ONS-2016-061, Submittal of Updated Final Safety Analysis Report, Revision 25
ML16197A293 | |
Person / Time | |
---|---|
Site: | Oconee ![]() |
Issue date: | 06/30/2016 |
From: | Batson S Duke Energy Carolinas |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
Shared Package | |
ML16197A231 | List: |
References | |
ONS-2016-061 | |
Download: ML16197A293 (80) | |
Text
Scott L. Batson Vice President Oconee Nuclear Station Duke Energy ON01VP I 7800 Rochester Hwy Seneca, SC 29672 ONS-2016-061 o: 864.873.3274
- f. 864.873.4208 Scott.Batson@duke-energy.com June 30, 2016 Attn: Document Control Desk 10 CFR 50.71(e)
U.S. Nuclear Regulatory Commission 10 CFR 50.59(d) 11555 Rockville Pike 10 CFR 54.37(b)
Rockville, MD 20852-2746
Subject:
Duke Energy Carolinas, LLC Oconee Nuclear Station, Units 1, 2, and 3 Docket Nos. 50-269, 50-270, 50-287 Updated Final Safety Analysis Report, Revision 25 Pursuant to 10 CFR 50.71(e), and in accordance with 10 CFR 50.4, Duke Energy Carolinas, LLC (Duke Energy) hereby submits the Oconee Nuclear Station Updated Final Safety Analysis Report (UFSAR), Revision 25. The effective date of the UFSAR revision is December 31, 2015, as indicated at the bottom of each pag~. Changes made in Revision 25 are indicated by side bars.
The Oconee UFSAR, Revision 25, is being provided in a non-redacted version (for Nuclear Regulatory Commission internal use) and a redacted version (for NRC public use). The two compact disks (CDs) enclosed are labelled accordingly. Duke Energy has marked the appropriate information in the redacted version as "Security-Related Information Withheld Under 10 CFR 2.390" using the criteria provided by the NRC in SECY-04-191. The contents are in Adobe Acrobat Portable Document Format (pdf).
As required by NRC guidance for electronic submissions, Attachment 1 provides a listing of the document Components that comprise the enclosed CD. Attachment 2 provides the List of Effective Pages (LOEP)for Tables and Figures. Attachment 3 provides insertion instructions for those receiving hardcopy distribution. Attachment 4 provides a listing of items removed in the 2015 UFSAR update. Attachment 5 provides the report of changes, tests, and experiments performed pursuant to 10 CFR 50.59( d).
In addition, 10 CFR 54.37(b) requires that after the renewed license is issued, the UFSAR update must include any systems, structures and components (SSCs) newly identified that would have been subject to an aging management review or evaluation of time-limited aging analysis in accordance with 10 CFR 54.21. The UFSAR update must describe how the effects of aging are managed such that the intended function(s) in 10 CFR 54.4{b) will be effectively maintained during the period of extended operation. A review was completed to determine whether any newly-identified SSCs existed in support of submitting UFSAR Revision 25. As a result of this review, there were no newly-identified SSCs for which aging management reviews or time-limited aging analyses would apply.
www.duke-energy.com
ONS-2016-061 Document Control Desk June 30, 2016 Page 2 This submittal document contains no new or revised regulatory commitments. If you have any questions regarding this submittal, please contact Kay Brocklesby at (864) 873-6661.
I dedare under penalty of perjury that the foregoing is true and correct. Executed on June 30, 2016*.
Sincerely,
~-5!~
Scott L. Batson Vice President Oconee Nuclear Station Attachments:
- 1.
- Document Components on CD
- 2. List of Effective Pages (LOEP) for Table*s and Figures
- 3. Update Insertion Instructions (for hardcopy distribution only)
- 4. List Of Removed Items
- 5. 10 CFR 50.59 Summary Report
Enclosures:
- 1. CD containing Non-Redacted Version of Oconee Nuclear Station Updated Final Safety Analysis Report, 2015 Update - Rev 25
- 2. CD containing. Redacted Version of Oconee Nuclear Station Updated Final Safety
- Analysis Report, 2015 Update ~ Rev 25
ONS-2016-061 Document Control Desk June 30, 2016 Page 3 cc (with attachments):
Ms. Catherine Haney, NRC Region II Administrator (CD)
U.S. Nuclear Regulatory Commission Marquis One Tower
- 245 Peachtree Center Ave., NE, Suite 1200 Atlanta, GA 30303-1257 Mr. James R. Hall, Project Manager (CD)
U.S. Nuclear Regulatory Commission 11555 Rockville Pike Mail Stop 0-8G9A Rockville, MD 20852 Mr. Eddy Crowe (hardcopy)
Senior Resident Inspector Oconee Nuclear Station
ONS-2016-061 Document Control Desk June 30, 2016 Attachment 1 Document Components on CD (2 pages attached)
ONS-2016-061 Document Control Desk June 30, 2016 Filename File Size 000 ONS UFSAR Rev 25 Title Page 99 KB 001 ONS UFSAR Rev 25 Ch 1 Text 334KB 002 ONS UFSAR Rev 25 Ch 1 Tables* 161 KB 003 ONS UFSAR Rev 25 Ch 1 Figures 4,270 KB 004 ONS UFSAR Rev 25 Ch 2 Text 959 KB 005 ONS UFSAR Rev 25 Ch 2 Tables 4,243 KB 006 ONS UFSAR Rev 25 Ch 2 Figures 7,069 KB 007 ONS UFSAR Rev 25 Ch 3 Text 2,184 KB 008 ONS UFSAR Rev 25 Ch 3Tables 1,654 KB 009 ONS UFSAR Rev 25 Ch 3 Figures 5,875 KB 010 ONS UFSAR Rev 25 Ch 4 Text 904KB 011 ONS UFSAR Rev 25 Ch 4 Tables 1,173 KB 012 ONS UFSAR Rev 25 Ch 4 Figures 1,247 KB 013 ONS UFSAR Rev 25 Ch 5 Text 955KB 014 ONS UFSAR Rev 25 Ch 5 Tables 1,652 KB 015 ONS UFSAR Rev 25 Ch 5 Figures 4,283 KB 016 ONS UFSAR Rev 25 Ch 6 Text 929 KB 017 ONS UFSAR Rev 25 Ch 6. Tables 1,911 KB 018 ONS UFSAR Rev 25 Ch 6 Figures 4,953 KB 019 ONS UFSAR Rev 25 Ch 7 Text 1,514 KB 020 ONS UFSAR Rev 25 Ch 7 Tables 363 KB 021 ONS UFSAR Rev 25 Ch 7 Figures 8,483 KB 022 ONS UFSAR Rev 25 Ch 8 Text 559 KB 023 ONS UFSAR Rev 25 Ch 8 Tables 433 KB 024 ONS UFSAR Rev 25 Ch 8 Figures 1,574 KB 025 ONS UFSAR Rev 25 Ch 9 Text 1,437 KB 026 ONS UFSAR Rev 25 Ch 9 Tables 1,075 KB 027 ONS UFSAR Rev 25 Ch 9 Figures 13,256 KB Attachment 1 - Page 1 of 2
ONS-2016-061 Document Control Desk June 30, 2016 Filename File Size 028 ONS UFSAR Rev 25 Ch 10 Text 593 KB 029 ONS UFSAR Rev 25 Ch 10 Tables 143 KB 030 ONS UFSAR Rev 25 Ch 10 Figures 8,056 KB 031 ONS UFSAR Rev 25 Ch 11 Text 852 KB 032 ONS UFSAR Rev 25 Ch 11 Tables 469 KB 033 ONS UFSAR Rev 25 Ch 11 Figures 276 KB 034 ONS U FSAR Rev 25 Ch 12 Text 422 KB 035 ONS UFSAR Rev 25 Ch 12 Tables 211 KB 036 ONS UFSAR Rev 25 Ch 13 Text 681 KB 037 ONS UFSAR Rev 25 Ch 13 Tables 77 KB 038 ONS UFSAR Rev 25 Ch 13 Figures 362 KB 039 ONS UFSAR Rev 25 Ch 14 Text 429 KB 040 ONS UFSAR Rev 25 Ch 14 Tables 133 KB 041 ONS UFSAR Rev 25 Ch 15 Text 1,818 KB 042 ONS UFSAR Rev 25 Ch 15 Tables 2,161 KB 043 ONS UFSAR Rev 25 Ch 15 Figures 5,587 KB 044 ONS UFSAR Rev 25 Ch 16 Text 100 KB 045 ONS UFSAR Rev 25 Ch 17 Text 104 KB 046 ONS UFSAR Rev 25 Ch 18 Text 773 KB 047 ONS UFSAR Rev 25 Ch 18 Tables 106 KB Attachment 1 - Page 2 of 2
ONS-2016-061 Document Control Desk June 30, 2016 Attachment 2 List of Effective Pages (LOEP) for Tables and Figures (60 pages attached)
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Chapter 1 1-1 31DEC2015 1-2 31 DEC 2015 1-3 31 DEC 2015 1.0-1 31 DEC 2015 1.0-2 31 DEC2015 1.1-1 31 DEC2015 1.1-2 31 DEC 2015 1.2-1 31 DEC 2015 1.2-2 31 DEC 2015 1.2-3 31 DEC2015 1.2-4 31DEC2015 1.3-1 31 DEC 2015 1.3-2 31 DEC 2015 1.4-1 31 DEC2015 1.4-2 31 DEC2015 Chapter 1 Tables Table 1-1 (Page 1 of 1) 31 DEC 2000 Table 1-2 (Page 1of1) 31 DEC 2000 Table 1-3 (Page 1of1) 31 DEC 2000 Chapter 1 Figures Figure 1-1 (Page 1 of 1) 31 DEC 2000 Figure 1-2 (Page 1 of 1) 31 DEC 2000 Figure 1-3 (Page 1 of 1) 31 DEC 2000 Figure 1-4 (Page 1 of 1) 31 DEC 2000 Figure 1-5 (Page 1 of 1) 31 DEC 2004 Figure 1-6 (Page 1 of 1) 31 DEC 2000 Figure 1-7 (Page 1 of 1) 31 DEC 2007 Figure 1-8 (Page 1 of 1) 31 DEC 2000 Figure 1-9 (Page 1 of 1) 31 DEC 2000 Chapter 2 2-1 31 DEC 2015 2-2 31 DEC 2015 2-3 31 DEC2015 Attachment 2 - Page 1 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 2-4 31DEC2015 2-5 31 DEC 2015 2-6 31 DEC 2015 2-7 31 DEC 2015 2-8 31DEC2015 2-9 31DEC2015 2-10 31 DEC 2015 2-11 31 DEC 2015 2-12 31DEC2015 2.0-1 31DEC2015 2.0-2 31 DEC 2015 2.1-1 31 DEC 2015 2.1-2 31 DEC 2015 /
2.1-3 31DEC2015 2.1-4 31 DEC 2015 2.2-1 31 DEC 2015 2.2-2 31 DEC 2015 2.3-1 31DEC2015 2.3-2 31DEC2015 2.3-3 31DEC2015 2.3-4 31 DEC 2015 2.3-5 31 DEC 2015 2.3-6 31 DEC 2015 2.3-7 31 DEC 2015 2.3-8 31 DEC 2015 2.3-9 31DEC2015 2.3-10 31 DEC 2015 2.3-11 31 DEC 2015 2.3-12 31 DEC 2015 2.3-13 31 DEC 2015 2.3-14 31 DEC 2015 2.3-15 31 DEC 2015 2.3-16 31DEC2015 2.3-17 31 DEC 2015 2.3-18 31DEC2015 2.3-19 31DEC2015 2.3-20 31 DEC 2015 2.3-21 31 DEC 2015 Attachment 2 - Page 2 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 2.3-22 31 DEC 2015 2.4-1 31 DEC 2015 2.4-2 31 DEC 2015 2.4-3 31 DEC 2015 Yes 2.4-4 31 DEC 2015 Yes 2.4-5 31 DEC 2015 Yes 2.4-6 31 DEC 2015 Yes 2.4-7 31 DEC 2015 Yes 2.4-8 31 DEC 2015 Yes 2.4-9 31 DEC 2015 Yes 2.4-10 31 DEC 2015 Yes 2.5-1 31 DEC 2015 2.5-2 31 DEC 2015 2.5-3 31 DEC 2015 2.5-4 31 DEC 2015 2.5-5 31 DEC 2015 2.5-6 31 DEC 2015 2.5-7 31 DEC 2015 2.5-8 31 DEC 2015 2.5-9 31 DEC 2015 2.5-10 31 DEC 2015 2.5-11 31 DEC 2015 2.5-12 31 DEC 2015 2.5-13 31 DEC 2015 2.5-14 31 DEC 2015 2.5-15 31 DEC 2015 2.5-16 31 DEC 2015 Chapter 2 Tables Table 2-1(Page1of1) 31 DEC 2000 Table 2-2 (Page 1 of 1) 31 DEC 2000 Table 2-3 (Page 1 of 1) 31 DEC 2000 Table 2-4 (Page 1 of 1) 31 DEC 2000 Table 2-5 (Page 1 of 1) 31 DEC 2000 Table 2-6 (Page 1 of 1) 31 DEC 2000 Table 2-7 (Page 1 of 1) 31 DEC 2008 Table 2-8 (Page 1 of 1) 31 DEC 2008 Table 2-9 (Page 1 of 1) 31 DEC 2008 Attachment 2 - Page 3 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 2-10 (Page 1 of 1) 31 DEC 2008 Table 2-11 (Page 1 of 1) 31 DEC 2008 Table 2-12 (Page 1 of 1) 31 DEC 2008 Table 2-13 (Page 1 of 1) 31 DEC 2008 Table 2-14 (Page 1 of 1) 31 DEC 2008 Table 2-15 (Page 1 of 1) 31 DEC 2008 Table 2-16 (Page 1 of 1) 31 DEC 2008 Table 2-17 (Page 1 of 1) 31 DEC 2008 Table 2-18 (Page 1 of 1) 31 DEC 2008 Table 2-19 (Page 1 of 1) 31 DEC 2008 Table 2-20 (Page 1 of 1) 31 DEC 2008 Table 2-21 (Page 1 of 1) 31 DEC 2008 Table 2-22 (Page 1 of 1) 31 DEC 2008 Table 2-23 (Page 1 of 1) 31 DEC 2008 Table 2-24 (Page 1 of 8) 31 DEC 2008 Table 2-24 (Page 2 of 8) 31 DEC 2008 Table 2-24 (Page 3 of 8) 31 DEC 2008 Table 2-24 (Page 4 of 8) 31 DEC 2008 Table 2-24 (Page 5 of 8) 31 DEC 2008 Table 2-24 (Page 6 of 8) 31 DEC 2008 Table 2-24 (Page 7 of 8) 31 DEC 2008 Table 2-24 (Page 8 of 8) 31 DEC 2008 Table 2-25 (Page 1 of 8) 31 DEC 2008 Table 2-25 (Page 2 of 8) 31 DEC 2008 Table 2-25 (Page 3 of 8) 31 DEC 2008 Table 2-25 (Page 4 of 8) 31 DEC 2008 Table 2-25 (Page 5 of 8) 31 DEC 2008 Table 2-25 (Page 6 of 8) 31 DEC 2008 Table 2-25 (Page 7 of 8) 31 DEC 2008 Table 2-25 (Page 8 of 8) 31 DEC 2008 Table 2-26 (Page 1 of 6) 31 DEC 2008 Table 2-26 (Page 2 of 6) 31 DEC 2008 Table 2-26 (Page 3 of 6) 31 DEC 2008 Table 2-26 (Page 4 of 6) 31 DEC 2008 Table 2-26 (Page 5 of 6) 31 DEC 2008 Table 2-26 (Page 6 of 6) 31 DEC 2008 Table 2-27 (Page 1 of 14) 31 DEC 2008 Table 2-27 (Page 2 of 14) 31DEC2008 Attachment 2 - Page 4 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 2-27 (Page 3 of 14) 31 DEC 2008 Table 2-27 (Page 4 of 14) 31 DEC 2008 Table 2-27 (Page 5of14) 31 DEC 2008 Table 2-27 (Page 6of14) 31 DEC 2008 Table 2-27 (Page 7 of 14) 31 DEC 2008 Table 2-27 (Page 8 of 14) 31 DEC 2008 Table 2-27 (Page 9 of 14) 31 DEC 2008 Table 2-27 (Page 10of14) 31 DEC 2008 Table 2-27 (Page 11 of 14) 31 DEC 2008 Table 2-27 (Page 12of14) 31 DEC 2008 Table 2-27 (Page 13 of 14) 31 DEC 2008 Table 2-27 (Page 14of14) 31 DEC 2008 Table 2-28 (Page 1 of 1) 31 DEC 2008 Table 2-29 (Page 1 of 1) 31 DEC 2008 Table 2-30 (Page 1 of 2) 31 DEC 2008 Table 2-30 (Page 2 of 2) 31 DEC 2008 Table 2-31 (Page 1 of 2) 31 DEC 2008 Table 2-31 (Page 2 of 2) 31 DEC 2008 Table 2-32 (Page 1 of 2) 31 DEC 2008 Table 2-33 (Page 1 of 2) 31 DEC 2008 Table 2-33 (Page 2 of 2) 31 DEC 2008 Table 2-34 (Page 1 of 1) 31 DEC 2008 Table 2-35 (Page 1 of 1) 31 DEC 2008 Table 2-36 (Page 1 of 1) 31 DEC 2008 Table 2-37 (Page 1 of 2) 31 DEC 2008 Table 2-27 (Page 2 of 2) 31 DEC 2008 Table 2-38 (Page 1 of 1) 31 DEC 2008 Table 2-39 (Page 1 of 4) 31 DEC 2008 Table 2-39 (Page 2 of 4) 31DEC2008 Table 2-39 (Page 3 of 4) 31 DEC 2008 Table 2-39 (Page 4 of 4) 31 DEC 2008 Table 2'"40 43 (Page 1 of 1) 31 DEC 2008 Table 2-44 (Page 1 of 1) 31 DEC 2008 Table 2 2-92 (Page 1 of 3) 31 DEC 2008 Table 2 2-92. (Page 2 of 3) 31 DEC 2008 Table 2 2-92 (Page 3 of 3) 31 DEC 2008 Table 2-93 (Page 1 of 1) 31 DEC 2000 Table 2-94 (Page 1 of 6) 31 DEC 2000 Attachment 2 - Page 5 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 2-94 (Page 2 of 6) 31DEC2000 Table 2-94 (Page 3 of 6) 31DEC2000 Table 2-94 (Page 4 of 6) 31DEC2000 Table 2-94 (Page 5 of 6) 31 DEC 2000 Table 2-94 (Page 6 of 6) 31 DEC 2000 Table 2-95 (Page 1 of 1) 31 DEC 2000 Table 2-96 (Page 1 of 1) 31DEC2000 Chapter 2 Figures Figure 2-1 (Page 1 of 1) 31DEC2000 Figure 2-2 (Page 1 of 1) 31 DEC 2000 Figure 2-3 (Page 1 of 1) 31 DEC 2000 Figure 2-4 (Page 1 of 1) 31 DEC 2000 Figure 2-5 (Page 1 of 1) 31DEC2011 Figure 2-6 (Page 1 of 1) 31 DEC 2000 Figure 2-7 (Page 1 of 1) 31 DEC 2008 Figure 2-8 (Page 1 of 1) 31DEC2008 Figure 2-9 (Page 1 of 1) 31 DEC 2008 Figure 2-10 (Page 1 of 1) 31 DEC 2008
. Figure 2-11 (Page 1 of 1) 31DEC2008 Figure 2-12 (Page 1 of 1) 31DEC2008 Figure 2-13 (Page 1 of 1) 31 DEC 2008 Figure 2-14 (Page 1 of 1) 31 DEC 2008 Figure 2-15 (Page 1 of 1) 31DEC2008 l=igure 2-16 (Page 1 of 1) 31DEC2008 Figure 2-17 (Page 1 of 1) 31DEC2008 Figure 2-18 (Page 1 of 1) 31 DEC 2008 Figure 2-19 (Page 1 of 1) 31 DEC 2008 Figure 2-20 (Page 1 of 1) 31 DEC 2008 Figure 2-21 (Page 1 of 1) 31DEC2008 Figure 2-22 (Page 1 of 1) 31 DEC 2008 Figure 2-23 (Page 1 of 1) 31 DEC 2008 Figure 2-24 (Page 1 of 1) 31 DEC 2008 Figure 2-25 (Page 1 of 1) 31 DEC 2008 Figure 2-26 (Page 1 of 1) 31 DEC 2008 Figure 2-27 (Page 1 of 1) 31 DEC 2008 Figure 2-28 (Page 1 of 1) 31DEC2008 Figure 2-29 (Page 1 of 1) 31DEC2008 Attachment 2 - Page 6 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 2-30 (Page 1 of 1) 31DEC2008 Figure 2-31 (Page 1 of 1) 31 DEC 2008 Figure 2-32 (Page 1 of 1) 31 DEC 2008 Figure 2-33 (Page 1 of 1) 31DEC2008 Figure 2-34 (Page 1 of 1) 31 DEC 2008 Figure 2 2-36 (Page 1 of 1) 31DEC2008 Figure 2-37 (Page 1 of 1) 31DEC2008 Figure 2-38 (Page 1 of 1) 31 DEC 2008 Figure 2-39 (Page 1 of 1) 31 DEC 2000 Figure 2-40 (Page 1 of 1) 31 DEC 2000 Figure 2-41 (Page 1 of 1). . 31 DEC 2000 Figure 2-42 (Page 1 of 1) 31 DEC 2000 Figure 2-43 (Page 1 of 1) 31DEC2000 Figure 2-44 (Page 1 of 1) 31DEC2000 Figure 2-45 (Page 1 of 1) 31 DEC 2000 Figure 2-46 (Page 1 of 1) 31DEC2000 Figure .2-47 (Page 1 of 1) _ 31DEC2000 Figure 2-48 (Page 1 of 1) 31DEC2000 Figure 2-49 (Page 1 of 1) 31DEC2000 Figure 2-50 (Page 1 of 1) 31DEC2000 Figure 2-51 (Page 1 of 1) 31DEC2000 Figure 2-52 (Page 1 of 1) 31DEC2000 Figure 2-53 (Page 1 of 1) 31DEC2000 Figure 2-54 (Page 1 of 1) 31DEC2000 Figure 2-55 (Page 1 of 1) 31DEC2000 Figure 2-56 (Page 1 of 1) 31DEC2000 Figure 2-57 (Page 1 of 1) 31DEC2000 Figure 2-58 (Page 1 of 1) 31DEC2000 Figure 2-59 (Page 1 of 1) 31DEC2000 Figure 2-60 (Page 1 of 1) 31DEC2000 Figure 2-61 (Page 1 of 1) 31 DEC 2000 Figure 2-62 (Page 1 of 1) 31 DEC 2000 Figure 2.,53 (Page 1 of 1) 31 DEC 2000 Figure 2-64 (Page 1 of 1) 31 DEC 2000 Figure 2-65 (Page 1 of 1) 31 DEC 2000 Figure 2-66 (Page 1 of 1) 31DEC2000 Figure 2-67 (Page 1 of 1) 31DEC2000 Figure 2-68 (Page 1 of 1) 31DEC2000 Attachment 2 - Page 7 of 60
ONS-2016-061 Document Control Desk June 30, 2016
.Page Effective Date Changed 2015 Update Figure 2-69 (Page 1 of 1) 31 DEC 2000 Figure 2-70 (Page 1 of 1) 31 DEC 2000 Figure 2-71 (Page 1 of 1) 31 DEC 2000 Figure 2-72 (Page 1 of 1) 31DEC2000 Figure 2-73 (Page 1 of 1) 31 DEC 2000 Figure 2-74 (Page 1 of 1) 31 DEC 2000 Figure 2-75 (Page 1 of 1) 31 DEC 2000 Figure 2-76 (Page 1 of 1) 31 DEC 2000 Figure 2-77 (Page 1 of 1) 31 DEC 2000 Figure 2-78 (Page 1 of 1) 31 DEC 2000 Figure 2-79 (Page 1 of 1) 31 DEC 2000 Figure 2-80 (Page 1 of 1) 31 DEC 2000 Figure 2-81 (Page 1 of 1) 31 DEC 2000 Figure 2-82 (Page 1 of 1) 31 DEC 2000 Figure 2-83 (Page 1 of 1) 31 DEC 2000 Figure 2-84 (Page 1 of 1) 31 DEC 2000 Figure 2-85 (Page 1 of 1) 31 DEC 2000 Figure 2-86 (Page 1 of 1) 31 DEC 2000 Figure 2-87 (Page 1 of 1) 31 DEC 2000 Figure 2-88 (Page 1 of 1) 31 DEC 2000 Figure 2-89 (Page 1 of 1) 31 DEC 2000 Figure 2-90 (Page 1 of 1) 31 DEC 2000 Figure 2-91 (Page 1 of 1) 31 DEC 2000 Figure 2-92 (Page 1 of 1) 31 DEC 2000 Figure 2-93 (Page 1 of 1) 31 DEC 2000 Figure 2-94 (Page 1 of 1) 31 DEC 2000 Figure 2-95 (Page 1 of 1) 31 DEC 2000 Figure 2-96 (Page 1 of 1) 31 DEC 2000 Figure 2-97 (Page 1 of 1) 31 DEC 2000 Figure 2-98 (Page 1 of 1) 31 DEC 2000 Figure 2-99 (Page 1 of 1) 31 DEC 2000 Figure 2-100 (Page 1 of 1) 31 DEC 2000 Figure 2-101 (Page 1 of 1) 31 DEC 2000 Figure 2-102 (Page 1 of 1) 31 DEC 2000 Figure 2-103 (Page 1 of 1) 31 DEC 2000 Figure 2-104 (Page 1 of 1) 31 DEC 2000 Figure 2-105 (Page 1 of 1) 31 DEC 2000 Figure 2-106 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 8 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 2-107 (Page 1 of 1) 31 DEC 2000 Figure 2-108 (Page 1 of 1) 31DEC2000 Figure 2-109 (Page 1 of 1) 31 DEC 2000 Figure 2-110 (Page 1 of 1) 31 DEC 2000 Figure 2-111 (Page 1 of 1) 31 DEC 2000 Figure 2-112 (Page 1 of 1) 31 DEC 2000 Figure 2-113 (Page 1 of 1) 31 DEC 2000 Figure 2-114 (Page 1 of 1) 31 DEC 2000 Figure 2-115 (Page 1 of 1) 31 DEC 2000 Figure 2-116 (Page 1 of 1) 31 DEC 2000 Figure 2-117 (Page 1 of 1) 31 DEC 2000 Figure 2-118 (Page 1 of 1) 31 DEC 2000 Chapter 3 3-1 31 DEC 2015 3-2 31 DEC 2015 3-3 31 DEC 2015 3-4 31 DEC 2015 3-5 31 DEC 2015 3-6 31 DEC 2015 3-7 31 DEC 2015 3-8 31 DEC 2015 3-9 31 DEC 2015 3-10 31 DEC 2015 3-11 31 DEC 2015 3-12 31 DEC 2015 3.0-1 31 DEC 2015 3.0-2 31 DEC 2015 3.1-1 31 DEC 2015 3.1-2 31 DEC 2015 3.1-3 31 DEC 2015 3.1-4 31 DEC 2015 3.1-5 31 DEC 2015 3.1-6 31 DEC 2015 3.1-7 31 DEC 2015 3.1-8 31 DEC 2015 3.1-9 31 DEC 2015 Yes 3.1-10 31 DEC 2015 Attachment 2 - Page 9 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 3.1-11 31DEC2015 3.1-12 31 DEC 2015 3.1-13 31 DEC 2015 3.1-14 31 DEC 2015 3.1-15 31DEC2015 3.1-16 31 DEC 2015 3.1-17 31 DEC 2015 3.1-18 31 DEC 2015 3.1-19 31 DEC 2015 3.1-20 31 DEC 2015 3.1-21 31 DEC 2015 3.1-22 31 DEC 2015 3.1-23 31 DEC 2015 3.1-24 31 DEC 2015 3.1-25 31 DEC 2015 3.1-26 31 DEC 2015 3.1-27 31 DEC 2015 3.1-28 31 DEC 2015 3.1-29 31 DEC 2015 3.1-30 31 DEC 2015 3.1-31 31 DEC 2015 3.1-32 31 DEC 2015 3.2-1 31 DEC 2015 3.2-2 31 DEC 2015 3.2-3 31 DEC 2015 3.2-4 31 DEC 2015 3.2-5 31 DEC 2015 3.2-6 31 DEC 2015 3.2-7 31 DEC 2015 3.2-8 31 DEC 2015 3.3-1 31 DEC 2015 3.3-2 31 DEC 2015 3.4-1 31 DEC 2015 Yes 3.4-2 31 DEC 2015 Yes 3.4-3 31 DEC 2015 Yes 3.4-4 31 DEC 2015 Yes 3.5-1 31 DEC 2015 3.5-2 31 DEC 2015 Attachment 2 - Page 1O of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 3.5-3 31 DEC 2015 3.5-4 31 DEC 2015 3.5-5 31 DEC 2015 3.5-6 31 DEC 2015 3.5-7 31 DEC 2015 Yes 3.5-8 31 DEC 2015 3.6-1 31 DEC 2015 3.6-2 31 DEC 2015 Yes 3.7-1 31 DEC 2015 3.7-2 31 DEC 2015 3.7-3 31 DEC 2015 3.7-4 31 DEC 2015 3.7-5 31 DEC 2015 3.7-6 31 DEC 2015 3.7-7 31 DEC 2015 3.7-8 31 DEC 2015 3.7-9 31 DEC 2015 3.7-10 31 DEC 2015 3.7-11 31 DEC 2015 3.7-12 31 DEC 2015 3.7-13 31 DEC 2015 3.7-14 31 DEC 2015 3.8-1 31 DEC 2015 3.8-2 31 DEC2015 3.8-3 31 DEC 2015 3.8-4 31 DEC 2015 3.8-5 31 DEC 2015 3.8-6 31 DEC2015 3.8-7 31 DEC 2015 3.8-8 31 DEC 2015 3.8-9 31 DEC 2015 3.8-10 31 DEC 2015 3.8-11 31 DEC 2015 3.8-12 31 DEC 2015 3.8-13 31 DEC 2015 3.8-14 31 DEC2015 3.8-15 31 DEC 2015 3.8-16 31 DEC 2015 Attachment 2 - Page 11 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 3.8-17 31 DEC 2015 3.8-18 31 DEC 2015 3.8-19 31 DEC 2015 3.8-20 31 DEC2015 3.8-21 31 DEC 2015 3.8-22 31 DEC 2015 3.8-23 31 DEC 2015 3.8-24 31 DEC 2015 3.8-25 31 DEC 2015 3.8-26 31 DEC 2015 3.8-27 31 DEC 2015 3.8-28 31 DEC 2015 3.8-29 31 DEC 2015 3.8-30 31 DEC 2015 3.8-31 31 DEC 2015 3.8-32 31 DEC 2015 3.8-33 31 DEC 2015 3.8-34 31 DEC 2015 3.8-35 31 DEC 2015 3.8-36 31 DEC 2015 3.8-37 31 DEC 2015 3.8-38 31 DEC 2015 3.8-39 31 DEC 2015 3.8-40 31 DEC 2015 3.8-41 31 DEC 2015 3.8-42 31 DEC 2015 3.8-43 31 DEC 2015 3.8-44 31 DEC 2015 3.8-45 31 DEC 2015 3.8-46 31 DEC 2015 3.8-47 31 DEC 2015 3.8-48 31 DEC 2015 3.8-49 31 DEC 2015 3.8-50 31 DEC 2015 3.8-51 31 DEC 2015 3.8-52 31 DEC 2015 3.8-53 31 DEC 2015 3.8-54 31 DEC 2015 Attachment 2 - Page 12 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 3.8-55 31 DEC 2015 Yes 3.8-56 31 DEC 2015 3.8-57 31 DEC 2015 3.8-58 31 DEC 2015 3.8-59 31 DEC 2015 3.8-60 31 DEC 2015 3.8-61 31 DEC2015 3.8-62 31 DEC 2015 3.8-63 31 DEC 2015 3.8-64 31 DEC 2015 3.8-65 31 DEC 2015 3.8-66 31 DEC 2015 3.8-67 31 DEC 2015 3.8-68 31 DEC 2015 3.8-69 31 DEC 2015 3.8-70 31 DEC 2015 3.8-71 31 DEC2015 3.8-72 31 DEC 2015 3.9-1 31 DEC 2015 3.9-2 31 DEC 2015 3.9-3 31 DEC 2015 3.9-4 31 DEC 2015 3.9-5 31 DEC 2015 3.9-6 31 DEC 2015 3.9-7 31 DEC 2015 3.9-8 31 DEC 2015 3.9-9 31 DEC 2015 3.9-10 31 DEC 2015 3.9-11 31 DEC 2015 3.9-12 31 DEC 2015 3.9-13 31 DEC 2015 3.9-14 31 DEC 2015 3.9-15 31 DEC 2015 3.9-16 31 DEC 2015 3.9-17 31 DEC 2015 3.9-18 31 DEC 2015 3.9-19 31 DEC 2015 3.9-20 31 DEC 2015 Attachment 2 - Page 13 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 3.9-21 31 DEC 2015 3.9-22 31 DEC 2015 3.9-23 31 DEC 2015 3.9-24 31 DEC 2015 3.9-25 31 DEC 2015 3.9-26 31 DEC 2015 3.10-1 31 DEC 2015 3.10-2 31 DEC 2015 3.11-1 31 DEC 2015 3.11-2 31 DEC 2015 3.12-1 31 DEC 2015 3.12-2 31 DEC 2015 3.13-1 31 DEC 2015 Yes 3.13-2 31 DEC 2015 Yes Chapter 3 Tables Table 3-1 (Page 1 of 1) 31 DEC 2004 Table 3-2 (Page 1 of 6) 31DEC2014 Table 3-2 (Page 2 of 6) 31DEC2014 Table 3-2 (Page 3 of 6) 31 DEC 2014 Table 3-2 (Page 4 of 6) 31 DEC 2014 Table 3-2 (Page 5 of 6) 31 DEC 2014 Table 3-2 (Page 6 of 6) 31 DEC 2014 Table 3-3 (Page 1 of 1) 31 DEC 2004 Table 3-4 (Page 1 of 1) 31 DEC 2000 Table 3-5 (Page 1 of 1) 31 DEC 2014 Table 3-6 (Page 1 of 2) 31 DEC 2003 Table 3-6 (Page 2 of 2) 31 DEC 2003 Table 3-7 (Page 1 of 1) 31 DEC 2000 Table 3-8 (Page 1 of 1) 31 DEC 2000 Table 3-9 (Page 1 of 2) 31 DEC 2000 Table 3-9 (Page 2 of 2) 31 DEC 2000 Table 3-10 (Page 1 of 1) 31 DEC 2000 Table 3-11 (Page 1 of 1) 31 DEC 2000 Table 3-12 (Page 1 of 5) 31 DEC 2000 Table 3-12 (Page 2 of 5) 31 DEC 2000 Table 3-12 (Page 3 of 5) 31 DEC 2000 Table 3-12 (Page 4 of 5) 31 DEC 2000 Attachment 2 - Page 14 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 3-12 (Page 5 of 5) 31 DEC 2000 Table 3-13 (Page 1 of 1) 31 DEC 2000 Table 3-14 (Page 1 of 2 31 DEC 2000 Table 3-14 (Page 2 of 2) 31 DEC 2000 Table 3-15 (Page 1 of 1) 31 DEC 2000 Table 3-16 (Page 1 of 1) 31 DEC 2003 Table 3-17 (Page 1 of 1) 31 DEC 2000 Table 3-18 (Page 1 of 1) 31 DEC 2003 Table 3-19 (Page 1 of 1) 31 DEC 2003 Table 3-20 (Page 1 of 1) 31 DEC 2003 Table 3-21 (Page 1 of 1) 31 DEC 2003 Table 3-22 (Page 1 of 1) 31 DEC 2000 Table 3-23 (Page 1 of 1) 31 DEC 2009 Table 3-24 (Page 1 of 1) 31 DEC 2000 Table 3-25 (Page 1 of 1) 31 DEC 2000 Table 3-26 (Page 1 of 1) 31 DEC 2000 Table 3-27 67 (Page 1 of 3) 31 DEC 2000 Table 3-27 67 (Page 2 of 3) 31 DEC 2000 Table 3-27 67 (Page 3 of 3) 31 DEC 2000 Table 3-68 (Page 1 of 8) 31 DEC 2013 Table 3-68 (Page 2 of 8) 31 DEC 2013 Table 3-68 (Page 3 of 8) 31 DEC 2013 Table 3-68 (Page 4 of 8) 31 DEC 2013 Table 3-68 (Page 5 of 8) 31 DEC 2013 Table 3-68 (Page 6 of 8) 31 DEC 2013 Table 3-68 (Page 7 of 8) 31 DEC 2013 Table 3-68 (Page 8 of 8) 31 DEC 2013 Chapter 3 Figures Figure 3-1 (Page 1 of 1) 31 DEC 2000 Figure 3-2 (Page 1 of 1) 31 DEC 2000 Figure 3-3 (Page 1 of 1) 31 DEC 2000 Figure 3-4 (Page 1 of 1) 31 DEC 2000 Figure 3-5 (Page 1 of 1) 31 DEC 2000 Figure 3-6 (Page 1 of 1) 31 DEC 2000 Figure 3-7 (Page 1 of 1) 31 DEC 2000 Figure 3-8 (Page 1 of 1) 31 DEC 2000 Figure 3-9 (Page 1 of 1) 31 DEC 2006 Attachment 2 - Page 15 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 3-10 (Page 1 of 1) 31 DEC 2006 Figure 3-11 (Page 1 of 1) 31 DEC 2006 Figure 3-12 (Page 1 of 1) 31 DEC 2006 Figure 3-13 (Page 1 of 1) 31 DEC 2006 Figure 3-14 (Page 1 of 1) 31 DEC 2006 Figure 3-15 (Page 1 of 1) 31 DEC 2006 Figure 3-16 (Page 1 of 1) 31 DEC 2000 Figure 3-17 (Page 1 of 1) 31 DEC 2000 Figure 3-18 (Page 1 of 1) 31 DEC 2000 Figure 3-19 (Page 1 of 3) 31 DEC 2000 Figure 3-19 (Page 2 of 3) 31 DEC 2000 Figure 3-19 (Page 3 of 3) 31 DEC 2000 Figure 3-20 (Page 1 of 1) 31 DEC 2011 Figure 3-21 (Page 1 of 1) 31 DEC 2000 Figure 3-22 (Page 1 of 1) 31 DEC 2000 Figure 3-23 (Page 1 of 1) 31 DEC 2000 Figure 3-24 (Page 1 of 1) 31 DEC 2000 Figure 3-25 (Page 1 of 4) 31 DEC 2000 Figure 3-25 (Page 2 of 4) 31 DEC 2000 Figure 3-25 (Page 3 of 4) 31 DEC 2000 Figure 3-25 (Page 4 of 4) 31 DEC 2000 Figure 3-26 (Page 1 of 6) 31 DEC 2000 Figure 3-26 (Page 2 of 6) 31 DEC 2000 Figure 3-26 (Page 3 of 6) 31 DEC 2000 Figure 3-26 (Page 4 of 6) 31 DEC 2000 Figure 3-26 (Page 5 of 6) 31 DEC 2000 Figure 3-26 (Page 6 of 6) 31 DEC 2000 Figure 3-27 (Page 1 of 1) 31 DEC 2000 Figure 3-28 (Page 1 of 2) 31 DEC 2000 Figure 3-28 (Page 2 of 2) 31 DEC 2000 Figure 3-29 (Page 1 of 1) 31 DEC 2000 Figure 3-30 (Page 1 of 1) 31 DEC 2000 Figure 3-31 (Page 1 of 1) 31 DEC 2000 Figure 3-32 (Page 1 of 1) 31 DEC 2000 Figure 3-33 (Page 1 of 1) 31 DEC 2000 Figure 3-34 (Page 1 of 1) 31 DEC 2000 Figure 3-35 (Page 1 of 1) 31 DEC 2000 Figure 3-36 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 16 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 3-37 (Page 1 of 4) 31 DEC 2000 Figure 3-37 (Page 2 of 4) 31 DEC 2000 Figure 3-37 (Page 3 of 4) 31 DEC 2000 Figure 3-37 (Page 4 of 4) 31 DEC 2000 Figure 3-38 (Page 1 of 1) 31 DEC 2000 Figure 3 3-51 (Page 1 of 1) 31 DEC 2000 Figure 3-52 (Page 1 of 1) 31 DEC 2003 Figure 3 3-56 (Page 1 of 1) 31 DEC 2003 Figure 3-57 (Page 1 of 1) 31 DEC 2000 Figure 3-58 (Page 1 of 1) 31 DEC 2000 Figure 3-59 (Page 1 of 1) 31 DEC 2000 Figure 3-60 (Page 1 of 1) 31 DEC 2000 Chapter 4 4-1 31 DEC 2015 4-2 31 DEC 2015 4-3 31 DEC2015 4-4 31 DEC 2015 4-5 31 DEC 2015 4-6 31 DEC 2015 4-7 31 DEC 2015 4.0-1 31 DEC 2015 4.0-2 31 DEC 2015 4.1-1 31 DEC 2015 4.1-2 31 DEC 2015 4.2-1 31 DEC 2015 4.2-2 31 DEC 2015 4.2-3 31 DEC 2015 4.2-4 31 DEC 2015 4.2-5 31 DEC 2015 4.2-6 31 DEC 2015 4.2-7 31 DEC 2015 4.2-8 31 DEC 2015 4.2-9 31 DEC 2015 4.2-10 31 DEC 2015 4.2-11 31 DEC 2015 4.2-12 31 DEC 2015 4.2-13 31 DEC 2015 Attachment 2 - Page 17 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 4.2-14 31 DEC 2015 4.3-1 31 DEC 2015 4.3-2 31 DEC 2015 4.3-3 31 DEC 2015 4.3-4 31 DEC 2015 4.3-5 31 DEC 2015 4.3-6 31 DEC 2015 4.3-7 31 DEC 2015 4.3-8 31 DEC 2015 4.3-9 31 DEC 2015 4.3-10 31 DEC 2015 4.3-11 31 DEC 2015 4.3-12 31 DEC 2015 4.3-13 31 DEC 2015 4.3-14 31 DEC 2015 4.3-15 31 DEC 2015 4.3-16 31 DEC 2015 4.3-17 31 DEC 2015 4.3-18 31 DEC 2015 4.3-19 31 DEC 2015 4.3-20 31 DEC 2015 4.4-1 31 DEC 2015 4.4-2 31 DEC 2015 4.4-3 31 DEC 2015 4.4-4 31 DEC 2015 4.4-5 31 DEC 2015 4.4-6 31 DEC 2015 4.4-7 31 DEC 2015 4.4-8 31 DEC 2015 4.5-1 31 DEC 2015 4.5-2 31 DEC 2015 4.5-3 31 DEC 2015 4.5-4 31 DEC 2015 4.5-5 31 DEC 2015 4.5-6 31 DEC 2015 4.5-7 31 DEC 2015 4.5-8 31 DEC 2015 4.5-9 31 DEC 2015 Attachment 2 - Page 18 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 4.5-10 31 DEC 2015 4.5-11 31 DEC 2015 4.5-12 31 DEC 2015 4.5-13 \ 31 DEC 2015 4.5-14 31 DEC 2015 4.5-15 31 DEC2015 4.5-16 31 DEC2015 4.5-17 31 DEC2015 4.5-18 31 DEC 2015 Chapter 4 Tables Table 4-1 (Page 1 of 5) 31 DEC 2009 Table 4-1 (Page 2 of 5) 31 DEC 2009 Table 4-1 (Page 3 of 5) 31 DEC 2009 Table 4-1 (Page 4 of 5) 31 DEC 2009 Table 4-1 (Page 5 of 5) 31 DEC 2009 Table 4-2 (Page 1 of 2) 31 DEC 2009 Table 4-2 (Page 2 of 2) 31 DEC 2009 Table 4-3 (Page 1 of 2) 31 DEC 2012 Table 4-3 (Page 2 of 2) 31 DEC 2012 Table 4-4 (Page 1 of 1) 31 DEC 2012 Table 4-5 (Page 1 of 1) 31 DEC 2000 Table 4-6 (Page 1 of 1) 31 DEC 2012 Table 4-7 (Page 1 of 1) 31 DEC 2009 Table 4-8 (Page 1 of 1) 31 DEC 2000 Table 4-9 (Page 1 of 1) 31 DEC 2012 Table 4-10 (Page 1 of 1) 31 DEC 2012 Table 4-11 (Page 1 of 1) 31 DEC 2012 Table 4-12 (Page 1of1) 31 DEC 2000 Table 4-13 (Page 1 of 1) 31 DEC 2000 Table 4-14 (Page 1 of 1) 31 DEC 2000 Table 4-15 (Page 1 of 1) 31 DEC 2000 Table 4-16 (Page 1 of 1) 31DEC2000 Table 4-17 (Page 1 of 1) 31 DEC 2000 Table 4-18 (Page 1 of 1) 31DEC2000 Table 4-19 (Page 1 of 1) 31 DEC 2000 Table 4-20 (Page 1 of 1) 31 DEC 2012 Table 4-21 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 19 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 4-22 (Page 1 of 1) 31 DEC 2013 Table 4-23 (Page 1 of 1) 31 DEC 2009 Table 4-24 (Page 1 of 1) 31 DEC 2013 Chapter 4 Figures Figure 4-1 (Page 1 of 1) 31 DEC 2000 Figure 4 4-3 (Page 1 of 1) 31 DEC 2000 Figure 4-4 (Page 1 of 1) 31 DEC 2000 Figure 4-5 (Page 1 of 1) 31 DEC 2012 Figure 4-6 (Page 1 of 1) 31 DEC 2012 Figure 4-7 (Page 1 of 1) 31 DEC 2000 Figure 4-8 (Page 1 of 1) 31 DEC 2000 Figure 4-9 (Page 1 of 1) 31 DEC 2000 Figure 4-1 O (Page 1 of 1) 31 DEC 2000 Figure 4-11 (Page 1 of 1) 31 DEC 2000 Figure 4-12 (Page 1 of 1) 31 DEC 2000 Figure 4-13 (Page 1 of 1) 31 DEC 2000 Figure 4-14 (Page 1 of 1) 31 DEC 2000 Figure 4-15 (Page 1 of 1) 31 DEC 2000 Figure 4-16 (Page 1 of 1) 31 DEC 2000 Figure 4-17 (Page 1 of 1) 31 DEC 2000 Figure 4-18 (Page 1 of 1) 31 DEC 2000 Figure 4 4-20 (Page 1 of 1) 31 DEC 2000 Figure 4-21 (Page 1 of 1) 31 DEC 2000 Figure. 4-22 (Page 1 of 1) 31 DEC 2000 Figure 4-23 (Page 1 of 1) 31 DEC 2000 Figure 4-24 (Page 1 of 1) 31 DEC 2000 Figure 4-25 (Page 1 of 1) 31 DEC 2000 Figure 4-26 (Page 1 of 1) 31 DEC 2000 Figure 4-27 (Page 1 of 1) 31 DEC 2000 Figure 4-28 (Page 1 of 1) 31 DEC 2000 Figure 4-29 (Page 1 of 1) 31 DEC 2000 Figure 4-30 (Page 1 of 1) 31 DEC 2000 Figure 4-31 (Page 1 of 1) 31 DEC 2000 Figure 4-32 (Page 1 of 1) 31 DEC 2000 Figure 4-33 (Page 1 of 1) 31 DEC 2000 Figure 4-34 (Page 1 of 1) 31 DEC 2000 Figure 4 4-36 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 20 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 4-37 (Page 1 of 1) 31 DEC 2000 Figure 4-38 (Page 1 of 1) 31 DEC 2004 Chapter 5 5-1 31 DEC 2015 5-2 31 DEC 2015 5-3 31 DEC 2015 5-4 31 DEC 2015 5-5 31 DEC 2015 5-6 31 DEC 2015 5-7 31 DEC 2015 5.0-1 31 DEC 2015 5.0-2 31 DEC2015 5.1-1 31 DEC2015 5.1-2 31 DEC 2015 5.1-3 31 DEC 2015 5.1-4 31 DEC 2015 5.1-5 31 DEC 2015 5.1-6 31 DEC 2015 5.2-1 31 DEC2015 5.2-2 31 DEC 2015 5.2-3 31 DEC 2015 5.2-4 31 DEC 2015 5.2-5 31 DEC 2015 5.2-6 31 DEC2015 5.2-7 31 DEC 2015 5.2-8 31 DEC 2015 5.2-9 31 DEC 2015 5.2-10 31 DEC 2015 5.2-11 31 DEC 2015 5.2-12 31 DEC 2015 5.2-13 31 DEC 2015 5.2-14 31 DEC 2015 5.2-15 31 DEC 2015 5.2-16 31 DEC 2015 5.2-17 31 DEC 2015 5.2-18 31 DEC 2015 5.2-19 31 DEC 2015 Attachment 2 - Page 21 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 5.2-20 31 DEC 2015 5.2-21 31 DEC 2015 5.2-22 31 DEC2015 15.2-23 31 DEC 2015 5.2-24 31 DEC 2015 5.2-25 31 DEC 2015 5.2-26 31 DEC 2015 5.2-27 31 DEC2015 5.2-28 31 DEC 2015 Yes 5.2-29 31 DEC 2015 5.2-30 31 DEC 2015 5.2-31 31 DEC 2015 5.2-32 31 DEC 2015 5.2-33 31 DEC2015 5.2-34 31 DEC 2015 5.2-35 31 DEC 2015 5.2-36 31 DEC 2015 5.2-37 31 DEC 2015 5.2-38 31 DEC 2015 5.2-39 31 DEC 2015 5.2-40 31 DEC2015 Yes 5.3-1 31 DEC 2015 5.3-2 31 DEC 2015 5.3-3 31 DEC 2015 5.3-4 31 DEC 2015 5.4-1 31 DEC 2015 5.4-2 31 DEC 2015 5.4-3 31 DEC 2015 5.4-4 31 DEC 2015 5.4-5 31 DEC 2015 5.4-6 31 DEC 2015 5.4-7 31 DEC 2015 5.4-8 31 DEC 2015 5.4-9 31 DEC 2015 5.4-10 31 DEC 2015 5.4-11 31 DEC 2015 5.4-12 31 DEC 2015 5.4-13 31 DEC 2015 Attachment 2 - Page 22 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 5.4-14 31 DEC 2015 5.4-15 31 DEC 2015 5.4-16 31 DEC 2015 5.4-17 31 DEC 2015 5.4-18 31 DEC 2015 5.4-19 31 DEC 2015 5.4-20 31 DEC 2015 Chapter 5 Tables Table 5-1 (Page 1 of 1) 31 DEC 2000 Table 5-2 (Page 1 of 3) 31 DEC 2004 Table 5-2 (Page 2 of 3) 31 DEC 2004 Table 5-2 (Page 3 of 3) 31 DEC 2004 Table 5-3 (Page 1 of 1) 31 DEC 2010 Table 5-4 (Page 1 of 1) 31 DEC 2004 Table 5-5 (Page 1 of 2) 31 DEC 2014 Table 5-5 (Page 2 of 2) 31 DEC 2014 Table 5-6 (Page 1 of 1) 31 DEC 2000 Table 5-7 (Page 1 of 1) 31 DEC 2000 Table 5-8 (Page 1 of 1) 31 DEC 2004 Table 5-9 (Page 1 of 1) 31 DEC 2004 Table 5-10 (Page 1 of 5) 31 DEC 2004 Table 5-10 (Page 2 of 5) 31 DEC 2004 Table 5-10 (Page 3 of 5) 31 DEC 2004 Table 5-10 (Page 4 of 5) 31 DEC 2004 Table 5-10 (Page 5 of 5) 31 DEC 2004 Table 5-11 (Page 1 of 2) 31 DEC 2003 Table 5-11 (Page 2 of 2) 31 DEC 2003 Table 5-12 (Page 1 of 2) 31 DEC 2003 Table 5-12 (Page 2 of 2) 31 DEC 2003 Table 5-13 (Page 1 of 1) 31 DEC 2003 Table 5-14 (Page 1 of 2) 31 DEC 2000 Table 5-14 (Page 2 of 2) 31 DEC 2000 Table 5-15 (Page 1 of 1) 31 DEC 2004 Table 5-16 (Page 1 of 1) 31 DEC 2011 Table 5-17 (Page 1 of 1) 31 DEC 2001 Table 5-18 (Page 1 of 3) 31 DEC 2000 Table 5-18 (Page 2 of 3) 31 DEC 2000 Attachment 2 - Page 23 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 5-18 (Page 3 of 3) 31 DEC 2000 Table 5-19 (Page 1 of 1) 31 DEC 2000 Table 5-20 (Page 1 of 3) 31 DEC 2004 Table 5-20 (Page 2 of 3) 31 DEC 2004 Table 5-20 (Page 3 of 3) 31 DEC 2004 Table 5-21 (Page 1 of 2) 31 DEC 2004 Table 5-21 (Page 2 of 2) 31 DEC 2004 Table 5-22 (Page 1 of 1) 31 DEC 2006 Table 5-23 (Page 1 of 3) 31 DEC 2000 Table 5-23 (Page 2 of 3) 31 DEC 2000 Table 5-23 (Page 3 of 3) 31 DEC 2000 Table 5-24 (Page 1 of 2) 31 DEC 2000 Table 5-24 (Page 2 of 2) 31 DEC 2000 Table 5-25 (Page 1 of 1) 31 DEC 2000 Table 5-26 (Page 1 of 2) 31 DEC 2000 Table 5-26 (Page 2 of 2) 31 DEC 2000 Table 5-27 (Page 1 of 2) 31 DEC 2000 Table 5-27 (Page 2 of 2) 31 DEC 2000 Table 5-28 (Page 1 of 1) 31 DEC 2000 Table 5-29 (Page 1 of 1) 31 DEC 2000 Chapter 5 Figures Figure 5-1 (Page 1 of 1) 31 DEC 2000 Figure 5-2 (Page 1 of 1) 31 DEC 2000 Figure 5-3 (Page 1 of 1) 31 DEC 2000 Figure 5-4 (Page 1 of 1) 31 DEC 2000 Figure 5-5 (Page 1 of 1) 31 DEC 2004 Figure 5-6 (Page 1 of 1) 31 DEC 2004 Figure 5-7 (Page 1 of 1) 31 DEC 2004 Figure 5-8 (Page 1 of 1) 31 DEC 2004 Figure 5-9 (Page 1 of 1) 31 DEC 2004 Figure 5-10 (Page 1 of 1) 31 DEC 2000 Figure 5-11 (Page 1 of 1) 31 DEC 2004 Figure 5-12 (Page 1 of 1) 31 DEC 2000 Figure 5-13 (Page 1 of 1) 31 DEC 2000 Figure 5-14 (Page 1 of 1) . -31 DEC 2003 Figure 5-15 (Page 1 of 1) 31 DEC 2003 Figure 5-16 (Page 1 of 1) 31 DEC 2003 Attachment 2 - Page 24 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 5-17 (Page 1 of 1) 31DEC2000 Figure 5-18 (Page 1 of 1) 31 DEC 2000 Figure 5-19 (Page 1 of 1) 31 DEC 2000 Figure 5-20 (Page 1 of 1) 31 DEC 2000 Figure 5-21 (Page 1 of 4) 31DEC2004 Figure 5-21 (Page 2 of 4) 31 DEC 2000 Figure 5-21 (Page 3 of 4) 31 DEC 2000 Figure 5-21 (Page 4 of 4) 31 DEC 2000 Figure 5-22 (Page 1 of 1) 31 DEC 2004 Figure 5-22 (Page 2 of 4) 31 DEC 2004 Figure 5-22 (Page 3 of 4) 31 DEC 2004 Figure 5-22 (Page 3 of 4) 31 DEC 2004 Figure 5-23 (Page 1 of 1) 31 DEC 2000 Figure 5-24 (Page 1 of 1) 31 DEC 2000 Figure 5-25 (Page 1 of 1) 31 DEC 2004 Figure 5-26 (Page 1 of 1) 31 DEC 2004 Figure 5-27 (Page 1 of 1) 31 DEC 2000 Figure 5-28 (Page 1 of 1) 31 DEC 2000 Figure 5-29 (Page 1 of 1) 31 DEC 2008 Figure 5-30 (Page 1 of 1) 31 DEC 2003 Figure 5-31 (Page 1 of 1) 31 DEC 2003 Figure 5-32 (Page 1 of 1) 31 DEC 2003 Figure 5-33 (Page 1 of 1) 31 DEC 2003 Chapter 6 6-1 31 DEC 2015 6-2 31 DEC2015 6-3 31 DEC 2015 6-4 31 DEC 2015 6-5 31 DEC 2015 6-6 31 DEC 2015 6-7 31 DEC 2015 6-8 31 DEC 2015 6.0-1 31 DEC 2015 6.0-2 31 DEC 2015 6.1-1 31 DEC 2015 6.1-2 31 DEC 2015 Attachment 2 - Page 25 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 6.1-3 31 DEC 2015 6.1-4 31 DEC 2015 6.1-5 31 DEC 2015 6.1-6 31 DEC 2015 6.2-1 31 DEC 2015 6.2-2 31 DEC 2015 6.2-3 31 DEC 2015 6.2-4 31 DEC 2015 6.2-5 31 DEC 2015 6.2-6 31 DEC2015 6.2-7 31 DEC 2015 6.2-8 31 DEC2015 6.2-9 31 DEC 2015 6.2-10 31 DEC 2015 6.2-11 31 DEC 2015 6.2-12 31 DEC 2015 6.2-13 31 DEC 2015 6.2-14 31 DEC 2015 6.2-15 31 DEC 2015 6.2-16 31 DEC 2015 6.2-17 31 DEC 2015 6.2-18 31 DEC 2015 6.2-19 31 DEC 2015 6.2-20 31 DEC 2015 6.2-21 31 DEC 2015 6.2-22 31 DEC 2015 6.3-1 31 DEC 2015 6.3-2 31 DEC 2015 6.3-3 31 DEC 2015 6.3-4 31 DEC 2015 6.3-5 31 DEC 2015 6.3-6 31 DEC 2015 6.3-7 31 DEC 2015 6.3-8 31 DEC 2015 6.3-9 31 DEC 2015 6.3-10 31 DEC 2015 6.3-11 31 DEC 2015 6.3-12 31 DEC 2015 Attachment 2 - Page 26 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 6.3-13 31 DEC 2015 6.3-14 31 DEC 2015 6.3-15 31 DEC 2015 6.3-16 31 DEC 2015 6.4-1 31 DEC 2015 6.4-2 31 DEC 2015 6.4-3 31 DEC 2015 6.4-4 31 DEC 2015 6.5-1 31 DEC2015 6.5-2 31 DEC 2015 6.5-3 31 DEC 2015 Yes 6.5-4 31 DEC 2015 6.6-1 31 DEC 2015 6.6-2 31 DEC 2015 Chapter 6 Tables Table 6-1 (Page 1 of 1) 31 DEC 2000 Table 6-2 (Page 1 of 1) 31 DEC 2000 Table 6-3 (Page 1 of 2) 31 DEC 2000 Table 6-3 (Page 2 of 2) 31 DEC 2000 Table 6-4 (Page 1 of 2) 31 DEC 2004 Table 6-4 (Page 2 of 2) 31 DEC 2004 Table 6-5 (Page 1 of 1) 31 DEC 2000 Table 6-6 (Page 1 of 1) 31 DEC 2000 Table 6-7 (Page 1 of 7) 31 DEC 2014 Table 6-7 (Page 2 of 7) 31 DEC 2014 Table 6-7 (Page 3 of 7) 31 DEC 2014 Table 6-7 (Page 4 of 7) 31 DEC 2014 Table 6-7 (Page 5 of 7) 31 DEC 2014 Table 6-7 (Page 6 of 7) 31 DEC 2014 Table 6-7 (Page 7 of 7) 31 DEC 2014 Table 6-8 (Page 1 of 2) 31 DEC 2005 Table 6-8 (Page 2 of 2) 31 DEC 2005 Table 6-9 (Page 1 of 1) 31 DEC 2009 Table 6-10 (Page 1 of 1) 31 DEC 2000 Table 6-11 (Page 1 of 2) 31 DEC 2005 Table 6-11 (Page 2 of 2) 31 DEC 2005 Table 6-12 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 27 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 6-13 (Page 1 of 1) 31DEC2000 Table 6-14 (Page 1 of 2) 31DEC2000 Table 6-14 (Page 2 of 2) 31 DEC 2000 Table 6-15 (Page 1 of 1) 31 DEC 2005 Table 6 6-17 (Page 1 of 1) 31 DEC 2000 Table 6-18 (Page 1 of 1) 31 DEC 2000 Table 6-19 (Page 1 of 1) 31 DEC 2015 Yes Table 6-20 (Page 1 of 1) 31 DEC 2000 Table 6-21 (Page 1 of 1) 31 DEC 2003 Table 6-22 (Page 1 of 1) 31DEC2013 Table 6-23 (Page 1 of 1) 31 DEC 2013 Table 6-24 (Page 1 of 1) 31 DEC 2013 Table 6-25 (Page 1 of 1) 31 DEC 2013 Table 6-26 (Page 1 of 2) 31 DEC 2013 Table 6-26 (Page 2 of 2) 31 DEC 2013 Table 6-27 (Page 1 of 1) 31 DEC 2008 Table 6-28 (Page 1 of 1) 31DEC2000 Table 6-29 (Page 1 of 15) 31 DEC 2003 Table 6-29 (Page 2 of 15) 31 DEC 2003 Table 6-29 (Page 3 of 15) 31 DEC 2003 Table 6-29 (Page 4 of 15) 31 DEC 2003 Table 6-29 (Page 5 of 15) 31 DEC 2003 Table 6-29 (Page 6 of 15) 31 DEC 2003 Table 6-29 (Page 7 of 15) 31DEC2003 Table 6-29 (Page 8 of 15 31DEC2003 Table 6-29 (Page 9 of 15) 31 DEC 2003 Table 6-29 (Page 10 of 15) 31 DEC 2003 Table 6-29 (Page 11 of 15) 31 DEC 2003 Table 6-29 (Page 12of15) 31 DEC 2003 Table 6-29 (Page 13 of 15) 31 DEC 2003 Table 6-29 (Page 14 of 15) 31DEC2003 Table 6-29 (Page 15 of 15) 31 DEC 2003 Table 6-30 (Page 1 of 40) 31 DEC 2003 Table 6-30 (Page 2 of 40) 31 DEC 2003 Table 6-30 (Page 3 of 10) 31 DEC 2003 Table 6-30 (Page 4 of 40) 31 DEC 2003 Table 6-30 (Page 5 of 40) 31 DEC 2003 Table 6-30 (Page 6 of 40) 31DEC2003 Attachment 2 - Page 28 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 6-30 (Page 7 of 40) 31 DEC 2003 Table 6-30 (Page 8 of 40) 31 DEC 2003 Table 6-30 (Page 9 of 40) 31 DEC 2003 Table 6-30 (Page 10 of 40) 31 DEC 2003 Table 6-30 (Page 11 of 40) 31 DEC 2003 Table 6-30 (Page 12 of 40) 31 DEC 2003 Table 6-30 (Page 13 of 10) 31 DEC 2003 Table 6-30 (Page 14 of 40) 31 DEC 2003 Table 6-30 (Page 15 of 40) 31 DEC 2003 Table 6-30 (Page 16 of 40) 31 DEC 2003 Table 6-30 (Page 17 of 40) 31 DEC 2003 Table 6-30 (Page 18 of 40) 31 DEC 2003 Table 6-30 (Page 19 of 40) 31 DEC 2003 Table 6-30 (Page 20 of 40) 31 DEC 2003 Table 6-30 (Page 21 of 40) 31 DEC 2003 Table 6-30 (Page 22 of 40) 31 DEC 2003 Table 6-30 (Page 23 of 10) 31 DEC 2003 Table 6-30 (Page 24 of 40) 31 DEC 2003 Table 6-30 (Page 25 of 40) 31 DEC 2003 Table 6-30 (Page 26 of 40) 31 DEC 2003 Table 6-30 (Page 27 of 40) 31 DEC 2003 Table 6-30 (Page 28 of 40) 31 DEC 2003 Table 6-30 (Page 29 of 40) 31 DEC 2003 Table 6-30 (Page 30 of 40) 31 DEC 2003 Table 6-30 (Page 31 of 40) 31 DEC 2003 Table 6-30 (Page 32 of 40) 31 DEC 2003 Table 6-30 (Page 33 of 10) 31 DEC 2003 Table 6-30 (Page 34 of 40) 31 DEC 2003 Table 6-30 (Page 35 of 40) 31 DEC 2003 Table 6-30 (Page 36 of 40) 31 DEC 2003 Table 6-30 (Page 37 of 40) 31 DEC 2003 Table 6-30 (Page 38 of 40) 31 DEC 2003 Table 6-30 (Page 39 of 40) 31 DEC 2003 Table 6-30 (Page 40 of 40) 31 DEC 2003 Table 6-31 (Page 1 of 2) 31 DEC 2013 Table 6-31 (Page 2 of 2) 31 DEC 2013 Table 6-32 (Page 1 of 5) 31 DEC 2003 Table 6-32 (Page 2 of 5) 31 DEC 2003 Attachment 2 - Page 29 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 6-32 (Page 3 of 5) 31 DEC 2003*
Table 6-32 (Page 4 of 5) 31 DEC 2003 Table 6-32 (Page 5 of 5) 31 DEC 2003 Table 6-33 (Page 1 of 1) 31 DEC 2005 Table 6-34 (Page 1 of 1) 31 DEC 2008 Table 6-35 (Page 1 of 18) 31 DEC 2003 Table 6-35 (Page 2 of 18) 31 DEC 2003 Table 6-35 (Page 3 of 18) 31 DEC 2003 Table 6-35 (Page 4of18) 31 DEC 2003 Table 6-35 (Page 5 of 18) 31 DEC 2003 Table 6-35 (Page 6 of 18) 31 DEC 2003 Table 6-35 (Page 7 of 18) 31 DEC 2003 Table 6-35 (Page 8 of 18) 31 DEC 2003 Table 6-35 (Page 9 of 18) 31 DEC 2003 Table 6-35 (Page 10 of 18) 31 DEC 2003 Table 6-35 (Page 11 of 18) 31 DEC 2003 Table 6-35 (Page 12 of 18) 31 DEC 2003 Table 6-35 (Page 13 of 18) 31 DEC 2003 Table 6-35 (Page 14 of 18) 31 DEC 2003 Table 6-35 (Page 15 of 18) 31 DEC 2003 Table 6-35 (Page 16of18) 31 DEC 2003 Table 6-35 (Page 17of18) 31 DEC 2003 Table 6-35 (Page 18 of 18) 31 DEC 2003 Chapter 6 Figures Figure 6-1 (Page 1 of 1) 31 DEC 2005 Figure 6-2 (Page 1 of 1) 31 DEC 2002 Figure 6-3 (Page 1 of 1) 31 DEC 2006 Figure 6-4 (Page 1 of 1) 31 DEC 2006 Figure 6-5 (Page 1 of 1) 31 DEC 2000 Figure 6-6 (Page 1 of 1) 31 DEC 2000 Figure 6-7 (Page 1 of 1) 31 DEC 2000 Figure 6-8 (Page 1 of 1) 31 DEC 2000 Figure 6-9 (Page 1 of 3) 31 DEC 2009 Figure 6-9 (Page 2 of 3) 31 DEC 2009 Figure 6-9 (Page 3 of 3) 31 DEC 2009 Figure 6 6-15 (Page 1 of 1) 31 DEC 2000 Figure 6-16 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 30 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 6-17 (Page 1 of 1) 31 DEC 2000 Figure 6-18 (Page 1 of 1) 31 DEC 2000 Figure 6-19 (Page 1 of 1) 31 DEC 2007 Figure 6-20 (Page 1 of 1) 31 DEC 2000 Figure 6-21 (Page 1 of 1) 31 DEC 2000 Figure 6-22 (Page 1 of 1) 31 DEC 2000 Figure 6-23 (Page 1 of 1) 31 DEC 2000 Figure 6-24 (Page 1 of 1) 31 DEC 2000 Figure 6-25 (Page 1 of 1) 31 DEC 2000 Figure 6-26 (Page 1 of 1) 31 DEC 2000 Figure 6-27 (Page 1 of 1) 31 DEC 2000 Figure 6-28 (Page 1 of 1) 31 DEC 2003 Figure 6-29 (Page 1 of 1) 31 DEC 2003 Figure 6-30 (Page 1 of 1) 31 DEC 2003 Figure 6-31 (Page 1 of 1) 31 DEC 2003 Figure 6-32 (Page 1 of 1) 31 DEC 2003 Figure 6-33 (Page 1 of 1) 31 DEC 2003 Figure 6-34 (Page 1 of 1) 31 DEC 2003 Figure 6-35 (Page 1 of 1) 31 DEC 2003 Figure 6-36 (Page 1 of 1) 31 DEC 2013 Figure 6-37 (Page 1 of 1) 31 DEC 2013 Figure 6 6-41 (Page 1 of 1) 31 DEC 2003 Figure 6-42 (Page 1 of 1) 31 DEC 2008 Figure 6-43 (Page 1 of 1) 31 DEC 2008 Figure 6-44 (Page 1 of 1) 31 DEC 2000 Figure 6-45 (Page 1 of 1) 31 DEC 2000 Figure 6-46 (Page 1 of 1) 31 DEC 2000 Figure 6-47 (Page 1 of 1) 31 DEC 2000 Figure 6-48 (Page 1 of 1) 31 DEC 2000 Figure 6-49 (Page 1 of 1) 31 DEC 2003 Figure 6-50 (Page 1 of 1) 31 DEC 2000 Figure 6-51 (Page 1 of 1) 31 DEC 2000 Figure 6-52 (Page 1 of 1) 31 DEC 2000 Figure 6-53 (Page 1 of 1) 31 DEC 2000 Chapter 7 7-1 31 DEC 2015 7-2 31 DEC 2015 Attachment 2 - Page 31 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 7-3 31 DEC 2015 7-4 31 DEC 2015 7-5 31 DEC 2015 7-6 31 DEC 2015 7-7 31 DEC 2015 7.0-1 31 DEC 2015 7.0-2 31 DEC 2015 7.1-1 31 DEC 2015 7.1-2 31 DEC 2015 7.1-3 31 DEC 2015 7.1-4 31 DEC 2015 7.2-1 31 DEC 2015 7.2-2 31 DEC2015 7.2-3 31 DEC 2015 7.2-4 31 DEC 2015 7.2-5 31 DEC 2015 7.2-6 31 DEC 2015 7.2-7 31 DEC 2015 7.2-8 31 DEC 2015 7.2-9 31 DEC 2015 7.2-10 31 DEC 2015 7.2-11 31 DEC 2015 7.2-12 31 DEC 2015 7.3-1 31 DEC 2015 7.3-2 31 DEC 2015 7.3-3 31 DEC 2015 7.3-4 31 DEC 2015 7.3-5 31 DEC 2015 7.3-6 31 DEC 2015 7.3-7 31 DEC 2015 7.3-8 31 DEC 2015 7.3-9 31 DEC 2015 7.3-10 31 DEC 2015 7.4-1 31 DEC 2015 7.4-2 31 DEC 2015 7.4-3 31 DEC 2015 7.4-4 31 DEC 2015 7.4-5 31 DEC 2015 7.4-6 31 DEC 2015 Attachment 2 - Page 32 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 7.4-7 31 DEC 2015 7.4-8 31 DEC 2015 7.4-9 31 DEC 2015 7.4-10 31 DEC 2015 7.4-11 31 DEC 2015 7.4-12 31 DEC 2015 7.4-13 31 DEC 2015 7.4-14 31 DEC 2015 7.4-15 31 DEC 2015 7.4-16 31 DEC 2015 7.5-1 31 DEC 2015 7.5-2 31 DEC 2015 7.5-3 31 DEC 2015 7.5-4 31 DEC 2015 7.5-5 31 DEC 2015 7.5-6 31 DEC 2015 7.5-7 31 DEC 2015 7.5-8 31DEC2015 7.5-9 31 DEC 2015 7.5-10 31 DEC 2015 7.5-11 31 DEC 2015 7.5-12 31 DEC 2015 7.5-13 31 DEC 2015 7.5-14 31 DEC 2015 7.5-15 31 DEC 2015 7.5-16 31 DEC 2015 7.5-17 31 DEC 2015 7.5-18 31 DEC 2015 7.5-19 31 DEC 2015 7.5-20 31DEC2015 7.5-21 31DEC2015 7.5-22 31DEC2015 7.5-23 31DEC2015 7.5-24 31 DEC 2015 7.5-25 31 DEC 2015 7.5-26 31 DEC 2015 7.6-1 31 DEC 2015 7.6-2 31 DEC 2015 Attachment 2 - Page 33 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 7.6-3 31 DEC 2015 7.6-4 31 DEC 2015 7.6-5 31 DEC 2015 7.6-6 31 DEC 2015 7.6-7 31 DEC 2015 7.6-8 31 DEC 2015 7.6-9 31 DEC 2015 7.6-10 31 DEC 2015 7.6-11 31 DEC2015 7.6-12 31 DEC 2015 7.6-13 31 DEC 2015 7.6-14 31 DEC 2015 7.6-15 31 DEC 2015 7.6-16 31 DEC 2015 7.6-17 31 DEC 2015 7.6-18 31 DEC 2015 7.7-1 31 DEC 2015 7.7-2 31 DEC 2015 7.7-3 31 DEC 2015 7.7-4 31 DEC 2015 7.7-5 31 DEC 2015 7.7-6 31 DEC 2015 7.8-1 31 DEC 2015 7.8-2 31 DEC 2015 7.8-3 31 DEC 2015 7.8-4 31 DEC 2015 7.9-1 31 DEC 2015 7.9-2 31 DEC 2015 7.9-3 31 DEC 2015 7.9-4 31 DEC 2015 7.9-5 31 DEC 2015 7.9-6 31 DEC 2015 7.10-1 31DEC2015 7.10-2 31DEC2015 7.11-1 31 DEC 2015 7.11-2 31 DEC 2015 Chapter 7 Tables Attachment 2 - Page 34 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 7-1 (Page 1 of 1) 31 DEC 2012 Table 7-2 (Page 1 of 1) 31 DEC 2012 Table 7-3 (Page 1 of 1) 31 DEC 2012 Table 7-4 (Page 1 of 1) 31 DEC 2013 Table 7-5 (Page 1 of 2) 31 DEC 2006 Table 7-5 (Page 2 of 2) 31 DEC 2006 Table 7-6 (Page 1 of 1) 31 DEC 2006 Chapter 7 Figures Figure 7-1 (Page 1 of 16) 31 DEC2013 Figure 7-2 (Page 2 of 16) 31 DEC 2013 Figure 7-1 (Page 3 of 16) 31 DEC 2013 Figure 7-1 (Page 4 of 16) 31 DEC 2013 Figure 7-1 (Page 5of16) 31 DEC 2013 Figure 7-1 (Page 6 of 16) 31 DEC 2013 Figure 7-1 (Page 7 of 16) 31 DEC 2013 Figure 7-1 (Page 8 of 16) 31 DEC 2013 Figure 7-1 (Page 9of16) 31 DEC 2013 Figure 7-1 (Page 10of16) 31 DEC 2013 Figure 7-1 (Page 11 of 16) 31 DEC 2013 Figure 7-1 (Page 12of16) 31 DEC 2013 Figure 7-1 (Page 13of16) 31 DEC 2013 Figure 7-1 (Page 14 of 16) 31 DEC 2013 Figure 7-1 (Page 15of16) 31 DEC 2013 Figure 7-1 (Page 16of16) 31 DEC 2013 Figure 7-2 (Page 1 of 1) 31 DEC 2000 Figure 7-3 (Page 1 of 1) 31 DEC 2003 Figure 7-4 (Page 1 of 1) 31 DEC 2012 Figure 7-5 (Page 1 of 8) 31 DEC 2013 Figure 7-5 (Page 2 of 8) 31 DEC 2013 Figure 7-5 (Page 3 of 8) 31 DEC 2013 Figure 7-5 (Page 4 of 8) 31 DEC 2013 Figure 7-5 (Page 5 of 8) 31 DEC 2013 Figure 7-5 (Page 6 of 8) 31 DEC 2013 Figure 7-5 (Page 7 of 8) 31 DEC2013 Figure 7-5 (Page 8 of 8) 31 DEC 2013 Figure 7-6 (Page 1 of 1) 31 DEC 2013 Figure 7-7 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 35 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 7-8 (Page 1 of 1) 31 DEC 2013 Figure 7-9 (Page 1 of 1) 31 DEC 2011 Figure 7-10 (Page 1 of 1) 31 DEC 2013 Figure 7-11 (Page 1 of 1) 31 DEC 2000 Figure 7-12 (Page 1 of 1) 31 DEC 2009 Figure 7-13 (Page 1 of 1) 31 DEC 2009 Figure 7-14 (Page 1 of 1) 31 DEC 2000 Figure 7-15 (Page 1 of 1) 31 DEC 2000 Figure 7-16 (Page 1 of 1) 31 DEC 2000 Figure 7-17 (Page 1 of 1) 31 DEC 2000 Figure 7-18 (Page 1 of 1) 31 DEC 2004 Figure 7-19 (Page 1 of 1) 31 DEC 2000 Figure 7-20 (Page 1 of 1) 31 DEC 2000 Figure 7-21 (Page 1 of 1) 31 DEC 2000 Figure 7 7-25 (Page 1 of 1) 31 DEC 2000 Figure 7-26 (Page 1 of 1) 31 DEC 2000 Chapter 8 8-1 31 DEC 2015 8-2 31 DEC 2015 8-3 31 DEC 2015 8-4 31 DEC 2015 8.0-1 31 DEC 2015 8.0-2 31 DEC 2015 8.1-1 31 DEC 2015 8.1-2 31 DEC 2015 8.2-1 31 DEC 2015 8.2-2 31 DEC 2015 8.2-3 31 DEC 2015 Yes 8.2-4 31 DEC 2015 8.2-5 31 DEC 2015 8.2-6 31 DEC 2015 8.3-1 31 DEC 2015 8.3-2 31 DEC 2015 8.3-3 31 DEC 2015 8.3-4 31 DEC 2015 8.3-5 31 DEC 2015 8.3-6 31 DEC 2015 Attachment 2 - Page 36 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 8.3-7 31 DEC 2015 8.3-8 31 DEC 2015 8.3-9 31 DEC 2015 Yes 8.3-10 31 DEC 2015 8.3-11 31 DEC 2015 8.3-12 31 DEC 2015 8.3-13 31 DEC2015 8.3-14 31 DEC 2015 8.3-15 31 DEC 2015 8.3-16 31 DEC 2015 8.3-17 31 DEC 2015 8.3-18 31 DEC 2015 8.3-19 31 DEC 2015 Yes 8.3-20 31 DEC 2015 8.4-1 31 DEC 2015 8.4-2 31 DEC 2015 Chapter 8 Tables Table 8-1 (Page 1 of 2) 31 DEC 2002 Table 8-1 (Page 2 of 2) 31 DEC 2002 Table 8-2 (Page 1 of 2) 31 DEC 2000 Table 8-2 (Page 2 of 2) 31 DEC 2000 Table 8-3 (Page 1 of 2) 31 DEC 2014 Table 8-3 (Page 2 of 2) 31 DEC 2014 Table 8-4 (Page 1 of 1) 31 DEC 2014 Table 8-5 (Page 1 of 3) 31 DEC 2000 Table 8-5 (Page 2 of 3) 31 DEC 2000 Table 8-5 (Page 3 of 3) 31 DEC 2000 Table 8-6 (Page 1 of 1) 31 DEC 2000 Table 8-7 (Page 1 of 1) 31 DEC 2000 Chapter 8 Figures Figure 8-1 (Page 1 of 1) 31 DEC 2015 Yes Figure 8-2 (Page 1 of 1) 31 DEC 2015 Yes Figure 8-3 (Page 1 of 2) 31 DEC 2015 Yes Figure 8-3 (Page 2 of 2) 31 DEC 2015 Yes Figure 8-4 (Page 1 of 3) 31 DEC 2015 Yes Figure 8-4 (Page 2 of 3) 31 DEC 2015 Yes Attachment 2 - Page 37 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 8-4 (Page 3 of 3) 31 DEC 2015 Yes Figure 8-5 (Page 1 of 1) 31 DEC 2013 Figure 8-6 (Page 1 of 1) 31 DEC 2013 Figure 8-7 (Page 1 of 1) 31 DEC 2006 Figure 8-8 (Page 1 of 1) 31 DEC 2000 Figure 8-9 (Page 1 of 1) 31 DEC 2000 Chapter 9 9-1 31 DEC 2015 9-2 31 DEC 2015 9-3 31 DEC 2015 9-4 31 DEC 2015 9-5 31 DEC2015 9-6 31 DEC 2015 9-7 31 DEC 2015 9-8 31 DEC2015 9.0-1 31 DEC 2015 9.0-2 31 DEC 2015 9.1-1 31 DEC 2015 9.1-2 31 DEC 2015 9.1-3 31 DEC 2015 9.1-4 31 DEC 2015 9.1-5 31 DEC 2015 9.1-6 31 DEC 2015 9.1-7 31 DEC 2015 9.1-8 31 DEC 2015 9.1-9 31 DEC 2015 9.1-10 31 DEC 2015 9.1-11 31 DEC 2015 9.1-12 31 DEC 2015 Yes 9.1-13 31 DEC 2015 Yes 9.1-14 31 DEC 2015 Yes 9.1-15 31 DEC 2015 Yes 9.1-16 31 DEC2015 9.1-17 31 DEC 2015 9.1-18 31 DEC 2015 9.1-19 31 DEC 2015 9.1-20 31 DEC 2015 Attachment 2 - Page 38 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 9.1-21 31 DEC 2015 9.1-22 31 DEC 2015 9.1-23 31 DEC 2015 9.1-24 31 DEC 2015 9.1-25 31 DEC 2015 9.1-26 31 DEC 2015 9.1-27 31 DEC 2015 Yes 9.1-28 31 DEC 2015 9.2-1 31 DEC 2015 9.2-2 31 DEC 2015 9.2-3 31 DEC 2015 Yes 9.2-4 31 DEC 2015 9.2-5 31 DEC 2015 9.2-6 31 DEC 2015 9.2-7 31 DEC 2015 9.2-8 31DEC2015 9.2-9 31 DEC 2015 9.2-10 31 DEC 2015 9.2-11 31 DEC 2015 Yes 9.2-12 31 DEC 2015 9.3-1 31 DEC 2015 9.3-2 31 DEC 2015 9.3-3 31 DEC 2015 9.3-4 31 DEC 2015 9.3-5 31 DEC 2015 9.3-6 31 DEC 2015 9.3-7 31 DEC 2015 9.3-8 31 DEC 2015 9.3-9 31 DEC 2015 9.3-10 31 DEC 2015 9.3-11 31 DEC 2015 9.3-12 31DEC2015 9.3-13 31 DEC 2015 9.3-14 31DEC2015 9.3-15 31 DEC 2015 9.3-16 31 DEC 2015 9.4-1 31 DEC 2015 9.4-2 31 DEC 2015 Attachment 2 - Page 39 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 9.4-3 31 DEC 2015 9.4-4 31 DEC 2015 9.4-5 31 DEC 2015 9.4-6 31 DEC 2015 9.4-7 31 DEC 2015 9.4-8 31DEC2015 9.4-9 31DEC2015 9.4-10 31 DEC 2015 9.4-11 31 DEC 2015 9.4-12 31 DEC 2015 9.5-1 31 DEC 2015 9.5-2 31 DEC 2015 9.5-3 31 DEC 2015 9.5-4 31 DEC 2015 9.5-5 31 DEC 2015 9.5-6 31 DEC 2015 9.5-7 31 DEC 2015 9.5-8 31DEC2015 9.5-9 31 DEC 2015 9.5-10 31 DEC 2015 9.5-11 31 DEC 2015 9.5-12 31 DEC 2015 9.5-13 31 DEC 2015 9.5-14 31 DEC 2015 9.5-15 31 DEC 2015 9.5-16 31 DEC 2015 9.5-17 31 DEC 2015 9.5-18 31 DEC 2015 9.6-1 31 DEC 2015 Yes 9.6-2 31 DEC 2015 Yes 9.6-3 31 DEC 2015 Yes 9.6-4 31 DEC 2015 Yes 9.6-5 31 DEC 2015 9.6-6 31 DEC 2015 9.6-7 31 DEC 2015 9.6-8 31 DEC 2015 9.6-9 31 DEC 2015 9.6-10 31 DEC 2015 Attachment 2 - Page 40 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 9.6-11 31 DEC 2015 9.6-12 31DEC2015 9.6-13 31 DEC 2015 9.6-14 31 DEC 2015 9.6-15 31 DEC 2015 9.6-16 31 DEC 2015 9.6-17 31 DEC 2015 Yes 9.6-18 31 DEC 2015 9.6-19 31DEC2015 Yes 9.6-20 31 DEC 2015 9.7-1 31 DEC 2015 9.7-2 31 DEC 2015 9.7-3 31 DEC 2015 9.7-4 31 DEC 2015 9.7-5 31 DEC 2015 9.7-6 31 DEC 2015 9.7-7 31 DEC 2015 Yes 9.7-8 31 DEC2015 9.7-9 31 DEC 2015 9.7-10 31 DEC 2015 9.7-11 31 DEC 2015 9.7-12 31 DEC2015 Chapter 9 Tables Table 9-1 (Page 1 of 2) 31 DEC 2000 Table 9-1 (Page 2 of 2) 31DEC2000 Table 9-2 (Page 1 of 2) 31DEC2015 Yes Table 9-2 (Page 2 of 2) 31 DEC 2015 Yes Table 9-3 (Page 1 of 1) 31 DEC 2000 Table 9-4 (Page 1 of 2) 31 DEC 2000 Table 9-4 (Page 2 of 2) 31DEC2000 Table 9-5 (Page 1 of 3) 31DEC2006 Table 9-5 (Page 2 of 3) 31 DEC 2006 Table 9-5 (Page 3 of 3) 31 DEC 2006 Table 9-6 (Page 1 of 1) 31 DEC 2011 Table 9-7 (Page 1 of 2) 31DEC2005 Table 9-7 (Page 2 of 2) 31 DEC 2005 Table 9-8 (Page 1 of 1) 31 DEC 2000 Attachment 2 - Page 41 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 9-9 (Page 1 of 2) 31 DEC 2009 Table 9-9 (Page 2 of 2) 31 DEC 2009 Table 9-10 (Page 1 of 2) 31 DEC 2000 Table 9-10 (Page 2 of 2) 31 DEC 2000 Table 9-11 (Page 1 of 2) 31 DEC 2000 Table 9-11 (Page 2 of 2) 31 DEC 2000 Table 9-12 (Page 1of1) 31 DEC 2002 Table 9-13 (Page 1 of 2) 31 DEC 2000 Table 9-13 (Page 2 of 2) 31 DEC 2000 Table 9-14 (Page 1 of 4) 31 DEC 2010 Table 9-14 (Page 2 of 4) 31 DEC 2010 Table 9-14 (Page 3 of 4) 31 DEC 2010 Table 9-14 (Page 4 of 4) 31 DEC 2010 Table 9-15 (Page 1 of 2) 31 DEC 2010 Table 9-15 (Page 2 of 2) 31 DEC 2010 Table 9-16 (Page 1 of 1) 31 DEC 2011 Table 9-17 (Page 1of1) 31 DEC 2000 Table 9-18 (Page 1 of 1) 31 DEC 2000 Table 9-19 (Page 1 of 1) 31 DEC 2000 Table 9-20 (Page 1 of 1) 31 DEC 2015 Yes Chapter 9 Figures Figure 9-1 (Page 1 of 1) 31 DEC 2000 Figure 9-2 (Page 1 of 1) 31 DEC 2000 Figure 9-3 (Page 1 of 1) 31 DEC 2000 Figure 9-4 (Page 1 of 1) 31 DEC 2000 Figure 9-5 (Page 1 of 1) 31 DEC2015 Yes Figure 9-6 (Page 1 of 1) 31 DEC 2000 Figure 9-7 (Page 1 of 2) 31 DEC 2000 Figure 9-7 (Page 2 of 2) 31 DEC 2000 Figure 9-8 (Page 1 of 1) 31 DEC 2000 Figure 9-9 (Page 1 of 1) 31 DEC 2000 Figure 9-10 (Page 1 of 1) 31 DEC 2006 Figure 9-11 (Page 1 of 1) 31 DEC 2007 Figure 9-12 (Page 1 of 1) 31 DEC 2015 Yes Figure 9-13 (Page 1 of 1) 31 DEC 2000 Figure 9-14 (Page 1 of 1) 31 DEC 2000 Figure 9-15 (Page 1 of 1) 31 DEC 2003 Attachment 2 - Page 42 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 9-16 (Page 1 of 1) 31 DEC 2007 Figure 9-17 (Page 1 of 1) 31 DEC 2015 Yes Figure 9-18 (Page 1 of 1) 31 DEC 2000 Figure 9-19 (Page 1 of 1) 31 DEC 2004 Figure 9-20 (Page 1 of 1) 31 DEC 2004 Figure 9-21 (Page 1 of 1) 31 DEC 2001 Figure 9-22 (Page 1 of 1) 31 DEC 2000 Figure 9-23 (Page 1 of 1) 31 DEC 2000 Figure 9-24 (Page 1 of 1) 31 DEC 2015 Yes Figure 9-25 (Page 1 of 1) 31 DEC 2000 Figure 9-26 (Page 1 of 1) 31 DEC 2000 Figure 9-27 (Page 1 of 1) 31 DEC 2011 Figure 9-28 (Page 1 of 1) 31 DEC 2001 Figure 9-29 (Page 1 of 1) 31 DEC 2000 Figure 9-30 (Page 1 of 1) 31 DEC 2013 Figure 9-31 (Page 1 of 1) 31 DEC 2013 Figure 9-32 (Page 1 of 1) 31 DEC 2013 Figure 9-33 (Page 1 of 1) 31 DEC 2013 Figure 9-34 (Page 1 of 1) 31 DEC 2013 Figure 9-35 (Page 1 of 1) 31 DEC 2000 Figure 9-36 (Page 1 of 1) 31 DEC 2013 Figure 9-37 (Page 1 of 1) 31 DEC 2013 Figure 9-38 (Page 1 of 1) 31 DEC 2013 Figure 9-39 (Page 1 of 1) 31 DEC 2000 Figure 9-40 (Page 1 of 1) 31 DEC 2013 Figure 9-41 (Page 1 of 1) 31 DEC 2000 Figure 9-42 (Page 1 of 1) 31 DEC 2000 Figure 9-43 (Page 1 of 1) 31 DEC 2000 Figure 9-44 (Page 1 of 1) 31 DEC 2015 Yes Figure 9-45 (Page 1 of 1) 31 DEC 2015 Yes Figure 9-46 (Page 1 of 1) 31 DEC 2015 Yes Chapter 10 10-1 31 DEC 2015 10-2 31 DEC 2015 10-3 31 DEC 2015 10-4 31 DEC 2015 10.0-1 31 DEC 2015 Attachment 2 - Page 43 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 10.0-2 31 DEC 2015 10.1-1 31 DEC 2015 Yes 10.1-2 31 DEC 2015 10.2-1 31 DEC 2015 10.2-2 31 DEC 2015 10.2-3 31 DEC 2015 10.2-4 31 DEC 2015 10.3-1 31 DEC 2015 10.3-2 31 DEC 2015 10.3-3 31 DEC 2015 10.3-4 31 DEC2015 10.3-5 31 DEC 2015 10.3-6 31 DEC 2015 10.4-1 31 DEC 2015 10.4-2 31 DEC 2015 10.4-3 31 DEC 2015 10.4-4 31 DEC 2015 10.4-5 31 DEC 2015 10.4-6 31 DEC 2015 10.4-7 31 DEC 2015 10.4-8 31 DEC 2015 10.4-9 31 DEC 2015 10.4-10 31 DEC 2015 10.4-11 31 DEC 2015 10.4-12 31 DEC 2015 10.4-13 31 DEC 2015 10.4-14 31 DEC 2015 10.4-15 31 DEC 2015 10.4-16 31 DEC 2015 10.4-17 31 DEC 2015 Yes 10.4-18 31 DEC 2015 10.4-19 31 DEC 2015 Yes 10.4-20 31 DEC 2015 10.4-21 31 DEC 2015 10.4-22 31 DEC 2015 10.4-23 31 DEC 2015 Yes 10.4-24 31 DEC2015 Attachment 2 - Page 44 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Chapter 10 Tables Table 10-1 (Page 1 of 1) 31 DEC 2000 Table 10-2 (Page 1 of 1) 31 DEC 2009 Chapter 1O Figures Figure10-1 (Page1 of1) 31 DEC 2007 Figure 10-2 (Page 1 of 1) 31DEC2015 Yes Figure 10-3 (Page 1 of 1) 31 DEC 2000 Figure 10-4 (Page 1 of 1) 31 DEC 2015 Yes Figure 10-5 (Page 1 of 1) 31 DEC 2000 Figure 10-6 (Page 1 of 1) 31 DEC 2007 Figure 10-7 (Page 1 of 1) 31 DEC 2015 Yes Figure 10-8 (Page 1 of 1) 31 DEC 2015 Yes Figure 10-9 (Page 1 of 2) 31DEC2004 Figure 10-9 *(Page 2 of 2) 31DEC2004 Chapter 11 11-1 31 DEC 2015 11-2 31 DEC 2015 11-3 31 DEC 2015 11-4 31 DEC 2015 11.0-1 31 DEC 2015 11.0-2 31 DEC 2015 11.1-1 31 DEC 2015 11.1-2 31DEC2015 11.2-1 31 DEC 2015 11.2-2 31 DEC 2015 11.2-3 31 DEC 2015 11.2-4 31 DEC 2015 11.3-1 31 DEC 2015 11.3-2 31 DEC 2015 11.3-3 31 DEC 2015 11.3-4 31 DEC 2015 11.4-1 31 DEC 2015 11.4-2 31DEC2015 11.5-1 31 DEC 2015 11.5-2 31 DEC 2015 11.5-3 31 DEC 2015 Attachment 2 - Page 45 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 11.5-4 31 DEC 2015 11.5-5 31 DEC 2015 11.5-6 31 DEC 2015 11.6-1 31 DEC 2015 11.6-2 31 DEC 2015 11.6-3 31 DEC 2015 11.6-4 31 DEC 2015 11.6-5 31DEC2015 11.6-6 31 DEC 2015 11.6-7 31 DEC 2015 11.6-8 31 DEC 2015 11.6-9 31 DEC 2015 11.6-10 31 DEC 2015 11.6-11 31 DEC 2015 11.5-12 31 DEC 2015 11.7-1 31DEC2015 11.7-2 31DEC2015 11.8-1 31DEC2015 11.8-2 31 DEC 2015 Chapter 11 Tables Table 11-1(Page1of1) 31 DEC 2000 Table 11-2 (Page 1 of 1) 31 DEC 2000 Table 11-3 (Page 1 of 1) 31 DEC 2000 Table 11-4 (Page 1 of 1) 31 DEC 2004 Table 11-5 (Page 1 of 2) 31 DEC 2000 Table 11-5 (Page 2 of 2) 31 DEC 2000 Table 11-6 (Page 1 of 7) 31 DEC 2012 Table 11-6 (Page 2 of 7) 31DEC2012 Table 11-6 (Page 3 of 7) 31DEC2012 Table 11-6 (Page 4 of 7) 31DEC2012 Table 11-6 (Page 5 of 7) 31 DEC 2012 Table 11-6 (Page 6 of 7) 31 DEC 2012 Table 11-6 (Page 7 of 7) 31 DEC 2012 Table 11-7 (Page 1 of 4) 31 DEC 2004 Table 11-7 (Page 2 of 4) 31 DEC 2004 Table 11-7 (Page 3 of 4) 31 DEC 2004 Table 11-7 (Page 4 of 4) 31 DEC 2004 Attachment 2 - Page 46 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Chapter 11 Figures Figure 11-1 (Page 1 of 1) 31 DEC 2000 Figure 11-2 (Page 1 of 1) 31 DEC 2000 Figure 11-3 (Page 1 of 1) 31 DEC 2000 Figure 11-4 (Page 1 of 1) 31 DEC 2011 Figure 11-5 (Page 1 of 1) 31 DEC 2000 Figure 11-6 (Page 1 of 1) 31 DEC 2000 Chapter 12 12-1 31 DEC 2015 12-2 31 DEC 2015 12.0-1 31 DEC 2015 12.0-2 31 DEC2015 12.1-1 31 DEC 2015 12.1-2 31 DEC 2015 12.1-3 31 DEC 2015 12.1-4 31 DEC 2015 12.2-1 31 DEC 2015 12.2-2 31 DEC2015 12.3-1 31 DEC 2015 12.3-2 31 DEC 2015 12.3-3 31 DEC 2015 12.3-4 31 DEC 2015 12.4-1 31 DEC 2015 12.4-2 31 DEC 2015 12.4-3 31 DEC 2015 12.4-4 31 DEC 2015 12.4-5 31 DEC 2015 12.4-6 31 DEC 2015 12.4-7 31 DEC 2015 12.4-8 31 DEC 2015 12.4-9 31 DEC 2015 12.4-10 31 DEC 2015 Chapter 12 Tables Table 12-1 (Page 1 of 1) 31 DEC 2000 Table 12-2 (Page 1 of 2) 31 DEC 2000 Attachment 2 - Page 47 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 12-2 (Page 2 of 2) 31 DEC 2000 Table 12-3 (Page 1 of 2) 31 DEC 2004 Table 12-3 (Page 2 of 2) 31 DEC 2004 Chapter 12 Figures No Figures in Chapter 12 Chapter 13 13-1 31 DEC 2015 13-2 31 DEC 2015 13-3 31 DEC 2015 13-4 31 DEC 2015 13.0-1 31 DEC 2015 13.0-2 31 DEC 2015 13.1-1 31 DEC 2015 13.1-2 31 DEC 2015 13.1-3 31 DEC 2015 13.1-4 31 DEC 2015 13.1-5 31 DEC 2015 13.1-6 31 DEC 2015 13.1-7 31 DEC 2015 13.1-8 31 DEC 2015 13.1-9 31 DEC 2015 13.1-10 31 DEC 2015 13.2-1 31 DEC 2015 13.2-2 31 DEC 2015 13.2-3 31 DEC 2015 13.2-4 31 DEC 2015 13.2-5 31 DEC 2015 13.2-6 31 DEC 2015 13.3-1 31 DEC 2015 13.3-2 31 DEC 2015 13.4-1 31 DEC 2015 13.4-2 31 DEC 2015 13.4-3 31 DEC 2015 13.4-4 31 DEC 2015 13.5-1 31 DEC 2015 13.5-2 31 DEC 2015 Attachment 2 - Page 48 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 13.5-3 31 DEC 2015 13.5-4 31 DEC 2015 13.5-5 31 DEC 2015 13.5-6 31 DEC 2015 13.5-7 31 DEC 2015 13.5-8 31 DEC 2015 13.6-1 31 DEC 2015 13.6-2 31 DEC 2015 Chapter 13 Tables Table 13-1 (Page 1 of 1) 31 DEC 2000 Table 13-2 (Page 1 of 1) 31 DEC 2000 Chapter 13 Figures Figure 13-1 (Page 1 of 1) 31 DEC 2014 Figure 13-2 (Page 1 of 1) 31 DEC 2000 Figure 13-3 (Page 1 of 1) 31 DEC 2014 Figure 13-4 (Page 1 of 1) 31 DEC 2014 Figure 13-5 (Page 1 of 1) 31 DEC 2000 Figure 13-6 (Page 1 of 1) 31 DEC 2000 Figure 13-7 (Page 1 of 1) 31 DEC 2012 Figure 13-8 (Page 1 of 1) 31 DEC 2014 Chapter 14 14-1 31 DEC2015 14-2 31 DEC 2015 14.0-1 31 DEC 2015 14.0-2 31 DEC 2015 14.1-1 31 DEC 2015 14.1-2 31 DEC 2015 14.1-3 31 DEC 2015 14.1-4 31 DEC 2015 14.2-1 31 DEC 2015 14.2-2 31 DEC 2015 14.3-1 31 DEC 2015 14.3-2 31 DEC 2015 14.4-1 31 DEC 2015 14.4-2 31 DEC 2015 Attachment 2 - Page 49 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 14.5-1 31 DEC 2015 14.5-2 31 DEC 2015 14,6-1 31 DEC2015 14.6-2 31 DEC 2015 Chapter 14 Tables Table 14-1 (Page 1 of 1) 31 DEC 2000 Table 14-2 (Page 1 of 1) 31 DEC 2000 Chapter 14 Figures No Figures in Chapter 12 Chapter 15 15-1 31 DEC 2015 15-2 31 DEC2015 15-3 31 DEC2015 15-4 31 DEC 2015 15-5 31 DEC 2015 15-6 31 DEC 2015 15-7 31 DEC 2015 15-8 31 DEC 2015 15-9 31 DEC 2015 15-10 31 DEC 2015 15-11 31 DEC 2015 15-12 31 DEC 2015 15-13 31 DEC 2015 15-14 31 DEC 2015 15-15 31 DEC 2015 15-16 31 DEC 2015 15-17 31 DEC 2015 15.0-1 31 DEC 2015 15.0-2 31 DEC 2015 15.1-1 31 DEC 2015 15.1-2 31 DEC 2015 15.1-3 31 DEC 2015 15.1-4 31 DEC 2015 15.1-5 31 DEC 2015 15.1-6 31 DEC 2015 Attachment 2 - Page 50 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 15.1-7 31 DEC 2015 15.1-8 31 DEC 2015 15.1-9 31 DEC 2015 15.1-10 31 DEC 2015 15.1-11 31 DEC 2015 15.1-12 31 DEC 2015 15.2-1 31 DEC 2015 15.2-2 31 DEC 2015 15.3-1 31 DEC 2015 15.3-2 31 DEC 2015 15.4-1 31 DEC 2015 15.4-2 31DEC2015 15.5-1 31 DEC 2015 Yes 15.5-2 31 DEC 2015 15.6-1 31 DEC 2015 15.6-2 31 DEC 2015 15.6-3 31 DEC 2015 15.6-4 31 DEC 2015 15.6-5 31 DEC 2015 15.6-6 31 DEC 2015
- 15. 7-1 31 DEC 2015 15.7-2 31 DEC 2015 15.8-1 31 DEC 2015 15.8-2 31 DEC 2015 15.9-1 31 DEC 2015 15.9-2 31 DEC 2015 15.9-3 31 DEC 2015 15.9-4 31 DEC 2015 15.10-1 31 DEC 2015 15.10-2 31 DEC 2015 15.11-1 31 DEC 2015 15.11-2 31 DEC 2015 15.11-3 31 DEC 2015 15.11-4 31 DEC2015 15.11-5 31 DEC 2015 15.11-6 31 DEC 2015 15.12-1 31 DEC 2015 15.12-2 31 DEC2015 Attachment 2 - Page 51 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 15.12-3 31 DEC 2015 15.12-4 31 DEC 2015 15.13-1 31 DEC 2015 15.13-2 31 DEC 2015 15.13-3 31 DEC 2015 15.13-4 31 DEC 2015 15.13-5 31DEC2015 15.13-6 31 DEC 2015 15.14-1 31 DEC 2015 15.14-2 31 DEC 2015 15.14-3 31 DEC 2015 15.14-4 31 DEC2015 15.14-5 31 DEC 2015 15.14-6 31 DEC 2015 15.14-7 31 DEC2015 Yes 15.14-8 31 DEC 2015 15.14-9 31 DEC 2015 15.14-10 31 DEC2015 15.14-11 31 DEC 2015 15.14-12 31 DEC 2015 Yes 15.14-13 31 DEC 2015 Yes 15.14-14 31 DEC 2015 15.14-15 31 DEC 2015 15.14-16 31 DEC 2015 15.14-17 31 DEC 2015 Yes 15.14-18 31 DEC 2015 15.14-19 31 DEC 2015 Yes 15-14.20 31 DEC 2015 15.15-1 31 DEC 2015 15.15-2 31 DEC 2015 15.16-1 31 DEC 2015 Yes 15.16-2 31 DEC 2015 15.16-3 31 DEC 2015 15.16-4 31 DEC 2015 15.16-5 31DEC2015 15.16-6 31 DEC 2015 Yes 15.16-7 31 DEC 2015 Yes 15.16-8 31DEC2015 Attachment 2 - Page 52 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 15.17-1 31 DEC 2015 Yes 15.17-2 31 DEC 2015 15.17-3 31 DEC 2015 15.17-4 31 DEC 2015 15.18-1 31 DEC 2015 15.18-2 31 DEC 2015 Chapter 15 Tables Table 15-1 (Page 1 of 1) 31 DEC 2010 Table 15-2 (Page 1 of 1) 31 DEC 2013 Table 15-3 (Page 1 of 1) 31 DEC 2008 Table 15-4 (Page 1 of 1) 31 DEC 2004 Table 15-5 (Page 1 of 1) 31 DEC 2003 Table 15-6 (Page 1 of 1) 31 DEC 2000 Table 15 15-14 (Page 1 of 1) 31 DEC 2000 Table 15-15 (Page 1 of 4) 31 DEC 2012 Table 15-15 (Page 2 of 4) 31 DEC 2012 Table 15-15 (Page 3 of 4) 31 DEC 2012 Table 15-15 (Page 4 of 4) 31 DEC 2012 Table 15-16 (Page 1 of 2) 31 DEC 2012 Table 15-16 (Page 2 of 2) 31 DEC 2012 Table 15-17-15-27 (Page 1of1) 31 DEC 2000 Table 15-28 (Page 1 of 1) 31 DEC 2015 Yes Table 15-29 (Page 1 of 1) 31 DEC2015 Yes Table 15-30 (Page 1 of 1) 31 DEC 2015 Yes Table 15-31 (Page 1 of 1) 31 DEC 2008 Table 15-32 (Page 1 of 2) 31 DEC 2015 Yes Table 15-32 (Page 2 of 2) 31 DEC 2015 Yes Table 15-33 (Page 1 of 1) 31DEC2013 Table 15-34 (Page 1 of 8) 31 DEC 2015 Yes Table 15-34 (Page 2 of 8) 31 DEC 2015 Yes Table 15-34 (Page 3 of 8) 31 DEC 2015 Yes Table 15-34 (Page 4 of 8) 31 DEC 2015 Yes Table 15-34 (Page 5 of 8) 31 DEC 2015' Yes Table 15-34 (Page 6 of 8) 31 DEC 2015 Yes Table 15-34 (Page 7 of 8) 31 DEC 2015 Yes Table 15-34 (Page 8 of 8) 31 DEC 2015 Yes Table 15-35 (Page 1 of 2) 31DEC2012 Attachment 2 - Page 53 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Table 15-35 (Page 2 of 2) 31 DEC 2012 Table 15-36 (Page 1 of 1) 31 DEC 2013 Table 15-37 (Page 1 of 1) 31 DEC 2008 Table 15-38 (Page 1 of 1) 31 DEC 2003 Table 15-39 (Page 1 of 1) 31 DEC 2015 Yes Table 15-40 (Page 1 of 1) 31 DEC 2008 Table 15-41 (Page 1 of 1) 31 DEC 2003 Table 15-42 (Page 1 of 1) 31 DEC 2003 Table 15-43 (Page 1 of 1) 31 DEC 2003 Table 15-44 (Page 1 of 1) 31 DEC 2008 Table 15-45 (Page 1 of 1) 31 DEC 2010 Table 15-46 (Page 1 of 1) 31 DEC 2013 Table 15-47 (Page 1 of 1) 31 DEC 2011 Table 15-48 (Page 1 of 1) 31 DEC 2003 Table 15-49 (Page 1 of 1) 31 DEC 2008 Table 15-50 (Page 1 of 2) 31 DEC 2009 Table 15-50 (Page 2 of 2) 31 DEC 2009 Table 15-51 (Page 1 of 1) 31 DEC 2009 Table 15-52-15-55 (Page 1 of 1) 31 DEC 2003 Table 15-56 (Page 1 of 1) 31 DEC 2014 Table 15-57 (Page 1 of 1) 31 DEC 2014 Table 15-58 (Page 1 of 1) 31 DEC 2003 Table 15-59 (Page 1 of 1) 31 DEC 2001 Table 15-60 (Page 1 of 1) 31 DEC 2014 Table 15-61 (Page 1 of 2) 31 DEC 2009 Table 15-61 (Page 2 of 2) 31 DEC 2009 Table 15-62 (Page 1 of 2) 31 DEC 2014 Table 15-62 (Page 2 of 2) 31 DEC 2014 Table 15-63 (Page 1 of 2) 31 DEC 2014 Table 15-63 (Page 2 of 2) 31 DEC 2014 Table 15-64 (Page 1 of 1) 31 DEC 2011 Table 15-65 (Page 1 of 1) 31 DEC 2012 Table 15-66 (Page 1 of 1) 31 DEC 2012 Table 15-67 (Page 1 of 1) 31 DEC 2014 Table 15-68 (Page 1 of 2) 31 DEC 2014 Table 15-68 (Page 2 of 2) 31 DEC 2014 Chapter 15 Figures Attachment 2 - Page 54 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 15-1 (Page 1 of 1) 31 DEC 2013 Figure 15-2 (Page 1 of 1) 31 DEC 2013 Figure 15-3 (Page 1 of 1) 31 DEC 2013 Figure 15-4 (Page 1 of 1) 31 DEC2013 Figure 15-5 (Page 1 of 1) 31 DEC 2013 Figure 15-6 (Page 1 of 1) 31 DEC 2013 Figure 15-7 10 (Page 1of1) 31 DEC 2000 Figure 15-11(Page1of1) 31 DEC 2003 Figure 15-12 (Page 1 of 1) 31 DEC 2003 Figure 15-13 (Page 1 of 1) 31 DEC 2003 Figure 15-14 (Page 1 of 1) 31 DEC 2003 Figure 15-15 (Page 1 of 1) 31 DEC 2003 Figure 15-16 (Page 1 of 1) 31 DEC 2003 Figure 15-17 (Page 1 of 1) 31 DEC 2003 Figure 15-18 (Page 1of1) 31 DEC2015 Yes Figure 15-19 (Page 1 of 1) 31 DEC 2008 Figure 15-20 (Page 1 of 1) 31 DEC 2008 Figure 15-21 (Page 1 of 1) 31 DEC 2008 Figure 15-22 (Page 1 of 1) 31 DEC 2008 Figure 15-23 (Page 1 of 1) 31 DEC 2008 Figure 15-24 (Page 1 of 1) 31 DEC2013 Figure 15-25 (Page 1 of 1) 31 DEC 2003 Figure 15-26 (Page 1 of 1) 31 DEC 2010 Figure 15-27 (Page 1 of 1) 31 DEC 2010 Figure 15-28 (Page 1 of 1) 31DEC2010 Figure 15-29 (Page 1 of 1) 31 DEC 2013 Figure 15-30 (Page 1 of 1) 31 DEC 2013 Figure 15-31 (Page 1 of 1) 31 DEC 2013 Figure 15-32 (Page 1 of 1) 31 DEC 2013 Figure 15-33 (Page 1 of 1) 31 DEC 2013 Figure 15-34 (Page 1 of 1) 31 DEC 2013 Figure 15-35 (Page 1 of 1) 31 DEC2013 Figure 15-36 (Page 1 of 1) 31 DEC 2013 Figure 15 15-39 (Page 1 of 1) 31 DEC 2000 Figure 15-40 (Page 1 of 1) 31 DEC 2003 Figure 15-41 (Page 1 of 1) 31 DEC 2003 Figure 15-42 (Page 1 of 1) 31 DEC 2003 Figure 15-43 (Page 1 of 1) 31 DEC 2003 Attachment 2 - Page 55 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 15-44 (Page 1 of 1) 31 DEC 2000 Figure 15 15-49 (Page 1 of 1) 31 DEC 2000 Figure 15-50 (Page 1 of 1) 31 DEC 2008 Figure 15 15-79 (Page 1 of 2) 31 DEC 2000 Figure 15 15-79 (Page 2 of 2) 31 DEC 2000 Figure 15-80 (Page 1 of 1) 31 DEC 2000 Figure 15-81-15-88 (Page 1of1) 31 DEC 2000 Figure 15-89 (Page 1 of 1) 31 DEC 2003 Figure 15 15-111 (Page 1 of 2) 31 DEC 2000 Figure 15 15-111 (Page 2 of 2) 31 DEC 2000 Figure 15-112 (Page 1 of 1) 31 DEC 2014 Figure 15-113 (Page 1 of 1) 31 DEC 2003 Figure 15-114 (Page 1 of 1) 31 DEC 2013 Figure 15-115 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-116 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-117 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-118 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-119 (Page 1of1) 31 DEC 2003 Figure 15-120 (Page 1 of 1) 31 DEC 2003 Figure 15-121(Page1 of 1) 31 DEC 2003 Figure 15-122 (Page 1 of 1) 31 DEC 2003 Figure 15-123 (Page 1of1) 31 DEC 2013 Figure 15-124 (Page 1 of 1) 31 DEC 2003 Figure 15-125 (Page 1 of 1) 31 DEC 2003 Figure 15-126 (Page 1of1) 31 DEC 2003 Figure 15-127 (Page 1of1) 31 DEC 2003 Figure 15-128 (Page 1 of 1) 31 DEC 2003 Figure 15-129 (Page 1of1) 31 DEC 2013 Figure 15-130 (Page 1 of 1) 31 DEC 2003 Figure 15-131(Page1of1) 31 DEC 2003 Figure 15-132 (Page 1 of 1) 31 DEC 2003 Figure 15-133 (Page 1of1) 31 DEC 2003 Figure 15-134 (Page 1of1) 31 DEC 2003 Figure 15-135 (Page 1 of 1) 31 DEC 2008 Figure 15-136 (Page 1 of 1) 31 DEC 2008 Figure 15-137 (Page 1of1) 31 DEC 2008 Figure 15-138 (Page 1of1) 31 DEC 2008 Figure 15-139 (Page 1 of 1) 31 DEC 2008 Attachment 2 - Page 56 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 15-140(Page1of1) 31 DEC 2008 Figure 15-141 (Page 1 of 1) 31 DEC 2011 Figure 15-142 (Page 1 of 1) 31 DEC 2000 Figure 15-143 (Page 1 of 1) 31 DEC 2010 Figure 15-144 (Page 1of1) 31 DEC 2013 Figure 15-145 (Page 1of1) 31 DEC 2013 Figure 15-146 (Page 1of1) 31 DEC 2013 Figure 15-147 (Page 1of1) 31 DEC 2013 Figure 15-148 (Page 1 of 1) 31 DEC 2013 Figure 15-149 (Page 1of1) 31 DEC 2013 Figure 15-150 (Page 1 of 1) 31 DEC 2011 Figure 15-151(Page1of1) 31 DEC 2011 Figure 15-152 (Page 1of1) 31 DEC 2011 Figure 15-153 (Page 1 of 1) 31 DEC 2011 Figure 15-154 (Page 1 of 1) 31 DEC 2011 Figure 15-155 (Page 1 of 1) 31 DEC 2011 Figure 15-156 (Page 1of1) 31 DEC 2011 Figure 15-157 (Page 1 of 1) 31 DEC 2003 Figure 15-158 (Page 1 of 1) 31 DEC 2003 Figure 15-159 (Page 1 of 1) 31 DEC 2003 Figure 15-160 (Page 1 of 1) 31 DEC 2003 Figure 15-161(Page1of1) 31 DEC 2003 Figure 15-162 (Page 1 of 1) 31 DEC 2003 Figure 15-163 (Page 1of1) 31 DEC 2003 Figure 15-164 (Page 1 of 1) 31 DEC 2003 Figure 15-165 (Page 1 of 1) 31 DEC 2003 Figure 15-166 (Page 1of1) 31 DEC 2003 Figure 15-167 (Page 1 of 1) 31 DEC 2013 Figure 15-168 (Page 1 of 1) 31 DEC 2003 Figure 15-169 (Page 1of1) 31 DEC 2003 Figure 15-170 (Page 1 of 1) 31 DEC 2011 Figure 15-171 (Page 1 of 1) 31 DEC 2003 Figure 15-172 (Page 1 of 1) 31 DEC 2003 Figure 15-173 (Page 1 of 1) 31 DEC 2003 Figure 15-174 (Page 1of1) 31 DEC 2014 Figure 15-175 (Page 1of1) 31DEC2003 Figure 15-176 (Page 1 of 1) 31 DEC 2001 Figure 15-177 (Page 1 of 1) 31 DEC 2003 Attachment 2 - Page 57 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update Figure 15-178-15-212 (Page 1 of 2) 31 DEC 2014 Figure 15-178-15-212 (Page 2 of 2) 31 DEC 2014 Figure 15-213 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-214 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-215 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-216 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-217 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-218 (Page 1 of 1) 31 DEC 2015 Yes Figure 15-219 (Page 1 of 1) 31 DEC 2011 Figure 15-220 (Page 1 of 1) 31 DEC 2011 Figure 15-221 (Page 1 of 1) 31 DEC 2011 Figure 15-222 (Page 1 of 1) 31 DEC 2011 Figure 15-223 (Page 1 of 1) 31DEC2011 Figure 15-224 (Page 1 of 1) 31 DEC 2011 Figure 15-225 (Page 1 of 1) 31 DEC 2011 Figure 15-226 (Page 1 of 1) 31 DEC 2011 Figure 15-227 (Page 1 of 1) 31 DEC 2011 Figure 15-228 (Page 1 of 1) 31 DEC 2011 Figure 15-229 (Page 1 of 1) 31 DEC 2011 Figure 15-230 (Page 1 of 1) 31 DEC 2011 Figure 15-231 (Page 1 of 1) 31 DEC 2011 Figure 15-232 (Page 1 of 1) 31 DEC 2011 Chapter 16 16-1 31 DEC 2015 16.0-1 31 DEC 2015 16.0-2 31 DEC 2015 Chapter 17 17-1 31 DEC 2015 17.0-1 31 DEC 2015 Chapter 18 18-1 31 DEC 2015 18-2 31 DEC 2015 18-3 31 DEC 2015 18.0-1 31 DEC 2015 18.0-2 31 DEC 2015 Attachment 2 - Page 58 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 18.1-1 31 DEC 2015 18.1-2 31 DEC 2015 18.2-1 31 DEC 2015 18.2-2 31DEC2015 18.2-3 31 DEC 2015 18.2-4 31 DEC 2015 18.2-5 31 DEC 2015 18.2-6 31 DEC 2015 18.2-7 31 DEC 2015 18.2-8 31 DEC 2015 18.2-9 31DEC2015 18.2-10 31 DEC 2015 18.2-11 31 DEC 2015 18.2-12 31 DEC 2015 18.3-1 31 DEC 2015 18.3-2 31 DEC 2015 18.3-3 31 DEC 2015 18.3-4 31 DEC 2015 18.3-5 31 DEC 2015 18.3-6 31 DEC 2015 18.3-7 31 DEC 2015 18.3-8 31 DEC 2015 18.3-9 31 DEC 2015 18.3-10 31 DEC 2015 18.3-11 31 DEC 2015 18.3-12 31 DEC 2015 18.3-13 31 DEC 2015 18.3-14 31 DEC 2015 18.3-15 31 DEC 2015 18.3-16 31 DEC 2015 18.3-17 31 DEC 2015 18.3-18 31 DEC 2015 18.3-19 31 DEC 2015 18.3-20 31 DEC 2015 18.3-21 31 DEC 2015 18.3-22 31 DEC 2015 18.3-23 31 DEC 2015 18.3-24 31 DEC 2015 Attachment 2 - Page 59 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Page Effective Date Changed 2015 Update 18.3-25 31 DEC 2015 18.3-26 31 DEC 2015 18.3-27 31 DEC 2015 18.3-28 31 DEC 2015 18.3-29 31 DEC 2015 18.3-30 31 DEC 2015 18.3-31 31 DEC 2015 18.3-32 31 DEC 2015 18.3-33 31 DEC 2015 18.3-34 31 DEC 2015 18.3-35 31 DEC2015 18.3-36 31 DEC 2015 18.4-1 31 DEC 2015 18.4-2 31 DEC 2015 Chapter 18 Tables Table 18-1 (Page 1 of 4) 31 DEC 2014 Table 18-1 (Page 2 of 4) 31 DEC 2014 Table 18-1 (Page 3 of 4) 31 DEC 2014 Table 18-1 (Page 4 of 4) 31 DEC 2014 Attachment 2 - Page 60 of 60
ONS-2016-061 Document Control Desk June 30, 2016 Attachment 3 Update Insertion Instructions (for hardcopy distribution only)
(2 pages attached)
ONS-2016-061 Document Control Desk June 30, 2016 Update Insertion Instructions (for hardcopy distribution only)
- 1. Replace 2014 List of Effective Pages (LOEP) for Tables and Figures with the 2015 LOEP for Tables and Figures.
- 2. Replace entire text portions for each chapter with the updated text portion (including the Table of Contents, List of Figures, and List of Tables).
- 3. Update Tables and Figures according to the instructions below.
Remove Insert Chapter 6 Table 6-19 (1 page) Table 6-19 (1 page)
Chapter 8 Figure 8-1 (1 page) Figure 8-1 (1 page)
Figure 8-2 (1 page) Figure 8-2 (1 page)
Figure 8-3 (2 pages) Figure 8-3 (2 pages)
Figure 8-4 (3 pages) Figure 8-4 (3 pages)
Chapter 9 Table 9-2 (2 pages) Table 9-2 (2 pages)
Table 9-20 (1 page) Table 9-20 (1 page)
Figure 9-5 (1 page) Figure 9-5 (1 page)
Figure 9-12 (1 page) Figure 9-12 (1 page)
Figure 9-17 (1 page) Figure 9-17 (1 page)
Figure 9-24 (1 page) Figure 9-24 (1 page)
Figure 9-44 (1 page) Figure 9-44 (1 page)
Figure 9-45 (1 page) Figure 9-45 (1 page)
Figure 9-46 (1 page) Figure 9-46 ( 1 page)
Chapter 10 Figure 10-2 (1 page) Figure 10-2 (1 page)
Figure 10-4 (1 page) Figure 10-4 (1 page)
Figure 10-7 (1 page) Figure 10-7 (1 page)
Figure 10-8 (1 page) Figure 10-8 ( 1 page)
Chapter 15 Table 15-28 (1 page) Table 15-28 (1 page)
Table 15-29 (1 page) Table 15-29 (1 page)
Table 15-30 (1 page) Table 15-30 (1 page)
Table 15-32 (2 pages) Table 15-32 (2 pages)
Table 15-34 (8 pages) Table 15-34 (8 pages)
Table 15-39 (1 page) Table 15-39 (1 page)
Figure 15-18 (1 page) Figure 15-18 (1 page)
Figure 15-115 (1 page) Figure 15-115 (1 page)
Figure 15-116 (1 page) Figure 15-116 (1 page)
Figure 15-117 (1 page) Figure 15-117 (1 page)
Figure 15-118 (1 page) Figure 15-118 (1 page)
Attachment 3 - Page 1 of 2
ONS-2016-061 Document Control Desk June 30, 2016 Remove Insert Figure 15-213 (1 page) Figure 15-213 (1 page)
Fig*ure 15-214 ( 1 page) Figure 15-214 (1 page)
Figure 16-215 (1 page) Figure 16-215 (1 page)
Figure 15-216 (1 page) Figure 15-216 (1 page)
Figure 15-217 (1 page) Figure 15-217 (1 page)
Figure 15-218 (1 page) Figure 15-218 (1 page)
Attachment 3 - Page 2 of 2
ONS-2016-061 Document Control Desk June 30, 2016 Attachment 4 List of Removed Items (1 page attached)
ONS-2016-061 Document Control Desk June 30, 2016 List of Removed Items
- 1. Section 6.5.1.4 - Test and Inspections Deleted the last paragraph which was a single sentence which stated, "Testing and inspection of the system is as required by the Technical Specifications."
This change is based on the NRG-approved License Amendment No, 338, 339, and 339; Adoption of Alternate Source Term, approved 06/01/2004. This amendment deleted information relative to reactor building penetration room ventilation.
- 2. Section 15.16. 7 - References Deleted Reference 17, "OSC-123 (rev. 1), "Activity on Filter RB Hydrogen Purge" This change is based on NRC exemption from the hydrogen recombiner requirements in SER dated 07/17/2001.
Attachment 4 - Page 1 of 1
ONS-2016-061 Document Control Desk June 30, 2016 Attachment 5 10 CFR 50.59 Report (7 pages attached)
ONS-2016-061 Document Control Desk June 30, 2016
Title:
EC 112282 - Revision 0 - 230KV Red Bus Differential Upgrade - Add a Second Set of Bus Differential relay Protection (AR 1348448 I 448448)
Summary:
Engineering Change (EC)-112282 Rev. 0 adds a redundant train of differential relaying protection for the red bus in the ONS 230 kV Switchyard. With the existing design, only a single train of differential relaying protection exists on the red bus. With the existing design a relay failure can result in a large loss of localized generation. The initiating event would be a phase to ground bus fault with failed bus differential relaying. A phase to ground fault with the failure of the associated single phase differential relay to operate would be expected to result in the de-energizing of the ONS 230kV switchyard by time delayed relays. At a minimum, a loss of generation for ONS Units 1 and 2 and a loss ofKeowee Units 1 and 2 would be expected. After the redundant train of differential eelay is installed and tested it will provide additional protection so that the loss of a single train, coupled with a fault within the protected zone, will not lead to such adverse effects.
This change is considered a NERC (Northeast Electric Reliability Council) requirement since NERC expects relaying designs at power generation plants to preclude single failures that affect the operation of the plant or the external grid. This change was reviewed and was found to fall within the boundary of the 10 CFR 50.59 scope for changes made to the ONS station that did not require prior NRC approval.
Title:
Change from End-of-Cycle Hot Full Power Moderator Temperature Coefficient of
-35.0 pcm/F to -38.0 pcm/F (AR 1350547 I 450547)
Summary:
The proposed activities are revisions to the Oconee Nuclear Station (ONS) UFSAR Table 15-34 and UFSAR Section 15.5 including associated Tables and Figures. End-of-Cycle (BOC) hot full power Moderator Temperature Coefficient (MTC) values were changed from -35.0E-5 ~k/k/ 0 P to -38.0E-5 ~k/k/ 0 P for both UFSAR Section 15.5 (Cold Water Accident) and Section 15.9 (Steam Generator Tube Rupture Accident). However, there was only an impact to UFSAR Section 15.5 and no impact to UFSAR Section 15.9.
A summary of the UFSAR changes include:
ONS UFSAR Table 15-34 (Summary of Input Parameters for Accident Analyses Using Computer Codes) for MTC value for Cold Water Accident (UFSAR Section 15 .5) and Steam Generator Tube Rupture (UFSAR Section 15.9) and associated impacts to Section 15.5:
(i) an update to Table 15-34 (Summary of Input Parameters for Accident Analysis Using 0
Computer Codes) to address a more negative MTC from -35.0E-5~k/k/ P to
-38.0E-5 ~k/k/ P.0 (ii) the associated analytical impacts of a more negative MTC on UFSAR Section 15.5 (Cold Water Accident) plots (Figures), sequence of events table, and text.
The changes to the calculations producing these results are summarized as:
Attachment 5 - Page 1 of 7
ONS-2016-061 Document Control Desk June 30, 2016 UFSAR Section 15.5 - Cold Water Accident:
(a) an analysis change for a revised EOC MTC of -35.0E-5 Lik/k/°F to -38.0E-5 Llk/k/°F.
This change resulted in new figures for this event and a change to the sequence of events table.
(b) Minor modeling changes to more accurately model the secondary system by including pieces of the Integrated Control System (ICS) and the addition of volumes to model the steam chest and condenser. In the cold water accident, the net effect of these minor modeling changes is increased steaming which resulted in reduced cold leg temperatures (i.e., greater cooldown) which are apparent by comparing cold leg temperature response prior to peak heat flux for current and former revisions. For negative MTC values, a greater cooldown will result in a larger increase in power in the analysis.
UFSAR Section 15.9 - Steam Generator Tube Rupture:
(c) an analysis change for a revised EOC MTC of -35.0E-5 Lik/k-°F to -38.0E-5 Llk/k-°F.
This change resulted in essentially no change to the integrated steam releases. The dose analyses (Reference 10 Appendix H) were bounded and were not impacted and there are no other impacts to UFSAR Section 15.9.
Per NEI 96-07, Rev. 1, this activity required a 10 CFR 50.59 evaluation because the increase in negative MTC adversely affects the design function of an SSC as described in the UFSAR. The change in this parameter (EOC MTC) does not impact the frequency of occurrence of an accident previously evaluated or the malfunction of an SSC important to safety. Since the MDNBR (minimum departure from nucleate boiling ratio) limit was not exceeded in any of the affected accidents and the steam generator tube rupture (SGTR) dose analysis was not impacted, there could be no dose impact on any accidents or SSC's. There are no physical changes to any SSC's, no different modes of operation, no procedure changes, or no failure of the design function from this activity. Thus, the proposed activity does not create the possibility for an accident of a different type or malfunction of an SSC important to safety with a different result. Since the MDNBR limit is not violated in any of the affected accidents, the fission product barrier for the RCS is also not exceeded or altered. The MTC change is a change in input. The use of the revised control system in the cold water accident described in (b) is a change to an element of the methodology. Since this change increased the cooldown which results in a higher power in the analysis, this change causes the results to be closer to the MDNBR limit. Thus, this change is conservative and does not result in a departure from a method of evaluation described in the UFSAR used in establishing the design bases or in the safety analyses.
Title:
EC 96549, Revision 0 - Unit 3 Main Power System Protective Relaying Upgrade (AR 1351688)
Summary:
The purpose of Engineering Change (EC) 96549 is to improve the reliability, security, and monitoring capabilities of the protective relaying for the main power system. This upgrade will be accomplished by replacing most of the existing protective relays with a set of multifunction Attachment 5 - Page 2 of 7
ONS-2016-061 Document Control Desk June 30, 2016 microprocessor-based relays. In addition to replacing the protective functions of the existing relays, the new microprocessor-based relays will include additional protective functions that are not provided by the existing relaying scheme. The manner in which the main power protective relaying can impact operability of the offsite power sources is unchanged. There is no impact on the ONS Technical Specifications.
The Main Power System and its associated protective relaying are non-safety systems but are designed to support accident mitigation functions. Because they are backed by the safety-related onsite emergency power system, the Main Power System is not required and is not qualified to withstand external events; however, either operation or misoperation of components within these systems can directly or indirectly lead to a turbine trip, analyzed in UFSAR Section 15.8. A failure or delay in the response in the primary protective relaying can also lead to partial or complete loss of non-emergency AC power to the station auxiliaries. The proposed change has been evaluated relative to each of the eight (8) evaluation questions in 10 CFR 50.59.
Considering the probability and consequences of the various hardware and software failure modes of the proposed changes, the evaluation concluded that this change can be implemented without prior NCR approval.
Title:
EC 91849 - Revision 20 - PSW Power to Unit 2 Pressurizer Heaters and Vital I&C Battery Chargers (AR 1931415)
Summary:
This 10 CFR 50.59 evaluation addresses Engineering Change (EC) 91849, Rev. 20, which has been developed to provide a backup power supply to Unit 2 Reactor Coolant System (RCS) pressurizer heaters by installing new Protected Service Water (PSW) system power feeds to existing Motor Control Centers (MCCs) 2XJ, 2XI and 2XK, which in turn power the following pressurizer heaters:
Bank 1, Group 2A Bank 1, Group 2K Bank 2, Group 2D Bank 3, Group 2F Bank 3, Group 2G Bank 4, Group 21 Bank 4, Group 2J The installation of the new PSW system power feeds to existing MCCs 2XJ, 2XI and 2XK will be accomplished by installing three new manual power transfer switches (2PSWSXTRN003, 2PSWSXTRN004 and 2PSWSXTRN005) in the Unit 2 East Penetration Room, including associated controls and cable. The power will be supplied from PSW 600V load center PSWLXPX13, breakers 2C, 4B and 2D in the PSW Building (installed by EC 91871).
In addition, EC 91849 will provide backup power to Unit 2, 125 VDC I&C power system battery chargers 2CA and 2CB from the PSW system by installing two new automatic power transfer switches (2PSWSXTRN001 and 2PSWSXTRN002) in the Unit 2 Electrical Equipment Room, including associated controls and cable. The power will be supplied from PSW MCC 2XPSWA, breakers 2D and 3F (installed by EC 91873).
Attachment 5 - Page 3 of 7
ONS-2016-061 Document Control Desk June 30, 2016 AR 1930012 is the 10 CFR50.59 screening that was prepared for EC 91849, Rev. 20. The screening concluded that only one aspect of EC 91849 resulted in an adverse effect to the design function of a Structure, System, or Component (SSC), as described in the UFSAR. Therefore, the scope ofthis 10 CFR50.59 Evaluation addressed the components installed by EC 91849 that resulted in this adverse effect.
10 CFR 50.59 Screening AR 1930012 concluded that the installation of new automatic power transfer switches 2PSWSXTRNOO 1 and 2PSWSXTRN002 will have an adverse effect on the design function of Unit 2 125 VDC Instrumentation & Control (l&C) power system battery chargers 2CA and 2CB because:
- 1. Each automatic power transfer switch is controlled by a digital controller that is integral to the power transfer switch. Since the two new automatic power transfer switches are identical to each other (i.e., same make/model) and since the power transfer switches will provide the normal power supply to safety-related, redundant battery chargers 2CA and 2CB, EC 91849 will result in battery chargers 2CA and 2CB potentially being susceptible to a software common mode failure that is initiated by the digital controller.
- 2. The automatic power transfer switches have failure modes which may result in the loss of the normal, credited power supply to battery chargers 2CA and 2CB.
The design, installation and testing of new automatic power transfers switches 2PSWSXTRNOO 1 and 2PSWSXTRN002, including that of the software within the automatic power transfer switch digital controllers, will ensure that a common mode failure of the automatic power transfer switches is not credible.
Postulated failures of the new automatic power transfer switches will only affect the ability of battery chargers 2CA and 2CB to provide power to the associated 125 VDC bus and to charge the associated battery. Failures with this result have been previously considered and in no instance do they affect the ability of the 125 VDC I&C power system to provide an uninterruptable supply of power to the components powered from the associated buses.
The new automatic power transfer switches will not create a new malfunction or accident with a different result than previously evaluated and will not affect design basis limits for fission product barriers.
A revision to the ONS Technical Specifications will not be required.
Title:
EC 91826 - Revision 11 - Unit 1 PSW Power to Pressurizer Heaters and Vital l&C Battery Chargers (AR 1931950)
Summary:
This 10 CFR 50.59 evaluation addresses Engineering Change (EC) 91826, Rev. 11, which has been developed to provide a backup power supply to Unit 1 Reactor Coolant System (RCS) pressurizer heaters by installing new Protected Service Water (PSW) system power feeds to existing Motor Control Centers (MCCs) lXJ and lXK, which in tum power the following pressurizer heaters:
Bank 1, Group A Attachment 5 - Page 4 of 7
ONS-2016-061 Document Control Desk June 30, 2016 Bank 1, Group K Bank 2, Group D Bank 3, Group G Bank 4, Group J The installation of the new PSW system power feeds to existing MCCs lXJ and lXK will be accomplished by installing two new manual power transfer switches (1PSWSXTRN004 and 1PSWSXTRN005) in the Unit 1 East Penetration Room, including all associated controls and cable. The power will be supplied from PSW 600V load center PSWLXPX13, breakers 2B and 3B in the PSW Building (installed by EC 91871).
In addition, EC 91826 will provide backup power to Unit 1 125 VDC l&C power system battery chargers 1CA and 1CB from the PSW system by installing two new automatic power transfer switches (lPSWSXTRNOOl and 1PSWSXTRN002) in the Unit 1 Electrical Equipment Room, including associated controls and cable. The power will be supplied from PSW MCC lXPSW, breakers 4B and 4C (installed by EC 91873).
AR 1931400 is the 10 CFR 50.59 screening that was prepared for EC 91826, Rev. 11. The screening concluded that only one aspect of EC 91826 resulted in an adverse effect to the design function of an SSC, as described in the UFSAR. Therefore, the scope of this 10 CPR 50.59 evaluation addressed the components installed by EC 91826 that resulted in this adverse effect.
10 CFR 50.59 screening AR 1931400 concluded that the installation of new automatic power transfer switches lPSWSXTRNOOl and 1PSWSXTRN002 will have an adverse effect on the design fun~tion of Unit 1, 125 VDC I&C power system battery chargers lCA and lCB because:
- 1. Each automatic power transfer switch is controlled by a digital controller that is integral to the. power transfer switch. Since the two new automatic power transfer switches are identical to each other (i.e., same make/model) and since the power transfer switches will provide the normal power supply to safety-related, redundant battery chargers 1CA and 1CB, EC 91826 will result in battery chargers 1CA and 1CB potentially being susceptible to a software common mode failure that is initiated by the digital controller.
- 2. The automatic power transfer switches have failure modes which may result in the loss of the normal, credited power supply to battery chargers lCA and lCB.
The design, installation and testing of new automatic power transfers switches lPSWSXTRNOOl and 1PSWSXTRN002, including that of the software within the automatic power transfer switch digital controllers, will ensure that a common mode failure of the automatic power transfer switches is not credible.
Postulated failures of the new automatic power transfer switches will only affect the ability of battery chargers lCA and lCB to provide power to the associated 125 VDC bus and to charge the associated battery. Failures with this result have been previously considered and in no instance do they affect the ability of the 125 VDC l&C power system to provide an uninterruptable supply of power to the components powered from the associated buses.
Attachment 5 - Page 5 of 7
ONS-2016-061 Document Control Desk June 30, 2016 The new automatic power transfer switches will not create a new malfunction or accident with a different result than previously evaluated and will not affect design basis limits for fission product barriers.
A revision to the ONS Technical Specifications will not be required.
Title:
EC 91859 Revision 11- Unit 3 PSW Power to Pressurizer Heaters and Vital l&C Battery Chargers (AR 1933299)
Summary:
This 10 CPR 50.59 evaluation addresses Engineering Change (EC) 91859, Rev. 11, which has been developed to provide a backup power supply to Unit 3 Reactor Coolant System ( RCS) pressurizer heaters by installing new Protected Service Water (PSW) system power feeds to existing Motor Control Centers (MCCs) 3XJ, 3XI and 3XK, which in turn power the following pressurizer heaters:
Bank 1, Group 3A Bank 1, Group 3K Bank 2, Group 3D Bank 3, Group 3P Bank 3, Group 3G Bank 4, Group 31 Bank 4, Group 3J The installation of the new PSW system power feeds to existing MCCs 3XJ, 3XI and 3XK. will be accomplished by installing three new manual power transfer switches (3PSWSXTRN003, 3PSWSXTRN004 and 3PSWSXTRN005) in the Unit 3 East Penetration Room, including associated controls and cable. The power will be supplied from PSW 600V load center PSWLXPX13, breakers lB, ID and 2A in the PSW Building (installed by EC 91871).
In addition, EC 91859 will provide backup power to Unit 3, 125 VDC I&C power system battery chargers 3CA and 3CB from the PSW system by installing two new automatic power transfer switches (3PSWSXTRN001 and 3PSWSXTRN002) in the Unit 3 Electrical Equipment Room, including associated controls and cable. The power will be supplied from PSW MCC 3XPSW, breakers 4B and 4C (installed by EC 91873).
AR 1932611 is the 10 CPR 50.59 screening that was prepared for EC 91859, Rev. 11. The screening concluded that only one aspect of EC 91859 resulted in an adverse effect to the design function of an SSC, as described in the UFSAR. Therefore, the scope of this 1OCPR50.59 Evaluation addressed the components installed by EC 91859 that resulted in this adverse effect.
10 CPR 50.59 Screening AR 1932611 concluded that the installation of new automatic power transfer switches 3PSWSXTRN001and3PSWSXTRN002 will have an adverse effect on the design function of Unit 3, 125 VDC I&C power system battery chargers 3CA and 3CB because:
- 1. Each automatic power transfer switch is controlled by a digital controller that is integral to the power transfer switch. Since the two new automatic power transfer switches are identical to each other (i.e., same make/model) and since the power transfer switches will provide the normal power supply to safety-related, redundant battery chargers 3CA and Attachment 5 - Page 6 of 7
ONS-2016-061 Document Control Desk June 30, 2016 3CB, EC 91859 will result in battery chargers 3CA and 3CB potentially being susceptible to a software common mode failure that is initiated by the digital controller.
- 2. The automatic power transfer switches have failure modes which may result in the loss of the normal, credited power supply to battery chargers 3CA and 3CB.
The design, installation and testing of new automatic power transfers switches 3PSWSXTRNOO 1 and 3PSWSXTRN002, including that of the software within the automatic power transfer switch digital controllers, will ensure that a common mode failure of the automatic power transfer switches is not credible.
Postulated failures of the new automatic power transfer switches will only affect the ability of battery chargers 3CA and 3CB to provide power to the associated 125 VDC bus and to charge the associated battery. Failures with this result have been previously considered and in no instance do they affect the ability of the 125 VDC l&C power system to provide an uninterruptable supply of power to the components powered from the associated buses.
The new automatic power transfer switches will not create a new malfunction or accident with a different result than previously evaluated and will not affect design basis limits for fission product barriers.
A revision to the ONS Technical Specifications will not be required.
Attachment 5 - Page 7 of 7