AO 50-313/74-01:on 740526,emergency Diesel Generator K4B Synchronized Through Breaker 152-408 & Tripped by Actuation of anti-motoring Relay.Caused by Incorrect tolerances.Anti- Motoring Relay Holding Coil Setting on K4B Adjusted