ML20083E552
| ML20083E552 | |
| Person / Time | |
|---|---|
| Site: | Fort Calhoun |
| Issue date: | 12/19/1983 |
| From: | William Jones OMAHA PUBLIC POWER DISTRICT |
| To: | John Miller Office of Nuclear Reactor Regulation |
| References | |
| LIC-83-305, NUDOCS 8312290273 | |
| Download: ML20083E552 (28) | |
Text
1
~
n a n.
-9 w
e g
Omaha Public Power District 1623 Harney Omaha, Nebraska 62102 402/536 4000 December 19, 1983 L IC-83-305 Mr. James R. Miller, Chief U.S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Licensing Operating Reactors Branch No. 3 Washington, D.C.
20555
Reference:
Docket No. 50-285
Dear Mr. Miller:
Adequacy of Station Electrical Distribution System Voltages at the Fort Calhoun Station Unit No.1 The Commission's letter to the Omaha Public Power District dated October 20, 1983, formalized the latest request for additional information on the sub-ject issue. The following responses are labeled by the number of the re-quest.
1.
The attached two tables ( Attachments 1 and 2) together with the fol-lowing discussion provide the District's response to the first request for additional infonnation.
The two tables contain analyzed voltage values which have been revised using more realistic loading rather than the more conservative loading which has been used in earlier analyses. These loading figures are based on a load survey which was conducted this past year (see Attach-ment 3) and also on the manufacturer's specifications of pump loading requirements under various operating conditions (see Attachment 4).
Specifically, the condensate and feedwater pumps which when operating m
in the recirculating mode, as they would be during accident conei-tions, require 70% and 63% of their motor horsepower, respectively.
So Also, there is an automatic 480V load shed initiated by the accideet no signal which was not taken into consideration by previous District
- o analyses. Thus, the maxinum post accident loading on either of the O
safeguards buses would be 9.82 MW on the 1A4 side, (tte 1A3 side han gg only 1/3 of the condensate system, thus it will always be more lignaly om loaded than the 1A4 side which feeds the other 2/3, therefore, volt -
7 ages were not analyzed for the 1A3 side).
The 9.82 MW includes bus y
1A2 and all loads which could be, but would not likely be, running, me.c.
i.e., worst case.
The minimum and maximum grid voltage values are detennined by the Sys-tem Operations Deoartment 9perating Guide 11-78 (Attachment 5). This
/ p) cmpioymeghfauagopponumty f
4sse4
=
Mr. James R. Miller December 19, 1983 Page Two i
requires that operators maintain the 161 kV level at the Fort Calhoun substation between 163 kV (101%) and 169 kV (105%) and the 345 kV at a minimum 351 kV with the unit out of service. As discussed in the Dis-trict's original design (see Attachment #6 of the August 28, 1978, sub-4 mittal) the gener.stor actually regulates the voltage on the 22 kV bus when it is operating in a preset range regardless of what level the offsite grid is at. To illustrate this point, a recent check with the unit at full load showed the 345 kV at 103% and bus 1A1 at 99% of 4160 v.
Because the unit does regulate the 22 kV bus, calculations were i
not done for the case where an automatic fast transfer had occurred switching buses 1A3 and 1A4 from the preferred 161 kV to the 345 kV with the unit remaining at 100% load. However, the hot shutdown oper-i ating mode would be the loading condition relevant to lower voltage on
-the 345 kV grid. This loading on the 1A4 side would be 7.14 MW, in-cluding one each: feedwater pump, condensate pump, and heater drain i
pump. Operation with buses IA3 and 1A4 on the 345/22 kV system with the unit at power is done only on very rare occasions, however, the District will take steps, via operating procedure, to assure that the bus voltage does not exceed 4400 volts (110% of 4000 volt rated i
motors). This will be satisfactory; the plant does have direct con-trol of the 22 kV bus voltage via the generator exciter control.
Also, in order to substantiate these maintained values, the actual 161 kV and 345 kV levels have been recorded beginning September 30, 1983, to the present at approximately 8-hour intervals. The lowest recorded i
{
voltages have been 164.3 kV and 347.0 kV (102.0% and 100.6%, respect-ively) and the highest voltages were 170.9 kV and 358.8 kV (106.2% and 104%, respectively), while the average values were approximately 168 kV and 352 kV. These minimum and maximum grid values are well within the safe operating range for the Class 1E motors at the Fort Calhoun Station which is guaranteed by motor manufacturers to be 90 to 110% of I-nameplate voltage. As shown in Attachment 1, the minimum analyzed grid voltage of 101.1% of 161 kV provides 96.6% of nameplate voltage (460V) at the motor teminals (worst case). This 101.1% of 161 kV is the analyzed minimum expected grid voltage (ref.: the District submit-i l
tal of August 30, 1983), while the minimum allowable ac per Operating l
Guide 11-78 is actually slightly higher at 163 kV or 101.2% (see
' ).
Calculations were not done for the steady-state maximum case simply be-cause it was obvious that the maximum expected 161 kV grid level would have to be in the range of 113 to 114% to cause a 110% motor tenninal voltage, and the maximum voltage analyzed on the grid is only 105.1%,
while the maximum recorded is only 106.2%. The maximum analyzed is lower than the maximum recorded for the same reason that the minimum analyzed is lower than the minimum recorded; because the voltage drop i
parameters used in the calculations are worst case and thus more con-servative than the real world operating conditions. This consistency points out the validity of the model used for calculating the grid voltages, i.e., the analyzed values are consistently in the range of 1% lower at both extremes, both minimum and maximum.
The minimum transient voltage values, as per the subject telephone con-ferences of September 26, 29 and October 6,1983, were to be calcu-
_, - - ~ -.
.,_v~-__.,.__
. _ _. _ ~,.. _. _ -. _ ~.. _ _ _ _. _ _. _ _....... _
Mr. James R. Miller December 19, 1983 Page Three lated based on the inadvertent starting of a large non-Class 1E load during. accident conditions to detennine if it would actuate the acci-dent undervoltage (0.P.L.S.) relays, thereby automatically transfer-ring the Class 1E buses to diesel-generator supply. The analysis determined that the starting of either a reactor coolant pump or a feedwater pump (both highly improbable occurrences during an accident) would cause a transient both low enough (83% voltage) and long enough (15 sec. in the case of the reactor coolant pump) to actuate the 0.P.L.S. relays. The 0.P.L.S. relay trip setpoint on bus 1A4 is 89.97% voltage for 5 seconds. At the end of the 15 second motor start transient (RC-3D) the bus voltage would recover to 93.4% and the 0.P.L.S. relays would reset at 90.9%, according to the manufacturer's specifications, allowing the transfer back to the 161 kV grid.
2.
In the District's submittal of August 31, 1981, the results of some transient starting tests were compared to the corresponding analyti-cally derived values. The District believes that this comparison showed the validity of the analytical model that has been used consis-tently since the original undervoltage study submitted on August 28, 1978. The important parameter to compare is the consistency of the difference between the calculated values and the tested values, and as discussed in the August 31, 1981, submittal this difference was consis-tent. The magnitude of this difference is a function of the selection of the input parameters and thus is not as important. For example, the conservative bus loading values used in the calculations of the August 28, 1978, submittal and all other earlier submittals, accounted for a comparative difference as large as 3.8%, however, the consisten-cy of this difference varied by only 0.3%, down to 3.5%.
Therefore, the actual voltage drop model is accurate and the District does not believe that any further testing is necessary.
3.
The taps on transformers TIA-3 and T1A-4 are on 161 kV and this is what has been used in the analysis.
4.
See Question #1, and Attachments #1 and #2.
In closing, the following list of District submittals to the Commission is provided so that the Commission may verify that they are all available for reference in the Commission's file on the adequacy of Fort Calhoun Station distribution system voltages.
It has been brought to the District's atten-tion in correspndence over the last 3 or 4 Commission requests for addition-al information, that due to personnel changes the Commission may not have reviewed past infonnation which has been provided by the District.
If any
.of these submittals are not in the Commission's files, the Commission is requested to notify the District so that copies may be sent.
1.
September 17, 1976, to George E. Lear, ONRR 2.
August 28, 1978, to Robert W. Reid, ONRR via H. H. Voigt of LeBoef, Lanh, Leiby and MacRae 3.
May 13, 1981, to Robert A. Clark, ONRR 4.
March 19, 1982, to Robert A. Clark, ONRR
i I
Mr. James R. Miller December 19, 1983 Page Four 5.
May 21, 1982, to Robert A. Clark, ONRR 6.
Decenber 1, 1982, to Robert A. Clark, ONRR 7.
April 22,1983, to R. A. Clark, ONRR 8.
August 30, 1983, to R. A. Clark, ONRR Sincerely, r'
W. C. Jon,es 4
Divisio'n} Manager Product' ion Operations
'JCJ/0JM/rh-A g
Attachments cc:
LeBoeuf, Lamb, Leiby & MacRae 1333 New Hampshire Avenue, N.W.
Washington, D.C.
20036 4
Mr. E. G. Tourigny, NRC Project Manager Mr. L. A. Yandell, Senior NRC Resident Inspector J
5 4
9 Worst Case Analyzed Voltages With the Plant Distribution System Supplied by the 161 kV Grid Plant Conditions: Normal Operation Plant Conditions:
Post Accident Operation, All Class 1E Loads Operating With Unit at 1005 Load Steady-State Steady-State Transient Minimum Steady-State Minimum After Maximum Minimum Due to Large Motor Start Large Motor Start Transient Offsite 101.1 See Note See Note Grid 105.1
(% of 161 kV) 93.4 96.2 83
(% of 4160v)
See Note (9.25 MW Load on Bus)
(Start RC-3D with (90.9% is required for reset Bus IA4 7.82 MW Load on Bus) of undervoltage relays) 96.0 93.3 Terminals of (AC-108)
See Note Class IE Load See Note
(% of 4160v) 90.4 Bus 184A
(% of 480v)
See Note 93.1 See Note 93.8 Terminals of Class IE Load See Note 96.6 See Note (AC-3B)
(% of 460v name-plate voltage l
rating)
See the discussion of the applicable question for explanation of why these calculations were not perfomed NOTE:
Worst Case Analyzed Voltages With the Plant Distribution System Supplied by the 345 kV Grid Plant Conditions:
Normal Operation Plant Conditions:
Post Accident Operation, With Unit at 100% toad All Class 1E Loads Operating Steady-State Steady-State Transient Minimum Steady-State Minimua After Maximum Minimum Due to Large Motor Start Large Motor Start Transient (Observed)
(Observed) l Offsite Grid 104 100.6 See Note See Note (3 of 345 kV)
Bus IA4 85.9
(% of 4160v)
See Note See Note (Start RC-30 with 92.8 7.14 MW Load on Bus)
Terminals of Class 1E Load See Hote See Note See Hote 92.7
(% of 4160v)
Bus 184A
(% of 480v)
See Note See Note See Note 91.4 Tenninals of Class 1E Load See Note See Note See Note 94.8 (S of 460v name-plate voltage rating i
NOTE:
See the discussion of the applicable question for explanation of why these calculations were not performed.
I
Load Survey Assume TIA1 Feeding Bus 1A1 T1A2 Feeding Bus 1A2 TIA3 Feeding Bus 1A3 TIA4 Feeding Bus 1A4 Alignment 1 is considered worst case loading on the 161 KV systen. T1A2 is shown at its lightest loading.
Alignment 2 is the Itghtest loading on the 161 KV system.
Alignments 1 and 2 are given assuming all equipment is running necessary for 100% power operation of the generator.
Actual data taken with the unit at 100% load on February 4,1982, at 0830.
Bus 1A1 7.5 MW RC-3 A, FW-2A, FW-14A, CW-1 A Bus 1A2 6.5 MW RC-38, FW-48, FW-58, CW-1B Bus 1A3 3.3 MW RC-3C, Misc. Loads Bus 1A4 6.2 MW RC-3D, FW-2C, FW-5C, CW-1C Alignment 1 Bus Ma,ior Loads 1Al RC-3A - 2 MW FW-2A - 1.62 MW FW-4A - 2.84 MW FW-5A
.49 MW CW-1A - 1 MW 1A2 RC 2MW FW-2B - 0 FW-4B - 0 FW-5B - 0 CW-1B - 1 MW 1A3 RC-3C - 2 MW Mi sc. - 1.3 MW 1A4 RC-3D - 2 MW FW-2C - 1.62 MW FW-4C - 2.84 MW FW-5C
.49 MW CW-1C - 1 MW Mi sc. - 1.3 MW
.o
-..... - - = - -
Alignment 2 Bus Ma.ior Loads 1A1 RC-3A - 2 MW FW-2A - 1.62 MW FW-4A - 2.84 MW FW-SA
.49 MW CW-1A - 1 MW 1A2 RC-3B - 2MW FW-2B - 1,62 MW FW-4B - 2.84 MW FW-5B
.49 MW CW-1B - 1 MW 1A3 RC-3C - 2 MW Mi sc. - 1.3 MW 1A4 RC 2 MW FW-2C - 0 1
FW-4C - 0 FW-SC - 0 CW-1C - 1 MW Mi sc. - 1.3 MW i
_ _ ~ _,.. _. _. _, _ _
A -rt ae.h me.n t +
(
Desian Parameters Items number CW-1A, CW-1B, CW-1C Number 3
Type Foster Wheeler 84" MFV-2 K6.6 Design capacity, each 120,000 gpm Total dynamic head 33 feet Operating temperature 85'F Pump Efficiency 86.57,as shown in Figure 2.1.2 Materials of construction Casing Cast Iron Impeller Ni-Al Bronze Shaft Carbon steel Hy-Ten B-3X Annealed Steel Pump Speed 295 rpm Drive Electric Motor 4160 V 3 P ase 60 cycle h
Design hp 1175
= o.88
^'1 W Flow requirements Condensing water 315,000 gpm (design flow @ 60*F)
Bearing cooling, (2) 17,900 condensate cooling Screen wash 3,000 Surface diversion 24,100 360,000 L
4
r' III-3-13
.+
2.0 SYSTEM COMPONENTS (Continued) 2.3 Condensate Pumos (W-2A. W-23. and W-2C) 2.3.1 General Description The condensate pumps are vertically mounted 10-stage motor driven turbine pumps.
They consist of two sections, each of which contains five stages. The sections are coupled together to form one unit.
Condensate is supplied to the pump through a suctior strainer.
The condensate flows down the casing to the bottom where the pump first stage takes a suction and discharges to the next stage bolted on top of it.
Eac.2 stage discharges to the next stage, increasing the pressure of the condensate as it progresses. The pump casing.
is equipped with a continuous vent connection that r e ren any noncondensable gases and vents them to the conde The pump shaft is sealed by a rotating mechanical se which is filled and flushed prior to startup and the cooled and lubricated by water from the discharge of
..r.
pump through valve PCV-1214 when the pump is running.
'.a i.a pump is capable of supplying 50 percent of the required condensate flow for 100 percent teactor power.
)
2.3.2 Desien Parameters g
w
(
Item Numbers W-2A, 23, 2C Number 3
Type Vertical, Turbine Shaft Seals Mechanical Power Supply W-2A Bus IAl W-23 Bus IA2 W-2C
. Bus 1A4 Design capacity, each 5600 gpo Total Dynamic Head 1150 Ft.
Operating Temperature 92*F.
Operating Flow at 100 percent load 4600 gpm d88 BED MAY 5 1981 t
^'
11I-3-14 2.0 SYSTEM COMPONENTS (Continued) 2.3.2 Design Parameters (Continued)
(
Materials of Construction Outer Casing Welded Steel Impellers S.S., 11.5-13 percent Chrome, 0.5 percent moly Shaft S.S., 11.5-13 percent Chrome, heat treated
' Pump NPSH Required at Design Flow 0 ft. @ base Pump Speed 1190 rpm Drive 2000 hp Electric Motor 4160V, 3 Phase, 60 Cycle Pump Horsepower at Design Conditions 2000 hp 2.3.3 Instrumentation and Control The condensate pumps are controlled from two locations, k
one is the main control room on C3-10 and the other is locally at the pumps.
Local control consists of push-bucton start and stop switches.
They are mounted on the west wall near the pumps. Remote control is ac-complished,in the main control room on Panel CB-10.
Three swittnes control the condensate pumps.
Also located on C3-10 are green stop/ red run lights and an ammeter for esch condeosate pug.
To start a condensate pump, the breaker must be racked in and the "69" permissive switch on the breaker cabinet must be in reset. The Auto /Off-Auto switch in the control room must be in Off-Auto.
khen these conditions are met the pump is elect.tically ready to be started.
After a condensate pump is running, the operational control of the pumps can be placed in an automatic standby mode.
The Auto /0ff-Auto switch is coc: mon to all three condensate pumps as well as all feed pumps, heatsr drain pumps and the motor driven auxiliary feed pump.
klen in Auto, this switch, along with the position of the individual conden-sate pump contn l switches on CB-10, set up an automatic control circuit for the standby condensate pump. The 1
Il s
(
4a R2 5-5-81 maiW MAY5 1981 i
\\
~
4 4
'I
- I
- i.
IfjN dcf*k.]. Gh. 5M
.!}f ih*;4 *iff!'... if;i 3:
n.._1'
_ b:.
_..:. a.a.
- .;... 4.
4... 6 R +4
-4aC
- W':P 1i
.! !if S T
' R?.
R: GUS4. La
.F k
. lb g
l!
i
..~.F._.,f;.s*.
7 y I y;;. : 'l'
- k
- r" '.'
. b.
.... TW
..... bt.. C. ib...
..t
+:
- 4..,
1-c. _....... '...~.-
".. 'I,
--. 7 -
~
' li:
K 3W MIF
- + + + ~..
/if i
[
Q t{
,jh. T."ij:p~ -[ , p r
jfsw..r n : L _...
i
......i-..
'.i'
. ~,..L....:
.. c...
.7..
...h:.:.:A. ~.
o
- y
.]
3, N,0 i
0 l.'f k. i.,
p...
.l 7
..,.=.
[
.f-1
.l l-I.,i.__.h;g. : 1.
- M i ~;
'f.ii f '
f ! a..
' ! E' !![ g (g) .}' ). h[/. ' ' i - l- ..l '-. ~ t-. J j. . jul.a.l!%. il! i. f'.... 4... j. )%gr i:: ,..g-..-~.. j.. .. Q l' {Ruo . ' *,, f,, p.,
- l
- [
- t: j'
~l'
- Q
--i" - - j,! Q
- d... If"... ---
.'. r - - - [' h i"-- 2 d.... r- ~ ii-- U:9 m *g..O #~" C ' 3 rl..; 2@.+' n 3 M' .1 uj...o... :. ,'- ;....l...
- u. :
- l:
- l.:'
- l. r a..
T . c.. .t. L a.. -*:
- n..
~
- i a
i .t.
- t..
g
- 11 :.
- ::h-t 5
r:
- J. +.:: '!y
... *. e 7. ,........ 1 %.4 + e J.. - [. ["
- 5..bi i
. ifh
- ". :--l: - '.
4 :..
- .; p ; i c{
- i;': _..?':
- ;)'j:.u...jMhh4.. i..C
- : i g.in{. 4{H{i._. au.!.{
!p.....k - Q1. L{'
- i.
ilii{iif! M !ili t A I. n:
- f..'
. { -,I I. ' l '. t.:. i. ' ' . '. ' '-- -- g p d l '.... :..g. 3 .r. t. -.i.... ::: r u. : I".- -... I:
- n:z;.n.ti:t..mn,a a.
~ [..i d.. d.. fr..:;'T* N... ".i.. ...-....t: l i .l + .... f ::*:l..
- ... '", h..
r.. 4. :.... ! -
- ~*
.{:.. m%g3.i.h-p} % - .m. ' r- ~ ~~ty* ~ '*-".:.t!-***
- "X:.:1,%;. ~
- t. -
- n.. :.: :. :
ehi:.. :
- r. # ~ r *:
o, c'
- .... nn
- }:...-
m d... *g.. =, n
- d.... {.:.....
...m.. .v I.
- M..."*
"":Q:: f::; f: k.. M4,N. p.g .... g" :f 6n;,.n:!.g.:,h..p:'.. ...In.... g:..ptr:a ; .... :._. *t:'
- 1
..w
- gn. w-
..n : c. .. *:u m g u ng
- ,. g g;n n{
- .,
s
- f!:ni::
b %. ;41fg:: '::...n 11
- l::..::::-*::$ @:
n:ji;r':{:., M'** 3 :. - 1.,. h :. : 4'hT:C
- . tim.;; m g. :. ~.
r" f':., . [" ::....j: t M "N: y T:" JQ*.]:V:i G. c ".. :] @:: - M. ; ~ :.-Q: :*l O '* *g : qaig; j g [ - tJ:.t : :. F
- m. i. :..- u.....
- 3. g.. A l f......
.7..... : n9.t :.... a. : 9.p:.tr. 2: *: r.$. _._r.
- (,
.. :. ttt Z ..z ., y m. .: r.. t.. 2 ":a. r,,. 2.nih_r.].g n. . u ,... l. : 1... . t. :. .MiAU 9.h.i..LM..~ : ~ M.. fih. i!.I.'.l.i.,!! :'id},N,q. l.i.g C,
- *:. p.... j'.1. :.
.. ::l3. i. ii .g
- -*n
- .M n* *
- -y g ;;;.
"L* "f1".}'ti!-
- l.
- : : ~!!: ". :n.. : f;**r.: y !
b"""II;*g; ;;,,,g:.t.y.gg !!'.(t : C ,Mr ::*J 1:=
- E : t*j:! -{: -.
6 o... -g {
- M
- L,
,t W::
- "{*"
Pr.U '!**" lw .... :l.. !T r i t* :" t %;: l. :::!... i.: :... *. ::;;::ni;;'
- O M :.:::;n..:[f:
{ :.. :...::
- ".;
- }; :u ;2{ ty.; ::.ipt ii: ':
- i
- n
- h
'[ (/) ...
- f, M.
7:
- r :r:r:
- ug~::*
- t.
T, . :!:... - W .. ;b.i.. f"' f "$*l ,p .._1.. .. T rm ~ p p-r-t-"- . m.I,st- . N.. j- .f.
- r. q:. :t:
- 1.
~l + r= 9 :...1" .... ] [r-- .t. c-m. 29
- i. -
. i. :. ' " ~ ~ - g. ' r. i.
- {.::. J:
.e . u.. L.. p.,.. : * : .t. N;t.: i:: V. i:: t _;;u.; p v -.7,._.. ....i4 4,;;;,.. t - - :::
- uzup
q..-
- .uu.
y
- f
- a:
k
- ~;
, ; :,, - f' - ! 9:, 1 d. fys.; i
- -.m-
.,j m :n-p - p W. J,--... o
- g., g{.
s j .g
- --g u em 1.:...-;...i a:
Ct " -. - - p :.
- -- -q:
,..r-....r..:...........-.- F(- M i s@t,M F w...m.--- 7- ...T s i wim t y-m s m t .q" l u.nc uk'....u. l ...nu.. 7... _'...'..' kc4" Mg_; .._._ p.,,._'!_ 4 a _ _,, q ;((_;{ Q',._ g t. { t! ,I I '*a. .S I 'O b - - :--]---- -
- . S.
'l.'. I 25 ' - [' .1: ..?
- l.. ;
.._ J n; j._,;,. m -- 7, .! 1[ . Cr-". t ..' _.y...7 ';n e. q.c,
- c 1
.I {, b d 7 I '.Q. I
- l. n
.. w% - n l .r~ . Lg .,l } 9 5 .A; ~~ ^ i. i -
- k_ L j
...._...:j y;'
- .-U
.1 .I. } s(. -
- Q,,.
g f .{. J! A e l. , x]: {, <j - u, ! x(- ,O{e t a, G +J --.... 7..-.._u .., _ f__._ m r g .t t /. L. j -.f ^ w;E i 2 N r4'S N.A 1 4 - ~ I s i s.4 t [ ' \\,, y " * ~ . ~... ....______._;.L.,,______,__j e-m a ql3f g i -4 y
- Q (3
n p F1
- A 1
7 "b.n ~ 3 c1 'k. 3 q" ~ yJ ..i 4 3 L ... w.. n... }, m i j L,.4.N! N H 17 i C f. I.p. * 'h L i ~.._._ _. _ n.., ,w ~ J
III-3-32 2.0 SYSTEM COMPONENTS (Continued) 2.10 Steam Generator Feed Pumus - W-4A. W-4B. and W-4C L h . ^- 2.10.1 General Description The steam generator feed pumps are horizontally mounted two-stage motor driven centrifugal pumps. The pumps function to supply feedwater to the Steam Generators. Each feed pump has a separate oil system that lubricates the one thrust and three journal bearings. The oil system consists of a sump, auxiliary motor driven gear pump, a gear pump connected to the feed pump shaft, cooler and interconnecting piping. During normal opera-tion the gear pump connected to the feed pump shaft supplies oil to the system. The motor driven auxiliary gear pump is intended for use during startup and shut-down of the feed pump. In the event of trouble with the shaf t driven gear pump the auxiliary gear pump can and will supply the feed pump with oil until it is stopped. Each feed pump has two rotating mechanical seals, one on each shaft end as it penetrates the pump casing. The seals are initially filled with water from the condensate system. They are then kept full and lubri-cated 'Jy pump leakage to the seals and the pumping groves on the rotating face circulating seal water through the ( seal water cooler. Each feed pump is provided with a suction relief valve to protect its suction piping from overpressurization in the event of back flow through the pump when it is stopped. Each pump is designed to supply 50 percent of the required feed flow for 100 peret:nt reactor power. 2.10.2 Desien Parameters Motors 3 Allis-Chalmers 4160 Volts - 3 phase - 60 hert: Size 3500 H.P. Speed 3570 RPM Power Supply W-4A Bus 1A1 W-4B Bus 1A2 W-4C Bus IA4 5C 3i 9 / hlI k R2 5-5-31 MAY 5 1981
III-3-33 2.0 SYSTF.M COMPONENTS (Continued) { 2.10.2 Design Parameters (Continued) Pumns 3 Byron Jackson Type Centrifugal, horizontal Shaft Seals Mechanical Total Dynamic Head 1740 ft. (full flow) Design Temperature 396*F. Operating Pressure 1090 psig Operating Temperature 396*F. Recire. Flow Rate per Pump 750 gpm <= Co,-r e s eand s +o a 18 c o H.P l encJ Pump Discharge Pressure f.p, o m puma at Recirculation 1560 psig \\ c w-ve. J Design Flow (each pump) 8000 gpm N.P.S.H. @ 100%. Load 133 ft. N.P.S.H. @ Design Flow 143 ft. Flow Dats @ 100% Load Feedwater Flow 15,200 gpm Nominal Operating Press. 1055 psig Final Feedwater Temperature 437.9*F. Blowdown Rate 2 percent 2.10.3 Instrumentation and Control The steam generator feed pumps are controlled from two locations, one is the main control room and the other is locally at the pump. Local control is performed on a control box for each pump mounted on the north wall directly adjacent to the pump. Each control panel consists of three sets of pushbuttons with associated lights. The pushbuttons control starting and stopping the feed pump and motor driven auxiliary oil pump and opening and closing the feed pump discharge valve. Remote control is performed via switches located on the desk section of C3-10. Three switches control the feed jQ g1 p pumps and three control the motor driven auxiliary oil 2f.S 5 Pumps. I i uf-Q *< r i J.2 5-5-31 MAY 5 1981
i i . LN33lH3 d-ADN313fd.-El i i i. .8.2 .R.E S 1 8 8 2 . ;y i n s d H 3 )lVd8 =-- 4 .g: ,,4 .... s 5... .....g..,. hM i $ (z, g t l . LL.. I l ) h I.
- o j
- m
.._....M R I } i i..i. .,i.... N Y M 3 ) Q ..p p ~ ~ 2q .i. i I 2 l Z_%.. t I -t I O . l m. s i. i ' ~ ? >- j $ C y) 's .';..".((......
- k. !N
,.A .. t...... :[....:.. !j[ j x v. rg .t....:. g .i
- k.. :: :....
- 2 '
4 ~1 M.\\ .b..!..'.. '...I
- ......li Sik.f..!.
I i ii l ..k YI [ .. i..k .i. l...{.. s. c .e O i g - .g... ...o....-..... s.. V i. !si aR W-ri 4 ,i.... .. 2 :
- g 0 tt-5 n
? 3 3 -- t-- N e i m. .g. .s g.. [. l .....k.. ..h....: N M,. t *'~~ gl j 4.t l l. i ,t. 2 1 g I Q l .jf j
- %~1 fi--t f,
3 i M l-[.; p. i i s . s. g i. l o ...,....g....... i _3 't. - -4 y .m .g g v t Oc g.g...........,-......._.._x .._,_..._...L.__..... 1 t,3 h. . C; $1 E e _p' N, ,s. ' d.N f N M N. .c g ..N s 1 i i pf l \\ l,. n.. \\ * ,1 I s i e ./ nn.< tv. :in w u n G - x. L I.. _9 L
AttaeI,nac.nt 5 SYSTD1 OPERATIONS DEPARTIEIT c OPERATING GUIDE 11-78
Subject:
Operatine Voltace at Substation 1251/3h51 (Fort Calhoun)
Reference:
D. D. Wittke -(P. K. Mazumder) letter GSE-FCI-78-390 of October 20, 1978, to System Operations Letter Text:
Subject:
Operating Voltage at Substation 1251 and 3h51 As requested by you, following are the liraiting operating voltages at Substation 1251 and 3h51: Substation 1251 Minimum allowable voltage: 163 KV Maximum allowable voltage: 169 Kv Substation 3h51 111nimum allowable voltage with the unit out: 351 Kv This is for your information and necessary action. If you need any further clarification, contact P. K. Mazumder (h590). Action for System Onerator: Maintain voltages within above limits. f i R. E. Taylor Supervicor - System Operations RET /jmm 10/30/78 I 1
f *' O D OP A16-1 Port Callioun Station Unit lio.1 Operating Procedure flo. 10 Ananunciator A-16 I f Panel CB-20 4 < s .lAN 18 Jg79 l l .= rruns TIA-L Trans TIA-1 14160 Volt l [ Secondary l Yrunu TIA-jl:160V llun Hus Trans Oil Level la Gil Iow Voltagt / Ground to 22KV lilocked 3 Teinp y A-1 MM A-1 A-h A-5 _ f. _6 Trans TIA-1 Unit to 1:160 V Bus h160V Bus h160V Bua o tii ndi rig llouse 1 A1 Iov 1 Al-1 A3 125 1 Al-1 A3 125 3-V DC Trans-V DC Trans-Teing 111 Trans fer Voltage Pural 1 el rer Switch rer Su. Orr flormal Emerg. O Supply Orr 3 141 B-2 11-3 B-b B-S trormal it.6 4 180V Bus Trans TIA-Trtuis TI A-i likr. lAll Bhr. l A13 h80V Bus 4 1113A/1B3A-p l'res sure Gas Press. Auto Trip Auto TrlP 1B3A/.1B3A-1(elay Oper Itel l t. r hA/1B3D/ f$f3c_ h3k,fUh,.Trans Sv. hC 125 VDC C-1 C-? c-1 c-h h$0N1 0 3 hFErMB 6 Tranu's lik r. lAll Bkr. 1 A13 TIA-1 & lockout lockout TlA-2 Itelay flelay We ul,e 'J 't v ope rute:d Oierated 0, -o ru i.. :.1 86/lAlI 8Is/l Al'i D-3 Dh D4 D -6 n. D m
1%rl Calhoun.s,at ion Unit flo.1 OP 10...o-2 Operatind l*rocedure flo. 10._ 30 Annuncialor A-16 Y, Panel Cli-po O JAN 1 a 1979 Tecu.sp$c. Tely Get Point Ui nilr.u Alarm Device (lleset) Corrective Action tiercrence A-1 Trans former TI Al Contact opera-Level low Mark Auto: Alarm 27 of1 Level 1.ow tion of gauge on gauge Follow-up-Check for oil con t, acts Temp. 90 C. leak and excessive Oil leak or cooler / fun R-2 Trnauformer T1 A-1 Secondary 27-lX 3115 volts Auto: Alarm 27 Low VolLuge 1Al-13 Follow-up-Check generator and or 3h5 KV voltage for 27-2x 3115 volts malfunction. 1r unable 1Al-13 to clear alarm, transrer or bus power to 161 KV rysten 2'(-Th h003 volts ir voltage below 3115V. TIA1 A-1 Tranurormer TlA-l Contact opera-Trans former Auto: Alarm 141f.oV Duu Grountleil Lion on ground faul t, or 1160V Follow-up-Locate grounded 2*7 4 rault, relay equipment component wit,h rault 6hX/1Al-D ruulL. locator and de -enet gize ir plant conditions allow Cont,act electrical mai nt.cnance. A. I. 16h,o VolL hua Trans Cont. net from 22KV uyatem flotify: 906 2.7 To. ;'t;V lilocheil cynch-check out or synch Electrical Maint,. relay 25-1/G1 wiLh IblKV or Check: Relays /Plud3 or umler-frey. gen. Treal. flot i ry: Sys t.cm pro t.ec t.J on relay 81/G1 ';911z. for check prior t.o resetti Ig any flugs/reluys. Do not. v g.. J_!crformJia_y_ hut. bun _tra nu_l
( O OP-10-A 1 Fort Calhoun Station Unit flo 1 Operating Procedure No. 10 g { [ Annunciator A-17 p l l Punel CB-20 (( ,5 ..g,y. Trans TIA-3 f!'rans T1 A-3 )}arans TlA-3 4160 Volt 1160V Bus Fire Sprink-Aux. Bldg. h80V Bus h80V Trans 4 Oil level Secondary 0 V Bus Bus Trans 1Al-1A3 ler Diesel Deluge Ib3A, IB3B Secondary lu 011 Terni Iow Voltage ' 1round to 161KV Trans fer RM-1 Valve open & IB3C Ekrs. Trip / lli Blocked Off Auto Actuated Ground Off Ilorng41 ,,,_,, A-1 x _ x A-2, ' M-3 A Is. A-S A-6 A-7 A-9 Trans TIA-3 4160 Bus lA (h160VBusL Diesel Bkr. h80V Bus 480V bus ) lADI 183A, IB3B( Tie lira. FeedersEkr[. 1A3 Win.fing Trans Iow Voltagt Trip & IB3C Iow Trip /Orr Te n.p. Ili f Voltage ' ilornal Auto Trip B-1 B-2 y B-3 ) Bli B-S B-6 B-... B-8 ) Ib9 I; 7; -- Trans Tl A .3 Trans TI A-3 Bkr. Y Ekr.1A33 OPLS Jock - Diesel ~ I /1U30-l f f B-lab II1 B 1 l'rcuu u re das Auto Trip Auto Trip out helay D1 Over-i i Hulay Oper l'ress Relle Test Switch load lli C 12 V I B C 12 V DC Transfer DC Transfer Open Ch. A Sw. Off Sw. Duerd. flormal Supply Off C-1 C-2 C-3 C-4 C-S C-6 C-7 C-8 g., rn,:.1 C-9. Tra nu 's Trans TI A-3 bkr. JA31 Ekr. 1A33 Bus JA3 Diesel Di is80V Bus Trans. T1.4-3 & I.oekout Inckout lockout Inckout Lockout IB3A-hA TIB-3A/3B/ TIA-h lielay Oper Helay Oper Relay Oper 8telay Oper Relay Oper IB3B-hD 3C Winiting sie l uce vi v. 36/TIA3 86/1A31 86/lA33 86/lA3-TPB 86/D1 1D3C-h C Tennp ll1 Ope raL ed Iow Volta e D-l D-2 D-1 D-h D-Sl D-6 D-7 D-D-9__ s 1.'( 1-2 ' 1.
.....s Operating Procedure 110. 10 g,,' ; i t.-.. op_ g o_g1 f_3 Annuneintor A-l 'f_ ,8 [,* P Cil-20 Panel - - - e4 3 Trip det Point Tei*h. : !'re. 'f t odou AIntm-Device fHeaeL) Co rrec t. i vit Action He fgi_ nce A-1 Transformer TI A-3 Cont.act opera-Ievel - low Auto: Alarm 2.7 011 I,evel inw
- t. ion or gauge mark on gauge Follow-up-Check for oilleals Oil I.evel 111 contact.s Temp - 90 C and excessive current.
C l A-2 Transformer Tl A-3 Secondary low 27-1X 3115y Aut.o : Alarm 2.7 Voltage 1A3-13 Follow-up-Check that alarm and is valid. Transfer power j 27-2X 311Sy supply from TI A3 If cause ~ l 1A3-13 is due to low voltage. or Cont.uct Elect.. Maint.. 27-73 Is003V l TlA3 l JW 1 I A-3 'frunuformer TIA-3 Contact opera-Trans former into-Alarm hidOV llos Cround tion on ground faul t o r 1160 Follow-up-Incate grounded 27 6 fault relay equipment, component with faul t lo-61s X/l A3-13 ra ul t.. cator and de-energize ir plant conditions allow. Contact electrical main-tenance. i A-h h160 Voit lius Trans Contact from 161KV out of Hotify: 906 j To 16thV filocked synch-check synch with Electrical Maint. relay 25-2/G1 02 22KV or gen. Check; Helays/FJugs under-freq. fregg459 liz. Ilot,i fy Sys tem l'ro tec t. ion l relay 81/G1 6 for check prior to reset.Liig l nny flags /reluyu. Ib not., perfvrm_any.ltot laus. transfers 8 when this alarm la in. R( 3a i V w/ m.
f Fcrt Calhoun St Oon Unit No. 1 ^ Operating Proce' dure flo. 10 i op-lo-Alt-S Annunciator A-17 Panel CH-20 L uJ l' li ~ i o.ro. Tech. Spec. Trip Set Point Utndow Alarm Device (Heset) Corrective Action Reference l p a 1 u-1 Transforner TIA-3 Contact opera-120 C Auto: Alarm Winding Temp 111 tion on winding Follow-up-Heduce load on temp. gauge transformer by transferrirq auxiliaries. Determine cause of hi temp. B-2 1:160 bus IA3 contact opera-CB-20 control Auto: Alarm 2.7 Trips 180V Transformer Feeder breakers tion of CB-20 switch in'the 4 Auto Tri. ped control switch after close-transformer second-l and breaker position and ary breaker and associatet position. the breaker island bus tie. open for the Follow-up-Close bus tie following breakers to feed the island and 180V bus from breakers: 4 TIB-3A, T1B-3B, Bus IAl4 after insuring TIB-30, or the trip was not a fault TIB-3D. on the bus. Cai ty out follow-up of D f f f H-3 le160V Bus IA3 low Voltage 27-1X 90% Auto: Alarm 2.7 \\ 1A3 Follow-up-Verify if alarm if valid. Transfer power 27-2X supply if power supply 1Ali has malfunctioned. Conta-t ~ 'Q ~ Elect. Maint. x \\ f M t-12-fl1 l
Port Calh(nin Station linit. I!o. 3 . g ( g' j., ; i ' * - OperaL.ing Proccabare flo. 10 ] Annnuelutor A-17 Op-l o-A I T-(. Pane 1 C8-20 k '. '. i Trip Set. Point I-,' Tech. Spac. tlinden A1:trm Device (Peset) t;orrective Act.lon lie ference l l 15-6 Diesel lireaker Contact opera-Breaker Buer-Aitto : Alarm 27 l 1ADI Tripped tion in breaker gency Cont.rol
- If lockout relay 1AD1 Switch in the 86/D1 operat.es, D2 i
" Trip" posi-will start.. ' Ioad I tion, control shed of Bus lA3 If I switch on no other power CB-20 in the supply on bus. " Trip" posi-Follow-up-Invest.igate tion, lock-reason for trip and trans-relay 86/D1 rer emergency loads to provided Bus 1Als insuring D-2 ir breaker pro-operating does not exceed tection over-overload rating. 4 I ride is not i: l! e rrect., or ir diesel D1 l, V shutdown. A' it-H h80V Bus Ill3A,11338 and Ill3C 27-lX 90% Auto: Alarm \\l !aw VolLage 1B3A Verify ir valid alarm; if and so, check for t.ransformer i i 27-2X malfunct. ion and inform i El" L#I "I M"I"'*"""'"' IB3A 3 or 27-1X / IB3B alld I 27-2X i 1B3B or 27-lX 1B3C littd 27-2X i l 1li3C ..o._. Q P Ir/,3 - 1 9 1
(~ D D OP-10-A18-1 Fort Calhoun Station Unit No. 1 Operating Procedure Ilo. 10 O {a Annunciator A-18 4 hO b , Panel CB-20 APR 2 1983 StlGR Roorn l'80V Bus Fire Sprink31160V Trans TlA 14 Trans T1A-b hfransTIA!: 4 I 1BsA, 1B!B ler Diesel Bus lA2-1Al. 1160V Bus Secondary 11 Level 4 ilVAC Al-187 4 Irouble and.lB1C Hm-2 Actuat Transfer Ground Low Voltage Io 011 Temp 4 Ground ed Off Auto 11 i A-1 _ e x A-2 A-3 A le A-5 A-6 n _A-7 A-{ A,,9 'Is80VBub Diesel Ekr. OV Bus (1160VBus h160V Trans TIA-h 480V Bus 1160V Bus 4 4 ^ IB3A-hA Bus- '1 bha, IBhB 1AD2 1 A2-1 AI. Bus 1Ali I A!6 Trans Winding V a & 1BlC Iov Trip 125V DC rep su ane Iow Voltage Feeder Bkrt Temp lli Tie Bkr. 4 Off Normal , Voltage Transfer St Suppl Off' g Auto Trip Off Normal Norma B-1I B-2 B-3 B-b B-5 B-6 B _7 ) B-8 B-9 480V Bus Diesel D2 OPLS Lock Bk r. 1 Ahh BkDAD Trans T1 A l TransTik-h i I B3B-hb Bus Overload out Relay Auto Trip Auto Trip Gas Press. Pres s ur'e Tie Breaker Test Switel Relier Relay Oper Off flormal Open Chan-C-1 C-2 C-3 C-h C-5 C-6 C-7 C-8 C-9 4 180V Bus Trans. Diesel D2 Bus 1Ah Bkr. 1Ahh Ekr. 1Als2 Trans TIA l. 6 lb3C 1.C TIB-hA/hB/ Lockout re-Lockout re-Lockout re-Lockout re-Lockout re-Bus Tie he Winding lay Oper lay Oper lay Oper lay Oper lay Oper breaker Off Temp 111 86/D2 86/lA!-TFB 86/1Ah!4 86/1 Ale 2 86/TIAh 4 flarmal p_) D-2 D-3 D la D-5 D-f, D-7 D-8 I}-S_. R4 4-2-83
Fort (':tJ lsous I. ions lini t N.). L Oper:st i ng, Pr.sceilisre llo. A-18 R
- OP-10-A18-3 Annnut Intor P:un!!
_._C B-20
- l
( Trip Set PoJnt Teels. Spee. Wi nslow Alarm Device (iter:et ) Cottective Action lie ference A-7 Trans former Tl A-h Contact opera-Transformer Auto: Alarm kl60V Bus Ground tion on ground fault or 1160V Follow-up-Locate grounded 4 fault relay equipment component with' fault lo-61sX/lAls-24 fault. cator and de-energized if plant conditions allow. Contact electrical main-A-8 Transformer T1A-b Secondary Low 27-1X 3115V Auto: Alarm 27 i Voltage 1A1-24 Follow-up: Check that 4 l and alarm is valid. Transfer i)- 27-2X 3115V power supply if cause is 1Als-24 due to low voltage from or the power supply. q 27-74 3980V TlAh A-9 Trans fo rmer Tl A 14 Contact opera-Level - Low Auto: Alarm Oil Level Lo tion of gauge mark on gauge Follow-up-Check for oil Oil Temp. !!i contacts. Temp - 90 C. leak and excessive Cause - oil current leaks.
T ForL Cullusun 1.i.alion IJni L flo. 1 Operating Procedure IJo. In OP-10-A18 le Annunciator A-18 I *'t 3g [j, Punel CB-20 yx s ~ 3,.I @ Trip Uet, Point Tee ls. : l *ee. Wi enlow Alarm Device (it er,et ) Correct!ce i.etion lie ference 180V Bus 1B3A IsA Contact opera-Bus tie Auto: Alarm 27 B-1 4 Bus Tie Breaker tion of breaker breaker Follow-up-Return bus Off Normal BT-1 bha BT-lbl A 1B3A 1A to normal line 4 4
- closed, up as soon as possible to insure a separation
[ ~ of safeguard loads. e 180V B.is 1B4 A,1Bl B, & IBl:C 27-1X 90 2.7 l B-2 4 4 Low Voltage 1 bha Follow-up: Verify if a and valid alarm. If so, check transformers for ( 27-2X 1Bl A ""I'""U 4 Electrical Maintenance. ,'w-or 27-1X 1Bhb l \\\\ and 27-2X 1BhB or 27-lX IBl C / 4 and 27-2X 13hC .---_./ p --R--------
I ]
- orL C: !hean Si/it. ion linil :10
.1 OP-10-A18-6 Opern Li rad i't occuner 11. J 0. Annunelater A-18 l' ui.r l. CB-20 t Trip liet Point Tech. U'ee. l 1/i ndc's Alarm Devire (Re M k D r'ecijve Action _ Heference N" Mr N V N N V ~ j ( B-7 4160 V Bus IAl4 Low Voltage 27-1X 90% Auto: Alarm 27 l 1A14 Follow-up: Verify if alarm valid. Transfer 27-2X power supply if power IAh supply has malfunctioned. / I l l l l e B-8 h]60V Bus lAh Contact opera-CB-20 Control Auto: Alarm
- 2. ~l l
Trans former Feeder Breakers tion of CB-20 switch in the
- Trips h80V trans-Aut > Trip control switch after close former secondary and breaker position and breaker and assoc-l position.
the breaker lated island bus j open for the tie. l following Follow-up-Close bus tie i breakers: breakers to feed the 5 i TlB-hA, island and 480V bus from l TIB-hB, Bus lA3, after insuring i j TIB-hC, and the trip was not a fault i I tlc-hA. on the bus. I l 1' i i i I l i i I i i l .e h i .--p--.-.-....----...----..---.--....-...-... .m
) V OP-10-Ai9-1 Fort Calhoun Station Unit lio. 1 Operating Procedure lio. 10 Annunciator A-19 3 gg{ Panel CB-20 s 8 8 3 I I j s A-A Trans T1A-2 Trans TIA-2) Trans 'I'1 A-2 i 1:160V Bus 5 Secondary '011 Level Ground / LowVoltagI Lo 011 Temp ( 111 A-1 A-2 A-3 A-b ( A A _ -5 DC llus #2 hl60V Bus Trans T1A-2 I Gropnd 1A2 Iow Winding Voltage Temp 111 I B-1 B-2 R-3 B 14 B-5 B-6 i Bkr. 1A24 Ekr. lA22 Trans T1A-2 Trans TIA-2 Auto Trip Auto Trip Gas Presa. Pressure l flelier Relay Oper C-1 C-2 C-3 c-4 C-s C-6 Panel Bkr. lA24 Bkr. lA22 Low Voltagt Weattwr' i AI-blB Lockout Iockout AC Iluses Tower Transfer Relay Oper relay oper IA and 2A Trouble i Sv. E=ai g 86/1A214 86/1A22 UC UI8t* 8 l Supply Ort g Pnlo.1 G ,'h6 ~ D-1 Normal D-2 D-3 116 12-3-81
() O O Fort Calhoun St.ation IJnit 11o.1 OP-10-A19-2 OpernLing l'roccature llo. 10-Annuneintor A-19 j Panel en_9n DEC 3 1981 Trip Set: Point Tech. C.ec. I l Ui nelow Alarm Device (Reset) Corrective Action Re fere:nce l A14 Transformer TI A-21160V Bus Contact opera-Transformer Auto: Al' arm 4 Cruund tion on ground fault or Follow-up-Locate grounded j fault relay 14160V equip-component with fault lo-l 61X/lA2-214 ment fault. cator and de-energize if l 4 plant cotiditions allow. Contact electrical O y maintenatice. q LA-5 Transformer TlA-2. Secondary 27-lX 311SV Auto: Alam 27 [ Iow Voltage 1A 2-214 Follow-up-Verify alarm. i l \\ and Check gen. and 315 KV volt-4 27-2X 3115V age. Transfer bus power s 1A2-214 supply if bus is being fed or frcm affected power supply 27-71: 3980V j i l TIA2 ^ 1 t A-6 . Transformer TlA-2 Contact opera-Level - Iov Auto: Alarm 011 Level In
- t. ion of gauge mark on gauge Follow-up-Check for oil 011 Ten.p 111 contacts Temp - 90 C.
leak and exceanive current Ensure cooling fans are in operation. g 6-~1F'F s~l~ ~f ' -' ~ ~ ~ ~ ~ ~ ' h}}