Proposed Tech Specs Re Limiting Conditions for Operation & Surveillance Requirements for Steam Generator Stop Valves & ESF Response Times
ML17328A717
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 05/14/1990
From:
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML17328A716 List:
References
NUDOCS 9005220066
Download: ML17328A717 (8)


Text

ATTACHMENT 2 TO AEP:NRC:1123 PROPOSED REVISED TECHNICAL SPECIFICATION PAGES I I I 4>>ll" g!f 5\,I lt)I~PLANT SYSTEMS STEAM GENERATOR STOP VALVES LIMITING CONDITION FOR OPERATION 3.7.1.5 Each steam generator stop valve shall be OPERABLE'PPLICABILITY:

MODES 1, 2 and 3.ACTION: MODE 1-With one steam generator stop valve inoperable but open, POWER OPERATION may continue provided the inoperable valve is restored to OPERABLE status within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />;otherwise, reduce power to less than or equal to 5 percent of RATED THERMAL POWER within the next 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.MODES 2-With one steam generator stop valve inoperable, subsequent and 3 operation in MODES 2 or 3 may proceed provided: a.The stop valve is maintained closed.b.The provisions of Specification 3.0.4 are not applicable.

Otherwise, be in HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.SURVEILLANCE RE UIREMENTS 4.7.1.5.1 Each steam generator stop valve shall be demonstrated OPERABLE by verifying full closure within 8 seconds when tested pursuant to Specification 4.0.5.4.7.1.5.2 The provisions of Specification 4.0.4 are not applicable for entry into MODE 3.4.7.'1.5.3 The provisions of Specification 4.0.4 are not applicable for entry into MODE 2 when performing PHYSICS TESTS at the beginning of a cycle provided the steam generator stop valves are maintained closed.COOK NUCLEAR PLANT-UNIT 2 3/4 7-10 AMENDMENT NO~

I'l Y I TABLE 3.3-5 Continued ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS 3.Pressurizer Pressure-Low a.b.C.d.e.Safety Injection (ECCS)Reactor Trip (from SI)Feedwater Isolation Containment Isolation-Phase"A" Containment Purge and Exhaust Isolation Motor Driven Auxiliary Feedwater Pumps E Essential Service Water System Less than or equal to Less than or equal to Less than or equal to Less than or equal to 24.0*/12.0¹ 2.0 8.0 18.0¹Not Applicable Less than or equal to 60.0 Less than or equal to 48.0*/13.0¹ 4.Differential Pressure Between Steam Lines-Hi h a..b.C.d.e.Safety Injection (ECCS)Reactor Trip (from SI)Feedwater Isolation Containment Isolation-Phase"A" Containment Purge and Exhaust Isolation Motor Driven Auxiliary Feedwater Pumps Essential Service Water System Less than or equal to Less than or equal to Less than or equal to Less than or equal to 12.0¹/24.0¹¹ 2.0 8.0 18.0¹/28.0¹¹ Not Applicable Less than or equal to 60..0 Less than or equal to 13.0¹/48.0¹¹ 5.Steam Flow in Two Steam Lines-Hi h Coincident with Tav--Low-Low a.b.C.d.e.g.h.Safety Injection (ECCS)Reactor Trip (from SI)Feedwater Isolation Containment Isolation-Phase"A" Containment Purge and Exhaust Isolation Auxiliary Feedwater Pumps Essential Service Water System Steam Line Isolation Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Less than or equal to 13.0 COOK NUCLEAR PLANT-UNIT 2 3/4 3-27 AMENDMENT NO~

)I<J I>TABLE 3.3-5 Continued ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS 6.Steam Line Pressure--Low a.b.C.d.e.g h.Safety Injection (ECCS)Reactor Trip (from SI)Feedwater Isolation Containment Isolation-Phase"A" Containment Purge and Exhaust Isolation Motor Driven Auxiliary Feedwater Pumps Essential Service Water System Steam Line Isolation Less than or equal Less than or equal Less than or equal Less than or equal Not Applicable to 12.0¹/24.0¹¹ to 2.0 to 8.0 to 18.0¹/28.0¹¹ Less than or equal to 60.0 Less than or equal to 14.0¹/48.0¹¹ Less than or equal to 11.0 7.Containment Pressure--Hi h-Hi h a.b.C.d.Containment Spray Containment Isolation-Phase"B" Steam Line Isolation Containment Air Recirculation Fan Less than or equal to 45.0 Not Applicable Less than or equal to 10.0 Less than or equal to 600.0 8.Steam Generator Water Level--Hi h-Hi h a.Turbine Trip b.Feedwater Isolation Not Applicable Not Applicable 9.Steam Generator Water Level--Low-Low Motor Driven Auxiliary Feedwater Pumps*Turbine Driven Auxiliary Feedwater Pumps Less than or equal to 60.0 Less than or equal to 60.0 10.4160 volt Emer enc Bus Loss of Volta e a.Motor Driven Auxiliary Feedwater Pumps Less than or equal to 60.0 11.Loss of Main Feedwater Pum s a.Motor Driven Auxiliary Feedwater Pumps Less than or equal to 60.0 12.Reactor Coolant Pum Bus Undervolta e a.Turbine Driven Auxiliary Feedwater Pumps Less than or equal to 60.0 COOK NUCLEAR PLANT-UNIT 2 3/4 3-28 AMENDMENT NO.

l.I 4'4 ATTACHMENT 3 TO AEP:NRC:1123 ANALYSIS OF MAIN STEAM LINE BREAK INSIDE CONTAINMENT (WCAP-11902 SUPPLEMENT 1)