ML18092A319: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(StriderTol Bot change)
 
(3 intermediate revisions by the same user not shown)
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:* INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.3.6 As a minimum, the fire detection instrumentation for each fire tion zone shown in Table 3.3-10 shal1 be OPERABLE.
{{#Wiki_filter:INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.3.6 As a minimum, the fire detection instrumentation for each fire detec-tion zone shown in Table 3.3-10 shal1 be OPERABLE.
APP LI CAB I LI TY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.
APP LI CAB I LI TY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.
ACTION: With the number of OPERABLE fire detection instruments less than the minimum number OPERABLE requirement of Table 3.3-10: a. Within 1 hour establ_ish a fire watch patrol to inspect the zone(s) with the inoperable instrument(s) at least once per hour, unJess . the ihstrument(s) is inside the containment, then inspect the containment at once per 8 hours or monitor the air temperature at least once per hour at the locations in Specification 4.6.1.5. b. Restore the inoperable instrument(s)  
ACTION:
*ta OPERABLE within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification  
With the number of OPERABLE fire detection instruments less than the minimum number OPERABLE requirement of Table 3.3-10:
: a. Within 1 hour establ_ish a fire watch patrol to inspect the zone(s) with the inoperable instrument(s) at least once per hour, unJess .
the ihstrument(s) is loc~ted inside the containment, then inspect the containment at le~st once per 8 hours or monitor the contain~ent air temperature at least once per hour at the locations list~d in Specification 4.6.1.5.
: b. Restore the inoperable instrument(s) *ta OPERABLE st~tus within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within t.he next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument(s) to OPERABLE ~tatus .* *
: c.      The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.3.3.6.1      Each of the above required fire detection instruments which are acc~ssible      during operation shall be demonstrated OPERABLE at least once per 6 months by performance of a' function al test which includes subj ect.ing the detector to smoke or heat, as applicable. Fire detection instruments which are not accessible during operation shall be demonstrated OP£RABLE by performance of this functional test during each COLD SHUTDOWN ~xceeding 24 hours except that s*uch demonstration need not be* performed rnore often than once per 6 months.
SALEM - UN IT 1                          3/ 4 3-49 l


====6.9.2 within====
INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION (Continued) 4.3.3.6.2 The circuits between the above required detection instruments and the control room shall be demonstrated OPERABLE at least once per 92 days per approved procedures.
t.he next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument(s) to OPERABLE
SALEM - UNIT 1             3/4 3-50
.*
 
* c. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed   Inst.a 11 ed Instruments Instrument Location                       Thermal       Smoke       OPERABLE*
SURVEILLANCE REQUIREMENTS 4.3.3.6.1 Each of the above required fire detection instruments which are during operation shall be demonstrated OPERABLE at least once per 6 months by performance of a' function al test which includes subj ect.ing the detector to smoke or heat, as applicable.
Fire detection instruments which are not accessible during operation shall be demonstrated OP£RABLE by performance of this functional test during each COLD SHUTDOWN 24 hours except that s*uch demonstration need not be* performed rnore often than once per 6 months. SALEM -UN IT 1 3/ 4 3-49 l INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION (Continued) 4.3.3.6.2 The circuits between the above required detection instruments and the control room shall be demonstrated OPERABLE at least once per 92 days per approved procedures.
SALEM -UNIT 1 3/4 3-50 TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed Inst.a 11 ed Instruments Instrument Location Thermal Smoke OPERABLE*
: 1. Containment*
: 1. Containment*
Main Coolant Pumps #11 4 3 #12 4 3 #13 4 3 !114 4 3 2. Control Room A. Ceiling Void 6 4 B. Control Console 2 1 c. Aux. Equip. Room 8 6 D. Computer Room 2 1 3. Cable Vaults . #lC&D el 113 3 2 #2A&B e 1 113 3 2 #2C&D el 113 3 2 4. Switchgear Rooms A. Relay Room el 100 18 16 13. Switch Gear el 84 18 16 c. Vital Bus el 64 18 16 n. El ec. Pent el 78 13 11 5. Battery Rooms A. #lA 125 V el 100 2 1 B. #1 2.50 V el 100 3 2 c. #lB 125 V el 100 2 1 o. #lC 125 V el 64 2 1 6. Diesel Generators*
Main Coolant Pumps
A. #lA 5 4 B. #18 5 4 c. #lC 5 4 *The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests. SALEM -UN IT 1 3/4 3-51 TABLE 3.3-10 (Continued)
      #11                                                         4           3
FIRE DETECTION INSTRUMENTS Instrument Locat}on 7. Diesel Fuel Storage A. #11 Tank el 84 B * # 12 Tank el 84 C. #11 Fuel Transfer Pump D. #12 Fuel Transfer Pump 8. Aux. Bldg. Vent System -El. 122 A. Elec. Penetration Area B. Switch Gear Room C. Relay Room & .Control Room 9. Fuel Handling Bldg. A. *vent Equip. Room B.
      #12                                                         4           3
Control Area C. New/Spent Fuel Storage Area 10. Diesel Gen. Control Room A. #11 B. #12 c. #13 11. Pumps A. Auxiliary Feed B. Boric Acid C. RHR #11 #12 D. Safety Injection E. Component Cooling F. Containment Spray G. Charging Pumps 12. Auxiliary Bldg. Vent -122' A. Building Supply/Exh.
      #13                                                         4           3
Fans B. Control Area Vent Fans Installed Thermal 2 2 1 1 3 2 SALEM -UNIT 1 3/4 3-52 Ins ta 11 ed Smoke 2 1 \ 3 5 1 1 1 5 3 4 4 3 3* 3 3 9 5 Minimum Instruments OPERABLE 1 1 1 1 2 1 3 2 1 4 1 1 1 4 2 3 3 2 2 2 3 7 4 TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Instrument Location 13. Auxiliary Building Corridors A. Resin Storage -122 1 B. Evaporators
      !114                                                       4           3
-100 1 c. Waste Gas -64' 14. .Penetration Rooms A. 78 1 -Mechanical B. 100' -Mechanical Installed Thermal C. 100' -Electrical (Chillers)
: 2. Control Room A. Ceiling Void                                         6           4 B. Control Console                                     2           1
D. 100 1 -Inner Piping (North) E. 100 1* -Outer Piping (South) 15. Service Water A. #11, 12, 13 Pump Bay B. #14, 15, 16 Pump Bay C. #11, 12, 13 Control Room 0 * # 14 , 1 5 , 1 6 C on t r o 1 Ro om Main Steam Radiation Monitor Area 1 17. Auxiliary Building A. #11 & 12 Monitor Tank B. * #11 Waste Holdup Tank -El
: c. Aux. Equip. Room                                     8           6 D. Computer Room                                       2           1
* 64
: 3. Cable Vaults
* C. #12 Waste Holdup Tank D. #1 Waste Mon HU Tank E. East Aisle 2 F. West Aisle 2 G. East Aisle 2 H. West Aisle 2 I. L tdn/ Sea 1 Wtr HX Entry SALEM -UNIT 1 -El. 64 El. 64 -El
    . #lC&D el 113                                               3           2
* 64 El. 64 El. 64 El. 84 El. 84 El. 84 3/4 3-53 Installed Smoke 4 5 7 8 5 6 .6 5 6 6 1 1 .4 2 2 2 4 7 4 6 2 Minimum Instruments OPERABLE 3 4 6 6 4 4 4 4 4 4 1 1 1 4 2 2 2 4 7 4 6 2 . ' 
      #2A&B e1 113                                               3           2
. ' PLANT SY.STEMS 3/4.7.10 FIRE SUPPRESSION SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.1 Two fire suppression water systems shall *be OPERABLE each with: a. One fire suppression pump with a capacity of 2500 gpm with its discharge aligned to the fire suppression header. b. A separate water supply with a minimum contained volume of 300,000 gallons, and c. An OPERABLE flow path capable of taking suction from the tank and transferring the water through distribution piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm device on each system, the valve for each hose standpipe, the last valve ahead of the deluge valve on each deluge or spray* system required to be OPERABLE per Specifications 3.7.10.2 and 3.7.10.4.
      #2C&D el 113                                               3           2
APPLICABI'LITY:
: 4. Switchgear Rooms A. Relay Room     el 100                             18           16
*At:all times. ACTION: a. With one pump and/or one water supply inoperable, restore the ' inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special to the Commission pursuant to Specification
: 13. Switch Gear     el 84                               18           16
: c. Vital Bus       el 64                               18           16
: n. El ec. Pent   el 78                               13           11
: 5. Battery Rooms A.   #lA   125 V el   100                   2                         1 B.   #1   2.50 V el   100                   3                         2
: c.   #lB   125 V el   100                   2                         1
: o.   #lC   125 V el     64                   2                         1
: 6. Diesel Generators*
A.   #lA                                     5                         4 B.   #18                                     5                         4
: c.   #lC                                     5                         4
*The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests.
SALEM - UN IT 1                             3/4 3-51


====6.9.2 within====
TABLE 3.3-10 (Continued)
the next 30 days outlining the plans and procedures to be used . to provide for the lass of redundancy in this system. The prov1 s.i ans of Specifications and 3.0.4 not
FIRE DETECTION INSTRUMENTS Minimum Installed    Ins ta 11 ed Instruments Instrument Locat}on                  Thermal        Smoke      OPERABLE
: 7. Diesel Fuel Storage A.    #11 Tank el 84                    2                          1 B*    #12 Tank el 84                    2                          1 C.    #11 Fuel Transfer Pump            1                          1 D.    #12 Fuel Transfer Pump            1                          1
: 8. Aux. Bldg. Vent System - El. 122 A. Elec. Penetration Area                          2          2 B. Switch Gear Room                                1            1 C. Relay Room & .Control Room                    \3            3
: 9. Fuel Handling Bldg.
A.  *vent Equip. Room                  3                          2 B. Elec~ Control Area                2                          1 C. New/Spent Fuel Storage Area                      5            4
: 10. Diesel Gen. Control Room A.    #11                                              1          1 B.    #12                                              1            1
: c.    #13                                              1          1
: 11. Pumps A. Auxiliary Feed                                  5          4 B. Boric Acid                                      3          2 C. RHR #11                                          4          3
              #12                                          4          3 D. Safety Injection                                3          2 E. Component Cooling                                3*          2 F. Containment Spray                                3          2 G. Charging Pumps                                  3          3
: 12. Auxiliary Bldg. Vent - 122' A. Building Supply/Exh. Fans                        9          7 B. Control Area Vent Fans                          5          4 SALEM - UNIT 1                        3/4 3-52
 
TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed  Installed Instruments Instrument Location                        Thermal    Smoke    OPERABLE
: 13. Auxiliary Building Corridors A. Resin Storage - 122      1 4        3 B. Evaporators - 100 1                                  5        4
: c. Waste Gas - 64'                                      7        6
: 14.  .Penetration Rooms A. 78 1 - Mechanical                                  8          6 B. 100' - Mechanical                                  5          4 C. 100' - Electrical (Chillers)                        6        4 D. 100 1 - Inner Piping (North)                      .6          4 E. 100 1* - Outer Piping (South)                        5        4
: 15. Service Water A.    #11,  12,  13 Pump Bay                            6          4 B.    #14,  15,  16 Pump Bay                            6          4 C.    #11,  12,  13 Control Room                        1          1 0*    #14 ,  1 5, 16 Con t r o1 Ro om                    1          1 16~  Main Steam Radiation Monitor Area              1                  1
: 17. Auxiliary Building A.    #11 & 12 Monitor      Tank      - El
* 64 *        .4        4 B. * #11 Waste Holdup      Tank      - El. 64            2        2 C.    #12 Waste Holdup      Tank      El. 64            2        2 D.    #1 Waste Mon HU        Tank    - El
* 64          2        2 E. East Aisle 2                      El. 64            4        4 F. West Aisle 2                      El. 64            7        7 G. East Aisle 2                      El. 84            4        4 H. West Aisle 2                      El. 84            6        6 I. Ltdn/ Sea 1 Wtr HX    Entry      El. 84            2        2 SALEM - UNIT 1                              3/4 3-53
 
PLANT SY.STEMS 3/4.7.10    FIRE SUPPRESSION SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.1    Two fire suppression water systems shall *be OPERABLE each with:
: a. One fire suppression pump with a capacity of 2500 gpm with its discharge aligned to the fire suppression header.
: b. A separate water supply with a minimum contained volume of 300,000 gallons, and
: c. An OPERABLE flow path capable of taking suction from the tank and transferring the water through distribution piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm device on each sp~i~kler system, the i~olation valve for each hose standpipe, ~nd the last valve ahead of the deluge valve on each deluge or spray*
system required to be OPERABLE per Specifications 3.7.10.2 and 3.7.10.4.
APPLICABI'LITY: *At:all times.
ACTION:
: a. With one pump and/or one water supply inoperable, restore the '
inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special R~port to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the plans and procedures to be used
            . to provide for the lass of redundancy in this system. The prov1 s.i ans of Specifications 3.0~3 and 3.0.4 a~e not appli~able.
: b. With both fire suppression water systems inoperable:
: b. With both fire suppression water systems inoperable:
: 1. Establish a backup fire suppression water system within 24 hours,. and 2. Submit a Special Report in accordance with Specification 6.9.2: a) By telephone .within 24 hours, b) Confirmed by telegraph, mailgram*ar facsimile transmission no 1 ater than the first working day fa 11 owing the event, and . c) In writing within 14 days following the event, outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status. SALEM -UNIT 1 3/4 7-34 PLANT SYSTEMS' SURVEILLANCE REQUIREMENTS 4.7.10.1.1 The fire suppression water system shall be dem6nstrated OPERABLE:
: 1. Establish a backup fire suppression water system within 24 hours,.
: a. At least once per 7 days by verifying the contained water supply volume. b. At least once per 31 days by verifying that each valve (manual, po\'1er operated or automatic) in the flow path is in its correct position.
and
: c. At least once per 12 months by performance of a system flush. d. At 1 east once per 18 months by performing a system funct i anal test which includes simulated automatic actuation of the system throughout its operating sequence, and: 1. Verifying that each pump develops at *least 2500 gpm at a system head 250 feet, 2. Cycling each manual valve in the flow path through at least one complete cycle of* full travel, and 3 *. Verifying that each high *p.ressure pump starts (sequentially) to maintain the fire suppression water system pressure greater than or equal to 135 psig. e.* At 1 east once per 3 years by performing a fl ow test of the system in with Chapter 5, Section 11 of the Protection Handbook, 14th Edition, published by the National Fire Protection Association.
: 2. Submit a Special Report in accordance with Specification 6.9.2:
SALEM -UNIT 1 3/4 7-35
a)   By telephone .within 24 hours, b)   Confirmed by telegraph, mailgram*ar facsimile transmission no 1ater than the first working day fa 11 owing the event, and .
.. ----*---PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.1.2 The fire pump diesel engine shall be demonstrated OPERABLE:
c)   In writing within 14 days following the event, outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.
SALEM - UNIT 1                         3/4 7-34
 
PLANT SYSTEMS' SURVEILLANCE REQUIREMENTS 4.7.10.1.1   The fire suppression water system shall be dem6nstrated OPERABLE:
: a. At least once per 7 days by verifying the contained water supply volume.
: b. At least once per 31 days by verifying that each valve (manual, po\'1er operated or automatic) in the flow path is in its correct position.
: c. At least once per 12 months by performance of a system flush.
: d. At 1east once per 18 months by performing a system funct i anal test which includes simulated automatic actuation of the system throughout its operating sequence, and:
: 1. Verifying that each pump develops at *least 2500 gpm at a system head ~f. 250 feet,
: 2. Cycling each manual valve in the flow path through at least one complete cycle of* full travel, and 3*. Verifying that each high *p.ressure pump starts (sequentially) to maintain the fire suppression water system pressure greater than or equal to 135 psig.
e.*   At 1east once per 3 years by performing a fl ow test of the system in ac~ordance with Chapter 5, Section 11 of the Fi~e Protection Handbook, 14th Edition, published by the National Fire Protection Association.
SALEM - UNIT 1                         3/4 7-35
 
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.1.2   The fire pump diesel engine shall be demonstrated OPERABLE:
: a. At least once per 31 days by verifying;
: a. At least once per 31 days by verifying;
: 1. The fuel storage tank contains at least 300 gallons of fuel, and 2. The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow. b. At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank, obtained in accordance with ASTM-0270-65, is within the acceptable limits specified in Table 1 of ASTM 0975-74 when checked for visocity, water and sediment.
: 1. The fuel storage tank contains at least 300 gallons of fuel, and
: c. At. least once per 18 months, during shutdown, by subjecting the diesel to an inspection*
: 2. The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow.
in accordance with procedures prepared in conjunctiion with its manufacturer's recommendations for class of service. 4.7.10.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
: b. At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank, obtained in accordance with ASTM-0270-65, is within the acceptable limits specified in Table 1 of ASTM 0975-74 when checked for visocity, water and sediment.
: a. At least once per 7 days by verifying that: 1. The electrolyte level of each battery is above the plates, and 2. The overal 1 battery voltage is greater than or equal to 24 volts. b. At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery. c. At 1 east once per 18 months by verifying that: 1. The batteries, cell plates and battery racks show no visual indication of physical damage'or abnormal deterioration, and 2. The battery-to-battery and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material.
: c. At. least once per 18 months, during shutdown, by subjecting the diesel to an inspection* in accordance with procedures prepared in conjunctiion with its manufacturer's recommendations for class of service.
SALEM -UNIT 1 3/4 7-36
4.7.10.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
.. PLANT SYSTEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.2 The following spray and/or sprinkler systems shall be OPERABLE:
: a. At least once per 7 days by verifying that:
: a. Reactor Coolant Pump Lube Oil b. Charcoal Fi 1 ters 1. Containment Iodine Removal 2. Auxiliary Building Ventilation
: 1. The electrolyte level of each battery is above the plates, and
: 2. The overal 1 battery voltage is greater than or equal to 24 volts.
: b. At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.
: c. At 1east once per 18 months by verifying that:
: 1. The batteries, cell plates and battery racks show no visual indication of physical damage'or abnormal deterioration, and
: 2. The battery-to-battery and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material.
SALEM - UNIT 1                         3/4 7-36
 
PLANT SYSTEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.2 The following spray and/or sprinkler systems shall be OPERABLE:
: a. Reactor Coolant Pump Lube Oil
: b. Charcoal Fi 1ters
: 1. Containment Iodine Removal
: 2. Auxiliary Building Ventilation
: 3. Control Room Emergency Air Conditioning
: 3. Control Room Emergency Air Conditioning
: 4. Containment Pressure*
: 4. Containment Pressure* Relief
Relief 5. Fuel Handling Building Ventilation
: 5. Fuel Handling Building Ventilation
: c. Charging Pumps d. Diesel Fuel Oil Storage Tanks and Transfer Pumps e. Auxiliary Feedwater Pumps APPLICABILITY:
: c. Charging Pumps
Whenever equipment*
: d. Diesel Fuel Oil Storage Tanks and Transfer Pumps
protected by the spray /spri nk.l e'r system is required to be OPERABLE:
: e. Auxiliary Feedwater Pumps APPLICABILITY: Whenever equipment* protected by the spray /spri nk.l e'r system is required to be OPERABLE:
ACTION: a. th one or more of the above required spray and/or sprinkler systems inoperable, within one hour establish a continuous fire watch with backup fire equipment for those areas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification  
ACTION:
: a. l~i th one or more of the above required spray and/or sprinkler systems inoperable, within one hour establish a continuous fire watch with backup fire suppressi~n equipment for those areas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and plans and schedule for restoring the system to OPERABLE status.
: b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
SALEM - UNIT 1                        3/4 7-37


====6.9.2 within====
PLANT SYSTEMS*
the next 30 days outlining the action taken, the cause of the inoperability and plans and schedule for restoring the system to OPERABLE status. b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
* SURVEILLANCE REQUIREMENTS 4.7.10.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:
SALEM -UNIT 1 3/4 7-37
* PLANT SYSTEMS* SURVEILLANCE REQUIREMENTS 4.7.10.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:
: a. At least once per 31 days by verifying that each valve (manual , powe.r operated or automatic) in the flow path is in its correct position.
: a. At least once per 31 days by verifying that each valve (manual , powe.r operated or automatic) in the flow path is in its correct position.
: b. At least once per 12 months by cycling each testable automatic valve in the flow path through at least one complete cycle of full travel. c. At least once per 18 months: d. 1. -Sy performing a system functional test which includes simulated automatic actuation of the system and verifying that the automatic valves in the flow path actuate to their correct positions.
: b. At least once per 12 months by cycling each testable automatic valve in the flow path through at least one complete cycle of full travel.
: 2. By a visual inspection of the dry pipe spray and sprinkler headers to verify their integrity, and 3. By a visual inspection of each nozzle's spray area to verify that the spray pattern is not obstructed.
: c. At least once per 18 months:
At least once per 3 years by performing an air flow te.st through each open 0 head spray header and verifying each open head spray nozzle is unobstructed.
: 1.   -Sy performing a system functional test which includes simulated automatic actuation of the system and verifying that the automatic valves in the flow path actuate to their correct positions.
SALEM -UNIT 1 3/4 7-38 I I I I I i 
: 2. By a visual inspection of the dry pipe spray and sprinkler headers to verify their integrity, and                           II
*,
: 3. By a visual inspection of each nozzle's spray area to verify that the spray pattern is not obstructed.                       I
* PLANT SYSTEMS LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.3 The following low pressure C02 system*s shall be OPERABLE with a minimum level of 50% and a minimum pressure of 285 psig in the associated
: d. At least once per 3 years by performing an air flow te.st through each open head spray header and verifying each open head spray nozzle is I
.... storage tanks. a. Diesel Generator Areas b. Diesel Fuel Oil Storage c. Vital Switchgear Rooms d. Electrical Penetration Area APPLICABILITY:
I i
Whenever equipment protected by the C02 systems is required to be OPERABLE.
0 unobstructed.
ACTION: a. Within one or more of the above required C02 systems i noperab 1 e, within one hour establish a continuous fire watch with backup fire suppression equipment for those reas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days_ or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification
SALEM - UNIT 1                         3/4 7-38


====6.9.2 within====
PLANT SYSTEMS LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.3 The following low pressure C02 system*s shall be OPERABLE with a minimum level of 50% and a minimum  ....
the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for res tori rig the system to OPERABLE status.
pressure of 285 psig in the associated storage tanks.
* b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
: a. Diesel Generator Areas
: b. Diesel Fuel Oil Storage
: c. Vital Switchgear Rooms
: d. Electrical Penetration Area APPLICABILITY:      Whenever equipment protected by the C02 systems is required to be OPERABLE.
ACTION:
: a. Within one or more of the above required C02 systems i noperab 1e, within one hour establish a continuous fire watch with backup fire suppression equipment for those reas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days_ or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for res tori rig the system to OPERABLE status. *
: b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.10.3 Each of the above required low pressure C02 systems shall be demonstrated OPERABLE:
SURVEILLANCE REQUIREMENTS 4.7.10.3 Each of the above required low pressure C02 systems shall be demonstrated OPERABLE:
: a. At letastd onc.e tper tbyh valve (manua'.,.power  
opera e or au oma 1c 1n e 1 ow pa 1s 1n 1ts correct pos1t1on.
*\1 opera e or au oma 1c 1n e ow pa 1s 1n 1ts correct pos1t1on.
: a. At letastd onc.e tper t3~ d)a~s tbyh vef rifyintght~at.ea~h valve (manua'.,.power 1
: b. At least once per 7 days by verifying C02 storage tank level and pressure, and SALEM -UN IT 1 3/4 7-39
                                                                                                *\
,* * *e PLANT SYSTEMS LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS
: b. At least once per 7 days by verifying C02 storage tank level and pressure, and SALEM - UN IT 1                             3/4 7-39
: 4. 7 .10.3 Each of the above required 1 ow pressure C02 sy_stems shal_l be demonstrated OPERABLE:
 
PLANT SYSTEMS
                    *                             *e LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS
: 4. 7.10.3 Each of the above required 1ow pressure C02 sy_stems shal_l be demonstrated OPERABLE:
: c. At least once per 18 months by verifying:
: c. At least once per 18 months by verifying:
: 1. The system valves and associated ventilation dampers actuate manually and automatically, upon receipt of a simulated actuation signal, and 2.
: 1. The system valves and associated ventilation dampers actuate manually and automatically, upon receipt of a simulated actuation signal, and
* Flow from each nozzle during a "Puff Test.11 SALEM -UNIT 1 3/4 7-39a
: 2.
* PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION 3.7.10.4 The fire hose stations shown in Table 3.7-11 shall be OPERABLE.
* Flow from each nozzle during a "Puff Test. 11 SALEM - UNIT 1                       3/4 7-39a
APPLICABILITY:
Whenever equipment in the areas protected by the fire hose stations is required to be OPERABLE.
ACTION: a. With one or more of the fire hose stations shown in Table 3.7-11 inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an OPERABLE hose station within 1 hour if the inoperable fire hose i.s the primary means of fire suppress ion; otherwise, route the additional hose withtn 24 hours. Restore the *fire hose station to OPERABLE status within* 14. days or; in* lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification


====6.9.2 within====
PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION 3.7.10.4 The fire hose stations shown in Table 3.7-11 shall be OPERABLE.
the next 30 days outlining the action taken, the cause of the inoperability and plans and schedul.e for restoring.the station to OPERABLE status. b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
APPLICABILITY: Whenever equipment in the areas protected by the fire hose stations is required to be OPERABLE.
ACTION:
: a. With one or more of the fire hose stations shown in Table 3.7-11 inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an OPERABLE hose station within 1 hour if the inoperable fire hose i.s the primary means of fire suppress ion; otherwise, route the additional hose withtn 24 hours. Restore the
          *fire hose station to OPERABLE status within* 14. days or; in* lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and plans and schedul.e for restoring.the station to OPERABLE status.
: b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:
SURVEILLANCE REQUIREMENTS 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:
: a. At least once per 31 days by visual inspection of the hose stations outside the containment to assure all required equipment is at the station. b. At least once per 92 days by visual inspection of containment hose stations to assure all required equipment is at the station. c. At least once per 18 months by: 1. Removing the hose for inspection and re-racking, and 2. Inspecting all gaskets and replacing any degraded gaskets in the couplings.
: a. At least once per 31 days by visual inspection of the hose stations outside the containment to assure all required equipment is at the station.
SALEM -UNIT 1 3/4 7-40
: b. At least once per 92 days by visual inspection of containment hose stations to assure all required equipment is at the station.
* PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:
: c. At least once per 18 months by:
: d. At least once per 3 years by: 1. Partially opening each hose station valve to verify OPERABILITY and no flow blockage.
: 1. Removing the hose for inspection and re-racking, and
: 2. Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure available at that* hose station. SALEM -UNIT 1 3/4 7-40a
: 2. Inspecting all gaskets and replacing any degraded gaskets in the couplings.
** TABLE 3. 7-11 1-1/2" FIRE HOSE STATIONS HOSE STATION NO. LOCATION lFP-137 100-Al-GG14 Aux i 1 i ary Bldg. lFP-75 100-Al-NN14 Au xi 1 i ary Bldg. lFP-74 84-Al-NN14 Au xi 1 i ary Bldg. lFP-136 84-Al-GG14 Auxiliary Bldg. lFP-135 64-Al-GG14 Auxi 1 i ary Bldg. lFP-73 64-Al-NN14 Auxiliary Bldg. lFP-134 55-Al-GG14 . Au xi 1 i ary Bldg
SALEM - UNIT 1                       3/4 7-40
* lFP-138 122-Al-.GG14 Aux i 1 i ary Bldg. lFP-76 122-Al-NN14 Au x i 1 i a ry B 1 d g
 
* lFP-277 122-A-BB13.8 Aux il i a ry B 1 dg. (Control  
PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:
-lFP-262 100-Al-KKl0.4 Mechanical Penetr.Area lFP-279 100-Al-KK17.8 Auxiliary Bldg. lFP-88 El. 78 Cont. #1 lFP-97 El. 78 Cont. #1 lFP-89 El. 130 Cont. #1 lFP-96 El
: d. At least once per 3 years by:
* 130 Cont. #1 SALEM -UNIT 1 3/4 7-41 PLANT SYSTEMS HALON SYSTEMS -* LIMITING CONDITION FOR OPERATION 3.7.10.5 *The Relay Room Halon system shall be OPERABLE with the storage tanks having at least 95% of full liquid volume and 90% of full pressure.
: 1. Partially opening each hose station valve to verify valv~
APPLICABILITY:
OPERABILITY and no flow blockage.
Whenever equipment in tlie Halon protected area is-required to be OPERABLE.
: 2. Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure available at that* hose station.
ACTION: a. With the above required Halon system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area(s) within 1 hour; restore the system to OPERABLE status within 14 days or, in 1 i eu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification
SALEM - UNIT 1                       3/4 7-40a
 
                  **       TABLE 3. 7-11 1-1/2" FIRE HOSE STATIONS HOSE STATION NO.                               LOCATION lFP-137                   100-Al-GG14       Aux i 1i ary Bldg.
lFP- 75                   100-Al-NN14       Au xi 1i ary Bldg.
lFP- 74                     84-Al-NN14       Au xi 1 i ary Bldg.
lFP-136                     84-Al-GG14       Auxiliary Bldg.
lFP-135                     64-Al-GG14       Auxi 1i ary Bldg.
lFP- 73                     64-Al-NN14       Auxiliary Bldg.
lFP-134                     55-Al-GG14   . Au xi 1 i ary Bldg
* lFP-138                   122-Al-.GG14     Aux i 1i ary Bldg.
lFP- 76                   122-Al-NN14       Au xi 1 i a ry B1dg
* lFP-277                   122-A-BB13.8     Aux il i a ry B1dg.
(Control Ar~a) lFP-262                   100-Al-KKl0.4 Mechanical Penetr.Area lFP-279                     100-Al-KK17.8 Auxiliary Bldg.
lFP- 88                     El. 78 Cont. #1 lFP- 97                     El. 78 Cont. #1 lFP- 89                     El. 130 Cont. #1 lFP- 96                     El
* 130 Cont. #1 SALEM - UNIT 1               3/4 7-41


====6.9.2 within====
PLANT SYSTEMS HALON SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.5 *The Relay Room Halon system shall be OPERABLE with the storage tanks having at least 95% of full liquid volume and 90% of full pressure.
the next 30 days outlinin*g the action taken, the cause of the inoperability and the plans and sc::hedule for restoring the system to OPERABLE status. b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
APPLICABILITY:    Whenever equipment in tlie Halon protected area is- required to be OPERABLE.
SURVEILLANCE REQUIREMENTS  
ACTION:
-4.7.10.5 The above required Halon system shall be OPERARLE:
: a. With the above required Halon system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area(s) within 1 hour; restore the system to OPERABLE status within 14 days or, in 1i eu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlinin*g the action taken, the cause of the inoperability and the plans and sc::hedule for restoring the system to OPERABLE status.
: b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS -
4.7.10.5 The above required Halon system shall be     demonstr~ted OPERARLE:
: a. At least once per 6 months by verifying Halon storage tank li*quid volume and pressure.
: a. At least once per 6 months by verifying Halon storage tank li*quid volume and pressure.
: b. At least once per 18 months by: 1. Verifying the system, including associated ventilation dampers actuates manually and automatically, upon receipt of a simulated actuation signal, and 2. Performance of a visual inspection of the nozzles to assure that they are. free of debris or obstruction.
: b. At least once per 18 months by:
SALEM -UNIT 1 3/4 7-42
: 1. Verifying the system, including associated ventilation dampers actuates manually and automatically, upon receipt of a simulated actuation signal, and
' . . . PLANT SYSTEMS 3/4.7.11 PENETRATION FIRE BARRIERS LIMITING CONDITION FOR OPERATION 3.7.11 All penetration fire barriers (including cable penetration barriers, firedoors and fire dampers), in fire zone boundaries, protecting safety related areas shall OPERABLE.
: 2. Performance of a visual inspection of the ~scharge nozzles to assure that they are. free of debris or obstruction.
APPLICABILITY:
SALEM - UNIT 1                           3/4 7-42
At all times. ACTION: a. With one or more of the above required penetration fire barriers I inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one side of the inoperable fire barrier and establish an hourly fire watch patrol. Restore the inoperable penetration fire barriers(s) to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant .to Specification


====6.9.2 within====
PLANT SYSTEMS 3/4.7.11    PENETRATION FIRE BARRIERS LIMITING CONDITION FOR OPERATION 3.7.11 All penetration fire barriers (including cable penetration barriers, firedoors and fire dampers), in fire zone boundaries, protecting safety related areas shall b~ OPERABLE.
the next 30 days outlining the action taken, the cause of the inoperable fire barrier and plans and schedule for restoring the penetration fire barrier(s) to OPERABLE status. b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
APPLICABILITY:      At all times.
ACTION:
: a. With one or more of the above required penetration fire barriers      I inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one side of the inoperable fire barrier and establish an hourly fire watch patrol. Restore the inoperable penetration fire barriers(s) to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant
              .to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperable fire barrier and plans and schedule for restoring the penetration fire barrier(s) to OPERABLE status.
: b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.11 Each of the above required penetration fire barriers shall be verified to be OPERABLE:
SURVEILLANCE REQUIREMENTS 4.7.11 Each of the above required penetration fire barriers shall be verified to be OPERABLE:
: a. At least once per 18 months by a visual inspection, and b. Prior to returning a penetration fire barrier to OPERABLE status following repairs or maintenance by the performance of a visual inspection of the affected penetration fire barrier(s).
: a. At least once per 18 months by a visual inspection, and
SALEM -UNIT 1 3/4 7-43 SALEM UNIT NO. 2
: b. Prior to returning a penetration fire barrier to OPERABLE status following repairs or maintenance by the performance of a visual inspection of the affected penetration fire barrier(s).
*' INSTRUMENTATION FIRE DETtCTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.3.6 As a m1n1mum, the fire detection instrumentation for each fire tion zone shown in Table 3.3-10 shall be OPERABLE.
SALEM - UNIT 1                         3/4 7-43
APPLICABILITY:
 
Whenever equipment protected by the fire detection instrument is required to be OPERABLE.
SALEM UNIT NO. 2 INSTRUMENTATION FIRE DETtCTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.3.6 As a m1n1mum, the fire detection instrumentation for each fire detec-tion zone shown in Table 3.3-10 shall be OPERABLE.
ACTION: With the number of OPERABLE fire detection instruments less than the minimum number OPERABLE requirement of Table 3.3-10: a. Within 1 hour establish*
APPLICABILITY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.
a fire watch patrol to inspect*the zone(s) with the inoperable instrument(s) at least. once hour, unless the instrument(s) is locate9 inside the containment, then inspect the containment at least once per 8 hours or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6.1.5. b. Restore the inoperable instrument(s) to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification  
ACTION:
With the number of OPERABLE fire detection instruments less than the minimum number OPERABLE requirement of Table 3.3-10:
: a. Within 1 hour establish* a fire watch patrol to inspect*the zone(s) with the inoperable instrument(s) at least. once pe~ hour, unless the instrument(s) is locate9 inside the containment, then inspect the containment at least once per 8 hours or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6.1.5.
: b. Restore the inoperable instrument(s) to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days *outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument(s) to OPERABLE status.
: c. The provisions of  Specifi~ations 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.3.3.6.1 Each of the above required fire detection instruments which are accessible during operation shall be demonstrated OPERABLE at least once per 6 months by performance of a functional test which includes subjecting the detector to smoke or heat, as applicable. Fire detection instruments which are not accessible during operation shall be demonstrated OPERABLE by performance of this functional test during each COLD SHUTDOWN exceeding 24 hours except that such demonstration need not be performed more often than once per 6 months.
* SALEM - UNIT 2                      3/4 3-46


====6.9.2 within====
,1 . '
the next 30 days *outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument(s) to OPERABLE status. c. The provisions of 3.0.3 and 3.0.4 are not applicable.
INSTRUMENT ATI ON FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION (Continued) 4.3.3.6.2 The circuits between the above- re*quired detection instruments and the control room shall be demonstrated OPERABLE at least once per 92 days per.
SURVEILLANCE REQUIREMENTS 4.3.3.6.1 Each of the above required fire detection instruments which are accessible during operation shall be demonstrated OPERABLE at least once per 6 months by performance of a functional test which includes subjecting the detector to smoke or heat, as applicable.
approved procedures.
Fire detection instruments which are not accessible during operation shall be demonstrated OPERABLE by performance of this functional test during each COLD SHUTDOWN exceeding 24 hours except that such demonstration need not be performed more often than once per 6 months.
* I SALEM - UNIT 2             3/4 3-47
* SALEM -UNIT 2 3/4 3-46 
,1 . ' . . INSTRUMENT A TI ON FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION (Continued) 4.3.3.6.2 The circuits between the above-re*quired detection instruments and the control room shall be demonstrated OPERABLE at least once per 92 days per. approved procedures.
* I SALEM -UNIT 2 3/4 3-47
,. TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Instrument Location 1. Containment Main Coolant Pumps #21 #22 #23 #24 2. Control Room A. Ceiling Void B. Control Console C. Aux. Equip. Room I). Computer Room 3. Cable Vaults #lC&D e 1 113 . #2A&B el 113 #2C&D el 113 4. Switchgear Rooms A. Relay Room el 100 B. Switch Gear el 84 C. Vital Bus el 64 D. El ec. Pent el 78
* 5. Battery Rooms A. B. c. D. #2A 125 V el #2 250 V el #2B 125 V el #2C 125 V el 6. Diesel Generators A. #2A B. #2B C. #2C 100 . 100 100 64 Inst a 11 ed Thermal 2 3 2 2 5 5 5 Inst a 11 ed Smoke 4 4 4 4 6 2 8 2 3 3 3 18 18 18 13 Minimum Instruments OPERABLE*
3 3 3 3 4 1 6 1 2 2 2 16 16 16 11 1 2 1 1 4 4 4 *The fire detection jnstruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage. Rate Tests. SALEM -UN IT 2 3/4 3-48 A\ ' I TABLE 3.3-10 (Continued)
FIRE DETECTION INSTRUMENTS Instrument Location 7. Diesel Fuel Storage A. #21 Tank el *s4 B. #22 Tank el 84 C. #21 Fuel Transfer Pump IJ. #22 Fuel Transfer Pump 8. Aux. Bldg. Vent System -El. 122 A. Elec. Penetration Area B. Switch Gear Room C. Relay Room & Control Room 9. Fuel Handling Bldg. A. Vent Equip. Room B. Elec. Control Area C. New/Spent Fuel Storage Area 10. Diesel Gen. Control Room A. #21 B. . #22 c. #23 11. Pumps A. Auxiliary Feed Boric Acid C. RHR #21 #22 D. Safety Injection E. Component Cooling F. Containment Spray G. Charging Pumps Installed Thermal 2 2 1 1 3 2 SALEM.-UNIT 2 3/4 3-49 Instal l.ed Smoke 2 1 3 5 1 1 1 5 3 4 4 3 3 3 3 Minimum Instruments OPERABLE 1 1 1 1 2 1 3. 2 1 4 1 1 1 4 2 3 3 2 2 2 3 . I I ! 
'' . l. 9* TABLE 3*.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed 11 ed Instruments Instrument Location Thermal Smoke OPERABLE 12. Auxiliary Bldg. Vent -122 1 A. Building Supply/Exh.
Fans 9 7 B. Control Area Vent Fans 5 4 13. Auxiliary Building Corridors A. Resin Storage -122' 4 3 B. Evaporators
-100 1 5 4 c. Waste Gas -64 1 7 6 14. Penetration Rooms A. 78 1 -Mechanical 8 6 B. 100 1 -Mechanical
.5 4 c .. *100 1 ..: Electrical (Chillers) 6 4 o. 100' *-Inner Piping (North) 6 4 E. 100 1 -Outer Piping (South) 5 4 15. Service Water A. #21, 22, 23 Pump Bay 6 4 B. #24, 2 5, 2*6 Pump Bay 6 4 c. #21, 22, 23 Control Room 1 1 D. #24, 2 5, 26 Control Room 1 1 16. Main Steam Radiation Monitor Area 1 1 SALEM -UNIT 2 . 3/4 3-50 
'; PLANT SYSTEMS 3/4.7.10 FIRE SUPPRESSION SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.1 Two fire suppression water systems shall be OPERABLE each with:* a. One fire suppression pump with a capacity of 2500 gpm with its discharge aligned to the fire suppression header. b. A separate water supply with a minimum contained volume of 300,000 gallons, and c. An OPERABLE flow path capable of taking suction from the tank and transferring the water through distribution piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm device on each sprinkler system, the isolation valve for each hose standpipe, and the last valve ahead of the deluge valve on each deluge or spray system required to be OPERABLE per Specifications 3.7.10.2 and 3.7.10.4.
APPLICABILITY:
At all times. ACTION: a. With one pump and/or one water supply inoperable, restore the inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification


====6.9.2 within====
TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Inst a 11 ed Inst a11 ed Instruments Instrument Location                    Thermal      Smoke      OPERABLE*
the next 30 days outlining the plans and procedures to be used to-provide for the loss of redundancy .in this system. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
: 1. Containment Main Coolant Pumps
        #21                                                      4          3
        #22                                                      4          3
        #23                                                      4          3
        #24                                                      4          3
: 2. Control Room A. Ceiling Void                                      6          4 B. Control Console                                    2          1 C. Aux. Equip. Room                                  8          6 I). Computer Room                                      2          1
: 3. Cable Vaults
        #lC&D e 1 113 .                                          3          2
        #2A&B el 113                                            3          2
        #2C&D el 113                                              3          2
: 4. Switchgear Rooms A. Relay Room    el 100                              18          16 B. Switch Gear    el 84                              18          16 C. Vital Bus      el 64                              18          16 D. El ec. Pent  el 78
* 13          11
: 5. Battery Rooms A.  #2A  125 V el 100                    2                        1 B.  #2    250 V el . 100                  3                        2
: c.  #2B  125 V el 100                    2                        1 D.  #2C  125 V el    64                  2                        1
: 6. Diesel Generators A.  #2A                                    5                      4 B.  #2B                                    5                        4 C.  #2C                                    5                        4
  *The fire detection jnstruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage.
Rate Tests.
SALEM - UN IT 2                          3/4 3-48
 
      ~--------*
A\ ' I TABLE 3.3-10 (Continued)
FIRE DETECTION INSTRUMENTS Minimum Installed    Instal l.ed Instruments Instrument Location                  Thermal      Smoke      OPERABLE
: 7. Diesel Fuel Storage A.    #21 Tank el *s4                    2                        1 B.    #22 Tank el 84                    2                        1 C.    #21 Fuel Transfer Pump            1                        1 IJ.    #22 Fuel Transfer Pump            1                        1
: 8. Aux. Bldg. Vent System - El. 122 A. Elec. Penetration Area                          2            2 B. Switch Gear Room                                1            1 C. Relay Room & Control Room                      3            3.
: 9. Fuel Handling Bldg.
                                                                                        . I A. Vent Equip. Room                  3                        2        I B. Elec. Control Area                2                        1 C. New/Spent Fuel Storage Area                    5          4
: 10. Diesel Gen. Control Room A.    #21                                            1          1 B.  . #22                                            1          1
: c.    #23                                            1          1
: 11. Pumps A. Auxiliary Feed                                  5          4 B~    Boric Acid                                      3          2 C. RHR #21                                        4          3
                        #22                                        4          3 D. Safety Injection                                3          2 E. Component Cooling                              3          2 F. Containment Spray                              3          2 G.      Charging Pumps                                  3          3 SALEM.- UNIT 2                        3/4 3-49
 
. l.
9*
TABLE 3*.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed    Inst~ 11 ed Instruments Instrument Location                      Thermal      Smoke      OPERABLE
: 12. Auxiliary Bldg. Vent - 122 1 A. Building Supply/Exh. Fans                          9          7 B. Control Area Vent Fans                              5          4
: 13. Auxiliary Building Corridors A. Resin Storage - 122'                                4          3 B. Evaporators - 100 1                                5          4
: c. Waste Gas - 64 1                                    7          6
: 14. Penetration Rooms A. 78 1 - Mechanical                                  8          6 B. 100 1 - Mechanical                                .5          4 c..  *100 1 ..: Electrical (Chillers)                    6          4
: o. 100' *- Inner Piping (North)                        6          4 E. 100 1 - Outer Piping (South)                        5          4
: 15. Service Water A.    #21,  22,  23  Pump Bay                            6          4 B.    #24,  2 5,  2*6 Pump Bay                            6          4
: c.    #21,  22,  23  Control Room                        1          1 D.    #24,  2 5,  26  Control Room                        1          1
: 16. Main Steam Radiation Monitor Area          1                        1 SALEM - UNIT 2                          . 3/4 3-50
 
PLANT SYSTEMS 3/4.7.10  FIRE SUPPRESSION SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.1  Two fire suppression water systems shall be OPERABLE each with:*
: a. One fire suppression pump with a capacity of 2500 gpm with its discharge aligned to the fire suppression header.
: b. A separate water supply with a minimum contained volume of 300,000 gallons, and
: c. An OPERABLE flow path capable of taking suction from the tank and transferring the water through distribution piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm device on each sprinkler system, the isolation valve for each hose standpipe, and the last valve ahead of the deluge valve on each deluge or spray system required to be OPERABLE per Specifications 3.7.10.2 and 3.7.10.4.
APPLICABILITY:  At all times.
ACTION:
: a. With one pump and/or one water supply inoperable, restore the inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the plans and procedures to be used to-provide for the loss of redundancy .in this system. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
: b. With both fire suppression water systems inoperable:
: b. With both fire suppression water systems inoperable:
: 1. Establish a backup fire suppression water system within 24 hours, and 2. Submit a Special Report in accordance with Specification 6.9.2: a) By telephone within 24 hours, b) Confirmed by telegraph, _mailgram or facsimile transmission no later than the first working day following the event, and c) In writing within 14 days following the event, outlining the act ion taken, the cause of the i noperab il i ty and the pl ans and schedule for restoring the .system to OPERABLE status. SALEM -UNIT 2 3/4 7-31
: 1. Establish a backup fire suppression water system within 24 hours, and
'' '* I
: 2. Submit a Special Report in accordance with Specification 6.9.2:
* I I PLA.NT SYSTEMS SURVEILLANCE REQUIREMENTS 4.7.10.1.1 The fire suppression water system shall he demonstrated OPERABLE:
a)   By telephone within 24 hours, b)   Confirmed by telegraph, _mailgram or facsimile transmission no later than the first working day following the event, and c)   In writing within 14 days following the event, outlining the act ion taken, the cause of the i noperab il i ty and the pl ans and schedule for restoring the .system to OPERABLE status.
: a. At least once per 7 days by verifying the contained water supply volume. b. At least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path is in its correct position.
SALEM - UNIT 2                       3/4 7-31
: c. At least once per 12 months by performance of a system flush. d. At 1 east once per 18 months by performing a system function al test which includes simulated automatic actuation of the system throughout its operating sequence, and: 1. Verifying that each pump develops_
 
at 1 east 2500 gpm at a system
PLA.NT SYSTEMS SURVEILLANCE REQUIREMENTS 4.7.10.1.1   The fire suppression water system shall he demonstrated OPERABLE:
* head of 250 feet, 2. *cycling each manual valve in the flow path through at least one complete cycle of full travel, and 3. Verifying that each high pressure pump starts (sequentially) to maintain the fire suppression water system pressure greater than or equal to 135 psig. e. At 1 east once per 3 years by performing a fl ow test of the. system in accordance with Chapter 5, Section 11 of the Fire Protection Handbook, 14th Edition, published by the National Fire Protection Association.
: a. At least once per 7 days by verifying the contained water supply volume.
SALEM UNIT 2 3/4 7-32
: b. At least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path is in its correct position.
, ' e* PLANT SYSTEMS SURVEILLANCE REQUIREMENTS
: c. At least once per 12 months by performance of a system flush.
{Continued) 4.7.10.1.2 The fire pump diesel engine shall be demonstrated OPERABLE:
: d. At 1east once per 18 months by performing a system function al test which includes simulated automatic actuation of the system throughout its operating sequence, and:
: a. At 1 east once per 31 days by verifying;
: 1. Verifying that each pump develops_ at 1east 2500 gpm at a system
: 1. The fuel storage tank contains at least 300 gallons of fuel, and 2. The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow. b. At 1 east once per 92 days by verifying*
* head of 250 feet,
that a sample* of di es el f ue 1 from the fuel tank, obtained in accordance with ASTM-0270-65, is within the accept ab 1 e 1 i mits s pee ifi ed in Tab 1 e *1 of ASTM 097 5-7 4 when checked for visocity, water and sediment.
: 2.   *cycling each manual valve in the flow path through at least one complete cycle of full travel, and
: c. At least o*nce per 18*months, during shutdown, by subjecting the diesel to an inspection in accordance with procedures prepared in conjunctiion with its manufacturer's recommendations for class of service. . 4.7.10.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
: 3. Verifying that each high pressure pump starts (sequentially) to maintain the fire suppression water system pressure greater than or equal to 135 psig.
: a. At 1 east once per 7 days by verifying that: 1. The electrolyte 1 evel of each battery is above the pl ates, and 2. The overall battery voltage is greater than or equal to 24 volts -. b. At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery. c. At 1 east once per 18 months by verifying that: 1. The batteries, cell plates .and battery racks show no visual indication of physical damage or abnormal deterioration, and 2. The battery-to-battery.and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion materi a 1
: e. At 1east once per 3 years by performing a fl ow test of the. system in accordance with Chapter 5, Section 11 of the Fire Protection Handbook, 14th Edition, published by the National Fire Protection Association.
* SALEM -UN IT 2 3/4 7-33
I
'' . PLANT s*y STEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION' 3.7.10.2 The following spray and/or sprinkler systems shall be OPERABLE:
* I I
: a. Reactor Coolant Lube Oil b. Charcoal Filters 1. Containment Iodine Removal 2. Auxiliary Building Ventilation
SALEM   UNIT 2                         3/4 7-32
 
e*
PLANT SYSTEMS SURVEILLANCE REQUIREMENTS {Continued) 4.7.10.1.2   The fire pump diesel engine shall be demonstrated OPERABLE:
: a. At 1east once per 31 days by verifying;
: 1. The fuel storage tank contains at least 300 gallons of fuel, and
: 2. The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow.
: b. At 1east once per 92 days by verifying* that a sample* of di es el f ue 1 from the fuel stora~e tank, obtained in accordance with ASTM-0270-65, is within the accept ab 1e 1 i mits s pee ifi ed in Tab 1 e *1 of ASTM 097 5- 74 when checked for visocity, water and sediment.
: c. At least o*nce per 18*months, during shutdown, by subjecting the diesel to an inspection in accordance with procedures prepared in conjunctiion with its manufacturer's recommendations for class of service.
4.7.10.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:
: a. At 1east once per 7 days by verifying that:
: 1. The electrolyte 1evel of each battery is above the pl ates, and
: 2. The overall battery voltage is greater than or equal to 24 volts
      . b. At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.
: c. At 1east once per 18 months by verifying that:
: 1. The batteries, cell plates .and battery racks show no visual indication of physical damage or abnormal deterioration, and
: 2. The battery-to-battery.and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion materi a1
* SALEM - UN IT 2                       3/4 7-33
 
PLANT s*y STEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION' 3.7.10.2   The following spray and/or sprinkler systems shall be OPERABLE:
: a. Reactor Coolant ~ump  Lube Oil
: b. Charcoal Filters
: 1. Containment Iodine Removal
: 2. Auxiliary Building Ventilation
: 3. Control Room Emergency Air Conditioning
: 3. Control Room Emergency Air Conditioning
: 4. Containment Pressure Relief 5. Fuel Handling Building Ventilation
: 4. Containment Pressure Relief
: c. Charging Pumps do Diesel Fuel Oil Storage Tanks and Transfer Pumps e. Auxiliary Feedwater Pumps APPLICABILITY:
: 5. Fuel Handling Building Ventilation
Whenever equipment protected by the spray/sprinkler system is required to be OPERABLE:
: c. Charging Pumps do     Diesel Fuel Oil Storage Tanks and Transfer Pumps
ACTION: a. With one or more of the above required spray and/or sprinkler systems inoperable, within one hour establish a continuous fire watch with backup fire suppression equipment for those areas in which redundant systems or components could be damaged; for .other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission.
: e. Auxiliary Feedwater Pumps APPLICABILITY: Whenever equipment protected by the spray/sprinkler system is required to be OPERABLE:
pursuant to Specification  
ACTION:
: a. With one or more of the above required spray and/or sprinkler systems inoperable, within one hour establish a continuous fire watch with backup fire suppression equipment for those areas in which redundant systems or components could be damaged; for .other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission. pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and plans and schedule for restoring the system to OPERABLE status.
: b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
SALEM - UNIT 2                          3/4 7-34


====6.9.2 within====
'l '
the next 30 days outlining the action taken, the cause of the inoperability and plans and schedule for restoring the system to OPERABLE status. b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
PLANT SYSTEMS' SURVEILLANCE REQUIREMENTS
SALEM -UNIT 2 3/4 7-34 
'l ' PLANT SYSTEMS' SURVEILLANCE REQUIREMENTS
: 4. 7 .10.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:
: 4. 7 .10.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:
: a. ll.t least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path is in its correct position.
: a. ll.t least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path is in its correct position.
: b. At least once per 12 months by cycling each testable automatic valve in the flow path through at least one complete cycle of full travel. c. At least once per 18 months: 1. By performing a sYstem functional test which includes simulated automatic actuation of the system and verifying that the automatic valves in the flow path actuate to their correct positions.  
: b. At least once per 12 months by cycling each testable automatic valve in the flow path through at least one complete cycle of full travel.
* *2. By a visual inspection of the dry pipe spray and sprinkler  
: c. At least once per 18 months:
*headers to verify their integrity, and 3. By a visual inspection of each nozzle 1 s spray area to verify that the s_pray pattern is not ob'structed.
: 1.     By performing a sYstem functional test which includes simulated automatic actuation of the system and verifying that the automatic valves in the flow path actuate to their correct positions.           *
* d. At least once per 3 years by performing an air flow test through each open head spray header and verifying each open head spray nozzle is unobstructed.
                *2.     By a visual inspection of the dry pipe spray and sprinkler
SALEM -UN IT 2 3/4 7-35
                        *headers to verify their integrity, and
'' ' " ----PLANT SVSTEMS. LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION The following low pressure C02 systems shall be OPERABLE.with a minimum level of 50% and a minimum pressure of 285 psig in the associated storage tanks. a. Diesel Generator Areas b. Diesel Fuel o*il Storage c. Vital Switchgear Rooms d. Electrical Penetration Area APP LI CAB I LI TY: _Whenever equipment protected by the C02 systems is required to be OPERABLE.
: 3.       By a visual inspection of each nozzle 1 s spray area to verify that the s_pray pattern is not ob'structed. *
ACTION: a. Within one or more of the above required C02 systems inoperable, within one hour a continuous fire watch with backup fire suppression equipment for those reas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status-within 14 days or, in lieu of any other report required by Specification prepare.and submit a Special Report to the Commission pursuant to Specification
: d. At least once per 3 years by performing an air flow test through each open head spray header and verifying each open head spray nozzle is unobstructed.
SALEM - UN IT 2                             3/4 7-35


====6.9.2 within====
PLANT SVSTEMS.
the next 30 days outlining action taken; the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status. b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION 3~7.10.3      The following low pressure C02 systems shall be OPERABLE.with a minimum level of 50% and a minimum pressure of 285 psig in the associated storage tanks.
: a. Diesel Generator Areas
: b. Diesel Fuel o*il Storage
: c. Vital Switchgear Rooms
: d. Electrical Penetration Area APP LI CAB I LI TY: _Whenever equipment protected by the C02 systems is required to be OPERABLE.
ACTION:
: a. Within one or more of the above required C02 systems inoperable, within one hour establis~ a continuous fire watch with backup fire suppression equipment for those reas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status- within 14 days or, in lieu of any other report required by Specification 6.9'~1.
prepare.and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining th~ action taken; the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.
: b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.10.3 Each of the above required l_ow pressure C02 systems shall be demonstrated OPERABLE:
SURVEILLANCE REQUIREMENTS 4.7.10.3 Each of the above required l_ow pressure C02 systems shall be demonstrated OPERABLE:
: a. At least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path _is in its correct position.
: a. At least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path _is in its correct position.
: b. At least once per 7 days by verifying C02 storage tank level and pressure, and SAlEM -UNIT 2. 3/4 7-36
: b. At least once per 7 days by verifying C02 storage tank level and pressure, and SAlEM - UNIT 2.                           3/4 7-36
: t. I I
: t. I I
* PLANT SYSTEMS' LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 4.7.10.3 Each cif the above required low pressure C02 systems shall be demonstrated OPERABLE:
* PLANT SYSTEMS' LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 4.7.10.3 Each cif the above required low pressure C02 systems shall be demonstrated OPERABLE:
: c. At least once per 18 months by verifying:
: c. At least once per 18 months by verifying:
: 1. The system valves and associated ventilation dampers actuate manually and automatically, upon receipt of a simulated act u at i on s i g na 1 , an d 2. Fl ow from each nozzle during a "Puff Test. 11 SALEM -UNIT 2 3/4 7-36a
: 1. The system valves and associated ventilation dampers actuate manually and automatically, upon receipt of a simulated act uat i on s i gna 1 , an d
.,_ '* ,) .. PLANT SYSTEMS. FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION 3.7.10.4 The fire hose stations shown in Table 3.7-11 shall be OPERABLE.
: 2. Fl ow from each nozzle during a "Puff Test. 11 SALEM - UNIT 2                               3/4 7-36a
APPLICABILITY:
 
Whenever equipment in the areas protected by the fire hose stations is required to be OPERABLE.
.,_ '* ,) ..
ACTION: a. With one or more of the fire hose stations shown in Table 3.7-11 inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an OPERABLE hose station within 1 hour if the inoperable fire hose is the primary means of fire suppression; otherwise, route the additional hose within 24 hours. Restore the fire hose station to OPERABLE status within 14 days or, in lieu of any other *report reqwired by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification  
PLANT SYSTEMS.
FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION 3.7.10.4   The fire hose stations shown in Table 3.7-11 shall be OPERABLE.
APPLICABILITY: Whenever equipment in the areas protected by the fire hose stations is required to be OPERABLE.
ACTION:
: a. With one or more of the fire hose stations shown in Table 3.7-11 inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an OPERABLE hose station within 1 hour if the inoperable fire hose is the primary means of fire suppression; otherwise, route the additional hose within 24 hours. Restore the fire hose station to OPERABLE status within 14 days or, in lieu of any other *report reqwired by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining th.e action taken, the cause of the inoperability and plans and schedule for restoring the station to OPERABLE status.
: b. The provisions of Specifications 3.0.3 and 3.0.4 are not appl.icable.
SURVEILLANCE. REQUIREMENTS 4.7.10.4 Each of the fire hose
                                          -    stations shown in Table 3.7-11 shall
                                                                              . be demonstrated OPERABLE:
: a. At least once per 31 days by visual inspection of the hose stations outside the containment to assure all required equipment is a_t the station.
: b. At least once per 92 days by visual inspection of containment hose stations to assure all required equipment is at the station.
: c. At least once per 18 months by:
: 1. Removing the hose for inspection and re-racking, and
: 2. Inspecting all gaskets and replacing any degraded gaskets in the couplings.
SALEM - UN IT 2                        3/4 7-37
 
!..- '  )      I I\  f PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:
: d. At least once per 3 years by:
: 1. Partially opening each hose station val*ve to veri~ valve OPERABILITY and no flow blockage.
: 2. Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure available at that hose station.
SALEM - UNIT 2                        3/4 7-37a


====6.9.2 within====
6.- I  I       J
the next 30 days outlining th.e action taken, the cause of the inoperability and plans and schedule for restoring the station to OPERABLE status. b. The provisions of Specifications 3.0.3 and 3.0.4 are not appl.icable.
        ~
SURVEILLANCE.
t \I   ......
REQUIREMENTS 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be -. demonstrated OPERABLE:
TABLE   ~.7-11 1-1/2" FIRE HOSE STATIONS HOSE STATION NO.                             LOCATION 2FP-137                 100-A2-GG14       Aux i 1 i ary Bldg.
: a. At least once per 31 days by visual inspection of the hose stations outside the containment to assure all required equipment is a_t the station. b. At least once per 92 days by visual inspection of containment hose stations to assure all required equipment is at the station. c. At least once per 18 months by: 1. Removing the hose for inspection and re-racking, and 2. Inspecting all gaskets and replacing any degraded gaskets in the couplings.
2FP- 75                 100-A2-NN14       Aux i 1 i ary Bldg.
SALEM -UN IT 2 3/4 7-37 i I I   
2FP- 74                 84"'."A2-NN14   Auxiliary Bldg.
!..-' ) I -I\ f .-. . PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:
2FP-136                 84-A2-GG14       Auxiliary Bldg.
: d. At least once per 3 years by: 1. Partially opening each hose station val*ve to valve OPERABILITY and no flow blockage.
2FP-135                 64-A2-GG14       Auxiliary Bldg.
: 2. Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure available at that hose station. SALEM -UNIT 2 3/4 7-37a 6.-I I J t \I ...... TABLE 1-1/2" FIRE HOSE STATIONS HOSE STATION NO. LOCATION 2FP-137 100-A2-GG14 Aux i 1 i ary Bldg. 2FP-75 100-A2-NN14 Aux i 1 i ary Bldg. 2FP-74 84"'."A2-NN14 Auxiliary Bldg. 2FP-136 84-A2-GG14 Auxiliary Bldg. 2FP-135 64-A2-GG14 Auxiliary Bldg. 2FP-73 64-A2-NN14 Au xi 1 i ary Bldg. 2FP-134 55-A2-GG14 Auxiliary Bldg. 2FP-138 122-A2-GG14 Auxiliary Bldg. 2FP-76 122-A2-NN14 Auxiliary Bldg. 2FP-231 100-A-AA14.2 Auxiliary Bldg. 2FP-283 100-A2-EE 14 Auxiliary Bldg. 2FP-27.9 100-A2-KK17  
2FP- 73                 64-A2-NN14       Au xi 1 i ary Bldg.
.8 Auxiliary Bldg* 2FP-230 84-A2-AA14.2 Auxi 1 i ary Bldg. 2FP-229 64-A2-AA14.2 Au xi li a ry Bldg. 2FP-88 El. 78 Cont. #2 2FP-97 El. 78 Cont. #2 ' 2FP-89 El. 130 Cont. #2 2FP-96 El. 130 Cont. #2 SALEM -UN IT 2 3/4 7-38 PLANT SYSTEMS-HALON SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.5 The Relay Room Halon system shall be OPERABLE with the storage tanks having* at least 95% of full liquid volume and 90% of full pressure.
2FP-134                 55-A2-GG14       Auxiliary Bldg.
APPLICABILITY:
2FP-138                 122-A2-GG14       Auxiliary Bldg.
Whenever equipment in the Halon protected area is required to be OPERABLE.
2FP- 76                 122-A2-NN14       Auxiliary Bldg.
ACTION: a. With the above required Halon system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area(s) within 1 hour; restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare a*nd submit a Special Report to the Commission pursuant to Specification
2FP-231                 100-A-AA14.2     Auxiliary Bldg.
2FP-283                 100-A2-EE 14     Auxiliary Bldg.
2FP-27.9               100-A2-KK17 .8   Auxiliary Bldg*
2FP-230                 84-A2-AA14.2     Auxi 1 i ary Bldg.
2FP-229                 64-A2-AA14.2     Au xi li a ry Bldg.
2FP- 88                 El. 78     Cont. #2 2FP- 97                 El. 78     Cont. #2 2FP- 89                 El. 130 Cont. #2 2FP- 96                 El. 130 Cont. #2 SALEM - UN IT 2         3/4 7-38


====6.9.2 within====
PLANT SYSTEMS-HALON SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.5 The Relay Room Halon system shall be OPERABLE with the storage tanks having* at least 95% of full liquid volume and 90% of full pressure.
the next 30 days outlining the action the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status. b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
APPLICABILITY:  Whenever equipment in the Halon protected area is required to be OPERABLE.
SURVEILLANCE REQUIREMENTS 4.7.10.5 The above required Halon system shall be demonstrated OPERABLE:
ACTION:
: a. With the above required Halon system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area(s) within 1 hour; restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare a*nd submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken~ the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.
: b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.10.5   The above required Halon system shall be demonstrated OPERABLE:
: a. At least once per 6 months by verifying Halon storage tank liquid volume and pressure.
: a. At least once per 6 months by verifying Halon storage tank liquid volume and pressure.
: b. At least once per 18 months by: 1. Verifying the system, including associated ventilation dampers actuates manually and automatically, upon receipt of a simulated  
: b. At least once per 18 months by:
; . actuation signal, and ' 2. Performance of a visual inspection of the discharge nozzles to assure that they are free of debris or obstruction.
: 1. Verifying the system, including associated ventilation dampers actuates manually and automatically, upon receipt of a simulated ;.
SALEM -UNIT 2 3/4 7-39
actuation signal, and                                           '
'-'* 1 .J .. . A I 1 a '---* PLANT SYSTEMS 3/4.7.11 PENETRATION FIRE BARRIERS LIMITING CONDITION FOR OPERATION 3.7.11 All penetration fire barriers (including cable penetration barriers, firedoors and fire dampers), in fire zone boundaries, protecting safety related areas shall be OPERABLE.
: 2. Performance of a visual inspection of the discharge nozzles to assure that they are free of debris or obstruction.
APPLICABILITY:
SALEM - UNIT 2                         3/4 7-39
At a 11 ti mes. ACTION: a. With one or of the above required penetration fire barriers inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one*side of the inoperable fire barrier and establish an hourly fire watch patrol. Restore. the inoperable penetration fire barriers(s) to OPERABLE status within 7 days or, in lieu of any other report required by Specification
-6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification


====6.9.2 within====
  '- '*  1    .J
the next 30 days outlining the action taken, the cause of the inoperable fire barrier and plans and schedule-for restoring the penetration fire barr'ier(s) to OPERABLE status. b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
. A  I  1 a  '-
PLANT SYSTEMS 3/4.7.11  PENETRATION FIRE BARRIERS LIMITING CONDITION FOR OPERATION 3.7.11 All penetration fire barriers (including cable penetration barriers, firedoors and fire dampers), in fire zone boundaries, protecting safety related areas shall be OPERABLE.
APPLICABILITY:    At a11 ti mes.
ACTION:
: a. With one or mo~e of the above required penetration fire barriers inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one*side of the inoperable fire barrier and establish an hourly fire watch patrol. Restore. the inoperable penetration fire barriers(s) to OPERABLE status within 7 days or, in lieu of any other report required by Specification
                            -6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperable fire barrier and plans and schedule-for restoring the penetration fire barr'ier(s) to OPERABLE status.
: b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
SURVEILLANCE REQUIREMENTS 4.7.11 Each of the above required penetration fire barriers shall be verified to be OPERABLE:
SURVEILLANCE REQUIREMENTS 4.7.11 Each of the above required penetration fire barriers shall be verified to be OPERABLE:
: a. At 1 east once per 18 months by a vi sua 1 inspection, and b. Prior to returning a penetration fire barrier to OPERABLE status following repairs or maintenance by the performance of a visual inspection of the affected penetration fire barrier(s).
: a. At 1east once per 18 months by a vi sua 1 inspection, and
SALEM -UN IT 2 3/4 7-40}}
: b. Prior to returning a penetration fire barrier to OPERABLE status following repairs or maintenance by the performance of a visual inspection of the affected penetration fire barrier(s).
SALEM - UN IT 2                       3/4 7-40}}

Latest revision as of 12:19, 23 February 2020

Proposed Tech Specs,Adding New Equipment & Correcting Errors Re Fire Detection & Suppression
ML18092A319
Person / Time
Site: Salem  PSEG icon.png
Issue date: 09/21/1984
From:
Public Service Enterprise Group
To:
Shared Package
ML18092A318 List:
References
NUDOCS 8410190112
Download: ML18092A319 (35)


Text

INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.3.6 As a minimum, the fire detection instrumentation for each fire detec-tion zone shown in Table 3.3-10 shal1 be OPERABLE.

APP LI CAB I LI TY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.

ACTION:

With the number of OPERABLE fire detection instruments less than the minimum number OPERABLE requirement of Table 3.3-10:

a. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establ_ish a fire watch patrol to inspect the zone(s) with the inoperable instrument(s) at least once per hour, unJess .

the ihstrument(s) is loc~ted inside the containment, then inspect the containment at le~st once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or monitor the contain~ent air temperature at least once per hour at the locations list~d in Specification 4.6.1.5.

b. Restore the inoperable instrument(s) *ta OPERABLE st~tus within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within t.he next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument(s) to OPERABLE ~tatus .* *
c. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.3.3.6.1 Each of the above required fire detection instruments which are acc~ssible during operation shall be demonstrated OPERABLE at least once per 6 months by performance of a' function al test which includes subj ect.ing the detector to smoke or heat, as applicable. Fire detection instruments which are not accessible during operation shall be demonstrated OP£RABLE by performance of this functional test during each COLD SHUTDOWN ~xceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> except that s*uch demonstration need not be* performed rnore often than once per 6 months.

SALEM - UN IT 1 3/ 4 3-49 l

INSTRUMENTATION FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION (Continued) 4.3.3.6.2 The circuits between the above required detection instruments and the control room shall be demonstrated OPERABLE at least once per 92 days per approved procedures.

SALEM - UNIT 1 3/4 3-50

TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed Inst.a 11 ed Instruments Instrument Location Thermal Smoke OPERABLE*

1. Containment*

Main Coolant Pumps

  1. 11 4 3
  1. 12 4 3
  1. 13 4 3

!114 4 3

2. Control Room A. Ceiling Void 6 4 B. Control Console 2 1
c. Aux. Equip. Room 8 6 D. Computer Room 2 1
3. Cable Vaults

. #lC&D el 113 3 2

  1. 2A&B e1 113 3 2
  1. 2C&D el 113 3 2
4. Switchgear Rooms A. Relay Room el 100 18 16
13. Switch Gear el 84 18 16
c. Vital Bus el 64 18 16
n. El ec. Pent el 78 13 11
5. Battery Rooms A. #lA 125 V el 100 2 1 B. #1 2.50 V el 100 3 2
c. #lB 125 V el 100 2 1
o. #lC 125 V el 64 2 1
6. Diesel Generators*

A. #lA 5 4 B. #18 5 4

c. #lC 5 4
  • The fire detection instruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage Rate Tests.

SALEM - UN IT 1 3/4 3-51

TABLE 3.3-10 (Continued)

FIRE DETECTION INSTRUMENTS Minimum Installed Ins ta 11 ed Instruments Instrument Locat}on Thermal Smoke OPERABLE

7. Diesel Fuel Storage A. #11 Tank el 84 2 1 B* #12 Tank el 84 2 1 C. #11 Fuel Transfer Pump 1 1 D. #12 Fuel Transfer Pump 1 1
8. Aux. Bldg. Vent System - El. 122 A. Elec. Penetration Area 2 2 B. Switch Gear Room 1 1 C. Relay Room & .Control Room \3 3
9. Fuel Handling Bldg.

A. *vent Equip. Room 3 2 B. Elec~ Control Area 2 1 C. New/Spent Fuel Storage Area 5 4

10. Diesel Gen. Control Room A. #11 1 1 B. #12 1 1
c. #13 1 1
11. Pumps A. Auxiliary Feed 5 4 B. Boric Acid 3 2 C. RHR #11 4 3
  1. 12 4 3 D. Safety Injection 3 2 E. Component Cooling 3* 2 F. Containment Spray 3 2 G. Charging Pumps 3 3
12. Auxiliary Bldg. Vent - 122' A. Building Supply/Exh. Fans 9 7 B. Control Area Vent Fans 5 4 SALEM - UNIT 1 3/4 3-52

TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed Installed Instruments Instrument Location Thermal Smoke OPERABLE

13. Auxiliary Building Corridors A. Resin Storage - 122 1 4 3 B. Evaporators - 100 1 5 4
c. Waste Gas - 64' 7 6
14. .Penetration Rooms A. 78 1 - Mechanical 8 6 B. 100' - Mechanical 5 4 C. 100' - Electrical (Chillers) 6 4 D. 100 1 - Inner Piping (North) .6 4 E. 100 1* - Outer Piping (South) 5 4
15. Service Water A. #11, 12, 13 Pump Bay 6 4 B. #14, 15, 16 Pump Bay 6 4 C. #11, 12, 13 Control Room 1 1 0* #14 , 1 5, 16 Con t r o1 Ro om 1 1 16~ Main Steam Radiation Monitor Area 1 1
17. Auxiliary Building A. #11 & 12 Monitor Tank - El
  • 64 * .4 4 B. * #11 Waste Holdup Tank - El. 64 2 2 C. #12 Waste Holdup Tank El. 64 2 2 D. #1 Waste Mon HU Tank - El
  • 64 2 2 E. East Aisle 2 El. 64 4 4 F. West Aisle 2 El. 64 7 7 G. East Aisle 2 El. 84 4 4 H. West Aisle 2 El. 84 6 6 I. Ltdn/ Sea 1 Wtr HX Entry El. 84 2 2 SALEM - UNIT 1 3/4 3-53

PLANT SY.STEMS 3/4.7.10 FIRE SUPPRESSION SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.1 Two fire suppression water systems shall *be OPERABLE each with:

a. One fire suppression pump with a capacity of 2500 gpm with its discharge aligned to the fire suppression header.
b. A separate water supply with a minimum contained volume of 300,000 gallons, and
c. An OPERABLE flow path capable of taking suction from the tank and transferring the water through distribution piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm device on each sp~i~kler system, the i~olation valve for each hose standpipe, ~nd the last valve ahead of the deluge valve on each deluge or spray*

system required to be OPERABLE per Specifications 3.7.10.2 and 3.7.10.4.

APPLICABI'LITY: *At:all times.

ACTION:

a. With one pump and/or one water supply inoperable, restore the '

inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special R~port to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the plans and procedures to be used

. to provide for the lass of redundancy in this system. The prov1 s.i ans of Specifications 3.0~3 and 3.0.4 a~e not appli~able.

b. With both fire suppression water systems inoperable:
1. Establish a backup fire suppression water system within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />,.

and

2. Submit a Special Report in accordance with Specification 6.9.2:

a) By telephone .within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b) Confirmed by telegraph, mailgram*ar facsimile transmission no 1ater than the first working day fa 11 owing the event, and .

c) In writing within 14 days following the event, outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.

SALEM - UNIT 1 3/4 7-34

PLANT SYSTEMS' SURVEILLANCE REQUIREMENTS 4.7.10.1.1 The fire suppression water system shall be dem6nstrated OPERABLE:

a. At least once per 7 days by verifying the contained water supply volume.
b. At least once per 31 days by verifying that each valve (manual, po\'1er operated or automatic) in the flow path is in its correct position.
c. At least once per 12 months by performance of a system flush.
d. At 1east once per 18 months by performing a system funct i anal test which includes simulated automatic actuation of the system throughout its operating sequence, and:
1. Verifying that each pump develops at *least 2500 gpm at a system head ~f. 250 feet,
2. Cycling each manual valve in the flow path through at least one complete cycle of* full travel, and 3*. Verifying that each high *p.ressure pump starts (sequentially) to maintain the fire suppression water system pressure greater than or equal to 135 psig.

e.* At 1east once per 3 years by performing a fl ow test of the system in ac~ordance with Chapter 5, Section 11 of the Fi~e Protection Handbook, 14th Edition, published by the National Fire Protection Association.

SALEM - UNIT 1 3/4 7-35

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.1.2 The fire pump diesel engine shall be demonstrated OPERABLE:

a. At least once per 31 days by verifying;
1. The fuel storage tank contains at least 300 gallons of fuel, and
2. The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow.
b. At least once per 92 days by verifying that a sample of diesel fuel from the fuel storage tank, obtained in accordance with ASTM-0270-65, is within the acceptable limits specified in Table 1 of ASTM 0975-74 when checked for visocity, water and sediment.
c. At. least once per 18 months, during shutdown, by subjecting the diesel to an inspection* in accordance with procedures prepared in conjunctiion with its manufacturer's recommendations for class of service.

4.7.10.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:

a. At least once per 7 days by verifying that:
1. The electrolyte level of each battery is above the plates, and
2. The overal 1 battery voltage is greater than or equal to 24 volts.
b. At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.
c. At 1east once per 18 months by verifying that:
1. The batteries, cell plates and battery racks show no visual indication of physical damage'or abnormal deterioration, and
2. The battery-to-battery and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion material.

SALEM - UNIT 1 3/4 7-36

PLANT SYSTEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.2 The following spray and/or sprinkler systems shall be OPERABLE:

a. Reactor Coolant Pump Lube Oil
b. Charcoal Fi 1ters
1. Containment Iodine Removal
2. Auxiliary Building Ventilation
3. Control Room Emergency Air Conditioning
4. Containment Pressure* Relief
5. Fuel Handling Building Ventilation
c. Charging Pumps
d. Diesel Fuel Oil Storage Tanks and Transfer Pumps
e. Auxiliary Feedwater Pumps APPLICABILITY: Whenever equipment* protected by the spray /spri nk.l e'r system is required to be OPERABLE:

ACTION:

a. l~i th one or more of the above required spray and/or sprinkler systems inoperable, within one hour establish a continuous fire watch with backup fire suppressi~n equipment for those areas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and plans and schedule for restoring the system to OPERABLE status.
b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.

SALEM - UNIT 1 3/4 7-37

PLANT SYSTEMS*

a. At least once per 31 days by verifying that each valve (manual , powe.r operated or automatic) in the flow path is in its correct position.
b. At least once per 12 months by cycling each testable automatic valve in the flow path through at least one complete cycle of full travel.
c. At least once per 18 months:
1. -Sy performing a system functional test which includes simulated automatic actuation of the system and verifying that the automatic valves in the flow path actuate to their correct positions.
2. By a visual inspection of the dry pipe spray and sprinkler headers to verify their integrity, and II
3. By a visual inspection of each nozzle's spray area to verify that the spray pattern is not obstructed. I
d. At least once per 3 years by performing an air flow te.st through each open head spray header and verifying each open head spray nozzle is I

I i

0 unobstructed.

SALEM - UNIT 1 3/4 7-38

PLANT SYSTEMS LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.3 The following low pressure C02 system*s shall be OPERABLE with a minimum level of 50% and a minimum ....

pressure of 285 psig in the associated storage tanks.

a. Diesel Generator Areas
b. Diesel Fuel Oil Storage
c. Vital Switchgear Rooms
d. Electrical Penetration Area APPLICABILITY: Whenever equipment protected by the C02 systems is required to be OPERABLE.

ACTION:

a. Within one or more of the above required C02 systems i noperab 1e, within one hour establish a continuous fire watch with backup fire suppression equipment for those reas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days_ or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and the plans and schedule for res tori rig the system to OPERABLE status. *
b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.10.3 Each of the above required low pressure C02 systems shall be demonstrated OPERABLE:

opera e or au oma 1c 1n e 1 ow pa 1s 1n 1ts correct pos1t1on.

a. At letastd onc.e tper t3~ d)a~s tbyh vef rifyintght~at.ea~h valve (manua'.,.power 1
  • \
b. At least once per 7 days by verifying C02 storage tank level and pressure, and SALEM - UN IT 1 3/4 7-39

PLANT SYSTEMS

  • *e LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS
4. 7.10.3 Each of the above required 1ow pressure C02 sy_stems shal_l be demonstrated OPERABLE:
c. At least once per 18 months by verifying:
1. The system valves and associated ventilation dampers actuate manually and automatically, upon receipt of a simulated actuation signal, and
2.
  • Flow from each nozzle during a "Puff Test. 11 SALEM - UNIT 1 3/4 7-39a

PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION 3.7.10.4 The fire hose stations shown in Table 3.7-11 shall be OPERABLE.

APPLICABILITY: Whenever equipment in the areas protected by the fire hose stations is required to be OPERABLE.

ACTION:

a. With one or more of the fire hose stations shown in Table 3.7-11 inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an OPERABLE hose station within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> if the inoperable fire hose i.s the primary means of fire suppress ion; otherwise, route the additional hose withtn 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore the
  • fire hose station to OPERABLE status within* 14. days or; in* lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and plans and schedul.e for restoring.the station to OPERABLE status.
b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:

a. At least once per 31 days by visual inspection of the hose stations outside the containment to assure all required equipment is at the station.
b. At least once per 92 days by visual inspection of containment hose stations to assure all required equipment is at the station.
c. At least once per 18 months by:
1. Removing the hose for inspection and re-racking, and
2. Inspecting all gaskets and replacing any degraded gaskets in the couplings.

SALEM - UNIT 1 3/4 7-40

PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:

d. At least once per 3 years by:
1. Partially opening each hose station valve to verify valv~

OPERABILITY and no flow blockage.

2. Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure available at that* hose station.

SALEM - UNIT 1 3/4 7-40a

    • TABLE 3. 7-11 1-1/2" FIRE HOSE STATIONS HOSE STATION NO. LOCATION lFP-137 100-Al-GG14 Aux i 1i ary Bldg.

lFP- 75 100-Al-NN14 Au xi 1i ary Bldg.

lFP- 74 84-Al-NN14 Au xi 1 i ary Bldg.

lFP-136 84-Al-GG14 Auxiliary Bldg.

lFP-135 64-Al-GG14 Auxi 1i ary Bldg.

lFP- 73 64-Al-NN14 Auxiliary Bldg.

lFP-134 55-Al-GG14 . Au xi 1 i ary Bldg

  • lFP-138 122-Al-.GG14 Aux i 1i ary Bldg.

lFP- 76 122-Al-NN14 Au xi 1 i a ry B1dg

  • lFP-277 122-A-BB13.8 Aux il i a ry B1dg.

(Control Ar~a) lFP-262 100-Al-KKl0.4 Mechanical Penetr.Area lFP-279 100-Al-KK17.8 Auxiliary Bldg.

lFP- 88 El. 78 Cont. #1 lFP- 97 El. 78 Cont. #1 lFP- 89 El. 130 Cont. #1 lFP- 96 El

  • 130 Cont. #1 SALEM - UNIT 1 3/4 7-41

PLANT SYSTEMS HALON SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.5 *The Relay Room Halon system shall be OPERABLE with the storage tanks having at least 95% of full liquid volume and 90% of full pressure.

APPLICABILITY: Whenever equipment in tlie Halon protected area is- required to be OPERABLE.

ACTION:

a. With the above required Halon system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area(s) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />; restore the system to OPERABLE status within 14 days or, in 1i eu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlinin*g the action taken, the cause of the inoperability and the plans and sc::hedule for restoring the system to OPERABLE status.
b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS - 4.7.10.5 The above required Halon system shall be demonstr~ted OPERARLE:

a. At least once per 6 months by verifying Halon storage tank li*quid volume and pressure.
b. At least once per 18 months by:
1. Verifying the system, including associated ventilation dampers actuates manually and automatically, upon receipt of a simulated actuation signal, and
2. Performance of a visual inspection of the ~scharge nozzles to assure that they are. free of debris or obstruction.

SALEM - UNIT 1 3/4 7-42

PLANT SYSTEMS 3/4.7.11 PENETRATION FIRE BARRIERS LIMITING CONDITION FOR OPERATION 3.7.11 All penetration fire barriers (including cable penetration barriers, firedoors and fire dampers), in fire zone boundaries, protecting safety related areas shall b~ OPERABLE.

APPLICABILITY: At all times.

ACTION:

a. With one or more of the above required penetration fire barriers I inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one side of the inoperable fire barrier and establish an hourly fire watch patrol. Restore the inoperable penetration fire barriers(s) to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant

.to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperable fire barrier and plans and schedule for restoring the penetration fire barrier(s) to OPERABLE status.

b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.11 Each of the above required penetration fire barriers shall be verified to be OPERABLE:

a. At least once per 18 months by a visual inspection, and
b. Prior to returning a penetration fire barrier to OPERABLE status following repairs or maintenance by the performance of a visual inspection of the affected penetration fire barrier(s).

SALEM - UNIT 1 3/4 7-43

SALEM UNIT NO. 2 INSTRUMENTATION FIRE DETtCTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION 3.3.3.6 As a m1n1mum, the fire detection instrumentation for each fire detec-tion zone shown in Table 3.3-10 shall be OPERABLE.

APPLICABILITY: Whenever equipment protected by the fire detection instrument is required to be OPERABLE.

ACTION:

With the number of OPERABLE fire detection instruments less than the minimum number OPERABLE requirement of Table 3.3-10:

a. Within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> establish* a fire watch patrol to inspect*the zone(s) with the inoperable instrument(s) at least. once pe~ hour, unless the instrument(s) is locate9 inside the containment, then inspect the containment at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> or monitor the containment air temperature at least once per hour at the locations listed in Specification 4.6.1.5.
b. Restore the inoperable instrument(s) to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days *outlining the action taken, the cause of the inoperability and the plans and schedule for restoring the instrument(s) to OPERABLE status.
c. The provisions of Specifi~ations 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.3.3.6.1 Each of the above required fire detection instruments which are accessible during operation shall be demonstrated OPERABLE at least once per 6 months by performance of a functional test which includes subjecting the detector to smoke or heat, as applicable. Fire detection instruments which are not accessible during operation shall be demonstrated OPERABLE by performance of this functional test during each COLD SHUTDOWN exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> except that such demonstration need not be performed more often than once per 6 months.

  • SALEM - UNIT 2 3/4 3-46

,1 . '

INSTRUMENT ATI ON FIRE DETECTION INSTRUMENTATION LIMITING CONDITION FOR OPERATION (Continued) 4.3.3.6.2 The circuits between the above- re*quired detection instruments and the control room shall be demonstrated OPERABLE at least once per 92 days per.

approved procedures.

  • I SALEM - UNIT 2 3/4 3-47

TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Minimum Inst a 11 ed Inst a11 ed Instruments Instrument Location Thermal Smoke OPERABLE*

1. Containment Main Coolant Pumps
  1. 21 4 3
  1. 22 4 3
  1. 23 4 3
  1. 24 4 3
2. Control Room A. Ceiling Void 6 4 B. Control Console 2 1 C. Aux. Equip. Room 8 6 I). Computer Room 2 1
3. Cable Vaults
  1. lC&D e 1 113 . 3 2
  1. 2A&B el 113 3 2
  1. 2C&D el 113 3 2
4. Switchgear Rooms A. Relay Room el 100 18 16 B. Switch Gear el 84 18 16 C. Vital Bus el 64 18 16 D. El ec. Pent el 78
  • 13 11
5. Battery Rooms A. #2A 125 V el 100 2 1 B. #2 250 V el . 100 3 2
c. #2B 125 V el 100 2 1 D. #2C 125 V el 64 2 1
6. Diesel Generators A. #2A 5 4 B. #2B 5 4 C. #2C 5 4
  • The fire detection jnstruments located within the Containment are not required to be OPERABLE during the performance of Type A Containment Leakage.

Rate Tests.

SALEM - UN IT 2 3/4 3-48

~--------*

A\ ' I TABLE 3.3-10 (Continued)

FIRE DETECTION INSTRUMENTS Minimum Installed Instal l.ed Instruments Instrument Location Thermal Smoke OPERABLE

7. Diesel Fuel Storage A. #21 Tank el *s4 2 1 B. #22 Tank el 84 2 1 C. #21 Fuel Transfer Pump 1 1 IJ. #22 Fuel Transfer Pump 1 1
8. Aux. Bldg. Vent System - El. 122 A. Elec. Penetration Area 2 2 B. Switch Gear Room 1 1 C. Relay Room & Control Room 3 3.
9. Fuel Handling Bldg.

. I A. Vent Equip. Room 3 2 I B. Elec. Control Area 2 1 C. New/Spent Fuel Storage Area 5 4

10. Diesel Gen. Control Room A. #21 1 1 B. . #22 1 1
c. #23 1 1
11. Pumps A. Auxiliary Feed 5 4 B~ Boric Acid 3 2 C. RHR #21 4 3
  1. 22 4 3 D. Safety Injection 3 2 E. Component Cooling 3 2 F. Containment Spray 3 2 G. Charging Pumps 3 3 SALEM.- UNIT 2 3/4 3-49

. l.

9*

TABLE 3*.3-10 FIRE DETECTION INSTRUMENTS Minimum Installed Inst~ 11 ed Instruments Instrument Location Thermal Smoke OPERABLE

12. Auxiliary Bldg. Vent - 122 1 A. Building Supply/Exh. Fans 9 7 B. Control Area Vent Fans 5 4
13. Auxiliary Building Corridors A. Resin Storage - 122' 4 3 B. Evaporators - 100 1 5 4
c. Waste Gas - 64 1 7 6
14. Penetration Rooms A. 78 1 - Mechanical 8 6 B. 100 1 - Mechanical .5 4 c.. *100 1 ..: Electrical (Chillers) 6 4
o. 100' *- Inner Piping (North) 6 4 E. 100 1 - Outer Piping (South) 5 4
15. Service Water A. #21, 22, 23 Pump Bay 6 4 B. #24, 2 5, 2*6 Pump Bay 6 4
c. #21, 22, 23 Control Room 1 1 D. #24, 2 5, 26 Control Room 1 1
16. Main Steam Radiation Monitor Area 1 1 SALEM - UNIT 2 . 3/4 3-50

PLANT SYSTEMS 3/4.7.10 FIRE SUPPRESSION SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.1 Two fire suppression water systems shall be OPERABLE each with:*

a. One fire suppression pump with a capacity of 2500 gpm with its discharge aligned to the fire suppression header.
b. A separate water supply with a minimum contained volume of 300,000 gallons, and
c. An OPERABLE flow path capable of taking suction from the tank and transferring the water through distribution piping with OPERABLE sectionalizing control or isolation valves to the yard hydrant curb valves, the last valve ahead of the water flow alarm device on each sprinkler system, the isolation valve for each hose standpipe, and the last valve ahead of the deluge valve on each deluge or spray system required to be OPERABLE per Specifications 3.7.10.2 and 3.7.10.4.

APPLICABILITY: At all times.

ACTION:

a. With one pump and/or one water supply inoperable, restore the inoperable equipment to OPERABLE status within 7 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the plans and procedures to be used to-provide for the loss of redundancy .in this system. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.
b. With both fire suppression water systems inoperable:
1. Establish a backup fire suppression water system within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and
2. Submit a Special Report in accordance with Specification 6.9.2:

a) By telephone within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b) Confirmed by telegraph, _mailgram or facsimile transmission no later than the first working day following the event, and c) In writing within 14 days following the event, outlining the act ion taken, the cause of the i noperab il i ty and the pl ans and schedule for restoring the .system to OPERABLE status.

SALEM - UNIT 2 3/4 7-31

PLA.NT SYSTEMS SURVEILLANCE REQUIREMENTS 4.7.10.1.1 The fire suppression water system shall he demonstrated OPERABLE:

a. At least once per 7 days by verifying the contained water supply volume.
b. At least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path is in its correct position.
c. At least once per 12 months by performance of a system flush.
d. At 1east once per 18 months by performing a system function al test which includes simulated automatic actuation of the system throughout its operating sequence, and:
1. Verifying that each pump develops_ at 1east 2500 gpm at a system
  • head of 250 feet,
2. *cycling each manual valve in the flow path through at least one complete cycle of full travel, and
3. Verifying that each high pressure pump starts (sequentially) to maintain the fire suppression water system pressure greater than or equal to 135 psig.
e. At 1east once per 3 years by performing a fl ow test of the. system in accordance with Chapter 5, Section 11 of the Fire Protection Handbook, 14th Edition, published by the National Fire Protection Association.

I

  • I I

SALEM UNIT 2 3/4 7-32

e*

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS {Continued) 4.7.10.1.2 The fire pump diesel engine shall be demonstrated OPERABLE:

a. At 1east once per 31 days by verifying;
1. The fuel storage tank contains at least 300 gallons of fuel, and
2. The diesel starts from ambient conditions and operates for at least 30 minutes on recirculation flow.
b. At 1east once per 92 days by verifying* that a sample* of di es el f ue 1 from the fuel stora~e tank, obtained in accordance with ASTM-0270-65, is within the accept ab 1e 1 i mits s pee ifi ed in Tab 1 e *1 of ASTM 097 5- 74 when checked for visocity, water and sediment.
c. At least o*nce per 18*months, during shutdown, by subjecting the diesel to an inspection in accordance with procedures prepared in conjunctiion with its manufacturer's recommendations for class of service.

4.7.10.1.3 The fire pump diesel starting 24-volt battery bank and charger shall be demonstrated OPERABLE:

a. At 1east once per 7 days by verifying that:
1. The electrolyte 1evel of each battery is above the pl ates, and
2. The overall battery voltage is greater than or equal to 24 volts

. b. At least once per 92 days by verifying that the specific gravity is appropriate for continued service of the battery.

c. At 1east once per 18 months by verifying that:
1. The batteries, cell plates .and battery racks show no visual indication of physical damage or abnormal deterioration, and
2. The battery-to-battery.and terminal connections are clean, tight, free of corrosion and coated with anti-corrosion materi a1
  • SALEM - UN IT 2 3/4 7-33

PLANT s*y STEMS SPRAY AND/OR SPRINKLER SYSTEMS LIMITING CONDITION FOR OPERATION' 3.7.10.2 The following spray and/or sprinkler systems shall be OPERABLE:

a. Reactor Coolant ~ump Lube Oil
b. Charcoal Filters
1. Containment Iodine Removal
2. Auxiliary Building Ventilation
3. Control Room Emergency Air Conditioning
4. Containment Pressure Relief
5. Fuel Handling Building Ventilation
c. Charging Pumps do Diesel Fuel Oil Storage Tanks and Transfer Pumps
e. Auxiliary Feedwater Pumps APPLICABILITY: Whenever equipment protected by the spray/sprinkler system is required to be OPERABLE:

ACTION:

a. With one or more of the above required spray and/or sprinkler systems inoperable, within one hour establish a continuous fire watch with backup fire suppression equipment for those areas in which redundant systems or components could be damaged; for .other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare and submit a Special Report to the Commission. pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperability and plans and schedule for restoring the system to OPERABLE status.
b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.

SALEM - UNIT 2 3/4 7-34

'l '

PLANT SYSTEMS' SURVEILLANCE REQUIREMENTS

4. 7 .10.2 Each of the above required spray and/or sprinkler systems shall be demonstrated OPERABLE:
a. ll.t least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path is in its correct position.
b. At least once per 12 months by cycling each testable automatic valve in the flow path through at least one complete cycle of full travel.
c. At least once per 18 months:
1. By performing a sYstem functional test which includes simulated automatic actuation of the system and verifying that the automatic valves in the flow path actuate to their correct positions. *
  • 2. By a visual inspection of the dry pipe spray and sprinkler
  • headers to verify their integrity, and
3. By a visual inspection of each nozzle 1 s spray area to verify that the s_pray pattern is not ob'structed. *
d. At least once per 3 years by performing an air flow test through each open head spray header and verifying each open head spray nozzle is unobstructed.

SALEM - UN IT 2 3/4 7-35

PLANT SVSTEMS.

LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION 3~7.10.3 The following low pressure C02 systems shall be OPERABLE.with a minimum level of 50% and a minimum pressure of 285 psig in the associated storage tanks.

a. Diesel Generator Areas
b. Diesel Fuel o*il Storage
c. Vital Switchgear Rooms
d. Electrical Penetration Area APP LI CAB I LI TY: _Whenever equipment protected by the C02 systems is required to be OPERABLE.

ACTION:

a. Within one or more of the above required C02 systems inoperable, within one hour establis~ a continuous fire watch with backup fire suppression equipment for those reas in which redundant systems or components could be damaged; for other areas, establish an hourly fire watch patrol. Restore the system to OPERABLE status- within 14 days or, in lieu of any other report required by Specification 6.9'~1.

prepare.and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining th~ action taken; the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.

b. The provisions of Specification 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.10.3 Each of the above required l_ow pressure C02 systems shall be demonstrated OPERABLE:

a. At least once per 31 days by verifying that each valve (manual, power operated or automatic) in the flow path _is in its correct position.
b. At least once per 7 days by verifying C02 storage tank level and pressure, and SAlEM - UNIT 2. 3/4 7-36
t. I I
  • PLANT SYSTEMS' LOW PRESSURE C02 SYSTEMS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 4.7.10.3 Each cif the above required low pressure C02 systems shall be demonstrated OPERABLE:
c. At least once per 18 months by verifying:
1. The system valves and associated ventilation dampers actuate manually and automatically, upon receipt of a simulated act uat i on s i gna 1 , an d
2. Fl ow from each nozzle during a "Puff Test. 11 SALEM - UNIT 2 3/4 7-36a

.,_ '* ,) ..

PLANT SYSTEMS.

FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION 3.7.10.4 The fire hose stations shown in Table 3.7-11 shall be OPERABLE.

APPLICABILITY: Whenever equipment in the areas protected by the fire hose stations is required to be OPERABLE.

ACTION:

a. With one or more of the fire hose stations shown in Table 3.7-11 inoperable, route an additional equivalent capacity fire hose to the unprotected area(s) from an OPERABLE hose station within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> if the inoperable fire hose is the primary means of fire suppression; otherwise, route the additional hose within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore the fire hose station to OPERABLE status within 14 days or, in lieu of any other *report reqwired by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining th.e action taken, the cause of the inoperability and plans and schedule for restoring the station to OPERABLE status.
b. The provisions of Specifications 3.0.3 and 3.0.4 are not appl.icable.

SURVEILLANCE. REQUIREMENTS 4.7.10.4 Each of the fire hose

- stations shown in Table 3.7-11 shall

. be demonstrated OPERABLE:

a. At least once per 31 days by visual inspection of the hose stations outside the containment to assure all required equipment is a_t the station.
b. At least once per 92 days by visual inspection of containment hose stations to assure all required equipment is at the station.
c. At least once per 18 months by:
1. Removing the hose for inspection and re-racking, and
2. Inspecting all gaskets and replacing any degraded gaskets in the couplings.

SALEM - UN IT 2 3/4 7-37

!..- ' ) I I\ f PLANT SYSTEMS FIRE HOSE STATIONS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS (Continued) 4.7.10.4 Each of the fire hose stations shown in Table 3.7-11 shall be demonstrated OPERABLE:

d. At least once per 3 years by:
1. Partially opening each hose station val*ve to veri~ valve OPERABILITY and no flow blockage.
2. Conducting a hose hydrostatic test at a pressure of at least 50 psig greater than the maximum pressure available at that hose station.

SALEM - UNIT 2 3/4 7-37a

6.- I I J

~

t \I ......

TABLE ~.7-11 1-1/2" FIRE HOSE STATIONS HOSE STATION NO. LOCATION 2FP-137 100-A2-GG14 Aux i 1 i ary Bldg.

2FP- 75 100-A2-NN14 Aux i 1 i ary Bldg.

2FP- 74 84"'."A2-NN14 Auxiliary Bldg.

2FP-136 84-A2-GG14 Auxiliary Bldg.

2FP-135 64-A2-GG14 Auxiliary Bldg.

2FP- 73 64-A2-NN14 Au xi 1 i ary Bldg.

2FP-134 55-A2-GG14 Auxiliary Bldg.

2FP-138 122-A2-GG14 Auxiliary Bldg.

2FP- 76 122-A2-NN14 Auxiliary Bldg.

2FP-231 100-A-AA14.2 Auxiliary Bldg.

2FP-283 100-A2-EE 14 Auxiliary Bldg.

2FP-27.9 100-A2-KK17 .8 Auxiliary Bldg*

2FP-230 84-A2-AA14.2 Auxi 1 i ary Bldg.

2FP-229 64-A2-AA14.2 Au xi li a ry Bldg.

2FP- 88 El. 78 Cont. #2 2FP- 97 El. 78 Cont. #2 2FP- 89 El. 130 Cont. #2 2FP- 96 El. 130 Cont. #2 SALEM - UN IT 2 3/4 7-38

PLANT SYSTEMS-HALON SYSTEMS LIMITING CONDITION FOR OPERATION 3.7.10.5 The Relay Room Halon system shall be OPERABLE with the storage tanks having* at least 95% of full liquid volume and 90% of full pressure.

APPLICABILITY: Whenever equipment in the Halon protected area is required to be OPERABLE.

ACTION:

a. With the above required Halon system inoperable, establish a continuous fire watch with backup fire suppression equipment for the unprotected area(s) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />; restore the system to OPERABLE status within 14 days or, in lieu of any other report required by Specification 6.9.1, prepare a*nd submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken~ the cause of the inoperability and the plans and schedule for restoring the system to OPERABLE status.
b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.10.5 The above required Halon system shall be demonstrated OPERABLE:

a. At least once per 6 months by verifying Halon storage tank liquid volume and pressure.
b. At least once per 18 months by:
1. Verifying the system, including associated ventilation dampers actuates manually and automatically, upon receipt of a simulated ;.

actuation signal, and '

2. Performance of a visual inspection of the discharge nozzles to assure that they are free of debris or obstruction.

SALEM - UNIT 2 3/4 7-39

'- '* 1 .J

. A I 1 a '-

PLANT SYSTEMS 3/4.7.11 PENETRATION FIRE BARRIERS LIMITING CONDITION FOR OPERATION 3.7.11 All penetration fire barriers (including cable penetration barriers, firedoors and fire dampers), in fire zone boundaries, protecting safety related areas shall be OPERABLE.

APPLICABILITY: At a11 ti mes.

ACTION:

a. With one or mo~e of the above required penetration fire barriers inoperable, within one hour either establish a continuous fire watch on at least one side of the affected penetration, or verify the OPERABILITY of fire detectors on at least one*side of the inoperable fire barrier and establish an hourly fire watch patrol. Restore. the inoperable penetration fire barriers(s) to OPERABLE status within 7 days or, in lieu of any other report required by Specification

-6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperable fire barrier and plans and schedule-for restoring the penetration fire barr'ier(s) to OPERABLE status.

b. The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 4.7.11 Each of the above required penetration fire barriers shall be verified to be OPERABLE:

a. At 1east once per 18 months by a vi sua 1 inspection, and
b. Prior to returning a penetration fire barrier to OPERABLE status following repairs or maintenance by the performance of a visual inspection of the affected penetration fire barrier(s).

SALEM - UN IT 2 3/4 7-40