AO 50-271/72-12:on 721106,offgas Sample Chamber Isolated Intentionally to Permit Replacement of Chamber Flow Metering Valve.Valve Found Leaking.Valve Replaced & Three Fittings & One Union Tightened
ML20086H228
Person / Time
Site: Vermont Yankee Entergy icon.png
Issue date: 11/07/1972
From: Rosalyn Jones
VERMONT YANKEE NUCLEAR POWER CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086H216 List:
References
AO-50-271-72-12, VYV-2319, NUDOCS 8401160086
Download: ML20086H228 (1)


Text

_ ..,

. O O ""7# \

E

,z .

a n: ._

.fi ;.

VERMONT YANKEIo NUCLEAR POWER CORPORATION {;[

sEVcNTY SCVcN OMOVC STHcCT l$tJTLAND, YEftMONT 05701 kY, as.n.y voi g. . '-

VYV-2319 , ,.. o. nox 107

.~

VERNON. VERMONT 05354 November 7, 1972 United States Atornic Energy Corcission Ditectorate of Regulatory operations, Region I 970 Broad Street Ncuark, New Jercey 07102 REFEPJWCE: Operating License DPR-28 Docket No. 50-271 Abnorttal Occurrence No. A0-72-12 Centlement As defined by Technical Specifications for the Vermont Yankee Hucicar Power Station, Section 6.7.A.c, we are reporting the following Abnormal Occurrence ao AO-72-12 and confirming our telephone conversation vith your of fice yesterday.

At approximately 1240 on the af ternoon of November 6 with the reactor oporating at approximately 75% power, the off -Cas Sample Chanber van intentionally inolated to permit replacenent of the Sanple Chanber Flow Hetering Valve. Air ejector off-gas van unnonitored for approxinately 15 tainutes and this constituted a violation of Technical Specificationo, r Section 3.8.A.1. During the period that the Off-Cas Sanple Chanber van foolated, and aubnequent to that time, off-gas activity at the atack ohowed a conutant level of 19x103 pci/nce on the atack gas monitoring systen and a grab canplo van obtained at the air ejector.

The Sampic chattber riow Metering Valve van found to he leaking when high nirborno particulate activity in the hirbine Building initiated n nearch for leakage into the building. Besides replacement of the valve, three fittings and one union were tightened.

The off-gaa monitoring nyatem is currently operabic in accordance with Technical Specifications.

8401160086 721110 Very truly youro, PDR ADOCK 05000271 S PDR VEP DNT YA! ATE NUC12AR I'OWER CORPORATION j j l( p Robert F.. Onca b

. Plent Superintendent