ML18194A882
ML18194A882 | |
Person / Time | |
---|---|
Site: | FitzPatrick ![]() |
Issue date: | 08/24/2018 |
From: | Booma Venkataraman Plant Licensing Branch 1 |
To: | Bryan Hanson Exelon Generation Co, Exelon Nuclear |
Venkataraman B, NRR/DORL/LPL1 | |
References | |
EPID L-2017-LLA-0311 | |
Download: ML18194A882 (6) | |
Text
SUBJECT: JAMES A. FITZPATRICK NUCLEAR POWER PLANT- ISSUANCE OF AMENDMENT NO. 321 RE: REVISION TO TECHNICAL SPECIFICATIONS TO ADOPT TECHNICAL SPECIFICATIONS TASK FORCE (TSTF) TRAVELER TSTF-542, REVISION 2, "REACTOR PRESSURE VESSEL WATER INVENTORY CONTROL" (EPID L-2017-LLA-0311)
Dear Mr. Hanson:
The U.S. Nuclear Regulatory Commission (the Commission) has issued the enclosed Amendment No. 321 to Renewed Facility Operating License No. DPR-59 for the James A. FitzPatrick Nuclear Power Plant (JAFNPP). The amendment is in response to your application dated October 2, 2017, (Agencywide Documents Access and Management System (ADAMS) Accession No. ML17275A520.) as supplemented by letters dated January 22 and April 19, 2018. (ADAMS Accession Nos. ML18022A829 and ML18109A371, respectively.)
The amendment revises existing JAFNPP technical specification (TS) requirements related to "operations with a potential for draining the reactor vessel," with new requirements on reactor pressure vessel water inventory control to protect the JAFNPP TS Safety Limit 2.1.1.3, which states, "Reactor vessel water level shall be greater than the top of active irradiated fuel."
A copy of the related Safety Evaluation is enclosed. The Notice of Issuance will be included in the Commission's biweekly Federal Register notice.
Sincerely,
Tonya E. Hood, Project Manager
Plant Licensing Branch I
Division of Operating Reactor Licensing
Office of Nuclear Reactor Regulation
Enclosures:
1. Amendment No. 321 to DPR-59
2. Safety Evaluation
1.0 INTRODUCTION
By letter dated October 2, 2017 (Reference 1 ), and as supplemented by letters dated
January 22 and April 19, 2018 (References 2 and 3, respectively), Exelon Fitzpatrick, LLC and
Exelon Generation Company, LLC (the licensee) requested to adopt Technical Specifications
Task Force (TSTF) Traveler TSTF-542, Revision 2, "Reactor Pressure Vessel Water Inventory
Control," (Reference 4) for the James A. FitzPatrick Nuclear Power Plant (JAFNPP). The final
safety evaluation (SE) for TSTF-542, Revision 2, was approved by the U.S. Nuclear Regulatory
Commission (NRC, the Commission) on December 20, 2016 (Reference 5).
The proposed changes would replace existing technical specification (TS) requirements
associated with "operations with a potential for draining the reactor vessel" (OPDRVs) with
revised TSs providing alternative requirements for reactor pressure vessel (RPV) water
inventory control (WIC). These alternative requirements would protect the JAFNPP TS Safety
Limit 2.1.1.3, which states, "Reactor vessel water level shall be greater than the top of active
irradiated fuel."
Additionally, a new definition "DRAIN TIME" would be added to the JAFNPP TSs, Section 1.1,
"Definitions." DRAIN TIME would establish requirements for the licensee to make RPV water
level inventory determinations and to calculate RPV water inventory drain rates for Modes 4 and
5 outage-related activities. Adequate licensee management of secondary containment
requirements or mitigation of certain emergency core cooling system (ECCS) safety
injection/spray systems during Modes 4 and 5 would require a properly calculated DRAIN TIME.
The licensee proposed several JAFNPP plant-specific variations from the TS changes
described in the applicable parts of TSTF-542, Revision 2, or the NRG-approved TSTF-542 SE.
These are explained and evaluated, respectively, in Sections 2.2.5 and 3.5 of this SE.
The supplemental letters dated January 22 and April 19, 2018, provided additional information
that clarified the application, did not expand the scope of the application as originally noticed,
and did not change the NRC staff's original proposed no significant hazards consideration
determination as published in the Federal Register on November 21, 2017 (82 FR 55405).
2.0 REGULATORY EVALUATION
2.1 System Description
The JAFNPP boiling-water reactor (BWR) RPV has a number of penetrations located below the
top of active irradiated fuel (TAF). These penetrations provide entry for control rod drives,
recirculation flow, reactor water cleanup (RWCU), and shutdown cooling. Since these
penetrations are below the TAF, this creates a potential to drain the reactor vessel water
inventory and lose effective core cooling. The loss of water inventory and effective core cooling
can potentially lead to fuel cladding failure and radioactive release.
During operation in Mode 1 (Power Operation - Reactor Mode Switch in Run), Mode 2
(Startup - Reactor Mode Switch in Refuel (with all reactor vessel head closure bolts fully
tensioned) or Startup/Hot Standby), and Mode 3 (Hot Shutdown - Reactor Mode Switch in
Shutdown and average reactor coolant temperature greater than(>) 212 degrees Fahrenheit
(°F), the TS for instrumentation and ECCS require operability of sufficient equipment to ensure
large quantities of water can be injected into the reactor vessel should level decrease below the
preselected value. These requirements are designed to mitigate the effects of a loss-of-coolant
accident (LOCA), but also provide protection for other accidents and transients that involve a
water inventory loss.
During operation in Mode 4 (Cold Shutdown - Reactor Mode Switch in Shutdown with all reactor
vessel head closure bolts fully tensioned and average reactor coolant temperature less than or
equal to (:S) 212 °F), and Mode 5 (Refueling - One or more reactor vessel head closure bolts
less than fully tensioned and Reactor Mode Switch in Shutdown or Refuel), the pressures and
temperatures that could cause a LOCA are not present. During certain phases of refueling
(Mode 5), a large volume of water is available above the RPV (i.e., the RPV head is removed,
the water level is greater than or equal to(~) 22 feet 2 inches above the top of the RPV flange),
and the spent fuel storage pool gates are removed (existing TS limiting condition for operation
(LCO) 3.5.2).
The large volume of water available in and above the RPV ( during much of the time when in
Mode 5) provides time for operator detection and manual operator action to stop and mitigate an
RPV draining event. However, at other times during a refueling outage (i.e., Mode 4 or
Mode 5), there may be a potential for significant drainage paths from certain outage activities,
human error, and other events when it is more likely to have some normally available
equipment, instrumentation, and systems inoperable due to maintenance and outage activities.
There may not be as much time for operator action as compared to times when there are large
volumes of water above the RPV.
In comparison to Modes 1, 2, and 3, with typical high temperatures and pressures (especially in
Modes 1 and 2), Modes 4 and 5 generally do not have the high pressure and temperature
considered necessary for a LOCA envisioned from a high energy pipe failure. Thus, while the
potential sudden loss of large volumes of water from a LOCA are not expected, operators
monitor for BWR RPV water level decrease from potential significant or even unexpected
drainage paths. These potential drainage paths in Modes 4 and 5 generally would require less
water replacement capability to maintain water above TAF. To address the drain down potential
during Modes 4 and 5, the current JAFNPP TSs contain specifications that are applicable during
an OPDRV, or require suspension of OPDRVs if certain equipment is inoperable. The term
OPDRV is not specifically defined in the TSs and historically has been subject to inconsistent
application by licensees. The changes discussed in this SE are intended to resolve any
ambiguity by creating new RPV WIC TSs with attendant equipment operability requirements,
required actions and surveillance requirements (SRs), and deleting references to OPDRVs
throughout the JAFNPP TSs.
2.2 Proposed TS Changes
Section 2.2.1 of this SE discusses the proposed addition of a new definition, "DRAIN TIME"
( evaluated below in SE Section 3.1 ). Section 2.2.2 of this SE discusses the proposed revisions
to TS 3.3, "INSTRUMENTATION," including the proposed revisions to TS 3.3.5.1, "Emergency
Core Cooling System (ECCS) Instrumentation," the proposed addition of a new TS 3.3.5.2,
"Reactor Pressure Vessel Water (RPV) Inventory Control Instrumentation," and the proposed
renumbering of existing TS 3.3.5.2, "Reactor Core Isolation Cooling (RCIC) System
Instrumentation," to TS 3.3.5.3. Section 2.2.3 of this SE discusses the proposed revisions to
TS 3.5, "Emergency Core Cooling System (ECCS) and Reactor Core Isolation Cooling (RCIC)
System," including the proposed revisions to TS 3.5.2, "ECCS - Shutdown" (evaluated below in
SE Section 3.3). Section 2.2.4 of this SE discusses the proposed deletion of existing TS
references to OPDRVs (evaluated below in SE Section 3.6). Section 2.2.5 of this SE discusses
JAFNPP plant-specific variations to TSTF-542, Revision 2 (evaluated below in SE Section 3.5).
In addition, the licensee proposes administrative changes to the table of contents (TOC) to
reflect the above TS changes.
2.2.1 Addition of DRAIN TIME Definition
The following definition of "DRAIN TIME" would be added to Section 1.1, "Definitions":
The DRAIN TIME is the time it would take for the water inventory in and above
the Reactor Pressure Vessel (RPV) to drain to the top of the active fuel (TAF)
seated in the RPVassuming:
a) The water inventory above the TAF is divided by the limiting drain rate:
b) The limiting drain rate is the larger of the drain rate through a single
penetration flow path with the highest flow rate, or the sum of the drain
rates through multiple penetration flow paths susceptible to a common
mode failure (e.g., seismic event, loss of normal power, single human
error), for all penetration flow paths below the T AF except:
1. Penetration flow paths connected to an intact closed system, or
isolated by manual or automatic valves that are locked, sealed, or
otherwise secured in the closed position, blank flanges, or other
devices that prevent flow of reactor coolant through the penetration
flow paths;
2. Penetration flow paths capable of being isolated by valves that will
close automatically without offsite power prior to the RPV water level
being equal to the TAF when actuated by RPV water level isolation
instrumentation; or
3. Penetration flow paths with isolation devices that can be closed prior
to the RPV water level being equal to the TAF by a dedicated operator
trained in the task, who is in continuous communication with the
control room, is stationed at the controls, and is capable of closing the
penetration flow path isolation device without offsite power.
c) The penetration flow paths required to be evaluated per paragraph b) are
assumed to open instantaneously and are not subsequently isolated, and
no water is assumed to be subsequently added to the RPV water
inventory;
d) No additional draining events occur; and
e) Realistic cross-sectional areas and drain rates are used.
A bounding DRAIN TIME may be used in lieu of a calculated value.
2.2.2 TS 3.3, Instrumentation
The following subsections describe the existing and proposed changes to the JAFNPP TS,
Section 3.3, "Instrumentation."
2.2.2.1 TS 3.3.5.1, "Emergency Core Cooling System (ECCS) Instrumentation"
Proposed changes to TS 3.3.5.1 include the deletion of Note 1 in Required Actions B.1, C.1,
and E.1, which states:
Only applicable in MODES 1, 2, and 3.
For TS Table 3.3.5.1-1, the applicability in Modes 4 and 5 was proposed for deletion because
the instrumentation requirements during shutdown would be consolidated into the new
TS 3.3.5.2, "Reactor Pressure Vessel (RPV) Water Inventory Control Instrumentation."
Modes 4 and 5 applicability and associated requirements would be deleted for the following
functions:
1. Core Spray (CS) System
a. Reactor Vessel Water Level - Low Low Low (Level 1)
c. Reactor Pressure - Low (Injection Permissive)
d. Core Spray Pump Start-Time Delay Relay
e. Core Spray Pump Discharge Flow- Low (Bypass)
f. Core Spray Pump Discharge Pressure - High (Bypass)
- 5 -
2. Low Pressure Coolant Injection (LPCI) System
a. Reactor Vessel Water Level - Low Low Low (Level 1)
c. Reactor Pressure - Low (Injection Permissive)
f. Low Pressure Coolant Injection Pump Start - Time Delay Relay
g. Low Pressure Coolant Injection Pump Discharge Flow - Low (Bypass)
TS Table 3.3.5.1-1 Footnote (a), which states, "When associated ECCS subsystem(s) are
required to be OPERABLE per LCO 3.5.2," would be deleted. As a result, existing
Footnotes (b), (c), and (d) would be renumbered (a), (b), and (c), respectively.
2.2.2.2 New TS 3.3.5.2, "Reactor Pressure Vessel (RPV) Water Inventory
Control Instrumentation"
The proposed new TS 3.3.5.2 would contain functions that are comprised of requirements
moved from TSs 3.3.5.1 and 3.3.6.1, as well as new requirements. The proposed new
TS 3.3.5.2 is shown below:
3.3.5.2 Reactor Pressure Vessel (RPV) Water Inventory Control
Instrumentation
LCO 3.3.5.2 The Reactor Pressure Vessel (RPV) Water Inventory Control
instrumentation for each Function in Table 3.3.5.2-1 shall be
APPLICABILITY: According to Table 3.3.5.2-1.
ACTIONS
NOTE-------------------------------------------------------
Separate Condition entry is allowed for each channel.
CONDITION REQUIRED ACTION COMPLETION TIME
A. One or more A.1 Enter the Immediately
channels Condition referenced in
inoperable. Table 3.3.5.2-1 for the
channel.
B. As required by B.1 Declare associated Immediately
Required penetration flow path{s)
Action A.1 and incapable of automatic
referenced in isolation.
Table 3.3.5.2-1.
AND
B.2 Calculate DRAIN TIME. Immediately
- 6 -
CONDITION REQUIRED ACTION COMPLETION TIME
C. As required by C. 1 Place channel in trip. 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />
Required
Action A.1 and
referenced in
Table 3.3.5.2-1.
D. As required by D.1 Restore channel to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />
Required OPERABLE status.
Action A.1 and
referenced in
Table 3.3.5.2-1.
E. Required E.1 Declare associated low Immediately
Action and pressure ECCS
associated injection/spray subsystem
Completion Time inoperable.
of Condition C or D
not met.
SURVEILLANCE REQUIREMENTS
NOTE---------------------------------------------------
Refer to Table 3.3.5.2-1 to determine which SRs apply for each ECCS Function.
SURVEILLANCE
SR 3.3.5.2.1 Perform CHANNEL CHECK.
SR 3.3.5.2.2 Perform CHANNEL
FUNCTIONAL TEST.
FREQUENCY
In accordance with the
Surveillance Frequency
Control Program
In accordance with the
Surveillance Frequency
Control Program
- 7 -
Table 3.3.5.2-1 (page 1 of 1)
Reactor Pressure Vessel {RPV} Water Inventory Control Instrumentation
APPLICABLE REQUIRED CONDITIONS
MODES OR REFERENCED
FUNCTION OTHER CHANNELS FROM SURVEILLANCE ALLOWABLE
SPECIFIED PER REQUIRED REQUIREMENTS VALUE
CONDITIONS FUNCTION ACTION A.1
1. Core Spray
System
a. Reactor 4, 5 4(a) C SR 3.3.5.2.1 s 490 psig
Pressure - SR 3.3.5.2.2
Low
(Injection
Permissive)
4,5 1 per pump D SR 3.3.5.2.1 ::: 510 gpm
b. Core Spray (a) SR 3.3.5.2.2 and
Pump S 980 gpm
Discharge
Flow- Low
(Bypass) ::: 90 psig and
4,5 1 per pump D SR 3.3.5.2.1 s 110 psig
C. Core Spray (a) SR 3.3.5.2.2
Pump
Discharge
Pressure -
High
(Bypass)
2. Low Pressure
Coolant Injection
(LPCI) System
a. Reactor 4, 5 4(a) C SR 3.3.5.2.1 s 490 psig
Pressure - SR 3.3.5.2.2
Low
(Injection
Permissive)
b. Low Pressure 4,5 1 per pump D SR 3.3.5.2.1 ::: 1040 gpm
Coolant (a) SR 3.3.5.2.2 and
Injection s 1665 gpm
Pump
Discharge
Flow- Low
(Bypass)
3. RHR System
Isolation
a. Reactor (b) 2 in one trip B SR 3.3.5.2.1 ::: 177 inches
Vessel Water system SR 3.3.5.2.2
Level - Low,
Level3
- 8 -
APPLICABLE REQUIRED CONDITIONS
MODES OR CHANNELS REFERENCED SURVEILLANCE ALLOWABLE FUNCTION OTHER PER FROM REQUIREMENTS VALUE SPECIFIED FUNCTION REQUIRED
CONDITIONS ACTION A.1
4. Reactor Water
Cleanup (RWCU)
System Isolation
a. Reactor (b) 2 in one trip B SR 3.3.5.2.1 .:".. 177 inches
Vessel Water system SR 3.3.5.2.2
Level - Low
Level3
(a) Associated with an ECCS subsystem required to be OPERABLE by LCO 3.5.2, "Reactor
Pressure Vessel (RPV) Water Inventory Control."
(b) When automatic isolation of the associated penetration flow path( s) is credited in calculating
DRAIN TIME.
2.2.2.3 TS 3.3.5.2, "Reactor Core Isolation Cooling (RCIC) System
Instrumentation"
The existing TS 3.3.5.2, "Reactor Core Isolation Cooling (RCIC) System Instrumentation
Isolation," and its subsections would be renumbered to TS 3.3.5.3 in order to maintain the TS
numbering conventions.
2.2.3 TS Section 3.5, "Emergency Core Cooling System (ECCS) and Reactor
Core Isolation Cooling (RCIC) System"
The title of JAFNPP TS Section 3.5 would be revised from "Emergency Core Cooling System
(ECCS) and Reactor Core Isolation Cooling (RCIC) System" to "Emergency Core Cooling
Systems (ECCS), Reactor Pressure Vessel (RPV) Water Inventory Control, and Reactor Core
Isolation Cooling (RCIC) System." This also would affect TSs 3.5.1 and 3.5.3 with modification
of the title at the top of the page.
- 9 -
The title of JAFNPP TS Section 3.5.2 would be revised from "ECCS - Shutdown" to "Reactor
Pressure Vessel (RPV) Water Inventory Control," and TS 3.5.2 would be revised as follows:
3.5.2 Reactor Pressure Vessel (RPV) Water Inventory Control
LCO 3.5.2 DRAIN TIME of RPV water inventory to the top of active fuel
(T AF) shall be ~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />
One low pressure ECCS injection/spray subsystem shall be
NOTE----------------------------------------
A Low Pressure Coolant Injection (LPCI) subsystem may be
considered OPERABLE during alignment and operation for decay
heat removal if capable of being manually realigned and not
otherwise inoperable.
APPLICABILITY: MODES 4 and 5
ACTIONS
CONDITION REQUIRED ACTION COMPLETION TIME
A. Required low A.1 Restore required low 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />
injection/spray injection/spray
subsystem subsystem to
inoperable. OPERABLE status.
B. Required Action and B.1 Initiate action to Immediately
associated establish a method of
Completion Time of water injection
Condition A not met. capable of operating
without offsite
electrical power.
CONDITION
C. DRAIN TIME
< 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> and
~ 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
- 10 -
REQUIRED ACTION COMPLETION TIME
C. 1 Verify secondary 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />
containment boundary
is capable of being
established in less
than the DRAIN TIME.
AND
4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />
C.2 Verify each secondary
containment
penetration flow path
is capable of being
isolated in less than
the DRAIN TIME.
AND 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />
C.3 Verify one standby
gas treatment
subsystem is capable
of being placed in
operation in less than
DRAIN TIME.
CONDITION
D. DRAIN TIME
< 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
- 11 -
REQUIRED ACTION
D. 1 ----------NOTE------------
Required ECCS
injection/spray
subsystem or
additional method of
water injection shall
be capable of
operating without
offsite electrical
power.
Initiate action to
establish an additional
method of water
injection with water
sources capable of
maintaining RPV water
level > T AF for
~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
AND
D.2 Initiate action to
establish secondary
containment
boundary.
AND
D.3 Initiate action to
isolate each
secondary
containment
penetration flow path
or verify it can be
manually isolated from
the control room.
AND
D.4 Initiate action to verify
one standby gas
treatment subsystem
is capable of being
placed in operation.
COMPLETION TIME
Immediately
Immediately
Immediately
Immediately
E.
CONDITION
Required Action and E.1
associated
Completion Time of
Condition C or D not
met.
DRAIN TIME < 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
- 12 -
REQUIRED ACTION
Initiate action to
restore DRAIN TIME
to ::::: 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
COMPLETION TIME
Immediately
The proposed TS 3.5.2 SRs would be added as shown below:
SURVEILLANCE FREQUENCY
SR 3.5.2.1 Verify DRAIN TIME ::::: 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. In accordance with
the Surveillance
Frequency Control
Program
SR 3.5.2.2 Verify, for a required low pressure coolant In accordance with
injection (LPCI) subsystem, the the Surveillance
suppression pool water level is ::::: 10.33 ft. Frequency Control
Program
SR 3.5.2.3 Verify, for a required Core Spray (CS) In accordance with
subsystem, the: the Surveillance
Frequency Control
a. Suppression pool water level is Program
- 10.33 ft; or
b. The water level in each condensate
storage tank is ::::: 324 inches
SR 3.5.2.4 Verify for the required ECCS In accordance with
injection/spray subsystem, the piping is the Surveillance
filled with water from the pump discharge Frequency Control
valve to the injection valve. Program
SR 3.5.2.5 Verify for the required ECCS In accordance with
injection/spray subsystem, each manual, the Surveillance
power operated, and automatic valve in Frequency Control
the flow path, that is not locked, sealed or Program
otherwise secured in position, is in the
correct position.
SR 3.5.2.6 Operate the required ECCS In accordance with
injection/spray subsystem through the the Surveillance
recirculation line for ::::: 10 minutes. Frequency Control
Program
- 13 -
SURVEILLANCE FREQUENCY
SR 3.5.2.7 Verify each valve credited for
automatically isolating a penetration flow
path actuates to the isolation position on
an actual or simulated isolation signal.
In accordance with
the Surveillance
Frequency
Control Program
SR 3.5.2.8 ------------------------NOTE-----------------------
Vessel injection/spray may be excluded.
Verify the required ECCS injection/spray
subsystem can be manually operated.
In accordance with
the Surveillance
Frequency Control
Program
2.2.4 Deletion of OPDRV References and Other Changes
In its license amendment request {LAR) dated October 2, 2017 (Reference 1 ), the licensee
proposed to revise existing TS requirements related to OPDRVs or "Initiate action to suspend
OPDRVs" with new requirements on RPV WIC that would protect the JAFNPP TS Safety
Limit 2.1.1.3. To remain consistent with TSTF-542, Revision 2, all references to the term
OPDRVs in the JAFNPP TSs would be deleted. The existing TS locations of these references
are summarized below:
JAFNPP LCO Location of OPDRV Reference
3.3.6.1, Primary Containment Isolation Required Action J.2, Table 3.3.6.1-1,
Instrumentation Function 6.b. and Footnote (e) (See
Below)
3.3.6.2, Secondary Containment Table 3.3.6.2-1 Footnote (a)
Isolation Instrumentation
3.3.7.1, Control Room Emergency Applicability
Ventilation Air Supply (CREVAS)
System Instrumentation
3.6.1.3, Primary Containment Isolation Required Action G.1
Valves (PCIVs)
3.6.4.1, Secondary Containment Applicability, Condition C, Required
Action C.2
3.6.4.2, Secondary Containment Applicability, Condition D, Required
Isolation Valves (SCIVs) Action D.2
3.6.4.3, Standby Gas Treatment (SGT) Applicability, Condition C, Required
System Action C.2.2, Condition E, Required
Action E.2
3. 7.3, Control Room Emergency Applicability, Condition D, Required
Ventilation Air Supply (CREVAS) Action D.2.2, Condition F, Required
System Action F.2
3.7.4, Control Room Air Conditioning Applicability, Condition D, Required
(AC) System Action D.2.2, Condition E, Required
Action E.2
- 14 -
JAFNPP LCO Location of OPDRV Reference
3.8.2, AC Sources Shutdown Required Actions A.2.3, B.3, and
3.8.5, DC Sources - Shutdown Required Action A.2.3
3.8.8, Distribution Systems-Shutdown Required Action A.2.3
For each of these TS, the applicability and/or Actions table sections would be revised to delete
references to OPDRVs and delete required actions for OPDRVs. Additionally, conforming
changes would be made by renumbering remaining required actions or in the case of
SR 3.8.2.1, to revise the title of a reference to LCO 3.5.2 to the newly proposed title, "Reactor
Pressure Vessel (RPV) Water Inventory Control."
2.2.5 JAFNPP Plant-Specific TSTF-542 TS Variations
In Section 2.2 of the LAR dated October 2, 2017 (Reference 1 ), the licensee identified several
JAFNPP plant-specific TS variations from the TS changes described in TSTF-542, Revision 2,
or the applicable parts of the NRC staff's SE. The licensee stated in the LAR that these
variations do not affect the applicability of the TSTF-542, Revision 2, or the NRC staff's SE to
the proposed license amendment. Specific details of these variations are described in the LAR.
2.2.5.1 Variation 1, Relocation of LPCI Injection Mode Notes from SRs to TS LCO
The licensee proposed to relocate JAFNPP TS notes in SRs 3.5.1.2 and 3.5.2.4 to notes in
LCOs 3.5.1 and 3.5.2. The notes permit the LPCI subsystem to be considered operable during
alignment and operation for decay heat removal (OHR) if capable of being manually realigned
and not otherwise inoperable.
2.2.5.2 Variation 2, CS and LPCI Manual Initiation Logic
There are Standard Technical Specifications (STS) SRs proposed in TSTF-542 related to
"manual initiation," that do not appear in the current JAFNPP TSs. The "manual initiation" logic
does not exist in the JAFNPP design. These functions, as well as related TSTF-542,
Revision 2, SRs 3.3.5.2.3 and 3.5.2.8, do not apply to JAFNPP.
As an alternative, the licensee proposed that TS 3.5.2 include SR 3.5.2.8 to verify that the
JAFNPP-required ECCS injection/spray subsystem can be manually operated through the
manipulation of subsystem components from the Main Control Room (MCR).
2.2.5.3 Variation 3, RWCU System Isolation Occurs at Reactor Vessel Water
Level - Low Level 3
The licensee stated in the LAR that the JAFNPP design for RWCU isolation is on Reactor
Vessel Water Level - Low (Level 3), not Reactor Vessel Water Level - Low, Low (Level 2) in the
JAFNPP design. Therefore, the licensee proposed to revise JAFNPP TS Table 3.3.5.2-1 to
reflect this plant-specific design difference.
- 15 -
2.2.5.4 Variation 4, CS Time Delay Relay Function Deleted in Modes 4 and 5
The licensee stated in the LAR that the JAFNPP TS for the CS time delay relay function does
not appear in the STS table and this function is proposed to be deleted in Modes 4 and 5 using
the same justification provided in TSTF-542 for deletion of the LPCI time delay relay.
2.2.5.5 Variation 5, CS Pump Discharge Pressure - High (Bypass) Function
The JAFNPP CS pump discharge pressure high bypass function does not appear in the STS
table. Therefore, the licensee proposed to carry this function into TS Table 3.3.5.2-1 consistent
with the justification for CS and LPCI pump discharge flow low bypass functions.
2.2.5.6 Variation 6, JAFNPP TSs Contain the Surveillance Frequency
Control Program
The JAFNPP TSs contain a TS 5.5.15, Surveillance Frequency Control Program. Therefore,
the SR frequencies for Specification 3.3.5.2 and 3.5.2 are "In accordance with the Surveillance
Frequency Control Program."
2.3 Applicable Regulatory Requirements
2.3.1 Rules
The regulation under Title 1 O of the Code of Federal Regulations ( 1 O CFR), Paragraph
50.36(a)(1 ), requires an applicant for an operating license to include in the application proposed
TSs in accordance with the requirements of 10 CFR 50.36. The applicant must also include in
the application, a "summary statement of the bases or reasons for such specifications, other
than those covering administrative controls." However per 10 CFR 50.36(a)(1 ), these TS bases
"shall not become part of the technical specifications."
The categories of items required to be in the TSs are provided in 10 CFR 50.36(c). As required
by 10 CFR 50.36( c )( 1 )(i)(A), safety limits for nuclear are limits upon important process variables
that are found to be necessary to reasonably protect the integrity of certain of the physical
barriers that guard against the uncontrolled release of radioactivity. If any safety limit is
exceeded, the reactor must be shut down. The licensee shall notify the Commission, review the
matter, and record the results of the review, including the cause of the condition and the basis
for corrective action taken to preclude recurrence. Operation must not be resumed until
authorized by the Commission.
The regulation under 10 CFR 50.36(c)(2)(i) requires that the TSs include LCOs, which are the
lowest functional capability or performance levels of equipment required for safe operation of
the facility. Per 10 CFR 50.36(c)(2)(i), when an LCO of a nuclear reactor is not met, the
licensee shall shut down the reactor or follow any remedial action permitted by the TSs until the
condition can be met.
The regulation under 10 CFR 50.36(c)(2)(ii) requires licensees to establish TS LCOs for items
meeting one or more of the listed criteria. Specifically, Criterion 4, "A structure, system, or
component which operating experience or probabilistic risk assessment has shown to be
significant to public health and safety," supports the establishment of LCOs for RPV WIC due to
insights gained via operating experience.
- 16 -
The regulation under 10 CFR 50.36(c)(3) requires TSs to include items in the category of SRs,
which are requirements relating to test, calibration, or inspection to assure that the necessary
quality of systems and components is maintained, that facility operation will be within safety
limits, and that the LCOs will be met.
Pursuant to 1 O CFR 50.90, whenever a holder of an operating license desires to amend the
license, application for an amendment must be filed with the Commission fully describing the
changes desired, and following as far as applicable, the form prescribed for original
applications. The technical information to be included in an application for an operating license
is governed in particular by 10 CFR 50.34(b).
As described in 1 O CFR 50.92(a), in determining whether an amendment to a license will be
issued to the applicant, the Commission will be guided by the considerations which govern the
issuance of initial licenses to the extent applicable and appropriate. The general considerations
that guide the Commission include, as stated in 10 CFR 50.40(a), how the TSs provide
reasonable assurance that the health and safety of the public will not be endangered. Also, to
issue an operating license, of which TSs are a part, the Commission must make the findings of
10 CFR 50.57, including the 10 CFR 50.57(a)(3)(i) finding that there is reasonable assurance
that the activities authorized by the operating license can be conducted without endangering the
health and safety of the public.
2.3.2 Guidance
The NRC staff's guidance for review of TSs is in Chapter 16, "Technical Specifications," of
NUREG-0800, Revision 3, "Standard Review Plan for the Review of Safety Analysis Reports for
Nuclear Power Plants" (SRP), March 2010 (Reference 6). As described therein, as part of the
regulatory standardization effort, the NRC staff prepared STS for each of the light-water reactor
nuclear designs.
NUREG-1433, Revision 4, "Standard Technical Specifications, General Electric BWR/4," April
2012 (Reference 7), contains the STS for BWR/4 plants and therefore is applicable to JAFNPP.
2.3.3 Conformance to Applicable Design Requirements
The construction permit for JAFNPP was issued by the Atomic Energy Commission (AEC) on
May 20, 1970. On February 20, 1971, the AEC published in the Federal Register(36 FR 3255)
a final rule that added Appendix A to 10 CFR Part 50, "General Design Criteria for Nuclear
Power Plants" (hereinafter referred to as the "final GDC"). As discussed in Chapter 16,
Appendices, Section 16.6 to the JAFNPP Final Safety Analysis Report (FSAR), JAFNPP was
evaluated against the 10 CFR 50, Appendix A, GDC for Nuclear Power Plants, effective May 21,
1971. It was concluded that JAFNPP conformed with the intent of the AEC GDC for Nuclear
Power Plants to the maximum extent possible consistent with the state of design and
construction at the time of issuance of the criteria.
The following criteria for JAFNPP are related to the evaluation of this LAR:
• Criterion 13 - Instrumentation and control. Instrumentation shall be provided to monitor
variables and systems over their anticipated ranges for normal operation, for anticipated
operational occurrences, and for accident conditions as appropriate to assure adequate
safety, including those variables and systems that can affect the fission process, the
integrity of the reactor core, the reactor coolant pressure boundary, and the containment
- 17 -
and its associated systems. Appropriate controls shall be provided to maintain these
variables and systems within prescribed operating ranges.
• Criterion 14 - Reactor coolant pressure boundary. The reactor coolant pressure
boundary shall be designed, fabricated, erected, and tested so as to have an extremely
low probability of abnormal leakage, of rapidly propagating failure, and of gross rupture.
• Criterion 30 - Quality of reactor coolant pressure boundary. Components which are part
of the reactor coolant pressure boundary shall be designed, fabricated, erected, and
tested to the highest quality standards practical. Means shall be provided for detecting
and, to the extent practical, identifying the location of the reactor coolant leakage source.
• Criterion 33 - Reactor coolant makeup. A system to supply reactor coolant makeup for
protection against small breaks in the reactor coolant pressure boundary shall be
provided. The system safety function shall be to assure that specified acceptable fuel
design limits are not exceeded as a result of reactor coolant loss due to leakage from the
reactor coolant pressure boundary and rupture of small piping or other small
components which are part of the boundary. The system shall be designed to assure
that for onsite electric power system operation (assuming offsite power is not available)
and for offsite electric power system operation (assuming onsite power is not available)
the system safety function can be accomplished using the piping, pumps, and valves
used to maintain coolant inventory during normal reactor operation.
• Criterion 35 - Emergency core cooling. A system to provide abundant emergency core
cooling shall be provided. The system safety function shall be to transfer heat from the
reactor core following any loss of reactor coolant at a rate such that ( 1) fuel and clad
damage that could interfere with continued effective core cooling is prevented and
(2) clad metal-water reaction is limited to negligible amounts.
3.0 TECHNICAL EVALUATION
Section 2.2 of this SE lists the proposed TS changes, as included in the licensee's letters dated
October 2, 2017, and January 22 and April 19, 2018 (References 1, 2, and 3, respectively), for
the licensee to adopt TSTF-542, Revision 2. The licensee states in the LAR dated October 2,
2017, that it performed a review of the information provided in approved TSTF-542, Revision 2
(Reference 4), as well as the SE provided to the TSTF group on December 20, 2016
(Reference 5). The licensee concluded that the justifications presented in TSTF-542,
Revision 2, and the SE prepared by the NRC staff are applicable to JAFNPP and justify this
amendment for the incorporation of the changes into the JAFNPP TSs. The following sections
include the NRC staff's evaluation of each of these proposed changes.
3.1 Staff Evaluation of Proposed DRAIN TIME Definition
As discussed in Section 2.2.1 of this SE, the DRAIN TIME is the time it would take the RPV
water inventory to drain from the current level to the TAF assuming the most limiting of the RPV
penetrations flow paths with the largest flow rate, or a combination of penetration flow paths that
could open due to a common mode failure, were to open.
The NRC staff reviewed the proposed DRAIN TIME definition from TSTF-542, Revision 2. For
the purpose of NRC staff considerations, the term "break" describes a pathway for water to
drain from the RPV that has not been prescribed in the "DRAIN TIME" definition in TSTF-542,
Revision 2. Based on the information furnished by the licensee, the NRC staff has determined
that the licensee is appropriately adopting the principles of DRAIN TIME, as specified in
TSTF-542, Revision 2.
The NRC staff has reasonable assurance that the licensee will include all RPV penetrations
below the TAF in the determination of DRAIN TIME as potential pathways. As part of this
evaluation, the staff reviewed requests for additional information used during the development
of TSTF-542, Revision 2, which provided examples of bounding DRAIN TIME calculations for
three examples: (1) water level at or below the RPV flange; (2) water level above the RPV
flange with fuel pool gates installed, and (3) water level above the RPV flange with fuel pool
gates removed. The DRAIN TIME is calculated by taking the water inventory above the break
and dividing by the limiting drain rate until the TAF is reached. The limiting drain rate is a
variable parameter depending on the break size and the reduction of elevation head above
break location during the drain down event. The discharge point will depend on the lowest
potential drain point for each RPV penetration flow path on a plant-specific basis. This
calculation provides a conservative approach to determining the DRAIN TIME of the RPV.
The NRC staff concluded that the licensee will use methods resulting in conservative
calculations to determine RPV DRAIN TIME, thereby, protecting the JAFNPP TS Safety
Limit 2.1.1.3, which meets the requirements of 10 CFR 50.36(c)(3). Based on these
considerations, the NRC staff has determined that the licensee's proposed addition of DRAIN
TIME definition to the JAFNPP TSs is acceptable.
3.2 Staff Evaluation of Proposed TS 3.3.5.2, "Reactor Pressure Vessel (RPV) Water Inventory Control Instrumentation"
The existing JAFNPP TS 3.3.5.2, "Reactor Core Isolation Cooling (RCIC) System
Instrumentation," would be renumbered as TS 3.3.5.3. This achieves consistency within the
TSs and is acceptable.
The purpose of the proposed new TS 3.3.5.2 regarding RPV WIC Instrumentation is to support
the requirements of new TS LCO 3.5.2, and the proposed new definition of DRAIN TIME. There
are instrumentation and controls that are required for manual pump starts or required as a
permissive or operational controls on the equipment of the systems that provide water injection
capability, certain start commands, pump protection, and isolation functions. These instruments
are required to be operable if the systems that provide water injection and isolation functions are
to be considered operable as described in Section 3.3 this SE for new TS 3.5.2. In the JAFNPP
design, 'manual initiation logic' does not exist; however, reactor operators can manually
manipulate subsystem components from the control room for injecting water. This is more
complex than the preferred simple push button switch start but can still be accomplished within
the time frames assumed in development of TSTF-542, Revision 2. This variation is evaluated
in Section 3.5.2 of this SE.
Specifically, the proposed new TS 3.3.5.2 regarding RPV WIC Instrumentation is to support the
operation of the CS and LPCI manual starts when needed as well as the system isolation of the
residual heat removal (RHR) system and the RWCU system. The equipment involved with each
of these systems is described in the evaluation of TS 3.5.2 and the Bases for LCO 3.5.2.
3.2.1 Staff Evaluation of Proposed TS 3.3.5.2 LCO and Applicability
In the LAR dated October 2, 2017 (Reference 1 ), the licensee proposed new TS 3.3.5.2 to
provide alternative instrumentation requirements to support manual initiation of the low pressure
ECCS injection/spray subsystem required in new TS 3.5.2 and automatic isolation of
penetration flow paths that may be credited in the determination of DRAIN TIME. The current
TSs contain instrumentation requirements related to OPDRVs in TS Tables 3.3.5.1-1, 3.3.6.1-1,
and 3.3.6.2-1, and TS 3.3.7.1. These requirements from TS Tables 3.3.5.1-1 and 3.3.6.1-1
would be consolidated into new TS 3.3.5.2.
The proposed LCO 3.3.5.2 would state:
The Reactor Pressure Vessel (RPV) Water Inventory Control Instrumentation for
each Function in Table 3.3.5.2-1 shall be OPERABLE.
The proposed applicability would state:
According to Table 3.3.5.2-1.
Revision 2 of TSTF-542 selected TS Table 3.3.5.2-1 to contain those instrumentation functions
needed to support manual initiation of the low pressure ECCS injection/spray subsystem
required by LCO 3.5.2 and automatic isolation of penetration flow paths that may be credited in
a calculation of DRAIN TIME. The functions in TS Table 3.3.5.2-1 are moved from existing
TS 3.3.5.1, "Emergency Core Cooling System (ECCS) Instrumentation," and TS 3.3.6.1,
"Primary Containment Isolation Instrumentation," functions that are required in Modes 4 or 5 or
during OPDRVs. Creation of TS 3.3.5.2 places these functions in a single location with
requirements appropriate to support the safety function for TS 3.5.2. As identified in
Section 2.2.5.2 of this SE, the JAFNPP design does not include a manual initiation logic for the
CS or LPCI systems. Therefore as an alternative, the licensee proposed to include an
SR 3.5.2.8 to TS 3.5.2 to verify that the required ECCS injection/spray subsystems can be
manually operated from the MCR.
The NRC staff concluded that the licensee's proposed alternative is acceptable for JAFNPP
since either CS or LPCI (or both) subsystems would be available to perform the intended
function to inject water into the RPV which meets the intent of the NRG-approved TSTF-542,
Revision 2.
3.2.2 Staff Evaluation of Proposed TS 3.3.5.2 Actions
As discussed in Section 2.2.2.2 above, the NRC staff has determined that the licensee's
proposed new TS 3.3.5.2 Actions are sufficient and necessary because when one or more
instrument channels are inoperable, the equipment and function controlled by these instruments
cannot complete the required function in the normal manner. The Actions are evaluated as
follows:
Action A would be applicable when one or more instrument channels are inoperable
from TS Table 3.3.5.2-1 and directs the licensee to immediately enter the
Condition referenced in TS Table 3.3.5.2-1 for that channel.
Action B (concerning the RHR System Isolation and RWCU System Isolation functions)
would be applicable when automatic isolation of the associated penetration flow path is
credited as a path for potential drainage in calculating DRAIN TIME. If the
instrumentation is inoperable, Required Action 8.1 directs an immediate declaration that
the associated penetration flow path(s) are incapable of automatic isolation. Required
Action B.2 requires an immediate re-calculation of DRAIN TIME, but automatic isolation
of the affected penetration flow paths cannot be credited.
Action C (concerning low reactor pressure permissive functions necessary for ECCS
subsystem manual injection valve opening) would address an event in which the
permissive is inoperable. The function must be placed in the trip condition within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
With the permissive function instrument in the trip condition, manual initiation valve
opening may now be performed using the control board hand-switches. This 1-hour
completion time is acceptable, because despite the preferred start method being
prevented, the reactor operator can take manual control of the pump and the injection
valve to inject water into the RPV and achieve the safety function in that time. The time
of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> also provides reasonable time for evaluation and placing the channel in trip.
Action D (concerning pump discharge flow bypass functions) would address actions
when the bypass is inoperable and then there is a risk that the associated ECCS pump
could overheat when the pump is operating and the associated injection valve is not fully
open. In this condition, the operator can take manual control of the pump and the
injection valves. Similar to the justification for Action C, while this is not the preferred
method, if a manual initiation function is inoperable, the CS and LPCI subsystem pumps
can be started manually and the valves can be opened manually. The 24-hour
completion time is acceptable, because the functions can be performed manually and it
allows time for the operator to evaluate and have necessary repairs completed.
Action E becomes necessary if the required actions and associated completion times of
Conditions C or D are not met. In this condition, the associated low pressure ECCS
injection/spray subsystem may be incapable of performing the intended function, and the
ECCS subsystem must be declared inoperable immediately.
These Actions direct the licensee to take appropriate actions as necessary and enter
immediately into the Conditions referenced in TS Table 3.3.5.2-1. The NRC staff determined
that these actions satisfy the requirements of 10 CFR 50.36( c)(2)(i) by providing a remedial
action permitted by the TSs until the LCO can be met. Therefore, the staff concludes that there
is reasonable assurance that the licensee will take appropriate actions during an unexpected
draining event to either prevent or mitigate RPV water level being lowered to the JAFNPP TS
Safety Limit 2.1.1.3 and, therefore, the proposed actions are acceptable.
3.2.3 Staff Evaluation of Proposed TS 3.3.5.2 Surveillance Requirements
The proposed new TS 3.3.5.2 SRs include Channel Checks and Channel Functional Tests
numbered SR 3.3.5.2.1 and SR 3.3.5.2.2, respectively. The NRC staff determined that these
tests are sufficient and adequate, because they are essential to ensure that the functions of
TS 3.3.5.2 are operable (i.e., capable of performing the specified safety function in support of
TS 3.5.2, DRAIN TIME, and the protection from a potential drain down of the RPV in Modes 4
and 5). The NRC staff determined that the proposed SRs of LCO 3.3.5.2, as described in
Section 3.3.3 of the TSTF-542 justification, satisfy 10 CFR 50.36(c)(3) by providing the specific
SRs relating to test, calibration, or inspection to assure that the necessary quality of systems
and components is maintained.
Surveillance requirement 3.3.5.2.1 would require a Channel Check and applies to all functions
in the TS Table 3.3.5.2-1. Performance of the Channel Check ensures that a gross failure of
instrumentation has not occurred. A Channel Check is normally a comparison of the parameter
indicated on one channel to a similar parameter on other related channels. A Channel Check is
significant in assuring that there is a low probability of an undetected complete channel failure
and is a key safety practice to verifying the instrumentation continues to operate properly
between each Channel Functional Test. The frequency is in accordance with the Surveillance
Frequency Control Program (SFCP), which is consistent with the existing requirements and
supports operating shift situational awareness.
Surveillance requirement 3.3.5.2.2 would require a Channel Functional Test and applies to all
functions in the TS Table 3.3.5.2-1. A Channel Functional Test is the injection of a simulated or
actual signal into the channel as close to the sensor as practicable to verify operability of all
devices in the channel required for channel operability. It would be performed on each required
channel to ensure that the entire channel will perform the intended function. The frequency
would be in accordance with the SFCP. The NRC staff has determined that this is acceptable
because it is consistent with the existing requirements for these functions and is based upon
operating experience that demonstrates channel failure is rare. In addition, this SR could be
included as part of a refueling activity, since during refueling outages, periods in Modes 4 and 5
are often 30 days or less.
In the LAR dated October 2, 2017 (Reference 1 ), the licensee originally proposed a
SR 3.3.5.2.3 to perform a logic system functional test even though Section 2.2.6 of
Attachment 1 of the LAR stated that no manual initiation logic existed at JAFNPP. See
Variation 2 of Section 3.5 of this SE for a full discussion. Additionally, no TS functions included
in the proposed TS Table 3.3.5.2-1 referenced SR 3.3.5.2.3. Because of the apparent
discrepancy, the NRC staff requested clarification via use of a request for additional information
dated March 26, 2018 (Reference 8). In its response letter dated April 19, 2018 (Reference 3),
the licensee identified the inclusion of SR 3.3.5.2.3 as an error and proposed removal of the
logic system functional test. The NRC staff accepts removal of formerly proposed SR 3.3.5.2.3
because of the reasoning in Variation 2 of Section 3.5 of this SE and the clarification provided in
Reference 3.
Revision 2 of TSTF-542 did not include SRs to verify or adjust the instrument setpoint derived
from the allowable value using a channel calibration or a surveillance to calibrate the trip unit.
Since a draining event in Mode 4 or 5 is not an analyzed accident, there is no accident analysis
on which to base the calculation of a setpoint. The purpose of the function is to allow ECCS
manual initiation or to automatically isolate a penetration flow path, but no specific RPV water
level is assumed for those actions. Therefore, the Mode 3 allowable value was chosen for use
in Modes 4 and 5 as it will perform the desired function. Calibrating the functions in Modes 4
and 5 is not necessary, as TS 3.3.5.1 and TS 3.3.6.1 continue to require the functions to be
calibrated on an established interval. Also, a draining event in Modes 4 or 5 is not an analyzed
accident and, therefore, there are no accident analysis assumptions on response time. The
NRC staff concluded this is adequate to ensure the channel responds with the required pumping
systems to inject water when needed and isolation equipment to perform when commanded.
Based on the above, the NRC staff concludes that the proposed SRs of LCO 3.3.5.2 satisfy
1 O CFR 50.36(c)(3) by providing the specific SRs relating to test, calibration, or inspection to
assure that the necessary quality of systems and components is maintained and, are, therefore,
acceptable.
3.2.4 Staff Evaluation of Proposed TS Table 3.3.5.2-1, "Reactor Pressure Vessel (RPV) Water Inventory Control Instrumentation"
In order to support the requirements of proposed TS 3.5.2, the associated instrumentation
requirements would be designated in TS Table 3.3.5.2-1. These instruments are required to be
operable if the systems that provide water injection and isolation functions are to be considered
operable as described in the NRC staff's evaluation of TS 3.5.2 (Section 3.3 of this SE).
Proposed TS Table 3.3.5.2-1 specifies the instrumentation that shall be operable for each
function in the table for Modes 4 and 5 (or other specified conditions), the required number of
channels per function, conditions referenced from Required Action A.1, SR for the functions, the
allowable value, and footnotes concerning items of the table.
Proposed TS Table 3.3.5.2-1, "Reactor Pressure Vessel (RPV) Water Inventory Control
Instrumentation," presents details on the functions required to support the equipment and
functions of TS 3.5.2. The NRC staff finds the presentation in this table to be acceptable,
because this section sufficiently discusses the purpose of the functions, the applicability, the
number of required channels, the references to the Condition to be entered by letter (e.g., A, B,
and C) if the function is inoperable, the applicable SRs, the selection of the allowable value, and
justification of differences between the existing and proposed TS functions. This RPV WIC
Instrumentation set is acceptable, because it is adequate to ensure the channels of
instrumentation respond with the required accuracy permitting pumps and associated systems
to operate to inject water when needed and isolating equipment when commanded to support
the prevention of or mitigate a potential RPV draining event.
Each of the ECCS subsystems in Modes 4 and 5 can be started by manual alignment of a small
number of components. Automatic initiation of an ECCS injection/spray subsystem may be
undesirable because it could lead to overflowing the RPV cavity, due to injection rates of
thousands of gallons per minute (gpm). Thus, there is adequate time to take manual actions
(e.g., hours versus minutes). Considering the action statements as the DRAIN TIME decreases
(the proposed TS 3.5.2, Action E, prohibits plant conditions that could result in a DRAIN TIME
less than(<) 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />), there is sufficient time for the reactor operators to take manual action to
stop the draining event and to manually start an ECCS injection/spray subsystem or the
additional method of water injection as needed. Consequently, there is no need for automatic
initiation of ECCS to respond to an unexpected draining event. This is acceptable, because a
draining event is a slow evolution when compared to a design basis LOCA assumed to occur at
a significant power level.
3.2.4.1 Staff Evaluation of Proposed TS Table 3.3.5.2-1, Functions
For the TS Table 3.3.5.2-1, Functions 1.a. and 2.a., CS and LPCI Systems, Reactor
Pressure - Low (Injection Permissive), these signals are used as permissives and protection for
these low pressure ECCS injection/spray subsystem manual initiation functions. This function
would ensure that the reactor pressure has fallen to a value below these subsystems' maximum
design pressure before permitting the operator to open the injection valves of the low pressure
ECCS subsystems. Even though the reactor pressure is expected to virtually always be below
the ECCS maximum design pumping pressure during Modes 4 and 5, the Reactor
Pressure - Low signals are required to be operable to permit manual initiation of the ECCS
equipment to inject water into the vessel, if needed. The proposed allowable value would be
s; 490 pounds per square inch gauge (psig) with four required channels per function.
- 23 -
For the TS Table 3.3.5.2-1, Functions 1.b., 2.b., and 1.c., CS and LPCI Pump Discharge
Flow - Low (Bypass), and CS Pump Discharge Pressure - High (Bypass), these minimum flow
instruments are provided to protect the associated low pressure ECCS pumps from overheating
when the pump is operating and the associated injection valve is not fully open.
Each CS pump and LPCI subsystem has one differential pressure indicating switch used to
detect the associated subsystems' flow rates. In addition, for CS, one pressure indicating
switch per pump is used to detect the associated pump's discharge pressure. The logic is
arranged such that each differential pressure indicating switch causes its associated minimum
flow valve to open. For CS both the differential pressure indicating switch and the pressure
switch must actuate to cause the valve to open. The logic will close the minimum flow valve
once the closure setpoint of the associated pressure indicating switch is exceeded.
The proposed allowable values for each of these instruments will be unchanged and moved
from TS Table 3.3.5.1-1 to the proposed TS Table 3.3.5.2-1.
For the TS Table 3.3.5.2-1, Function 3.a., RHR System Isolation, Reactor Vessel Water
Level - Low, Level 3, the function is only required to be operable when automatic isolation of the
associated penetration flow path is credited in the DRAIN TIME calculation. The number of
required instrument channels is "2 in one trip system" which retains the requirement that the two
instrument channels must be associated with the same trip system. Each trip system isolates
one of two redundant isolation valves, and only one trip system is required to be operable to
ensure that automatic isolation of one of the two isolation valves will occur on low reactor vessel
water level indication. The allowable value was chosen to be the same as the Primary
Containment Isolation Instrumentation Reactor Vessel Water Level - Low, Level 3 Allowable
Value from LCO 3.3.6.1.
In current TS Table 3.3.6.1-1, there is a footnote referenced by this function that states:
Only one trip system required in MODES 4 and 5 when RHR Shutdown Cooling
System integrity maintained.
As stated above, it is understood that only one trip system is required to be operable to ensure
automatic isolation and the concept that shutdown cooling system integrity be maintained;
therefore, this footnote is not needed and not carried forward for this function into proposed TS
Table 3.3.5.2-1.
For TS Table 3.3.5.2-1, Function 4.a., RWCU System Isolation, Reactor Vessel Water
Level - Low, Level 3, the function is only required to be operable when automatic isolation of the
associated penetration flow path is credited in the DRAIN TIME calculation. The number of
required channels is "2 in one trip system" which retains the requirement that the two instrument
channels must be part of the same trip system. Only one trip system is required to be operable
to ensure that automatic isolation of one of the two isolation valves will occur on low reactor
vessel water level. The Allowable Value was chosen to be the same as the RPS Reactor
Vessel Water Level - Low, Level 3 Allowable Value.
The NRC staff determined that the proposed new LCO 3.3.5.2 correctly specifies the lowest
functional capability or performance levels of equipment required for safe operation of the
facility. There is reasonable assurance that the required actions to be taken when the LCO is
not met can be conducted without endangering the health and safety of the public. This meets
- 24 -
the requirements of 10 CFR 50.36(c)(2)(i) and, therefore, the staff concluded that the licensee's
proposed changes to LCO 3.3.5.2 are acceptable.
3.3 Staff Evaluation of TS 3.5.2 - Reactor Pressure Vessel {RPV) Water
Inventory Control
The NRC staff reviewed the water sources that would be applicable to the proposed new
The licensee's proposed TS 3.5.2, "Reactor Pressure Vessel (RPV) Water Inventory Control,"
LCO contains two parts. The first part states that:
DRAIN TIME of RPV water inventory to the top of active fuel (TAF) shall be
- 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
The second part states that:
One low pressure ECCS injection/spray subsystem shall be OPERABLE.
The proposed applicability for TS 3.5.2 is Modes 4 and 5. Both of these conditions must be met
during operational Modes 4 and 5 to meet the proposed LCO. "One low pressure ECCS
injection/spray subsystem" would consist of either one CS subsystem or one LPCI subsystem.
At JAFNPP, a CS subsystem consists of two motor-driven pumps, piping, and valves to transfer
water from the suppression pool or condensate storage tanks to the RPV. At JAFNPP, LPCI is
one mode of operation of the RHR system and the LPCI subsystems share four common
pumps. An LPCI subsystem consists of two motor-driven pumps, piping, and valves to transfer
water from the suppression pool to the RPV.
The ECCS pumps are high-capacity pumps, with flow rates of thousands of gallons per minute.
Most RPV penetration flow paths would have a drain rate on the order of tens or hundreds of
gallons per minute. The manual initiation/start of an ECCS pump would provide the necessary
water source to counter these expected drain rates. The LPCI subsystem is to be considered
operable during alignment and operation for DHR if capable of being manually realigned and not
otherwise inoperable. Decay heat removal in Modes 4 and 5 is not affected by the proposed
change. The requirements on the number of RHR shutdown cooling subsystems that must be
operable and in operation to ensure adequate DHR from the core are unchanged. These
requirements can be found in JAFNPP TS 3.4.8, "Residual Heat Removal (RHR) Shutdown
Cooling System-Cold Shutdown," TS 3.9.7, "Residual Heat Removal (RHR)-High Water Level,"
and TS 3.9.8, "Residual Heat Removal (RHR)-Low Water Level." Based on these
considerations, the NRC staff finds that the water sources provide assurances that the lowest
functional capability required for safe operation is maintained and supports the safety limit.
The NRC staff reviewed the proposed TS 3.5.2, focusing on ensuring the fuel remains covered
with water and the changes made compared to the current TSs. The proposed TS 3.5.2
contains Conditions A through E based on either required ECCS injection/spray subsystem
operability or DRAIN TIME.
The existing TS LCO states that two ECCS injection/spray subsystems shall be operable,
whereas the proposed LCO 3.5.2 states that only one ECCS injection/spray subsystem shall be
operable. This change is reflected in Condition A. Changing from two ECCS injection/spray
subsystems to one ECCS injection/spray subsystem is satisfactory because this level of
- 25 -
redundancy is not required given the low drain rates during Modes 4 and 5. With one ECCS
injection/spray subsystem and non-safety related injection sources, defense-in-depth will be
maintained. The defense-in-depth measure is consistent with other events considered during
shutdown with no additional single failure assumed. The DRAIN TIME controls, in addition to
the required ECCS injection/spray subsystem, provide reasonable assurance that an
unexpected draining event can be prevented or mitigated before the RPV water level would be
lowered to the JAFNPP TS Safety Limit 2.1.1.3.
The proposed Modes 4 and 5 applicability of TS 3.5.2 is appropriate given that the TS
requirements on ECCS in Modes 1, 2, and 3 will be unaffected.
The proposed Condition A states that if the required ECCS injection/spray subsystem is
inoperable, it is to be restored to operable status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.
The proposed Condition B states that if Condition A is not met, a method of water injection
capable of operating without offsite electrical power should be established immediately. The
proposed Condition B provides adequate assurance of an available water source should
Condition A not be met within the 4-hour completion time.
The proposed Condition C states that for a DRAIN TIME< 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> and~ 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, to (Required
Action C. 1) verify secondary containment boundary is capable of being established in less than
the DRAIN TIME, and (Required Action C.2) verify each secondary containment penetration
flow path is capable of being isolated in less than DRAIN TIME, and (Required Action C.3) verify
one SGT subsystem is capable of being placed in operation in less than the DRAIN TIME all
with a completion time of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. The proposed Condition C provides adequate protection
should the DRAIN TIME be < 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> and ~ 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> because of the ability to establish
secondary containment, isolate additional flow paths, and have the SGT subsystem capable of
being placed in operation.
The proposed Condition D states that when DRAIN TIME < 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> to (Required Action D.1)
immediately initiate action to establish an additional method of water injection with water
sources capable of maintaining RPV water level > TAF for ~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />, (Required Action D.2)
immediately initiate action to establish secondary containment boundary, (Required Action D.3)
immediately initiate action to isolate each secondary containment penetration flow path or verify
it can be manually isolated from the control room, and (Required Action D.4) immediately initiate
action to verify one SGT subsystem is capable of being placed in operation. Additionally, there
is a note stating that required ECCS injection/spray subsystem or additional method of water
injection shall be capable of operating without offsite electrical power, which is similar to
proposed Condition B. The existing JAFNPP TS for Condition D (Required Action C.2 and
associated Completion Time not met) is similar to the proposed Condition D. The proposed
Condition D provides adequate protection should the DRAIN TIME be < 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> because of the
ability to establish additional method of water injection (without electric power), establish
secondary containment, isolate additional flow paths, and have the SGT subsystem capable of
being placed in operation.
The proposed new Condition E states that when the required action and associated completion
time of Condition C or D is not met, or the DRAIN TIME is < 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, then (Required Action E.1)
initiate action to restore DRAIN TIME to~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> immediately. The proposed Condition Eis
acceptable as it provides the necessary step to restore the DRAIN TIME to~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> should
the other conditions not be met, or if the DRAIN TIME is < 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.
- 26 -
The NRC staff evaluated the proposed changes to TS 3.5.2 and finds them acceptable based
on the actions taken to mitigate the RPV water level reaching the JAFNPP TS Safety
Limit 2.1.1.3 with the water sources available and maintaining DRAIN TIME ~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.
LCO 3.5.2 correctly specifies the lowest functional capability or performance levels of equipment
required for safe operation of the facility. The NRC staff concludes there is reasonable
assurance that the TS Required Actions to be taken when the LCO is not met can be conducted
without endangering the health and safety of the public and, therefore, they are acceptable.
3.3.1 Staff Evaluation of Proposed TS 3.5.2 Surveillance Requirements
The proposed TS 3.5.2 SRs (Section 2.2.3 of this SE) includes verification of DRAIN TIME,
verification of water levels/volumes that support ECCS injection/spray subsystems, verification
of water filled pipes to preclude water hammer events, verification of correct valves positions for
the required ECCS injection/spray subsystem, operation of the ECCS injection/spray systems
through the recirculation line, verification of valves credited for automatic isolation actuated to
the isolation position, and verification that the required ECCS injection/spray subsystem can be
manually operated. Each of the eight SRs are described below.
• SR 3.5.2.1: The DRAIN TIME would be determined or calculated, and required to be
verified to be~ 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> in accordance with the SFCP. This is a new surveillance and
would verify that the LCO for DRAIN TIME is met. Numerous indications of changes in
RPV level are available to the operator. The period of 36 hour4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />s3 is considered
reasonable to identify and initiate action to mitigate draining of reactor coolant. Changes
in RPV level would necessitate recalculation of the DRAIN TIME.
• SR 3.5.2.2: The suppression pool water level(~ 10.33 ft.) for a required LPCI
subsystem would be required to be verified to ensure pump net positive suction head
and vortex prevention is available for the LPCI injection subsystem required to be
operable by the LCO. This SR is retained from the existing SR 3.5.2.1 and would be
required to be performed in accordance with the SFCP.
• SR 3.5.2.3: The suppression pool water level(~ 10.33 ft.} or condensate storage tank
level(~ 324 inches) for a required CS subsystem would be required to be verified to
ensure pump net positive suction head and vortex prevention is available for the CS
subsystem required to be operable by the LCO. This SR is retained from the existing
SR 3.5.2.2 and would be required to be performed in accordance with the SFCP. The
note prior to part b is removed due to the removal of all OPDRV references.
• SR 3.5.2.4: The SR to verify the ECCS injection/spray subsystem piping is sufficiently
filled with water would be retained from the existing SR 3.5.2.3. The proposed change
would update the SR to reflect the change to LCO 3.5.2, which would require, in part,
one low pressure ECCS injection/spray subsystem to be operable instead of two. The
wording would change from "Verify, for each required ECCS ... " to "Verify, for the
required ECCS ... " This change clarifies the requirement to maintain consistency with the
proposed LCO. This SR would be performed in accordance with the SFCP.
• SR 3.5.2.5: The SR to verify the correct alignment for manual, power operated, and
automatic valves in the required ECCS subsystem flow p~th would be retained from the
3 Typically equivalent to three operator shifts.
- 27 -
existing SR 3.5.2.4. Again similar to proposed SR 3.5.2.4, the proposed SR wording,
"Verify for the required ECCS injection/spray subsystem each manual. .. " would replace
"Verify each required ECCS injection/spray subsystem manual ... " SR 3.5.2.5 would
provide assurance that the proper flow path will be available for ECCS operation to
support TS 3.5.2. This SR would not apply to valves that are locked, sealed, or
otherwise secured in position, since these valves would be verified to be in the correct
position prior to locking, sealing, or securing. The note just prior to the SR allowing one
LPCI subsystem to be considered operable during alignment and operation for OHR is
relocated to the LCO. This is an administrative deviation further discussed in
Section 3.5 of this SE (Variation 1 ). This SR would be performed in accordance with the
SFCP.
• SR 3.5.2.6: The required ECCS injection/spray subsystem would be required to be
operated through its recirculation line for~ 10 minutes in accordance with the SFCP.
This would demonstrate that the subsystem is capable for operation to support TS 3.5.2
and is retained from SR 3.5.2.5.
• SR 3.5.2. 7: Verification that each valve credited for automatically isolating a penetration
flow path actuates to the isolation position on an actual or simulated RPV water level
isolation signal would be required to prevent RPV water inventory from dropping below
the JAFNPP TS Safety Limit 2.1.1.3 should an unexpected draining event occur. This
SR would be performed in accordance with the SFCP and is new for JAFNPP.
• SR 3.5.2.8: This SR would state, "Verify the required ECCS injection/spray subsystem
can be manually operated." This SR is retained from existing JAFNPP SR 3.5.2.6. It
demonstrates that the required CS or LPCI subsystem could be manually operated
through the manipulation of subsystem components in the MCR to provide additional
RPV water inventory, if needed. By operating the associated pump and valve switches
which operates all active components, water flow can be demonstrated by recirculation
through the test line. Vessel injection/spray may be excluded from the SR, per the
accompanying note. Previously, JAFNPP relied only on automatic initiation of ECCS
subsystems and manual actuation, while possible, this was not discussed in the TSs.
Section 3. 5 of this SE, evaluation of Variation 2, contains amplifying information. As
further discussed in Section 3.3 of this SE, manual initiation is sufficient to counter
expected drain rates within the DRAIN TIME. This SR would be performed in
accordance with the SFCP.
The NRC staff evaluated each of these proposed SRs associated with the new LCO 3.5.2 and
determined that they are appropriate for ensuring the operability of the equipment and
instrumentation specified in LCO 3.5.2. That traveler is TSTF-523, "Generic Letter 2008-01,
Managing Gas Accumulation," which was approved by the NRC on January 14, 2014. The
TSTF-523 traveler affected existing SR 3.5.2.3, which verifies that the ECCS piping is full of
water, and existing SR 3.5.2.4, which verified that the valves are in correct position.
Furthermore, the NRC staff concluded that each of the proposed SRs are acceptable since they
meet the requirements of 10 CFR 50.36(c)(2)(ii) regarding insights gained via operating
experience and 10 CFR 50.36( c)(3) for SRs by ensuring that the necessary quality of systems
and components is maintained.
3.4 Staff Evaluation of TS Table 3.3.5.1, Emergency Core Cooling System Instrumentation
Limiting Condition for Operation 3.3.5.1 currently states that, "The ECCS instrumentation for
each Function in Table 3.3.5.1-1 shall be OPERABLE," with the applicability as stated in the
table. TS Table 3.3.5.1-1, "Emergency Core Cooling System Instrumentation," currently
contains requirements for function operability during Modes 4 and 5 when the associated ECCS
subsystem(s) are required to be operable per LCO 3.5.2, "ECCS - Shutdown." Conforming
changes were proposed for the Actions table of LCO 3.3.5.1 as well.
For the following functions in TS Table 3.3.5.1-1, Mode 4 and 5 requirements would be deleted:
1. Core Spray System:
(a) Reactor Vessel Water Level - Low Low Low (Level 1)
(c) Reactor Pressure - Low (Injection Permissive)
( d) Core Spray Pump Start - Time Delay Relay
(e) Core Spray Pump Discharge Flow - Low (Bypass)
(f) Core Spray Pump Discharge Pressure - High (Bypass)
2. Low Pressure Coolant Injection:
(a) Reactor Vessel Water Level - Low Low Low (Level 1)
(c) Reactor Pressure - Low (Injection Permissive)
(f) Low Pressure Coolant Injection Pump Start - Time Delay Relay
(g) Low Pressure Coolant Injection Pump Discharge Flow - Low (Bypass)
The Mode 4 and 5 requirements for the nine functions above would be deleted to support the
consolidation of RPV WIC Instrumentation requirements into the proposed new TS 3.3.5.2. The
requirements for Functions 1.c., 1.e., 1.f., 2.c., and 2.g., would be moved to proposed new TS
Table 3.3.5.2-1 as discussed in Section 3.2.4.1 of this SE.
For the other TS Table 3.3.5.1-1, Functions, 1.a., 1.d., 2.a., and 2.f., the Mode 4 and 5
requirements would not be retained. The JAFNPP TSs currently requires automatic initiation of
ECCS pumps on low Reactor Vessel water level. Functions 1.a. and 2.a., provide signals that
automatically initiate the associated CS or LPCI pumps. Functions 1.d. and 2.f., are time delay
relay functions that prevent overloading of the power source during an automatic initiation.
However, as stated previously in this SE in Modes 4 and 5, automatic initiation of ECCS pumps
could result in overfilling the refueling cavity or water flowing into the main steam lines,
potentially damaging plant equipment. The NRC staff finds the deletion of TS
Table 3.3.5.1-1, Functions 1.a. and 2.a., to be acceptable because manual ECCS initiation is
preferred over automatic initiation during Modes 4 and 5, and the operator would be able to use
the most appropriately sized pumps if needed to mitigate a draining event.
The NRC staff finds the deletion of TS Table 3.3.5.1-1, Functions 1.d. and 2.f., to be acceptable
for the CS and LPCI pump start time delay relays because the staggered starting of ECCS
pumps is unnecessary for manual ECCS operation. Unlike automatic starts, which initiate all of
the ECCS pumps to start requiring the delay logic, the operator will control which ECCS pumps
to start, one at a time as needed for water inventory control.
- 29 -
3.5 Staff Evaluation of the Proposed Technical Variations
The licensee proposed the following variations from the TS changes described in TSTF-542 or
the applicable parts of the NRC staff's SE for TSTF-542 (Reference 5). The licensee stated in
the LAR that these variations do not affect the applicability of TSTF-542, Revision 2, or the NRC
staff's SE for TSTF-542 to the proposed license amendment. The NRC staff evaluated each
variation below.
3.5.1 Variation 1, Relocation of LPCI Injection Mode Notes From SRs to LCO
The licensee proposed to relocate JAFNPP TS notes in SRs 3.5.1.2 and 3.5.2.4 to TS notes in
LCOs 3.5.1 and 3.5.2. In both cases, the notes permit the LPCI subsystem to be considered
operable during alignment and operation if capable of being manually realigned and not
otherwise inoperable.
The NRC staff finds that the added notes to LCOs 3.5.1 and 3.5.2 associated with the LPCI
subsystem are appropriate and consistent with TSTF-542, Revision 2, which places this note
within the LCO. Without the note, the associated RHR pump would be declared inoperable,
which would be contrary to the intent of the existing notes for SRs 3.5.1.2 and 3.5.2.4 which
allow the LPCI subsystem to be operable when aligned for OHR. Therefore, the NRC staff
concludes that Variation 1 is acceptable.
3.5.2 Variation 2, CS and LPCI Manual Initiation Logic
There are STS SRs proposed in TSTF-542, Revision 2, related to "manual initiation," that do not
appear in the current JAFNPP TSs. The licensee stated in the LAR that the "manual initiation"
logic does not exist in the JAFNPP design. Since this is the case, these functions as well as
related TSTF-542, Revision 2, SRs 3.3.5.2.3 and 3.5.2.8 do not apply to JAFNPP.
As an alternative, the licensee proposed that TS 3.5.2 include an SR 3.5.2.8 to verify that the
JAFNPP-required ECCS injection/spray subsystem can be manually operated through the
manipulation of subsystem components from the MCR.
Additionally, as stated by the licensee in the LAR dated October 2, 2017:
The manual operation of the required ECCS injection/spray subsystem for the
control of reactor cavity or RPV inventory is a relatively simple evolution and
involves the manipulation of a small number of components. These subsystem
alignments can be performed by licensed operators from the Main Control Room.
This alternative is justified by the fact that a draining event is a slow evolution
when compared to a design basis loss of coolant accident, which is assumed to
occur at full power, and thus, there is adequate time to take manual actions
(i.e., hours versus minutes). Adequate time to take action is assured since the
proposed TS 3.5.2, Condition E, prohibits plant conditions that result in drain
times that are less than one hour. Therefore, there is sufficient time for the
licensed operators to take manual action to stop an unanticipated draining event,
and to manually start an ECCS injection/spray subsystem or the additional
method of water injection.
- 30 -
Since the ECCS injection/spray subsystem can be placed in service using
manual means in a short period of time (i.e., within the time frames assumed in
the development of TSTF-542), using controls and indications that are readily
available in the Main Control Room, manual operation of the required subsystem
would be an equivalent alternative to system initiation via manual initiation logic.
Current SR 3.5.1.6 and SR 3.5.2.4 manually operate the ECCS injection/spray
pumps to verify each required ECCS injection/spray pump develops the specified
flow rate against a system head corresponding to the specified reactor pressure
at a frequency specified by the lnservice Testing (1ST} Program. The 1ST
Program requires the ECCS injection/spray subsystems motor operated injection
valves, minimum flow valves and test flow path valves (with the exception of the
CS test flow path valves) be cycled to demonstrate operability and compliance
with 1ST stroke time requirements at a frequency specified by the 1ST Program.
The CS test flow path valves are part of the 1ST Program but do not have stroke
time requirements. The CS valves are cycled for position indication verification
only.
The manual operation of the ECCS injection/spray subsystem to demonstrate
operability required by the proposed SR 3.5.2. 7 is equivalent to the testing that is
presently required to be performed on the ECCS injection/spray subsystems.
The NRC staff reviewed the licensee's proposed alternative and determined that although
JAFNPP does not have the capability to start an ECCS subsystem with a single push button,
the components that provide ECCS injection/spray into the RPV can be started from the MCR,
as required, to support Modes 4 and 5 operations. The manipulation of low pressure ECCS
subsystem components from the MCR would be verified in accordance with new SR 3.5.2.8.
This SR verifies that the required CS or LPCI subsystem (including associated pump switches,
and valves) can be manually operated to provide additional RPV water inventory, if needed.
Therefore, the NRC staff concludes that Variation 2 is acceptable.
3.5.3 Variation 3, RWCU System Isolation Occurs at Reactor Vessel Water
Level - Low Level 3
The licensee stated in the LAR that the JAFNPP design for RWCU isolation is on Reactor
Vessel Water Level - Low (Level 3), not Reactor Vessel Water Level - Low, Low (Level 2) as in
STS. The licensee states in the LAR:
The intent of the TSTF is to change the applicability of this function, but does not
change the setpoint or allowable value. This variation is technical however is
consistent with the intent of TSTF 542.
This variation clarifies the JAFNPP design differences when compared to TSTF-542,
Revision 2, concerning the requirements for RWCU isolation. The NRC staff concludes that
Variation 3 is acceptable because the JAFNPP function proposed for RWCU system isolation is
appropriate to meet the intent of TSTF-542, Revision 2.
3.5.4 Variation 4, CS Time Delay Relay Function Deleted in Modes 4 and 5
The licensee stated in the LAR that the JAFNPP TS for the CS time delay relay function
(Function 1.d. of TS Table 3.3.5.1-1) does not appear in the STS table and this function is
- 31 -
proposed to be deleted in Modes 4 and 5 using the same justification provided in the TSTF for
deletion of the LPCI time delay relay function (Function 2.f. of TS Table 3.3.5.1-1 ). The TSTF
discussion in part mentions that the time delay relay is part of the automatic initiation system
which will not be needed in Modes 4 and 5 because manual manipulation of the necessary
components for CS subsystem initiation will be used from the control room to provide make-up
water to the RPV in a drain down event.
The NRC staff finds that electrical emergency bus staggering is not necessary for manual
operation. This function can be removed from the TS because the required ECCS subsystem is
proposed to be started by manual operation. Therefore, NRC staff concludes that Variation 4 is
acceptable.
3.5.5 Variation 5, CS Pump Discharge Pressure - High (Bypass) Function
The JAFNPP CS pump discharge pressure high bypass function (Function 1.f. of TS
Table 3.3.5.1-1) does not appear in the STS table. The licensee proposed to carry this function
into proposed TS Table 3.3.5.2-1 consistent with the justification for CS and LPCI pump
discharge flow low bypass functions.
The licensee explains in Section 2.2.7 of the LAR dated October 2, 2017:
JAFNPP TS Table 3.3.3.5.1-1 contains Function 1.f, "Core Spray Pump
Discharge Pressure - High (Bypass)", that does not appear in the STS table.
The Function is required to be operable in Modes 1, 2, 3, 4 and 5. The
Function is required for protection of the low pressure ECCS pump from
overheating when the associated injection valve is not fully open, similar to STS
Function 1.d and 2.g, "Core Spray and Low Pressure Coolant Injection Pump
Discharge Flow- Low (Bypass)". Modes 4 and 5 of JAFNPP TS Function 1.f are
being moved to the new TS 3.3.5.2 as Function 1.c. Justification for this move is
consistent with the justification provided in TSTF-542 Section 3.4.2 for STS
Functions 1.d and 2.g from TS Table 3.3.5.1-1.
The NRC staff reviewed the proposed change and concludes that the inclusion of Function 1.c.
in TS Table 3.3.5.2-1 in addition to Function 1.b. is consistent with the requirements described
in TSTF-542 Section 3.3.4.2 regarding ECCS pump minimum flow instrumentation. Therefore,
the NRC staff concludes that Variation 5 is acceptable.
3.6 Staff Evaluation of Proposed Deletion of Reference to OPDRVS
(incl. Related Requirements
Section 2.2.4 of this SE lists the numerous OPDRVs references located in the JAFNPP TSs
where the licensee proposed deletion of phrases used for controls during OPDRVs from the
various TS elements.
The proposed changes remove the following from the current JAFNPP TS: the term "operations
with a potential for draining the reactor vessel," the acronym "OPDRVs," and related concepts
such as "RHR Shutdown Cooling System integrity maintained," and Required Actions to
"suspend OPDRVs." The TS OPDRV requirements have existed for many years, but there is no
clearly stated description of the event that is being prevented or mitigated. However, from the
existing TS requirements, one can infer the postulated event that forms the basis of the existing
TS.
The current JAFNPP TSs contain instrumentation requirements related to OPDRVs in four TSs;
three of them, which have the OPDRVs phrases described above, and TS 3.3.5.1. The
proposed TS 3.3.5.2 consolidates the instrumentation requirements into a single location to
simplify the presentation and provide requirements consistent with TS 3.5.2. The remaining
TSs with OPDRVs requirements are for containment, containment isolation valves, SGT
system, control room habitability, temperature control, and electrical sources. Each of these
systems' requirements during OPDRVs were proposed for consolidation into new TS 3.5.2 for
RPV WIC, based on the appropriate plant conditions and calculated DRAIN TIME.
The NRC staff has determined that the deletion of OPDRVs references, along with the
corresponding editorial changes, are appropriate because the proposed TSs governing RPV
WIC and the associated instrumentation, TSs 3.5.2 and 3.3.5.2, respectively, are a clarified and
simplified alternative set of controls for ensuring RPV water level is maintained above the
JAFNPP TS Safety Limit 2.1.1.3.
3.7 Staff Evaluation of TS 3.10, Special Operations and TSTF 484, "Use of TS 3.10.1 for Scram Time Testing activities"
The current JAFNPP TS LCO 3.10.1, "lnservice Leak and Hydrostatic Testing Operation,"
allows performance of an inservice leak or hydrostatic test with the average reactor coolant
temperature greater than 212 °F, while considering operational conditions to still be in Mode 4,
provided certain secondary containment and SGT system LCOs were met.
The licensee's adoption of TSTF-484 (Reference 9) revised this LCO to expand its scope to
include operations where RCS temperature exceeds 212 °F: (1) as a consequence of
maintaining adequate reactor pressure for an inservice leak or hydrostatic test, or (2) as a
consequence of maintaining adequate reactor pressure for control rod scram time testing
initiated in conjunction with an inservice leak or hydrostatic test.
When the NRC approved LCO 3.10.1 and TSTF-484 for JAFNPP, the staff stated, in part, that
"two low-pressure emergency core cooling systems (ECCS) injection/spray [i.e., CS or LPCI]
subsystems are required to be operable in Mode 4 by TS 3.5.2, ECCS-Shutdown"; however, per
the new LCO 3.5.2 adopted as part of TSTF-542, Revision 2, only one low pressure ECCS
injection/spray subsystem would be required to be operable in Mode 4.
The NRC staff determined that changing from two ECCS injection/spray subsystems to one
ECCS injection/spray subsystem is acceptable because this level of redundancy is not required,
even during application of LCO 3.10.1. When the licensee applies LCO 3.10.1 at the end of a
refueling outage, an exceptionally large volume of water is present in the reactor vessel since
the vessel is nearly water solid. There is much more water in the reactor vessel than is present
during power operation and more than that present during most of an outage. Small leaks from
the RCS would be detected by inspections before a significant loss of inventory occurred. In the
event of a large RCS leak, the RPV would rapidly depressurize and allow operation of the low
pressure ECCS. At low decay heat values, and near Mode 4 conditions, the stored energy in
the reactor core will be very low. Therefore, the reasoning that operators would have time to
respond with manual actions to start any ECCS pumps and properly align valves for injection
from the control room remains valid.
As previously stated in Section 3.3 of this SE, with one ECCS injection/spray subsystem and
non-safety related injection sources, defense-in-depth will be maintained. The defense-in-depth
measure is consistent with other events considered during shutdown with no additional single
failure assumed. The DRAIN TIME controls, in addition to the required ECCS injection/spray
subsystem, provide reasonable assurance that an unexpected draining event can be prevented
or mitigated before the RPV water levelwould be lowered to the TAF.
After considering the reasoning presented elsewhere in this SE for TSTF-542, Revision 2, and
after additional review of the SE for JAFNPP TS 3.10.1 and TSTF-484, the NRC staff
determined that LCOs 3.3.5.2 and 3.5.2 adopted as part of TSTF-542, Revision 2, are
satisfactory and will therefore be acceptable even during application of LCO 3.10.1.
Proposed Changes to the TS Table of Contents
In the LAR, the licensee proposed administrative changes to the table of contents (TOC) to
reflect the above TS changes. These changes are administrative and do not affect the
applicability of TSTF 542, Revision 2, to the JAFNPP TSs. In addition, the proposed changes
do not change any requirements in the JAFNPP TS. Therefore, the NRC staff concludes that
these changes are acceptable.
3.8 Technical Conclusion
The JAFNPP TS Safety Limit 2.1.1.3 requires that the RPV water level shall be greater than the
TAF. Maintaining RPV water level above the TAF ensures that the fuel cladding fission product
barrier is protected during shutdown conditions. The proposed changes to the TS establish new
LCO requirements that address the preventive and mitigative equipment and associated
instrumentation that provide an alternative means to support the JAFNPP TS Safety
Limit 2.1.1.3 during Mode 4 and 5 operations.
During operation in Modes 4 and 5, the reactor coolant system is at a low operating temperature
(:S 212 °F) and is depressurized. An event involving a loss of inventory while in the shutdown
condition does not exceed the capacity of one ECCS subsystem. The accident that is
postulated to occur during shutdown conditions, the fuel handling accident, does not involve a
loss of inventory. Therefore, the equipment and instrumentation associated with the reactor
vessel water inventory control TS do not provide detection or mitigation related to this design
basis accident.
The proposed TS LCO 3.5.2 contains requirements for operability of one ECCS subsystem
along with requirements to maintain a sufficiently long DRAIN TIME so that plant operators
would have time to diagnose and mitigate an unplanned draining event. The NRC staff has
determined that LCOs 3.5.2 and 3.3.5.2 provide for the lowest functional capability or
performance levels of equipment required for safe operation of the facility, and therefore, meet
the LCO requirements of 10 CFR 50.36(c)(2)(i).
Additionally, the proposed TS LCOs 3.5.2 and 3.3.5.2 provide remedial actions to be taken in
the event the LCO is not satisfied and, therefore, meeting the requirements of
10 CFR 50.36(c)(2)(i). The NRC staff has determined that the remedial actions provide
reasonable assurance that an unexpected draining event can be prevented or mitigated before
the RPV water level would be lowered to the TAF.
The NRC staff evaluated the proposed DRAIN TIME definition, TS 3.5.2, which contains the
requirements for RPV WIC, and TS 3.3.5.2, which contains the requirements for instrumentation
necessary to support TS 3.5.2. Based on the considerations discussed above, the NRC staff
concludes that the proposed revisions are acceptable because they consolidate and clarify the
RPV WIC requirements, which meet 10 CFR 50.36(c)(2)(ii) Criterion 4 to establish LCOs for
structures, systems, or components significant to public health and safety as evidenced by
operating experience.
The licensee proposed to delete OPDRVs references from JAFNPP TS elements. The NRC
staff reviewed the proposed changes and determined that the deletion of OPDRVs references,
along with the corresponding editorial changes, are appropriate because the proposed TSs
governing RPV WIC and the associated instrumentation, TSs 3.5.2 and 3.3.5.2, respectively,
are a clarified and simplified alternative set of controls for ensuring that RPV water level is
maintained above the JAFNPP TS Safety Limit 2.1.1.3.
The NRC staff reviewed the SRs associated with the new LCOs 3.5.2 and 3.3.5.2. The NRC
staff has determined that the proposed TS 3.5.2 SRs are acceptable since they support DRAIN
TIME requirements, assure that water inventory is available for ECCS injection/spray subsystem
RPV injection and pump performance, ECCS injection/spray subsystem are adequately filled,
the subsystems have verified valve positions to support RPV injection, verified pumps provide
adequate flow to support DRAIN TIME and RPV injection, verification of automatic isolation, and
ECCS injection/spray subsystems can be manually operated to inject. The NRC staff finds that
the two SRs proposed for TS 3.3.5.2 are sufficient and adequate, because they are essential to
ensure that the functions are capable of performing their specified safety functions in support of
TS 3.5.2, DRAIN TIME, and the protection from a potential drain down of the RPV in Modes 4
and 5. Therefore, the NRC staff concludes that the proposed SRs satisfy 10 CFR 50.36(c)(3).
The NRC staff evaluated the proposed changes against JAFNPP's applicable design
requirements listed in Section 2.3.3 of this SE. The NRC staff finds that the proposed changes
for Mode 4 and 5 operations related to the new DRAIN TIME definition and the removal of
OPDRVs references are consistent with the GDCs in that the JAFNPP design requirements are
maintained for instrumentation, reactor coolant leakage detection, the reactor coolant pressure
boundary, and reactor coolant makeup.
The regulation at 10 CFR 50.36(a)(1) states that a summary statement of the bases or reasons
for such specifications, other than those covering administrative controls, shall also be included
in the application, but shall not become part of the TSs. In accordance with this requirement,
the licensee provided TS Bases changes in Attachment 3 of the LAR dated October 2, 2017.
The NRC staff concluded that the TS Bases changes provided describe the basis for the
affected TS and follow the Final Policy Statement on Technical Specifications Improvements for
Nuclear Power Reactors (58 FR 39132; July 22, 1993).
Additionally, the proposed TS changes were reviewed for technical clarity and consistency with
the existing JAFNPP requirements for customary terminology and formatting. The NRC staff
found that the proposed changes were consistent with TSTF-542, Revision 2, and Chapter 16 of
the SRP.
4.0 STATE CONSULTATION
In accordance with the Commission's regulations, the appropriate official for the State of New
York was notified of the NRC's proposed issuance of the amendment on August 10, 2018. The
State official had no comments.
5.0 ENVIRONMENTAL CONSIDERATION
The amendment changes requirements with respect to the installation or use of facility
components located within the restricted area as defined in 10 CFR Part 20 and changes SRs.
The NRC staff has determined that the amendment involves no significant increase in the
amounts, and no significant change in the types, of any effluents that may be released offsite,
and that there is no significant increase in individual or cumulative occupational radiation
exposure. The Commission has previously issued a proposed finding that the amendment
involves no significant hazards consideration (82 FR 55406; November 21, 2017), and there has
been no public comment on such finding. Accordingly, the amendment meets the eligibility
criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b),
no environmental impact statement or environmental assessment need be prepared in
connection with the issuance of the amendment.
6.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there
is reasonable assurance that the health and safety of the public will not be endangered by
operation in the proposed manner, (2) there is reasonable assurance that such activities will be
conducted in compliance with the Commission's regulations, and (3) the issuance of the
amendment will not be inimical to the common defense and security or to the health and safety
of the public.
7.0 REFERENCES
1. Barstow, James, Exelon Generation Company, LLC, letter to U.S. Nuclear Regulatory
Commission, "Application to Revise Technical Specifications to Adopt [Technical
Specifications Task Force] TSTF-542, 'Reactor Pressure Vessel Water Inventory
Control,' Revision 2," dated October 2, 2017 (Agencywide Documents Access and
Management System (ADAMS) Accession No. ML 17275A520).
2. Gudger, David T., Exelon Generation Company, LLC, letter to U.S. Nuclear Regulatory
Commission, "Supplemental Response Concerning License Amendment Request to
Revise Technical Specifications to Adopt TSTF-542, 'Reactor Pressure Vessel Water
Inventory Control,' Revision 2," dated January 22, 2018 (ADAMS Accession
No. ML 18022A829).
3. Gudger, David T., Exelon Generation Company, LLC, letter to U.S. Nuclear Regulatory
Commission, "Response to Request for Additional Information Application to Revise
Technical Specifications to Adopt TSTF-542, 'Reactor Pressure Vessel Water Inventory
Control,' Revision 2," dated April 19, 2018 (ADAMS Accession No. ML 18109A371).
4. Technical Specifications Task Force letter to U.S. Nuclear Regulatory Commission,
"Response to NRC Request for Additional Information Regarding TSTF-542, Revision 1,
'Reactor Pressure Vessel Water Inventory Control' and Submittal of Revision 2," dated
March 14, 2016 (ADAMS Accession No. ML 16074A448).
5. Klein, Alexander, U.S. Nuclear Regulatory Commission, letter to Technical
Specifications Task Force, "Final Safety Evaluation of Technical Specifications Task
Force Traveler TSTF-542, Revision 2, 'Reactor Pressure Vessel Water Inventory
Control' (TAC No. MF3487)," dated December 20, 2016 (ADAMS Accession
No. ML 16343B008).
6. U.S. Nuclear Regulatory Commission, NUREG-0800, Revision 3, "Standard Review
Plan for the Review of Safety Analysis Reports for Nuclear Power Plants," Chapter 16.0,
"Technical Specifications," March 2010 (ADAMS Accession No. ML 100351425).
7. Haskell II, Russell, U.S. Nuclear Regulatory Commission, electronic mail to Christian
Williams, Exelon Generation Company, LLC, "James A. FitzPatrick Nuclear Power Plant,
Unit 1 - Request for Information to Adopt Traveler TSTF-542, 'Reactor Pressure Vessel
Water Inventory Control' (EPID: L-2017-LLA-0311 )," dated March 26, 2018 (ADAMS
Accession No. ML 18085A692).
8. U.S. Nuclear Regulatory Commission, NUREG-1433, Revision 4.0, "Standard Technical
Specifications, General Electric BWR/4," April 2012 (ADAMS Accession
No. ML 12104A192).
9. Beska, John P., U.S. Nuclear Regulatory Commission, letter to Michael Kansler, Entergy
Nuclear Operations, Inc., "James A. FitzPatrick Nuclear Power Plant - Issuance of
Amendment Re: Technical Specification 3.10.1, lnservice Leak and Hydrostatic Testing
Operation, Consistent with Technical Specifications Task Force Traveler-484," dated
June 21, 2007 (ADAMS Accession No. ML071550079).
Principal Contributors: Pete Snyder, NRR
Daniel Warner, NRR
Date of issuance: August 2 4 , 2 o 18