LGS UFSAR APPENDIX 9A - FIRE PROTECTION EVALUATION REPORT TABLE OF CONTENTS 9A.1 INTRODUCTION 9A.2 FIRE PROTECTION SYSTEM DESCRIPTION 9A.2.1 Fire Protection Water Supply Systems 9A.2.1.1 Water Source 9A.2.1.2 Pumps 9A.2.1.3 Yard Piping 9A.2.2 Wet Pipe Sprinkler Systems 9A.2.3 Preaction Sprinkler Systems 9A.2.4 Deluge Systems 9A.2.5 Water Deluge Application for Charcoal Filters 9A.2.6 Wet Standpipes and Hose Stations 9A.2.7 Foam Extinguishing System 9A.2.8 Low Pressure Carbon Dioxide System 9A.2.9 Halon Extinguishing Systems 9A.2.10 Water Curtain Systems 9A.2.11 Portable Fire Extinguishers 9A.2.12 Fire and Smoke Detection System 9A.3 COMPARISON BETWEEN LGS FIRE PROTECTION PROGRAM AND NRC GUIDELINE DOCUMENTS 9A.3.1 NRC Branch Technical Position CMEB 9.5-1 9A.3.1.1 Detailed Comparison to Branch Technical Position CMEB 9.5-1 9A.3.1.2 Explanatory Notes for Comparison to Branch Technical Position CMEB 9.5-1 9A.3.2 10CFR50, Appendix R 9A.3.2.1 Detailed Comparison to 10CFR50, Appendix R 9A.3.2.2 Explanatory Notes for Appendix R Comparison APPENDIX 9A 9A.i REV. 18, SEPTEMBER 2016
LGS UFSAR 9A.4 EVALUATION OF POTENTIAL FIRE HAZARDS 9A.4.1 Scope of Evaluation 9A.4.2 Procedure 9A.5 ANALYSIS OF CAPABILITY TO ACHIEVE SAFE SHUTDOWN Security Related Information Table withheld Under 10 CFR 2.390 APPENDIX 9A 9A.ii REV. 18, SEPTEMBER 2016
LGS UFSAR Security Related Information Table withheld Under 10 CFR 2.390 APPENDIX 9A 9A.iii REV. 18, SEPTEMBER 2016
LGS UFSAR Security Related Information Table withheld Under 10 CFR 2.390 APPENDIX 9A 9A.iv REV. 18, SEPTEMBER 2016
Security Related Information Table withheld Under 10 CFR 2.390 APPENDIX 9A 9A.v REV. 18, SEPTEMBER 2016
LGS UFSAR 9A.6.1.4 Summary 9A.6.2 Analysis of High/Low Pressure Interfaces 9A.6.3 Fire Barrier Penetration Assemblies for 4 kV Bus Ducts 9A.6.4 Analysis of Effects of Multiple High Impedance Faults on the Safe Shutdown Capability of the Plant 9A.6.4.1 Methodology and Assumptions 9A.6.4.2 Results 9A.6.5 Minimum Effective Design Density (MEDD) 9A.6.5.1 Cable Tray Fires 9A.6.5.2 Oil Spill Fires 9A.6.5.3 Conclusion 9A.7 REFERENCES 9A.7.1 Appendix A to BTP APCSP 9.5-1 Guidelines for Fire Protection for Nuclear Power Plants docketed prior to July 1, 1976 9A.7.2 BTP CMEB 9.5-1 Guidelines for Fire Protection for Nuclear Power Plants", Rev. 2, dated July ,1981 9A.7.3 Appendix R to 10 CFR 50 Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979 9A.7.4 NUREG-0991, LGS SER, August 30, 1983.
9A.7.5 NUREG-0991, Supplement 2, October 1984.
9A.7.6 NUREG-0991, Supplement 8, June 1989.
9A.7.7 NUREG-0991, Supplement 9, August 1989.
9A.7.8 Letter from Eugene J. Bradley (PECO) to Dr. Thomas E. Murley (USNRC) dated April 5, 1988 (Revision 10 to FPER).
9A.7.9 Engineering Analysis LEAF-0001 Smoke Detector Engr Analysis For Fire Areas 1, 2 & 7.
9A.7.10 Engineering Analysis LEAF-0002 Suppression System Evaluation.
9A.7.11 Engineering Analysis LEAF-0009 Galvanized Steel Cable Tray Covers In CFZ-5.
9A.7.12 Engineering Analysis LEAF-0010, Switchgear Room Bus Duct Penetrations.
APPENDIX 9A 9A.vi REV. 18, SEPTEMBER 2016
LGS UFSAR APPENDIX 9A - FIRE PROTECTION EVALUATION REPORT LIST OF TABLES TABLE TITLE 9A-1 Fire Protection Evaluation 9A-2 Heat of Combustion Valves 9A-3 Insulation and Jacketing Materials Used for Electrical Cabling 9A-4 Major Components Analyzed for Fire Safe Shutdown 9A-5 Deleted 9A-6 Deleted 9A-7 Deleted 9A-8 Deleted 9A-9 Deleted 9A-10 Deleted 9A-11 Deleted 9A-12 RCPB Valves Susceptible to Fire Induced Spurious Operation 9A-13 Location of Critical High/Low Pressure Interface Valves by Fire Area 9A-14 Operations that may be Required to be Performed Outside the Control Room 9A-15 Deleted 9A-16 Deleted 9A-17 Deleted 9A-18 Deleted 9A-19 Deleted 9A-20 Deleted 9A-21 Deleted 9A-22 Deleted APPENDIX 9A 9A.vii REV. 18, SEPTEMBER 2016
LGS UFSAR LIST OF TABLES (Cont'd)
TABLE TITLE 9A-23 Deleted 9A-24 Deleted 9A-25 Deleted 9A-26 Deleted 9A-27 Deleted APPENDIX 9A 9A.viii REV. 18, SEPTEMBER 2016
LGS UFSAR APPENDIX 9A - FIRE PROTECTION EVALUATION REPORT LIST OF FIGURES FIGURE TITLE Security Related Information Text withheld Under 10 CFR 2.390 APPENDIX 9A 9A.ix REV. 18, SEPTEMBER 2016
LGS UFSAR APPENDIX 9A - FIRE PROTECTION EVALUATION REPORT 9A.1 INTRODUCTION On September 30, 1976, the Director of the Division of Project Management, of the Office of Nuclear Reactor Regulation, requested a re-evaluation of the fire protection program for the LGS.
Attached to that document was Appendix A to BTP ASB 9.5-1, "Guidelines for Fire Protection for Nuclear Power Plants Docketed Prior to July 1, 1976". The following report was prepared in response to that request and discusses the fire protection program as it relates to nuclear safety and addresses our conformance to BTP CMEB 9.5-1 (which superseded BTP ASB 9.5-1).
It is the licensees philosophy that fire protection be provided for all company facilities to minimize the effects of a fire. Therefore, proper fire protection was an original design objective for LGS.
Responsibility for the fire protection program is vested in licensee managerial personnel in the same manner as other operating and design responsibilities. To support these responsibilities, the licensee employs qualified fire protection personnel to ensure an adequate fire protection program is provided.
Bechtel Power Corporation provided the fire protection engineers and consultants to develop the design concept, prepare specifications, and select experienced fire protection contractors. Bechtel has designed the fire protection systems for several operating nuclear plants and has a specialized staff that monitors the latest in fire protection methods.
The term "fire protection system" refers to the integrated complex of components and equipment provided for detection and suppression of fires. In addition to this system, the "fire protection program" includes the concepts of design and layout implemented to prevent or mitigate fires, administrative controls and procedures, and personnel training. The fire protection program uses a defense-in-depth approach aimed at preventing fires, minimizing the effect of any fires that occur, providing appropriate fire detection and suppression equipment, and training personnel in fire prevention and fire fighting.
LGS has been evaluated with regard to fire protection to verify that the total fire protection program provides reasonable assurance that a fire will not prevent the performance of necessary safe shutdown functions and will not cause an undue risk to the health and safety of the public.
Section 9A.2 of this report provides a general description of the fire detection and suppression systems provided for LGS. Section 9A.3 presents point-by-point comparisons of the LGS fire protection program with the guidelines set forth in BTP CMEB 9.5-1 and 10CFR50, Appendix R.
Section 9A.4 provides an evaluation of the combustible loadings in the plant and the ability of specific fire barriers to withstand postulated fires. Section 9A.5 provides an evaluation of the ability to safely shut the plant down in the event of a fire in any fire area. Section 9A.6 discusses special topics. Section 9A.7 provide a listing of references associated with this document.
APPENDIX 9A 9A-1 REV. 14, SEPTEMBER 2008
LGS UFSAR 9A.2 FIRE PROTECTION SYSTEM DESCRIPTION This chapter provides a description of the fire suppression and fire detection systems. The specific guidelines contained in BTP CMEB 9.5-1 are addressed in Section 9A.3.
Figure 9A-1 shows the legend and symbols for P&IDs. The P&ID for the fire protection system is shown in Figure 9A-2.
9A.2.1 FIRE PROTECTION WATER SUPPLY SYSTEMS 9A.2.1.1 Water Source The source of water for the fire protection system is two cooling tower basins which have a capacity of 7,200,000 gallons each, for a total capacity of 14,400,000 gallons. For a system pumping capacity of 5000 gpm, this allows continuous operation of both fire pumps for 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />. If one cooling tower basin or supply line is not available, the remaining water source provides both fire pumps with a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> supply of water. Water for the fire pumps is taken from either Unit 1 or Unit 2 cooling tower water basins through connections to the circulating water lines. Check valves are installed at the pump discharges to prevent water from one source from being pumped into the other source.
9A.2.1.2 Pumps There are two (2) horizontal centrifugal-type fire pumps, each capable of 2500 gpm at a system head of 125 psig. The 100% capacity lead pump is electric motor-driven and the 100% capacity lag pump is diesel engine-driven. The pumps and their controllers are UL-listed.
The fire water system is capable of delivering 100 gpm per hose station at no less than 65 psig to any hose station, considering the operation of two hose stations simultaneously with the largest water demand flowing from any automatic suppression system in the vicinity of the hose stations.
In addition to the 100 gpm per hose station, 300 gpm is assumed at the nearest outside fire hydrant to support manual fire fighting activities. This meets BTP section C.6.b.(11) requirement of 500 gpm for manual hose streams in addition to the largest suppression system design. When the fire pumps are not running, the standpipes are maintained full of water by a 2 inch connection to the service water system which is capable of replenishing 50 gpm for leakage.
When a portion of the fire water system is activated, a low pressure switch set at 100 psig provides a signal to start the motor-driven pump automatically. If the motor-driven pump fails to start, the diesel-driven pump receives a start signal at a lower pressure signal setpoint of 95 psig to start the diesel-driven pump automatically. Both pumps are stopped manually.
A third Fire pump is provided as a backup to the two primary pumps. This pump is diesel engine driven and is placed in service as stated in the technical requirements manual bases 3/4 7.6 to satisfy the requirement of providing an alternate pump.
The electric power for the motor-driven fire pump is taken from a load center that is supplied from the non-Class 1E, 13 kV switchgear. The primary power source for the switchgear is the unit auxiliary transformer, and the secondary power source is the offsite power supplies. If the primary power source fails, the switchgear is automatically transferred to one of the two offsite power supplies. Switching from one offsite power supply to the other can be performed manually from the control room.
APPENDIX 9A 9A-2 REV. 17, SEPTEMBER 2014
LGS UFSAR Security Related Information Text withheld Under 10 CFR 2.390 9A.2.1.3 Yard Piping Security Related Information Text withheld Under 10 CFR 2.390 APPENDIX 9A 9A-3 REV. 17, SEPTEMBER 2014
LGS UFSAR Security Related Information Text withheld Under 10 CFR 2.390 9A.2.3 PREACTION SPRINKLER SYSTEMS Security Related Information Text withheld Under 10 CFR 2.390 APPENDIX 9A 9A-4 REV. 17, SEPTEMBER 2014
LGS UFSAR Security Related Information Text withheld Under 10 CFR 2.390 9A.2.4 DELUGE SYSTEMS Security Related Information Text withheld Under 10 CFR 2.390 APPENDIX 9A 9A-5 REV. 17, SEPTEMBER 2014
LGS UFSAR Charcoal filters in the ventilation systems of the plant are provided with water deluge application systems for fire protection. The water is supplied to the filters by means of a fixed piping system.
An indicating gate valve is manually opened when a thermal sensor actuates a local alarm system and registers an alarm condition on the fire protection panels in the control room. The operation is terminated manually by shutting the gate valve.
9A.2.6 WET STANDPIPES AND HOSE STATIONS Wet standpipes are designed for Class II service in accordance with NFPA 14. All areas in the power block are within reach of at least one effective hose stream. Each hose station has nominally 100 feet of NFPA compliant fire hose. Hose stations are located outside entrances to normally unoccupied areas, and outside both entrances of the control room. Most areas of the plant have adjustable fog nozzles that can be adjusted down to a straight stream. In areas with electrical hazards, there are adjustable fog nozzles (intrinsically safe) that will not go down below a 30 degree fog pattern.
9A.2.7 FOAM EXTINGUISHING SYSTEM A foam system is provided for the protection of the fuel oil transfer structure and one outdoor fuel oil storage tank, and is designed in accordance with NFPA 11. The foam is educted from a foam solution tank by water from the main fire water header. Contacts are provided to annunciate operation of the system in the control room.
The one storage tank is provided with a fixed foam maker at the tank. Foam making is initiated manually from a local station after a high temperature condition at the tank has been alarmed locally and annunciated on the fire protection panels in the control room. Fire protection inside the fuel oil transfer structure is provided by a foam play pipe with hose rack. When the play pipe is removed from its holder, an electric switch located in the holder actuates a control valve to allow foam solution to enter the hose. A squeeze-type play pipe valve enables the operator to control the flow of foam.
9A.2.8 LOW PRESSURE CARBON DIOXIDE SYSTEM The low pressure CO2 system is designed in accordance with NFPA 12. In addition to the total flooding CO2 system provided for the cable spreading rooms a manually actuated, fixed CO2 local application system is provided for Units 1 and 2 turbine generator exciter bearings 11 and 12. CO2 fire protection is also provided by CO2 hose reels in the 13.2 kV switchgear compartment, outside both entrances to the control room, and along the north side of the turbine enclosure operating deck.
The design discharge rate of the total flooding CO2 system for the cable spreading rooms is based on reaching a 50% concentration within 7 minutes. The carbon dioxide storage tank has sufficient capacity to maintain a 50% concentration in both cable spreading rooms simultaneously with Unit 1 for a period of 15 minutes and Unit 2 for a period of 20 minutes, while leaving a reserve in the tank for hose reel operation. A Generic Letter 86-10 evaluation was performed for a NFPA code deviation with respect to the Unit 1 cable spreading room since the CO2 system performance concentration met 50% for 15 minutes versus 20, as was the case for Unit 2.
APPENDIX 9A 9A-6 REV. 17, SEPTEMBER 2014
LGS UFSAR The total flooding CO2 system provided for the cable spreading rooms is actuated manually, using individual pushbutton stations for the Unit 1 and Unit 2 portions of the system. Manual actuation for Unit 1 and/or Unit 2 is accomplished at separate pushbutton stations located in Stairwell 7 adjacent to the cable spreading room. Unit 2 may also be manually actuated by a pushbutton station at the doorway between the Unit 1 and Unit 2 cable spreading rooms. Predischarge alarms are provided to sound locally in the cable spreading rooms and remotely in the control room. In addition to the audible alarms, rotating red alarm beacons are provided in the Unit 1 and Unit 2 static inverter rooms to alert personnel who may be in those rooms when a CO2 discharge occurs. The static inverter rooms are located adjacent to the cable spreading rooms and therefore are potentially subject to CO2 flooding due to leakage, primarily through doorways. A discharge of CO2 into one of the cable spreading rooms will be accompanied by actuation of the predischarge alarms in both cable spreading rooms as well as the rotating alarm beacons in both static inverter rooms. HVAC system penetrations into the area are sealed off by steam isolation dampers which close automatically when the CO2 system is actuated.
The low pressure CO2 system was changed from automatically actuated to manually actuated following a pre-licensing NRC audit of fire protection features (4/9-12/1984). The change was based on the fact that the NRC no longer required automatic actuation due to the installation of an automatic sprinkler system in the cable spreading rooms. This change was deemed necessary in order to achieve a fire protection design that would be acceptable to the NRC. Wet pipe sprinkler system WP-75 serves both cable spreading rooms (fire zones 22 and 23) and is maintained and tested pursuant to Technical Requirements Manual requirements for Spray and/or Sprinkler Systems.
The fixed CO2 local application system for the Unit 1 and 2 turbine generator exciter bearings 11 and 12 within the exciter enclosure is manually actuated by two remote push-buttons located in the vicinity of the exciter housing. One push-button station actuates a timed discharge and a second push-button station actuates a spurt discharge. The timed discharge is set to permit two discharges with the simultaneous operation of two CO2 hose reels on el 269'0" of the turbine building. Operation of either push-button will actuate a rotating beacon and klaxon inside and outside the exciter housing to alert personnel when a CO2 discharge occurs.
CO2 hose reels are activated by removing a play pipe from its holder. An electric switch, located in the play pipe holder, actuates a control valve to allow CO2 into the hose. A squeeze-type play pipe valve enables the operator to control the flow of the CO2 discharge.
9A.2.9 HALON EXTINGUISHING SYSTEMS Three independent Halon extinguishing systems are provided for the raised flooring at el 289' in the control structure. Two of the systems serve the auxiliary equipment room; one system is designed to discharge simultaneously into all floor sections on the Unit 1 side of the room, and the other system is designed to discharge simultaneously into all floor sections on the Unit 2 side of the room. The third Halon system serves the remote shutdown room.
The flooring in the auxiliary equipment room and the remote shutdown room consists of 1 foot high floor sections resting on the concrete slab at el 289'. The floor sections are of all-steel construction (except for aluminum honeycomb in the floor plates) and are used for the routing of cabling to and from the electrical equipment located in the two rooms. In the auxiliary equipment room, this equipment includes the PGCC equipment, the plant computers, the Samac panels, the river evacuation and PA panel, a tone cabinet, and fault detection equipment. The PGCC for each unit consists of floor sections that are 8 feet wide and 20 feet long, each of which has vertical panels APPENDIX 9A 9A-7 REV. 17, SEPTEMBER 2014
LGS UFSAR mounted near the center of the floor section. A termination cabinet is located at one end of each PGCC floor section. Smoke detectors are located in the floor sections and termination cabinets.
The equipment located in the remote shutdown room consists of the remote shutdown panels for Unit 1 and Unit 2. Smoke detectors are located within the floor sections in the remote shutdown room.
The Halon extinguishing systems are designed in accordance with NFPA 12A. Each Halon system is designed to achieve a concentration of 20% by volume with the raised flooring that it serves fully installed and secured. Each system includes two banks of Halon cylinders, each of which has sufficient capacity to maintain a 20% concentration for 20 minutes. In addition to having two banks of Halon cylinders, each system consists of distribution piping and nozzles, heat detectors, and a manual selector switch. The heat detectors serve to actuate the Halon system; a predischarge alarm is sounded first, followed by a time-delayed discharge of Halon. The manual selector switch is used to designate which of the two banks of Halon cylinders in each system will discharge automatically. Halon cylinders can be discharged manually at the hand switch location or at the cylinder locations. The unused bank of cylinders can be used to provide a supplemental discharge of Halon by manually actuating the release.
9A.2.10 WATER CURTAIN SYSTEMS Two types of water curtain suppression systems are provided in the plant: (a) systems that subdivide certain fire areas into two zones, and (b) systems that protect floor slab openings associated with equipment hatchways in the reactor enclosures.
Water curtain systems that serve to subdivide fire areas are provided at el 217', el 253', and el 313' in the reactor enclosures. Each water curtain system consists of an OS&Y gate valve, a deluge valve, a local pull station, piping, and open sprinkler heads. Each water curtain system is actuated manually, using the local pull station to open the deluge valve. The pull station is located inside a stairwell near the location of the water curtain. Actuation of a water curtain system is sounded throughout the plant by a coded alarm. Operation of the system is terminated manually by shutting the OS&Y gate valve, which is located near the stairwell in which the pull station is located.
Each of the water curtain systems is designed to achieve a discharge density of 0.3 gpm/ft2 at floor level. This is accomplished through the use of open sprinkler heads arranged in a linear array across the top of the water curtain location. In addition, sprinkler heads discharging horizontally inward from the sides of the water curtain are provided where necessary to achieve the design discharge density.
Water curtain systems that serve to protect the equipment hatchways in the reactor enclosures are designed similarly to the water curtain systems described above. The equipment hatchways are located in the southeast corner of the Unit 1 reactor enclosure and the southwest corner of the Unit 2 reactor enclosure. Each hatchway consists of openings in the concrete floor slabs at el 253', el 283', and el 313', with the openings arranged above one another. The opening in each slab is protected by an individual water curtain system having its distribution piping located at the underside of the slab and arranged around the perimeter of the opening. Each water curtain system is actuated manually, using a local pull station to open the deluge valve. The pull station is installed inside the stairwell near the location of the water curtain. In addition to the pull station, each water curtain system can be actuated by use of an emergency trip valve located near the system's local control panel.
9A.2.11 PORTABLE FIRE EXTINGUISHERS APPENDIX 9A 9A-8 REV. 17, SEPTEMBER 2014
LGS UFSAR Portable fire extinguishers, using extinguishing agents compatible with the combustible material in the area in which they are located, are provided throughout the plant.
9A.2.12 FIRE AND SMOKE DETECTION SYSTEM The fire and smoke detection system is in compliance with NFPA 72A (1979). The system also complies with the requirements of NFPA 72D (1975), with the following exceptions and clarifications:
- a. No device is provided for permanently recording incoming signals with the date and time of receipt. (The logging of fire events by a device for permanently recording incoming signals is not needed, because plant operating procedures will require the operator on duty in the control room to update the plant log book with the date and time of alarms from the fire detection system and of initiation of any fire suppression system.)
- b. Operation and supervision of the system is not the primary function of the operators. (The control room operators are responsible for monitoring and supervision of all plant systems, including the fire detection and fire suppression systems.)
- c. The locations of early warning fire and smoke detectors were established under the direction of a registered fire protection engineer. (The locations of fire and smoke detectors are in compliance with the guidance of NFPA 72E, with the clarification that ionization-type detectors in certain areas of the plant are located in accordance with subsections 4-3.1 and 4-3.1.1 of NFPA 72E. These subsections allow detector location to be determined based on engineering judgement considering ceiling shape, ceiling surfaces, ceiling height, configuration of contents, combustible characteristics, and ventilation. In areas where concrete floor slabs are supported by structural steel beams, the diffusion of ionized particles throughout the compartment volume during the incipient stage of the fire will negate the effect of beam depth and result in an appropriate level of detection capability.
NFPA 72E (1978) requires functional testing of smoke detectors semiannually.
Functional testing of smoke detectors at Limerick is performed in accordance with the Technical Requirements Manual.
- e. In fire area 2, the smoke detection system is upgraded to NFPA 72, 1996, Chapter 5 for detector location and spacing.
- f. In fire area 98, the smoke detection system above the ASD System is upgraded to NFPA 72, 2010, Chapter 17 for detector location and spacing.
- g. In fire area 25, the locations of in-cabinet and under floor smoke detectors accepted was by the NRC in their review of GE NEDO-10466A Power Generation Control Complex Design Criteria and Safety Evaluation.
- h. In fire area 111, the smoke detection system above the ASD System is upgraded to NFPA 72, 2010, Chapter 17 for detector location and spacing.
APPENDIX 9A 9A-9 REV. 17, SEPTEMBER 2014
LGS UFSAR Fire and smoke monitoring, detection, and alarm are accomplished by installing smoke detectors and/or heat-responsive detectors in areas where fire potential exists. Fire and smoke detection systems for annunciation are separate from fire detection systems for actuation of fire extinguishing systems, except for the 13kV Switchgear Area (Fire Area 2). The smoke detection system in the 13 kV Switchgear Area (Fire Area 2) provides early warning notification while also providing an input signal to the double interlock preaction system that provides localized protection.
Although the fire and smoke detection system is primarily a Class B system, certain portions of it are designed as Class A. The local fire detection panels in safety-related areas of the plant (control structure, reactor enclosures, and diesel generator enclosures) and in the Unit 2 turbine enclosure are Class A. All other local fire detection panels are Class B. The detector systems and local panels for the Halon system in the raised flooring of the auxiliary equipment room and the carbon dioxide system in the cable spreading room are Class A. The heat detector wiring and local panel wiring for all sprinkler systems is Class B. Transmitter circuits from all local panels (both Class A and Class B) back to the fire protection alarm panel near the control room are Class B. Circuits in the fire protection alarm panel (00C926) are Class B.
Both the Class A and Class B portions of the fire and smoke detection system are electrically supervised to detect circuit breaks, ground faults, and power failure. Class A portions of the system have the capability to detect fire and smoke concurrent with a single break or single ground in the detection circuit; Class B portions of the system do not have this capability. Class A detection circuits utilize a four-wire system, whereas Class B detection circuits utilize a two-wire system with end-of-line resistor. Functional testing of the supervised circuits is done annually in accordance with NFPA Standard 72E(1990).
Annunciator circuits from the local fire suppression system panels to fire protection alarm panel 00C926 and from 00C926 to control room fire protection annunciator 0BC850 are not electrically supervised. Detection of smoke or fire is registered visually on a window of control room fire protection annunciator 0AC850 (identifying the location of the fire) and is sounded throughout the plant by a coded alarm. Trouble conditions (circuit breaks, ground faults, and power failures) in the fire and smoke detection system are registered by an audible alarm in the control room and by visual indication on the affected local fire detection panel as well as on a common window of control room fire protection annunciator 00C650. Actuation of any fire suppression system is sounded throughout the plant by a coded alarm. Trouble conditions in any fire suppression system are registered by an audible alarm in the control room and by visual indication on panel 00C926 and a common window of control room fire protection annunciator 0BC850.
APPENDIX 9A 9A-10 REV. 17, SEPTEMBER 2014
LGS UFSAR 9A.3 COMPARISON BETWEEN LGS FIRE PROTECTION PROGRAM AND NRC GUIDELINE DOCUMENTS 9A.3.1 NRC BRANCH TECHNICAL POSITION CMEB 9.5-1 The purpose of this section is to compare the fire protection provisions of LGS Units 1 and 2 with the guidelines in BTP CMEB 9.5-1.
To identify areas of potential impact and to facilitate comparison, a matrix addressing each guideline of the BTP and relating to the plant systems, equipment, and components, is included as Section 9A.3.1.1. The matrix has extracted all suggested guidelines from the BTP and given each an item number, 1 through 255. Each item has condensed a particular guideline and makes reference to the section in the BTP where that guideline can be found. The general degree of conformance to the guideline is indicated in the COMPARISON column, using codes defined as follows:
C - indicates conformance to the guideline or conformance to its intent.
Substantiating statements may be included as part of the matrix or in Section 9A.3.1.2.
AC - indicates conformance to the guidelines by alternate means or methods.
The manner of conformance is included in the matrix or discussed in Section 9A.3.1.2.
NC - indicates that the plant is not in conformance and no design changes are planned. The basis for nonconformance to the guideline is included in the matrix or discussed in Section 9A.3.1.2.
NA - indicates that the guideline is not applicable to LGS Units 1 and 2.
Substantiating statements are included as part of the matrix in Section 9A.3.1.1.
In the REMARKS column, additional information is provided to explain or expand on the degree of conformance. Alternatively, reference may be made to Section 9A.3.1.2 (or other sections in this report) for a more detailed discussion. The item numbers in Section 9A.3.1.2 correspond to those in Section 9A.3.1.1.
9A.3.1.1 Detailed Comparison to Branch Technical Position CMEB 9.5-1 Specific items in the following table identify compliance to specific National Fire Protection Association (NFPA) codes (or standards) for the design, installation, and maintenance of fire protection systems. The fire protection systems at Limerick Generating Station were originally designed and installed using the criteria found in the NFPA codes in order to comply with NRC guidance. NFPA codes provide guidance for the requirements for the performance of fire protection systems. This guidance provides reasonable assurance that the fire protection systems installed at Limerick Generating Station will provide timely warning and adequate suppression for the purpose of life safety and property protection.
APPENDIX 9A 9A-11 REV. 18, SEPTEMBER 2016
LGS UFSAR The Fire Protection Program at Limerick Generating Station is based on a defense-in-depth philosophy with numerous barriers in place to ensure adequate protection of plant structures, systems and components as well as the health and safety of the public in the event of a postulated fire occurring. It is recognized that there are situations in the plant where verbatim compliance with all aspects of the NFPA codes have not been satisfied. When the fire protection systems were initially designed and installed, the NFPA codes were considered guidance documents, not verbatim compliance documents. Through the use of qualified designers, engineers, and installation personnel, alternative plant configurations may have been employed to satisfy the intent of the NFPA requirements.
Deviations that could potentially affect system performance are documented in the design record for the plant. Minor deviations, while considered during initial design and installation, are not necessarily documented in the design record for the plant.
APPENDIX 9A 9A-12 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Fire Protection Program
- 1. The fire protection program should be under the direction C.1.a(1) C of an individual who has been delegated authority commensurate with the responsibilities of the position and who has available staff personnel knowledgeable in both fire protection and nuclear safety.
- 2. The fire protection program should extend the concept C.1.a(2) C of defense-in-depth to fire protection in fire areas important to safety, with the following objectives:
to prevent fires from starting; to detect rapidly, control, and extinguish promptly those fires that do occur; to provide protection for structures, systems, and components important to safety so that a fire that is not promptly extinguished by the fire suppression activities will not prevent the safe shutdown of the plant.
- 3. Responsibility for the overall fire protection program C.1.a(3) C should be assigned to a person who has management control over all organizations involved in fire protection activities. Formulation and assurance of program implementation may be delegated to a staff composed of personnel prepared by training and experience in fire protection and personnel prepared by training and experience in nuclear plant safety to provide a balanced approach in directing the fire protection program for the nuclear power plant.
- 4. The staff should be responsible for: C.1.a(3) C (a) Fire protection program requirements, including consideration of potential hazards associated with postulated fires, with knowledge of building layout and systems design.
(b) Post-fire shutdown capability.
(c) Design, maintenance, surveillance, and quality assurance of all fire protection features (e.g.,
detection systems, suppression systems, barriers, dampers, doors, penetration seals, and fire brigade equipment).
(d) Fire prevention activities (administrative controls and training).
(e) Fire brigade organization and training.
(f) Prefire planning.
- 5. The organizational responsibilities and lines of C.1.a(4) C communication pertaining to fire protection should be defined through the use of organizational charts and functional description.
APPENDIX 9A 9A-13 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 6. Personnel qualification requirements for fire protection C.1.a(5) C See Section 3.1.2 engineer reporting to the position responsible for formulation and implementation of the fire protection program.
- 7. The fire brigade members qualifications should include C.1.a(5)(b) C a physical examination for performing strenuous activity, and the training described in Position C.3.d.
- 8. The personnel responsible for the maintenance and C.1.a(5)(c) C testing of the fire protection systems should be qualified by training and experience for such work.
- 9. The personnel responsible for the training of the fire C.1.a(5)(d) C brigade should be qualified by training and experience for such work.
- 10. The following NFPA publications should be used for C.1.a(6) C guidance to develop the fire protection program; No. 4, No. 4A, No. 6, No. 7, No. 8, No. 27.
- 11. On sites where there is an operating reactor and C.1.a(7) C construction of modification of other units is underway, the superintendent of the operating plant should have a lead responsibility for site fire protection.
Fire Hazards Analysis
- 12. The fire hazards analysis should demonstrate that the C.1.b C See Sections 9A.4 and 9A.5.
plant will maintain the ability to perform safe shutdown functions and minimize radioactive releases to the environment in the event of a fire.
- 13. The fire hazards analysis should be performed by fire C.1.b C protection and reactor systems engineers to (1) consider potential in situ and transient fire hazards: (2) determine the consequences of a fire in any location in the plant; and (3) specify measures for fire prevention, detection, suppression, and containment.
- 14. Fires involving facilities shared between units should C.1.b C Fires are postulated to occur in structures be considered. such as the control structure and the spray pond pump structure that are common to both reactor units.
- 15. Fires due to man-made site-related events that have a C.1.b C See Section 9A.3.1.2.
reasonable probability of occurring and affecting more than one reactor unit should be considered.
APPENDIX 9A 9A-14 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 16. Establishment of three levels of fire damage limits C.1.b C according to safety function (hot shutdown; cold shutdown; design basis accidents.)
- 17. The fire hazards analysis should separately identify C.1.b C hazards and provide appropriate protection in locations where safety-related losses can occur.
Fire Suppression System Design Basis
- 18. Total reliance should not be placed on a single fire C.1.c(1) C All automatic fire suppression systems are suppression system. Backup fire suppression capability backed up by two methods of manual should be provided. extinguishment (hose stations and portable extinguishers).
- 19. A single active failure or a crack in a moderate energy C.1.c(2) C See Section 9A.3.1.2.
line in the fire suppression system should not impair both the primary and backup fire suppression capability.
- 20. The fire suppression system should be capable of C.1.c(3) NC See item 155.
delivering water to manual hose stations located within hose reach of areas containing equipment required for safe shutdown following an SSE.
- 21. The fire protection systems should retain their original C.1.c(4) C See Section 9A.3.1.2 design capability for natural phenomena of less severity and greater frequency than the most severe natural phenomena.
- 22. The fire protection systems should retain their original C.1.c(4) NC See Section 9A.3.1.2 design capability for potential man-made site-related events that have a reasonable probability of occurring at a specific plant site.
- 23. The effects of lightning strikes should be included in C.1.c(4) C Lightning protection is provided per NFPA the overall plant fire protection program. No. 78
- 24. The consequences of inadvertent operation or of a crack C.1.c(5) C See Section 9A.3.1.2.
in a moderate energy line in the fire suppression system should meet the guidelines specified for moderate energy systems outside containment in SRP section 3.6.1.
Alternative or Dedicated Shutdown
- 25. Alternative or dedicated shutdown capability should be C.1.d C See item 20 of Section 9A.3.2.2.
provided where the protection of systems whose functions are required for a safe shutdown is not provided by established fire suppression methods or by Position C.5.b.
APPENDIX 9A 9A-15 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Im plementation of Fire Protection Programs
- 26. The fire protection program for buildings storing new C.1.e(1) C The fire protection program for the new reactor fuel and for adjacent fire areas that could fuel area will be completed and fully affect the fuel storage area should be fully operational operational before fuel is received at the before fuel is received at the site. Site.
- 27. The fire protection program for an entire reactor unit C.1.e(2) C should be fully operational prior to initial fuel loading in that reactor unit.
- 28. Special considerations for the fire protection program C.1.e(3) C See Section 9A.3.1.2.
on reactor sites where there is an operating reactor and construction or modification of other units is under way.
Administrative Controls
- 29. Establishment of administrative controls to maintain the C.2 C performance of the fire protection system and personnel.
Fire Brigade
- 30. The guidance in Regulatory Guide 1.101 should be C.3.a C followed as applicable.
- 31. Establishment of site brigade: minimum number of fire C.3.b C brigade members on each shift; qualification of fire brigade members; competence of brigade leader.
- 32. The minimum equipment provided for the brigade should C.3.c C consists of turnout coats, boots, gloves, hard hats, emergency communications equipment, portable ventilation equipment, and portable extinguishers.
- 33. Self-contained breathing apparatus using full-face C.3.c C See Section 9A.3.1.2.
positive-pressure masks approved by NIOSH (National Institute for Occupational Safety and Healthapproval formerly given by the U.S. Bureau of Mines) should be provided for fire brigade, damage control, and control room personnel. At least 10 masks shall be available for fire brigade personnel. Control room personnel may be furnished breathing air by a manifold system piped from a storage reservoir if practical. Service or rated operating life shall be a minimum of one-half hour for the self contained units.
APPENDIX 9A 9A-16 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS At least two extra air bottles should be located onsite for each self contained breathing unit. In addition, an onsite 6-hour supply of reserve air should be provided and arranged to permit quick and complete replenishment of exhausted supply air bottles as they are returned. If compressors are used as a source of breathing air, only units approved for breathing air shall be used; compressors shall be operable assuming a loss of offsite power. Special care must be taken to locate the compressor in areas free of dust and contaminants.
- 34. Recommendations for the fire brigade training program. C.3.d AC See Section 9A.3.1.2.
Quality Assurance Program
- 35. Establishment of quality assurance programs for the fire C.4 AC See Section 9A.3.1.2.
protection systems for safety- related areas; identification of specific criteria for QA programs.
Building Design
- 36. Fire barriers with a minimum rating of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> should C.5.a(1)(a) C Structures housing safety-related systems be provided to separate safety-related systems from any are separated from nonsafety- related potential fires in nonsafety-related areas. structures by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls.
- 37. Fire barriers with a minimum rating of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> should C.5.a(1)(b) AC See Section 9A.3.1.2.
be provided to separate redundant divisions of safety-related systems from each other.
- 38. Fire barriers with a minimum rating of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> should C.5.a(1)(c) C Fire barriers rated for 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> are be provided to separate individual units on a multiunit provided to separate Unit 1 structures from site. Unit 2 structures. Those structures that are common to both reactor units (such as the control structure and the central portion of the turbine enclosure) are separated form the adjacent structures of both reactor enclosures by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers.
- 39. Fire barriers should be provided within a single safety C.5.a(2) AC See Section 9A.3.1.2.
division to separate components or cabling that present a fire hazard to other safety-related components.
- 40. Openings through fire barriers for pipe, conduit, and C.5.a(3) AC See Section 9A.3.1.2.
cable trays which separate fire areas should be sealed or closed to provide a fire resistance rating equal to that required of the barrier.
APPENDIX 9A 9A-17 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 41. Recommendations for internal sealing of conduits C.5.a(3) AC See Section 9A.3.1.2 penetrating fire barriers.
- 42. Fire barrier penetrations that must maintain C.5.a(3) C Fire-rated penetration seals that are also environmental isolation or pressure differentials should required to perform other barrier functions be qualified by test. (such as maintaining a pressure differential) are qualified by test for all the intended functions. The fire barrier function of a penetration seal is not required to be performed simultaneously with other barrier functions.
- 43. Penetration designs should utilize only noncombustible C.5.a(3) AC See Section 9A.3.1.2.
materials.
- 44. The penetration qualification tests should use the C.5.a(3) C The time-temperature exposure curve used in time-temperature exposure curve specified by ASTM E-119. qualification tests for penetration seals is a specified by ASTM E-119-73.
- 45. Acceptance criteria for penetration qualification tests. C.5.a(3) AC See Section 9A.3.1.2.
- 46. Penetration openings for ventilation systems should be C.5.a(4) AC See Section 9A.3.1.2.
protected by fire dampers having a rating equivalent to that required of the barrier.
- 47. Flexible air duct couplings in ventilation and filter C.5.a(4) C systems should be noncombustible.
- 48. Door openings in fire barriers should be protected with C.5.a(5) AC See Section 9A.3.1.2.
equivalently rated doors, frames, and hardware that have been tested and approved by a nationally recognized laboratory.
- 49. Fire doors should be self-closing or provided with C.5.a(5) AC See Item 40 of Section 9A.3.2.2.
closing mechanisms.
- 50. Fire doors should be inspected semiannually to verify C.5.a(5) AC See Item 41 of Section 9A.3.2.1.
that automatic hold open, release, and closing mechanisms and latches are operable.
- 51. Alternative means for ensuring that fire doors protect C.5.a(5) C See Item 42 of Section 9A.3.2.2.
the door opening as required in case of fire.
- 52. The fire brigade leader should have ready access to keys C.5.a(5) C for any locked fire doors.
- 53. Areas protected by automatic total flooding gas C.5.a(5) C See Item 44 of Section 9A.3.2.1.
suppression systems should have electrically supervised self-closing fire doors or should satisfy option (a) above.
APPENDIX 9A 9A-18 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 54. Personnel access routes and escape routes should be C.5.a(6) C All fire areas are provided with personnel provided for each fire area. access routes and escape routes.
- 55. Stairwells serving as escape routes, access routes for C.5.a(6) C Stairwells of the type described in the fire fighting, or access routes to areas containing guideline are each enclosed by a 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> equipment necessary for safe shutdown should be enclosed rated envelope consisting or either in masonry or concrete towers with a minimum fire rating reinforced concrete or concrete unit of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and self-closing Class B fire doors. masonry walls with a minimum thickness of 8 inches. Each door opening that is a part of this envelope is provided with a UL Class B fire door. All penetrations through the walls of the envelope are sealed using penetration seal details that are qualified for use in 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers.
- 56. Fire exit routes should be clearly marked. C.5.a(7) C
- 57. Each cable spreading room should contain only one C.5.a(8) NC The cable spreading room for each reactor redundant safety division. unit contains all four divisions of safety-related cabling. Raceways containing the different divisions of cabling are separated from each other in accordance with Regulatory Guide 1.75. Cabling associated with the remote shutdown panel is not routed through the cable spreading room.
- 58. Cable spreading rooms should be separated from each C.5.a(8) C See Section 9A.3.1.2.
other and from other areas of the plant by barriers having a minimum fire resistance of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />.
- 59. Interior wall and structural components, thermal C.5.a(9) AC See Section 9A.3.1.2.
insulation materials, radiation shielding materials, and soundproofing should be noncombustible.
- 60. Interior finishes should be noncombustible. C.5.a(9) AC See Section 9A.3.1.2.
61 Metal deck roof construction should be non-combustible C.5.a(10) C See Section 9A.3.1.2.
and listed as acceptable for fire in the UL Building Materials Directory, or listed as Class 1 in the Factory Mutual Approval Guide.
- 62. Suspended ceilings and their supports should be of C.5.a(11) C See Section 9A.3.1.2.
noncombustible construction.
- 63. Concealed spaces should be devoid of combustibles except C.5.a(11) AC See Section 9A.3.1.2.
as noted in Position C.6.b.
APPENDIX 9A 9A-19 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 64. Transformers installed inside fire areas containing C.5.a(12) C All indoor transformers are either air safety-related systems should be of the dry-t ype or cooled, dry-t ype, or cooled by insulated and cooled with noncombustible liquid. noncombustible gases.
- 65. Outdoor oil-filled transformers should have oil spill C.5.a(13) C See Section 9A.3.1.2.
confinement features or drainage away from the buildings.
- 66. Outdoor oil-filled transformers should be located at C.5.a(13) AC See Section 9A.3.1.2.
least 50 feet distant from the building, or building walls within 50 feet of oil-filled transformers should be without openings and have a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire resistance rating.
- 67. Floor drains sized to remove expected fire fighting C.5.a(14) AC See Section 9A.3.1.2 water flow without flooding safety-related equipment should be provided in areas where fixed water fire suppression systems are installed.
- 68. Floor drains should be provided in areas where hand hose C.5.a(14) AC See Section 9A.3.1.2.
lines may be used if such fire fighting water could cause unacceptable damage to safety-related equipment.
- 69. W here gas suppression systems are installed, the drains C.5.a(14) C The capacity of the carbon dioxide storage should be provided with adequate seals, or the gas tank is sufficient to compensate for losses suppression system should be sized to compensate for through the floor drains in the cable the loss of the suppression agent through the drains. spreading rooms.
- 70. Drains in areas containing combustible liquids should C.5.a(14) C See Section 9A.3.1.2.
have provisions for preventing the backflow of combustible liquids to safety- related areas through the interconnected drain systems.
- 71. W ater drainage from areas that may contain C.5.a(14) C Potentially radioactive liquid wastes are radioactivity should be collected, sampled, and collected and monitored prior to discharge.
analyzed before discharge to the environment.
Safe Shutdown Capability
- 72. Fire damage should be limited so that one train of C.5.b(1) C systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergency control station is free of fire damage.
- 73. Fire damage should be limited so that one train of C.5.b(1) C systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergency control station can be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
APPENDIX 9A 9A-20 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 74. Alternative means of ensuring that one train of systems C.5.b(2) AC See Item 18 of Section 9A.3.2.2.
necessary to achieve and maintain hot shutdown is free of fire damage.
- 75. Provision of alternative or dedicated shutdown C.5.b(3) C See Item 20 of Section 9A.3.2.2 capability in certain fire areas.
- 76. Alternative or Dedication Shutdown Capability C.5.c C See Items 25 through 36 of Section 9A.3.2.
Control of Combustibles
- 77. Safety-related systems should be separated from C.5.d(1) C To the maximum extent possible, significant combustible materials where possible; where not concentrations of combustible materials are possible, special protection should be provided to located outside structures containing prevent a fire from defeating safety system safety-related components. In those cases function. for which this is not possible, such as the standby diesel generator fuel oil day tanks, special fire protection consisting of automatic fire suppression systems and/or construction capable of withstanding a fire is provided.
- 78. Bulk gas storage (compressed or cryogenic) should not C.5.d(2) NC See Section 9A.3.1.2.
be permitted inside structures housing safety-related equipment. Flammable gases should be stored outdoors or in separate detached buildings.
- 79. High pressure gas storage containers should be located C.5.d(2) NC See Section 9A.3.1.2.
with the long axis parallel to building walls.
- 80. Use of compressed gases inside buildings should be C.5.d(2) C See Section 9A.3.1.2.
controlled.
- 81. The use of plastic materials should be minimized. C.5.d(3) C See Section 9A.3.1.2.
Halogenated plastics such as PVC and neoprene should be used only when substitute noncombustible materials are not available.
- 82. Storage of flammable liquids should comply with NFPA C.5.d(4) C Liquid fuels are stored either in
- 30. aboveground tanks that have been provided with suitable fire barriers or in underground tanks.
- 83. Hydrogen lines in safety-related areas should be either C.5.d(5) C Hydrogen lines in safety-related areas are designed to seismic Class I requirements, or sleeved, designed to seismic Class I requirements.
or equipped with excess flow valves.
APPENDIX 9A 9A-21 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Electrical Cable Construction, Cable Trays, and Cable Penetrations
- 84. Only metal should be used for cable trays. C.5.e(1) C Cable trays are of all-metal construction.
- 85. Only metallic tubing should be used for conduit. C.5.e(1) NC See Section 9A.3.1.2.
Thin-wall metallic tubing should not be used.
- 86. Flexible metallic tubing should only be used in short C.5.e(1) C Flexible metallic tubing used at raceway lengths to connect components to equipment. connections to components is limited to 5 feet in length.
- 87. Other raceways should be made of noncombustible C.5.e(2) C Gutter-t ype raceways are of all-metal materials. construction.
- 88. Redundant safety-related cable systems outside the cable C.5.e(2) AC See Section 9A.3.1.2.
spreading room should be separated from each other and from potential fire exposure hazards in nonsafety-related areas by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers.
- 89. These cable trays should be provided with continuous C.5.e(2) NC See Section 9A.3.1.2.
line-t ype heat detectors.
- 90. Cables should be designed to allow wetting down with C.5.e(2) C Cable insulating systems include fire suppression water without electrical faulting. proprietary jacketing materials designed for wetting.
- 91. Redundant safety-related cable trays outside the cable C.5.e(2) C spreading room should be accessible for manual fire fighting. Manual hose stations and portable hand extinguishers should be provided.
- 92. Safety-related cable trays of a single division that are C.5.e(2) AC See Section 9A.3.1.2.
separated from redundant divisions by a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barrier and are accessible for manual fire fighting should be protected from the effects of a potential exposure fire by providing automatic water suppression.
- 93. Safety-related cable trays that are not accessible for C.5.e(2) NA Safety-related cable trays are not routed manual fire fighting should be protected by an automatic through areas that are inaccessible for water systems. Manual fire fighting.
- 94. Safety-related cable trays that are not separated from C.5.e(2) AC See Section 9A.3.1.2 and Item 92 above.
redundant divisions by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers should be protected by automatic water suppression systems.
- 95. The capability to achieve safe shutdown considering the C.5.e(2) C See Section 9A.5.
effects of a fire involving fixed and transient combustibles should be evaluated with and without actuation of the automatic suppression system.
APPENDIX 9A 9A-22 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS
- 96. Electric cable construction should pass the flame test C.5.e(3) AC See Section 9A.3.1.2.
in IEEE 383.
- 97. Cable raceways should be used only for cables. C.5.e(4) C
- 98. Miscellaneous storage and piping for combustible liquids C.5.e(5) C See Section 9A.3.1.2.
or gases should not create a potential exposure hazard to safety-related systems.
Ventilation
- 99. Smoke and corrosive gases should be discharged directly C.5.f(1) AC See Section 9A.3.1.2.
outside to an area that will not affect safety-related plant areas.
100. To facilitate manual fire fighting, separate smoke and C.5.f(1) NC See Section 9A.3.1.2.
heat vents should be provided in certain areas.
101. Release of smoke and gases containing radioactive C.5.f(2) C See Section 9A.3.1.2.
materials to the environment should be monitored.
102. Any ventilation system designed to exhaust potentially C.5.f(2) AC See Section 9A.3.1.2.
radioactive smoke or gases should be evaluated to ensure that inadvertent operation or single failures will not violate the radiologically controlled areas of the plant.
103. The power supply and controls for mechanical C.5.f(3) AC See Section 9A.3.1.2.
ventilation systems should be run outside the fire areas served by the system.
104. Engineered safety feature filters should be protected C.5.f(4) C See Section 9A.3.1.2.
in accordance with the guidelines of Regulatory Guide 1.52.
105. Air intakes for ventilation systems serving areas C.5.f(5) C Air intakes serving areas which contain containing safety-related equipment should be located safety-related equipment are remote from remote from the exhaust air outlets and smoke vents of exhaust and smoke outlets of other fire other fire areas. areas.
106. Stairwells should be designed to minimize smoke C.5.f(6) C Stair towers are provided with self-closing infiltration during a fire. doors, which will minimize smoke infiltration during a fire.
107. W here total flooding gas extinguishing systems are C.5.f(7) C See Section 9A.3.1.2.
used, ventilation dampers, should be controlled in accordance with NFPA 12 and NFPA 12A.
APPENDIX 9A 9A-23 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Lighting and Communication 108. Fixed self-contained lighting units with individual 8 C.5.g(1) AC See Item 108 of Section 9A.3.1.2, and hour battery power supplies should be provided in areas Item 23 of Section 9A.3.2.2.
that must be manned for safe shutdown and for access and egress routes to and from all fire areas.
109. Sealed beam battery-powered portable hand lights should C.5.g(2) C Portable lights are provided be provided for emergency use.
110. Fixed emergency communications independent of the C.5.g(3) AC See Section 9A.3.1.2.
normal plant communication system should be installed at preselected stations.
111. A portable radio communications system should be C.5.g(4) AC See Section 9A.3.1.2.
provided for use by the fire brigade and other operations personnel required to achieve safe plant shutdown.
Fire Detection 112. Detection systems should be provided for all areas that C.6.a(1) AC See Section 9A.3.1.2.
contain or present a fire exposure to safety-related equipment.
113. Fire detection systems should comply with the C.6.a(2) AC The fire and smoke detection system is requirements of Class A systems as defined in NFPA 72D partially Class A and partially Class B, as and Class I circuits as defined in NFPA 70. described in Section 9A.2.12. (Class A and Class B systems are defined in the 1975 edition of NFPA 72D.)
114. Fire detectors should be selected and installed in C.6.a(3) C See Section 9A.2.12.
accordance with NFPA 72E.
115. Testing of pulsed line-type heat detectors should C.6.a(3) NA Pulsed line-t ype detectors are not used in demonstrate that the frequencies used will not affect the plant.
the actuation of protective relays in other plant systems.
116. Fire detection systems should give audible and visual C.6.a(4) C alarm and annunciation in the control room.
APPENDIX 9A 9A-24 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 117. W here zoned detection systems are used in a given fire C.6.a(4) C A coding system has been established for area, local means should be provided to identify which all fire alarms in the plant so that the zone has actuated. location of a fire can be determined from the sound of the alarm. A list of these codes and their corresponding detection areas will be posted at each fire alarm pull station.
118. Local audible alarms should sound in the fire area. C.6.a(4) C Fire alarms are annunciated throughout the plant, as well as in the local area in which a fire detector has been actuated.
119. Fire alarms should be distinctive and unique so they C.6.a(5) C will not be confused with any other plant system alarms.
120. Primary and secondary power supplies which satisfies the C.6.a(6) AC See Section 9A.3.1.2.
provisions of section 2220 of NFPA 72D should be provided for the fire detection system and for electrically operated control valves for automatic suppression systems.
Fire Protection W ater Supply Systems 121. An underground yard fire main loop should be installed C.6.b(1) C An underground yard fire main loop has been to furnish anticipated water requirements. provided and is in compliance with NFPA 24.
122. T ype of pipe and water treatment should be design C.6.b(1) C The yard fire main loop utilizes consideration with tuberculation as one of the cement-lined cast iron pipe to reduce parameters. tuberculation. W ater used fire protection service meets the requirements of NFPA 22 and does not require treatment.
123. Means of inspecting and flushing the systems should be C.6.b(1) C Following its installation, the yard fire provided. main loop was flushed and tested in accordance with NFPA 24 (1973), sections 98 and 99. Flushing of the loop is accomplished through the use of sectional control valves to direct the flow and yard hydrants to serve as discharge points.
124. Approved visually indicating sectional control valves C.6.b(2) C Postindicator valves provided for should be provided to isolate portions of the main for sectionalized control and isolation of maintenance or repair. portions of the yard fire main loop.
125 Valves should be installed to permit isolation of C.6.b(3) C A key-operated gate valve with a curb box outside hydrants from the fire main for maintenance or is provided in each lateral from the yard repair without interrupting the water supply to fire main loop to a fire hydrant.
automatic or manual fire suppression system.
APPENDIX 9A 9A-25 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 126. The fire main system piping should be separate from C.6.b(4) C See Section 9A.3.1.2.
service or sanitary water system piping.
127. A common yard fire main loop may serve multiunit nuclear C.6.b(5) C The yard fire main loop is common to both power plant sites if cross-connected between units. reactor units. The loop is cross-connected Sectional control valves should permit maintaining between units and provided with sectional independence of the loop around each unit. control valves.
128. A sufficient number of pumps should be provided to C.6.b(6) C Two fire pumps (one diesel-driven and one ensure that 100% capacity will be available assuming electric motor-driven) are provided, each failure of the largest pump or a LOOP. capable of supplying 100% of the systems flow requirements.
129. Individual fire pump connections to the yard fire main C.6.b(6) C loop should be separated with sectionalizing valves between connections.
130. Each pump and its driver and controls should be C.6.b(60 C separated from the remaining fire pumps by a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire wall.
131. The fuel for the diesel fire pump should be separated C.6.b(6) C The diesel oil day tank is located in a so that it does not provide a fire source exposing curbed area within the diesel-driven fire safety-related equipment. pump compartment. This compartment is located in the circulating water pump structure, which is separated from all structures containing safety-related equipment.
132. Alarms indicating pump running, driver availability, C.6.b(6) AC Pump running, driver availability, and failure to start, and low fire main pressure should be failure to start are annunciated in the provided in the control room. control room. Fire main pressure is indicated in the control room but not annunciated.
133. The fire pump installation should conform to NFPA 20. C.6.b(6) C 134. Outside manual hose installation should be sufficient C.6.b(7) AC Hydrants are space between 250 rod and 300 to provide an effective hose stream to any onsite feet apart along the fire main loop.
location where fixed or transient combustibles could jeopardize safety-related equipment. Hydrants should be installed approximately every 250 feet on the yard main system.
135. Recommendations for hose houses and hose carts. C.6.b(7) AC See Section 9A.3.1.2.
136. Threads compatible with those used by local fire C.6.b(8) C departments should be provided on all hydrants, hose couplings, and standpipe risers.
APPENDIX 9A 9A-26 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 137. Two separate, reliable freshwater supplies should be C.6.b(9) C The cooling tower basins of the Unit 1 and provided. Unit 2 circulating water systems are used as the two sources of water for the fire pumps.
138. Recommendations for tanks used to supply fire protection C.6.b(9) NA Tanks are not utilized for fire protection water. W ater supply.
139. Recommendations for tanks used to supply fire protection C.6.b(10) NA Tanks are not utilized for fire protection water. water supply.
140. The fire water supply should be based on the largest C.6.b(11) C See Section 9A.3.1.2.
expected flow rate for a period of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, but not less than 300,000 gallons.
141. The fire water supply should be capable of delivering C.6.b(11) C In the event that a portion of the yard the design demand over the longest route of the water fire main loop is valved out of service, supply system. the fire pumps are capable of delivering the design demand over the longest route of the water supply system.
142. Recommendations for freshwater lakes or ponds used to C.6.b(12) NA Lakes or ponds are not utilized for fire supply fire protection water. protection water supply.
143. Recommendations concerning use of other water systems C.6.b(13) NA The fire protection system and the ultimate for fire protection and the ultimate heat sink. heat sink do not share a common water supply.
144. Recommendations concerning use of other water systems C.6.b(14) AC See Section 9A.3.1.2.
as the source of fire protection water.
145. Recommendations concerning connection of sprinkler C.6.c(1) C See Item 19.
systems and manual hose station standpipes to the yard fire main loop.
146. Each sprinkler and standpipe system should be equipped C.6.c(1) AC See Section 9A.3.1.2.
with OS&Y gate valve or other approved shutoff valve and water flow alarm.
147. Safety-related equipment should be protected from C.6.c(1) AC See Section 9A.3.1.2.
sprinkler discharge if such discharge could result in unacceptable damage to the equipment.
148. Control and sectionalizing valves in the fire water C.6.c(2) C See Section 9A.3.1.2.
systems should be electrically supervised (with indication in the control room) or administratively controlled.
149. All valves in the fire protection systems should be C.6.c(2) C periodically checked to verify position.
APPENDIX 9A 9A-27 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 150. Fixed water extinguishing systems should conform to C.6.c(3) AC See Section 9A.3.1.2.
requirements of NFPA 13 and NFPA 15.
151. Recommendations for interior manual hose installations. C.6.c(4) NC See Section 9A.3.1.2.
152. Individual standpipes should be at least 4 inches in C.6.c(4) AC See Section 9A.3.1.2.
diameter for multiple hose connections and 2.5 inches in diameter for single hose connections.
153. Standpipe and hose station installations should follow C.6.c(4) C the requirements of NFPA 14.
154. Hose stations should be located as dictated by the fire C.6.c(4) C hazards analysis to facilitate access and use for fire fighting operations.
155. Recommendations concerning seismic design of standpipes C.6.c(4) NC See Section 9A.3.1.2.
and hose connections.
156. Recommendations concerning hose nozzle selection. C.6.c(5) C 157. Fire hose should be hydrostatically tested in C.6.c(6) C accordance with NFPA 1962. Hose stored in outside hose houses should be tested annually. Interior standpipe houses should be tested every 3 years.
158. Consideration of foam suppression systems for flammable C.6.c(7) C See Section 9A.3.1.2.
liquid fires.
Halon Suppression Systems 159. Halon fire extinguishing systems should comply with C.6.d C Design and installation of the Halon 1301 NFPA 12A ad NFPA 12B. Only UL-Listed or FM-approved system is in accordance with NFPA 12A.
agents should be used.
160. Provisions for locally disarming automatic Halon C.6.d NC Administrative controls do not exist systems should be key-locked and under administrative permitting disarming of the Halon system.
control. Automatic Halon systems should not be disarmed unless controls as described in Position C.2.j are provided.
161. Preventive maintenance and testing of the systems, C.6.d C including check-weighing of the Halon cylinders, should be done at least quarterly.
APPENDIX 9A 9A-28 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 162. Considerations for design of Halon suppression systems. C.6.d C See Section 9A.3.1.2.
Carbon Dioxide Suppression Systems 163. Carbon dioxide extinguishing systems should comply C.6.e C A Generic Letter 86-10 evaluation was the requirements of NFPA 12. performed for a NFPA code deviation with respect to the Unit 1 cable spreading room since the CO2 s ystem performance concentration met 50% for 15 minutes versus 20, as was the case for Unit 2.
164. Carbon dioxide extinguishing systems should comply with C.6.e C Although the total flooding carbon dioxide with a predischarge alarm system and a discharge delay system for the cable spreading rooms is to permit personnel egress. actuated manually, a predischarge alarm and discharge delay are provided. The fixed CO2 local application system for the Unit 1 and 2 turbine generator exciter bearing 11 and 12 is manually actuated. The coded fire alarm actuated by the heat and smoke detectors will alert plant personnel of a potential manually initiated CO2 discharge.
W hen either the timed discharge or the spurt discharge push-buttons are activated, rotating beacons and audible alarms located inside and outside the exciter enclosure are actuated to warn site personnel of the CO2 discharge.
165. Provisions for locally disarming automatic carbon C.6.e NA The total flooding carbon dioxide system dioxide systems should be key-locked and under that is provided for the cable spreading administrative control. The systems should not be rooms is actuated manually. A manual block disarmed unless controls as described in Position C.2.c valve for the generator exciter CO2 system are provided. (Unit 1 and 2) is provided and controlled by station procedures.
166. Considerations for design of carbon dioxide suppression C.6.e C See Section 9A.3.1.2.
systems.
167. Fire extinguishers should be provided in areas that C.6.f C See Section 9A.3.1.2 contain, or could present a fire exposure hazard to, safety-related equipment in accordance with NFPA 10.
168. Dry chemical extinguishers should be installed with due C.6.f C consideration given to possible adverse effects on safety-related equipment.
Primary and Secondary Containment 169. Fire protection for the primary and secondary C.7.a(1) C Fire hazards have been identified, as containment areas should be provided for hazards discussed in Section 9A.4, and fire identified by the fire hazards analysis. suppression system have been provided APPENDIX 9A 9A-29 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS accordingly. The types and locations of suppression systems are identified in Table 9A.1 and Figures 9A-4 through 9A-12.
170. Because of the general inaccessibility of primary C.7.a(1) NC See Section 9A.3.1.2.
containment during normal plant operation, protection should be provided by automatic fixed systems.
171. Operation of the fire protection systems should not C.7.a(1)(a) C The fire protection systems does not compromise the integrity of the containment or other penetrate the primary containment boundary.
safety-related systems. Also see Item 24.
172. Recommendations for protection of safety-related cables C.7.a(1)(b) NA The primary containment is inerted with and equipment inside noninerted containments. nitrogen during reactor operation.
173. Recommendations concerning fire detection inside the C.7.a(1)(c) NC See Section 9A.3.1.2.
174. For BW R drywells, standpipe and hose stations should be C.7.a(1)(d) C The hose reels located nearest the drywell placed outside the drywell with adequate lengths of entrances are equipped with a 100 foot hose, no longer than 100 feet, to reach any location length of fire hose. To supplement this inside the drywell with an effective hose stream. hose length, a hose station equipped with enough hose to reach any location within the drywell is located near each drywell entrance.
175. Recommendations for reactor coolant pump oil collection C.7.a(1)(e) NA The primary containment is inerted with system in noninerted containments. nitrogen during normal reactor operation.
176. For secondary containment areas, cable fire hazards C.7.a(1)(f) -- See Items 88 through 95.
that could affect safety should be protected as described in Position C.5.e(2).
177. Self-contained breathing apparatus should be provided C.7.a(2) C See Item 33.
near the containment entrances for fire fighting and damage control personnel. These units should be independent of any breathing apparatus provided for general plant activities.
Control Room Complex 178. The control room complex should be separated from other C.7.b C The control room is separated from other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers. parts of the control structure by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated floor slabs at el 269 and el 289.
Three hour rated walls at the north, south, east, and west sides of the control room separate it from the reactor enclosures and turbine enclosures.
APPENDIX 9A 9A-30 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 179. Recommendations concerning peripheral rooms in the C.7.b NC See Section 9A.3.1.2.
control room complex.
180. Recommendations concerning the use of Halon and carbon C.7.b NA The peripheral rooms adjacent to the dioxide flooding systems in the peripheral rooms. control room are not provided with Halon or carbon dioxide flooding systems.
181. Recommendations concerning manual fire fighting C.7.b C See Section 9A.3.1.2.
capability in the control room.
182. Recommendations concerning fire detection in the C.7.b AC See Section 9A.3.1.2.
control room.
183. Breathing apparatus for control room operators should C.7.b C See Item 33.
be readily available.
184. Recommendations concerning control room ventilation. C.7.b C See Section 9A.3.1.2.
185. All cables that enter the control room should terminate C.7.b C in the control room.
186. Cables in under-floor and ceiling spaces should meet C.7.b C See Section 9A.3.1.2.
the separation criteria necessary for fire protection.
187. Air handling functions should be ducted separately from C.7.b C The space above the suspended ceiling in cable runs in such spaces. the control room is not used as an air plenum for ventilation of the control room.
Ventilation air is deducted through the space above the suspended ceiling.
188. Fully enclosed electrical raceways located in under- C.7.b C None of the fully enclosed raceways in the floor and ceiling spaces, if over 1 square foot in space above the suspended ceiling in the cross-sectional area, should have automatic fire control room has a cross-sectional area suppression inside. exceeding 1 square foot. The raceways in the raised flooring of the auxiliary equipment room are provided with an automatic Halon suppression system, as described in Section 9A.2.9.
189. Recommendations concerning automatic fire suppression C.7.b AC See Section 9A.3.1.2.
in under-floor and ceiling spaces.
190. There should be no carpeting in the control room. C.7.b NC See Section 9A.3.1.2.
Cable Spreading Room 191. Recommendations concerning automatic fire suppression C.7.c C See Section 9A.3.1.2.
in the cable spreading room.
APPENDIX 9A 9A-31 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 192. Open-head deluge and open directional spray systems C.7.c NA Open-head water suppression systems are not should be zoned. used in the cable spreading room.
193. Cable spreading rooms should have at least two remote C.7.c(1) C and separate entrances for access by fire brigade personnel.
194. Cable spreading rooms should have an aisle separation C.7.c(2) NC Cable trays in the cable spreading rooms between tray stacks at least 3 feet wide and 8 feet are arranged to provide aisleways with a high. minimum headroom approximately 6.5 feet high and and a minimum width between tray stacks of approximately 3 feet. At certain locations, structural supports for the cable trays reduce the aisle width to a minimum of 17 inches. All points in the cable spreading rooms can be reached by an effective hose stream.
195. Cable spreading rooms should have hose stations and C.7.c(3) C The locations of hose stations in the portable extinguishers installed immediately outside the vicinity of the cable spreading rooms are room. shown in Figure 9A.7.
196. Cable spreading rooms should have area smoke detection. C.7.c(4) C The fire and smoke detection system is described in Section 9A.2.12. The number of detectors located in each fire area is listed in Table 9A.1.
197. Cable spreading rooms should have continuous line-t ype C.7.c(5) NC Continuous line-t ype heat detectors are not heat detectors for cable trays inside the cable used in cable trays. Smoke detectors are spreading room. provided in the cable spreading room (as specified in Table 9A-1) and will provide early warning for cable tray fires occurring in the cable spreading room.
See Item 89 for further discussion.
198. Drains to remove fire-fighting water should be provided. C.7.c C 199. W hen gas systems are installed, drains should have C.7.c C The capacity of the carbon dioxide storage adequate seals or the gas extinguishing system should tank is sufficient to compensate for losses be sized to compensate for losses through the drains. through the floor drains in the cable spreading rooms.
200. A separate cable spreading room should be provided for C.7.c NC See Item 57.
each redundant division.
201. Cable spreading rooms should not be shared between C.7.c C Each reactor unit is provided with its own reactors. separate cable spreading room.
202. Each cable spreading room should be separated from the C.7.c C See Item 58 of Section 9A.3.1.2.
others and from other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers.
APPENDIX 9A 9A-32 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 203. The ventilation system for the cable spreading room C.7.c C In the event of actuation of the carbon should be designed to isolate the area upon actuation dioxide system in the cable spreading room, of the gas extinguishing system. ventilation ducts penetrating the boundaries of the room are automatically isolated by steam isolation dampers. The dampers are actuated by pressure switches connected to the carbon dioxide distribution piping.
204. Separate manually actuated smoke venting that is C.7.c C Portable smoke ejectors are used to clear operable from outside the room should be provided for smoke, toxic gases, and carbon dioxide from the cable spreading room. the cable spreading rooms.
Plant Computer Rooms 205. Recommendations concerning fire protection for computers C.7.d NA The plant computer is not safety-related.
performing safety-related functions.
206. Nonsafety-related computers outside the control room C.7.d AC The plant computer is nonsafety-related and should be separated from safety-related areas by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> is located in the auxiliary equipment room.
fire barriers and should be protected as needed to The auxiliary equipment room is separated prevent damage to safety-related equipment. from other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, but the computer is not separated (other than by distance) from safety-related panels in the auxiliary equipment room. Automatic fire suppression for the raised flooring in the auxiliary equipment room is discussed in Section 9A.2.9.
S witchgear Rooms 207. S witchgear rooms containing safety-related equipment C.7.e AC The safety-related switchgear rooms at el should be separated from the remainder of the plant by 239 in the control structure are separated 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers. Redundant switchgear safety from each other and from the remaining divisions should be separated from each other by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire fire barriers. walls. The concrete slab above these rooms is a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated barrier, and the slab below the room is capable of a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating with the exception of exposed structural steel members supporting the slabs.
208. Automatic fire detectors should alarm and annunciate in C.7.e C Each safety-related switchgear room is the control room and alarm locally. provided with smoke and heat detectors that annunciate in the control room and alarm locally.
APPENDIX 9A 9A-33 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 209. Fire hose stations and portable fire extinguishers C.7.e C should be readily available outside the switchgear rooms.
210. Drains should be provided to prevent water accumulation C.7.e AC See Section 9A.3.1.2.
from damaging safety-related equipment.
211. Remote manually actuated ventilation should be provided C.7.e NC Ventilation features separate from the for venting smoke when manual fire suppression effort normal ventilation system are not provided is needed. for the switchgear rooms. Smoke removal can be accomplished using portable exhaust fans, if necessary.
Remote Safety-Related Panels 212. Recommendations concerning separation and electrical C.7.f AC See Section 9A.3.1.2.
isolation of remote safety-related panels.
213. The general area housing remote safety-related panels C.7.f C should be provided with automatic fire detectors that alarm locally and alarm and annunciate in the control room. Combustible materials should be controlled and limited to those required for operation. Portable extinguishers and manual hose stations should be readily available in the general area.
Safety-Related Battery Rooms 214. Safety-related battery rooms should be separated from C.7.g AC The safety-related battery room are each other and other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated located in the control structure. These fire barriers. rooms are separated from each other and from the remaining areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls. The floor slabs above and below the battery rooms are capable of 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire ratings with the exception of exposed structural steel members supporting the concrete slabs.
215. DC switchgear and inverters should not be located in C.7.g AC See section 3.1.2.
safety-related battery rooms.
216. Automatic fire detection should be provided to C.7.g C Each safety-related battery room is annunciate in the control room and alarm locally. provided with smoke and heat detectors that annunciate in the control room and alarm locally.
APPENDIX 9A 9A-34 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 217. Ventilation system in the battery rooms should be C.7.g C See Section 9A.3.1.2.
capable of maintaining the hydrogen concentration below 2%.
218. Loss of ventilation should be alarmed in the control C.7.g C See Section 9A.3.1.2.
room.
219. Portable extinguishers and manual hose stations should C.7.g C be readily available outside the battery rooms.
Turbine Building 220. The turbine building should be separated from adjacent C.7.h C The turbine enclosure is separated from the structures containing safety-related equipment by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> reactor enclosure and control structure by fire barriers. 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls.
221. The fire barriers should be designed so as to maintain C.7.h C See Section 9A.3.1.2.
structural integrity in the event of collapse of the turbine structure.
222. Openings and penetration in the fire barrier should be C.7.h C See Section 9A.3.1.2.
minimized and should not be located where the turbine oil system or generator hydrogen cooling system creates a fire exposure hazard to the barrier.
Diesel Generator Areas 223. Diesel generators should be separated from each other C.7.i C The individual diesel generator cells, each and from other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire of which encloses a single diesel barriers. generator, are separated from adjacent fire areas by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated barriers consisting of 24 inch thick reinforced concrete walls and 18 inch thick reinforced concrete slabs. Each door opening in the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated walls is provided with a UL Class A fire door. All penetration through the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated walls and floor slabs are sealed using penetration seal details that are qualified for use in 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers.
APPENDIX 9A 9A-35 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS 224. Automatic fire suppression should be installed to combat C.7.i AC See Section 9A.3.1.2.
diesel generator or lubricating oil fires. Such systems should be designed for operation when the diesel is running without affecting the diesel.
225. Automatic fire detection should be provided to C.7.i C annunciate in the control room and alarm locally.
226. Portable extinguishers and manual hose stations should C.7.i C Portable extinguishers are available be readily available outside the area. outside the diesel generator cells. Fire hydrants located in the yard can reach any area of the diesel generator cells.
227. Drainage for fire fighting water and means for local C.7.i AC See Section 9A.3.1.2.
manual venting of smoke should be provided.
228. Day tanks with total capacity up to 1100 gallons are C.7.i C The day tank for each diesel generator has permitted in the diesel generator area under specified a capacity of 850 gallons.
conditions.
229. The day tank should be located in a separated enclosures C.7.i C The day tank for each diesel generator is with a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating. located in a vault that is separated from the remainder of the diesel generator cell by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls.
230. The day tank enclosures should be capable of containing C.7.i C the entire contents of the tank.
231. The day tank enclosure should be protected by an C.7.i C The preaction sprinkler system provided in automatic fire suppression system. each diesel generator cell includes coverage of the day tank vault.
Diesel Fuel Oil Storage Areas 232. Recommendations concerning diesel fuel oil tanks. C.7.j C Each diesel generator is provided with a diesel fuel oil storage tank that has a capacity of 41,500 gallons. All eight tanks are located adjacent to each other and are buried underground.
233. Above-ground tanks should be protected by an automatic C.7.j NA See Item 232.
fire suppression system.
APPENDIX 9A 9A-36 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Safety Related Pumps 234. Pump houses and rooms housing redundant safety-related C.7.k C The safety-related pump compartments pump trains should be separated from each other and from located at el 177 in the reactor enclosure other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers. are separated from each other and from other areas of the plant by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls. The spray pond pump structure is located remote from other plant structures, and the two divisions of pumps within the structure are separated by a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire wall.
235. These rooms should be protected by automatic fire C.7.k C The HPCI compartment and the RCIC pump suppression unless a fire hazards analysis can compartment are protected by automatic demonstrate that a fire will not endanger equipment preaction sprinkler systems. Fires required for safe shutdown. originating in other safety-related pump compartments would not endanger other safety-related equipment required for safe shutdown, as discussed in Section 9A.5.
236. These rooms should be provided with automatic fire C.7.k C detection to annunciate in the control room and alarm locally.
237. Portable extinguishers and manual hose stations should C.7.k NC Portable extinguishers are provided for use be readily accessible. in all areas housing safety-related pumps.
Manual hose stations are provided for use in all areas housing safety-related pumps, except for the spray pond pump structure.
In consideration of the low combustible loading in the spray pond pump structure, portable extinguishers are deemed adequate to control and extinguish a fire at any pump.
238. Floor drains should be provided to prevent water C.7.k C accumulation from damaging safety-related equipment.
239. Provisions should be made for manual control of the C.7.k C The ventilation systems in areas housing ventilation systems to facilitate smoke removal. safet y-related pumps are provided with controls that are sufficient to permit manual control of the ventilation as necessary to facilitate smoke removal.
240. Recommendations for fire protection of the new fuel C.7.l NA/AC The normal storage area for new fuel is the area. spent fuel pool. Prior to plant operation and during the initial phases of plant operation, new fuel may be stored in a temporary outdoor storage area. Fire protection for this temporary new fuel storage area will be provided in accordance with guidelines established by ANI.
APPENDIX 9A 9A-37 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Spent Fuel Pool Area 241. Protection for the spent fuel pool area should be C.7.m C Hose stations and portable extinguishers provided by hose stations and portable extinguishers. are located near the spent fuel pool.
242. Automatic fire detection should be provided to C.7.m NC See Section 9A.3.1.2, item 112.j.
annunciate in the control room and to alarm locally.
Radwaste and Decontamination Areas 243. Fire barriers, automatic fire suppression and detection, C.7.n C See Section 9A.3.1.2.
and ventilation controls should be provided.
Safety-Related W ater Tanks 244. Fire protection provisions for safety-related water C.7.o NA The plant has no safety-related water tanks. tanks.
Records Storage Areas 245. Records storage areas should be so located and protected C.7.p C that a fire in these areas does not expose safety-rel ated systems or equipment.
Cooling Towers 246. Cooling towers should be of noncombustible construction C.7.q C The cooling towers are of noncombustible or so located and protected that a fire will not construction except for the fill material, adversely affect any safety-related systems or which is polyvinyl chloride. No equipment. safety-related structures or systems are located near the cooling towers such that they could be affected by a fire in the cooling towers.
247. Cooling towers should be of noncombustible construction C.7.q AC See Section 9A.3.1.2.
when the basins are used for the ultimate heat sink or for the fire protection water supply.
Miscellaneous Areas 248. Location and protection of miscellaneous areas. C.7.r C See Section 9A.3.1.2.
APPENDIX 9A 9A-38 REV. 18, SEPTEMBER 2016
LGS UFSAR CMEB 9.5-1 NO. CMEB 9.5-1 GUIDELINE ITEM NO. COMPARISON REMARKS Storage of Acetylene/Oxygen Fuel Gases 249. Gas cylinder storage locations should not be in areas C.8.a C Compressed gas storage cylinders for that contain or expose safety-related equipment or the welding are located outdoors, away from fire protection systems that serve those safety-related safety-related components.
areas.
250. A permit system should be required to use this equipment C.8.a C in safety-related areas of the plant.
Storage Areas for Ion Exchange Resins 251. Unused ion exchange resins should not be stored in areas C.8.b AC Storage areas for dry ion exchange resins that contain or expose safety-related equipment. in safety-related equipment areas utilize approved metal storage containers.
Hazardous Chemicals 252. Hazardous chemicals should not be stored in areas that C.8.c AC Procedural controls exist to ensure contain or expose safety-related equipment. hazardous chemical storage in safety-related areas do not pose a fire risk.
Materials Containing Radioactivity 253. Materials that collect and contain radioactivity should C.8.d C be stored in closed metal tanks or containers that are located in areas free from ignition sources or combustibles.
254. These materials should be protected from exposure to C.8.d C fires in adjacent areas.
255. Consideration should be given to requirements for C.8.d C Provisions for accommodating decay heat are removal of decay heat from entrained radioactive considered when selecting containers.
Materials.
APPENDIX 9A 9A-39 REV. 18, SEPTEMBER 2016
9A.3.1.2 Explanatory Notes for Comparison to Branch Technical Position CMEB 9.5-1 Item 6 BTP Guideline The position responsible for formulation and implementation of the fire protection program should have within his organization or as a consultant a fire protection engineer who is a graduate of an engineering curriculum of accepted standing and shall have completed not less than 6 years of engineering attainment indicative of growth in engineering competency and achievement, 3 years of which shall have been in responsible charge of fire protection engineering work. These requirements are the eligibility requirements as a Member in the Society of Fire Protection Engineers.
LGS Design The Vice President, LGS, is responsible for the formulation and implementation of the fire protection program. In this capacity, he has access to the services of corporate support personnel, other Exelon sites, or vendors as necessary in the capacity of a fire protection engineer. The individual meets the requirements for membership in the Society of Fire Protection Engineers (i.e.,
a graduate of an engineering curriculum of accepted standing and shall have completed not less than 6 years of engineering attainment indicative of growth in engineering competency and achievement, 3 years of which shall have been in responsible charge of fire protection work).
In addition, fire protection consultants are available to assist in design and review tasks as required.
Item 15 BTP Guideline Fires involving facilities shared between units and fires due to man-made site-related events that have a reasonable probability of occurring and affecting more than one reactor unit (such as an aircraft crash) should be considered.
LGS Design The control structure, the spray pond pump structure, and the radwaste enclosure are common to the two reactor units. Fires are postulated to occur in these structures just as in other structures, and appropriate provisions are made for fire prevention, fire detection, and fire suppression.
For a discussion of fires due to man-made site-related events, refer to Item 22.
Item 19 BTP Guideline A single active failure or a crack in a moderate energy line (pipe) in the fire suppression system should not impair both the primary and backup fire suppression capability. For example, neither the failure of a fire pump, its power supply or controls, nor a crack in a moderate energy line in the fire suppression system, should result in loss of function of both sprinkler and hose standpipe systems in an area protected by such primary and backup systems.
APPENDIX 9A 9A-40 REV. 18, SEPTEMBER 2016
LGS Design As described in Section 9A.2.1.2, fire water is supplied by two redundant pumps, each of which is capable of providing the design fire protection system flow rate at the design pressure. Power for the motor-driven fire pump is provided from either of two independent offsite power sources. The controls for the diesel engine-driven fire pump are dc-operated and are powered from batteries which supply only the engine-driven fire pump. Therefore, no single failure of the power supplies or controls can affect both fire pumps.
If a crack should occur in the yard fire main loop, sectional isolation valves can be used to isolate the damaged portion of the loop without affecting the majority of the loop. There is no single active failure that could affect the operability of both the sprinkler systems and manual hose stations for a given area. The standpipes supplying water to the sprinklers and manual hose stations have been designed to minimize the probability of a moderate energy crack occurring in these portions of piping. The standpipes were designed in accordance with NFPA requirements, for which the materials and standards of construction are the same as for ANSI B31.1, "Power Piping." The standpipes were seismically analyzed for safe shutdown earthquake loads in order to verify piping integrity under such loads. In the unlikely event that a crack does occur in a standpipe that supplies water to sprinklers and hose stations serving the same area, such that the ability to achieve design flow rates for the sprinklers and hose stations is affected, an effective hose stream could be provided to the area from a hose station attached to the closest unaffected standpipe.
Item 21 BTP Guideline The fire protection systems should retain their original design capability for natural phenomena of less severity and greater frequency than the most severe natural phenomena (approximately once in 10 years) such as tornadoes, hurricanes, floods, ice storms, or small intensity earthquakes that are characteristic of the geographic region.
LGS Design The fire pumps, the yard fire main loop, distribution piping within structures, manual hose stations, and fixed suppression systems are conservatively designed so as to retain their operability following the occurrence of natural phenomena with severities corresponding to a recurrence interval of once in 10 years.
Item 22 BTP Guideline The fire protection systems should retain their original design capability for potential man-made site-related events such as oil barge collisions or aircraft crashes that have a reasonable probability of occurring at a specific plant site.
LGS Design Transportation activities taking place near LGS, and the potential for accidents affecting the plant, are discussed in Section 2.2. As indicated in Section 2.2.2.4, there is no commercial traffic on the Schuylkill River in the vicinity of the site. As discussed in Section 2.2.3, the potential effects of an explosion occurring on nearby highways are exceeded in severity by the potential effects of a APPENDIX 9A 9A-41 REV. 18, SEPTEMBER 2016
railway explosion. Structures housing safety-related systems and components are designed to withstand impact from missiles generated by a railway explosion. Portions of fire protection systems that are located outside the safety-related structures could potentially be damaged by missiles generated by a railway explosion. However, such damage will not jeopardize safe shutdown capability since the systems and components, excluding offsite power, needed for safe shutdown are protected from damage due to missile impact and are isolated from the effects of fires occurring outside the safety-related structures.
Hazards to the plant resulting from aircraft operating in the vicinity of the site are discussed in Section 3.5.1.6. The control structure, reactor enclosure, and spray pond pump structure are designed to withstand the impact of the design aircraft (a Learjet) without loss of structural integrity.
Portions of fire protection systems that are located outside these structures could potentially be damaged by aircraft impact. However, such damage will not jeopardize safe shutdown capability since the systems and components, excluding offsite power, needed for safe shutdown are protected from damage due to aircraft impact and are isolated from the effects of fires occurring outside the control structure, reactor enclosure, and spray pond pump structure.
Item 24 BTP Guideline The consequences of inadvertent operation of or a crack in a moderate energy line in the fire suppression system should meet the guidelines specified for moderate energy systems outside containment in SRP section 3.6.1.
LGS Design Moderate energy leakage cracks in fire suppression system piping are analyzed as discussed in Section 3.6. Section 3.6.1.2.2 summarizes the results of the moderate energy fluid system analysis and also provides references to other UFSAR sections that discuss the design bases and criteria that were used in the moderate energy fluid system analysis. The analysis demonstrates that the occurrence of a crack in moderate energy piping, including the fire suppression system piping, will not prevent the plant from being brought to a safe, cold shutdown.
Automatic suppression systems have been designed and located so that operation of the systems, either intentional or inadvertent, will not cause damage to redundant trains of safety-related equipment that is needed for safe shutdown of the plant. To the greatest extent practical, safety-related electrical components are located outside the coverage zones of automatic suppression systems. Where necessary, components that are needed in order to achieve safe shutdown and also are located within automatic suppression system coverage zones are designed to remain functional in the event of suppression system actuation. Four of the areas that are provided with automatic water-type suppression systems are the HPCI pump compartment, the RCIC pump compartment, the diesel generator cells, and the 13.2 kV switchgear room. Actuation of the suppression systems in the HPCI and RCIC pump compartments could cause damage significant enough to affect the operability of the systems in those compartments. In the diesel generator cells, baffles are provided to protect the generators and control devices from damage due to suppression system actuation. In the 13.2 kV switchgear room, the design features of the system mitigate the effects due to spurious actuation or MELB. This system is supervised with instrument air and incorporates a double interlock deluge valve that is maintained normally closed.
Sprinkler flow is initiated only when two seperate inputs are received; one from a pneumatic actuator, due to the melting of the sprinkler fusible link(s) allowing the supervised air to be APPENDIX 9A 9A-42 REV. 18, SEPTEMBER 2016
released; and the other from the fire detection system that sends a signal to an electric solenoid valve. Loss of any of these four systems (HPCI, RCIC, or a single diesel generator and 13.2 kV switchgear room) due to suppression system actuation is acceptable, since redundant systems will remain available to bring the plant to a safe, cold shutdown.
There are no cases in which safe shutdown components have electrical interconnections with fire detection or fire suppression systems. Therefore, safe shutdown components cannot be inadvertently actuated or shut down due to either normal or abnormal signals in the control and power circuits of the fire detection and fire suppression systems.
The HPCI and RCIC pump compartments and the diesel generator cells are the only safety-related areas of the plant that are provided with automatic suppression systems and also are potentially subject to steam flooding as a result of high energy pipe breaks. Elevated compartment temperatures due to steam flooding could result in suppression system actuation if the temperatures are high enough to cause the deluge valve to open and the fusible links on the sealed sprinkler heads to open. However, loss of the HPCI system, RCIC system, or a single diesel generator due to suppression system actuation is acceptable, since redundant systems will remain available to bring the plant to a safe, cold shutdown.
Automatic (water) suppression systems located in safety-related areas of the plant are of the type that have fusible heads (either preaction or wet pipe). These systems cannot be actuated in the absence of a significant heat source in the vicinity of the sprinkler heads. Therefore, electrical anomalies in the circuits of the smoke and heat detection systems or the suppression system power supplies cannot cause inadvertent actuation of these suppression systems.
Item 28 BTP Guideline On reactor sites where there is an operating reactor and construction or modification of other units is under way, the fire protection program should provide for continuing evaluation of fire hazards.
Additional fire barriers, fire protection capability, and administrative controls should be provided as necessary to protect the operating unit from construction fire hazards.
LGS Design Administrative procedures will be prepared to protect the operating Unit 1 from fire hazards associated with construction of Unit 2. Special precautions will be taken to prevent and control fire hazards. Use of open flames and welding or cutting equipment will be properly supervised.
Construction of both the underground yard fire main and the fire water distribution piping inside both units of the plant will be completed prior to Unit 1 operation so that manual hose station coverage will be available in Unit 2 as well as Unit 1. Portable fire extinguishers will also be available in the Unit 2 portions of the plant during its construction. The construction site will be kept clean and orderly and contractors' sheds will be kept outside the confines of new construction.
Item 33 BTP Guideline APPENDIX 9A 9A-43 REV. 18, SEPTEMBER 2016
Self-contained breathing apparatus using full face positive- pressure masks approved by the National Institute for Occupational Safety and Health (approval formerly given by the U.S. Bureau of Mines) should be provided for fire brigade, damage control, and control room personnel. At least 10 masks shall be available for fire brigade personnel. Control room personnel may be furnished breathing air by a manifold system piped from a storage reservoir if practical. Service or rated operating life shall be a minimum of one-half hour for the self-contained units.
At least two extra air bottles should be located onsite for each self-contained breathing unit. In addition, an onsite 6 hour6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> supply of reserve air should be provided and arranged to permit quick and complete replenishment of exhausted supply air bottles as they are returned. If compressors are used as a source of breathing air, only units approved for breathing air shall be used; compressors shall be operable assuming a LOOP. Special care must be taken to locate the compressor in areas free of dust and contaminants.
LGS Design Self-contained breathing apparatus will be available for use by control room personnel and fire brigade members. The breathing apparatus will have a minimum operating life of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for control room personnel and 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> for fire brigade members.
An onsite reserve air supply of six hours for at least five persons will be provided in stored air bottles. Compressors, if used, will be units approved for breathing air.
Item 34 BTP Guideline Recommendations for the fire brigade training program.
LGS Design Fire Protection program objectives for training fire brigade members is accomplished by using a combination of in plant areas and an off-site training facility that simulates plant physical conditions.
Drills are conducted in conformance with plant fire drill procedures.
An off-site facility enables drills to include the use of live fire conditions. These elements plus the use of breathing apparatus and full protective clothing create actual conditions that would be encountered during a real plant fire emergency. Additional drills, including backshift unannounced drills are conducted in plant areas throughout the year. Unannounced drills are scheduled on a "per shift basis" in accordance with the corporate fire protection procedures.
Local fire departments are offered annual training associated with the responsibilities and duties of the plant fire brigade and offsite responders, operational precautions when fighting fires on nuclear power plant sites including awareness of the need for radiological protection of personnel and the special hazards associated with a nuclear power plant site.
Item 35 BTP Guideline The quality assurance programs of applicants and contractors should ensure that the guidelines for design, procurement, installation, and testing and the administrative controls for the fire protection systems for safety-related areas are satisfied. The QA program should be under the management APPENDIX 9A 9A-44 REV. 18, SEPTEMBER 2016
control of the QA organization. This control consists of (1) formulating a fire protection QA program that incorporates suitable requirements and is acceptable to the management responsible for fire protection or verifying that the program incorporates suitable requirements and is acceptable to the management responsible for fire protection, and (2) verifying the effectiveness of the QA program for fire protection through review, surveillance, and audits. Performance of other QA program functions for meeting the fire protection program requirements may be performed by personnel outside of the QA organization. The QA program for fire protection should be part of the overall plant QA program.
LGS Design The QA program described below will be under the management control of the licensee and their agent's organizations during the construction and operation phases.
- a. Design and Procurement Document Control The design review performed to compare the LGS design to the BTP guidelines provides assurance that necessary design features are included in appropriate design and procurement documents.
Deviations from the design and procurement documents will be controlled by mechanisms specified in the 10CFR50, Appendix B, QA program for this project.
- b. Instructions, Procedures, and Drawings These requirements will be met through the use of a documented, final installation inspection and through implementation of a written preoperational test.
- c. Control of Purchased Material, Equipment, and Services Based upon the status of procurement and the identification of significant design or manufacturing features, certain fire protection equipment may be subject to shop inspection during manufacture.
Receipt inspection at the site shall be performed.
- d. Inspection These requirements will be met through the use of a documented, final installation inspection and through implementation of a written preoperational test.
- e. Test and Test Control Documented preoperational test procedures including evaluation of results and follow-up action, if indicated, shall be employed to meet these requirements.
- f. Inspection, Test, and Operating Status Installation inspections, as described in Item 4 above, shall be documented in such a manner as to indicate the acceptability of the item/activity inspected. Deficiencies APPENDIX 9A 9A-45 REV. 18, SEPTEMBER 2016
shall be identified and corrected in accordance with mechanisms specified in the 10CFR50, Appendix B, QA program for this project.
Satisfactory completion of the preoperational test and release for operation shall be accomplished and documented in accordance with mechanisms specified in the 10CFR50, Appendix B, QA program for this project.
- g. Nonconforming Items Nonconforming items shall be identified, controlled, and corrected in accordance with the mechanisms specified in the 10CFR50, Appendix B, QA program for this project.
- h. Corrective Action Conditions adverse to fire protection (such as failures, malfunctions, deficiencies, deviations, defective components, and nonconformances) during the construction phase shall be reported and corrected in accordance with mechanisms specified in the 10CFR50, Appendix B, QA program for this project.
- i. Records Records shall be prepared and maintained to furnish evidence that the criteria described in Items 1 through 10 are being met for activities affecting the fire protection program.
- j. Audits The activities described above are subject to audit. In addition, implementation of receipt inspections, final installation inspections, and preoperational tests shall be subject to audit to conform with documented instructions, procedures, and drawings.
Item 37 BTP Guideline Fire barriers with a minimum rating of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> should be provided to separate redundant divisions of safety-related systems from each other.
LGS Design Redundant divisions of safety-related systems will be separated from each other so as to achieve the three levels of fire damage limits established in Position C.1.b. The provision of fire barriers between redundant divisions of safety-related systems that do not have safe shutdown functions is not required. Fire barriers will be provided between redundant divisions of safe shutdown systems as necessary to ensure that one train of equipment necessary to achieve safe shutdown is maintained free of fire damage to the degree specified in Position C.1.b unless specified otherwise in Section 9A.5.
APPENDIX 9A 9A-46 REV. 18, SEPTEMBER 2016
The reactor enclosures, turbine enclosures, diesel generator enclosures, radwaste enclosure, and administration building are separated from each other by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls. Walls internal to these structures (and also the spray pond pump structure) which serve as boundaries between different fire areas are provided with fire ratings or construction details consistent with the fire hazard existing in each area. The locations of fire-rated walls are shown on Figures 9A-4 through 9A-12, and the walls surrounding each fire area are further described in the fire area discussions contained in Sections 9A.5.3 through 9A.5.9.
The structural steel beams supporting the floor slabs at el 254', el 269', el 289' and el 304' in the control structure have been fireproofed to provide a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rating for the complete floor assembly.
The structural steel beams supporting floor slabs in other areas have not been fireproofed. The fire ratings of floor slabs above and below each fire area are listed in the fire area discussions contained in Sections 9A.5.3 through 9A.5.9. Those slabs which are shown as "3 hr*" are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for the lack of fireproofing on the structural steel beams supporting the slab.
Reinforced concrete walls without penetrations are considered to qualify for a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating, provided that the wall has a thickness of at least 6 inches. Concrete block walls designated as fire walls are constructed in accordance with UL Design No. U904, as a minimum. Fire walls incorporating metal studs with lath and plaster are constructed in accordance with UL Design No.
U409. Fireproofing material is applied to structural steel beams in accordance with UL Design No.
N706, N712, N742, or N760.
Item 39 BTP Guideline Appropriate fire barriers should be provided within a single safety division to separate components that present a fire hazard to other safety-related components or high concentrations of safety-related cables within that division.
LGS Design The diesel generator day tanks constitute the most significant fire hazard posed by components within safety-related systems. As stated in Item 229, the day tank for each diesel generator is located in a vault that is separated from the remainder of the diesel generator cell by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls. The HPCI, RCIC, RHR, and LPCI systems contain lesser fire hazards in the form of lubricating oil associated with the pumps and drivers in these systems. These pumps are located at el 177' in the reactor enclosure, which is compartmentalized to separate the pumps from each other and from other safety-related systems.
Fire barriers are not provided solely for the purpose of separating safety-related cables from other safety-related cables in the same division. Separation by distance or by fire barriers between redundant divisions is provided as necessary to ensure safe shutdown capability in the event of a fire. Separation to ensure independence between Class 1E and non-Class 1E circuits and between redundant divisions of Class 1E circuits is discussed in Section 8.1.6.1.14.
Item 40 BTP Guideline APPENDIX 9A 9A-47 REV. 18, SEPTEMBER 2016
Openings through fire barriers for pipe, conduit, and cable trays which separate fire areas should be sealed or closed to provide a fire resistance rating at least equal to that required of the barrier itself.
LGS Design Pipe, conduit, and cable tray penetrations through fire-rated barriers will be sealed to provide a fire resistance rating that is consistent with that of the overall barrier. Such seals in fire barrier penetrations will be installed in accordance with the manufacturer's tested configurations where possible. Individual penetration seals that include configurations or features that constitute deviations from the manufacturer's tested configuration are reviewed and accepted by LGS's authorized insuring agency for use as fire-rated seals.
Item 41 BTP Guideline Openings inside conduit larger than 4 inches in diameter should be sealed at the fire barrier penetration. Openings inside conduit 4 inches or less in diameter should be sealed at the fire barrier unless the conduit extends at least 5 feet on each side of the fire barrier and is sealed either at both ends or at the fire barrier with noncombustible material to prevent the passage of smoke and hot gases.
LGS Design In areas of the plant that contain safety-related equipment, conduits that penetrate fire barriers will be sealed internally to prevent the passage of smoke and hot gases. For each penetrating conduit that extends 5 feet or more on both sides of the fire barrier, noncombustible seals will be provided on both sides of the fire barrier at the access point (junction box, termination at a cable tray, or equipment connection) that is closest to the fire barrier. For each penetrating conduit that extends less than 5 feet on either side of the fire barrier, a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rated seal will be provided either at the fire barrier or on one side of the barrier at the access point that is closest to the barrier. For the cases in which access to the interior of a conduit has been provided at the fire barrier via a junction box or condulet, the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> seal is located at the barrier. Where no access has been provided at the barrier, the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> seal is located at the access point that is closest to the barrier. For the cases in which the penetrating conduit is larger than 4 inches in diameter and the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> seal is not located at the barrier, the conduit forms part of the fire barrier in combination with the seal.
Conduits in this category are schedule 40 rigid steel and will maintain their integrity while exposed to a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire.
Any installation which deviates from the above criteria for internal conduit seals is documented in a technical evaluation in the form of a fire hazards and safe shutdown analysis that is performed and reviewed by personnel responsible for fire protection and safe shutdown analyses for the plant.
Each technical evaluation documents the as-built configuration and presents the rationale for concluding that the affected seal does not degrade the effectiveness of the fire barrier in preventing the spread of a postulated fire and in limiting the migration of smoke and hot gases. Each technical evaluation performed is retained as part of the permanent plant records.
For conduits that enter the bottom of floor-mounted components that are mounted on fire-rated floor slabs, 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals are normally installed inside each conduit at the point where it enters the component. In some cases, however, the congestion of cables in a conduit prevents the fire APPENDIX 9A 9A-48 REV. 18, SEPTEMBER 2016
sealant material from being installed to the minimum thickness necessary to qualify as a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seal. In each such situation, a second seal is installed inside the conduit at the access point nearest to the component, with the thickness of the sealant material in the second seal being selected so that the combined thickness of the first and second seals is not less than the thickness required for a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seal.
For fire barriers that separate safety-related areas from nonsafety-related areas of the plant, conduit penetrations will be provided with internal seals in the same manner as discussed above for safety-related areas.
In areas of the plant not containing safety-related equipment, internal seals will be provided for conduits penetrating fire barriers that are adjacent to fire areas with high combustible loadings.
The locations of the conduit seals with respect to the fire barrier being penetrated will be the same as discussed above for safety-related areas.
Item 43 BTP Guideline Penetration designs should utilize only noncombustible materials.
LGS Design All materials used in fire-rated penetration seals are either noncombustible or are listed by an independent testing laboratory for flame spread, smoke generation, and fuel contribution of 25 or less, as determined by testing in accordance with ASTM E-84. Alternatively, the fire retardation of caulking and adhesive materials that are used in small quantities as part of penetration seal assemblies may be demonstrated by successful completion of the fire test specified in section 3.B of the "ANI/MAERP Standard Method of Fire Tests of Cable and Pipe Penetration Fire Stops,"
issued in February of 1976. The following different types of seals will be used in fire-rated applications:
- a. Cement-type grout.
- b. Foamed silicone polymer. This is a self-vulcanizing material that results from the mixture of two liquid components.
- c. Solid silicone polymer. The polymer is impregnated with a powdered high density filler.
- d. Flexible boot with ceramic fiber. The boot material is silicone rubber with woven glass fiber reinforcing. Ceramic fiber is installed inside the boot, in the space between the penetrating object and the edge of the penetration. Stainless steel compression straps and silicone adhesives are used in attaching the boot.
- e. Flexible boot with gel. The boot material is silicone rubber with woven glass fiber reinforcing. The boot is filled with a high density silicone dielectric gel. Stainless steel compression straps and silicone adhesives are used in attaching the boot.
APPENDIX 9A 9A-49 REV. 18, SEPTEMBER 2016
Item 45 BTP Guideline The acceptance criteria for the test should require that:
- a. The fire barrier penetration has withstood the fire endurance test without passage of flame or ignition of cables on the unexposed side for a period of time equivalent to the fire resistance rating required of the barrier.
- b. The temperature levels recorded for the unexposed side are analyzed and demonstrate that the maximum temperature does not exceed 325oF.
- c. The fire barrier penetration remains intact and does not allow projection of water beyond the unexposed surface during the hose stream test. The stream shall be delivered through a 11/2 inch nozzle set at a discharge angle of 30% with a nozzle pressure of 75 psi and a minimum discharge of 75 gpm with the tip of the nozzle a maximum of 5 ft from the exposed face; or the stream shall be delivered through a 11/2 inch nozzle set at a discharge angle of 15% with a nozzle pressure of 75 psi and a minimum discharge of 75 gpm with the tip of the nozzle a maximum of 10 ft from the exposed face; or the stream shall be delivered through a 21/2 inch national standard play pipe equipped with 11/8 inch tip, nozzle pressure of 30 psi, located 20 ft from the exposed face.
LGS Design In accordance with American Nuclear Insurer's NEL-PIA/MAERP, Standard Test method for penetration fire stops, a maximum allowable temperature of 325F above ambient is applicable to temperature measurements taken at the seal surface on the unexposed side at locations not involving interfaces with objects that penetrate the seal. In accordance with IEEE 634 (1978), a maximum allowable temperature of 700F is applicable to temperature measurements taken on the unexposed side at interfaces between the seal material and objects that penetrate the seal.
The acceptance criteria for penetration qualification tests are in agreement with those specified in paragraphs (a) and (c) above. The maximum unexposed side temperature criteria used by the ANI test standard was 325F above ambient. Annular pipe anchors are used in the type of penetration involving a single pipe routed through a steel penetration sleeve that is embedded in a concrete wall. The pipe anchor consists of a steel plate spanning the annular space between the pipe and the penetration sleeve, and which is welded to both the pipe and the penetration sleeve over its entire circumference. Fire resistance for this type of penetration assembly is provided by installing mineral wool in the annular space to a minimum depth of 12 inches. This configuration has been tested for a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating at the National Gypsum Company Research Center in cooperation with Factory Mutual Research. The assembly withstood the fire test and hose stream test with a maximum temperature of 425F on the unexposed side of the annular anchor, measured at a location 1 inch from the surface of the pipe. This temperature is attributable to heat conduction through the steel pipe. This seal configuration is acceptable because no cables are associated with the penetration.
APPENDIX 9A 9A-50 REV. 18, SEPTEMBER 2016
Item 46 BTP Guideline Penetration openings for ventilation systems should be protected by fire dampers having a rating equivalent to that required of the barrier.
LGS Design Except for Fire Areas 3, 4, 5, and 6, ventilation ducts that penetrate fire barriers are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire dampers at penetrations of 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated barriers and with 1.5 hour5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> rated dampers at penetrations of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> fire barriers. Both classifications of fire dampers are UL-listed and manufactured to comply with NFPA 90 and the Commonwealth of Pennsylvania Fire Protection Code.
Fire Areas 3, 4, 5, and 6 ventilation duct penetrations, which communicate with Fire Area 2, have fire damper assemblies which have been evaluated per an Engineering Evaluation, dated 03/26/98 (Reference NCR-ECR LG 98-00470) and are commensurate with the postulated fire in these areas.
Item 48 BTP Guideline Door openings in fire barriers should be protected with equivalently rated doors, frames, and hardware that have been tested and approved by a nationally recognized laboratory.
LGS Design Door openings in fire barriers are protected with equivalently rated doors, frames, and hardware that have been rated as follows:
- a. Hollow metal doors are listed by UL and classified as Class A (3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />) for use in 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers, Class B (1.5 hour5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />) for use in 2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> rated fire barriers, or Class C (3/4 hour) for use in 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> rated fire barriers.
- b. Roll-up doors less than 120 ft2 in size are labeled with classification markings as described above for hollow metal doors. Roll-up doors larger than 120 ft2 are not provided with UL classification labels but are certified by their manufacturer to be manufactured in compliance (except for size) with the requirements for doors of this class and type that are normally labeled as Class A.
- c. Watertight doors are not provided with UL classification labels but are certified by the manufacturer to be equivalent to the requirements of the UL classification for special purpose type fire door and frame assemblies that are rated as Class A.
- d. Missile-resistant doors are certified by the manufacturer to be designed so that the doors provide a degree of fire resistance equivalent to a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating based on exposure to temperatures as defined by the NFPA standard time-temperature curve. Because the missile-resistant doors are custom designed for each specific application, they are not provided with UL classification labels. Only three APPENDIX 9A 9A-51 REV. 18, SEPTEMBER 2016
missile-resistant doors are specified for use in fire barriers, two of which are 3'-0" by 7'-0" single-leaf doors and one of which is a 7'-0" by 10'-0" double-leaf door. The manufacturer has verified by calculation that the deformation of these doors resulting from exposure to a standard 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire will remain within the values specified in the acceptance criteria of ASTM E-152-81.
- e. Steamtight, airlock, and bullet-resistant doors are labeled as described above for hollow metal doors, except for doors with conditions that do not exactly match the physical units tested and approved by UL. Doors that are not labeled are certified by the door manufacturers to be fabricated in the same manner as the labeled units, except for variances due to special functions required for the doors. These variances include the following:
- 1. Door size - the size of double-leaf door tested by UL is 6'-0" by 7'-2" whereas the maximum size of the LGS doors is 9'-0" by 10'-0".
- 2. Door thickness - the maximum thickness tested by UL is 23/4" whereas the maximum thickness of the LGS doors is 41/4".
- 3. LGS' double-leaf steamtight and airlock doors contain a removable mullion that is not present in the UL-tested assemblies.
- 4. Minor hardware differences as follows:
(a) Customized hinges (b) Locksets by Sonicbar Door Systems (c) Additional security hardware (d) Surface-mounted hardware
- 5. LGS' bullet-resistant doors have additional structural features for greater strength that were not included in the tested doors.
The fire loadings on either side of the subject doors are low. The maximum equivalent severity in adjacent compartments is 35 minutes. In none of the cases are the in situ combustibles located immediately adjacent to the doors.
- f. Door/frame assemblies not installed in tested configurations that have been evaluated to withstand for three hours the maximum fire expected in the Fire Area.
Doors that are specified for use in fire barriers but are not listed by UL are identified in the fire area discussions contained in Sections 9A.5.3 through 9A.5.9 by a double asterisk (**) following the indicated fire rating.
Item 58 BTP Guideline APPENDIX 9A 9A-52 REV. 18, SEPTEMBER 2016
Cable spreading rooms should be separated from each other and from other areas of the plant by barriers having a minimum fire resistance of 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />.
LGS Design The cable spreading rooms are separated from each other and from adjacent fire areas by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers consisting of either reinforced concrete or concrete unit masonry walls with a minimum thickness of 12 inches, and reinforced concrete slabs with a minimum thickness of 12 inches. Exposed structural steel supporting the floor slabs above and below the cable spreading rooms are coated with fireproofing material in order to achieve a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire rating. Each door opening in the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls is provided with a UL Class A fire door. All penetrations through the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated walls and slabs are sealed using penetration seal details that are qualified for use in 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barriers. HVAC duct penetrations through the 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated walls are equipped with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire dampers.
Item 59 BTP Guideline Interior wall and structural components, thermal insulation materials, radiation shielding materials, and soundproofing should be noncombustible.
LGS Design Most interior walls are constructed of either reinforced concrete, or concrete masonry units.
Limited use is made of walls constructed of metal studs with either gypsum wallboard or gypsum plaster on expanded metal lath. Structural components consist of structural steel or reinforced concrete. Soundproofing materials, if required, will be noncombustible. Radiation shielding consists of concrete, concrete masonry unit, steel plates, or other noncombustible materials.
Thermal insulation materials are noncombustible, with the following exceptions:
- a. Insulation for domestic cold water piping (in the administration building only) is a closed-cell foamed elastomer with an ASTM E-84 flame spread rating of 25 or less.
- b. Insulation for the offgas refrigeration equipment (located only in the offgas enclosure) has an ASTM E-84 flame spread rating of 25 or less.
- c. Insulation for duct-work and plenums of the ventilation systems has an ASTM E-84 flame spread rating of 25 or less and a smoke generation rating of 50 or less.
Item 60 BTP Guideline Interior finishes should be noncombustible.
LGS Design Areas containing systems or equipment required for safe shutdown of the plant are unfinished, or are finished with materials that are either noncombustible or (except for floor coverings and vinyl APPENDIX 9A 9A-53 REV. 18, SEPTEMBER 2016
cove base) are rated by an independent testing laboratory for flame spread and smoke generation of 25 or less.
Floor coverings in areas containing systems or equipment required for safe shutdown of the plant are Class I material as defined in NFPA 101. In order to qualify for this classification, the floor covering material must have a minimum critical radiant flux of 0.45 watts per square centimeter as determined by NFPA 253 ("Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source").
Vinyl cove base is considered trim and incidental finish and may be Class III material as defined in NFPA 101. As such, it is rated for flame spread of 200 or less and smoke generation of 450 or less. Trim and incidental finish shall not exceed 10% of the aggregate wall and ceiling area of a room.
Item 61 BTP Guideline Metal deck roof construction should be noncombustible and listed as "acceptable for fire" in the UL Building Materials Directory, or listed as Class 1 in the Factory Mutual System Approval Guide.
LGS Design Metal deck roof construction is used only for the turbine enclosure, which is a nonsafety-related structure. The roof is constructed to meet the requirements of a Class 1 roofing system in accordance with the Factory Mutual System Approval Guide.
Item 62 BTP Guideline Suspended ceilings and their supports should be of noncombustible construction.
LGS Design Two different design details are used for the suspended ceiling in the control room. One detail includes mineral fiber panels resting on a metal grid system which is supported by steel wires. A second detail, used above the peripheral rooms adjacent to the control room, includes gypsum board panels supported from galvanized steel studs. The materials used in both of these details are either noncombustible or are listed by an independent testing laboratory for flame spread, smoke generation, and fuel contribution of 25 or less.
Item 63 BTP Guideline Concealed spaces should be devoid of combustibles except as noted in Position C.6.b.
LGS Design APPENDIX 9A 9A-54 REV. 18, SEPTEMBER 2016
There are no combustible materials in the space above the suspended ceiling in the control room, other than electrical cables. These cables (associated primarily with control room annunciators and control room lighting) are routed in conduits, fully enclosed gutters, and cable trays. The cable trays are fully enclosed through the use of solid (steel) top and bottom covers. The only exposed cables in the space above the suspended ceiling are the control room annunciator cables that extend through the bottom covers on the cable trays. Since the annunciators are located immediately adjacent to the cable trays, the exposed length of cable is very short. The cable dropout openings in the tray bottoms will be sealed with ceramic fiber and a flame-retardant mastic coating to ensure that any fire originating within the cable trays is contained within the trays. Eleven smoke detectors are located above the suspended ceiling to provide early warning of fires occurring within the area.
Table 9A-3 lists the insulation and jacketing materials used for electrical cabling. As noted in the table, cable insulation and jacketing materials are specified to meet the IEEE 383 flame test requirements except for lighting, communications, and grounding cables. Lighting cables and communication cables are routed exclusively in conduit, and grounding cables are not routed through the space above the suspended ceiling in the control room.
Electrical cables are routed through the raised floor sections in the auxiliary equipment room.
Access to the cables for manual fire fighting efforts is obtained by the removal of floor plates covering the floor sections. The floor plates are constructed of aluminum honeycomb bonded between sheet metal, and are easily removable using two quick-disconnect fasteners on each plate. Automatic fire detection systems and automatic Halon suppression systems are provided in the floor sections. Additional discussion of the auxiliary equipment room raised flooring and the Halon suppression system is provided in Sections 9A.2.9 and 9A.5.3.25.
Item 65 BTP Guideline Outdoor oil-filled transformers should have oil spill confinement features or drainage away from the buildings.
LGS Design The main transformers, the safeguard transformers, and the auxiliary transformers are each surrounded by a curb approximately 2 feet high. A floor drain is provided within each curbed area to drain liquids to the normal waste drainage system.
The fire walls that are located on three sides of each plant services transformer would prevent spilled oil from flowing toward the circulating water pump structure. The pavement in the vicinity of each transformer is sloped to provide drainage to nearby catch basins.
Item 66 BTP Guideline Outdoor oil-filled transformers should be located at least 50 feet distant from the building, or by ensuring that such building walls within 50 feet of oil-filled transformers are without openings and have a fire resistance rating of at least 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br />.
APPENDIX 9A 9A-55 REV. 18, SEPTEMBER 2016
LGS Design The main transformers are located more than 50 feet from any building. The plant services transformers are located adjacent to the circulating water pump structure, but are separated from it by free-standing 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire walls. The safeguard transformers and auxiliary transformers are located approximately 14 feet from the north side of the turbine enclosure. As described in Section 9A.2.4, the latter transformers are provided with automatically actuated deluge systems to suppress fires involving the transformers. This automatic suppression will prevent the turbine enclosure from being damaged as a result of a transformer fire. In addition, the turbine enclosure is nonsafety-related and does not contain any components that are needed in order to achieve safe shutdown of the plant.
Item 67 BTP Guideline Floor drains sized to remove expected fire fighting water without flooding safety-related equipment should be provided in areas where fixed water fire suppression systems are installed.
LGS Design Two water suppression systems are located in areas with no floor drains. A wet pipe system is located in the elevation 239 corridor (fire area 7) and localized preaction system in the 13.2 kV switchgear room, elevation 217 (fire area 2).
Although no floor drains are located in fire area 7, equipment in adjacent areas are provided with curbs, installed on 4 raised pads or the floor was sloped away from the equipment. Floor drains are also available in the adjacent battery rooms. No safety-related equipment (other than cabling) is located in fire area 7 which is also maintained as a combustible free zone, with the primary combustible loading from cables and cable tray encapsulating material. Although the UFSAR (Section 9A.5.3.7.c) states that ignition of electrical cabling in tray is extremely unlikely in the absence of a fire source, a smoke detector system provides early warning of the slow developing incipient fire that would be typical for the types of combustibles in the area. The early activation of the smoke detection system provides an audible/visual annunciation in the control room whereby operator actions are expected to mitigate the consequences of the fire before it could develop sufficiently to cause the system to actuate. If the system were to actuate due to a fire event, a flow switch provides an additional alarm to the control room requiring immediate operator actions. As discussed in response to Item 68 below, credit was taken for the opening of doors due to fire brigade response, which would allow water from hand hoses to drain into adjacent nonsafety-related areas containing floor drains.
Although no floor drains are located in fire area 2, the design feature of the installed partial preaction system minimizes the impact to equipment. This system is supervised with instrument air and incorporates a double interlock deluge valve that is maintained normally closed. Sprinkler flow is initiated only when two separate inputs are received; one from a pneumatic actuator, due to the melting of the sprinkler fusible link(s) allowing the supervised air to be released; and the other from the fire detection system that sends a signal to an electric solenoid valve. This system is installed to protect redundant cable trays encapsulated with a 1-hour fire rated material. Although the UFSAR (Section 9A.5.3.2.c) states that ignition of electrical cabling in tray is extremely unlikely in the absence of a fire source, a smoke detector system provides early warning of a fire throughout the entire area. The early activation of the smoke detection system provides an APPENDIX 9A 9A-56 REV. 18, SEPTEMBER 2016
audible/visual annunciation in the control room whereby operator actions are expected to mitigate the consequence of the fire before it could develop sufficiently to cause the system to actuate.
However, should the system actuate due to a fire, the impact to safe shutdown is mitigated by the location of redundant components outside of this area. This is further supported by MELB evaluations performed in accordance with UFSAR Section 3.6 (Reference; Item 24 of Section 9A.3.1.1, Detailed Comparison to Branch Technical Position CMEB 9.5-1, of Appendix 9A of the LGS UFSAR) that indicated that equipment was waterspray proof, or judged as not being required to ensure safe shutdown, containment integrity, or containment activity release to 10CFR50.67 limits. In addition, in accordance with Item 210 below, since floor drains were not provided in the safety-related switchgear rooms to prevent water accumulation, credit was taken for the opening of doors to drain water into areas not containing safety-related components.
Item 68 BTP Guideline Floor drains should also be provided in other areas where hand hose lines may be used if such fire fighting water could cause unacceptable damage to safety-related equipment in the area.
LGS Design All plant areas that are provided with drainage facilities have adequately sized drains to remove all the water discharged from a hand hose line. The only fire areas that are not provided with floor drains and which contain safety-related equipment that is needed for safe shutdown are the 4 kV switchgear compartments (fire areas 12 through 19), the static inverter compartments (fire areas 20 and 21), auxiliary equipment room (fire area 25), and remote shutdown room (fire area 26).
The use of hand-held fire hoses in any of these fire areas will not result in flooding that causes unacceptable damage to safety-related equipment.
A fire hose can be used in the 4 kV switchgear compartments only by bringing the hose in through a doorway from adjacent fire areas. For fire areas 12, 14, 16, and 18, the fire hose would be brought in from the generator equipment area (fire zone 113B) along the north side of the control structure. Water discharged from a hose in one of these 4 kV switchgear compartments would flow through the open doorway to fire zone 113B and drain into the floor drains in that area. For fire areas 13, 15, 17, and 19, the fire hose would be brought in from the equipment hatch corridor (fire areas 97 for Unit 1 and 110 for Unit 2) via the control structure corridor (fire area 7). Water discharged from a hose in one of these 4 kV switchgear compartments would flow through the open doorway to fire area 7 and then through the doorway to the equipment hatch corridor. The equipment hatch corridor is provided with floor drains to dispose of the fire fighting water. Since the control structure corridor does not contain any safe shutdown components, the drainage of fire fighting water through the corridor will not have an adverse effect on safe shutdown capability.
A fire hose can be used in the Unit 1 static inverter compartment (fire area 20) only by bringing the hose in from the Unit 1 cable spreading room through an open doorway. Although the Unit 2 static inverter compartment (fire area 21) contains a manual hose station, the fire brigade would fight a fire in this compartment using a hose brought in from the generator equipment area (fire zone 113B) through an open doorway. For both the Unit 1 and Unit 2 static inverter compartments, the doorway that is used for access will remain open during fire fighting activities within the compartment. Water discharged from a hose in the Unit 1 static inverter compartment would flow through the open doorway to the Unit 1 cable spreading room, whereas water discharged from a hose in the Unit 2 static inverter compartment would flow to the generator equipment area. The APPENDIX 9A 9A-57 REV. 18, SEPTEMBER 2016
cable spreading rooms and the generator equipment area are each provided with floor drains to dispose of the fire fighting water. Since the cable spreading room does not contain any safe shutdown components, the drainage of fire fighting water into the spreading room from the static inverter compartment will not have an adverse effect on safe shutdown capability.
A fire hose can be used in the remote shutdown room (fire area 26) only by bringing the hose in from the control structure stairwell through an open doorway. This stairwell hose reel is the only hose reel available to fight a fire in this area so the door will remain open during fire fighting activities within the room. Water discharged from the hose in the remote shutdown room would flow through the open doorway into the stairwell, which does not contain any safe shutdown components.
A fire hose can be used in the auxiliary equipment room (fire area 25) only by bringing the hose in from the control structure stairwell through an open doorway. This stairwell hose reel is the only hose reel available to fight a fire in this area from the primary attack route so the door will remain open during fire fighting activities within the room. Water discharged from the hose in the auxiliary equipment room would flow through the open doorway into the stairwell, which does not contain any safe shutdown components. The secondary attack route for this area is from fire area 111 through an open door on the east wall of the auxiliary equipment room. Water discharged from the hose in the auxiliary equipment room would flow through the open doorway into the fire area 111, which does not contain any safe shutdown components.
Nonsafety-related areas of the plant that adjoin safety-related areas are provided with floor drains.
As a result, fire fighting water that is discharged into the nonsafety-related areas will be disposed of through the floor drains, so that water will not accumulate on the floor and create a potential for inadvertent flooding of the adjoining safety-related areas.
Item 69 BTP Guideline Where gas suppression systems are installed, the drains should be provided with adequate seals, or the gas suppression system should be sized to compensate for the loss of the suppression agent through the drains.
LGS Design Gas suppression systems are provided for the cable spreading rooms (carbon dioxide), remote shutdown room (Halon 1301), and the raised flooring in the auxiliary equipment room (Halon 1301).
The carbon dioxide suppression system is sized to compensate for the loss of carbon dioxide through floor drains. Loss of Halon 1301 through floor drains is not possible, since the auxiliary equipment and remote shutdown rooms do not have floor drains.
Item 70 BTP Guideline Drains in areas containing combustible liquids should have provisions for preventing the backflow of combustible liquids to safety-related areas through the interconnected drain systems.
LGS Design APPENDIX 9A 9A-58 REV. 18, SEPTEMBER 2016
For the safety-related pump compartments at el 177' of the reactor enclosure, floor drains leading to the reactor enclosure floor drain sump are each provided with backflow prevention devices. The only other safety-related areas of the plant that contain significant quantities of combustible liquids are the diesel generator cells. The drains from the diesel generator cells are not interconnected with drains from other safety-related areas of the plant. The drains from each diesel generator cell are provided with traps upstream of their connection to an oil separator receiver.
The turbine enclosure contains several oil storage tanks, but the floor drains from the turbine enclosure are not interconnected with drains from safety-related areas of the plant.
Item 78 BTP Guideline Bulk gas storage (either compressed or cryogenic), should not be permitted inside structures housing safety-related equipment. Storage of flammable gas such as hydrogen should be located outdoors or in separate detached buildings so that a fire or explosion will not adversely affect any safety-related systems or equipment.
LGS Design Compressed gases are stored either outdoors or in nonsafety-related structures whenever possible. Compressed gas cylinders used for welding are stored in the construction shop (during periods of usage only) and the machine shop. Hydrogen used in cooling of the main generators is provided from the HWC system tube trailer facility located outside the protected area.
Compressed gas cylinders are stored in safety-related areas of the plant for use with three different systems: PCIG, containment combustible gas monitoring, and offgas hydrogen monitoring. The PCIG system includes compressed gas cylinders located at el 217' in the reactor enclosure. These cylinders contain nitrogen only, and therefore do not constitute a hazard with respect to fire protection. The containment combustible gas monitoring system includes compressed gas cylinders located at el 253' and el 283' in the reactor enclosure. These cylinders contain oxygen and oxygen/nitrogen mixtures, which also do not constitute a hazard with respect to fire protection, since oxygen is not a fuel gas.
The span and reagent gas bottles for the containment combustible gas monitoring systems are located outside the south wall of the Reactor Enclosures. These bottles of high purity oxygen, high purity hydrogen, 7% oxygen and 7% hydrogen are considered transportable, not bulk. The bottles are oriented with the long axis parallel to the Reactor Enclosure walls, minimizing the impact of a bottle failure when combined with the robust design of the Reactor Enclosure.
The offgas hydrogen monitoring system includes two compressed gas cylinders located at el 200' in the control structure. One of these cylinders contains nitrogen and the other contains a nitrogen/hydrogen mixture with a hydrogen content of 7%. An inadvertent release of the nitrogen/hydrogen mixture into the control structure air volume would result in immediate dilution of the hydrogen concentration to less than 4%. Since a hydrogen concentration of less than 4% in air is not combustible, the nitrogen/hydrogen mixture does not constitute a hazard with respect to fire protection.
Item 79 APPENDIX 9A 9A-59 REV. 18, SEPTEMBER 2016
BTP Guideline High pressure gas storage containers should be located with the long axis parallel to building walls.
LGS Design High pressure gas storage cylinders are stored vertically with their long axis parallel to turbine enclosure walls.
Item 80 BTP Guideline Use of compressed gases (especially flammable and fuel gases) inside buildings should be controlled.
LGS Design The usage of compressed gases for cutting and welding is limited to those activities authorized as to be outlined in the administrative procedures.
The usage of compressed fuel gases for laboratory and shop use is limited to a low pressure supply system for Bunsen burners in the radioactive chemistry laboratory in the radwaste enclosure and the instrument repair shop on the 269 foot level of the control structure.
Compressed fuel gas cylinders and gas pressure- reducing stations are installed outside of the building at a location that does not expose nuclear safety-related structures, systems, and equipment to potential damage from fire at the storage location.
Item 81 BTP Guideline The use of plastic materials should be minimized. In particular, halogenated plastics such as PVC and neoprene should be used only when substitute noncombustible materials are not available.
LGS Design The use of plastic materials within the plant has been minimized to the greatest extent practicable.
However, alternatives to plastic or elastomeric materials for electrical cable insulating systems, with an optimum balance of electrical, physical, and environmental characteristics, are not available.
Cable insulation and jacketing materials are chosen for their fire-retardant and self-extinguishing properties, such that fuel contribution to a cable fire is minimized and propagation of a fire along cables is self-limiting in the absence of an external fire hazard. The types of electrical cable insulation and jacketing used in the plant are listed in Table 9A-3.
Electrical components located throughout the plant, such as control panels, relay panels, motor control centers, and power distribution panels, contain relatively small amounts of plastic in the form of terminal blocks, relay cases, circuit breaker cases, and other small items. The use of plastic in these applications is necessary because of its electrically insulating properties.
APPENDIX 9A 9A-60 REV. 18, SEPTEMBER 2016
Item 92 BTP Guideline Safety-related cable trays of a single division that are separated from redundant divisions by a fire Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-62 REV. 18, SEPTEMBER 2016
Item 110 Security Related Information Text withheld under 10 CFR 2.390 Item 111 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-68 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 Item 112 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-69 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-70 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-71 REV. 18, SEPTEMBER 2016
Item 120 Security Related Information Text withheld under 10 CFR 2.390 Item 126 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-72 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 Item 135 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-73 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 Item 152 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-77 REV. 18, SEPTEMBER 2016
Item 155 Security Related Information Text withheld under 10 CFR 2.390 Item 158 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-78 REV. 18, SEPTEMBER 2016
Item 162 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-79 REV. 18, SEPTEMBER 2016
Item 166 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-80 REV. 18, SEPTEMBER 2016
due to the installation of an automatic sprinkler system in the cable spreading Item 167 Security Related Information Text withheld under 10 CFR 2.390 Item 170 Security Related Information Text withheld under 10 CFR 2.390 Item 173 APPENDIX 9A 9A-81 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 Item 179 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-82 REV. 18, SEPTEMBER 2016
Item 181 Security Related Information Text withheld under 10 CFR 2.390 Item 182 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-83 REV. 18, SEPTEMBER 2016
Item 189 Security Related Information Text withheld under 10 CFR 2.390 Item 190 APPENDIX 9A 9A-85 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 Item 248 Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-91 REV. 18, SEPTEMBER 2016
Security Related Information Text withheld under 10 CFR 2.390 APPENDIX 9A 9A-92 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS W ater Supplies for Fire Suppression Systems
- 1. Two separate water supplies shall be provided to furnish A C necessary water volume and pressure to the fire main loop.
- 2. Each supply shall consist of a storage tank, pump, A AC In lieu of storage tanks, the cooling tower piping, and appropriate isolation and control valves. basins of the Unit 1 and Unit 2 circulating water systems are used as the two sources of water for the fire main loop.
- 3. These supplies shall be separated so that a failure of A C See Section 9A.3.2.2.
one supply will not result in a failure of the other supply.
- 4. Each supply of the fire water distribution system shall A C The storage capacity of each cooling tower be capable of providing the maximum expected water is 7,200,000 gallons, which is well in demands for a period of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />. excess of the 387,000 gallon volume required for two hour operation of the largest sprinkler system concurrent with hose stream operation at 500 gpm.
- 5. Requirements for ensuring minimum water volume when A NA See Section 9A.3.2.2.
storage tanks are used for combined service water/fire water uses.
- 6. Requirements for other water systems used as sources of A AC See Section 9A.3.2.2 fire protection water.
Sectional Isolation Valves
- 7. Sectional isolation valves such as postindicator valves B C or key operated valves shall be installed in the fire main loop to permit isolation of portions of the main fire main loop for maintenance or repair without interrupting the entire water supply.
APPENDIX 9A 9A-93 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS Hydrant Isolation Valves
- 8. Valves shall be installed to permit isolation of outside C C hydrants from the fire main for maintenance or repair without interrupting the water supply to automatic or manual fire suppression systems.
Manual Fire Suppression
- 9. Standpipe and hose systems shall be installed so that at D AC See Section 9A.3.2.2 least one effective hose stream will be able to reach any location that contains or presents an exposure fire hazard to structures, systems, or components important to safety.
- 10. Access to permit effective functioning of the fire D C brigade shall be provided to all areas that contain or present an exposure fire hazard to structures, systems, or components important to safety.
- 11. Standpipe and hose stations shall be inside PW R D NA The primary containment is inerted with containments and BW R containments that are not inerted. nitrogen during reactor operation.
- 12. For BW R drywells, standpipe and hose stations shall be D C The hose reels located nearest the drywell placed outside the drywell with adequate lengths of hose entrances are equipped with a 100 foot to reach any location inside the drywell with an length of fire hose. To supplement this effective hose stream. hose length, a hose station equipped with enough hose to reach any location within the drywell is located near each drywell entrance.
APPENDIX 9A 9A-94 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS Hydrostatic Hose Tests
- 13. Fire hose shall be hydrostatically tested at a pressure E C of 150 psi or 50 psi above maximum fire main operating pressure, whichever is greater. Hose stored in outside hose houses shall be tested annually. Interior standpipe hose shall be tested every three years.
Automatic Fire Detection
- 14. Automatic fire detection systems shall be installed in F AC See Item 112 of Section 9A.3.1.2 all areas of the plant that contain or present an exposure fire hazard to safe shutdown or safety-related systems or components. These fire detection systems shall be capable of operating with or without offsite power.
Fire Protection of Safe Shutdown Capability
- 15. Fire damage shall be limited so that one train of G.1.a C systems necessary to achieve and maintain hot shutdown conditions from either the control room or emergency control station is free of fire damage.
- 16. Fire damage shall be limited so that systems necessary G.1.b C to achieve and maintain cold shutdown from either the control room or emergency control station can be repaired within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
- 17. Consideration of associated nonsafety circuits as G.2 (part C See Section 9A.6.1 requiring protection to ensure freedom from fire damage. of first paragraph)
- 18. Alternative means of ensuring that one train of systems G.2.a AC See Section 9A.3.2.2 necessary to achieve and maintain hot shutdown is free G.2.b of fire damage (where cables or equipment of redundant G.2.c trains are located in the same fire area).
APPENDIX 9A 9A-95 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS
- 19. Alternative means of providing fire protection inside G.2.d NA The primary containment is inerted with noninerted containments. G.2.e nitrogen during reactor operation.
G.2.f
- 20. Provision of alternative or dedicated shutdown G.3 NC See Section 9A.3.2.2 capability in certain fire areas.
Fire Brigade
- 21. Requirements for the onsite fire brigade. H C Fire Brigade Training
- 22. Requirements for training of fire brigade members. I AC See Section 9A.3.2.2.
- 23. Emergency lighting units with at least an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> battery J C See Section 9A.3.2.2.
power supply shall be provided in all areas needed for operation of safe shutdown equipment and in access and egress routes thereto.
Administrative Controls
- 24. Establishment of administrative controls to minimize K C fire hazards.
Alternative and Dedicated Shutdown Capability
- 25. The shutdown capability provided for a specific fire L.1 C area shall be able to achieve and maintain subcritical reactivity conditions in the reactor, maintain reactor coolant inventory, achieve and maintain hot shutdown conditions, achieve cold shutdown conditions within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, and maintain cold shutdown conditions thereafter.
APPENDIX 9A 9A-96 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS
- 26. During the postfire shutdown, the reactor coolant system L.1 C process variables shall be maintained within those predicted for a loss of normal ac power, and the fission product boundary integrity shall not be affected.
- 27. performance goals for the shutdown functions. L.2 C The systems and components relied on for hot shutdown and cold shutdown in the event of a fire have been selected so as to ensure that the listed goals are achieved.
- 28. The alternative shutdown capability shall be independent L.3 C of the specific fire areas.
- 29. The shutdown capability shall accommodate postfire L.3 C All systems and components relied on for conditions where offsite power is available and where hot shutdown and cold shutdown in the event offsite power is not available for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. of a fire are capable of being powered from the onsite power supplies, i.e., the station batteries and standby diesel generators.
- 30. If the capability to achieve and maintain cold shutdown L.4 C will not be available because of fire damage, the equipment and systems comprising the means to achieve and maintain the hot shutdown condition shall be capable of maintaining such conditions until cold shutdown can be achieved.
- 31. If the equipment and systems comprising the means to L.4 NA See Section 9A.3.2.2 achieve and maintain hot shutdown conditions will not be capable of being powered by both onsite and offsite electric power systems because of fire damage, an independent onsite power system shall be provided.
APPENDIX 9A 9A-97 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS
- 32. Equipment and systems comprising the means to achieve L.5 C and maintain cold shutdown conditions shall not be damaged by fire; or the fire damage to such equipment and systems shall be limited so that the systems can be made operable and cold shutdown can be achieved within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
- 33. Materials for such repairs shall be readily available L.5 C See Section 9A.3.2.2.
onsite and procedures shall be in effect to implement such repairs.
- 34. If the equipment and systems comprising the means to L.5 NA See Section 9A.3.2.2.
achieve and maintain cold shutdown conditions (and which are used prior to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after the fire) will not be capable of being powered by both offsite and onsite power systems because of fire damage, and independent onsite power system shall be provided.
- 35. Shutdown systems installed to ensure positive shutdown L.6 C capability need not be designed to meet seismic Category I criteria, single failure criteria, or other design basis accident criteria, except where required for other reasons.
- 36. Isolation of safe shutdown equipment and systems from L.7 C See Section 9A.6.1 associated nonsafety circuits.
Fire Barrier Cable Penetration Seal Qualification
- 37. Requirement Deleted M N/A The non-combustibility requirement for fire barrier penetration seals was deleted from 10 CFR 50 Appendix R as documented in the Federal Register, volume 65, No. 119, Tuesday June 20, 2000 (Doc. 00-15544).
- 38. Penetration seal designs shall be qualified by tests M C See Section 9A.3.2.2 that are comparable to tests used to rate fire barriers.
APPENDIX 9A 9A-98 REV. 18, SEPTEMBER 2016
APPENDIX R NO. APPENDIX R GUIDELINE ITEM NO. COMPARISON REMARKS Fire Doors
- 39. Acceptance criteria for tests of penetration seal M.1 C The listed criteria are included in designs. M.2 documents discussed under item 38.
M.3
- 40. Fire doors shall be self-closing or provided with N AC See Section 9A.3.2.2 closing mechanisms.
- 41. Fire doors shall be inspected semiannually to verify N AC Fire doors that are not electrically that automatic hold open, release, and closing supervised will be inspected semiannually.
mechanisms and latches are operable. For doors that are electrically supervised, this supervision provides continual verification that the doors are in the closed position.
- 42. Alternative means for ensuring that fire doors protect N.1 C See Section 9A.3.2.2 the door opening as required in case of fire. N.2 N.3 N.4
- 43. The fire brigade Leader shall have ready access to keys N C for any locked fire doors.
- 44. Areas protected by automatic total flooding gas N C The only automatic total flooding gas suppression systems shall have electrically supervised suppression systems are the halon systems self-closing fire doors or shall satisfy option 1 above. in the areas under the raised floor of the auxiliary equipment room and the remote shutdown room. There are no fire doors into these areas.
Oil Collection System for Reactor Coolant Pump
- 45. The reactor coolant pump shall be equipped with an oil 0 NA The primary containment is inerted with collection system if the containment is not inerted nitrogen during normal reactor operation.
during normal operation.
APPENDIX 9A 9A-99 REV. 18, SEPTEMBER 2016
9A.3.2.2 Explanatory Notes for Appendix R Comparison Item 3 Appendix R Guideline These supplies shall be separated so that a failure of one supply will not result in a failure of the other supply.
LGS Design The Unit 1 and Unit 2 circulating water systems are completely separate, so that any failures occurring in one system will not affect the other system. The two fire pumps are located in separate compartments within the circulating water pump structure. The connections of the fire pump discharge lines to the fire main loop are located underground to minimize the potential for damage to the piping.
Item 5 Appendix R Guideline When storage tanks are used for combined service water/fire water uses, the minimum volume for fire uses shall be ensured by means of dedicated tanks or by some physical means such as a vertical standpipe for other water service. Administrative controls, including locks for tank outlet valves, are unacceptable as the only means to ensure minimum water volume.
LGS Design Storage tanks are not used as the sources of fire protection water. As noted in items 2 and 4 of Section 9A.3.2.1, fire protection water is obtained from the cooling tower basins of the Unit 1 and Unit 2 circulating water systems, each of which has a storage capacity of 7,200,000 gallons.
Although the cooling tower basins also serve as the water sources for the service water systems, the storage capacity of the cooling tower basins is sufficient to ensure an adequate water supply for both systems (service water and fire protection water) without dedicating a certain volume of water to either system.
One of the two cooling tower basins will become unavailable as a source of fire protection water if the basin is drained to allow maintenance of it, or if the stop logs are inserted in the 96 inch circulating water lines from the cooling tower to allow work on some portion of the circulating water system. In this situation, the fire pump suction valves from the affected circulating water line will be closed in order to avoid jeopardizing the operability of the fire pumps. The unaffected circulating water lines and cooling tower will remain available to provide fire protection water to both the fire pumps.
Item 6 Appendix R Guideline Other water systems used as one of the two fire water supplies shall be permanently connected to the fire main system and shall be capable of automatic alignment to the fire main system. Pumps, controls, and power supplies in these systems shall satisfy the requirements for the main fire APPENDIX 9A 9A-100 REV. 18, SEPTEMBER 2016
pumps. The use of other water systems for fire protection shall not be incompatible with their functions required for safe plant shutdown. Failure of the other system shall not degrade the fire main system.
LGS Design The suction piping of the fire pumps is permanently connected to the 96 inch circulating water lines that supply water from the cooling towers to the main condensers. Since there are no pumps or valves located in the circulating water lines between the cooling tower basins and the connection points of the fire pump suction lines, no realignments are necessary to make the circulating water system available to provide water to the fire pumps. Therefore, there are no active failures of the circulating water system that could degrade the fire main system, and no special requirements are needed for the circulating water pumps or their associated power supplies and controls.
Item 9 Appendix R Guideline Standpipe and hose systems shall be installed so that at least one effective hose stream will be able to reach any location that contains or presents an exposure fire hazard to structures, systems, or components important to safety.
LGS Design Hose reels are located throughout the plant in areas that either contain systems and components important to safety or present an exposure fire hazard to such areas, with the exception of the spray pond pump structure. Fire suppression capability for the spray pond pump structure is provided by portable fire extinguishers.
As shown in Table 9A-1, the combustible loading in the various compartments of the spray pond pump structure is low enough that portable fire extinguishers are sufficient to extinguish any postulated fire. Those compartments that contain combustible materials are provided with fire detectors that annunciate in the control room. In addition, the spray pond pump structure is divided into two separate fire areas by a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire wall along the centerline of the structure. A postulated fire in either fire area will leave at least one method available to safely shut the plant down.
Item 18 Appendix R Guideline Except as provided for in paragraph G.3 of this section, where cables or equipment, including associated nonsafety circuits that could prevent operation or cause maloperation due to hot shorts, open circuits, or shorts to ground, of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located within the same fire area outside of primary containment, one of the following means of ensuring that one of the redundant trains is free of fire damage shall be provided:
- a. Separation of cables and equipment and associated nonsafety circuits of redundant trains by a fire barrier having a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rating. Structural steel forming a part of or APPENDIX 9A 9A-101 REV. 18, SEPTEMBER 2016
supporting such fire barriers shall be protected to provide fire resistance equivalent to that required of the barrier;
- b. Separation of cables and equipment and associated nonsafety circuits of redundant trains by a horizontal distance of more than 20 feet with no intervening combustible or fire hazards. In addition, fire detectors and an automatic fire suppression system shall be installed in the fire area; or
- c. Enclosure of cable and equipment and associated nonsafety circuits of one redundant train in a fire barrier having a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> rating. In addition, fire detectors and an automatic fire suppression system shall be installed in the fire area.
LGS Design To the greatest extent practical, redundant trains of systems necessary to achieve and maintain hot shutdown are located in different fire areas, so that the redundant trains are separated by 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers. In fire areas where this is not possible due to restrictions on equipment location and electrical cable routing, the capability to achieve hot shutdown is maintained by one of the following alternate means:
- a. Enclosing the equipment and cabling of one redundant train in a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barrier.
- b. Enclosing the equipment and cabling of one redundant train in a 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> rated fire barrier, and providing fire detection and automatic fire suppression in the fire area.
- c. Dividing a fire area into two portions so that a fire is postulated to occur in only one portion at a time. Division of a fire area is accomplished by establishing a 20 foot wide zone that is free of combustible materials, and providing a water curtain suppression system within the combustible free zone. Components and equipment of redundant trains of systems that are necessary to achieve hot shutdown are located on opposite sides of the combustible free zone. Cables that are needed for operation of one redundant train and are routed through the portion of the fire area that contains equipment of the other redundant train are enclosed in a 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated fire barrier. Fire detection capability is provided on both sides of the combustible free zone.
- d. Methods alternative to the foregoing are utilized in certain fire areas; these individual fire areas are discussed in Sections 9A.5.3, 9A.5.4, and 9A.5.5.
Item 20 Appendix R Guideline Alternative or dedicated shutdown capability and its associated circuits, independent of cables, systems or components in the area, room or zone under consideration, shall be provided:
- a. Where the protection of systems whose function is required for hot shutdown does not satisfy the requirement of paragraph G.2 of this section; or APPENDIX 9A 9A-102 REV. 18, SEPTEMBER 2016
- b. Where redundant trains of systems required for hot shutdown located in the same fire area may be subject to damage from fire suppression activities or from the rupture or inadvertent operation of fire suppression systems.
In addition, fire detection and a fixed fire suppression system shall be installed in the area, room, or zone under consideration.
LGS Design Systems whose function is required for hot shutdown are provided with protection against fire-caused damage in order to ensure that at least one of the redundant trains of these systems remains available in the event of a postulated fire and/or operation of a fire suppression system in any fire area or an alternative shutdown capability is provided to ensure that hot shutdown can be achieved. Alternative methods of shutdown are identified for fires which may occur in the control complex as discussed in Section 9A.5.3.
Components required for hot shutdown are designed so that rupture or inadvertent operation of fire suppression systems will not adversely affect the operability of these components. Where necessary, appropriate protection is provided to prevent impingement of water spray on components required for hot shutdown.
Alternative shutdown capability has been identified for fires that may occur in the control complex.
However, a fixed fire suppression system may not be provided in the area, room, or zone under consideration. Compliance with Position C.5.c of BTP CMEB 9.5-1 is discussed in Section 9A.3.1.1, Item 76.
Item 22 Appendix R Guideline Requirements for training of fire brigade members.
LGS Design Fire Protection program objectives for training fire brigade members is accomplished by using a combination of in plant areas and an off-site training facility that simulates plant physical conditions.
Drills are conducted in conformance with plant fire drill procedures.
An off-site facility enables drills to include the use of live fire conditions. These elements plus the use of breathing apparatus and full protective clothing create actual conditions that would be encountered during a real plant fire emergency. Additional drills, including backshift unannounced drills are conducted in plant areas throughout the year.
Item 23 Appendix R Guideline Emergency lighting units with at least an 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> battery power supply shall be provided in all areas needed for operation of safe shutdown equipment and in access and egress routes thereto.
APPENDIX 9A 9A-103 REV. 18, SEPTEMBER 2016
LGS Design Fixed self-contained lighting units with individual 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> battery power supplies are provided in all areas to which access may be needed for manual actuation of safe shutdown of equipment, and in access and egress routes thereto. The locations where remote actions are required for achieving safe shutdown in the event of a postulated fire are listed in Table 9A-14. Self-contained battery powered lighting units will maintain a lighting level of at least nominal 0.5 footcandle in the listed areas and in access and egress paths thereto.
In addition to the self-contained individual battery powered lighting units, there is an emergency lighting system consisting of an ac subsystem and an ac/dc subsystem. The emergency ac lighting is powered from Class IE buses which automatically transfer to the standby diesel generators upon loss of the normal power source. Emergency ac lighting is provided throughout the plant to maintain minimum lighting levels necessary for access to and operation of equipment for a period greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The general location of the emergency ac lighting and the associated lighting levels are shown on Table 9.5-12.
The emergency ac/dc lighting is normally powered from the Class IE buses. In the event of loss of the Class IE ac source, an automatic transfer switch immediately transfers this lighting to the 125 V dc non-Class IE station battery source. This power source will sustain the ac/dc lighting load on battery power for some period of time and could sustain the lights indefinitely if the diesel generator feeding the battery charger is available. All emergency ac/dc lighting fixtures are of the incandescent type. Emergency ac/dc lighting is provided throughout the plant to maintain minimum lighting levels necessary for access to and operation of equipment. The general location of the ac/dc lighting and the associated lighting levels are shown on Table 9.5-12.
The cables for both emergency lighting subsystems are routed exclusively in conduit, most of which is embedded in concrete. The locations of the power distribution buses and the cable routing for the two emergency lighting subsystems are separated to the extent practical such that a fire in any given area is not likely to cause the loss of both lighting subsystems in areas to which access is needed for the operation of safe shutdown equipment.
Item 31 Appendix R Guideline If the equipment and systems comprising the means to achieve and maintain hot shutdown conditions will not be capable of being powered by both onsite and offsite electric power systems because of fire damage, an independent onsite power system shall be provided.
LGS Design There is no postulated fire in any given fire area that could cause the simultaneous loss of both the offsite and onsite power supplies. Therefore, an additional redundant onsite power supply is not needed to ensure that safe shutdown can be achieved.
Item 33 Appendix R Guideline APPENDIX 9A 9A-104 REV. 18, SEPTEMBER 2016
Materials for such repairs shall be readily available onsite and procedures shall be in effect to implement such repairs.
LGS Design A total of six different types of repair actions may be needed in order to compensate for the effects of fire-caused damage to equipment and systems involved in achieving and maintaining cold shutdown conditions. The six types of repair actions are described below.
- a. It may be necessary to install a temporary cable in order to provide power to the ADS valves or the MSRVs and monitoring instruments at the Remote Shutdown Panel. The repair action is intended to ensure continued availability of electrical power to the ADS valves or MSRVs so that the valves can be opened by operators at the Control Room, PGCC, or Remote Shutdown Panel as necessary. In the case of power for the operation of the MSRVs from the Remote Shutdown Panel, power is also provided for the continued operation of Reactor Vessel and Suppression Pool instrumentation at the RSP. This repair action is only needed in the event of a loss of the ac power supplies to the battery chargers associated with the normal dc battery power supply. The temporary cable will be used to supply power from the Division 2 dc distribution panel to either the Division 1 or Division 3 circuit that provides power to the ADS valves or the MSRVs/RSP instruments.
- b. The design of the ESW system includes intertie lines with both the Unit 1 service water system and the Unit 2 service water system. The intertie lines that allow water in the ESW piping to return to the service water system are each provided with two redundant air-operated isolation valves in series. When a given loop of the ESW system is placed in operation, the intertie lines associated with that particular loop need to be isolated in order to prevent long-term diversion of water from the ESW system to the service water system. It may be necessary to remove the air supply tubing for individual isolation valves to ensure that at least one valve in each intertie line closes and remains closed. This action is needed only if both isolation valves in a given intertie line remain open and cannot be reclosed during the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of ESW system operation. The isolation valves affected are HV-011-043, HV-011-048, HV-011-121, HV-011-124, HV-011-125, HV-011-221, and HV-011-225.
- c. A source of compressed gas may be required to support ADS valve or MSRV operation. The gas is required to allow opening of the valves as required for depressurization and shutdown. An air jumper will be used to connect the tank of a diesel generator air start system to the primary containment instrument gas system. Another air jumper will be connected to open valve HV-059-1(2)29B and leads to valve SV-059-1(2)52A or B may be cut to open it and allow the compressed gas system to function. This repair is only required if the primary containment instrument gas system does not operate.
- d. If the Control Room or Auxiliary Equipment Room HVAC system becomes unavailable due to fire damage, it may be necessary to provide a temporary means of ventilating the affected rooms. Ventilation for the control room will need to be re-established no earlier than nine hours after the loss of HVAC. Ventilation of the auxiliary equipment room and remote shutdown panel room will need to be re-established no earlier than seven hours after the loss of HVAC. Ventilation of the 4 APPENDIX 9A 9A-105 REV. 18, SEPTEMBER 2016
kV switchgear rooms and static inverter rooms via natural convection will need to be re-established no earlier than four hours after the loss of HVAC. If necessary, a temporary ventilation capability will be established for the main control room, auxiliary equipment room and remote shutdown panel area by setting up portable fans and flexible duct-work and by opening doors to create an air flow pathway.
The portable fans will be powered from either an onsite power source or a mobile diesel generator. A diesel generator that is dedicated to this service is stored onsite in a readily accessible location. Operability of the diesel generator will be ensured by a surveillance and maintenance program. This repair is only required if the normal HVAC fails as a result of the fire.
- e. If the Spray Pond Pump Structure HVAC becomes unavailable due to fire damage, it may be necessary to provide a temporary means of ventilating the structure.
Ventilation of the structure needs to be re-established no earlier than four and a half hours after the loss of HVAC. If necessary, a repair will be performed to establish a flow path for natural convection through the structure. In addition to opening doors in the spray pond pump structure, it will be necessary to partially disassemble a damper mechanism in order to permit the damper to be opened manually. This repair is only required if the normal HVAC fails as a result of the fire.
- f. It may be necessary to utilize existing station procedures for "Loss of Shutdown Cooling" to establish a flow path for RHR shutdown cooling. Permissives to open the shutdown cooling suction line inboard and outboard isolation valves and the shutdown cooling return line outboard isolation valves are not included in the FSSD model and may not be available post-fire. Existing station procedures provide direction to Operations to establish the shutdown cooling flow path. Repair actions will operate the valves at the MCC via the use of jumpers.
For all six types of repairs described above, the tools and materials needed to perform the repairs are stored in readily accessible locations on site. Procedures governing the implementation of the repairs are in effect.
Item 34 Appendix R Guideline If the equipment and systems comprising the means to achieve and maintain cold shutdown conditions (and which are used prior to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after the fire) will not be capable of being powered by both onsite and offsite power systems because of fire damage, an independent onsite power system shall be provided.
LGS Design There is no postulated fire in any given fire area that could cause the simultaneous loss of both the offsite and onsite power supplies. Therefore, an additional redundant onsite power supply is not needed for permanent plant equipment to ensure that safe shutdown can be achieved. A mobile diesel generator is stored onsite for use in providing power to temporary fans that may be needed to provide ventilation for the control room, auxiliary equipment room, and remote shutdown room.
Item 38 APPENDIX 9A 9A-106 REV. 18, SEPTEMBER 2016
Appendix R Guideline Penetration seal designs shall be qualified by tests that are comparable to tests used to rate fire barriers.
LGS Design The designs of penetration seals in fire-rated barriers are tested to verify that the penetration seals are adequate to provide a specific degree of protection against the propagation of fire through the barriers. These tests are performed in accordance with the guidelines provided in the following documents:
- a. Institute of Electrical and Electronics Engineers, IEEE 634 (1978), "IEEE Standard Cable Penetration Fire Stop Qualification Test".
- b. NRC, Draft Regulatory Guide, "Qualification Test for Cable Penetration Fire Stops for Use in Nuclear Power Plants", (July 1979).
- c. NEL-PIA/MAERP, "Standard Method of Fire Tests of Cable and Pipe Penetration Fire Stops", (February 1976).
- d. American Nuclear Insurers, "ANI Position on Fire Stop Test Standards",
(September 1979).
Item 40 Appendix R Guideline Fire doors shall be self-closing or provided with closing mechanisms.
LGS Design With the exception of watertight doors, all fire doors are provided with one of the following two features:
- a. A self-closer to ensure that a normally closed door returns to the closed position after someone passes through it.
- b. An automatic closing mechanism to ensure that a normally open door will close if there is a fire in the vicinity of the door.
Watertight doors that also serve as fire doors cannot be provided with self-closers or automatic closing mechanisms, due to the inherent restrictions of their design and function. These watertight doors are electrically supervised or inspected daily.
Item 42 Appendix R Guideline APPENDIX 9A 9A-107 REV. 18, SEPTEMBER 2016
One of the following measures shall be provided to ensure they will protect the opening as required in case of fire:
- a. Fire doors shall be kept closed and electrically supervised at a continuously manned location;
- b. Fire doors shall be locked and inspected weekly to verify that the doors are in the closed position;
- c. Fire doors shall be provided with automatic hold open and release mechanisms and inspected daily to verify that doorways are free of obstructions; or
- d. Fire doors shall be kept closed and inspected daily to verify that they are in the closed position.
LGS Design Appropriate steps are taken to ensure that safe shutdown fire doors either are closed or will close when required in the event of a fire. One of the four measures listed above is followed for each safe shutdown fire door .
APPENDIX 9A 9A-108 REV. 18, SEPTEMBER 2016
9A.4 EVALUATION OF POTENTIAL FIRE HAZARDS 9A.4.1 SCOPE OF EVALUATION This chapter provides an evaluation of the potential for occurrence of fires within the plant and a summary of the capabilities of the existing fire protection program. This evaluation was performed for all structures that contain safety-related equipment or could affect safety-related structures by virtue of the fire hazards present.
A review of the plant was made to identify the combustible materials present, quantify the fire hazard in terms of combustible loading, and relate the potential hazard to the capabilities of the existing fire barriers and fire suppression systems. This information is presented in Table 9A-1 which lists the type of combustible materials present in each fire zone, the corresponding combustible loading, and the availability of detection and suppression equipment. Figures 9A-4 through 9A-12 show the locations of the fire zones, fire barriers, and fire suppression coverage.
9A.4.2 PROCEDURE The evaluation of fire hazards was performed using a procedure that is summarized by the following steps:
- a. For identification purposes, the various structures of the plant were divided into specific fire areas. A fire area is defined as that portion of a structure that is separated from other areas by boundaries (walls, floors, and ceilings) which are of a type of construction which is sufficient to prevent the spread of fire across the boundary, considering the combustible loading in the area. Many fire areas were further subdivided into fire zones to permit more precise identification of the locations of combustible materials, fire detection and suppression systems, and components associated with safety-related systems. The breakdown into fire zones was based on the locations of interior walls and slabs within each fire area. Fire areas are identified by a unique number, and fire zones within the same fire area are identified by a subletter. The fire area and fire zone designations are listed in Table 9A-1 "AREA-ZONE".
- b. Each fire zone was surveyed to determine the type, quantity, and distribution of combustible materials present.
- c. The combustible loading for each fire zone is determined based on the quantity of combustible materials present and the heat of combustion of each type of combustible material. The heat of combustion values used in this analysis are listed in Table 9A-2. The quantity of each type of combustible material (UNIT) is multiplied by the appropriate heat of combustion (BTU/UNIT) to determine the heat release (BTU) of each type of combustible material. The total heat release of all combustibles in the fire zone was then calculated by adding the heat release of each combustible material. To obtain the combustible loading (in BTU/ft2) for each fire zone, the total heat release (in BTU) was divided by floor area of the fire zone.
- d. The methodology for calculating fire severity (hours) is based on information presented in the 17th edition of the NFPA Handbook. The methodology uses the relationship between the calculated fire load in an area and an exposure to a fire severity which is equivalent to the standard time-temperature curve which is used APPENDIX 9A 9A-109 REV. 14, SEPTEMBER 2008
as the exposure fire in the fire resistance rating tests (ASTM E-119). The steps involved in calculating fire severity are as follows:
- 1. Calculate the fire load (BTU/ft2) for an area as stated within the methodology.
- 2. Divide the calculated fire load by 80,000 BTU/ft 2hr to obtain fire severity:
Fire Load BTU / ft2 Fire Severity 80,000 BTU / ft2 hr
- e. The clarification of the fire loading in a zone is based on the results of fire loading studies performed by the British (contained in the 17th edition of the Fire Protection Handbook). The results of the study show that the loading in an occupancy can be classified as low, moderate, or high, defined by the fire loading (BTU/ft2) of the occupancy. The classifications are defined as follows:
Low - The fire load of a zone is classified as low if it does not exceed an average of 60,000 BTU/ft2 of floor area. This loading corresponds to a fire severity of 45 minutes using the standard time temperature curve (ASTM E-119). Classification of fire load in a fire zone or area as low identifies the zone as having a fire severity below that which could be expected to be contained within a 1-hr fire rated enclosure.
Moderate - The fire load of a zone is classified as moderate if it exceeds an average of 60,000 BTU/ft2 but does not exceed an average of 140,000 BTU/ft2 of floor area. This loading corresponds to a fire severity of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, 45 minutes using the standard time temperature curve. Classification of fire load in fire zone or area as moderate identifies the zone as having a fire severity below that which could be expected to be contained within a 2-hr fire rated enclosure.
High - The fire load of a zone is classified as high if it exceeds an average of 140,000 BTU/ft2 of floor area. This loading corresponds to a fire severity in excess of 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />, 45 minutes using the standard time temperature curve. Classification of fire zone or area as high identifies the zone as having a fire severity which could be expected to be contained within a 3-hour fire rated enclosure provided the defense in depth concept has been provided for high hazard concentrations of combustibles.
No Combustibles Allowed - Item 112 of Section 9A.3.1.2, Explanatory Notes for Comparison to Branch Technical Position CMEB 9.5-1 address a deviation from the installation of automatic fire detection in certain fire zones based on the lack of combustible material located in these APPENDIX 9A 9A-110 REV. 14, SEPTEMBER 2008
areas. Therefore, in order to comply with the commitments identified in item 112 no combustible materials are allowed.
Control of Combustibles - The NRC granted a deviation on separation requirements based on fire protection defense-in-depth features and low combustible loading. In order to maintain the basis for the deviation from separation requirements, the combustible loading in these areas shall be controlled. Any increase in combustible loading shall be reviewed and approved by the licensee's fire protection engineer.
APPENDIX 9A 9A-111 REV. 14, SEPTEMBER 2008
9A.5 ANALYSIS OF CAPABILITY TO ACHIEVE SAFE SHUTDOWN 9A.5.1 METHODOLOGY This chapter provides an evaluation of the effects of postulated fires in each fire area on the ability of the operator to achieve a safe shutdown of the plant. Of the numerous possible combinations of equipment that could be used to effect a safe shutdown, four specific combinations were selected for detailed study for the purposes of this evaluation. These four shutdown methods are described in Section 9A.5.2.
In performing the safe shutdown analysis, the four shutdown methods were examined to determine the minimum equipment, control, and power requirements for operability of each method. The locations of the equipment itself and the cabling associated with the required equipment were identified with respect to the various fire areas.
Each fire area was then examined to determine which components associated with the shutdown methods, if any, would be rendered inoperable by the occurrence of a fire within the fire area. The results of the safe shutdown analysis are summarized in Sections 9A.5.3 through 9A.5.9 for each fire area.
The following assumptions were used in performing the safe shutdown analysis:
- a. No credit is taken for manual fire fighting efforts or the operation of automatic fire suppression systems. The fire is assumed to disable all equipment and electrical cabling located in the fire area, unless the fire hazard analysis demonstrates otherwise. An electrical cable tray fire is assumed not to propagate from one tray to another, since separation is provided in accordance with Regulatory Guide 1.75.
- b. Plant accidents and severe natural phenomena are not considered to occur concurrently with the postulated fire.
- c. A single active component failure is not assumed to occur concurrently with the fire.
- d. Credit is taken for reactor trip. Any fire affecting the RPS or the CRD circuitry will not prevent the reactor from being tripped. A reactor trip can be performed manually (in the control room), automatically (by the RPS logic), or by tripping the RPS power supplies (in the auxiliary equipment room).
- e. No credit is taken for proper operation or proper positioning of equipment which is not separated or protected in accordance with the guidelines of 10CFR50, Appendix R, unless the safe shutdown analyses presented in Sections 9A.5.3 and 9A.5.4 demonstrate the adequacy of the existing design. For such equipment, loss of operability or spurious operation is assumed, whichever is more conservative.
This assumption provides a worst case analysis regarding spurious signals associated with cabling failures in a fire area.
- f. For Alternative or Dedicated Shutdown Capability as defined in Chemical Mechanical Engineering Branch Technical Position (CMEBTP) 9.5-1, "Fire Protection Program", and 10CFR50, Appendix R, III, L, offsite power is assumed to be unavailable during the first 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after the onset of the fire. However, no APPENDIX 9A 9A-112 REV. 18, SEPTEMBER 2016
credit is taken for loss of offsite power in situations for which a loss of offsite power would be advantageous.
- g. For Safe Shutdown, as defined in Chemical Mechanical Engineering Branch Technical Position 9.5-1, (CMEBTP) "Fire Protection Program", and 10CFR50, Appendix R, III, offsite power is assumed to be available: except if the fire would cause a loss of offsite power.
One single spurious operation of a non-high/low pressure interface FSSD component is postulated to occur for a fire event. Any number of hot shorts, open circuits, or shorts to ground may occur, but they will result in only one single spurious actuation. Three phase hot shorts of the proper voltage and phase sequence capable of spuriously operating a device are not postulated.
In the discussions of individual fire areas contained in Sections 9A.5.3 through 9A.5.9, paragraph (c) addresses the nature of the fire that is postulated to occur in each fire area. Paragraph (c) relates to potential fires involving in situ combustible materials, and does not preclude the postulation of fires involving transient combustibles. In all cases, the safe shutdown analysis and the resulting fire protection features for each fire area are based on the potential for an exposure fire to affect all components and cables within the fire area.
Those floor slabs identified by an asterisk following the indicated fire rating in the fire area discussions contained in Sections 9A.5.3 through 9A.5.9 are discussed in Item 37 of Section 9A.3.1. Those fire doors identified in Sections 9A.5.3 through 9A.5.9 by a double asterisk (**)
following the indicated fire rating are discussed in Item 48 of Section 9A.3.1.
9A.
5.2 DESCRIPTION
OF REACTOR SHUTDOWN METHODS The following sections provide descriptions of methods that can be used for reactor shutdown and cooldown. Each of these methods includes a system by which makeup water can be added to the reactor vessel, a system by which energy can be removed from the reactor vessel, and any support systems needed to accommodate energy removal to an ultimate heat sink or to return water to its supply source.
Although the safe shutdown analysis for the various fire areas places primary emphasis on achievement of reactor shutdown using the methods described below, many alternative shutdown methods would be available. Use of safety-related and nonsafety-related systems not addressed in the safe shutdown analysis, plus manual operation of certain equipment and controls, would provide numerous combinations of systems with adequate capability to safely shut the plant down.
9A.5.2.1 Reactor Shutdown With Balance of Plant Cooling Systems Available After the turbine-generator has been tripped and all control rods inserted into the reactor core during the course of a normal shutdown and cooldown, reactor decay heat and sensible heat is removed by bypassing main steam to the condenser. Heat is removed from the condenser by the circulating water system and rejected to the atmosphere by the cooling tower. Makeup water is supplied to the reactor vessel by the condensate and feedwater system, taking suction on the condenser hotwell. When the reactor has been depressurized below a nominal 75 psig, the RHR system is initiated in the shutdown cooling mode of operation. In this mode, reactor water is circulated through the RHR heat exchangers, where it is cooled by the RHRSW system. Heat is rejected from the RHRSW system to the atmosphere by using either the cooling tower or the spray pond. The reactor vent valves are opened when reactor pressure reaches atmospheric.
APPENDIX 9A 9A-113 REV. 18, SEPTEMBER 2016
9A.5.2.2 Reactor Shutdown Without Balance of Plant Cooling Systems Available Four specific methods of achieving cold shutdown and maintaining the plant in that condition have been defined for use in analyzing the capability to safely shut the plant down in the event of a fire.
Three of the specific shutdown methods (designated as methods A, B and C) are directed from the Main Control Room and may be supplemented by local operator actions, including actions at the Remote Shutdown Panel (RSP). The fourth shutdown method (designated as method R) is directed from the RSP and may be supplemented by local operator actions. Shutdown methods A, B, C and R each include systems and components necessary to accomplish the major functions of (a) providing makeup water to the reactor vessel, (b) depressurizing the reactor vessel, and (c) removing decay heat and sensible heat from the primary containment. The systems in each shutdown method that are directly relied on for accomplishing these functions are as follows:
Shutdow Pressure Inventory Decay Heat Removal Decay Heat Removal n Method Control Control (Vessel) (Pool)
A ADS RCIC RHR in Shutdown RHR in the Suppression or Cooling Mode Pool Cooling Mode MSRV or Alternate Shutdown Cooling Mode B ADS HPCI RHR in Shutdown RHR in the Suppression or Cooling Mode Pool Cooling Mode MSRV or Alternate Shutdown Cooling Mode C ADS RHR in the RHR in Shutdown RHR in the Suppression or LPCI Mode Cooling Mode Pool Cooling Mode MSRV or Alternate Shutdown Cooling Mode R MSRV RCIC RHR (Loop A) in RHR (Loop A) in the Shutdown Cooling Mode Suppression Pool Cooling Mode The main safe shutdown components that may be relied upon to achieve safe shutdown using these methods are listed in Table 9A-4.
Method A After closure of the Main Steam Isolation Valves (MSIVs), the RCIC system is used to supply makeup water to the reactor vessel from the suppression chamber. The operation of the RCIC system also removes energy from the reactor in the form of steam to drive the RCIC turbine.
During the period in which steam is generated at a rate greater than the consumption of the RCIC system, steam is relieved to the suppression pool by automatic actuation of the Main Steam Relief Valves (MSRVs), which open when reactor pressure reaches the valve setpoint.
Heat is removed from the suppression pool by operating a loop of the RHR system in the suppression pool cooling mode. In this mode, water from the suppression pool is circulated through the RHR heat exchanger and then returned to the suppression pool. In order to initiate APPENDIX 9A 9A-114 REV. 18, SEPTEMBER 2016
operation of the shutdown cooling mode of the RHR system, it is necessary to depressurize the reactor below a nominal pressure of 75 psig. This is accomplished by using the ADS valves or MSRVs to discharge steam to the suppression pool. When the reactor has been depressurized below 75 psig, operation of the RCIC system is terminated and the RHR system is switched from the suppression pool cooling mode to the shutdown cooling mode. An alternate shutdown cooling mode has been defined and may be used with Method A instead of the standard shutdown cooling mode. This involves using the RHR pump to circulate water from the suppression pool through the RHR heat exchanger and discharge it into the reactor vessel through the LPCI injection line or through the shutdown cooling return line to the reactor recirculation loop. Water from the reactor vessel is returned to the suppression pool by opening one or more of the ADS valves or MSRVs. The water level in the reactor vessel rises to the main steam line nozzles , allowing water to partially fill the main steam lines and then flow through the open relief valve and down the MSRV discharge line to the suppression pool.
In the suppression pool cooling mode and the shutdown cooling modes, heat is removed from the RHR heat exchanger by the RHRSW system, which in turn dissipates heat at the spray pond. The shutdown cooling or alternate shutdown cooling mode of RHR will maintain the reactor in a cold shutdown condition.
Depending on the location of a fire within the plant, certain operations that are used in this shutdown method may need to be performed manually from outside the control room. The specific operations are identified in Table 9A-14.
Method B After closure of the Main Steam Isolation Valves (MSIVs), the HPCI system is used to supply makeup water to the reactor vessel from the suppression chamber. The operation of the HPCI system also removes energy from the reactor in the form of steam to drive the HPCI turbine.
During the period in which steam is generated at a rate greater than the consumption of the HPCI system, steam is relieved to the suppression pool by automatic actuation of the Main Steam Relief Valves (MSRVs), which open when reactor pressure reaches the valve setpoint.
Heat is removed from the suppression pool by operating a loop of the RHR system in the suppression pool cooling mode. In this mode, water from the suppression pool is circulated through the RHR heat exchanger and then returned to the suppression pool. In order to initiate operation of the shutdown cooling mode of the RHR system, it is necessary to depressurize the reactor below a nominal pressure of 75 psig. This is accomplished by using the ADS valves or MSRVs to discharge steam to the suppression pool. When the reactor has been depressurized below 75 psig, operation of the HPCI system is terminated and the RHR system is switched from the suppression pool cooling mode to the shutdown cooling mode. An alternate shutdown cooling mode has been defined and may be used with Method B instead of the standard shutdown cooling mode. This involves using the RHR pump to circulate water from the suppression pool through the RHR heat exchanger and discharge it into the reactor vessel through the LPCI injection line or through the shutdown cooling return line to the reactor recirculation loop. Water from the reactor vessel is returned to the suppression pool by opening one or more of the ADS valves or MSRVs. The water level in the reactor vessel rises to the main steam line nozzles , allowing water to partially fill the main steam lines and then flow through the open relief valve and down the MSRV discharge line to the suppression pool.
In the suppression pool cooling mode and the shutdown cooling modes, heat is removed from the RHR heat exchanger by the RHRSW system, which in turn dissipates heat at the spray APPENDIX 9A 9A-115 REV. 18, SEPTEMBER 2016
pond. The shutdown cooling or alternate shutdown cooling mode of RHR will maintain the reactor in a cold shutdown condition.
Depending on the location of a fire within the plant, certain operations that are used in this shutdown method may need to be performed manually from outside the control room. The specific operations are identified in Table 9A-14.
Method C After closure of the MSIVs, the reactor is depressurized by manually controlling the valves of the ADS or three or more MSRVs. The opening of these valves allows reactor steam to be discharged to the suppression pool. Makeup water is supplied to the reactor vessel from the suppression pool by operating a loop of the RHR system in the LPCI mode after reactor pressure has decreased to a nominal 295 psig. When the reactor has been depressurized below 75 psig, the RHR system is switched from the suppression pool cooling mode to the shutdown cooling mode. An alternate shutdown cooling mode has been defined and may be used with method C instead of the standard shutdown cooling mode. This involves using the RHR pump to circulate water from the suppression pool through the RHR heat exchanger and discharge it into the reactor vessel through the LPCI injection line or through the shutdown cooling return line to the reactor recirculation loop. Water from the reactor vessel is returned to the suppression pool by opening one or more of the ADS valves or MSRVs. The water level in the reactor vessel rises to the main steam line nozzles , allowing water to partially fill the main steam lines and then flow through the open relief valve and down the MSRV discharge line to the suppression pool.
In the suppression pool cooling mode and the shutdown cooling modes, heat is removed from the RHR heat exchanger by the RHRSW system, which in turn dissipates heat at the spray pond. The shutdown cooling or alternate shutdown cooling mode of RHR will maintain the reactor in a cold shutdown condition.
Depending on the location of a fire within the plant, certain operations that are used in this shutdown method may need to be performed manually from outside the control room. The specific operations are identified in Table 9A-14.
Method R - Reactor Shutdown from Outside the Control Room In the unlikely event that a fire disables or requires evacuation of the Control Room, an alternative shutdown capability is provided compliant with Position C.5.c of BTP CMEB 9.5-1.
The capability is designated as shutdown method R and is used to effect a plant shutdown directed from the Remote Shutdown Panel (RSP).
The shutdown sequence is similar to Shutdown Method A except that the methodology is centered around equipment that may be controlled from the RSP. After closure of the Main Steam Isolation Valves (MSIVs), the RCIC system is used to supply makeup water to the reactor vessel from the suppression chamber. The operation of the RCIC system also removes energy from the reactor in the form of steam to drive the RCIC turbine. During the period in which steam is generated at a rate greater than the consumption of the RCIC system, steam is relieved to the suppression pool by automatic actuation of the Main Steam Relief Valves (MSRVs), which open when reactor pressure reaches the valve setpoint. Heat is removed from the suppression pool by operating the A loop of the RHR system in the suppression pool cooling mode. In this mode, water from the suppression pool is circulated through the RHR heat APPENDIX 9A 9A-116 REV. 18, SEPTEMBER 2016
exchanger and then returned to the suppression pool. In order to initiate operation of the shutdown cooling mode of the RHR system, it is necessary to depressurize the reactor below a nominal pressure of 75 psig. This is accomplished by using the MSRVs A, C, and N to discharge steam to the suppression pool. When the reactor has been depressurized below 75 psig, operation of the RCIC system is terminated and the A loop of the RHR system is switched from the suppression pool cooling mode to the shutdown cooling mode. In the suppression pool cooling mode and the shutdown cooling modes, heat is removed from the RHR heat exchanger by the RHRSW system, which in turn dissipates heat at the spray pond. The shutdown cooling mode of RHR will maintain the reactor in a cold shutdown condition.
Depending on the location of a fire within the plant, certain operations that are used in this shutdown method may need to be performed manually from outside the control room. The specific operations are identified in Table 9A-14.
9A.5.3 SAFE SHUTDOWN ANALYSIS - CONTROL STRUCTURE 9A.5.3.1 Fire Area 1: Recombiner Compartments, Condensate Backwash Compartments, and Control Structure Water Chiller Areas (el 180'-0" and 200'-0")
Construction Rating Walls: W - Reinforced concrete 3 hr N - Reinforced concrete (part; 3 hr contains 5 ft2 of unrated metal blowout panels)
N- Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
E- Reinforced concrete 3 hr S- Reinforced concrete (part 3 hr below el 200'-0")
S- Concrete masonry unit (part 3 hr above el 200'-0", eastern half)
S- Concrete masonry unit (part None above el 200'-0", western half, contains two HVAC penetrations without fire dampers)
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Steamtight door connecting to 1.5 hr stairwell no. 7 Double steamtight doors connecting 3 hr**
to areas 89 and 102
- b. Major safety-related components in fire area:
- 1. Control structure water chillers 0AK112 and 0BK112 APPENDIX 9A 9A-117 REV. 18, SEPTEMBER 2016
- 2. Control structure chilled water circulation pumps 0AP162 and 0BP162
- c. Postulated fire in area:
- 1. Ignition of electrical cabling in cable trays. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- 2. Ignition of oil in a waste oil collection drum associated with the floor drain sump oil removal belt.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 1 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Units 1 and 2 are either:
encapsulated by qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2.
9A.5.3.2 Fire Area 2: 13 kV Switchgear Area (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N- Reinforced concrete 3 hr E - Concrete masonry unit - (part 3 hr adjacent to battery rooms)
E - Reinforced concrete - (remainder) 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Concrete masonry unit (part 3 hr adjacent to battery rooms)
W - Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
APPENDIX 9A 9A-118 REV. 18, SEPTEMBER 2016
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Door connecting to stairwell no. 7 1.5 hr Doors connecting to areas 3, 3 hr 4, 5, and 6 Double steamtight doors connecting to 3 hr**
areas 94, 107, and 113
- b. Major safety-related components in fire area:
- 1. Emergency switchgear and battery room fan cabinets OAV118 and OBV118 and associated ventilation dampers
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to the area.
A localized sprinkler system is provided in the area adjacent to the Column Line J wall, to provide protection for 1-hour encapsulated safe shutdown cables. When the temperature in the area reaches a nominal 200°F, combined with a smoke detection signal, the sprinklers will open to control the fire.
- e. Effect of fire on safe shutdown:
Fire area 2 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Units 1 and 2 are either:
encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
Equipment associated with shutdown method C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, method C will be available to shutdown Units 1 and 2.
9A.5.3.3 Fire Area 3: Unit 1 Class 1E Battery Room (el 217'-0")
APPENDIX 9A 9A-119 REV. 18, SEPTEMBER 2016
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 2 hr E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
(See Section 9A.3.1.2, Item 46)
Access: Door connecting to area 2 3 hr
- b. Major safety-related components in fire area:
- 1. Class 1E battery 1DD101 (Div. 4)
- 2. Battery charger 1DD103
- 3. Fuse box 1DD105
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detector, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 3 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
APPENDIX 9A 9A-120 REV. 18, SEPTEMBER 2016
9A.5.3.4 Fire Area 4: Unit 1 Class 1E Battery Room (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
(See Section 9A.3.1.2, Item 46)
Access: Door connecting to area 2 3 hr
- b. Major safety-related components in fire area:
- 1. Class 1E battery 1CD101 (Div. 3)
- 2. Battery charger 1CD103
- 3. Fuse box 1CD105
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detector, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 4 contains safe shutdown cables and equipment.
Cables associated with shutdown method A for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method A for Units 1 and 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
APPENDIX 9A 9A-121 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.3.5 Fire Area 5: Unit 2 Class 1E Battery Room (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
(See Section 9A.3.1.2, Item 46)
Access: Door connecting to area 2 3 hr
- b. Major safety-related components in fire area:
- 1. Class 1E battery 2DD101 (Div. 4)
- 2. Battery charger 2DD103
- 3. Fuse box 2DD105
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detector, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 5 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 APPENDIX 9A 9A-122 REV. 18, SEPTEMBER 2016
and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.3.6 Fire Area 6: Unit 2 Class 1E Battery Room (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Reinforced concrete 3 hr S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
(See Section 9A.3.1.2, Item 46)
Access: Door connecting to area 2 3 hr
- b. Major safety-related components in fire area:
- 1. Class 1E battery 2CD101 (Div. 3)
- 2. Battery charger 2CD103
- 3. Fuse box 2CD105
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 6 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 APPENDIX 9A 9A-123 REV. 18, SEPTEMBER 2016
and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.3.7 Fire Area 7: Corridor (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Doors connecting to areas 9, 11, 13, 3 hr 15, 17, and 19 Steamtight doors connecting to 3 hr**
areas 97 and 110
- b. Major safety-related components in fire area: None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. When the temperature in the area reaches a nominal 200°F, the sprinkler will open to control the fire. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to the area.
- e. Effect of fire on safe shutdown:
Fire area 7 contains safe shutdown cables but does not contain safe shutdown equipment.
Cables required to support shutdown methods A and C for Units 1 and 2 are either:
encapsulated by a qualified fire barrier, associated with equipment that have redundant APPENDIX 9A 9A-124 REV. 18, SEPTEMBER 2016
components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2.
9A.5.3.8 Fire Area 8: Unit 1 Class 1E Battery Room (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling:Reinforced concrete 3 hr Access: Door connecting to area 9 3 hr Steamtight door connecting to area 113 3 hr
- b. Major safety-related components in fire area:
- 1. Class 1E batteries 1B1D101 and 1B2D101 (Div. 2)
- 2. Battery chargers 1B1D103 and 1B2D103
- 3. Fuse box 1BD105
- 4. Class 1E dc distribution panels 1BD162 (Div. 2) and 1DD162 (Div. 4)
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 8 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-125 REV. 18, SEPTEMBER 2016
Cables associated with shutdown methods A and C for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 1 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2.
9A.5.3.9 Fire Area 9: Unit 1 Class 1E Battery Room (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Doors connecting to areas 7 3 hr and 8
- b. Major safety-related components in fire area:
- 1. Class 1E batteries 1A1D101 and 1A2D101 (Div. 1)
- 2. Battery chargers 1A1D103 and 1A2D103
- 3. Fuse box 1AD105
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors which will cause an audible/visual annunciation to register on the fire protection panels in the control APPENDIX 9A 9A-126 REV. 18, SEPTEMBER 2016
room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 9 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2.
9A.5.3.10 Fire Area 10: Unit 2 Class 1E Battery Room (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 11 3 hr Steamtight door connecting to 3 hr area 113
- b. Major safety-related components in fire area:
- 1. Class 1E batteries 2B1D101 and 2B2D101 (Div. 2)
- 2. Battery chargers 2B1D103 and 2B2D103
- 3. Fuse box 2BD105
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control APPENDIX 9A 9A-127 REV. 18, SEPTEMBER 2016
room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 10 contains safe shutdown cables and equipment.
Cables associated with shutdown methods A and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 1 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area. The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods A and C will be available to shutdown Unit 2.
9A.5.3.11 Fire Area 11: Unit 2 Class 1E Battery Room (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Reinforced concrete 3 hr S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Doors connecting to areas 7 and 10 3 hr
- b. Major safety-related components in fire area:
- 1. Class 1E batteries 2A1D101 and 2A2D101 (Div. 1)
- 2. Battery chargers 2A1D103 and 2A2D103
- 3. Fuse box 2AD105
- c. Postulated fire in area:
APPENDIX 9A 9A-128 REV. 18, SEPTEMBER 2016
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 11 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2.
9A.5.3.12 Fire Area 12: Unit 1 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr§ E - Concrete masonry unit 3 hr§ S - Concrete masonry unit 3 hr§ W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 13 3 hr Steamtight door connecting to 3 hr area 113 Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 12 from fire areas 13, 14, and 113.
APPENDIX 9A 9A-129 REV. 18, SEPTEMBER 2016
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 10A117 (Div. 3)
- 2. Class 1E dc distribution panels 1CD102 and 1CD162 (Div. 3)
- 3. Class 1E instrument ac distribution panel 10Y103 (Div. 3)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 12 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions may be taken to recover any functions that could be lost. Equipment associated with shutdown methods A, B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B and C will be available to shutdown Units 1 and 2.
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.13 Fire Area 13: Unit 1 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N- Concrete masonry unit 3 hr§ E - Concrete masonry unit 3 hr§ APPENDIX 9A 9A-130 REV. 18, SEPTEMBER 2016
S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr*
Ceiling:Reinforced concrete 3 hr Access: Doors connecting to areas 7 and 12 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 13 from fire areas 12 and 15.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 10A115 (Div. 1)
- 2. Class 1E dc distribution panels 1AD102 and 1AD162 (Div. 1)
- 3. Class 1E instrument ac distribution panel 10Y101 (Div. 1)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 13 contains safe shutdown cables and equipment.
Cables associated with shutdown methods B and C for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods B and C for Units 1 & 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2.
APPENDIX 9A 9A-131 REV. 18, SEPTEMBER 2016
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.14 Fire Area 14: Unit 1 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Concrete masonry unit 3 hr§ S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr§ Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 15 3 hr Steamtight door connecting to area 113 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 14 from fire areas 12 and 16.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 10A118 (Div. 4)
- 2. Class 1E instrument ac distribution panel 10Y104 (Div. 4)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
APPENDIX 9A 9A-132 REV. 18, SEPTEMBER 2016
Fire area 14 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2.
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.15 Fire Area 15: Unit 1 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Concrete masonry unit 3 hr§ S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr§ Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Doors connecting to areas 7 and 14 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 15 from fire areas 13 and 17.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 10A116 (Div. 2)
- 2. Class 1E instrument ac distribution panel 10Y102 (Div. 2)
- c. Postulated fire in area:
APPENDIX 9A 9A-133 REV. 18, SEPTEMBER 2016
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 15 contains safe shutdown cables and equipment.
Cables associated with shutdown methods A and C for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 1 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2.
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.16 Fire Area 16: Unit 2 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Concrete masonry unit 3 hr§ S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr§ Floor: Reinforced concrete 3 hr*
APPENDIX 9A 9A-134 REV. 18, SEPTEMBER 2016
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 17 3 hr Steamtight door connecting to area 113 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 16 from fire areas 14 and 18.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 20A118 (Div. 4)
- 2. Class 1E instrument ac distribution panel 20Y104 (Div. 4)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 16 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
APPENDIX 9A 9A-135 REV. 18, SEPTEMBER 2016
9A.5.3.17 Fire Area 17: Unit 2 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Concrete masonry unit 3 hr§ S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr§ Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Doors connecting to areas 7 and 16 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 17 from fire areas 15 and 19.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 20A116 (Div. 2)
- 2. Class 1E instrument ac distribution panel 20Y102 (Div. 2)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 17 contains safe shutdown cables and equipment.
Cables associated with shutdown methods A and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C APPENDIX 9A 9A-136 REV. 18, SEPTEMBER 2016
for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods A and C will be available to shutdown Unit 2.
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.18 Fire Area 18: Unit 2 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr§ E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr§ W - Concrete masonry unit 3 hr§ Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 19 3 hr Steamtight door connecting to area 113 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 18 from fire areas 16, 19, and 113.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 20A117 (Div. 3)
- 2. Class 1E dc distribution panel 2CD102 (Div. 3)
APPENDIX 9A 9A-137 REV. 18, SEPTEMBER 2016
- 3. Class 1E instrument ac distribution panel 20Y103 (Div. 3)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 18 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.19 Fire Area 19: Unit 2 4 kV Switchgear Compartment (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr§ E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr§ Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr APPENDIX 9A 9A-138 REV. 18, SEPTEMBER 2016
Access: Doors connecting to areas 7 and 18 3 hr Walls denoted above by the "§" symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4 kV nonsegregated phase bus ducts. These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in each of the walls indicated above.
These walls separate fire area 19 from fire areas 17 and 18.
- b. Major safety-related components in fire area:
- 1. Class 1E 4 kV switchgear 20A115 (Div. 1)
- 2. Class 1E dc distribution panel 2AD102 (Div. 1)
- 3. Class 1E instrument ac distribution panel 20Y101 (Div. 1)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 19 contains safe shutdown cables and equipment.
Cables associated with shutdown methods B and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods B and C for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2.
APPENDIX 9A 9A-139 REV. 18, SEPTEMBER 2016
- f. Deviations:
The unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts are a deviation from the requirements of CMEB 9.5-1, C.5.b. See section 9A.6.3.
9A.5.3.20 Fire Area 20: Unit 1 Static Inverter Compartment (el 254'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 2 hr E - Concrete masonry unit 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr Access: Two doors connecting to area 22 3 hr Door providing access to panel 1BD102 3 hr
- b. Major safety-related components in fire area:
- 1. 125 V dc power distribution panels 1BD102 (Div. 2) and 1DD102 (Div. 4)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, and excessive heat in the enclosure around 1BD102 will activate the heat detector, which will cause an audible/visual annunciation to register on the fire protection panels in the control room.
Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 20 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area may have redundant APPENDIX 9A 9A-140 REV. 18, SEPTEMBER 2016
components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Panel 1BD102 is enclosed by a 3-hour rated enclosure and is available for dsafe shutdown.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2.
9A.5.3.21 Fire Area 21: Unit 2 Static Inverter Compartment (el 254'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr Access: Two doors connecting to area 23 3 hr Steamtight door connecting to area 113 3 hr
- b. Major safety-related components in fire area:
- 1. 125 V dc power distribution panels 2BD102 (Div. 2) and 2DD102 (Div. 4)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 21 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-141 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods A and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods A and C will be available to shutdown Unit 2.
9A.5.3.22 Fire Area 22: Unit 1 Cable Spreading Room (el 254'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Concrete masonry unit 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Concrete masonry unit (part) 3 hr Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr Access: Two doors connecting to area 20 3 hr Doors connecting to area 23 3 hr and stairwell no. 7
- b. Major safety-related components in fire area:
- 1. Cabling for Division 1, 2, 3, and 4 safeguard equipment (in cable tray, gutter, and conduit)
- 2. Cabling for Division A1, A2, B1, and B2 of the RPS (in cable tray)
- c. Postulated fire in area:
APPENDIX 9A 9A-142 REV. 18, SEPTEMBER 2016
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. If the compartment temperature rises to 212 F, individual sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. If necessary, the fire brigade may actuate discharge of the total flooding CO2 system, using a local hand switch. HVAC system penetrations into the area will be sealed off by steam isolation dampers which close automatically when the CO2 system is actuated.
- e. Effect of fire on safe shutdown:
Fire area 22, the Unit 1 cable spreading room, contains safe shutdown cables associated with shutdown methods A, B, and C for Units 1 and 2 but does not contain safe shutdown equipment.
Alternative shutdown capabilities are available via the use of transfer/isolation and control switches on the remote shutdown panel and other local control stations as well as manual operator actions.
Offsite power cannot be credited for alternative shutdown.
Therefore, method R will be available to shutdown Units 1 and 2.
9A.5.3.23 Fire Area 23: Unit 2 Cable Spreading Room (el 254'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Concrete masonry unit 3 hr S - Reinforced concrete 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr Access: Two doors connecting to area 21 3 hr Door connecting to area 23 3 hr
- b. Major safety-related components in fire area:
- 1. Cabling for Division 1, 2, 3, and 4 safeguard equipment (in cable tray, gutter, and conduit)
APPENDIX 9A 9A-143 REV. 18, SEPTEMBER 2016
- 2. Cabling for Division A1, A2, B1, and B2 of the RPS (in cable tray)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. If the compartment temperature rises to 212 F, individual sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. If necessary, the fire brigade may actuate discharge of the total flooding CO2 system, using a local hand switch. HVAC system penetrations into the area will be sealed off by steam isolation dampers which close automatically when the CO2 system is actuated.
- e. Effect of fire on safe shutdown:
Fire area 23, the Unit 2 cable spreading room, contains safe shutdown cables associated with shutdown methods A, B, and C for Units 1 and 2 but does not contain safe shutdown equipment.
Alternative shutdown capabilities are available via the use of transfer/isolation and control switches on the remote shutdown panel and other local control stations as well as manual operator actions.
Offsite power cannot be credited for alternative shutdown.
Therefore, method R will be available to shutdown Units 1 and 2.
9A.5.3.24 Fire Area 24: Control Room and Peripheral Rooms (el 269'-0")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating Walls: N - Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
N - Reinforced concrete (part) 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
Floor: Reinforced concrete 3 hr APPENDIX 9A 9A-144 REV. 18, SEPTEMBER 2016
Ceiling: Reinforced concrete 3 hr Access: Two steamtight doors connecting to 3 hr**
area 114
- b. Safety-related components in fire area:
Safety-related control panels as listed below are located in the control room.
Unit 1 Panels 10C600 Radiation monitoring Containment combustible gas analyzer (Div. 3 & 4) 10C601 RHR (Div. 1, 2, 3, 4)
CS (Div. 1, 2, 3, 4)
MSIVs (Div. 1, 2, 3, 4)
Reactor pressure and level (Div. 1 & 2)
CAC system (Div. 1, 2, 3, 4) 10C602 RWCU (Div. 1 & 2)
Reactor recirculation system Reactor head vent valves Drywell floor and equipment drain sumps 10C603 Reactor control (Div. 1, 2, 3, 4) 10C614 NSSS temperature recorder and leak detection 10C626 ADS (Div. 1 & 3)
Suppression pool temperature monitoring (Div. 1 & 2) 10C647 HPCI (Div. 2 & 4) 10C648 RCIC (Div. 1 & 3) 10C651 Feedwater, condensate, and turbine (Div. 1, 2, 3) 10C668 Feedwater (Div. 1) 10C669 Condensate (Div. 1) 10C681 Reactor enclosure HVAC (Div. 1 & 2) 1AC661 Safeguard ac power supply (Div. 1) 1BC661 Safeguard ac power supply (Div. 2) 1CC661 Safeguard ac power supply (Div. 3)
APPENDIX 9A 9A-145 REV. 18, SEPTEMBER 2016
1DC661 Safeguard ac power supply (Div. 4) 1AC696 Containment hydrogen recombiner package "A" (Div. 1) 1BC696 Containment hydrogen recombiner package "B" (Div. 2)
Unit 2 Panels 20C600 Radiation monitoring Containment combustible gas analyzer (Div. 3 & 4) 20C601 RHR (Div. 1, 2, 3, 4)
CS (Div. 1, 2, 3, 4)
MSIVs (Div. 1, 2, 3, 4)
Reactor pressure and level (Div. 1 & 2)
CAC system (Div. 1, 2, 3, 4) 20C602 RWCU (Div. 1 & 2)
Reactor recirculation system Reactor head vent valves Drywell floor and equipment drain sumps 20C603 Reactor control (Div. 1, 2, 3, 4) 20C614 NSSS temperature recorder and leak detection 20C626 ADS (Div. 1 & 3)
Suppression pool temperature monitoring (Div. 1 & 2) 20C647 HPCI (Div. 2 & 4) 20C648 RCIC (Div. 1 & 3) 20C651 Feedwater, condensate, and turbine (Div. 1, 2, 3) 20C668 Feedwater (Div. 1) 20C669 Condensate (Div. 1) 20C681 Reactor enclosure HVAC (Div. 1 & 2) 2AC661 Safeguard ac power supply (Div. 1) 2BC661 Safeguard ac power supply (Div. 2) 2CC661 Safeguard ac power supply (Div. 3) 2DC661 Safeguard ac power supply (Div. 4)
APPENDIX 9A 9A-146 REV. 18, SEPTEMBER 2016
2AC696 Containment hydrogen recombiner package "A" (Div. 1) 2BC696 Containment hydrogen recombiner package "B" (Div. 2)
Common Panels 0AC667 ESW and RHRSW (Div. 1) 0BC667 ESW and RHRSW (Div. 2) 0CC667 ESW and RHRSW (Div. 3) 0DC667 ESW and RHRSW (Div. 4) 00C681 Control structure HVAC (Div. 3 & 4)
Spray pond pump structure HVAC (Div. 1, 2, 3, 4) 00C691 Control room normal fresh air radiation monitoring (Div. 3 & 4)
Control room emergency fresh air radiation monitoring (Div. 3 & 4)
Containment area radiation monitoring (Div. 2 & 3) 00C692 Suppression pool temperature monitoring (Div. 1 & 2)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray, gutter, or control panels. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The raceways and control panels in the control room have been designed to incorporate divisional separation in order to maintain the independence of redundant divisions of safety-related cables and electrical devices. Considering the absence of combustibles which could contribute to an exposure fire in this area, the separation is adequate to prevent an electrical fire in one division of cabling from propagating and affecting a redundant division.
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. The operator will then bring the plant fire brigade to manually extinguish the fire. An electrical fire occurring in any of the control room panels will generate substantial quantities of smoke with an acrid odor, thereby ensuring immediate detection and location of such a panel fire.
APPENDIX 9A 9A-147 REV. 18, SEPTEMBER 2016
- e. Effect of fire on safe shutdown:
Fire area 24, the main control room, contains safe shutdown cables and equipment associated with shutdown methods A, B, and C for Units 1 and 2.
Alternative shutdown capabilities are available via the use of transfer/isolation and control switches on the remote shutdown panel and other local control stations as well as manual operator actions.
Offsite power cannot be credited for alternative shutdown.
Therefore, method R will be available to shutdown Units 1 and 2.
- f. Deviations:
Carpeting installed in the Main Control Room that has been tested in accordance with NFPA or ASTM standards to assure minimum critical radiant heat flux values does not create a fire hazard in the area. See Section 9A.3.1.2, Item 190.
The peripheral rooms in the control room complex do not have automatic water suppression; however, incipient detection is provided and manual fire fighting capabilities are provided. Additionally, the entrance doors to the main control room peripheral rooms are kept open as it has been shown that they do not perform any credited barrier function. See Section 9A3,1.2, Item 179.
9A.5.3.25 Fire Area 25: Auxiliary Equipment Room (el 289'-0")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating Walls: N - Reinforced concrete (part) 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
W - Gypsum board (part adjacent 3 hr to fire area 26)
Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr Access: Door connecting to stairwell 1.5 hr no. 7 Steamtight door connecting to area 3 hr 111 Door connecting to area 26 3 hr **
- b. Major safety-related components in fire area:
APPENDIX 9A 9A-148 REV. 18, SEPTEMBER 2016
Figure 9A-21 shows the locations of all panels, consoles, and vertical boards in the auxiliary equipment room. Those panels that are associated with the shutdown methods described in Section 9A.5.2.2 are identified in the figure.
The safety-related components located in the auxiliary equipment room consist mainly of the PGCC for Unit 1 and Unit 2. The PGCC for each unit consists of vertical boards mounted on raised floor sections, with a termination cabinet located at one end of each floor section. The safety-related portions of the PGCC are identified in the following listing.
The listing applies specifically to Unit 1, but the Unit 2 PGCC is identical.
Floor Section &
Terminating Cabinet Vertical Board 10U791 & 10C617 RHR and CS (Div. 1) 10C791 10C640 RHR and CS (Div. 3) 10C621 RCIC 10C628 ADS (Div. 1) 10C631 ADS (Div. 3) 10U792 & 10C618 RHR and CS (Div. 2) 10C792 10C641 RHR and CS (Div. 4) 10C620 HPCI 10C613 Process instrumentation (Div. 2 & 4) 10U786 10C634 RRCS logic cabinet (Div. 1) 10C635 RRCS logic cabinet (Div. 2) 10U787 & 10C608 Power range neutron monitoring 10C787 10U788 & 10C619 Jet pump instrumentation 10C788 10C623 Outboard containment isolation valves 10U789 & 10C606 Startup range neutron monitoring "A" 10C789 10C609 RPS channel A 10U790 & 10C633 Startup range neutron monitoring "B" 10C790 10C611 RPS channel B 10C646 Nuclear boiler system 10U793 & 10C622 Inboard containment isolation valves 10C793 10C612 Feedwater and reactor recirculation instrumentation (Div. 1 & 3)
The PGCC and the computer facilities, both of which are located in the auxiliary equipment room, utilize raised flooring approximately 1 foot high. The raised flooring is divided into sections typically 8 feet wide and approximately 20 feet long; PGCC panels or computer equipment are mounted near the center of each floor section. The floor sections are of APPENDIX 9A 9A-149 REV. 18, SEPTEMBER 2016
all-steel construction (except for the floor plates, which are aluminum) and are each divided into four longitudinal raceways and numerous lateral raceways, each of which is totally enclosed and therefore physically isolated from adjacent raceways. To minimize the possibility of occurrence of a fire, the cabling routed in these raceways is provided with flame retardant insulation, and no other combustible material exists in the floor sections.
The highest voltages present within the floor sections are 125 V dc and 120 V ac. To prevent the spread of a postulated fire between different divisions of raceways within a floor section or between adjacent floor sections, fire stops are provided at the ends of the longitudinal raceways, at the ends of those lateral raceways which do not have end caps, in the lateral raceways where cables run from a longitudinal to a lateral raceway, and at the raceway openings at the bottom of the vertical panels. These fire stops consist of refractory material covered by silicone rubber.
The GE licensing topical report NEDO-10466-A, "Power Generation Control Complex Design Criteria and Safety Evaluation" (February 1979), describes the design concepts for the construction of the PGCC components, their arrangement within the PGCC, and the routing of interpanel cabling. The report includes test data that demonstrates the adequacy of the design with regard to fire protection. Additionally, a safety evaluation is provided which addresses NRC and industry safety guidelines and demonstrates design compliance.
A detailed comparison has been made between the design of the LGS PGCC and the design description of the generic PGCC contained in NEDO-10466-A. In all areas that could have an impact on fire protection capability (such as fire resistance, separation features, fire detection, and fire suppression), it was verified that the LGS design is either identical or equivalent to the design described in NEDO-10466-A.
The LGS design floor plates are constructed of aluminum honeycomb core bonded between aluminum sheet metal. The bottom skin is also covered by aluminum coated, steel sheet metal. This provides magnetic shielding and an optimum strength to weight ratio. The top surface of each plate is covered in an aesthetic tile that meets the following requirements:
- Flame spread rating < 25 per ASTM E84.
- Critical radiant flux > 0.45 watts /sq.cm. per NFPA 253.
Each individual floor plate is lightweight and can be easily removed by one person using the installed, recessed, quick-disconnect fasteners. The LGS design has been determined to be equivalent to the design described in NEDO-10466-A.
The RPS and UPS power distribution panels (1AY160 and 1BY160 for Unit 1; 2AY160 and 2BY160 for Unit 2), which are not safety-related, are also located in the auxiliary equipment room.
In addition to the cabling routed through the raised flooring of the auxiliary equipment room, cables associated with safety-related systems are routed in conduits, gutter, and cable tray through the space above the raised flooring.
- c. Postulated fire in area:
APPENDIX 9A 9A-150 REV. 18, SEPTEMBER 2016
Ignition of electrical cabling in cable tray, termination cabinets, raised flooring, or vertical boards. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.) An electrical fire occurring within any of these enclosures or raceways is precluded from affecting two redundant shutdown methods simultaneously, through implementation of the electrical separation criteria presented in Section 8.1.6.1.14.
An exposure fire due to transient combustibles in the auxiliary equipment room would not prevent safe shutdown from being achieved for both units of the plant. A liquid combustible spilled onto the surface of the raised floor sections would flow through the cracks between adjacent floor plates, down into the longitudinal raceways of the floor sections. The heat detectors in the floor sections would detect the fire and initiate operation of the Halon suppression system, thereby extinguishing the fire promptly.
An exposure fire involving solid transient combustibles would be extremely limited in scope and confined to a small area due to the lack of available floor space in the auxiliary equipment room. The smoke detectors below the ceiling would detect the fire promptly and annunciate in the control room. The fire brigade would then be dispatched to extinguish the fire.
- d. Consequences of fire with active fire suppression:
The raceways, raised flooring, termination cabinets, and vertical boards in the auxiliary equipment room have been designed to incorporate divisional separation in order to maintain the independence of redundant divisions of safety- related cables and electrical devices. The only fire potential in this area is ignition of cable insulation due to electrical faulting. Since the majority of the cables in the area involve low voltage instrument and control circuits, overload protection is provided, and cable insulation is flame retardant, this potential source of fire is minimal.
Particular attention has been given to minimizing the potential for fire and maximizing divisional separation in the PGCC and associated facilities. Considering the absence of combustibles which could contribute to an electrical fire in this area, the separation is adequate to prevent a fire in one division of cabling from propagating and affecting a redundant division.
Smoke detectors are located inside each of the termination cabinets and floor sections in the auxiliary equipment room to provide early warning of fires originating in these components. Additional fire detectors are located near the ceiling, to provide early warning of fires originating outside the termination cabinets and floor sections. Activation of any of the above smoke detectors will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. A local panel is provided to identify the floor section in which smoke has been detected. In the event that a fire in the floor sections is not extinguished by fire brigade response, heat detectors in the floor sections will activate the Halon extinguishing system. The Halon system is described in Section 9A.2.9.
- e. Effect of fire on safe shutdown:
Fire area 25 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-151 REV. 18, SEPTEMBER 2016
Cables required to support shutdown method C for Units 1 and 2 are either:
encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
Equipment associated with shutdown method C for Units 1 and 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, method C will be available to shutdown Units 1 and 2.
For a fire in the auxiliary equipment room, manual operator actions at the remote shutdown panel may be required. Ventilation air for the remote shutdown room is provided by duct-work that passes through the auxiliary equipment room. The air supply duct for the remote shutdown room does not contain any diffusers within the auxiliary equipment room.
However, the air exhaust duct from the remote shutdown room includes two registers that exhaust air from the auxiliary equipment room. The auxiliary equipment room HVAC system, which serves the remote shutdown room as well as the auxiliary equipment room, normally operates in the recirculation mode. When a fire in the auxiliary equipment room is confirmed, the HVAC supply and exhaust smoke dampers for the remote shutdown room are closed minimizing the leakage of smoke into the remote shutdown room. In addition, special features of the walls between the remote shutdown room and the auxiliary equipment room will minimize the infiltration of smoke into the remote shutdown room. The potential smoke infiltration paths in those walls have been sealed, including installation of gaskets on both of the access doors into the remote shutdown room.
During initial plant licensing, the NRC had a concern that a fire in the auxiliary equipment room (AER) could affect plant safe shutdown actions and habitability in the remote shutdown panel room due to smoke infiltration through the HVAC ductwork. In Limerick SER, Supplement 2, Section 9.5.1.4.2 titled "Safe Shutdown Capability," PECO committed to modify the HVAC system so that the remote shutdown panel (RSP) room is maintained at a positive pressure, thereby preventing the infiltration of smoke.
In 1989, it was determined that the AER HVAC may be disabled during the postulated AER fire, and therefore could not maintain the RSP room at a positive pressure to prevent smoke infiltration.
To address this concern and commitment to minimize smoke infiltration into the RSP room, qualified manually operated smoke dampers were installed in the HVAC ductwork and all potential smoke infiltration paths in the RSP room walls have been sealed, including installation of gaskets on both of the access doors into the remote shutdown room. The fire brigade will manually isolate the dampers after verification of a fire in the AER. The dampers can also be manually isolated during plant remote shutdown if smoke is entering the RSP room through ventilation ducts due to a fire. The NRC reviewed the final configuration prior to Unit 2 fuel loading and found it acceptable. Reference Bechtel Letter to PECO #47554, NRC Inspection Report 50-352/89-12 and 50-353/89-19, LER 1-89-039, Letter from PECO to NRC dated June 30, 1989, Letter from PECO to NRC dated June 2, 1989, and NRC Inspection Report 50-352/90-04.
APPENDIX 9A 9A-152 REV. 18, SEPTEMBER 2016
9A.5.3.26 Fire Area 26: Remote Shutdown Room (el 289'-0")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating Walls: N - Reinforced concrete (part 3 hr adjacent to stairwell no. 7)
E - Gypsum board 3 hr S - Gypsum board 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr Access: Door connecting to stairwell no. 7 3 hr Door connecting to area 25 3 hr **
- b. Major safety-related components in fire area:
- 1. Remote shutdown panel 10C201 (for Unit 1)
- 2. Remote shutdown panel 20C201 (for Unit 2)
- c. Postulated fire in area:
Ignition of electrical cabling in raceways, raised flooring, or the remote shutdown panels.
(As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.) An electrical fire occurring within these raceways or enclosures is precluded from affecting two redundant divisions of circuitry simultaneously, through implementation of the electrical separation criteria presented in Section 8.1.6.1.14.
An exposure fire due to transient combustibles in the remote shutdown room would not prevent safe shutdown from being achieved for both units of the plant. Damage to the remote shutdown panels due to an exposure fire would be either extremely limited or nonexistent because of the provisions described below.
Access to the remote shutdown panels is restricted by a woven wire partition that divides the remote shutdown room into two portions, as shown in Figure 9A-21. Access to the aisle-ways at the front and back sides of the remote shutdown panels can be gained only through locked doorways in the woven wire partition. The portion of the remote shutdown room that is outside the partition consists of only a short corridor that leads from stairwell no. 7 to fire area 25 (the auxiliary equipment room). This partition will prevent transient combustibles from being stored or transported in close proximity to the remote shutdown panels. The only portion of fire area 26 in which transient combustibles can be assumed to exist is the portion outside the partition. Any liquid combustible spilled onto the surface of the raised floor sections would flow through the cracks between adjacent floor plates, down into the raised flooring. The heat detectors in the raised flooring would detect the fire and APPENDIX 9A 9A-153 REV. 18, SEPTEMBER 2016
initiate operation of the Halon suppression system, thereby extinguishing the fire promptly.
Any solid combustible material would be located outside the woven wire partition and be of limited size due to the space constraints of the area.
- d. Consequences of fire with active fire suppression:
Smoke detectors are located within the raised flooring of the remote shutdown room to provide early warning of fires originating in the raised flooring. Additional smoke detectors are located near the ceiling, to provide early warning of fires originating above the raised flooring. Activation of any of the above smoke detectors will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. A local panel is provided to identify the floor section in which smoke has been detected. In the event that a fire in the raised flooring is not extinguished by fire brigade response, heat detectors in the raised flooring will activate the Halon extinguishing system.
The Halon system is described in Section 9A.2.9.
- e. Effect of fire on safe shutdown:
Fire area 26 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Units 1 and 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods C will be available to shutdown Units 1 and 2.
9A.5.3.27 Fire Area 27: Control Structure Fan Room (el 304'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete (parts 2 hr adjacent to stairwell nos. 7 and 8)
N - Reinforced concrete (part) 3 hr E - Reinforced concrete (part 2 hr adjacent to stairwell no. 8)
E - Reinforced concrete (part) 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
APPENDIX 9A 9A-154 REV. 18, SEPTEMBER 2016
Floor: Reinforced concrete 3 hr Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell 1.5 hr nos. 7 and 8 Double steamtight door connecting 3 hr**
to area 99 Steamtight doors connecting to areas 3 hr 99 and 112 Equipment hatch in ceiling (filled None with 95 ft2 of steel plate)
- b. Major safety-related components in fire area:
- 1. HVAC 120 V ac distribution panel 10Y206 (Div. 1), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 1AC563 (b) RHRSW radiation monitor 0AS578 (c) Control structure HVAC local panel 0CC101 (d) SGTS control panel 0AC124 (e) RERS control panel 10C207 (f) Reactor enclosure differential pressure panel 1AC253 (g) Refueling area differential pressure panel 0AC254
- 2. HVAC 120 V ac distribution panel 10Y207 (Div. 2), which serves the following components:
(a) RHRSW radiation monitor 0BS578 (b) Control structure HVAC local panel 0CC101 (c) SGTS control panel 0BC124 (d) RERS control panel 10C207 (e) Reactor enclosure differential pressure panel 1BC253 (f) Refueling area differential pressure panel 0BC254
- 3. HVAC 120 V ac distribution panel 10Y163 (Div. 3), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 1CC563 (b) DELETED (c) Control structure HVAC local panel 0AC101 (d) SGTS control panel 0CC124 (e) Containment combustible gas analyzer package 10S206 (f) ESW control valve XC-11-053A (for control structure chiller "A")
(g) Control structure chilled water control valves XC-90-042A, XC-90-043A, and XC-90-044A (h) Containment combustible gas analyzer heat tracing panel 10C902
- 4. HVAC 120 V ac distribution panel 10Y164 (Div. 4), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 1DC563 (b) DELETED (c) Control structure HVAC local panel 0BC101 APPENDIX 9A 9A-155 REV. 18, SEPTEMBER 2016
(d) SGTS control panel 0CC124 (e) Containment combustible gas analyzer 10S205 (f) ESW control valve XC-11-053B (for control structure chiller "B" (g) Control structure chilled water control valves XC-90-042B, XC-90-043B, and XC-90-044B (h) Containment combustible gas analyzer heat tracing panel 10C901
- 5. HVAC 120 V ac distribution panel 20Y207 (Div. 2), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 2BC563 (b) Control structure HVAC local panel 0CC101 (c) RERS control panel 20C207 (d) Reactor enclosure differential pressure panel 2BC253
- 6. HVAC 120 V ac distribution panel 20Y164 (Div. 4), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 2DC563 (b) Deleted (c) Containment combustible gas analyzer package 20S205 (d) Containment combustible gas analyzer heat tracing panel 20C901
- 7. Motor control center 00B131 (Div. 3), which serves the following components:
(a) HVAC 120 V ac distribution panel 10Y163 (b) Control room emergency supply air fan (0AV127) and intake heater (0AE191)
(c) Control room emergency air intake isolation valve HV-78-020C (d) Control room air supply fan cabinet (0AV116) and heater (0AE192)
(e) Control room return air fan 0AV121 (f) Auxiliary equipment room supply air fan cabinet (0AV114) and heater (0AE193)
(g) Auxiliary equipment room return air fan 0AV120 (h) Emergency switchgear and battery room supply air fan cabinet 0AV118 (i) Control structure chilled water pump (0AP162), oil pump (0AP168), pump-out compressor (0AK114)
- 8. Motor control center 00B132 (Div. 4), which serves the following components:
(a) HVAC 120 V ac distribution panel 10Y164 (b) Control room emergency supply air fan (0BV127) and intake heater (0BE191)
(c) Control room emergency air intake isolation valve HV-78-020D (d) Control room air supply fan cabinet (0BV116) and heater (0BE192)
(e) Control room return air fan 0BV121 (f) Auxiliary equipment room supply air fan cabinet (0BV114) and heater (0BE193)
(g) Auxiliary equipment room return air fan 0BV120 (h) Emergency switchgear and battery room supply air fan cabinet 0BV118 (i) Control structure chilled water pump (0BP162), oil pump (0BP168), and pump-out compressor (0BK114)
- 9. Control structure HVAC local panels 0AC101, 0BC101, 0CC101, and 0DC101 APPENDIX 9A 9A-156 REV. 18, SEPTEMBER 2016
- 10. Auxiliary equipment room supply air fan cabinets OAV114 and OBV114
- 11. Control room supply air fan cabinets OAV116 and OBV116
- 12. Auxiliary equipment room return air fans OAV120 and OBV120
- 13. Control room return air fans OAV121 and OBV121 (14) Control room emergency fresh air supply fans and filter trains OAV127 and OBV127
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190 F, the deluge valve will open and prime the preaction sprinkler system with water. At 212 F, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished. In the event of a fire in one of the control room emergency fresh air filters, a heat detector inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum.
The preaction sprinkler system in this area has been installed to provide protection against an exposure fire hazard. Other than the charcoal filters, which have their own water spray systems, electrical cable insulation and jacketing constitutes the only in situ combustible material in the fire area. The insulation and jacketing is qualified in accordance with the IEEE 383 flame test requirements, and is present in such a small quantity that it constitutes a low combustible loading. The cable trays in this area are located at approximately the same elevation as the sprinkler heads. The sprinkler heads are provided with heat collecting shields to ensure prompt actuation in the event of a fire.
- e. Effect of fire on safe shutdown:
Fire area 27 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Unit 1 and shutdown method C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Unit 1 and shutdown method C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2.
APPENDIX 9A 9A-157 REV. 18, SEPTEMBER 2016
- f. Deviations The existence of an equipment hatch with unrated steel panels in the ceiling of this fire area is acceptable because of the low combustible loadings in the areas above and below the equipment hatch, the low potential for transient combustibles in these areas, and the height of the equipment hatch above the floor (28 feet). These factors minimize the possibility of fire propagating through the equipment hatch. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the equipment hatch in the slab at elevation 332, safe shutdown capability would still be assured. Fire area 27 and fire area 28 both credit methods A and C for safe shutdown of Unit 1. Fire area 27 and fire area 28 both credit method C for safe shutdown of Unit 2.
The equipment hatch with unrated steel panels is a deviation from the requirements of CMEB 9.5-1, C.5.b. Although the steel panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
The existence of an equipment hatch with unrated steel panels in the floor of this fire area is acceptable because of the low combustible loadings in the areas above and below the equipment hatch, the low potential for transient combustibles in these areas, and the height of the equipment hatch above the floor (28 feet) of the fire area below.
These factors minimize the possibility of fire propagating through the equipment hatch.
Penetrations of piping and electrical raceway through the floor are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the equipment hatch in the slab at elevation 332', safe shutdown capability would still be assured. Fire area 27 and fire area 28 both credit methods A and C for safe shutdown of Unit 1. Fire area 27 and fire area 28 both credit method C for safe shutdown of Unit 2.
The equipment hatch with unrated steel panels is a deviation from the requirements of CMEB 9.5-1, C.5.b. Although the steel panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.3.28 Fire Area 28: SGTS Filter Compartments and Access Area (el 332'-0")
- a. Structural and architectural design features of fire area (Figure 9A-10):
Construction Rating Walls: N - Reinforced concrete None (exterior wall, also contains louver openings)
N - Reinforced concrete (parts 2 hr adjacent to stairwell nos. 7 and 8)
E - Reinforced concrete (part 2 hr adjacent to stairwell no. 8)
APPENDIX 9A 9A-158 REV. 18, SEPTEMBER 2016
E - Reinforced concrete (part 3 hr adjacent to fire area 69)
E - Reinforced concrete (part, None exterior wall)
S - Reinforced concrete 3 hr W - Reinforced concrete (part, None exterior wall)
W - Reinforced concrete (part 3 hr adjacent to fire area 46)
W - Reinforced concrete (part 2 hr adjacent to stairwell no. 7)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (roof slab) None Access: Two doors connecting to stairwell 1.5 hr no. 7 Door connecting to stairwell no. 8 1.5 hr Steamtight doors connecting to 3 hr areas 46 and 69 Equipment hatch in floor (filled None with 95 ft2 of steel plate)
- b. Major safety-related components in fire area:
- 1. SGTS filters Train A: 0AF169, 0AF170, 0AF183 Train B: 0BF169, 0BF170, 0BF183
- 2. SGTS exhaust fans 0AV109 and 0BV109
- 3. SGTS local control panels 0AC124, 0BC124, 0CC124, 0DC124
- 4. HVAC 120 V ac distribution panel 20Y206 (Div. 1), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 2AC563 (b) Control structure HVAC local panel 0CC101 (c) RERS control panel 20C207 (d) Reactor enclosure differential pressure panel 2AC253
- 5. HVAC 120 V ac distribution panel 20Y163 (Div. 3), which serves the following components:
(a) Diesel generator enclosure HVAC control panel 2CC563 (b) DELETED (c) Containment combustible gas analyzer package 20S206 (d) Containment combustible gas analyzer heat tracing panel 20C902
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-159 REV. 18, SEPTEMBER 2016
In the event of a fire in one of the SGTS filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum.
- e. Effect of fire on safe shutdown:
Fire area 28 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A , B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4 SAFE SHUTDOWN ANALYSIS - UNIT 1 REACTOR ENCLOSURE 9A.5.4.1 Fire Area 29: Suppression Chamber (el 181'-11")
Construction Rating Walls: All around - Reinforced concrete None (primary containment wall)
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (diaphragm None slab)
Access: Two access hatches connecting to None area 44
- b. Major safety-related components in fire area:
- 1. Primary containment vacuum relief valve assemblies PSV-57-137 A, B, C & D
- c. Postulated fire in area:
Since there are no combustible materials located in this area, no fire is postulated to occur.
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-160 REV. 18, SEPTEMBER 2016
Not applicable (see item (c)).
- e. Effect of fire on safe shutdown:
Fire area 29 contains safe shutdown cables and equipment.
During normal operation, primary containment is inerted. Since containment is inerted no fire is postulated.
9A.5.4.2 Fire Area 30: Drywell (el 237'-11")
Construction Rating Walls: All around - Reinforced concrete None (primary containment wall)
Floor: Reinforced concrete (diaphragm None slab)
Ceiling: Steel dome (drywell head) None Access: Equipment hatch connecting to None area 45 Equipment hatch with personnel None lock connecting to area 45
- b. Major safety-related components in fire area:
- 1. CRDM (total of 185)
- 2. MSIV (inboard, one per steam line)
- 3. MSRV (total of 14)
- 4. Drywell unit coolers (total of 8)
- 5. Inboard containment isolation valves for HPCI steam supply line, RCIC steam supply line, RWCU letdown line, and RHR shutdown cooling suction line
- c. Postulated fire in area:
- 1. Leakage of lube oil from a recirculation pump motor onto the diaphragm slab, with subsequent ignition of the oil.
- 2. Ignition of electrical cabling in cable tray, gutter or direct supported metal clad cable.
- 3. Ingnition of non-scheduled electrical cabling.
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-161 REV. 18, SEPTEMBER 2016
The possibility of a fire in the drywell is limited to periods when the reactor is shut down.
This is because the primary containment is inerted with nitrogen during reactor operation, so that the oxygen concentration is maintained below 4% by volume. This inert atmosphere will prevent fires from occurring in the primary containment during reactor operation.
In the event of a fire in the drywell while the reactor is shut down and the drywell deinerted, the operator will dispatch the plant fire brigade to el 253' in the reactor enclosure. The fire brigade will enter the drywell through the personnel airlock and will ensure extinguishment of the fire through the use of portable fire extinguishers or hoses from hose reels located outside the entrances to the drywell.
- e. Effect of fire on safe shutdown:
Fire area 30 contains safe shutdown cables and equipment.
During normal operation, primary containment is inerted. Since containment is inerted, no fire is postulated.
9A.5.4.3 Fire Area 31: Residual Heat Removal Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: NW - Reinforced concrete (primary None containment wall)
N - Reinforced concrete 3 hr E - Reinforced concrete (part None below el 201', exterior wall)
E - Reinforced concrete (part 3 hr above el 201')
S - Reinforced concrete (part None below el 198', exterior wall)
S - Reinforced concrete (part 3 hr above el 198')
W - Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling contains None 115 ft2 of unrated metal blowout panels leading to area 43)
Access: Watertight doors connecting to 3 hr**
areas 32 and 39 Steamtight doors (el 201') 3 hr connecting to areas 32 and 41
- b. Major safety-related components in fire area:
APPENDIX 9A 9A-162 REV. 18, SEPTEMBER 2016
- 1. RHR pumps 1BP202 and 1DP202
- 2. RHR heat exchanger 1BE205
- 3. RHR compartment unit coolers 1BV210, 1DV210, 1FV210, and 1HV210
- c. Postulated fire in area:
Leakage of lube oil from both RHR pump motors onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 31 contains safe shutdown cables and equipment.
Cables required to support shutdown method B for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method B for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
APPENDIX 9A 9A-163 REV. 18, SEPTEMBER 2016
Fire area 31 and the eastern portion of fire area 43 both credit method C for safe shutdown of Unit 1. The only exception is the need in the eastern portion of fire area 43 to use the Remote Shutdown Panel suppression pool temperature indicator TI-41-102.
Although main control room indication is credited for a fire which is contained within fire area 31, the RSP indicator would also be available. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 2.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.4.4 Fire Area 32: Residual Heat Removal Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: W - Reinforced concrete 3 hr NW - Reinforced concrete 3 hr NE - Reinforced concrete (primary None containment wall)
E - Reinforced concrete 3 hr S - Reinforced concrete (part None below el 198', exterior wall)
S - Reinforced concrete (part 3 hr above el 198')
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling None contains 150 ft2 of unrated metal blowout panels leading to area 43)
Access: Watertight doors connecting to 3 hr**
areas 31 and 33 Steamtight doors (el 201') 3 hr connecting to areas 31 and 42
- b. Major safety-related components in fire area:
- 1. RHR pumps 1AP202 and 1CP202
- 2. RHR heat exchanger 1AE205
- 3. RHR compartment unit coolers 1AV210, 1CV210, 1EV210, and 1GV210
- 4. ESW loop "A" valves (HV-11-041, HV-11-071, HV-11-121, and HV-11-123)
- c. Postulated fire in area:
APPENDIX 9A 9A-164 REV. 18, SEPTEMBER 2016
Leakage of lube oil from both RHR pump motors onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 32 contains safe shutdown cables and equipment.
Cables required to support shutdown method A for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method A for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 32 and the western portion of fire area 43 both credit method C for safe shutdown of Unit 1. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 2.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
APPENDIX 9A 9A-165 REV. 18, SEPTEMBER 2016
9A.5.4.5 Fire Area 33: Reactor Core Isolation Cooling Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: W - Reinforced concrete 3 hr N - Reinforced concrete 3 hr NW - Reinforced concrete 3 hr NE - Reinforced concrete (primary None containment wall)
SE - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (part 2 hr adjacent to stairwell no. 3)
S - Reinforced concrete (part, None exterior wall below el 198')
S - Reinforced concrete (part, 3 hr exterior wall above el 198')
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling None contains 25 ft2 of unrated metal blowout panels leading to area 43)
Access: Watertight doors connecting to 3 hr**
areas 32 and 34 Door connecting to stairwell no. 3 1.5 hr
- b. Major safety-related components in fire area:
- 1. RCIC pump 10P203
- 2. RCIC turbine 10S212
- 3. RCIC compartment unit coolers 1AV208 and 1BV208
- c. Postulated fire in area:
Leakage of lube oil from RCIC turbine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212 F, individual sprinkler heads will open to APPENDIX 9A 9A-166 REV. 18, SEPTEMBER 2016
control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 33 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Unit 1 and shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Unit 1 and shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 33 and the western portion of fire area 43 both credit method C for safe shutdown of Unit 1. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 2.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.4.6 Fire Area 34: High Pressure Coolant Injection Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: W - Reinforced concrete 3 hr N - Reinforced concrete 3 hr E - Reinforced concrete (primary None containment wall)
SE - Reinforced concrete 3 hr S - Reinforced concrete 3 hr APPENDIX 9A 9A-167 REV. 18, SEPTEMBER 2016
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling None contains 160 ft2 of unrated metal blowout panels leading to area 43)
Access: Watertight doors connecting to 3 hr**
areas 33 and 40
- b. Major safety-related components in fire area:
- 1. HPCI pump 10P204
- 2. HPCI turbine 10S211
- 3. HPCI compartment unit coolers 1AV209 and 1BV209
- 4. Instrument rack 10C014 (HPCI)
- c. Postulated fire in area:
Leakage of lube oil from HPCI turbine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire will activate the smoke detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190F, the deluge valve will open and prime the preaction sprinkler system with water. At 212F, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 34 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Unit 1 and shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Unit 1 and shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
- f. Deviations:
APPENDIX 9A 9A-168 REV. 18, SEPTEMBER 2016
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 34 and the western portion of fire area 43 both credit method C for safe shutdown of Unit 1. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 2.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.4.7 Fire Area 35: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: W- Reinforced concrete 3 hr N- Reinforced concrete 3 hr E- Reinforced concrete (primary None containment wall)
S- Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 40 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 1AP206
- 2. Core spray compartment unit coolers 1AV211 and 1EV211
- 3. Safeguard piping fill pump 1AP256
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire will activate the smoke detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control APPENDIX 9A 9A-169 REV. 18, SEPTEMBER 2016
room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 35 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.8 Fire Area 36: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: W - Reinforced concrete 3 hr N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr SE - Reinforced concrete (primary containment wall) None S - Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 40 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 1CP206
- 2. Core spray compartment unit coolers 1CV211 and 1GV211
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
APPENDIX 9A 9A-170 REV. 18, SEPTEMBER 2016
- e. Effect of fire on safe shutdown:
Fire area 36 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.9 Fire Area 37: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: W - Reinforced concrete 3 hr N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr SW - Reinforced concrete (primary containment wall) None Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 39 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 1DP206
- 2. Core spray compartment unit coolers 1DV211 and 1HV211
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
APPENDIX 9A 9A-171 REV. 18, SEPTEMBER 2016
Fire area 37 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.10 Fire Area 38: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N -Reinforced concrete 3 hr E -Reinforced concrete 3 hr S -Reinforced concrete 3 hr W -Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 39 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 1BP206
- 2. Core spray compartment unit coolers 1BV211 and 1FV211
- 3. Safeguard piping fill pump 1BP256
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire will activate the smoke detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
APPENDIX 9A 9A-172 REV. 18, SEPTEMBER 2016
Fire area 38 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.11 Fire Area 39: Sump Room and Passageway (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (part adjacent to stairwell no. 1) 2 hr E - Reinforced concrete (part) 3 hr S - Reinforced concrete (part adjacent to unexcavated None area),
S - Reinforced concrete (part) 3 hr W - Reinforced concrete (part, primary containment wall) None W - Reinforced concrete (part) 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight doors connecting to areas 31, 37 and 38 3 hr**
Door connecting to stairwell no. 1 1.5 hr
- b. Major safety-related components in fire area:
- 1. Containment isolation valves (HV-52-127 and HV-52-128) for suppression pool cleanup pump suction line
- 2. Instrument rack 10C076 (RHR pump "B" discharge pressure)
- 3. Instrument rack 10C078 (RHR pump "D" discharge pressure)
- c. Postulated fire in area:
- 1. Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
APPENDIX 9A 9A-173 REV. 18, SEPTEMBER 2016
- 2. Ignition of oil in a waste oil collection drum associated with the floor drain sump oil removal belt
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 39 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Unit 1 and shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Unit 1 and shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
9A.5.4.12 Fire Area 40: Corridor (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N - Reinforced concrete (part adjacent to stairwell no. 4) 2 hr N - Reinforced concrete (part) 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Reinforced concrete (part adjacent to stairwell no. 4) 2 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight doors connecting to areas 34, 35 and 36 3 hr**
Door connecting to stairwell no. 4 1.5 hr Elevator door 0.75 hr
- b. Major safety-related components in fire area:
- 1. HPCI pump discharge flow transmitters (FT-55-1N008 and FT-55-1N051)
- c. Postulated fire in area:
APPENDIX 9A 9A-174 REV. 18, SEPTEMBER 2016
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 40 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Unit 1 and shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Unit 1 and shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
9A.5.4.13 Fire Area 41: Reactor Enclosure Cooling Water Equipment Area (el 201'-0")
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (part adjacent to stairwell no. 1) 2 hr E - Reinforced concrete (part) 3 hr E - Reinforced concrete (part adjacent to unexcavated None area)
S - Reinforced concrete 3 hr W - Reinforced concrete (part) 3 hr W - Reinforced concrete (primary containment wall) None Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (one portion of the ceiling slab, 3 hr*
covering an area of 10 ft2, has a reduced concrete thickness that varies between 4.5 inches and 9.0 inches.)
Access: Door connecting to stairwell no. 1 1.5 hr Door connecting to area 31 3 hr APPENDIX 9A 9A-175 REV. 18, SEPTEMBER 2016
- b. Major safety-related components in fire area:
- 2. Suppression chamber pressure transmitter (PT-57-101)
- 3. ESW loop "B" valves (HV-11-044, HV-11-074, HV-11-124, HV-11-125, HV-11-126, HV-11-127 and HV-11-128)
- 4. HVAC unit cooler control panels 1BC208 and 1DC208
- 5. Motor control center 10B218, which serves the following components:
(a) RHR loop "D" valves (b) RHR compartment unit coolers 1DV210 and 1HV210 (c) Core spray loop "B" valves (d) Core spray compartment unit coolers 1DV211 and 1HV211 (e) RHRSW outlet valve from RHR "B" heat exchanger (HV-51-1F068B)
(f) Drywell unit cooler fans 1D2V212 and 1F2V212 (g) Containment hydrogen recombiner 1BS403 and associated valves
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190 F, the deluge valve will open and prime the preaction sprinkler system with water. At 212 F, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 41 contains safe shutdown cables and equipment.
Cables required to support shutdown method B for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method B for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
APPENDIX 9A 9A-176 REV. 18, SEPTEMBER 2016
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
9A.5.4.14 Fire Area 42: Safeguard System Access Area (el 201'-0")
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete (part adjacent to stairwell no. 4) 2 hr N - Reinforced concrete (part) 3 hr E - Reinforced concrete 3 hr SE - Reinforced concrete (primary containment wall) None S - Reinforced concrete (part adjacent to stairwell no. 3) 2 hr S - Reinforced concrete (part) 3 hr W - Reinforced concrete (part) 3 hr W - Reinforced concrete (part adjacent to stairwell no. 4) 2 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (One portion of the ceiling slab, 3 hr*
covering an area the ceiling slab, covering an area of 10 ft2, has a reduced concrete thickness that varies between 4.5 inches and 9.0 inches.)
Access: Elevator door 0.75 hr Doors connecting to stairwell nos. 3 and 4 1.5 hr Door connecting to area 32 3 hr Watertight door connecting to area 75 3 hr**
- b. Major safety-related components in fire area:
- 4. Instrument rack 10C017 (RCIC)
APPENDIX 9A 9A-177 REV. 18, SEPTEMBER 2016
- 5. RCIC turbine exhaust pressure transmitters (PT-50-1N055C&G)
- 7. Instrument rack 10C075 (RHR pump "A" discharge pressure)
- 8. Instrument rack 10C077 (RHR pump "C" discharge pressure)
- 9. HVAC unit cooler control panels 1AC208 and 1CC208
- 10. Motor control center 10B217, which serves the following components:
(a) RHR loop "C" valves (b) RHR compartment unit coolers 1CV210 and 1GV210 (c) Core spray pump suction valve (HV-52-1F001C)
(d) Core spray compartment unit coolers 1CV211 and 1GV211 (e) RHRSW outlet valve from RHR "A" heat exchanger (HV-51-1F068A)
(f) Drywell unit cooler fans 1C2V212 and 1G2V212 (g) Containment hydrogen recombiner 1AS403 and associated valves
- c. Postulated fire in Area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190F, the deluge valve will open and prime the preaction sprinkler system with water. At 212F, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 42 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 1 and shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown method C for Unit 1 and shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, method C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
9A.5.4.15 Fire Area 43: Safeguard System Isolation Valve Area (el 217'-0")
APPENDIX 9A 9A-178 REV. 18, SEPTEMBER 2016
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (part) 3 hr S - Reinforced concrete (exterior wall, contains 150 ft2 None of unrated blowout panels)
W - Concrete masonry unit 3 hr Interior boundary - Reinforced concrete (primary None containment wall Floor: Reinforced concrete (contains 450 ft2 of unrated None metal blowout panels from areas 31, 32, 33, and 34)
Ceiling: Reinforced concrete 3 hr*
Access: Two steamtight doors connecting to area 44 3 hr
- b. Major safety-related components in fire area:
- 1. HPCI steam line containment isolation valves (HV-55-1F003 and HV-55-1F100)
- 2. RCIC steam line containment isolation valves (HV-49-1F008 and HV-49-1F076)
- 3. RHR system valves:
(a) HV-51-1F008 (shutdown cooling suction containment isolation)
(b) HV-51-1F015A&B (shutdown cooling return containment isolation)
(c) HV-51-1F047A&B (heat exchanger inlet)
(d) HV-C-51-1F048A&B (heat exchanger bypass)
(e) HV-51-1F023 (head spray containment isolation )
- 4. CAC containment isolation valves (HV-57-109, HV-57-121, HV-57-123, HV-57-124, HV-57-131, HV-57-135, HV-57-147, HV-57-163, and HV-57-164)
- 5. PCIG containment isolation valves (HV-59-102, HV-59-129A, HV-59-129B, HV-59-131, HV-59-135, HV-59-151A, and HV-59-151B)
- 6. HPCI system leakage detection temperature elements
- 7. RCIC system leakage detection temperature elements
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-179 REV. 18, SEPTEMBER 2016
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 43 is divided into an eastern (43E) and a western (43W) portion through the establishment of a 20 foot wide zone that is free of combustible materials.
43E The eastern portion of fire area 43 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods B and C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 43.
43W The western portion of fire area 43 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 1 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that APPENDIX 9A 9A-180 REV. 18, SEPTEMBER 2016
are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, method C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2, for a fire in the western half of fire area 43.
- f. Deviations:
Fire area 43 is divided into a western portion and an eastern portion through the establishment of a 20 foot wide zone that is free of combustible materials. This combustible-free zone was created by using 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> rated fire barriers to enclose the cable trays that pass through the zone.
Several valves associated with the credited safe shutdown methods are located in fire area 43. Valves performing active, credited, redundant functions are located on opposite sides of fire area 43 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray. The fire barriers that enclose the portions of the cable trays that are within the combustible-free zone, eliminate the potential for a postulated fire to propagate through the combustible-free zone within the cable trays. The in situ combustible loading in fire area 43 is low. The potential for transient combustibles to exist in the space between credited, redundant valves is severely restricted by the arrangement of fire area 43 and the locations of commodities within it. The space between the credited, redundant equipment is relatively narrow and contains a high concentration of pipes and pipe supports. These obstructions effectively prevent the introduction of significant quantities of combustible materials into this space. The factors discussed above preclude the occurrence of a fire, involving either in situ combustibles or transient combustibles, that could simultaneously affect credited, redundant equipment.
The measures described above for physical separation and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 43.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
The existence of unrated metal panels in the floor of this fire area is acceptable because the low combustible loadings in the areas above and below the panels. Penetrations of piping and electrical raceway through the floor are provided with 3- hour rated seals.
Unrated blowout panels exist in the south wall of the fire area that release to the outside of the reactor enclosure, which has no adjoining tire area impacts.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the floor at elevation 217, safe shutdown capability would still be assured. Fire area 43, 31, 32, 33, and 34 all credit method C for safe shutdown of Unit 1. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 2.
APPENDIX 9A 9A-181 REV. 18, SEPTEMBER 2016
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.4.16 Fire Area 44: Safeguard System Access Area (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete (parts adjacent to stairwell 2 hr nos. 1 and 4)
N - Reinforced concrete (part) 3 hr E - Reinforced concrete (part adjacent to stairwell no. 2 hr 1)
E - Reinforced concrete (part) 3 hr S - Reinforced concrete (part adjacent to stairwell no. 2 hr 3)
S - Reinforced concrete (part adjacent to fire area 124) 3 hr S - Reinforced concrete (part, exterior wall) None W - Reinforced concrete (part adjacent to stairwell 2 hr nos. 3 and 4)
W - Reinforced concrete (part) 3 hr Interior boundary (part) - Reinforced concrete and 3 hr concrete masonry unit walls Interior boundary (part) - Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete (Two portions of the floor slab, 3 hr*
each of which covers an area of 10 ft2, have a reduced concrete thickness that varies between 4.5 inches and 9.0 inches.)
Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell nos. 1, 3, and 4 1.5 hr Two steamtight doors connecting to area 43 3 hr Missile-resistant door connecting to area 76 3 hr**
Equipment airlock door None Elevator door 0.75 hr Suppression chamber access hatches None Equipment hatchway in ceiling (200 ft2 opening; None protected by water curtain suppression system)
- b. Major safety-related components in fire area:
- 1. Core spray full flow test recirculation valves (HV-52-1F015A&B)
- 2. CAC containment isolation valves (HV-57-104, HV-57-105, HV-57-112, HV-57-118, and HV-57-162)
APPENDIX 9A 9A-182 REV. 18, SEPTEMBER 2016
- 3. RHR system valves:
(a) HV-51-125A&B (containment isolation for recirculation to suppression chamber)
(b) HV-51-1F027A&B (containment isolation for suppression chamber spray)
(c) HV-51-1F010A&B (loops C and D recirculation to suppression chamber)
(d) HV-51-1F024A&B (loops A and B recirculation to suppression chamber)
- 4. Instrument racks 10C001 (core spray loop A) and 10C019 (core spray loop B)
- 5. Instrument racks 10C015, 10C025, 10C041, and 10C042 (main steam and reactor recirculation flow)
- 6. Instrument racks 10C016 and 10C036 (HPCI)
- 7. Instrument racks 10C035 and 10C038 (RCIC)
- 8. Instrument racks 10C006, 10C009, 10C010, and 10C022 (reactor recirculation system pressure and jet pump flow)
- 9. RHR flow transmitters (FT-51-1N015A,B,C&D and FT-51-1N052A,B,C&D)
- 10. Motor control center 10B211, which serves the following components:
(a) RHR loop "A" valves (b) RHR compartment unit coolers 1AV210 and 1EV210 (c) Core spray loop "A" valves (d) Core spray compartment unit coolers 1AV211 and 1EV211 (e) RHRSW inlet valve to RHR "A" heat exchanger (HV-51-1F014A)
(f) RHR shutdown cooling suction inboard isolation valve (HV-51-1F009)
(g) RCIC compartment unit coolers 1AV208 and 1BV208 (h) RWCU inboard isolation valve (HV-44-1F001)
(i) Main steam drain line inboard isolation valve (HV-41-1F016)
(j) Drywell unit cooler fans 1A1V212, 1C1V212, 1E1V212, and 1G1V212
- 11. Motor control center 10B212, which serves the following components:
(a) RHR loop "B" valves (b) RHR compartment unit coolers 1BV210 and 1FV210 (c) Core spray loop "B" valves (d) Core spray compartment unit coolers 1BV211 and 1FV211 (e) RHRSW inlet valve to RHR "B" heat exchanger (HV-51-1F014B)
(f) RHR shutdown cooling return isolation valve (HV-51-1F015A)
(g) Reactor recirculation pump suction valve (HV-43-1F023B)
(h) HPCI compartment unit coolers 1AV209 and 1BV209 (i) Drywell unit cooler fans 1B1V212, 1D1V212, 1F1V212, and 1H1V212
- 12. Motor control center 10B215, which serves the following components:
(a) RHR loop "A" valves (b) RCIC system valves (c) Deleted (d) Suppression pool cleanup pump suction isolation valve (HV-52-127)
(e) Drywell pressure tap isolation valve (HV-42-147A)
APPENDIX 9A 9A-183 REV. 18, SEPTEMBER 2016
(f) Drywell floor drain and equipment drain containment isolation valves (HV-61-112 and HV-61-132)
- 13. Motor control center 10B216, which serves the following components:
(a) RHR loop "B" valves (b) HPCI system valves (c) Deleted (d) Suppression pool cleanup pump isolation valve (HV-52-128)
(e) Drywell pressure tap isolation valve (HV-42-147B)
(f) Suppression pool level tap isolation valves (HV-55-120 and HV-55-121)
(g) RHR shutdown cooling suction outboard isolation valve (HV-51-1F008)
(h) RWCU outboard isolation valve (HV-44-1F004)
(i) Main steam drain line outboard isolation valve (HV-41-1F019)
- 14. Dc motor control center 10D201, which serves the following components:
(a) RCIC system (b) Div. 1 RPS and UPS static inverter
- 15. Dc motor control center 10D202, which serves the HPCI system
- 16. Dc motor control center 10D203, which serves the following components:
(a) HPCI system (b) Div. 2 RPS and UPS static inverter
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the fire occurs within the coverage area of one of the two preaction sprinkler systems in this fire area, the system will provide automatic suppression of the fire. When the compartment temperature rises to 190 F, the deluge valve will open and prime the preaction sprinkler system with water. At 212 F, individual fusible link sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 44 is divided into an eastern (44E) and a western (44W) portion through the establishment of two 20 foot wide zones.
44E The eastern portion of fire area 44 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-184 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods A and C for Units 1 and 2 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2, for a fire in the eastern half of fire area 44.
44W The western portion of fire area 44 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, method C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2, for a fire in the western half of fire area 44.
- f. Deviation:
A 20 foot wide zone that is free of combustibles was created at two locations in fire area 44 by using a galvanized steel cable tray enclosure system to cover the cable trays that pass through the zone. This non-combustible configuration together with the enclosure end seals will prevent fire propagation across the combustible free zone. A fixed suppression system of the water curtain-type is located within each combustible-free zone to provide assurance that a postulated fire due to transient combustibles can be prevented from propagating through the combustible-free zones. The two combustible-free zones, one located in the southwest quadrant of the fire area and one located in the northeast quadrant of the fire area, divide fire area 44 into a western portion and an eastern portion.
APPENDIX 9A 9A-185 REV. 18, SEPTEMBER 2016
Several components associated with the credited safe shutdown methods are located in fire area 44. Components performing active, credited, redundant functions are located on opposite sides of fire area 44 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray up to the boundaries of the combustible free zone.
The locations of preaction sprinkler systems and water curtain suppression systems in fire area 44 are shown in Figure 9A-6.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 44.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.5.7.
9A.5.4.17 Fire Area 45: CRD Hydraulic Equipment Area and Neutron Monitoring System Area (el 253'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete (parts adjacent to stairwell nos. 1 2 hr and 4)
N - Reinforced concrete (part) 3 hr E - Reinforced concrete (part adjacent to stairwell no. 1) 2 hr E - Reinforced concrete (part) 3 hr S - Reinforced concrete (part adjacent to stairwell no. 3) 2 hr S - Reinforced concrete (part, exterior wall) None W - Reinforced concrete (parts adjacent to stairwell nos. 2 hr 3 and 4)
W - Reinforced concrete (part) 3 hr Interior boundary (part adjacent to main steam tunnel) - 3 hr Reinforced concrete Interior boundary (part) - Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell nos. 1, 3, and 4 1.5 hr Elevator door 0.75 hr Drywell access hatches None Watertight door connecting to area 46 3 hr**
Equipment hatchways in floor and protected by water None curtain suppression systems)
- b. Major safety-related components in fire area:
APPENDIX 9A 9A-186 REV. 18, SEPTEMBER 2016
- 1. DCWS valves HV-87-122, HV-87-123, HV-87-128, and HV-87-129 (supply and return line containment isolation)
- 2. CRD master control station
- 3. CRD hydraulic control units
- 4. Containment combustible gas analyzer sample package 10S206
- 5. Load center 10B203 (Div. 3)
- 6. Deleted
- 7. Instrument racks 10C004, 10C005, 10C026, and 10C027 (RPV instrumentation and LPCI injection valve P transmitters)
- 8. SLCS injection line containment isolation valves (HV-48-1F006A&B)
- 9. Motor control center 10B223, which serves the following components:
(a) LPCI injection containment isolation valve (HV-51-1F017C)
(b) RHR loop "C" minimum flow recirculation isolation valve (HV-51-105A)
(c) RCIC system valves (d) SLCS pump 1AP208 (e) SLCS injection outboard isolation valve (HV-48-1F006)
(f) Drywell pressure tap isolation valve (HV-42-147C)
(g) Drywell unit cooler fans 1A2V212 and 1E2V212 (h) Reactor recirculation pump cooling water isolation valves (HV-13-106 and HV-13-107)
- 10. Motor control center 10B224, which serves the following components:
(a) LPCI injection containment isolation valve (HV-51-1F017D)
(b) RHR loop "D" minimum flow recirculation isolation valve (HV-51-105B)
(c) HPCI system valves (d) SLCS pump 1BP208 (e) Drywell pressure tap isolation valve (HV-42-147D)
(f) Reactor recirculation pump cooling water source select valves (HV-13-108, HV-13-109, HV-13-110, and HV-13-111)
(g) Drywell unit cooler fans 1B2V212 and 1H2V212
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the fire occurs within the coverage area of the preaction sprinkler system in this fire area, the system will provide automatic suppression of the fire. When the compartment APPENDIX 9A 9A-187 REV. 18, SEPTEMBER 2016
temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual fusible link sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 45 is divided into an eastern (45E) and a western (45W) portion through the establishment of a 20 foot wide zone that is free of combustible materials.
45E The eastern portion of fire area 45 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 1 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods B and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods B and C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, method C will be available to shutdown Unit 1 and methods B and C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 45.
45W The western portion of fire area 45 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods B and C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
APPENDIX 9A 9A-188 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2, for a fire in the western half of fire area 45.
A postulated fire in the vicinity of the reactor vessel instrumentation reference leg backfill system could adversely affect reactor vessel water level indication due to reference leg density changes caused by an increase in water temperature. Since there are no fire initiators in close proximity to the backfill system tubing, administratively controlled combustible free zones, throughout the locations of the backfill system will preclude any adverse effect on level indication, due to fire, prior to annunciation in the main control room.
Following annunciation in the main control room, the backfill system will be administratively isolated from the reference legs.
- f. Deviation A 20 foot wide zone that is free of combustibles was created by ensuring, by analysis, that there are no intervening combustibles which could provide a path for fire propagation through the combustible-free zone. A fixed suppression system of the water curtain-type is located within the combustible-free zone to provide assurance that a postulated fire due to transient combustibles can be prevented from propagating through the combustible-free zone. The combustible-free zone divides the fire area into a western portion and an eastern portion.
Several components associated with the credited safe shutdown methods are located in fire area 45. Components performing active, credited, redundant functions are located on opposite sides of fire area 45 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray up to the boundaries of the combustible free zone. The locations of the preaction sprinkler system and the water curtain suppression system in fire area 45 are shown in Figure 9A-7.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 45.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
If the fire occurs within the coverage area of the wet pipe sprinkler systems in this fire area, the systems will provide automatic suppression of the fire. When the compartment temperature rises to 212F, individual fusible link sprinklers will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
APPENDIX 9A 9A-189 REV. 18, SEPTEMBER 2016
9A.5.4.18 Fire Area 46: Main Steam Tunnel (el 253'-0")
Construction Rating Walls: N - Reinforced concrete (contains 188 ft2 of unrated 3 hr metal blowout panels)
E - Reinforced concrete 3 hr S - Reinforced concrete (part , primary containment wall) None S - Reinforced concrete (part) 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (part at el 295'-3") 3 hr*
Reinforced concrete (part at el 365' roof slab) None Access: Watertight door connecting to area 45 3 hr**
Steamtight doors connecting to areas 28 and 47 3 hr
- b. Major safety-related components in fire area:
- 1. Main steam line outboard containment isolation valves (HV-41-1F028 A,B,C&D)
- 2. Feedwater line outboard containment isolation valves (HV-41-1F032A&B and HV-41-1F074A&B)
- 3. Main steam drain line outboard containment isolation valve (HV-41-1F019)
- 4. RCIC injection valve (HV-49-1F013)
- 5. Steam line radiation sensors (RE-41-1N006A,B,C&D)
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the plant fire brigade will be dispatched to el 253' and/or el 283' in the reactor enclosure and will enter the main steam tunnel through doors at those elevations. The fire brigade will extinguish the fire using portable fire extinguishers or hoses from hose stations located outside the entrances to the main steam tunnel.
- e. Effect of fire on safe shutdown:
Fire area 46 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-190 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods B and C for Unit 1 and shutdown methods A, B, and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Unit 1 and shutdown methods A, B, and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Unit 1, and methods A, B, and C will be available to shutdown Unit 2.
9A.5.4.19 Fire Area 47: RWCU Compartments, FPCC Compartment, and General Equipment Area (el 283'-0" and el 295'-3")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating Walls: N - Reinforced concrete (parts adjacent to stairwell nos. 2 hr 1 and 4)
N - Reinforced concrete (part) 3 hr E - Reinforced concrete (part adjacent to stairwell no. 1) 2 hr E - Reinforced concrete (part) 3 hr S - Reinforced concrete (part adjacent to stairwell no. 3) 2 hr S - Reinforced concrete (part, exterior wall) None W - Reinforced concrete (parts adjacent to stairwell nos. 2 hr 3 and 4)
W - Reinforced concrete (part) 3 hr Interior boundary (east and west walls of area 46) - 3 hr Reinforced concrete Interior boundary (primary containment wall) - Reinforced None concrete Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell nos. 1, 3, and 4 1.5 hr Steamtight door connecting to area 46 3 hr Elevator door 0.75 hr Equipment hatchways in floor and ceiling (200 ft2 None openings; protected by water curtain suppression systems)
- b. Major safety-related components in fire area:
- 1. Containment hydrogen recombiner packages 1AS403 and 1BS403
- 2. SLCS components:
APPENDIX 9A 9A-191 REV. 18, SEPTEMBER 2016
Storage tank 10T204 Injection pumps 1AP208, 1BP208, and 1CP208 Explosive valves XV-48-1F004A,B&C
- 3. Core spray loop "A" injection valves (HV-52-1F004A and HV-52-1F005)
- 4. Core spray loop "B" injection valves (HV-52-1F004B, HV-52-1F037, and HV-52-108)
- 5. RHR system valves:
HV-51-1F017A,B,C&D (LPCI injection line containment isolation)
HV-51-1F021A&B (drywell spray line containment isolation)
HV-51-1F016A&B (drywell spray line shutoff)
- 6. HPCI system injection valve (HV-55-1F006)
- 7. RWCU supply line containment isolation valve (HV-44-1F004)
- 8. CAC purge line containment isolation valves (HV-57-111, HV-57-115, HV-57-114, and HV-57-161)
- 9. Containment combustible gas analyzer sample cabinet 10S205
- 10. Load center 10B204 (Div. 4)
- 11. Motor control center 10B213, which serves the following components:
(a) RHR loop "A" valves (b) Core spray loop "A" valves (c) Feedwater startup recirculation valves (HV-41-109A&B)
(d) Shutoff valves for main steam to miscellaneous steam-driven components (HV-01-108, HV-01-109, HV-01-111, and HV-01-150)
(e) Drywell chilled water source select valves (f) SGTS heater 0AE188 (g) SGTS exhaust fan 0AV109
- 12. Motor control center 10B214, which serves the following components:
(a) RHR loop "B" valves (b) Core spray loop "B" valves (c) Drywell cooling water containment isolation valves (d) SGTS heater 0BE188 (e) SGTS exhaust fan 0BV109
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-192 REV. 18, SEPTEMBER 2016
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the fire occurs within the coverage area of the preaction sprinkler system in this fire area, the system will provide automatic suppression of the fire. When the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual fusible link sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 47 is divided into an eastern (47E) and a western (47W) portion through the establishment of a 20 foot wide zone that is free of combustible materials; no cable trays are located within this combustible-free zone.
47E The eastern portion of fire area 47 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 1 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods B and C for Unit 2 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
Equipment associated with shutdown methods B and C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, method C will be available to shutdown Unit 1 and methods B and C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 47.
47W The western portion of fire area 47 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Unit 1 are either encapsulated by a qualified barrier, associated with equipment that have redundant APPENDIX 9A 9A-193 REV. 18, SEPTEMBER 2016
components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost.
Equipment associated with shutdown methods B and C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2, for a fire in the western half of fire area 47.
A postulated fire in the vicinity of the reactor vessel instrumentation reference leg backfill system could adversely affect reactor vessel water level indication due to reference leg density changes caused by an increase in water temperature. Since there are no fire initiators in close proximity to the backfill system tubing, administratively controlled combustible free zones, throughout the locations of the backfill system will preclude any adverse effect on level indication, due to fire, prior to annunciation in the main control room.
Following annunciation in the main control room, the backfill system will be administratively isolated from the reference legs.
- f. Deviations:
A 20 foot wide zone that is free of combustible materials is maintained; no cable trays are located within this combustible-free zone. The combustible-free zone divides fire area 47 into a western portion and an eastern portion.
Several components associated with the credited safe shutdown methods are located in the eastern half of fire area 47. Components and cables performing active, credited, redundant functions are located on opposite sides of fire area 47 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray up to the boundaries of the combustible free zone. The location of the precaution sprinkler system on fire area 47 is shown in Figure 9A-8.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 47.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.4.20 Fire Area 48: RWCU Holding Pump Compartments, RERS Fan Area, and Corridors (el 313'-0")
APPENDIX 9A 9A-194 REV. 18, SEPTEMBER 2016
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete (part 2 hr adjacent to stairwell no. 4)
N - Reinforced concrete (part) 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (part) 3 hr S - Reinforced concrete (part 2 hr adjacent to stairwell no. 3)
W - Reinforced concrete (part, None exterior wall)
W - Reinforced concrete (part 2 hr adjacent to stairwell no. 4)
Interior boundary - Reinforced concrete None (primary containment wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell 1.5 hr nos. 3 and 4 Airlock door connecting to 3 hr area 49 Double airlock door connecting to 3 hr**
area 49 Elevator door 0.75 hr Equipment hatchway in floor None (200 ft2 opening; protected by water curtain suppression system)
- b. Major safety-related components in fire area:
- 1. RERS fans (1AV213 and 1BV213)
- 2. Load center 10B201 (Div. 1)
- 3. Load center 10B202 (Div. 2)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control APPENDIX 9A 9A-195 REV. 18, SEPTEMBER 2016
room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 48 is divided into an eastern (48E) and a western (48W) portion through the establishment of a 20 foot wide zone that is free of combustible materials.
48E The eastern portion of fire area 48 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 1 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2, for a fire in the eastern half of fire area 48.
48W The western portion of fire area 48 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2, for a fire in the western half of fire area 48.
- f. Deviations:
APPENDIX 9A 9A-196 REV. 18, SEPTEMBER 2016
Load centers 10B201 and 10B202 and their associated transformers are the only components credited for safe shutdown which are located in fire area 48. The horizontal separation between the two load centers is greater than 35 feet, and the only combustible materials in the intervening space are electrical cables in a cable tray. A 20 foot wide zone that is free of combustibles was created between the two load centers by using a galvanized steel cable tray enclosure system to cover the cable trays that pass through the zone. This non-combustible configuration together with the enclosure and seals will prevent fire propagation across the combustible zone. A fixed suppression system of the water curtain-type is located within the combustible-free zone to provide assurance that a postulated fire due to transient combustibles can be prevented from propagating through the combustible-free zone. To preclude the possibility of a spilled combustible liquid spreading across the area between the two load centers, a concrete curb is provided between the load centers, spanning the full width of the corridor in which the load centers are located. The curb is located within the coverage area of the water curtain system. To protect the load centers from radiant heat that could be generated by a postulated fire occurring in the area between the load centers, each load center is provided with a radiant heat shield. The heat shields are constructed of Marinite sheet and are located adjacent to the side of each load center that faces the concrete curb.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 48.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.4.21 Fire Area 49: Reactor Enclosure Lower Fan Room (el 313'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (part, None exterior wall)
S - Louvers open to outside None atmosphere (part)
W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (part None below fire area 50)
Reinforced concrete (part 3 hr*
below fire area 51)
Access: Airlock door connecting to 3 hr area 48 Double airlock door connecting 3 hr**
APPENDIX 9A 9A-197 REV. 18, SEPTEMBER 2016
to area 48 Emergency exit in ceiling None (6.25 ft2 opening)
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Once the control room operators have been notified that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 49 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.22 Fire Area 50: Reactor Enclosure Upper Fan Room and Equipment Compartment Exhaust Filter Rooms (el 331'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete None (exterior wall)
W - Reinforced concrete (part 2 hr adjacent to stairwell no. 3)
W - Reinforced concrete (part) 3 hr Floor: Reinforced concrete None Ceiling: Reinforced concrete 3 hr*
Access: Door connecting to stairwell 1.5 hr no. 3 Two doors connecting to area 51 3 hr Emergency exit in floor None APPENDIX 9A 9A-198 REV. 18, SEPTEMBER 2016
(6.25 ft2 opening)
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
In the event of a fire in one of the reactor enclosure equipment compartment exhaust filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the affected ventilation system will be shut down and the plant fire brigade will be dispatched to extinguish the fire. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum.
- e. Effect of fire on safe shutdown:
Fire area 50 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.23 Fire Area 51: RERS Filter Compartments (el 331'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete None (exterior wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Two doors connecting to area 50 3 hr
- b. Major safety-related components in fire area:
- 1. RERS filter assemblies (1AS297 and 1BS297)
APPENDIX 9A 9A-199 REV. 18, SEPTEMBER 2016
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
In the event of a fire in one of the RERS filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum.
- e. Effect of fire on safe shutdown:
Fire area 51 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.24 Fire Area 75: Service Water Pipe Tunnel (el 198'-0")
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete None S - Reinforced concrete (part 3 hr adjacent to diesel generator enclosures)
S - Reinforced concrete None (exterior wall)
W - Reinforced concrete 3 hr Floor: Reinforced concrete foundation None Ceiling: Reinforced concrete (portion below 3 hr*
fire areas 44, 67, and 79 through 86)
Reinforced concrete (portion below None fire areas 76, 124, and 125)
Access: Watertight doors connecting 3 hr**
to areas 42 and 65
- b. Major safety-related components in fire area:
APPENDIX 9A 9A-200 REV. 18, SEPTEMBER 2016
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receipt of notification in the control room that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire. Depending on the severity and location of the fire, certain components in the ESW and/or RHRSW systems may be affected.
- e. Effect of fire on safe shutdown:
Fire area 75 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
- f. Deviations:
The existence of an unrated ceiling for this fire area is acceptable because of the low combustible loadings in the pipe tunnel (fire area 75) below the ceiling and in the corridors and condensate pump rooms (fire areas 124 and 125) above the ceiling. In the highly unlikely event that a fire in this area should propagate through the unrated ceiling, safe shutdown capability would still be assured. Fire area 75 and fire areas 124 and 125 all credit methods A, B, and C for safe shutdown of both Units 1 and 2.
The unrated steel ceiling is a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the ceiling is unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barrier.
9A.5.4.25 Fire Area 76: Refueling Hoist-way (el 217'-0")
APPENDIX 9A 9A-201 REV. 18, SEPTEMBER 2016
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete foundation None Ceiling: Concrete hatch plugs connecting None to area 78 Access: Missile-resistant doors connecting 3 hr**
to areas 44 and 67 Railroad car airlock doors None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receipt of notification in the control room that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 76 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.26 Fire Area 77: South Ventilation Exhaust Stack
Construction Rating Walls: N - Reinforced concrete 3 hr E - Precast concrete panels None S - Precast concrete panels None W - Precast concrete panels None APPENDIX 9A 9A-202 REV. 18, SEPTEMBER 2016
Floor: None (open to outside)
Ceiling: None (open to outside)
Access: Door connecting to area 78 3 hr
- b. Major safety-related components located in fire area:
None
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receipt of notification in the control room that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 77 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.27 Fire Area 78: Refueling Area (el 352'-0")
- a. Structural and architectural design features of fire area (Figure 9A-10):
Construction Rating Walls: N - Reinforced concrete (part 2 hr adjacent to stairwell nos.
4 and 6)
N - Reinforced concrete (part 3 hr adjacent to fire areas 28, 46, and 69)
N - Reinforced concrete (part, None exterior wall)
E - Reinforced concrete (part 2 hr adjacent to stairwell nos. 5 and 6)
E - Reinforced concrete (part) None S - Reinforced concrete (part 2 hr adjacent to stairwell nos. 3 and 5)
APPENDIX 9A 9A-203 REV. 18, SEPTEMBER 2016
S - Reinforced concrete (part, None exterior wall)
W - Reinforced concrete (part 2 hr adjacent to stairwell nos. 3 and 4)
W - Reinforced concrete (part, None exterior wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Doors to stairwell nos. 1.5 hr 3, 4, 5, and 6 Two doors to area 77 3 hr
- b. Major safety-related components in fire area:
- 1. Reactor enclosure crane
- 2. Refueling platforms for Units 1 and 2
- 3. Gate seals, stop seals, and reactor well seals
- c. Postulated fire in area:
Ignition of stored materials as a result of an exposure fire. An exposure fire involving stored combustible materials in this fire area would be extremely limited in scope and confined to a small area due to the sparsely distributed combustibles within the refueling area. Ignition of the stored combustible materials is extremely unlikely in the absence of a fire source external to the materials.
- d. Consequences of fire with active fire suppression:
Upon receipt of notification in the control room that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire. No effect on safety related systems will result from a fire in the fire area.
- e. Effect of fire on safe shutdown:
Fire area 78 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.28 Fire Area 126: North Stack Instrument Room and Vestibule (el 411'-9")
- a. Structural and architectural design features of fire area (Figure 9A-10):
APPENDIX 9A 9A-204 REV. 18, SEPTEMBER 2016
Construction Rating Walls: N - Precast concrete panels 2 hr E - Insulated metal siding None S - Insulated metal siding None W - Insulated metal siding None Floor: Reinforced concrete None Ceiling: Built-up roofing UL Class A Access: Door connecting to north stack 1.5 hr Two doors to outside None
- b. Major safety-related components in fire area:
- 1. Wide range accident monitors 01S908 and 02S908
- 2. Wide range accident monitor microprocessor (RY-26-076)
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 126 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.4.29 Fire Area 127: South Stack Instrument Room (el 411'-9")
- a. Structural and architectural design features of fire area (Figure 9A-10):
Construction Rating Walls: N - Insulated metal siding None E - Insulated metal siding None S - Precast concrete panels 2 hr APPENDIX 9A 9A-205 REV. 18, SEPTEMBER 2016
W - Insulated metal siding None Floor: Reinforced concrete None Ceiling: Built-up roofing UL Class A Access: Door connecting to south stack 1.5 hr Two doors to outside None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 127 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5 SAFE SHUTDOWN ANALYSIS - UNIT 2 REACTOR ENCLOSURE 9A.5.5.1 Fire Area 52: Suppression Chamber (el 181'-11")
Construction Rating Walls: All around - Reinforced concrete None (primary containment wall)
Floor: Reinforced concrete foundation None mat Ceiling: Reinforced concrete (diaphragm None slab)
APPENDIX 9A 9A-206 REV. 18, SEPTEMBER 2016
Access: Two access hatches connecting to None area 67
- b. Major safety-related components in fire area:
- 1. Primary containment vacuum relief valve assemblies (PSV-57-237A,B,C&D)
- c. Postulated fire in area:
Since there are no combustible materials located in this area, no fire is postulated to occur.
- d. Consequences of fire with active fire suppression:
Not applicable (see item (c)).
- e. Effect of fire on safe shutdown:
Fire area 52 contains safe shutdown cables and equipment.
During normal operation, primary containment is inerted. Since containment is inerted no fire is postulated.
9A.5.5.2 Fire Area 53: Drywell (el 237'-11")
Construction Rating Walls: All around - Reinforced concrete None (primary containment wall)
Floor: Reinforced concrete (diaphragm None slab)
Ceiling: Steel dome (drywell head) None Access: Equipment hatch connecting to None area 68 Equipment hatch with personnel None lock connecting to area 68
- b. Major safety-related components in fire area:
- 1. Control rod drive mechanisms (total of 185)
- 2. Main steam isolation valves (inboard, one per steam line)
- 3. Main steam relief valves (total of 14)
- 4. Drywell unit coolers (total of 8)
APPENDIX 9A 9A-207 REV. 18, SEPTEMBER 2016
- 5. Inboard containment isolation valves for HPCI steam supply line, RCIC steam supply line, RWCU letdown line, and RHR shutdown cooling suction line
- c. Postulated fire in area:
- 1. Leakage of lube oil from a recirculation pump motor onto the diaphragm slab, with subsequent ignition of the oil.
- 2. Ignition of electrical cabling in cable tray or direct supported metal clad cable.
- d. Consequences of fire with active fire suppression:
The possibility of a fire in the drywell is limited to periods when the reactor is shut down.
This is because the primary containment is inerted with nitrogen during reactor operation, so that the oxygen concentration is maintained below 4% by volume. This inert atmosphere will prevent fires from occurring in the primary containment during reactor operation.
In the event of a fire in the drywell while the reactor is shut down and the drywell deinerted, the operator will dispatch the plant fire brigade to el 253' in the reactor enclosure. The fire brigade will enter the drywell through the personnel airlock and will ensure extinguishment of the fire through the use of portable fire extinguishers or hoses from hose reels located outside the entrances to the drywell.
- e. Effect of fire on safe shutdown:
Fire area 53 contains safe shutdown cables and equipment.
During normal operation, primary containment is inerted. Since containment is inerted no fire is postulated.
9A.5.5.3 Fire Area 54: Residual Heat Removal Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: NE - Reinforced concrete (primary None containment wall)
N - Reinforced concrete 3 hr W - Reinforced concrete (part None below el 201', exterior wall)
W - Reinforced concrete (part 3 hr above el 201')
S - Reinforced concrete (part None below el 198', exterior wall)
S - Reinforced concrete (part 3 hr above el 198')
E - Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None APPENDIX 9A 9A-208 REV. 18, SEPTEMBER 2016
Ceiling: Reinforced concrete (ceiling contains None 115 ft2 of unrated metal blowout panels leading to area 66)
Access: Watertight doors connecting to 3 hr**
areas 55 and 62 Steamtight doors (at el 201') 3 hr connecting to areas 55 and 64
- b. Major safety-related components in fire area:
- 1. RHR pumps 2AP202 and 2CP202
- 2. RHR heat exchanger 2AE205
- 3. RHR compartment unit coolers 2AV210, 2CV210, 2EV210, and 2GV210
- c. Postulated fire in area:
Leakage of lube oil from both RHR pump motors onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 54 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B and C for Unit 1 and methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B and C for Unit 1 and methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B and C will be available to shutdown Unit 1 and methods B and C will be available to shutdown Unit 2.
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the APPENDIX 9A 9A-209 REV. 18, SEPTEMBER 2016
panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 54 and the western portion of fire area 66 both credit method C for safe shutdown of Unit 2. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 1.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.5.4 Fire Area 55: Residual Heat Removal Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: E - Reinforced concrete 3 hr NE - Reinforced concrete 3 hr NW - Reinforced concrete (primary None containment wall)
W - Reinforced concrete 3 hr S - Reinforced concrete (part below None el 198', exterior wall)
S - Reinforced concrete (part 3 hr above el 198')
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling None contains 150 ft2 of unrated metal blowout panels leading to area 66)
Access: Watertight doors connecting to 3 hr**
areas 54 and 56 Steamtight doors (at el 201') 3 hr connecting to areas 54 and 65
- b. Major safety-related components in fire area:
- 1. RHR pumps 2BP202 and 2DP202
- 2. RHR heat exchanger 2BE205
- 3. RHR compartment unit coolers 2BV210, 2DV210, 2FV210, and 2HV210
- 4. RCIC turbine exhaust line vacuum breaker valves HV-49-2F080 and HV-49-2F084
- 5. ESW loop "B" valves (HV-11-047, HV-11-077, HV-11-225, and HV-11-226)
APPENDIX 9A 9A-210 REV. 18, SEPTEMBER 2016
- c. Postulated fire in area:
Leakage of lube oil from both RHR pump motors onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 55 contains safe shutdown cables and equipment.
Cables required to support shutdown method B for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method B for Unit 1 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A and C for Unit 1 and method C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Unit 1 and method C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2.
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 55 and the eastern portion of fire area 66 both credit method C for safe shutdown of Unit 2. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 1.
APPENDIX 9A 9A-211 REV. 18, SEPTEMBER 2016
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.5.5 Fire Area 56: Reactor Core Isolation Cooling Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: E - Reinforced concrete None (exterior wall)
N - Reinforced concrete 3 hr NE - Reinforced concrete 3 hr NW - Reinforced concrete (primary None containment wall)
SW - Reinforced concrete 3 hr W - Reinforced concrete 3 hr S - Reinforced concrete (part 2 hr adjacent to stairwell no. 5)
S - Reinforced concrete (part, None exterior wall below el 198')
S - Reinforced concrete (part, 3 hr exterior wall above el 198')
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling None contains 25 ft2 of unrated metal blowout panels leading to area 66)
Access: Watertight doors connecting to 3 hr**
areas 55 and 57 Door connecting to stairwell no. 5 1.5 hr
- b. Major safety-related components in fire area:
- 1. RCIC pump 20P203
- 2. RCIC turbine 20S212
- 3. RCIC compartment unit coolers 2AV208 and 2BV208
- c. Postulated fire in area:
Leakage of lube oil from RCIC turbine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control APPENDIX 9A 9A-212 REV. 18, SEPTEMBER 2016
room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 56 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2.
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 56 and the eastern portion of fire area 66 both credit method C for safe shutdown of Unit 2. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 1.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers 9A.5.5.6 Fire Area 57: High Pressure Coolant Injection Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: E - Reinforced concrete None (exterior wall)
N - Reinforced concrete 3 hr W - Reinforced concrete (primary None containment wall)
SW - Reinforced concrete 3 hr APPENDIX 9A 9A-213 REV. 18, SEPTEMBER 2016
S - Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (ceiling None contains 160 ft2 of unrated metal blowout panels leading to area 66)
Access: Watertight doors connecting to 3 hr**
areas 56 and 63
- b. Major safety-related components in fire area:
- 1. HPCI pump 20P204
- 2. HPCI turbine 20S211
- 3. HPCI compartment unit coolers 2AV209 and 2BV209
- 4. Instrument rack 20C014 (HPCI)
- c. Postulated fire in area:
Leakage of lube oil from HPCI turbine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire will activate the smoke detectors in this area, which will cause an audible-visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190F, the deluge valve will open and prime the preaction sprinkler system with water. At 212F, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 57 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods A and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods A and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods A and C will be available to shutdown Unit 2.
APPENDIX 9A 9A-214 REV. 18, SEPTEMBER 2016
- f. Deviations:
The existence of unrated metal panels in the ceiling of this fire area is acceptable because the low combustible loadings in the areas above and below the panels and the height of the panels above the floor (40 feet) minimize the possibility of fire propagating through the panels. Penetrations of piping and electrical raceway through the ceiling are provided with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> rated seals.
In the highly unlikely event that a fire in this area should propagate through the metal panels in the ceiling at elevation 217, safe shutdown capability would still be assured.
Fire area 57 and the eastern portion of fire area 66 both credit method C for safe shutdown of Unit 2. The unlikely propagation of a fire through the metal panels does not impact safe shutdown of Unit 1.
The unrated metal panels are a deviation from the requirements of CMEB 9.5-1, C.5.b.
Although the metal panels are unrated, safe shutdown requirements are met in that safe shutdown can be achieved even with the unlikely failure of the unrated barriers.
9A.5.5.7 Fire Area 58: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: E - Reinforced concrete 3 hr N - Reinforced concrete 3 hr W - Reinforced concrete (primary None containment wall)
S - Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 63 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 2BP206
- 2. Core spray compartment unit coolers 2BV211 and 2FV211
- 3. Safeguard piping fill pump 2BP256
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire will activate the smoke detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control APPENDIX 9A 9A-215 REV. 18, SEPTEMBER 2016
room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 58 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5.8 Fire Area 59: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: E - Reinforced concrete 3 hr N - Reinforced concrete (part 3 hr adjacent to fire areas 102 and 115)
N - Reinforced concrete (part None adjacent to unexcavated area)
W - Reinforced concrete 3 hr SW - Reinforced concrete (primary None containment wall)
S - Reinforced concrete 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 63 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 2DP206
- 2. Core spray compartment unit coolers 2DV211 and 2HV211
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
APPENDIX 9A 9A-216 REV. 18, SEPTEMBER 2016
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 59 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5.9 Fire Area 60: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: E - Reinforced concrete 3 hr N - Reinforced concrete 3 hr W - Reinforced concrete 3 hr S - Reinforced concrete 3 hr SE - Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 62 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 2CP206
- 2. Core spray compartment unit coolers 2CV211 and 2GV211
- c. Postulated fire in area:
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
APPENDIX 9A 9A-217 REV. 18, SEPTEMBER 2016
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 60 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2.
9A.5.5.10 Fire Area 61: Core Spray Compartment (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N - Reinforced concrete 3 hr W - Reinforced concrete 3 hr S - Reinforced concrete 3 hr E - Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight door connecting to area 62 3 hr**
- b. Major safety-related components in fire area:
- 1. Core spray pump 2AP206
- 2. Core spray compartment unit coolers 2AV211 and 2EV211
- 3. Safeguard piping fill pump 2AP256
- c. Postulated fire in area:
APPENDIX 9A 9A-218 REV. 18, SEPTEMBER 2016
Leakage of lube oil from core spray pump motor onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire will activate the smoke detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 61 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5.11 Fire Area 62: Sump Room and Passageway (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N - Reinforced concrete 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 2)
W - Reinforced concrete (part) 3 hr S - Reinforced concrete (part None adjacent to unexcavated area)
S - Reinforced concrete (part) 3 hr E - Reinforced concrete (part, None primary containment wall)
E - Reinforced concrete (part) 3 hr Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight doors connecting to 3 hr**
areas 54, 60, and 61 Door connecting to stairwell no. 2 1.5 hr
- b. Major safety-related components in fire area:
APPENDIX 9A 9A-219 REV. 18, SEPTEMBER 2016
- 1. Containment isolation valves (HV-52-227 and HV-52-228) for suppression pool cleanup pump suction line.
- 2. Instrument rack 20C075 (RHR pump "A" discharge pressure)
- 3. Instrument rack 20C077 (RHR pump "C" discharge pressure)
- c. Postulated fire in area:
- 1. Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- 2. Ignition of oil in waste oil collection drum associated with the floor drain sump oil removal belt.
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 62 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5.12 Fire Area 63: Corridor (el 177'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N - Reinforced concrete (part 2 hr adjacent to stairwell no. 6)
N - Reinforced concrete None (part adjacent to APPENDIX 9A 9A-220 REV. 18, SEPTEMBER 2016
unexcavated area)
W - Reinforced concrete 3 hr S - Reinforced concrete 3 hr E - Reinforced concrete (part None adjacent to unexcavated area)
E - Reinforced concrete (part 2 hr adjacent to stairwell no. 6)
Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete 3 hr*
Access: Watertight doors connecting to 3 hr**
areas 57, 58, and 59 Door connecting to stairwell no. 6 1.5 hr Elevator door 0.75 hr
- b. Major safety-related components in fire area:
- 1. HPCI pump discharge flow transmitters (FT-55-2N008 and FT-55-2N051)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 63 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods A and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods A and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1 and methods A and C will be available to shutdown Unit 2.
9A.5.5.13 Fire Area 64: Reactor Enclosure Cooling Water Equipment Area (el 201'-0")
APPENDIX 9A 9A-221 REV. 18, SEPTEMBER 2016
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 2)
W - Reinforced concrete (part 3 hr adjacent to fire area 41)
W - Reinforced concrete (part None adjacent to unexcavated area)
S - Reinforced concrete 3 hr E - Reinforced concrete (part) 3 hr E - Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (One portion 3 hr*
of the ceiling slab, covering an area of 10 ft2, has a reduced concrete thickness that varies between 4.5 inches and 9.0 inches.)
Access: Door connecting to stairwell 1.5 hr no. 2 Door connecting to area 54 3 hr
- b. Major safety-related components in fire area:
- 1. Core spray loop "A" minimum flow recirculation valve (HV-52-2F031A)
- 2. Containment atmosphere sample return line isolation valves (SV-57-290 and SV-57-291)
- 3. ESW loop "A" valves (HV-11-046, HV-11-076, HV-11-221, HV-11-223, HV-11-224, HV-11-227 and HV-11-228)
- 4. HVAC unit cooler control panels 2AC208 and 2CC208
- 5. Motor control center 20B217, which serves the following components:
(a) RHR loop "C" valves (b) RHR compartment unit coolers 2CV210 and 2GV210 (c) Core spray loop "A" valves (d) Core spray compartment unit coolers 2CV211 and 2GV211 (e) RHRSW outlet valve from RHR "A" heat exchanger (HV-51-2F068A)
(f) Drywell unit cooler fans 2C2V212 and 2G2V212 (g) Containment hydrogen recombiner 2AS403 and associated valves (h) HVAC 120 V ac transformer 20X283 (i) PCIG supply header containment isolation valve (HV-59-251A)
APPENDIX 9A 9A-222 REV. 18, SEPTEMBER 2016
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190 F, the deluge valve will open and prime the preaction sprinkler system with water. At 212 F, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 64 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods B and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods B and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2.
9A.5.5.14 Fire Area 65: Safeguard System Access Area (el 201'-0")
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete (part 2 hr adjacent to stairwell no. 6)
N - Reinforced concrete (part) 3 hr W - Reinforced concrete 3 hr SW - Reinforced concrete (primary None containment wall)
S - Reinforced concrete (part 2 hr APPENDIX 9A 9A-223 REV. 18, SEPTEMBER 2016
adjacent to stairwell no. 5)
S - Reinforced concrete (part) 3 hr E - Reinforced concrete (part None adjacent to unexcavated area)
E - Reinforced concrete (part 2 hr adjacent to stairwell no. 6)
E - Reinforced concrete (part 3 hr adjacent to auxiliary boiler pipe tunnel)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (One portion 3 hr*
of the ceiling slab, covering an area of 10 ft2, has a reduced concrete thickness that varies between 4.5 inches and 9.0 inches.)
Access: Elevator door 0.75 hr Doors connecting to stairwell 1.5 hr nos. 5 and 6 Door connecting to area 55 3 hr Watertight door connecting 3 hr**
to area 75
- b. Major safety-related components in fire area:
- 3. HPCI level transmitters (LT-55-2N061B&F) and turbine exhaust pressure transmitters (PT-56-2N055D&H)
- 4. RCIC pump suction line level transmitters (LT-49-2N035A&E)
- 5. ESW loop "B" valves (HV-11-048, HV-11-049, HV-11-078, and HV-11-079)
- 6. Suppression chamber pressure transmitter (PT-57-201)
- 7. Instrument rack 20C017 (RCIC)
- 9. Instrument rack 20C076 (RHR pump "B" discharge pressure)
- 10. Instrument rack 20C078 (RHR pump "D" discharge pressure)
- 11. HVAC unit cooler control panels 2BC208 and 2DC208
- 12. Motor control center 20B218, which serves the following components:
APPENDIX 9A 9A-224 REV. 18, SEPTEMBER 2016
(a) RHR loop "D" valves (b) RHR compartment unit coolers 2DV210 and 2HV210 (c) Core spray pump suction valve (HV-52-2F001D)
(d) Core spray compartment unit coolers 2DV211 and 2HV211 (e) RHRSW outlet valve from RHR "B" heat exchanger (HV-51-2F068B)
(f) Drywell unit cooler fans 2D2V212 and 2F2V212 (g) Containment hydrogen recombiner 2BS403 and associated valves (h) HVAC 120 V ac transformer 20X284 (i) PCIG supply header containment isolation valve (HV-59-251B)
- c. Postulated fire in Area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 65 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2.
9A.5.5.15 Fire Area 66: Safeguard System Isolation Valve Area (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
APPENDIX 9A 9A-225 REV. 18, SEPTEMBER 2016
Construction Rating Walls: N- Reinforced concrete 3 hr E- Reinforced concrete 3 hr S- Reinforced concrete (part) 3 hr S- Reinforced concrete (exterior None wall, contains 150 ft2 of unrated blowout panels)
W - Reinforced concrete 3 hr Interior boundary - Reinforced None concrete (primary containment wall)
Floor: Reinforced concrete (contains 450 ft2 None of unrated metal blowout panels from areas 54, 55, 56, and 57)
Ceiling: Reinforced concrete 3 hr*
Access: Two steamtight doors connecting to 3 hr area 67
- b. Major safety-related components in fire area:
- 1. HPCI steam line containment isolation valves (HV-55-2F003 and HV-55-2F100)
- 2. RCIC steam line containment isolation valves (HV-49-2F008 and HV-49-2F076)
- 3. RHR system valves:
(a) HV-51-2F008 (shutdown cooling suction containment isolation)
(b) HV-51-2F015A&B (shutdown cooling return containment isolation)
(c) HV-51-2F047A&B (heat exchanger inlet)
(d) HV-C-51-2F048A&B (heat exchanger bypass)
- 4. CAC system containment isolation valves (HV-57-209, HV-57-221, HV-57-223, HV-57-224, HV-57-231, HV-57-235, HV-57-247, HV-57-263, and HV-57-264)
- 5. PCIG system containment isolation valves (HV-59-202, HV-59-229A, HV-59-229B, HV-59-235, HV-59-251A, and HV-59-251B)
- 6. HPCI system leakage detection temperature elements
- 7. RCIC system leakage detection temperature elements
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-226 REV. 18, SEPTEMBER 2016
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 66 is divided into an eastern (66E) and a western (66W) portion through the establishment of a 20 foot wide zone that is free of combustible materials; no cable trays are located within this combustible-free zone.
66E The eastern portion of fire area 66 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 66.
66W The western portion of fire area 66 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either encapsulated by a qualified fire barrier, or associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown method C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
APPENDIX 9A 9A-227 REV. 18, SEPTEMBER 2016
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the western half of fire area 66.
- f. Deviations:
Fire area 66 is divided into a western portion and an eastern portion through the establishment of a 20 foot wide zone that is free of combustible materials. No cable trays are located within this combustible-free zone.
Several valves associated with the credited safe shutdown methods are located in fire area 66. Valves performing active, credited, redundant functions are located on opposite sides of fire area 66 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable trays, and none of these cable trays are located within the combustible-free zone. The in situ combustible loading in fire area 66 is relatively light, with an equivalent severity of only 13 minutes. The potential for transient combustibles to exist in the space between credited, redundant valves is severely restricted by the arrangement of fire area 66 and the locations of commodities within it. The space between credited, redundant valves is relatively narrow and contains a high concentration of pipes and pipe supports. These obstructions effectively prevent the introduction of significant quantities of combustible materials into this space. The factors discussed above preclude the occurrence of a fire, involving either in situ combustibles or transient combustibles, that could simultaneously affect credited, redundant equipment.
The measures described above for physical separation and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or eastern portion of fire area 66.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.5.16 Fire Area 67: Safeguard System Access Area (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 2 hr (parts adjacent to stairwell nos. 2 and 6)
N - Reinforced concrete (part) 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 2)
W - Reinforced concrete (part) 3 hr S - Reinforced concrete (part 2 hr adjacent to stairwell no. 5)
S - Reinforced concrete (part 3 hr adjacent to fire area 125)
APPENDIX 9A 9A-228 REV. 18, SEPTEMBER 2016
S - Reinforced concrete (part, None exterior wall)
E - Reinforced concrete (part 2 hr adjacent to stairwell nos. 5 and 6)
E - Reinforced concrete (part) 3 hr Interior boundary (part) - 3 hr Reinforced concrete walls Interior boundary (part) - None Reinforced concrete (primary containment wall)
Floor: Reinforced concrete (Two portions 3 hr*
of the floor slab, each of which covers an area of 10 ft2, have a reduced concrete thickness that varies between 4.5 inches and 9.0 inches.)
Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell 1.5 hr nos. 2, 5, and 6 Two steamtight doors connecting to 3 hr area 66 Missile-resistant door connecting to 3 hr**
area 76 Equipment airlock door None Elevator door 0.75 hr Suppression chamber access hatches None Equipment hatchway in ceiling None (200 ft2 opening; protected by water curtain suppression system)
- b. Major safety-related components in fire area:
- 1. Core spray full flow test recirculation valves (HV-52-2F015A&B)
- 2. CAC system containment isolation valves (HV-57-204, HV-57-205, HV-57-212, HV-57-218, and HV-57-262)
- 3. RHR system valves:
(a) HV-51-225A&B (containment isolation for recirculation to suppression chamber)
(b) HV-51-2F027A&B (containment isolation for suppression chamber spray)
(c) HV-51-2F010A&B (loops C and D recirculation to suppression chamber)
(d) HV-51-2F024A&B (loops A and B recirculation to suppression chamber)
- 4. Instrument racks 20C001 (core spray loop A) and 20C019 (core spray loop B)
- 5. Instrument racks 20C015, 20C025, 20C041, and 20C042 (main steam and reactor recirculation flow)
APPENDIX 9A 9A-229 REV. 18, SEPTEMBER 2016
- 6. Instrument racks 20C016 and 20C036 (HPCI)
- 7. Instrument racks 20C035 and 20C038 (RCIC)
- 8. Instrument racks 20C006, 20C009, 20C010, and 20C022 (reactor recirculation system pressure and jet pump flow)
- 9. RHR flow transmitters (FT-51-2N015A,B,C&D and FT-51-2N052A,B,C&D)
- 10. Motor control center 20B211, which serves the following components:
(a) RHR loop "A" valves (b) RHR compartment unit coolers 2AV210 and 2EV210 (c) Core spray loop "A" valves (d) Core spray compartment unit coolers 2AV211 and 2EV211 (e) RHRSW inlet valve to RHR "A" heat exchanger (HV-51-2F014A)
(f) RHR shutdown cooling suction inboard isolation valve (HV-51-2F009)
(g) RCIC compartment unit coolers 2AV208 and 2BV208 (h) RWCU inboard isolation valve (HV-44-2F001)
(i) Main steam drain line inboard isolation valve (HV-41-2F016)
(j) Drywell unit cooler fans 2A1V212, 2C1V212, 2E1V212, and 2G1V212 (k) Safeguard piping fill pump 2AP256 (l) PCIG compressor suction line containment isolation valve (HV-59-201)
(m) 120 V instrument ac distribution panel 20Y101 (n) Battery chargers 2A1D103 and 2A2D103 (o) Motor control center 20B215
- 11. Motor control center 20B212, which serves the following components:
(a) RHR loop "B" valves (b) RHR compartment unit coolers 2BV210 and 2FV210 (c) Core spray loop "B" valves (d) Core spray compartment unit coolers 2BV211 and 2FV211 (e) RHRSW inlet valve to RHR "B" heat exchanger (HV-51-2F014B)
(f) RHR shutdown cooling return isolation valve (HV-51-2F015A)
(g) Reactor recirculation pump suction valve (HV-43-2F023B)
(h) HPCI compartment unit coolers 2AV209 and 2BV209 (i) Drywell unit cooler fans 2B1V212, 2D1V212, 2F1V212, and 2H1V212 (j) Safeguard piping fill pump 2BP256 (k) CAC system purge line isolation valve (HV-57-205)
(l) 120 V instrument ac distribution panel 20Y102 (m) Battery chargers 2B1D103 and 2B2D103 (n) Motor control center 20B216
- 12. Motor control center 20B215, which serves the following components:
(a) RHR loop "A" valves (b) RCIC system valves (c) Deleted.
(d) Suppression pool cleanup pump suction isolation valve (HV-52-227)
(e) Drywell pressure tap isolation valve (HV-42-247A)
(f) Drywell floor drain and equipment drain containment isolation valves (HV-61-212 and HV-61-232)
(g) Main steam drain line flow control valve (HV-C41-2F020)
APPENDIX 9A 9A-230 REV. 18, SEPTEMBER 2016
- 13. Motor control center 20B216, which serves the following components:
(a) RHR loop "B" valves (b) HPCI system valves (c) Deleted (d) Suppression pool cleanup pump isolation valve (HV-52-228)
(e) Drywell pressure tap isolation valve (HV-42-247B)
(f) Suppression pool level tap isolation valves (HV-55-220 and HV-55-221)
(g) Reactor head spray outboard isolation valve (HV-51-2F023)
(h) RHR shutdown cooling suction outboard isolation valve (HV-51-2F008)
(i) RWCU outboard isolation valve (HV-44-2F004)
(j) Main steam drain line outboard isolation valve (HV-41-2F019)
(k) RHR to radwaste discharge line isolation valve (HV-51-2F049)
- 14. Dc motor control center 20D201, which serves the following components:
(a) RCIC system (b) Div. 1 RPS and UPS static inverter
- 15. Dc motor control center 20D202, which serves the HPCI system
- 16. Dc motor control center 20D203, which serves the following components:
(a) HPCI system (b) Div. 2 RPS and UPS static inverter
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the fire occurs within the coverage area of one of the three preaction sprinkler systems in this fire area, the system will provide automatic suppression of the fire. When the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual fusible link sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 67 is divided into an eastern (67E) and a western (67W) portion through the establishment of a 20 foot wide zone that is free of combustible materials.
67E The eastern portion of fire area 67 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-231 REV. 18, SEPTEMBER 2016
Cables required to support shutdown method C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 67.
67W The western portion of fire area 67 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the western half of fire area 67.
- f. Deviations:
Fire area 67 is divided into a western portion and an eastern portion through the establishment of a 20 foot wide zone that is free of combustible materials. All cable trays located within this combustible-free zone are enclosed by a galvanized steel cable tray enclosure system to cover the cable trays that pass through the zone. This non-combustible configuration together with the enclosure and seals will prevent fire propagation across the combustible zone. A fixed suppression system of the water curtain-type is located within the combustible-free zone to provide assurance that a postulated fire APPENDIX 9A 9A-232 REV. 18, SEPTEMBER 2016
due to transient combustibles can be prevented from propagating through the combustible-free zone.
Several components associated with the credited safe shutdown methods are located in fire area 67. Components performing active, credited, redundant functions are located on opposite sides of fire area 67 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray up to the boundaries of the combustible free zone.
The locations of preaction sprinkler systems and water curtain suppression systems in fire area 67 are shown in Figure 9A-6.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 67.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.5.17 Fire Area 68: CRD Hydraulic Equipment Area and Neutron Monitoring System Area (el 253'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete (parts 2 hr adjacent to stairwell nos. 2 and 6)
N - Reinforced concrete (part) 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 2)
W - Reinforced concrete (part) 3 hr S - Reinforced concrete (part 2 hr adjacent to stairwell no. 5)
S - Reinforced concrete (part, None exterior wall)
E - Reinforced concrete (parts 2 hr adjacent to stairwell nos.
5 and 6)
E - Reinforced concrete (part, None exterior wall)
Interior boundary (part adjacent 3 hr to main steam tunnel) - Reinforced concrete Interior boundary (part) - Reinforced None concrete (primary containment wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
APPENDIX 9A 9A-233 REV. 18, SEPTEMBER 2016
Access: Doors connecting to stairwell 1.5 hr nos. 2, 5, and 6 Elevator door 0.75 hr Drywell access hatches None Watertight door connecting to 3 hr**
area 69 Equipment hatchways in floor and None ceiling (200 ft2 openings; protected by water curtain suppression systems)
- b. Major safety-related components in fire area:
- 1. DCWS valves HV-87-222, HV-87-223, HV-87-228, and HV-87-229 (supply and return line containment isolation)
- 2. CRD system master control station
- 3. CRD system hydraulic control units
- 4. Containment combustible gas analyzer sample package 20S206
- 5. Load center 20B203 (Div. 3)
- 6. Deleted
- 7. Instrument racks 20C004, 20C005, 20C026, and 20C027 (RPV instrumentation and LPCI injection valve P transmitters)
- 8. SLCS injection line containment isolation valves (HV-48-2F006A&B)
- 9. Reactor vessel pressure transmitters (PT-42-203A&B)
- 10. Reactor vessel water level transmitters (LT-42-215A&B)
- 11. Drywell pressure transmitters (PT-42-201 and PT-42-270)
- 12. PCIG supply line pressure monitoring instrumentation (PT-59-252A&B and PDS-59-206A&B)
- 13. Motor control center 20B223, which serves the following components:
(a) LPCI injection containment isolation valve (HV-51-2F017C)
(b) RHR loop "C" minimum flow recirculation isolation valve (HV-51-205A)
(c) RCIC system valves (HV-49-2F007 and HV-49-2F084)
(d) Standby liquid control pump 2CP208 (e) Containment combustible gas analyzer sample package 20S206 (f) Drywell pressure tap isolation valve (HV-42-247C)
(g) Drywell unit cooler fans 2A2V212 and 2E2V212 (h) Reactor recirculation pump cooling water isolation valves (HV-13-206 and HV-13-207)
APPENDIX 9A 9A-234 REV. 18, SEPTEMBER 2016
(i) Battery charger 2CD103 (j) Instrument ac transformer 20X108 (k) Feedwater line inboard maintenance isolation valve (HV-41-2F011B)
- 14. Motor control center 20B224, which serves the following components:
(a) LPCI injection containment isolation valve (HV-51-2F017D)
(b) RHR loop "D" minimum flow recirculation isolation valve (HV-51-205B)
(c) HPCI system valves (HV-55-2F002 and HV-55-2F095)
(d) Containment combustible gas analyzer sample package 20S205 (e) Drywell pressure tap isolation valve (HV-42-247D)
(f) Reactor recirculation pump cooling water source select valves (HV-13-208 and HV-13-211)
(g) Drywell unit cooler fans 2B2V212 and 2H2V212 (h) Battery charger 2DD103 (i) Instrument ac transformer 20X109
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the fire occurs within the coverage area of one of the two preaction sprinkler systems in this fire area, the system will provide automatic suppression of the fire. When the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual fusible link sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
If the fire occurs within the coverage area of the wet pipe sprinkler systems in this fire area, the systems will provide automatic suppression of the fire. When the compartment temperature rises to 200F, individual fusible link sprinklers will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 68 is divided into an eastern (68E) and a western (68W) portion through the establishment of a 20 foot wide zone that is free of combustible materials; no cable trays are located within this combustible-free zone.
68E The eastern portion of fire area 68 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-235 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods A and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 68.
68W The western portion of fire area 68 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the western half of fire area 68.
A postulated fire in the vicinity of the reactor vessel instrumentation reference leg backfill system could adversely affect reactor vessel water level indication due to reference leg density changes caused by an increase in water temperature. Since there are no fire initiators in close proximity to the backfill system tubing, administratively controlled APPENDIX 9A 9A-236 REV. 18, SEPTEMBER 2016
combustible free zones, throughout the locations of the backfill system will preclude any adverse effect on level indication, due to fire, prior to annunciation in the main control room.
Following annunciation in the main control room, the backfill system will be administratively isolated from the reference legs.
- f. Deviations:
Fire area 68 is divided into a western portion and an eastern portion through the establishment of a 20 foot wide zone that is free of combustible materials. No cable trays are located within this combustible-free zone. A fixed suppression system of the water curtain-type is located within the combustible-free zone to provide assurance that a postulated fire due to transient combustibles can be prevented from propagating through the combustible-free zone.
Several components associated with the credited safe shutdown methods are located in fire area 68. Components performing active, credited, redundant functions are located on opposite sides of fire area 68 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray up to the boundaries of the combustible free zone.
The locations of the preaction sprinkler systems and the water curtain suppression system in fire area 68 are shown in Figure 9A-7.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 68.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.5.18 Fire Area 69: Main Steam Tunnel (el 253'-0")
Construction Rating Walls: N - Reinforced concrete (contains 3 hr 233 ft2 of unrated metal blowout panels)
E - Reinforced concrete 3 hr S - Reinforced concrete (part, None primary containment wall)
S - Reinforced concrete (part) 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (part at 3 hr*
el 295'-3")
Reinforced concrete (part None at el 365' roof slab)
Access: Watertight door connecting to 3 hr**
APPENDIX 9A 9A-237 REV. 18, SEPTEMBER 2016
area 68 Steamtight doors connecting to areas 3 hr 28 and 70
- b. Major safety-related components in fire area:
- 1. Main steam line outboard containment isolation valves (HV-41-2F028A,B,C&D)
- 2. Feedwater line outboard containment isolation valves (HV-41-2F032A&B and HV-41-2F074A&B)
- 3. Main steam drain line outboard containment isolation valve (HV-41-2F019)
- 4. Deleted
- 5. RCIC injection valve (HV-49-2F013)
- 6. Steam line radiation sensors (RE-41-2N006A,B,C&D)
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the plant fire brigade will be dispatched to el 253' and/or el 283' in the reactor enclosure and will enter the main steam tunnel through doors at those elevations. The fire brigade will extinguish the fire using portable fire extinguishers or hoses from hose stations located outside the entrances to the main steam tunnel.
- e. Effect of fire on safe shutdown:
Fire area 69 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2.
9A.5.5.19 Fire Area 70: RWCU Compartments, FPCC Compartment, and General Equipment Area (el 283'-0" and el 295'-3")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating APPENDIX 9A 9A-238 REV. 18, SEPTEMBER 2016
Walls: N - Reinforced concrete (parts 2 hr adjacent to stairwell nos. 2 and 6)
N - Reinforced concrete (part) 3 hr W - Reinforced concrete (part 2 hr adjacent to stairwell no. 2)
W - Reinforced concrete (part) 3 hr S - Reinforced concrete (part 2 hr adjacent to stairwell no. 5)
S - Reinforced concrete (part, None exterior wall)
E - Reinforced concrete (parts 2 hr adjacent to stairwell nos.
5 and 6)
E - Reinforced concrete (part, None exterior wall)
Interior boundary (east and west 3 hr walls of area 69) - Reinforced concrete Interior boundary (primary None containment wall) - Reinforced concrete Floor: Reinforced concrete 3 hr*
Ceiling: einforced concrete 3 hr*
Access: Doors connecting to stairwell 1.5 hr nos. 2, 5, and 6 Steamtight door connecting to 3 hr area 69 Elevator door 0.75 hr Equipment hatchways in floor and None ceiling (200 ft2 openings; protected by water curtain suppression systems)
- b. Major safety-related components in fire area:
- 1. Containment hydrogen recombiner packages 2AS403 and 2BS403
- 2. SLCS components:
(a) Storage tank 20T204 (b) Injection pumps 2AP208, 2BP208, and 2CP208 (c) Explosive valves XV-48-2F004A,B&C
- 3. Core spray loop "A" injection valves (HV-52-2F004A and HV-52-2F005)
- 4. Core spray loop "B" injection valves (HV-52-2F004B, HV-52-2F037, and HV-52-208)
APPENDIX 9A 9A-239 REV. 18, SEPTEMBER 2016
- 5. RHR system valves:
(a) HV-51-2F017A,B,C&D (LPCI injection line containment isolation)
(b) HV-51-2F021A&B (drywell spray line containment isolation)
(c) HV-51-2F016A&B (drywell spray line shutoff)
- 6. HPCI system injection valve (HV-55-2F006)
- 7. RWCU supply line containment isolation valve (HV-44-2F004)
- 8. CAC system purge line containment isolation valves (HV-57-211, HV-57-215, HV-57-214, and HV-57-261)
- 9. Containment combustible gas analyzer sample package 20S205
- 10. Load center 20B204 (Div. 4)
- 11. Motor control center 20B213, which serves the following components:
(a) RHR loop "A" valves (b) Core spray loop "A" valves (c) Feedwater startup recirculation valve (HV-41-209A)
(d) Shutoff valves for main steam to miscellaneous steam-driven components (HV-01-208, HV-01-209, HV-01-211, and HV-01-250)
(e) Drywell chilled water source select valves (HV-87-220A&B, HV-87-221A&B, HV-87-224A&B, and HV-87-225A&B)
(f) Feedwater line outboard containment isolation valve (HV-41-2F032B)
(g) Feedwater line inboard maintenance isolation valve (HV-41-2F011A)
(h) SLCS pump 2AP208 (i) SLCS injection line containment isolation valve (HV-48-2F006A)
(j) RERS train "A" valves (HV-76-209, HV-76-284A, and HV-76-291A)
(k) CAC system containment isolation valves (HV-57-212 and HV-57-215)
(l) HVAC 120 V ac distribution panel 20X281
- 12. Motor control center 20B214, which serves the following components:
(a) RHR loop "B" valves (b) Core spray loop "B" valves (c) Drywell cooling water containment isolation valves (HV-87-222, HV-87-223, HV-87-228, and HV-87-229)
(d) Feedwater startup recirculation valve (HV-41-209B)
(f) Feedwater line outboard containment isolation valve (HV-41-2F032A)
(g) SLCS pump 2BP208 (h) SLCS injection line containment isolation valve (HV-48-2F006B)
(i) RERS train "B" valves (HV-76-210, HV-76-284B, and HV-76-291B)
(j) CAC system containment isolation valve (HV-57-211)
(k) HVAC 120 V ac distribution panel 20X282
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
APPENDIX 9A 9A-240 REV. 18, SEPTEMBER 2016
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the fire occurs within the coverage area of the preaction sprinkler system in this fire area, the system will provide automatic suppression of the fire. When the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual fusible link sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 70 is divided into an eastern (70E) and a western (70W) portion through the establishment of a 20 foot wide zone that is free of combustible materials; no cable trays are located within this combustible-free zone.
70E The eastern portion of fire area 70 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 70.
70W The western portion of fire area 70 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either encapsulated by a qualified fire barrier, associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area have redundant APPENDIX 9A 9A-241 REV. 18, SEPTEMBER 2016
components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the western half of fire area 70.
A postulated fire in the vicinity of the reactor vessel instrumentation reference leg backfill system could adversely affect reactor vessel water level indication due to reference leg density changes caused by an increase in water temperature. Since there are no fire initiators in close proximity to the backfill system tubing, administratively controlled combustible free zones, throughout the locations of the backfill system will preclude any adverse effect on level indication, due to fire, prior to annunciation in the main control room.
Following annunciation in the main control room, the backfill system will be administratively isolated from the reference legs.
- f. Deviations:
Fire area 70 is divided into a western portion and an eastern portion through the establishment of a 20 foot wide zone that is free of combustible materials. No cable trays are located within this combustible-free zone.
Several components associated with the credited safe shutdown methods are located in fire area 70. Components performing active, credited, redundant functions are located on opposite sides of fire area 70 and are separated by the combustible free zone. The only combustible materials in the intervening space are electrical cables in cable tray up to the boundaries of the combustible free zone.
The location of the preaction sprinkler system in fire area 70 is shown in Figure 9A-8.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 70.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.5.20 Fire Area 71: RWCU Holding Pump Compartments, RERS Fan Area, and Corridors (el 313'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating APPENDIX 9A 9A-242 REV. 18, SEPTEMBER 2016
Walls: N - Reinforced concrete (part adjacent to stairwell no. 6) 2 hr N - Reinforced concrete (part) 3 hr W - Reinforced concrete 3 hr S - Reinforced concrete (part) 3 hr S - Reinforced concrete (part adjacent to stairwell no. 5) 2 hr E - Reinforced concrete (part, exterior wall) None E - Reinforced concrete (part adjacent to stairwell no. 6) 2 hr Interior boundary - Reinforced concrete (primary None containment wall)
Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Doors connecting to stairwell nos. 5 and 6 1.5 hr Airlock door connecting to area 72 3 hr Double airlock door connecting to area 72 3 hr**
Elevator door 0.75 hr Equipment hatchway in floor None (200 ft2 opening; protected by water curtain suppression system)
- b. Major safety-related components in fire area:
- 1. RERS fans (2AV213 and 2BV213)
- 2. Load center 20B201 (Div. 1)
- 3. Load center 20B202 (Div. 2)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
For the purposes of safe shutdown analyses, fire area 71 is divided into an eastern (71E) and a western (71W) portion through the establishment of a 20 foot wide zone that is free of combustible materials; no cable trays are located within this combustible-free zone.
71E APPENDIX 9A 9A-243 REV. 18, SEPTEMBER 2016
The eastern portion of fire area 71 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown methods A and C for Unit 2 located in this fire area either have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods A and C will be available to shutdown Unit 2, for a fire in the eastern half of fire area 71.
71W The western portion of fire area 71 contains safe shutdown cables and equipment.
Cables required to support shutdown method C for Unit 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area, or can be credited for safe shutdown by manual operator actions to recover any functions that could be lost.
Cables required to support shutdown methods A, B, and C for Unit 1 are associated with equipment that have redundant components that are not affected by a fire in this area.
Equipment associated with shutdown methods A, B, and C for Unit 1 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and method C will be available to shutdown Unit 2, for a fire in the western half of fire area 71.
- f. Deviation:
Load centers 20B201 and 20B202 and their associated transformers are the only components credited for safe shutdown which are located in fire area 71. The horizontal separation between the two load centers is approximately 35 feet, and there are no cable trays located in the intervening space. A 20 foot wide zone that is free of combustible materials is maintained between the two load centers. A fixed suppression system of the APPENDIX 9A 9A-244 REV. 18, SEPTEMBER 2016
water curtain-type is located within the combustible-free zone to provide assurance that a postulated fire due to transient combustibles can be prevented from propagating through the combustible-free zone. To preclude the possibility of a spilled combustible liquid spreading across the area between the two load centers, a concrete curb is provided between the load centers, spanning the full width of the corridor in which the load centers are located. The curb is located within the coverage area of the water curtain system. To protect the load centers from radiant heat that could be generated by a postulated fire occurring in the area between the load centers, each load center is provided with a radiant heat shield. The heat shields are constructed of Marinite sheet and are located adjacent to the side of each load center that faces the concrete curb.
The measures described above for physical separation, fire suppression, and provision of fire barriers ensure that the plant can be safely shut down in the event of a fire in either the western portion or the eastern portion of fire area 48.
This is a deviation from the CMEB 9.5-1, C.5.b requirement for automatic suppression.
This deviation is documented in reference 9A.7.5.
9A.5.5.21 Fire Area 72: Reactor Enclosure Lower Fan Room (el 313'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (part, exterior wall) None S - Louvers open to outside atmosphere (part) None W - Reinforced concrete 3 hr Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete (part below fire area 73) None Reinforced concrete (part below fire area 74) 3 hr*
Access: Airlock door connecting to area 71 3 hr Double airlock door connecting to area 71 3 hr**
Emergency exit in ceiling (6.25 ft2 opening) None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Once the control room operators have been notified that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect on fire safe shutdown:
APPENDIX 9A 9A-245 REV. 18, SEPTEMBER 2016
Fire area 72 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5.22 Fire Area 73: Reactor Enclosure Upper Fan Room and Equipment Compartment Exhaust Filter Rooms (el 331'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete 3 hr W - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None E - Reinforced concrete (part adjacent to stairwell no. 5) 2 hr E - Reinforced concrete (part) 3 hr Floor: Reinforced concrete None Ceiling: Reinforced concrete 3 hr*
Access: Door connecting to stairwell no. 5 1.5 hr Two doors connecting to area 74 3 hr Emergency exit in floor (6.25 ft2 opening) None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
In the event of a fire in one of the reactor enclosure equipment compartment exhaust filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the affected ventilation system will be shut down and the plant fire brigade will be dispatched to extinguish the fire.
The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum.
- e. Effect on fire safe shutdown:
Fire area 73 does not contain safe shutdown cables and equipment.
APPENDIX 9A 9A-246 REV. 18, SEPTEMBER 2016
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.5.23 Fire Area 74: RERS Filter Compartments (el 331-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Reinforced concrete 3 hr W - Reinforced concrete 3 hr S - Reinforced concrete 3 hr E - Reinforced concrete (exterior wall) None Floor: Reinforced concrete 3 hr*
Ceiling: Reinforced concrete 3 hr*
Access: Two doors connecting to area 73 3 hr
- b. Major safety-related components in fire area:
- 1. RERS filter assemblies (2AS297 and 2BS297)
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
In the event of a fire in one of the reactor enclosure recirculation system filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum.
- e. Effect on fire safe shutdown:
Fire area 74 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.6 SAFE SHUTDOWN ANALYSIS - DIESEL GENERATOR ENCLOSURES APPENDIX 9A 9A-247 REV. 18, SEPTEMBER 2016
9A.5.6.1 Fire Area 79: Diesel Generator Cell 1A (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete (exterior wall) None Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 1A and auxiliaries
- 2. ESW supply and return shutoff valves (11-1131A, HV-11-132A, HV-11-133A, and HV-11-134A)
- 3. Diesel generator air exhaust fans 1AV512 and 1EV512
- 4. Diesel generator control board 1AC514
- 5. Dc distribution panel 1AD501 (serving diesel generator 1A and auxiliaries)
- 6. Motor control center 10B515, which serves the following components:
(a) Auxiliaries of diesel generator 1A (b) ESW loop "A" discharge valve (HV-11-011A)
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 79 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-248 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2.
9A.5.6.2 Fire Area 80: Diesel Generator Cell 1C (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 1C and auxiliaries
- 2. ESW supply and return shutoff valves (11-1131C, HV-11-132C, HV-11-133C, and HV-11-134C)
- 3. Diesel generator air exhaust fans 1CV512 and 1GV512
- 4. Diesel generator control board 1CC514
- 5. Dc distribution panel 1CD501 (serving diesel generator 1C and auxiliaries)
- 6. Motor control center 10B517, which serves auxiliaries of diesel generator 1C
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-249 REV. 18, SEPTEMBER 2016
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 80 contains safe shutdown cables and equipment.
Cables required to support shutdown method A for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method A for Units 1 and 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.6.3 Fire Area 81: Diesel Generator Cell 1B (el. 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 1B and auxiliaries APPENDIX 9A 9A-250 REV. 18, SEPTEMBER 2016
- 2. ESW supply and return shutoff valves (HV-11-131B, HV-11-132B, 11-1133B, and HV-11-134B)
- 3. Diesel generator air exhaust fans 1BV512 and 1FV512
- 4. Diesel generator control board 1BC514
- 5. Dc distribution panel 1BD501 (serving diesel generator 1B and auxiliaries)
- 6. Motor control center 10B516, which serves auxiliaries of diesel generator 1B
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190F, the deluge valve will open and prime the preaction sprinkler system with water. At 212F, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 81 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2.
9A.5.6.4 Fire Area 82: Diesel Generator Cell 1D (el. 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (part adjacent to equipment airlock) 3 hr E - Reinforced concrete (part, exterior wall) None S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr APPENDIX 9A 9A-251 REV. 18, SEPTEMBER 2016
Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 1D and auxiliaries
- 2. ESW supply and return shutoff valves (HV-11-131D, HV-11-132D, 11-1133D, and HV-11-134D)
- 3. Diesel generator air exhaust fans 1DV512 and 1HV512
- 4. Diesel generator control board 1DC514
- 5. Dc distribution panel 1DD501 (serving diesel generator 1D and auxiliaries)
- 6. Motor control center 10B518, which serves the following components:
(a) Auxiliaries of diesel generator 1D (b) ESW loop "B" discharge valve (HV-11-015B)
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 82 contains safe shutdown cables and equipment.
Cables required to support shutdown method B for Units 1 and 2 are either associated with equipment that have redundant components that are not affected by a fire in this area, or associated with equipment for which manual operator actions can be taken to recover any functions that could be lost. Equipment associated with shutdown method B for Units 1 and 2 located in this fire area may have redundant components that are not affected by a fire in this area, or manual operator actions may be taken to recover any essential functions that could be lost.
APPENDIX 9A 9A-252 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods A and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.6.5 Fire Area 83: Diesel Generator Cell 2A (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete (part adjacent to equipment airlock) 3 hr W - Reinforced concrete (part, exterior wall) None Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 2A and auxiliaries
- 2. ESW supply and return shutoff valves (11-2231A, HV-11-232A, HV-11-233A, and HV-11-234A)
- 3. Diesel generator air exhaust fans 2AV512 and 2EV512
- 4. Diesel generator control board 2AC514
- 5. Dc distribution panel 2AD501 (serving diesel generator 2A and auxiliaries)
- 6. Motor control center 20B515, which serves auxiliaries of diesel generator 2A
- c. Postulated fire in area:
APPENDIX 9A 9A-253 REV. 18, SEPTEMBER 2016
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 83 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods B and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods B and C will be available to shutdown Unit 2.9A.5.6.6 Fire Area 84: Diesel Generator Cell 2C (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 2C and auxiliaries
- 2. ESW supply and return shutoff valves (11-2231C, HV-11-232C, HV-11-233C, and HV-11-234C)
APPENDIX 9A 9A-254 REV. 18, SEPTEMBER 2016
- 3. Diesel generator air exhaust fans 2CV512 and 2GV512
- 4. Diesel generator control board 2CC514
- 5. Dc distribution panel 2CD501 (serving diesel generator 2C and auxiliaries)
- 6. Motor control center 20B517, which serves the following components:
(a) Auxiliaries of diesel generator 2C (b) ESW loop "A" discharge valve (HV-11-015A)
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 84 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.6.7 Fire Area 85: Diesel Generator Cell 2B (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr Floor: Reinforced concrete (portion on foundation slab) None APPENDIX 9A 9A-255 REV. 18, SEPTEMBER 2016
Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 2B and auxiliaries
- 2. ESW supply and return shutoff valves (HV-11-231B, HV-11-232B, 11-2233B, and HV-11-234B)
- 3. Diesel generator air exhaust fans 2BV512 and 2FV512
- 4. Diesel generator control board 2BC514
- 5. Dc distribution panel 2BD501 (serving diesel generator 2B and auxiliaries)
- 6. Motor control center 20B516, which serves the following components:
(a) Auxiliaries of diesel generator 2B (b) ESW loop "B" discharge valve (HV-11-011B)
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 85 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Unit 1 and methods A and C for Unit 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Unit 1 and methods A and C for Unit 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
APPENDIX 9A 9A-256 REV. 18, SEPTEMBER 2016
Therefore, methods A, B, and C will be available to shutdown Unit 1, and methods A and C will be available to shutdown Unit 2.
9A.5.6.8 Fire Area 86: Diesel Generator Cell 2D (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (exterior wall) None S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr Floor: Reinforced concrete (portion on foundation slab) None Reinforced concrete (portion above fire area 75) 3 hr*
Ceiling: Reinforced concrete roof slab None Access: Door at north side of cell 3 hr Door at south side of cell None
- b. Major safety-related components in fire area:
- 1. Diesel generator 2D and auxiliaries
- 2. ESW supply and return shutoff valves (HV-11-231D, HV-11-232D, 11-2233D, and HV-11-234D)
- 3. Diesel generator air exhaust fans 2DV512 and 2HV512
- 4. Diesel generator control board 2DC514
- 5. Dc distribution panel 2DD501 (serving diesel generator 2D and auxiliaries)
- 6. Motor control center 20B518, which serves auxiliaries of diesel generator 2D
- c. Postulated fire in area:
Leakage of fuel oil or lubricating oil from the diesel engine onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
A fire will activate the detectors in this area, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 190oF, the deluge valve will open and prime the preaction sprinkler system with water. At 212oF, individual sprinkler heads will open to control and/or extinguish the fire.
The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 86 contains safe shutdown cables and equipment.
APPENDIX 9A 9A-257 REV. 18, SEPTEMBER 2016
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.6.9 Fire Area 124: Diesel Generator Access Corridor for Unit 1 (el. 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Reinforced concrete (exterior wall) None Floor: Reinforced concrete None Ceiling: Reinforced concrete roof slab None Access: Door to outside at west end of corridor None Four doors at south side of corridor, leading to diesel generator cells 3 hr
- b. Major safety-related components in fire area:
- 1. RHRSW radiation monitors 0AS578 and 0BS578
- 2. Deleted
- 3. Primary containment post-LOCA radiation monitoring electronics (RY-26-191A,B,C,D)
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receipt of notification in the control room that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire.
APPENDIX 9A 9A-258 REV. 18, SEPTEMBER 2016
- e. Effect of fire on safe shutdown:
Fire area 124 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.6.10 Fire Area 125: Diesel Generator Access Corridor for Unit 2 (el. 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (exterior wall) None S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete None Ceiling: Reinforced concrete roof slab None Access: Door to outside at east end of corridor None Four doors at south side of corridor, 3 hr leading to diesel generator cells
- b. Major safety-related components in fire area:
- 1. Deleted
- 2. Primary containment post-LOCA radiation monitoring electronics (RY-26-291A,B,C,D)
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receipt of notification in the control room that a fire has occurred in this area, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 125 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
APPENDIX 9A 9A-259 REV. 18, SEPTEMBER 2016
9A.5.7 SAFE SHUTDOWN ANALYSIS - SPRAY POND PUMP STRUCTURE 9A.5.7.1 Fire Area 122: Spray Pond Pump Structure, Western Half
Construction Rating Walls: N - Reinforced concrete(exterior wall) None E - Reinforced concrete 3 hr S - Reinforced concrete (exterior wall) None W - Reinforced concrete (exterior wall) None Floor: Reinforced concrete foundation None Ceiling: Reinforced concrete roof slab None Access: Door connecting to area 123 3 hr Door connecting to outside None Roll-up door connecting to outside None
- b. Major safety-related components in fire area:
- 1. ESW pumps OAP548 and OCP548
- 2. RHRSW pumps OAP506 and OCP506
- 3. Sluice gates HV-12-003A&C
- 4. RHRSW valves:
(a) HV-12-031A&C (winter bypass line)
(b) HV-12-032A&C (spray networks A and C)
(c) HV-12-034A (spray network cross-connection)
(d) HV-12-112 and HV-12-114 (inlet from the Unit 1 cooling tower)
- 5. Spray pond pump structure supply fans OAV543 and OCV543
- 6. Motor control centers OOB519 (Div. 1) and OOB521 (Div. 3), which serve the following components:
(a) ESW loop "A" valves (b) RHRSW loop "A" valves (c) Spray pond pump structure supply fan OAV543 and associated heaters and dampers (d) Spray pond pump structure supply fan OCV543 and associated heaters and dampers
- 7. Class 1E instrument ac distribution panels 01Y501 (Div. 1) and 03Y501 (Div. 3)
- c. Postulated fire in area:
APPENDIX 9A 9A-260 REV. 18, SEPTEMBER 2016
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 122 contains safe shutdown cables and equipment.
Cables required to support shutdown methods B and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods B and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods B and C will be available to shutdown Units 1 and 2.
9A.5.7.2 Fire Area 123: Spray Pond Pump Structure, Eastern Half
Construction Rating Walls: N - Reinforced concrete(exterior wall) None E - Reinforced concrete (exterior wall) None S - Reinforced concrete (exterior wall) None W - Reinforced concrete 3 hr Floor: Reinforced concrete foundation None Ceiling: Reinforced concrete roof slab None Access: Door connecting to area 122 3 hr Door connecting to outside None Roll-up door connecting to outside None
- b. Major safety-related components in fire area:
- 1. ESW pumps OBP548 and ODP548
- 2. RHRSW pumps OBP506 and ODP506
- 3. Sluice gates HV-12-003B&D
- 4. RHRSW valves:
(a) HV-12-031B&D (winter bypass line)
APPENDIX 9A 9A-261 REV. 18, SEPTEMBER 2016
(b) HV-12-032B&D (spray networks B and D)
(c) HV (spray network cross-connection)
(d) HV-12-212 and HV-12-214 (inlet from the Unit 2 cooling tower)
- 5. Spray pond pump structure supply fans OBV543 and ODV543
- 6. Motor control centers OOB520 (Div. 2) and OOB522 (Div. 4), which serve the following components:
(a) ESW loop "B" valves (b) RHRSW loop "B" valves (c) Spray pond pump structure supply fan OBV543 and associated heaters and dampers (d) Spray pond pump structure supply fan ODV543 and associated heaters and dampers
- 7. Class 1E instrument ac distribution panels 02Y501 (Div. 2) and 04Y501 (Div. 4)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire.
- e. Effect of fire on safe shutdown:
Fire area 123 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A and C will be available to shutdown Units 1 and 2.
9A.5.8 SAFE SHUTDOWN ANALYSIS - TURBINE ENCLOSURE 9A.5.8.1 Fire Area 87: Condensate Pump-Room (el 189'-0")
Construction Rating APPENDIX 9A 9A-262 REV. 18, SEPTEMBER 2016
Walls: N - Reinforced concrete(exterior wall) None E - Reinforced concrete (below el 217 feet) 3 hr E - Concrete masonry unit (above el 217 feet) 2 hr S - Reinforced concrete (above el 217 feet) 3 hr W - Reinforced concrete 3 hr S- Reinforced concrete (below el 217 feet) None Floor: Reinforced concrete foundation mat None Reinforced concrete (supported by structural steel Ceiling: members without fireproofing) None Access: Watertight door connecting to area 88 3 hr**
Two doors connecting to area 113 1.5 hr Roll-up door connecting to area 113 2 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
- 1. Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- 2. Ignition of oil in a waste oil collection drum associated with the floor drain sump oil removal belt.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 87 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.2 Fire Area 88: Main Condenser Area and Feedwater Heater Rooms (el 200'-0" and el 239'-0")
Construction Rating Walls: N - Reinforced concrete and concrete masonry unit None APPENDIX 9A 9A-263 REV. 18, SEPTEMBER 2016
(exterior wall, below el 217')
N - Reinforced concrete and precast concrete panels (exterior wall, above el 217') None E - Reinforced concrete (below el 217'; contains 25 ft2 of unrated steel plate as separation from area 115) 3 hr E - Reinforced concrete and concrete masonry unit (above el 217') 3 hr S - Reinforced concrete and concrete masonry unit (below el 217') 3 hr S - Reinforced concrete (between el 217' and el 239') 3 hr S - Reinforced concrete (above el 239', contains 188 ft2 of unrated metal blowout panels) 3 hr W - Reinforced concrete (portion north of column line N) 3 hr W - Concrete masonry unit and precast concrete panels (exterior wall south of column line N) None Reinforced concrete foundation mat (el 200' and el Floor: 217') None Reinforced concrete (el 239' supported by structural steel ;members without fireproofing) None Ceiling: Reinforced concrete None Access: Watertight doors connecting to areas 87 and 94 3 hr**
Three doors connecting to area 89 3 hr Five doors connecting to area 97 3 hr Doors connecting to areas 95 and 113 3 hr
- b. Major safety-related components in fire area:
- 1. Main turbine stop valve position switches (ZS-01-104A,B,C&D)
- 2. Turbine control valve fast closure pressure switches (PS-01-102A,B,C&D)
- 3. Main steam line area temperature detectors
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. If the fire is in the main condenser area and the compartment temperature rises to 212oF, individual sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire.
- e. Effect of fire on safe shutdown:
APPENDIX 9A 9A-264 REV. 18, SEPTEMBER 2016
Fire area 88 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.3 Fire Area 89: Reactor Feedwater Pump Lube Oil Areas, Control Rod Drive Water Pump Area, and Condensate Filter/Demineralizer Compartments (el 200'-0")
Construction Rating N -Reinforced concrete and concrete masonry unit Walls: (part adjacent to fire areas 88 and 115) 3 hr N -Reinforced concrete (part adjacent to unexcavated area) None E -Reinforced concrete 3 hr S -Reinforced concrete 3 hr W -Reinforced concrete(exterior wall) None Reinforced concrete foundation mat (contains 76 ft2 Floor: grating opening connecting to area 115) None Reinforced concrete (contains156 ft2 grating opening Ceiling: connecting to area 94) None Access: Three doors connecting to area 88 3 hr Double steamtight door connecting to area 1 3 hr**
Door connecting to stairwell no. 30 1.5 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Leakage of lube oil from the reactor feedwater pump lube oil reservoirs onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-265 REV. 18, SEPTEMBER 2016
The heat generated by a fire in this area will activate the heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 212oF, individual fusible link sprinkler heads in the wet pipe sprinkler systems will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 89 contains cables associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.4 Fire Area 90: Air Ejector and Steam Packing Exhauster Compartment (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr concrete masonry unit S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr and concrete masonry unit Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to area 113 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-266 REV. 18, SEPTEMBER 2016
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 90 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.5 Fire Area 91: Air Ejector and Steam Packing Exhauster Compartment (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr and concrete masonry unit S - Reinforced concrete 3 hr and concrete masonry unit W - Reinforced concrete 3 hr Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to area 113 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-267 REV. 18, SEPTEMBER 2016
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 91 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.6 Fire Area 92: Mechanical Vacuum Pump-Room (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Reinforced concrete 3 hr S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr and concrete masonry unit Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to area 94 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
APPENDIX 9A 9A-268 REV. 18, SEPTEMBER 2016
Fire area 92 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.7 Fire Area 93: Air Compressor Area, EHC Power Unit Area, and Turbine Lube Oil Storage Tank Area (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Precast concrete None panels (exterior wall)
E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr W - Precast concrete None panels (exterior wall)
Floor: Reinforced concrete foundation None mat Ceiling: Reinforced concrete (contains None equipment hatch with 55 ft2 of steel plate and a 96 ft2 opening partially filled with grating)
Access: Door connecting to area 94 3 hr Door connecting to stairwell 1.5 hr no. 32 Roll-up door to outside None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Leakage of lube oil from the turbine lube oil storage tanks onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The heat generated by a fire in this area will activate the heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 212oF, individual fusible link sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished. No effect on safety-related systems will result from such a fire.
APPENDIX 9A 9A-269 REV. 18, SEPTEMBER 2016
- e. Effect of fire on safe shutdown:
Fire area 93 contains cables associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.8 Fire Area 94: Reactor Feedwater Pump-Turbine Compartments Reactor Feedwater Pump Access Area, Deep Bed Demineralizer Compartments (EL 217'-
0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr.
E - Reinforced concrete and 3 hr.
concrete masonry unit S - Reinforced concrete 3 hr.
(part)
S - Reinforced concrete 2 hr.
(part adjacent to area 120)
S - Reinforced concrete and None concrete masonry unit (part adjacent to area 89; contains 8 HVAC duct pene-trations without fire dampers)
S - Precast concrete panels None (part, exterior wall)
W - Precast concrete panels None (exterior wall)
Floor: Reinforced concrete (contains 156 ft2 None grating opening connecting to area 89)
Ceiling: Reinforced concrete contains None equipment hatch with 66 ft2 of steel plate)
Access: Doors connecting to areas 92 3 hr.
and 93 Doors connecting to area 120 1.5 hr.
Steamtight door connecting 3 hr.**
to area 2 Watertight door connecting to 3 hr.**
APPENDIX 9A 9A-270 REV. 18, SEPTEMBER 2016
area 88 Door connecting to stairwell 1.5 hr.
no. 30 Open stairwell leading up to None area 95 Roll-up doors to Entry Access None (5-Line Outage Support Facility)
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 94 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.9 Fire Area 95: MCC Room, TECW Equipment Area, and Turbine Lube Oil Reservoir and Centrifuge Area (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Precast concrete None panels (exterior wall)
E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr APPENDIX 9A 9A-271 REV. 18, SEPTEMBER 2016
W - Precast concrete None panels (exterior wall)
Floor: Reinforced concrete (contains None equipment hatch with 55 ft2 of steel plate and a 96 ft2 opening partially filled with grating)
Ceiling: Reinforced concrete None Access: Doors connecting to areas 3 hr 88 and 96 Door connecting to stairwell 1.5 hr no. 32 Open stairwell leading down None to area 94
- b. Major safety-related components in fire area:
- 1. Main turbine first-stage pressure transmitters (PT-01-1N052A,B,C&D)
- 2. Main steam line pressure transmitters (PT-01-1N076A,B,C&D)
- c. Postulated fire in area:
Leakage of lube oil from the turbine lube oil reservoir onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The heat generated by a fire in this area will activate the heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 212F, individual fusible link sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. In addition, a compartment temperature of 190F will cause actuation of the deluge systems located over the turbine lube oil reservoir and the turbine lube oil centrifuge. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 95 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
APPENDIX 9A 9A-272 REV. 18, SEPTEMBER 2016
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.10 Fire Area 96: Battery Room (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Reinforced concrete 3 hr S - Concrete masonry unit 3 hr W - Concrete masonry unit 3 hr Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 95 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke and heat generated by a fire in this area will activate the smoke and heat detectors which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 96 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
APPENDIX 9A 9A-273 REV. 18, SEPTEMBER 2016
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.11 Fire Area 97: Equipment Hatch Corridor (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr (part)
S - Precast concrete None panels (part, exterior wall)
W - Precast concrete None panels (exterior wall)
Floor: Reinforced concrete (contains None equipment hatch with 66 ft2 of steel plate)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Five doors connecting to 3 hr area 88 Steamtight door connecting 3 hr**
to area 7 Door connecting to stairwell 1.5 hr no. 30
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
APPENDIX 9A 9A-274 REV. 18, SEPTEMBER 2016
Fire area 97 contains cables associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.12 Fire Area 98: Reactor Recirculation Pump MG Set Area and Feedwater Heater Rooms (el 269'-0")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating Walls: N - Concrete masonry 3 hr unit E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr (part)
S - Precast concrete None panels (part, exterior wall)
W - Precast concrete None panels (exterior wall)
Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (contains None two equipment hatches covered with steel plate, one of 75 ft2 and one of 110 ft2)
Access: Door connecting to stairwell 1.5 hr no. 30 Door connecting to area 45 3 hr Two doors connecting to 3 hr area 114 Two roll-up doors connecting 3 hr**
to area 114
- b. Major safety-related components in fire area:
- 1. Junction boxes containing cables associated with the following components:
(a) Main turbine stop valve position switches (ZS-01-104A,B,C&D)
APPENDIX 9A 9A-275 REV. 18, SEPTEMBER 2016
(b) Turbine control valve fast closure pressure switches (PS-01-102A,B,C&D)
- c. Postulated fire in area:
Ignition of electrical cables in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. The preaction sprinkler system over the MG sets has been spared and is not in service. The ASD System has replaced the MG sets. Smoke detection has been added in the area over the ASD System.
- e. Effect of fire on safe shutdown:
Fire area 98 contains safe shutdown cables and equipment.
Cables required to support shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 201 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.13 Fire Area 99: Turbine Enclosure HVAC Area and Equipment Compartment Exhaust Filter Area (el 302'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Concrete masonry 3 hr unit E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr (part)
S - Precast concrete None panels (part, exterior wall)
W - Precast concrete None panels (exterior wall)
Floor: Reinforced concrete (contains None APPENDIX 9A 9A-276 REV. 18, SEPTEMBER 2016
two equipment hatches covered with steel plate, one of 75 ft2 and one of 110 ft2)
Ceiling: Metal deck, nonreinforced UL Class A concrete, and built-up roofing Access: Door connecting to stairwell 1.5 hr no. 30 Steamtight door connecting 3 hr to area 27 Double steamtight door connecting 3 hr**
to area 27
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
In the event of a fire in one of the turbine enclosure equipment compartment exhaust filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum. No effect on safety-related systems will result from a fire in this area.
- e. Effect of fire on safe shutdown:
Fire area 99 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.14 Fire Area 100: Condensate Pump-Room (el 189'-0")
Construction Rating Walls: N - Reinforced concrete None (exterior wall)
E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr APPENDIX 9A 9A-277 REV. 18, SEPTEMBER 2016
W - Reinforced concrete 3 hr (below el 217')
W - Reinforced concrete 2 hr (above el 217')
Floor: Reinforced concrete foundation None mat Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Watertight door connecting to 3 hr**
area 101 Two doors connecting to area 113 1.5 hr Roll-up door connecting 1.5 hr to area 113
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
- 1. Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- 2. Ignition of oil in waste oil collection drum associated with the floor drain sump oil removal belt.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 100 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear, via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.15 Fire Area 101: Main Condenser Area and Feedwater Heater Rooms (el 200'-0" and el 239'-0")
Construction Rating APPENDIX 9A 9A-278 REV. 18, SEPTEMBER 2016
Walls: N - Reinforced concrete None and concrete masonry unit (exterior wall, below el 217')
N - Reinforced concrete None and precast concrete panels (exterior wall, above el 217')
E - Reinforced concrete 3 hr (portion north of column line N)
E - Concrete masonry unit None and precast concrete panels (exterior wall south of column line N)
S - Reinforced concrete 3 hr and concrete masonry unit (below el 217')
S - Reinforced concrete 3 hr (between el 217'and el 239')
S - Reinforced concrete 3 hr (above el 239';
contains 188 ft2 of unrated metal blowout panels)
W - Reinforced concrete 3 hr (below el 217';
contains 25 ft2 of unrated steel plate as separation from area 115)
W - Reinforced concrete 3 hr and concrete masonry unit (above el 217')
Floor: Reinforced concrete foundation None mat (el 200' and el 217')
Reinforced concrete (el 239'; None supported by structural steel members without fireproofing)
Ceiling: Reinforced concrete None Access: Watertight doors connecting 3 hr**
to areas 100 and 107 Three doors connecting to 3 hr area 102 Five doors connecting to 3 hr area 110 Doors connecting to areas 3 hr 108 and 113 APPENDIX 9A 9A-279 REV. 18, SEPTEMBER 2016
- b. Major safety-related components in fire area:
- 1. Main turbine stop valve position switches (ZS-01-204A,B,C&D)
- 2. Turbine control valve fast closure pressure switches (PS-01-202A,B,C&D)
- 3. Main steam line area temperature detectors
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. If the fire is in the main condenser area and the compartment temperature rises to 212F, individual sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire.
- e. Effect of fire on safe shutdown:
Replacement text for paragraph e.
Fire area 101 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.16 Fire Area 102: Reactor Feedwater Pump Lube Oil Areas, Control Rod Drive Water Pump Area, and Condensate Filter/Demineralizer Compartments (el 200'-0")
Walls: N - Reinforced concrete 3 hr and concrete masonry unit (part adjacent to fire areas 101 and 115)
N - Reinforced concrete None APPENDIX 9A 9A-280 REV. 18, SEPTEMBER 2016
(part adjacent to unexcavated area)
E - Reinforced concrete None (exterior wall)
S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete foundation None mat Ceiling: Reinforced concrete (contains None 156 ft2 grating opening connecting to area 107)
Access: Three doors connecting to 3 hr area 101 Two double steamtight doors 3 hr**
connecting to area 1 Door connecting to stairwell 1.5 hr no. 31 Door connecting to area 115 None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area; Leakage of lube oil from the reactor feedwater pump lube oil reservoirs onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The heat generated by a fire in this area will activate the heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 212oF, individual fusible link sprinkler heads in the wet pipe sprinkler systems will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 102 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
APPENDIX 9A 9A-281 REV. 18, SEPTEMBER 2016
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.17 Fire Area 103: Air Ejector and Steam Packing Exhauster Compartment (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr and concrete masonry unit S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr and concrete masonry unit Floor: Reinforced concrete foundation None mat Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to area 113 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 103 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
APPENDIX 9A 9A-282 REV. 18, SEPTEMBER 2016
9A.5.8.18 Fire Area 104: Air Ejector and Steam Packing ExhausterCompartment (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete 3 hr and concrete masonry unit W - Reinforced concrete 3 hr and concrete masonry unit Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to area 113 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 104 contains cables associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
APPENDIX 9A 9A-283 REV. 18, SEPTEMBER 2016
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.19 Fire Area 105: Mechanical Vacuum Pump-Room (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Reinforced concrete 3 hr and concrete masonry unit S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to area 107 3 hr
- b. Major safety-related components in fire area; None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 105 contains cables associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
APPENDIX 9A 9A-284 REV. 18, SEPTEMBER 2016
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.20 Fire Area 106: Air Compressor Area, EHC Power Unit Area, and Turbine Lube Oil Storage Tank Area (el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Precast concrete None panels (exterior wall)
E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete foundation None mat Ceiling: Reinforced concrete (contains None equipment hatch with 55 ft2 of steel plate and a 96 ft2 opening partially filled with grating)
Access: Door connecting to area 107 3 hr Door connecting to stairwell 1.5 hr no. 33 Roll-up door to outside None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Leakage of lube oil from the turbine lube oil storage tanks onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The heat generated by a fire in this area will activate the heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 212oF, individual fusible link sprinkler heads in the APPENDIX 9A 9A-285 REV. 18, SEPTEMBER 2016
wet pipe sprinkler system will open to control and/or extinguish the fire. The plant fire brigade will be dispatched to ensure that the fire is extinguished. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 106 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.21 Fire Area 107: Reactor Feedwater Pump-Turbine Compartments and Reactor Feedwater Pump Access Area Deep Bed Demineralizer Compartments(el 217'-0")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr (part)
S - Reinforced concrete None and concrete masonry unit (part adjacent to area 102; contains 8 HVAC duct penetrations without fire dampers)
W - Reinforced concrete 3 hr and concrete masonry unit Floor: Reinforced concrete (contains None 156 ft2 grating opening connecting to area 102)
Ceiling: Reinforced concrete (contains None equipment hatch with 66 ft2 of steel plate)
Access: Doors connecting to areas 3 hr 105, 106, and an entryway to the Unit 2 reactor enclosure Two doors connecting to the 3 hr administration complex Steamtight door connecting 3 hr**
APPENDIX 9A 9A-286 REV. 18, SEPTEMBER 2016
to area 2 Watertight door connecting 3 hr**
to area 101 Door connecting to stairwell 1.5 hr no. 31 Roll-up door to outside None Open stairwell leading to None area 108
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 107 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.22 Fire Area 108: MCC Room, TECW Equipment Area, and Turbine Lube Oil Reservoir and Centrifuge Area (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Precast concrete None panels (exterior APPENDIX 9A 9A-287 REV. 18, SEPTEMBER 2016
wall)
E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete (contains None equipment hatch with 55 ft2 of steel plate and a 96 ft2 opening partially filled with grating)
Ceiling: Reinforced concrete None Access: Doors connecting to areas 3 hr 101 and 109 Door connecting to stairwell 1.5 hr no. 33 Open stairwell leading down None to area 107
- b. Major safety-related components in fire area:
- 1. Main turbine first-stage pressure transmitters (PT-01-2N052A,B,C&D)
- 2. Main steam line pressure transmitters (PT-01-2N076A,B,C&D)
- c. Postulated fire in area:
Leakage of lube oil from the turbine lube oil reservoir onto the floor of the compartment, with subsequent ignition of the oil.
- d. Consequences of fire with active fire suppression:
The heat generated by a fire in this area will activate the heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. If the compartment temperature rises to 212F, individual fusible link sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. In addition, a compartment temperature of 212F will cause actuation of the deluge systems located over the turbine lube oil reservoir and the turbine lube oil centrifuge. The plant fire brigade will be dispatched to ensure that the fire is extinguished.
- e. Effect of fire on safe shutdown:
Fire area 108 contains cables and equipment associated with providing power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown APPENDIX 9A 9A-288 REV. 18, SEPTEMBER 2016
methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.23 Fire Area 109: Battery Room (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Concrete masonry unit 3 hr S - Concrete masonry unit 3 hr W - Reinforced concrete 3 hr Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete 3 hr Access: Door connecting to area 108 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of battery cases and/or battery spacers as the result of an exposure fire.
- d. Consequences of fire with active fire suppression:
The smoke and heat generated by a fire in this area will activate the smoke and heat detectors which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 109 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by APPENDIX 9A 9A-289 REV. 18, SEPTEMBER 2016
a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.24 Fire Area 110: Equipment Hatch Corridor (el 239'-0")
- a. Structural and architectural design features of fire area (Figure 9A-7):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr (part)
S - Precast concrete None panels (part, exterior wall)
W - Reinforced concrete 3 hr Floor: Reinforced concrete (contains None equipment hatch with 66 ft2 of steel plate)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Five doors connecting to 3 hr area 101 Steamtight door connecting to 3 hr**
area 7 Door connecting to stairwell 1.5 hr no. 30
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
APPENDIX 9A 9A-290 REV. 18, SEPTEMBER 2016
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 110 contains cables associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.25 Fire Area 111: Reactor Recirculation Pump MG Set Area and Feedwater Heater Rooms (el 269'-0")
- a. Structural and architectural design features of fire area (Figure 9A-8):
Construction Rating Walls: N - Concrete masonry unit 3 hr E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr (part)
S - Precast concrete None panels (part, exterior wall)
W - Reinforced concrete 3 hr Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (contains None two equipment hatches covered with steel plate, one of 75 ft2 and one of 110 ft2)
Access: Door connecting to stairwell 1.5 hr no. 31 Door connecting to administration 3 hr complex Two doors connecting to area 114 3 hr Two roll-up doors connecting to 3 hr**
area 114 APPENDIX 9A 9A-291 REV. 18, SEPTEMBER 2016
- b. Major safety-related components in fire area:
- 1. Junction boxes containing cables associated with the following components:
(a) Main turbine stop valve position switches (ZS-01-204A,B,C&D)
(b) Turbine control valve fast closure pressure switches (PS-01-202A,B,C&D)
- c. Postulated fire in area:
Ignition of electrical cables in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling).
- d. Consequences of fire with active fire suppression:
The smoke generated by a fire in this area will activate the smoke detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. The preaction sprinkler system over MG sets has been spared and is not in service.
The ASD System has replaced the MG sets. Smoke detection has been added in the area over the ASD System.
- e. Effect of fire on safe shutdown:
Fire area 111 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 201 safeguard bus may be affected by a fire in this area. Offsite power to the 4kV switchgear via the 101 safeguard bus is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.26 Fire Area 112: Turbine Enclosure HVAC Area and Equipment Compartment Exhaust Filter Area (el 302'-0")
- a. Structural and architectural design features of fire area (Figure 9A-9):
Construction Rating Walls: N - Concrete masonry 3 hr unit E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr (part)
APPENDIX 9A 9A-292 REV. 18, SEPTEMBER 2016
S - Precast concrete None panels (part, exterior wall)
W - Reinforced concrete 3 hr Floor: Reinforced concrete (contains None two equipment hatches covered with steel plate, one of 75 ft2 and one of 110 ft2)
Ceiling: Metal deck, nonreinforced UL Class A concrete, and built-up roofing Access: Door connecting to stairwell 1.5 hr no. 31 Steamtight door connecting 3 hr to area 27
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of charcoal filters.
- d. Consequences of fire with active fire suppression:
In the event of a fire in one of the turbine enclosure equipment compartment exhaust filters, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum. No effect on safety-related systems will result from a fire in this area.
- e. Effect of fire on safe shutdown:
Fire area 112 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.8.27 Fire Area 113: Railroad Access Area and Generator Equipment Area (el 217'-0" and el 239'-0")
Construction Rating APPENDIX 9A 9A-293 REV. 18, SEPTEMBER 2016
Walls: N - Reinforced concrete None and concrete masonry unit (exterior wall)
E - Reinforced concrete 3 hr and concrete masonry unit (part)
E - Concrete masonry 2 hr unit (part adjacent to area 100)
S - Reinforced concrete 3 hr§ and concrete masonry unit W - Reinforced concrete 3 hr and concrete masonry unit (part)
W - Concrete masonry 2 hr unit (part adjacent to area 87)
Floor: Reinforced concrete foundation mat 3 hr Ceiling: Reinforced concrete (contains None a 1960 ft2 hatchway partially filled \
with grating)
Access: Two doors connecting to area 87 1.5 hr and two doors connecting to area 100 Roll-up door panel connecting 2 hr to area 87 Roll-up door connecting to area 100 1.5 hr Door connecting to areas 88, 90, 3 hr 91, 101, 103, and 104 Steamtight doors connecting to 3 hr areas 8, 10, 12, 14, 16, and 18 Steamtight door connecting to 3 hr**
stairwell no. 7 Double steamtight door connecting 3 hr**
to area 2 Walls denoted above by the § symbol are capable of being rated as 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> fire barriers, except for unrated wall penetration assemblies associated with the 4kV nonsegregated phase bus ducts.
These penetration assemblies are described in Section 9A.6.3. A maximum of two penetration assemblies are located in the wall indicated above. This wall separates fire area 113 from fire areas 12 and 18.
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
APPENDIX 9A 9A-294 REV. 18, SEPTEMBER 2016
Leakage of seal oil from the generator hydrogen seal oil units onto the floor of the compartment, with subsequent ignition of the oil or ignition of material stored in the Facility/laydown area, Floor Operators Break Facility (Rm 468A,B,C) and Plant Operators Building (Rm 468).
- d. Consequences of fire with active fire suppression:
A rise in compartment temperature to 140oF will cause the deluge valve to open and prime the preaction sprinkler system with water. At 165oF, individual sprinkler heads will open to control and/or extinguish the fire. A rise in the temperature of the Facility/laydown area, Floor Operators Break Facility (Rm 468A, B, C) or Plant Operators Building (Rm 468) to 155oF will open individual sprinklers of the wet pipe sprinkler system in that area to control and/or extinguish the fire in the associated area. In addition, a compartment temperature of 212oF will cause actuation of the deluge systems located over the generator hydrogen seal oil units. The plant fire brigade will be dispatched to ensure that the fire is extinguished. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 113 contains cables and equipment associated with providing offsite power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area. Equipment associated with providing offsite power to shutdown methods A, B, and C for Units 1 and 2 located in this fire area have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
- f. Deviations:
See Section 9A.6.3.
9A.5.8.28 Fire Area 114: Turbine Operating Floor (el 269'-0")
Construction Rating Walls: N - Precast concrete None panels (exterior wall)
E - Precast concrete None panels (exterior wall)
S - Reinforced concrete 3 hr and concrete masonry unit W - Precast concrete None panels (exterior wall)
Floor: Reinforced concrete (contains None a 1960 ft2 hatchway partially filled with grating, plus 14 equipment hatches APPENDIX 9A 9A-295 REV. 18, SEPTEMBER 2016
covered with steel plate)
Ceiling: Metal deck, nonreinforced UL Class A concrete, and built-up roofing Access: Doors connecting to stairwell 1.5 hr nos. 32 and 33 Two doors connecting to area 3 hr 98 and two doors connecting to area 111 Two roll-up doors connecting 3 hr**
to area 98 and two roll-up doors connecting to area 111 Two steamtight and bullet-resistant 3 hr**
doors connecting to area 24 Steamtight door connecting to 3 hr**
stairwell no. 7
- b. Major safety-related components located in fire area:
- 1. Main condenser pressure transmitters (PT-01-1N075A,B,C&D)
- 2. Junction boxes containing cables associated with the following components:
(a) Main turbine first-stage pressure transmitters (PT-01-1N052A,B,C&D)
(b) Main steam line pressure transmitters (PT-01-1N076A,B,C&D)
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray and ignition of materials present in the Control Room Annex. As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling, and an exposure fire involving the materials in the Control Room Annex would be extremely limited in scope and would be confined to a small area due to the configuration of the combustibles within the Control Room Annex. Ignition of the materials in the Control Room Annex is extremely unlikely in the absence of a fire source external to the materials.
- d. Consequences of fire with active fire suppression:
The smoke and heat generated by a fire in this area will activate the early warning smoke and heat detectors, which will cause an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. If the fire occurs under the turbine's appearance lagging or under the generator's appearance lagging, the preaction sprinkler system will provide automatic suppression of the fire. At 190F, the deluge valve will open and prime the preaction sprinkler system with water. At 212F, individual sprinkler heads will open to control and/or extinguish the fire. If the fire occurs at the Unit 1 and 2 turbine generator exciter bearings, the heat detectors within the exciter enclosure will annunciate the fire condition on the fire protection panel in the control room and initiate the coded alarm annunciation within the plant. A smoke detector suitable for high-velocity air flow in the exciter exhaust ductwork will annunciate the fire. The fixed CO2 local application system will be manually initiated by either a timed discharge or a spurt APPENDIX 9A 9A-296 REV. 18, SEPTEMBER 2016
discharge from push-button stations located in the vicinity of the exciter enclosure. No effect on safety-related systems will result from a turbine generator exciter bearing fire.
- e. Effect of fire on safe shutdown:
Fire area 114 contains cables associated with providing power to safe shutdown components.
Cables for offsite power which supports shutdown methods A, B, and C for Units 1 and 2 are associated with equipment that have redundant components that are not affected by a fire in this area.
The availability of offsite power to the 4kV switchgear via the 101 and 201 safeguard buses may be affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9 SAFE SHUTDOWN ANALYSIS - RADWASTE ENCLOSURE 9A.5.9.1 Fire Area 115: Radwaste Pipe Tunnel (el 183'-0", el 187'-0", el 191'-0", and el 200'-0")
Construction Rating Walls: West wall near column line 18, None approx. 19 feet north of column line N, between el 200' and el 205' - Steel plate (25 ft2)
East wall near column line 28, approx. None 19 feet north of column line N, between el 200' and el 205' - Steel plate (25 ft2)
North wall at 7.5 feet north of 3 hr column line J, between columns 23 and 26.6, and between el 200' and el 217' - Concrete masonry unit East wall at column line 26.6 3 hr between el 200' and el 217' - reinforced concrete South walls - Reinforced concrete 3 hr All other walls - Reinforced concrete None and concrete masonry unit Floor: Below zone 115D between column None lines 19.4 and 26.6 - Reinforced concrete (supported by structural steel members without fireproofing)
Below all other portions of the fire None area - Reinforced concrete foundation mat APPENDIX 9A 9A-297 REV. 18, SEPTEMBER 2016
Ceiling: Reinforced concrete (contains 76 ft2 None grating opening connecting to area 89)
Access: Door connecting to area 102 None Door connecting to area 118 3 hr
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 115 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9.2 Fire Area 116: Miscellaneous Radwaste Equipment Areas (el 162'-0")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (part 3 hr north of column line D)
E - Reinforced concrete (part None south of column line D, exterior wall)
S - Reinforced concrete None (exterior wall)
W - Reinforced concrete None Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (contains None equipment hatch filled with 49 ft2 of steel plate)
Access: Doors connecting to stairwell 1.5 hr APPENDIX 9A 9A-298 REV. 18, SEPTEMBER 2016
nos. 1 and 2
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
- 1. Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- 2. Ignition of charcoal filters.
- 3. Ignition of oil in a waste oil collection drum associated with the floor drain sump oil removal belt.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. In the event of a fire in the waste tank vent exhaust filter, a thermal sensor inside the filter plenum will cause an audible/visual annunciation to register on the fire protection panels in the control. The fire brigade will utilize a manual valve in the fire protection water supply system to initiate operation of a water spray system inside the filter plenum. No effect on safety-related systems will result from a fire in this area.
- e. Effect of fire on safe shutdown:
Fire area 116 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9.3 Fire Area 117: Offgas Pipe Tunnel (el 186'-0" and el 187'-6")
- a. Structural and architectural design features of fire area (Figure 9A-4):
Construction Rating Walls: All walls - Reinforced concrete None Floor: Reinforced concrete foundation mat None Ceiling: Reinforced concrete (supported by None structural steel members without fireproofing)
Access: Concrete hatch plugs None APPENDIX 9A 9A-299 REV. 18, SEPTEMBER 2016
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Since no combustible materials are located in this area, the origin of a postulated fire is indeterminate.
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 117 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9.4 Fire Area 118: Miscellaneous Radwaste Equipment Areas (el 191'-0")
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete (part 3 hr north of column line C)
E - Reinforced concrete (part, None exterior wall)
S - Reinforced concrete None (exterior wall)
W - Reinforced concrete (part, None exterior wall)
W - Reinforced concrete None (part adjacent to area 119; contains piping and electrical penetrations without fire-rated seals and HVAC duct penetrations without fire dampers)
Floor: Reinforced concrete (contains None equipment hatch filled with 49 ft2 of steel plate)
Ceiling: Reinforced concrete (supported by None structural steel members without fireproofing)
APPENDIX 9A 9A-300 REV. 18, SEPTEMBER 2016
Access: Door connecting to area 115 3 hr Doors connecting to stairwell 1.5 hr nos. 1 and 2 Door connecting to area 119 None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 118 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9.5 Fire Area 119: Offgas Equipment Areas (el 195'-0")
- a. Structural and architectural design features of fire area (Figure 9A-5):
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete None (contains piping and electrical penetrations without fire-rated seals and HVAC duct penetrations without fire dampers)
S - Reinforced concrete None (exterior wall)
W - Reinforced concrete None (exterior wall)
Floor: Reinforced concrete (supported None in some areas by structural steel members without fireproofing)
APPENDIX 9A 9A-301 REV. 18, SEPTEMBER 2016
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to stairwell 1.5 hr no. 1 Door connecting to area 118 None
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
Upon receiving notification that a fire has occurred in this area, the operator will dispatch the plant fire brigade to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 119 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9.6 Fire Area 120: Radwaste Control Room, Laundry, Decontamination and Change Areas, Waste Drum Storage Room, and Cask Loading Area (el 217'-0")
Renovated Area of Radwaste
Enclosure:
Data Acquisition Room, Storage Room, Source Storage/Standard's Preparation Room, Technician's Area (el 217'-0)
Chemical Building: Hot Lab, Frisk Area (corridor - RCA), Office Area, Air Lock, Corridor (Non RCA), Conference/Lunch, Cold Lab, Toilets, Locker Vestibule; Count Room, Instrument Lab (el 217;-0"); Penthouse (el. 234'6")
- a. Structural and architectural design features of fire area (Figure 9A-6):
Construction Rating Walls: N - Reinforced concrete 2 hr E - Reinforced concrete 3 hr S - Reinforced concrete (part, None exterior wall)
APPENDIX 9A 9A-302 REV. 18, SEPTEMBER 2016
S - Reinforced concrete (part 2 hr adjacent to stairwell no. 1)
W - Reinforced concrete None (exterior wall)
Chemistry Lab Building N - Precast Concrete Exterior None with Gypsum Board Interior S - Precast Concrete Exterior None with Gypsum Board Interior W - Precast Concrete Exterior None with Gypsum Board Interior E - Reinforced Concrete None Chemistry Lab Building (Penthouse)
N - Metal Siding with None Interior Insulation E - Metal Siding with None Interior Insulation S - Metal Siding with None Interior Insulation W - Metal Siding with None Interior Insulation Floor: Reinforced concrete (supported by None structural steel members without fireproofing)
Terrazzo Tile (Chem Lab Bldg) None Concrete (Chem Lab Bldg) None Ceiling: Reinforced concrete (supported by None structural steel members without fireproofing)
Suspended Tile (Chem Lab Bldg) None Roof: Metal Deck, Insulation and Built None Up Roofing (chem Lab Bldg, Penthouse)
Access: Door connecting to area 94 1.5 hr Door connecting to stairwell no. 4 3 hr Doors connecting to stairwell 1.5 hr nos. 2 and 3 Two doors to outside None Roll-up door to outside None Open stairwell leading up None to area 121 Two Doors open to exterior, one door None Connecting to Radwaste Enclosure Door connecting to Frisk Area/Corridor None (Chem Lab Bldg)
APPENDIX 9A 9A-303 REV. 18, SEPTEMBER 2016
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
If a fire occurs in the fire zones which are provided with smoke or heat detectors, the smoke and heat generated by the fire will activate the detectors, causing an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. If a fire occurs in the waste drum storage room and the temperature in that area rises to 212oF, individual fusible link sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. If the fire occurs in the Count room, Instrument Lab, health physics room, radwaste supervisors office, warm chem. Lab, counting room, file storage area, conventional chem. room, radiation chemical lab, or in the Penthouse, the preaction sprinkler system will provide automatic suppression of the fire. At 190oF, the deluge valve will open and prime the preaction sprinkle system with water. At 212oF, individual sprinkler will open to control and/or extinguish the fire.
If a fire occurs in the Chem Lab rooms and the temperature in that area raised to 165oF, individual fusible link sprinkler heads in the wet pipe sprinkler system will open to control and/or extinguish the fire. Again, the plant fire brigade will be dispatched to ensure that the fire is extinguished. No effect on safety-related systems will result from a fire in this area.
- e. Effect of fire on safe shutdown:
Fire area 120 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
9A.5.9.7 Fire Area 121: Centrifuge Rooms, Solid Radwaste Equipment Rooms, Ventilation Filter Compartments, and Supply and Exhaust Fan Areas (el 237'-0" and el 257'-0")
Construction Rating Walls: N - Reinforced concrete 3 hr E - Reinforced concrete 3 hr S - Reinforced concrete None (part, exterior wall)
S - Reinforced concrete (part None adjacent to area 120 between el 237' and el 257'; contains APPENDIX 9A 9A-304 REV. 18, SEPTEMBER 2016
piping and electrical penetrations without fire-rated seals)
W - Reinforced concrete (part None adjacent to area 120 between el 237' and el 257'; contains piping penetrations without fire-rated seals)
W - Reinforced concrete (part, None exterior wall)
Floor: Reinforced concrete (supported None by structural steel members without fireproofing)
Ceiling: Reinforced concrete (supported None by structural steel members without fireproofing)
Access: Door connecting to stairwell 1.5 hr no. 2 Two doors connecting to stairwell 1.5 hr no. 3 Open stairwell leading down to area None 120
- b. Major safety-related components in fire area:
None
- c. Postulated fire in area:
Ignition of electrical cabling in cable tray. (As discussed in Table 9A-3, the ignition of electrical cabling is extremely unlikely in the absence of a fire source external to the cabling.)
- d. Consequences of fire with active fire suppression:
If a fire occurs in the fire zones which are provided with smoke detectors, the smoke generated by the fire will activate the detectors, causing an audible/visual annunciation to register on the fire protection panels in the control room. Once the alarm has been received in the control room, the plant fire brigade will be dispatched to extinguish the fire. No effect on safety-related systems will result from such a fire.
- e. Effect of fire on safe shutdown:
Fire area 121 does not contain safe shutdown cables and equipment.
Offsite power to the 4kV switchgear via the 101 and 201 safeguard buses is not affected by a fire in this area.
Therefore, methods A, B, and C will be available to shutdown Units 1 and 2.
APPENDIX 9A 9A-305 REV. 18, SEPTEMBER 2016
9A.6 SPECIAL TOPICS 9A.6.1 ANALYSIS OF ASSOCIATED CIRCUITS Generic Letter 81-12, issued by the NRC on February 20, 1981, discussed the types of information that the NRC considers necessary for the completion of their reviews of safe shutdown capability in the event of a fire. One of the enclosures to Generic Letter 81-12 addressed the subject of associated circuits and the possibility that fire-induced damage to associated circuits could prevent operation or cause maloperation of the shutdown methods designated to be used in the event of a fire in the plant. Generic Letter 81-12 defines associated circuits to be those circuits (either safety-related or nonsafety-related) that have a separation from the equipment and cables of the redundant safe shutdown methods that is less than that required by section III.G.2 of Appendix R to 10CFR50 and also have any of the following:
- a. A common power source with the safe shutdown equipment, and the power source is not electrically protected from the circuit by coordinated circuit breakers, fuses, or similar devices.
- b. A connection to circuits of equipment whose spurious operation could adversely affect the shutdown capability.
- c. A common enclosure or raceway with safe shutdown cables, and are not electrically protected by circuit breakers, fuses, or similar devices.
In accordance with guidance contained in Generic Letter 81-12, an analysis has been performed for LGS to verify that fire-induced damage to associated circuits will not jeopardize the plant's safe shutdown capability. This analysis utilizes a systems approach, wherein the features of circuit design, such as overcurrent protection, are evaluated together with cable routing and separation criteria in order to confirm the adequacy of the electrical system design to prevent fire-induced damage to nonsafe shutdown circuits from jeopardizing safe shutdown capability. The methodology and results of the analysis are summarized in the following sections.
9A.6.1.1 Associated Circuits Involving Common Power Sources All systems and components that are relied on for achieving safe shutdown receive power from the Class 1E ac distribution system or Class 1E dc power system. Offsite power may be credited as the source for the Class 1E ac distribution system for fire areas which do not require Alternative Shutdown and for which the offsite source(s) to the 4kV switchgear is not affected by fire damage. The Emergency Seal Oil Pump (ESOP) that services the main generator and the Emergency Bearing Oil Pump (EBOP) that services the main turbine are powered exclusively by a dedicated non-Class 1E battery and do not involve a common power source with other plant equipment or systems. The main feed from the battery and the battery charger to both motors are protected by coordinated fault actuated protective devices. All other circuits, both Class 1E and non-Class 1E, are individually protected by coordinated fault actuated protective devices. Proper coordination among these protective devices is demonstrated by the time-current coordination curves shown in Figures 9A-13 through 9A-15 for the 4 kV and 440 V ac system, Figure 9A-16 for the 120 V ac system, and Figures 9A-17 through 9A-20 for the 125/250 V dc system. These curves are typical for each type of protective device and application that is represented. The time-current coordination curves show that for each voltage level, the individual circuit breakers or fuses will clear a fault prior to the operation of the source breaker or fuse protecting the source bus. Consequently, the fault-actuated protective devices will act to isolate any APPENDIX 9A 9A-306 REV. 16, SEPTEMBER 2016
faulted circuit without jeopardizing the availability of other circuits connected to the same power source.
Because of the use of fault-actuated protective devices in power circuits as described above, LGS does not have associated circuits involving common power sources, as defined by Generic Letter 81-12.
9A.6.1.2 Associated Circuits Involving Spurious Operation Components whose spurious operation could adversely affect the shutdown capability are considered to be essential for safe shutdown of the plant. These components and the circuits that serve them are therefore treated as part of the safe shutdown systems and are included in the review of separation between the different shutdown methods. Item 18 of Section 9A.3.2.2 describes the physical separation, fire barriers, and suppression systems that are provided to ensure that at least one shutdown method remains available to shut the plant down in the event of a fire.
Because of the design and analysis approach described above, LGS does not have associated circuits involving spurious operation, as defined by Generic Letter 81-12.
9A.6.1.3 Associated Circuits Involving Common Enclosures and Raceways Separation between the different divisions of Class 1E circuits and between Class 1E and non-Class 1E circuits is discussed in Sections 7.1.2.2.3.2 and 8.1.6.1.14.b. Cabling for Class 1E circuits is routed only in raceways designated for Class 1E use. Cabling for non-Class 1E circuits is routed only in raceways designated for non-Class 1E use, except for selected non-Class 1E loads fed from Class 1E buses, which are identified and treated as Class 1E and are routed in dedicated Class 1E raceways. Non-Class 1E cables identified and treated as Class 1E do not become associated with other Class 1E divisions.
The potential for propagation of an electrical fire in enclosures (either raceways or panels) is minimized by the selection of appropriate cable construction systems and by the provision of physical separation. Insulation and jacketing materials used in both Class 1E and non-Class 1E cables are flame retardant, as discussed in Table 9A-3.
As discussed in Section 9A.6.1.1, circuits are individually protected by coordinated fault-actuated protective devices. This protection ensures that faulted circuits in common enclosures will be isolated.
Because of the provisions described above for preventing fire propagation and isolating circuit faults in common enclosures, LGS does not have associated circuits involving common enclosures, as defined by Generic Letter 81-12.
9A.6.1.4 Summary For the reasons discussed in the preceding sections, LGS does not have associated circuits in any of the three categories established by Generic Letter 81-12. Therefore, fire-induced damage to circuits that are not designated as necessary for safe shutdown will not affect the operability of any of the four safe shutdown methods described in Section 9A.5.2.2.
9A.6.2 ANALYSIS OF HIGH/LOW PRESSURE INTERFACES APPENDIX 9A 9A-307 REV. 16, SEPTEMBER 2016
Generic Letter 81-12, issued by the NRC on February 20, 1981, discussed the types of information that the NRC considers necessary for the completion of their reviews of safe shutdown capability in the event of a fire. One of the enclosures to Generic Letter 81-12 addressed the subject of interfaces between high pressure and low pressure systems. The NRC's concern involves the valves that serve to isolate low pressure systems from the high pressure reactor coolant system. If the isolation valves at a given interface point consist of two electrically controlled valves in series, and a single fire could damage the cabling associated with both valves, both valves could be caused to open. This consequence could result in a fire-induced LOCA through the high/low pressure system interface.
Information Notice 87-50, issued by the NRC on October 9, 1987, expressed a concern that spurious opening of high/low pressure interface isolation valves would overpressurize the low pressure systems connected to the reactor coolant system, thereby creating the potential for a LOCA that cannot be isolated. The information notice specifically addressed the case of a bypass line around a check valve in the discharge lines of the RHR system for certain plants. This information notice states that "Because of this bypass line around the check valve, credit for the check valve in preventing a LOCA at the high and low pressure interface can no longer be given."
A review of the LGS design has been performed to verify that a high/low pressure interface LOCA cannot be caused by a single fire. Each system that contains interfaces between the RCPB and low pressure portions of the system was reviewed to identify the valves that provide isolation at the interface point, and also to assess the susceptibility of the valves to simultaneous opening due to fire-caused damage. Table 9A-12 identifies each such high/low pressure interface and lists the valves at the interface point.
9A.6.3 FIRE BARRIER PENETRATION ASSEMBLIES FOR 4 KV BUS DUCTS At el 239' in the control structure, 4 kV nonsegregated phase bus ducts penetrate some of the walls that separate the 4 kV switchgear compartments (fire areas 12 through 19) from each other and from adjacent compartments. The bus ducts are either 15.4 by 36 inches or 19.4 by 36 inches in size, and are constructed of steel plate having a thickness of 0.119 inch. Inside these steel ducts, copper bus bars are supported by porcelain insulators. At each wall penetration, a smoke and hot gas barrier is provided internal to the duct. The bus duct penetrations have been evaluated as being adequate for the hazards present. See reference 9A.7.12.
9A.6.4 ANALYSIS OF EFFECTS OF MULTIPLE HIGH-IMPEDANCE FAULTS ON THE SAFE SHUTDOWN CAPABILITY OF THE PLANT The NRC response to question No. 5.3.8 of "Appendix R Questions and Answers", an enclosure to Generic Letter 86-10 (issued by the NRC on April 24, 1986) states that in order to meet the separation criteria of sections III.G.2 and III.G.3 of Appendix R, multiple high impedance faults should be considered for all associated (nonsafe shutdown) circuits located in the fire area of concern.
In accordance with the guidelines contained in Generic Letter 86-10, a calculation has been performed for LGS to verify that postulated high impedance faults resulting from fire-induced damage to safe shutdown cables and associated (nonsafe shutdown) cables supplied from the same bus will not jeopardize the plant's safe shutdown capability. The calculation involved a review of protective device coordination with consideration given to multiple high impedance faults for power cables at the 13.2 kV, 4.16 kV, 480 V, and 120/208 V levels of the ac power distribution APPENDIX 9A 9A-308 REV. 16, SEPTEMBER 2016
system and at the 125 V and 250 V levels of the dc power distribution system. The methodology used in the calculation is based on the intention of implementing restorative actions for manually clearing the effects of multiple high impedance faults if the effects were determined to be detrimental to safe shutdown capability. The methodology used and the results of this study are summarized in the following sections.
9A.6.4.1 Methodology and Assumptions To determine if restorative actions were required for a particular circuit, a phase analysis approach was utilized as described below.
Phase 1 analysis is a gross screening of the power sources that support safe shutdown loads to evaluate the effects of a High Impedance Fault (HIF) load on the power source circuit breaker or fuse. All circuits from a safe shutdown bus are considered as experiencing simultaneous HIFs regardless of fire area influence. The combined load and HIF current is assumed just below the trip setpoint of the associated branch breaker and to continue indefinitely. The sum of all HIF and load currents on bus is determined and compared with the trip characteristics of the power supply protective device. The high impedance fault current contribution for each load was taken to be equal to the 1000 second current rating of the load's protective device. This value was chosen since it is the maximum current the protective device can pass for an indefinite time without a trip.
The high impedance fault currents were summed and compared to the 60 second rating of the feeder breaker. If the sum was less than this rating, no restorative actions were considered to be necessary.
The basis for this approach is a flame test that was performed by the licensee for the PBAPS and which showed that 54 seconds was the maximum duration of an high impedance fault. As before, if the high impedance fault current applied to the feeder breaker did not exceed its 60 second rating, no restorative actions were deemed necessary.
Phase 2 of the analysis is applied to those panels that fail the Phase 1 analysis. This analysis is performed in more detail using the actual circuit routing on a per fire area basis, with only those cables routed through the fire area of concern experiencing a simultaneous HIF. Phase 3 of the analysis is applied to those panels that fail the Phase 2 analysis and review normally de-energized loads while considering the routing of both power and control cables when evaluating specific fire areas. Phase 4 of the analysis is applied to those panels that fail the Phase 3 analysis. This Phase determines if the failed panels are required for safe shutdown in the subject fire area and whether restorative procedures are technically feasible to maintain panel operability in the event of a fire.
9A.6.4.2 Results The results and conclusions derived in this calculation were input into the LGS Fire Area Analysis Calculations which sufficiently demonstrate that the LGS post-fire safe shutdown capability for both units will not be jeopardized due to fire-induced multiple high impedance faults.
9A.6.5 MINIMUM EFFECTIVE DESIGN DENSITY (MEDD)
This Section will discuss the use of the Minimum Effective Design Density (MEDD) concept for determining the operability of water based suppression systems at the Limerick Generating Station Units 1 and 2 (LGS).
APPENDIX 9A 9A-309 REV. 16, SEPTEMBER 2016
In general, the design basis of the Limerick Generating Station sprinkler systems is to provide a density of 0.30 gpm/ft2 over the hydraulically most remote 3000 ft2 (unless specified otherwise).
Limerick Technical Specifications (now Technical Requirements Manual) define OPERABILITY as...
A system, subsystem, train, component, or device shall be operable or have operability when it is capable of performing its specified function(s).
In the referenced paragraph above, the words capable of performing its specific function(s) as applied to suppression systems, means their ability to control a fire. A literature review of fire test information on cable and oil fires was performed to determine the minimum effective design density. The focus of this review was to determine how low the design density could be and still extinguish a fire. The literature review was intended to determine the minimum effective design density that will control a fire.
EPRI Research, Sandia National Laboratories and Factory Mutual test reports were reviewed to determine the minimum effective density necessary to extinguish a cable tray fire or oil spill fire.
These two fire scenarios were selected because they present the greatest challenge to the plant sprinkler systems and these were the fires postulated in the FPER for the plant areas protected by the majority of the Technical Requirements Manual sprinkler systems.
A variety of tests and studies performed by Factory Mutual Research Corporation and Sandia National Laboratories were reviewed to determine the minimum effective density for automatic water based suppression systems at LGS. The purpose of the tests and studies performed was to determine the required automatic sprinkler design density necessary to extinguish a developing fire in grouped cable tray installations and oil spill fires.
9A.6.5.1 Cable Tray Fires Literature reviewed indicated that a delivered water application rate of 0.16 gpm/ft2 would control the most severe fire investigated.
Water application rate is generally quantified in terms of discharge density. The discharge density is the average rate of water reaching a unit floor area in unit time and is expressed in units of gpm/ft2 of floor area. In the tests reviewed, the water application rates are referenced as delivered densities. Specifically, delivered density means the density (gpm/ft2) which was delivered at the (top) surface of the burning test array. The delivered density should not be confused with the design density commonly used in sprinkler installation standards which is the density available from the sprinkler system in the absence of a fire. (Note: The LGS Specification for fire sprinkler system (M-49) is based on the design density concept) In a fire situation, the actual water reaching the burning fuel is usually less than the design density due to phenomena such as evaporation, or entrainment of droplets in the hot gas rising from a fire. A delivered density of 0.16 gpm/ft2 is expected to be equivalent to a design density of 0.25 gpm/ft2 because test indicates that the overall penetration of water is approximately 65% when 1/2 orifice standard sprinklers are used. Therefore, a design density of 0.25 gpm/ft2 is required to provide the minimum effective density for extinguishment of grouped cable tray fires.
9A.6.5.2 Oil Spill Fires Factory Mutual Research Corporation has conducted a series of fire tests with the purpose of determining whether automatic sprinklers will protect against lubricating oil spill fires. In all the tests, the floor based fires were quickly controlled and the test building was satisfactorily protected APPENDIX 9A 9A-310 REV. 16, SEPTEMBER 2016
by the sprinkler system. The conclusion of Factory Mutual Research Corporation testing indicated that automatic sprinklers will stop the spread and extinguish the fire in an oil spill on the floor with a design density of 0.13 gpm/ft2 with some margin of safety.
9A.6.5.3 Conclusion The design density specified for the systems at LGS is not required to be met to provide control and extinguishment of the anticipated fires at the plant and, therefore, is not required to be met for system(s) to be considered operable. The design density for the sprinkler systems at LGS will continue to be 0.3 gpm/ft2 (as specified specification M-49), however, for a system to be considered operable it needs to provide the minimum effective design densities of 0.25 gpm/ft2 for grouped electrical cable hazards or 0.13 gpm/ft2 for oil spill fire hazards.
APPENDIX 9A 9A-311 REV. 16, SEPTEMBER 2016
9A.7 REFERENCES 9A.7.1 Appendix A to BTP APCSP 9.5-1 Guidelines for Fire Protection for Nuclear Power Plants docketed prior to July 1, 1976 9A.7.2 BTP CMEB 9.5-1 Guidelines for Fire Protection for Nuclear Power Plants", Rev.
2, dated July ,1981 9A.7.3 Appendix R to 10 CFR 50 Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979 9A.7.4 NUREG-0991, LGS SER, August 30, 1983.
9A.7.5 NUREG-0991, Supplement 2, October 1984.
9A.7.6 NUREG-0991, Supplement 8, June 1989.
9A.7.7 NUREG-0991, Supplement 9, August 1989.
9A.7.8 Letter from Eugene J. Bradley (PECO) to Dr. Thomas E. Murley (USNRC) dated April 5, 1988 (Revision 10 to FPER).
9A.7.9 Engineering Analysis LEAF-0001 Smoke Detector Engr Analysis For Fire Areas 1, 2 & 7.
9A.7.10 Engineering Analysis LEAF-0002 Suppression System Evaluation.
9A.7.11 Engineering Analysis LEAF-0009 Galvanized Steel Cable Tray Covers In CFZ-5.
9A.7.12 Engineering Analysis LEAF-0010, Switchgear Room Bus Duct Penetrations.
9A.7.13 Letter from Darrell G. Eisenhut (NRC) to G. Bauer, Jr. (PECO) dated October 15, 1981,
Subject:
Appendix R of 10 CFR Part 50 - Fire Protection Rule (Limerick Generating Station, Units 1 and 2).
APPENDIX 9A 9A-312 REV. 14, SEPTEMBER 2008
LGS UFSAR Table 9A-1 FIRE PROTECTION EVALUATION Legend for Table 9A-1 The information presented in each column of Table 9A-1 is explained as follows:
Area-Zone: Identification code for fire areas and zones. Fire zones with identification codes beginning with the same number are located in the same fire area.
Structure: Location of the fire area-zone, by structure. Locations are shown on Figures 9A-4 through 9A-12.
Elevation: Elevation of the fire area-zone.
Room No.: The room number as indicated on the Architectural drawings.
Fire Area-Zone
==
Description:==
Description of compartments included within the fire area or fire zone.
SR (Safety-Related): Indicates whether or not the fire area or zone contains safety-related equipment or electrical cabling.
Floor Area (sqft): Floor area of the fire area or fire zone.
Fire Hazard Material: Type of combustible material located in the fire area-zone.
Combustible Loading: Designator of "Low" (<60,000 BTU/ft2), "Moderate"
(>60,000 BTU/ft2 or < 140,000 BTU/ft2) or "High"
(>140,000 BTU/ft2).
Combustible Loading Combustible loading changes which do not Change Limit (BTU/ ft2) exceed these limits do not require additional documentation/justification by the plant Fire Protection Program Engineer.
Detection Type/No.: Type of fire detectors and number detectors provided in the fire area or zone. Unless indicated otherwise, all smoke detectors are of the ionization type.
Suppression Type of fire suppression system and Type/Actuation: method of actuation in the fire area APPENDIX 9A 9A-314 REV. 17, SEPTEMBER 2014
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-315 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-316 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-317 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-318 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-319 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-320 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-321 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-322 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-323 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-324 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-325 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-326 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-327 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-328 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-329 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-330 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-331 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-332 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-333 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-334 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-335 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-336 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-337 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-338 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-339 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-340 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-341 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-342 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-343 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-344 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-345 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-346 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-347 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-348 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-349 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-350 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-351 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-352 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-353 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-354 REV. 18, SEPTEMBER 2016
LGS UFSAR LGS FIRE PROTECTION PROGRAM TABLE 9A-1 (Contd)
Security Related Information Figure withheld under 10 CFR 2.390 APPENDIX 9A 9A-355 REV. 18, SEPTEMBER 2016
Notes: (1) These smoke detectors are located below the suspended ceiling in the control room.
(2) These smoke detectors are located above the suspended ceiling in the control room.
(3) These heat detectors are located inside the charcoal filter plenum.
(4) These heat detectors are used to actuate the automatic suppression systems.
(5) Fire zone 113a and 113B are located in a portion of the turbine enclosure that is common to Unit 1 and Unit 2.
The detectors identified by this note will be installed east of column line 23 for Unit 2 operation.
(6) These smoke detectors are of the photoelectric-type.
(7) These detectors are located inside offices 467, 568, and 569.
(8) These detectors are located inside offices 552, 553, 570, and 571.
(9) These smoke detectors are located inside the test engineers workshop.
(10) Deleted (11) This sprinkler system is installed above and inside facility/laydown area.
(12) This sprinkler system is installed in the Floor Operations Break Facility (Rm 468A, B, C).
(13) This sprinkler system is installed in the Plant Operations Building (Rm 468).
(14) These heat detectors are located inside the Unit 1/2 turbine generator exciter enclosures (2 per unit).
(15) This smoke detectors are located in the Unit 1/2 turbine generator exciter exhaust ductwork (1 per unit).
(Detector suitable for high velocity airstream)
(16) This local application CO2 system is manually actuated for the Unit 1/2 turbine generator exciter bearings 11 and 12.
(17) Room 258A floor area is contained in Room 258 floor area.
(18) Room 236A floor area is contained in Room 263 floor area.
(19) Common - Ceiling level.
(20) Unit 1 - PGCC Floor.
(21) Unit 1 - non-PGCC Floor.
(22) Unit - Termination Cabinets.
(23) Unit 2 - PGCC Floor.
(24) Unit 2 - non-PGCC Floor.
(25) Unit 2 - Termination Cabinets.
(26) Ceiling Level.
(27) Raised Floor.
(28) Charcoal enclosed in steel filter plenums has been accepted by NRC.
APPENDIX 9A 9A-356 REV. 18, SEPTEMBER 2016
LGS UFSAR Table 9A-2 Heat of Combustion for Specific Materials (All values rounded to nearest 100 BTU/Unit)
Material Units Heat of Combustion (BTU/Unit)
Acetylene Gas lb 21,500 Alcohol (Ethyl) gal. 83,800 Alcohol (Methyl) gal. 65,500 Alpha Maritex Lead Shielding Blanket Linear foot 2404 Battery Cases (Butadiene Acrylonitrile) lb 17,200 Battery Spacers (Polystyrene Foam) lb 17,100 Cable Insulation lb 10,000 Carpet (Nylon) lb 13,600 Charcoal lb 14,900 Cloth (Cotton) lb 8,800 Floor Tiles (Polyester Resin) lb 10,000 Fuel Oil gal. 135,500 Gasoline gal. 120,600 Hydrogen lb 61,000 Lube Oil gal. 150,900 Lubricant (Grease) lb 150,900 Methane Gas cu. ft. 23,900 Oxygen cu. ft. 0 Paper lb 8,500 Plastic (Polyethylene) lb 20,000 Propane lb 21,700 Rubber (Butyl) lb 19,700 Trash (40 lb bag) ea. 290,500 Wood (White Pine) lb 8,300 R/A Insulation lb 8,000 Polycarbonate lb 13,300 Thermo-Lag 330-1 lb 7,000 Thermo-Lag 770-1 lb 4,800 Polyvinyl Chloride (PVC) lb 7,730 APPENDIX 9A 9A-357 REV. 18, SEPTEMBER 2016
LGS UFSAR Table 9A-3 INSULATION AND JACKETING MATERIALS USED FOR ELECTRICAL CABLING CABLE APPLICATION INSULATION JACKETING Communication Polyvinyl chloride Polyvinyl chloride Lighting Thermoplastic (THHN, None THWN, or THW)
Grounding Thermoplastic (THW) None Instrumentation Cross-linked Neoprene polyethylene Flamtrol (flame- Flamtrol retardant cross-linked polyolefin)
Coaxial and triaxial Cross-linked Cross-linked Polyolefin polyolefin 600 V control Cross-linked Neoprene polyethylene Rubber Neoprene Rockbestos Rockbestos "Heatzone I" "Heatzone I" 600 V power Cross-linked Neoprene polyethylene Ethylene propylene Hypalon rubber Cross-linked Polyvinyl chloride polyethylene(4)
Cross-linked Chlorinated Polyethylene polyethylene 5 kV and 15 kV Ethylene propylene Hypalon power(5) rubber Ethylene propylene Semi-conducting Rubber chlorinated polyethylene Cross-linked Polyvinyl chloride polyethylene Computer cables Cross-linked Neoprene polyethylene Rayolin F (cross-linked Flamtrol radiation-resistant polyolefin)
Multiconductor(1) Cross-linked Neoprene polyethylene APPENDIX 9A 9A-358 REV. 15, SEPTEMBER 2010
CABLE APPLICATION INSULATION JACKETING Multiconductor Cross-linked Neoprene or (shielded)(1) polyethylene or cross-linked cross-linked polyolefin modified polyolefin Twisted shielded Cross-linked Cross-linked pairs(1) polyalkene and modified polyolefin polyvinylidene fluoride Thermocouple(1) Cross-linked Cross-linked polyethylene polyethylene Coaxial (RG-type)(1) Cross-linked Cross-linked polyethylene polyethylene polyvinyl chloride Coaxial (twin Alkaneimide polymer Cross-linked conductor)(1) cross-linked polyethylene polyolefin polyvinyl chloride polyethylene Coaxial (high Cross-linked Cross-linked temperature, polyethylene polyethylene radiation resistant)(1)
Twisted pairs or Polyalkene and Cross-linked twisted triples polyvinylidene polyvinylidene (high performance)(1) fluoride fluoride and cross-linked polyolefin Armored Coaxial Cable Cross-linked Polyvinyl Chloride for Video signals from polyethylene Drywell video cameras(6)
Armored Multiconductor Cross-linked Polyvinyl Chloride cable for Drywell polyethylene video camera control and audio signals(6)
APPENDIX 9A 9A-359 REV. 15, SEPTEMBER 2010
(1)
These cables are associated with the PGCC and the deep bed demineralizer system.
(2)
Insulation for lighting cables and grounding cables is specified as flame retardant in accordance with the National Electric Code. Insulation and jacketing for all other cables, with the exception of communications cables, are specified to meet the IEEE 383 flame test requirements. An insignificant length of data cable which is not IEEE 383 rated is added to the Unit 1 and Unit 2 drywell as a part of the MUR (Measurement Uncertainty Recapture)
Project. The cables were evaluated and found to be acceptable. The cables were not routed together with cables associated with other plant systems.
(3)
Ignition of electrical cabling, in the absence of a fire source external to the cabling, is extremely unlikely. The consequences of an overload condition are minimized by conservative cable ratings and by the use of overload devices in power circuits and fault current interrupting devices in essentially all circuits. In addition, cable insulation and jacketing materials are chosen for their fire retardant and self-extinguishing properties, such that fuel contribution to a cable fire is minimized and propagation of a fire along cables is self-limiting.
(4)
This cable is used in the main condenser areas and condensate pump rooms.
(5)
Use of cross-linked polyethylene insulation and polyvinyl chloride applies to 15kV cable only.
(6)
These cables are used with the Health Physics temporary video cameras and Remote Console. The cables route video signals, control and audio signals to and from the Remote console, which is located outside the Drywell, to the cameras located inside the Drywell during outages.
APPENDIX 9A 9A-360 REV. 15, SEPTEMBER 2010
LGS UFSAR Table 9A-4 MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
00A119 101 SAFEGUARD BUS APS 0 428 018 429 019 430 016 431 017 432 014 433 015 434 012 435 013 447 113 YARD YARD 00A120 201 SAFEGUARD BUS APS 0 428 018 429 019 430 016 431 017 432 014 433 015 434 012 435 013 465 113 YARD YARD 00B131 480V MCC EPS C 619 027 00B132 480V MCC EPS D 619 027 00B519 480V MCC EPS A 1000 122 00B520 480V MCC EPS B 1005 123 00B521 480V MCC EPS C 1000 122 00B522 480V MCC EPS D 1005 123 01X566 TRANSFORMER EPS A 1000 122 01Y501 120V AC INST PANEL EPS A 1000 122 02X566 TRANSFORMER EPS B 1005 123 02Y501 120V AC INST PANEL EPS B 1005 123 03X566 TRANSFORMER EPS C 1000 122 03Y501 120V AC INST PANEL EPS C 1000 122 04X566 TRANSFORMER EPS D 1005 123 04Y501 120V AC INST PANEL EPS D 1005 123 0AP506 RHRSW PUMP "A" RHRSW A 1000 122 1-RHRSW-A 2-RHRSW-A 0AP548 ESW PUMP "A" ESW A 1000 122 0-ESW-A 0-ESW-R 0AV543 SYSTEM "A" FAN SPPV A 1000 122 1-RHRSW-A CABINET 2-RHRSW-A 0-ESW-R 0-ESW-A 0AX103 101 SAFEGUARD XMFR APS 0 YARD YARD APPENDIX 9A 9A-361 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
0AX104 101 SAFEGUARD XMFR APS 0 YARD YARD GROUNDING RESISTOR 0BP506 RHRSW PUMP "B" RHRSW B 1005 123 1-RHRSW-B 2-RHRSW-B 0BP548 ESW PUMP "B" ESW B 1005 123 0-ESW-B 0BV543 SYSTEM "B" FAN SPPV B 1005 123 2-RHRSW-B CABINET 1-RHRSW-B 0-ESW-B 0BX103 201 SAFEGUARD XMFR APS 0 YARD YARD 0BX104 201 SAFEGUARD XMFR APS 0 YARD YARD GROUNDING RESISTOR 0CP506 RHRSW PUMP "C" RHRSW A 1000 122 1-RHRSW-A 2-RHRSW-A 0CP548 ESW PUMP "C" ESW C 1000 122 0-ESW-A 0CV543 SYSTEM "C" FAN SPPV C 1000 122 1-RHRSW-A CABINET 2-RHRSW-A 0-ESW-A 0DP506 RHRSW PUMP "D" RHRSW B 1005 123 2-RHRSW-B 1-RHRSW-B 0DP548 ESW PUMP "D" ESW D 1005 123 0-ESW-B 0DV543 SYSTEM "D" FAN SPPV D 1005 123 0-ESW-B CABINET 1-RHRSW-B 2-RHRSW-B 101D112 101 NON-SAFEGUARD APS 0(D) 443 096 BATTERY 101D113 BATTERY CHARGER APS 0(D) 445 095 102D112 102 NON-SAFEGUARD APS 0(D) 443 096 BATTERY 102D113 BATTERY CHARGER APS 0(D) 445 095 105CROM* 105 CROMBY APS 0 YARD YARD SUBSTATION BREAKER 10A103 10 STATION AUX BUS APS 0 336 002 13.2 KV 10A115 D11 SAFEGUARD SWGR EPS A 435 013 10A116 D12 SAFEGUARD SWGR EPS B 433 015 10A117 D13 SAFEGUARD SWGR EPS C 434 012 10A118 D14 SAFEGUARD SWGR EPS D 432 014 APPENDIX 9A 9A-362 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
10B129 480V MCC EPS A 548 098 10B201 480V SAFEGUARD EPS A 602W 048W LOAD CTR 10B202 480V SAFEGUARD EPS B 602E 048E LOAD CTR 10B203 480V SAFEGUARD EPS C 402W 045W LOAD CTR 10B204 480V SAFEGUARD EPS D 506E 047E LOAD CTR 10B211 480V MCC EPS A 304W 044W 10B212 480V MCC EPS B 304E 044E 10B213 480V MCC EPS A 506W 047W 10B214 480V MCC EPS B 506E 047E 10B215 480V MCC EPS A 304W 044W 10B216 480V MCC EPS B 304E 044E 10B217 480V MCC EPS C 200 042 10B218 480V MCC EPS D 207 041 10B223 480V MCC EPS C 402W 045W 10B224 480V MCC EPS D 402E 045E 10B515 480V MCC EPS A 311A 079 10B516 480V MCC EPS B 311B 081 10B517 480V MCC EPS C 311C 080 10B518 480V MCC EPS D 311D 082 10D106 125/250V DC GROUND APS 0(D) 445 095 DETECTION CABINET 10D114 125/250V DC FUSE BOX APS 0(D) 445 095 10D115 125/250V DC FUSE APS 0(D) 338 089 BOX 10D116 UNIT CROSS TIE APS 0(D) 445 095 FUSE BOX 10D201 250V DC MCC EPS A 304W 044W 10D202 250V DC MCC EPS B 304E 044E 10D203 250V DC MCC EPS B 304E 044E 10P203 RCIC PUMP RCIC N/A 108 033 1-RCIC APPENDIX 9A 9A-363 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
10P204 HPCI PUMP HPCI N/A 109 034 1-HPCI 10P213 HPCI TURBINE HPCI B 109 034 1-HPCI AUXILIARY OIL PUMP 10TB-HPCIEGM* HPCI TURBINE FLOW HPCI B 200 042 CONTROL 10TB-RCICEGM* RCIC TURBINE FLOW RCIC A 108 033 CONTROL 10X106 TRANSFORMER EPS A 435 013 10X107 TRANSFORMER EPS B 433 015 10X108 TRANSFORMER EPS C 434 012 10X109 TRANSFORMER EPS D 432 014 10X110 TRANSFORMER EPS 0(A) 438 088 10X182 TRANSFORMER EPS C 619 027 10X183 TRANSFORMER EPS D 619 027 10X201 TRANSFORMER EPS A 602W 048W 10X202 TRANSFORMER EPS B 602E 048E 10X203 TRANSFORMER EPS C 402W 045W 10X204 TRANSFORMER EPS D 506E 047E 10X281 TRANSFORMER EPS A 619 027 10Y101 120V AC INST PANEL EPS A 435 013 10Y102 120V AC INST PANEL EPS B 433 015 10Y103 120V AC INST PANEL EPS C 434 012 10Y104 120V AC INST PANEL EPS D 432 014 10Y105 120V AC INST PANEL EPS 0(A) 438 088 10Y163 120V AC DIST PANEL EPS C 619 027 10Y164 120V AC DIST PANEL EPS D 619 027 10Y206 120V AC DIST PANEL EPS A 619 027 1A1D101 125V BATTERY EPS A 436 009 1A1D103 BATTERY CHARGER EPS A 436 009 1A1K513 1A1 DG STARTING SDG A 311A 079 AIR COMPRESSOR 1A1T558 A DG STARTING AIR SDG N/A 311A 079 RESERVOIR A1 1A2D101 125V BATTERY EPS A 436 009 1A2D103 BATTERY CHARGER EPS A 436 009 1A2T558 A DG STARTING AIR SDG N/A 311A 079 RESERVOIR A2 1AD102 125V DC DIST PANEL EPS A 435 013 APPENDIX 9A 9A-364 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
1AD105 125/250V DC BUS EPS A 436 009 FUSE BOX 1AD162 125V DC DIST PANEL EPS A 435 013 1AD501 125V DC POWER DIST EPS A 311A 079 PANEL 1AE205 1A RHR HEAT RHR N/A 203 032 1-RHRASC-C EXCHANGER 1-RHRSPC-C 1-RHRSPC-A 1-RHRSC-C 1-RHRLPCI-A 1-RHRASC-A 1-RHRSC-A 1AG501 DIESEL GENERATOR "A" SDG A 311A 079 1AP202 RHR PUMP "A" RHR A 102 032 1-RHRASC-A 1-RHRSPC-A 1-RHRSC-A 1-RHRLPCI-A 1AP514 DIESEL OIL SDG A YARD YARD TRANSFER PUMP 1AS252-1 A PCIG/ADS LONG PCIG N/A 304W 044W 1-RHRASC-A TERM NITROGEN 1-RHRASC-B BOTTLE 1AS252-2 A PCIG/ADS LONG PCIG N/A 304W 044W 1-RHRASC-A TERM NITROGEN 1-RHRASC-B BOTTLE 1AS252-3 A PCIG/ADS LONG PCIG N/A 304W 044W 1-RHRASC-A TERM NITROGEN 1-RHRASC-B BOTTLE 1AT003 MSRV ACCUMULATOR MSRV N/A 400 030 1AV208 RCIC COMPARTMENT REV A 108 033 1-RCIC UNIT COOLER 1AV209 HPCI COMPARTMENT REV B 109 034 1-HPCI UNIT COOLER 1AV210 RHR COMPARTMENT REV A 102 032 1-RHRASC-A UNIT COOLER 1-RHRLPCI-A 1-RHRSC-A 1-RHRSPC-A 1AV512 CELL "A" AIR DGEV A 311A 079 EXHAUST FAN 1B1D101 125V BATTERY EPS B 425 008 1B1D103 BATTERY CHARGER EPS B 425 008 APPENDIX 9A 9A-365 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
1B1K513 1B1 DG STARTING SDG B 311B 081 AIR COMPRESSOR 1B1T558 B DG STARTING AIR SDG N/A 311B 081 RESERVOIR B1 1B2D101 125V BATTERY EPS B 425 008 1B2D103 BATTERY CHARGER EPS B 425 008 1B2T558 B DG STARTING AIR SDG N/A 311B 081 RESERVOIR B2 1BD102 125V DC DIST PANEL EPS B 452 020 1BD105 125/250V DC BUS EPS B 425 008 FUSE BOX 1BD501 125V DC POWER DIST EPS B 311B 081 PANEL 1BE205 1B RHR HEAT RHR N/A 204 031 1-RHRASC-D EXCHANGER 1-RHRSPC-D 1-RHRSPC-B 1-RHRSC-D 1-RHRLPCI-B 1-RHRASC-B 1-RHRSC-B 1BG501 DIESEL GENERATOR SDG B 311B 081 "B"
1BP202 RHR PUMP "B" RHR B 103 031 1-RHRSC-B 1-RHRLPCI-B 1-RHRASC-B 1-RHRSPC-B 1BP514 DIESEL OIL SDG B YARD YARD TRANSFER PUMP 1BS252-1 B PCIG/ADS LONG PCIG N/A 304E 044E 1-RHRASC-A TERM NITROGEN 1-RHRASC-B BOTTLE 1BS252-2 B PCIG/ADS LONG PCIG N/A 304E 044E 1-RHRASC-A TERM NITROGEN 1-RHRASC-B BOTTLE 1BS252-3 B PCIG/ADS LONG PCIG N/A 304E 044E 1-RHRASC-A TERM NITROGEN 1-RHRASC-B BOTTLE 1BV208 RCIC COMPARTMENT REV A 108 033 1-RCIC UNIT COOLER 1BV209 HPCI COMPARTMENT REV B 109 034 1-HPCI UNIT COOLER APPENDIX 9A 9A-366 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
1BV210 RHR COMPARTMENT REV B 103 031 1-RHRASC-B UNIT COOLER 1-RHRLPCI-B 1-RHRSC-B 1-RHRSPC-B 1BV512 CELL "B" AIR DGEV B 311B 081 EXHAUST FAN 1C1K513 1C1 DG STARTING SDG C 311C 080 AIR COMPRESSOR 1C1T558 C DG STARTING AIR SDG N/A 311C 080 RESERVOIR C1 1C2T558 C DG STARTING AIR SDG N/A 311C 080 RESERVOIR C2 1CD101 125V BATTERY EPS C 324 004 1CD102 125V DC DISTPANEL EPS C 434 012 1CD103 BATTERY CHARGER EPS C 324 004 1CD105 125V DC BUS FUSE EPS C 324 004 BOX 1CD108 125V DC POWER DIST APS 0(D) 338 089 PANEL 1CD501 125V DC POWER DIST EPS C 311C 080 PANEL 1CG501 DIESEL GENERATOR SDG C 311C 080 "C"
1CP202 RHR PUMP "C" RHR C 102 032 1-RHRSC-C 1-RHRSPC-C 1-RHRLPCI-C 1-RHRASC-C 1CP514 DIESEL OIL SDG C YARD YARD TRANSFER PUMP 1CT003 MSRV ACCUMULATOR MSRV N/A 400 030 1CV210 RHR COMPARTMENT REV C 102 032 1-RHRASC-C UNIT COOLER "C" 1-RHRLPCI-C 1-RHRSC-C 1-RHRSPC-C 1CV512 CELL "C" AIR DGEV C 311C 080 EXHAUST FAN 1D1T558 D DG STARTING AIR SDG N/A 311D 082 RESERVOIR D1 1D2T558 D DG STARTING AIR SDG N/A 311D 082 RESERVOIR D2 1DD101 125V BATTERY EPS D 323 003 APPENDIX 9A 9A-367 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
1DD102 125V DC DIST PANEL EPS D 452 020 1DD103 BATTERY CHARGER EPS D 323 003 1DD105 125V DC BUS FUSE EPS D 323 003 BOX 1DD501 125V DC POWER DIST EPS D 311D 082 PANEL 1DG501 DIESEL GENERATOR SDG D 311D 082 "D"
1DP202 RHR PUMP "D" RHR D 103 031 1-RHRASC-D 1-RHRLPCI-D 1-RHRSC-D 1-RHRSPC-D 1DP514 DIESEL OIL SDG D YARD YARD TRANSFER PUMP 1DV210 RHR COMPARTMENT REV D 103 031 1-RHRSPC-D UNIT COOLER "D" 1-RHRASC-D 1-RHRLPCI-D 1-RHRSC-D 1DV512 CELL "D" AIR DGEV D 311D 082 EXHAUST FAN 1ET003 MSRV ACCUMULATOR ADS N/A 400 030 1EV210 RHR COMPARTMENT REV A 102 032 1-RHRASC-A UNIT COOLER 1-RHRLPCI-A 1-RHRSC-A 1-RHRSPC-A 1EV512 CELL "A" AIR DGEV A 311A 079 EXHAUST FAN 1FV210 RHR COMPARTMENT REV B 103 031 1-RHRASC-B UNIT COOLER 1-RHRSPC-B 1-RHRLPCI-B 1-RHRSC-B 1FV512 CELL "B" AIR DGEV B 311B 081 EXHAUST FAN 1GV210 RHR COMPARTMENT REV C 102 032 1-RHRSPC-C UNIT COOLER 1-RHRASC-C 1-RHRLPCI-C 1-RHRSC-C 1GV512 CELL "C" AIR DGEV C 311C 080 EXHAUST FAN 1HT003 MSRV ACCUMULATOR ADS N/A 400 030 APPENDIX 9A 9A-368 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
1HV512 CELL "D" AIR DGEV D 311D 082 EXHAUST FAN 1KT003 MSRV ACCUMULATOR ADS N/A 400 030 1MT003 MSRV ACCUMULATOR ADS N/A 400 030 1NT003 MSRV ACCUMULATOR MSRV N/A 400 030 1ST003 MSRV ACCUMULATOR ADS N/A 400 030 201D112 201 NON-SAFEGUARD APS 0(D) 460 109 BATTERY 201D113 BATTERY CHARGER APS 0(D) 461 108 202D112 202 NON-SAFEGUARD APS 0(D) 460 109 BATTERY 202D113 BATTERY CHARGER APS 0(D) 461 108 205WHIT* 205 WHITPAIN APS 0 YARD YARD SUBSTATION BREAKER 20A103 20 STATION AUX BUS APS 0 336 002 13.2 KV 20A115 D21 SAFEGUARD EPS A 429 019 SWITCHGEAR 20A116 D22 SAFEGUARD EPS B 431 017 SWITCHGEAR 20A117 D23 SAFEGUARD EPS C 428 018 SWITCHGEAR 20A118 D24 SAFEGUARD EPS D 430 016 SWITCHGEAR 20A121 CABLE BUS APS 0 336 002 346 107 354 107 357A 107 YARD YARD 20B129 480V MCC EPS A 564 111 20B201 480V SAFEGUARD EPS A 638W 071W LOAD CTR 20B202 480V SAFEGUARD EPS B 638E 071E LOAD CTR 20B203 480V SAFEGUARD EPS C 475W 068W LOAD CTR 20B204 480V SAFEGUARD EPS D 580W 070W LOAD CTR APPENDIX 9A 9A-369 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
20B211 480V MCC EPS A 370W 067W 20B212 480V MCC EPS B 370E 067E 20B213 480V MCC EPS A 580W 070W 20B214 480V MCC EPS B 580E 070E 20B215 480V MCC EPS A 370W 067W 20B216 480V MCC EPS B 370E 067E 20B217 480V MCC EPS C 284 064 20B218 480V MCC EPS D 279 065 20B223 480V MCC EPS C 475W 068W 20B224 480V MCC EPS D 475E 068E 20B515 480V MCC EPS A 315A 083 20B516 480V MCC EPS B 315B 085 20B517 480V MCC EPS C 315C 084 20B518 480V MCC EPS D 315D 086 20D106 125/250V DC GROUND APS 0(D) 463 108 DETECTION CABINET 20D114 125/250V DC FUSE APS 0(D) 461 108 BOX 20D115 125/250V DC FUSE APS 0(D) 351 102 BOX 20D201 250V DC MCC EPS A 370W 067W 20D202 250V DC MCC EPS B 370E 067E 20D203 250V DC MCC EPS B 370E 067E 20P203 RCIC PUMP RCIC N/A 179 056 2-RCIC 20P204 HPCI PUMP HPCI N/A 180 057 2-HPCI 20P213 HPCI TURBINE HPCI B 180 057 2-HPCI AUXILIARY OIL PUMP 20TB- HPCI TURBINE FLOW HPCI B 279 065 HPCIEGM* CONTROL 20TB- RCIC TURBINE FLOW RCIC A 179 056 RCICEGM* CONTROL 20X106 TRANSFORMER EPS A 429 019 20X107 TRANSFORMER EPS B 431 017 20X108 TRANSFORMER EPS C 428 018 20X109 TRANSFORMER EPS D 430 016 20X110 TRANSFORMER EPS 0(A) 464 101 20X201 TRANSFORMER EPS A 638W 071W 20X202 TRANSFORMER EPS B 638E 071E 20X203 TRANSFORMER EPS C 475W 068W APPENDIX 9A 9A-370 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
20X204 TRANSFORMER EPS D 580W 070W 20X281 TRANSFORMER EPS A 625 028 20X282 TRANSFORMER EPS B 619 027 20X283 TRANSFORMER EPS C 625 028 20X284 TRANSFORMER EPS D 619 027 20Y101 120V AC INST PANEL EPS A 429 019 20Y102 120V AC INST PANEL EPS B 431 017 20Y103 120V AC INST PANEL EPS C 428 018 20Y104 120V AC INST PANEL EPS D 430 016 20Y105 120V AC INST PANEL EPS 0(A) 464 101 20Y163 120V AC DIST PANEL EPS C 625 028 20Y164 120V AC DIST PANEL EPS D 619 027 20Y206 120V AC DIST PANEL EPS A 625 028 20Y207 120V AC DIST PANEL EPS B 619 027 2A1D101 125V BATTERY EPS A 427 011 2A1D103 BATTERY CHARGER EPS A 427 011 2A1K513 2A1 DG STARTING SDG A 315A 083 AIR COMPRESSOR 2A1T558 A DG STARTING AIR SDG N/A 315A 083 RESERVOIR A1 2A2D101 125V BATTERY EPS A 427 011 2A2D103 BATTERY CHARGER EPS A 427 011 2A2T558 A DG STARTING AIR SDG N/A 315A 083 RESERVOIR A2 2AD102 125V DC DIST PANEL EPS A 429 019 2AD105 125/250V DC BUS EPS A 427 011 FUSE BOX 2AD501 125V DC POWER DIST EPS A 315A 083 PANEL 2AE205 2ARHR HEAT RHR N/A 280 054 2-RHRSC-A EXCHANGER 2-RHRSPC-C 2-RHRSC-C 2-RHRLPCI-A 2-RHRASC-C 2-RHRASC-A 2-RHRSPC-A 2AG501 DIESEL GENERATOR "A" SDG A 315A 083 APPENDIX 9A 9A-371 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
2AP202 RHR PUMP "A" RHR A 173 054 2-RHRSPC-A 2-RHRASC-A 2-RHRLPCI-A 2-RHRSC-A 2AP514 DIESEL OIL SDG A YARD YARD TRANSFER PUMP 2AS252-1 A PCIG/ADS LONG PCIG N/A 370E 067E 2-RHRASC-A TERM NITROGEN 2-RHRASC-B BOTTLE 2AS252-2 A PCIG/ADS LONG PCIG N/A 370E 067E 2-RHRASC-A TERM NITROGEN 2-RHRASC-B BOTTLE 2AS252-3 A PCIG/ADS LONG PCIG N/A 370E 067E 2-RHRASC-A TERM NITROGEN 2-RHRASC-B BOTTLE 2AT003 MSRV ACCUMULATOR MSRV N/A 473 053 2AV208 RCIC COMPARTMENT REV A 179 056 2-RCIC UNIT COOLER 2AV209 HPCI COMPARTMENT REV B 180 057 2-HPCI UNIT COOLER 2AV210 RHR COMPARTMENT REV A 173 054 2-RHRASC-A UNIT COOLER 2-RHRLPCI-A 2-RHRSC-A 2-RHRSPC-A 2AV512 CELL "A" AIR DGEV A 315A 083 EXHAUST FAN 2B1D101 125V BATTERY EPS B 426 010 2B1D103 BATTERY CHARGER EPS B 426 010 2B1K513 2B1 DG STARTING SDG B 315B 085 AIR COMPRESSOR 2B1T558 B DG STARTING AIR SDG N/A 315B 085 RESERVOIR B1 2B2D101 125V BATTERY EPS B 426 010 2B2D103 BATTERY CHARGER EPS B 426 010 2B2T558 B DG STARTING AIR SDG N/A 315B 085 RESERVOIR B2 2BD102 125V DC DIST EPS B 453 021 PANEL 2BD105 125/250V DC BUS EPS B 426 010 FUSE BOX 2BD501 125V DC POWER EPS B 315B 085 DIST PANEL APPENDIX 9A 9A-372 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
2BE205 2B RHR HEAT RHR N/A 281 055 2-RHRSC-B EXCHANGER 2-RHRSPC-D 2-RHRSC-D 2-RHRLPCI-B 2-RHRASC-D 2-RHRASC-B 2-RHRSPC-B 2BG501 DIESEL GENERATOR "B" SDG B 315B 085 2BP202 RHR PUMP "B" RHR B 174 055 2-RHRSPC-B 2-RHRASC-B 2-RHRLPCI-B 2-RHRSC-B 2BP514 DIESEL OIL SDG B YARD YARD TRANSFER PUMP 2BS252-1 B PCIG/ADS LONG PCIG N/A 370E 067E 2-RHRASC-A TERM NITROGEN 2-RHRASC-B BOTTLE 2BS252-2 B PCIG/ADS LONG PCIG N/A 370E 067E 2-RHRASC-A TERM NITROGEN 2-RHRASC-B BOTTLE 2BS252-3 B PCIG/ADS LONG PCIG N/A 370E 067E 2-RHRASC-A TERM NITROGEN 2-RHRASC-B BOTTLE 2BV208 RCIC COMPARTMENT REV A 179 056 2-RCIC UNIT COOLER 2BV209 HPCI COMPARTMENT REV B 180 057 2-HPCI UNIT COOLER 2BV210 RHR COMPARTMENT REV B 174 055 2-RHRLPCI-B UNIT COOLER 2-RHRSC-B 2-RHRASC-B 2-RHRSPC-B 2BV512 CELL "B" AIR DGEV B 315B 085 EXHAUST FAN 2C1T558 CDG STARTING AIR SDG N/A 315C 084 RESERVOIR C1 2C2T558 C DG STARTING AIR SDG N/A 315C 084 RESERVOIR C2 2CD101 125V BATTERY EPS C 361 006 2CD102 125V DC DIST PANEL EPS C 428 018 2CD103 BATTERY CHARGER EPS C 361 006 APPENDIX 9A 9A-373 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
2CD105 125V DC BUS FUSE EPS C 361 006 BOX 2CD108 125V DC POWER DIST APS 0(D) 351 102 PANEL 2CD162 125V DC DIST PANEL EPS C 428 018 2CD501 125V DC POWER DIST EPS C 315C 084 PANEL 2CG501 DIESEL GENERATOR SDG C 315C 084 "C"
2CP202 RHR PUMP "C" RHR C 173 054 2-RHRASC-C 2-RHRLPCI-C 2-RHRSC-C 2-RHRSPC-C 2CP514 DIESEL OIL SDG C YARD YARD TRANSFER PUMP 2CT003 MSRV ACCUMULATOR MSRV N/A 473 053 2CV210 RHR COMPARTMENT REV C 173 054 2-RHRLPCI-C UNIT COOLER "C" 2-RHRSC-C 2-RHRSPC-C 2-RHRASC-C 2CV512 CELL "C" AIR DGEV C 315C 084 EXHAUST FAN 2D1T558 D DG STARTING AIR SDG N/A 315D 086 RESERVOIR D1 2D2T558 D DG STARTING AIR SDG N/A 315D 086 RESERVOIR D2 2DD101 125V BATTERY EPS D 360 005 2DD102 125V DC DIST PANEL EPS D 453 021 2DD103 BATTERY CHARGER EPS D 360 005 2DD105 125V DC BUS FUSE EPS D 360 005 BOX 2DD501 125V DC POWER DIST EPS D 315D 086 PANEL 2DG501 DIESEL GENERATOR SDG D 315D 086 "D"
2DP202 RHR PUMP "D" RHR D 174 055 2-RHRASC-D 2-RHRLPCI-D 2-RHRSC-D 2-RHRSPC-D 2DP514 DIESEL OIL SDG D YARD YARD TRANSFER PUMP APPENDIX 9A 9A-374 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
2DV210 RHR COMPARTMENT REV D 174 055 2-RHRASC-D UNIT COOLER "D" 2-RHRLPCI-D 2-RHRSC-D 2-RHRSPC-D 2DV512 CELL "D" AIR DGEV D 315D 086 EXHAUST FAN 2ET003 MSRV ACCUMULATOR ADS N/A 473 053 2EV210 RHR COMPARTMENT REV A 173 054 2-RHRLPCI-A UNIT COOLER 2-RHRSC-A 2-RHRSPC-A 2-RHRASC-A 2EV512 CELL "A" AIR DGEV A 315A 083 EXHAUST FAN 2FV210 RHR COMPARTMENT REV B 174 055 2-RHRASC-B UNIT COOLER 2-RHRLPCI-B 2-RHRSC-B 2-RHRSPC-B 2FV512 CELL "B" AIR DGEV B 315B 085 EXHAUST FAN 2GV210 RHR COMPARTMENT REV C 173 054 2-RHRSPC-C UNIT COOLER 2-RHRASC-C 2-RHRLPCI-C 2-RHRSC-C 2GV512 CELL "C" AIR DGEV C 315C 084 EXHAUST FAN 2HT003 MSRV ACCUMULATOR ADS N/A 473 053 2HV210 RHR COMPARTMENT REV D 174 055 2-RHRASC-D UNIT COOLER 2-RHRLPCI-D 2-RHRSC-D 2-RHRSPC-D 2HV512 CELL "D" AIR DGEV D 315D 086 EXHAUST FAN 2KT003 MSRV ACCUMULATOR ADS N/A 473 053 2MT003 MSRV ACCUMULATOR ADS N/A 473 053 2NT003 MSRV ACCUMULATOR MSRV N/A 473 053 2ST003 MSRV ACCUMULATOR ADS N/A 473 053 51-1F067A RHR PUMP SHUTDOWN RHR N/A 203 032 1-RHRSC-C COOLING SUCTION VALVE APPENDIX 9A 9A-375 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
51-1F067B RHR PUMP SHUTDOWN RHR N/A 204 031 1-RHRSC-D COOLING SUCTION VALVE 51-2F067A RHR PUMP SHUTDOWN RHR N/A 280 054 2-RHRSC-C COOLING SUCTION VALVE 51-2F067B RHR PUMP SHUTDOWN RHR N/A 281 055 2-RHRSC-D COOLING SUCTION VALVE FC-55-1R600 FLOW CONTROLLER HPCI B 533 024 FC-55-2R600 FLOW CONTROLLER HPCI B 533 024 FI-11-013A ESW LOOP A SUPPLY ESW A 533 024 0-ESW-A FI-11-013B ESW LOOP B SUPPLY ESW B 533 024 0-ESW-B FI-49-1R001-1 PUMP DISCHARGE RCIC A 540 026 1-RCIC LINE FLOW INDICATOR FI-49-1R600-1 PUMP DISCHARGE RCIC A 533 024 1-RCIC LINE FLOW INDICATOR FI-49-2R001-1 PUMP DISCHARGE RCIC A 540 026 2-RCIC LINE FLOW INDICATOR FI-49-2R600-1 PUMP DISCHARGE RCIC A 533 024 2-RCIC LINE FLOW INDICATOR FI-51-1R005 HEAT EXCHANGER RHR A 540 026 1-RHRSC-A DISCHARGE LINE 1-RHRSPC-A FLOW INDICATOR FI-51-1R602A RHR HEAT EXCHANGER RHRSW A 533 024 1-RHRSW-A "A" SHELL SIDE INLET FLOW INDICATOR FI-51-1R602B RHR HEAT EXCHANGER RHRSW B 533 024 1-RHRSW-B "B" SHELL SIDE INLET FLOW INDICATOR FI-51-1R603A HEAT EXCHANGER RHR A 533 024 1-RHRSC-C DISCHARGE LINE 1-RHRSPC-C FLOW INDICATOR 1-RHRSPC-A 1-RHRLPCI-A 1-RHRASC-C 1-RHRASC-A 1-RHRSC-A APPENDIX 9A 9A-376 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
FI-51-1R603B HEAT EXCHANGER RHR B 533 024 1-RHRSC-B DISCHARGE LINE 1-RHRSPC-D FLOW INDICATOR 1-RHRSC-D 1-RHRLPCI-B 1-RHRASC-D 1-RHRASC-B 1-RHRSPC-B FI-51-1R603C LOOP "C" DISCHARGE RHR C 533 024 1-RHRLPCI-C LINE FLOW INDICATOR FI-51-1R603D LOOP "D" DISCHARGE RHR D 533 024 1-RHRLPCI-D LINE FLOW INDICATOR FI-51-2R005 HEAT EXCHANGER RHR A 540 026 2-RHRSC-A DISCHARGE LINE 2-RHRSPC-A FLOW INDICATOR FI-51-2R602A RHR HEAT EXCHANGER RHRSW A 533 024 2-RHRSW-A "A" SHELL SIDE INLET FLOW INDICATOR FI-51-2R602B RHR HEAT EXCHANGER RHRSW B 533 024 2-RHRSW-B "B" SHELL SIDE INLET FLOW INDICATOR FI-51-2R603A HEAT EXCHANGER RHR A 533 024 2-RHRSPC-C DISCHARGE LINE 2-RHRASC-C FLOW INDICATOR 2-RHRLPCI-A 2-RHRSC-A 2-RHRSC-C 2-RHRSPC-A 2-RHRASC-A FI-51-2R603B HEAT EXCHANGER RHR B 533 024 2-RHRSPC-D DISCHARGE LINE 2-RHRSPC-B FLOW INDICATOR 2-RHRSC-D 2-RHRSC-B 2-RHRLPCI-B 2-RHRASC-B 2-RHRASC-D FI-51-2R603C LOOP "C" DISCHARGE RHR C 533 024 2-RHRLPCI-C LINE FLOW INDICATOR FI-51-2R603D LOOP "D" DISCHARGE RHR D 533 024 2-RHRLPCI-D LINE FLOW INDICATOR FI-55-1R600-1 PUMP DISCHARGE HPCI B 533 024 1-HPCI LINE FLOW INDICATOR FI-55-2R600-1 PUMP DISCHARGE HPCI B 533 024 2-HPCI LINE FLOW INDICATOR APPENDIX 9A 9A-377 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
FIC-49-1R001 FLOW INDICATING RCIC A 540 026 CONTROLLER FIC-49-1R600 FLOW INDICATING RCIC A 533 024 CONTROLLER FIC-49-2R001 FLOW INDICATING RCIC A 540 026 CONTROLLER FIC-49-2R600 FLOW INDICATING RCIC A 533 024 CONTROLLER FIS-49-1N651 FLOW INDICATING RCIC A 542 025 SWITCH FIS-49-2N651 FLOW INDICATING RCIC A 542 025 SWITCH FIS-55-1N651 PUMP DISCHARGE HPCI B 542 025 LINE FLOW INDICATING SWITCH FIS-55-2N651 PUMP DISCHARGE HPCI B 542 025 LINE FLOW INDICATING SWITCH FISL-51-1N652A FLOW INDICATING RHR A 542 025 SWITCH FISL-51-1N652B FLOW INDICATING RHR B 542 025 SWITCH FISL-51-1N652C FLOW INDICATING RHR C 542 025 SWITCH FISL-51-1N652D FLOW INDICATING RHR D 542 025 SWITCH FISL-51-2N652A FLOW INDICATING RHR A 542 025 SWITCH FISL-51-2N652B FLOW INDICATING RHR B 542 025 SWITCH FISL-51-2N652C FLOW INDICATING RHR C 542 025 SWITCH FISL-51-2N652D FLOW INDICATING RHR D 542 025 SWITCH FS-49-1N659 FLOW SWITCH RCIC A 542 025 FS-49-2N659 FLOW SWITCH RCIC A 542 025 FS-55-1N659 FLOW SWITCH HPCI B 542 025 FS-55-2N659 FLOW SWITCH HPCI B 542 025 FT-49-2N051 FLOW TRANSMITTER RCIC A 279 065 FT-51-1N001 FLOW TRANSMITTER RHR A 304W 044W FT-51-1N007A FLOW TRANSMITTER RHRSW A 200 042 FT-51-1N007B FLOW TRANSMITTER RHRSW B 207 041 APPENDIX 9A 9A-378 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
FT-51-1N015A FLOW TRANSMITTER RHR A 304W 044W FT-51-1N015B FLOW TRANSMITTER RHR B 304E 044E FT-51-1N015C FLOW TRANSMITTER RHR C 304W 044W FT-51-1N015D FLOW TRANSMITTER RHR D 304E 044E FT-51-1N052A FLOW TRANSMITTER RHR A 304W 044W FT-51-1N052B FLOW TRANSMITTER RHR B 304E 044E FT-51-1N052C FLOW TRANSMITTER RHR C 304W 044W FT-51-1N052D FLOW TRANSMITTER RHR D 304E 044E FT-51-2N001 FLOW TRANSMITTER RHR A 370W 067W FT-51-2N007A FLOW TRANSMITTER RHRSW A 189 062 FT-51-2N007B FLOW TRANSMITTER RHRSW B 279 065 FT-51-2N015A FLOW TRANSMITTER RHR A 370W 067W FT-51-2N015B FLOW TRANSMITTER RHR B 370E 067E FT-51-2N015C FLOW TRANSMITTER RHR C 370W 067W FT-51-2N015D FLOW TRANSMITTER RHR D 370E 067E FT-51-2N052A FLOW TRANSMITTER RHR A 370W 067W FT-51-2N052B FLOW TRANSMITTER RHR B 370E 067E FT-51-2N052C FLOW TRANSMITTER RHR C 370W 067W FT-51-2N052D FLOW TRANSMITTER RHR D 370E 067E FT-55-1N008 FLOW TRANSMITTER HPCI B 111 040 FT-55-1N051 FLOW TRANSMITTER HPCI B 111 040 FT-55-2N008 FLOW TRANSMITTER HPCI B 182 063 FT-55-2N051 FLOW TRANSMITTER HPCI B 182 063 FV-50-113 TURBINE CONTROL RCIC N/A 108 033 1-RCIC VALVE FV-50-213 TURBINE CONTROL RCIC N/A 179 056 2-RCIC VALVE FV-56-111 TURBINE CONTROL HPCI N/A 109 034 1-HPCI VALVE FV-56-112 TURBINE STOP VALVE HPCI B 109 034 1-HPCI FV-56-112 TURBINE STOP VALVE HPCI B 109 034 1-HPCITRIP FV-56-211 TURBINE CONTROL HPCI N/A 180 057 2-HPCI VALVE FV-56-212 TURBINE STOP VALVE HPCI B 180 057 2-HPCI FV-56-212 TURBINE STOP VALVE HPCI B 180 057 2-HPCITRIP FY-11-013A ESW LOOP A SUPPLY ESW A 533 024 FY-11-013B ESW LOOP B SUPPLY ESW B 533 024 FY-11-060B ESW LOOP B SUPPLY ESW B 533 024 APPENDIX 9A 9A-379 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
FY-49-1K001 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-1K013 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-1K014 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-1K015 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-1K601 SIGNAL ISOLATOR - RCIC A 533 024 FLOW FY-49-2K001 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-2K013 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-2K014 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-2K015 SIGNAL ISOLATOR - RCIC A 540 026 FLOW FY-49-2K601 SIGNAL ISOLATOR - RCIC A 533 024 FLOW FY-51-114A SQUARE ROOT RHRSW A 542 025 CONVERTER FY-51-114B SQUARE ROOT RHRSW B 542 025 CONVERTER FY-51-1K600A SQUARE ROOT RHR A 542 025 CONVERTER FY-51-1K600B SQUARE ROOT RHR B 542 025 CONVERTER FY-51-1K600C SQUARE ROOT RHR C 542 025 CONVERTER FY-51-1K600D SQUARE ROOT RHR D 542 025 CONVERTER FY-51-1K011 SQUARE ROOT RHR A 540 026 CONVERTER-RHR LOOP A FLOW FY-51-214A SQUARE ROOT RHRSW A 542 025 CONVERTER FY-51-214B SQUARE ROOT RHRSW B 542 025 CONVERTER FY-51-2K600A SQUARE ROOT RHR A 542 025 CONVERTER FY-51-2K600B SQUARE ROOT RHR B 542 025 CONVERTER APPENDIX 9A 9A-380 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
FY-51-2K600C SQUARE ROOT RHR C 542 025 CONVERTER FY-51-2K600D SQUARE ROOT RHR D 542 025 CONVERTER FY-55-1K601 SQUARE ROOT HPCI B 533 024 CONVERTER FY-55-2K601 SQUARE ROOT HPCI B 533 024 CONVERTER HD-81-041A SYSTEM "A" OUTSIDE SPPV A 1000 122 0-ESW-A AIR INLET DAMPER 0-ESW-R 1-RHRSW-A 2-RHRSW-A HD-81-041B SYSTEM "B" OUTSIDE SPPV B 1005 123 2-RHRSW-B AIR INLET DAMPER 1-RHRSW-B 0-ESW-B HD-81-041C SYSTEM "C" OUTSIDE SPPV C 1000 122 1-RHRSW-A AIR INLET DAMPER 2-RHRSW-A 0-ESW-A HD-81-041D SYSTEM "D" OUTSIDE SPPV D 1005 123 0-ESW-B AIR INLET DAMPER 1-RHRSW-B 2-RHRSW-B HD-81-042A SYSTEM "A" SPPV A 1000 122 0-ESW-A RECIRCULATION AIR 0-ESW-R DAMPER 1-RHRSW-A 2-RHRSW-A HD-81-042B SYSTEM "B" SPPV B 1005 123 0-ESW-B RECIRCULATION AIR 1-RHRSW-B DAMPER 2-RHRSW-B HD-81-042C SYSTEM "C" SPPV C 1000 122 0-ESW-A RECIRCULATION AIR 2-RHRSW-A DAMPER 1-RHRSW-A HD-81-042D SYSTEM "D" SPPV D 1005 123 0-ESW-B RECIRCULATION AIR 1-RHRSW-B DAMPER 2-RHRSW-B HV-11-011A LOOP "A" DISCHARGE ESW A 202 075 0-ESW-A VALVE TO RHRSW 0-ESW-R RETURN HEADERS HV-11-011B LOOP "B" DISCHARGE ESW B 202 075 0-ESW-B VALVE TO RHRSW RETURN HEADERS HV-11-015A LOOP "A" DISCHARGE ESW C 202 075 0-ESW-A VALVE TO RHRSW 0-ESW-R RETURN HEADERS APPENDIX 9A 9A-381 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-015B LOOP "B" DISCHARGE ESW D 202 075 0-ESW-B VALVE TO RHRSW RETURN HEADERS HV-11-041 LOOP "A" EQUIPMENT ESW A 203 032 0-ESW-A HEADER RETURN 0-ESW-R VALVE HV-11-042 HPCI COMPARTMENT HPCI B 109 034 1-HPCI UNIT COOLER RETURN VALVE HV-11-043 SERVICE WATER ESW B 109 034 0-ESW-B INTERTIE VALVE FOR HPCI UNIT COOLER HV-11-044 LOOP "B" EQUIPMENT ESW B 207 041 0-ESW-B HEADER RETURN VALVE HV-11-046 LOOP "A" EQUIPMENT ESW A 281 055 0-ESW-R HEADER RETURN 0-ESW-A VALVE HV-11-047 LOOP "B" EQUIPMENT ESW B 281 055 0-ESW-B HEADER RETURN VALVE HV-11-048 SERVICE WATER ESW A 279 065 0-ESW-A INTERTIE VALVE FOR 0-ESW-R RCIC UNIT COOLER HV-11-049 RCIC COMPARTMENT RCIC A 279 065 2-RCIC UNIT COOLER RETURN 0-ESW-R VALVE HV-11-051A SERVICE WATER ESW 258 001 0-ESW-A INTERTIE VALVE FOR 0-ESW-R CONTROL STRUCTURE CHILLER HV-11-051B SERVICE WATER ESW 263 001 0-ESW-B INTERTIE VALVE FOR CONTROL STRUCTURE CHILLER HV-11-055A SERVICE WATER ESW 258 001 0-ESW-A INTERTIE FOR CONTROL STRUCTURE CHILLER APPENDIX 9A 9A-382 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-055B SERVICE WATER ESW 263 001 0-ESW-B INTERTIE VALVE FOR CONTROL STRUCTURE CHILLER HV-11-071 LOOP "A" EQUIPMENT ESW C 203 032 0-ESW-A HEADER RETURN VALVE HV-11-072 HPCI COMPARTMENT HPCI D 109 034 1-HPCI UNIT COOLER RETURN VALVE HV-11-073 SERVICE WATER ESW D 109 034 0-ESW-B INTERTIE FOR HPCI UNIT COOLER HV-11-074 LOOP "B" EQUIPMENT ESW D 207 041 0-ESW-B HEADER RETURN VALVE HV-11-076 LOOP "A" EQUIPMENT ESW C 284 064 0-ESW-A HEADER RETURN VALVE HV-11-077 LOOP "B" EQUIPMENT ESW D 281 055 0-ESW-B HEADER RETURN VALVE HV-11-078 SERVICE WATER ESW C 279 065 0-ESW-A INTERTIE VALVE FOR RCIC UNIT COOLER HV-11-079 RCIC COMPARTMENT RCIC C 279 065 2-RCIC UNIT COOLER RETURN VALVE HV-11-103A HPCI COMPARTMENT ESW B 109 034 1-HPCI UNIT COOLER INLET VALVE HV-11-103B HPCI COMPARTMENT ESW B 109 034 1-HPCI UNIT COOLER INLET VALVE HV-11-104A RHR COMPARTMENT ESW A 102 032 1-RHRLPCI-A UNIT COOLER "A" 1-RHRSC-A INLET VALVE 1-RHRASC-A 1-RHRSPC-A HV-11-104B RHR COMPARTMENT ESW B 103 031 1-RHRASC-B UNIT COOLER "B" 1-RHRLPCI-B INLET VALVE 1-RHRSC-B 1-RHRSPC-B HV-11-104C RHR COMPARTMENT ESW C 102 032 1-RHRASC-C UNIT COOLER "C" 1-RHRSPC-C INLET VALVE 1-RHRSC-C 1-RHRLPCI-C APPENDIX 9A 9A-383 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-104D RHR COMPARTMENT ESW D 103 031 1-RHRASC-D UNIT COOLER "D" 1-RHRLPCI-D INLET VALVE 1-RHRSC-D 1-RHRSPC-D HV-11-104E RHR COMPARTMENT ESW A 102 032 1-RHRLPCI-A UNIT COOLER "E" 1-RHRSC-A INLET VALVE 1-RHRASC-A 1-RHRSPC-A HV-11-104F RHR COMPARTMENT ESW B 103 031 1-RHRASC-B UNIT COOLER "F" 1-RHRLPCI-B INLET VALVE 1-RHRSC-B 1-RHRSPC-B HV-11-104G RHR COMPARTMENT ESW C 102 032 1-RHRASC-C UNIT COOLER "G" 1-RHRSPC-C INLET VALVE 1-RHRLPCI-C 1-RHRSC-C HV-11-104H RHR COMPARTMENT ESW D 103 031 1-RHRASC-D UNIT COOLER "H" 1-RHRLPCI-D INLET VALVE 1-RHRSC-D 1-RHRSPC-D HV-11-105 ESW TO TECW HX ESW A YARD YARD 0-ESW-A INTERTIE SHUTOFF 0-ESW-R VALVE HV-11-106A RCIC COMPARTMENT ESW A 108 033 1-RCIC UNIT COOLER INLET VALVE HV-11-106B RCIC COMPARTMENT ESW A 108 033 1-RCIC UNIT COOLER INLET VALVE HV-11-107 ESW TO TECW HX ESW C YARD YARD 0-ESW-A INTERTIE SHUTOFF 0-ESW-R VALVE HV-11-121 SERVICE WATER ESW A 203 032 0-ESW-R INTERTIE VALVE FOR 0-ESW-A LOOP "A" EQUIPMENT HV-11-123 SERVICE WATER ESW C 203 032 0-ESW-A INTERTIE VALVE FOR LOOP "A" EQUIPMENT HV-11-124 SHUT OFF VALVE FOR ESW B 207 041 0-ESW-B ESW TO RECW HEAT EXCHANGER INTERTIE LINE APPENDIX 9A 9A-384 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-125 SERVICE WATER ESW B 207 041 0-ESW-B INTERTIE VALVE FOR LOOP "B" EQUIPMENT HV-11-126 SERVICE WATER ESW D 207 041 0-ESW-B INTERTIE VALVE FOR "B" LOOP EQUIPMENT HV-11-128 SHUTOFF VALVE FOR ESW D 207 041 0-ESW-B ESW TO RHRSW HEAT EXCHANGER INTERTIE LINE 11-1131A DIESEL GENERATOR ESW A 311A 079 "A" COOLING LOOP INLET VALVE HV-11-131B DIESEL GENERATOR ESW B 311B 081 0-ESW-A "B" COOLING LOOP 0-ESW-R INLET VALVE 11-1131C DIESEL GENERATOR ESW C 311C 080 "C" COOLING LOOP INLET VALVE HV-11-131D DIESEL GENERATOR ESW D 311D 082 0-ESW-A "D" COOLING LOOP 0-ESW-R INLET VALVE HV-11-132A DIESEL GENERATOR ESW A 311A 079 "A" COOLING LOOP OUTLET VALVE HV-11-132B DIESEL GENERATOR ESW B 311B 081 "B" COOLING LOOP OUTLET VALVE HV-11-132C DIESEL GENERATOR ESW C 311C 080 "C" COOLING LOOP OUTLET VALVE HV-11-132D DIESEL GENERATOR ESW D 311D 082 "D" COOLING LOOP OUTLET VALVE HV-11-133A DIESEL GENERATOR ESW A 311A 079 0-ESW-B "A" COOLING LOOP INLET VALVE 11-1133B DIESEL GENERATOR ESW B 311B 081 "B" COOLING LOOP INLET VALVE HV-11-133C DIESEL GENERATOR ESW C 311C 080 0-ESW-B "C" COOLING LOOP INLET VALVE 11-1133D DIESEL GENERATOR ESW D 311D 082 "D" COOLING LOOP INLET VALVE APPENDIX 9A 9A-385 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-134A DIESEL GENERATOR ESW A 311A 079 "A" COOLING LOOP OUTLET VALVE HV-11-134B DIESEL GENERATOR ESW B 311B 081 "B" COOLING LOOP OUTLET VALVE HV-11-134C DIESEL GENERATOR ESW C 311C 080 "C" COOLING LOOP OUTLET VALVE HV-11-134D DIESEL GENERATOR ESW D 311D 082 "D" COOLING LOOP OUTLET VALVE HV-11-203A HPCI COMPARTMENT ESW B 180 057 2-HPCI UNIT COOLER INLET VALVE HV-11-203B HPCI COMPARTMENT ESW B 180 057 2-HPCI UNIT COOLER INLET VALVE HV-11-204A RHR COMPARTMENT ESW A 173 054 2-RHRASC-A UNIT COOLER "A" 2-RHRLPCI-A INLET VALVE 2-RHRSC-A 2-RHRSPC-A HV-11-204B RHR COMPARTMENT ESW B 174 055 2-RHRSC-B UNIT COOLER "B" 2-RHRSPC-B INLET VALVE 2-RHRASC-B 2-RHRLPCI-B HV-11-204C RHR COMPARTMENT ESW C 173 054 2-RHRASC-C UNIT COOLER "C" 2-RHRLPCI-C INLET VALVE 2-RHRSC-C 2-RHRSPC-C HV-11-204D RHR COMPARTMENT ESW D 174 055 2-RHRLPCI-D UNIT COOLER "D" 2-RHRSC-D INLET VALVE 2-RHRASC-D 2-RHRSPC-D HV-11-204H RHR COMPARTMENT ESW D 174 055 2-RHRASC-D UNIT COOLER"H" 2-RHRLPCI-D INLET VALVE 2-RHRSC-D 2-RHRSPC-D HV-11-205 ESW TO TECW HX ESW B YARD YARD 0-ESW-B INTERTIE SHUTOFF VALVE HV-11-206A RCIC COMPARTMENT ESW A 179 056 2-RCIC UNIT COOLER INLET VALVE APPENDIX 9A 9A-386 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-206B RCIC COMPARTMENT ESW A 179 056 2-RCIC UNIT COOLER INLET VALVE HV-11-207 ESW TO TECW HX ESW D YARD YARD 0-ESW-B INTERTIE SHUTOFF VALVE HV-11-221 SERVICE WATER ESW A 284 064 0-ESW-A INTERTIE VALVE FOR 0-ESW-R LOOP "A" EQUIPMENT HV-11-223 SERVICE WATER ESW C 284 064 0-ESW-A INTERTIE VALVE FOR LOOP "A" EQUIPMENT HV-11-224 SHUTOFF VALVE FOR ESW A 284 064 0-ESW-A ESW TO RECW HEAT 0-ESW-R EXCHANGER INTERTIE LINE HV-11-225 SERVICE WATER ESW B 281 055 0-ESW-B INTERTIE VALVE FOR LOOP "B" EQUIPMENT HV-11-226 SERVICE WATER ESW D 281 055 0-ESW-B INTERTIE VALVE FOR LOOP "B" EQUIPMENT HV-11-228 SHUTOFF VALVE FOR ESW C 284 064 0-ESW-R ESW TO RECW HEAT 0-ESW-A EXCHANGER INTERTIE LINE 11-2231A DIESEL GENERATOR "A" ESW A 315A 083 COOLING LOOP INLET VALVE HV-11-231B DIESEL GENERATOR "B" ESW B 315B 085 0-ESW-R COOLING LOOP INLET 0-ESW-A VALVE 11-2231C DIESEL GENERATOR "C" ESW C 315C 084 COOLING LOOP INLET VALVE HV-11-231D DIESEL GENERATOR "D" ESW D 315D 086 0-ESW-A COOLING LOOP INLET 0-ESW-R VALVE HV-11-232A DIESEL GENERATOR "A" ESW A 315A 083 COOLING LOOP OUTLET VALVE APPENDIX 9A 9A-387 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-11-232B DIESEL GENERATOR "B" ESW B 315B 085 COOLING LOOP OUTLET VALVE HV-11-232C DIESEL GENERATOR "C" ESW C 315C 084 COOLING LOOP OUTLET VALVE HV-11-232D DIESEL GENERATOR "D" ESW D 315D 086 COOLING LOOP OUTLET VALVE HV-11-233A DIESEL GENERATOR "A" ESW A 315A 083 0-ESW-B COOLING LOOP INLET VALVE 11-2233B DIESEL GENERATOR "B" ESW B 315B 085 COOLING LOOP INLET VALVE HV-11-233C DIESEL GENERATOR "C" ESW C 315C 084 0-ESW-B COOLING LOOP INLET VALVE 11-2233D DIESEL GENERATOR "D" ESW D 315D 086 COOLING LOOP INLET VALVE HV-11-234A DIESEL GENERATOR "A" ESW A 315A 083 COOLING LOOP OUTLET VALVE HV-11-234B DIESEL GENERATOR "B" ESW B 315B 085 COOLING LOOP OUTLET VALVE HV-11-234C DIESEL GENERATOR "C" ESW C 315C 084 COOLING LOOP OUTLET VALVE HV-11-234D DIESEL GENERATOR "D" ESW D 315D 086 COOLINGLOOP OUTLET VALVE HV-12-003A WET PIT SLUICE GATE RHRSW A 1000 122 0-ESW-A 0-ESW-R 1-RHRSW-A 2-RHRSW-A HV-12-003B WET PIT SLUICE GATE RHRSW B 1005 123 1-RHRSW-B 2-RHRSW-B 0-ESW-B APPENDIX 9A 9A-388 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-12-003C WET PIT SLUICE GATE RHRSW C 1000 122 0-ESW-A 0-ESW-R 1-RHRSW-A 2-RHRSW-A HV-12-003D WET PIT SLUICE GATE RHRSW D 1005 123 0-ESW-B 1-RHRSW-B 2-RHRSW-B HV-12-017A LOOP "A" TO UNIT 2 RHRSW A YARD YARD 0-ESW-A COOLING TOWER 2-RHRSW-B CROSS-TIE VALVE 1-RHRSW-B 2-RHRSW-A 1-RHRSW-A 0-ESW-B 0-ESW-R HV-12-017B LOOP "B" TO UNIT 1 RHRSW B YARD YARD 0-ESW-A COOLING TOWER 2-RHRSW-B CROSS-TIE VALVE 1-RHRSW-B 2-RHRSW-A 0-ESW-B 1-RHRSW-A HV-12-031A SPRAY NETWORK BYPASS RHRSW A 1010 122 0-ESW-A VALVE 0-ESW-R 1-RHRSW-A 2-RHRSW-A HV-12-031B SPRAY NETWORK BYPASS RHRSW B 1015 123 0-ESW-B VALVE 1-RHRSW-B 2-RHRSW-B HV-12-031C SPRAY NETWORK BYPASS RHRSW C 1010 122 2-RHRSW-A VALVE 0-ESW-A 0-ESW-R 1-RHRSW-A HV-12-031D SPRAY NETWORKBYPASS RHRSW D 1015 123 2-RHRSW-B VALVE 1-RHRSW-B 0-ESW-B HV-12-032A SPRAY NETWORK INLET RHRSW A 1010 122 0-ESW-A VALVE 0-ESW-R 1-RHRSW-A 2-RHRSW-A HV-12-032B SPRAY NETWORK INLET RHRSW B 1015 123 0-ESW-B VALVE 1-RHRSW-B 2-RHRSW-B APPENDIX 9A 9A-389 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-12-032C SPRAY NETWORK INLET RHRSW C 1010 122 0-ESW-A VALVE 0-ESW-R 1-RHRSW-A 2-RHRSW-A HV-12-032D SPRAY NETWORK INLET RHRSW D 1015 123 1-RHRSW-B VALVE 2-RHRSW-B 0-ESW-B HV-12-034A RHR SERVICE WATER ESW A 1010 122 2-RHRSW-B SPRAY NOZZLE CROSS 0-ESW-B TIE VALVE 0-ESW-R 1-RHRSW-A 2-RHRSW-A 1-RHRSW-B 0-ESW-A HV-12-034B RHR SERVICE WATER ESW B 1015 123 1-RHRSW-B SPRAY NOZZLE CROSS 2-RHRSW-A TIE VALVE 1-RHRSW-A 0-ESW-A 2-RHRSW-B 0-ESW-B HV-12-111 RHRSW TO COOLING RHRSW A YARD YARD 2-RHRSW-A TOWER INTERTIE 1-RHRSW-A SHUTOFF VALVE 0-ESW-R 0-ESW-A HV-12-113 RHRSW TO COOLING RHRSW C YARD YARD 0-ESW-A TOWER INTERTIE 0-ESW-R SHUTOFF VALVE 1-RHRSW-A 2-RHRSW-A HV-12-211 RHRSW TO COOLING RHRSW B YARD YARD 0-ESW-B TOWER INTERTIE 1-RHRSW-B SHUTOFF VALVE 2-RHRSW-B HV-12-213 RHRSW TO COOLING RHRSW D YARD YARD 0-ESW-B TOWER INTERTIE 1-RHRSW-B SHUTOFF VALVE 2-RHRSW-B HV-41-109A REACTOR FEEDWATER HI/LOW A 518 046 1-HI/LOW BYPASS VALVE 1-HPCI APPENDIX 9A 9A-390 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-41-109B REACTOR HI/LOW B 518 046 1-HI/LOW FEEDWATER BYPASS VALVE 1-RCIC HV-41-110 RX FW STARTUP HI/LOW C 407 046 1-HI/LOW FLUSHING SHUTOFF HV-41-140 BYPASS LEAKAGE HI/LOW C 407 046 1-HI/LOW BARRIER VENT MAIN STEAM LINE BLEED DRAIN HV-41-141 BYPASS LEAKAGE HI/LOW D 407 046 1-HI/LOW BARRIER VENT MAIN STEAM LINE BLEED DRAIN HV-41-1F001 NUCLEAR BOILER SYS HI/LOW 0 400 030 1-HI/LOW HEAD VENT VALVE HV-41-1F002 NUCLEAR BOILER SYS HI/LOW 0 400 030 1-HI/LOW HEAD VENT VALVE HV-41-1F011A FEEDWATER LINE "A" HPCI A 400 030 1-HPCI INBD MAINT ISO VALVE HV-41-1F011B FEEDWATER LINE "B" RCIC C 400 030 1-RCIC INBD MAINT ISO VALVE HV-41-1F016 MAIN STEAM LINE HI/LOW A 400 030 1-HI/LOW DRAIN INBD PCIV HV-41-1F019 MAIN STEAM LINE HI/LOW B 407 046 1-HI/LOW DRAIN OUTBD PCIV HV-41-1F021 NUCLEAR BOILER HI/LOW B 407 046 1-HI/LOW SYSTEM MSL DRAIN TO COND.
HV-41-1F022A A MAIN STEAM ISO HI/LOW A,W 400 030 1-HI/LOW VALVE INBD PCIV HV-41-1F022B BMAIN STEAM ISO HI/LOW A,W 400 030 1-HI/LOW VALVE INBD PCIV HV-41-1F022C C MAIN STEAM ISO HI/LOW A,W 400 030 1-HI/LOW VALVE INBD PCIV HV-41-1F022D D MAIN STEAM ISO HI/LOW A,W 400 030 1-HI/LOW VALVE INBD PCIV APPENDIX 9A 9A-391 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-41-1F028A A MAIN STEAM ISO HI/LOW B,X 407 046 1-HI/LOW VALVE OUTBD PCIV HV-41-1F028B B MAIN STEAM ISO HI/LOW B,X 407 046 1-HI/LOW VALVE OUTBD PCIV HV-41-1F028C C MAIN STEAM ISO HI/LOW B,X 407 046 1-HI/LOW VALVE OUTBD PCIV HV-41-1F028D D MAIN STEAM ISO HI/LOW B,X 407 046 1-HI/LOW VALVE OUTBD PCIV HV-41-1F084 MAIN STEAM LINE C HI/LOW A 400 030 1-HI/LOW INBD SAMPLE PCIV HV-41-1F085 MAIN STEAM LINE C HI/LOW B 510 047W 1-HI/LOW OUTBD SAMPLE PCIV HV-41-209A REACTOR FEEDWATER HI/LOW A 587 069 2-HI/LOW BYPASS VALV 2-HPCI HV-41-209B REACTOR FEEDWATER HI/LOW B 587 069 2-HI/LOW BYPASS VALVE 2-RCIC HV-41-210 RX FW STARTUP HI/LOW C 480 069 2-HI/LOW FLUSHING SHUTOFF HV-41-240 BYPASS LEAKAGE HI/LOW C 480 069 2-HI/LOW BARRIER VENT MAIN STEAM LINE BLEED DRAIN HV-41-241 BYPASS LEAKAGE HI/LOW D 480 069 2-HI/LOW BARRIER VENT MAIN STEAM LINE BLEED DRAIN HV-41-2F001 NUCLEAR BOILER SYS HI/LOW 0 473 053 2-HI/LOW HEAD VENT VALVE HV-41-2F002 NUCLEAR BOILER SYS HI/LOW 0 473 053 2-HI/LOW HEAD VENT VALVE HV-41-2F011A FEEDWATER LINE "A" HPCI A 473 053 2-HPCI INBD MAINT ISO VALVE HV-41-2F011B FEEDWATER LINE "B" RCIC C 473 053 2-RCIC INBD MAINT ISO VALVE HV-41-2F016 MAIN STEAM LINE HI/LOW A 473 053 2-HI/LOW DRAIN INBD PCIV HV-41-2F019 MAIN STEAM LINE HI/LOW B 480 069 2-HI/LOW DRAIN OUTBD PCIV APPENDIX 9A 9A-392 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-41-2F021 NUCLEAR BOILER HI/LOW B 480 069 2-HI/LOW SYSTEM MSL DRAIN TO COND.
HV-41-2F022A A MAIN STEAM ISO HI/LOW A,W 473 053 2-HI/LOW VALVE INBD PCIV HV-41-2F022B B MAIN STEAM ISO HI/LOW A,W 473 053 2-HI/LOW VALVE INBD PCIV HV-41-2F022C C MAIN STEAM ISO HI/LOW A,W 473 053 2-HI/LOW VALVE INBD PCIV HV-41-2F022D D MAIN STEAM ISO HI/LOW A,W 473 053 2-HI/LOW VALVE INBD PCIV HV-41-2F028A A MAIN STEAM ISO HI/LOW B,X 480 069 2-HI/LOW VALVE OUTBD PCIV HV-41-2F028B B MAIN STEAM ISO HI/LOW B,X 480 069 2-HI/LOW VALVE OUTBD PCIV HV-41-2F028C C MAIN STEAM ISO HI/LOW B,X 480 069 2-HI/LOW VALVE OUTBD PCIV HV-41-2F028D D MAIN STEAM ISO HI/LOW B,X 480 069 2-HI/LOW VALVE OUTBD PCIV HV-41-2F084 MAIN STEAM LINE C HI/LOW A 473 053 2-HI/LOW INBD SAMPLE PCIV HV-41-2F085 MAIN STEAM LINE C HI/LOW B 584 070E 2-HI/LOW OUTBD SAMPLE PCIV HV-43-1F019 RECIRC LOOP SAMPLE HI/LOW A 400 030 1-HI/LOW INBD PCIV HV-43-1F020 RECIRC LOOP SAMPLE HI/LOW B 501 047E 1-HI/LOW OUTBD PCIV HV-43-2F019 RECIRC LOOP SAMPLE HI/LOW A 473 053 2-HI/LOW INBD PCIV HV-43-2F020 RECIRC LOOP SAMPLE HI/LOW B 575 070W 2-HI/LOW OUTBD PCIV HV-44-1F031 RWCU RESTRICTED HI/LOW 0 510 047W 1-HI/LOW ORFICE BYPASS VALVE HV-44-1F034 RWCU DISCHARGE TO HI/LOW 0 510 047W 1-HI/LOW MAIN CONDENSER HV-44-1F035 RWCU DISCHARGE TO HI/LOW 0 510 047W 1-HI/LOW EQUIP DRAIN COLLECTION TANK HV-44-2F031 RWCU RESTRICTED HI/LOW 0 584 070E 2-HI/LOW ORFICEBYPASS VALVE APPENDIX 9A 9A-393 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-44-2F034 RWCU DISCHARGE TO HI/LOW 0 584 070E 2-HI/LOW MAIN CONDENSER HV-44-2F035 RWCU DISCHARGE TO HI/LOW 0 584 070E 2-HI/LOW EQUIP DRAIN COLLECTION TANK HV-49-1F007 STEAM SUPPLY LINE RCIC C 400 030 1-RCIC INBD CTMT ISO VALVE 1-RCICTRIP HV-49-1F008 STEAM SUPPLY LINE RCIC A 309E 043E 1-RCIC OUTBDCTMT ISO VALVE 1-RCICTRIP HV-49-1F010 PUMP SUCTION VALVE RCIC A 108 033 1-RCIC FROM CONDENSATE STORAGE TANK HV-49-1F012 RCIC PUMP DISCHARGE RCIC A 200 042 1-RCIC VALVE HV-49-1F013 INJECTION VALVE TO RCIC A 518 046 1-RCIC FEEDWATER LINE HV-49-1F019 MINIMUM FLOW BYPASS RCIC A 108 033 1-RCIC LINE CTMT ISO VALVE HV-49-1F022 SHUTOFF VALVE IN RCIC A 200 042 1-RCIC DISCHARGE LINE TO CONDENSATE STORAGE TANK HV-49-1F029 PUMP SUCTION VALVE RCIC A 108 033 1-RCIC FROM SUPPRESSION CHAMBER HV-49-1F031 PUMP SUCTION VALVE RCIC A 108 033 1-RCIC FROM SUPPRESSION CHAMBER CTMT ISO VALVE HV-49-1F060 TURBINE EXHAUST RCIC A 289 033 1-RCIC LINE CTMT ISO VALVE HV-49-1F080 TURBINE EXHAUST RCIC A 203 032 1-RCIC LINE VACUUM BREAKER VALVE HV-49-1F084 TURBINE EXHAUST RCIC C 203 032 1-RCIC LINE VACUUM BREAKER VALVE HV-49-2F007 STEAM SUPPLY LINE RCIC C 473 053 2-RCIC INBD CTMT ISO VALVE 2-RCICTRIP HV-49-2F008 STEAM SUPPLY LINE RCIC A 376E 066E 2-RCIC OUTBD CTMT ISO VALVE 2-RCICTRIP HV-49-2F010 PUMP SUCTION VALVE RCIC A 179 056 2-RCIC FROM CONDENSATE STORAGE TANK APPENDIX 9A 9A-394 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-49-2F012 RCIC PUMP DISCHARGE RCIC A 279 065 2-RCIC VALVE HV-49-2F013 INJECTION VALVE TO RCIC A 587 069 2-RCIC FEEDWATER LINE HV-49-2F019 MINIMUM FLOW BYPASS RCIC A 281 055 2-RCIC LINE CTMT ISO VALVE HV-49-2F022 SHUTOFF VALVE IN RCIC A 279 065 2-RCIC DISCHARGE LINE TO CONDENSATE STORAGE TANK HV-49-2F029 PUMP SUCTION VALVE RCIC A 179 056 2-RCIC FROM SUPPRESSION CHAMBER HV-49-2F031 PUMP SUCTION VALVE RCIC A 179 056 2-RCIC FROM SUPPRESSION CHAMBER CTMT ISO VALVE HV-49-2F060 TURBINE EXHAUST LINE RCIC A 285 056 2-RCIC CTMT ISO VALVE HV-49-2F080 TURBINE EXHAUST LINE RCIC A 281 055 2-RCIC VACUUM BREAKER VALVE HV-49-2F084 TURBINE EXHAUST LINE RCIC C 281 055 2-RCIC VACUUM BREAKER VALVE HV-50-112 TURBINE STOP VALVE RCIC A 108 033 1-RCIC 1-RCICTRIP HV-50-1F045 STEAM SUPPLY LINE RCIC A 108 033 1-RCIC INLET VALVE TO 1-RCICTRIP TURBINE HV-50-1F046 COOLING WATER LINE RCIC A 108 033 1-RCIC SHUTOFF VALVE HV-50-212 TURBINE STOP VALVE RCIC A 179 056 2-RCIC 2-RCICTRIP HV-50-2F045 STEAM SUPPLY LINE RCIC A 179 056 2-RCIC INLET VALVE TO 2-RCICTRIP TURBINE HV-50-2F046 COOLING WATER LINE RCIC A 179 056 2-RCIC SHUTOFF VALVE HV-51-105A MINIMUM FLOW BYPASS RHR C 203 032 1-RHRASC-C LINE CTMT ISO VALVE 1-RHRLPCI-C 1-RHRSC-C 1-RHRSPC-C APPENDIX 9A 9A-395 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-105B MINIMUM FLOW BYPASS RHR D 204 031 1-RHRLPCI-D LINE CTMT ISOVALVE 1-RHRSC-D 1-RHRASC-D 1-RHRSPC-D HV-51-125A SUPPRESSION POOL RHR A 304W 044W 1-RHRASC-A COOLING LINE CTMT 1-RHRLPCI-A ISO VALVE 1-RHRSPC-A 1-RHRSPC-C HV-51-125B SUPPRESSION POOL RHR B 304E 044E 1-RHRSC-B COOLING LINE CTMT 1-RHRSPC-B ISO VALVE 1-RHRASC-B 1-RHRLPCI-B 1-RHRSPC-D HV-51-142A 1A LPCI INJECTION HI/LOW A 400 030 1-HI/LOW HEADER INBD PCIV HV-51-142B 1B LPCI INJECTION HI/LOW B 400 030 1-HI/LOW HEADER INBD PCIV HV-51-142C 1C LPCI INJECTION HI/LOW C 400 030 1-HI/LOW HEADER INBD PCIV HV-51-142D 1D LPCI INJECTION HI/LOW D 400 030 1-HI/LOW HEADER INBD PCIV HV-51-151A 1A RHR SHUTDOWN HI/LOW A 400 030 1-HI/LOW COOLING INJ HDR INLET PCIV HV-51-151B 1B RHR SHUTDOWN HI/LOW B 400 030 1-HI/LOW COOLING INJ HDR INLET PCIV HV-51-182A RHR LOOP A/LOOP C RHR A 309W 043W 1-RHRASC-A INTERTIE ISO VALVE 1-RHRSPC-A 1-RHRSC-C 1-RHRSC-A 1-RHRLPCI-C 1-RHRASC-C 1-RHRSPC-C 1-RHRLPCI-A HV-51-182B RHR LOOP B/LOOP D RHR B 309E 043E 1-RHRSC-B INTERTIE ISO VALVE 1-RHRSPC-D 1-RHRSPC-B 1-RHRSC-D 1-RHRLPCI-D 1-RHRLPCI-B 1-RHRASC-B 1-RHRASC-D APPENDIX 9A 9A-396 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-1F003A HEAT EXCHANGER RHR A 203 032 1-RHRASC-A SHELL SIDE 1-RHRASC-C DISCHARGE VALVE 1-RHRSC-A 1-RHRSC-C 1-RHRSPC-A 1-RHRSPC-C HV-51-1F003B HEAT EXCHANGER RHR B 204 031 1-RHRASC-B SHELL SIDE 1-RHRSPC-D DISCHARGE VALVE 1-RHRSPC-B 1-RHRASC-D 1-RHRSC-D 1-RHRSC-B HV-51-1F004A PUMP SUCTION VALVE RHR A 102 032 1-RHRASC-A FROM SUPPRESSION 1-RHRLPCI-A CHAMBER 1-RHRSC-A 1-RHRSPC-A HV-51-1F004B PUMP SUCTION VALVE RHR B 103 031 1-RHRASC-B FROM SUPPRESSION 1-RHRSPC-B CHAMBER 1-RHRLPCI-B 1-RHRSC-B HV-51-1F004C PUMP SUCTION VALVE RHR C 102 032 1-RHRSPC-C FROM SUPPRESSION 1-RHRASC-C CHAMBER 1-RHRLPCI-C 1-RHRSC-C HV-51-1F004D PUMP SUCTION VALVE RHR D 103 031 1-RHRSPC-D FROM SUPPRESSION 1-RHRSC-D CHAMBER 1-RHRASC-D 1-RHRLPCI-D HV-51-1F006A PUMP SUCTION VALVE RHR A 102 032 1-RHRASC-A FROM SHUTDOWN 1-RHRLPCI-A COOLING HEADER 1-RHRSC-A 1-RHRSC-B 1-RHRSC-C 1-RHRSC-D 1-RHRSPC-A HV-51-1F006B PUMP SUCTION VALVE RHR B 103 031 1-RHRSC-B FROM SHUTDOWN 1-RHRASC-B COOLING HEADER 1-RHRLPCI-B 1-RHRSC-C 1-RHRSC-D 1-RHRSPC-B 1-RHRSC-A HV-51-1F007A PUMP DISCHARGE RHR A 102 032 1-RHRASC-A MINIMUM FLOW BYPASS 1-RHRLPCI-A VALVE 1-RHRSC-A 1-RHRSPC-A APPENDIX 9A 9A-397 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-1F007B PUMP DISCHARGE RHR B 103 031 1-RHRASC-B MINIMUM FLOW BYPASS 1-RHRSPC-B VALVE 1-RHRLPCI-B 1-RHRSC-B HV-51-1F007C PUMP DISCHARGE RHR C 102 032 1-RHRASC-C MINIMUM FLOW BYPASS 1-RHRLPCI-C VALVE 1-RHRSC-C 1-RHRSPC-C HV-51-1F007D PUMP DISCHARGE RHR D 103 031 1-RHRSC-D MINIMUM FLOW BYPASS 1-RHRSPC-D VALVE 1-RHRASC-D 1-RHRLPCI-D HV-51-1F008 SHUTDOWN COOLING RHR/ B 309E 043E 1-HI/LOW SUCTION LINE OUTBD HILOW 309W 043W 1-RHRSC-A CTMT ISO VALVE 1-RHRSC-B 1-RHRSC-C 1-RHRSC-D HV-51-1F009 SHUTDOWN COOLING RHR/ A 400 030 1-HI/LOW SUCTION LINE INBD HILOW 1-RHRSC-A CTMT ISO VALVE 1-RHRSC-B 1-RHRSC-C 1-RHRSC-D HV-51-1F010A PUMP DISCHARGE FULL RHR C 304W 044W 1-RHRSPC-A FLOW BYPASS VALVE 1-RHRSC-C 1-RHRLPCI-C 1-RHRASC-C 1-RHRSPC-C HV-51-1F010B PUMP DISCHARGE FULL RHR D 304E 044E 1-RHRSPC-D FLOW BYPASS VALVE 1-RHRASC-D 1-RHRLPCI-D 1-RHRSC-D 1-RHRSPC-B HV-51-1F011A HEAT EXCHANGER RHR N/A 203 032 1-RHRSPC-C DISCH LINE TO SUPPRESSION CHAMBER 1-RHRSPC-A SHUTOFF VALVE 1-RHRSC-C 1-RHRLPCI-A 1-RHRSC-A HV-51-1F011B HEAT EXCHANGER RHR N/A 204 031 1-RHRSC-D DISCH LINE TO SUPPRESSION CHAMBER 1-RHRSPC-D SHUTOFF VALVE 1-RHRLPCI-B 1-RHRASC-D 1-RHRASC-B 1-RHRSPC-B APPENDIX 9A 9A-398 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-1F014A RHR HEAT EXCHANGER RHRSW A 203 032 1-RHRSW-A TUBE SIDE INLET VALVE HV-51-1F014B RHR HEAT EXCHANGER RHRSW B 204 031 1-RHRSW-B TUBE SIDE INLET VALVE HV-51-1F015A SHUTDOWN COOLING RHR B 309W 043W 1-RHRASC-C RETURN LINE OUTBD 1-RHRSPC-C CTMT ISO VALVE 1-RHRSPC-A 1-RHRSC-C 1-RHRLPCI-A 1-RHRASC-A 1-HI/LOW 1-RHRSC-A HV-51-1F015B SHUTDOWN COOLING RHR B 309E 043E 1-RHRASC-B RETURN LINE OUTBD 309W 043W 1-RHRSC-D CTMT ISO VALVE 1-RHRSPC-D 1-RHRSPC-B 1-HI/LOW 1-RHRASC-D 1-RHRLPCI-B 1-RHRSC-B HV-51-1F016A DRYWELL SPRAY LINE RHR A 501 047E 1-RHRASC-A OUTBD CTMT ISO VALVE 1-RHRASC-C 1-RHRLPCI-A 1-RHRSC-A 1-RHRSC-C 1-RHRSPC-A 1-RHRSPC-C HV-51-1F016B DRYWELL SPRAY LINE RHR B 523 047W 1-RHRSC-B OUTBD CTMT ISO VALVE 1-RHRSPC-D 1-RHRSC-D 1-RHRLPCI-B 1-RHRASC-D 1-RHRASC-B 1-RHRSPC-B HV-51-1F017A LPCI INJECTION LINE RHR A 510 047W 1-RHRLPCI-A OUTBD CTMT ISO VALVE 1-RHRSPC-C 1-RHRSPC-A 1-RHRSC-A 1-RHRASC-C 1-RHRASC-A 1-HI/LOW 1-RHRSC-C APPENDIX 9A 9A-399 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-1F017B LPCI INJECTION LINE RHR B 599 047E 1-RHRLPCI-B OUTBD CTMT ISO VALVE 1-RHRSPC-B 1-RHRSPC-D 1-RHRSC-B 1-RHRASC-B 1-HI/LOW 1-RHRSC-D 1-RHRASC-D HV-51-1F017C LPCIINJECTION LINE RHR C 510 047W 1-RHRSPC-C OUTBD CTMT ISO VALVE 1-HI/LOW 1-RHRASC-C 1-RHRLPCI-C 1-RHRSC-C HV-51-1F017D LPCI INJECTION LINE RHR D 599 047E 1-RHRSPC-D OUTBD CTMT ISO VALVE 1-RHRSC-D 1-RHRLPCI-D 1-HI/LOW 1-RHRASC-D HV-51-1F021A DRYWELL SPRAY LINE RHR A 400 030 1-RHRASC-A INBD CTMT ISO VALVE 1-RHRASC-C 1-RHRLPCI-A 1-RHRSC-A 1-RHRSC-C 1-RHRSPC-A 1RHRSPC-C HV-51-1F021B DRYWELL SPRAY LINE RHR B 400 030 1-RHRASC-B INBD CTMT ISO VALVE 1-RHRASC-D 1-RHRLPCI-B 1-RHRSC-B 1-RHRSC-D 1-RHRSPC-B 1-RHRSPC-D HV-51-1F024A SUPPRESSION POOL RHR A 304W 044W 1-RHRSC-C COOLING LINE 1-RHRASC-A SHUTOFF VALVE 1-RHRSPC-A 1-RHRSPC-C 1-RHRSC-A 1-RHRASC-C 1-RHRLPCI-A HV-51-1F024B SUPPRESSION POOL RHR B 304E 044E 1-RHRASC-B COOLING LINE 1-RHRASC-D SHUTOFF VALVE 1-RHRLPCI-B 1-RHRSC-B 1-RHRSC-D 1-RHRSPC-B 1-RHRSPC-D APPENDIX 9A 9A-400 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-1F026A HEAT EXCHANGER RHR N/A 102 032 1-RHRSC-C DISCHARGE LINE TO 1-RHRSPC-A RCIC SHUTOFF VALVE 1-RHRSC-A 1-RHRLPCI-A 1-RHRSPC-C HV-51-1F026B HEAT EXCHANGER RHR N/A 103 031 1-RHRSPC-B DISCHARGE LINE TO 1-RHRSPC-D RCIC SHUTOFF VALVE 1-RHRSC-D 1-RHRLPCI-B 1-RHRASC-D 1-RHRASC-B HV-51-1F027A SUPPRESSION POOL RHR A 304W 044W 1-RHRASC-C SPRAY LINE CTMT 1-RHRLPCI-A ISO VALVE 1-RHRSC-A 1-RHRSC-C 1-RHRASC-A HV-51-1F027B SUPPRESSION POOL RHR B 304E 044E 1-RHRLPCI-B SPRAY LINE CTMT 1-RHRSC-B ISO VALVE 1-RHRASC-D 1-RHRASC-B 1-RHRSC-D HV-51-1F040 HEAT EXCHANGER RHR A 203 032 1-RHRSPC-A DISCHARGE LINE TO RADWASTE SHUTOFF 1-RHRSPC-C VALVE 1-RHRSC-C 1-RHRSC-A 1-RHRLPCI-A 1-RHRASC-C 1-RHRASC-A HV-51-1F047A HEAT EXCHANGER RHR A 309W 043W 1-RHRSPC-C INLET VALVE FROM 1-RHRASC-C PUMP DISCHARGE 1-RHRSC-A 1-RHRSC-C 1-RHRSPC-A 1-RHRASC-A HV-51-1F047B HEAT EXCHANGER RHR B 309E 043E 1-RHRSPC-D INLET VALVE FROM 1-RHRSPC-B PUMP DISCHARGE 1-RHRSC-D 1-RHRASC-B 1-RHRSC-B 1-RHRASC-D HV-51-1F049 HEAT EXCHANGER RHR B 203 032 1-RHRSC-C DISCHARGE LINE TO 1-RHRSPC-A RADWASTE SHUTOFF 1-RHRSC-A VALVE 1-RHRLPCI-A 1-RHRASC-C 1-RHRASC-A 1-RHRSPC-C APPENDIX 9A 9A-401 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-1F068A RHR HEAT EXCHANGER RHRSW C 203 032 1-RHRSW-A TUBE SIDE OUTLET VALVE HV-51-1F068B RHR HEAT EXCHANGER RHRSW D 204 031 1-RHRSW-B TUBE SIDE OUTLET VALVE HV-51-1F073 RHRSW TO RHR RHR B 204 031 1-RHRSW-B INTERTIE LINE SHUTOFF VALVE HV-51-1F068A RHR HEAT EXCHANGER RHRSW C 203 032 1-RHRSW-A HV-51-1F074 RHR SW CROSSTIE RHR B 103 031 1-RHRSW-B DRAIN VALVE HV-51-1F075 RHRSW TO RHR RHR B 204 031 1-RHRSW-B INTERTIE SHUTOFF VALVE APPENDIX 9A 9A-402 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-205A MINIMUM FLOW BYPASS RHR C 280 054 2-RHRSPC-C LINE CTMT ISO VALVE HV-51-205A MINIMUM FLOW BYPASS RHR C 280 054 2-RHRSC-C 2-RHRASC-C 2-RHRLPCI-C HV-51-205B MINIMUM FLOW BYPASS RHR D 281 055 2-RHRASC-D LINE CTMT ISO VALVE 2-RHRLPCI-D 2-RHRSC-D 2-RHRSPC-D HV-51-225A SUPPRESSION POOL RHR A 370W 067W 2-RHRASC-A COOLING LINE CTMT 2-RHRLPCI-A ISO VALVE 2-RHRSPC-A HV-51-225A SUPPRESSION POOL RHR A 370W 067W 2-RHRSPC-C HV-51-225B SUPPRESSION POOL RHR B 370E 067E 2-RHRASC-B COOLING LINE CTMT 2-RHRSPC-D ISO VALVE 2-RHRSPC-B 2-RHRLPCI-B 2-RHRSC-B HV-51-242A 2A LPCI INJECTION HI/LOW A 473 053 2-HI/LOW HEADER INBD PCIV HV-51-242B 2B LPCI INJECTION HI/LOW B 473 053 2-HI/LOW HEADER INBD PCIV HV-51-242C 2C LPCI INJECTION HI/LOW C 473 053 2-HI/LOW HEADER INBD PCIV HV-51-242D 2D LPCI INJECTION HI/LOW D 473 053 2-HI/LOW HEADER INBD PCIV HV-51-251A 2A RHR SHUTDOWN HI/LOW A 473 053 2-HI/LOW COOLING INJ HDR INLET PCIV HV-51-251B 2B RHR SHUTDOWN HI/LOW B 473 053 2-HI/LOW COOLING INJ HDR INLET PCIV HV-51-282A RHR LOOP A/LOOP C RHR A 376W 066W 2-RHRASC-C INTERTIE ISO VALVE 2-RHRSPC-A 2-RHRSC-C 2-RHRSC-A 2-RHRLPCI-A 2-RHRSPC-C 2-RHRASC-A 2-RHRLPCI-C APPENDIX 9A 9A-403 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-282B RHR LOOP B/LOOP D RHR B 376E 066E 2-RHRSC-B INTERTIE ISO VALVE 2-RHRSPC-D 2-RHRSPC-B 2-RHRSC-D 2-RHRLPCI-D 2-RHRLPCI-B 2-RHRASC-B 2-RHRASC-D HV-51-2F003A HEAT EXCHANGER RHR A 280 054 2-RHRASC-A SHELL SIDE 2-RHRASC-C DISCHARGE VALVE 2-RHRSC-A 2-RHRSC-C 2-RHRSPC-A 2-RHRSPC-C HV-51-2F003B HEAT EXCHANGER RHR B 281 055 2-RHRASC-B SHELL SIDE 2-RHRSPC-D DISCHARGE VALVE 2-RHRSPC-B 2-RHRASC-D 2-RHRSC-B 2-RHRSC-D HV-51-2F004A PUMP SUCTION VALVE RHR A 173 054 2-RHRASC-A FROM SUPPRESSION 2-RHRLPCI-A CHAMBER 2-RHRSC-A 2-RHRSPC-A HV-51-2F004B PUMP SUCTION VALVE RHR B 174 055 2-RHRASC-B FROM SUPPRESSION 2-RHRLPCI-B CHAMBER 2-RHRSC-B 2-RHRSPC-B HV-51-2F004C PUMP SUCTION VALVE RHR C 173 054 2-RHRSC-C FROM SUPPRESSION 2-RHRSPC-C CHAMBER 2-RHRASC-C 2-RHRLPCI-C HV-51-2F004D PUMP SUCTION VALVE RHR D 174 055 2-RHRLPCI-D FROM SUPPRESSION 2-RHRSC-D CHAMBER 2-RHRSPC-D 2-RHRASC-D HV-51-2F006A PUMP SUCTION VALVE RHR A 173 054 2-RHRLPCI-A FROM SHUTDOWN 2-RHRSPC-A COOLING HEADER 2-RHRSC-D 2-RHRSC-C 2-RHRSC-A 2-RHRASC-A 2-RHRSC-B APPENDIX 9A 9A-404 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-2F006B PUMP SUCTION VALVE RHR B 174 055 2-RHRSC-A FROM SHUTDOWN 2-RHRSC-D COOLING HEADER 2-RHRSPC-B 2-RHRASC-B 2-RHRSC-C 2-RHRLPCI-B 2-RHRSC-B HV-51-2F007A PUMP DISCHARGE RHR A 173 054 2-RHRASC-A MINIMUM FLOW 2-RHRLPCI-A BYPASS VALVE 2-RHRSC-A 2-RHRSPC-A HV-51-2F007B PUMP DISCHARGE RHR B 174 055 2-RHRASC-B MINIMUM FLOW 2-RHRSPC-B BYPASS VALVE 2-RHRLPCI-B 2-RHRSC-B HV-51-2F007C PUMP DISCHARGE RHR C 173 054 2-RHRASC-C MINIMUM FLOW 2-RHRLPCI-C BYPASS VALVE 2-RHRSC-C 2-RHRSPC-C HV-51-2F007D PUMP DISCHARGE RHR D 174 055 2-RHRSC-D MINIMUM FLOW 2-RHRSPC-D BYPASS VALVE 2-RHRASC-D 2-RHRLPCI-D HV-51-2F008 SHUTDOWN COOLING RHR/ B 376E 066E 2-HI/LOW SUCTION LINE OUTBD HILOW 376W 066W 2-RHRSC-A CTMT ISO VALVE 2-RHRSC-B 2-RHRSC-C 2-RHRSC-D HV-51-2F009 SHUTDOWN COOLING RHR/ A 473 053 2-HI/LOW SUCTION LINE INBD HILOW 2-RHRSC-A CTMT ISO VALVE 2-RHRSC-B 2-RHRSC-C 2-RHRSC-D HV-51-2F010A PUMP DISCHARGE FULL RHR C 370W 067W 2-RHRSPC-C FLOW BYPASS VALVE 2-RHRLPCI-C 2-RHRASC-C 2-RHRSPC-A 2-RHRSC-C HV-51-2F010B PUMP DISCHARGE FULL RHR D 370E 067E 2-RHRSPC-D FLOW BYPASS VALVE 2-RHRASC-D 2-RHRLPCI-D 2-RHRSC-D 2-RHRSPC-B HV-51-2F011A HEAT EXCHANGER RHR N/A 280 054 2-RHRSPC-C DISCH LINE TO 2-RHRSPC-A SUPPRESSION CHAMBER 2-RHRSC-C SHUTOFF VALVE 2-RHRLPCI-A 2-RHRSC-A APPENDIX 9A 9A-405 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-2F011B HEAT EXCHANGER RHR N/A 281 055 2-RHRLPCI-B DISCH LINE TO 2-RHRSPC-D SUPPRESSION CHAMBER 2-RHRSC-D SHUTOFFVALVE 2-RHRASC-B 2-RHRASC-D 2-RHRSPC-B HV-51-2F014A RHR HEAT EXCHANGER RHRSW A 280 054 2-RHRSW-A TUBE SIDE INLET VALVE HV-51-2F014B RHR HEAT EXCHANGER RHRSW B 281 055 2-RHRSW-B TUBE SIDE INLET VALVE HV-51-2F015A SHUTDOWN COOLING RHR B 376W 066W 2-RHRASC-C RETURN LINE OUTBD 2-RHRSPC-C CTMT ISO VALVE 2-RHRSPC-A 2-RHRSC-C 2-RHRLPCI-A 2-RHRASC-A 2-HI/LOW 2-RHRSC-A HV-51-2F015B SHUTDOWN COOLING RHR B 376E 066E 2-HI/LOW RETURN LINE OUTBD 2-RHRSPC-D CTMT ISO VALVE 2-RHRSPC-B 2-RHRSC-D 2-RHRLPCI-B 2-RHRASC-B 2-RHRASC-D 2-RHRSC-B HV-51-2F016A DRYWELL SPRAY LINE RHR A 575 070W 2-RHRASC-A OUTBD CTMT ISO VALVE 2-RHRASC-C 2-RHRLPCI-A 2-RHRSC-A 2-RHRSC-C 2-RHRSPC-A 2-RHRSPC-C HV-51-2F016B DRYWELL SPRAY LINE RHR B 593 070E 2-RHRSC-B OUTBD CTMT ISO VALVE 2-RHRSPC-D 2-RHRSC-D 2-RHRLPCI-B 2-RHRASC-D 2-RHRASC-B 2-RHRSPC-B APPENDIX 9A 9A-406 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-2F017A LPCI INJECTION LINE RHR A 589 070W 2-RHRLPCI-A OUTBD CTMT ISO VALVE 2-RHRSPC-C 2-RHRSPC-A 2-RHRSC-A 2-RHRASC-C 2-RHRASC-A 2-HI/LOW 2-RHRSC-C HV-51-2F017B LPCI INJECTION LINE RHR B 584 070E 2-RHRLPCI-B OUTBD CTMT ISO VALVE 2-RHRSPC-B 2-RHRSPC-D 2-RHRSC-B 2-RHRASC-B 2-HI/LOW 2-RHRSC-D 2-RHRASC-D HV-51-2F017C LPCI INJECTION LINE RHR C 589 070W 2-RHRSPC-C OUTBD CTMT ISO VALVE 2-HI/LOW 2-RHRASC-C 2-RHRLPCI-C 2-RHRSC-C HV-51-2F017D LPCI INJECTION LINE RHR D 584 070E 2-RHRSPC-D OUTBD CTMT ISO VALVE 2-RHRSC-D 2-RHRLPCI-D 2-HI/LOW 2-RHRASC-D HV-51-2F021A DRYWELL SPRAY LINE RHR A 473 053 2-RHRASC-A INBD CTMT ISO VALVE 2-RHRASC-C 2-RHRLPCI-A 2-RHRSC-A 2-RHRSC-C 2-RHRSPC-A 2-RHRSPC-C HV-51-2F021B DRYWELL SPRAY LINE RHR B 473 053 2-RHRASC-B INBD CTMT ISO VALVE 2-RHRASC-D 2-RHRLPCI-B 2-RHRSC-B 2-RHRSC-D 2-RHRSPC-B 2-RHRSPC-D HV-51-2F024A SUPPRESSION POOL RHR A 370W 067W 2-RHRSC-C COOLING LINE 2-RHRASC-A SHUTOFF VALVE 2-RHRSPC-A 2-RHRSPC-C 2-RHRSC-A 2-RHRASC-C 2-RHRLPCI-A APPENDIX 9A 9A-407 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-2F024B SUPPRESSION POOL RHR B 370E 067E 2-RHRASC-B COOLING LINE 2-RHRASC-D SHUTOFF VALVE 2-RHRLPCI-B 2-RHRSC-B 2-RHRSC-D 2-RHRSPC-B 2-RHRSPC-D HV-51-2F026A HEAT EXCHANGER RHR N/A 173 054 2-RHRSC-C DISCHARGE LINE TO 2-RHRSPC-A RCIC SHUTOFF VALVE 2-RHRLPCI-A 2-RHRSPC-C 2-RHRSC-A HV-51-2F026B HEAT EXCHANGER RHR N/A 174 055 2-RHRSPC-B DISCHARGE LINE TO 2-RHRSPC-D RCIC SHUTOFF VALVE 2-RHRSC-D 2-RHRLPCI-B 2-RHRASC-D 2-RHRASC-B HV-51-2F027A SUPPRESSION POOL RHR A 370W 067W 2-RHRSC-C SPRAY LINE CTMT ISO 2-RHRASC-C VALVE 2-RHRLPCI-A 2-RHRSC-A 2-RHRASC-A HV-51-2F027B SUPPRESSION POOL RHR B 370E 067E 2-RHRSC-B SPRAY LINE CTMT ISO 2-RHRSC-D VALVE 2-RHRLPCI-B 2-RHRASC-B 2-RHRASC-D HV-51-2F040 HEAT EXCHANGER RHR A 280 054 2-RHRASC-A DISCHARGE LINE TO 2-RHRASC-C RADWASTE SHUTOFF 2-RHRLPCI-A VALVE 2-RHRSC-A 2-RHRSC-C 2-RHRSPC-A 2-RHRSPC-C HV-51-2F047A HEAT EXCHANGER RHR A 376W 066W 2-RHRSC-C INLET VALVE FROM 2-RHRSPC-A PUMP DISCHARGE 2-RHRSPC-C 2-RHRSC-A 2-RHRASC-C 2-RHRASC-A HV-51-2F047B HEAT EXCHANGER RHR B 376E 066E 2-RHRSPC-B INLET VALVE FROM 2-RHRSPC-D PUMP DISCHARGE 2-RHRSC-D 2-RHRSC-B 2-RHRASC-D 2-RHRASC-B APPENDIX 9A 9A-408 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-51-2F049 HEAT EXCHANGER RHR B 280 054 2-RHRASC-C DISCHARGE LINE TO 2-RHRLPCI-A RADWASTE SHUTOFF 2-RHRSC-A VALVE 2-RHRSC-C 2-RHRSPC-A 2-RHRSPC-C 2-RHRASC-A HV-51-2F068A RHR HEAT EXCHANGER RHRSW C 280 054 2-RHRSW-A TUBE SIDE OUTLET VALVE HV-51-2F068B RHR HEAT EXCHANGER RHRSW D 281 055 2-RHRSW-B TUBE SIDE OUTLET VALVE HV-51-2F073 RHRSW TO RHR RHR A 280 054 2-RHRSW-A INTERTIE LINE SHUTOFF VALVE HV-51-2F074 RHR SW CROSS TIE RHR A 173 054 2-RHRSW-A DRAIN VALVE HV-51-2F075 RHRSW TO RHR RHR A 280 054 2-RHRSW-A INTERTIE SHUTOFF VALVE HV-52-139 CTMT ISO VALVE FOR SPI B 118 039 LEVEL SENSING LINES HV-52-1F005 CORE SPRAY INBD ISO CS/ A 523 047W 1-HI/LOW VALVE "A" LOOP HILOW HV-52-1F037 CORE SPRAY INBD ISO CS/ B 523 047W 1-HPCI VALVE "B" LOOP HPCI HV-52-1F039A 1A LOOP CHECK HI/LOW A 400 030 1-HI/LOW EQUALIZING PCIV HV-52-239 CTMT ISO VALVE FOR SPI B 189 062 LEVEL SENSING LINES HV-52-2F005 CORE SPRAY INBD ISO CS/ A 593 070E 2-HI/LOW VALVE "A" LOOP HILOW HV-52-2F037 CORE SPRAY INBD ISO CS/ B 593 070E 2-HPCI VALVE "B" LOOP HPCI HV-52-2F039A 2A LOOP CHECK HI/LOW A 473 053 2-HI/LOW EQUALIZING PCIV HV-55-120 CTMT ISO VALVE FOR SPI B 204 031 LEVEL SENSING LINES HV-55-121 CTMT ISO VALVE FOR SPI B 204 031 LEVEL SENSING LINES HV-55-124 CSTTO SAFEGUARD HPCI A CST YARD 1-HPCI SYSTEM ISOLATING RCIC DIKED 1-RCIC VALVE (OUTLET) AREA HV-55-125 CST TOSAFEGUARD HPCI B CST YARD 1-HPCI SYSTEM ISOLATING RCIC DIKED 1-RCIC VALVE (OUTLET)
APPENDIX 9A 9A-409 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-55-126 CTMT ISO VALVE FOR SPI A 204 031 LEVEL SENSING LINES HV-55-1F001 STEAM SUPPLY LINE HPCI B 109 034 1-HPCITRIP INLET VALVE TO 1-HPCI TURBINE HV-55-1F002 STEAM SUPPLY LINE HPCI D 400 030 1-HPCITRIP INBD CTMT ISO VALVE 1-HPCI HV-55-1F003 STEAM SUPPLY LINE HPCI B 309W 043W 1-HPCI OUTBD CTMT ISO VALVE 1-HPCITRIP HV-55-1F004 PUMP SUCTION VALVE HPCI B 109 034 1-HPCI FROM CONDENSATE STORAGE TANK HV-55-1F006 INJECTION VALVE TO HPCI B 500 047E 1-HPCI CORE SPRAY LINE HV-55-1F007 PUMP DISCHARGE VALVE HPCI B 200 042 1-HPCI HV-55-1F008 FULL FLOW TEST HPCI B 200 042 1-HPCI THROTTLE VALVE HV-55-1F012 MINIMUM FLOW BYPASS HPCI B 288 034 1-HPCI LINE CTMT ISO VALVE HV-55-1F041 PUMP SUCTION VALVE HPCI B 109 034 1-HPCI FROM SUPPRESSION CHAMBER HV-55-1F042 PUMP SUCTION VALVE HPCI B 109 034 1-HPCI FROM SUPPRESSION CHAMBER CTMT ISO VALVE HV-55-1F072 TURBINE EXHAUST HPCI B 288 034 1-HPCI LINE CTMT ISO VALVE HV-55-1F093 TURBINE EXHAUST HPCI B 200 042 1-HPCI LINE VACUUM BREAKER VALVE HV-55-1F095 TURBINE EXHAUST HPCI D 288 034 1-HPCI LINE VACUUM BREAKER VALVE HV-55-1F105 HPCI PUMP DISCHARGE HPCI B 518 046 1-HPCI VALVE TO FEEDWATER HV-55-220 CTMT ISO VALVE FOR SPI B 280 054 LEVEL SENSING LINES HV-55-221 CTMT ISO VALVE FOR SPI B 280 054 LEVEL SENSING LINES HV-55-224 CST TO SAFEGUARD HPCI A CST YARD 2-HPCI SYSTEM ISOLATING RCIC DIKED 2-RCIC VALVE (OUTLET) AREA HV-55-225 CST TO SAFEGUARD HPCI B CST YARD 2-HPCI SYSTEM ISOLATING RCIC DIKED 2-RCIC VALVE (OUTLET) AREA APPENDIX 9A 9A-410 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-55-2F001 STEAM SUPPLY LINE HPCI B 180 057 2-HPCI INLET VALVE TO TURBINE 2-RCICTRIP HV-55-2F002 STEAM SUPPLY LINE HPCI D 473 053 2-HPCI INBD CTMT ISO VALVE 2-HPCITRIP HV-55-2F003 STEAM SUPPLY LINE HPCI B 376W 066W 2-HPCI OUTBD CTMT ISO VALVE 2-HPCITRIP HV-55-2F004 PUMP SUCTION VALVE HPCI B 180 057 2-HPCI FROM CONDENSATE STORAGE TANK HV-55-2F006 INJECTION VALVE TO HPCI B 580E 070E 2-HPCI CORE SPRAY LINE HV-55-2F007 PUMP DISCHARGE HPCI B 279 065 2-HPCI VALVE HV-55-2F008 FULL FLOW TEST HPCI B 279 065 2-HPCI THROTTLE VALVE HV-55-2F012 MINIMUM FLOW HPCI B 283 057 2-HPCI BYPASS LINE CTMT ISO VALVE HV-55-2F041 PUMP SUCTION VALVE HPCI B 180 057 2-HPCI FROM SUPPRESSION CHAMBER HV-55-2F042 PUMP SUCTION VALVE HPCI B 180 057 2-HPCI FROM SUPPRESSION CHAMBER CTMT ISO VALVE HV-55-2F072 TURBINE EXHAUST HPCI B 283 057 2-HPCI LINE CTMT ISO VALVE HV-55-2F093 TURBINE EXHAUST HPCI B 279 065 2-HPCI LINE VACUUM BREAKER VALVE HV-55-2F095 TURBINE EXHAUST HPCI D 283 057 2-HPCI LINE VACUUM BREAKER VALVE HV-55-2F105 HPCI PUMP DISCHARGE HPCI B 587 069 2-HPCI VALVE TO FEEDWATER HV-56-1F059 COOLING WATER LINE HPCI B 109 034 1-HPCI SHUTOFF VALVE HV-56-2F059 COOLING WATER LINE HPCI B 180 057 2-HPCI SHUTOFF VALVE HV-59-129B INST GAS OUTBD PCIV PCIG B 306 043W 1-MSRV HV-59-151A CTMT ISO VALVE PCIG C 306 043W 1-RHRASC-C 1-RHRASC-D 1-RHRASC-B 1-RHRASC-A HV-59-151B CTMT ISO VALVE PCIG D 307 043E 1-RHRASC-B 1-RHRASC-C 1-RHRASC-D 1-RHRASC-A APPENDIX 9A 9A-411 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
HV-59-229B INST GAS OUTBD PCIV PCIG B 375 066W 2-MSRV HV-59-251A CTMT ISO VALVE PCIG C 375 066W 2-RHRASC-D 2-RHRASC-C 2-RHRASC-A 2-RHRASC-B HV-59-251B CTMT ISO VALVE PCIG D 374 066E 2-RHRASC-A 2-RHRASC-B 2-RHRASC-C 2-RHRASC-D HV-C41-1F020 MAIN STEAM LINE HI/LOW A 407 046 1-HI/LOW PRESSURE EQUALIZING VALVE HV-C41-2F020 MAIN STEAM LINE HI/LOW A 480 069 2-HI/LOW PRESSURE EQUALIZING VALVE HV-C44-1F033 RWCU DUMP FLOW HI/LOW 0 510 047W 1-HI/LOW CONTROL VALVE HV-C44-2F033 RWCU DUMP FLOW HI/LOW 0 584 070E 2-HI/LOW CONTROL VALVE HV-C51-1F048A HEAT EXCHANGER RHR A 309W 043W 1-RHRASC-A BYPASS VALVE FROM 1-RHRSPC-C PUMP DISCHARGE 1-RHRSPC-A 1-RHRSC-C 1-RHRASC-C 1-RHRLPCI-A 1-RHRSC-A HV-C51-1F048B HEAT EXCHANGER RHR B 309E 043E 1-RHRASC-B BYPASS VALVE FROM 1-RHRASC-D PUMP DISCHARGE 1-RHRLPCI-B 1-RHRSC-B 1-RHRSC-D 1-RHRSPC-B 1-RHRSPC-D HV-C51-2F048A HEAT EXCHANGER RHR A 376W 066W 2-RHRSC-C BYPASS VALVE FROM 2-RHRSPC-A PUMP DISCHARGE 2-RHRSC-A 2-RHRSPC-C 2-RHRASC-C 2-RHRASC-A 2-RHRLPCI-A HV-C51-2F048B HEAT EXCHANGER RHR B 376E 066E 2-RHRSC-D BYPASS VALVE FROM 2-RHRSPC-B PUMP DISCHARGE 2-RHRSC-B 2-RHRLPCI-B 2-RHRASC-D 2-RHRASC-B 2-RHRSPC-D APPENDIX 9A 9A-412 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
KS-81-101A CELL "A" TIMER DGEV A 311A 079 KS-81-101B CELL "B" TIMER DGEV B 311B 081 KS-81-101C CELL "C" TIMER DGEV C 311C 080 KS-81-101D CELL "D" TIMER DGEV D 311D 082 KS-81-101E CELL "A" TIMER DGEV A 311A 079 KS-81-101F CELL "B" TIMER DGEV B 311B 081 KS-81-101G CELL "C" TIMER DGEV C 311C 080 KS-81-101H CELL "D" TIMER DGEV D 311D 082 KS-81-201A CELL "A" TIMER DGEV A 315A 083 KS-81-201B CELL "B" TIMER DGEV B 315B 085 KS-81-201C CELL "C" TIMER DGEV C 315C 084 KS-81-201D CELL "D" TIMER DGEV D 315D 086 KS-81-201E CELL "A" TIMER DGEV A 315A 083 KS-81-201F CELL "B" TIMER DGEV B 315B 085 KS-81-201G CELL "C" TIMER DGEV C 315C 084 KS-81-201H CELL "D" TIMER DGEV D 315D 086 LI-42-1R010 REACTOR VESSEL RVI A 540 026 1-RVI WATER LEVEL INDICATOR LI-42-2R010 REACTOR VESSEL RVI A 540 026 2-RVI WATER LEVEL INDICATOR LI-52-140A SUPPRESSION POOL SPI A 533 024 1-SPI LEVEL INDICATOR LI-52-140B SUPPRESSION POOL SPI B 533 024 1-SPI LEVEL INDICATOR LI-52-240A SUPPRESSION POOL SPI A 533 024 2-SPI LEVEL INDICATOR LI-52-240B SUPPRESSION POOL SPI B 533 024 2-SPI LEVEL INDICATOR LI-52-241 SUPPRESSION POOL SPI A 540 026 2-SPI LEVEL INDICATOR LI-55-115-1 SUPPRESSION POOL SPI 0(A) 533 024 1-SPI LEVEL INDICATOR LI-55-115-2 SUPPRESSION POOL SPI 0(A) 540 026 1-SPI LEVEL INDICATOR LI-55-141 SUPPRESSION POOL SPI A 540 026 1-SPI LEVEL INDICATOR LI-55-215-2 SUPPRESSION POOL SPI 0(A) 540 026 2-SPI LEVEL INDICATOR LI-55-217 SUPPRESSION POOL SPI B 533 024 2-SPI LEVEL INDICATOR APPENDIX 9A 9A-413 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
LIS-42-1N691A LEVEL INDICATING CS A 542 025 SWITCH LIS-42-1N691B LEVEL INDICATING CS B 542 025 SWITCH LIS-42-1N691C LEVEL INDICATING CS C 542 025 SWITCH LIS-42-1N691D LEVELINDICATING CS D 542 025 SWITCH LIS-42-1N691E LEVEL INDICATING CS A 542 025 SWITCH LIS-42-1N691F LEVEL INDICATING CS B 542 025 SWITCH LIS-42-1N691G LEVEL INDICATING CS C 542 025 SWITCH LIS-42-1N691H LEVEL INDICATING CS D 542 025 SWITCH LIS-42-1N695A LEVEL INDICATING ADS A 542 025 SWITCH LIS-42-1N695C LEVEL INDICATING ADS C 542 025 SWITCH LIS-42-1N697A LEVEL INDICATING RCIC A 542 025 SWITCH LIS-42-1N697E LEVEL INDICATING RCIC A 542 025 SWITCH LIS-42-2N691A LEVEL INDICATING CS A 542 025 SWITCH LIS-42-2N691B LEVEL INDICATING CS B 542 025 SWITCH LIS-42-2N691C LEVEL INDICATING CS C 542 025 SWITCH LIS-42-2N691D LEVEL INDICATING CS D 542 025 SWITCH LIS-42-2N691E LEVEL INDICATING CS A 542 025 SWITCH LIS-42-2N691F LEVEL INDICATING CS B 542 025 SWITCH LIS-42-2N691G LEVEL INDICATING CS C 542 025 SWITCH LIS-42-2N691H LEVEL INDICATING CS D 542 025 SWITCH LIS-42-2N695A LEVEL INDICATING ADS A 542 025 SWITCH LIS-42-2N695C LEVEL INDICATING ADS C 542 025 SWITCH APPENDIX 9A 9A-414 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
LIS-42-2N697A LEVEL INDICATING RCIC A 542 025 SWITCH LIS-42-2N697E LEVEL INDICATING RCIC A 542 025 SWITCH LIS-49-1N635A LEVEL INDICATING RCIC A 542 025 SWITCH LIS-49-1N635E LEVEL INDICATING RCIC A 542 025 SWITCH LIS-49-2N635A LEVEL INDICATING RCIC A 542 025 SWITCH LIS-49-2N635E LEVEL INDICATING RCIC A 542 025 SWITCH LIS-55-1N661B LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-1N661F LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-1N662B LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-1N662F LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-2N661B LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-2N661F LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-2N662B LEVEL INDICATING HPCI B 542 025 SWITCH LIS-55-2N662F LEVEL INDICATING HPCI B 542 025 SWITCH LS-42-1N692A LEVEL SWITCH RCIC A 542 025 LS-42-1N692B LEVEL SWITCH HPCI B 542 025 LS-42-1N692D LEVEL SWITCH HPCI D 542 025 LS-42-1N692E LEVEL SWITCH RCIC A 542 025 LS-42-1N692F LEVEL SWITCH HPCI B 542 025 LS-42-1N692H LEVEL SWITCH HPCI D 542 025 LS-42-1N693A LEVEL SWITCH RCIC A 542 025 LS-42-1N693B LEVEL SWITCH HPCI B 542 025 LS-42-1N693D LEVEL SWITCH HPCI D 542 025 LS-42-1N693E LEVEL SWITCH RCIC A 542 025 LS-42-1N693F LEVEL SWITCH HPCI B 542 025 LS-42-1N693H LEVEL SWITCH HPCI D 542 025 LS-42-1N698A LEVEL SWITCH RCIC A 542 025 LS-42-1N698E LEVEL SWITCH RCIC A 542 025 APPENDIX 9A 9A-415 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
LS-42-2N692A LEVEL SWITCH RCIC A 542 025 LS-42-2N692B LEVEL SWITCH HPCI B 542 025 LS-42-2N692D LEVEL SWITCH HPCI D 542 025 LS-42-2N692E LEVEL SWITCH RCIC A 542 025 LS-42-2N692F LEVEL SWITCH HPCI B 542 025 LS-42-2N692H LEVEL SWITCH HPCI D 542 025 LS-42-2N693A LEVEL SWITCH RCIC A 542 025 LS-42-2N693B LEVEL SWITCH HPCI B 542 025 LS-42-2N693D LEVEL SWITCH HPCI D 542 025 LS-42-2N693E LEVEL SWITCH RCIC A 542 025 LS-42-2N693F LEVEL SWITCH HPCI B 542 025 LS-42-2N693H LEVEL SWITCH HPCI D 542 025 LS-42-2N698A LEVEL SWITCH RCIC A 542 025 LS-42-2N698E LEVEL SWITCH RCIC A 542 025 LSHL-20-121A LEVEL SWITCH SDG A 312A 079 LSHL-20-121B LEVEL SWITCH SDG B 312B 081 LSHL-20-121C LEVEL SWITCH SDG C 312C 080 LSHL-20-121D LEVEL SWITCH SDG D 312D 082 LSHL-20-122A LEVEL SWITCH SDG A 312A 079 LSHL-20-122B LEVEL SWITCH SDG B 312B 081 LSHL-20-122C LEVEL SWITCH SDG C 312C 080 LSHL-20-122D LEVEL SWITCH SDG D 312D 082 LSHL-20-221A LEVEL SWITCH SDG A 316A 083 LSHL-20-221B LEVEL SWITCH SDG B 316B 085 LSHL-20-221C LEVEL SWITCH SDG C 316C 084 LSHL-20-221D LEVEL SWITCH SDG D 316D 086 LSHL-20-222A LEVEL SWITCH SDG A 316A 083 LSHL-20-222B LEVEL SWITCH SDG B 316B 085 LSHL-20-222C LEVEL SWITCH SDG C 316C 084 LSHL-20-222D LEVEL SWITCH SDG D 316D 086 LSL-20-127A LEVEL SWITCH SDG A 311A 079 LSL-20-127B LEVEL SWITCH SDG B 311B 081 LSL-20-127C LEVEL SWITCH SDG C 311C 080 LSL-20-127D LEVEL SWITCH SDG D 311D 082 LSL-20-227A LEVEL SWITCH SDG A 315A 083 LSL-20-227B LEVEL SWITCH SDG B 315B 085 LSL-20-227C LEVEL SWITCH SDG C 315C 084 LSL-20-227D LEVEL SWITCH SDG D 315D 086 LT-42-115A LEVEL TRANSMITTER RVI A 402W 045W LT-42-115B LEVEL TRANSMITTER RVI B 402E 045E APPENDIX 9A 9A-416 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
LT-42-1N010 LEVEL TRANSMITTER RVI A 402W 045W LT-42-1N091A LEVEL TRANSMITTER CS A 402W 045W LT-42-1N091B LEVEL TRANSMITTER HPCI B 402E 045E LT-42-1N091C LEVEL TRANSMITTER CS C 402E 045E 402W 045W LT-42-1N091D LEVEL TRANSMITTER CS D 402E 045E 402W 045W LT-42-1N091E LEVEL TRANSMITTER CS A 402W 045W LT-42-1N091F LEVEL TRANSMITTER HPCI B 402E 045E LT-42-1N091G LEVEL TRANSMITTER CS C 402E 045E 402W 045W LT-42-1N091H LEVEL TRANSMITTER CS D 402E 045E 402W 045W LT-42-1N095A LEVEL TRANSMITTER ADS A 402W 045W LT-42-1N095C LEVEL TRANSMITTER ADS C 402E 045E 402W 045W LT-42-1N097A LEVEL TRANSMITTER RCIC A 402W 045W LT-42-1N097E LEVEL TRANSMITTER RCIC A 402W 045W LT-42-215A LEVEL TRANSMITTER RVI A 475W 068W LT-42-215B LEVEL TRANSMITTER RVI B 475E 068E LT-42-2N010 LEVEL TRANSMITTER RVI A 475W 068W LT-42-2N091A LEVEL TRANSMITTER CS A 475W 068W LT-42-2N091B LEVEL TRANSMITTER CS B 475E 068E LT-42-2N091C LEVEL TRANSMITTER CS C 475E 068E 475W 068W LT-42-2N091D LEVEL TRANSMITTER CS D 475E 068E 475W 068W LT-42-2N091E LEVEL TRANSMITTER CS A 475W 068W LT-42-2N091F LEVEL TRANSMITTER CS B 475E 068E LT-42-2N091G LEVEL TRANSMITTER CS C 475E 068E 475W 068W LT-42-2N091H LEVEL TRANSMITTER CS D 475E 068E 475W 068W LT-42-2N095A LEVEL TRANSMITTER ADS A 475W 068W LT-42-2N095C LEVEL TRANSMITTER ADS C 475E 068E 475W 068W LT-42-2N097A LEVEL TRANSMITTER RCIC A 475W 068W LT-42-2N097E LEVEL TRANSMITTER RCIC A 475W 068W LT-49-1N035A LEVEL TRANSMITTER RCIC A 200 042 LT-49-1N035E LEVEL TRANSMITTER RCIC A 200 042 LT-49-2N035A LEVEL TRANSMITTER RCIC A 279 065 LT-49-2N035E LEVEL TRANSMITTER RCIC A 279 065 LT-52-140A LEVEL TRANSMITTER SPI A 118 039 APPENDIX 9A 9A-417 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
LT-52-140B LEVEL TRASNMITTER SPI B 118 039 LT-52-240A LEVEL TRANSMITTER SPI A 189 062 LT-52-240B LEVEL TRANSMITTER SPI B 189 062 LT-52-241 LEVEL TRANSMITTER SPI A 189 062 LT-55-115 LEVEL TRANSMITTER SPI 0(A) 204 031 LT-55-141 LEVEL TRANSMITTER SPI A 203 032 LT-55-1N061B LEVEL TRANSMITTER HPCI B 200 042 LT-55-1N061F LEVEL TRANSMITTER HPCI B 200 042 LT-55-1N062B LEVEL TRANSMITTER HPCI B 204 031 LT-55-1N062F LEVEL TRANSMITTER HPCI B 204 031 LT-55-215 LEVEL TRANSMITTER SPI 0(A) 280 054 LT-55-217 LEVEL TRANSMITTER SPI B 174 055 LT-55-2N061B LEVEL TRANSMITTER HPCI B 279 065 LT-55-2N061F LEVEL TRANSMITTER HPCI B 279 065 LT-55-2N062B LEVEL TRANSMITTER HPCI B 280 054 LT-55-2N062F LEVEL TRANSMITTER HPCI B 280 054 PCV-59-152A-1 PRESSURE CONTROL PCIG N/A 304W 044W 1-RHRASC-A VALVE 1-RHRASC-B 1-RHRASC-C 1-RHRASC-D PCV-59-152A-2 PRESSURE CONTROL PCIG N/A 304W 044W 1-RHRASC-A VALVE 1-RHRASC-B 1-RHRASC-C 1-RHRASC-D PCV-59-152A-3 PRESSURE CONTROL PCIG N/A 304W 044W 1-RHRASC-B VALVE 1-RHRASC-C 1-RHRASC-A 1-RHRASC-D PCV-59-152B-1 PRESSURE CONTROL PCIG N/A 304E 044E 1-RHRASC-A VALVE 1-RHRASC-B 1-RHRASC-C 1-RHRASC-D PCV-59-152B-2 PRESSURE CONTROL PCIG N/A 304E 044E 1-RHRASC-B VALVE 1-RHRASC-C 1-RHRASC-A 1-RHRASC-D PCV-59-152B-3 PRESSURE CONTROL PCIG N/A 304E 044E 1-RHRASC-A VALVE 1-RHRASC-B 1-RHRASC-C 1-RHRASC-D PCV-59-252A-1 PRESSURE CONTROL PCIG N/A 370E 067E 2-RHRASC-B VALVE 2-RHRASC-C 2-RHRASC-A 2-RHRASC-D APPENDIX 9A 9A-418 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PCV-59-252A-2 PRESSURE CONTROL PCIG N/A 370E 067E 2-RHRASC-A VALVE 2-RHRASC-B 2-RHRASC-C 2-RHRASC-D PCV-59-252A-3 PRESSURE CONTROL PCIG N/A 370E 067E 2-RHRASC-B VALVE 2-RHRASC-C 2-RHRASC-A 2-RHRASC-D PCV-59-252B-1 PRESSURE CONTROL PCIG N/A 370E 067E 2-RHRASC-A VALVE 2-RHRASC-B 2-RHRASC-C 2-RHRASC-D PCV-59-252B-2 PRESSURE CONTROL PCIG N/A 370E 067E 2-RHRASC-A VALVE 2-RHRASC-D 2-RHRASC-B 2-RHRASC-C PCV-59-252B-3 PRESSURE CONTROL PCIG N/A 370E 067E 2-RHRASC-A VALVE 2-RHRASC-B 2-RHRASC-C 2-RHRASC-D PDIS-49-1N657A PRESSURE RCIC A 542 025 DIFFERENTIAL INDICATING SWITCH PDIS-49-1N657C PRESSURE RCIC C 542 025 DIFFERENTIAL INDICATING SWITCH PDIS-49-2N657A PRESSURE RCIC A 542 025 DIFFERENTIAL INDICATING SWITCH PDIS-49-2N657C PRESSURE RCIC C 542 025 DIFFERENTIAL INDICATING SWITCH PDIS-55-1N657B STEAM SUPPLY LINE HPCI B 542 025 DIFFERENTIAL PRESURE INDICATING SWITCH PDIS-55-1N657D STEAM SUPPLY LINE HPCI D 542 025 DIFFERENTIAL PRESURE INDICATING SWITCH PDIS-55-2N657B STEAM SUPPLY LINE HPCI B 533 024 DIFFERENTIAL PRESURE INDICATING SWITCH PDIS-55-2N657D STEAM SUPPLY LINE HPCI D 533 024 DIFFERENTIAL PRESURE INDICATING SWITCH APPENDIX 9A 9A-419 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PDISH-51-1N660A PRESSURE RHR A 542 025 DIFFERENTIAL INDICATING SWITCH PDISH-51-1N660B PRESSURE RHR B 542 025 DIFFERENTIAL INDICATING SWITCH PDISH-51-2N660A PRESSURE RHR A 542 025 DIFFERENTIAL INDICATING SWITCH PDISH-51-2N660B PRESSURE RHR B 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-1N658A PRESSURE RHR A 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-1N658B PRESSURE RHR B 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-1N658C PRESSURE RHR C 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-1N658D PRESSURE RHR D 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-2N658A PRESSURE RHR A 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-2N658B PRESSURE RHR B 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-2N658C PRESSURE RHR C 542 025 DIFFERENTIAL INDICATING SWITCH PDISL-51-2N658D PRESSURE RHR D 542 025 DIFFERENTIAL INDICATING SWITCH PDS-49-1N660A PRESSURE RCIC A 542 025 DIFFERENTIAL SWITCH PDS-49-1N660C PRESSURE RCIC C 542 025 DIFFERENTIAL SWITCH PDS-49-2N660A PRESSURE RCIC A 542 025 DIFFERENTIAL SWITCH PDS-49-2N660C PRESSURE RCIC C 542 025 DIFFERENTIAL SWITCH APPENDIX 9A 9A-420 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PDS-55-1N660B DIFFERENTIAL HPCI B 542 025 PRESSURE SWITCH PDS-55-1N660D DIFFERENTIAL HPCI D 542 025 PRESSURE SWITCH PDS-55-2N660B DIFFERENTIAL HPCI B 542 025 PRESSURE SWITCH PDS-55-2N660D PRESSURE HPCI D 542 025 DIFFERENTIAL SWITCH PDS-59-106A PRESSURE PCIG C 402W 045W DIFFERENTIAL SWITCH PDS-59-106B PRESSURE PCIG D 402E 045E DIFFERENTIAL SWITCH PDS-59-206A PRESSURE PCIG C 475W 068W DIFFERENTIAL SWITCH PDS-59-206B PRESSURE PCIG D 475E 068E DIFFERENTIAL SWITCH PDSH-20-122A PRESSURE SDG A 311A 079 DIFFERENTIAL SWITCH PDSH-20-122B PRESSURE SDG B 311B 081 DIFFERENTIAL SWITCH PDSH-20-122C PRESSURE SDG C 311C 080 DIFFERENTIAL SWITCH PDSH-20-122D PRESSURE SDG D 311D 082 DIFFERENTIAL SWITCH PDSH-20-222A PRESSURE SDG A 315A 083 DIFFERENTIAL SWITCH PDSH-20-222B PRESSURE SDG B 315B 085 DIFFERENTIAL SWITCH PDSH-20-222C PRESSURE SDG C 315C 084 DIFFERENTIAL SWITCH PDSH-20-222D PRESSURE SDG D 315D 086 DIFFERENTIAL SWITCH PDSH-50-101 PRESSURE RCIC A 108 033 DIFFERENTIAL SWITCH PDSH-50-201 PRESSURE RCIC A 179 056 DIFFERENTIAL SWITCH PDSL-51-1N661A PRESSURE RHR A 542 025 DIFFERENTIAL SWITCH PDSL-51-1N661B PRESSURE RHR B 542 025 DIFFERENTIAL SWITCH PDSL-51-2N661A PRESSURE RHR A 542 025 DIFFERENTIAL SWITCH PDSL-51-2N661B PRESSURE RHR B 542 025 DIFFERENTIAL SWITCH APPENDIX 9A 9A-421 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PDT-49-1N057A DIFFERENTIAL RCIC A 304E 044E PRESSURE TRANSMITTER PDT-49-1N057C DIFFERENTIAL RCIC C 304E 044E PRESSURE TRANSMITTER PDT-49-2N057A DIFFERENTIAL RCIC A 370E 067E PRESSURE TRANSMITTER PDT-49-2N057C DIFFERENTIAL RCIC C 370E 067E PRESSURE TRANSMITTER PDT-51-1N058A DIFFERENTIAL RHR A 402W 045W PRESSURE TRANSMITTER PDT-51-1N058B DIFFERENTIAL RHR B 402E 045E PRESSURE TRANSMITTER PDT-51-1N058C DIFFERENTIAL RHR C 402E 045E PRESSURE 402W 045W TRANSMITTER PDT-51-1N058D DIFFERENTIAL RHR D 402E 045E PRESSURE 402W 045W TRANSMITTER PDT-51-1N060A DIFFERENTIAL RHR A 506E 047E PRESSURE TRANSMITTER PDT-51-1N060B DIFFERENTIAL RHR B 402E 045E PRESSURE TRANSMITTER PDT-51-2N058A DIFFERENTIAL RHR A 475W 068W PRESSURE TRANSMITTER PDT-51-2N058B DIFFERENTIAL RHR B 475E 068E PRESSURE TRANSMITTER PDT-51-2N058C DIFFERENTIAL RHR C 475E 068E PRESSURE 475W 068W TRANSMITTER PDT-51-2N058D DIFFERENTIAL RHR D 475E 068E PRESSURE 475W 068W TRANSMITTER PDT-51-2N060A DIFFERENTIAL RHR A 580W 070W PRESSURE TRANSMITTER PDT-51-2N060B DIFFERENTIAL RHR B 475E 068E PRESSURE TRANSMITTER APPENDIX 9A 9A-422 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PDT-55-1N057B DIFFERENTIAL HPCI B 304W 044W PRESSURE TRANSMITTER PDT-55-1N057D DIFFERENTIAL HPCI D 304W 044W PRESSURE TRANSMITTER PDT-55-2N057B DIFFERENTIAL HPCI B 370W 067W PRESSURE TRANSMITTER PDT-55-2N057D DIFFERENTIAL HPCI D 370W 067W PRESSURE TRANSMITTER PI-11-003A-1 ESW PUMP A ESW A 533 024 0-ESW-A DISCHARGE HEADER PI-11-003A-2 ESW PUMP A ESW A 540 026 0-ESW-R DISCHARGE HEADER PI-11-003B ESW PUMP B ESW B 533 024 0-ESW-B DISCHARGE HEADER PI-12-001A-1 RHRSW LOOP A RHRSW A 533 024 2-RHRSW-A HEADER PRESSURE 1-RHRSW-A PI-12-001A-2 RHRSW LOOP A RHRSW A 540 026 1-RHRSW-A HEADER PRESSURE PI-12-001A-3 RHRSW LOOP A RHRSW A 540 026 2-RHRSW-A HEADER PRESSURE PI-12-001B RHRSW LOOP B RHRSW B 533 024 1-RHRSW-B HEADER PRESSURE 2-RHRSW-B PI-42-1R011 REACTOR VESSEL RVI A 540 026 1-RVI PRESSURE INDICATOR PI-42-2R011 REACTOR VESSEL RVI A 540 026 2-RVI PRESSURE INDICATOR PI-51-105A-1 RHR HEAT EXCHANGER RHRSW A 533 024 1-RHRSW-A 1AE205 SERVICE WATER DISCHARGE PI-51-105A-2 RHR HEAT EXCHANGER RHRSW A 540 026 1-RHRSW-A 1AE205 SERVICE WATER DISCHARGE PI-51-105B RHR HEAT EXCHANGER RHRSW B 533 024 1-RHRSW-B 1BE205 SERVICE WATER DISCHARGE PI-51-1R003A RHR PUMP A RHR N/A 200 042 1-RHRSC-A DISCHARGE PRESSURE 1-RHRSPC-A (LOCAL)
APPENDIX 9A 9A-423 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PI-51-205A-1 RHR HEAT EXCHANGER RHRSW A 533 024 2-RHRSW-A 2AE205 SERVICE WATER DISCHARGE PI-51-205A-2 RHR HEAT EXCHANGER RHRSW A 540 026 2-RHRSW-A 2AE205 SERVICE WATER DISCHARGE PI-51-205B RHR HEAT EXCHANGER RHRSW B 533 024 2-RHRSW-B 2BE205 SERVICE WATER DISCHARGE PI-55-1R601 PUMP DISCHARGE LINE HPCI B 533 024 1-HPCI PRESSURE INDICATOR PI-55-2R601 PUMP DISCHARGE LINE HPCI B 533 024 2-HPCI PRESSURE INDICATOR PIS-42-1N690A PRESSURE INDICATING CS A 542 025 SWITCH PIS-42-1N690B PRESSURE INDICATING CS B 542 025 SWITCH PIS-42-1N690C PRESSURE INDICATING CS C 542 025 SWITCH PIS-42-1N690D PRESSURE INDICATING CS D 542 025 SWITCH PIS-42-1N690E PRESSURE INDICATING CS A 542 025 SWITCH PIS-42-1N690F PRESSURE INDICATING CS B 542 025 SWITCH PIS-42-1N690G PRESSURE INDICATING CS C 542 025 SWITCH PIS-42-1N690H PRESSURE INDICATING CS D 542 025 SWITCH PIS-42-1N694A PRESSURE INDICATING CS A 542 025 SWITCH PIS-42-1N694B PRESSURE INDICATING CS B 542 025 SWITCH PIS-42-1N694C PRESSURE INDICATING CS C 542 025 SWITCH PIS-42-1N694D PRESSURE INDICATING CS D 542 025 SWITCH PIS-42-1N694E PRESSURE INDICATING CS A 542 025 SWITCH PIS-42-1N694F PRESSURE INDICATING CS B 542 025 SWITCH PIS-42-1N694G PRESSURE INDICATING CS C 542 025 SWITCH APPENDIX 9A 9A-424 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PIS-42-1N694H PRESSURE CS D 542 025 INDICATING SWITCH PIS-42-2N690A PRESSURE CS A 542 025 INDICATING SWITCH PIS-42-2N690B PRESSURE CS B 542 025 INDICATING SWITCH PIS-42-2N690C PRESSURE CS C 542 025 INDICATING SWITCH PIS-42-2N690D PRESSURE CS D 542 025 INDICATING SWITCH PIS-42-2N690E PRESSURE CS A 542 025 INDICATING SWITCH PIS-42-2N690F PRESSURE CS B 542 025 INDICATING SWITCH PIS-42-2N690G PRESSURE CS C 542 025 INDICATING SWITCH PIS-42-2N690H PRESSURE CS D 542 025 INDICATING SWITCH PIS-42-2N694A PRESSURE CS A 542 025 INDICATING SWITCH PIS-42-2N694B PRESSURE CS B 542 025 INDICATING SWITCH PIS-42-2N694C PRESSURE CS C 542 025 INDICATING SWITCH PIS-42-2N694D PRESSURE CS D 542 025 INDICATING SWITCH PIS-42-2N694E PRESSURE CS A 542 025 INDICATING SWITCH PIS-42-2N694F PRESSURE CS B 542 025 INDICATING SWITCH PIS-42-2N694G PRESSURE CS C 542 025 INDICATING SWITCH PIS-42-2N694H PRESSURE CS D 542 025 INDICATING SWITCH PIS-49-1N650 PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-49-1N658A PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-49-1N658C PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-49-1N658E PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-49-1N658G PRESSURE RCIC C 542 025 INDICATING SWITCH APPENDIX 9A 9A-425 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PIS-49-2N650 PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-49-2N658A PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-49-2N658C PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-49-2N658E PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-49-2N658G PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-50-1N652 PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-1N653 PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-1N655A PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-1N655C PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-50-1N655E PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-1N655G PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-50-1N656A PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-1N656E PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-2N652 PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-2N653 PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-2N655A PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-2N655C PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-50-2N655E PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-2N655G PRESSURE RCIC C 542 025 INDICATING SWITCH PIS-50-2N656A PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-50-2N656E PRESSURE RCIC A 542 025 INDICATING SWITCH PIS-51-1N655A PRESSURE ADS A 542 025 INDICATING SWITCH APPENDIX 9A 9A-426 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PIS-51-1N655C PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-1N655E PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-1N655G PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-1N656A PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-1N656C PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-1N656E PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-1N656G PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-2N655A PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-2N655C PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-2N655E PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-2N655G PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-2N656A PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-2N656C PRESSURE ADS C 542 025 INDICATING SWITCH PIS-51-2N656E PRESSURE ADS A 542 025 INDICATING SWITCH PIS-51-2N656G PRESSURE ADS C 542 025 INDICATING SWITCH PIS-52-1N655A PRESSURE ADS A 542 025 INDICATING SWITCH PIS-52-1N655C PRESSURE ADS C 542 025 INDICATING SWITCH PIS-52-1N655E PRESSURE ADS A 542 025 INDICATING SWITCH PIS-52-1N655G PRESSURE ADS C 542 025 INDICATING SWITCH PIS-52-2N655A PRESSURE ADS A 542 025 INDICATING SWITCH PIS-52-2N655C PRESSURE ADS C 542 025 INDICATING SWITCH PIS-52-2N655E PRESSURE ADS A 542 025 INDICATING SWITCH APPENDIX 9A 9A-427 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PIS-52-2N655G PRESSURE ADS C 542 025 INDICATING SWITCH PIS-55-1N650 PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-55-1N658B PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-55-1N658D PRESSURE HPCI D 542 025 DIFFERENTIAL INDICATING SWITCH PIS-55-1N658F PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-55-1N658H PRESSURE HPCI D 542 025 DIFFERENTIAL INDICATING SWITCH PIS-55-2N650 PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-55-2N658B PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-55-2N658D PRESSURE HPCI D 542 025 INDICATING SWITCH PIS-55-2N658F PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-55-2N658H PRESSURE HPCI D 542 025 INDICATING SWITCH PIS-56-1N652 PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-1N653 PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-1N655B PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-1N655D PRESSURE HPCI D 542 025 INDICATING SWITCH PIS-56-1N655F PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-1N655H PRESSURE HPCI D 542 025 INDICATING SWITCH PIS-56-1N656B PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-1N656F PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-2N652 PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-2N653 PRESSURE HPCI B 542 025 INDICATING SWITCH APPENDIX 9A 9A-428 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PIS-56-2N655B PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-2N655D PRESSURE HPCI D 542 025 INDICATING SWITCH PIS-56-2N655F PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-2N655H PRESSURE HPCI D 542 025 INDICATING SWITCH PIS-56-2N656B PRESSURE HPCI B 542 025 INDICATING SWITCH PIS-56-2N656F PRESSURE HPCI B 542 025 INDICATING SWITCH PISH-51-1N653A PRESSURE RHR A 542 025 INDICATING SWITCH PISH-51-1N653B PRESSURE RHR B 542 025 INDICATING SWITCH PISH-51-1N653C PRESSURE RHR C 542 025 INDICATING SWITCH PISH-51-1N653D PRESSURE RHR D 542 025 SWITCH INDICATING PISH-51-1N657 PRESSURE RHR B 542 025 INDICATING SWITCH PISH-51-2N653A PRESSURE RHR A 542 025 INDICATING SWITCH PISH-51-2N653B PRESSURE RHR B 542 025 INDICATING SWITCH PISH-51-2N653C PRESSURE RHR C 542 025 INDICATING SWITCH PISH-51-2N657 PRESSURE RHR B 542 025 INDICATING SWITCH PIT-51-105A RHR HEAT EXCHANGER RHRSW A 200 042 1AE205 SERVICE WATER DISCHARGE PIT-51-105B RHR HEAT EXCHANGER RHRSW B 207 041 1BE205 SERVICE WATER DISCHARGE PIT-51-205A RHR HEAT EXCHANGER RHRSW A 284 064 2AE205 SERVICE WATER DISCHARGE PIT-51-205B RHR HEAT EXCHANGER RHRSW B 179 056 2BE205 SERVICE WATER DISCHARGE PSH-12-004A PRESSURE SWITCH - RHRSW A 1000 122 HIGH APPENDIX 9A 9A-429 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PSH-12-004B PRESSURE SWITCH - RHRSW B 1005 123 HIGH PSH-12-004C PRESSURE SWITCH - RHRSW A 1000 122 HIGH PSH-12-004D PRESSURE SWITCH - RHRSW B 1005 123 HIGH PSL-11-002A PRESSURE SWITCH - ESW A 1000 122 LOW PSL-11-002B PRESSURE SWITCH - ESW B 1005 123 LOW PSL-11-002C PRESSURE SWITCH - ESW C 1000 122 LOW PSL-11-002D PRESSURE SWITCH - ESW D 1005 123 LOW PSL-12-001A PRESSURE SWITCH - RHRSW A 1000 122 LOW PSL-12-001B PRESSURE SWITCH - RHRSW B 1005 123 LOW PSL-12-001C PRESSURE SWITCH - RHRSW A 1000 122 LOW PSL-12-001D PRESSURE SWITCH - RHRSW B 1005 123 LOW PSL-12-102A PRESSURE SWITCH - RHRSW A 202 075 LOW PSL-12-102B PRESSURE SWITCH - RHRSW B 202 075 LOW PSL-12-202A PRESSURE SWITCH - RHRSW A 202 075 LOW PSL-12-202B PRESSURE SWITCH - RHRSW B 202 075 LOW PSL-42-101 PRESSURE SWITCH - RHR/ B 402E 045E LOW HILOW PSL-42-201 PRESSURE SWITCH - RHR/ B 475E 068E LOW HILOW PSL-50-101 PRESSURE SWITCH - RCIC A 108 033 LOW PSL-50-201 PRESSURE SWITCH - RCIC A 179 056 LOW PSL-51-1N654A PRESSURE SWITCH - RHR A 542 025 LOW PSL-51-1N654B PRESSURE SWITCH - RHR B 542 025 LOW PSL-51-1N654C PRESSURE SWITCH - RHR C 542 025 LOW APPENDIX 9A 9A-430 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PSL-51-1N654D PRESSURE SWITCH - RHR D 542 025 LOW PSL-51-2N653D PRESSURE SWITCH - RHR D 542 025 LOW PSL-51-2N654A PRESSURE SWITCH - RHR A 542 025 LOW PSL-51-2N654B PRESSURE SWITCH - RHR B 542 025 LOW PSL-51-2N654C PRESSURE SWITCH - RHR C 542 025 LOW PSL-51-2N654D PRESSURE SWITCH - RHR D 542 025 LOW PSV-41-1F013A MAIN STEAM RELIEF MSRV A 400 030 1-MSRV VALVE "A" PSV-41-1F013C MAIN STEAM RELIEF MSRV A 400 030 1-MSRV VALVE "C" PSV-41-1F013E MAIN STEAM RELIEF ADS A,C 400 030 1-ADS VALVE "E" (ADS)
PSV-41-1F013H MAIN STEAM RELIEF ADS A,C 400 030 1-ADS VALVE "H" (ADS)
PSV-41-1F013K MAIN STEAM RELIEF ADS A,C 400 030 1-ADS VALVE "K" (ADS)
PSV-41-1F013M MAIN STEAM RELIEF ADS A,C 400 030 1-ADS VALVE "M" (ADS)
PSV-41-1F013N MAIN STEAM RELIEF MSRV A 400 030 1-MSRV VALVE "N" PSV-41-1F013S MAIN STEAM RELIEF ADS A,C 400 030 1-ADS VALVE "S" (ADS)
PSV-41-2F013A MAIN STEAM RELIEF MSRV A 473 053 2-MSRV VALVE "A" PSV-41-2F013C MAIN STEAM RELIEF MSRV A 473 053 2-MSRV VALVE "C" PSV-41-2F013E MAIN STEAM RELIEF ADS A,C 473 053 2-ADS VALVE "E" (ADS)
PSV-41-2F013H MAIN STEAM RELIEF ADS A,C 473 053 2-ADS VALVE "H" (ADS)
PSV-41-2F013K MAIN STEAM RELIEF ADS A,C 473 053 2-ADS VALVE "K" (ADS)
PSV-41-2F013M MAIN STEAM RELIEF ADS A,C 473 053 2-ADS VALVE "M" (ADS)
PSV-41-2F013N MAIN STEAM RELIEF MSRV A 473 053 2-MSRV VALVE "N" PSV-41-2F013S MAIN STEAM RELIEF ADS A,C 473 053 2-ADS VALVE "S" (ADS)
APPENDIX 9A 9A-431 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PT-11-003A ESW PUMP A ESW A 1011 122 DISCHARGE HEADER PT-11-003B ESW PUMP B ESW B 1016 123 DISCHARGE HEADER PT-12-001A RHRSW LOOP A RHRSW A 1011 122 HEADER PRESSURE PT-12-001B RHRSW LOOP B RHRSW B 1016 123 HEADER PRESSURE PT-42-103A PRESSURE RVI A 402W 045W TRANSMITTER PT-42-103B PRESSURE RVI B 402E 045E TRANSMITTER PT-42-1N006 PRESSURE RVI A 402W 045W TRANSMITTER PT-42-1N090A PRESSURE CS A 402W 045W TRANSMITTER PT-42-1N090B PRESSURE CS B 402E 045E TRANSMITTER PT-42-1N090C PRESSURE CS C 402E 045E TRANSMITTER 402W 045W PT-42-1N090D PRESSURE CS D 402E 045E TRANSMITTER 402W 045W PT-42-1N090E PRESSURE CS A 402W 045W TRANSMITTER PT-42-1N090F PRESSURE CS B 402E 045E TRANSMITTER PT-42-1N090G PRESSURE CS C 402E 045E TRANSMITTER 402W 045W PT-42-1N090H PRESSURE CS D 402E 045E TRANSMITTER 402W 045W PT-42-1N094A PRESSURE CS A 402W 045W TRANSMITTER PT-42-1N094B PRESSURE CS B 402E 045E TRANSMITTER PT-42-1N094C PRESSURE CS C 402E 045E TRANSMITTER 402W 045W PT-42-1N094D PRESSURE CS D 402E 045E TRANSMITTER 402W 045W PT-42-1N094E PRESSURE CS A 402W 045W TRANSMITTER PT-42-1N094F PRESSURE CS B 402E 045E TRANSMITTER PT-42-1N094G PRESSURE CS C 402E 045E TRANSMITTER 402W 045W APPENDIX 9A 9A-432 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PT-42-1N094H PRESSURE CS D 402E 045E TRANSMITTER 402W 045W PT-42-203A PRESSURE RVI A 475W 068W TRANSMITTER PT-42-203B PRESSURE RVI B 475E 068E TRANSMITTER PT-42-2N006 PRESSURE RVI A 475W 068W TRANSMITTER PT-42-2N090A PRESSURE CS A 475W 068W TRANSMITTER PT-42-2N090B PRESSURE CS B 475E 068E TRANSMITTER PT-42-2N090C PRESSURE CS C 475E 068E TRANSMITTER 475W 068W PT-42-2N090D PRESSURE CS D 475E 068E TRANSMITTER 475W 068W PT-42-2N090E PRESSURE CS A 475W 068W TRANSMITTER PT-42-2N090F PRESSURE CS B 475E 068E TRANSMITTER PT-42-2N090G PRESSURE CS C 475E 068E TRANSMITTER 475W 068W PT-42-2N090H PRESSURE CS D 475E 068E TRANSMITTER 475W 068W PT-42-2N094A PRESSURE CS A 475W 068W TRANSMITTER PT-42-2N094B PRESSURE CS B 475E 068E TRANSMITTER PT-42-2N094C PRESSURE CS C 475E 068E TRANSMITTER 475W 068W PT-42-2N094D PRESSURE CS D 475E 068E TRANSMITTER 475W 068W PT-42-2N094E PRESSURE CS A 475W 068W TRANSMITTER PT-42-2N094F PRESSURE CS B 475E 068E TRANSMITTER PT-42-2N094G PRESSURE CS C 475E 068E TRANSMITTER 475W 068W PT-42-2N094H PRESSURE CS D 475E 068E TRANSMITTER 475W 068W PT-49-1N050 PRESSURE RCIC A 200 042 TRANSMITTER PT-49-1N058A PRESSURE RCIC A 304E 044E TRANSMITTER APPENDIX 9A 9A-433 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PT-49-1N058C PRESSURE RCIC C 304E 044E TRANSMITTER PT-49-1N058E PRESSURE RCIC A 304E 044E TRANSMITTER PT-49-1N058G PRESSURE RCIC C 304E 044E TRANSMITTER PT-49-2N050 PRESSURE RCIC A 279 065 TRANSMITTER PT-49-2N058A PRESSURE RCIC A 370E 067E TRANSMITTER PT-49-2N058C PRESSURE RCIC C 370E 067E TRANSMITTER PT-49-2N058E PRESSURE RCIC A 370E 067E TRANSMITTER PT-49-2N058G PRESSURE RCIC C 370E 067E TRANSMITTER PT-50-1N052 PRESSURE RCIC A 108 033 TRANSMITTER PT-50-1N053 PRESSURE RCIC A 108 033 TRANSMITTER PT-50-1N055A PRESSURE RCIC A 200 042 TRANSMITTER PT-50-1N055C PRESSURE RCIC C 108 033 TRANSMITTER PT-50-1N055E PRESSURE RCIC A 200 042 TRANSMITTER PT-50-1N055G PRESSURE RCIC C 108 033 TRANSMITTER PT-50-1N056A PRESSURE RCIC A 200 042 TRANSMITTER PT-50-1N056E PRESSURE RCIC A 200 042 TRANSMITTER PT-50-2N052 PRESSURE RCIC A 179 056 TRANSMITTER PT-50-2N053 PRESSURE RCIC A 179 056 TRANSMITTER PT-50-2N055A PRESSURE RCIC A 279 065 TRANSMITTER PT-50-2N055C PRESSURE RCIC C 179 056 TRANSMITTER PT-50-2N055E PRESSURE RCIC A 279 065 TRANSMITTER PT-50-2N055G PRESSURE RCIC C 179 056 TRANSMITTER APPENDIX 9A 9A-434 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PT-50-2N056A PRESSURE RCIC A 279 065 TRANSMITTER PT-50-2N056E PRESSURE RCIC A 279 065 TRANSMITTER PT-51-1N053A PRESSURE RHR A 200 042 TRANSMITTER PT-51-1N053B PRESSURE RHR B 118 039 TRANSMITTER PT-51-1N053C PRESSURE RHR C 200 042 TRANSMITTER PT-51-1N053D PRESSURE RHR D 118 039 TRANSMITTER PT-51-1N055A PRESSURE ADS A 200 042 TRANSMITTER PT-51-1N055C PRESSURE ADS C 118 039 TRANSMITTER PT-51-1N055E PRESSURE ADS A 200 042 TRANSMITTER PT-51-1N055G PRESSURE ADS C 118 039 TRANSMITTER PT-51-1N056A PRESSURE ADS A 200 042 TRANSMITTER PT-51-1N056C PRESSURE ADS C 118 039 TRANSMITTER PT-51-1N056E PRESSURE ADS A 200 042 TRANSMITTER PT-51-1N056G PRESSURE ADS C 118 039 TRANSMITTER PT-51-1N057 PRESSURE RHR B 304E 044E TRANSMITTER PT-51-2N053A PRESSURE RHR A 189 062 TRANSMITTER PT-51-2N053B PRESSURE RHR B 279 065 TRANSMITTER PT-51-2N053C PRESSURE RHR C 189 062 TRANSMITTER PT-51-2N053D PRESSURE RHR D 279 065 TRANSMITTER PT-51-2N055A PRESSURE ADS A 189 062 TRANSMITTER PT-51-2N055C PRESSURE ADS C 279 065 TRANSMITTER PT-51-2N055E PRESSURE ADS A 189 062 TRANSMITTER APPENDIX 9A 9A-435 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PT-51-2N055G PRESSURE ADS C 279 065 TRANSMITTER PT-51-2N056A PRESSURE ADS A 189 062 TRANSMITTER PT-51-2N056C PRESSURE ADS C 279 065 TRANSMITTER PT-51-2N056E PRESSURE ADS A 189 062 TRANSMITTER PT-51-2N056G PRESSURE ADS C 279 065 TRANSMITTER PT-51-2N057 PRESSURE RHR B 370W 067W TRANSMITTER PT-52-1N055A PRESSURE ADS A 110 035 TRANSMITTER PT-52-1N055C PRESSURE ADS C 117 038 TRANSMITTER PT-52-1N055E PRESSURE ADS A 113 036 TRANSMITTER PT-52-1N055G PRESSURE ADS C 114 037 TRANSMITTER PT-52-2N055A PRESSURE ADS A 188 061 TRANSMITTER PT-52-2N055C PRESSURE ADS C 181 058 TRANSMITTER PT-52-2N055E PRESSURE ADS A 185 060 TRANSMITTER PT-52-2N055G PRESSURE ADS C 184 059 TRANSMITTER PT-55-1N050 PRESSURE HPCI B 109 034 TRANSMITTER PT-55-1N058B PRESSURE HPCI B 304W 044W TRANSMITTER PT-55-1N058D PRESSURE HPCI D 304W 044W TRANSMITTER PT-55-1N058F PRESSURE HPCI B 304W 044W TRANSMITTER PT-55-1N058H PRESSURE HPCI D 304W 044W TRANSMITTER PT-55-2N050 PRESSURE HPCI B 180 057 TRANSMITTER PT-55-2N058B PRESSURE HPCI B 370W 067W TRANSMITTER PT-55-2N058D PRESSURE HPCI D 370W 067W TRANSMITTER APPENDIX 9A 9A-436 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
PT-55-2N058F PRESSURE HPCI B 370W 067W TRANSMITTER PT-55-2N058H PRESSURE HPCI D 370W 067W TRANSMITTER PT-56-1N052 PRESSURE HPCI B 109 034 TRANSMITTER PT-56-1N053 PRESSURE HPCI B 109 034 TRANSMITTER PT-56-1N055B PRESSURE HPCI B 109 034 TRANSMITTER PT-56-1N055D PRESSURE HPCI D 200 042 TRANSMITTER PT-56-1N055F PRESSURE HPCI B 109 034 TRANSMITTER PT-56-1N055H PRESSURE HPCI D 200 042 TRANSMITTER PT-56-1N056B PRESSURE HPCI B 109 034 TRANSMITTER PT-56-1N056F PRESSURE HPCI B 109 034 TRANSMITTER PT-56-2N052 PRESSURE HPCI B 180 057 TRANSMITTER PT-56-2N053 PRESSURE HPCI B 180 057 TRANSMITTER PT-56-2N055B PRESSURE HPCI B 180 057 TRANSMITTER PT-56-2N055D PRESSURE HPCI D 279 065 TRANSMITTER PT-56-2N055F PRESSURE HPCI B 180 057 TRANSMITTER PT-56-2N055H PRESSURE HPCI D 279 065 TRANSMITTER PT-56-2N056B PRESSURE HPCI B 180 057 TRANSMITTER PT-56-2N056F PRESSURE HPCI B 180 057 TRANSMITTER SI-50-101 SPEED INDICATOR RCIC A 533 024 SI-50-1R003 SPEED INDICATOR RCIC A 540 026 SI-50-201 SPEED INDICATOR RCIC A 533 024 SI-50-2R003 SPEED INDICATOR RCIC A 540 026 SI-56-161 SPEED INDICATOR HPCI B 533 024 SI-56-261 SPEED INDICATOR HPCI B 533 024 APPENDIX 9A 9A-437 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
SV-52-139 CTMT ISO VALVE FOR SPI A 118 039 LEVEL SENSING LINES SV-52-239 CTMT ISO VALVE FOR SPI A 189 062 LEVEL SENSING LINES SV-57-101 CTMT ISO VALVE FOR SPI A 207 041 LEVEL SENSING LINES SV-57-183 CTMT ISO VALVE FOR SPI A 309W 043W LEVEL SENSING LINES SV-57-201 CTMT ISO VALVE FOR SPI A 284 064 LEVEL SENSING LINES SV-59-150A COMPRESSED GAS PCIG C 304W 044W 1-RHRASC-A SUPPLY SELECT 1-RHRASC-B VALVE 1-RHRASC-C 1-RHRASC-D SV-59-150B COMPRESSED GAS PCIG D 304E 044E 1-RHRASC-B SUPPLY SELECT 1-RHRASC-A VALVE 1-RHRASC-D 1-RHRASC-C SV-59-152A COMPRESSED GAS PCIG C 304W 044W 1-RHRASC-A SUPPLY SELECT 1-RHRASC-B VALVE 1-RHRASC-C 1-RHRASC-D 1-MSRV SV-59-152B COMPRESSED GAS PCIG D 304E 044E 1-RHRASC-B SUPPLY SELECT 1-RHRASC-C VALVE 1-RHRASC-A 1-RHRASC-D SV-59-250A COMPRESSED GAS PCIG C 370E 067E 2-RHRASC-A SUPPLY SELECT 2-RHRASC-B VALVE 2-RHRASC-C 2-RHRASC-D SV-59-250B COMPRESSED GAS PCIG D 370E 067E 2-RHRASC-B SUPPLY SELECT 2-RHRASC-A VALVE 2-RHRASC-D 2-RHRASC-C SV-59-252A COMPRESSED GAS PCIG C 370E 067E 2-RHRASC-A SUPPLY SELECT 2-RHRASC-B VALVE 2-RHRASC-C 2-RHRASC-D 2-MSRV APPENDIX 9A 9A-438 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
SV-59-252B COMPRESSED GAS PCIG D 370E 067E 2-RHRASC-B SUPPLY SELECT VALVE 2-RHRASC-C 2-RHRASC-A 2-RHRASC-D TD-81-102A CELL "A" AIR DGEV A 311A 079 EXHAUST DAMPER TD-81-102B CELL "B" AIR DGEV B 311B 081 EXHAUST DAMPER TD-81-102C CELL "C" AIR DGEV C 311C 080 EXHAUST DAMPER TD-81-102D CELL "D" AIR DGEV D 311D 082 EXHAUST DAMPER TD-81-102E CELL "A" AIR DGEV A 311A 079 EXHAUST DAMPER TD-81-102F CELL "B" AIR DGEV B 311B 081 EXHAUST DAMPER TD-81-102G CELL "C" AIR DGEV C 311C 080 EXHAUST DAMPER TD-81-102H CELL "D" AIR DGEV D 311D 082 EXHAUST DAMPER TD-81-202A CELL "A" AIR DGEV A 315A 083 EXHAUST DAMPER TD-81-202B CELL "B" AIR DGEV B 315B 085 EXHAUST DAMPER TD-81-202C CELL "C" AIR DGEV C 315C 084 EXHAUST DAMPER TD-81-202D CELL "D" AIR DGEV D 315D 086 EXHAUST DAMPER TD-81-202E CELL "A" AIR DGEV A 315A 083 EXHAUST DAMPER TD-81-202F CELL "B" AIR DGEV B 315B 085 EXHAUST DAMPER TD-81-202G CELL "C" AIR DGEV C 315C 084 EXHAUST DAMPER TD-81-202H CELL "D" AIR DGEV D 315D 086 EXHAUST DAMPER TE-41-101A TEMPERATURE ELEMENT SPI A 101 029 TE-41-101B TEMPERATURE ELEMENT SPI A 101 029 TE-41-101C TEMPERATURE ELEMENT SPI A 101 029 TE-41-101D TEMPERATURE ELEMENT SPI A 101 029 TE-41-101E TEMPERATURE ELEMENT SPI A 101 029 TE-41-101F TEMPERATURE ELEMENT SPI A 101 029 APPENDIX 9A 9A-439 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TE-41-101G TEMPERATURE ELEMENT SPI A 101 029 TE-41-101H TEMPERATURE ELEMENT SPI A 101 029 TE-41-103A TEMPERATURE ELEMENT SPI B 101 029 TE-41-103B TEMPERATURE ELEMENT SPI B 101 029 TE-41-103C TEMPERATURE ELEMENT SPI B 101 029 TE-41-103D TEMPERATURE ELEMENT SPI B 101 029 TE-41-103E TEMPERATURE ELEMENT SPI B 101 029 TE-41-103F TEMPERATURE ELEMENT SPI B 101 029 TE-41-103G TEMPERATURE ELEMENT SPI B 101 029 TE-41-103H TEMPERATURE ELEMENT SPI B 101 029 TE-41-201A TEMPERATURE ELEMENT SPI A 172 052 TE-41-201B TEMPERATURE ELEMENT SPI A 172 052 TE-41-201C TEMPERATURE ELEMENT SPI A 172 052 TE-41-201D TEMPERATURE ELEMENT SPI A 172 052 TE-41-201E TEMPERATURE ELEMENT SPI A 172 052 TE-41-201F TEMPERATURE ELEMENT SPI A 172 052 TE-41-201G TEMPERATURE ELEMENT SPI A 172 052 TE-41-201H TEMPERATURE ELEMENT SPI A 172 052 TE-41-203A TEMPERATURE ELEMENT SPI B 172 052 TE-41-203B TEMPERATURE ELEMENT SPI B 172 052 TE-41-203C TEMPERATURE ELEMENT SPI B 172 052 TE-41-203D TEMPERATURE ELEMENT SPI B 172 052 TE-41-203E TEMPERATURE ELEMENT SPI B 172 052 TE-41-203F TEMPERATURE ELEMENT SPI B 172 052 TE-41-203G TEMPERATURE ELEMENT SPI B 172 052 TE-41-203H TEMPERATURE ELEMENT SPI B 172 052 TE-76-121A TEMPERATURE ELEMENT REV A 108 033 TE-76-121B TEMPERATURE ELEMENT REV A 108 033 TE-76-122A TEMPERATURE ELEMENT REV B 109 034 TE-76-122B TEMPERATURE ELEMENT REV B 109 034 TE-76-123A TEMPERATURE ELEMENT REV A 102 032 TE-76-123B TEMPERATURE ELEMENT REV B 103 031 TE-76-123C TEMPERATURE ELEMENT REV C 102 032 TE-76-123D TEMPERATURE ELEMENT REV D 103 031 TE-76-123E TEMPERATURE ELEMENT REV A 102 032 TE-76-123F TEMPERATURE ELEMENT REV B 103 031 TE-76-123G TEMPERATURE ELEMENT REV C 102 032 APPENDIX 9A 9A-440 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TE-76-123H TEMPERATURE ELEMENT REV D 103 031 TE-76-221A TEMPERATURE ELEMENT REV A 179 056 TE-76-221B TEMPERATURE ELEMENT REV A 179 056 TE-76-222A TEMPERATURE ELEMENT REV B 180 057 TE-76-222B TEMPERATURE ELEMENT REV B 180 057 TE-76-223A TEMPERATURE ELEMENT REV A 173 054 TE-76-223B TEMPERATURE ELEMENT REV B 174 055 TE-76-223C TEMPERATURE ELEMENT REV C 173 054 TE-76-223D TEMPERATURE ELEMENT REV D 174 055 TE-76-223E TEMPERATURE ELEMENT REV A 173 054 TE-76-223F TEMPERATURE ELEMENT REV B 174 055 TE-76-223G TEMPERATURE ELEMENT REV C 173 054 TE-76-223H TEMPERATURE ELEMENT REV D 174 055 TE-81-040A TEMPERATURE ELEMENT SPPV A 1000 122 TE-81-040B TEMPERATURE ELEMENT SPPV B 1005 123 TE-81-040C TEMPERATURE ELEMENT SPPV C 1000 122 TE-81-040D TEMPERATURE ELEMENT SPPV D 1005 123 TE-81-041A TEMPERATURE ELEMENT SPPV A 1000 122 TE-81-041B TEMPERATURE ELEMENT SPPV B 1005 123 TE-81-041C TEMPERATURE ELEMENT SPPV C 1000 122 TE-81-041D TEMPERATURE ELEMENT SPPV D 1005 123 TE-81-101A TEMPERATURE ELEMENT DGEV A 311A 079 TE-81-101B TEMPERATURE ELEMENT DGEV B 311B 081 TE-81-101C TEMPERATURE ELEMENT DGEV C 311C 080 TE-81-101D TEMPERATURE ELEMENT DGEV D 311D 082 TE-81-101E TEMPERATURE ELEMENT DGEV A 311A 079 TE-81-101F TEMPERATURE ELEMENT DGEV B 311B 081 TE-81-101G TEMPERATURE ELEMENT DGEV C 311C 080 TE-81-101H TEMPERATURE ELEMENT DGEV D 311D 082 TE-81-201A TEMPERATURE ELEMENT DGEV A 315A 083 TE-81-201B TEMPERATURE ELEMENT DGEV B 315B 085 TE-81-201C TEMPERATURE ELEMENT DGEV C 315C 084 TE-81-201D TEMPERATURE ELEMENT DGEV D 315D 086 TE-81-201E TEMPERATURE ELEMENT DGEV A 315A 083 TE-81-201F TEMPERATURE ELEMENT DGEV B 315B 085 TE-81-201G TEMPERATURE ELEMENT DGEV C 315C 084 TE-81-201H TEMPERATURE ELEMENT DGEV D 315D 086 APPENDIX 9A 9A-441 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TI-41-101 SUPPRESSION POOL SPI A 533 024 1-SPI TEMPERATURE INDICATOR TI-41-102 SUPPRESSION POOL SPI A 540 026 1-SPI TEMPERATURE INDICATOR TI-41-103 SUPPRESSION POOL SPI B 533 024 1-SPI TEMPERATURE INDICATOR TI-41-201 SUPPRESSION POOL SPI A 533 024 2-SPI TEMPERATURE INDICATOR TI-41-202 SUPPRESSION POOL SPI A 540 026 2-SPI TEMPERATURE INDICATOR TI-41-203 SUPPRESSION POOL SPI B 533 024 2-SPI TEMPERATURE INDICATOR TI-50-140B TEMPERATURE RCIC A 108 033 INDICATOR TI-50-240B TEMPERATURE RCIC A 179 056 INDICATOR TISH-20-121A TEMPERATURE SDG A 312A 079 INDICATING SWITCH TISH-20-121B TEMPERATURE SDG B 312B 081 INDICATING SWITCH TISH-20-121C TEMPERATURE SDG C 312C 080 INDICATING SWITCH TISH-20-121D TEMPERATURE SDG D 312D 082 INDICATING SWITCH TISH-20-221A TEMPERATURE SDG A 316A 083 INDICATING SWITCH TISH-20-221B TEMPERATURE SDG B 316B 085 INDICATING SWITCH TISH-20-221C TEMPERATURE SDG C 316C 084 INDICATING SWITCH TISH-20-221D TEMPERATURE SDG D 316D 086 INDICATING SWITCH TISL-81-040A TEMPERATURE SPPV A 1000 122 INDICATING SWITCH TISL-81-040B TEMPERATURE SPPV B 1005 123 INDICATING SWITCH TISL-81-040C TEMPERATURE SPPV C 1000 122 INDICATING SWITCH APPENDIX 9A 9A-442 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TISL-81-040D TEMPERATURE SPPV D 1005 123 INDICATING SWITCH TIT-76-121A RCIC COMPARTMENT REV A 200 042 TEMPERATURE INDICATING TRANSMITTER TIT-76-121B RCIC COMPARTMENT REV A 200 042 TEMPERATURE INDICATING TRANSMITTER TIT-76-122A HPCI COMPARTMENT REV B 207 041 TEMPERATURE INDICATING TRANSMITTER TIT-76-122B HPCI COMPARTMENT REV B 207 041 TEMPERATURE INDICATING TRANSMITTER TIT-76-123A RHR COMPARTMENT REV A 200 042 TEMPERATURE INDICATING TRANSMITTER TIT-76-123B RHR COMPARTMENT REV B 207 041 TEMPERATURE INDICATING TRANSMITTER TIT-76-123C RHR COMPARTMENT REV C 200 042 TEMPERATURE INDICATING TRANSMITTER TIT-76-123D RHR COMPARTMENT REV D 207 041 TEMPERATURE INDICATING TRANSMITTER TIT-76-123E RHR COMPARTMENT REV A 200 042 TEMPERATURE INDICATING TRANSMITTER TIT-76-123F RHR COMPARTMENT REV B 207 041 TEMPERATURE INDICATING TRANSMITTER TIT-76-123G RHR COMPARTMENT REV C 200 042 TEMPERATURE INDICATING TRANSMITTER APPENDIX 9A 9A-443 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TIT-76-123H RHR COMPARTMENT REV D 207 041 TEMPERATURE INDICATING TRANSMITTER TIT-76-221A RCIC COMPARTMENT REV A 284 064 TEMPERATURE INDICATING TRANSMITTER TIT-76-221B RCIC COMPARTMENT REV A 284 064 TEMPERATURE INDICATING TRANSMITTER TIT-76-222A HPCI COMPARTMENT REV B 279 065 TEMPERATURE INDICATING TRANSMITTER TIT-76-222B HPCI COMPARTMENT REV B 279 065 TEMPERATURE INDICATING TRANSMITTER TIT-76-223A RHR COMPARTMENT REV A 284 064 TEMPERATURE INDICATING TRANSMITTER TIT-76-223B RHR COMPARTMENT REV B 279 065 TEMPERATURE INDICATING TRANSMITTER TIT-76-223C RHR COMPARTMENT REV C 284 064 TEMPERATURE INDICATING TRANSMITTER TIT-76-223D RHR COMPARTMENT REV D 279 065 TEMPERATURE INDICATING TRANSMITTER TIT-76-223E RHR COMPARTMENT REV A 284 064 TEMPERATURE INDICATING TRANSMITTER TIT-76-223F RHR COMPARTMENT REV B 279 065 TEMPERATURE INDICATING TRANSMITTER APPENDIX 9A 9A-444 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TIT-76-223G RHR COMPARTMENT REV C 284 064 TEMPERATURE INDICATING TRANSMITTER TIT-76-223H RHR COMPARTMENT REV D 279 065 TEMPERATURE INDICATING TRANSMITTER TRS-41-101 DIV. I SUPPRESSION SPI A 533 024 POOL TEMPERATURE MONITORING SYSTEM TRS-41-103 DIV. II SUPPRESSION SPI B 533 024 POOL TEMPERATURE MONITORING SYSTEM TRS-41-201 DIV. I SUPPRESSION SPI A 533 024 POOL TEMPERATURE MONITORING SYSTEM TRS-41-203 DIV. II SUPPRESSION SPI B 533 024 POOL TEMPERATURE MONITORING SYSTEM TSH-HH76-121A TEMPERATURE SWITCH REV A 200 042 TSH-HH76-121B TEMPERATURE SWITCH REV B 200 042 TSH-HH76-122A TEMPERATURE SWITCH REV A 207 041 TSH-HH76-122B TEMPERATURE SWITCH REV B 207 041 TSH-HH76-123A TEMPERATURE SWITCH REV A 200 042 TSH-HH76-123B TEMPERATURE SWITCH REV B 207 041 TSH-HH76-123C TEMPERATURE SWITCH REV C 200 042 TSH-HH76-123D TEMPERATURE SWITCH REV D 207 041 TSH-HH76-123E TEMPERATURE SWITCH REV A 200 042 TSH-HH76-123F TEMPERATURE SWITCH REV B 207 041 TSH-HH76-123G TEMPERATURE SWITCH REV C 200 042 TSH-HH76-123H TEMPERATURE SWITCH REV D 207 041 TSH-HH76-221A TEMPERATURE SWITCH REV A 284 064 TSH-HH76-221B TEMPERATURE SWITCH REV B 284 064 TSH-HH76-222A TEMPERATURE SWITCH REV A 279 065 TSH-HH76-222B TEMPERATURE SWITCH REV B 279 065 TSH-HH76-223A TEMPERATURE SWITCH REV A 284 064 TSH-HH76-223B TEMPERATURE SWITCH REV B 279 065 TSH-HH76-223C TEMPERATURE SWITCH REV C 284 064 TSH-HH76-223D TEMPERATURE SWITCH REV D 279 065 TSH-HH76-223E TEMPERATURE SWITCH REV A 284 064 TSH-HH76-223F TEMPERATURE SWITCH REV B 279 065 TSH-HH76-223G TEMPERATURE SWITCH REV C 284 064 TSH-HH76-223H TEMPERATURE SWITCH REV D 279 065 APPENDIX 9A 9A-445 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TSH-HH81-101A TEMPERATURE SWITCH DGEV A 311A 079 TSH-HH81-101B TEMPERATURE SWITCH DGEV B 311B 081 TSH-HH81-101C TEMPERATURE SWITCH DGEV C 311C 080 TSH-HH81-101D TEMPERATURE SWITCH DGEV D 311D 082 TSH-HH81-101E TEMPERATURE SWITCH DGEV A 311A 079 TSH-HH81-101F TEMPERATURE SWITCH DGEV B 311B 081 TSH-HH81-101G TEMPERATURE SWITCH DGEV C 311C 080 TSH-HH81-101H TEMPERATURE SWITCH DGEV D 311D 082 TSH-HH81-201A TEMPERATURE SWITCH DGEV A 315A 083 TSH-HH81-201B TEMPERATURE SWITCH DGEV B 315B 085 TSH-HH81-201C TEMPERATURE SWITCH DGEV C 315C 084 TSH-HH81-201D TEMPERATURE SWITCH DGEV D 315D 086 TSH-HH81-201E TEMPERATURE SWITCH DGEV A 315A 083 TSH-HH81-201F TEMPERATURE SWITCH DGEV B 315B 085 TSH-HH81-201G TEMPERATURE SWITCH DGEV C 315C 084 TSH-HH81-201H TEMPERATURE SWITCH DGEV D 315D 086 TSHL-76-121A TEMPERATURE SWITCH REV A 200 042 TSHL-76-121B TEMPERATURE SWITCH REV B 200 042 TSHL-76-122A TEMPERATURE SWITCH REV A 207 041 TSHL-76-122B TEMPERATURE SWITCH REV B 207 041 TSHL-76-123A TEMPERATURE SWITCH REV A 200 042 TSHL-76-123B TEMPERATURE SWITCH REV B 207 041 TSHL-76-123C TEMPERATURE SWITCH REV C 200 042 TSHL-76-123D TEMPERATURE SWITCH REV D 207 041 TSHL-76-123E TEMPERATURE SWITCH REV A 200 042 TSHL-76-123F TEMPERATURE SWITCH REV B 207 041 TSHL-76-123G TEMPERATURE SWITCH REV C 200 042 TSHL-76-123H TEMPERATURE SWITCH REV D 207 041 TSHL-76-221A TEMPERATURE SWITCH REV A 284 064 TSHL-76-221B TEMPERATURE SWITCH REV B 284 064 TSHL-76-222A TEMPERATURE SWITCH REV A 279 065 TSHL-76-222B TEMPERATURE SWITCH REV B 279 065 TSHL-76-223A TEMPERATURE SWITCH REV A 284 064 TSHL-76-223B TEMPERATURE SWITCH REV B 279 065 TSHL-76-223C TEMPERATURE SWITCH REV C 284 064 TSHL-76-223D TEMPERATURE SWITCH REV D 279 065 TSHL-76-223E TEMPERATURE SWITCH REV A 284 064 TSHL-76-223F TEMPERATURE SWITCH REV B 279 065 APPENDIX 9A 9A-446 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TSHL-76-223G TEMPERATURE SWITCH REV C 284 064 TSHL-76-223H TEMPERATURE SWITCH REV D 279 065 TSHL-81-341A TEMPERATURE SWITCH SPPV A 1000 122 TSHL-81-341B TEMPERATURE SWITCH SPPV B 1005 123 TSHL-81-341C TEMPERATURE SWITCH SPPV C 1000 122 TSHL-81-341D TEMPERATURE SWITCH SPPV D 1005 123 TTICSL-81-041A SYSTEM "A" FAN SPPV A 1000 122 CABINET TEMPERATURE INDICATING CONTROLLER TTICSL-81-041B SYSTEM "B" FAN SPPV B 1005 123 CABINET TEMPERATURE INDICATING CONTROLLER TTICSL-81-041C SYSTEM "C" FAN SPPV C 1000 122 CABINET TEMPERATURE INDICATING CONTROLLER TTICSL-81-041D SYSTEM "D" FAN SPPV D 1005 123 CABINET TEMPERATURE INDICATING CONTROLLER TTICSHL-81-101A CELL "A" EXHAUST DGEV A 311A 079 FAN CONTROLLER TTICSHL-81-101B CELL "B" EXHAUST DGEV B 311B 081 FAN CONTROLLER TTICSHL-81-101C CELL "C" EXHAUST DGEV C 311C 080 FAN CONTROLLER TTICSHL-81-101D CELL "D" EXHAUST DGEV D 311D 082 FAN CONTROLLER TTICSHL-81-101E CELL "A" EXHAUST DGEV A 311A 079 FAN CONTROLLER TTICSHL-81-101F CELL "B" EXHAUST DGEV B 311B 081 FAN CONTROLLER TTICSHL-81-101G CELL "C" EXHAUST DGEV C 311C 080 FAN CONTROLLER TTICSHL-81-101H CELL "D" EXHAUST DGEV D 311D 082 FAN CONTROLLER TTICSHL-81-201A CELL "A" EXHAUST DGEV A 315A 083 FAN CONTROLLER TTICSHL-81-201B CELL "B" EXHAUST DGEV B 315B 085 FAN CONTROLLER APPENDIX 9A 9A-447 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
TTICSHL-81-201C CELL "C" EXHAUST DGEV C 315C 084 FAN CONTROLLER TTICSHL-81-201D CELL "D" EXHAUST DGEV D 315D 086 FAN CONTROLLER TTICSHL-81-201E CELL "A" EXHAUST DGEV A 315A 083 FAN CONTROLLER TTICSHL-81-201F CELL "B" EXHAUST DGEV B 315B 085 FAN CONTROLLER TTICSHL-81-201G CELL "C" EXHAUST DGEV C 315C 084 FAN CONTROLLER TTICSHL-81-201H CELL "D" EXHAUST DGEV D 315D 086 FAN CONTROLLER TY-41-102 TEMPERATURE SPI A 540 026 CONVERTER TY-41-202 TEMPERATURE SPI A 540 026 CONVERTER TY-81-101A TEMPERATURE SIGNAL DGEV A 311A 079 SELECTOR TY-81-101B TEMPERATURE SIGNAL DGEV B 311B 081 SELECTOR TY-81-101C TEMPERATURE SIGNAL DGEV C 311C 080 SELECTOR TY-81-101D TEMPERATURE SIGNAL DGEV D 311D 082 SELECTOR TY-81-201A TEMPERATURE SIGNAL DGEV A 315A 083 SELECTOR TY-81-201B TEMPERATURE SIGNAL DGEV B 315B 085 SELECTOR TY-81-201C TEMPERATURE SIGNAL DGEV C 315C 084 SELECTOR TY-81-201D TEMPERATURE SIGNAL DGEV D 315D 086 SELECTOR XR-42-1R623A REACTOR VESSEL RVI A 533 024 1-RVI PRESSURE AND WATER LEVEL RECORDER XR-42-1R623B REACTOR VESSEL RVI B 533 024 1-RVI PRESSURE AND WATER LEVEL RECORDER XR-42-2R623A REACTOR VESSEL RVI A 533 024 2-RVI PRESSURE AND WATER LEVEL RECORDER XR-42-2R623B REACTOR VESSEL RVI B 533 024 2-RVI PRESSURE AND WATER LEVEL RECORDER APPENDIX 9A 9A-448 REV. 17, SEPTEMBER 2014
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Plant Sfgd. Fire FSSD Sys.
Component Description Sys. Chan. Room Area Design.
ZC-81-102A POSITION CONTROLLER DGEV A 311A 079 ZC-81-102B POSITION CONTROLLER DGEV B 311B 081 ZC-81-102C POSITION CONTROLLER DGEV C 311C 080 ZC-81-102D POSITION CONTROLLER DGEV D 311D 082 ZC-81-102E POSITION CONTROLLER DGEV A 311A 079 ZC-81-102F POSITION CONTROLLER DGEV B 311B 081 ZC-81-102G POSITION CONTROLLER DGEV C 311C 080 ZC-81-102H POSITION CONTROLLER DGEV D 311D 082 ZC-81-202A POSITION CONTROLLER DGEV A 315A 083 ZC-81-202B POSITION CONTROLLER DGEV B 315B 085 ZC-81-202C POSITION CONTROLLER DGEV C 315C 084 ZC-81-202D POSITION CONTROLLER DGEV D 315D 086 ZC-81-202E POSITION CONTROLLER DGEV A 315A 083 ZC-81-202F POSITION CONTROLLER DGEV B 315B 085 ZC-81-202G POSITION CONTROLLER DGEV C 315C 084 ZC-81-202H POSITION CONTROLLER DGEV D 315D 086 APPENDIX 9A 9A-449 REV. 17, SEPTEMBER 2014
LGS UFSAR LEGEND FOR TABLE 9A-4 (Contd)
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN The information presented in each column of Table 9A-4 is explained as follows.
Component Major Safe Shutdown Components NOTE: Components identified with an asterix (*) designate associations of equipment and cables that perform common functions. These designations are used for analysis purposes only, and do not represent plant identification.
Description Brief description of the component Plant Sys. General FSSD system designation for the component, based on the function the component provides KEY:
ADS Automatic Depressurization System APS 13kV Power Supply to the 4kV Safeguard Busses CS Core Spray DGEV Diesel Generator Enclosure Ventilation EPS Class 1E Power Distribution System ESW Emergency Service Water System HI/LOW Selected Reactor Coolant Pressure Boundaries and High Low Pressure Interfaces HPCI High Pressure Coolant Injection System MSRV Main Steam Relief Valves PCIG Primary Containment Instrument Gas System RCIC Reactor Core Isolation Cooling System REV Reactor Enclosure Ventilation RHR Residual Heat Removal System RHRSW Residual Heat Removal Service Water System RVI Reactor Vessel Instrumentation SDG Standby Diesel Generators and Auxiliaries SPI Suppression Pool Instrumentation SPPV Spray Pond Pump Structure Ventilation APPENDIX 9A 9A-450 REV. 17, SEPTEMBER 2014
LGS UFSAR LEGEND FOR TABLE 9A-4 (Contd)
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN Sfgd. Chan. Safeguard Channel designation for electrical components NOTE: Components identified with a letter in parenthesis are not designated as safeguard, but are energized from the Safeguard Channel indicated.
Room Room location for the component Components located in rooms which are subdivided by Combustible Free Zones have an East or West suffix provided to more precisely identify their location.
Fire Area Fire Area location for the component Components located in Fire Areas which are subdivided by Combustible Free Zones have an East or West suffix provided to more precisely identify their location.
FSSD Sys. Fire Safe Shutdown System/Train Designation Desig. Populated for components which directly support a Safe Shutdown Function.
KEY:
A-BBBBB-C A Unit (0, 1, 2)
BBBBB System Function Designation (see table below)
C Loop/Train (provided for multi-train systems)
APPENDIX 9A 9A-451 REV. 17, SEPTEMBER 2014
LGS UFSAR LEGEND FOR TABLE 9A-4 (Contd)
MAJOR COMPONENTS ANALYZED FOR FIRE SAFE SHUTDOWN System Function Designations:
ESW Emergency Service Water ADS Automatic Depressurization System HI/LOW Selected Reactor Coolant Pressure Boundaries and High Low Pressure Interfaces HPCI High Pressure Coolant Injection System HPCITRIP HPCI shutdown capability MSRV Main Steam Relief Valves RCIC Reactor Core Isolation Cooling System RCICTRIP RCIC shutdown capability RHRASC RHR Alternate Shutdown Cooling Mode RHRLPCI RHR Low Pressure Coolant Injection Mode RHRSC RHR Shutdown Cooling Mode RHRSPC RHR Suppression Pool Cooling Mode RHRSW RHR Service Water RVI Reactor Vessel Instrumentation -
Direct-reading indication of Reactor parameters SPI Suppression Pool Instrumentation -
Direct-reading indication of Suppression Pool parameters APPENDIX 9A 9A-452 REV. 17, SEPTEMBER 2014
LGS UFSAR Tables 9A-5 through 9A-11 Tables 9A-5 through 9A-11 (Deleted)
APPENDIX 9A 9A-453 REV. 13, SEPTEMBER 2006
LGS UFSAR Table 9A-12 RCPB VALVES SUSCEPTIBLE TO FIRE INDUCED SPURIOUS OPERATION P&ID INTERFACE (1,2)
NUMBER VALVES REMARKS M-41 (U) HV-41-1F001 Located in piping from the RPV head vent line to the (D) HV-41-1F002 drywell equipment drain tank. If both valves open due to fire damage, the steam released into the drain tank would (U) HV-41-2F001 be vented into the drywell via the 4 inch vent line. No (D) HV-41-2F002 equipment needed for safe shutdown would be damaged.
M-41 (S) PSV-41-1F013A Located in a branch line connected to the main steam piping inside primary containment. Typical for suffix "B",
(S) PSV-41-2F013A "C", "D", "E", "F", "G", "H", "J", "K", "L", "M", "N", and "S" valves. If this valve opens, steam will be discharged from the reactor vessel to the suppression pool. Released reactor coolant will be retained inside the primary containment, and no equipment needed for safe shutdown will be damaged.
M-41 (U) HV-41-1F016 Located in the main steam drain line. If both of these valves (D) HV-41-1F019 open due to fire damage, various leakage paths downstream of the valves could allow reactor coolant to be (U) HV-41-2F016 discharged to the main condenser or the main steam (D) HV-41-2F019 tunnel. For all of the potential flow paths, this condition is acceptable because (a) the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods, (b) the mass inventory expected to be released is less than that expected for a main steam line break outside primary containment, and (c) the release of reactor coolant will not cause damage to any equipment needed for safe shutdown M-41 (U) HV-41-1F022A Located in the main steam lines between the reactor vessel (D) HV-41-1F028A and the turbine-generator. Typical for suffix "B", "C", and "D" valves. If both of these valves open simultaneously due (U) HV-41-2F022A to fire damage, the main steam piping outside primary (D) HV-41-2F028A containment would be pressurized. Although the main steam piping leading to the main turbine is designed as high pressure piping, there are a number of potential leakage paths associated with branch lines from the main steam lines. Because of the high reliability of the MSIVs and because of the fail-safe features of their design, these valves are assumed to retain their capability to close and remain closed during a postulated fire.
APPENDIX 9A 9A-454 REV. 15, SEPTEMBER 2010
P&ID INTERFACE (1,2)
NUMBER VALVES REMARKS M-41 (U) HV-41-1F084 Located in the sample line from main steam line C to sample (D) HV-41-1F085 station 10S292 (20S292). If both valves open due to fire damage, a closed manual valve at the sample station would prevent steam blowdown.
M-41 (U) HV-41-109A Located in the feedwater recirculation line between the main (U) HV-41-109B feedwater headers and the main condenser. Spurious opening (D) HV-41-110 of either of the upstream valves together with the downstream valve as a result of fire-caused damage would allow water from (U) HV-41-209A the RWCU return line to be discharged to the main condenser (U) HV-41-209B via the feedwater headers. Plant procedures require that the (D) HV-41-210 circuit breakers for the upstream valves be locked open at motor control centers 10B213 (20B213) and 10B214 (20B214),
with the valves in the fully closed position, after warmup of the feedwater lines has been completed. By de-energizing the breakers, fires which effect the control circuits to the valves are prevented from causing the valves to spuriously open. This action prevents the interface from opening in fire areas where RCIC is relied upon for safe shutdown. For other postulated fires, this condition is acceptable because (a) the reactor vessel inventory can be maintained by the available coolant makeup pumps, (b) the mass inventory expected to be released is less than expected for a main steam line break outside containment, and (c) the release of reactor coolant will not cause damage to any equipment needed for safe shutdown.
M-43 (U) HV-43-1F019 Located in the sample line from recirculation loop B to sample (D) HV-43-1F020 station 10S292 (20S292). This spurious operation or loss of capability to close these valves due to fire damage, will allow the (U) HV-43-2F019 sample line to blowdown to clean radwaste system (CRWS). The (D) HV-43-2F020 leakage is acceptable because the inventory loss is within the RCIC pump make-up capability, the blowdown is limited by the 1/4 inch sample line and the release of reactor coolant will not cause damage to any equipment needed for safe shutdown.
APPENDIX 9A 9A-455 REV. 15, SEPTEMBER 2010
P&ID INTERFACE (1,2)
NUMBER VALVES REMARKS M-44 (U) HV-44-1F031 Located in the blowdown line from the RWCU system. If only (U) HV-C44-1F033 valve HV-C44-1(2)F033 opens spuriously together with either (D) HV-44-1F034 HV-44-1(2)F034 or HV-44-1(2)F035 valve water from the RWCU (D) HV-44-1F035 system would be discharged to either the main condenser or the equipment drain collection tank. No equipment needed for safe (U) HV-44-2F031 shutdown would be damaged by the discharge of reactor coolant (U) HV-C44-2F033 and the reactor vessel inventory can be maintained by the (D) HV-44-2F034 coolant makeup pumps that are available for each of the (D) HV-44-2F035 shutdown methods. To ensure that HV-44-1(2)F031 does not open and the blowdown flow rate is limited to an acceptable value, the power circuit for valve HV- 44-1F031 (2F031) will be isolated (with the valve in the fully closed position) when reactor pressure exceeds 75 psig.
M-44 (S) SV-45-101A Located in the RWCU filter/demineralizer sample line. Typical for the suffix "B" valve. The loss of capability to close these valves (S) SV-45-201A due to fire damage, will allow the sample line to blowdown to clean radwaste system (CRWS). The leakage is acceptable because the inventory loss is within the RICI pump make-up capability, the blowdaown is limited by the 1/4 inch sample line and the release of reactor coolant will not cause damage to any equipment needed for safe shutdown.
M-47 (U) XV-47-1F010 Located in the vent line from the scram discharge volume to an (D) XV-47-1F180 open floor drain. The SDV would be at high pressure only (U) XV-47-2F010 during the period following a scram and prior to reset of the (D) XV-47-2F180 scram signal. The discharge of water from the SDV into a floor drain during this period would not cause damage to any equipment needed for safe shutdown, and the flow rate would be low enough so that reactor vessel inventory could be maintained by the coolant makeup pumps that are available for each shutdown method.
M-47 (U) XV-47-1F011 Located in the drain line from the scram discharge volume to the (D) XV-47-1F181 equipment drain collection tank (via 8" HBC-133/233). The SDV (U) XV-47-2F011 would be at high pressure only during the period following a (D) XV-47-2F181 scram and prior to reset of the scram signal. The discharge of water from the SDV to the equipment drain collection tank during this period would not cause damage to any equipment needed for safe shutdown, and the flow rate would be low enough so that reactor vessel inventory could be maintained by the coolant makeup pumps that are available for each shutdown method.
APPENDIX 9A 9A-456 REV. 15, SEPTEMBER 2010
P&ID INTERFACE (1,2)
NUMBER VALVES REMARKS M-49 (S) LV-49-1F054 Located in the drain line from the drain pot in the RCIC steam supply line. If this valve opens due to fire damage, main steam (S) LV-49-2F054 would be discharged to the main condenser. This condition is acceptable because (a) the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods, (b) the mass inventory expected to be released is less than that expected for a main steam line break outside primary containment, and (c) the release of reactor coolant will not cause damage to any equipment needed for safe shutdown.
M-50 (S) LV-50-110 Located in the drain line from the drain pot in the RCIC turbine exhaust line. If this valve opens due to fire damage, at a time (S) LV-50-210 when RCIC steam supply line shutoff valve HV-50-1F045 (2F045) is open, main steam could bleed into the RCIC barometric condenser. This condition is acceptable because (a) the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods, (b) the mass inventory expected to be released is less than that expected for a main steam line break outside primary containment, and (c) the release of reactor coolant will not cause damage to any equipment needed for safe shutdown.
M-51 (U) HV-51-1F009 Located in the RHR shutdown cooling suction line. If both valves (D) HV-51-1F008 open due to fire damage, the RHR pump suction lines could be damaged. In order to prevent both the upstream and downstream (U) HV-51-2F009 valves from opening simultaneously, an additional interlock by (D) HV-51-2F008 means of a pressure switch, is added to monitor the reactor vessel pressure for the downstream valve. Whenever the reactor vessel pressure exceeds the design capabilities of the RHR low pressure piping the contacts of the pressure switch will open, thereby isolating the opening relay of the downstream valves and preventing the valve to open.
APPENDIX 9A 9A-457 REV. 15, SEPTEMBER 2010
P&ID INTERFACE (1,2)
NUMBER VALVES REMARKS M-51 (U) HV-51-151A Located in the RHR loop A shutdown cooling return line.
(U) HV-51-1F050A HV-51-1F050A (2F050A) is a check valve that will close to (D) HV-51-1F015A prevent reverse flow if HV-51-1F015A (2F015A) fails in the (U) 51-1200A open position. The pneumatic operator on HV-51-1F050A (U) HV-51-251A (2F050A) is for testing purposes only and cannot unseat the (U) HV-51-2F050A valve disk or hold it open when a differential pressure exists (D) HV-51-2F015A across the valve. However, if bypass valve HV-51-151A (U) 51-2200A (251A) and the outboard containment isolation valve both open due to fire damage, the flow through the bypass line will pressurize the shutdown cooling return piping outside the drywell. The flow through the bypass line will be limited by 1/4" flow restricting orifice F0-51-151A (251A) to a value that is less than the capacity of downstream relief valve PSV-51-1F025A (2F025A). The discharged reactor coolant will not overpressurize or overheat the low pressure piping and will not cause damage to any equipment required for safe shutdown.
In addition, the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods. (Typical for the loop B shutdown cooling return line.)
Outboard isolation valve HV-051-1F015A (2F015A) has an additional piping path from the reactor coolant pressure boundary to penetration X-13A. This small-bore piping path connects the equalizing line of valve HV-51-1F050A (2F050A) to the bonnet vent line of the recirculation pump suction block valve HV-043-1F023A (2F023A). Spring-assisted, check valve 51-1200A (2200A) in this flow path will acts as an inboard isolation valve to penetration X-13A from the recirculation system. Check valve 51-1200A (2200A) performs the same PCIVs/PIVs functions in penetration X-13A as valves HV-051-1F050A (2F050A) and HV-051-151A (251A). (Typical for the loop B shutdown cooling return line.)
M-51 (U) HV-51-142A Located in the loop A LPCI injection line. HV-51-1F041A (U) HV-51-1F041A (2F041A) is a check valve that will close to prevent reverse flow if (D) HV-51-1F017A HV-51-1F017A (2F017A) fails in the open position. The pneumatic operator on HV-51-1F041A (2F041A) is for testing (U) HV-51-242A purposes only and cannot unseat the valve disk or hold it open (U) HV-51-2F041A when a differential pressure exists across the valve. However, if (D) HV-51-2F017A bypass valve HV-51-142A (242A) and the outboard containment isolation valve both open due to fire damage, the flow through the bypass line will pressurize the LPCI injection piping outside the drywell. The flow through the bypass line will be limited by 1/4" flow restricting orifice F0 142A(242A) to a value that is less than the capacity of downstream relief valve PSV-51-1F025A (2F025A). The discharged reactor coolant will not overpressurize or overheat the low pressure piping and will not cause damage to any equipment required for safe shutdown.
In addition, the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods. (Typical for LPCI injection lines B, C, and D.)
APPENDIX 9A 9A-458 REV. 15, SEPTEMBER 2010
P&ID INTERFACE (1,2)
NUMBER VALVES REMARKS M-52 (U) HV-52-1F039A Located in the loop A core spray injection line. HV-52-1F006A (U) HV-52-1F006A (2F006A) is a check valve that will close to prevent reverse flow if (D) HV-52-1F005 HV-52-1F005 (2F005) fails in the open position. The pneumatic operator on HV-52-1F006A (2F006A) is for testing purposes only (U) HV-52-2F039A and cannot unseat the valve disk or hold it open when a (U) HV-52-2F006A differential pressure exists across the valve. However, if bypass (D) HV-52-2F005 valve HV-52-1F039A (2F039A) and the outboard containment isolation valve both open due to fire damage, the flow through the bypass line will pressurize the core spray injection piping outside the drywell. The flow through the bypass line will be limited by 1/4" flow restricting orifice F0-52-106A (206A) to a value that is less than the capacity of downstream relief valve PSV 1F012A (2F012A). The discharged reactor coolant will not overpressurize or overheat the low pressure piping and will not cause damage to any equipment required for safe shutdown. In addition, the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods.
M-52 (U) HV-52-1F039B Located in the loop B core spray injection line. The pneumatic (U) HV-52-1F006B operator on check valve HV-52-1F006B (2F006B) is for testing (D) HV-52-108 purposes only and cannot unseat the valve disk or hold it open when a differential pressure exists across the valve. If bypass (U) HV-52-2F039B valve HV-52-1F039B (2F039B) opens due to fire damage, (U) HV-52-2F006B reverse flow cannot occur because outboard containment (D) HV-52-208 isolation valve HV-52-108 (208) is a check valve.
M-55 (S) HV-55-1F054 Located in the drain line of the HPCI steam supply line drain (S) HV-55-1F054 pot. If this valve opens due to fire damage, main steam could be discharged to the main condenser. This condition is acceptable because (a) the reactor vessel inventory can be maintained by the coolant makeup pumps that are available for each of the shutdown methods, (b) the mass inventory expected to be released is less than expected for a main steam line break outside primary containment, and (c) the release of reactor coolant will not cause damage to any equipment needed for safe shutdown.
(1) Upstream valves are identified by the (U) designation. Downstream valves are identified by the (D) designation. Single valves are identified by the (S) designation. For the purposes of this study, upstream valves are defined as those valves that are closest to the RCPB.
(2) For each entry in this table, two groups of interface valves are listed. The first group consists of valves in Unit 1 and the second group consists of the corresponding valves in Unit 2.
APPENDIX 9A 9A-459 REV. 15, SEPTEMBER 2010
LGS UFSAR Table 9A-13 has been DELETED.
APPENDIX 9A 9A-460 REV. 13, SEPTEMBER 2006
LGS UFSAR Table 9A-14 Operations That May Be Required To Be Performed Outside The Control Room Equipment ID Action Description 10-A116 Operate Local Control Switches 10-A118 Trip B Control Room Chiller For MHIF 10-C601-X1 Position Valves Using Emergency Control Switches - HV-51-125B, 1F004B, 1F015B, 1F027B, HV-C-51-1F048B 10-C601-X2 Position Valve Using Emergency Control Switch - HV-51-1F017B 10TB-49-1F007 Operate Power Transfer Switch - HV-49-1F007 1A-C514 Start Diesel 1AG501 Generator Using Local Controls 1B-C514 Start Diesel 1BG501 Generator Using Local Controls 20-A116 Operate Local Control Switches 20-C601-X1 Position Valves Using Emergency Control Switches - HV-51-2F015B, 2F027B, HV-C-51-2F048B 20-C601-X2 Position Valve Using Emergency Control Switch - HV-51-2F017B 20TB-49-2F007 Operate Power Transfer Switch - HV-49-2F007 2A-C514 Start Diesel 2AG501 Generator Using Local Controls 2B-C514 Start Diesel 2BG501 Generator Using Local Controls APPENDIX 9A 9A-461 REV. 17, SEPTEMBER 2014
Operations That May Be Required To Be Performed Outside The Control Room Equipment ID Action Description ADS Control at 289 Operate ADS Valves At The PGCC HS-51-282B Open Valve Using Local Controls - HV 282B HS-56-162 Operate Switch At 10C201 To Runback HPCI Turbine HS-56-262 Operate Switch At 20C201 To Runback HPCI Turbine HV-11-011B Close Manually To Prevent Long Term ESW Flow Diversion HV-11-015A Close Manually To Prevent Long Term ESW Flow Diversion HV-11-015B Open Manually HV-11-132A Open Manually HV-11-232A Open Manually APPENDIX 9A 9A-462 REV. 17, SEPTEMBER 2014
Operations That May Be Required To Be Performed Outside The Control Room Equipment ID Action Description HV-12-031B Close Manually HV-12-031C Open Manually HV-12-032B Open Manually HV-12-032C Open Manually HV-12-032D Open / Close Manually HV-49-1F084 Open Manually HV-49-2F084 Open Manually HV-51-1F003B Open Manually HV-51-1F006B Close Manually HV-51-1F008 Open Manually HV-51-1F010A Close Manually HV-51-1F014B Open Manually HV-51-1F015A Close Manually HV-51-1F017B Close Manually HV-51-1F024B Open Manually HV-51-1F047B Open Manually HV-51-1F049 Close Manually APPENDIX 9A 9A-463 REV. 17, SEPTEMBER 2014
Operations That May Be Required To Be Performed Outside The Control Room Equipment ID Action Description HV-51-1F068A Open Manually HV-51-1F068B Open Manually HV-51-2F006B Close Manually HV-51-2F008 Open Manually HV-51-2F010A Close Manually HV-51-2F015A Close Manually HV-51-2F024B Open Manually HV-51-2F049 Close Manually HV-51-2F068A Open Manually HV-51-2F068B Open Manually HV-51-2F073 Close Manually HV-55-126 Open Manually HV-C-51-1F048A Close Manually HV-C-51-2F048B Close Manually Remote Shutdown Operate Equipment, Monitor Instruments Panel (289)
APPENDIX 9A 9A-464 REV. 17, SEPTEMBER 2014