ML18093B017

From kanterella
Jump to navigation Jump to search
1 to Updated Safety Analysis Report, Penetration Seal Data, M-663-00017A, Rev W06, B1-99 to B2-40
ML18093B017
Person / Time
Site: Wolf Creek 
Issue date: 03/08/2018
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 M-663-00017A, Rev W01
Download: ML18093B017 (123)


Text

M -663-000 l 7 A, Revision W01 Penetration Seal Data Penetration #:

Penetration Type:

Loc.IEiev.:

2065'- 0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants :
4. Sealant Type:
5. Damming Side1 :

P153W2550 M-6A 12" 12"0 (1)8"P Foam 1 /4" recessed

6. Damming Side 2:

Flush

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

NIA

9. Sealant Depth:

9-3/4" Walkdown Comments:

Page B 1-99 of B 1-I 72 Appendix:

B1 Fire Area (Side 1): A-20 Fire Area (Side 2): A-5 M-OX Dwg: M-OX1946

10. Annular Gap (smallest):

1-7/8"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Barrier thickness based on drawing C-OC1531. Changed Detail from M-1 to M-6A based on actual seal depth.

Sketch:

FA: A-20 Slda 1 P153W2550

,-r, C> * -

P....."

FA: A-5 Slda2

M-663-00017A, Revision W01 Page B 1-100 of B 1-I 72 Penetration Seal Data Appendix:

81 Photos:

P153W2550 Fire Area A-20 (Side 1)

Fire Area A-20 (Side 1)

Fire Area A-5 (Side 2)

Fire Area A-5 (Side 2)

M-663-00017A, Revi ion WOI Page Bl-IOJ ofBI-172 Penetration Seal Data Appendix:

B1 Penetration #:

P153W2627 Penetration Type:

M-6A Fire Area (Side 1): A-20 Fire Area (Side 2): A-5 Loc./Eiev.: 2065'-2" M-OX Dwg: M-1X1948

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

1-3/4"

2. Opening Size:

12"0 11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Flush

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

1 0" Reviewed By:

Walkdown Comments:

Barrier thickness based on drawing C-OC1531. Changed Detail from M-1 to M-6A based on actual seal depth.

There are restraint lugs installed on one side. Length of Lug can not be determined.

Sketch:

FA: A-20 Side 1 f'of:\\1\\'\\-----f---1 Crh'J P153W2627

  • t>.

FA: A-$

Sid 2

M-663-000I?A, Revision WOI Page 81-102 ofBJ-172 Penetration Seal Data Appendix:

81 Photos:

P153W2627 Fire Area A-20 (Side 1)

Fire Area A-20 (Side 1)

Fire Area A-5 (Side 2)

Fire Area A-5 (Side 2)

M-663-000l?A, Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 1980'-8 7

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:
6. Damming Side 2:

P311W0846 M-6A 36" 10"D (1 )6"P Foam Flush 25"recessed

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth:

9" Walkdown Comments:

Page B 1-103 of BI-J 72 Appendix:

B1 Fire Area (Side 1 ):

C-1 Fire Area (Side 2): CC-1 M*OX Dwg: M-1X3901

10. Annular Gap (smallest):

1-1/4"

11. Gap between pen:

N/A

12. Barrier Type:

A F

w

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Barrier thickness determined by Drawing C-1C3111. Changed Detail M-1 to M-6A based on actual sealant depth.

Sketch:

FA: C-1 Slda1 P311W0846 f:aAtrl (~} *.

_.. b

. /)
b. '

FA: CC-1 Side 2

M-663-00017A, Revision WOl Page 81-1 04 of 8 J-J 72 Penetration Seal Data Appendix:

81 Photos:

P311W0846 Fire Area C-1 (Side 1)

Fire Area C-1 (Side 1)

Fire Area CC-1 (Side 2)

Fire Area CC-1 (Side 2)

M-663-000J7A, Revision WOl Page B l-1 0- of B 1-1 72 Penetration Seal Data Appendix:

B1 Penetration #:

P321S0083 Penetration Type:

M-6A Fire Area (Side 1): C-6 Fire Area (Side 2): C-1 Loc./Eiev.:

1984'-0" M-OX Dwg: M-1X3211

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

12"0

11. Gap between pen:

N/A

3. Penetrants:

(1 }B"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Foam Flush w/sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:

Unknown Wayne Aregood

7. Damming Continuity (Acc/Rej):

Unknown Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1C3211. Bottom side damming position and continuity can not be verified due to insulation. Insulation completely covers bottom side opening. However. inspection report indicates 6" depth within barrier.

Sketch:

FA: C-&

Slde 1 SI:CTIO P321 S0083

M-663-00017 A, Revi ion WO I Page B 1-1 06 of B 1-1 72 Penetration Seal Data Appendix:

81 Photos:

P321S0083 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-000 l 7 A, Revision WO 1 Page 8 1-1 07 ofB I-172 Penetration Seal Data Appendix:

B1 Penetration #:

P321S0084 Penetration Type:

M-6A Fire Area (Side 1 ):

C-6 Fire Area (Side 2): C-1 Loc./Eiev.: 1984' -0" M-OX Dwg: M-1X3211

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

12"0

11. Gapbetweenpen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Foam flush w/sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:

Unknown Wayne Aregood

7. Damming Continuity (Acc/Rej):

Unknown Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

1 0" **

Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1C3211. Bottom side damming position and continuity can not be verified due to insulation. Insulation completely covers bottom side opening.

Sketch:

FA: c~

Slo. 1

.SecrcoN A P321SOOU llil G. "TJenA \\of'tN ~

~

~T.AIL FA. C-1 Side2

M-663-00017A, Revi ion WOl Page B 1-1 0 of B 1-I 72 Penetration Seal Data Appendix:

81 Photos:

P321S0084 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1 )

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M -663-00017 A Revision WO J Page 8 l-1 09 of 8 1-1 72 Penetration Seal Data Appendix:

B1 Penetration #:

P321S0097 Penetration Type:

M-6A Fire Area (Side 1 ): C-6 Fire Area (Side 2): C-1 Loc./Eiev.: 1984'-0" M-OX Dwg: M-1X3211

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1/2"

2. Opening Size:

12"0

11. Gap between pen:

N/A

3. Penetrants:

(1)6"'P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/ top of support and S

14. Pipe Insulated:

No

6. Damming Side 2:

Flush w/Q-Deck Valley Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

13" Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C3211. Changed Detail from M-1 to M-6A based on actual foam depth.

Sketch:

FA; C-6 Side1 P321S0097 FA: C*1 Side2

M-663-00017A, Revision WOJ Page Bl-110 ofBI-.172 Penetration Seal Data Appendix:

81 Photos:

P321S0097 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017A, Revision WOJ Page B 1-1 I I of B 1-1 72 Penetration Seal Data Appendix:

B1 Penetration #:

P32150110 Penetration Type:

M-6A Fire Area (Side 1 ):

C-6 Fire Area (Side 2):

C-1 Loc./Eiev.:

1984'-0" M-OX Dwg: M-1X3211

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1/4"

2. Opening Size:

10"0

11. Gap between pen:

N/A

3. Penetrants:

(1)6"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Foam flush w/ top of sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush w/Q-Deck Valley Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

11" Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C3211. Changed Detail from M-1 to M-6A due to seal depth (WSA)

Sketch:

FA: C-6 Side I 5ea" I0!9 A P321SD110 FA: C-t Slde 2 Steel

M-663-00017A Revision WOI Page BJ-112 ofBI -172 Penetration Seal Data Appendix:

81 Photos:

P32150110 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1 )

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017A, Revision WOl Page B 1-1 13 of B 1-1 72 Penetration Seal Data Appendix:

B1 Penetration #:

P321S0115 Penetration Type:

M-6A Fire Area (Side 1): C-5 Fire Area (Side 2): C-1 Loc./Eiev.: 1984'-0" M-OX Dwg: M-1X321 1

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1"

2. Opening Size:

10"0 11. Gap between pen:

N/A

3. Penetrants:

(1)6"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

2"recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

9" Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1C3211. Changed Detail from M-1 to M-6A based on actual sealant depth Sketch:

FA: C-5 Sid 1 PJ21S0115 FA: C-1 Side2

M-663-00017A, Revision WOI Page 81-114 ofB! -1.72 Penetration Seal Data Appendix:

81 Photos:

P321S0115 Fire Area C-5 (Side 1)

Fire Area C-5 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-0001 7A, Revision WOl Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P331S0127 M-6A 10" 12"0 (1 )6"P Foam Page 8 1-1 15 of 8 l-1 72 Appendix:

B1 Fire Area (Side 1): C-10 Fire Area (Side 2):

C-6 M-OX Dwg: M-1X3311

10. Annular Gap (smallest):

2" 11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Foam Flush w/top of sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

1"recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

12" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1C3211. Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

FA; C*10 Sldo 1 P33150127 FA: c-&

Slde2

M-663-00017A, Revision WOI Page B 1-1 16 of B 1-172 Penetration Seal Data Appendix:

81 Photos:

P331S0127 Fire Area C-1 0 (Side 1)

Fire Area C-1 0 (Side 1)

Fire Area C-6 (Side 2)

Fire Area C-6 (Side 2)

M-663-00017A, Revi ion WOI Page B 1-J I 7 of B I - I 72 Penetration Seal Data Appendix:

B1 Penetration #:

P331S0136 Penetration Type:

M-6A Fire Area (Side 1): C-10 Fire Area (Side 2): C-6 Loc./Eiev.: 2000'-0" M*OXOwg: M-1 X3311

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

1-1/2"

2. Opening Size:

12"0

11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:
  • Unknown Wayne Aregood
7. Damming Continuity (Acc/Rej):
  • Unknown Prepared By:
8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1C3211.

  • Bottom side damming covered w/insulation and the area is behind the security barrier (not accessible). Side photo can not be taken.

Sketch :

FA: C-10 Slde1 P331S0136 1\\>0 ~o -k

!:. I tlt=

P~o1 ~t+' 1>

5 c.~~t'N B~ etl I

~ENcw oe~

.... ~~:;s P~te \\m~"

f OA!I'I FLUSOI li>/~

o t:= SL£10.\\1£

  • o :.. *-

4

. /}.

0 J

.. o '**

I

/J ~

4.*.. *...;.
  • f.J.

FA:. C-6 Side 2

M-663-0001 7A, Revision WOl Page B 1-1 I 8 of 8 1-1 72 Penetration Seal Data Appendix:

81 Photos:

P331S0136 Fire Area C-10 (Side 1)

Fire Area C-1 0 (Side 1 )

Fire Area C-6 (Side 2)

Fire Area C-6 (Side 2)

M-663-00017A, Revi ion WOl Page 8 1-1 19 of 81 -172 Penetration Seal Data Appendix:

B1 Penetration #:

P33150137 Penetration Type:

M-6A Fire Area (Side 1): C-10 Fire Area (Side 2):

C-6 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X3311

1. Barrier Thickness:

10

10. Annular Gap (smallest):

1"

2. Opening Size:

12"0 11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:
  • Unknown Wayne Aregood
7. Damming Continuity (Acc/Rej):
  • Unknown Prepared By:
8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

1 0" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C3211. ~ Bottom side damming covered w/insulation and the area is behind the security barrier (not accessible)_ Side 2 photo can not be taken _

Sketch:

FA: C-10 Slde 1 t-Jo~~~nG l>Ao'To1 fa£ttttjD Sc:cu.~1N ~'\\~ et, H!Nc~ o

~es Plktro l'(t\\111,~

P331S0137 roM)l FW&I/ W{ror 0? ::,u;e'ifr FA: C-6 Slde2

M-663-00017A, Revision WOl Page Bl -J 20 of B 1-172 Penetration Seal Data Appendix:

B1 Photos:

P331S0137 Fire Area C-10 (Side 1)

Fire Area C-1 0 (Side 1}

Fire Area C-6 (Side 2)

Fire Area G-6 (Side 2}

M-663-00017A, Revision WOl Penetration Seal Data Penetration#:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P331S0138 M-6A 10" 12"0 (1)8"P Foam Page B 1-12 I of B I -I 72 Appendix:

B1 Fire Area (Side 1 ):

C-1 0 Fire Area (Side 2): C-6 M-OXDwg: M-1X3311

10. Annular Gap (smallest):

1"

11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:
  • Unknown Wayne Aregood
7. Damming Continuity (Acc/Rej):
  • Unknown Prepared By:
8. Boot Condition (Ace/Rei):

N/A Jeff Suter

9. Sealant Depth:

1 0" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C3211.

  • Bottom side damming covered wlinsulation and the area Is behind the security barrier (not accessible).

Sketch:

FA: C-10 S de 1 No~S,tiG P ro1 l>..:lt~Nt)

~(~ ll't t.~

'FfN(.IC oesc.u~

f't-\\o'ro \\ m E!,E P331S0138 FA:~

Side2

M-663-0001 7A, Revision WOl Page Bl-122 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P331S0138 Fire Area C-1 0 (Side 1 )

Fire Area C-1 0 (Side 1 )

Fire Area C-6 (Side 2)

Fire Area C-6 (Side 2)

M-663-00017A, Revision WOI Page B J -1 2" of B J-J 72 Penetration Seal Data Appendix:

B1 Penetration #:

P331S0139 Penetration Type:

M-6A Fire Area (Side 1): C-10 Fire Area (Side 2): C-6 Loc./Eiev.: 2000'-0" M-OXDwg: M-1X3311

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

314"

2. Opening Size:

12"0

11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:
  • Unknown Wayne Aregood
7. Damming Continuity (Acc/Rej):
  • Unknown Prepared By:
8. Boot Condition (Acc/Rej):

NIA Jeff Suter

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1C3211.

  • Bottom side damming covered w/insulation and the area is behind the security barrier (not accessible).

Sketch:

FA: C-10 Side1 P331S0139

~*

p '.

  • *. /:>' ~ ~

. 0

'* 6 I.

b * ~

FA: C-6 Slde2

M-663-00017A, Revision WOl Page BI-124 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P331S0139 Fire Area C-1 0 (Side 1)

Fire Area C-1 0 (Side 1)

Fire Area C-6 (Side 2)

Fire Area C-6 (Side 2)

M-663-00017A, Revision WOJ Page 8 l -125 of B 1-1 72 Penetration Seal Data Appendix:

B1 Penetration #:

P33150143 Penetration Type:

M-6A FireArea(Side1): C-1 0 Fire Area (Side 2): C-6 Loc./Eiev.:

2000'-0" M-OX Dwg: M-1 X3311

1. Barrier Thickness:

8"

2. Opening Size:

1 O"D

3. Penetrants:

(1)6"P

4. Sealant Type:

Foam

5. Damming Side1:

Foam Flush w/top of sleeve

6. Damming Side 2:

Flush w/Q-Deck valley

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

NIA

9. Sealant Depth:

11" Walkdown Comments:

Slab thickness determined by Drawing C-1 C3211.

Sketch:

FA: C-10 Slde 1 P331S0143

10. Annular Gap (smallest):

1-1/4" 11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Fk C-8 Skle2 w

Steel

M -663-00017 A, Revision WO I Page Bl-126 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P331S0143 Fire Area C-1 0 (Side 1)

Fire Area C-1 0 (Side 1 )

Fire Area C-6 (Side 2)

Fire Area C-6 (Side 2)

M-663-00017A Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P331S0200 M-18 1 0" 10"D (1)6'*p Foam PageBI-127 ofBI-172 Appendix:

B1 Fire Area (Side 1 ): C-9 Fire Area (Side 2): C-5 M-OX Dwg: M-1 X3311

10. Annular Gap (smallest):

1" 11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Foam Flush w2/top of support

14. Pipe Insulated:

No

6. Damming Side 2:

Outside opening Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

15-1/2" Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1 C321 1. Changed Detail from M-1 lo M-18 based actual foam depth.

Sketch:

FA: C-9 Sde 1 P331S0200 FA: C*S Slde2

M-663-0001 7A, Revision WOJ Page 81-12 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P33150200 Fire Area C-9 (Side 1)

Fire Area C-9 (Side 1)

Fire Area C-5 (Side 2)

Fire Area C-5 (Side 2)

M-663-00017A, Revision WOI Page Bl-129 ofBI-172 Penetration Seal Data Appendix:

81 Penetration #:

P331W0882 Penetration Type:

M-6A Fire Area (Side 1): C-10 Fire Area (Side 2): D-1 Loc./Eiev.: 20 13'-0" M-OX Dwg: M-1X3903

1. Barrier Thickness:

24"

10. Annu lar Gap (smallest):

1-112"

2. Opening Size:

12"0 11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

A F

w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:
  • Flush
14. Pipe Insulated:

No

6. Damming Side 2:

7" recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

15" Reviewed By:

Walkdown Comments:

  • Covered by insulation, slight manipulation of insulation indicated flush damming. Changed Detail from M-1 toM-6A based on actual sealant depth.

Sketch:

FA: C-10 Sde 1 P331W0811:2 p :

p

~

f)',

  • A *. f>_ * *

. ~..

. B *

  • '--..i. t>. ~-- 7t I

~ '* -

... I....

p

. ~

I.,

FA:D-1 Slde2

M-663-000 17 A Revision WOl Page B 1-J 30 of B I -J 72 Penetration Seal Data Appendix:

81 Photos:

P331W0882 Fire Area C-1 0 (Side 1 )

Fire Area C-1 0 (Side 1 )

Fire Area D-1 (Side 2)

Fire Area D-1 (Side 2)

M-663-00017 A, Revision WO 1 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2013'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:
6. Damming Side 2:

P331W0883 M-6A 24" 12"0 (1)8"P Foam

~ Flush 6" recessed

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth:

16" Walkdown Comments:

Page Bl-131 ofBl-172 Appendix:

B1 Fire Area (Side 1): C-10 Fire Area (Side 2):

D-1 M-OX Dwg: M-1 X3903

10. Annular Gap (smallest):

2"

11. Gap between pen:

N/A

12. Barrier Type:

A F

w

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

  • Covered by insulation, slight manipulation of insulation indicated flush damming. Changed Detail from M-1 toM-6A based on actual sealant depth.

Sketch:

FA: C*10 Sfde 1 P331W0883 0.

. ** 1>.'

I e:q I

a>

~

0..

. t>:.,... -. *7(6

'I I

FA: 0*1 Slde2

M-663-00017A, Revision WOl Page 81 -1 32 of BI-172 Penetration Seal Data Appendix:

81 Photos:

P331W0883 Fire Area C-1 0 (Side 1 )

Fire Area C-1 0 (Side 1)

Fire Area D-1 (Side 2)

Fire Area D-1 (Side 2)

M-663-00017A, Revision WOl Page 81-133 ofBI - 172 Penetration Seal Data Appendix:

B1 Penetration #:

P331W0890 Penetration Type:

M-6A Fire Area (Side 1): C-10 Fire Area (Side 2): D-2 Loc./Eiev.: 2013'-0" M-OX Dwg: M-1X3903

1. Barrier Thickness:

24"

10. Annular Gap (smallest):

1"

2. Opening Size:

12"D 11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

A F

w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

~ Fl u s h

14. Pipe Insulated:

No

6. Damming Side 2:

10" recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

NIA Jeff Suter

9. Sealant Depth:

12" Reviewed By:

Walkdown Comments:

Changed Detail from M-1 to M-6A based on actual sealant depth.

  • Damming flush under insulation.

Sketch:

FA! C-10 Side 1 Q

P331W0890

  • /)

'----+--.DAmtnoJfj (t'(~)

I

  • . ~ -

FA! D-2 Slde2

M-663-00017A, Revision WOJ Page 81-134 of 8 J-1 72 Penetration Seal Data Appendix:

81 Photos:

P331W0890 Fire Area C-1 0 (Side 1)

Fire Area C-1 0 (Side 1)

Fire Area 0-2 (Side 2)

Fire Area 0-2 (Side 2)

M-663-00017A, Revision WOl Page 81-135 ofBI-172 Penetration Seal Data Appendix:

B1 Penetration #:

P341S0272 Penetration Type:

M-6A Fire Area (Side 1 ):

C-6 Fire Area (Side 2):

C-6 Loc./Eiev.: 2016'-0" M-OX Dwg: M-1X3411

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

1/2"

2. Opening Size:

10"0 11. Gap between pen:

N/A

3. Penetrants:

(1)8P

12. Barrier Type:
4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Foam flush w/sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

13" Reviewed By:

Walkdown Comments:

Stairwell Landing. Changed Data Base to reflect Non-Appendix R (WSA). Could be bounded without damming w/12" foam..

Sketch:

FA: C-6 SIOE1 T

l_

FA; C-6 SIOET

M-663-00017A, Revision WOI Page B l-136 of B I-I 72 Penetration Seal Data Appendix:

81 Photos:

P34150272 Fire Area C-6 (Side 1)

Fire Area C-6 (Side 1 )

Fire Area C-6 (Side 2)

Fire Area C-6 (Side 2)

M -663-00017 A, Revision WO I Page B l-1 '""7 of B 1-172 Penetration Seal Data Appendix:

81 Penetration #:

P341S0288 Penetration Type:

M-6A Fire Area (Side 1 ):

C-15 Fire Area (Side 2): C-10 Loc./Eiev_:

2016'-0" M-OX Dwg: M-1 X3411

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

1/8" to 1/4"

2. Opening Size:

8"0 11. Gap between pen:

N/A

3. Penetrants:

(1)6'"P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Flush w/sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush w/sleeve Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

NIA Jeff Suter

9. Sealant Depth:

13" Reviewed By:

Walkdown Comments:

Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

FA: C-15 SIDE 1 FA: C-10 SIDE2

M-663-0001 7A Revision WOJ Page Bl-J38 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P34150288 Fire Area C-15 (Side 1)

Fire Area C-15 (Side 1)

Fire Area C-1 0 (Side 2)

Fire Area C-1 0 (Side 2)

M-663-00017A, Revision WOI Page 8 1-1 39 ofB I-172 Penetration Seal Data Appendix:

B1 Penetration#:

P34150306 Penetration Type:

M-6A Fire Area (Side 1 ): C-1 6 Fire Area (Side 2): C-9 Loc./Eiev.: 2016'-0" M-OX Dwg: M-1 X341 1

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

3/4"

2. Opening Size:

8"0

11. Gapbetweenpen:

N/A

3. Penetrants:

(1)6"'P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Flush w/sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush w/sleeve Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

NIA Jeff Suter

9. Sealant Depth:

13" Reviewed By:

Walkdown Comments:

Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

FA: C-16 SIDE 1 15-4 FA: C*9 SIDE 2

+

M-663-000 J 7 A, Revision WO J Page B 1-J 40 of 8 I -J 72 Penetration Seal Data Appendix:

B1 Photos:

P341S0306 Fire Area C-16 (Side 1 )

Fire Area C-16 (Side 1) n Fire Area C-9 (Side 2)

Fire Area C-9 (Side 2)

M-663-000I?A, Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2016'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P341S0311 M-6A 1 0" 10"0 (1)6"'P Foam Page B 1-141 of B 1-1 72 Appendix:

B1 Fire Area (Side 1 ): C-16 Fire Area (Side 2):

C-9 M-OX Dwg: M-1 X341 1

10. Annular Gap (smallest):

1/4"

11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam Flush w/sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

NIA

9. Sealant Depth:

13" Walkdown Comments:

Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

FA; C-16 SIDE 1 FA: C-9 SIDE2 Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

M-663-000 I?A Revision WOl Page B 1-142 of B 1-1 72 Penetration Seal Data Appendix:

81 Photos:

P341 50311 Fire Area C-16 (Side 1 )

Fire Area C-16 (Side 1)

Fire Area C-9 (Side 2)

Fire Area C-9 (Side 2)

M-663-000 17 A, Revision WO 1 Penetration Seal Data Penetration#:

P341W0380 Penetration Type:

M-1 Loc./Eiev.: 2028' 1. Barrier Thickness:

8" Nominal

2. Opening Size:

1 O"D

3. Penetrants:

(1)6"P

4. Sealant Type:

Foam

5. Damming Side1 :

Flush w/sleeve

6. Damming Side 2:

Flush w/sleeve

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth:

6 3/4" Nominal Walkdown Comments:

Bounding not requi red, not Appendix R.

Sketch:

Page Bl-14"' of8J - l72 Appendix:

B1 Fire Area {Side 1 ): C-16 M-OX Dwg: M-1X0342 Fire Area {Side 2):

C-16

10. Annular Gap {smallest):

1" 11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Steel

M-663-00017A, Revision WOJ Page B I -144 of B 1-1 72 Penetration Seal Data Appendix:

81 Photos:

P341W0380 Fire Area C-16 (Side 1}

Fire Area C-16 (Side 1)

Fire Area C-16 (Side 2)

Fire Area C-16 (Side 2)

M-663-00017A Revision WOl Page Bl-145 of 8 1-172 Penetration Seal Data Appendix:

B1 Penetration #:

P351S0339 Penetration Type:

M-6A Fire Area (Side 1):

C-21 Fire Area (Side 2):

C-15 Loc./Eiev.: 2032'-0'"

M-OX Dwg: M-1X3511

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1"

2. Opening Size:

10" D

11. Gap between pen:

N/A

3. Penetrants:

(1)6"P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of support

14. Pipe Insulated:

No

6. Damming Side 2:

1" recessed Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

11-1/4" Reviewed By:

Walkdown Comments:

Barrier thickness determined by Drawing C-OC3511. Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

FA: C-21 Slde 1 P351S0339 FA:. C-1!

de2

M-663-00017 A, Revision WO I Page B 1-146 of B 1-1 72 Penetration Seal Data Appendix:

81 Photos:

P351S0339 Fire Area C-21 (Side 1)

Fire Area C-21 (Side 1)

Fire Area C-15 (Side 2)

Fire Area C-1 5 (Side 2)

M -663-000 17 A, Revision WO I Page B 1-14 7 of B 1-J 72 Penetration Seal Data Appendix:

B1 Penetration #:

P351S0356 Penetration Type:

M-6A Fire Area (Side 1 ): C-21 Fire Area (Side 2):

C-15 Loc./Elev.: 2032'-0" M-OX Dwg: M-1X3511

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

1/4"

2. Opening Size:

10" D

11. Gap between pen:

NfA

3. Penetrants:

(1)6"'P

12. Barrier Type:

F w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Foam 1/2" below top of sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

NIA Jeff Suter

9. Sealant Depth:

10-1 /4" Reviewed By:

Walkdown Comments:

Changed Detail from M-1 to M-6A based on actual sealant depth. Barrier thickness determined by Drawing C-1C3511.

Sketch:

FA: C-21 Slde1 P3!1S0356 F

  • C-15 Sldt2

M-663-00017A Revision WOI Page B 1-14 of B 1-1 72 Penetration Seal Data Appendix:

B1 Photos:

P351S0356 Fire Area C-21 (Side 1)

Fire Area C-21 (Side 1)

Fire Area C-15 (Side 2)

Fire Area C-15 (Side 2)

M-663-00017A, Revi ion WOl Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2047'-6"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P36150462 M-6A 8"

10"0 (1 )6"P Foam Page 81-149 of B 1-172 Appendix:

B1 Fire Area (Side 1): C-27 Fire Area (Side 2):

C-21 M-OX Dwg: M-1X3611

10. Annular Gap (smallest):

2" 11. Gap between pen:

N/A

12. Barrier Type:

A F

w

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush w/top of sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Ace/Rei):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suler

9. Sealant Depth:

1 0-3/4" Reviewed By:

Walkdown Comments:

Slab thickness based on C-1 C3611. Changed Detail M-1 to M-6A based on actual sealant depth.

Sketch:

FA: C-Z7 Slde1 P361S0462 CJ. '

t> *.

I FA: C-21 SICS. :Z

M-663-00017A, Revision WOI Page 81-150 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P36150462 Fire Area C-27 (Side 1)

Fire Area C-27 (Side 1)

Fire Area C-21 (Side 2)

Fire Area C-21 (Side 2)

M-663-00017A, Revision WOI Page 81 -l -J ofBJ-172 Penetration Seal Data Appendix:

B1 Penetration #:

P361S1052 Penetration Type:

E-2A Fire Area (Side 1): C-30 Fire Area (Side 2):

C-23 Loc./Eiev.:

204 7'-6" M-OX Dwg: M-1X3611

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

NfA

2. Opening Size:

8" X 2'-4"

11. Gap between pen:

N/A

3. Penetrants:

ET

12. Barrier Type:

A F

w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

1' recess area within top side foam

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

1 0" Reviewed By:

Walkdown Comments:

PMR 01756 evaluates this seal as acceptable with only 8" of foam. PMR 01756 is no longer valid, 1 0" foam is installed.

Sketch:

FA; C-30 Slde1 P361S1052 FA; C.-23 Side2

M-663-00017A, Revi ion WO I Page Bl-152 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P361S1052 Fire Area C-30 (Side 1)

Fire Area C-30 (Side 1)

Fire Area C-23 (Side 2)

Fire Area C-23 (Side 2)

M-663-00017A, Revision WO l Page 8 1-153 of B 1-J 72 Penetration Seal Data Appendix:

B1 Penetration #:

P36151055 Penetration Type:

E-2A Fire Area (Side 1 ):

C-30 Fire Area (Side 2): C-23 Loc./Eiev.:

204 7'-6" M-OXDwg: M-1X3611

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

N/A

2. Opening Size:

8" X 2'-4"

11. Gap between pen:

N/A

3. Penetrants:

ET

12. Barrier Type:

A F

w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam flush wltop of sleeve

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

11" Reviewed By:

Walkdown Comments:

PMR 01756 evaluates this seal as acceptable with only 8" of foam. PMR 01756 is no longer valid, 11" foam is installed.

Sketch:

FA: C...JO Side 1 ll

~M------~===i~~~~~rt~

(t'~l')

P361S1055 FA.: C-23 Sd 2

M-663-00017A, Revision WOI Page Bl-154 ofBJ-172 Penetration Seal Data Appendix:

81 Photos:

P361S1055 Fire Area C-30 (Side 1)

Fire Area C-30 (Side 1)

Fire Area C-23 (Side 2)

Fire Area C-23 (Side 2)

M -663-0001 7 A, Revision WO I Page B 1-1 -5 of B 1-1 72 Penetration Seal Data Appendix:

B1 Penetration #:

P361S1083 Penetration Type:

E-2A Fire Area (Side 1): C-32 Fire Area (Side 2): C-25 Loc./Eiev.: 2047'-6" M-OX Dwg: M-1X3611

1. Barrier Thickness:

8"

10. Annular Gap (smallest):

N/A

2. Opening Size:

2'-4"X8" 11. Gap between pen:

N/A

3. Penetrants:

ET

12. Barrier Type:

A F

w

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

foam recessed 1/2" from top of sle

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

10-1/2" Reviewed By:

Walkdown Comments:

PMR 01756 evaluates this seal as acceptable with only 8" of foam. PMR 01756 is no longer valid, 1 0-1 /2" foam is installed.

Sketch:

FA: C--32 Slda 1 FoQN1 _..:__..:::::=:::-.iiJ=~~~~~!Ji (T'fl")

PAm~, v~----------~

(~~~

~~~~--~

P361S1083 FA; C-25 Slda2

M-663-00017A, Revision WOI Page Bl-156 ofBI -1 72 Penetration Seal Data Appendix:

81 Photos:

P3615 1083 Fire Area C-32 (Side 1)

Fire Area C-32 (Side 1)

Fire Area C-25 (Side 2)

Fire Area C-25 (Side 2)

M-663-000I?A Revision WOl Page 81-157 ofBJ-172 Penetration Seal Data Appendix:

B1 Penetration #:

P45150318 Penetration Type:

N/R FireArea(Side1): T-12 Fire Area (Side 2): T-8 Loc./Eiev.: 2065'-0" M-OX Dwg: M-OX4511

1. Barrier Thickness:

6"

10. Annular Gap (smallest):

N/A

2. Opening Size:

8"0 11. Gap between pen:

N/A

3. Penetrants:

(1)2"P. (1) 1"P

12. Barrier Type:

N

4. Sealant Type:

None

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

N/A

14. Pipe Insulated:

Yes

6. Damming Side 2:

N/A Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

NIA Jeff Suter

9. Sealant Depth:

N/A Reviewed By:

Walkdown Comments:

This seal is Non-Appendix R located in the Turbine 9-3/4" North of column line T-8 and approximately 7' west of T-0.

There is no seal in this penetration. Changed Detail to "NR".

Sketch:

M-663-00017A Revision WOI Page Bl-15 ofBI-172 Penetration Seal Data Appendix:

B1 Penetration #:

P45150321 Penetration Type:

NR Fire Area (Side 1): T-12 Fire Area (Side 2):

T-8 Loc./Eiev.: 2065'-0" M-OX Dwg: M-OX4511

1. Barrier Thickness:

6"

10. Annular Gap (smallest):

N/A

2. Opening Size:

16"0 11. Gap between pen:

N/A

3. Penetrants:

{2)1""(1)3/4""P.(1)6"P

12. Barrier Type:

N

4. Sealant Type:

None

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

N/A

14. Pipe Insulated:

Yes

6. Damming Side 2:

N/A Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Ace/Rei):

N/A Jeff Suter

9. Sealant Depth:

N/A Reviewed By:

Walkdown Comments:

This seal is Non-Appendix R located in the Turbine 9'-3" North of column line T-8 and approximately 6'-6" west ofT-F. There is no seal in th is penetration. Changed Detail to "NR".

Sketch:

M-663-00017A, Revision WOI Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2020'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P611W0071 M-6A 12" 12"0 (1)8P Foam Recessed 1/2"

6. Damming Side 2:

Fl ush

7. Damming Continuity (Acc/Rej):

Accept

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth:

9-1 /2" Walkdown Comments:

Page B I-I 59 ofB 1-172 Appendix:

81 Fire Area (Side 1):

F-1 Fire Area (Side 2): F-3 M-OX Dwg: M-1X6906

10. Annular Gap (smallest):

1" 11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Wall thickness determined by Drawing C-1 C61 11. Changed Detail from M-1 to M-6A based on actual sealant depth.

Sketch:

FA: F-1 Side 1 P611W0071 FA: f-3 Slde 2

M-663-0001 7A Revision WO l Page 8 1-160 of 8 1-1 72 Penetration Seal Data Appendix:

81 Photos:

P611W0071 Fire Area F-1 (Side 1)

Fire Area F-1 (Side 1)

Fire Area F-3 (Side 2)

Fire Area F-3 (Side 2)

M-663-000l?A Revision WOl Page B 1-161 of B 1-J 72 Penetration Seal Data Appendix:

B1 Penetration#:

P611W0201 Penetration Type:

M-6A Fire Area (Side 1 ):

F-2 Fire Area (Side 2): F-3 Loc./Eiev.: 2015' -3" M-OX Dwg: M-1X6906

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

1-1 /2"

2. Opening Size:

12"0

11. Gap between pen:

N/A

3. Penetrants:

(1)8"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Flush

14. Pipe Insulated:

No

6. Damming Side 2:

Flush Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing C-1C6111. Changed Detail from M-1lo M-6A based no actual foam depth.

Sketch:

FA: F*2 Slde1 P611W0201 FA: F-3 Sfde2

M-663-00017A Revision WOl Page B 1-162 of B l-1 72 Penetration Seal Data Appendix:

81 Photos:

P611W0201 Fire Area F-2 (Side 1)

Fire Area F-2 (Side 1)

Fire Area F-3 (Side 2)

Fire Area F-3 (Side 2)

M-663-00017A, Revision WOl Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2026'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

P62150137 M-6A 1 0" 10"0 (1)6"P Foam Page Bl-1 63 ofBI-172 Appendix:

B1 Fire Area (Side 1): F-5 Fire Area (Side 2): F-2 M-OX Dwg: M-OX6211

10. Annular Gap (smallest):

1-1/2"

11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Foam 3" above Slab

14. Pipe Insulated:

No

6. Damming Side 2:

Recessed 2" Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc!Rej):

N/A Jeff Suter

9. Sealant Depth:

10" Reviewed By:

Walkdown Comments:

Slab thickness (12") determined by C-1 C6211. Changed Detail from M-1 to M-6A based on actual foam thickness.

Sketch:

FA; F-5 Slde1 r -----~

I 1------+--

f,Q-D&t'Y'M4.6

~

I>

P621S0137 FA: f-2 S de 2

M-663-00017A Revision WOl Page Bl-164 ofBI -1 72 Penetration Seal Data Appendix:

81 Photos:

P62150137 Fire Area F-5 (Side 1)

Fire Area F-5 (Side 1)

Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017A Revision WOl Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2026'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P621S0158 M-6A 1 0" 14"0 (1)10"P Foam 3-3/4" above slab Page B l-165 of B I-I 72 Appendix:

B1 Fire Area (Side 1 ): F-5 Fire Area (Side 2): F-2 M-OX Dwg: M-OX6211

10. Annular Gap (smallest):

1/4" 11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No

6. Damming Side 2:

2" recessed w/Q-Deck Valley Wayne Aregood

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Jeff Suter

9. Sealant Depth:

1 0-3/4" Reviewed By:

Walkdown Comments:

Slab thickness (12") determined by C-1 C6211. Changed Detail M-1 to M-6A based on actual foam depth.

Sketch:

P621S0153 FA: f*2 Slde2

M-663-00017A, Revision WOJ Page B 1-166 of B 1-172 Penetration Seal Data Appendix:

81 Photos:

P621S0158 Fire Area F-5 (Side 1)

Fire Area F-5 (Side 1)

Fire Area F-2 (Side 2)

Fire Area F-2 (Side 2)

M-663-00017A Revision WOJ Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.: 2040'-11/

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:
6. Damming Side 2:

P621W0011 M-6A 12" 10"D (1)6"P Foam Flush 1/2" recessed

7. Damming Continuity (Acc/Rej):

Accepl

8. Boot Condition (Acc/Rej):

N/A

9. Sealant Depth:

9-1 /2" Walkdown Comments:

Page B 1-167 of B 1-L 72 Appendix:

B1 Fire Area (Side 1): F-4 Fire Area (Side 2):

F-5 M-OX Dwg: M-OX6908

10. Annular Gap (smallest):

3/4"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Wall thickness (12") determined by C-1C6211. Changed Detail from M-1 to M-6A based on actual foam depth.

Sketch:

FA: F-4 Side 1 P621W0011 fOQ tn ----+-'

C.n'P)

FA: F-5 Sld*2

M-663-00017A, Revision WOl Page Bl-16 ofBI-172 Penetration Seal Data Appendix:

81 Photos:

P621W0011 Fire Area F-4 (Side 1)

Fire Area F-4 (Side 1)

Fire Area F-5 (Side 2)

Fire Area F-5 (Side 2)

M -663-00017 A, Revision WO 1 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

1986'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1:
6. Damming Side 2:

P712S0013 RB-5A 14"0 (1) 6"' p

7. Damming Continuity (Acc/Rej):
8. Boot Condition (Acc/Rej):
9. Sealant Depth:

Walkdown Comments:

Page B1-169 ofBl-172 Appendix:

B1 Fire Area (Side 1):

Fire Area (Side 2):

M-OX Dwg: M-OX7113

10. Annular Gap (smallest):
11. Gap between pen:
12. Barrier Type:

R

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

No Jeff Suter Prepared By:

Wayne Aregood Reviewed By:

This is not an Appendix R Barrier. The Penetration is located in the Radwaste Building.

Sketch:

M-663-00017A, Revision WOl Page B 1-170 of B 1-172 Penetration Seal Data Appendix:

B1 Penetration #:

P712S0014 Penetration Type:

N/A Fire Area (Side 1):

Fire Area (Side 2):

Loc./Eiev.: 1986'-0" M-OXDwg: M-OX7113

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:

10" X 12"

11. Gap between pen:
3. Penetrants:

6" X 8" V

12. Barrier Type:

R

4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Side1:
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (Acc/Rej):

Prepared By:

8. Boot Condition (Acc/Rej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This is not an Appendix R Barrier. The Penetration is located in the Radwaste Building.

Sketch:

M-663-00017A, Revision W01 Page B 1-1 71 of B 1-172 Penetration Seal Data Appendix:

B1 Penetration #:

P71250015 Penetration Type:

RB-1 Fire Area (Side 1):

Fire Area (Side 2):

Loc./Eiev.:

1986'-0" M-OX Dwg: M-OX7113

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:

6"0

11. Gap between pen:
3. Penetrants:

(1) 3" p

12. Barrier Type:

R

4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Side1:
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (Acc/Rej):

Prepared By:

8. Boot Condition (Acc/Rej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This is not an Appendix R Barrier. The Penetration is located in the Radwaste Building.

Sketch:

M-663-00017 A, Revision WOl Page Bl-172 of Bl-172 Penetration Seal Data Appendix:

B1 Penetration #:

P712W1006 Penetration Type:

N/R Fire Area (Side 1):

Fire Area (Side 2):

Loc./Eiev.: 1988'-4" M-OX Dwg: M-OX7907

1. Barrier Thickness:
10. Annular Gap (smallest):
2. Opening Size:

6"0

11. Gap between pen:
3. Penetrants:

(1) 3" p

12. Barrier Type:
4. Sealant Type:
13. Opening Sleeved or Concrete:
5. Damming Side1:
14. Pipe Insulated:

No

6. Damming Side 2:

Jeff Suter

7. Damming Continuity (Acc/Rej):

Prepared By:

8. Boot Condition (Acc/Rej):

Wayne Aregood

9. Sealant Depth:

Reviewed By:

Walkdown Comments:

This penetration is not in an Appendix R Barrier. It is located in the wall between Radwaste and the Radwaste Tunnel.

Sketch:

N

M-663-000 17 A Attachment B2 Revision W04 Table of Contents Page 2 of 9 Revision Log................................................................................................................................. 3 1.0 Purpose............................................................................................................................. 4 2.0 Scope................................................................................................................................ 4 3.0 References........................................................................................................................ 4 4.0 Evaluation......................................................................................................................... 5 5.0 Conclusions....................................................................................................................... 9 Appendix 82, Penetration Seal Data....................................................... (95 Total Pages)

M-663-00017 A 2 Revision W04 Revision Reason for Revision W01 Original Issue Page 3 of9 Revision Log W04 Included new penetration P135S0943 added by Change Package 012957.

M-663-000 17 A Attachment B2 Revision W04 1.0 Purpose Page 4 of9 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10.

2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1.

2.2 Refer to Section 7.0 of M-663-00017A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017. In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern.

3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April24, 1986 3.2 NRC Information Notice 88-04, "Inadequate Qualification and Documentation of Fire Barrier Penetration Seals".

3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details, Rev. W20 3.6 PIR 2005-2384, Penetrations Requiring Field Work 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth.

M-663-00017 A Attachment B2 Revision W04 Page 5 of 9 5.0 Evaluation Penetration Number P112W1378 P112W1380 P121S0264 P121S0271 P121S0277 P121S0278 P122S0362 P131S0492 P132S0682 P132S0683 P132S0684 5.1 Assessment of Condition to Design Requirements The Table I penetrations are large diameter openings containing a large pipe penetrant. Each Table I penetration opening exceeds the opening size limitation of the assigned typical detail from M-663-000 17. The M-663-000 17 typical detail opening size limitations are based on successful fire test configurations.

TABLE I Penetrations with Opening Sizes Exceeding Typical Detail Limitations Communicating Opening Size Data Fire Areas Typical Detail Detail Actual Actual Seal Comments/Disposition Side 1 Side2 Limit Openin~ Size Surface Area (in2)

(in')

(in2)

A-1 C-1 FB-1 113 1385 679 Acceptable annular gap. See Section 5.2.2.

A-1 C-1 FB-1 113 1385 679 Acceptable annular gap. See Section 5.2.2.

A-1 A-4 RB-1 154 201 151 Acceptable annular gap. See Section 5.2.1.

A-1 A-4 FB-1 113 201 88 Acceptable annular gap. See Section 5.2.2.

A-1 A-4 RB-1 154 707 553 Acceptable annular gap. See Section 5.2.1.

A-1 A-4 RB-1 154 380 226 Acceptable annular gap. See Section 5.2.1.

A-1 A-2 RB-1 154 201 173 Acceptable annular gap. See Section 5.2.1.

A-8 A-1 FB-1 113 707 254 Acceptable annular gap. See Section 5.2.2.

A-8 A-1 FB-1 113 707 254 Acceptable annular gap. See Section 5.2.2.

A-8 A-1 M-1 648 707 254 Acceptable annular gap and free area. See Section 5.2.1 and Note 1.

Pipe insulation abuts bottom side damming. This configuration provides additional structural support for the damming and foam sealant during fire exposures.

A-8 A-1 M-1 648 707 254 Acceptable annular gap and free area. See Section 5.2.1 and Note 1.

Insulation completely covers the seal configuration, providing additional shielding from direct flame impingement, enhancing structural integrity of the enclosed seal configuration.

M-663-000 17 A 2 Revision W04 Communicating Penetration Fire Areas Number Side 1 Side2 P132S0693 A-10 A-1 P132S0739 A-8 A-1 P132W1844 A-8 A-3 P133S0799 A-25 A-1 P134S0860 A-24 A-1 P134W2053 A-8 A-24 P135S0232 A-15 A-33 P135S0233 A-15 A-33 P135S0943 A-15 A-33 P141S1014 A-16 A-8 P141W2486 A-16 A-26 P142S1083 A-16 A-8 P142S1086 A-16 A-8 P142W1933 A-16 A-10 P143W1488 A-5 F-4 P143W1489 A-5 F-4 P145S0943 A-23 A-29 P145S0944 A-23 A-29 Typical Detail Detail Limit (in2)

RB-1 154 FB-1 113 FB-1 113 RB-1 154 RB-1 154 RB-8 154 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 M-1 648 FB-1 113 RB-8 154 FB-1 113 FB-1 113 FB-1 113 FB-1 113 Page 6 of 9 Opening Size Data Actual Actual Seal Comments/Disposition Openin~ Size Surface Area (in")

(in2) 452 374 Acceptable annular gap. See Section 5.2.1.

201 151 Acceptable annular gap. See Section 5.2.2.

707 254 Acceptable annular gap. See Section 5.2.2.

452 339 Acceptable annular gap. See Section 5.2.1.

452 339 Acceptable annular gap. See Section 5.2.1.

254 141 Acceptable annular gap. See Section 5.2.1.

201 123 Acceptable annular gap. See Section 5.2.2.

154 104 Acceptable annular gap. See Section 5.2.2.

154 75 Acceptable annular gap. See Section 5.2.2.

707 254 Acceptable annular gap. See Section 5.2.2.

254 141 Acceptable annular gap. See Section 5.2.2.

707 254 Acceptable annular gap and free area. See Section 5.2.1 and Note 1.

Bottom side insulation completely covers the seal configuration providing additional shielding from direct flame impingement, thus enhancing the overall configuration significantly.

Refer to Attachment 813 for as left configuration following field action necessary to address PIR 2005-2384.

707 254 Acceptable annular gap. See Section 5.2.2.

452 198 Acceptable annular gap. See Section 5.2.1.

254 141 Acceptable annular gap. See Section 5.2.2.

254 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

M-663-00017 A 2 Revision W04 Communicating Penetration Fire Areas Number Side 1 Side2 P145S0946 A-23 A-30 P145S0947 A-23 A-30 P145S0952 A-23 A-15 P145S0954 A-23 A-15 P145W2468 A-23 T-2 P145W2469 A-23 T-2 P145W2470 A-23 T-2 P145W2471 A-23 T-2 P152W2585 A-19 A-22 P311W0839 C-1 CC-1 P611W0197 F-2 F-3 P621S0153 F-5 F-3 P621S0156 F-4 F-3 P621S0157 F-4 F-2 P621S0162 F-4 F-2 P621W0009 F-4 F-5 P621W0017 F-5 F-4 P621W0221 A-5 F-4 P621W0224 A-5 F-4 Typical Detail Detail Limit (in2)

FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 FB-1 113 Page 7 of 9 Opening Size Data Actual Actual Seal Comments/Disposition Openin~ Size Surface Area

{in')

(in1_

154 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

Refer to Attachment B 13 for as left configuration following field action necessary to address PIR 2005-2384.

154 141 Acceptable annular gap. See Section 5.2.2.

Refer to Attachment B 13 for as left configuration following field action necessary to address PIR 2005-2384.

154 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

154 141 Acceptable annular gap. See Section 5.2.2.

154 75 Acceptable annular gap. See Section 5.2.2.

1018 311 Acceptable annular gap. See Section 5.2.2.

201 88 Acceptable annular gap. See Section 5.2.2.

154 75 Acceptable annular gap. See Section 5.2.2.

201 88 Acceptable annular gap. See Section 5.2.2.

201 88 Acceptable annular gap. See Section 5.2.2.

201 88 Acceptable annular gap. See Section 5.2.2.

201 88 Acceptable annular gap. See Section 5.2.2.

201 88 Acceptable annular gap. See Section 5.2.2.

254 141 Acceptable annular gap. See Section 5.2.2.

254 141 Acceptable annular gap. See Section 5.2.2.

M-663-00017 A Page 8 of 9 2 Revision W04 Communicating Opening Size Data Penetration Fire Areas Typical Detail Actual Actual Seal Comments/Disposition Number Detail Surface Area Notes:

1.

Side 1 Side2 Limit Openin~ Size (in1_

(in')

(in2)

Additional justification for acceptability is provided in "Comments/Disposition" column. The comments addresses in-plant configurations that provide additional seal structural enhancement and shielding from direct flame impingement.

5.2 Evaluation of Condition 5.2.1 Silicone Foam (M-1) and Radflex (RB-1 and RB-8) Seals In most of the Table I cases, the annular gap between the opening sidewall and penetrant are relatively small in size, resulting in small free areas, and/or seal surface areas.

When this is the case, the small free area (area of seal with no penetrants) minimizes the concern of structural failures during fire and hose stream exposures.

Structural failures during fire exposures is a concern primarily in Silicone Foam, Radflex, or Silicone Elastomer type seals with large free areas due to charring of the primary sealant. During the char process the primary sealant undergoes physical changes that tend to degrade structural integrity and the cohesion between the sealant, opening sidewall and penetrant.

However, due to smaller annular gaps and free areas, the smaller unsupported spans of primary sealant material resist the affects of sag and structural degradation. Industry testing has demonstrated that larger free areas have successfully sustained structural integrity during fire and hose stream exposure.

Therefore, if the annular gap or free area limitation is maintained, structurally the seal is unaffected regardless of opening size, due to the large pipe penetrant.

Based on this, it is reasonable to conclude that the penetration seal with opening sizes in excess of limitations and with annular gaps that are within limitations, will function and perform equal to tested configurations. In all cases, annular gap/free area limitations of the assigned M-663-00017 typical detail are satisfied by the Table I penetrations sealed with Silicone Foam or Radflex. Therefore, the opening sizes for the M-1, RB-1 and RB-8 seals in Table I are acceptable, and will not present a negative affect regarding seal performance.

M-663-000 17 A Attachment B2 Revision W04 Page 9 of9 5.2.2 Ceramic Fiber (FB-1) Seals Ceramic fiber materials are inert and not affected by char or sag caused by material characteristic changes during fire exposure.

If the annular gap limitation is maintained, structurally the seal is unaffected regardless of opening size.

Based on this, it is reasonable to conclude that the penetration seal with opening sizes in excess of limitations and with annular gaps that are within limitations, will function and perform equal to tested configurations.

In all cases, annular gap/free area limitations of M-663-00017 typical detail FB-1 are satisfied by the Table I penetrations sealed with ceramic fiber. Therefore, the opening sizes for the FB-1 seals in Table I are acceptable, and will not present a negative affect regarding seal performance.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation.

The opening sizes presented by the Table I penetrations do not impact the penetration seal capability to provide fire boundary protection for a 3-hour duration.

6.0 Conclusions Based on the above discussions, it is reasonable to conclude that the Table I penetrations seal are acceptable and will perform their intended function regardless of opening size deviations.

The penetrations satisfy regulatory requirements and commitments, as well as WCNOC Fire Protection Program requirements.

Rev.

No.

W01 W04 M-663-00017A 2 Fire Protection Evaluation For Penetrations That Exceed Opening Size Limitation Prepared By Date Reviewed By

~~~

08/19/05 ~~

Wayne S Aregood Jeff Suter

~ti.4L/'-

12/14/11 ~~

Don Garbe Jeff Suter Page 1 Date 08/19/05 12/15/2011

M-663-00017 A Revision W04 Penetration Seal Data Penetration #:

P112W1378 Penetration Type:

FB-1 Loc./Eiev.: 1979'-6"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:

36" 42"0 (1) 30"P

4. Sealant Type:

Ceramic Fiber

5. Damming Side1 :

Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept Pa e B2-1 of B2-95 Appendix:

B2 Fire Area (Side 1 ):

A-1 M-OX Dwg: M-1X1902 Fire Area (Side 2): C-1

10. Annular Gap (smallest):

3" 11. Gap between pen:

N/A

12. Barrier Type:

A F

13. Opening Sleeved or Concrete:
14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter Steel

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Insulation abuts boot, does not transition through seal zone. Insulation removed. no longer insulated.

Sketch:

M-663-00017 A, Revision W04 Pa e 82-2 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P112W1378 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-3 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P112W1380 Penetration Type:

FB-1 Fire Area (Side 1): A-1 Fire Area (Side 2): C-1 Loc./Eiev.:

1979'-6" M-OX Dwg: M-1X1902

1. Barrier Thickness:

36"

10. Annular Gap (smallest):

3"

2. Opening Size:

42"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 30"P

12. Barrier Type:

A F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Sketch:

M-663-000 17 A, Revision W04 Pa e 82-4 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P112W1380 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area C-1 (Side 2)

Fire Area C-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-5 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P12150264 Penetration Type:

RB-1 Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc./Eiev.:

1988'-0" M*OXDwg: M-OX1211

1. Barrier Thickness:

19"

10. Annular Gap (smallest):

1"

2. Opening Size:

16" D

11. Gap between pen:

N/A

3. Penetrants:

(1)8P

12. Barrier Type:

F R

W

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Unknown

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined by drawing C-OC1211 Sketch :

FA: A-1 SIDE 1 FA: A-4 SIDE2

M-663-00017 A Revision W04 Pa e 82-6 of 82-95 Penetration Seal Data Appendix:

B2 Photos:

P121S0264 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

Loc.JEiev.:

1988'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants :
4. Sealant Type:
5. Damming Side1 :
6. Damming Side 2:

P121S0271 FB-1 22" 16" D (1) 12"P Ceramic Fiber Boot Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept Pa e 82-7 of 82-95 Appendix:

B2 Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 M-OX Dwg: M-OX1211

10. Annular Gap (smallest):

1/2"

11. Gap between pen:

N/A

12. Barrier Type:

F R

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC 1211.

Sketch:

FA: A-1 SIDE 1 FA: A-4 SIDE2

(~)

P121S0271

M-663-00017A, Revision W04 Pa e 82-8 of 82-95 Penetration Seal Data Appendix:

B2 Photos:

P121S0271 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1 )

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017 A, Revision W04 Pa e B2-9 of B2-95 Penetration Seal Data Appendix:

B2 Penetration #:

P12150277 Penetration Type:

RB-1 Fire Area (Side 1 ): A-1 Fire Area (Side 2): A-4 Loc./Eiev.: 1988'-0" M-OX Dwg: M-OX1211

1. Barrier Thickness:

19"

10. Annular Gap (smallest):

6"

2. Opening Size:

30" D 11. Gap between pen:

N/A

3. Penetrants:

(1) 14"P

12. Barrier Type:

F R

W

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC1211.

Insulation appears to transition through seal area. Penetrant appears to be concentrically positioned and annulus is equal all the way around.

Sketch:

M-663-00017 A, Revision W04 Pa e 82-10 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P121S0277 Fire Area A-1 (Side 1 )

Fire Area A-1 (Side 1)

Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-11 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P121S0278 Penetration Type:

RB-1 Fire Area (Side 1 ): A-1 Fire Area (Side 2):

A-4 Loc./Eiev.:

1988'-0" M-OX Dwg: M-OX1211

1. Barrier Thickness:

19"

10. Annular Gap (smallest):

2"

2. Opening Size:

22" D

11. Gap between pen:

N/A

3. Penetrants:

(1) 14P

12. Barrier Type:

F R

W

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Ace/Rei):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth :

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined from drawing C-OC12 11.

Sketch:

FA: A-1 SlOE 1 FA: A-4 SIDE2 P121S0278

M-663-00017 A, Revision W04 Pa e 82-12 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P12150278 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1}

y Fire Area A-4 (Side 2)

Fire Area A-4 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

loc./Eiev.:

1988'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P122S0362 RB-1 1 9" 16"D (1 )6"P Radflex Flush w/sleeve

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept

9. Sealant Depth:

.. 32" Walkdown Comments:

Pa e B2-13 of B2-95 Appendix:

B2 Fire Area (Side 1 ): A-1 Fire Area (Side 2):

A-2 M-OX Dwg: M-OX1221

10. Annular Gap (smallest):

3" 11. Gap between pen:

N/A

12. Barrier Type:

F R

W

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Wayne Aregood Prepared By:

Jeff Suter Reviewed By:

Slab thickness determined from drawing C-OC1211... Rad Flex in bottom side boot is not included in sealant depth.

Sketch:

FA: A*1 S de1 SEC1tOIIJ A P122S0382 b (-rn*)

FA:A--2 Sldo2

M-663-00017 A, Revision W04 Pa e 82-14 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P12250362 Fire Area A-1 (Side 1)

Fire Area A-1 (Side 1)

Fire Area A-2 (Side 2)

Fire Area A-2 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-15 of 82-95 Penetration Seal Data Appendix:

B2 Penetration#:

P131S0492 Penetration Type:

FB-1 Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1311

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

2"

2. Opening Size:

30"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NJA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on C-1 C 131 1.

Sketch:

FA: A-8 Slde1 st:cno"-1 A 1>131$0.492 AN ('N e) f'J0<111--DlS'ULJtr.o ~

(rtP)

FA! A-1 S de 2

M-663-00017 A, Revision W04 Pa e 82-16 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P131S0492 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1 )

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-17 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P132S0682 Penetration Type:

FB-1 Fire Area (Side 1 ):

A-8 Fire Area (Side 2): A-1 Loc./Eiev.:

2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness:

10"

10. Annular Gap (smallest):

2"

2. Opening Size:

30"D

11. Gap between pen:

N/ A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Wayne Aregood

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness determined by Drawing C-1C1311 (wsa)

Sketch:

FA: A~

Slde1 P1l2S0682 FA:A-1 de 2

M-663-000 17 A, Revision W04 Pa e 82-18 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P132S0682 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-19 of 82-95 Penetration Seal Data Appendix:

B2 Penetration#:

P132S0683 Penetration Type:

M-6A Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

1"

2. Opening Size:

30"0 11. Gap between pen:

N/A

3. Penetrants:

(1)24"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Assumed per detail

14. Pipe Insulated:

Yes

6. Damming Side 2:

Recessed 4" Jeff Suter

7. Damming Continuity (Acc/Rej):

Accept Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth:

11".

Reviewed By:

Walkdown Comments:

Top side seal is enclosed within support insulation. Insulation abuts damming board on bottom side. Slab thickness determined by Drawing C-1C1311 (wsa ).

  • 11" foam depth based on installation QC documentation (WSA). (See Drawing M-13EF02; Essential Service Water Supply [EF] Line Number 076-HBC-24 ", 95F Design Temp, 1-1/2"thick, Classification "AS" [Anti-Sweat) Fiberglass Type Insulation)

Sketch:

FA: A-41 Sld a 1 P1 l2S0683 FA:. A-1 Sk>>2

M-663-00017 A, Revision W04 Pa e 82-20 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P132S0683 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-21 of 82-95 Penetration Seal Data Appendix:

B2 Penetration#:

P13250684 Penetration Type:

M-1 Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321

1. Barrier Thickness:

1 0"

10. Annular Gap (smallest):

lndeterminant

2. Opening Size:

30"0

11. Gap between pen :

N/ A

3. Penetrants:

(1 )24"P

12. Barrier Type:

F

4. Sealant Type:

Foam

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1:

Assumed per detail

14. Pipe Insulated:

Yes

6. Damming Side 2:

Assumed per detail Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

N/A Wayne Aregood

9. Sealant Depth:

Assumed per detail Reviewed By:

Walkdown Comments:

Insulation covers opening on both barrier sides. Slab thi1ckness determined by Drawing C-1 C1311 (wsa) (See Drawing M-13EF03: Essential Service Water Return [EF] Line Number 080-HBC-24", 110F Design Temp, 1-1/2" thick, Classification hAS [Anti-Sweat] Fiberglass Type Insulation)

Sketch:

FA: A-8 Side 1

.... Po P132S068..

o...~- -~

.q~._-.a

,, \\)c.._ \\

FA: A*1 Side 2

M-663-00017 A, Revision W04 Pa e 82-22 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P13250684 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-23 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P13250693 Penetration Type:

RB-1 Fire Area (Side 1 ): A-1 0 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:

20" 24"0 (1 )10"P Radflex M-OX Dwg: M-1X1321

10. Annular Gap (smallest):

5"

11. Gap between pen:

N/A

12. Barrier Type:

F

13. Opening Sleeved or Concrete:
5. Damming Side1:

Radflex flush w/top of sleeve

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

27" Reviewed By:

Walkdown Comments:

R Steel Slab thickness based on C-1 C 1311. Insulation appear to transition through the seal. FB-6 could not be confirmed.

Sketch:

FA: A-10 Side 1 P13250693

~A~

(TYP)

..... El -

  • ~.l>.

. 0

~.. * *..!" ~~

FA: A*t Side 2

M-663-00017 A, Revision W04 Pa e 82-24 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P13250693 Fire Area A-1 0 (Side 1)

Fire Area A-1 0 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

Penetration Type:

Loc./Eiev.:

2000'-0"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:
4. Sealant Type:
5. Damming Side1 :

P132S0739 FB-1 12" 16"0 (1) 8.. P Ceramic Fiber Boot

6. Damming Side 2:

Boot

7. Damming Continuity (Acc/Rej):

N/A

8. Boot Condition (Acc/Rej):

Accept Pa e 82-25 of 82-95 Appendix:

82 Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 M-OX Dwg: M-1X1321

10. Annular Gap (smallest):

3"

11. Gap between pen:

NIA

12. Barrier Type:

F

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

Yes Wayne Aregood Prepared By:

Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on C-1 C1311.

Sketch:

FA: A-8 Side 1 P132S0739 111/ S(II..If TI~u (nt) eoo ~ (T'lf)

FA: A*1 Side2

M-663-00017 A Revision W04 Pa e 82-26 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P132S0739 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-27 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P132W1844 Penetration Type:

FB-1 Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-3 loc./Eiev.:

2013'-9" M-OX Dwg: M-1X1918

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

3"

2. Opening Size:

30"D

11. Gap between pen:

N/A

3. Penetrants:

{1) 24P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:
5. Damming Side1 :

Boot

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):
  • Accept Jeff Suter
9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Wall thickness determined by Drawing 1-C01321. Insulation encapsulated, assumed OK.

Sketch:

FA: A..S Slde1 I>.;, **

  • I ***

. ~. *, F:. t;;J '

D.. '

., *.... fl. 0' *

. c**... *.......

... Q' *. D L_ -

    • ..... o *,

J "o

'. ' \\

, /)

1 IN J, 141./t'f/iUt/

I

~

eFJCMS4./JA17~1J

.D *

  • P1l2W1844 FA:. "'-3*

Slde2 Steel

M-663-00017 A, Revision W04 Pa e 82-28 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P132W1844 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-3 (Side 2)

Fire Area A-3 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-29 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P133S0799 Penetration Type:

RB-1 Fire Area (Side 1): A-25 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331

1. Barrier Thickness:

12

10. Annular Gap (smallest):

4"

2. Opening Size:

24"D

11. Gap between pen:

N/A

3. Penetrants:

(1) 12P

12. Barrier Type:

F R

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Unknown

14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept

  • Jeff Suter
9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

  • Boot for bottom side only, top side enclosed. Insulation appears to transition through the sealant zone. (WSA)

(See Drawing M-13EJ02; Residual Heat Removal Train 8 [EJ] Line Number 009-ECB-12", 350F Design Temp, 2" thick, Classification "X" Calcium Silicate Type Insulation)

Sketch:

FA: A*25 Side 1 P1335Dn9 L

.. ll -

... b I

t

.' D

  • 1:> :*

'a.

f).J5c.tUI(C"j)

S'-<ffb r FA: A-1 Slde2

M-663-00017 A, Revision W04 Pa e 82-30 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P13350799 Fire Area A-25 (Side 1)

Fire Area A-25 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-31 of 82-95 Penetration Seal Data Appendix:

B2 Penetration#:

P134S0860 Penetration Type:

RB-1 Fire Area (Side 1 ): A-24 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1341

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

4"

2. Opening Size:

24"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 12"P

12. Barrier Type:

F R

4. Sealant Type:

Radflex

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :
  • Unknown
14. Pipe Insulated:

Yes

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):
  • Accept Jeff Suter
9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Slab thickness based on drawing C-1 C 131 1.

  • Top side seal is covered with support insulation and shielding, obscuring inspection attributes. Insulation appears to transition through the sealant via bottom side examination.

Sketch:

FA: A-24 S de 1

/-- ~

~

,r-St.af'tt~CT tNSIIIAT1 I _

_l __ I_ --~

(O~I:C l

~~11-,.

, "' I l' *,

  • ~

'o

'o:l 1,- -

-,'~-,-,1 r I~

J'O I

BR~~-----~~~~~~

(T'IP)

FA: A-1 Slda2

M-663-00017 A, Revision W04 Pa e 82-32 of 82-95 Penetration Seal Data Appendix:

B2 Photos:

P134S0860 Fire Area A-24 (Side 1)

Fire Area A-24 (Side 1)

Fire Area A-1 (Side 2)

Fire Area A-1 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Penetration #:

P134W2053 Penetration Type:

Loc./Eiev.: 2012'-3"

1. Barrier Thickness:
2. Opening Size:
3. Penetrants:

RB-8 36" 18"0 (1) 12P

4. Sealant Type:

Radflex/foam

5. Damming Side1 :

N/A

6. Damming Side 2:

N/A

7. Damming Continuity (Acc!Rej):

N/A

8. Boot Condition (Ace/Rei):

Accept

9. Sealant Depth:

34" **

Walkdown Comments:

Pa e 82-33 of 82-95 Appendix:

B2 Fire Area (Side 1): A-8 Fire Area (Side 2):

A-24 M-OX Dwg: M-1X1921

10. Annular Gap (smallest):

2" 11. Gap between pen:

N/A

12. Barrier Type:

F w

13. Opening Sleeved or Concrete:

Steel

14. Pipe Insulated:

No Jeff Suter Prepared By:

Wayne Aregood Reviewed By:

Barrier thickness determined by Drawing C-OC1341 (wsa). ** Sealant depth determined by inspection report.

Sketch:

FA: A~

Side 1 P13AW2.053 t

FA: A-24 Slde2

M-663-00017 A, Revision W04 Pa e 82-34 of 82-95 Penetration Seal Data Appendix:

B2 Photos:

P134W2053 Fire Area A-8 (Side 1)

Fire Area A-8 (Side 1)

Fire Area A-24 (Side 2)

Fire Area A-24 (Side 2)

M-663-000 17 A, Revision W04 Pa e 82-35 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P135S0232 Penetration Type:

FB-1 Fire Area (Side 1 ):

A-15 Fire Area (Side 2): A-33 Loc./Eiev.: 2000'-0" M-OXDwg: M-1X1151

1. Barrier Thickness:

16"

10. Annular Gap (smallest):

1 1/2"

2. Opening Size:

16"0

11. Gap between pen:

N/A

3. Penetrants:

(1) 10"P

12. Barrier Type:

A F w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Assumed Per Detail Reviewed By:

Walkdown Comments:

Underside of slab has Q-Decking, effective barrier thickness is measured from corrugated valley.

Sketch:

FA: A-15 SIDE 1

M-663-000 17 A, Revision W04 Pa e 82-36 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P135S0232 Fire Area A-15 (Side 1)

Fire Area A-15 (Side 1)

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-37 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P135S0233 Penetration Type:

FB-1 Fire Area (Side 1): A-15 Fire Area (Side 2): A-33 Loc./Eiev.: 2000'-0" M-OXDwg: M-1X1151

1. Barrier Thickness:

16"

10. Annular Gap (smallest):

1"

2. Opening Size:

14"0

11. Gap between pen:

N/A

3. Penetrants:

(1) a**p

12. Barrier Type:

A F

w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Wayne Aregood

7. Damming Continuity (Acc/Rej):

NIA Prepared By:

8. Boot Condition (Acc/Rej):

Accept Jeff Suter

9. Sealant Depth:

Asummed Per Detail Reviewed By:

Walkdown Comments:

Underside of slab has Q-Decking, effective barrier thickness is measured from corrugated valley.

Sketch:

FA: A-15 SIDE1

~-

M-663-00017 A, Revision W04 Pa e 82-38 of 82-95 Penetration Seal Data Appendix:

82 Photos:

P13550233 Fire Area A-15 (Side 1 )

Fire Area A-15 (Side 1)

Fire Area A-33 (Side 2)

Fire Area A-33 (Side 2)

M-663-00017 A, Revision W04 Pa e 82-39 of 82-95 Penetration Seal Data Appendix:

B2 Penetration #:

P135S0943 Penetration Type:

FB-1 Fire Area (Side 1): A-15 Fire Area (Side 2): A-33 Loc./Eiev.: 2013'-6" M-OX Dwg:

M-1X1352

1. Barrier Thickness:

12"

10. Annular Gap (smallest):

Not Reviewed

2. Opening Size:

14"0 11. Gap between pen:

Not Reviewed

3. Penetrants:

(1) 10" p

12. Barrier Type:

A F

P w

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

NIA

14. Pipe Insulated:

No

6. Damming Side 2:

NIA Jeff Suter

7. Damming Continuity {Acc/Rej): NIA Prepared By:
8. Boot Condition (Acc/Rej):

Not Reviewed Don Garbe

9. Sealant Depth:

Not Reviewed Reviewed By:

Walkdown Comments:

The walkdown review was based on design location of the penetration, as identified on Sketch:

FA. A--IS

'itttlt. I PlOSS<ZPI"-\\3 CER ~Io<t<. FXBE~

Tlo>50U.~ (;r<(P.)

M-1X1352

M-663-00017 A, Revision W04 Pa e 82-40 of 82-95 Penetration Seal Data Appendix:

B2 Penetration#:

P14151014 Penetration Type:

FB-1 Fire Area (Side 1): A-16 Fire Area (Side 2): A-B Loc.IEiev.: 2026'-0" M-OXDwg: M-1X1411

1. Barrier Thickness:

20"

10. Annular Gap (smallest):

2-1 /4"

2. Opening Size:

30"0 11. Gap between pen:

N/A

3. Penetrants:

(1) 24"P

12. Barrier Type:

F

4. Sealant Type:

Ceramic Fiber

13. Opening Sleeved or Concrete:

Steel

5. Damming Side1 :

Boot

14. Pipe Insulated:

No

6. Damming Side 2:

Boot Jeff Suter

7. Damming Continuity (Acc/Rej):

N/A Prepared By:

8. Boot Condition (Acc/Rej):

Accept Wayne Aregood

9. Sealant Depth:

Assumed per detail Reviewed By:

Walkdown Comments:

Slab thickness based on C-OC 1411.

Sketch:

FA: 4*16 Sfde 1 P141S1014 FA: A-s Slde2