ML20041B500

From kanterella
Jump to navigation Jump to search
Proposed Changes to Tech Specs Re Fire Protection Sys
ML20041B500
Person / Time
Site: Peach Bottom  
Issue date: 02/16/1982
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20041B495 List:
References
NUDOCS 8202240138
Download: ML20041B500 (16)


Text

PBAPS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14.A (Cont'd) c.

Turbine Building

c. Hose station valve
d. Circulating Water Pump operability and blockage Structure check - once every 3 years.

6.

,When a hose station serving

d. Hose hydrostatic test at an area which contains a pressure at least equipment which is required 50 psig greater than to be operable becomes the maximum pressure inoperable; establish a available at that hose continuous fire watch station but not less equipped with portable than 150 psig, or replace fire suppression equip-with an appropriately ment within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> tested hose. Testing and provide equivalent frequency shall be annually protection to the area for hose stored outside, and served by the inoperable every 3 years for interior station from the operable hoses.

hose station within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />

6. None 7.

Except as specified in

7. The SGTS fire suppression 3.14.A.8 below, the spray system testing fire suppression shall be performed as follows:

spray system serving a Standby Gas Treatment

a. Simulated automatic System charcoal filter actuation test - once train shall be operable every 18 months.

when a train is required to be operable.

8.

If the requirements of 3.14.A.7 b.

Inspection of nozzles cannot be met, and spray header-once every 18 months

a. establish a fire watch patrol to inspect the area with inoperable
c. Header and nozzle air fire suppression equipment flow test - once every at least once per shift.

3 years l

b.

restore the system to an l

operable status within 14 l

days, or in lieu of any I

other report required by Specification 6.9.2 submit a Special Report to the Commission pursuant to Speci fication 6.9.3 within f

31 days outlining the l

cause of the malfunction and.the plans for restoring the system to an operable

(

status.

The SGTS may be considered operable for the purposes of l

Specification 3.7.B.

8202240138 820218

- 240f -

PDR ADOCK 05000277 P

PDR

PBAPS LIMITING CONDITION FOR OPERATION SURVEILLANCC REQUIREMENTS 3.14.B CO2 Fire Protection 4.14.B.

CO2 Fire Protection Systems Systems

1. The HPCI room CO2 Fire Protection
1. The CO2 Fire Protection System shall be operable Systems testing shall be when the HPCI system is performed as follows:

regoired to be operable with the system comprised of:

a.

a minimum inventory of 2400

a. CO2 storage tank level and pounds of CO2 and a minimum pressure-checked once every pressure of 280 psig in the 7 days.

CO2 storage tank.

b. an operable flow path to the
b. Simulated actuation test of HPCI room and valves, dampers, fans - once every 18 months.

c.

three heat detectors, except

c. Header and nozzle air flow test -

that one detector may be once every 18 months.

inoperable for a period not to exceed 7 days, d.

Heat detector functional test at a frequency consistent with 2.

The CO2 Fire Protection System the schedule specified serving the Control Room, Cable in 4.14.C.1,2, and 3.

Spreading Room, and Computer Room shall be operable with the system comprised of:

a. a minimum inventory of 11,000 pounds of CO2 and a minimum pressure of 280 psig in the CO2 storage tank (s) and b.

an operable flow path to each room.

3. The Diesel Generator CO2 Fire Protection System shall be operable when the Diesel Generators are required to be operable with the system comprised of:
a. a minimum inventory of 2200 pounds of CO2 and a minimum pressure of 280 psig in the CO2 storage tank.

- 240g-

PBAPS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14.C Fire Detection 4.14.C Fire Detection

1. The fire detection instru-
1. a. The smoke detectors listed mentation for each plant listed in Table 3.14.C.1 shall be in Table 3.14.C.1 shall be functionally tested annually, operable when the equipment except as required by in that area is required 4.14.C.3, in accordance with to be operable.

the manufacturer's instructions.

2.

If the number of operable

b. The heat detectors listed fire detection instruments in Table 3.14 C.1 shall be are less than the minimum functionally tested annually, instrument operability re-except as required by quirement of Table 3.14.C.1:

4.14.C.3, with a heat source.

a. establish a fire watch
c. The NFPA Code 72D Class A patrol to inspect each supervised circuits between accessible area at the local panel and control intervals of at least:

room of each of the above required fare detection

1) Once per shift for instruments shall be areas with less than demonstrated OPERABLE at the minimum number of least once per year, operable instruments except as required by required by Table 4.14.C.3.

3.14.C.1 but with at least one instrument operable.

2. The testing interval for smoke and heat detectors which are
2) Once every hour for inaccessible due to high areas without an radiation or inerting may be operable instrument.

extended until such time as the detectors become accessible

b. restore accessible system for a minimum of 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />.

components to an operable Such detectors shall be status within 14 days, functionally tested at a or in lieu of any other maximum interval of once report required by per refueling cycle.

Specification 6.9.2, sub-mit a Special Report to 3.

If the same individual detector the Commission pursuant to is inoperable on two consecutive Specification 6.9.3 with-annual tests, as demonstrated I

in 31 days outlining the during a test required by I

cause of the malfunction 4.14.C.1, then the test shall and the plans for be repeated on a semi-annual restoring the instru-frequency for that detector ments to an operable until two consecutive semi-status. Reactor startup annual tests have demonstrated and/or continued reactor its operability.

operation is permissible.

l

- 240 i-

PBAPS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14.E. Water Suppression Systems 4.14.E. Water Suppression Systems

1. The M-G Set room and the
1. The M-G set room and the M-G set lube oil room water M-G set lube oil room water suppression systems shall be suppression system testing operable whenever the shall be performed as follows:

unit-is in reactor power cperation.

2.

If the requirements of

a. Simulated actuation of 3.14.E.1 cannot be met, the automatic valve (s) and system alarms every refueling cycle.

a.

Establish a continuous

b. Functional test of fire watch with portable system integrity alarm fire suppression equipment (Iow pipe air pressure) within one hour.

every refueling cycle.

b. Restore the system to an operable status within 14 days, or in lieu of any other report required by Speci fication 6.9. 2, submit a Special Report to the Commission pursuant to Specification 6.9.3 within 31 days outlining the cause of the malfunction and the plans for restoring the system to an operable status. Reactor startup and/or continued reactor operation is permissible.

1

-240k-i l

i I

PBAPS LIMITING CONDITION FOR OPERATION SURVEILLANCE REQUIREMENTS 3.14.F. Battery Room Ventilation 4.14.F Battery Room Ventilation Flow Detector Flow Detector

1. The battery room ventilation
1. The battery room ventilation exhaust air flow detector exhaust air flow detector shall shall be functional be functionally tested annually.

2.

If the requirement of 3.14.F.1 cannot be met,

a. verify the operability of the battery room ventilation exhaust system at least once per day.
b. restore the flow detector to an operable status within 14 days, or in lieu of any other report required by specification 6.9.2, submit a Special Report to the Commission pursuant to Speci fication 6.9. 3 withi n 31 days outlining the cause of the malfunction and the plans for restoring the instrument to an operable status. Reactor startup and continued reactor operation is permissible.

- 2401 -

Tablo 3.14.C.1 FIRE DETECTORS Detector Type /

Minimum Detectors Location Designation (1)

Operable Ut3IT 2 Primary Containment (2)(3)

S1, S 2, S8 3

CRD ' Areb (135')Rms. 208, 209 07A, S8A, S9A,S10A 13 212 311A,S12A,S13A,S14A S15A,S16A, S17A,S18A S19A, S20A Neut. Mon. Rm. ( 135 ' ) Rm. 210 S22A 1

Isol. Valve Compt.(135')Rm.204 S21A 1

Operating Area (165')Rm.402,403 S31A.S32A,S33A,S34A 12 S35A,S36A,S37A,S38A S39A,S40A,S41A,S42A S43A Laydown Area (195')Rm.501,502 S45A,S46A,S47A,S48A 7

508 S49A,S50A,S51A,S52A Vent. Equip. Area (195')Rm.506 S53A, S54A 2

Vent Stack Rad. Mon.-hefuel S58A, S59A 2

floor (234')

HPCI Room S78 1

H 5, H6, H7 (see 3.14.B.1.c)

RCIC Room S45, S46 2

Reactor Bldg. Sump Area S79 1

Core Spray Pump Rooms S41, S42, S43, S44 4

Vac. Breaker Area-Rm. 107,108 S91, S92, S93 3

RHR Rooms Room 101 S30,S31,S32 3

Room 102 S33,S34,S35 3

Room 103 S36,S37,S38 3

Room 104 S39,S40 2

Torus Area S83,S84,S85,S86 7

S87,S88,S89,S90

- 240m i

l

Detector Type /

Minimum Detectors Location De'signation (1)

Operable M-G Set Lube Oil Rm(Rm105)

S94,S95,S96,S97,S98 4

Recirc. Pump MG Set Room S15,S16,S17 5

S18,S19,S20 Emerg.Switchgear Rooms S11, S12, S13, S14 4

^

Batterf Rooms Room 218 S70,S71 2

S68,S69 2

Room 225 13KV Switchgear Area (116')

S72,S73,S74 3

HPSW Pump Room S390 1

UNIT 3 t

Primary Containment (2)(3)

S103,S104,S106 3

CRD Area (135 ' ) Rms 250 S166,S167,S168,S169 13 252, 257 S170,S171,S177,S173 S174,S175,S176,S177 S178,S179 Neut. Mon.Rm.(135')Rm 255 S180 1

Isol. Valve Compt.

S181 1

(135')Rm 249 Operating Area (165')

S182,S183,S184,S185 12 Rm. 443, 444 S186,S187,S188,S189 S190,S191,S192,S193 S194 Laydown Area (195')

S196,S197,S198,S199 7

Rm.517, 518, 523 S103A,S104A,S105A,S106A Vent. Equip Area (195')

S107A,S108A 2

Rm 520 Vent Stack Rad. Mon.-Refuel S109A, S110A 2

floor (234')

HPCI Room S148 1

H115, H116, H117 (See 3.14.B.I.c)

RCIC Room S131, S132 2

Reactor Bldg. Sump Area S149 1

l

- 240 n -

1

Detector Type /

Minimum Dctcetore De'139nntion (1)

Opereb30 Location S133, S134, S135, S136 4

Core Spray Pump Rooms 3

S158, S159,S160 Vac. Breaker Area-Rm 160, 161 RHR Rooms 2

S120, S?21 Room 1,56 S122, S123, S124 3

Rcom 157 S125, S126, S127 3

Room 158 S128, S129, S130 3

Room 159 SISO, S151, S152, S153 7

Torus Area S154, S155, S156, S157 4

M-G Set Lube Oil Room (Rm 162)

S161, S162, S163 S164, S165 Recirc. Pump MG Set Room Sill, S112, S113 5

S114,S116,S117 Emerg. Switchgear Rooms S107,S108, S109 4

S110 Battery Rooms 2

S147, S148 Room 266 2

S145, S146 Room 268 3

13KV Switchgear Area (116')

S75, S76, S77 1

S391 HPSW Pump Room COMMON S21, S22, S23, S24 4

Control Room Control Room Offices S137, S138, S139 6

S140, S141, S142 23 Cable Spreading Room S4, S 7, S9,S10 S47 through S67 (total: 25) 2 SS, S6 Computer Room Diesel Generator Rooms H550A,B thru H557A,B (See 3.14.B.3.c)

(4 in each room) 3 D-G Bldg.-Cardox Room S540, S541,SS42

- 240 o -

Datsctor Type /

Minimum Datectore Location Danignation (1)

Operable Standby Gas Treatment System 6 per filter train 5

Radwaste Bldg.

Room 31(91')

S80, S81, S82 3

Rooms 142,143,145 S99, S1A,S2A 7

147, 154(116')

S3A, S4A, SSA S6A Rooms 236,237,238 S23A,S24A, S25A 8

239,242(135')

S26A,S27A,S28A S29A,S30A Far Room (Rm 381)

S3, S44A 4

S105, S195 Emergency Cooling Tower H562, H563, H564 4

Switchgear rooms H565 Laboratory Area H1, H2, H3, H4 4

Recombiner Building H566, H567, H568 3

Startup Switchgear H558, H559 2

Building H560, H561 (1)S = Smoke Detector H= Heat Detector (2) Detector (s) inaccessible during normal operation due to inerting (3)May be disabled during ILRT

=

- 240 P -

PBAPS 3.14 BASES The Water and CO2 Fire Protection Systems, although not classified as safety related systems, provide fire suppression capabilities in those areas of the plant where protection of plant equipment is deemed necessary.

A.

Water Fire Protection System Two fire pumps supply water to sprinklers, manual hose s^ations, and hydrants in or surrounding the plant.

One electrically driven pump is powered from an emergency power bus; the other pump is diesel driven.

The capacity of each pump is in excess of the system design load.

In the event that both fire pumps become inoperable, immediate corrective measures are taken since this system is a major portion of the fire suppression capability of the plant.

The requirement for a twenty-four hour report to the Commission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued protection of the plant.

B.

CO2 Fire Protection Systems The CO2 Fire Protection Systems provide fire suppression capability for the Cable Spreading Room, Computer Room, Control Room, HPCI Rooms, and the Diesel Generator Rooms.

The specified minimum quantities of CO2 provide the capability to flood the Cable Spreading Room, Computer Room, a HPCI room, or a Diesel Generator Room with sufficient CO2 to meet concentration objectives.

In the event that portions of the CO2 Pire Protection System are inoperable, alternate backup fire fighting equipment is required to be made available in the affected areas until the affected fire suppression equipment can be returned to service.

C.

Fire Detection Operability of the fire detectors ensures that adequate warning is available for the prompt detection of fires.

This capability is required in order to detect and locate fires in their early stages.

Prompt detection of fires will reduce the potential for damage to plant equipment and is an integral element in the overall plant fire protection program.

- 240 q-

PBAPS In the event that a portion of the fire detection instrumentation is inoperable, the establishment of fire patrols in the eccessible affected areas is required to provide detection capability until the inoperable instrumentation is returned to service.

D.

Fire Barrier Penetrations The functional integrity of the fire barrier penetration seal ensures that fires will be confined or adequately retarded from spreading to adjacent portions of the facility.

This design feature minimizes the possibility of a single fire rapidly involving several areas of the facility prior to detection and extinguishment.

The fire barrier penetration seals are a passive element in the facility fire protection program and are subject to periodic inspections.

During periods of time when the seals are not functional, a continuous fire watch is required to be maintained in the vicinity of the affected seal until the seal is restored to functional status.

E.

Water Suppression System Water suppression systems for the oil systems located within the M-G set room and M-G set lube oil room are provided to contain a possible oil fire to the respective fire area.

The_ suppression system is a pre-action type using smoke detectors to charge the sprinkler headers with fire water and spray nozzle actuation on high temperature.

Both fire water ficw (Iow pipe pressure swi tch ) and smoke detector actuation annunciates in the control room.

The sprinkler header is normally pressurized with air, with a low pressure annunciator to monitor header and nozzle integrity.

F.

Battery Room Ventilation Flow Detector Loss of the battery room exhaust ventilation flow will result in a buildup of combustible gases and a potential fire hazard to safety-related cables.

A flow detector will annunciate an alarm i

in the control room upon poor ventilation conditions.

l

- 240 r -

PBAPS 4.14 BASES A.

Water Fire Protection System The monthly test of the fire pumps is conducted to check for equipment failures and deterioration.

The fire pump minimum capacity is based on a design load of 2400 gpm for the largest oprinkler plus 300 gpm for manual hose lines.

When it is determined that a fire pump is inoperable, the increased surveillance required by 4.14.A.2 provides adequate assurance that the remaining pump will be operable when required.

B.

CO2 Fire Protection Systems Weekly checking of the storage tank level and pressure is deemed adequate to provide assurance that sufficient CO2 will be available in the event of a fire occurrence.

The method for testing heat detectors in the automatic discharge systems is in accordance with NFPA-72E-1974.

Testing of the discharge initiation logic, injection valve, damper closings, and fan trippings without actual discharge of CO2 into a room demonstrates operability of the active components of the systems.

System operability is demonstrated by both manual and automatic initiation for automatic discharge systems.

Testing of the headers and nozzle by an air flow test will detect buildups of material which may affect continued availability.

C.

Fire Detection The method for testing fire detectors is in accordance with NFPA-72E,1974.

D.

Fire Barrier Penetrations Penetration fire barrier seals are visually inspected to verify that they are functional.

- 240 s -

P isn P S LINITING COUDITIONS F 0lt OPERATI0ll SURVEILLANCE REQUIREMENTS 3.15 Seismic Monitoring 4.15 Seismic Monitoring

'I'n s t r u m e n t a t i o n Instrumentation

~

Applicability Applicability 3

Applies to the operational Applies to the surveillance status of the seismic requirements of the seismic monitoring instrumentation.

monitoring instrumentation.

Sp,e c i f i c a t i o n n Specifications A.

The seismic monitoring A.

Each of the required inutrumentation' shown in seismic monitoring instruments Table 3.15 shall be shall be demonstrated operable.

operabic by the performance I

of the Instrument Check, II. With one or more seismic Instrument Functional Test, monitoring instruments and Instrument Calibration inoperable for more than operations at the frequencies 30 days, in lieu of any shown in Table 4.15.

other report required by Specification 6.9.2, B.

Each of the required prepare and submit a seismic monitoring instruments Special Iteport to the actuated during a seismic Director of the event shall be restored to approprir,te Regional Of fic(

operable status within 24 pursuant to Specification hours and an Instrument 6.9.3 within the next 10 Calibration performed within working days outlining the 5 days following the seismic cause of the malfunction event. Data shall be and the plans for restoring.

retrieved from actuated the instrument (s) to instruments and analyzed to operable status.

determine the magnitude of the vibratory ground motion.

C.

The provisions of S pecif icc tion in lieu of any other report 3.0.c are not applienble.

required by Specification 6.9.2, a Special tieport shall be prepared and submitted to the Director of the appropriate 1( e gi o na l Office pursuant to Specification 6.9.3 within 10 working days describing the magnitude, frequency spectrum and resultant effect upon facility features important to safety.

- 24 0 t-

. ~ - _

~ _ -

T A ll L E 3.15**

S_E ISMIC !!ONITORI NG INSTRUMENTATION Minimum Measurement Instruments Instruments and Sensor Locations #

Range Operabic l.

Triaxial Time-Itistory Accelerographs

~

a.

Containment Foundation (torus compartment) 0.1-10g 1

h.

Rel'uuling F loo r U.1-10n 1

c.

RCiC Pump (Rm #7) 0.1-10g 1

d.

"C" Diesel Generator 0.1-10g 1

4

2. Triaxial Peak Accelerdgraphs

)

a.

Reactor Piping (Drywell) 0.01-?g 1

4 b.

Refueling Floor 0.01-2g 1

c.

RCIC Pump (Rm #7) 0.01-2g 1

3. Trinxini Response-Spectrum Recorders a.

Cable Spreading Rm 0.1-10g 1*

1

}

With reactor control room annunciation j

    • Effective upon completion of installation.

Seismic instrumentation located ir. Unit 2 r

- 2 4 0 (u ) -

}

_T A.B L E_ 4.15 *

  • h EIS: llc *10NITORitiG INSTRUllENTATION SURVELLLANCE REQUIREMENTS Instrument
  • Instrument
  • Functional Instrument
  • Instruments and Sensor Locations #

Check Test Calibration

1. Triaxial Time-liistory Accelerographs a.

Containment Foundation (torus compartment)

M SA R

b.

Refueling Floor M

SA R

c.

RCIC Pump (Rm #7)

M SA R

d.

"C" Diesel Cencrator M

SA R

2. Triaxial Peak Accelerographs l

a.

Reactor Piping (Drywell)

NA NA R

b.

Refueling Floor NA NA R

j' RCIC Pump Rm (!!m #7)

NA NA R

c.

3. T r i a ::I a l Renponse-Spectrum it e c o r d e r s i

n.

Cable Spreading Rm H

SA R

4 3

Surveillance Frequencies M:

every month SA:

every 6 months R:

every 18 months 4

    • Effective upon completion of installation.

Seismic instrumentation located in Unit 2.

'k i

1

-240v-i i

h

PBAPS 3.15/4.15 BASES The operability of the. seismic monitoring instrumentation e dsu re s that sufficient capability is available to promptly determine the magnitude of a seismic event and evaluate the response of those features important to safety.

This capability is required to permit comparison of the measured response to that used in the design basis for the plant.

e

.l l

l o

-24 W -

-