PMP 7200.RST.004 Rev.S Page 1 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Information Robert E. Larson nter Michael Finissi wner Effective Date:

NE ogtuzant rgantzatton TABLEOF CONTENTS 1

PURPOSE AND SCOPE o ~ esses

~ esse

~ ~ ~ ~ ~ ~ oo ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ooooooo

~ ~ so 3 2

DEFIMTIONS ANDABBREVIATIONS................

I ~ ~ 06 3

RESPONSIBILITIES o ~ ~ oo ~ ~ ~ ~ ~ oooo ~ oo ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ooooooo. ~ o ~

'o ~ ~ ~

.10 4

DETAILS-

~ ~ ~ oo ~ ~ ~ ~ ooooe ~ ~ oeooo ~ ~ ooooooooo ~ ~ ~ ~ ~ ~ ~ ~ oo ~ ~ oooo ~ ~ eooo ~ ~ ooooooo

~ ~ ~ ~ eoo ~ ~ ~ ~ ooooooeooo-13 4.1 4.2 4.3 4.4 4.5 4.6 Scope And Selection Of Systems For Expanded System Readiness Review...'...... 13 Use Of The System Assessment Matrix, SIDS, And The Assessment Data Base....

14 Phase 1 Initial Expanded System Readiness Review...........~.....................

16 Phase 2 Restart Activities Monitoring.....................................

27 Phase 3 Final Expanded System Readiness Review......................

32 Phase 4 Startup And Power A.,ensiOn.................'..............................

37 4 ~7 Reports......,...,........~..........,...

~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ o ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ 41 FINALCONDITIONS e o o s o o o o o e o o o ~ o o o o o o e e o o ~ e o o ~ ~ ~ ~ o e ~ ~ oooo ~ ~ ~ o o e o o o o o o e o o o o o o o o o o o o o o o o o o o e o o o o ~ 42 5

REFERENCES

~ ~ o o o o o o o o o o o o o o ~ o o o o o o ~ ~ ~ ~ o o e o o o o o o o ~ o o o o o o o o e o o o o o o o ~ ~ ~ ~ o o o e o o o o ~ e o o o o o o o ~ o o ~ ~ ~ o o ~ 42 6

ATTACHMENT1 SYSTEM READINESS REVIEW BOARD (SRRB) CHARTER.. 44 ATTACHMENT2 21 LEVEL 1 SYSTEMS INCLUDEDIN THE PREVIOUS SYSTEM ADINESS~RE~VIEW esses'oooooeooooooooooooooooooo

~ ~ eoooooooooooooeoooooo

~ ooooooooo

~ ~ 46 RE ATTACHMENT3 RATIONALEFOR SELECTION LEVEL 1 SYSTEMS FOR EXPANDED ADINESS REVIEW oo ~ ooeooooooeoo

~ so ~ ~ eoo ~ ~ ~ sooooosoooooeooooooooooooooooeo.

~ ~ ~ oo ~ ~ ~ o 48 RE ATTACHMENT4 EXPANDED SYSTEM READINESS REVIEW LEVEL 1 SYSTEMS

~ ooooooe

~ oooo ~ oooo ~ ~ osooo

~ ooooooooooo

~ ooooooooeooeooosoo

~ ~ ~ oooooooe

~ ~ ooooe ~ ooooo ~ ~ ~ ~ ~ ~ o 49 ATTACHMENT5 EXPANDED SYSTEM READINESS REVIEW TRAINING QUIREMENTS ooo ~ oooooooooooooeoooo

~ ooeoeoooooooo

~ ooooooeeoooooooooooooooooo

~ os ~ oo ~ ooo 51 RE ATTACHMENT6 SYSTEM'READINESS REVIEW DOCUMENTATIONANDDATA OURCESoooooo

~ ooooooosoeooooooooooooeeoooooooooeoooooooooooooooooooe

~ eooooooooooooeo

~ ~ esses 52 S

f 9905170136 9q0507 PDR ADOCK 050003i5 P

PDR

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 2 of 101 ATTACHMENT7 SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWN UIDELINES) o ~ ~ ~ ~ oo ~ ~ oo ~ oeoooooooo

~ ~ ~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ oo ~ ~ oo ~ ~ ~ ~ ~

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ o 54 G

ATTACHMENT8 CRITERIA FOR WORK INCLUDEDIN RESTART SCOPE.... 62 ATTACHMENT9 PHASE 2 OUTAGE SCOPE APPROVAL PROCESS...............

69 ATTACHMENT10 RESTART REQUIRED SCOPE DEFERRAL FORM............. 70 ATTACHMENT11 EXPANDED SYSTEM READINESS REVIEW CLARIFICATION SHEET

~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ o ~ ~ ~ ~ ~ ~ oe ~ ~ ~ ~ ~ ~ ~ oo ~ eo ~ oo ~ ~ ~ o ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ e ~ ~ o ~ e ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ 71 ATTACHMENT12 INITIALEXPANDED SYSTEM READINESS REVIEW REPORT

~ ~ e e ~ e e ~ ~ e ~ ~ ~ e ~ o e e o ~ e ~ o ~ ~ e ~ ~ ~ ~ o ~ e ~ o ~ e ~ e ~ o ~ o ~ e ~ e ~ ~ e ~ ~ ~ ~ e ~ ~ e ~ ~ ~ ~ o ~ e ~ o o ~ ~ o ~ ~ ~ ~ e ~ e ~ e ~ ~ ~ ~ 72 ATTACHMENT13 FINALEXPANDED SYSTEM READINESS REVIEW REPORT

~ ~ oooooo ~ eoooo ~ oooooooo ~ ~ ~ oo ~ ~ ~ oooooooooooo

~ ~ oo ~ eo ~ ~ ~ ~ ~ ~ ~ ~ ~ ooooooo

~ ooeoo ~ ~ ~ ~ oooooo ~ ~ 75 ATTACHMENT14 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED ULTS oooooooeooooo

~ oo ~ ooooooooooooooooeooooooooooooooooo

~ ~ oo ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ oooooo ~ ~ ~

ooooo ~ oo ~ ~ 78 RES ATTACHMENT15 SYSTEM WALKDOWNREPORT.....................................

83 ATTACHMENT16 SYSTEM READINESS AFFIRMATIONREPORT................ 84 FIGURE 1 SYSTEM ASSESSMENT MATRIXMAJOR TOPICS........................

85 FIGURE 2 SYSTEM ASSESSMENT MATRIXEXA'MPLE-AUXILIARYFEEDWATER SYSTEM

~ ~ ~ ~ oooooo ~ ~ ~ ~ ~ ~ ~ ~ ~ oooooo ~ ~ oo

~ ~ ooee

~ ~ oooo ~ oooo ~ oo ~ ~ oooooooooo

~ ~

oooo ~ ooo ~ oo ~ ~ ~ ~ ~ ~ ~ ~ oo 95 FIGURE 3 READINESS REVIEW ATTRIBUTEASSESSMENT FORM..............100 FIGURE 4 SAMPLE COMPLETED READINESS REVIEW ATTRIBUTEASSESSMENT

. FORM

~ oo ~ ~ ~ ~ ~ ooo ~ ~ o'o ~ ~ ooooooooooooooooooooooooeoo

~ oo ~ oooeoooooooooooo

~ oo ~ ~ ~ oo ~ ~ oooooooeo101

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 3 of 101 1

PURPOSE AND SCOPE

[Ref. 6.8]

1.1 The purpose of this document is to define the Expanded System Readiness Review (ESRR) Program and provide guidance in evaluating and determining system restart readiness for the Cook plant.

This document also describes the process forscoping work items as either required or not required to support unit restart.

These guidelines support startup from the current extended outage in support of Reference 6.1.

1.2 Several independent reviews, including a self assessment of the Auxiliary Feedwater

'ystem and an independent Engineering Issues Review Group report identified vulnerabilities in the preservation of the Design and Licensing Basis that suggested a

need for a more rigorous review of overall system readiness, 1.3 The ESRR willprovide reasonable assurance that:

~

the plant systems are capable of meeting their safety and accident mitigation functions as defined in their design and licensing bases [Ref. 6.11], and

~

in conjunction with other ongoing improvement programs and resolution of identified issues, that the plant is modified, tested, operated and maintained consistent with the design and licensing bases.

[Ref. 6.12]

1.4 The Expanded System Readiness Review consists of four phases Phase 1: Initial Expanded System Readiness Review Phase 2: Restart Activities Monitoring Phase 3: Final Expanded System Readiness Review Phase 4: Startup and Power Ascension 1.4.1 Phase 1 is to include the following:

a.

Formation and training of system teams for readiness review using representatives from various station departments.

b.

A review of system design and license basis documentation.

c.

Review of safety and accident mitigation functions for each system.

d.

Verification, in conjunction with other ongoing improvement programs and resolution of identified issues, that the plant is modified, tested, operated and maintained consistent with the design and licensing bases.

Information PMP 7200.RST.004 Rev. 5 Page 4 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM e.

Evaluation of the extent of condition for identified problems and identification of potential programmatic or generic issues.

Performance of multi-disciplined system walkdowns.

Evaluation of open items in the System Indexed DataBase System (SIDS) (see definitions) against the Restart Screening Criteria.

NOTE:

The Plant Nuclear Safety Review Committee (PNSRC) is making a transition to be known as Plant Operations Review Committee (PORC).

This document uses the acronym, PORC, but documents such as the UFSAR and Technical Specifications may use PNSRC that represents the same group.

h.

Presentation of the Initial Expanded System Readiness Review Report

'o the System Readiness Review Board (SRRB) and the Plant Operations Review Committee (PORC).

/

Begin scheduling restart work in the Restart Schedule.

1.4.2 Phase 2 is to include the following:

ao Continued review of open corrective action items through closure.

b.

Continued evaluation of emergent action items for unit restart against the Restart Screening Criteria.

C.

Scheduling of restart work into the appropriate System Work Window.

d.

Monitoring of field.work, including presence at the job site, when appropriate.

e.

Development of System Test Plans.

Preparation for System Window closure and the Final Expanded System Readiness Reviews.

g.

Completion of regularly scheduled walkdowns by the System Manager (See definitions).

h.

Management of work closure through use of performance indicators and priorities.

Update of the SIDS data base, as the System Manager evaluates emergent and open items.

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 5 of 101 1.4.3 Phase 3 is to include the following:

a... Final System Readiness Walkdown completed by the System Manager and an assigned Operations representative.

b.

Presentation of the Final System Readiness Report, prior to restart, to the SRRB and PORC by the assigned operations representative and the System Manager.

c.

Review work that is not complete prior to restart and review the aggregate impact of deferred work.

d.

Finalize the System Test Plans.

e.

System Manager willdevelop performance monitoring baseline for system performance tracking and trending 1.4A Phase 4 is to include the following:

a.

Designated test results identified by the Test Review Board (TRB).

b.

System Manager willimplement performance monitoring baseline for system performance tracking and trending.

c.

System Manager willmonitor any new corrective maintenance activities or condition reports, and continuously monitor system readiness.

d.

Completion of System Readiness Affirmation.

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 6 of 101 2

DEFINITIONS ANDABBREVIATIONS Term System Assessment Matrix Attribute Topic Review Area Discrepancy Generic Issue Assessment Data Base Meaning The matrix consists of attributes (rows) and topic review areas (columns) that define the scope of the work and when completed provides the summary basis of the conclusions of the Expanded System Readiness Review.

Figure 1 provides the Assessment Matrix Form.

Figure 2 provides a sample completed assessment matrix.

Key system parameters, including system safety and accident mitigation functions, that willbe evaluated against various topic review areas.

The attributes make up the rows of the matrix and are selected by the Expanded System Readiness Review Teams using guidance provided in Section 4.3.4.

Consists of documents and sources of information in the following areas: Design, Licensing, Operations, Maintenance, Surveillance, Physical Plant, and Programs, Processes and Procedures.

The review areas make up the columns of the assessment matrix. The addendum to Figure 1 provides guidance on the evaluation to be performed for each topic area.

A finding generated as a result of an activity performed in accordance with this procedure which indicates a potential need for corrective action or process improvement.

Discrepancies identified during the Expanded System Readiness Review are documented via Condition Reports (CRs) in the Cook Plant Corrective Action Program (CAP) or as Action Requests in the Work Control System (NPM). A Condition Report shall be issued for any item that falls within the scope of the Corrective Action Program.

Discrepancies identified in several systems for the same topic

..review area that potentially identify a process or programmatic problem..

The data base used to document Expanded System Readiness Review assessments, confirming consistent use of design and licensing information, and identifying discrepancies.

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 7 of 101 2

DEFINITIONS AND ABBREVIATIONS(Continued)

Term System Indexed Data Base System Current Licensing Basis Design Basis (as Defined by 10CFR 50.2)

Meaning The SIDS data base is used to track open items identified as required for restart.

Open items in this data base include open items from existing plant data sources, and discrepancies identified by the Expanded System Readiness Review.

Thus, discrepancies identified during the Expanded System Readiness Review generate entries in the SIDS Database.

The set of NRC information applicable to a specific plant and a licensee's written commitments for ensuring compliance with, and operating within applicable NRC requirements and the plant specific design basis, including all modifications and additions to such commitments over the life of the license, that are docketed and in effect.

The CLB includes NRC regulations contained in 10CFR Parts 2, 19, 20, 21, 26, 30, 40, 50, 51, 54, 55, 70, 72, 73, 100 and appendices thereto: Orders, License Conditions, Exemptions, and Technical Specifications (TSs). It also includes the plant specific design basis information defined in 10CFR 50.2 as documented in the most recent UFSAR as required by 10CFR 50.71 and NRC commitments remaining in effect that were made in docketed licensing correspondence such as responses to NRC Bulletins, Generic Letters and enforcement actions, as well as licensee commitments documented in the NRC Safety Evaluations or Licensee Event Reports.

Information that identifies the specific functions to be performed by a structure, system or component of a facility and the specific values or range of values chosen for controlling parameters as reference bounds for design.

These

.values may be (1) restraints derived from generally accepted state-of-the-art practices for achieving functional goals or (2) requirements derived from analysis (based on calculations and/or experiments) of the effect of a postulated accident for which a structure, system or component must meet functional goals.

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 8 of 101 2

DEFINITIONS AND ABBREVIATIONS(Continued)

Term Engineering Design Basis Vertical Slice Review Horizontal Slice Review System Readiness Review Board (SRRB)

System Manager System Manager "APPROVE" Meaning The Engineering Design Basis is the entire set of design-restraints that are implemented, including (1) those that are part of the current licensing basis, and (2) those that are not part of the current licensing basis, but are implemented to achieve certain. economies of operation, maintenance, procurement, installation, or construction.

(See Reference 6.2 for further clarification, including definitions of Design Basis Document, Design Requirements and Design Output Document).

A structured review approach derived from the Safety System Function Inspection (SSFI) methodology that allows an assessment of specific aspects of the plant physical configuration and operation against selected aspects of the plant licensing and design basis.

The scope of the ESRR vertical slice review for each system is defined by the System Assessment Matrix.

A review of a programmatic issue or plant documents across multiple plant systems, such as a review of the UFSAR, evaluation of Appendix R fire protection requirements, review and upgrade of calculations, etc.

A board of personnel conducting business in accordance with the Charter in Attachment 1.

The leader of the Expanded System Readiness Review Team and engineering owner of assigned systems for purposes of this procedure.

Indicates the fact that the System Manager has reviewed the scope (i.e., the screening of the item as required or not required to support unit restart) of an item in SIDS and the associated comments that justify the item's scope. This "APPROVAL" is denoted in the Initial System Manager Approval box in SIDS and is used by the System Manager during all Phases for new items in SIDS, meaning that the System Manager agrees with the scope and justification.

f g%'\\,

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 9 of 101 2

DEFINITIONS AND ABBREVIATIONS(Continued)

Term System Manager "CONCUR" System Manager "EXCEPT" System Manager "Post Restart Deferred" System Manager "Restart Required Deferred" Meaning During Phases 3 and 4, "CONCURRENCE" is denoted in the Final System Manager Approval box in SIDS and is used by the System Manager to mean that restart items, or post restart items that are not included in the aggregate impact, have been completed to the satisfaction of the System Manager.

Indicates that this Restart scoped SIDS item is not complete and remains an exception to restart (i.e., completion of the item still needed to enter the mode identified in the mode restraint box in SIDS). This "EXCEPTION" is denoted in the Final System Manager Approval box in SIDS and is used by the System Manager during. Phases 3 and 4.

Denoted on items associated with a component that has (2) or.

more post restart deferred items, excluding PM post restart items.

Denoted on items with deferred scope that were initially

approved, as restart required.

These items must be accompanied by a Restart Required Scope Deferral Form (Attachment 10).

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 10 of 101 3

RESPONSIBILITIES 3.1 The Director of Engineering Restart is responsible for overseeing Engineering preparations for restart, for the ESRR Program and, when needed, for chairing the System Readiness Review Board; ensuring that the requisite members are in attendance.

3.2 The System Readiness Review Manager is responsible for:

3.2.1 Expanded System Readiness Review Program content and oversight.

3.2.2 Determination of the scope of the review for ESRR systems.

3.2.3 Ensuring adequate training and logistics support is provided to participating'eam members j

3.2.4 Reviewing the results of the individual system readiness reviews, identifying any generic. concerns and defining progranunatic corrective action (ifany).

3.2.5 Reviewing the attribute selection and the corresponding Assessment Matrix for each system (Figure 1).

3.2.6 Maintaining and revising this procedure on the Expanded System Readiness Review Program, annotating the changes made, and obtaining appropriate approvals.

3.2.7 Owns and manages the SIDS Database 3.3 The System Engineering Manager is responsible for the assignment of System Managers to systemrbeing reviewed, and for providing additional oversight for the ESRR Program.

3A The System Engineering Supervisors are responsible for supervision and effective implementation of the Expanded System Readiness Review Program through active coaching, counseling and oversight of the System Manager.

The System Engineering Supervisors jointly own the ESRR results with the System Managers.

3.5 The Expanded System Readiness Review Program Coordinator is responsible for:

3.5.1 Expanded System Readiness Review program development and implementation.

3.5,2 Schedule and coordination

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 11 of 101 3.5.3 Reviewing and recommending for approval the attribute selection and the corresponding Assessment Matrix for each system.

3.5.4 Review the Assessment Data Base to identify generic issues and trends.

3.6 The Assessment Data Base Coordinator is responsible for:

3.6.1 Assuring that the Assessment Data Base is operational and available to the ESRR teams.

3.6.2 Maintaining the data in the Assessment Data Base and providing status.and summary reports regarding the ESRR.

3.7 The SIDS Data Base Coordinator is responsible for:

3.7.1 Assuring that the SIDS Data Base is operational and available to the ESRR.

teams, and to program owners and functional area managers (or designees).

3.7.2 Making any required changes or improvements to the SIDS Data Base.

3.7.3 Ensuring that items required to be scoped are entered into the SIDS Data Base.

3.7.4 Providing and maintaining the quality of SIDS reports.

3.8 System Managers are responsible for:

3.8.1 Overall system health and performance.

3.8.2 Organizing and leading each ESRR Team.

The Team willbe composed of

'he necessary multi-discipline resources to conduct Phase 1 of the Expanded System Rea'diness Reviews.

The System Teams willinclude the following:

a.

System Manager b.

Operations Representative c.

Design Engineering Representative d.

Maintenance Representative.

e.

Licensing Representative f.

Outside member(s) with varied industry experience

Information PMP 7200.RST.004 Rev. 5 Page 12 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 3.8.3 Coordinating team requests for system design and licensing basis documentation from the appropriate sources.

3.8.4 Performing Phases 1, 2, and 3, and supporting Phase 4 of the ESRR.

3.8.5 Coordinating preparation of the ESRR Initial and Final Reports, and presenting these reports to the SRRB and PORC.

3.8.6 Assembling ESRR review results and restart action items into the SIDS Database for tracking.

3.8.7 Maintaining a status of restart action items and submitting status updates to plant management as required.

3.8.8 Coordinating and conducting system.walkdowns with appropriate team members.

3.8.9 Organizing and leading each work window team (see Section 4.4.2b.1).

3.9 The Expanded System'Readiness Review Teams are responsible for:

3.9.1 Identifying attributes appropriate to their specific system for assessment.

3.9.2 3.9.3 Selecting topic areas appropriate to the identified attributes.

Performing system attribute checks and walkdowns and documenting the results, including any noted discrepancies, in the assessment data base.

3.9.4 Reviewing items in the SIDS data base and scoping the items as discussed in section 4,3.12.

3.9.5 Entering the deficiencies in the Cook Plant Corrective Action Program and/or Work Control System as appropriate.

3.9.6 Providing assistance to the System Manager as required.

3.10 The Operations Manager is responsible for assigning appropriate Operations representatives to support the ESRR Program.

3.11 The Director of Regulatory Affairs is responsible for assigning appropriate Licensing representatives to support the ESRR Program.

3.12 The Maintenance Manager is responsible for assigning appropriate maintenance representatives to support the ESRR Program.

I, ik.$ g

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 13 of 101 3.13 The Design Engineering Director is responsible for assigning appropriate Design Engineering representatives to support the ESRR Program.

3.14 The SRRB w'illperform management oversight and assessment of the Expanded

=-

System Readiness Review Program and willbe the final approval authority over work item screening.

The SRRB willperform activities applicable to this procedure, including approval of the System Assessment Matrices.

The SRRB Charter is included in Attachment l. An expected product of the SRRB oversight is improved consistency and technical depth of the ESRR results.

3.15 The PORC is responsible to provide a cross-discipline oversight of the ESRR Program by reviewing ESRR reports for each system and the Integrated Readiness Review Report.

3.16 The Outage Scope Management Team (OSMT) willreview emergent work items following Phase 1 to determine whether or not they are required to support Unit restart.

4 DETAILS 4.1 Scope And Selection Of Systems For Expanded System Readiness Review NOTE:

The term "TBDL"when used in this document refers to detail To Be Developed Later and incorporated in a subsequent revision to this document or in other documents.

4.1.1 Previously, a plant System Readiness Review was conducted as discussed in Reference 6.3. A graded approach was used in performing the previous system readiness reviews, with high-risk systems receiving more thorough reviews.

The previous system readiness reviews were broken down into three levels-with.the following attributes:

a.

Level 1 Systems

.1.

Risk-significant Maintenance Rule systems 2.

Some important non-risk significant standby maintenance rule systems b.

Level 2 Systems 1.

Remaining non-risk significant Maintenance Rule systems c.

Level 3 Systems

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 14 of 101 1.

Non-Maintenance Rule systems that support power generation 2.

Systems that are required for plant operation, are easily monitored in service, and present little or no challenge to safety 4.1.2 The 21 Level 1 systems included in the previous System Readiness Review are listed in Attachment 2.

4.1.3 Subsequent to the completion of the previous System Readiness

Review, several independent reviews were conducted, including a Safety System Functional Inspection (SSFI) of the AuxiliaryFeedwater System (Reference 6.4) and an Engineering Issues Review Group final report (Reference 6.5).

These reviews identified vulnerabilities with respect to the scope of systems reviewed during the previous System Readiness Review, additional system design basis and licensing basis issues, and weaknesses in engineering programs and processes.

4.1.4 The classification of Level 1, 2, and 3 systems utilized during the previously performed system readiness reviews were based solely on Maintenance Rule input. The Level 1 systems were Maintenance Rule Risk

'ignificant systems.

Level 2 systems were non-risk significant systems, but systems that were still included in the scope of the Maintenance Rule.

Level 3 systems were systems that were not included in the scope of the Maintenance Rule.

4.1.5 The classification of Level 1 and 2 systems utilized during the ESRR Program is based on Maintenance Rule input, systems required for safe shutdown, significant attendant/support

systems, and systems identified by the System Engineering Manager that have experienced an abnormal amount of corrective maintenance.

The basis for the selection of Level 1 systems is found in Attachment 3.

4.1.6 Expanded System Readiness Reviews under this procedure willbe conducted on all of the previous Level 1 systems, plus additional systems that were determined to warrant an Expanded System Readiness Review (Refer to Attachment 4).

Expanded System Readiness Reviews for the new Level 2 Systems willbe addressed in a separate procedure.

4.2 Use OfThe System Assessment Matrix, SIDS, And The Assessment Data Base 4.2.1 The ESRR employs a vertical slice approach derived from the methodology of a Safety System Functional Inspection (SSFI).

This approach evaluates system safety important to safe operation and accident mitigation functions (Attributes) against plant configuration and design, licensing, operations and maintenance documents (Topic Areas).

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 15 of 101 4.2.2 The scope of the vertical slice review performed on a system is shown in a System Assessment Matrix. The system attributes selected for each system's review form the rows of this matrix, as further discussed in section 4.3.4.

The sources of information or topic areas that are included in the vertical slice form the columns of the matrix.

4.2.3 The System Manager, accompanied by the cognizant System Engineering Supervisor, presents a description of the system scope and the system specific Assessment Matrix to the SRRB for approval.

This helps the SRRB ascertain that attributes are appropriate.

4.2;4 The requirements associated with each of the attributes are evaluated against specific topic areas or sources of information.

4.2.5 The assessments include comparison,and evaluation of documents as well as observations of plant condition and configuration during system walkdowns.

The ESRR willemphasize those attributes, topic areas and activities necessary to satisfy the program purpose.

4.2.6 The results are documented using Attribute Assessment Forms (Figure 3) in the Assessment Data Base.

Discrepancies are entered into the Cook Plant Corrective Action Program and/or Work Control System (NPM).

Assessment Data Base manipulation and reporting capabilities assist in reporting, tracking and identification of generic issues and trends.

4.2.7 By assessing the results for all topic areas across all the systems reviewed, the ESRR can assist in determining the extent ofcondition of vulnerabilities in plant programs and processes already identified by previous inspections and reviews (e.g., References 6.4 and 6.5). The ESRR willalso be used to identify other potential vulnerabilities and the potential need for further improvement in plant processes and programs.

4.2.8 In summary, the ESRRs result in a vertical slice evaluation of selected design and licensing bases for the ESRR systems.

These evaluations do not guarantee that future external or internal assessments willnot uncover additional problem reviews.

However, in conjunction with other ongoing horizontal slice restart programs at Cook Plant and resolution of issues that are recommended for restart, the ESRRs provide reasonable assurance that key systems are capable of meeting their safety and accident mitigation functions as defined in their design and licensing basis.

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 16 of 101 4.2.9 The SIDS Data Base is being used to track items being evaluated, scoped and justified as either Restart or Post Restart for both Units. This data base is the central repository for such items.

SIDS willgenerate reports listing Restart and Post Restart items for SRRB and PORC approval.

This data base willbe managed and controlled by the System Manager for his particular system(s).

4.3 Phase 1 Initial Expanded System Readiness Review 4.3.1 Expanded System Readiness Review Team Formation a.

The System Engineering Manager willassign a System Manager to each of the Expanded System Readiness Review teams.

b.

The System Manager willlead the Expanded System Readiness Review'eam comprised of a licensed member from Operations and members from Design Engineering, Maintenance, Licensing, and outside members with strong industry experience; 4.3.2 Training a.

Prior to performing the reviews, training willbe conducted for the AEP System Managers and the ESRR Team members on Expanded System Readiness Review Program knowledge and skill needs.

These needs are defined-in Attachment 5.

4.3.3 b.

The training for the AEP System Managers and the ESRR Teams was determined based on an evaluation of the tasks to be performed and lessons learned form the original System Readiness Reviews, the original System Engineering Review Board, and previously performed engineering and programmatic assessments.

A Review Design and Licensing Basis Documentation a.

The ESRR Team shall become familiar with the design and licensing basis of the system to gain an understanding of the system functional and safety requirements under normal operating and accident conditions.

The design and license basis documentation listed in willbe available to the ESRR Team.

b.

Access to the followingwillbe provided to the ESRR Teams.

1.

EQ information 2.

Appendix R information

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 17 of 101 3.

Station Blackout information 4.

ISI/IST Program Information 5;

Seismic qualification information 6.

Electrical design criteria (separation, etc.)

7.

Maintenance Rule Program Information 8.

Individual Plant Examination (IPE) Results 9.

High Energy Line Break Program'Information

10. Generic Letters GL89-13, GL83-28, GL96-01, and responses thereto.
11. Generic Letter GL89-10 program information.
12. Generic Letter GL96-06 information (as available)
13. LER 97-021 and associated single failure commitments
14. 1998 AFW SSFI Report
15. 1998 Containment Spray SSFI Report
16. Engineering Issues Review Group Report (Reference 6.5) c.

The expectation is that the System Manager willreview the above information to determine its impact on his system.

d.

Licensing willprovide the results of a review of licensing commitments on a system basis.

4.3.4 Define System Specific Attributes a.

During the review and evaluation of design and licensing information, each ESRR Team willdevelop a list of attributes to be included in the assessment on the System Assessment Matrix.

Information PMP 7200.RST.004 Rev. 5 EXPANDED SYSTEM READINESS REVIEW PROGRAM Page 18 of 101 b.

Attributes willbe selected by a thorough review of the design and, licensing basis to identify the system safety and accident mitigation functions. Additional functional requirements of the system and critical components may also be selected.

Information from the Licensing Review Program willbe considered as willPRA insights on risk significant components and functions.

Functionality of attendant/support systems and important passive equipment (e.g.,

tanks, bladders, strainers) willalso be considered in selection of system attributes.

Generic requirements such as Station Blackout, EQ, Appendix R, etc. willalso be selected as system attributes when appropriate.

A detailed example of and some requirements for attribute selection and their bases are provided in the Figure 2 addendum.

4.3.5 Establish Scope of Review a.

Each ESRR Team willperform a vertical slice review of its assigned system by evaluating the system and common attributes against specific topic review areas as documented in the system Assessment Matrix.

The topic areas to be assessed for each attribute willbe defined in an initial System Assessment Matrix at the start of the ESRR, taking into account the results ofprevious evaluations at Cook Plant.

This initial System Assessment Matrix willbe reviewed and recommended by the ESRR Program Coordinator or Manager and the Nuclear Licensing Manager or Director of Regulatory Affairs, and approved by the SRRB.

Changes made in response to SRRB comments need not be re-reviewed by the other parties who previously reviewed the matrix.

These reviews and approvals willbe based on the matrix and other supporting material as dictated by the board. Typically, this information willconsist of:

~

A listing of the system safety and accident mitigation functions

~

The matrix itself, showing the attributes chosen and the topics to be reviewed for each

~

A marked-up system flow diagram or schematic depicting system boundaries

<>>>

Greg Gibbs>>>>

Phil Hildebrandt>>>>

Larry Demick>>>>

Jeff Bass>>>> (primary) or BiH Bryant' (alternate) Westinghouse representative System engineering supervisors Board Secretary Non-voting members:

Additional occasional attendance by members of the Plant Operations Review Committee, the Restart group, and the Engineering Effectiveness organization is expected to reinforce expectations and provide oversight for the restart issue review process=.Additionally, the SRRB Chairman may invite guest, non-voting members to supplement the board when reviewing nonwngineering program or functional area assessment results or SIDS issues.

QUORUM:

(ESRR Related Board

-Functions)

Chair (or Vice Chair), an Operations and EOP Project representative, and a minimum of two of the double asterisked named members, and one engineering supervisor, not associated with the system or document/program under review. A SRRB Secretary shall also be present but may be one of the SRRB members. No board willconsist of more than six voting members.

Other members may participate at their discretion as non-voting members in such cases.

5 5

QJ

Information PMP '7200.RST.004 Rev. 5 Page 45 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Attachment 1

SYSTEM READINESS REVIEW BOARD (SRRB) CHARTER Pages:

44-45 QUORUM (Programmatic and Functional Area Readiness Board Functions)

Chair (or Vice Chair), minimum of two of the double asterisked members and two other members.

One of the additional members shall be an engineering representative for reviews of engineering programs.

No board shall consist of more than five voting members.

An SRRB Secretary shall also be present but may be one of the SRRB members.

Other members may participate at their discretion as non-voting members in such cases.

ACTIONS:

The SRRB will:

l.

Serve as the primary independent engineering review body for 0350 checklist item restart action plans as required by PMP 7200.RST.001'nd, as delineated further in PMP 7200.RST.004 and PMP 7200.RST.006, expanded system readiness review identified issues and reports. The SRRB willalso perform functions related to assuring proper dispositioning of programmatic and function area readiness discrepancies as detailed in PMP 7200.RST.009 and PMP 7200.RST.010.

The SRRB affirms and approves the scoping of potential deficient conditions as either restart or post-restart based on criteria defined in the restart plan.

2.

In its reviews, enforce technical rigor, consistency of approach, and a thorough assessment of system readiness.

The SRRB willalso challenge engineers to ensure the issues are fullyunderstood.

3.

Ensure a record of decisions and concerns raised by the SRRB review is documented for future review.

Programmatic implementation concerns raised by the SRRB willbe documented on condition reports initiated by the SRRB secretary.

4.

Ensure that nuclear engineering principles and the attributes of good engineering are demonstrated by the engineering staff.

5.

Ensure that the engineers understand their roles and responsibilities.

The Director of Engineering Restart is responsible for management oversight of SRRB activities and for disbanding this board after startup when directed by the Site Vice President.

PORC=will'provide oversight of the SRRB and approve Expanded System Readiness Reports as discussed in PMP. 7200.RST.004 and PMP 7200.RST.006 in that oversight role.

This charter becomes effective with the issuance of PMP 7200.RST.004 REVISION 5.

Information PMP 7200.RST.004 Rev. 5 Page 46 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 21 LEVEL 1 SYSTEMS INCLUDEDIN THE PREVIOUS SYSTEM READINESS REVIEW Pages:

46-47 THE 21 LEVEL 1,SYSTEMS FOR THE PREVIOUS EXPANDED SYSTEM READINESS REVIEW WERE 120 volt AC/CRID Inverters AirRecirculation/Hydrogen Recombiner AuxiliaryFeedwater 250 volt DC Station Batteries Component Cooling Water Containment Containment Spray Control Air ECCS Accumulators ECCS Charging/CVCS High Head Injection ECCS Residual Heat Removal ECCS Safety Injection Emergency Diesel Generators Essentiai Service Water Ice Condenser Main Steam Non-essential Service Water Plant AirCompressors

J 0

Information PMP 7200.RST.004 Rev. 5 Page 47 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 21 LEVEL 1 SYSTEMS INCLUDEDIN THE PREVIOUS SYSTEM READINESS REVIEW Pages:

46-47 Reactor Coolant System Reactor Protection System/Solid-state Protection/ESFAS Electrical Safety Buses 4000 volt and 600 volt

Information PMP 7200.RST.004 Rev. 5 Page 48 of 101

"- EXPANDED SYSTEM READINESS REVIEW PROGRAM RATIONALEFOR SELECTING LEVEL 1 SYSTEMS FOR EXPANDED SYSTEM READINESS REVIEW Pages:

48-48 The following rationale was used in selecting the 39 systems to be reviewed in accordance with this procedure.

Allselected systems are identified in Attachment 4.

Maintenance Rule Risk Si ificant S stems AllCook Plant Maintenance Rule Risk Significant systems were included in the Level 1 ESRR.

S stems Re uired to Su ort Safe Shutdown The Cook Plant specific fire protection/Appendix R reports/documents were reviewed to identify systems required to support safe shutdown. Allof these systems were included in t5e scope of the Level 1 ESSR.

Attendant/Su ort S stems Attendant systems were considered during the identification of Level 1 systems being selected for the ESRR.

Heating, Ventilation and AirConditioning systems such as Control Area Ventilation, Switchgear Ventilation and Containment Ventilation were included in the scope of the ESRR.

The Screenwash and Fire Protection Systems were also included as attendant/support system.

Historical Performance of Cook Plant S stems The historical performance of Cook Plant systems was considered.

Based on input from the System Engineering Manager and the Operations Manager additional systems such as Emergency Lighting, and Post Accident Sampling System (PASS) were included.

Third Pa Review of the Sco The scope of the systems chosen for ESRR was reviewed by a peer group and an independent third party to ensure that successful completion of the ESRR on these systems would provide a reasonable assurance that the Cook Plant can be restarted safely and reliably.

Information PMP 7200.RST.004 Rev. 5 Page 49 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM EXPANDED SYSTEM READINESS REVIEW LEVEL 1 SYSTEMS Pages:

49-50 SYSTEM DESCRIPTION ECCS CHARGING ECCS SI POST ACCIDENTSAMPLINGSYSTEM AUXBUILDINGVENTESF CONTROL ROOM COMPLEX VENTILATION SWITCHGEAR VENTILATION 250 VDCSTATION BATI'ERIES ICE CONDENSER CONTROL ROD &CONTROL ROD DRIVE RPS/SSPS/ESFAS LOCALSHUTDOWN INDICATIONSYSTEM RADIATIONMONITORING RVLIS COMPONENT COOLING WATER CNTMTISOLATIONCOMPONENTS SPENT FUEL PIT COOLING 120 VACVITALBUSES &CRID INVERTER MAINSTEAM AIR RECIRC/H2 SKIMMER CONTAINMENTVENTILATION VENTILATION-DIESEL GENERATOR EMERGENCY DIESEL GENERATORS ABB CVCS Ir PASS CRAC SWGR 250 VDC ICE CRDM LSI RMS RVLIS CCW CIV CRID MS

~CE CV DG VENT SYSTEM LEVEL RELATEDSYSTEMS Includes Cha in Letdown Boron Path and SINJ Includes ABVGEN &AF/ESW V Includes N TRN Includes RPI Includes DUMP& N2 for PORVs RISK SIG N

N N

SAFE SHUT DOWN SIG SUPPORT SYSTEM SIG CORRECTIVE MAINT.

"S" in the "Safe Shutdown Column" indicates a support system for safe shutdown

Information PMP 7200.RST.004 Rev. 5 Page 50 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM EXPANDED SYSTEM READINESS REVIEW LEVEL 1 SYSTEMS Pages:

49-50 SYSTEM DESCRIFTION ELECTRICALSAFETY BUSES SCREENWASH FIRE PROTECTION - HALON&CARDOX AUXILIARYBUILDING TURBINEBUILDING CONTROL AIR PLANTAIR COMPRESSOR CONTAINMENT CONTAINMENTSPRAY AUXFEEDWATER SYSTEM ECCS ACCUMULATORS RCS/RCS PRESSURE RELIEF EMERGENCY LIGHTINGPACKS OFFSITE POWER ESSENTIAL SERVICE WATER NON ESSENTIAL SERVICE WATER NUCLEAR INSTRUMENTATION ABB T BUS SCRN PAC CNTMT ACCUM E LTG OFPW ESW NESW NI SYSTEM LEVEL RELATED SYSTEMS Includes 4KV& 600 V Includes Screcnhouse/Intake Includes RCP FP Includes Com ressed AirHeader &

CNTMTControl AirHeader Includes BAC Includes DIS & H2 REC &HDS Includes CST Includes MLMS Includes SWYD Includes T/C RISK SIG SAFE SHUT DOWN N

N N

SIG SUPPORT SYSTEM SIG-CORRECTIVE MAINT.

"S" in the "Safe Shutdown Column" indicates a support system for safe shutdown

Information PMP 7200.RST.004 Rev. 5 Page 51 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM EXPANDED SYSTEM READINESS REVIEW TRAININGREQUIREMENTS Pages:

51-51 1.0 TECHNICA'LTRAINING 1.1 Human Error Reduction Techniques for Engineers* (including record review and verification) 1.2 Electronic Corrective Action System

'.3 Folio Database*

1.4 Calculation Matrix 1.5 System Design and Licensing Basis~

1.6 SRO level self taught systems training with test and remediation*

1.7 Causal Analysis and effective problem solving techniques 1.8 Operability Determinations*

1.9 50.59 Screens and Evaluations*

1.10 PRA/Maintenance Rule 1.11 INPO Database/NRC Web Page~

1.12 Environmental*Qualification 1.13 Generic Letter 89-13 1.14 Generic Letter 89-10 1.15 High Energy Line Break Analysis 1.16 Appendix R 1.17 Station Blackout 1.18 Communications-Elevating Issues to Mgnt.

2.0 PROCESS TRAINING 2.1 2.2 2.3 2.4 2.5 The Enhanced System Readiness Review Program and Procedure Use of the Assessment Database Systems Indexed Database System (SIDS), access and data entry Use of.computers Lessons Learned and Vulnerabilities from previous independent inspections and reviews.

  • For System Managers only. Senunars to indoctrinate other team members in design and licensing basis fundamentals and key concepts and definitions related to operability determinations and 50.59 screens and evaluations willalso be conducted for other team members.

0

Information PMP 7200.RST.004 Rev. 5 Page 52 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW DOCUMENTATIONANDDATASOURCES Pages:

52-53 DESIGN BASIS DOCUMENTATION P&IDs Elementary and One Line Diagrams DBDs &Associated Notebooks Calculations Modifications Open and Closed Safety Evaluations and Screenings TMODS

~

Com nent Evaluations Design Change Determinations LICENSE BASIS DOCUMENTS UFSAR, FSAR &SER including Amendments General Design Criteria &FSAR Q&A Licensing History Books Commitment Database Reg Guides LERs & NOVs Tech S ecs and Bases NRC 0 n Item List DATASOURCES Operating Procedures Abnormal 0 rating Procedures Emergency Operating Procedures Annunciator Response Procedure Preventive Maintenance Procedures/PMCR Surveillance Test Procedures s Training Lesson Plans Condition Reports - 0 en and Closed Previously conducted audits, assessments (SSFIs, EDSFIs, QA/PA, 3 a

reviews)

Results of relevant NRC &INPO ins tions (Ins tion Re rts, etc.)

Generic Letters and Res nses IENs IEBs and Res onses SOERs SERs Part 21 Notifications Westinghouse Information Vendor Manuals JO/ARs including AR Evals rability Determinations &,TDMs Ops 0 n Item Log DATASOURCES (CONTINUED) 0 rator Workarounds/Concerns Restart Plan Strategies Engineering Evaluations S

ifications and Standards PRA Com onents Based and 0 rator Action Based Risk Ranking Engineering Memos

Information PMP 7200.RST.004 Rev. 5 Page 53 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW DOCUMENTATIONAND DATASOURCES Pages:

52-53 Receipt Ins ection Procedures Relay Document Technical Data Book PMI 5023 Dedication Plans Long Standing Clearances/Caution Tags Operator Aids

Information

'MP 7200.RST.004 Rev. 5 Page 54 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM

'SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61 1.0 PURPOSE

'hiswalkdown guideline is to be used as a reference while conducting the Expanded System Readiness Review Team (or individual) walkdowns.

The completed walkdowns, during the initial SRR, should be taken into account in setting the scope of the ESRR walkdowns.

2.0 GENERAL METHODS 2.1 Define the purpose of the walkdown,'areas to be visited/observed, roles of the individual team members, and assistance from Health Physics or other departments to access areas.

2.2 Plan the walkdown execution and implementation.

Pre-define how the walkdown willassess the conformance of the plant with design and licensing basis requirements (For example, piping and component configuration, electrical separation, etc.).

Ensure remote electrical cabinets, tanks, etc. and instrumentation including control Room and Remote Shutdown Panel instruments are included in the walkdown plan.

Contact Health Physics supervision to obtain any special ALARAreviews prior to actual system walkdowns.

2.3 Briefthe team on the purpose and plan.

2.4 Conduct the walkdown.

Focus the team on observation of equipment.

Work independently and discuss concerns for clarity. Take concise and accurate notes to quantify and describe findings in sufficient detail to prevent having to walkdown the item twice.

2.5 Conduct a formal post walkdown briefing. Review the notes, discuss issues and document the results on the ESRR Assessment forms, entering the data into the ESRR Assessment database.

Identify any impact on equipment or system operation.

Immediate concerns are to be identified to the engineering supervisor and the operations Shift Manager.

2.6 Identify the items that need to be completed for the system to meet its intended design function.

Assess each item against the restart criteria,. The items are to be documented for disposition and tracking in SIDS.

~

Information PMP 7200.RST.004 Rev.5, Page 55 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61 3.0 GUIDELINES 3.1 The team (lead by the System Manager) is to outline the system walkdown strategy.

Key system components and system concerns are to be identified.

3.2 The team is to identify necessary operational or plant configuration drawings to accompany the team during the walkdown.

3.3 Throughout the walkdown, the team is to function as a cohesive unit, maintaining focus on either individual system coinponents or specific system areas.

3.4 The walkdown is to focus on operability issues as well as conformance with-system design configuration and design basis. Other conditions including potential impact on equipment reliability should be noted during the walkdown.

3.S Each Team member is expected to record detailed notes identified during the walkdown. Any areas of the system that could not be walked down shall be noted and justified in the walkdown report.

3.6 Examples of team focus areas include:

Condition of snubbers, pipe supports, hangers and fasteners Condition and placement of coatings and insulation Evidence of corrosion Evidence of boric acid or boric acid buildup especially on carbon steel components, and material wastage Unauthorized modifications, partial modifications or temporary modifications not in accordance with station programs Surface condition of visible structural welds Condition ofbarrier or penetration seals Use ofunauthorized chemicals on components

Information PMP 7200.RST.004 Rev. 5 Page 56 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61

~

Evidence of bolt torque relaxation.

Evidence of discoloration on relays, cable insulation or electrical components Condition inside electrical cabinets Unauthorized or expired scaffolding in unauthorized locations or impacting equipment performance Hoses or other connections for vents or drains Presence of abandoned equipment not clearly labeled 3.7 The following is a general list of electrical and mechanical equipment physical plant inspection items:

3.7.1 Electrical Panels Equipment

~

Identify missing water plugs or holes/openings in cabinets (water or moisture intrusion can degrade or damage equipment).

~

Identify missing or loose bolts or thumb screws (ifmissing can violate seismic evaluation and it is not good work practice).

~

Identify open doors or back panels (ensure properly closed and latched, otherwise can violate seismic evaluation or allow dirt,

,,water, etc., to enter panel).

~

Identify mis-positioned breaker switches (anything that is different).

Identify improper labeling on key component breakers/switches (ensure that they are accurate and legible per controlled drawings; also includes modules, relays, conduit).

Identify dirt or debris covering cooling gratings or filters (if blocked, can prevent cooling and cause heat buildup and subsequent equipment degradation).

Information PMP 7200.RST.004 Rev. 5,',

Page 57 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61 Feel panels and equipment enclosures where appropriate to check for excessive heat buildup (can be an indication of degraded equipment; initiate request for themography check).

Check cable trays.

(Cable should not be hanging outside of cable tray; can overstress cable tray).

Check cables and conduit for degradation (cracked, brittle, chafed, bend radius, etc.).

Check MCCs overall for anything that is different.

Note any deficiency tags, especially old tags not being worked.

These may need increased priority or have had work complete'd but the tags have not been removed.

~

Check for any abnormal sounds or smells coming from the, cabinet (may indicate degraded equipment)

~

Verifyequipment-grounding cable is connected and intact.

~

Look at general materiel condition of cabinet (rust, dirt, consider qualitative impact on heat transfer).

~

Inspect seismic supports and trays.

~

s Inspect overall condition ofterminal strips and mechanical connections (lug landings).

Inspect conduit and junction boxes for external damage, loose conduit connections and missing parts and fasteners.

~

Inspect solenoid valves and motor covers for evidence of damage or equipment degradation.

3.7.2 Mechanical Components

~

Identify any abnormal sounds or smells coming from pump or motor operation.

Bearing housings and motors and pumps are to be inspected for signs of excessive heat or, vibration.

f

Information PMP 7200.RST.004 Rev. 5 Pago 58 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM

'ttachment 7

SYSTEM READINESS REVIEW PROGRAM (SYSTEM WAIKDOWN GUIDELINES)

Pages:

54-61

~

Look at general material condition of pump or motor for steam, oil, water leaks, proper levels in oil reservoirs or sight glasses (and properly marked), missing insulation, proper conduit installation.,

Identify pinned hangers.

Inspect system gauges for proper operation or typical values.

Look for pump rotation or reverse rotation ifpart of a dual train common header system (could indicate check valve degradation or isolation valves leaking by)

Identify dirt or debris covering cooling gratings or filters (if blocked can prevent cooling and cause heat buildup and subsequent equipment degradation)

Note any deficiency tags, especially old tags not being worked.

(These may indicate a need for increased priority or they may be an indication that the work was completed but that the tags have not been removed.)

Check equipment/equipment skid/foundation bolting., (Are all bolts present with proper thread engagement'?)(minimum of flush or better)

~

Review trends of parameters on key system equipment; visually inspect identified equipment'with degraded

.performance.

. ~

Visually inspect for old leak repair fittings, ensure Temporary Modifications exist to restore components with leak repair fittings.

~

Inspect equipment labeling/tags (ensure they are accurate and legible per controlled drawings).

Information PMP 7200.RST.004 Rev. 5 Page 59 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61 3.8 The following list contains material conditions indicating equipment operability issues:

3.8.1 Operability Issues Leaks (water, steam, oil, air-packing, flanges, rust on components or floor).

Lubrication (sight glasses, bull's eyes, grease cups, grease fittings, valve stems).

Handwheels/valve operators (missing, key or pin missing, unlocked, not labeled).

H Filters, screen or louvers (clogged, dirty, missing).

Instruments or gauges (out of calibration, inoperable, bent pointers).

Drains or drain holes (clogged, blocked, full, screens or grating missing).

Lines or pipes (loose, unbracketed, vibrating, insulation missing or damaged, not properly sloped).

Fasteners/bolts (loose, stripped, corroded, missing).

Indicating lamps (missing, burned out, missing covers).

Control room annunciators.

Panels (covers missing, bolt missing or not tightened, dirt and debris inside).

Area lighting (bulbs missing or burned out, inadequate to support activities).

Look for consistency between similar parameters.

Packing (bottomed out, out of adjustment, dirty or rusted glands).

Information PMP 7200.RST.004 Rev. 5 Page 60 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61

~

Cables or leads (unsecured, worn or frayed insulation, improper terminations).

Motors or generators (dirty, brush rigging pigtails broken, carbon dust, excessive noise or vibration, ground straps loose or missing).

Preservation (rust, corrosion, missing or damaged insulation or

- lagging).

Check valves (oscillating lever, banging, stuck open).

MOVs (lubricant leaks, missing T-Drains).

Valves (dried grease caked on stem, packing or stem leaks, bent stem).

3.9 The following is a general list of additional inspection items that apply to both mechanical and electrical equipment:

3.9.1 Mechanical or Electrical Equipment

~

Identify inadequate or degraded structural components.

~

Inspect system piping for evidence of water hammer, severe transients, or improper venting.

Damaged supports, base plate grouting, anchors (pulled-out or deformed) are to be identified for further root cause analysis.

~

Inspect for,unauthorized loads supported from cable trays, coiiduits or piping systems,

~

Identify undocumented system modifications.

~

Identify damaged heat trace and damaged or missing insulation.

Note piping exhibiting cyclical vibration for possible high cycle fatigue concerns.

Safety postings, radiological postings (properly positioned, legible and understandable).

4

Information PMP 7200.RST.004 Rev. 5 Page 61 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM

..Attachment 7 SYSTEM READINESS REVIEW PROGRAM (SYSTEM WALKDOWNGUIDELINES)

Pages:

54-61 3.10 The System Manager is to ensure that team members record identified walkdown issues in Walkdown Reports, and during Phase 1 on the Attribute Assessment forms.

The System Manager is responsible to ensure that any discrepancies have appropriate follow-up corrective actions initiated to resolve any identified issues.

Information

~

PMP 7200.RST;004 Rev. 5 Page 62 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIAFOR WORK INCLUDED IN.

RESTART SCOPE Pages:

62-68 NOTE CHANGES TO THE RESTART CRITERIA REQUIRE THE APPROVAL OF THE SENIOR MANAGEMENTREVIEW TEAM (SMRT) 1.

Review the open corrective action item against the Restart Screening Criteria. The Restart Screening Criteria is used to identify scope of items reviewed during Phases 1, 2, and 3. Ifnone of the criteria apply, then the action item is not applicable to the restart effort. Ifthe restart screening criteria applies the System Manager should determine when the action item must be completed to support safe and event free restart and reliable power operation.

Program owners and functional area managers (or their designees) shall also follow the guidance in this attachment for scoping non system-specific programmatic and functional area SIDS items when directed by the Director of Restart.

In this capacity; these owners/managers/designees function, in effect, as the System Manager for these items.

Restartl Activities required to be completed prior to entering Startup/Power Ascension of Unit 1. This classification includes necessary restart and power ascension testing activities Restart2 Activities required to be completed prior to entering Startup/Power Ascension of Unit 2. This classification includes necessary restart and power ascension testing activities.

Post Restartl Activities which should be completed on a schedule consistent with the Unit 1 normal plant work controls process.

Post Restart2 Activities which should be completed on a schedule consistent with the Unit 2 normal plant work controls process.

Not Applicable Activities that are not required to be completed.

2.

Enter descriptive text that describes a specific issue in the ISSUES box. This is a searchable text field ofup to 255 characters and is designed to assist the System Managers in readily retrieving information on associated issues.

Some examples are packing leaks, oil leaks, housekeeping, etc.

Information PMP 7200.RST.004 Rev. 5 Page 63 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIA FOR WORK INCLUDEDIN RESTART SCOPE Pages:

62-68 3 Ifthe issue is system-specific but also is related to an existing station program, consider identifying the PROGRAM by scrolling, then selecting the most appropriate program source and dragging the appropriate program(s) into the RELATED PROGRAM box.

This information may help program owners identify programmatic weaknesses.

Examples of program s'ources include High Energy Line Break, Appendix R, Station Blackout, etc.

For new items placed in the "No system entered" bin in SIDS, the ESRR group willreview the item and assign it to a system or programmatic and/or functional area. Ifa needed program is not listed, contact the SIDS data base coordinator.

Information PMP 7200.RST.004 Rev. 5 Page 64 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIA FOR WORK INCLUDEDIN RESTART SCOPE Pages:

62-68 4.

Identify the applicable Restart Screening Criteria as outlined in this attachment.

Enter this criteria in SIDS by scrolling and selecting the most appropriate criteria (e.g.

RESTART1A, RESTART2A, RESTART2B, etc.).

5.

Identify the applicable mode restraint for the item by scrolling, then selecting the appropriate mode (e.g., 1, 2, 3, 4, etc.).

6 Complete the INITIALCOMMENT field in the INITIALREVIEW screen.

The comment field should contain specific reasons for the item being included or excluded from the restart effort. Ensure that the information is accurate and concise, technically justifying from a design basis view point, the SCOPE and RESTART CRITERIA selected.

The COMMENT field must be comple'ted prior to System Manager approval.

Note: The FINALCOMMENT field on the FINALREVIEW screen is to be completed prior to the final readiness review presentations.

This field is to justify that the work completed willsupport restart readiness.

7.

During Phases 1, 2, and 3, the System Manager willapprove SIDS items as Restartl, Restart2, Post Restartl, Post Restart2, or N/A. The System Manager willsignify his approval of the scope by "Approving" the scope and justification comments in the Initial System Manager Approval Box in SIDS.

Later, during Phase 3, ifa restart item is not completed, the System Manager willdenote the item as an "Exception" in the Final System Manager Approval Box in SIDS. Ifan item is satisfactorily completed, the System Manager willdenote his "Concurrence" in the Final System Manager Approval Box in SIDS.

8.

During Phase 4, items willbe scoped as WCP or RESTART1 or RESTART2.

9.

Additional information is available in the Systems Indexed Data Base Systems Operator's Manual.

J

Information PMP 7200. RST.004 Rev. 5 Page 65 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIA.FOR WORK INCLUDEDIN RESTART SCOPE Pages:

62-68 RESTART SCREENING CRITERIA Issues willbe evaluated against criteria 1 through 9. Ifcriteria 1 through 7 do not apply, then categorize the issue using criteria 8 or 9.

Issues shall be resolved prior to restart ifthey are:.

1)

Nuclear Safety Required to address a nuclear safety issue.

Issues may be classified as follows:

a)

Items that could result in significant personnel radiation exposure, radioactivity release or effluent discharge, in excess of limits.

b)

Reduces cumulative deficiencies, backlogs or conditions that, in the aggregate, are evaluated to have significant negative impact on nuclear safety.

(Not applicable to individual work issues).

2)

Operability Required to address an operability issue.

Issues may be classified as follows:

a)

Eliminates an existing component failure, deficiency, or condition that could result m operation in, or entry to, an LCO action statement ifleft uncorrected.

b)

Would result in failure or inability to perform a required surveillance test during the current outage or the following operating cycle in accordance with the plant technical specifications.

c)

Would increase the risk to operation or safety associated with performing a surveillance.

Information

'MP 7200.RST.004 Rev. 5 Page 66 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIAFOR WORK INCLUDEDIN

'ESTART SCOPE Pages:

62-68 d)

Testing or retesting that must be performed to certify'system or component operability, including testing on systems or components during power ascension that result in breeching a system regardless of the work being classified as a restart issue or not.

e)

Reduces cumulative deficiencies, backlogs or conditions that, in the aggregate, are evaluated to have significant negative impact on operability. (Not applicable to individual work issues).

3)

Design Basis Required to restore acceptable design margin or conformance. with the design basis.

Issues may be classified as follows:

a)

Corrects design basis deficiencies; i.e., deficiencies in safety-related or technical specification equipment not in conformance with design basis documents.

4)

License and Licensing Basis Required to resolve unreviewed safety questions (USQs) or to restore conformance with the license, license conditions or licensing basis.

Issues may be classified as follows:

a)

Restores licensing basis deficiencies to conforming conditions.

b)

TechmcaI Specification changes to support safe plant operation.

5)

Licensing Commitments Required to meet restart licensing commitments such as A/E inspection and related programmatic issues, and confirmatory action letter issues.

Issues may be classified as follows:

a)

Resolves existing deficiencies or conditions that would result in the failure to meet a license requirement or a restart commitment to an outside agency.

Information PMP 7200.RST.004 Rev. 5 Page 67 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIA FOR WORK INCLUDEDIN RESTART'SCOPE Pages:

62-68 6)

Configuration Management Required to address an organizational, programmatic, or process deficiency that could prevent maintenance of adequate design margins or conformance with the design or licensing basis.

Issues may be classified as follows:

a)

Corrects deficiencies in configuration management programs, processes, engineering analysis codes, or operating, maintenance, or test procedures that have a reasonable probability of affecting equipment OPERABILITY.

7)

Reliability Required to address significant equipment material condition deficiencies singly or in aggregate; or repetitive failures that could affect safety system availability, impact plant reliability, or reduce the ability of operators to operate the plant safely.

Issues may be classified as follows:

a)

Reduces cumulative deficiencies, backlogs or conditions that, in the aggregate, are evaluated to have significant negative impact on safety system availability or reliable plant operation.

(Not applicable to individual work issues).

b)

Restores degraded critical components or conditions that could result in a plant transient, power reduction or shutdown.

c)

Resolves"conditions that have resulted in repetitive safety system or equipment failures.

Information PMP 7200.RST.004 Rev. 5 Page 68 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM CRITERIA FOR WORK INCLUDEDIN RESTART SCOPE Pages:

62-68 Issues that are not classified as restart should be classified as follows:

8)

Post Restart Issues a)

Issue can be scheduled for a subsequent outage.

b)

Issue can be readily worked on line, does not affect safe and reliable operation, does not represent a significant challenge to Maintenance Rule Goals or LCO allowed outage time, and does not impair operations necessary to perform surveillance or monitoring.

c)

Issue is classified as minor maintenance, or housekeeping, and does not affect plant operation.

d)

Issue is an administrative issue.

e)

Issue is a documentation deficiency that has no safety impact.

9)

Industrial Safety Concern NOTE:

Industrial safety concerns willnot be classified as "restart" because the priority and resolution of these concerns willbe addressed under the established work control process priorities and scheduling.

Although an industrial safety issue is not classified as restart, it willbe worked promptly, commensurate with the safety risk.

~td~

Information PMP 7200.RST.004 Rev. 5 Page 69 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM PHASE 2 OUTAGE SCOPE APPROVAL PROCESS Pages:

69-69 NEW WORK SYSTEM MANAGER ENGINEERING SUPERVISOR Allother new work Field work items-System Readiness Review Board e.g. AR s/JO s Outage Scope Management Team (See Note)

SIDS update to NPM Scheduling NOTE:

SRRB (or subcommittee thereof ) reviews the scoping of these items separately.

SIDS is then updated to reflect SRRB comments by the System Manager.

Information PMP 7200.RST.004 Rev. 5 Page 70 of 101

" EXPANDED SYSTEM READINESS REVIEW PROGRAM 0 RESTART REQUIRED SCOPE DEFERRAL FORM Pages:

70- 70 UNIT:

DATE:

SYSTEM:

DOCUMENT TYPE:

(e.g., Condition Report, Action Request)

KEY I. D:

(e.g., Condition Report or Action Request Number)

Item

Description:

InitialTechnical Justification for Restart Scope Designation (ensure the original basis for scoping the item as required for restart is addressed);

Technical Justification for Restart Deferral:

New Scheduled Completion Date:

(Scope Addition/Deletion form attached ifapplicable)

Originator Date:

System Manager Date:

Designated Ops. Rep.

Engineering Supervisor Date:

Date:

Nuclear Licensing Manager/

Director of Regulatory Affairs Date:

System Engineer Manager Date:

Date:

PORC Mtg. ¹ Date:

Information PMP 7200.RST.004 Rev. 5 Page 71 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM

. Attachment 11 EXPANDED SYSTEM READINESS REVIEW CLARIFICATIONSHEET Pages:

71-71 S stem Mana er A royal Concur Item closed and work completed satisfies restart requirements, or for those post restart items that are not included in the aggregate impact.

Except Open restart items (including those items that are "work complete" but not administratively closed), or items that are closed but do not satisfy restart requirements..

Post Restart Deferred Denoted on items associated with a component that has two (2) or more post restart deferred items, excluding PM post restart items.

Restart Required Deferred Denoted on items with deferred scope that were initially

approved, as restart required.

These items must be accompanied by a Restart Required Scope Deferral Form (Attachment 10).

Information PMP 7200.RST.004 Rev. 5 Page 72 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 2 INITIALEXPANDED SYSTEM READINESS REVIEW REPORT Pages:

72-74 INITIALEXPANDED SYSTEM READINESS REPORT COVER SHEET SYSTEM TITLE SYSTEM REVIEWERS System Manager Signature / Date Operations Representative

  • Signature./ Date Licensing Representative

~

Signature / Date Engineering Supervisor Signature / Date ESRR Manager/Coordinator

. Signature / Date System Readiness Review Board.

Signature / Date Plant Operations Review Committee PORC MTG. ¹ Chairman, Signature / Date,

~ These signatures maybe obtained by routing the report to both individuals simultaneously.

Retain copies of both signatures with the original of the report in the SRRB meeting minutes.

Information PMP 7200.RST.004 Rev. 5 Page 73 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 2 INITIALEXPANDED SYSTEM READINESS REVIEW REPORT Pages:

72-74 INITIALEXPANDED SYSTEM READINESS REVIEW REPORT FORMAT EXECUTIVE

SUMMARY

1.0 INTRODUCTION

1.1 Purpose 1.2 Scope and Approach (Include specific identification of the system's safety and accident mitigation functions) 2.0 RESULTS AND CONCLUSIONS 2.1 Summary of Attribute Assessments 2.2 Suimnary of Review of SIDS Items 2.3 Summary of Open Items 2.4 Observations and Conclusions (including recurring items judged to need further extent of condition determination) (see step 4.3.10a) 3.0 ATIRIBUTEASSESSMENTS 3.1 Assessment Matrix 3.2 Attribute Assessments and review of system functions.

3.3 Discrepancies 4.0 WALKDOWNRESULTS 4.1 Walkdown Scope 4.2 Observations 5.0 REVIEW OF SIDS ITEMS 5.1 Review of Open Items (Summary Information)

0

Information PMP 7200.RST.004 Rev. 5 Page 74 of 101

~,

EXPANDED SYSTEM READINESS REVIEW PROGRAM 2 INITIALEXPANDED SYSTEM READINESS REVIEW REPORT Pages:

72-74 5.2 Revie'w of Closed Items (Summary Information)

6.0 REFERENCES

6.1 ENCLOSURES

Attribute Assessment Forms : :

Restart Items (SIDS)

Post-restart Open Items (SIDS) :

Review of Closed Items From SIDS :

System Boundaries :

Walkdown Plan 6.2 FIGURES AND TABLES Figure 1:

System Boundaries Table 1:

Final System Readiness Review Assessment Matrix Table 2:

Attribute Assessment Summary Table 3:

Assessment Discrepancies Recommended for Corrective Action Prior to Restart Table 4:

Assessment Discrepancies Recommended for Closure Post Restart

Information PMP 7200. RST.004 Rev. 5 Page 75 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM A~ichment 13 FINALEXPANDED SYSTEM READINESS REVIEW REPORT Pages:

75-77 FINALEXPANDED SYSTEM READINESS REPORT COVER SHEET SYSTEM TITLE DATE SYSTEM REVIE%ERS System Manager Date Operations Representative

~

Date Licensing Representative

~

Date Engineering Supervisor Date ESRR Manager/Coordinator Date System Readiness Review Board Date Plant Operations Review Committee Date PORC MTG. ¹

~ These signatures maybe obtained by routing the report to both individuals simultaneously.

Retain copies of both signatures with the original of the report in the SRRB meeting minutes.

  • A< g L

Information PMP 7200.RST.004 Rev. 5 Page 76 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 3 FINALEXPA'NDED SYSTEM READINESS REVIEW REPORT Pages:

75-77 FINALEXPANDED SYSTEM READINESS REVIEW REPORT FORMAT 1.0 OVERVIEW 1.1 Summary of items closed since the initial report issuance 91-18 Operability Determinations (list each item)

Engineering Evaluations (list each item)

DCPs (list each item)

I Action Requests (list each item)

Condition Reports (list each item)

NRC Commitment Data Base items (list each item)

Operator Workarounds (list each item)

Outage Required PMs 2.0 OPEN ITEMREVIEW 2.1 Items 91-18 Operability Reviews (list each item)

Engineering Evaluations (list each item)

DCPs (list each item)

Work Requests (list each item)

Condition Reports (list each item)

Commitment Data Base (list each item)

Operator Workarounds (list each item) k

'I

Information PMP 7200.RST.004 Rev. 5 Page 77 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM

, Attachment 13 FINALEXPANDED SYSTEM READINESS REVIEW REPORT Pages:

75-77 2.1 Items (Continued)

Outage Required PM's that willbecome overdue prior to next planned outage 2.2 Restart Scoping 2.3 Schedule for Resolution of Open Items 3.0 DESIGN AND LICENSE BASIS ISSUES

SUMMARY

Explain the significance of each issue (one or two sentences on safety, risk, or system operability/reliability impact.

Discuss what plans(s) is in place for resolution of each issue.

Include when the issue is scheduled to be resolved.

4.0 WALEDOWN 4.1 Walkdown purpose and scope 4.2 Walkdown Team 4.3 Walkdown Results 4.4,Conclusions 4.5 Restart Scoping 5.0 AGGREGATE IMPACTOF DEFERRED WORK

Attachment:

Marked up drawings showing components with multiple (two or more) Post-restart or restart deferred work items.

Information PMP 7200.RST.004 Rev. 5 Page 78 of 101

'XPANDED SYSTEM READINESS REVIEW PROGRAM 4 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED RESULTS Pages:

78-82 ESRR Program Coordinator Date ESRR Program Manager Date Director, Engineering Restart Date System Readiness Review Board Date Plant Operations Review Committee PORC Mtg. ¹ Date

Information PMP 7200.RST.004 Rev. 5 Page 79 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 4 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED RESULTS Pages:

78-82 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED RESULTS FORMAT

1.0 INTRODUCTION

AND PURPOSE 1.1 Introduction 1.2 Purpose 2.0 SCOPE AND STRUCTURE FOR LEVEL 1 ESRRs 2.1 Overall Approach and Scope 2.2 System Prioritization 2.3 Structure of Level 1 ESRR Teams 2.4 Vertical Slice Methodology 2.5 Screening of Open Items for Restart Requirements 2.6 Reviews and Self-Assessments 3.0

SUMMARY

OF PHASE 1 RESULTS 3.1 Vertical Slice Results and Characterization of Findings 3.2 Screening ofOpen Items 3.3 Walkdown Results

4.0 ASSESSMENT

OF RESULTS BYTOPIC AREA 4.1 Lessons learned to be included in Level 2 ESRR 4.2 Identification of Potential Programmatic Issues

Information PMP 7200.RST.004 Rev. 5:

Page 80 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 4 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED RESULTS Pages:

78-82

5.0 CONCLUSION

S 5.1 System Readiness 5.2 Potential Programmatic Issues

6.0 REFERENCES

APPENDICES A

RESTART ISSUES, SELECTION/SCREENING CRITERIA B

EVALUATIONOF DISCREPANCIES BY TOPIC AREA Topic Area 1: Electrical Calculations and Analysis Topic Area 2: I&C Calculations and Analysis Topic Area 3: Mechanical &Structural Calculations and Analysis Topic Area 4: Accident Analysis Topic Area 5: Drawings Topic Area 6: Logic Diagrams Topic Area 7: Configuration Management Topic Area 8: Specifications Topic Area 9: DBD Topic Area 10: Change Documentation/50.59 Reviews Topic Area 11: Temporary Modifications/Bypasses Topic Area 12: FSAR Review Topic Area 13: TS and Bases

Information PMP 7200.RST.004 Rev. 5 Page 81 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 4 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED RESULTS Pages:

78-82 Topic Area 14: Licensing Commitments Topic Area 15: Notices / Bulletins/Generic Letters Topic Area 16: Procedures Topic Area 17: Operator Workarounds Topic Area 18: Industry Operating Experience Reviews Topic Area 19: Maintenance Procedures Topic Area 20: Vendor Technical Information Topic Area 21: Preventive Maintenance Topic Area 22: Surveillance and Periodic Tests and Inspections Topic Area 23: ISVSection XIIST Topic Area 24: As-BuiltVerification Topic Area 25: Control Room Drawings Topic Area 26: Surveillance Programs Topic Area 27: Corrective Actions

~P Topic Area 28: QA Audits and Self Assessments Topic Area 29: Training Lesson Plans Topic Area 30: Open Items (Backlog)

Topic Area 31: Strategy Documents

Information PMP 7200.RST.004 Rev. 5 Page 82 of 101 EXPA'NDED SYSTEM READINESS REVIEW PROGRAM 4 EXPANDED SYSTEM READINESS REVIEWS INTEGRATED RESULTS Pages:

78-82 C

GROUPING OF ESRR-IDENTIFIED ITEMS BY TOPIC AREA FIGURES 2.1 Graded Approach for Enh'anced System Readiness Review 2.2 Typical Topic Areas for Enhanced System Readiness Review Vertical Slices 2.3 Enhanced System Readiness Review Plan 2.4 Level 1 Enhanced System Readiness Reviews 2.5 Typical System Assessment Matrix 4.1 Topic Review Sutmnary - Level 1 Systems Checks and Discrepancies 4.2 Topic Revjew Summary - Level 1 Systems Discrepancies as Percent of Checks 4.3 Issues by Topic Areas - Level 1 Systems by severity-4A Issues by Topic Area - Level 1 Systems (Restart Recommended Issues Only)

TABLES 3-1 Summary Statistics for Level 1 System Reviews 3-2 Summary of Areas Covered During the Walkdowns

Information PMP 7200.RST.004 Rev. 5 Page 83 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM 5 SYSTEM WALKDOWNREPORT Pages:

83-83 Date ofWalkdown:

System Manager/Team Leader:

~Setem:

Pu ose of Walkdown:

Provide a brief description of the purpose of the walkdown.

Walkdown Sco e:

Provide an overall synopsis as to the scope of the walkdown, primary objectives, time spent'n the walkdown, total number of all deficiencies noted as well as noting ifany operability concerns were noted.

Walkdown Tea Provide a listing of the walkdown team members as well as their respective organizations.

Walkdown Results:

Provide an overall characterization as to the items identified, and safety or operability concerns, etc.

==

Conclusions:==

Provide an overall assessment of the system condition based on observations.

Summarize any specific need for improvements and all follow-up actions being pursued.

Information PMP 7200.RST.004 Rev. 5 Page 84 of 101 EXPA'NDED SYSTEM READINESS REVIEW PROGRAM 6 SYSTEM READINESS AFFIRMATION REPORT Pages:

84-84 1.0 THE READINESS AFFIRMATIONREPORT WILLINCLUDETHE FOLLOWINGINFORMATION 1.1 Current system License Change Request(s).

1.2 Current operator workarounds.

1.3 Current corrective actions required of control room equipment.

1.4 Currently installed T-Mods.

1.5 Active operability determinations and JCOs, with the 10CFR50.59 for each OD or JCO.

1.6 The remaining open "Exceptions" items and any "Exceptions" identified during the affirmation process.

Exceptions are remaining open restart required items.

1.7 An Operations priorities list compiled from or identical to the Focus List or Operations Priorities Addendum List (but not necessarily limited to these lists) for the system.

1.8 Reference Initial Expanded System Readiness Review Report 1.9 Reference Final Expanded System Readiness Review report.

1.10 Reference the system tests per the System Test Plan.

0

Information PMP 7200.RST.004 Rev. 5 Page 85 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 SYSIKMASSESShKNT hIATRIX MAJOR TOPICS DESIGN BASIS LICENSING DOCUMENTS OPERATIONS mi~~~NCP.

SURV PHYSICAL PLANT 'ROGRAMS, PROCESS 4 PROCEDURES 5

6 7

8 9

10 11 12 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ASSESShKNT ATTRIUTES K0 K0

Information PMP 7200,RST.004 Rev. 5 Page 86 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 OVERVIEW The following guidance for each of the 31 major topics in Figure 1 is provided regarding the types of documents and sources of information to be used and to provide a consistent definition of the topic areas for grouping and documenting the results.

Individual reviewers willuse their experience and that of the ESRR Team to determine the specific documents and sources of information to be assessed.

Completed scope of the previous System Readiness Reviews should be taken into account.

DESIGN BASIS Electrical Calcs/Analysis:,Calculations related to motors, electrical devices, circuits, and associated power supplies for system components shall be reviewed.

The reviews should assess the appropriateness of design inputs, assumptions, consistency with as-built configuration, and general approach.

Also, calculation results should be verified for appropriate use in other design basis documents.

The potential effect ofmodifications on the emergency electrical load calculation, including load sequencing, should be considered.

In addition, fuse coordination shall be addressed against the requirements ofIEEE 308.

2 I&CCalcs/Analysis: Calculations related to the performance, set points, and stability ofI&C components and loops for system components shall be reviewed.

The scope of the reviews should be

. similar to the electrical calculations.

In addition, reference 6.5 identifies a potential concern with instrument uncertainty calculations, such as due to dynamic fiow effects, and with lack of trending of instrument drift and use of unverified driftvalues provided by the equipment vendors.

3 Mech and Struct Calcs/Analysis: Calculations related to hydraulics, heat transfer, equipment/support loads, equipment/pipe stresses, and other mechanical performance issues related to system components shall be reviewed.

The scope of the reviews should be similar to the electrical calculations.

ot'

Information PMP 7200.RST.004 Rev. 5 Page 87 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85 -94 4.

Accident Analysis: Analysis of UFSAR Chapter 14 events shall be reviewed for assumptions regarding system configuration, performance and conditions.

5.

Drawings:

Controlled drawings documenting system design, configuration, layout, and conformance to programs (e.g.,

Appendix R, testing, and EQ) shall be reviewed for system design basis information and system interaction/dependency information.

Drawings that are excluded from this topic are logic diagrams (covered in Topic 6), Control Room drawings (covered in Topic 25), and vendor drawings (covered in Topic 20).

6.

Logic Diagrams: The logic diagrams shall be reviewed for system design basis information and system interaction/dependency information.

7.

Configuration Management:

Cross-referenced documents shall be verified to be current, applicable, and appropriate.

In particular, ESRR teams shall specifically review several input changes looking for a lack of integration between calculations, accident analysis assumptions, design values, design basis documents, system description and normal and emergency operating procedures.

Additionally, the facilitydata base should be checked for accuracy and consistency with design requirements.

8.

Specifications:

Equipment design, procurement, and installation

.specifications shall be reviewed for consistency of system design basis information and for adherence to code and safety requirements.

General design specifications shall also be reviewed for system design basis information.

9.

DBD: Related design basis documents shall be reviewed for system design basis requirements, identification of possible cross-referenced documents, and appropriate applicability. Potential vulnerabilities include identification of and compliance with single failure criteria.

Adequate closure of open items identified during preparation of the DBDs should be considered.

Based on the results in reference 6.5, this topic area should be a focus area for the ESRR.

Information ',

PMP 7200.RST.004 Rev. 5 Page 88 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM SYSTEM ASSESSMENT MATRIX MAJOR TOPICS "Pages:

85 -94 10.

Change Documents/50.59 Reviews: Change documents, including DCPs, Component Evaluations (CEs) and UFSAR changes, shall be assessed for completeness, consistency with the system safety and accident mitigation functions as defined in the design and licensing basis, appropriate consideration of interdisciplinary impact/input, and effective follow through (changes made or posted against the appropriate documents).

50.59 screens and 50.59 safety reviews shall be reviewed to assess whether the change may have resulted in a current plant configuration or operation that is outside the design or licensing basis, Cook Plant has, in the past, not performed some 50.59 screens when required because station personnel did not recognize that they were changing the facility as described in the UFSAR. As part of the ESRR, teams should review past 50.59 screens associated with change documents being reviewed to ensure that an excessively liberal interpretation of the words "system as described in the UFSAR" was not used.

See NEI 9647 for additional guidance and current industry standards.

L a el+

Information

'PMP 7200.RST.004 Rev. 5 Page 89 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 11.

Temporary Modifications/Bypasses:

Temporary modifications and "bypasses" shall be reviewed to verify that they were evaluated against appropriate design basis information and do not result in an unreviewed safety question.

Based on the results of reference 6.5, "Bypasses" should be a focus area for the ESRR. Additionally, teams should be alert for engineering evaluations, action requests, partially installed modifications, and other changes to ensure that necessary screenings were done in each case, Cook Plant has identified 23 specific processes with a potential to bypass the 50.59 process as follows:

Engineering Specifications Action Request/Job Orders Drawing changes Operability determinations Technical Direction Memos NPM (Engineering)

Evaluations Mechanical Engineering Memo Electrical Engineering Memos Design Change Determination Condition Report Receipt Inspection Practices Design Standards

~

Design Change Addenda

~

Setpoints

~

DCDIRs

~

Technical data books

~

PMI-5023 addressing plant fabrication and repairs

~

Dedication Plans

~

Old clearances/Caution Tags

~

Open Items Log

~

Work Arounds/Watch List

~

Temporary Operator Aids

~

Permanent Operator Aids These items should be reviewed in assessing the health of the 50.59 process for the system.

Also, the temporary modification shall be assessed to assure the duration is not excessive.

50.59 applicability evaluations and 50.59 reviews shall be reviewed to assess whether the temporary modifications may have resulted in a current plant configuration or operation that is outside the regulatory design basis or licensing basis.

Abandoned Equipment without a 50.59 should also be considered.

Information PMP 7200.RST.004 Rev. 5 Page 90 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 LICENSING DOCUMENTS-12.

UFSAR Review: Chapters related to the system, interfacing systems (e.g., power distribution, I&C, and support systems),

accident analysis, and applicable design criteria shall be reviewed for regulatory design basis and licensing basis information.

Scope of this review should take into account the ongoing UFSAR validation effort (which was initiallyrestricted to 21 systems of the original SRR).

Pending UFSAR changes should be assessed and selected UFSAR questions and requirements should be validated against installed equipment specifications and operational/test procedures as applicable.

13.

TS/Bases: LCOs, Surveillance requirements, and their bases for the system and its components shall be reviewed for regulatory design basis and licensing requirements Other appropriate sections (e.g.,

for interfacing systems, EQ-related, and containment isolation-related) should also be reviewed for system/component regulatory design requirements.

14.

Licensing Commitments: Open items from NRC inspections, commitments in the license (and not in the UFSAR or TS), and other commitments made to the NRC by docketed correspondence shall be reviewed for additional licensing basis requirements.

For example, reference 6.5 notes that not all systems may meet the criteria of the response to LER 97-021-01 regarding single failure interpretation. A list of system specific licensing commitments willbe provided to the ESRR by the Licensing Basis Review Group.

15.

Notices/Bulletins/Generic Letters: NRC generic communications and evaluations and responses to them related to the system shall be reviewed for additional regulatory design basis requirements and information.

~ t

~

Information PMP 7200.RST.004 Rev. 5 Page 91 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MA'i'RIX MAJOR TOPICS Pages:

85 -94 OPERATIONS 16.

Procedures:

Operating and emergency operating procedures related to the system shall be reviewed for conformance with design basis information. Based on the results of reference 6.5, Emergency Operating Procedures should be a focus of the ESRR.

17.

Operator Workarounds: Operator workarounds shall be reviewed for impact on system operation or performance.

The impact should be assessed for conformance with the design basis information.

18.

Industry Operating Experience Reviews: Industry experience reviews related to the system shall be assessed and compared to current design basis information.

Specifically, Operating Experience information from the INPO Industry Database and generic NRC information shall be reviewed and effectiveness of application/consideration reviewed.

Based on the results of reference 6.5, industry operating experience should be a focus of the ESRR. [Ref. 6.15t MAIN'IKNANCE'aintenance Procedures:

Procedures for the overhaul of or general repair of system components shall be reviewed for appropriate use of and conformance with design basis information. Also,

. completed work documentation, including any applicable data sheets, should. be. assessed for adequacy of the use of the procedure.

This topic does not cover preventive maintenance activities (covered in item 21) and surveillance type procedures (covered in item 22).

20.

Vendor Technical Information: Vendor technical manuals, vendor drawings, and design data forwarded by the vendor related to system components shall be reviewed for conformance with design basis information.

Based on the results of reference 6.5, vendor technical information should be a focus area of the ESRR.

Information PMP 7200.RST.004 Rev. 5.,

Page 92 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 21.

Preventive Maintenance: Regularly scheduled maintenance work items to assure proper equipment operation, including calibrations, lubrication, and filter flushing/changing, shall be reviewed for appropriate schedules, timeliness of performing the activity, and appropriate use of materials, Procedures for preventive maintenance scheduling and documentation shall also be reviewed.

SURVEILLANCE 22.

Surveillance and Periodic Tests & Inspections: Each ESRR team shall, in the course of its assessment, verify that design basis safety and accident mitigation functions of the system are validated and verified, either by periodic testing or by engineering calculation for those portions of the system that cannot be tested periodically.

Procedures for tests and inspections required to verify compliance with TS Surveillance Requirements for system components shall be reviewed to assess compliance with the TS and its Bases, appropriate methodology, and consistency with other design basis information. Results of the most recent surveillance and periodic performance tests shall also be reviewed for compliance with design basis information and for the presence of adverse trends that have not been addressed.

23.

ISI and Section XIIST: Procedures forInservice Inspection and Inservice testing of system pumps and valves and other performance tests (e.g., heat exchanger performance tests, MOV tests, special pump/system performance tests) shall be reviewed for

. appropriate use of and conformance with design basis information.

Results of.the. most recent tests shall also be reviewed for compliance with design basis information.

~ ~

+=

I N ~

Information PMP 7200.RST.004 Rev. 5 Page 93 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 PHYSICAL PLANT 24.

As-BuiltVerifications: Walkdowns of the system to verify conformance with design basis information, system layout against the drawings, system condition, component configuration, interactions with other systems, and other characteristics shall be performed based on checklists developed from the documentation reviews.

These walkdowns should consider the adequacy of system vent provisions and how the provisions are incorporated into system procedures.

25.

Control Room Drawings (i.e. the OP-series and the 9800 series drawings) shall be reviewed for conformance with design basis information. Also, the timeliness of the incorporation of changes to the current drawings should be assessed.

26.

Surveillance Programs: Surveillances not associated with Items 22 and 23, such as Erosion/Corrosion, Fire Protection, or HELB, shall be reviewed for direct or indirect applicability to the system and its components and conformance with design basis.

Results of the most recent surveillances should be assessed against design basis information.

C Information PMP 7200.RST.004

'ev. 5 Page 94 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 1 Addendum SYSTEM ASSESSMENT MATRIX MAJOR TOPICS Pages:

85-94 PROGRAMS, PROCESS AND PROCEDURES 27.

Corrective Actions: Closed Condition Reports (CRs), Maintenance Action Requests, NPM Engineering Evaluation Requests, and other corrective action type reports related to the system shall be assessed for appropriate evaluation of problem against design basis, generic considerations, appropriate resolution, timeliness of resolution, and adverse trends.

Included in this review shall be an assessment to determine ifany existing conditions should be the subject of an operability Determination, 50.59 screen or justification for continued operation.

(See Generic Letter 91-18 for further details).

28.

PA Audits and other Assessments:

PA audits, EDSFIs, SSFIs, and other completed similar system or program assessments related to the system including Maintenance Rule Risk Significance determination shall be reviewed to assess effectiveness of the audit, appropriate resolution, including addressing extent ofcondition, timeliness of resolution, and adverse trends.

Implementation of any generic lessons learned from system - specific SSFIs and the 9/97 IST self assessment should be evaluated.

29.

Training Lesson Plans: Operations and engineering training lesson plans for the system shall be reviewed for consistency with design basis information and operating procedures.

30.. Open Items (Backlog): Maintenance, engineering, and operations open itemsxelated to the system shall be evaluated with respect to the current Restart Criteria within the SIDS data base; 31.

Strategy Documents: Some Cook Plant systems had specific strategy documents prepared to articulate actions taken in response to NRC Identified Issues.,

ESRR teams shall review these documents and mark them up to refiect any changes needed to fully address issues ofextent of condition, t'ransportability to the other unit, or to ensure a technically accurate and thorough approach to resolving the issue.

This markup should be brief but should focus on identifying major unaddressed or unresolved issues in the system that may impact on resolution of the issue addressed by the strategy document.

Information PMP 7200.RST.

Rev. 5 Page 95 of 101 EXPANDED SYSTEM READINESS REVIE% PROGRAM Figure 2 SYSTEM ASSESSMENT MATRIX EXAMPLE-AUXILIARYFEEDWATER SYSTEM Pages:

95 -99 SYSrEM ASSESSMENT MATRIX EXAMPLE-AUXILIARYFEEDWATER SYSTEM MAJOR TOPlCS DESIGN BASIS LICENSING DOCUMENTS OPERATIONS MAINTENANCE SURV PHYSICAL PROGRAMS, PROCESS PLANT Ec PROCEDURES I

2 5

6 9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Cl 9

AFW01 AFW02 AFW03 AFWOS AFWC01 AFWC02 ASSESSMENT ATIRIBVIKS WATERSUIHY l4JKRDUVEHANDTD.AFWmIS X

'lURHNEANDSIEAM SURD AFWIMWCKNIKLVALVES HHNGDBXiN CXÃl'AINMENrKXAlKN X

X X

X X

X E

K0 X

X X

X X

X X

X X

X X

AFWC07 AFWC08 AFWC09 AFWC10 AFWCl1 AFWC12 AFWC13 HKiHHIERGYIJNEBREAKS BA1KCblBIPALQIALRKhlKN AHEÃmR SNGZFAILURECRIIERIAICMF

(%&0

'IEMP.HRCISCNSYS(XBIAB8LTY HCIHINALHA7AKS X

X X

X X

X X

X X

X X

X X

Information PMP 7200.RST.004 Rev. 5 Page 96 of 101 EXPA'NDED SYSTEM READINESS REVIEW PROGRAM Figure 2 Addendum SYSTEM ASSESSMENT MATRIX EXAMPLE-AUXILIARYFEEDWATER SYSTEM ATTRIBUTESELECTION GUIDANCE Pages:

95-99 (typical example only - not a complete treatment of the AFW system critical attributes or design considerations)

Note:

System attributes are selected based on a thorough research of the system design basis.

Attributes chosen for detailed review should be those vital to accomplishing the various safety and accident mitigation functions as defined in the design and licensing basis for the specified mission times (where applicable) and in the design plant conditions. Cook Plant has sometimes overlooked the critical functions of passive components (such as tanks, strainers, spray headers) to assure that appropriate performance has been demonstrated by testing, calculatioh.

or analysis.

Additionally, such passive components have sometimes not received thorough materiel condition inspections to assure that the component contains the heat tracing, instrumentation, and other necessary features are functional such that the component remains operable in all required modes.

ESRR teams shall assess obvious passive components for these types of issues.

SYSTEM FUNCTIONS BEING ASSESSED AFW01 Water Supply: An adequate water supply inventory is required for the AFW system to remove decay heat from the reactor coolant system (RCS) following events resulting in a loss ofmain feedwater; Issues related to water volume and level'indication, switchover to other sources, and overpressure/vacuum pressure are to be assessed.

Included in this assessment should be a review of the capability of backup water supplies to function as designed.

AFW02

~ Motor-driven and turbine-driven auxiliary feedwater pumps (list component IDs): the AFW-pumps are critical components for delivery of the required AFW flow. Issues related to pump performance, NPSH, mitiitnum flow requirements, motor and power supplies, power supply reliability, and design

'equirements are to be assessed.

AFW03 Initiation and control: The auxiliary feedwater system initiation and control circuitry is required to automatically initiate the system and assure adequate decay heat removal and to allow control ofcooldown rates.

Issues related to initiation and control setpoints, instrumentation, flow, and level control are to be assessed.

Information PMP /200.RST.004 Rev. 5 Page 97 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 2 Addendum SYSTEM ASSESSMENT MATRIX EXAMPLE-AUXILIARYFEEDWATER SYSTEM Pages:

95 -99 Turbine and steam supply: The turbine driver for the turbine-driven auxiliary feedwater pumps (component IDs) and its steam supply and exhaust

're critical components for the operation of the pump.

These components have a negative industry operating experience history, and at Cook Plant have a seismic classification (in part) that has been questioned in the past.

Issues related to steam line warming and draining, trip and governor valve design, operation, and maintenance, speed controls, overspeed protection, and pump alignment are to be assessed.

AFW05 AFW flow control valves (FMO-212, 222,232,242,211,221,231,241).

The flow control valves are critical to limitflow to specified limits to achieve adequate decay heat removal and to miiumize overcooling of the RCS.

Issues related to valve and actuator design requirements, power supplies, and positioning capability are to be assessed.

Generic Attributes to be a lied where a licable b all ESRR teams

~ Note:

The below listed generic or common attributes, including items AFWC01 to AFWC13, are broadly applicable based on Cook Plant operating history, experience, and issues and, as such, each ESRR team shall be aware ofpotential effects of these attributes on functionality of their system.

AFWC01 Piping design: Changes in piping design criteria since original plant design MAYresult in confusion in piping design, installation, and inspection for existing piping and new piping installation. Other examples include material condition of buried pipe, ASME Code classification boundaries, and design temperature and pressures.

Containment isolation: Example of potential concerns are modification, maintenance, and testing (Appendix J) of containment isolation features.

AFWC03 Station blackout operation: Significant effort has been made by the industry to address rules regarding loss of all AC power. The AFW system is an important mitigator for this event.. Example issues include water supply, flow control and manual actions for the AFW system under station blackout conditions.

Information PMP 7200.RST.004 Rev. 5 Page 98 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 2 Addendum SYSTEM ASSESSMENT MATRIX EXAMPLE-AUXILIARYFEEDWATER SYSTEM Pages:

95-99 High Energy line breaks: Cook Plant systems should be protected against the effects of high energy line breaks.

Line break issues are interdisciplinary, involving piping design, environmental qualification, fiooding, bamer design, and accident analyses. Walkdown of physical barriers intended to ensure protection against such line breaks shall be considered to verify their mitigation capability. Additionally, consider test verification of detection and mitigation schemes.

AFWC05 Environmental qualification: EQ is a highly regulated program to assure system operation during adverse environmental conditions associated with design basis accident conditions.

The EQ program is being assessed independently of this review.

Potential issues from that review affecting system functions important to safe operation and accident mitigation should be considered.

AFWC06 Appendix R: Appendix R is a highly regulated program that required significant utilityeffort to address. The Appendix R program is being assessed independently of this review.

Potential issues from that review affecting system functions important to safe operation and accident mitigation should be considered.

Specific consideration should also be given to fire barriers and equipment required for safe shutdown.

AFWC07 Electrical separation: Redundant electrical trains and instrument channels are required to be separated by Regulatory Guide 1.75. Compliance with these requirements should be considered in the system walkdowns.

AFWC08 Seismic qualification: The AFW system is generally classified as seismic Category'.in. accordance with Regulatory Guide 1.29. Compliance with the requirements and the impact on design basis should be verified to the extent that the seismic classification and calculational basis are consistent.

AFWC09.

Year 2000 (Y2K): Considerable industry effort is being expended to ensure the reliable operation of microprocessor-based control and indication systems willnot be vulnerable to year 2000 related problems. Identify microprocessor based controls within the system, confirm they are within the Y2K scope, and identify outstanding work remaining.

Information'IMP 7200.RST.004 Rev. 5 Page 99 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 2 Addendum SYSTEM ASSESSMENT MATRIX EXAMPLE-AUXILIARYFEEDWATER SYSTEM Pages:

95-99 AFWC10 Single Failure Criteria/Common Mode Failure (CMF): The Cook Plant single failure design basis is not straightforward and misunderstanding or misapplication has led to issues of nonconformance in the past.

Additionally, some events at Cook Plant have been related to a failure to adequately consider possible failure modes of both system and supporting or attendant system components, ESRR teams must clearly understand the design basis in these areas and should evaluate whether possible failure modes of both the system and attending systems have been assessed to ensure the design is robust.

(see LER 97-021) Additionally, ESRR teams should be alert for and identify common mode failure mechanisms (if encountered) during their reviews.

These mechanisms include inappropriate-operations, maintenance, testing, or procurement priorities or poor material condition..

AFWCII Generic Letter 89-13 (GL 89-13): Cook Plant has had problems

,implementing Generic Letter 89-13 on service water cooling systems.

The GL 89-13 program is being assessed independently of this review.

Potential.

issues from the review affecting system functions important to safe operation and accident mitigation should be considered. ESRR teams should also be alert for instances where service water system dead legs are not properly or effectively addressed under the program or where Cook operating experience shows that, the existing provisions are insufficient.

AFWC12 Temperature Effects on System Operability: Cook Plant has not yet properly accounted for lake temperature variations in all system design bases.

ESRR teams shall specifically assess, where applicable, whether the design basis for the system or system components is at odds with the maximum seasonal lake temperature expected, which could be as high as 87.5 degrees during certain summer months.

Where such instances are found, the effect on system operability shall be assessed.

AFWC13 External Hazards:

Potential external hazards that may be applicable include flooding from both external and internal sources, missiles from both internal and external potential sources, wind loading, tornado and electric storm effects.

Information PjVIP 7200.RST.004 Rev. 5 Page 100 of 101 EXPANDED SYSTEM READINESS REVIEW PROGRAM Figure 3 READINESS REVIEW ATTRIBUTE ASSESSMENT FORM Pages:

100 - 100 Readiness Review Attribute Assessment Form s

Reviewer:

Reviewer Number:~

Attribute Description Major topic Date:

System Attribute Checks CRs Major Topic Item Number Attribute Number Attribute Checks CRs Electrical Calcs/analysis 1

1&C Calcs/Analysis 2

Mech./struct Calcs/Analysis 3

Accident Analysis 4

Drawings 5

Logic Diagrams.

6 Config. Management Info.

7 Specifications 8

DBDs 9

Change Docs/50.59 Reviews.

10 Temporary Mods/Bypasses 11 UFSAR Reviews 12 TS/Bases 13 Licensing Commitments 14 Notices, Bulletins and GLs.

15 16 17 18 19 20 21 22 Operating Procedures Operator Work Arounds Industry Op Exp Reviews Maintenance Procedures Vendor/Technical Info Preventive Maintenance Surveillance and Periodic Tests &inspections ISUSection XIIST'3 As-Built Verification 24 Control Room Drawings, 25 Surveillance Programs 26 Correction Action Program 27 PA Audits/Other Assessments 28 Training Lesson Plans 29 Open Items (Backlog) 30 Strategy Documents 31 CR Number:

Documents Reviewed Attribute Assessment

Information, PMP 7200.RST.004 Rev. 5 Page 101 of 101 EXPA'NDED SYSTEM READINESS REVIEW PROGRAM Figure 4 SAMPLE COMPLETED READINESS REVIEW ATTRIBUTEASSESSMENT FORM Pages:

101-101 Readiness Review Attribute Assessment Form Reviewer:

Russell Date:

2/5/99 Reviewer Number: ~ABROi System

~AFW Item Number Attribute Number AFWO1 Attribute Description CONDENSATE STORAGE TANKDESIGN BASIS Major topic, Attribute Checks CRs Major Topic Attribute Checks Electrical Calcs/analysis 1&C Calcs/Analysis Mech/struct Calcs/Analysis Accident Analysis Drawings Logic Diagrams, Config. Management info.

Specifications DBDs Change Docs/50.59 Reviews Temporary Mods/Bypasses UFSAR Reviews ITS/Bases Licensing Commitments Notices, Bulletins and GLs 8

9 10 11 12 13 14 15 0

1 0

0 0

0 0

0 Operating Procedures Operator Work Arounds Industry Op Exp Reviews Maintenance Procedures Vendor/Technical Info Preventive Maintenance Surveillance and Periodic Test &Inspections Section XIIST/Perf. Tests As-Built Verification Control Room Drawings Surveillance Programs Correction Action Program PA Audits/Other Assessments Training Lesson Plans, Open Items (Backlog)

Strategy Documents 16

" 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0

0

. 0 0

0 0

0 0

0 CR Number:

CR 4 984000 to provide basis for the statement that 174,451 gallons is sufficient to remove decay heat.

Documents Reviewed

1. DBD - DB-12, AFWS, AuxiliaryFeedwater System, Rev. 0, Change 6, Section 3.0.
2. UFSAR 10.5.2, Rev.
3. TS 3.7.6 and Bases; Attribute Assessment No Calculation or other documentation or data could be found to establish the basis for this minimum value.

The basis for the 9 hour1.041667e-4 days <br />0.0025 hours <br />1.488095e-5 weeks <br />3.4245e-6 months <br /> decay heat cooling capacity needs to be established

Attachment 2

Expanded System Readiness Review Procedure For Level 2 Systems PMP 7200.RST.006, Rev.

1