Clarifies 900913 Application for Amends to Licenses DPR-31 & DPR-41,eliminating RTD Bypass.Util Will Perform cross-calibr of All RTDs During Each Refueling Cycle by Comparing Installed RTDs to Each Other
ML17348A772
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 12/13/1990
From: Plunkett T
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-90-442, NUDOCS 9012180037
Download: ML17348A772 (4)


Text

, ACCELERATED DISTRIBUTION DEMONSTRATION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR: 9012180037 DOC. DATE: 90/12/13 NOTARIZED: NO DOCKET,C FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH. NAME AUTHOR AFFILIATION PLUNKETT,T.F. Florida Power & Light Co.

RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Clarifies 900913 application for amends to Licenses DPR-31 &

DPR-41,eliminating RTD bypass. Util will perform cross-calibr of all RTDs during each refueling cycle by comparing installed RTDs to each other.

DISTRIBUTION CODE: A001D COPIES RECEIVED:LTR EWCZ g SZZE:

TITLE: OR Submittal: General Distribution NOTES:

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR EN CL ID CODE/NAME LTTR ENCL PD2-2 LA 1 PD2-2 PD EDISON,G 2 INTERNAL: NRR/DET/ECMB 9H NRR/DET/ESGB NRR/DOEA/OTSB11 NRR/DST 8E2 NRR/DST/SELB 8D NRR/DST/SICB 7E NRR/DST/SRXB 8E NUDOCS-ABSTRACT OC/LFMB OGC/HDS2 RE 01 RES/DSIR/EIB EXTERNAL: NRC PDR NSIC NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED: LTTR 18 ENCL

DEC 18 1SSO L-90-442 U. S. Nuclear Regulatory Commission Attn: Document Control Desk washington, D. C. 20555 Gentlemen:

Re: Turkey Point Units 3 and 4 Docket No. 50-250 and 50-251 R sistance Tem erature Detector B ass Elimin, i n Pro'ect By letter L-90-6SA, dated September 13, 1990, Florida Power and Light (FPL) submitted a request to amend the Turkey Point Technical Specifications by eliminating the Resistance Temperature Detector (RTD) Bypass. Subsequently, the NRC and FPL met on November 27, 1990, to discuss the above submittal. At this meeting FPL agreed to review initial implementation testing and subsequent periodic testing of RTD response time and the T,median signal selector, and initial and subsequent RTD cross-calibration.

In addition to the initial RTD cross-calibration, RTD response time testing, and the T,median signal selector testing which will be performed as part of the normal start-up and turnover process, FPL will perform periodic testing as described below.

FPL will perform RTD response time testing meeting the following criteria:

o In-situ response time testing of the RTDs will be performed using the Loop Current Step Response method.

o The above testing will be performed for the three channels once every three refueling cycles on a staggered test basis, with a separate channel being tested during each refueling cycle (1S months).

FPL willperform cross-calibration of all RTDs during each refueling cycle by comparing the installed RTDs to each other.

FPL will test the T,median signal selector quarterly.

The above testing does not require a change to the proposed license amendment. Procedures implementing this testing will be issued consistent with the system start-up schedule.

Should there be any questions, please contact us.

Very truly yours, T. F. Plunkett Vice President Turkey Point Plant Nuclear TFP/GS CC: Stewart D. Ebneter, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant 90i2i80037 9012i3 PDR ADOCK 05000250 P PDR an FPL Group company rll ~ A <u 4~