALYSIS CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
5 of 8 CSP 3.03 Attachment E Page 5 of 8 Revision 2 XNB02. Failure of this cable does not cause the relays to change state and cause a loss of power to XNB02. Therefore, cable 16NBK16AA is not a PSFFD related cable. Drawing E-1F9426 is impacted by this change and will be revised by DCP 012513 via WIP-E-1F9426-002-A-1. The proposed changes to XX-E-013 as a result of DCP 012513 are acceptable.
3.0 References 3.1 Wolf Creek Calculation XX-E-013, PFSSD Analysis, Rev. 4 3.2 E-074-00001, Outline (Trans-Sealed), Rev. W09 3.3 DCP 012513, XNB02 Replacement, Rev. 0 3.4 E-1F9426, Post Fire Safe Shutdown Logic Diagram Support Function
- Electrical, NB002 Off-Site Power Availability, Rev. 2 3.5 E-1F9910, Post Fire Safe Shutdown Fire Area Analysis, Rev. 16 3.6 E-009-00061, Arrangement Diagram, PA02, Rev. W15 3.7 E-009-00198, Connection Diagram (Metal Clad Switchgear, Cust. Unit PA201), Rev. W12 3.8 E-15000, Electrical Cable and Raceway List, Rev. 67 3.9 E-1R4431, Raceway Plan Turbine Building Area-3 EL. 2033-0, Rev.
2 3.10 E-1R4331, Raceway Plan Turbine Building Area-3 EL. 2000-0, Rev.
1 3.11 E-1R4321, Raceway Plan Turbine Building Area-2 EL. 2000-0, Rev.
2 3.12 E-1R4322, Exposed Conduit Turbine Building Area-2 EL. 2000-0, Rev. 5 3.13 E-13NB11, Schematic diagram 13.8 KV XNB02 Feeder BRKR.
252PA0201, Rev. 6 3.14 E-13NB16, ESF Transformers Auxiliary Power and Control Schematic Diagram, Rev. 1 4.0 Assumptions There are no assumptions used in the calculation.
UPDATE TO WCNOC CALCULATION XX-E-013, PFSSD ANALYSIS CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
6 of 8 CSP 3.03 Attachment E Page 6 of 8 Revision 2 5.0 Design Inputs Reviews of existing change notices against XX-E-013 were performed to determine if any of the documents impact the changes being performed by DCP 012513. Results are as follows:
x XX-E-013-004-CN001 - VOID x
XX-E-013-004-CN002 - FINAL - DCP 14209 removes the HMCP breakers from MCC cubicles NG03DBF6 and NG04DBF6, which were added as PFSSD components in CCN XX-E-013-002-CN014 per DCP 13800. These breaker cubicles provide power and control functions for Train A and B emergency diesel generator room supply fan motors DCGM01A and DCGM01B, respectively. Due to breaker coordination issues, DCP 14209 will modify the power supply to supply 480 VAC power to the diesel generator room supply fan motors DCGM01A and DCGM01B directly from new load center breakers NG0308 and NG0408, respectively. Breakers NG0308 and NG0408 will supply power to the fan control functions within NG03DBF6 and NG04DBF6, respectively. Therefore, MCC cubicles NG03DBF6 and NG04DBF6 will remain as PFSSD components. The changes per this update do not impact the evaluation performed by this calculation.
x XX-E-013-004-CN003 - COMMITTED - Change Package 14658 is replacing cable from EDGs speed signal generators to the EDGs speed switches. Appendices 1, 2 and 3 are updated to reflect these changes. The changes per this update do not impact the evaluation performed by this calculation.
x XX-E-013-004-CN004 - FINAL - CP 15070 is changing the 120VAC source from system NG to NN for the control room a/c unit inlet and
UPDATE TO WCNOC CALCULATION XX-E-013, PFSSD ANALYSIS CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
7 of 8 CSP 3.03 Attachment E Page 7 of 8 Revision 2 exhaust dampers GKHZ0029A/B (Train A) & GKHZ0040A/B (Train B).
The changes per this update do not impact the evaluation performed by this calculation.
x XX-E-013-004-CN005 - COMMITTED - CP 20021 is replacing XNB01 and the change impacts the PFSSD components for XNB01. The changes per this update do not impact the evaluation performed by this calculation.
6.0 Methodology This calculation is a tabulation of cables and components that are required to support the PFSSD power sources and functions. XNB02 is a power source that is required to support the PFSSD functions. The impact of the LTC controls on the PFSSD power supply function was reviewed and determined to not impact the PFSSD power supply function of XNB02.
PFSSD components associated with XNB02 are listed in calculation XX-E-013. Some of the components are being removed by DCP 012513. The calculation was reviewed and components 287/T2(B) and 287/T2(C) are removed from the plant and will be removed from the calculation. Relay 287/T2(A) is changed to 287/T2(A,B,C) because the new digital relay monitors all three phases. Fault pressure monitors 263-1/T2 and 263-2/T2 are being removed from the plant and will be removed from the calculation. Auxiliary relays 263X-1/T2 and 263X-2/T2 are being disconnected/
abandoned-in-place and will be removed from the calculation. A new sudden pressure monitor at XNB02 contains trip relays that are used to trip the 252PA0201 breaker on a fault pressure signal, 263FP relays K4A and K4B.
These relays will be added to the calculation. The changes to the relays also impact drawing E-1F9426. This drawing update will be addressed in DCP 012513 via WIP-E-1F9426-002-A-1. PK3207 via cable 16NBK16AA supplies
UPDATE TO WCNOC CALCULATION XX-E-013, PFSSD ANALYSIS CALC NO.
WCN-025-CALC-019 REV.
1 PAGE NO.
8 of 8 CSP 3.03 Attachment E Page 8 of 8 Revision 2 125VDC to the sudden pressure monitor. Failure of this power source or cable does not cause the relays to change state and loss of XNB02. Therefore, PK3207 and cable 16NBK16AA are not required for PFSSD.
7.0 Calculations N/A 8.0 Computer Software NONE APPENDIX A - Markups to Calculation XX-E-013 Rev. 4 (4 pages)
)250$3)'5(9
APPENDIX 1 PFSSD FUNCTION EVALUATIONS (PFSSD SUPPORT)
CALCULATION NO.
REVISION NO.
XX-E-013 4
Page 63
3$LVLQFOXGHGLQWKH3)66'GHVLJQEHFDXVH3$FRQWUROVHFWLRQSURYLGHVFRQWUROSRZHUIRU3$1R
3)66'ORDGVRWKHUWKDQ3$FRQWUROSRZHUDUHVXSSOLHGE\\3$
2IIVLWHSRZHUDYDLODELOLW\\UHTXLUHVWKDWRIIVLWHSRZHUFDEOHVDQGFDEOHVDVVRFLDWHGZLWK;1%DQG;1%
SURWHFWLYHUHOD\\VUHPDLQIUHHRIILUHGDPDJH7KHSRZHUFDEOHVDUHDVVRFLDWHGZLWKWKHFLUFXLWEUHDNHUVLQWKH
SUHFHGLQJWDEOH2IIVLWHSURWHFWLYHUHOD\\VDQGSRWHQWLDOWUDQVIRUPHUVUHTXLUHGIRU3)66'DUHLGHQWLILHGLQ
$SSHQGL[DQG$SSHQGL[
7KHDERYHGLVFXVVLRQDGGUHVVHVVDIHW\\UHODWHGSRZHUUHTXLUHGIRUSRVWILUHVDIHVKXWGRZQ$OLPLWHGQXPEHURI
FRPSRQHQWVGHULYHWKHLUSRZHUIURPQRQVDIHW\\UHODWHGEXVVHV3$DQG3$7KHQRQVDIHW\\UHODWHGSRZHULV
QRUPDOO\\VXSSOLHGIURPWKHXQLWDX[LOLDU\\WUDQVIRUPHU;052QDIDLOXUHRI;05RUWKHSRZHUWR;05D
IDVWEXVWUDQVIHUWRWKHVWDUWXSWUDQVIRUPHU;05RFFXUV7KHSRZHUSDWKIURP;05LVQRWLQFOXGHGLQWKH
3)66'GHVLJQEHFDXVHWKH;05SRZHUSDWKLVLQWKH3)66'GHVLJQ2WKHUWKDQ90&&VWKHUHDUHQR
RWKHUQRQVDIHW\\UHODWHG3)66'ORDGVSRZHUHGIURP3$DQG3$&RQWUROVUHTXLUHGIRURIIVLWHDQGRQVLWH
SRZHUDUHLGHQWLILHGLQ$SSHQGL[
)RUFHGFRROLQJRI(6)WUDQVIRUPHUV;1%DQG;1%LVQRWUHTXLUHGIRU3)66'(DFKWUDQVIRUPHUKDVDVHOI
FRROHGUDWLQJRI09$DQGDIRUFHGDLUFRROHGUDWLQJRI09$7KHPD[LPXPGHVLJQEDVLVDFFLGHQW'%$
ORDGLVDSSUR[LPDWHO\\0:ZKLFKHTXDWHVWR09$DVVXPLQJDSRZHUIDFWRURIDFWXDOSRZHUIDFWRULV
EHWZHHQDQG7KHUHIRUHWKHUHLVDPDUJLQIRUWKH'%$ORDGLQJIRUWKHVHOIFRROHGUDWLQJ3)66'
ORDGLQJZRXOGEHHTXDOWRRUOHVVWKDQWKH'%$UDWLQJVLQFHVRPHRIWKH'%$ORDGVDUHQRWFUHGLWHGIRU3)66'
HJFRQWDLQPHQWVSUD\\SXPSVDQGVDIHW\\LQMHFWLRQSXPSV7KHUHIRUHWKHUHLVDGHTXDWHMXVWLILFDWLRQIRUQRW
LQFOXGLQJ(6)WUDQVIRUPHUFRROLQJLQWKH3)66'DQDO\\VLV
/RZHUPHGLXPYROWDJH+/-.9FRPSRQHQWVDQGUHOD\\VUHTXLUHGIRU3)66'DUHLGHQWLILHGLQ$SSHQGL[DQG
$SSHQGL[
$QHYDOXDWLRQRIWKHSRWHQWLDOIRUDILUHLQGXFHGORVVRIRIIVLWHSRZHULVFRQWDLQHGLQ$SSHQGL[7KLVHYDOXDWLRQ
LGHQWLILHGWKHSODQWORFDWLRQVZKHUHDILUHLQLWLDWHGORVVRIRIIVLWHSRZHUORVVRIQRQVDIHW\\UHODWHGSRZHUFRXOG
RFFXU
/RZ9ROWDJH6\\VWHP+/-9
7KHORZYROWDJHV\\VWHPLVGLYLGHGLQWRWZRORDGJURXSVWKDWDUHUHGXQGDQWDQGLQGHSHQGHQWORDGJURXSDQGORDG
JURXS(LWKHURQHRIWKHDVVRFLDWHGORDGJURXSVLVFDSDEOHRIDFKLHYLQJ3)66'
7KH&ODVV(9V\\VWHPFRQVLVWVRIORDGFHQWHUXQLWVXEVWDWLRQVDQGPRWRUFRQWUROFHQWHUV6XSSOLHGIURPWKH
.9EXVHV1%DQG1%WKHORDGFHQWHUVWUDQVIRUPSRZHUIURP.9WR97KHORDGFHQWHUVVXSSO\\
SRZHUDW9GLUHFWO\\WRPRWRUVDERYHKSDQGOHVVWKDQKS0RWRUVKSDQGEHORZWZRVSHHGRU
UHYHUVLEOHPRWRUVDQGPRWRUVVXEMHFWWRUHSHDWHGF\\FOLQJDUHVXSSOLHGIURPPRWRUFRQWUROFHQWHUV
3RVWILUHVDIHVKXWGRZQFRPSRQHQWVSRZHUHGE\\QRQVDIHW\\UHODWHGSRZHUZHUHHYDOXDWHGWRGHWHUPLQHWKH
FRPSRQHQWVWKDWUHTXLUHGSRZHUSRZHUUHTXLUHGWRUHSRVLWLRQWKHFRPSRQHQWIRUSRVWILUHVDIHVKXWGRZQ7KH
UHYLHZGHWHUPLQHGWKDWVRPHRIWKHFRPSRQHQWVXVHGWRLVRODWHVWHDPIORZGRZQVWUHDPRIWKH06,9VUHTXLUH
SRZHUWRLVRODWHVWHDPIORZ$SSHQGL[GHWHUPLQHGWKDWWKHVHFRPSRQHQWVZHUHRQO\\UHTXLUHGIRUDILUHLQILUH
DUHDV$DQG$1RQHRIWKHSUHIHUUHGSRZHUFDEOHVDUHURXWHGLQILUHDUHDV$DQG$7KHUHIRUHWKH
QRQVDIHW\\UHODWHGSRZHUZRXOGEHDYDLODEOHZKHQUHTXLUHG
7UDQVIRUPHUVHPSOR\\HGLQWKH3)66'GHVLJQWRWUDQVIRUP.9WR9DUHLGHQWLILHGLQ$SSHQGL[
9ORDGFHQWHUDQGPRWRUFRQWUROFHQWHUFRPSRQHQWVXVHGLQWKH3)66'GHVLJQDUHLGHQWLILHGLQ$SSHQGL[
CALC NO. WCN-025-CALC-019 REV. 1 APPENDIX A PAGE 1 OF 4 XNB02 has a Load Tap Changer (LTC) that is used to maintain a set voltage level on the NB02 bus even though voltage level changes on the 13.8kV switchyard supply voltage may occur. This function is local to the transformer. The power for the LTC and transformer auxiliary loads is supplied from either the auxiliary winding local to the transformer or an external 480VAC power supply. When operated in a "fixed tap" position (fixed tap setting by Operations) the transformer functions as a standard step down transformer and there are no new failure modes. When placed in the "automatic" mode of operation, the LTC controller monitors the 4.16 kV output and adjusts the tap changer position to maintain the NB bus voltage at a set level. A failure of the main LTC controller would result in the LTC controls being shifted to the backup LTC controller and the Control Room being informed of the change via an alarm. The backup LTC controller has limited control function and prevents the transformer from being in an undesirable position. A loss of 480VAC power feeding the LTC/auxiliary loads for XNB02 will result in loss of power to the main and backup LTC controllers. This would keep the tap setting at a fixed position (the same as the "fixed tap" operation) and the transformer functions as a standard step down transformer.
Therefore, a loss of power to the LTC controllers will not impact the PFSSD function of XNB02.
FORM APF 05D-001-01, REV. 10 APPENDIX 2 LOSS OF OFF-SITE POWER EVALUATION CALCULATION NO.
REVISION NO.
XX-E-013 4
Page 8 7$%/($
2))6,7(32:(5$1'(0(5*(1&<',(6(/*(1(5$725&$%/(6
&$%/(
$662&,$7('%86',(6(/
- (1(5$725
'(6&5,37,21
1%
'*$
1%
'*%
1%$$'
1%,QSXWWR6ZLWFK\\DUG7ULS5HOD\\3DQHO
0$$
1%%$$
- 1%3KDVH$)HHGHUWR1%
1%%$&
- 1%3KDVH%)HHGHUWR1%
1%%$(
- 1%3KDVH&)HHGHUWR1%
1%%$+
- 1%1HXWUDO*URXQG2YHU&XUUHQW5HOD\\
17
1%%$-
- 1%3KDVH'LIIHUHQWLDO5HOD\\7
1%%$/
- 1%3KDVH'LIIHUHQWLDO5HOD\\7
1%%$$
- 1%3KDVH$)HHGHU7R1%
1%%$%
- 1%3KDVH%)HHGHU7R1%
1%%$&
- 1%3KDVH&)HHGHU7R1%
3**$/
3*5)HHGHU
3**$0
3*5)HHGHU
050$$
- 057UDQVIRUPHU&RROLQJ
05;$*
- 053KDVH'LIIHUHQWLDO5HOD\\7
05;$+
- 053KDVH'LIIHUHQWLDO5HOD\\7
05;$-
- 053KDVH'LIIHUHQWLDO5HOD\\7
05;$1
- 053KDVH2YHUFXUUHQW5HOD\\
- 7
05;$3
- 051HXWUDO*URXQG5HOD\\17
- 051HXWUDO*URXQG5HOD\\17
05;$7
- 05)HHGHU7R3$
1%$$$
- 1%)DXOW3UHVVXUH6ZLWFK7
- 1%)DXOW3UHVVXUH6ZLWFK7
- 1%)DXOW3UHVVXUH5HOD\\;7
- 1%)DXOW3UHVVXUH5HOD\\;7
1%$$%
3$+DQG,QGLFDWLQJ6ZLWFK1%+,6
1%$$&
3$+DQG,QGLFDWLQJ6ZLWFK1%+,6
- 1%/RFNRXW5HOD\\7
1%$$'
- 05/RFNRXW5HOD\\7
- 05/RFNRXW5HOD\\7
1%%$$
- 1%3KDVH$IHHGHUWR1%
1%%$%
- 1%3KDVH%IHHGHUWR1%
1%%$&
- 1%3KDVH&IHHGHUWR1%
1%%$%
- 1%3KDVH'LIIHUHQWLDO5HOD\\7
1%%$$
- 1%3KDVH$)HHGHU7R1%
1%%$%
- 1%3KDVH%)HHGHU7R1%
1%%$&
- 1%3KDVH&)HHGHU7R1%
1%%$'
- 1%3KDVH'LIIHUHQWLDO5HOD\\7
1%%$*
- 1%3KDVH$)HHGHU)URP3$
1%%$+
- 1%3KDVH%)HHGHU)URP3$
CALC NO. WCN-025-CALC-019 REV. 1 APPENDIX A PAGE 2 OF 4
- 1%)DXOW3UHVVXUH6ZLWFK7
- 1%)DXOW3UHVVXUH6ZLWFK7
- 1%)DXOW3UHVVXUH5HOD\\;7
- 1%)DXOW3UHVVXUH5HOD\\;7
\\
XNB02 Fault Pressure Trip
onitor relays 263FP 4A and
4B
$33(1',;
3)66'5(/$</,67
6RUWHGE\\5HOD\\/RFDWLRQ5HOD\\,'
&$/&8/$7,2112;;(
5(9,6,2112
3DJH
Relay ID S/G Relay Name Room Fire Area Relay Location SSD Fun Sprtd Fun Hot Stdby Cold Shdwn Normal Shdwn Alt Shdwn Schematic /
One Line Other Drawing Power Feeder Breaker Notes Logic Diagram (E-1F)
R E
V 250G/T2 6
Ground Over Current Relay 4401W TURB PA0201 S
R, M, H X
X X
E-13NB05 E-13NB11 E-13PA14 PK6204 9426 0
263X-1/T2 6
Fault Pressure Relay 4401W TURB PA0201 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
263X-2/T2 6
Fault Pressure Relay 4401W TURB PA0201 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
287/T2(A) 6 Phase A Differential Relay 4401W TURB PA0201 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
287/T2(B) 6 Phase B Differential Relay 4401W TURB PA0201 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
287/T2(C) 6 Phase C Differential Relay 4401W TURB PA0201 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
1XEF31 1
ESW Pump Motor A Interposing Relay 3301 C-9 RP139 S
R, M, H X
X X
E-K3EF01 NK4122 XX-E-013-001-CN013 9402A 2
1XEF33 1
ESW Pump Motor A Interposing Relay 3301 C-9 RP139 S
R, M, H X
X X
E-K3EF01 NK4122 XX-E-013-001-CN013 9402A 2
1XEF35 1
ESW Pump Motor A Interposing Relay 3301 C-9 RP139 S
R, M, H X
X X
E-K3EF01 NK4122 XX-E-013-001-CN013 9402A 2
3XEG01 1
CCW Pump A Auxiliary Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13EG01A NK4101 XX-E-013-001-CN013 9401A 9401B 2
3XEG03 1
CCW Pump C Auxiliary Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13EG01B NK4101 XX-E-013-001-CN013 9401A 9401B 2
62XBB01 1
Pressurizer PORV Block Valve Auxiliary Relay 3301 C-9 RP139 M
X X
X X
E-13BB39 NG01BBR3 NK4101 XX-E-013-002-CN002 9301 3
62XBB03 1
Pressurizer PORV Block Valve Auxiliary Relay 3301 C-9 RP139 M
X X
X X
E-13BB39 NG01BBR3 NK4101 XX-E-013-002-CN002 9301 3
63TDEEG02 1
CCW Pump A Auxiliary Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13EG01A E-13EG01B NK4101 XX-E-013-001-CN013 9401A 9401B 2
63TDEEG04 1
CCW Pump C Auxiliary Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13EG01A E-13EG01B NK4101 XX-E-013-001-CN013 9401A 9401B 2
83XGK03 1
GKHZ0029A/29B Auxiliary Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13GK02C NG03CLF115 XX-E-013-001-CN013 9442 2
83XGK05 1
SGK05A Indication Circuit Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13GK13 NG01ACR130 Required to indicate spurious shutdown of SGK05A. Revised in CCN-XX-E-013-000-CN005.
9444 1
K1119 1
Load Sequencer Relay 3301 C-9 RP139 S
R, M, H X
X X
E-13GK13 NG01AAF4 XX-E-013-001-CN013 9444 2
0 0
9426 9426 PK6204 PK6204 E-13NB11 E-13PA14 E-13NB11 E-13PA14 X
X X
X X
X R, M, H R, M, H S
S PA0201 PA0201 263X-1/T2 6
Fault Pressure Relay 4401W TURB 263X-2/T2 6
Fault Pressure Relay 4401W TURB 0
0 9426 9426 PK6204 PK6204 E-13NB11 E-13PA14 E-13NB11 E-13PA14 X
X X
X X
X R, M, H R, M, H S
S PA0201 PA0201 401W TURB URB 287/T2(B) 6 Phase B Differential Relay 440 287/T2(C) 6 Phase C Differential Relay 4401W TUR 0
9426 PK6204 E 13NB11 X
X X
R M H S
PA0201 401W TURB 287/T2(B) 6 Ph B Diff ti l R l 44 Phase A,B,C Differential Current Relay Phase A Differential Relay Phase A Differential Relay 287/T2(A)
( )
28/T2 (A,B,C)
These two relays are no longer inservice and can be removed.
These two relays are removed from the plant.
CALC NO. WCN-025-CALC-019 REV. 1 APPENDIX A PAGE 3 OF 4
$33(1',;
3)66'5(/$</,67
6RUWHGE\\5HOD\\/RFDWLRQ5HOD\\,'
&$/&8/$7,2112;;(
5(9,6,2112
3DJH
Relay ID S/G Relay Name Room Fire Area Relay Location SSD Fun Sprtd Fun Hot Stdby Cold Shdwn Normal Shdwn Alt Shdwn Schematic /
One Line Other Drawing Power Feeder Breaker Notes Logic Diagram (E-1F)
R E
V K526 4
Safety Injection Master Relay 3605 C-27 SB032D S
R, M, H X
X X
M-767-00374 M-767-00350 NK4416 NN0412 9432 0
K713 4
Pressurizer High Pressure Relay 3601 C-27 SB032D M
X X
X E-13BB40 E-13SB05 M-767-00186 M-767-00189 NK4421 NN0412 NK4416 BBPCV0456A opens if K713 is energized. XX-E-013-002-CN002 9301 3
K726 4
Low-Low TAVG or ABHS0064 in 'OFF/RESET' Relay 3605 C-27 SB032D R, H X
X E-13AB08 M-767-00188 NK4416 NN0412 9103 0
K727 4
Low-Low TAVG or ABHS0064 in 'OFF/RESET' Relay 3605 C-27 SB032D R, H X
X E-13AB11A E-13AB11B E-13AB11C M-767-00188 NK4416 NN0412 9103 0
K728 4
Low-Low TAVG or ABHS0064 in 'OFF/RESET' Relay 3605 C-27 SB032D R, H X
X E-13AB11C M-767-00188 NK4416 NN0412 9103 0
K734 4
High-1 RCS Pressure Relay 3605 C-27 SB032D H
X E-13BB12A E-13BB12B M-767-00186 M-767-00189 NG02BCF2 NG02BBF3 NN0412 NK4416 9205 0
K740 4
Safety Injection Signal Relay 3605 C-27 SB032D H
X E-13EJ06B E-13SB05 M-767-00189 NG02BEF2 NN0412 NK4416 9205 0
K741 4
RWST Low-Low 1 Level Relay 3605 C-27 SB032D H
X E-13EJ06B E-13SB05 M-767-00189 NG02BEF2 NN0412 NK4416 9205 0
K811 4
Block Test Relay 3605 C-27 SB033A M
X X
X X
E-13BB40 NK4421 9301 0
263-1/T1 5
Fault Pressure Switch Relay Yard XNB01 S
R, M, H X
X X
E-13NB10 PK6108 9425 0
263-2/T1 5
Fault Pressure Switch Relay Yard XNB01 S
R, M, H X
X X
E-13NB10 PK6108 9425 0
263-1/T2 6
Fault Pressure Switch Relay Yard XNB02 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
263-2/T2 6
Fault Pressure Switch Relay Yard XNB02 S
R, M, H X
X X
E-13NB11 E-13PA14 PK6204 9426 0
CALC NO. WCN-025-CALC-019 REV. 1 APPENDIX A PAGE 4 OF 4 263-2/T2 263 2/T2 263-1/T2 2
263FP (4A) 263FP (4B)
P320
P320is connected to cable 16NB16AA. This supplies power to the monitor that houses relays at XNB02. PK3207 and associated cable 16NBK16AA are not required for PFSSD. Loss of power or cable failure will not cause a loss of XNB02.
13NB16
13NB16 P320
FORM AIF 05C-002-02, REV. 3A WCNOC OWNERS ACCEPTANCE REVIEW CHECKLIST FOR EXTERNAL CALCULATIONS AND SPECIFICATIONS PAGE 1 OF 5
Title:
Post Fire Safe Shutdown (PFSSD) Analysis Wolf Creek document #: XX-E-013-004-CN006 Revision #: N/A ECDE: Enercon INITIATING DOCUMENT and revision:
(e.g., PO, CR, SWO)
CP 012513 R/0 CHANGE TYPE:
X Calculation Specification SAFETY CLASS:
SR X
SS NSR WCNOC Reviewer signature:
DigsigVer 5, 0.45 Date:
02/24/2020 WCNOC Approver:
DigsigVer 5, 0.45 Date:
2/26/2020 Prepared By:
Init / Date William M. Wilkins WMW 02/24/2020
FORM AIF 05C-002-02, REV. 3A WCNOC OWNERS ACCEPTANCE REVIEW CHECKLIST FOR EXTERNAL CALCULATIONS AND SPECIFICATIONS PAGE 2 OF 5
Title:
Post Fire Safe Shutdown (PFSSD) Analysis Wolf Creek document #: XX-E-013-004-CN006 Revision #: N/A ECDE: Enercon No.
Question Instructions and Guidance YES NO N/A 1
Do assumptions have sufficient documented rationale?
All Assumptions should be stated in clear terms with enough justification to confirm that the assumption is conservative:
For example, 1) the exact value of a particular parameter may not be known or that parameter may be known to vary over the range of conditions covered by the Calculation. It is appropriate to represent or bound the parameter with an assumed value.
- 2) The predicted performance of a specific piece of equipment in lieu of actual test data. It is appropriate to use the documented opinion/position of a recognized expert on that equipment to represent predicted equipment performance.
Consideration should also be given as to any qualification testing that may be needed to validate the Assumptions. Ask yourself, would you provide more justification if you were performing this analysis? If yes, the rationale is likely incomplete.
X 2
Are assumptions compatible with the way the plant is operated and with the licensing basis?
Ensure the documentation for source and rationale for the assumption supports the way the plant is currently or will be operated post change and they are not in conflict with any design parameters. If the Analysis purpose is to establish a new licensing basis, this question can be answered yes, if the assumption supports that new basis.
X
FORM AIF 05C-002-02, REV. 3A WCNOC OWNERS ACCEPTANCE REVIEW CHECKLIST FOR EXTERNAL CALCULATIONS AND SPECIFICATIONS PAGE 3 OF 5
Title:
Post Fire Safe Shutdown (PFSSD) Analysis Wolf Creek document #: XX-E-013-004-CN006 Revision #: N/A ECDE: Enercon No.
Question Instructions and Guidance YES NO N/A 3
Do all unverified assumptions have a tracking and closure mechanism in place?
If there are unverified assumptions without a tracking mechanism indicated, then create the tracking item either through an ATI or a work order attached to the implementing WO. Due dates for these actions need to support verification prior to the analysis becoming operational or the resultant plant change being op authorized.
X 4
Do the design inputs have sufficient rationale?
The origin of the input, or the source should be identified and be readily retrievable within WCNOC's documentation system.
If not, then the source should be attached to the analysis. Ask yourself, would you provide more justification if you were performing this analysis? If yes, the rationale is likely incomplete.
X 5
Are design inputs correct and reasonable with critical parameters identified, if appropriate?
The expectation is that an WCNOC Engineer should be able to clearly understand which input parameters are critical to the outcome of the analysis. That is, what is the impact of a change in the parameter to the results of the analysis? If the impact is large, then that parameter is critical.
X 6
Are design inputs compatible with the way the plant is operated and with the licensing basis?
Ensure the documentation for source and rationale for the inputs supports the way the plant is currently or will be operated post change and they are not in conflict with any design parameters.
X 7
Are Engineering Judgments clearly documented and justified?
Ask yourself, would you provide more justification if you were performing this analysis? If yes, the rationale is likely incomplete.
X
FORM AIF 05C-002-02, REV. 3A WCNOC OWNERS ACCEPTANCE REVIEW CHECKLIST FOR EXTERNAL CALCULATIONS AND SPECIFICATIONS PAGE 4 OF 5
Title:
Post Fire Safe Shutdown (PFSSD) Analysis Wolf Creek document #: XX-E-013-004-CN006 Revision #: N/A ECDE: Enercon No.
Question Instructions and Guidance YES NO N/A 8
Are Engineering Judgments compatible with the way the plant is operated and with the licensing basis?
Ensure the justification for the engineering judgment supports the way the plant is currently or will be operated post change and is not in conflict with any design parameters.
If the Analysis purpose is to establish a new licensing basis, then this question can be answered yes, if the judgment supports that new basis.
X 9
Do the results and conclusions satisfy the purpose and objective of the Design Analysis?
Why was the analysis being performed?
Does the stated purpose match the expectation from WCNOC on the proposed application of the results? If yes, then the analysis meets the needs of the contract.
X 10 Are the results and conclusions compatible with the way the plant is operated and with the licensing basis?
Make sure that the results support the USAR defined system design and operating conditions, or they support a proposed change to those conditions. If the analysis supports a change, are all of the other changing documents included on the cover sheet as impacted documents?
X 11 Have any limitations on the use of the results been identified and transmitted to the appropriate organizations?
Does the analysis support a temporary condition or procedure change? Make sure that any other documents needing to be updated are included and clearly delineated in the design analysis. Make sure that the cover sheet includes the other documents where the results of this analysis provide the input.
X 12 Have margin impacts been identified and documented appropriately for any negative impacts.
Make sure that the impacts to margin are clearly shown within the body of the analysis.
If the analysis results in reduced margins ensure that this has been appropriately dispositioned in the EC being used to issue the analysis.
X
FORM AIF 05C-002-02, REV. 3A WCNOC OWNERS ACCEPTANCE REVIEW CHECKLIST FOR EXTERNAL CALCULATIONS AND SPECIFICATIONS PAGE 5 OF 5
Title:
Post Fire Safe Shutdown (PFSSD) Analysis Wolf Creek document #: XX-E-013-004-CN006 Revision #: N/A ECDE: Enercon No.
Question Instructions and Guidance YES NO N/A 13 Does the Design Analysis include the applicable design basis documentation?
Are there sufficient documents included to support the sources of input, and other reference material that is not readily retrievable in WCNOC controlled Documents?
X 14 Have all affected design analyses been documented on the Affected Documents List (ADL) for the associated Configuration Change?
Determine if sufficient searches have been performed to identify any related analyses that need to be revised along with the base analysis. It may be necessary to perform some basic searches to validate this.
X 15 Do the sources of inputs and analysis methodology used meet committed technical and regulatory requirements?
Compare any referenced codes and standards to the current design basis and ensure that any differences are reconciled. If the input sources or analysis methodology are based on an out-of-date methodology or code, additional reconciliation may be required if the site has since committed to a more recent code X
16 Have vendor supporting technical documents and references (including GE DRFs) been reviewed when necessary?
Based on the risk assessment performed during the pre-job brief for the analysis, ensure that sufficient reviews of any supporting documents not provided with the final analysis are performed.
X 17 If the design includes digital assets, does it adequately address digital and cyber security requirements?
Ensure the design addresses and meets digital and cyber security requirements. Refer to AP 15D-008 and contact the Cyber Security Group to perform additional reviews prior to approval. The CSAT is required to review modifications impacting Cyber Security.
X
- END -