MONTHYEARML20217H6231999-10-18018 October 1999 Discusses Completion of Licensing Action for GL 98-01 & Suppl 1, Yr 2000 Readiness of Computer Sys at Npps, to All Holders of Operating Licenses for NPPs ML20217J4331999-10-15015 October 1999 Forwards Insp Rept 50-461/99-19 on 990913-17.One Violation Re Individual Failure to Follow Radiation Protection Procedures When Accessing High Radiation Area Noted & Being Treated as Noncited Violation U-603280, Forwards Rev 27 to Clinton Power Station Physical Security Plan,Iaw 10CFR50.54(p).Encl Withheld from Public Disclosure, Per 10CFR50.54(p)1999-10-12012 October 1999 Forwards Rev 27 to Clinton Power Station Physical Security Plan,Iaw 10CFR50.54(p).Encl Withheld from Public Disclosure, Per 10CFR50.54(p) ML20217C0871999-10-11011 October 1999 Forwards Proprietary Attachment Inadvertently Omitted from Encl 2 to Submitting Responses to NRC RAI Re License Transfer Application for Plant.Proprietary Encl Withheld U-603276, Forwards Rev 8 to CPS USAR, Which Includes Changes from 970701 Through 990630 & Available Changes Approved After 990630 That Reduce Overall Burden of Submittal Changes for Forthcoming Reporting period.10CFR50.59 Rept Included1999-10-0808 October 1999 Forwards Rev 8 to CPS USAR, Which Includes Changes from 970701 Through 990630 & Available Changes Approved After 990630 That Reduce Overall Burden of Submittal Changes for Forthcoming Reporting period.10CFR50.59 Rept Included U-603279, Forwards non-proprietary & Proprietary Responses to NRC RAI Re License Transfer Application for Plant.Attached Responses Also Respond to Comments of Environ Law & Policy Center Dtd 990920.Proprietary Encl Withheld1999-10-0707 October 1999 Forwards non-proprietary & Proprietary Responses to NRC RAI Re License Transfer Application for Plant.Attached Responses Also Respond to Comments of Environ Law & Policy Center Dtd 990920.Proprietary Encl Withheld U-603275, Provides Updated Illinois Power Rept on Status of Decommissioning Funding for Clinton Power Station1999-10-0707 October 1999 Provides Updated Illinois Power Rept on Status of Decommissioning Funding for Clinton Power Station ML20217A9881999-10-0101 October 1999 Advises of NRC Plans for Future Insp Activities at Facility for Licensee to Have Opportunity to Prepare for Insps & to Provide NRC with Feedback on Any Planned Insps Which May Conflict with Plant Activities ML20217A7361999-10-0101 October 1999 Forwards Insp Repts 50-461/99-14 & 50-461/98-12 on 990729-0908.Two Violations Identified,One Re Failure to Place Control Switch in Proper Position to Identify Piece of out-of-svc Equipment & Being Treated as NCVs ML20217J1251999-09-30030 September 1999 Refers to Investigation 3-1997-040 Conducted from 971028- 980921 & Forwards Nov.Investigations Determined That During Jan 1997,supervisor Qv Dept Discriminated Against Qv Inspector in Retaliation for Inspector Contacts with NRC ML20217J1421999-09-30030 September 1999 Refers to Investigation 3-97-040 Conducted from 971028- 980921 & Forwards Nov.Investigation Concluded That Recipient Engaged in Deliberate Misconduct in That Recipient Discriminated Againt Qv Inspector for Having Contacted NRC ML20212G6751999-09-22022 September 1999 Forwards Comment Submitted to NRC by Environ Law & Policy Ctr Re Proposed License Transfer for Clinton Power Station U-603272, Provides Update to Final Response to GL 98-01, Y2K Readiness of Computer Sys at Nuclear Power Plants. 3-D Monicore & Station Security Sys remediated.Y2K Readiness Disclosure for Cps,Encl1999-09-22022 September 1999 Provides Update to Final Response to GL 98-01, Y2K Readiness of Computer Sys at Nuclear Power Plants. 3-D Monicore & Station Security Sys remediated.Y2K Readiness Disclosure for Cps,Encl U-603225, Provides Closure of Util Commitments Re Ci Cv Noted in Previous Ltr to Nrc.Basis for Expecting Valves to Remain in leak-tight Condition Throughout Operating Cycle & Basis That Justifies Not Performing mid-cycle Leak Testing,Encl1999-09-20020 September 1999 Provides Closure of Util Commitments Re Ci Cv Noted in Previous Ltr to Nrc.Basis for Expecting Valves to Remain in leak-tight Condition Throughout Operating Cycle & Basis That Justifies Not Performing mid-cycle Leak Testing,Encl ML20212G6981999-09-20020 September 1999 Requests That NRC Reject Proposed License Transfer for Clinton Power Station & That NRC State That Public Interest in Safe Nuclear Power Industry Will Not Be Subordinated to Interest in Maximizing Profit by Limiting Liability ML20217H3421999-09-17017 September 1999 Forwards Request for Addl Info Re Licensee 990723 Application for License Transfer & Conforming Administrative License Amend.Response Requested within 20 Days of Receipt of Ltr 05000461/LER-1996-010, Forwards LER 96-010-01, Plant Shutdown Due to Unidentified RCS Leakage from Degraded Reactor Recirculation Pump Seal Greater than TS Limit. Revised Rept Includes Cause of Event,Corrective Actions & Discussion of Similar Events1999-09-13013 September 1999 Forwards LER 96-010-01, Plant Shutdown Due to Unidentified RCS Leakage from Degraded Reactor Recirculation Pump Seal Greater than TS Limit. Revised Rept Includes Cause of Event,Corrective Actions & Discussion of Similar Events 05000461/LER-1999-011, Forwards LER 99-011-00 Re Improper Restoration of a APRM Which Caused Monitor to Not Meet Seismic Qualification Requirements.Rept Contains Listed Commitments1999-09-10010 September 1999 Forwards LER 99-011-00 Re Improper Restoration of a APRM Which Caused Monitor to Not Meet Seismic Qualification Requirements.Rept Contains Listed Commitments U-603269, Certifies That DB Livingston,License OP-31136,successfully Completed Facility Licensees Requirements to Be Licensed as Ro,Per 10CFR55 & Has Need for RO License to Perform Assigned Duties.Five Significant Control Manipulations,Listed1999-09-10010 September 1999 Certifies That DB Livingston,License OP-31136,successfully Completed Facility Licensees Requirements to Be Licensed as Ro,Per 10CFR55 & Has Need for RO License to Perform Assigned Duties.Five Significant Control Manipulations,Listed ML20211Q2671999-09-0808 September 1999 Informs That NRC Tentatively re-scheduled Initial Licensing Exams for License Operator License Applicants During Weeks of June 5 & 12,2000.Validation of Exams Will Occur at Station During Weeks of May 15,2000 U-603229, Provides Response to NRC RAI Re GL 95-07, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves, Dtd 990528.Rev 0 to Calculation IP-M-0556 & Rev 0 to Calculation IP-M-0570,encl1999-08-25025 August 1999 Provides Response to NRC RAI Re GL 95-07, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves, Dtd 990528.Rev 0 to Calculation IP-M-0556 & Rev 0 to Calculation IP-M-0570,encl U-603243, Forwards Response to NRC GL 99-02, Lab Testing of Nuclear-Grade Activated Charcoal. Util Performing Testing of ESF Ventilation Sys Charcoal Samples Using ASTM D3803- 1989 Methodology as Required by TS 5.5.71999-08-23023 August 1999 Forwards Response to NRC GL 99-02, Lab Testing of Nuclear-Grade Activated Charcoal. Util Performing Testing of ESF Ventilation Sys Charcoal Samples Using ASTM D3803- 1989 Methodology as Required by TS 5.5.7 ML20211D2201999-08-23023 August 1999 Confirms 990817 Telcon with J Neuschwanger & D Mcneil Re Arrangements Made for NRC to Inspect Licensed Operator Requalification Program at Plant U-603258, Forwards ISI Summary Rept, IAW ASME Section Xi,Article IWA-6000.Summary Rept Addresses ISI Activities Performed at Plant from 950429-990527,including Extended Sixth Refueling Outage1999-08-23023 August 1999 Forwards ISI Summary Rept, IAW ASME Section Xi,Article IWA-6000.Summary Rept Addresses ISI Activities Performed at Plant from 950429-990527,including Extended Sixth Refueling Outage ML20211B0871999-08-20020 August 1999 Responds to J Hopkins Inquiry Re Application for Order Consenting to License Transfer & Approving Conforming Administrative License Amend Filed by Ilpr & Amergen Energy Co on 990723 U-603259, Provides Notification That Cl Kreidler Has Resigned Position with Util,Effective 990818.License Status Should Be Changed to Expired1999-08-19019 August 1999 Provides Notification That Cl Kreidler Has Resigned Position with Util,Effective 990818.License Status Should Be Changed to Expired ML20211A8931999-08-19019 August 1999 Forwards Insp Rept 50-461/99-13 on 990611-0728.Two Violations Noted & Being Treated as Ncvs.Violation Re Three Examples Where Licensee Procedural Requirements for Minor Maint Work Were Not Followed U-603253, Notifies NRC That Je Smith,License SOP-30819-1,has Resigned from Position with Ilpr Effective 990813.Status of License Should Be Changed to Expired,Effective 9908131999-08-16016 August 1999 Notifies NRC That Je Smith,License SOP-30819-1,has Resigned from Position with Ilpr Effective 990813.Status of License Should Be Changed to Expired,Effective 990813 ML20210U3771999-08-12012 August 1999 Forwards Notice of Consideration of Approval of Transfer of FOL & Issuance of Conforming Amend & Opportunity for Hearing Re Amend Request for Approval of Clinton Power Station License NPF-62 Transfer to Amergen U-603250, Notifies NRC That Ma Freihofer (License SOP-31296-1) Has Resigned from Position with Illinois Power Effective 990729 & License Status Should Be Changed to Expired Effective 9907291999-08-10010 August 1999 Notifies NRC That Ma Freihofer (License SOP-31296-1) Has Resigned from Position with Illinois Power Effective 990729 & License Status Should Be Changed to Expired Effective 990729 U-603249, Notifies NRC That He Bouska (License SOP-3055-1) Has Resigned from Position with Illnois Power Effective 990809. & License Status Should Be Changed to Expired Effective 9908091999-08-10010 August 1999 Notifies NRC That He Bouska (License SOP-3055-1) Has Resigned from Position with Illnois Power Effective 990809. & License Status Should Be Changed to Expired Effective 990809 ML20210N2961999-08-0909 August 1999 Forwards Form of Nuclear Decommissioning Master Trust Agreement,Per CPS Application for License Transfer & Conforming Administrative License Amend U-603248, Requests Unrestricted License for Kc Scott,License SOP-31532.Scott Has Successfully Completed Facility Licensee Requirements to Be Licensed as Operator/Senior Operator Per 10CFR551999-08-0606 August 1999 Requests Unrestricted License for Kc Scott,License SOP-31532.Scott Has Successfully Completed Facility Licensee Requirements to Be Licensed as Operator/Senior Operator Per 10CFR55 U-603236, Forwards Revised Data Point Ref File Sheets for Clinton Power Station Computer Points That Input to ERDS1999-08-0202 August 1999 Forwards Revised Data Point Ref File Sheets for Clinton Power Station Computer Points That Input to ERDS ML20210J0541999-07-30030 July 1999 Forwards Three Original Signature Pages of Gr Rainey for Application for License Transfer & Conforming Administrative License Amend, for NRC Files U-603178, Forwards Four ASME Section XI Relief Requests Re Performance of non-destructive Exams for First 120-month Inservice Insp for CPS1999-07-29029 July 1999 Forwards Four ASME Section XI Relief Requests Re Performance of non-destructive Exams for First 120-month Inservice Insp for CPS U-603237, Informs That Util Will Provide Response to fire-related Questions One & Two of NRC RAI Re CPS Ipeee,By 0001311999-07-28028 July 1999 Informs That Util Will Provide Response to fire-related Questions One & Two of NRC RAI Re CPS Ipeee,By 000131 U-603240, Forwards Clinton Power Station semi-annual Fitness for Duty Rept for Period Ending 990630,IAW 10CFR26.711999-07-27027 July 1999 Forwards Clinton Power Station semi-annual Fitness for Duty Rept for Period Ending 990630,IAW 10CFR26.71 U-603235, Forwards Application for License Transfer & Conforming Administrative License Amend for OL NPF-62.Proprietary & Nonproprietary Asset Purchase Agreement Encl.Proprietary Info Withheld,Per 10CFR2.7901999-07-23023 July 1999 Forwards Application for License Transfer & Conforming Administrative License Amend for OL NPF-62.Proprietary & Nonproprietary Asset Purchase Agreement Encl.Proprietary Info Withheld,Per 10CFR2.790 ML20210A4401999-07-16016 July 1999 Forwards Insp Rept 50-461/99-10 on 990422-0610.Four Violations Being Treated as Noncited Violations ML20209G7671999-07-12012 July 1999 Ack Receipt of Encl FEMA Correspondence ,which Transmitted FEMA Evaluation Rept for 981118 Biennial EP Exercise at Clinton Power Station.No Deficiencies Were Observed ML20209D5691999-07-0707 July 1999 Forwards Insp Rept 50-461/99-12 on 990607-11.No Violations Noted.Insp Consisted of Selective Exam of Procedures & Representative Records,Observations of Work in Progress & Interviews with Personnel U-603231, Forwards Summary of Status of Plan for Excellence (Pee) Initiatives & Clinton Power Station (CPS) 1999 Business Plan.Encl Documents Provide Status & Disposition for Actions Not Completed to Date1999-07-0707 July 1999 Forwards Summary of Status of Plan for Excellence (Pee) Initiatives & Clinton Power Station (CPS) 1999 Business Plan.Encl Documents Provide Status & Disposition for Actions Not Completed to Date U-603214, Forwards Results of Analysis Performed on Recently Completed Vendor Contracts,Per GL 83-28, Required Actions Based on Generic Implications of Salem ATWS Events1999-07-0606 July 1999 Forwards Results of Analysis Performed on Recently Completed Vendor Contracts,Per GL 83-28, Required Actions Based on Generic Implications of Salem ATWS Events ML20196J9651999-07-0202 July 1999 Confirms Discussion Between Members of Staffs to Conduct Meeting on 990714 at Clinton Power Station to Discuss Results of Restart Insp & Licensee Progress in Addressing Remaining Long Term C/A Actions to Sustain Improvements ML20196J7131999-06-30030 June 1999 Informs of Closure of Response to Requests for Addl Info to GL 92-01,Rev 1,Supplement 1, Reactor Vessel Structural Integrity, for Clinton Power Station Unit 1 U-603218, Provides Final Response to GL 98-01, Y2K Readiness of Computer Sys at Nuclear Power Plants. Attachment Provides Y2K Readiness Disclosure for Plant1999-06-28028 June 1999 Provides Final Response to GL 98-01, Y2K Readiness of Computer Sys at Nuclear Power Plants. Attachment Provides Y2K Readiness Disclosure for Plant U-603212, Forwards Response to NRC 990315 Telcon Re Proposed Amend of License NPF-62,implementing Feedwater Leakage Control Sys Mode of RHR Sys1999-06-24024 June 1999 Forwards Response to NRC 990315 Telcon Re Proposed Amend of License NPF-62,implementing Feedwater Leakage Control Sys Mode of RHR Sys U-603227, Provides Updated Rept on Status of Decommissioning Funding for Plant.Updated Rept Provides Min Decommissioning Fund Estimate,Per 10CFR50.75(b) & (C) Utilizing NUREG-1307,Rev 8 Methodology1999-06-24024 June 1999 Provides Updated Rept on Status of Decommissioning Funding for Plant.Updated Rept Provides Min Decommissioning Fund Estimate,Per 10CFR50.75(b) & (C) Utilizing NUREG-1307,Rev 8 Methodology ML20196A3471999-06-16016 June 1999 Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Insp Rept 50-461/99-11 Issued on 990430.Corrective Actions Will Be Examined During Future Inspections 1999-09-08
[Table view] Category:OUTGOING CORRESPONDENCE
MONTHYEARML20217H6231999-10-18018 October 1999 Discusses Completion of Licensing Action for GL 98-01 & Suppl 1, Yr 2000 Readiness of Computer Sys at Npps, to All Holders of Operating Licenses for NPPs ML20217J4331999-10-15015 October 1999 Forwards Insp Rept 50-461/99-19 on 990913-17.One Violation Re Individual Failure to Follow Radiation Protection Procedures When Accessing High Radiation Area Noted & Being Treated as Noncited Violation ML20217A7361999-10-0101 October 1999 Forwards Insp Repts 50-461/99-14 & 50-461/98-12 on 990729-0908.Two Violations Identified,One Re Failure to Place Control Switch in Proper Position to Identify Piece of out-of-svc Equipment & Being Treated as NCVs ML20217A9881999-10-0101 October 1999 Advises of NRC Plans for Future Insp Activities at Facility for Licensee to Have Opportunity to Prepare for Insps & to Provide NRC with Feedback on Any Planned Insps Which May Conflict with Plant Activities ML20217J1421999-09-30030 September 1999 Refers to Investigation 3-97-040 Conducted from 971028- 980921 & Forwards Nov.Investigation Concluded That Recipient Engaged in Deliberate Misconduct in That Recipient Discriminated Againt Qv Inspector for Having Contacted NRC ML20217J1251999-09-30030 September 1999 Refers to Investigation 3-1997-040 Conducted from 971028- 980921 & Forwards Nov.Investigations Determined That During Jan 1997,supervisor Qv Dept Discriminated Against Qv Inspector in Retaliation for Inspector Contacts with NRC ML20212G6751999-09-22022 September 1999 Forwards Comment Submitted to NRC by Environ Law & Policy Ctr Re Proposed License Transfer for Clinton Power Station ML20217H3421999-09-17017 September 1999 Forwards Request for Addl Info Re Licensee 990723 Application for License Transfer & Conforming Administrative License Amend.Response Requested within 20 Days of Receipt of Ltr ML20211Q2671999-09-0808 September 1999 Informs That NRC Tentatively re-scheduled Initial Licensing Exams for License Operator License Applicants During Weeks of June 5 & 12,2000.Validation of Exams Will Occur at Station During Weeks of May 15,2000 ML20211D2201999-08-23023 August 1999 Confirms 990817 Telcon with J Neuschwanger & D Mcneil Re Arrangements Made for NRC to Inspect Licensed Operator Requalification Program at Plant ML20211A8931999-08-19019 August 1999 Forwards Insp Rept 50-461/99-13 on 990611-0728.Two Violations Noted & Being Treated as Ncvs.Violation Re Three Examples Where Licensee Procedural Requirements for Minor Maint Work Were Not Followed ML20210U3771999-08-12012 August 1999 Forwards Notice of Consideration of Approval of Transfer of FOL & Issuance of Conforming Amend & Opportunity for Hearing Re Amend Request for Approval of Clinton Power Station License NPF-62 Transfer to Amergen ML20210A4401999-07-16016 July 1999 Forwards Insp Rept 50-461/99-10 on 990422-0610.Four Violations Being Treated as Noncited Violations ML20209G7671999-07-12012 July 1999 Ack Receipt of Encl FEMA Correspondence ,which Transmitted FEMA Evaluation Rept for 981118 Biennial EP Exercise at Clinton Power Station.No Deficiencies Were Observed ML20209D5691999-07-0707 July 1999 Forwards Insp Rept 50-461/99-12 on 990607-11.No Violations Noted.Insp Consisted of Selective Exam of Procedures & Representative Records,Observations of Work in Progress & Interviews with Personnel ML20196J9651999-07-0202 July 1999 Confirms Discussion Between Members of Staffs to Conduct Meeting on 990714 at Clinton Power Station to Discuss Results of Restart Insp & Licensee Progress in Addressing Remaining Long Term C/A Actions to Sustain Improvements ML20196J7131999-06-30030 June 1999 Informs of Closure of Response to Requests for Addl Info to GL 92-01,Rev 1,Supplement 1, Reactor Vessel Structural Integrity, for Clinton Power Station Unit 1 ML20196A3471999-06-16016 June 1999 Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Insp Rept 50-461/99-11 Issued on 990430.Corrective Actions Will Be Examined During Future Inspections ML20207D1261999-05-28028 May 1999 Forwards Request for Addl Info Re GL 95-07, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves ML20206P0641999-05-12012 May 1999 Informs That NRC Office of Nuclear Reactor Regulation Reorganized Effective 990328.As Part of Reorganization,Div of Licensing Project Mgt Created.Aj Mendiola Will Be Section Chief for Clinton Power Station.Organization Chart Encl ML20206K4351999-05-0707 May 1999 Discusses NRC OI Investigation Rept 3-99-002 Re 981018 Personnel Error Which Resulted in Loss of Offsite Power Which Caused Loss of Only Operating Shutdown Cooling Subsystem ('A' RHR Pump) ML20206J7461999-05-0505 May 1999 Forwards Insp Rept 50-461/99-04 on 990301-0407.Four Violations of NRC Requirements Identified & Being Treated as non-cited Violations Consistent with App C of Enforcement Policy ML20206L5191999-05-0303 May 1999 Informs That on 990420-21 NRC Senior Managers Met to Evaluate Nuclear Safety Performance of Operating Reactors, Fuel Cycle Facilities & Other Matl Licenses ML20206G9691999-04-30030 April 1999 Forwards Insp Rept 50-461/99-11 on 990408-21 & NOV Re Failure to Correctly Translate Design Basis for Hydrogen Mixing Compressors Into EDG Load Calculation ML20206G6671999-04-30030 April 1999 Discusses Insp Rept 50-461/99-01 on 990208-0325.Number of Weaknesses Were Identified in C/A Program Re Approval Process for Issuing Condition Repts,Program Effectiveness Reviews & Issue Resolution.Six non-cited Violations Noted ML20206F2111999-04-27027 April 1999 Informs That NRC Considers Util Actions Associated with demand-for-info Pursuant to 10CFR50.54(f) Re C/A Program Performance at Clinton Power Station,Satisfactory & Therefore DFI Closed ML20206F2141999-04-27027 April 1999 Documents Completion of NRC Review of Specific Corrective Actions Util Committed to Complete Prior to Restarting Clinton Power Station & Forwards NRC Manual Chapter 0350 Restart Action Plan ML20206F1741999-04-27027 April 1999 Informs of Completion of Review of Actions Taken by Illinois Power as Specified in NRC CAL-III-97-09 Issued on 970806. Considers Actions Taken to Be Satisfactory & CAL Re 970805 W Circuit Breaker Failure at CPS Closed ML20205S6921999-04-21021 April 1999 Forwards Insp Rept 50-461/99-06 on 990217-0407.Four Violations Noted Re Professional Atmosphere of Main Control Room & Being Treated as Non-Cited Violations ML20205T5711999-04-21021 April 1999 Forwards Insp Rept 50-461/99-03 on 990208-0318.Eight Violations Occurred & Being Treated as non-cited Violations Consistent with App C of Enforcement Policy ML20205M9421999-04-13013 April 1999 Forwards Emergency Response Data System Implementation Documents.Data Point Library Updates for Kewaunee (271), San Onofre (272) & Clinton (273) Encl.Also Encl Plant Attribute Library Update for Grand Gulf (274).Without Encls ML20205P3921999-04-0909 April 1999 Forwards Emergency Preparedness Exercise Insp Rept 50-461/99-08 on 990309-12.No Violations Identified.Exercise Weakness Re Maintenance of Status of Repair Teams Identified During Insp ML20205H3001999-04-0101 April 1999 Confirms Plans to Have Meeting on 990416 at Clinton Power Station to Discuss Results of Plant Performance Review Process & Discuss Progress in Addressing Remaining Open Items in NRC Specific Checklist Which Need Resolution ML20205G2141999-04-0101 April 1999 Ack Receipt of ,Which Transmitted Changes Identified as Rev 26 to CPS Security Plan,Per 10CFR50.54(p) ML20205G5471999-03-26026 March 1999 Advises of Completion of Plant Performance Review on 990202 to Develop Integrated Understanding of Safety Performance. Three Areas of Concern Are Operator Performance,Cap Implementation & Resolution of Engineering Design Issues ML20205C5181999-03-26026 March 1999 Ack Receipt of Revising 2 Previously Communicated Corrective Action Commitments Contained in . Corrections Reviewed & NRC Have No Questions at Present Time ML20204J5071999-03-24024 March 1999 Forwards Insp Rept 50-461/98-29 on 981214-990217.No Violations Noted.Insp Conducted to Review Circumstances Surrounding Unsatisfactory Licensed Operator Performance That Staff Identified During Sept 1998 Operator Exam ML20204F4281999-03-18018 March 1999 Forwards Insp Rept 50-461/99-02 on 990107-0216.Violations Noted.Violation Re Engineering & Work Mgt Personnel Failure to Ensure Overdue Preventive Maint Items Were Completed ML20204E6311999-03-10010 March 1999 Forwards Insp Rept 50-461/99-05 on 990208-12 & Notice of Violation Re Inadequate Radiological Surveys Were Performed in Residual Heat Removal Heat Exchanger Room ML20207K2841999-03-0909 March 1999 Confirms Discussion Between Members of Staffs to Have Meeting on 990325 at Illinois Power Energy & Environ Ctr. Purpose of Meeting to Discuss Performance Improvement Initiatives ML20203F2541999-02-10010 February 1999 Informs That Beginning 990216,DE Hills Will Be Chief of Operations Branch Which Includes Operator Licensing Function ML20202J8541999-02-0505 February 1999 Forwards Notice of Proposed No Significant Hazards Consideration & Opportunity for Hearing ML20202H9941999-02-0303 February 1999 Forwards SE Accepting Changes in Quality Assurance Program Continuing to Meet Requirements of App B to 10CFR50 ML20202G4951999-02-0101 February 1999 Forwards Insp Rept 50-461/98-28 on 981214-18.No Violations Noted.Inspector Concluded That Risk Assessment Process for Evaluating on-line & Outage Maint Activities Has Been Developed ML20202H6851999-01-26026 January 1999 Forwards Request for Addl Info Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves ML20202D7871999-01-22022 January 1999 Confirms Discussion Between Members of Staff to Have Meeting on 990205 at NRC Office in Lisle,Il to Discuss Performance Improvement Initiatives.Meeting Will Be Open to Public ML20203A0501999-01-22022 January 1999 Requests Expedited Publication of Encl Notice of Consideration of Issuance of Amend to Facility Operating License,Proposed NSHC Determination & Opportunity for Hearing on 990129 ML20206S0931999-01-22022 January 1999 Forwards Insp Rept 50-461/98-20 on 981118-0106 & Notice of Enforcement Discretion.Inspectors Identified That Operations Personnel Did Not Initiate Condition Repts for Several Nonconforming Conditions Documented in Main Control Room ML20199E1431999-01-12012 January 1999 Refers to Info Provided on 981229 That Was Requested by NRC in .Informs That Info Has Been Reviewed & Forwards List of Mods & Other Engineering Work Products Which Will Be Reviewed During Ssei ML20198S8221999-01-0505 January 1999 Confirms Discussion Between Members of Staff to Have Meeting on 990114 in Clinton,Il to Discuss Licensee Performance Improvement Initiatives 1999-09-08
[Table view] |
Text
_- . - . - - - - - . _ _ ~ _ _ . . . - - - . - , .-- .
l . .
[/*4r,hh UNITED STATE 3 NUCLEAR REGULATORY COMMISSION 4 % REGION lil l E j 801 WARREtMLLE ROAD
/ UsLE, ILLINOls 60532-4351
+...+ June 9, 1997 Mr. John G. Cook Senior Vice President Clinton Power Station Illinois Power Company Mail Code V-275 P. O. Box 678 -
Clinton, IL G1727
Dear Mr. Cook:
I am writing to document recent conversations between members of our respective staffs regarding safety related circuit breaker and suppression pool emergency core cooling (ECCS) suction strainer operability.
During an engineering and technical support inspection earlier this year, NRC inspectors identified that safety related 480,4160, and 6900 voit safety related breakers had not been maintained in an appropriate manner (Inspection Report No. 50-461-97003), Further, a number of the circuit breakers failed to operate properly in service or while being tested thereby questioning the breakers' operability and reliability until they can be appropriately refurbished. Based on our findings, your engineering statf developed a test and inspection program to provide reasonable assurance that, prior to being fully refurbished, the breakers would perform their intended function. Our review of your program generated a number of questions which were verbally presented to your staff on May 22,1997; enclosure "A'" to this letter documents those questions.
In April of this year, NRC inspectors identified material conditions (i.e., signs, placards,
'j etc.) and degraded coatings in Clinton's containment end raised a concern over their impact on suppression pool ECCS suction strainer operability. Your staff evaluated the material condition and initiated actions to remove the material and improve control over j
such items in the future. The degraded coatings' issue remains to be resoived. Following '
discussions during restart panel meetings on May 15 and 28,1997, a conference call 1
between members of our staffs was held on June 3,1997, to discuss the current status.
On June 4,1997, folicwup discussions addressed the need for Illinois Power (IP) to provide reasonable assurance that all containment and drywell coating is appropriately qualified. During the calls the NRC stated that if the containment coatings could not be qualified, IP must provide reasonable assurance that the ECCS suction strainers will remain operable, i.e., will not clog, following a design basis event. During those calls, our staffs discussed some possible options (refer to enclosure "B") available to IP to address the degraded coatings.
i
~~
9706170154 970609 PDR ADOCK 05000451 O PM
, ! flfffl !!
f l
J. G. Cook I It is our understanding that IP will document its basis for reasonable assurance that safety l related circuit breakers and suppression pool ECCS suction strainers are operable and will l
' perform their intended functions. The documentation, including responses to specific questions, will be provided to NRC prior to unit restart and in sufficient time to allow an appropriate review.
If you have any questions pertaining to these issues, please contact Geoffrey Wright or Chris Miller at (630) 829-9601 or 829-9627 respectively.
Sincerely, y.<
t James L. Caldwell
, Deputy Regional Administrator Docket No. 50-461 l
Enclosures:
As Stated I
cc w/ encl: W. D. Romberg, Assistant Vice President P. Yocum, Plant Manager Clinton Power Station L R. Phares, Manager-Nuclear Assessment '
l J. Sir.x, Director - Licensing L
Nr.mn Schloss, Economist Office of the Attorney General G. Stramback, Regulatory Licensing Services Project Manager General Electric Company Chairman, DeWitt County Board State Liaison Officer Chairrnan, Illinois Commerce Commission i
i 1
i
e - e." I J. G. Cook It is our understanding that IP will document its basis for reasonable assurance that safety related circuit breakers and suppression pool ECCS suction strainers are operable and will perform their intended functions. The documentation, including responses to specific questions, will be provided to NRC prior to unit restart and in sufficient time to allow an appropriate review.
If you have any questions pertaining to these issues, please contact Geoffrey Wright or Chris Millar at (630) 829-9601 or 829-9627 respectively.
Sincerely, !
/s/ James L. Caldwell James L. Caldwell Docket No. 50-461
Enclosures:
As Stated cc w/ encl: W. D. Romberg, Assistant Vice President P. Yocum, Plant Manager >
Clinton Power Station R. Phares, Manager-Nuclear Assessment I J. Sipek, Director - Licensing Nathan ScNoss, Economist :
Office of the Attorney General G. Stramback, Regulatory Licensing Services Project Manager l
General Electric Company Chairman, DeWitt County Boaid State Liaison Officer Chairman, Illinois Commerce Commission Docket File w/ encl DRP w/ encl OC/LFDC8 w/ encl PUBLIC IE-01 w/ encl SRI Clinton, Dresden, Rlli PRR w/enci
' LaSalle, Quad Cities Project Manager, NRR w/ encl A. B. Beach, w/ encl Rlli Enf. Coordinator, w/ encl DOCUMENT NAME: G:/ Clin.ir\BKR& coat. doc To semelve e copy of this docuenent, Indicate in the bom 'C' = Copy without ettechenentlencloeuse 'E' = Copy with attachenent/wncloevee n = ne o. ,y OFFICE Rill pp), E Rlli ppj gr NRR yg C- Rlli & [g Rilh
{ NAME Wright:fp" MillerP Picke'tt e Tradjling' qagwell j DATE 06/4 /97 06/6/97 06/6/97 06/ b/97 0F/4/97
- OFFICIAL RECORD COPY 1
F 1 ;
- i l
i Enclosure A i
Questions Pertaining to the Breaker Testing Program '
- l. A number of breakers in your program have been listed as Critical Non-safety breakers, what is their impact on safety system operability?
. II. By not refurbishing any of the 4160 volt breakers, what affect does that have on reasonable assurance?
Ill. Construct an equipment history / failure history for the breakers.
IV. You have specified an acceptance criteria of 100ms for the low voltage tests.
What is the basis for that criteria?
V. Specific questions:
A. ABB 480V Breakers
- 1. What type of post refurbishment testing was performed?
- 2. Wiring errors on breakers returned from ABB were identified.
Miswiring of the cts can cause the breaker to trip prematurely.
What have you done in this area?
- 3. When the breakers were refurbished, were the trip units replaced with solid state units, i.e., was the breakers' design changed from the original design?
- 4. How and on what time schedule do you plan on refurbishing the remaining 480V ABB safety related breakers?
B. General Electric 4160 Volt Breakers
- 1. Exactly how many of these breakers are going to be tested and inspected?
- 2. Check list questions:
- a. Items 9-12: What is the basis for the > 1 ohm criteria?
- b. Item 46: What is basis for 1000V test rather than a higher voltage?
- c. Item 47: What wrs the amperage for the ductor used?
- d. Was a hypotential test considered?
l I
f
f . -
l C. Westinghouse 4160 Volt Breakers
- 1. You indicated during a restart panel meeting that Illinois Power is going to purchase breakers from another utility as replacements for some of Clinton's breakers. Are the breakers being purchased as safety related breakers? If not, how are they being dedicated?
2.
What is the schedule for refurbishrnent of the remaining breakers?
- 3. Given relative similar history on GE and Westinghouse breakers, why -
is there such a difference between the GE and Westinghouse inspection check lists?
- 4. Check list questions:
- a. What does item 12 mean?
- b. Page 4 - clarify items 6 & 7 regarding criteria for inspecting ,
other breakers. l l c. Items la and 2a: Are these tests conducted at 90 & 70 volts?
- d. Item 6: Same question as item 2a for GE.
- e. Were meggar/ductor tests considered? .
D. Westinghouse 6.9kV Breakers:
l l What criteria / check list was used to inspect and test DVP breakers?
l l
l l
I -
- l. '
l i
l l
t 1
i e , - , , - ,
_ -_ ___ m . . _ . _ _ _ ____ _ . _ _ . . . _ _ _ _ . . _.._ _ .__ _ _ _ _ . ___
Enclosure B The staff is concerned about the integrity of the containment coatings at the Clinton Power Station during post-accident conditions. While paint has been observed to be i blistered and peeling at multiple locations within both the drywell and containment, the staff is particularly concerned with areas above the 828 foot elevation on the refueling floor. It is our understanding that a significant amount of post-construction touch-up painting has been performed in this region and that an excessive amount of degradation has been associated with these repairs. Illinois Power needs to provide justification that either the containment coatings are qualified for the post accident environment or that the ;
ECCS pump suction strainers in the suppression pool will not become clogged due to debris and LOCA-generated paint chips.
Due to the observed degradation of the coatings and the apparent deficiencies in the surface preparation for touch-up paint repairs, it may be difficult to ensure that all the current coatings are qualified for the LOCA environment. Assuming that the existing containment coatings cannot be qualified, reasonable assurance must be provided that the ECCS sump suction strainers will remain operable, i.e., will not clog, during the post- J accident phase. Several options for providing this assurance were discussed:
- 1) Perform multiole adhesion null tests Implement a program utilizing adhesion pull test and provide the basis for the number and location of such tests. It would be expected that multiple adhesion pull tests would need to be performed and that they would need to include construction touch-up areas, areas adjacent to observed degradation, and original liner plate coatings. Tests would be expected in the drywell area and the areas above and below the 828 foot refueling floor in the containment.
- 2) Calculations l
Calculations using the BWR Utility Resolution Guidance (URG) methodology as opposed to the methodology described in the USAR. The URG provides a transport methodology which more appropriately characterizes the anticipated phenomena following a LOCA and includes the results of BWROG and NRC research into debris transport and behavior in the suppression pool. The amount of coatings assumed to detach from the containment liner during the LOCA must be justified. During our initial phone call, Clinton staff indicated that approximately 1500 sq ft of coating was visibly degraded. Because of the uncertainties associated with all the post
' construction repaired areas, NRC would expect the analysis to consider all post-construction touch-up areas as well as all areas currently observed to be degraded (both drywell and containment areas).
I 4
h
. - _ _ - . . _ _ . _ _ . . _ . _ . _ _ . . _ - _ _ _ . _ . m. _ _ _ _ _ . . . . _ . _ _ _ _ _ _ _ _ _ _ . _ .
- 3) Coatina Removal and Test Acoroach f
This approach combines removal of known and suspected degraded coatings in those areas where the coatings would be transported to the suppression pool with an adhesion pull test program. By removing the suspect coatings and testing the remaining coating, reasonable assurance would be provided that the suppression pool strainers will remain operable over the next operating cycle. This approach must include an assessment for those areas left without coating covering the period between unit restart and appropriate re-coating.
E ,
l
[
I C
l t
...