Forwards Supplemental Info Re Status of Human Engineering Discrepancies 113 & 263,in Response to Questions Raised in 891201 Telcon
ML20005G065
Person / Time
Site: Fort Calhoun Omaha Public Power District icon.png
Issue date: 01/10/1990
From: Morris K
OMAHA PUBLIC POWER DISTRICT
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LIC-89-1201, NUDOCS 9001180074
Download: ML20005G065 (4)


Text

4 ,

V e-I

4 te
  1. Omaha Public Power District 1623 Harney Omaba. Nebraska 68102 2247 402/636 4000

' January 10, 1990 LIC-89 1201 4

U. S. Nuclear Regulatory Commission m Attn: Document Control Desk

'Miil Station P1-137 f" Washington, DC.20555

References:

1. - Docket No. 50-285-
2. Letter from OPPD (K. J. Morris) to NRC (Document Control Desk) dated November 15, 1989 (LIC-89 1023)

'entlemen:

G

SUBJECT:

. Supplemental Information Concerning Status of Human Engineering Discrepancies (HEDs) 113 and 263 The purpose of this letter is to respond to questions raised in a December 1, 1989 telephone conversation between the NRC and.0maha Public Power District (OPPD) .- Specifically, this letter explains why HEDs No.113 and No. 263 in Reference 2 are no. longer considered to be Human Engineering Discrepancies.

Enclosed please find OPPD's revised resolutions to HED Nos.113 and 263. The revisions are denoted by vertical lines in-the right hand margin.

.If you should have any questions, please contact me.

Sincerely, ik*

, 4. orris

. Division Manager gp Nuclear Operations KJM/pje Enclosures c: LeBoeuf, Lamb, Leiby & MacRae R. D. Martin, NRC Regional Administrator, Region IV A. Bournia, NRC Project Manager P. H. Harrell, NRC Senior Resident Inspector

- 0 9001180074 900110 - 0 PDR ADOCK 05000285 l P PDC ,j 45 st24 Enipioumen guai opportunitu 9

D h.

p', FORT CALHOUN STATION DETAILED CONTROL ROOM DESIGN REVIEW HED FINAL RESOLUTION HED NO 113 l HED #113 states that the neon indicator lights are "hard to see." This HED previously had a criticality rating (error potential, plant impact) of 2, 2.  ;

MR-FC-85143 was initiated to correct this human engineering discrepancy. l The criticality rating of this HED has since been re evaluated, and OPPD I has determined that the rating should have been a 4, 4. The following gives a history of the devices and an explanation for why the criticality rating _

was changed:

In 1976, the neon indicating lights were installed to prevent randomly induced noise spikes from tripping the Reactor Protection System (RPS). j During installation of the neon lights, extensive trouble shooting was conducted to maintain the illumination level as high as possible while )

eliminating noise spikes in the RPS. '

The thirteen sets of indicating lights listed in HED #113 involve the Raw 1 1 I

Water / Component Cooling Water (RW/CCW) and Chemical and Volume Control systems.

1) TwtM of the thirteen sets of lights referenced are status lights l !

for GI/CCW header pressure. These lights serve to warn Operations

staff when the header pressure falls below desired pressure.

Status of RW/CCW header pressure is properly displayed (per NUREG 0700 guidelines) on flow indicators (FI-2890, FI-2891) I and on a pressure indicator (PI 2892 located on C8-10/11).

RW/CCW header pressure and flow are also annunicated in L annunciator A-1 located on the upper section of C810/11. i

? The subject indicating lights are not needed for normal, l abnormal or emergency operation. They serve as additional informational aides to the operators. Therefore, these lights are not considered safety related.

2) The last set of lights referenced provide valve position indication

! (open/ closed) for HCV-239. I There is "off-normal status" and " closed signal failure" annunciation for the shutdown cooling valves in annunciator A2 l

on CB 10/ll. Indication of this valve is not required per  !

Regulatory Guide 1.97. Therefore, these lights are not l 1

considered safety related. l l

l l

l

)

'n i

l CRITICALITY RATING The criticality rating is made up of two numbers, a categorization number o and a prioritization number both of which range from one (high criticality) to four (low criticality). J The categorization number for HED fil3 was originally determined to be two, which indicated that this human engineering discrepancy had (1) a low potential for error and (2) was safety related (as explained in Fort Calhoun Control Room Design Review Summary Report Section 2.3.2).

Re-evaluation of the thirteen sets of subject indicating lights against the Plant impact criteria (Section 2.3.2.2) determined that the lights are '

non-safety related and have a low potential for error, as originally determined (Section 2.3.2.1). Therefore, the categorization number was changed from two to four.

The prioritization number' for HED #113 was originally deternnned to be two.

The HED was reviewed against the criteria for establishing a prioritization number (Section 2.3.3). A prioritization number of 4 is appropriate since:

o Changing the neon indicating lights back to the original configuration ,

(incandescent lights) could result in randomly induced noise spikes, e A major control room redesign effort would be required to correct the HED. Since the HED is non-safety related, a major design expenditure is not justifiable.

In conclusion, this HED has been re evaluated and a new criticality rating of 4, 4 established. As a result of the low safety concern and the expected high cost of design correction implementation, a modification is not justified.

i i l

Modification MR-FC-85-143 has been cancelled and no further action is l required.

l 1

b

<r il FORT CALHOUN STATION t .
j. DETAILED CONTROL ROOM DESIGN REVIEW HED FINAL RESOLUTION HED NO. 263 Description of Discrepancy 1

The use of neon bulbs does not provide enough illumination to determine what state the equipment is in.

HED No. 263 is no longer considered to be a Human Engineering Discrepancy. See Final Resolution for HED No.113 i

i l

l

.a