.. 0 DEC L919N MEMORANDUM FOR:.E. Adensam, Chief, Licensing Branch No. 4 Division of Licensing FROM:
F. Rosa, Chief Instrumentation & Control Systems Branch Division of Systems Integration
SUBJECT:
ICSB REQUEST FOR ADDITIONAL INFORMATION - V0GTLE UNITS 1 & 2 Plant Name:
Vogtle Units 1 & 2 Docket Nos.:
50-424/425 Licensing Status:
OL Responsible Branch: LB #4 Project Manager:
M. Miller Review Branch:
'ICSB Review Status:
. Incomplete In an effort to complete the review associated with Open Item 65 in the draft SER for the subject plant, ICSB has enclosed a request for additional information which should be transmitted to the applicant for a formal, written response.
/
F ust osa, Chief Instrumentation & Control Systems Branch Division of Systems Integration
Enclosure:
Distribution:
As stated Docket File ICSB Rdg.
cc:
R. Bernero
-F. Burrows (PF)(2)
R. W. Houston T. Dunning M. Miller F. Rosa Vogtle Subject File
Contact:
F. Burrows, ICSB X29455 C :IC5B/DSI
- IC 5
- If5B/D5I
___ Q...__:__. ________:.___________:.___________: _________.
(ME :
t :TDunning
- FRosa LTE 12//9 /84
- 12/ 1 4 /84 :12/ / /84 y
w g 0FFICI'AL RECORD COPY
(&yvJovg'
?
\\
k,.
()
INSTRUMENTATION AND CONTROL SYSTEMS BRANCH REQUEST FOR ADDITIONAL INFORMATION V0GTLE UNITS 1 & 2 In FSAR Question 420.2 the staff requested a response to IE Bulletin 79-27 concerns. Since the response, contained in FSAR Amendment 8, was not reviewed in detail by the staff prior to issuance of the draft SER, Open Item 65 was written covering the issue.
ICSB, with support from PSB, has now reviewed the resp.onse and requests lthat.the following information be provided for the staff to complete its review:
o IE Bulletin 79-27 and IE Circular 79-02 requires a determination if time delay circuits are used with inverters.
If so, a detennination is to be made if they are adjusted appropriately.
For inverters used for Vogtle, this would more than likely be low /high voltage cutoff on input and maybe output depending on the specific design. This should be addressed.