Category:NOTICE OF VIOLATION OF A REGULATION
MONTHYEARML20205D7051999-04-0202 April 1999 Notice of Violation from Insp & Investigation Concluded on 981119.Violation Noted:On 980511,supervisor Employed by Raytheon Corp Contractor at Lasalle,Confirmed Odor of Alcohol on Employee & Failed to Perform for-cause FFD Test ML20205D5891999-03-29029 March 1999 Notice of Violation from Insp & Investigation Concluded on 981119.Violation Noted:On 980511,supervisor Employed by Raytheon Corp Contractor at Lasalle,Confirmed Odor of Alcohol on Employee & Failed to Have Require for-cause Test ML20237A5901998-08-0707 August 1998 Notice of Violation from Insp on 980713-16.Violation Noted: on 980526,two Construction Laborers Permitted to Enter Unit 2 a Reactor Water Cleanup Heat Exchanger Room,W/O Satisfying Provisions of TS 6.1.1.1 ML20236U3841998-07-24024 July 1998 Notice of Violation from Insp on 980706-21.Violation Noted: as of 980717,testable Valves 1FP-160A,160B,161,236 & 234 in Fire Protection Sys Lines That Supply Fire Suppression Water to Control Room Not Cycled in Preceding 12 Months ML20236L4541998-07-0202 July 1998 Notice of Violation from Insp on 980423-0605.Violation Noted:Two Operators,Performing OOS Tag Removal & Positioning of Control Room Ventilation Sys Dampers,Did Not Perform an apart-in-time Independent Verification ML20248M1271998-06-0505 June 1998 Notice of Violation from Insp on 980319-0421.Violations Noted:As of 980421,licensee Failed to Adequately Perform Combustible Loading Calculations Required by LaSalle Administrative Procedure 240-6,rev 36,dtd 970821 ML20217D0611998-03-23023 March 1998 Notice of Violation from Insp on 971222-980306.Violation Noted:Licensee Failed to Ensure,Through Documentation & Other Activities That Applicable Design Basis & Regulatory Requirements Translated Into Procedures & Instructions IR 07100101/20120181998-01-23023 January 1998 Notice of Violation from Insp on 971101-1218.Violation Noted:Activities Affecting Quality Were Not Accomplished IAW Applicable Procedures ML20198T3631998-01-21021 January 1998 Notice of Violation from Insp on 971215-17.Violation Noted:On 971201 Contract Workers Failed to Contact Radiation Protection Prior to Cutting Grinding & Welding Activities on Reactor Water Cleanup Sys Piping Respectively ML20197A8221997-11-0707 November 1997 Notice of Violation from Insp on 971010 & 20.Violation Noted:On 970908,SM Jozwiak Reported for Duty at LaSalle County Nuclear Station & Was Found to Have Used an Illegal Drug,Marijuana ML20212B3101997-10-15015 October 1997 Notice of Violation from Insp on 970628-0808.Violations Noted:Licensee CA for NOV Issued on 970124 Re Inadequate Instructions for Performing Manual Backwash,Were Not Adequate to Preclude Repetition ML20212B5271997-10-10010 October 1997 Notice of Violation from Insp on 970908-12.Violation Noted: on 970904,listed Sys Were Inoperable & Licensee Unable to Restore One Subsysten/Sys within 4 H or Established Secondary Containment Integrity within Following 8 H ML20217B4251997-08-29029 August 1997 Notice of Violation from Insp on 970510-0627.Violation Noted:Inspectors Identified That Surveillance Test Results Indicated That 1B Rhrp Parameters in Required Action Range & Licensee Did Not Immediately Declare Pump Inoperable ML20151J8221997-07-22022 July 1997 Notice of Violation from Insp on 970322-0509.Violation Noted:Procedures Recommended in App a of RG.133,Rev 2 Were Not Implemented ML20149F0221997-07-17017 July 1997 Notice of Violation from Insp on 970428-0620.Violation Noted:Test Engineer Conducting Residual Heat Removal SWS post-mod Testing,Safety Related Function Returned to Work W/O Break of 8 H Between Work Periods ML20140B6731997-05-20020 May 1997 Notice of Violation from Insp on 970207-0321.Violation Noted:Applicable Procedures Recommended in App a of RG 1.33,Rev 2,Feb 1978,were Not Correctly Implemented ML20137J7461997-03-26026 March 1997 Notice of Violation from Insp on 961207-970206.Violations Noted:Applicable Procedures Recommended in App a of RG 1.33 Rev 2,Feb 1978 Were Not Correctly Implemented ML20140C3901997-03-24024 March 1997 Notice of Violation from Insp on 970224-28.Violation Noted: as of 970223,technician Did Not Ensure Reasonable Efforts Made to Prevent Spread of Contamination from Contaminated Areas in Unit 1 a & B Heater Drain Pump Rooms ML20134N1171997-02-14014 February 1997 Notice of Violation from Insp on 961106-07,1204,970103 & 0203.Violation Noted:Minor Mod Was Performed on Components & Sys Using Nuclear Design Info Transmittal Form Rather than Process in Lap 1300-14 from Late 1995 to Oct 1996 ML20134M5291997-02-13013 February 1997 Notice of Violation from Insp on 961026-1213.Violation Noted:Operator Performing LaSalle Operation Surveillance DG-Q2 Did Not Have Copy of Surveillance Procedure ML20134G4871997-01-29029 January 1997 Notice of Violation from Insp on 960914-1025 & 1213. Violation Noted:Applicable Procedures Recommended in App a of RG 1.33,Rev 2,dtd Feb 1978,were Not Correctly Implemented in Listed Instances ML20132E8941996-12-0909 December 1996 Notice of Violation from Insp on 961001-08.Violation Noted: Licensee Staff Performed Bench Tests & Determined AOV Actuators in RCIC & PCIS Did Not Exhibit Preloaded Spring Closing Forces Specified in Written Specifications ML20135A4321996-11-26026 November 1996 Notice of Violation from Insp on 960803-0913.Violation Noted:Failure to Use Appropriate Root Cause Analysis procedure,LTP-500-1,to Troubleshoot & Determine Failure Mechanism When Output Breaker O DG Failed ML20134N2641996-11-20020 November 1996 Notice of Violation from Insp on 961015-18.Violation Noted:Licensee Did Not Make Surveys to Assure Compliance w/10CFR20.1201(a) Which Limits Radiation Exposure to 5 Rem Total Effective Dose Equivalent ML20134M9861996-11-15015 November 1996 Notice of Violation from Insp on 960903-24.Violations Noted: on 960331,for Unit 1 & on 960531,for Unit 2,fuel Pool Emergency Makeup Pumps Removed from Svc to Be Modified by Adding SS Weld Overlay to CS Pump Casing ML20129D5661996-09-23023 September 1996 Notice of Violation from Insp on 960622-0802.Violation Noted:C/As for 941224,MSIV Closure & C/As for Problem Identification Form Written on 950306,not Effective in Preventing Recurrence of MSIV Closure & Reactor Scram ML20134C6971996-09-17017 September 1996 Notice of Violation from Insp on 960525-0622.Violation Noted:Hydrogen & Oxygen Monitoring Systems for Units 1 & 2 Were Being Operated in Continuous Mode for More than 1 Yr ML20149H2871994-11-0909 November 1994 Notice of Violation from Insp on 940820-1007.Violation Noted:Licensee Did Not Promptly Identify,Nor Take Proper Actions to Correct Flow Measuring Orifices,Which Were Installed Backwards ML20058H3811993-12-0606 December 1993 Notice of Violation from Radiation Insp on 931102-09. Violations Noted:On 931031,operator Did Not Immediately Leave Area as Required When Dosimeter Alarm Went Off. Operator Entered Contaminated Area W/Required Clothing ML20058B8241993-11-18018 November 1993 Notice of Violation from Insp on 930927-1001,06-08,18-20 & 25-29.Violation Noted:Radiation Protection Procedures Not Adhered to & During Concument Work Activities on Refuel Floor.Licensee Failed to Peform Adquate Surveys ML20058A8981993-11-17017 November 1993 Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $112,500 from Insp on 930908-14.Violation Noted:Surveys to Determine That Individual Exposures to Airborne Concentrations Do Not Exceed Limits Not Made ML20059K6511993-11-0303 November 1993 Notice of Violation from Insp on 930827-1015.Violation Noted:Hoses & Electrical Cord Which Breached Contaminated Area Boundaries Were Not Taped as Required to Avoid Spread of Contamination from Controlled Area ML20059D9591993-10-26026 October 1993 Notice of Violation from Insp on 930923-25.Violations Noted: Failure to Follow Procedures Re Mispositioning of Spent Fuel Assembly in Unit 2 Spent Fuel Pool on 930913 & Inadequate Corrective Actions to Prevent Similiar May 1993 Event ML20059D0901993-10-22022 October 1993 Notice of Violation from Insp on 930823-0930.Violation Noted:Written Safety Evaluation Not Performed for Changes to Facility in Listed Cases ML20059A1211993-10-15015 October 1993 Notice of Violation from Insp on 920603-0720.Violation Noted:Licensee Records Required to Be Maintained by NRC Regulations Not Complete or Accurate in All Matl Respects ML20057G0741993-10-0707 October 1993 Notice of Violation from Insp on 930729-0916.Violation Noted:Maint Procedures Used to Repair O DG Cooling Water Pump Oil Fill Line Did Not Include Critical Tolerances Necessary to Adequately Reset Oil Levels ML20057D2631993-09-27027 September 1993 Notice of Violation from Insp on 930811-18.Violation Noted: Hose Storage Area on 754' Elevation of Turbine Building Contained Smearable Levels of Contamination in Excess of 1,00dpm/100cm2 & Not Posted W/Caution.. ML20057B8741993-09-17017 September 1993 Notice of Violation from Insp on 930713-0827.Violation Noted:Relay Was Miswired While Performing Mod on 2B Diesel Generator Cooling Water Pump & Hoses & Electrical Cords Which Breached Contaminated Area Boundaries Were Not Taped ML20127A6401993-01-0505 January 1993 Notice of Violation from Insp on 921126-1228.Violation Noted:Incorrect Fuse Removed During Performance of LaSalle Electrical Surveillance (LES)-PC-101 ML20126C0811992-12-16016 December 1992 Notice of Violation from Insp on 9211102-1214.Violation Noted:As of 921120,inappropriate Equation Was Used to Evaluate Design Basis Capability of safety-related MOVs ML20125C8281992-12-0404 December 1992 Notice of Violation from Insp on 921014-1125.Violation Noted:Procedures for Preparation for Refueling & Refueling Equipment Operation,Rwcu Sys & Liquid Radioactive Waste Not Adhered to ML20128B6161992-11-25025 November 1992 Notice of Violation from Insp on Stated Dates.Violation: Operator Not Fully Familiar W/Requirements of RWP Under Which He Worked,Observed Climbing While Wearing Minimal Protective Clothing (Booties & Gloves) ML20127D8191992-09-0909 September 1992 Notice of Violation from Insp on 920824-28.Violation Noted: Package of Radioactive Spent Resins Transported W/O Required Info of Content,Activity & Transport Index ML20062E0321990-11-0909 November 1990 Notice of Violation from Insp on 900902-1020.Violation Noted:Failure to Specifically Address 10CFR50.59 Reviews, Activities & Updated FSAR Changes in Util Annual Rept ML20055D9751990-06-28028 June 1990 Notice of Violation from Insp on 900530.Violation Noted: Licensee Failed to Conduct Adequate Evaluation to Determine Radiological Conditions Associated W/Floor Contamination Before Allowing Worker Entry Onto Contaminated Floor ML20248A2271989-09-22022 September 1989 Notice of Violation from Insp on 890725-0911.Violations Noted:Licensee Attempted to Lineup Common Reactor Bldg Closed Cooling Water HX from Unit 2 to 1 W/O Approved Procedure ML20245E8831989-08-0303 August 1989 Notice of Violation from Insp on 890610-0724.Violation Noted:Equipment Contaminated W/Byproduct Matl Transferred to Unauthorized Offsite Equipment Repair Vendor ML20246D6221989-06-30030 June 1989 Notice of Violation from Insp on 890523-0616.Violations Noted:Licensee Failed to Include Appropriate Quantitative & Qualitative Acceptance Criteria Specified by Tech Specs for Aforementioned Ventilation Sys Into Implementing Procedure ML20245K8011989-06-28028 June 1989 Notice of Violation from Insp on 890501-05,15-19 & 25. Violations Noted:Failure to Demonstrate That Diesel Generator Automatic Trips Automatically Bypassed as Stated & Failure to Review Listed Procedures for Adequacy ML20245E6011989-06-20020 June 1989 Notice of Violation from Insp on 890425-0609.Violation Noted:On 890405 & 19,util Failed to Identify Cause of Failure & Corrective Action Re Reactor Bldg Ventilation Isolation Damper 1999-04-02
[Table view] Category:TEXT-INSPECTION & AUDIT & I&E CIRCULARS
MONTHYEARIR 05000373/19990151999-10-0606 October 1999 Insp Repts 50-373/99-15 & 50-374/99-15 on 990729-0916.One Violation Noted & Being Treated as Ncv.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support IR 05000373/19990141999-09-0808 September 1999 Insp Repts 50-373/99-14 & 50-374/99-14 on 990809-13.No Violations Noted.Major Areas Inspected:Quality of Emergency Preparedness Program,Related Audits & Emergency Response Facilities & Equipment IR 05000373/19990131999-08-25025 August 1999 Insp Repts 50-373/99-13 & 50-374/99-13 on 990804-06 & 09-11. No Violations Noted.Major Areas Inspected:Effectiveness of Licensee Fire Protection Program IR 05000373/19990121999-08-17017 August 1999 Insp Repts 50-373/99-12 & 50-374/99-12 on 990623-0728.No Violations Noted.Major Areas Inspected:Plant Operations, Maint,Engineering & Plant Support IR 05000373/19990111999-07-14014 July 1999 Insp Repts 50-373/99-11 & 50-374/99-11 on 990614-18.No Violations Noted.Major Areas Inspected:Routine,Announced Insp Assessed Effectiveness of Licensee Solid Radioactive Waste (Radwaste) Mgt & Transportation Program IR 05000373/19990041999-07-13013 July 1999 Insp Repts 50-373/99-04 & 50-374/99-04 on 990513-0622.No Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support IR 05000373/19990031999-05-19019 May 1999 Insp Repts 50-373/99-03 & 50-374/99-03 on 990401-0512.Two Violations Noted & Being Treated as non-cited Violation. Major Areas Inspected:Aspects of Licensee Operation,Maint, Engineering & Plant Support IR 05000373/19990101999-05-14014 May 1999 Insp Repts 50-373/99-10 & 50-374/99-10 on 990419-23. Violations Noted.Major Areas Inspected:Security Procedures & Documentation,Staff Knowledge & Performance,Security Force Training & Qualification & Quality Assurance in Security IR 05000373/19990091999-05-0303 May 1999 Insp Repts 50-373/99-09 & 50-374/99-09 on 990406-09.No Violations Noted.Major Areas Inspected:Operational & Outage Radiation Protection Program IR 05000373/19990071999-05-0303 May 1999 Insp Repts 50-373/99-07 & 50-374/99-07 on 990329-0402. Non-cited Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support IR 05000373/19990081999-04-20020 April 1999 Insp Repts 50-373/99-08 & 50-374/99-08 on 990311-26.No Violations Noted.Major Areas Inspected:Review of Engineering Changes & Plant Matl Condition in Preparation for re-start of Unit 2 IR 05000373/19990021999-04-16016 April 1999 Insp Repts 50-373/99-02 & 50- 374/99-02 on 990217-0331.Non- Cited Violation Identified.Major Areas Inspected:Aspects of Licensee Operations,Maint,Engineering & Plant Support PNO-III-99-020, on 990409,Unit 2 Had Been Shut Down Since Sept 1996 for Refueling Outage That Was Extended in Order to Address Extensive Equipment Condition.Util Completed Comprehensive Corrective Action Program1999-04-13013 April 1999 PNO-III-99-020:on 990409,Unit 2 Had Been Shut Down Since Sept 1996 for Refueling Outage That Was Extended in Order to Address Extensive Equipment Condition.Util Completed Comprehensive Corrective Action Program ML20205D7051999-04-0202 April 1999 Notice of Violation from Insp & Investigation Concluded on 981119.Violation Noted:On 980511,supervisor Employed by Raytheon Corp Contractor at Lasalle,Confirmed Odor of Alcohol on Employee & Failed to Perform for-cause FFD Test ML20205D5891999-03-29029 March 1999 Notice of Violation from Insp & Investigation Concluded on 981119.Violation Noted:On 980511,supervisor Employed by Raytheon Corp Contractor at Lasalle,Confirmed Odor of Alcohol on Employee & Failed to Have Require for-cause Test IR 05000373/19990011999-03-10010 March 1999 Insp Repts 50-373/99-01 & 50-374/99-01 on 990106-0216.No Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support IR 05000373/19980231999-02-0202 February 1999 Insp Repts 50-373/98-23 & 50-374/98-23 on 981121-990105.No Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plant Support IR 05000373/19980261998-12-18018 December 1998 Insp Repts 50-373/98-26 & 50-374/98-26 on 981026-1106.No Violations Noted.Major Areas Inspected:Engineering & Assessment of Actions Planned or Completed to Address Number of Events Discussed in LERs IR 05000373/19980221998-12-17017 December 1998 Insp Repts 50-373/98-22 & 50-374/98-22 on 981010-1120.No Violations Noted.Major Areas Inspected:Plant Operations, Maint,Engineering & Plant Support IR 05000373/19980251998-12-16016 December 1998 Insp Repts 50-373/98-25 & 50-374/98-25 on 981102-06.No Violations Noted.Major Areas Inspected:Findings & Conclusions from Special Insp of Licensee Operator Workaround Program IR 05000373/19980211998-11-0707 November 1998 Insp Repts 50-373/98-21 & 50-374/98-21 on 980901-1009.No Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support PNO-III-98-047, on 981005,diver Lost Consciousness While in Unit 2 Suppression Pool.Diver Received Minor Contamination on Hair During Removal of Mask & Diving Suit.Diver Was Successfully Decontaminated1998-10-0606 October 1998 PNO-III-98-047:on 981005,diver Lost Consciousness While in Unit 2 Suppression Pool.Diver Received Minor Contamination on Hair During Removal of Mask & Diving Suit.Diver Was Successfully Decontaminated IR 05000373/19980191998-09-24024 September 1998 Insp Repts 50-373/98-19 & 50-374/98-19 on 980716-0831.No Violations Noted.Major Areas Inspected:Plant Operations, Maint,Engineering & Plant Support IR 05000373/19980201998-09-0808 September 1998 Insp Repts 50-373/98-20 & 50-374/98-20 on 980812-13. Non-cited Violation Noted.Major Areas Inspected: Circumstances Surrounding 980723 Incident Re Transfer of Radioactive Samples from Storage Areas on Refuel Floor IR 05000373/19980171998-09-0202 September 1998 Insp Repts 50-373/98-17 & 50-374/98-17 on 980713-17.No Violations Noted.Major Areas Inspected:Security Program Aspect of Plant Support ML20237A5901998-08-0707 August 1998 Notice of Violation from Insp on 980713-16.Violation Noted: on 980526,two Construction Laborers Permitted to Enter Unit 2 a Reactor Water Cleanup Heat Exchanger Room,W/O Satisfying Provisions of TS 6.1.1.1 IR 05000373/19980181998-08-0707 August 1998 Insp Repts 50-373/98-18 & 50-374/98-18 on 980713-16. Violations Noted.Major Areas Inspected:Effectiveness of Aspects of Radiation Protection Program IR 05000373/19980151998-07-24024 July 1998 Insp Repts 50-373/98-15 & 50-374/98-15 on 980706-21. Violations Noted.Major Areas Inspected:Operations,Maint & Engineering Performance Areas ML20236U3841998-07-24024 July 1998 Notice of Violation from Insp on 980706-21.Violation Noted: as of 980717,testable Valves 1FP-160A,160B,161,236 & 234 in Fire Protection Sys Lines That Supply Fire Suppression Water to Control Room Not Cycled in Preceding 12 Months PNO-III-98-037, on 980724,Region III Issued Ltr to Util Indicating Sufficient Improvements Made to Support Unit 1 Restart.Unit 2 Will Remain Shut Down for Continuing Mods & Performance Improvement Activities1998-07-24024 July 1998 PNO-III-98-037:on 980724,Region III Issued Ltr to Util Indicating Sufficient Improvements Made to Support Unit 1 Restart.Unit 2 Will Remain Shut Down for Continuing Mods & Performance Improvement Activities IR 05000373/19980121998-07-23023 July 1998 Insp Repts 50-373/98-12 & 50-374/98-12 on 980511-0605.No Violations Noted.Major Areas Inspected:Operations & Effectiveness of Corrective Action Program IR 05000373/19980111998-07-23023 July 1998 Insp Repts 50-373/98-11 & 50-374/98-11 on 980605-0716.No Violations Noted.Major Areas Inspected:Plant Operations, Maint & Engineering IR 05000373/19980161998-07-23023 July 1998 Insp Repts 50-373/98-16 & 50-374/98-16 on 980626-0706.No Violations Noted.Major Areas Inspected:Observations of Crew Performance During Dynamic Simulator Requalification Exam IR 05000373/19980011998-07-0202 July 1998 Insp Repts 50-373/98-01 & 50-374/98-01 on 980423-0605. Violations Noted.Major Areas Inspected:Licensee Operations, Maint,Engineering & Plan Support ML20236L4541998-07-0202 July 1998 Notice of Violation from Insp on 980423-0605.Violation Noted:Two Operators,Performing OOS Tag Removal & Positioning of Control Room Ventilation Sys Dampers,Did Not Perform an apart-in-time Independent Verification ML20248M1271998-06-0505 June 1998 Notice of Violation from Insp on 980319-0421.Violations Noted:As of 980421,licensee Failed to Adequately Perform Combustible Loading Calculations Required by LaSalle Administrative Procedure 240-6,rev 36,dtd 970821 IR 05000373/19980051998-06-0505 June 1998 Insp Repts 50-373/98-05 & 50-374/98-05 on 980319-0421. Violations Noted.Major Areas Inspected:Engineering IR 05000373/19980091998-05-22022 May 1998 Insp Repts 50-373/98-09 & 50-374/98-09 on 980311-0422. Violations Noted.Major Areas Inspected:Operations, Maintenance,Engineering & Plant Support IR 05000373/19980041998-04-10010 April 1998 Insp Repts 50-373/98-04 & 50-374/98-04 on 980124-0310.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000373/19980081998-04-0101 April 1998 Insp Repts 50-373/98-08 & 50-374/98-08 on 980317-19.No Violations Noted.Major Areas Inspected:Evaluation of Licensee Performance During Plant Biennial Exercise of Emergency Plan IR 05000373/19980071998-03-25025 March 1998 Partially Withheld Insp Repts 50-373/98-07 & 50-374/98-07 on 980223-27.No Violations Noted.Major Areas Inspected:Plant Support ML20217D0671998-03-23023 March 1998 Insp Repts 50-373/97-23 & 50-374/97-23 on 971222-980306. Violations Noted.Major Areas Inspected:Engineering ML20217D0611998-03-23023 March 1998 Notice of Violation from Insp on 971222-980306.Violation Noted:Licensee Failed to Ensure,Through Documentation & Other Activities That Applicable Design Basis & Regulatory Requirements Translated Into Procedures & Instructions IR 05000373/19980061998-03-18018 March 1998 Insp Repts 50-373/98-06 & 50-374/98-06 on 980223-27.No Violations Noted.Major Areas Inspected:Chemistry & Radiological Environ Monitoring Programs & Selected RP Program Activities IR 05000373/19970171998-02-27027 February 1998 Insp Repts 50-373/97-17OL & 50-374/97-17OL on 971020-24 & 980121-22.No Viiolations Noted.Major Areas Inspected:Review of Licensed RO & SRO Requalification Training Programs, Including Review of Written & Operating Exam Matls IR 05000373/19980031998-02-18018 February 1998 Insp Repts 50-373/98-03 & 50-374/98-03 on 980126-30.No Violations Noted.Major Areas Inspected:Review of Emergency Preparedness Program,An Aspect of Plant Support IR 05000373/19970221998-02-0505 February 1998 Insp Repts 50-373/97-22 & 50-374/97-22 on 971219-980123.No Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 05000373/19970181998-01-26026 January 1998 Insp Repts 50-373/97-18 & 50-374/97-18 on 971024-1218.No Violations Noted.Major Areas Inspected:Initial Operability Evaluation of Potential DG Cooling Water Piping Waterhammer ML20199F5291998-01-23023 January 1998 Insp Repts 50-373/97-20 & 50-374/97-20 on 971101-1218. Violations Noted.Major Areas Inspected:Operations,Maint, Engineering & Plant Support IR 07100101/20120181998-01-23023 January 1998 Notice of Violation from Insp on 971101-1218.Violation Noted:Activities Affecting Quality Were Not Accomplished IAW Applicable Procedures 1999-09-08
[Table view] |
Text
_ _ _ . _ .__ .
r h
NOTICE OF VIOLATION Commonwealth Edison Company Docket Nos. 50-373; 50-374 LaSalle County Station, Units 1 and 2 License Nos. NPF-11; NPF-18 F
During an NRC inspection conducted on August 23 through September 30, 1993, violations of NRC requirements were identified. In accordance with the
" General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C, the violations are listed below:
- 1. 10 CFR 50.59 requires the licensee to maintain records of changes in the facility and procedures described in the safety analysis report including a written safety evaluation which provides the bases for the determination the change does not involve an unreviewed safety question.
t LaSalle Updated Final Safety Analysis Report (UFSAR), Section 6.4.4, states the emergency makeup air filter trains and control room shielding were designed to limit the occupational doses below levels required by Criterion 19 of 10 CFR 50, Appendix A.
LaSalle UFSAR, Section 10.4.7.5, states that an automatic dump to condenser action on high feedwater heater level was provided.
LaSalle UFSAR, Appendix H.3.5.1, states that the steel beams supporting i the ceiling slab at elevation 794 feet - 0 inches in fire zone 5Al was protected to a rating of three hours. .
Contrary to the above, a written safety evaluation was not performed for_ ,
changes to the facility in the following cases:
- a. A change to the control room ventilation radiation monitors was completed on April 20, 1993, such that the emergency make-up air filter trains and control room shielding would not limit the occupational doses below levels required by Criterion 19 of 10 CFR 4 50, Appendix A, while in the purge mode. (50-373/93020-Ola(DRP)) -
- b. A Unit 2 emergency drain valve for feedwater heater 26B was taken ;
out-of-service on March 12, 1992, for an entire operating cycle
~
which defeated the automatic dump to condenser action on high level in the feedwater heater. (50-374/93020-Olb(DRP))
Contrary to the above, a written safety evaluation conducted on January 23, 1992, for removal of fire proofing material on steel beams ,
supporting the ceiling slab at elevation 794 feet - 0 inches in fire zone 5Al did not provide an adequate basis for the determination that the change did not involve an unreviewed safety question. Fire ,
protection concerns were not addressed in the safety evaluation. (50-373/93020-Olc(DRP))
This is a Severity Level IV violation (Supplement 1).
9311020131 931022 PDR ADOCK 05000373 O PDR .i
_j
r .
- = * .
Notice of Violation 2
- 2. Technical specification 6.1.G.2.a(4) states that the onsite review and investigative function personnel shall be responsible for conducting reviews of all proposed changes or modifications to plant systems or equipment that affect nuclear safety. -
Contrary to the above, no onsite review was conducted for a proposed change and modification completed on April 20, 1993, that affected nuclear safety by increasing the control room ventilation radiation monitors' delay time through alteration of capacitors and resistors on an electronic circuit board. (50-373/93020-03(DRP))
This is a Severity Level IV violation (Supplement 1).
Pursuant to the provisions of 10 CFR 2.201, Commonwealth Edison is hereby required to submit a written statement or explanation. to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington D.C. 20555, with a copy to the Regional Administrator, Region III, and a copy to the NRC Resident inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation '
(Notice). This reply should be clearly marked as a " Reply to a Notice of Violation" and should include for each violation: (1) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4).the ;
date when full compliance will be achieved. If an adequate reply is not received within the time specified in this Notice, an order or a Demand for Information may be issued to show cause why the license should not be modified, suspended, or revoked, or why such other action as may be proper should not be taken. Where good cause is shown, consideration will be given to extending the resnonse time.
6 Dated at Glen Ellyn, Illinois this 22adday of October 1993 ,
i e + r- % v - p w q