ML20086E155

From kanterella
Jump to navigation Jump to search
AO 75-08:on 750408,air Ejector Suction Valve Isolation Time Delay Relay Timer 17-157A Actuated Slow.Cause Not Stated. Timer Reset
ML20086E155
Person / Time
Site: Vermont Yankee Entergy icon.png
Issue date: 04/08/1975
From: Riley B
VERMONT YANKEE NUCLEAR POWER CORP.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086E153 List:
References
AO-75-08, AO-75-8, VYV-3821, NUDOCS 8312060099
Download: ML20086E155 (1)


Text

--- - - - - - - - - ~ '

"g=

, O~

~

VERMONT YANKEE NUCLEAR POWER CORPOR AT10N o

i

! /

i sevcNTY ScVEN OROVE STREET

! RUTI,AND. VHMMONT 05708 VYV-3821 P. O. sox 157 4'

VERNON. VERMONT c5354 April 8, 1975 j

United States Nuclear Regulatory Cemission f - Office of Inspection and Enforcement Region I l 631 Park Avenue j King of Prussia. Pennsylvania 19406

ATTENTION
James P. O'Reilly, Director

REFERENCE:

Operating 1.icenso DPR-28 i Docket No. 50-271 ,

Abnormal Occurrence No. A0-75-08 (24 Hour Report) j

Dear Sir:

i

! As defined by Technical Specifications for the Verrmat Yankee ,

l Nucicar Power Station. Section 6.7. we are reporting the folicniing

Abnormal Occurrence as AO-75-08 and confirming.our telephone conversa-tion with your office. ,

i j At approximately 0900 on April 8,1975, while performing a routine surveillance test, it was discovered that the Air Ejector Suction Valve I Isolation tima delay timer 17-157A actuated at one (1) minute and six (6) seconds. Table 3.2.4 of the Technical Specifications requires that the i trip setting of this timer be set at less than or equal to one (1) minute.

i Failura of this timer to actuate within the specified tolerance resulted j l

in fewer operable instrument channels per trip system than that required j hy Table 3.2.4 of the Technical Specifications.

j The timer was immediately reset to a trip setting of forty-seven (47) i seconds which precluded the necessity of performing the action specified

' in Notes 1 and 2 of Table 3.2.4 of the Technical Specifications.. The plant was operating at full power at the time of tha discovery of this occurrence.

'~

l

! l 1 ~,

Very truly yours, i 'B'radford W. Riley? "

HE/sjp Plant Superintendent

+

~

8312060099 pDR ADOCK 05000271 750418 PDR j S e

  • - r- n y

O O 1

5 5

-p W, A,

- D*t g 7S m e,r, t?%