{{#Wiki_filter:. -      .    -                                                                  __
REFERENCE (1)
GENERAL ;                    ELECTRIC                                CONTRACTOR                l EQUIPMENT                !
BUSINESS                  ,
cENERAL ELtcTRIC COMPANY 41 WooDFoRo AVENUE. PLAINVILLE. CONN. 06062 Poone tros) 747 7          O PER AT10N S            l April 21,1983 f
W. Richard C. DeYoung Director of Office of Inspections                                                                      :
U.S. Nuclear Regulatory Comission                                                                    .  ;
Office of Inspection and Enforcement                                                                    4 Washington, D.C.        20555                                                                          p
 
==Dear W. DeYoung:==
                                                                            )
The contractor Equipment Business Operations of the General Electric ' -s Company has determined that a reportable defect exists on certain of its                        ' '
AK-25, AKR-30 and. AKR-50 Low-Voltage Power Circuit Breakers. The                                      :
following is a text of our notification for your use as necessary:
It has come to our attention that AK-25, AKR-30, and AKR-50                              i Low-Voltage Power Circuit Breakers equipped with                                                  '
electro-mechanical trip units may contain .assen611es improperly                                  l manufactured such that the circuit breaker fails to trip as                                      !
intended. These circuit breakers are used in direct current                                      !
applications.                                                                                    '
The General Electric Company proposes to correct this                                    !
potential problem in all Nuclear Class IE applications. The                                      ;
l                    correction will consist of returning the devices in question to                                  j l                    the factory for inspection, repair and re-assen61y as necessary, and re-testing to ensure proper operation. General Electric personnel are presently reviewing their files to determine which Nuclear facilities have these breakers and will soon be                                          ;
contacting the affected Nuclear sites to arrange for the                                          :
corrections at a mutually convenient time.                                                        !
The potentially affected circuit breakers were manufactured from mid-1976 until March,1983. Only the AK-25 AKR-30, and
                                                                                                                      )
l AKA-50 Circuit Breakers equipped with electro-mechanical trip                                    !
units are involved.                                                                              ,
l If you require any further information, please contact me.                                        !
s, i VeryTrug 8405140396 840427 PDR ADOCK 05000423                                    $7'  /          )'                    I i
S                      PDR David    . 185, Manager              !
y Qualit' Assurance N*
cit /(1776P)                                                          l: l  : M*dN"
_ _ _ _ . . _ _ _ _ . . . . _ _ . _ __ _ _,_ _ _ ___.__ _ ___ _ . 1 1. E.__KDnikows_ki___ _ _ _ __ __ j
_}}

Latest revision as of 18:10, 13 May 2020

Deficiency Rept Re Defective AK-25,AKR-30 & AKR-50 Low Voltage Power Circuit Breakers.Breakers Will Be Returned to Factory for Insp,Repair,Reassembly & Retesting
ML20084L237
Person / Time
Site: Millstone Dominion icon.png
Issue date: 04/21/1983
From: Dixon D
GENERAL ELECTRIC CO.
To: Deyoung R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
Shared Package
ML20084L226 List:
References
NUDOCS 8405140396
Download: ML20084L237 (1)


Text

. - . - __

REFERENCE (1)

GENERAL ; ELECTRIC CONTRACTOR l EQUIPMENT  !

BUSINESS ,

cENERAL ELtcTRIC COMPANY 41 WooDFoRo AVENUE. PLAINVILLE. CONN. 06062 Poone tros) 747 7 O PER AT10N S l April 21,1983 f

W. Richard C. DeYoung Director of Office of Inspections  :

U.S. Nuclear Regulatory Comission .  ;

Office of Inspection and Enforcement 4 Washington, D.C. 20555 p

Dear W. DeYoung:

)

The contractor Equipment Business Operations of the General Electric ' -s Company has determined that a reportable defect exists on certain of its ' '

AK-25, AKR-30 and. AKR-50 Low-Voltage Power Circuit Breakers. The  :

following is a text of our notification for your use as necessary:

It has come to our attention that AK-25, AKR-30, and AKR-50 i Low-Voltage Power Circuit Breakers equipped with '

electro-mechanical trip units may contain .assen611es improperly l manufactured such that the circuit breaker fails to trip as  !

intended. These circuit breakers are used in direct current  !

applications. '

The General Electric Company proposes to correct this  !

potential problem in all Nuclear Class IE applications. The  ;

l correction will consist of returning the devices in question to j l the factory for inspection, repair and re-assen61y as necessary, and re-testing to ensure proper operation. General Electric personnel are presently reviewing their files to determine which Nuclear facilities have these breakers and will soon be  ;

contacting the affected Nuclear sites to arrange for the  :

corrections at a mutually convenient time.  !

The potentially affected circuit breakers were manufactured from mid-1976 until March,1983. Only the AK-25 AKR-30, and

)

l AKA-50 Circuit Breakers equipped with electro-mechanical trip  !

units are involved. ,

l If you require any further information, please contact me.  !

s, i VeryTrug 8405140396 840427 PDR ADOCK 05000423 $7' / )' I i

S PDR David . 185, Manager  !

y Qualit' Assurance N*

cit /(1776P) l: l  : M*dN"

_ _ _ _ . . _ _ _ _ . . . . _ _ . _ __ _ _,_ _ _ ___.__ _ ___ _ . 1 1. E.__KDnikows_ki___ _ _ _ __ __ j