This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10. 2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1. 2.2 Refer to Section 7.0 of M-663-00017 A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017.
This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10. 2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1. 2.2 Refer to Section 7.0 of M-663-00017 A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017.
In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern. 3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details 3.6 TR-187 (M-663-00154), Fire and Hose Stream Test of a 8" thick specimen of #TC0-026 Ceramic Blanket used as a penetration seal material in a 12" diameter sleeve penetrated by bare pipe, insulated pipe, and copper, monel, and stainless steel instrument tubing 3.7 CTP-1002, (M-663-00083), Fire Qualification Test on Silicone Foam Floor Penetration Seals 3.8 CTP-1020 & 1021 (M-663-00060), Fire Qualification Test on Penetration Seals 3.9 Change Package 012957, Install Turbine Driven Auxiliary Feedwater Pump Standby Tanks, Rev. 0 M-663-00017 A Attachment B7 Revision W04 Page 5 of 8 3.10 WIP-M-1X1352-002-A-1, Auxiliary Bldg.-Area 5 Penetration Closure Plan EL. 2013'-6", EL. 2026'-0", EL. 2090'-0", Rev. 0 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.
In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern. 3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details 3.6 TR-187 (M-663-00154), Fire and Hose Stream Test of a 8" thick specimen of #TC0-026 Ceramic Blanket used as a penetration seal material in a 12" diameter sleeve penetrated by bare pipe, insulated pipe, and copper, monel, and stainless steel instrument tubing 3.7 CTP-1002, (M-663-00083), Fire Qualification Test on Silicone Foam Floor Penetration Seals 3.8 CTP-1020 & 1021 (M-663-00060), Fire Qualification Test on Penetration Seals 3.9 Change Package 012957, Install Turbine Driven Auxiliary Feedwater Pump Standby Tanks, Rev. 0 M-663-00017 A Attachment B7 Revision W04 Page 5 of 8 3.10 WIP-M-1X1352-002-A-1, Auxiliary Bldg.-Area 5 Penetration Closure Plan EL. 2013'-6", EL. 2026'-0", EL. 2090'-0", Rev. 0 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.
This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth. 5.0 Evaluation  
This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth. 5.0 Evaluation 5.1 Assessment of Condition to Design Requirements The penetration openings identified in Table I contain a pipe penetrant that exceeds the size limitation directly bounded by typical detail FB-1 from M-663-00017. The FB-1 detail, which is comprised of a 12" ceramic fiber depth between silicone impregnated fiberglass boots, directly qualifies a seal with up to a 6" diameter penetrant as 3-hour fire (F) and temperature (T) rated. TABLE I Penetrations with Penetrant Size Exceeding Detail FB-1 Limitations Penetration Communicating Pipe Penetrant Number Fire Areas Diameter Comments/
 
===5.1 Assessment===
 
of Condition to Design Requirements The penetration openings identified in Table I contain a pipe penetrant that exceeds the size limitation directly bounded by typical detail FB-1 from M-663-00017. The FB-1 detail, which is comprised of a 12" ceramic fiber depth between silicone impregnated fiberglass boots, directly qualifies a seal with up to a 6" diameter penetrant as 3-hour fire (F) and temperature (T) rated. TABLE I Penetrations with Penetrant Size Exceeding Detail FB-1 Limitations Penetration Communicating Pipe Penetrant Number Fire Areas Diameter Comments/
Disposition Side 1 Side2 P112W1378 A-1 C-1 30" See 5.2 P112W1380 A-1 C-1 30" See 5.2 P121S0271 A-1 A-4 12" See 5.2 P131S0492 A-8 A-1 24" See 5.2 P132S0682 A-8 A-1 24" See 5.2 P132S0739 A-8 A-1 8" See 5.2 P132W1844 A-8 A-3 24" See 5.2 P135S0232 A-15 A-33 10" See 5.2 P135S0233 A-15 A-33 8" See 5.2 P141S1014 A-16 A-8 24" See 5.2 P141W2486 A-16 A-26 12" See 5.2 P143W1488 A-5 F-4 12" See 5.2 P143W1489 A-5 F-4 12" See 5.2 P152W2585 A-19 A-22 10" See 5.2 P152W2617 A-19 A-22 8" See 5.2 P311W0839 C-1 CC-1 30" See 5.2 M-663-00017 A Page 6 of 8 Attachment B7 Revision W04 Penetration Communicating Pipe Penetrant Fire Areas Comments/
Disposition Side 1 Side2 P112W1378 A-1 C-1 30" See 5.2 P112W1380 A-1 C-1 30" See 5.2 P121S0271 A-1 A-4 12" See 5.2 P131S0492 A-8 A-1 24" See 5.2 P132S0682 A-8 A-1 24" See 5.2 P132S0739 A-8 A-1 8" See 5.2 P132W1844 A-8 A-3 24" See 5.2 P135S0232 A-15 A-33 10" See 5.2 P135S0233 A-15 A-33 8" See 5.2 P141S1014 A-16 A-8 24" See 5.2 P141W2486 A-16 A-26 12" See 5.2 P143W1488 A-5 F-4 12" See 5.2 P143W1489 A-5 F-4 12" See 5.2 P152W2585 A-19 A-22 10" See 5.2 P152W2617 A-19 A-22 8" See 5.2 P311W0839 C-1 CC-1 30" See 5.2 M-663-00017 A Page 6 of 8 Attachment B7 Revision W04 Penetration Communicating Pipe Penetrant Fire Areas Comments/
Disposition Number Side 1 Side2 Diameter P321S0085 C-6 C-1 8" See 5.2 P321S0086 C-6 C-1 8" See 5.2 P321S0123 C-6 C-1 8" See 5.2 P611W0082 F-1 F-2 8" See 5.2 P611W0197 F-2 F-3 12" See 5.2 P621S0153 F-5 F-3 10" See 5.2 P621S0156 F-4 F-3 12" See 5.2 P621S0157 F-4 F-2 12" See 5.2 P621S0162 F-4 F-2 12" See 5.2 P621W0009 F-4 F-5 12" See 5.2 P621W0017 F-5 F-4 12" See 5.2 P621W0221 A-5 F-4 12" See 5.2 P621W0224 A-5 F-4 12" See 5.2 P135S0943 A-15 A-33 10" See 5.2 P145S1019 A-23 A-15 8" See 5.2 5.2 Evaluation of Condition The Table I penetrations are considered 3-hour F rated based on the successful performance of the following fire tested configurations, which demonstrate that a minimum 8" depth of ceramic fiber will prevent the passage of flame and hose stream to the unexposed barrier side.
Disposition Number Side 1 Side2 Diameter P321S0085 C-6 C-1 8" See 5.2 P321S0086 C-6 C-1 8" See 5.2 P321S0123 C-6 C-1 8" See 5.2 P611W0082 F-1 F-2 8" See 5.2 P611W0197 F-2 F-3 12" See 5.2 P621S0153 F-5 F-3 10" See 5.2 P621S0156 F-4 F-3 12" See 5.2 P621S0157 F-4 F-2 12" See 5.2 P621S0162 F-4 F-2 12" See 5.2 P621W0009 F-4 F-5 12" See 5.2 P621W0017 F-5 F-4 12" See 5.2 P621W0221 A-5 F-4 12" See 5.2 P621W0224 A-5 F-4 12" See 5.2 P135S0943 A-15 A-33 10" See 5.2 P145S1019 A-23 A-15 8" See 5.2 5.2 Evaluation of Condition The Table I penetrations are considered 3-hour F rated based on the successful performance of the following fire tested configurations, which demonstrate that a minimum 8" depth of ceramic fiber will prevent the passage of flame and hose stream to the unexposed barrier side.

Latest revision as of 16:12, 5 May 2019

Revision 31 to Updated Safety Analysis Report, Penetration Seal Data, M-663-00017A, Rev W06, B6-3 to B7-79
ML18093B021
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 03/08/2018
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 M-663-00017A, Rev W06
Download: ML18093B021 (109)


Text

M-6 63-000 17A, Re vi sion WO l Page B6-3 ofB6-24 Penetration Seal Data Appendix:

86 Heat Affected Zone Review: P13150491 Fire Area (Side 1) A-8 Review Distances (Refe<enee I No i ssues w i th i n Heat Affected Zone 12" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1712 4.6 5.9 -1 1524 3.1 5.1 Fire Area (S i de 2) A-1 1.5 1357 3 4.3 No issues withi n Heat Affectea Zone 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 J 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 I 1 Side 1 Photo Side2Photo 5.5 555 0.7 6 4 9 9 I 0.4 6.5 1 4 50 0.2 7 4 06 0 7.5 368 Contac t ' No photo required. No photo required.

I l i Sk e tch No sketch required.

M-663-00017A , Revision WOI Page B -4 of 86-2 4 Penetration Seal Data Appendix:

B6 Penetration#:

P133S0780 Penetration Type: M-6A Fire Area (Side 1 ): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331 1. Barrier Thickness:

12" 10. Annular Gap (smallest)

2" 2. Opening S i ze: 18" 0 11. Gap between pen: N/A 3. Penetrants
(1) 12"P 12. Barrier Type: F 4. Sealant Type: Foam 13. Opening Sleeved or Concrete: Steel 5. Damm in g Side1: F oam fl ush wffloor 14. Pipe Insulated:

No 6. Damm in g Side 2: 2"recessed

7. Damming Continuity (Acc/Rej):

Accept 8. Boot Condition (Acc/Rej):

N/A 9. Sealant Depth: 9" Walkdown Comments:

Slab thickness determined by D rawing C-1 C13 11 Sketch: FA:. A*1 SIDE2 Wayne Aregood Prepared By: Jeff Suter Reviewed By:

M-6 63-0001 7 A , R evi ion WOJ P age 8 6-5 o f 86-2 4 Penetration Seal Data Append i x: 86 Photos: P133S0780 Fire Area A-8 (S i de 1) F i r e Ar ea A-8 (S i de 1) Fire Area A-1 (S i de 2) Fire Area A-1 (S id e 2)

M-663-0001 7 A , Rev i sion WOl Pa g e B6-6 of 8 6-24 Penetration Seal Data Append ix: B6 Heat Affected Zone Review: P133S0780 F i re Area (Side 1) A-8 Review Distances FigUre , No Issues wi t hin Heat Aff e cte d Zone Pipe ' l1&L2 Temp. R1 Radius R2 Radius Oist. (ft) ("F) (in) (in) 05 1712 4-.6 5.9 1 1524 3.7 5.1 --F i re Area (Side 2) A-1 1.5 1357 3 4.3 No i ssues with i n Heat Affect e d Zone 2 1209 2.3 3.6 2.5 1078 1.7 3.1 I 3 962 1.2 2.5 3.5 860 0.7 2.1 I 4 : 769 0.3 1.7 I i 4.5 1 689 Contac! 1.3 5 618 ' 1 S i de 1 Photo Side 2 Photo 5.5 555 i 0.7 6 499 I o.4 6.5 450 ! 02 7 406 l o 7.5 368 1 Contact No photo required.

No photo required.

I Sketch No sketch required.

l M-663-000l?A , R evisio n WOl Page 86-7 ofB6-24 Penetration Seal Data Appendix:

86 Penetration

  1. P133S0781 Penetration Type: M-6A Fire Area (Side 1): A-8 Fire Area (Side 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-OX1331 1. Barrier Thickness: 12" 10. Annular Gap (smallest):

2" 2. Opening Size: 1 8"0 11. Gap between pen: N/ A 3. Penetrants

(1) 12"P 12. Barrier Type: F 4. Seala nt Type: Foam 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: N/A 14. Pipe Insulated:

No 6. Damming Side 2: 2-1/2" recess Wayne Aregood 7. Damming Cont i nu ity (Ace/Rei):

Accept Prepared By: 8. Boot Condition (Acc/Rej):

N/A Jeff Suter 9. Sealant Depth: 12-1/2" Reviewed By: Walkdown Comments: Slab thicknes s dete rmined by Dr aw ing C-1 C1311. Changed from M-1 to M-6A based on sealant depth. Sketch: FA: A-8 1 M-663-00017A Revision WOI P age 86-8 of 8 6-24 Penetratio n Seal Data A ppend ix: 86 Photos: P133S0781 Fire Area A-8 (S i de 1) F ir e Area A-8 (S id e 1 ) Fi re Area A-1 (Side 2) Fi re Area A-1 (S ide 2)

M-663-0001 7A, Revision WOl Page B6-9 ofB6-24 Penetration Seal Data Appendix: B6 Heat Affected Zone Review: P133S0781 Fire Area (Side 1) A-8 Review Distances (Refe!81'101 M-U3-000 1 7A. F'll\ft 7.2.3-1 ) No issues within Heat Affected Zone 12ft Pipe l1&L2 Temp. R1 Radius R2 Radius Dist.l_f!}_

("F) iin) (in) 05 1712 4.6 5.9 1 1524 3.7 5.1 Fire Area (Side 2) A-1 1.5 1357 3 4.3 No issues with in Heat Affected Zone 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 I 86 0 0.7 2.1 4 769 0.3 1.7 4.5 689 Con tact 1 . .3 -5 618 1 Side 1 Photo Side 2 Photo 5.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 0 7.5 368 Con tact No photo required.

No photo required.

Sketch No sketch required.

l M-663-00017A Revi s ion WOl P age 86-J 0 of 86-24 Penetration Seal Data Appendix: B6 Penetration

  1. P141W2487 Penetration Type: M-6A Fire Area (Side 1): A-16 Fire Area (Side 2): A-26 Loc./Eiev.
2042'-11 M-OX Dwg: M-1X1938 1. Barr i er Thickness: 12" 10. Annular Gap (sma ll est): 1-1/2" 2. Opening Size: 18"0 11. Gap between pen: N/A 3. Penetrants
(1) 12"P 12. Barrier Type: F 4. Sealant Type: Foam 13. Opening Sleeved o r Concrete: Steel 5. Damm in g Side1: Flus h 14. P i pe Ins ul ated: No 6. Damming Side 2: Flus h Jeff Suter 7. Damming Cont i nuity (Ace/Rei): Accept Prepared By: 8. Boot Condition (Ace/Rei): N/A Wayne Aregood 9. Sealant Depth: 10" Reviewed B y: Wa l kdown Comments: Changed detail to M-6A based on field i nspection. Sketch: P141W2487 FA; A-26 Sld*2 M-663-00017A, Revision WOI P age 86-1 I of 86-24 Penetration Seal Data Appendix:

86 Photos: P141W2487 Fire Area A-16 (Side 1) Fi re Area A-16 (S ide 1) Fire Area A-26 (Side 2) Fire Area A-26 (S id e 2)

M-6 63-000l?A, R evisi o n WOl Penetration Seal Data Heat Affected Zone Review: P141W2487 F i re Area (Side 1) A-16 1. 1" Cond., (no 10): Not within Heat Affected Zone Fire Area {Side 2) A-26 2. 3" Cond. 4U3B2X, Not within Heat Affected Zone. Side 1 Photo Side 2 Photo No photo required. No photo required. Sketch Sklll:h FA: A-11 1 llde1 Page B6-12 ofB6-24 Append i x: B6 Review D i stances (Raferancl foMiS3.00017 A, FlgU'It 7 .2.3.1 ) 12* Pipe l1 &L2 Temp. R1 Radius R2 Rad i us D i st. (ft) (" F) (i n) (in) 0.5 1712 4.6 5.9 1 1524 3.7 5.1 1.5 1357 3 4.3 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 ! 1.2 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Conta ct 1.3 -5 618 1 5.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 0 7.5 368 Contact r I M-663-000 17 A , R e vi s ion WO I Pa ge 86-J3 of B6-24 Penetration Seal Data Appendix: 86 Penetration

  1. P14251079 Penetration Type: M-6A F i re Area (Side 1): A-16 F i re Area (Side 2): A-8 Loc./Eiev.: 2026'-0" M-OX Dwg: M-1 X 1 421 1. Barrier Thick n ess: 20" 10. Annular Gap (smallest): 1-3/4" 2. Open i ng S i ze: 18"0 1 1. Gap between pen: N/A 3. Penetrants
(1) 12" P 12. Barrier Type: F 4. Sealant Type: Foam 13. Open i ng S l eeved o r Concrete: Steel 5. Damm i ng Side 1: N/A 14. P i pe Insulated:

No 6. Damming Side 2: R ece s sed 8" Jeff Suter 7. Dammi n g Con t in uity (Acc/Rej): Accept Prepared By: 8. Boot Condition (Acc/Re j): N/A Wayne Aregood 9. Sea l ant Depth: 15-1/2" Rev i ewed By: Walkdown Comments: Slab thickness based on C-O C1411. Damming recessed on bottom side approx i mately 8" ba sed on observation from the floor. Detai l changed to M-6A. Sketch: I ( '1i>) 0 P142S1079 M-663-00017A Revision WOl P a2.e 86-14 of B6-24 Penetration Seal Data Append i x: 86 Photos: P142S1079 Fire Area A-16 (S ide 1) Fire Area A-16 (Side 1) F i re Area A-8 (S i de 2) F ire Area A-8 (Side 2)

M-663-0001 7A, R e isi on WOI Page B6-15 ofB6-24 Penetration Seal Data Appendix: B6 Heat Affected Zone Rev i ew: P14251079 F i re A r ea (S i de 1) A-16 Review D i sta n ces (Referlnc:e t.4-663-00017A.

FCilR 7 .2.).1 } No Issues within Heal Affected Zone 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius D i st. (ft) (o F) (in) (in) 0.5 1712 4.6 5.9 I 1 1524 3.7 5.1 F i re Area (S i de 2) A-8 1.5 1357 3 1 4.3 2 1209 2.3 3.6 No issues within Heat Affected Zone 2.5 1078 1.7 3.1 3 962 12 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 S i d e 1 P hoto S i de2 Photo 5.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 0 7.5 368 C ontact No photo required. No photo required. Ske t c h No sketch required.

I M-663-0001 7 A , R e vi s ion WOI Page 86-1 of 86-24 Penetration Seal Data Appendix:

B6 Penetration

  1. P151S1196 Penetration Type: M-6A Fire Area (Side 1): A-20 Fire Area (Side 2): A-26 Loc./Eiev.: 204 7'-6" M-OX Dwg: M-1X 1 511 1. Barrier Thickness: 12" 10. Annular Gap (sma ll est): 1/8" 2. Opening Size: 16"0 11. Gap between pe n: N/A 3. Penetrants
(1) 1 2"P 12. Barrie r Type: F 4. Sealan t T ype: Foam 13. Opening Sleeved o r Concrete: Steel 5. Damming S i de1: N/A 1 4. Pipe I nsulated: No 6. Damming S i de 2: Ceramic fiber flush w i th barr i er p i a Jeff Suter 7. Damming Continu i ty (Acc/Rej): Accept Prepared By: 8. Boot Conditio n (Acc/Rej): N/A Wayne Areg o od 9. Sealant Depth: 12" Reviewed By: Walkdown Comments: Slab th i ckness based on M-1 X 1 511. C h ange Detai l to M-6A based on fie l d i nspection Sketch: FA: A-2 0 S i de 1 c+ ? (T.,p-) I,. ,. . , .(. -I> ex....-.

F A: A-26 P15 1 S1 1 98 S l de2 M-663-0001 7A Rev i s i on W OI P age 8 6-1 7 of 8 6-2 4 Penetration Sea l Data Appendix: 86 Photos: P151S1196 F i re Area A-20 (S i d e 1) F ire A r e a A-2 0 (S ide 1 ) Fi re Area A-26 (S i de 2) Fire Area A-26 (S i de 2)

Revision WOl Page 86-J 8 of 86-24 Penetration Seal Data Appendix: B6 Heat Affected Zone Review: P15151196 Fire Area (Side 1) A-20 Review Distances No issues with i n Heat Affected Zone 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (in) (in) 0.5 1712 1 4.6 5.9 '-1 1524 3.7 5.1 Fire Area (Side 2) A-26 1357 3 4.3 No Issues with i n Heat Affected Zone 2 1209 2.3 3.6 2.5 107 8 1.7 3.1 3 962 1.2 2.5 3.5 860 0.7 : 2.1 ' 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 Side 1 Photo Side2 Photo 5.5 555 0.7 6 499 0.4 .6.5 450 0.2 7 406 0 7.5 368 Contact ' No photo required.

No photo required.

' Sketch No sketch required.

J M-663-000 17 A , Revision WO I P age B 6-I 9 of 86-24 Penetration Seal Data Appendix: B6 Penetration

  1. P153W2557 Penetration Type: M-6 A Fire Area (Side 1): A-19 Fire Area (Side 2): A-20 Loc./Eiev.: 2063'-9 M-OX Dwg: M-O X 19 46 1. Barrier Thickness:

12" 10. Annular Gap (smallest)

1/2" 2. Opening Size: 1 6" D 11. Gap between pen: N/A 3. Penetrants:

(1) 12"P 12. Barrier Type: F 4. Sea l ant Type: Foam 13. Opening Sleeved o r Concrete: St eel 5. Damm i ng Side1: 1/2" recessed 14. Pipe Insulated: No 6. Damming Side 2: Flus h Way n e Are g o o d 7. Damming Continuity (Acc/Rej):

A cc ept Prepared By: 8. Boot Condition (Acc/Rej):

N/A J eff Suter 9. Sealant Depth: 9-1/2" Reviewed By: Walkdown Comments:

Wall t h i ckness determ i n e d by D raw i ng C-1 C 1521. Need new labe l s. i ncorrec tl y l abeled in P l ant. Cha n ged De t ai l from M-1 to M-6A based o n ac t ual se a l depth. Sketch: FA; A-111 Si d e 1 P1S3W2 S57 l> FA: A-0 SkM2

-663-00017A , Revision WOI Page 8 6-20 of B6-24 Penetration Sea l Data A p p end ix: 86 Pho t os: P 153W2557 Fire Area A-19 (Side 1) Fire Area A-19 (Side 1 ) Fire Area A-20 (Side 2) Fire Area A-20 (S i de 2)

M-663-00 017A, Revision WOl Penetration Seal Data Heat Affected Zone Review: P153W2557 Fire Are a (S i d e 1) A-19 1 No i ssues w ith in Heat Affected Zone

  • Fire Are a (S ide 2) A-20 1. Pipe Strut; No Issue Side 1 Photo Si d e 2 Pho t o No photo requ i red. No photo required. Sketch FA: A-11 Side 1 Page 86-21 ofB6-24 Append i x: 86 R eview Distances M-663-00017A.

L1 & L2 Dist. (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 l s.s 7 7.5 12" Pipe Temp. R1 Radius ("F) (in) 1712 4.6 1524 3.7 1357 . 1209 2.3 1078 1.7 962 1.2 860 0.7 769 0.3 689 Contact 618 555 499 450 406 368 FA: A-20 Skle2 R2 Radius (in) ! 5.9 5.1 4.3 3.6 3.1 2 , 5 2.1 1.7 -1.3 1 0.7 0.4 0.2 0 Contact M-663-00017A , Revision WOI Pa ge 86-22 of B6-24 Penetration Seal Data Appendix:

B6 Penetration#:

P621S0161 Penetration Type: M-6A Fire Area (Side 1 ): F-4 Fire Area (Side 2): F-2 Loc./Eiev.: 2026'-0" M-OX Dwg: M-OX6211 1. Barrier Thickness: 10" 2. Opening Size: 16" 0 3. Penetrants:

(1) 12"P 4. Sealant Type: Foam 5. Damming S i de1: Foam 2" above s lab 6. Damming Side 2: Flush w/ Q-Deck Valley 7. Damming Continuity (Acc/Rej):

Accept 8. Boot Condition (Ace/Rei):

N I A 9. Sealant Depth: 11" Walkdown Comments: Changed De tail from M-1 to M-6A based on actual foam depth. Sketch:

A P62150161

10. Annular Gap (smallest)
1-1/4" 11. Gap between pen: N/A 12. Barrier Type: F 13. Opening Sleeved or Concrete: 14. Pipe In sulated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: FA: f*2 Slde2 w Steel M-663-00 017A , R evision WO I P age B6-23 ofB6-2 4 Penetration Seal Data Appendix:

86 Photos: P621S0161 F ire Area F-4 (S id e 1) Fire Area F-4 (S i de 1) F ir e Area F-2 (Side 2) Fire Area F-2 (Side 2)

M-663-0001 7A, R evis ion WOI Penetration Seal Oata Heat Affected Zone Review: P621S0161 Fire Area (Side 1) F-4 No Issues within Heat Affected Zone Fire Area (Side 2) F-2 1. 4U6030 2" Cond.: Within Heat Affected Zone. Further review determined that this condl,lit is not PFSSD. Set-route oontrol is necessary , Side 1 Photo Side2Photo No photo required. Sketch FA: F ... Sldt1 -...... *u . * * ,...... . . . . "*.*.'-u.* ,. t

  • JL . 6 .*.* . . . . . Page 86-24 of Appendix: B6 Review Distances

!Rel--=s M-663-00017.0..

fi!)Yte ) L1 &l2 D i st. (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 12" Pipe Temp. R1 Radius J"F) (in) 1712 4.6 _!524 3.7 _!357 3 1209 2.3 1078 1.7 962 1.2 860 0.7 769 0.3 689 Contact 618 555 499 --450 406 ' 3 68 I

  • fA: F-2 Sld-.2 R2 Radius (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1.7 1.3 1 0.7 0.4 0.2 0 Contact --.

Page 1 i a CREEK . .......:.\,/NUCLEAR OPERATING CORPORATION M-663-00017A Attachment 87 Fire Protection Evaluation For Penetrant Size Exceeding Typical Detail FB-1 Limitation Rev. Prepared By Date Reviewed By Date No. W01 08/19/05 08/19/05 Jeff Suter Wayne S Aregood W04 12/14/11 12/15/2011 Don Garbe Jeff Suter M-663-000 17 A Attachment 87 Revision W04 Table of Contents Page 2 of 8 Revision Log .................................................................................................................................

3 1.0 Purpose .............................................................................................................................

4 2.0 Scope ................................................................................................................................

4 3.0 References

........................................................................................................................

4 4.0 Evaluation

.........................................................................................................................

5 5.0 Conclusions

.......................................................................................................................

8 Appendix 87, Penetration Seal Data ....................................................

(89 Total Pages)

M-663-00017 A Attachment B7 Revision W04 Revision Reason for Revision W01 Original Issue Page 3 of 8 Revision Log W04 Included new penetrations P135S0943 and P145S1019 added by C.P. 012957.

M-663-00017 A Attachment B7 Revision W04 1.0 Purpose Page 4 of 8 1.1 The purpose of this document is to evaluate existing penetration seals that are not directly bounded to the typical detail limitations established in M-663-00017.

This evaluation was conducted in effort to satisfy regulatory expectation regarding qualification and documentation of fire barrier penetration seals, as discussed in NRC Information Notice 88-04. This evaluation was conducted in accordance with the guidance of NRC Generic Letter 86-10. 2.0 Scope 2.1 The Table I penetrations in relation to the design requirements discussed in Section 5.1. 2.2 Refer to Section 7.0 of M-663-00017 A for a cross-reference list of penetrations within Table I that are evaluated for additional seal parameters that do not satisfy the typical detail limitations of M-663-00017.

In these instances, the potential cumulative affects of multiple unbounded attributes were considered for each penetration of concern. 3.0 References 3.1 NRC Generic Letter 86-10, Implementation of Fire Protection Requirements, dated April 24, 1986 3.2 NRC Information Notice 88-04, Inadequate Qualification and Documentation of Fire Barrier Penetration Seals 3.3 10 CFR 50 Appendix R, Fire Protection Program For Nuclear Power Facilities Operating Prior To January 1, 1979 3.4 LER 87-10, Technical Specification Violations-Inoperable Fire Barriers Caused By Personnel Errors 3.5 M-663-00017, Penetration Seal Typical Details 3.6 TR-187 (M-663-00154), Fire and Hose Stream Test of a 8" thick specimen of #TC0-026 Ceramic Blanket used as a penetration seal material in a 12" diameter sleeve penetrated by bare pipe, insulated pipe, and copper, monel, and stainless steel instrument tubing 3.7 CTP-1002, (M-663-00083), Fire Qualification Test on Silicone Foam Floor Penetration Seals 3.8 CTP-1020 & 1021 (M-663-00060), Fire Qualification Test on Penetration Seals 3.9 Change Package 012957, Install Turbine Driven Auxiliary Feedwater Pump Standby Tanks, Rev. 0 M-663-00017 A Attachment B7 Revision W04 Page 5 of 8 3.10 WIP-M-1X1352-002-A-1, Auxiliary Bldg.-Area 5 Penetration Closure Plan EL. 2013'-6", EL. 2026'-0", EL. 2090'-0", Rev. 0 4.0 Assumptions 4.1 It is assumed that existing penetration seal materials have been installed as required by applicable typical design details and procedures.

This is an acceptable assumption based on a review of the Quality Control documentation maintained during initial penetration seal installation activities and the intrusive inspections conducted to address LER 87-10, regarding seal material depth. 5.0 Evaluation 5.1 Assessment of Condition to Design Requirements The penetration openings identified in Table I contain a pipe penetrant that exceeds the size limitation directly bounded by typical detail FB-1 from M-663-00017. The FB-1 detail, which is comprised of a 12" ceramic fiber depth between silicone impregnated fiberglass boots, directly qualifies a seal with up to a 6" diameter penetrant as 3-hour fire (F) and temperature (T) rated. TABLE I Penetrations with Penetrant Size Exceeding Detail FB-1 Limitations Penetration Communicating Pipe Penetrant Number Fire Areas Diameter Comments/

Disposition Side 1 Side2 P112W1378 A-1 C-1 30" See 5.2 P112W1380 A-1 C-1 30" See 5.2 P121S0271 A-1 A-4 12" See 5.2 P131S0492 A-8 A-1 24" See 5.2 P132S0682 A-8 A-1 24" See 5.2 P132S0739 A-8 A-1 8" See 5.2 P132W1844 A-8 A-3 24" See 5.2 P135S0232 A-15 A-33 10" See 5.2 P135S0233 A-15 A-33 8" See 5.2 P141S1014 A-16 A-8 24" See 5.2 P141W2486 A-16 A-26 12" See 5.2 P143W1488 A-5 F-4 12" See 5.2 P143W1489 A-5 F-4 12" See 5.2 P152W2585 A-19 A-22 10" See 5.2 P152W2617 A-19 A-22 8" See 5.2 P311W0839 C-1 CC-1 30" See 5.2 M-663-00017 A Page 6 of 8 Attachment B7 Revision W04 Penetration Communicating Pipe Penetrant Fire Areas Comments/

Disposition Number Side 1 Side2 Diameter P321S0085 C-6 C-1 8" See 5.2 P321S0086 C-6 C-1 8" See 5.2 P321S0123 C-6 C-1 8" See 5.2 P611W0082 F-1 F-2 8" See 5.2 P611W0197 F-2 F-3 12" See 5.2 P621S0153 F-5 F-3 10" See 5.2 P621S0156 F-4 F-3 12" See 5.2 P621S0157 F-4 F-2 12" See 5.2 P621S0162 F-4 F-2 12" See 5.2 P621W0009 F-4 F-5 12" See 5.2 P621W0017 F-5 F-4 12" See 5.2 P621W0221 A-5 F-4 12" See 5.2 P621W0224 A-5 F-4 12" See 5.2 P135S0943 A-15 A-33 10" See 5.2 P145S1019 A-23 A-15 8" See 5.2 5.2 Evaluation of Condition The Table I penetrations are considered 3-hour F rated based on the successful performance of the following fire tested configurations, which demonstrate that a minimum 8" depth of ceramic fiber will prevent the passage of flame and hose stream to the unexposed barrier side.

  • TR-187 -12" diameter opening containing a 2" bare and insulted pipe and three W' diameter tube penetrants.

The penetration was sealed with an 8" depth of ceramic fiber blanket.

  • CTP-1002 Penetration 6-12" diameter opening containing a 6" bare pipe penetrant.

The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

  • CTP-1 002 Penetration 10 -12" diameter opening containing a 6" insulated pipe penetrant.

The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

  • CTP-1020 Penetration 1 -6" diameter opening containing a 2" bare pipe penetrant.

The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots.

M-663-000 17 A Attachment 87 Revision W04 Page 7 of 8

  • CTP-1021 Penetration 1 -10" diameter opening containing a 2" bare pipe penetrant.

The penetration was sealed with a 12" depth of ceramic fiber blanket between silicone impregnated fiberglass boots. Ceramic fiber is an inert material comprised of compressed refractory fibers. It is not charred or consumed during fire exposure.

The material will not be negatively affected by heat transmission through the penetrating item. Therefore, penetrant size is not a concern regarding capability of a ceramic fiber seal to prevent flame and hose stream passage to the unexposed side. However, penetrant size is a concern regarding unexposed side temperature development.

Based on a comparison to the fire tested configurations bounding detail FB-1, the Table I penetrations are not considered T rated. M-663-00017 identifies that where piping penetrations exist that do not satisfy T rating requirements, a seal assembly with an F rating corresponding to the hourly rating of the associated barrier is acceptable, provided evaluation demonstrates that exposed insitu combustibles and redundant post fire safe shutdown (PFSSD) equipmenUcircuits on the unexposed barrier side will not be detrimentally affected by the increased penetrant temperatures.

In effort to evaluate fire area impact, field walkdowns and comprehensive assessment reviews, documented in Appendix 87, were conducted for each penetration of concern. For penetrations P135S0943 and P145S1019 the design location for the penetrations, as identified on M-1X1352, were reviewed and assessed in relation to the current field configuration.

The review for the Table 1 penetrations was completed in accordance with the criteria and review methodology established in M-663-00017A Section 7.2.3 for non-T rated penetrations.

The review identified that no exposed insitu combustibles or PFSSD circuits are located within the heat affected zone. Each of the penetrations satisfies the review criteria of M-663-00017 where T rating requirements are not met. Therefore, the penetrations are acceptable, as this evaluation demonstrates reasonable assurance that the penetration seals do not present a negative impact to PFSSD capability.

5.3 Post Fire Safe Shutdown Impact There is no impact to PFSSD systems or components as a result of this evaluation.

The Table I penetrations are 3-hour F rated. The comprehensive walkdown review for each of these penetrations revealed that no exposed insitu combustibles or PFSSD circuits are negatively affected by the non T rated penetrations.

M-663-000 17 A Attachment 87 Revision W04 6.0 Conclusions Page 8 of 8 Based on the above discussions, it is reasonable to conclude that the Table I penetration seals are acceptable as 3-hour F rated and will perform their intended function, regardless of not achieving a T rating. The penetration seals satisfy regulatory requirements and commitments as well as WCNOC Fire Protection Program requirements, to prevent spread of fire from one fire area to another. It has also been determined through this evaluation that the lack of a T rating will not affect the plant's ability to achieve and maintain PFSSD.

M-663-00017 A, Revision W04 Pa e 87-1 of 87-89 Penetration Seal Data Appendix: 87 Penetration

  1. P112W1378 Penetration Type: FB-1 Fire Area (Side 1): A-1 Fire Area (S i de 2): C-1 Loc./Eiev.: 19 7 9'-6" M-OX Dwg: M-1X1902 1. Barrier Thickness: 36" 10. Annu lar Gap (sma ll est): 3" 2. Opening Size: 42"0 11. Gap between pen: N/A 3. Penetrants
(1) 30"P 12. Barrier Type: A F 4. Seala nt Type: Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming S ide1: Boot 14. Pipe Insulated:

Yes 6. Damming Side 2: Boot Wayne Aregood 7. Damming Contin uity (A cc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Je ff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments:

Insulation abuts boot , does not tran si t i on t hrough seal zone. Insulation removed , no longer insul ated. Sketch:

M-663-000 17 A, Revision W04 Pa e B?-2 of B?-89 Penetration Sea l Data Appendix: B7 Photos: P112W1378 Fire Area A-1 (S ide 1) Fire Area A-1 (S ide 1) Fire Area C-1 (Side 2) F ir e Area C-1 (S i de 2)

M-663-00017 A Revision W04 Penetration Seal Data

  • Hea t Affected Zone Review: P112W1378
  • F i re Area (Side 1) A-1 No issues within Heat Affected Zone F i re Area (Side 2) C-1 No Issues within Heat Affected Zone S i de 1 Photo Side2Photo No photo required.

Sketch Pa e 87-3 of 87-89 Append i x: 87 Review Distances 30" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1706 1 4.5 5.9 1 1513 3.7 5 1.5 1342 2.9 4.2 2 1192 1 2.2 3.6 -2.5 1059 1.6 3 3 942 1.1 2.4 3.5 839 0.6 2 1 4 748 '0.2 1.6 ' 4.5 668 Conta ct 1..2 's 597 0.9 5.5 535 0.6 6 480 I 0.4 6.5 432 0.1 7 389 I Cont a ct No sketch required.

  • M-663-00017 A , Revision W04 Penetration Seal Data Penetration#:

P112W1380 Penetration Type: FB-1 Loc./Eiev.

1979'-6" 1. Barrier Thickness: 36" 2. Opening Size: 42"0 3. Penetrants
(1 l 30"P 4. Sea l ant Type: Ceram i c F iber 5. Damming Side1: Boot 6. Damming Side 2: Boot 7. Damming Continuity (A cc/Rej): N I A 8. Boot Condition (Acc/Rej):

Accept Pa e 87-4 of 87-89 Appendix:

B7 Fire Area (Side 1 ): A-1 M-OX Dwg: M-1X1902 Fire Area (Side 2): C-1 10. Annular Gap (smallest):

3" 11. Gap between pen: N/A 12. Barrier Type: A F 13. Opening Sleeved or Concrete: 14. Pipe In sulated: Yes Wayne Aregood Prepared By: J eff Suter Steel 9. Sealant Depth: Assumed Pe r Detail Reviewed By: Walkdown Comments: Sketch:

M-663-00017 A , Revision W04 Pa e 87-5 of 87-89 Penetration Seal Data Ap p e n d i x: 87 Photos: P112W1380 F ire A r ea A-1 (S i de 1) Fire Area A-1 (S i de 1) Fire A rea C-1 (Side 2) Fire Area C-1 (S i de 2)

M-663-000 17 A, Rev1s1on W04 Page 87-6 of 87-89 Penetration Seal Data Appendix: 87 Heat Affected Zone Review: P112W1380 Fire Area (Side 1) A-1 Review Distances

1. No issues within Heat Affected Zone 30" Pipe L1 & L2 Temp. R1 Radius R2 Radius Oist. (ft) (oF) (in) (in) 0.5 1706 4.5 5.9 1 1513 3.7 5 Fire Area (Side 2) C-1 1.5 1342 2.9 4.2 No Issues within Heat Affected Zone 2 1192 2.2 3.6 2.5 1059 1.6 3 3 942 1.1 2.4 3.5 839 0.6 2 4 748 0.2 1.6 4.5 66B Contact 1.2 Side 1 Photo Side2 Photo 5 597 1 0.9 5.5 535 0.6 6 480 I 0.4 6.5 432 1 0.1 7 389 Contact No photo required. I No photo required. Sketch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-7 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P121S0271 Penetration Type: F B-1 Fire Area (Side 1): A-1 Fire Area (Side 2): A-4 Loc J Eiev.: 1 988'-0" M-OX Dwg: M-O X12 11 1. Barrier Thickness:

22" 10. Annular Gap (smallest):

1/2" 2. Opening Size: 16" D 11. Gap between pen: N/A 3. Penetrants

(1) 12"P 12. Barrier Type: F R W 4. Sealant Type: Ceram ic F i ber 13. Open i ng Sleeved or Concrete: Steel 5. Damm i ng Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Ace/Rei): N J A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Ass ume d Per D et a i l Reviewed By: Walkdown Comments:

Slab thickness det e rm i ned from drawing C-OC1211. Sketch: FA: A-1 SIDE 1 FA: A-4 SIDE2 P121 S0271 M-663-00017 A, Revision W04 Pa e 87-8 of 87-89 Penetration Seal Data Append i x: B7 Photos: P12150271 F i re Ar e a A-1 (S i de 1 ) F i re Area A-1 (Side 1) F ir e Area A-4 (S ide 2) Fire Area A-4 (Side 2)

M-663-00017A, Rev1s1on W04 Page 67-9 of 67-89 Penetration Seal Data Appendix: 87 --Heat Affected Zone Review: P12150271 Fire Area (Side 1) A-1 Review Distances (Refer ence figure 7 2.3-1) No issues within Heat Affected Zone. 12" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (*f) (in) (in) 0.5 1712 4.6 5.9 I 1 1524 3.7 5.1 Fire Area (Side 2) A-4 1.5 135 7 3 4 , 3 No issues within Heat Affected Zone. 2 1209 2.3 3.6 -2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 Side 1 Photo Side2Photo 5.5 555 0.7

  • 6 499 0.4 6.5 450 0.2 7 406 0 7.5 368 Conta.ct No photo required.

No photo required.

I

' Sketch No sketch required.

M-663-00017 A , Revision W04 Pa e 87-10 of 87-89 Penetration Seal Data Appendix: B7 Penetration#:

P131S0492 Penetration Type: F B-1 Fire Area (Side 1): A-8 F i re Area (Side 2): A-1 Loc./Eiev.

2000'-0" M-OX Dwg: M-1 X 1311 1. Barrier Thickness:

10" 10. Annular Gap (smallest): 2" 2. Opening Size: 30"D 11. Gap between pen: N/A 3. Penetrants

(1) 24" P 12. Barrier Type: F 4. Sealant Type: Ceramic Fiber 13. Opening S l eeved or Concrete:

Steel 5. Damming S i de1: Boot 14. Pipe Ins ul ated: No 6. Damming S i de 2: Boot Wayne Aregood 7. Damming Con t inu it y (Acc/Rej): N/A Prepared By: 8. Boot Condit i on (Acc/Rej): Accept Jeff Suter 9. Sealant Depth: Assumed Per Deta il Reviewed By: Walkdown Comments: Slab th i ckness based on C-1 C 1311. Sketch: FA: A-8 Side 1 sec.no"-1 A .. , o. \0" AN (N eJ tJ -+=--_,_. (rtP) FA: A*1 Sid e 2 M-663-00017 A , Revision W04 Pa e 87-11 of 87-89 Penetration Seal Data Appe n dix: 87 Photos: P131S0492 F ir e Area A-8 (S i de 1) F ire A r ea A-8 (S i de 1) F ir e Area A-1 (S ide 2) F ir e Area A-1 (S i de 2)

M 663 00017A R . . W04 -..1 eVISIOn p age 8712 fB7 89 Penetration Seal Data Appendix: 87 H eat Affected Zone Review: P13150492

! F i re Area (Side 1) A-8 Review Distances FIQift 1.2.3-1 ) N o Issue s within H ea t Affected Zone I 24" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (*F) (in) (in) 0.5 1 1763 4.8 6.1 1 1615 4.1 5.5 F i re Area {Side 2) A-1 1.5 -1480 3.5 4.9 2 1357 3 4.3 No I ssues witrun H eat Af f e cted Zon e 2 , 5 3.8 2.5 1244 3 1141 2 3.3 3.5 1048 1.6 2.9 4 962 1.2 2.5 4.5 884 0.8 22 5 813 0.5 1.9 S i de 1 Photo Side 2Photo 5 , 5 748 I o.2 1.6 6 689 I Contact 1.3 I f 6.5 635 I 1.1 7 1 585 I 0.8 I' 7.5 1 540 0.6 -8 499 0.4 No photo required.

No photo required.

8.5 462 0.3 I* 9 427 0.1 I I 9.5 396 Contac t I I I Sketch No sketch required.

' I I I I M-663-00017 A , Revision W04 Pa eB7-13ofB7-89 Penetration Seal Data Appendix: B7 Penetration

  1. P13250682 Penetration Type: FB-1 Fire Area (Side 1 ): A-8 Fire Area (S i de 2): A-1 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1321 1. Barrier Thickness: 10" 10. Annular Gap (smallest): 2" 2. Opening S i ze: 30" D 11. Gap between pen: N/A 3. Penetrants
(1) 24" P 12. Barrier Type: F 4. Sealant Type: Ceram i c Fiber 13. Opening Sleeved or Concrete: Stee l 5. Damm i ng Side1: Boot 14. Pipe Insu l ated: No 6. Damming Side 2: Boot J ef f Suter 7. Damming Continu i ty (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): Ac c ept Wayne A r eg ood 9. Sealant Depth: Assumed Pe r De t ai l Reviewed By: Walkdown Comments: S lab t hi ckness determ i ned by Draw i ng C-1 C 1311 (wsa) Sketch: FA: A-4 Slde1 P1J2 S 0682 FA: A-1 Si d* 2 M-663-00017 A , Revision W04 Pa e 87-14 of 87-89 Penetration Seal Data Appendix: B7 Photos: P132S0682 F i re Area A-8 (S i de 1 ) F ir e Area A-8 (Side 1 ) Fire Area A-1 (S i de 2) F ir e Area A-1 (Side 2)

M 663 00017A R p B7 15 f87 89 W04 --' eVISIOn age -0 "' -* Penetration Seal Data Appendix: 87 Heat Affected Zone Review: P13250682 Fire Area (Side 1) A-8 Review Distances No issues with i n Heat Affected Zone I 24" Pipe L1 &U Temp. R1 Radius R2 Radius Dist. (ft) (O F) (in) (in) 0.5 1763 4.8 6.1 1 1615 4.1 5.5 F i re Area (Side 2) A-1 1 1.5 1480 3.5 4.9 No issues within Heat Affected Zone 2 1-35 7 3 1 4.3 2.5 1244 2.5 3.8 3 1141 2 3.3 3.5 1048 1.6 2.9 4 962 1.2 2.5 4.5 884 0.8 2.2 5 813 0.5 1.9 I S i de 1 Photo Side2 Photo 5.5 748 0.2 i 1.6 I 6 689 Contact 1.3 6.5 635 1.1 I 7 585 0.8 7.5 540 0.6 8 499 0.4 No photo requir ed. No photo required.

8.5 462 0.3 9 427 0.1 9.5 396 Conta ct J Sketch I No sketch required.

M-663-00017 A, Revision W04 Penetration Seal Data Penetration

  1. Penetration Type: Loc./Eiev.: 2000'-0" 1. Bar r ier T hi ckness: 2. Opening Size: 3. Penetrants
4. Seala n t Type: 5. Damm in g Side1: P132S0739 FB-1 12" 1 6"0 (1) 8" P Cer a m ic F i ber Bo ot 6. Damm in g S i de 2: Bo ot 7. Damming Continu i ty (Acc/Re j): N/A 8. Boot Condition (Acc/Rej): Accept Pa e 87-16 of 87-89 Appendix: B7 F i re Area (Side 1): A-8 F i re Area (S i de 2): A-1 M-OX Dwg: M-1 X 1 32 1 10. Annular G a p (smallest): 3" 11. Gap between pen: N f A 12. Barr i er T ype: F 13. Openi n g Sleeved o r Co n crete: S tee l 14. Pipe Ins ul ated: Yes Wayne A regood Prepared By: Jeff Su ter 9. Sealant Depth: Ass u m ed Pe r De t a il Reviewed By: Wa lk dow n Comments: S l a b thic k n e ss based on C-1 C 131 1. Sketch: FA: A-3 Slde 1 P132S0739
  • C) . . D .. I " . . . . 6 . *I tl. a OA ("T'ol?) FA: A*1 S i de 2 M-663-000 17 A , Revision W04 Pa e 87-17 of 87-89 Penetration Seal Data Appendix: 87 Photos: P132S0739 Fire Area A-8 (Side 1) Fire A r ea A-8 (Si de 1 ) Fire Area A-1 (S i de 2) F ir e Area A-1 (S ide 2)

M-663-00017 A, ReVISIOn W04 Page 87-18 ofB7-89 Penetration Seal Data Appendix:

B7 Heat Affected Zone Review: P132S0739 Fire Area (Side 1) A-8 Review Distances No issues within Heat Affected Zone &"Pipe L1 & L2 Temp. R1 Radius R2 Rad i us Dist. (ft) (*F) (in) (in) 0.5 1677 4.4 5.8 1 1463 3.4 4.8 F i re Area (Side 2) A-1 1.5 1277 2.6 3.9 No Issue$ within Heat Affected Zone 2 1116 1.9 3.2 2.5 976 . 1.2 2.6 3 855 0.7 2 3.5 750 : t 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 0.5 Side 1 Photo Side2Photo 5.5 453 0.2 6 402 0 6.5 358 Con tact No photo required.

o photo required.

Sketch No sketch requ1re

  • M-663-00017 A , Revision W04 Pa e 87-19 of 87-89 Penetration Seal Data Append i x: B7 Penetration
  1. P132W1844 Penetration Type: FB-1 Fire Area (Side 1): A-8 Fire A rea (S ide 2): A-3 Loc./Eiev.:

20 1 3'-9" M-OX Dwg: M-1X1918 1. Barrier Thickness:

12" 1 0. Annular Gap (smallest):

3" 2. Opening Size: 30" 0 11. Gap between pen: N/A 3. Penet rant s: (1) 24"P 12. Barrier Type: F 4. Sea lant Type: Ce r am i c F i be r 13. Opening Sleeved o r Concrete: 5. Damming Side1: Boot 14. P ipe Insulated:

Y es 6. Damm in g Side 2: Boot W ay n e Are g ood 7. Damming Continu ity (Acc/Rej):

N/A Prepared By: 8. Boot Condit i on (Acc/Rej):

  • A c cept Je ff Suter 9. Sealant Depth: Ass u med Pe r De t a il Reviewed By: Walkdown Comments: Wa l l thi ckness de t e rmined by Draw in g 1-CO 1321. I n s u lat i on encapsu l a t ed , ass u med OK. Sketch: FA; A-8 Side 1 p ....... -*. * * * * 'c:i: .. * .. *. fl . . *o. . . .... '
  • Q I
  • V * * * * \...-.--* .. ***o ." J 'o * ,_., * *
  • l /} I ' ;o., S.q'lr;J#AI
  • I D .D. * '.. ** P1 3.2W1844 FA: A-3 S lde2 Steel M-663-00017 A, Revision W04 Pa e 87-20 of 87-89 Penetration Seal Data Appendix: 87 Photos: P132W1844 F i re Area A-8 (S i de 1) F ir e Area A-8 (S i de 1 ) Fire Area A-3 (Side 2) Fire Area A-3 (S i de 2)

' M 663 00017A R --ev1s1on W04 p aoe B 21 f 87 89 7-0 -Penetrati.on Seal Data Appe n dix: 87 Heat Affected Zone Review: P132W1844 Fi r e Area (Si de 1) A-8 Review D i stances (Refwence .2.3-1 1 No Issues within Heat Affected Zone 24" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1763 4.8 6.1 1 1615 4.1 5.5 Fire Area (Side 2) A-3 1.5 1480 3.5 4.9 No i ssues within Heat Affected Zone 2 1357 3 4: 3 2.5 1244 2.5 3.8 3 1141 2 3.3 3.5 1048 1.6 2.9 4 962 1.2 2.5 4.5 884 0.8 2.2 5 813 0.5 1.9 Side 1 Photo Side 2 Photo 5.5 748 0.2 1.6 6 689 Contact 1.3 6.5 635 1.1 7 585 0.8 7.5 540 0.6 8 499 0.4 No photo required. No photo required. 8.5 462 0.3 9 427 0.1 9.5 3 96 Conta ct J Sketch No sketch required.

l !

M-663-00017 A, Revision W04 Pa e 87-22 of 87-89 Penetration Seal Data Appendix: B7 Penetration

  1. P135S0232 Penetration Type: F B-1 F i re Area (Side 1): A-15 Fire Area (S i de 2): A-33 Loc./Eiev.: 2000'-0" M-OX Dwg: M-1X1151 1. Barr i er Th i ckness: 16" 10. Annu lar Gap (smallest): 1 1/2" 2. Open i ng S i ze: 16"D 11. Gap be tw een pe n: N/A 3. Pe n etrants: (1) 10" P 12. Barr ierTy pe: A F w 4. Sea l a n t Type: Ce ramic F i ber 13. Open i ng Sleeved o r Concrete: St eel 5. D a mm ing S i de1: Boot 1 4. P i pe In s ulat ed: No 6. Damming S i de 2: Boot Wayne Aregood 7. Damm i ng Co n ti n u i ty (Acc/Rej): N/A Prepared B y: 8. Boot Condition (Acc/Rej): Accept Je ff Suter 9. Sea l ant Depth: Assumed Per Detai l Rev i ew ed B y: Walkdown Com m ents: Unders i de of slab has Q-Dec king , effect i ve barr i er th i ckness is measured from corrugated va lley. S k etch: FA:. A-15 SIDE 1 FA.: A-33 SIOE2 M-663-00017 A , Revision W04 Pa e 87-23 of 87-89 Penetration Seal Data Appendix: 87 Photos: P135S0232 F i re Area A-1 5 (S i de 1) Fire Area A-1 5 (S i de 1) Fire Area A-33 (S i d e 2) Fi r e Area A-33 (S i de 2)

, M 663 00017A R --eVISIOn W04 p ag_e 87 24 f B7 89 -0 ' -Penetration Seal Data Append i x: 87 -Heat Affected Zone Review: P13550232 Fire Area (Side 1) A*15 Review Distances

{Re!erenoa M-663-0001 7A. Figure 7.2.3-1 ) No issues within Heat Affected Zone 10R Pipe L1 &l2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1697 4.5 5.8 I I 1 1497 i 3.6 4.9 I Fire Area (Side 2) A-33 1.5 1321 [2.8 4.1 I No Issues within Heat Affected Zone 2 1167 : 2.1 3.5 2.5 1032 hs 2.8 I 3 914 1 2.3 3.5 810 0.5 1.8 4 719 0.1 1.4 4.5 639 Contact 1.1 5 569 0.8 Side 1 Photo Side 2 Photo 5.5 508 o.5 6 454 0.2 I 6.5 406 0 I 7 365 Contact -No photo requ i red. No photo required. Sketch No sketch required.

I I M-663-00017 A, Revision W04 Penetration Seal Data Penetration

  1. Pe n etration Type: Loc./Eiev.: 2000'-0" 1. Barrier Thickness: 2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming S i de 1: P135S0233 FB-1 16" 14"0 (1) S" P Ceramic F i ber Boot 6. Damming S i de 2: Boot 7. Damm i ng Cont i nuity (Acc/Rej): N I A 8. Boot Condition (Ace/Rei): Accept Pa e 87-25 of 87-89 Appendix: B7 Fire Area (Side 1): A-15 F i re Area (S i de 2): A-33 M-OXDwg: M-1X1151 10. Annular Gap (smallest): 1" 11. Gap betwee n pen: N/A 12. Barr i e r Type: A F w 13. Openi ng S l eeved o r Concrete: Steel 14. Pipe I nsu l ated: No Wayne A r eg ood Prepared B y: Jeff S u ter 9. Sealant Depth: Assumed Per Deta i l Rev i ewed By: Walkdown Com m ents: Underside of s l ab has Q-Deck i ng , effective barrier th ickness i s measured from corrugated valley. Sketch: FA: A-15 SIOE1 M-663-00017 A , Revision W04 Pa e 87-26 of 87-89 Penetration Seal Data Appendix: 87 Photos: P135S0233 Fire Area A-15 (Side 1 ) F ir e Are a A-15 (Side 1) Fire Area A-33 (Side 2) Fire Area A-33 (S ide 2)

M 663 00017A R . . W04 --eVISIOn p age B7 27 f 87 89 Penetration Seal Data Append ix: 87 --Heat Affected Zone Review: P13550233 F i re Area (Side 1) A-15 Review D i sta n ces Flgtn 7.2.3-1) No issues within Heat Affected Zone 8" Pipe L1 & l2 Temp. R1 Radius R2 Radius Dlst. {ft) (OF} (inJ (in) 0.5 1677 4.4 5.8 1 1 1463 3.4 4.8 F i re Area (Side 2) A-33 1.5 12n 2.6 3.9 No issues within Heat Affected Zone 2 1i16 1.9 3.2 I 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Con tad 1.2 4.5 581 0.8 5 512 0.5 S i de 1 Photo Side2Photo 5.5 453 02

  • 6 402 0 6.5 358 Contael No photo required. No photo required. I Sketch No sketch required.

I I I M-663-00017 A , Revision W04 Pa e 87-28 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P135S0943 Penetration Type: F B-1 Fire Area (Side 1): A-15 Fire Area (S i de 2): A-33 Loc./Eiev.: 2013'-6" M-OX Dwg: M-1X 1 352 1. Barrier Thickness: 12" 10. Annular Gap (smallest)
Not Rev i ewed 2. Opening Size: 14"0 11. Gap between pen: No t Rev i ewed 3. Penetrants
(1) 10" p 12. Barrier Type: A F P w 4. Sealant Type: Ceramic Fiber 13. Open i ng Sleeved or Concrete: Steel 5. Damming Side1: N I A 14. P i pe I ns ul ated: No 6. Damming Sid e 2: N I A Jeff Suter 7. Damming Con t inu i ty (Ace/Rei): N I A Prepared By: 8. Boot Condition (Acc/Rej): Not Reviewed Do n Garbe 9. Sealant Depth: Not Rev ie wed Reviewed By: Walkdown Comments:

T he wa l kdow n rev i ew was based on design location of the penetration , as i dent ifi ed on Ske t ch: FA. A-IS 'Srtlt. I T .. I>

M-1X 1 352 M-663-00017 A, Revision W04 Pa e 87-29 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P141S1014 Penet r at i on Type: FB-1 Fi r e Area (Side 1): A-16 F i re Area (Side 2): A-8 Loc./E ie v.: 2026'-0" M-OX Dwg: M-1X1411 1. Barrier Thickness: 20" 10. Annular Gap (smallest)
2-1/4" 2. Open i ng Size: 30"0 1 1. Gap between pen: N/A 3. Penetrants
(1) 24"P 12. Barrier Ty pe: F 4. Sealant T ype: Ceramic F i ber 13. Open i ng Sleeved or Concrete: Steel 5. Damming S i de1: Boo t 14. P i pe Insu l ated: No 6. Damming S i de 2: Boo t Jeff Suter 7. Damming Cont i nuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Re j): Accept Wayne Are good 9. Sealant Depth: Assumed per detail Reviewed By: Walkdown Comments: S lab thickness based on C-OC1 4 11. Sketch: FA: A-18 S i de 1 P141S1014 .a .. IJ' t ',P FA: A-8 Slde2 M-663-00017 A, Revision W04 Pa e B?-30 of B?-89 Penetration Seal Data Appendix: 87 Photos: P141S1014 F ire Area A-16 (S ide 1) Fire Area A-16 (S i de 1) Fire Area A-8 (Side 2} Fire Area A-8 (S ide 2)

M 663 00017A R . . W04 --eVJSJOn p age 67 31 fB7 89 Penetration Seal Data Appe n dix: 87 Heat Affected Zone Rev i ew: P14151014 F i r e Area (Sid e 1) A-16 Review D i stances F og iQ 7.2.3-1) No i ssues w i th i n Heat Affected Zone 24" Pipe L1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) (" F) (in) (in) 0.5 1763 4.8 6.1 1 1615 4.1 5.5 F i re Are a (Si de 2) A-8 1.5 1480 3.5 4.9 No issues within Heat Affected Zone 2 1357 3 4.3 2 , 5 1244 2.5 3.8 3 1 1141 2 3.3 3.5 1048 1.6 2.9 4 962 1.2 2.5 4.5 884 0.8 2.2 5 813 0.5 1.9 I S i d e 1 P hoto Side2Photo 5.5 748 0.2 1.6 6 689 Co n tact 1.3 6.5 635 1.1 7_ 585 0.8 7.5 540 0.6 8 499 0.4 I No photo required. No photo required. 8.5 462 0.3 I 9 427 0.1 I 9.5 396 Contact Sketch No sketch required.

I I I I I M-663-00017 A, Revision W04 Pa e 87-32 of 87-89 Penetration Sea l Data Appendix: B7 Penetration

  1. P141W2486 Penetration Typ e: F B-1 Fire Area (S id e 1): A-16 Fire A rea (Side 2): A-26 Loc./Eiev.: 2042'-11 M-OX Dwg: M-1X1 938 1. Barr ier Thickness:

1 2" 10. Annular Gap (smallest)

2" 2. Opening Size: 1 8"D 11. Gap between pen: N/A 3. Penet rants: (1) 1 2"P 12. Barrier Type: F 4. Seala nt Type: Ceram i c Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe I ns ul ated: No 6. Damming Side 2: Boot J eff Suter 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): A cc ep t Wayne Are g ood 9. Sealant Depth: Assumed per de t ai l Reviewed By: Walkdown Comments:

Sketch: F A: A*16 Skle1 P141W2486 ( ... ) (: 1 FA: A*26 Si d 2 M-663-00017 A, Revision W04 Pa e 87-33 of 87-89 Penetration Seal Data Appendix:

B7 Photos: P141W2486 Fire Area A-16 (S ide 1 ) Fire Area A-16 (Side 1) Fire Area A-26 (S ide 2) Fire Area A-26 (S ide 2)

M-663-000 17 A, Rev1s1on W04 PaQe 87-34 of 67-89 Penetration Seal Data Appendix:

87 . Heat Affected Zone Review: P141W2486 Fi r e Area (Side 1) A-1 6 No Issues within Heat Affected Zone Fi r e Area (Side 2) A-26 No Issues within Heat Affected Zone Side 1 Photo Side 2 Photo No photo required.

No photo required. Sketch No sketch required.

M-663-00017 A , Revision W04 Pa e 87-35 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P143W1488 Penetration Type: F B-1 F i re Area (Side 1 ): A-5 Fire Area (Side 2): F-4 Loc./Eiev.: 2043'-0" M-OX Dwg: M-O X 190 7 1. Barr i er Thickness: 48"
  • 10. Annular Gap (smallest)
2-1/2" 2. Opening Size: 18" 0 11. Gap between pen: N/A 3. Penetrants
(1) 1 2" P 12. BarrierType: A F 4. Sealant Type: Ceram i c F iber 13. Opening Sleeved or Concrete: Stee l 5. Damm i ng Side1: Boot 14. Pipe Insulated: N o 6. Damm i ng S i de 2: Bo o t W a y ne A regood 7. Damming Con t inuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): A cc ept Jeff Suter 9. Sealant Depth: 48"* Reviewed By: Walkdown Comments:
  • Th i s wa ll i s l ocated o n the East side of the A u x. B l dg and in t erfaces w i th the Fuel B l dg , in d ir e ctly. Ea ch bui l ding i s indep en dent w i t h a seism i c gap between t hem , re s u l ting in a 48" wall thickness. The corre s pond i ng F u e l B l dg Pe n. No. i s P621W0224. Que ri ed (L B) QC that was i nvolved w i th thi s sea l dur i ng co n str u ctio n. QC i nd i cated this sea l i s f u ll depth ceram i c fiber and is a separa t e seal from P62 1 W022 4. Sketch: FA: A..S Side 1 P143W 1 4811 o:. ,-., o**, *.,*t>* c.e llAII'I ,,

-:y,) FA: F-4 S kte2 M-663-00017 A , Revision W04 Pa e 87-36 of 87-89 Penetration Seal Data Append i x: 87 Photos: P143W1488 F i re Area A-5 (Side 1) F ir e Area A-5 (Side 1) Fire Area F-4 (S ide 2) F ir e Area F-4 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected Zone Review: P143W1488 Fire Area (Side 1) A-5 1. 5U5A96, Cable Tray, Not within Heat Affected Zone , F i re Area (Side 2) F-4

  • 2. 5U5P01 , 24" Cable Tray, Not within Heat Affected Zone. Seismic Gap, No issues. S i de 1 Photo Side 2 Photo No photo required.

No photo required. 1 Sketch Mf Pfll CIJM*T't' Pa e 87-37 of 87-89 Appendix: 87 Review Distances M-U3-<<JJ 17A fllura 7 11 1r Pipe L1 & L2 Temp. R1 Radius R2 Radius Oist. (ft) (*f) (in. (in) 0.5 1712 \4.6 '5.9 1 1524 3.7 5.1 1.5 1357 3 4.3 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 0.7 2.1 4 769 0.'3 1.7 4.5 689 Contact 1.3 5 618 1 -5.5 555 0_7 6 499 0.4 6.5 450 0.2 7 406 I 0 7.5 368 Co ntact M-663-00017 A , Revision W04 Pa e 87-38 of 87-89 Penetration Seal Data Appendix: B7 Penetration#:

P143W1489 Penetration Type: FB-1 Fire Area (Side 1): A-5 Fire Area (Side 2): F-4 Loc./E i ev.: 2043'-0" M-OX Dwg: M-OX 1 907 1. Barrier Thickness: 48"

  • 10. Annular Gap (smallest): 2" 2. Open i ng Size: 1 8"0 11. Gap between pen: N/A 3. Penetrants
(1) 12" P 12. Barr i er Type: A F 4. Sealant Type: Ceram i c F i be r 13. Opening Sleeved or Concrete: S teel 5. Damming Side 1: Bo ot 14. Pipe Insu l ated: No 6. Damm i ng Side 2: Bo ot Wayne A regood 7. Damming Cont i nu i ty (Acc/Rej): N I A Prepared By: 8. Boot Condition (Acc/Rej): A ccep t Jeff S u ter 9. Sealant Depth: 48". Reviewed B y: Wa l kdown Comments:
  • T h i s wa l l i s located on th e Eas t s i de of th e Aux. B l dg a n d in terf a ces w it h t he F u el B ldg , i nd irectly. Each bu i ld i ng i s in dependent w ith a se i sm ic g a p betwe en th e m , resu ltin g in a 48" wa ll th ickness. The co r respond i ng Fu el Bldg P e n. No. i s P 621W022 1. Quer i e d (L B) QC t hat was i n v olved w ith t his seal du r ing co n str u c ti o n. QC i nd i ca ted t hi s seal is f ul l depth ce r am i c fiber a nd is a s epara t e sea l f r om P62 1 W022 1. Sketch: FA: A-5 Slct.1 P621W0221

\) . . . . Sde2 M-663-00017 A , Revision W04 Pa e 87-39 of 87-89 Penetration Seal Data Appendix: 87 Photos: P143W 1 489 F i re Area A-5 (S i de 1) F ir e Area A-5 (S i de 1) Fire Area F-4 (S i de 2) Fi r e Area F-4 (S id e 2)

M-663-00017A, Revision W04 Penetration Seal Data Heat Affected Zone Review: P143W1489 Fire Area (Side 1) A-5 1. 5U485Q, 1" Cond.: Not within Heat Affected Zone 2. 5J1W28 , 3" Cond.: Not within Heat Affected Zone 3. 5U-5A1L, 1-112" Cond.: Not within Heat Affected Zone 4. 5J1W3L. 1-1/2" Cond.: Not within Heat Affected Zone 5. 5U5A96, 24" Cable Tray: Not within Heat Affected Zone I Fire Area (Side 2) F-4 See P621W0221 for Detail , No issues within Heat Affected Zone. Side 1 Photo Side2Photo No photo requ i red. Sketch Pa e 87-40 of 67-89 Appe n d ix: 87 Review Distances 7.2.3-1. 12" P i pe L1 & L2 Temp. R1 Radius R2 Radius D i st. (ft) (.F) (in) (in) 0.5 1712 4.6 5.9 1 1524 3.7 5.1 1.5 1357 3 4.'3 2 1209 2.3 3.6 2.5 1078 1.7 3J 3 962 1.2 2.5 3.5 860 0.7 2.1 4 .769 0.3 1.7 4.5 689 Contact 1.3 5 618 5.5 555 0.7 6 499 I 0.4 6.5 450 0.2 7 40 6 0 7.5 368 Contact I I M-663-00017 A, Revision W04 Pa e 87-41 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P145S1019 Penetration Type: F B-1 Fire Area (Side 1): A-2 3 Fire Area (Side 2): A-1 5 Loc./Eiev.: 2026'-0" M-OX Dwg: M-1 X 1352 1. Barrier Thick n ess: 24" 10. Annular Gap (sma ll est): Not Reviewed 2. Opening Size: 12"D 11. Gap between pen: No t Reviewed 3. Penetrants
(1) 8" p 12. Barrier Type: F P R W 4. Sealant Type: Cera mi c F i ber 13. Open i ng S l eeved o r Co n crete: S teel 5. Damming Side 1: N/A 14. Pipe I nsu l ated: No 6. Damming Side 2: N/A Jeff Suter 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Conditio n (Acc/Rej): Not Reviewed Don Garbe 9. Sealant Depth: No t Rev i ewed Reviewed By: Walkdown Comments: The walkdown review was based on des ig n location of the penetrat ion , as i de ntifie d on Sketch: fA* .4-:<.) '5l:i7E I ?1 4SSIC2>1"1 FJ: SER M-1X1352 M-663-00017 A, Revision W04 Pa e B7 -42 of B7 -89 Penetration Seal Data Appendix:

B7 Penetration

  1. P152W2585 Penetration Type: FB-1 Fire Area (Side 1): A-1 9 Fire Area (Side 2): A-22 Loc./Eiev.:

206 4'-1 1 M-OX Dwg: M-OX 1 947 1. Barrier Thickness: 12" 10. A nnular Gap (smallest)

1" 2. Opening Size: 14"0 11. Gap between pen: N/A 3. Penetrants
(1) 10" P 12. Barrier Type: A F 4. Se alant Type: Ceram i c F iber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Sid e 2: Boo t Wayne Aregood 7. Damm i ng Con tin uity (Acc/Rej):

N/A Prepared By: B. Boot Condit i o n (Acc/Rej):

Accept Jeff Suter 9. Seala nt Depth: Assumed P e r D eta i l Reviewed By: Walkdown Comments: Wall thickness de termin ed by Drawing C-1 C 1521. Sketch: P152W2S8S FA: A-.22 s dl2 M-663-00017 A , Revision W04 Pa e 87-43 of 87-89 Penetration Seal Data Appendix: 87 Photos: P152W2585 Fire Area A-19 (S ide 1 } Fire Area A-19 (Side 1) Fire Area A-22 (S ide 2} Fire Area A-22 (S ide 2}

M-663-00017 A, Revisjon W04 Page 87-44 of 87-89 Penetration Seal Data Appendix: 87 Heat Affected Zone Review: P152W2585 Fire Area (Side 1) A-19 Review Distances I {Ref8renat FJgUN ) No issues within Heat Affected Zone 10M Pipe L1 &l2 Temp. R1 Radius R2 Radius I Dist. (ft) ("F) (in) (in) 0.5 1697 4.5 5.8 1 1497 3.6 4.9 F ir e Area (Side 2) A-22 1.5 1321 2.8 4.1 No Issues within Heat Affected Zone 2 1167 2.1 3.5 2.5 1032 1.5 2.8 3 914 1 2.3 3.5 810 0.5 1.8 4 719 0.1 1.4 4.5 639 Con t a ct 1.1 5 569 0.8 S i de 1 Photo Side2Photo 5.5 508 0.5 6 454 02 6.5 406 0 I I 7 365 Contac t No photo required.

Sketch No sketch required.

M-663-00017 A, Revision W04 Penetration Seal Data Penetration

  1. Penetration Type: Loc./Eiev.: 2064'-11 1. Barrier Thickness:
2. Opening Size: 3. Penetrants:
4. Sea l a n t Type: 5. Damm i ng Side1: P152W2617 FB-1 1 0-1/2" 1 2" D (1) B"P Ceram i c Fiber Boot 6. Damming Side 2: Boot 7. Damming Con t inu i ty (Acc/Rej): N/A 8. Boot Condition (Acc/Rej): Accept Pa e B?-45 of B?-89 Appendix: B7 Fire Area (S i de 1): A-19 Fire Area (Side 2): A-22 M-OX Dwg: M-1X1948 10. Annular Gap (smallest)
0" 11. Gap between pen: N/A 12. Barrier Type: A F 13. Opening Sleeved o r Concrete: Steel 1 4. P i pe In s ula ted: No Wayne Aregood Prepared B y: Je ff S u ter 9. Sealant Depth: Assumed Per De tail Reviewed B y: Walkdow n Comments: Barrier th ickn ess based on drawing C-1C 1521. A-22 (side 2) co n crete ch i pped away to allow b oo t attachment.

Sketch: F A: A-19 S l de1 P152W2:617

' /) . #. t2."----. .. . . ' -C)* C>, * ** -. .

  • 0 f ** I), -* : D. F
  • A*22 Side2 M-663-00017 A, Revision W04 Pa e 87-46 of 87-89 Penetration Seal Data Append i x: 87 Photos: P152W2617 Fire Area A-19 (S id e 1 ) Fire Area A-19 (S ide 1) Fire Area A-22 (S i de 2) Fire Area A-22 (S ide 2)

M-663-00017 A, Revision W04 Penetration Seal Data Heat Affected Zone Review: P152W2617 Fire Area (Side 1) A-19 No Issues within Heat Affected Zone , fire Area (Side 2) A-22 1. 1-1/2" Cond. 5J1262 (seismic Monitor) within Heat Affected Zone. Further review de t ermined that this conduit is not PFSSD. Set-route control Is necessary. 2. 1-1/2" Cond. 1J3A18, not within Heat Affected Zone Side 1 Photo Side2Photo No photo required.

Sketch Pa e 87-47 of 87-89 Appendix: B7 Review Distances (Raferwloo M-663000171>..

Flgln 7.2.3-1 ) 8" Pipe l1 &L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) Jin) (in} 0.5 1677 4.4 5.8 1 1463 3.4 4.8 1.5 12n 2.6 3.'9 2 1116 1.9 32 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 12 4.5 581 0.8 5 512 0.5 5.5 453 0.2 6 402 0 6.5 35 8 Contac 1 M-663-00017 A Revision W04 Pa e 87-48 of 87-89 Penetration Seal Data Append i x: B7 Penetration

  1. P311W0839 Penetration Type: FB-1 Fire Area (Side 1): C-1 Fire Area (Side 2): CC-1 Loc./Eiev.: 1976'-0" M-OX Dwg: M-1X3901 1. Barrier Thick n ess: 36" 1 0. Annula r Gap (smallest): 2" 2. Opening Size: 36"0 11. Gap between pen: N/A 3. Penet ra nts: (1) 30"P 12. Barrier T ype: A F w 4. Sealant T ype: Ceram ic F i ber 13. Open in g S l eeved o r Concrete: Steel 5. Damming S i de 1: Boot 14. Pipe In sul ated: No 6. Damming S i de 2: Boo t Wayne Aregood 7. Damming Con t in u ity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Re j): A ccept Jeff Suter 9. Sealant Depth: Assumed Per Deta il Rev i ewed B y: Walkdown Comments: Barrier thickness determined by Draw i ng C-1 C3111. Sketch: FA: C-1 S l de1 Pl11W0839
  • ci , ...... " **
  • a ... -. t:>-I> D -* * -... " , . . ... . /J -o . ' V ' l 0 I -* />. , .. -(). --. FA: CC-1 Side2 M-663-00017 A , Revision W04 Pa e 87-49 of 87-89 Penetration Seal Data A pp end i x: 87 Photos: P311W0839 Fire Area C-1 (Side 1) Fi r e Area C-1 (Side 1 ) Fire Area CC-1 (Side 2) Fire Area CC-1 (Side 2)

M-663-000 17 A, Revision W04 Penet r ation Seal Data Heat Affected Zone Review: P311W0839 Fire Area (Side 1) 1. H/2* Cond. 5J1A1W: Not within Heat Affected Zone. Fire Area (Side 2) CC-1 1. No issues within Heat Affected Zone. Side 1 Photo Side 2 Photo No photo required. No photo required.

1 Sketch FA:c::-1 lld*1 .. Pa e 87-50 of B7 -89 Appendix:

87 Review Distances

{Refl!l'flllt.8 M-li63-00017A, 7.2 ,).1 ) L1 & L2 Dist. (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 1 6 6.5 7 30* Pipe Temp. R1 Radius (*F) (in) 1706 4.5 1513 3.7 1342 2.9 1 192 2.2 1059 1.6 942 1.1 839 0.6 1 748 0.2 ' 668 Contact 597 535 480 432 389 FA: CC.1 R2 Radius (in) 5.9 5 4.2 3.6 3 24 2 1.6 12 0.9 o.s OA 0.1 Con t ac t M-663-00017 A, Revision W04 Pa e 87-51 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P32150085 Penetration Type: F B-1 Fire Area (Side 1): C-6 Fire Area (Side 2): C-1 Loc./Eiev.: 1984'-0" M-OXDwg: M-1X3211 1. Barrier Thickness: 8" 10. Annular Gap (smallest)
1" 2. Opening Size: 12"D 11. Gap between pen: N/A 3. Penetrants
(1) 8"P 12. Barrier Type: F 4. Sealant Type: Ceramic F i ber 13. Opening Sleeved o r Concrete: Steel 5. Damming Side1: Boot 14. P i pe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth:

  • Assumed Pe r Deta i l Reviewed By: Walkdown Comments: Slab thickness based on draw i ng C-1 C3211.
  • 12" min Cer a mic Fiber required by Deta il. P i pes are not insulated loc a lly at boot and p i pe interface. Sketch: FA! C.(! Side 1 Pl21S0085 F
  • C*1 Sde2 M-663-00017 A, Revision W04 Pa e 87-52 of 87-89 Penetration Seal Data Appendix: 87 Photos: P321S0085 Fire Area C-6 (Side 1) Fire Area C-6 (Side 1) Fire Area C-1 (S ide 2) Fire Area C-1 (Side 2)

M-663-00017 A. Revtston W04 Penetration Seal Data Heat Affected Zone Rev i ew: P321S0085 F i re Ar ea (S ide 1) C-6 No issues within Heat Affected Zone F i re A re a (Side 2) C-1 No Issues within Heat Affected Zone Side 1 Ph ot o S i de 2 P h o to No photo requ i red. No photo required. I! Sketch Page 87-53 of 87-89 Append i x: 87 Rev i ew D i stances (ReWenc:a f'9R 7 2.3-1) 8"Pipe L1 & L2 Temp. R1 Radius R2 Radius D i st. (ftl (:E)_ (i'!l (in) 0.5 1677 4.4 I 5.8 1 1463 3.4 4.8 -1.5 1217 : 2.6 3.9 2 1116 1.9 3.2 2.5 976 1.2 2.6 3 855 i 0.7 2 3.5 750 0.2 1.6 4 659 Contact 12 4.5 58 1 0.8 5 512 0.5 5.5 453 02 6 402 0 -6.5 3 5 8 Contact No sketch

  • M-663-00017 A , Revision W04 Pa e 87-54 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P321S0086 Penetration Type: F B-1 Fire Area (Side 1 ): C-6 Fire Area (Side 2): C-1 Loc./Elev.: 1984'-0" M-OX Dwg: M-1X3211 1. Barr ier Thickness: 8" 10. Annular Gap (smallest)

1-1/2" 2. Open ing Size: 12"D 11. Gap between pen: N/A 3. Penetrants
(1) 8"P 12. Barrier Type: F 4. Sea lant Type: Ceramic F i ber 13. Open ing Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: B oot Wayne Aregood 7. Damming Con t inuity (Acc/Rej):

N I A Prepared By: 8. Boot Conditio n (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth:

  • Assumed Per Detail Reviewed By: Walkdown Comments: S l ab thickness based on drawing C-1C3211.
  • 1 2" m i n Ceram ic F iber required by Detail. Pipes are not insu l ated loca lly at boot and p i pe interface.

Sketch: FA: C-6 Sde 1 P321S0086 M-663-000 17 A , Revision W04 Pa e 87-55 of 87-89 Penetration Seal Data Appendix: 87 Photos: P321S0086 Fire Area C-6 (Side 1) Fire Area C-6 (S ide 1) F ire Area C-1 (S i de 2) Fire A rea C-1 (S ide 2)

M-663-00017 A, Rev1s1on W04 Penetration Seal Data Heat Affected Zone Review: P321S0086 F ire Ar e a (Si de 1) C-6 No issues within Heat Affected Zone Fire Area (S ide 2) c-1 No I ssues within Heat Affected Zone S ide 1 Pho to Side2 Photo No photo required. No photo required. Sketch Page 87-56 ofB7-89 Appendix: B7 Re vi ew D i sta n ces (Ral-t.U$3.00011A.F"9R 7.2.3-1) 8" Pipe L 1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) (°F) (in) (in) 0.5 1 1677 4.4 5.8 1 3A 4B 1463 1.5 1277 2.6 3.9 2 111 6 1.9 3.2 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 L S 4 659 Conlact 1.2 4.5 58 1 0.8 5 512 ' 0.5 5.5 453 I 02 6 402 0 6.5 3 5 8 Con lac! No sketch required.

M-663-00017 A , Revision W04 Pa e 87-57 of 87-89 Penetration Seal Data Appendix: B7 Penetration

  1. P32150123 Penetrat i on Type: FB-1 Fire Area (Side 1): C-6 Fire Area (S ide 2): C-1 Loc./Eiev.: 1984'-0" M-OX Dwg: M-1 X32 11 1. Barrier Thickness: 8" 10. Annular Gap (smallest)
1-1/2" 2. Open ing Size: 12" D 11. Gap between pen: N/A 3. Penetrants:

(1) 8"P 12. Barrier Type: F 4. Sea lant Type: Ceram ic F iber 13. Opening Sleeved or Concrete: Stee l 5. Damm in g Side1: Boot 14. Pipe In s ulat ed: No 6. Damming Side 2: Boot Wayne Are good 7. Damming Continu i ty (Ac e/Rei): N/A Prepared By: 8. Boot Condit ion (Ace/Rei): Ac cep t Jeff Suter 9. Sealant Depth: Ass umed Pe r Detai l Reviewed By: Walkdown Comments:

S l ab thickness based on draw i ng C-1 C3211. Sketch: FA: C*6 Sidtl1 P321S0123 z* FA: C-1 Side 2 M-663-00017 A , Revision W04 Pa e 87-58 of 87-89 Penetration Seal Data Ap p end i x: 87 Photos: P32150123 Fire Area C-6 (Side 1) Fire Area C-6 (Si de 1 ) Fire Area C-1 (S ide 2) Fire Area C-1 (S id e 2)

M 663 00017A R --evJsJon W04 p age 87 59 f 87 89 Penetration Seal Data Appendix: 87 Heat Affected Zone Review: P32150123 Fi r e Area (Side 1) C-6 Review Distances (fWereoceM-(;63-000H No issues within Heat Affected Zone an Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) linJ (in) 0.5 1677 4.4 5.8 -1 1463 3.4 4.8 Fi r e Area (Side 2) C-1 1.5 12n 2.6 No i ssues within Heat Affected Zone 2 1116 1.9 3.2 1 2.5 976 1.2 2.6 3 855 0.7 2 3.5 750 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 0.5 Side 1 Photo Side 2 Photo 5.5 453 0.2 6 402 0 6.5 358 Con tact No photo required. No photo required. Sketch No sketch required.

M-663-00017 A , Revision W04 Pa e 87-60 of 87-89 Penetration Seal Data Appendix:

B7 Penetration

  1. P611W0082 Penetration Type: FB-1 Fire Area (Side 1): F-1 Fire Area (Side 2): F-2 Loc./Eiev.: 2012'-10 M*OX Dwg: M-1X6906 1. Barr i er Thickness: 24" 10. Annular Gap (smallest): 1-1/2" 2. Opening Size: 12"D 11. Gapbetweenpen
N/A 3. Penetrants
(1) a**p 12. Barrier Type: F 4. Sealant Type: Ceram i c Fiber 13. Opening Sleeved or Concrete: Stee l 5. Damming Side1: Boot 14. P i pe Ins ul ated: No 6. Damm i ng Side 2: Boot Wayne Aregood 7. Damming Cont i nu i ty (Acc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej):

Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments: Wall thickness determined by Drawing C-1C6111 Sketch: FA; F*1 S i de1 e,ooT C*rm P611W0082

.--b' *. . /' SANb (r'lP) FA: F-2 S i de2 M-663-00017 A , Revis i on W04 Pa e 87-61 of 87-89 Penetration Seal Data Append i x: 87 Photos: P611W0082 Fire Area F-1 (Side 1) F ire Area F-1 (S i de 1) Fire Area F-2 (S ide 2) F ire Area F-2 (Side 2)

M-663-00017 A, Revision W04 Penetration Seal Data Heat Affected Zone Review: P611W0082 Fi r e Area (Side 1) F-1 1. 1* Pipe, lnspectorTestfor FP: No issues within Heat Affected Zone. Fi r e Area (Side 2) F-2 2. 5U6015, 3/4* Cond. for thermos ta t.: No issue Side 1 Photo Side2 Photo No photo required. Sketch Pa e 87-62 of 87-89 Appendix: B7 Review Distances (Rafe.oance TA. f9he 1.2.3-1) B" Pipe L1 & L2 Temp. R1 Radius R2 Radius O i st. (ft) (*F) (in) (i n) 0.5 1677 A.4 1 5.8 1 1463 1 3.4 4.8 1.5 1277 1 2.6 3.9 2 111 6 1 1.9 3.2 2.5 976 ! 1.2 2.6 3 855 I o.1 2 3.5 750 1 0.2 1.6 4 659 Contact 1.2 4.5 581 0.8 5 512 0.5 5.5 45 3 0.2 6 402 0 6.5 358 Contact M-663-00017 A. Revision W04 Pa e 87-63 of 87-89 Penetration Seal Data Appendix:

B7 Penetration#:

P611W0197 Penetration Type: FB-1 Fire Area (Side 1 ): F-2 F i re Area (S ide 2): F-3 Loc./Eiev.: 2019'-0" M-OX Dwg: M-1X6906 1. Barrier Thickness: 12" 2. Opening Size: 16"0 3. Penetran ts: (1) 12" P 4. Sealant Type: Ceramic F i ber 5. Damm in g Side1: Boot 6. Damming S ide 2: Boot 7. Damming Cont i nu i ty (A cc/Rej): N/A 8. Boot Condition (Acc/Rej): Accept 9. Sealant Depth: Assumed Per Detail Walkdown Comments:

Wall thickness determined by Draw i ng C-1 C6111. Sketch: FA: F*2 S i de 1 P611W0197

10. Annular Gap (smallest)
1-1/4" 11. Gap between pen: N/A 12. Bar rier Type: F 13. Opening Sleeved or Concrete: 14. Pipe Insu l ated: No Wayne Aregood Prepared By: Jeff Suter Reviewed By: . ' /) r> p ll' /J'. ,p. tr .. . ' .b .. FA: F-3 S l de2 Steel M-663-00017 A , Revision W04 Pa e 87-64 of 87-89 Penetration Seal Data Appendix: 87 Photos: P611W0197 Fire Area F-2 (Side 1) Fire Area F-2 (S i de 1) Fire Area F-3 (Side 2) F i re Area F-3 (Side 2)

M-663-00017A Revision W04 Penetration Seal Data Heat Affected Zone Review: P611W0197 Fire Area (Side 1) F-2 1. 5U5W1G, 1-112" Cond.: Additional Review is required. Further review determined that this conduit is not PFSSD. Set-route control is necessary. Fire Area (Side 2) F-3 No issues within Heal Affected Zone Side 1 Photo No photo required. Sketch FA: llde1 Side2 Photo Pa e 87-65 of 87-89 Appendix: 87 Review Distances (Rehlrwrlc:e Fq.ft 7.2.3-1 1 L1 & L2 Dlst (ft) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 12" Pipe Temp. R1 Radius (" F) (in) . 1712 4.6 152 4 3.7 1357 3 1209 2.3 1078 1.7 962 1.2 86 0 0.7 769 0.3 689 Contact 618 555 499 450 406 368 FA: f.J lkteZ R2 Radius (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1.7 1.3 1 0.7 0.4 0.2 0 Contact M-663-00017 A, Revision W04 Pa e 87-66 of 87-89 Penetration Seal Data Appendix: B7 Penetration#:

P621 50153 Penetration Type: FB-1 Fire Area (Side 1): F-5 Fire Area (S ide 2): F-3 loc./Eiev.

202 6'-0" M-OX Dwg: M-O X6211 1. Barrier Thickness:

1 0" 10. Annul ar Gap (smallest):

1" 2. Opening Size: 1 4" 0 11. Gap between pen: N/A 3. Penetrants

(1)10"P 12. Barrier Type: F w 4. Sealant Type: Ceram i c F iber 13. Open ing Sleeved or Concrete:

S teel 5. Damm ing Side1: B oot 14. Pipe Insulated:

No 6. Damming S ide 2: B oo t Wayne Aregood 7. Damming Continu it y (A cc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Sut e r 9. Sealant Depth: Ass u me d P er D etail Reviewed By: Walkdown Comments:

Sketch: FA; F..S Skkl 1 SE£.. rloll A PS21S0153 FA: F.J Slde2 M-663-00017 A, Revision W04 Pa e 87-67 of 87-89 Penetration Seal Data Appendix:

87 Photos: P62150153 Fire Area F-5 (Side 1) Fire Area F-5 (S i de 1) Fire Area F-3 (S ide 2) F ire Area F-3 (S ide 2)

M-663-00017A Revision W04 Page 87-68 of 87-89 Penetration Seal Data Appendix:

67 Heat Affected Zone Review: P62150153 Fire Area (Side 1) F-5 Review D i stances ., (Refefence 7.2.3-1 ) No issues within Heat Affected Zone 10" Pipe l1&L2 Temp. R1 Radius R2 Radius Dist. (ft) (" F) (In) (i n) ' 0.5 1 1697 4.5 5.8 I Fire Area (Side 2) 1 1 497 3.6 4 , 9 F-3 1.5 1321 2.8 4.1

  • No Issues within Heat Affected Zone 2 1167 2.1 1 3.5 2.5 1032 1.5 1 2.8 3 914 1 1 2.3 3.5 810 0.5 1.8 4 719 0.1 1.4 4.5 639 Contact 1.1 5 569 0.8 Side 1 Photo Side2 Photo 5.5 508 0.5 6 454 0.2 6.5 406 0 7 365 Contact No photo required.

No photo required. S k etch No sketch required.

M-663-00017 A, Revision W04 Pa e 87-69 of 87-89 Penetration Seal Data Appendix: B7 Penetration

  1. P621S0156 Penetration Type: FB-1 Fire Area (Side 1): F-4 Fire Area (S ide 2): F-3 Loc./Eiev.: 2026'-0" M-OX Dwg: M-OX6211 1. Barrier Thickness: 1 0" 10. Annular Gap (smallest): 1" 2. Opening Size: 16"D 11. Gap between pen: N/A 3. Penetrants:

(1) 12"P 12. Barrier Type: F w 4. Sealant Type: Ceramic F i ber 13. Opening Sleeved or Concrete:

Steel 5. Damming Side 1: Bo ot 14. Pipe Insulated: No 6. Damming Side 2: Boo t Wayne Arego od 7. Damming Cont i nuity (A cc/Rej): N/A Prepared By: 8. Boot Condition (Acc/Rej): Accept Jeff Suter 9. Sealant Depth: Assumed Per Detail Reviewed By: Walkdown Comments: Sketch: FA: F-4 Slde1 ,---I I St::CIIOl-l A P621S0156 ll 10" It" _j FA: F.J Slde2 M-663-00017 A , Revis i on W04 Pa e 87-70 of 87-89 Penetration Seal Data Appendix:

87 Photos: P621S0156 Fire Area F-4 (Side 1) Fire A rea F-4 (S ide 1) Fire Area F-3 (Side 2) Fire Area F-3 (S i de 2)

M 663 00017A R --8VISJOn W04 p age 87 71 f87 89 Penetration Seal Data Appendix: 87 Heat Affected Zone P621S0156 Fire Area (Side 1) F-4 Review Distances j

Mo663-00017 A, F'9ft 7.2.3-1 I No I ssues w ithin H eat Affected Zone 12" Pipe l1&L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1712 4.6 5.9 1 1524 3.7 5.1 F i r e Area (Side 2) F-3 1.5 1357 3 4.3 No I ssues w i th in Heat Affected ZQne 2 1209 2.3 3.6 2.5 107 8 1.7 3.1 3 9 62 1.2 2.5 3.5 8 60 0.7 2.1 4 769 0.3 1.7 4.5 689 Conta ct 1.3 5 618 1 Side 1 Photo Side2Photo 5.5 555 0.7 6 499 0.4 6.5 450 0.2 I 7 4 06 0 7.5 368 Con t ac t No photo required. No photo required. Sketc h No sketch

  • ed . requ1 M-663-00017 A , Revision W04 Penetration Seal Data Penetration
  1. Penetrat i on Type: Loc./Eiev.: 2026'-0" 1. Barrier Thickness: 2. Opening S ize: 3. Penetrants
4. Sealant Type: 5. Damming S ide1: P62150157 FB-1 1 0" 16" 0 (1)12"P Ceram ic F i ber Boot 6. Damming S ide 2: Boo t 7. Damm ing Cont inuity (Acc/Rej):

N I A 8. Boot Condition (Acc/Rej):

Accept Pa e 87-72 of 87-89 Appendix:

B7 Fire Area (Side 1): F-4 Fire Area (Side 2): F-2 M-OX Dwg: M-OX62 11 10. Annular Gap (sma ll est): 1/4" 11. Gap between pen: N/A 12. BarrierType

F w 13. Opening Sleeved or Concrete:

Steel 14. Pipe Insu late d: No Wayne Aregood Prepared By: Jeff Suter 9. Sealant Depth: Assumed Per Deta i l Reviewed By: Walkdown Comments:

S l ab thicknes s ( 12") determ in ed by C-1 C62 11. Ske tch: FA: F_. Side 1 . , . : . ,o* l't

  • E

._*. or.-H. '

_j 2. FA: F-3 Side 2 M-663-00017A , Revis i on W04 Pa e 87-73 of 87-89 Penetration Seal Data Ap p e n dix: B7 Photos: P621S0157 Fire Area F-4 (S id e 1) Fire Area F-4 (Side 1) Fire A rea F-2 (Side 2) Fire Area F-2 (S id e 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected Zone Review: P62150157 Fi r e Area (Side 1) F-4 No issues within Heat Affected Zone Fi r e Area (Side 2) F-2 1. 1/2" unscheduled Cond.: Not within Heat Affected Zone. Side 1 Photo No photo required.

Sketch FA: F .. , Side2Photo Pa e 87-74 of 87-89 Appendix:

87 'Review Distances (Refenlnc:e Ma3-00017A.

F'!llft 7 2.3-1 ) 12'" Pipe L1 & L2 Temp. R1 Radius R2 Radius Dist. (ft) ("F) (in) (in) 0.5 1712 4.6 5,9 1 1524 3.7 5.1 1.5 1357 3 4.3 2 1209 2.3 3.6 2.5 1078 1.7 3.1 3 962 1.2 2.5 3.5 860 0.7 2.1 4 769 0.3 1.7 4.5 689 Contact 1.3 5 618 1 5.5 555 0.7 6 499 0.4 6.5 450 0.2 7 406 l o 7.5 368 Contact M-663-00017 A, Revision W04 Pa e 87-75 of 87-89 Penetration Seal Data Appendix:

87 Penetration#:

P621S0162 Penetration Type: FB-1 Fire Area (Side 1): F-4 Fire Area (Side 2): F-2 Loc./Eiev.: 2026'-0" M-OX Dwg: M-OX62 11 1. Barrier Thickness: 10" 10. Annular Gap (smallest):

1-1/4" 2. Opening Size: 16" 0 11. Gap between pen: N/A 3. Penetrants:

(1) 1 2"P 12. Barrier Type: F w 4. Sealant Type: Ceramic Fiber 13. Opening Sleeved or Concrete: Steel 5. Damming Side1: Boot 14. Pipe Insulated:

No 6. Damming Side 2: Boot Wayne Aregood 7. Damming Continuity (Acc/Rej):

N/A Prepared By: 8. Boot Condition (Acc/Rej): Accept Je f f Suter 9. Sealant Depth: Assum ed Per Detail Reviewed By: Walkdown Comments:

Sketch: FA:. F-<1 Slcte 1 Stc.T'Iot-1 A P621S0162 FA: F*2 Slde2 M-663-00017 A, Revision W04 Pa e 87-76 of 87-89 Penetration Seal Data Appe n dix: 87 Photos: P62150162 F i re Area F-4 (S i de 1) F i re Area F-4 (Side 1 ) Fire Area F-2 (Side 2) Fire Area F-2 (Side 2)

M-663-00017 A Revision W04 Penetration Seal Data Heat Affected .Zone Review: P621S0162

  • Fi re A r ea (Si d e 1) F-4 No issu es within Heat Affected Zone Fire Ar e a {S i d e 2) F-2 1. 4U6030, 2" Cond.: Not within Heat Affected Zone S i de 1 P hot o Side 2 Photo No photo requ ired. No photo requ ired. Sketch FA: P:-4 81de 1
  • I l
  • Pa e 87-77 of B7 -89 Appendix: 87 Review D istances IU6J.<l0017A.!"ogLft7.2.J.1) 12" Pipe l1 & l2 Temp. R1 Radius R2 Radius Dist. (ft) (" F) (in) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 1712 4.6 152 4 3.7 1357 3 1209 2.3 1 1078 1.7 : 962 1.2 \860 0.7 \769 I o.3 \689 Con ta ct \618 555 ' 499 4 50 406 368
  • I . l FA: F.a SlcN2 (in) 5.9 5.1 4.3 3.6 3.1 2.5 2.1 1J 1 .. 3 1 0.7 0.4 0.2 0 Contact * ...

M-663-000 17 A , Revision W04 Pa e 87-78 of 87-89 Penetration Seal Data Appendix:

87 Penetration

  1. P621W0009 Penetration Type: FB-1 Fire Area (Side 1 ): F-4 Fire Area (S i de 2): F-5 Loc./Eiev.: 2041 '-6" M-OX Dwg: M-OX6908 1. Barrier Thickness:
2. Opening Size: 3. Penetrants
4. Sealant Type: 5. Damming Side1: 12" 16"0 (1) 12" P Ceram i c F i ber Boot 6. Damming Side 2: Boot 7. Damming Cont i nuity (Acc/Rej): N/A 8. Boot Condition (Acc/Rej); Accept 9. Sealan t Depth: Ass umed Per Deta i l Walkdown Comments:

Wall thickness (12") determ i ned by C-1C6211. Sketc h: FA: F .... S l da 1 P621W0009 10. Annular Gap (smallest):

3/4" 11. Gap between pen: N/A 12. Barrier Type: F 13. Ope ning Sleeved or Concrete:

14. Pipe Insulated:

No Wayne Aregood Prepared By: Jeff Suter Reviewed By: ' :. ;; b , 0 I> .. FA: F-5 Sdo2 Steel M-663-00017 A, Revision W04 Pa e 87-79 o f 87-89 Penetration Seal Data Append i x: 87 Photos: P621W0009 Fire Area F-4 (S i de 1) F ir e Area F-4 (Side 1) F i re Area F-5 (S i de 2) F i re Area F-5 (S ide 2)