LER 90-001-00:on 900209,Gilbert/Commonwealth,Inc Informed Util of Vendor Requirement to Rept Design Deficiency Re Failure of Safety Function,Per Part 21.Util Evaluating What Design Mods Can Be Made to Correct deficiency.W/900312 Ltr
ML20012C423
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 03/12/1990
From: Bradham O, Higgins W
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
REF-PT21-90 LER-90-001, LER-90-1, NUDOCS 9003210267
Download: ML20012C423 (4)


Text

r - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

4

,1b- '10CFR50.73 g# s j gi c ;:pne ti. cme a ces company gil:yp.er.dy.m.

nueezr operation

gngngvgigse mes ;

SCE&G

-- m.,

March 12, 1990 ,

Document Control Desk U. S. Nuclear Regulatory Commission >

Washington, DC 20555

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12. ,

LER 90-001 Gentlemen:

Attached.is Licensee Event Report No.90-001 for the Virgil C. Summer Nuclear Station. This report is submitted pursuant to the requirements of 10CFR50.73(a)(2)(v).

Should there be any questions, please call us at your convenience.

Very truly yours,

0. S. Bradham

' f &

DCH/0SB: led Attachment c: D. A. Nauman/0. W. Dixon, Jr./T. C. Nichols, Jr.

E. C. Roberts R. V. Tanner J. C. Snelson S. D. Ebneter R. L. Prevatte J. J. Hayes, Jr. J. B. Knotts, Jr.

General Managers INP0 Records Center C. A.-Price ANI Library G. J. Taylor Marsh & McLennan J. R. Proper NPCF R.._B. Clary NSRC F. H. Zander RIS (0N0900010)

T. L. Matlosz Files (818.05 & 818.07)

K. E. Nodland 9003210267 900312

{DR ADOCK 05000395 PDC f

if

/M

Jj.

(, .

N.C . . .. _ Li m e. m .. YCo . N Apenovt0 OMO es0 3113 4108 5 I UCENSEE EVENT REPOAT (LER) '"'a"'"

PActatTV seAast m 900a57 asuneen 13: raer m Virgil' C. Summer Nuclear Station oisIoloIol3;9 i5 i jorl0 l 3 TITLt tel Part 21 Report Indicates Failure of a Safety Function

~

SVONT Daf t 404 Lem Nyneta (4) IISP0mf oaf t (71 OTMen F ACILITies serv 0 Lyt 0 let MONTH DAY vsAR vtAR %QMh'6 $@ MONTH day vtan 'ACLiveNAMes DOCKET NUMetnisi 015101010 I I l 0l2 0l 9 90 9l0 0l 0l1 0l0 0l 3 1l2 9l0 ,,,,, ,,, ,

o,, ,,,,,,e T.a. . 0 T m .v mio ,v uANT TO TMt .. Oui.. NT. O, i. Cea t <ca - ., ,, ,, n i "a**

  • n .=w 1 mw m nw H . ruim l

[

=,

.. u,H.,

100i 4n,.

,o, 1 _

,u, t.,

H. n wnn.i m.ni. .

.nwaH . _g g M .eSteH1Hul es.?3 sit 3 Hil ge.73telttH.euHA) JesAJ 80 38tslOHl.1 se,73esH3Hul ge,79ts)WH.selHei M 4NieH1H.I 90.734st4Hitll 30.794siGHal lac 68888 CoefT ACT POR TMIO LaR Hal NAME TELE *MONE NUM0ER AmlaC005 W. R. Higgins, Supervisor, Regulatory Compliance 8033 i 3,4,S i ,40,42 i i i

CotAPL878 0884 LINE 90A 4ACM COhp00stNT f AILURE DGKme080 IN TMI6 Repom? Han CAust SYSTsu COMP 3NENT

"#$C' "fD PM s't CAUSS SvfT8M COMPON4NT "A A O*

RfD L

S" W's' j B KM i ,C iH ,U , , , Y i i I I I I I I I I I I I I SUPPLEAIGNTAL RIpoaf EMPSCTED H44 MONTH DAY vtAA SV9MI58 TON

"""* 12 31 T vn <,,,M. . . surerto sv .uw0 OArei 7 NO i 9i0 Anaf, ACT <L , ,. suo ., a. . , ,,. . ,, ~, , , os, On February 9, 1990, at approximately 1400 hours0.0162 days <br />0.389 hours <br />0.00231 weeks <br />5.327e-4 months <br />, Gilbert / Commonwealth. Incorporated (G/C), the Architectural Engineer (AE) for the Virgil C. Summer Nuclear Station, informed the plant of the G/C requirement to report a design deficiency per 10CFR21.

The AE evaluation of the present design had reached the point where it was clear that, in the event of a High Energy Line Break (HELB) in the Intermediate Building (where the chiller units are located), one train of chilled water would be lost and the status of the other train was indeterminate. Since then. the AE has further completed the evaluation and has confirmed that, in the event of an HELB in the Intermediate Building, both chilled water trains would be rendered inoperable. This represents a failure of a safety function as described in 10CFR50.72 (b)(2)(iii) and was reported as such by South Carolina Electric & Gas Company (SCE&G).  ;

The 10CFR21 report by G/C indicated that the previous evaluation of an HELB on the chilled water system addressed the effects of an HELB with respect to the chiller unit itself. However, the effects of the heat load on the cooling coils that would be exposed to the steam environment were not adequately addressed. Two actions were taken in order to protect the system from the recognized deficiency. The first action provided new guidance on balancing the chiller units such that each chiller is capable of supporting its respective loads during any accident, with the exception of an HELB in the Intermediate Building. The second action isolated the cooling coils, which if exposed to the steam environment created by an HELB in the Intermediate Building, would have placed excessive heat loads on the chillers.

SCE&G is evaluating the feasibility of what, if any, permanent design modifications can be made to correct the present deficiency. Upon completion of this evaluation, a supplemental LER is expected to be submitted by December 31, 1990.

ga,Cg . m.

q*v j Bhc form assa u s NUCLEAT. 5 EIUL ATORY COMMIS8CN

, . , LICENSEE EVENT REPORT (LER) TEXT CONTINUATION apeRovio ove No siso-oio. -

.- , EXP RE8 8131416 F ActLITV NAMt (14 DOCKET NUMBER (2) LIR NUMBE R (61 - PAGE (31 viaa MfJ.'. ' "'J### l Virgil C. Summer Nuclear Station ol5l0lolol3l9l5 9l0 -

0l0l1 -

0l0 0l2 or 0l3 taxim,,-..m e . .w ac w w unn  ;

i PLANT IDENTIFICATION:

- Westinghouse - Pressurized Water Reactor E0VIPMENT IDENTIFICATION: 1 Chilled Water System EIIS - KM s- i l

IDENTIFICATION OF EVENT:

A design deficiency reported per 10CFR21 indicated that a single event could preventthefulfillmentofasafetyfunctionasdescribedin10CFR50.73(a)(2)(v). >

EVENT DATE:

February 9, 1990, at 1415 EST t REPORT DATE:

March 12, 1990 l CONDITIONS PRIOR TO EVENT:

Mode 1,:100% power.

DESCRIPTION OF EVENT:

i On February 9, 1990 at approximately 1400 hours0.0162 days <br />0.389 hours <br />0.00231 weeks <br />5.327e-4 months <br />, Gilbert / Commonwealth, Incorporated l (G/C), the Architectural Engineer (AE) for the Virgil C. Summer Nuclear Station, informed the plant of the G/C requirement to report a design deficiency per

'10CFR21. The deficiency was identified as a result of an evaluation to resolve a concern expressed by Non-Conformance Notice (NCN) 3645 which was generated by on-I site personnel.

The AE evaluation of the present design had reached the point where it was clear l

that, in the event of an HELB in the Intermediate Building (where the chiller units' are located), one train of chilled water would be lost and the status of the other train was still indeterminate. It is important to note that upon failure of the chilled water train, the Component Cooling Water (CCW) Pumps and Charging / Safety Injection (SI) Pumps on the affected train would be rendered inoperable. Since 10CFR21 requires assumption of a single failure, this condition met the criteria for reportability. 10CFR50.72(b)(2)(iii) does not require the assumption of a single failure, but since the status of the other train of chilled water was questionable SCE&G made the decision to report the results to the NRC per 10CFR50.72(b)(2)(iii). This report was made at 1415 hours0.0164 days <br />0.393 hours <br />0.00234 weeks <br />5.384075e-4 months <br />.

Nic FORM 366A J _ _ . . -- n

.' =

. ; ey : e hee.=soon us Nuctsaa s.stutttonv commission

  • ** ' LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Arenovso ove No. siso-oio.

,* i rian er3m.

f ACILITV NAML (13 DOCKli NUM8t h L2) LEM NUMOER (61 PAOI (33 j

, nsa " M%" 3*n:

Virgil C. Summer Nuclear Station o p lo lo jo 13 l9 l5 9l0 -

0 l 0l 1 -

0l 0 0l 3 or 0l3 1 TEXT IU more space in requeed, use ed6toonel NRC Fon jim M (17> l 1

s The AE has further completed the evaluation and has confirmed that, in the event of I an HELB in the Intermediate Building, both chilled water trains would be rendered '

inoperable.

CAUSE OF EVENT:

The 10CFR21 report by G/C indicated that the previous evaluation of an HELB on the chilled water system addressed the effects of an HELB with respect to the chiller .

unit itself. However, the effects of an HELB with respect to the heat load on the cooling coils that would be exposed to the steam environment were not adequately addressed.

ANALYSIS OF EVENT:

-Since this is an analysis of the condition resulting from an HELB in the p Intermediate Building and not the result of an actual event, there has never been an actual challenge of the systems or a compromise of safety to the plant.

1.

IMMEDIATE CORRECTIVE ACTION:

l Due to NCN-3645 questioning the adequacy of the design, a interim solution was i implemented on January 26, 1990, to alleviate the concern pending an answer of the NCN. This solution performed two actions. The first action provided new guidance on balancing the chiller units such that each chiller is capable of supporting its respective loads during any accident, with the exception of an HELB in the i Intermediate Building. The second action isolated the cooling coils which would be exposed to the steam environment created by an HELB in the Intermediate Building.

Those coils service the Emergency Feedwater Pump and the Service Water Booster Pump I areas. It is important to note that the isolation of these coils was verified not to be essential to the affected areas during an accident.

These items were in place when SCE&G was notified of-the design deficiency and will remain in place until permanent modifications can be implemented.

l ADDITIONAL CORRECTIVE ACTION:

4 SCE&G is evaluating the feasibility of what, if any, permanent det,ign modifications can be made to correct the present deficiency. Upon completion of this evaluation, a supplemental LER is expected to be submitted by December 31, 1990.

PRIOR OCCURRENCES:

l None i