ML110420306

From kanterella
Jump to navigation Jump to search
GE Hitachi Nuclear Energy Report, NEDC-33532, Revision 2, Pilgrim Nuclear Power Station Safety Valve Setpoint Increase, Enclosure 4 to 2.11.007
ML110420306
Person / Time
Site: Pilgrim
Issue date: 01/31/2011
From:
GE-Hitachi Nuclear Energy Americas
To:
Office of Nuclear Reactor Regulation
References
2.11.007 DRF 0000-0108-5986-1, NEDC-33532, Rev 2
Download: ML110420306 (72)


Text

ENCLOSURE 4 To Entergy Letter No. 2.11.007 (Non-Proprietary Version)

GE Hitachi Nuclear Energy Report, NEDC-33532P, "Pilgrim Nuclear Power Station Safety Valve Setpoint Increase", Rev. 2, January 2011 (71 Pages)

HITACHI GE Hitachi Nuclear Energy NEDO-33532 Revision 2 DRF 0000-0108-5986-1 January 2011 NON-PROPRIETARY INFORMATION-CLASS I (PUBLIC)

Pilgrim Nuclear Power Station Safety Valve Setpoint Increase Copyright 2011 GE-Hitachi Nuclear Energy Americas, LLC All Rights Reserved

NEDO-33532 Revision 2 INFORMATION NOTICE This is a non-proprietary version of the document NEDC-33532P, Revision 2, from which the proprietary information has been removed. Portions of the document that have been removed are identified by white space within double square brackets, as shown here (( )).

IMPORTANT NOTICE REGARDING CONTENTS OF THIS REPORT Please Read Carefully The design, engineering, and other information contained in this document is furnished for the purposes of supporting: A License Amendment Request by Entergy Nuclear Operations, Inc.

(Entergy), for an increase in safety valve setpoints in proceedings before the U.S. Nuclear Regulatory Commission. The only undertakings of GEH with respect to information in this document are contained in the contract between GEH and Entergy, Agreement No. 10175939, effective October 01, 2001 and Contract Order No. 10242337, effective June 23, 2009, and nothing contained in this document will be construed as changing that contract. The use of this information by anyone for any purpose other than that for which it is intended is not authorized; and with respect to any unauthorized use, GEH makes no representation or warranty, and assumes no liability as to the completeness, accuracy, or usefulness of the information contained in this document.

ii

NEDO-33532 Revision 2 Revision Status Sheet Revision i i NRvi Section Content 0

N/A N/A 6.1.1, 1

6.1.10, Revised high pressure core injection total dynamic head.

Table 6-2

.1, Table 1-1, Table 3-3 notes Modified references to Recirculation Pump Trip (RPT) Setpoints 2

and follow-on or allowable values to RPT transient analysis setpoints for table in clarification.

Updated Input/Assumptions and Evaluations Section 3.4, subsections to the Setpoint Calculation section.

6.2.2, 6.2.3, & 8 iii

NEDO-33532 Revision 2 TABLE OF CONTENTS ACRONYMS AND ABBREVIATIONS.................................................................................

ix EXECUTIVE

SUMMARY

xii INTRODUCTION............................................................................................................

1-1 1.1 P U R P O S E....................................................................................................................

1-1 1.2 OVERALL EVALUATION APPROACH..................................................................

1-1 1.3

SUMMARY

AND CONCLUSIONS..........................................................................

1-2 2

VESSEL OVERPRESSURE/ANTICIPATED OPERATIONAL OCCURRENCE EVALUATION.................................................................................................................

2-1 2.1 A N A LY SIS O V ERV IEW...........................................................................................

2-1 2.2 OVERPRESSURE ANALYSIS..................................................................................

2-2 2.3 REVIEW OF FSAR TRANSIENT AND ACCIDENT EVENTS..............................

2-3 2.4 REVIEW OF EQUIPMENT OUT OF SERVICE OPTIONS.....................................

2-8 2.5 MARGIN TO SPRING SAFETY VALVE SETPOINT.............................................

2-8 2.6 EFFECTS ON INTERFACING SYSTEMS...............................................................

2-9 3

ATWS ANALYSIS...........................................................................................................

3-1 3.1 M ET H O D O LO G Y......................................................................................................

3-1 3.1.1 A nalytical M odels........................................................................................

3-1 3.2 K EY A SSU M PTIO N S.................................................................................................

3-2 3.3 A N A LY SIS O V ERV IEW............................................................................................

3-3 3.4 A N A LY SIS IN PU T S....................................................................................................

3-5 3.5 A N A LY SIS R ESU LTS.............................................................................................

3-10 3.6 C O N C L U SIO N S........................................................................................................

3-31 4

ECCS/LOCA EVALUATION.........................................................................................

4-1 4.1 ECCS/LOCA PERFORMANCE EVALUATION......................................................

4-1 iv

NEDO-33532 Revision 2 5

CONTAINMENT RESPONSE AND LOADS ANALYSIS..........................................

5-1 5.1 CONTAINMENT PRESSURE AND TEMPERATURE FOR DBA LOCA.............. 5-1 5.2 SM ALL STEAM LINE BREAKS...............................................................................

5-1 5.3 IBA AND SBA............................................................................................................

5-2 5.4 NUREG-0783 LOCAL SUPPRESSION POOL TEMPERATURE...........................

5-2 5.5 DBA LOCA HYDRODYNAM IC LOADS................................................................

5-3 5.6 SRV AND SSV DYNAM IC LOADS.........................................................................

5-3 5.7 RIPD EVALUATION.................................................................................................

5-3 5.8 A T W S..........................................................................................................................

5 -4 6

HIGH PRESSURE SYSTEMS PERFORMANCE.......................................................

6-1 6.1 HPCI & RCIC - SYSTEM DESCRIPTION AND FUNCTIONS..............................

6-1 6.1.1 Pump Flow and Head...................................................................................

6-1 6.1.2 System Boundary Components....................................................................

6-2 6.1.3 Pump and Turbine........................................................................................

6-2 6.1.4 Instrumentation............................................................................................

6-2 6.1.5 M otor Operated Valves................................................................................

6-3 6.1.6 Start Up Transient........................................................................................

6-3 6.1.7 Key Assumptions......................................

6-3 6.1.8 Key Input for RCIC.....................................................................................

6-3 6.1.9 Key Input for HPCI......................................................................................

6-4 6.1.10 Key Results..................................................................................................

6-4 6.1.11 Recommendations and Observations...........................................................

6-6 6.2 SETPOINT CALCULATIONS...................................................................................

6-6 6.2.1 Description...................................................................................................

6-6 6.2.2 Inputs and Assumptions...............................................................................

6-7 6.2.3 Evaluation....................................................................................................

6-7 6.2.4 Conclusion...................................................................................................

6-7 V

NEDO-33532 Revision 2 6.3 STANDBY LIQUID CONTROL SYSTEM...............................................................

6-8 7

APPENDIX R ANALYSIS...............................................................................................

7-1 8

REFERENCES................................................................................................................

8-1 vi

NEDO-33532 Revision 2 LIST OF TABLES TABLE.

TITLE.'

PAGE 1-1 Summary of Analyses Presented in this Report 1-2 2-1 SRV and SSV Configuration 2-2 2-2 Pilgrim Cycle 18 Overpressure Results With Current and 2-3 New SRV and SSV Configuration 2-3 FSAR Transient and Accident Event Review 2-4 3-1 Summary of ATWS Key Input Parameters 3-5 3-2 Axial Power Shapes 3-6 3-3 Key Equipment Parameters 3-7 3-4 Summary of Key ODYN Parameters for ATWS Calculation 3-10 3-5 Summary of Peak Suppression Pool Temperature, 3-11 Containment Pressure and Integrated SRV Flow 3-6 Sequence of Events for MSIVC at BOC 3-12 3-7 Sequence of Events for MSIVC at BOC 3-13 3-8 Sequence of Events for PRFO at EOC 3-14 3-9 Sequence of Events for PRFO at EOC 3-15 3-10 Acceptance Criteria Results 3-16 3-11 Peak Pressures for Other System Evaluations 3-16 6-1 Key Results for RCIC 6-5 6-2 Key Results for HPCI 6-6 vii

NEDO-33532 Revision 2 LIST OF FIGURES FIGURE.

TITLE PAGE 3-la MSIVC BOC - GE14 and GNF2 Fuel 3-17 3-lb MSIVC BOC - GEl4 and GNF2 Fuel 3-18 3-1c MSIVC BOC - GE14 and GNF2 Fuel 3-19 3-2a PRFO BOC - GE14 and GNF2 Fuel 3-20 3-2b PRFO BOC - GE14 and GNF2 Fuel 3-21 3-2c PRFO BOC - GEl4 and GNF2 Fuel 3-22 3-3a MSIVC EOC - GEl4 and GNF2 Fuel 3-23 3-3b MSIVC EOC - GE14 and GNF2 Fuel 3-24 3-3c MSIVC EOC - GEl4 and GNF2 Fuel 3-25 3-4a PRFO EOC - GEl4 and GNF2 Fuel 3-26 3-4b PRFO EOC - GE14 and GNF2 Fuel 3-27 3-4c PRFO EOC - GEl4 and GNF2 Fuel 3-28 3-5 Containment Response MSIVC BOC 3-29 3-6 Containment Response PRFO BOC 3-29 3-7 Containment Response MSIVC EOC 3-30 3-8 Containment Response PRFO EOC 3-30 3-9 Lower Plenum Pressure PRFO BOC 3-31 viii

NEDO-33532 Revision 2 ACRONYMS AND ABBREVIATIONS

.Term

.Definition ADS Automatic Depressurization System AFC Automatic Flow Control AL Analytical Limit AOO Anticipated Operational Occurrence ARI Alternate Rod Insertion ARTS Average Power Range Monitor, Rod Block Monitor, Technical Specifications Improvement Program ASME American Society of Mechanical Engineers ATWS Anticipated Transient Without Scram AV Allowable Value BIIT Boron Injection Initiation Temperature BOC Beginning of Cycle BPV Bypass Valve BWR Boiling Water Reactor BWROG Boiling Water Reactor Owners Group CPR Critical Power Ratio DBA Design Basis Accident DW Drywell ECCS Emergency Core Cooling System EOC End of Cycle EOOS Equipment Out-of-Service EQ Environmental Qualification FSAR Final Safety Analysis Report FW Feedwater ix

NEDO-33532 Revision 2 Term...

Definition"'

FWCF Feedwater Controller Failure HPCI High Pressure Coolant Injection HSBW Hot Shutdown Boron Weight IBA Intermediate Break Accident IORV Inadvertent Opening of Relief Valve LFWH Loss-of-Feedwater Heater LOFW Loss-of-Feedwater Flow LOCA Loss-of-Coolant Accident LOOP Loss-of-Offsite Power LPCI Low Pressure Coolant Injection LRNBP Load Rejection No Bypass LRWBP Load Rejection with Bypass MCPR Minimum Critical Power Ratio MELLLA Maximum Extended Load Line Limit Analysis MFC Manual Flow Control M/G Motor/Generator MOV Motor Operated Valve MSIV Main Steam Isolation Valve MSIVC Main Steam Isolation Valve Closure MSIVD Main Steam Isolation Valve Closure - Direct Scram MSIVF Main Steam Isolation Valve Closure with Flux Scram MW Million Watts NBR Nuclear Boiler Rated NMS Neutron Monitoring System NPSH Net Positive Suction Head X

NEDO-33532 Revision 2 Termn Definiti~on.

NRC Nuclear Regulatory Commission NTSP Nominal Trip Setpoint OOS Out-of-Service PCT Peak Clad Temperature PRFO Pressure Regulator Failure - Open PNPS Pilgrim Nuclear Power Station RCIC Reactor Core Isolation Cooling RHR Residual Heat Removal RIPD Reactor Internal Pressure Difference RPT Recirculation Pump Trip RPV Reactor Pressure Vessel RSLB Recirculation Suction Line Break SBA Small Break Accident SLB Steam Line Break SLCS Standby Liquid Control System SRV Safety Relief Valve SSV Spring Safety Valve TAF Top of Active Fuel TDH Total Dynamic Head TS Technical Specification TTNBP Turbine Trip No Bypass TTWBP Turbine Trip with Bypass UFSAR Updated Final Safety Analysis Report xi

NEDO-33532 Revision 2 EXECUTIVE

SUMMARY

The Pilgrim Nuclear Power Station (PNPS) safety valve set-point increase evaluation supports Entergy's pursuit of a solution to improve the current operating conditions at PNPS.

This solution provides a greater operational simmer margin as well as increasing allowed Safety Relief Valve (SRV)/Spring Safety Valve (SSV) setpoint tolerance.

This report specifically addresses several analyses/subject areas that are sensitive to the valve setpoint tolerances, nominal setpoint increases, and valve capacity increases. Other subjects that are insensitive to these valve setpoint and capacity changes are not addressed in this report.

This report also identifies the requirements necessary to implement the setpoint changes and the SSV capacity increase.

xii

NEDO-33532 Revision 2 1 INTRODUCTION 1.1 PURPOSE This report supports the following increase in setpoints, setpoint tolerance, SSV capacity increase, Plant Modifications and associated Technical Specification (TS) changes:

" Replace the full complement of four Target Rock 2-Stage SRVs with 3-Stage SRVs (No increase in SRV capacity)

  • Replace the full complement of two Dresser Safety Valves with higher capacity SSVs.

" Increase the nominal setpoint of the SRVs and SSVs by 40 psig to 1155 psig and 1280 psig respectively.

  • Increase the setpoint tolerance of the SRVs and SSVs from +1% to +3%.
  • Increase the Reactor Pressure Alternate Rod Insertion (ARI) and Recirculation Pump Trip (RPT) transient analysis setpoints by 40 psig to 1220 psig.
  • Increase the TS Reactor Steam Dome Safety Limit currently set at 1325 psig to 1340 psig.

Lower the High Reactor Pressure Feedwater Pump Trip Setpoint from 1415 psig to 1315 psig.

Reference 1 presents a generic evaluation of the effects of increasing the setpoint tolerance of the SRVs and identifies specific areas that should be evaluated on a plant specific basis. This report provides the results of the plant specific evaluations performed to assess the effect of the setpoint tolerance increase, nominal setpoint increase, and SSV capacity increase.

These evaluations support the operation of PNPS with an increase in the setpoint tolerance for the safety function of the Target Rock Dual Mode SRVs and the Dresser SSVs from 1% to 3%. The increase in setpoint tolerance includes both an increase in the upper limit of the setpoint tolerance as well as a decrease in the lower limit of the setpoint tolerance. The upper limit is defined as +3% and the lower limit is defined as -3%.

1.2 OVERALL EVALUATION APPROACH The effect of the SRV and SSV setpoint tolerance relaxation, SRV and SSV setpoint increase, and SSV capacity increase, on the following subjects is addressed in this report:

" Vessel Overpressure

NEDO-33532 Revision 2

  • Emergency Core Cooling (ECCS)/ Loss-of-Coolant Accident (LOCA)
  • Containment Response and Loads

" High Pressure Systems Performance

" Appendix R Analysis These subjects are affected by the changes in valve setpoints, setpoint tolerance, and capacity, as detailed above.

1.3

SUMMARY

AND CONCLUSIONS A summary of the results of the evaluations for each of the subjects of concern is provided in Table 1-1. The evaluation determined that the effect of the setpoint tolerance increase on the following subjects are acceptable:

1) Vessel Overpressure, 2) UFSAR Events, 3) ATWS Analysis, 4) Containment Response and Loads Assessment, and 5) High Pressure Systems Performance. These specific subjects were addressed in detail as described in this report.

Based on the results of the different analyses described in this report, several areas require further evaluation for implementation of the setpoint tolerance increase.

The subjects that require additional evaluation are identified in Table 1-1 and will be addressed by Entergy before the implementation of the setpoint tolerance increase.

Table 1-1: Summary of Analyses Presented in this Report Subject Section Result Vessel Overpressure, Transient Analysis and SSV Margin 2.0 Acceptable 4 ATWS Analysis 3.0 Acceptable' ECCS/LOCA Analysis 4.0 Acceptable Containment Response 5.0 Acceptable5 High Pressure Systems Performance 6.0 Acceptable 2' 3'6 Appendix R Analysis 7.0 Acceptable

1.

These evaluations did not include any SRV or SSV OOS.

2.

Motor Operated Valve (MOV) operation will be assessed by Entergy to ensure the requirements described in section 6 are met.

3.

The Standby Liquid Control System (SLCS) performance will be assessed by Entergy to ensure the requirements described in section 5 are met.

4.

Effects on Interfacing System Piping Design Pressures will be assessed by Entergy.

5.

SRV and SSV Dynamic Loads will be evaluated by Entergy.

6.

The ATWS high pressure RPT setpoint allowable value (AV) and nominal trip setpoint (NTSP) based on the transient analysis setpoint described in Section 3 will be determined by Entergy.

1-2

NEDO-33532 Revision 2 2

VESSEL OVERPRESSURE/ANTICIPATED OPERATIONAL OCCURRENCE EVALUATION 2.1 ANALYSIS OVERVIEW Reference 1 presents a generic evaluation of the effect of increasing the setpoint tolerance to

+/- 3% for safety valves in the pressure relief system. PNPS's configuration for Safety and Relief valves includes four safety-relief valves (SRV) that are piped to the suppression chamber and each of the two SSVs discharge to the drywell. This section presents the results of the plant specific evaluations associated with the increase of both the setpoint and the setpoint tolerance of the SSVs and the SRVs and the increase of the high pressure recirculation pump trip by 40 psi (1180 to 1220 psig) and the reduction of the ATWS high pressure feedwater pump trip by 100 psi (1415 to 1315 psig). The setpoint increases are 40 psi for both the SRVs (1115 to 1155 psig) and SSVs (1240 to 1280 psig). The setpoint tolerance is increased from +/- 1% to +/-3%. In addition, the existing SSVs will be replaced with new valves having a larger throat diameter, flow capacity, and performance characteristics that are consistent with the analysis presented in this report. The capacity of the SSVs was increased from 644,501 lbm/hr to 1,126,200 Ibm/hr.

The SSV capacity was increased to provide the analytical margin required to allow the SRV and SSV set pressure to be increased (to increase SRV simmer margin) and to allow the SRV and SSV set pressures tolerances to be increased.

Table 2-1 lists the SRV/SSV configurations (current and new). In this section, SSVs are defined as valves that are qualified for use in the American Society of Mechanical Engineers (ASME) overpressure protection analysis. SRVs are valves that function as relief valves but are also qualified for use in ASME overpressure protection analysis. The high reactor pressure recirculation pump trip was also increased 40 psi, consistent with the increase in SRV opening setpoints. This increase retains the margin between the SRV opening setpoint and the high reactor pressure recirculation pump trip and this increase is included in these analyses. It was also necessary to reduce the ATWS high pressure feedwater pump trip setpoint. This was necessary to ensure that all ATWS events, that have a Main Steam Isolation Valve (MSIV) closure, trip the feedwater pumps on high pressure.

In addition to the plant specific overpressure analysis, a plant specific review of the events in the UFSAR was performed to determine if any other events are impacted by change to the safety and relief valve configuration.

This review is summarized in Table 2-3. Based on the generic evaluation in Reference 1 and the review of the transient and accident events in Table 2-3, the overpressure analysis was evaluated with the SSVs and SRVs at the +3 % limit and the Loss of Feedwater Event was reviewed with the SSVs and SRVs setpoints at the -3% limit. All other events were determined to be unaffected by the change in setpoint tolerance.

2-1

NEDO-33532 Revision 2 Table 2-1: SRV and SSV Configuration No.minal SRV and Capacity.

SRV and SSV Setpoitts (psig)

SSV Configuration

  1. SRV
  1. SSV SRV.

SSV Tolerante jSV

'SV Tolerance

.,SRV

2 1115 1240

+/- 1%

870,000 644,501 New 4

2 1155 1280

+ 3%

870,000 1,126,200 Notes:

1. The reference pressure, for the capacities, are 1122.7 psig for SRV and 1277.2 psig for SSV. These pressures include 3% accumulation. The flow rate in the transient simulation varies primarily based on the upstream pressure condition relative to the reference pressure.

In addition, this evaluation proposes to increase the Technical Specification dome pressure Safety Limit to 1340 psig. Section 2.2 provides the assessment to increase the dome pressure safety limit.

2.2 OVERPRESSURE ANALYSIS The most recent Main Steam Isolation Valve Closure with Flux scram (MSIVF) transients (Cycle 18 Reload Licensing), for PNPS, were analyzed with the current SSV/SRV configuration and high pressure recirculation pump trip setpoint. The reload evaluation contains both GE14 and GNF2 fuel. These results and those with the new configuration with the increase to the high pressure recirculation pump trip are provided in Table 2-2 below. These results demonstrate that the dome pressure safety limit (1325 psig) and the peak vessel pressure limit (1375 psig) are met when analyzed with a 3% setpoint tolerance. The overpressure analyses were performed in accordance with the methodologies described in Reference 2.

These results show that the margin to the current dome pressure safety limit is less than 5 psi, but there is still large margin to the ASME overpressure limit of 1375 psig with over 30 psi of margin. This shows that the dome pressure safety limit has excess conservatism. The safety limit is placed on the dome pressure to have a plant measurable parameter to demonstrate compliance with the vessel pressure limit of 1375 psig. These results show that there is less than a 20 psi difference between the peak vessel pressure and the peak dome pressure. The dome pressure safety limit is proposed to increase to assure margin is available for cycle-to-cycle variation in cycle specific overpressure calculations while retaining margin in the vessel to dome pressure difference.

Establishing a safety limit at 1340 psig provides margin to the ASME overpressure analysis and provides for a 35 psi pressure difference between the vessel bottom to dome. This 35 psi is 75% higher than the observed pressure difference (-20 psi) for the limiting ASME overpressure event.

2-2

NEDO-33532 Revision 2 Table 2-2 PNPS Cycle 18 Overpressure Results With Current and New SRV and SSV Configuration Peak

".Dome Peak Vessel Dome Pressure:. Vessel.l" Pressure Power Flow

  1. SSVs
  1. SRVs j

SRV/SSV Pressure Safety Pressure Limit Credited Credited (psig)

Limit (psig)

Configuration" Rated).

Rated)

(ps..)

(psig) 102 107.5 2

4 1279 1325 1298 1375 Current 76.7 2

4 1280 1325 1296 1375 Current 102 107.5 2

4 1322 1325 1341 1375 New 76.7 2

4 1323 1325 1340 1375 New 2.3 REVIEW OF FSAR TRANSIENT AND ACCIDENT EVENTS The following table describes the effect of increasing both the SRV and SSV setpoints and setpoint tolerance and increasing the high pressure recirculation pump trip setpoint (high reactor pressure recirculation pump trip). In the event discussions in Table 2-3, note that if there is no SRV actuation, there will be no high reactor pressure recirculation pump trip. This results because the high reactor pressure recirculation pump trip was moved above the new SRV setpoint to be consistent with the current setpoints. The most limiting event for overpressure is the MSIVF and this event was analyzed in Section 2.2.

This evaluation considered the effect of lowering the ATWS high pressure feedwater pump trip.

The feedwater pump trip has the potential to reduce the peak pressure due to the reduction in vessel level. No Anticipated Operational Occurrence (AOO) has a peak dome pressure high enough to reach the new ATWS high pressure feedwater pump trip setpoint. Thus, these events are not impacted by lowering that setpoint. The only event that may reach the high pressure feedwater pump trip is the MSIVF. The MSIVF event is not an AOO and is not expected to occur due to the additional failure of the MSIV position scram. For the MSIVF, the peak vessel and dome pressure occur so quickly that the feedwater pump trip has no beneficial effect for this event.

2-3

NEDO-33532 Revision 2 Table 2-3: FSAR Transient and Accident Event Review Increase in Heat Removal by the Reactor Coolant System Loss of FW Heater (LFWH)

Manual Flow Control (MFC)

This transient results in a power increase due to increased core inlet subcooling. The increase in reactor power occurs at a moderate rate. No safety or relief valve actuation occurs during this transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Automatic Flow Control (AFC)

MFC is more severe than AFC because AFC would limit the power increase. No safety or relief valve actuation occurs during this transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Feedwater Controller Failure Maximum Demand (FWCF)

This transient is similar to a Turbine Trip, however it is initiated at a higher power. This transient is analyzed on a reload specific basis for CPR (Critical Power Ratio) as well as for pressure margin to the SSV setpoints. ((

)) Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Increase in Steam Flow Pressure Regulator Failure Upscale This event results in a decrease in vessel pressure followed by a low pressure isolation.

)) The vessel pressure increase is bounded by the Main Steam Isolation Valve Closure (MSIVC) with direct scram which does not result in SSV actuation. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Decrease in Heat Removal by the Reactor Coolant System Pressure Regulator Failure Downscale Backup pressure regulator controls pressure. This event results in a small pressure change and power perturbation. No safety or relief valve actuation occurs during this transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Load Rejection With Bypass (LRWBP)

Severity varies with Bypass Valve (BPV) capacity and the results are bounded by the Load Rejection without Bypass event.

))

Without Bypass (LRNBP)

This transient results in a large vessel pressurization and increase in reactor power and is analyzed on a reload specific basis for CPR as well as for pressure margin to the SSV setpoints. ((

)) ER

)) Therefore, this transient is not impacted by the changes to the safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

2-4

NEDO-33532 Revision 2 Turbine Trip With Bypass (TTWBP)

Severity varies with BPV capacity and the results are bounded by the Turbine Trip without Bypass event.

Without Bypass (TTNBP)

This transient results in a large vessel pressurization and increase in reactor power and is analyzed on a reload specific basis for CPR as well as for pressure margin to the SSV setpoints. ((

)) Er

)) Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

MSIV Closure Direct Scram (MSIVD)

This transient is not limiting from a CPR perspective because of the slow steam flow shutoff rate associated with the MSIV stroke times compared to turbine valves. This transient is analyzed on a cycle specific basis to determine the pressure margin to SSV setpoints. ((

))I Flux Scram (MSIVF)

This transient is analyzed on a cycle specific basis to ensure that the ASME boiler code requirements and dome pressure TS safety limits are met. The peak vessel pressure increases as the SSV opening setpoints are increased. This transient has been analyzed using the upper bound of the 3 % tolerance for the SSV opening setpoints and the safety mode of the dual mode relief valve opening setpoints.

Single MSIV Closure This event is bounded by the MSIVD transient for peak pressure and is a non-limiting MCPR transient compared to other analyzed pressurization events. While the peak pressure is expected increase by a few psi, this transient is not materially impacted by the changes to the SSV capacity, safety and relief setpoints, setpoint tolerance and high reactor pressure recirculation pump trip. [

))

Loss of Condenser Vacuum This event is similar to a Turbine Trip event with no bypass, but there is a period of time where bypass valve flow is available. The duration of the bypass valve flow depends on the rate of loss of vacuum. Because of the limited bypass flow, the event is less severe than a turbine trip without bypass. ((

))

Loss of Auxiliary Power This is a delayed turbine trip following a recirculation pump trip. This event is bounded by other pressurization events and the SRV configurations change does not change this conclusion. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip. ((

Loss of Feedwater Flow (LOFW)

This transient results in a low level scram followed by a low-low level isolation. The transient is not limiting from a CPR perspective and because of the time delay between the scram and the MSIV closure, this event is far from limiting from an overpressure concern. The low reactor water level scram setpoint is not impacted by the setpoint tolerance change because the low reactor water level scram setpoint is reached before any valve actuation occurs.

Decrease in Reactor Coolant System Flow Rate Trip of One Recirculation Pump 2-5

NEDO-33532 Revision 2 Motor-Generator (M/G) Set Field This event results in a pump coast-down and power decrease. No safety or relief valve Breaker Trip actuations occur during this transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

M/G Set Drive Motor Breaker Trip This event results in a pump coast-down and power decrease. No safety or relief valve actuations occur during this transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Trip of Two Recirculation Pumps M/G Set Field Breaker Trip for both This event results in a flow coast-down and power decrease and may result in high Level pumps Turbine Trip after a significant power decrease. No safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

M/G Set Drive Motor Breaker Trip This event results in a flow coast-down and power decrease and may result in high Level for both pumps Turbine Trip after a significant power decrease. No safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Recirculation Flow Controller Malfunction Decreasing Flow This event is similar to field breaker trip and results in a power decrease. No safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Shaft Seizure Two Loop Operation This event results in a rapid flow decrease, which causes reactor power to decrease. No safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Single Loop Operation This event results in a rapid flow decrease, which causes reactor power to decrease. No safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Reactivity and Power Distribution Anomalies.,

Control Rod Withdrawal Error During Startup This transient results in a power increase from very low powers. The increase in reactor power can occur at a high rate, but the neutron monitoring system is designed to limit the peak power achieved during the transient. The peak powers achieved are sufficiently low such that no safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

At Power This transient results in a power increase due to increased reactivity associated with the control rod withdrawal. The increase in reactor power occurs at a moderate rate. The pressure regulator maintains vessel pressure and no safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Startup of an Inactive Recirculation Loop

)) The pressure regulator maintains vessel pressure and no safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

2-6

NEDO-33532 Revision 2 Flow Controller Failure - Increasing The rapid flow increase results in a power increase that occurs at a moderate rate. The Flow pressure regulator maintains vessel pressure and no safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Slow Flow Run-out The slow recirculation flow run-out transient is not an original Final Safety Analysis Report (FSAR) event, however it is the basis for the flow dependent off-rated limits.

This event assumes a slow increase in recirculation flow rate in both loops from the minimum core flow to the maximum core flow. This analysis is a conservative process for evaluating flow run-out events. The slow increase in core flow causes an increase in reactor power and corresponding increase in steam flow. The pressure regulator maintains vessel pressure and no safety or relief valve actuation occurs during the transient. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Mislocated Fuel Assembly Accident This scenario is modeled with a 3 dimensional core simulator code. The event does not result in increased pressure or SSV actuation. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Misoriented Fuel Assembly This scenario is modeled with lattice physics codes in the bundle design process. The Accident event does not result in increased pressure or SSV actuation. Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Control Rod Drop Accident This results in a very rapid increase in neutron flux and a corresponding increase in fuel temperature. A reactor scram terminates the transient. The pressure regulator maintains vessel pressure. No safety or relief valve actuation occurs during the transient.

Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, setpoint tolerance change and high reactor pressure recirculation pump trip.

Increase in Coolant Inventory Inadvertent High Pressure Coolant This event is analyzed on a reload specific basis for CPR and margin to SSV. This is an Injection (HPCI) event where the HPCI system is inadvertently initiated. The increased core subcooling causes power to increase. It is possible that the inadvertent HPCI initiation could cause water level to increase to the high reactor water level turbine trip setpoint resulting in a turbine trip. This event is similar to the FWCF. As with the FWCF, the MCPR occurs prior to any SRV actuation.

)) Therefore, this transient is not impacted by the changes to the SSV capacity, safety and relief valve setpoints, I setpoint tolerance change and high reactor pressure recirculation pump trip.

Decrease in Reactor Coolant Inventory One SRV Opening This event is not limiting with respect to MCPR because the event results in a very small power change. Because there are no changes to the SRV capacity, this transient is not impacted by the changes to the SSV capacity, safety and relief valves setpoint, setpoint tolerance and high reactor pressure recirculation pump trip.

Instrument Line Break These events are considered in the Loss of Coolant Analysis section of this report.

Steam Line Break (SLB) Outside Containment LOCA Inside Containment Radioactive Release from a Subsystem or Component_

Liquid Release due to Tank Failure These events are evaluated for radiological consequences and are not affected by changes Fuel Handling Accident to the SSV capacity, safety and relief valves setpoint, setpoint tolerance and high reactor pressure recirculation pump trip.

2-7

NEDO-33532 Revision 2 2.4 REVIEW OF EQUIPMENT OUT OF SERVICE OPTIONS In addition to the events in the UFSAR, the following equipment Out-of-Service (OOS) options were considered when determining the effect of the setpoint tolerance change:

1.

Turbine Bypass OOS

2.

Final Feedwater Temperature Reduction / Feedwater Heater(s) OOS

3.

MSIV OOS

4.

Single Loop Operation Various combinations of equipment OOS options are allowed as described in Reference 2.

These flexibility options are considered when performing critical power ratio and peak vessel pressure analyses. The minimum CPR for these events occurs before SRV and SSV lift.

Therefore, changes to the SRV and SSV setpoint, setpoint tolerance and the high reactor pressure recirculation pump trip, does not affect the critical parameters for the equipment OOS options listed above. The Turbine Bypass OOS option considers the effects of not meeting the fast response performance analyzed for the reload. It does not remove the ability of the pressure regulator to open the bypass valves in an attempt to maintain vessel pressure for slow events such as the rod withdrawal error or loss of feedwater heating where core power and steam flow may increase above the rated value.

For vessel overpressure calculations, the limiting event is the MSIVF. This transient is evaluated from 102% of rated power at the high and low end of the rated power licensed core flow. The overpressure results are bounding for the equipment out-of-service options listed above.

Single loop operation is at low power reduced flow condition. Transients initiated from these low power conditions have a reduced overpressure and are bounded by the limiting overpressure events analyzed at high power.

Therefore, the equipment OOS options listed above are not impacted by the valve setpoint tolerance increase.

2.5 MARGIN TO SPRING SAFETY VALVE SETPOINT

((

2-8

NEDO-33532 Revision 2 2.6 EFFECTS ON INTERFACING SYSTEMS The piping systems connected to the Reactor Pressure Vessel (RPV) require evaluation for a Peak Vessel Bottom Pressure of 1375 psig, as appropriate.

These systems include Reactor Recirculation, HPCI, Reactor Core Isolation Cooling (RCIC), Residual Heat Removal (RHR),

Low Pressure Coolant Injection (LPCI), Core Spray, SLCS, Reactor Water Cleanup, Main Steam, Feedwater, Reactor Vents & Drains, and the RPV Flange Leakoff System. Entergy shall ensure that the piping systems affected by the proposed SRV and SSV upgrade meet the requirements of the applicable piping code (ASME or B31.1) for a maximum reactor vessel dome pressure of 1340 psig and maximum vessel bottom pressure of 1375 psig.

2-9

NEDO-33532 Revision 2 3

ATWS ANALYSIS 3.1 METHODOLOGY 3.1.1 Analytical Models The GE computer model ODYN is used for the reactor transient analysis. The Nuclear Regulatory Commission (NRC) has approved the application of ODYN to ATWS evaluations.

The major features of the model are:

  • One-dimensional reactor core neutron kinetics and thermal hydraulics.

" Drift-flux upper plenum and bulk water modeling.

" Multi-node steam line for modeling acoustic phenomena.

" Balance-of-plant control systems and equipment models.

" Emergency protection systems, including boron injection.

" Boron transport and reactivity consistent with one-dimensional nodalization.

The GE computer model STEMP04 is used for the suppression pool heatup analysis. The STEMP analytical models have been accepted by the NRC in previous applications and other ATWS analyses. STEMP calculates the temperature rise of the suppression pool due to SRV and SSV discharge. The temperature is calculated using a mass and energy balance for the suppression pool, including the effects of steam entering the pool and the heat removal capability of the RHR heat exchangers. The integrated steam flow from the SRVs and SSVs, calculated by ODYN, is input to STEMP to calculate the Boron Injection Initiation Temperature (BIIT) time and the peak suppression pool temperature.

The May-Witt decay heat model is used in both the ODYN code for reactor transient analysis, and the STEMP code for suppression pool energy balance analysis. The May-Witt correlation bounds the ANSIIANS-5.1-1979 + 2a decay heat curves during the ATWS events.

3-1

NEDO-33532 Revision 2 3.2 KEY ASSUMPTIONS

  • .Paramete

.r Reference/Basis I

Core and Fuel Design The ATWS analyses are performed using a representative core and fuel design based on the reference loading pattern for PNPS Cycle 18.

2 Reactor Water Level The ATWS analyses are performed with reactor water level controlled at Top of Active Fuel (TAF) + 5 feet due to limitations of the ODYN computer program. This limitation was factored into NRC approval for application of ODYN to ATWS.

3 Reactor Depressurization Reactor depressurization cannot be modeled with ODYN.

In the ATWS analyses, Automatic Depressurization System (ADS) operation is inhibited, and the vessel cycles on SRV setpoints until the reactor is shutdown.

4 Decay Heat The May-Witt decay heat correlation is used in the suppression pool temperature calculation following reactor shutdown. The May-Witt decay heat correlation is known to be conservative relative to the 1979 ANS 5.1 +

2c curve.

5 ATWS Parameters The ATWS analyses are generally a best estimate calculation at the maximum power and the lowest core flow at the Maximum Extended Load Line Limit Analysis (MELLLA) boundary. The NRC has approved the use of less conservative parameters in the ATWS analyses.

Equipment that is not OOS is assumed to function per its design.

6 ATWS Mitigation Alternate Rod Insertion is assumed to fail.

Equipment Performance

° ATWS Recirculation Pump Trip (RPT) and SLCS are assumed to function as designed. The SLCS pump discharge relief valves are assumed to not lift during the ATWS events. The acceptability of SLCS during ATWS is confirmed in the SLCS system evaluation.

0 Both loops of RHR are assumed to function with all pumps operational during the Pressure Regulator Failure-Open (PRFO) and MSIVC ATWS events.

3-2

NEDO-33532 Revision 2 Item Parameter Reference/Basis 7

SRV Operating Parameters The SRV valve opening/closing setpoints are statistically spread around the upper Analytical Limit (AL) setpoint.

The statistical spread is adequate for the SRV setpoint drift tolerance.

8 Fuel Cladding Oxidation Cladding oxidation is insignificant if the Peak Clad Temperature (PCT) remains below 1600 OF.

Consequently, no cladding oxidation calculation is performed if the calculated PCT is below 1600 OF.

9 Operator Action Operator is assumed to initiate boron injection within 120 sec after high pressure ATWS recirculation pump trip setpoint has been reached.

3.3 ANALYSIS OVERVIEW This section describes the effect of the setpoint tolerance increase, setpoint increase and SSV capacity increase on the PNPS ATWS analysis.

The ATWS analysis is performed in order to demonstrate that reactor integrity, containment integrity, and fuel integrity are maintained for scenarios where an automatic SCRAM fails to occur. Reactor integrity is demonstrated by ensuring that peak reactor vessel pressure is within the ASME Service Level C limit of 1500 psig.

Containment integrity is demonstrated by ensuring that the peak suppression pool temperature is below the maximum bulk suppression pool temperature limit of 185 0F and containment pressure is less than the containment design pressure limit of 56 psig.

Fuel integrity is demonstrated by ensuring that peak cladding temperature is below the 10CFR50.46 limit of 2200'F and fuel local cladding oxidation is below the 10CFR50.46 limit of 17 % total clad thickness. Because the cladding temperature increase for ATWS is of short duration and limited magnitude, cladding oxidation is not explicitly calculated in the ATWS analysis.

[R 3-3

NEDO-33532 Revision 2 Because the LOOP event, for PNPS, does not result in a reduction in the number of Residual Heat Removal (RHR) cooling loops, the LOOP event is not potentially limiting for the long-term suppression pool temperature or containment pressure response.

For the IORV event, the availability of the main condenser reduces the severity of the peak suppression pool temperature increase. The absence of reactor vessel isolation avoids the vessel pressurization; therefore, the peak vessel pressure remains at or below the initial value. A reactor power excursion does not occur and the fuel does not experience boiling transition. The IORV is not explicitly analyzed due to the non-limiting nature of the event for all acceptance criteria.

Both the MSIVC and PRFO ATWS events were evaluated for both Beginning of Cycle (BOC) and End of Cycle (EOG) exposure conditions and at rated core power (2028 MWt) and minimum core flow (76.7% of rated)

ATWS analyses were performed for the proposed SRV and SSV configuration changes, which include:

1. SRV setpoint increase of 40 psi and tolerance relaxation to +/-/- 3%
2. SSV setpoint increase of 40 psi and tolerance relaxation to +/- 3%
3. High reactor pressure recirculation pump trip setpoint increase of 40 psi
4. High reactor pressure feedwater pump trip setpoint decrease of 100 psi
5. SSV reference capacity increase from 644,501 lbmihr to 1,126,200 Ibm/hr at 1240 psig plus 3% accumulation.

The increased SRV, SSV and high reactor pressure recirculation pump trip setpoints would be expected to result in an increase of the ATWS peak vessel pressure. However, the replacement SSVs were selected to provide a large increase in SSV capacity and substantial decrease in the peak pressure. The Feedwater (FW) pump trip setpoint was reduced to ensure the peak dome pressure of all ATWS events, that have a MSIV isolation, will reach the FW pump trip setpoint.

The feedwater pump trip provides both protection (1) against the overpressurization of the reactor coolant pressure boundary (lowers peak vessel pressure) and (2) against the suppression pool exceeding both pressure and temperature limits.

Both the upper tolerance limit (+3%) and the lower tolerance limit (-3%) were considered. The MSIVC and PRFO transients were re-evaluated using the design inputs summarized in Table 3-1 through 3-3, which include the configuration changes described above. The MSIVC and PRFO events were reanalyzed at beginning and end of cycle exposure points (i.e., BOC and EOC).

3-4

NEDO-33532 Revision 2 3.4 ANALYSIS INPUTS Table 3-1 summarizes the initial conditions assumed for the ATWS event. These conditions are consistent with the initial conditions assumed for the ATWS analysis performed for the implementation of Thermal Power Optimization (TPO) (Reference 3).

Table 3-1: Summary of ATWS Key Input Parameters Parameter Value Dome Pressure, psig 1035 Rated Core Flow, Mlbmlhr 69.0 Core flow, Mlbm/hr / % of Rated 52.9/76.7 Rated Power, MWt 2028 Power, MWt / % of Rated 2028/100 Steam Flow, Rated, Mlbm/hr 8.12 Feedwater Temperature, 'F 364.3

-12.6 (BOC)

Initial Dynamic Void Reactivity Coefficient, ¢/%

-11.0 (EOC) 51.2 (BOC)

Core Average Void Fraction, %

39.2 (EOC)

-0.13 (BOC)

Initial Doppler Coefficient, 0/'F

-0.13 (EOC)

Initial Suppression Pool Liquid Volume (ft3) 84,000 Initial Suppression Pool Temperature (0F) 80 Initial Suppression Pool Mass, Mlbm 5.225 Initial Inventory in Condensate Storage Tank, ibm 883,000 3-5

NEDO-33532 Revision 2 Table 3-2 shows the initial axial power shapes for the beginning of cycle and end of cycle analyses. The ATWS analysis results are based on GEl4 and GNF2 fuel and the analysis is cycle independent. These analyses are applicable to the current PNPS core with GNF2 reloads.

Table 3-2 Axial Power Shapes

  • Nd, "O

(22 M,.,"

t NodeLocation

(.From Bottom of Active-Fuel)

& 76.7% Flow)

& 76j7% Flow).

1 0.42 0.15 2

1.36 0.45 3

1.64 0.55 4

1.66 0.64 5

1.61 0.74 6

1.53 0.86 7

1.45 0.97 8

1.38 1.07 9

1.31 1.15 10 1.23 1.22 11 1.18 1.30 12 1.14 1.35 13 1.09 1.39 14 1.04 1.41 15 0.93 1.33 16 0.89 1.35 17 0.84 1.38 18 0.76 1.37 19 0.70 1.35 3-6

NEDO-33532 Revision 2 Node Location BOC (2028 MWt EOC (2028 MWt.,

(Fro Bottom of Active Fuel)

& 76.7% Flow)

&7.7%F1ow)**

20 0.62 1.27 21 0.52 1.13 22 0.41 0.92 23 0.19 0.42 24 0.10 0.22 Table 3-3 summarizes key equipment parameters and input values used in the ATWS analysis.

Table 3-3: Key Equipment Parameters Parameter Analysis Value Nominal Closure Time of MSIV, sec 4.0 SRV System Capacity, % Nuclear Boiler Rated (NBR) Steam 42.9/4 Flow at 1122.7 psig / Number. of Valves SRV Nominal Opening Setpoint, psig 1155' SRV Setpoint Tolerance, %

3 Safety/Relief Valve Closing Setpoint, % of Opening Setpoint 97 SRV Time Delay On Opening Signal, sec 0.4 SRV Opening Stroke Time, sec 0.15 SRV Closure Time Delay, sec 0.4 SRV Closure Stroke Time, sec 0.15 SSV System Capacity, % NBR Steam Flow at 1240 psig /

27.7/2 Number of Valves 3-7

NEDO-33532 Revision 2 Parameter Analysis Value SSV Nominal Opening Setpoint, psig 1280 SSV Setpoint Tolerance, %

3 SSV Closing Setpoint, % of Opening Setpoint 94 Recirculation Pump Trip Logic Delay, sec 0.53 ATWS High Pressure Recirculation Pump Trip Setpoint, psig 12202 ATWS High Pressure Feedwater Pump Trip Setpoint, psig 13153 Feedwater Pump Trip Logic Delay, sec 0.6 SLCS Injection Location Lower Plenum Standpipe SLCS Injection Time, sec after High Pressure ATWS High 120 Pressure Recirculation Pump Trip SLCS Injection Rate per Pump, gpm 39 Minimum Boron-10 Enrichment, %

54.5 Sodium Pentaborate Concentration, %

8.42 BUT, TF 110 SLCS Liquid Transport Time, sec 60 SLCS Liquid Solution Enthalpy, Btu/lbm 78 Time to Inject Hot Shutdown Boron Weight, sec 1538 HPCI Flow Rate, gpm 4250 Enthalpy of the HPCI Flow, Btu/lbm 81.0 RCIC Flow Rate, gpm 400 3-8

NEDO-33532 Revision 2 parameter Analysis Value Enthalpy of the RCIC Flow, Btu/lbm 81.0 Low Pressure MSIV Isolation Setpoint, psig 782.3 Number of RHR Loops 2

Number of RHR Loops for LOOP event 2

RHR Service Water Temperature OF 75.0 RHR Heat Exchanger K-Factor per Loop in Containment 175.0 Cooling Mode, Btu/sec-OF RHR Heat Exchanger K-Factor per Loop during LOOP, 175.0 Btu/sec-OF Notes:

1.

The analysis setpoints were determined by (I) adding the 3% tolerance (1155 to 1190 psig) and (2) then applying a statistical spread (about 1190 psig). The resulting opening setpoints were then used in the ATWS evaluations.

2.

The current ATWS high pressure RPT transient analysis setpoint is 1180 psig. The new ATWS high pressure RPT transient analysis setpoint used in this analysis is 1220 psig. The increase of 40 psi is consistent with the increase in nominal setpoint proposed for the SRVs and SSVs. This 40 psi increase provides the same level of protection to avoid tripping both recirculation pumps during expected transients like the TTWBP, LRWBP, and MSIVD.

3.

The feedwater pump trip setpoint was originally set at 1415 psig. However, with the inclusion of the large capacity SSVs it became necessary to lower the setpoint to ensure that all ATWS isolation events will reach the feedwater trip setpoint.

Less limiting ATWS events, with the turbine bypass available, are also expected to experience a high pressure feedwater pump trip. The new setpoint (1315 psig) is high enough to ensure only ATWS events or the ASME Over-Pressure Protection event (MSIVF) will trip the feedwater pump on high pressure.

In general, nominal operating and equipment parameters are utilized for the evaluation of ATWS. The ATWS high pressure RPT setpoints used in the current and new analysis are summarized below:

Curient Tr'ansient New Transient S Function '::...*i*w rnln Analysis Setpoint Analysis Setpoint 1180 psig ATWS High Pressure RPT Upper AV 1220 psig (Reference 3) 3-9

NEDO-33532 Revision 2 3.5 ANALYSIS RESULTS The ATWS analysis yielded similar results to previous ATWS analyses. The ODYN results from this analysis are summarized in Table 3-4 below.

The suppression pool temperature, suppression pool airspace pressure and integrated valve flows are shown in Table 3-5.

A sequence of key events was developed for each of the transients analyzed. These are provided in Tables 3-6 through 3-9. Table 3-10 shows the ATWS acceptance criteria and the applicable limiting results, and Table 3-11 describes the peak pressures for other system evaluations. Plots of key ODYN outputs were generated for each of the transient analyzed and these are provided in Figures 3-la through 3-4c.

Plots of suppression pool temperature and suppression pool airspace pressure verses time are provided for the MSIVC and PRFO transients at beginning and end of cycle in Figures 3-5 through 3-8. Finally, Figure 3-9 shows the lower plenum pressure for the limiting event (PRFO BOC).

Table 3-4: Summary of Key ODYN Parameters' for ATWS Calculation Event Power Exposure Peak Neutron Peak Heat Peak Vessel Press.

(MWt)

Flux Flux ()2 (psi g)

Flux..%.

/Flow (%)

MSIVC

((

MSIVC PRFO PRFO Notes:

1. Values enclosed in parentheses represent the time of peak values in seconds.
2. The peak neutron and heat fluxes are normalized to their respective initial power.

3-10

NEDO-33532 Revision 2 Table 3-5: Summary' of Peak Suppression Pool Temperature, Containment Pressure and Integrated SRV Flow Peak

.Peak Suppression

  • owerSuppression Pool Integrated SSV ower

.Pool Airspace and SRV Flow at Temperature

-Pressure Hot Shutdown 2 Event

/Flow(%)

Exposure (OF)

(pSig)

(10 I MSIVC

((I MSIVC PRFO PRFO

]

Notes:

1. Values enclosed in parentheses represent the time of peak values in seconds.
2. Hot shutdown, in the ODYN ATWS evaluation, is defined as when the neutron flux is less than 0.1% for more than 100 sec.

3-11

NEDO-33532 Revision 2 Table 3-6: Sequence of Events for MSIVC at BOC Event Time (s)

MSIV Isolation Initiates MSIVs Closed Peak Neutron Flux ((

High Reactor Pressure Recirculation Pump Trip Setpoint Reached Opening of the First Relief Valve (fully open)

Recirculation Pumps Tripped Peak Heat Flux Occurs ((

))

High Reactor Pressure Feedwater Pump Trip Peak Vessel Pressure ((

SLCS Pumps Start Boron Solution Reaches Lower Plenum BIIT Reached Hot Shutdown Boron Weight (HSBW) Injected and Water Level Raised Peak Suppression Pool Temperature ((]

Water Level Restored to Normal Band Hot Shutdown Achieved (Neutron flux below 0.1% for more than 100 seconds) 3-12

NEDO-33532 Revision 2 Table 3-7: Sequence of Events for PRFO at BOC Event Time (s)

MSIV Isolation Initiates R

MSIVs Closed Peak Neutron Flux ((

High Reactor Pressure Recirculation Pump Trip Setpoint Reached Opening of the First Relief Valve (fully open)

Recirculation Pumps Tripped Peak Heat Flux Occurs ((

))

High Reactor Pressure Feedwater Pump Trip Peak Vessel Pressure ((

))

SLCS Pumps Start Boron Solution Reaches Lower Plenum BIIT Reached HSBW Injected and Water Level Raised Peak Suppression Pool Temperature ((

Water Level Restored to Normal Band Hot Shutdown Achieved (Neutron flux below 0.1% for more than 100 seconds) 3-13

NEDO-33532 Revision 2 Table 3-8: Sequence of Events for MSIVC at EOC Event Time..s" MSIV Isolation Initiates MSIVs Closed Peak Neutron Flux ((

))

High Reactor Pressure Recirculation Pump Trip Setpoint Reached Opening of the First Relief Valve (fully open)

Recirculation Pumps Tripped Peak Heat Flux Occurs ((

))

High Reactor Pressure Feedwater Pump Trip Peak Vessel Pressure ((

))

SLCS Pumps Start Boron Solution Reaches Lower Plenum BIT Reached HSBW Injected and Water Level Raised Peak Suppression Pool Temperature ((

))

Water Level Restored to Normal Band Hot Shutdown Achieved (Neutron flux below 0.1% for more than 100 seconds) 3-14

NEDO-33532 Revision 2 Table 3-9: Sequence of Events for PRFO at EOC Event Time s)

MSIV Isolation Initiates MSIVs Closed Peak Neutron Flux ((

]

High Reactor Pressure Recirculation Pump Trip Setpoint Reached Opening of the First Relief Valve (fully open)

Recirculation Pumps Tripped Peak Heat Flux Occurs ((

))

High Reactor Pressure Feedwater Pump Trip Peak Vessel Pressure ((

SLCS Pumps Start Boron Solution Reaches Lower Plenum BIIT Reached HSBW Injected and Water Level Raised Peak Suppression Pool Temperature ((

1]

Water Level Restored to Normal Band Hot Shutdown Achieved (Neutron flux below 0.1% for more than 100 seconds) 3-15

NEDO-33532 Revision 2 Table 3-10: Acceptance Criteria Results Acceptance Allowed Value Limiting Result ATWS Event and Criteria" Conditions Peak Vessel pressure 1500 1478 (psig)

U Peak Cladding 2200 Note 1 Temperature ('F)

Peak Suppression Pool temperature 185 175.9 (OF)

Peak Suppression 56 10.4 Pool pressure (psig)

Notes:

1. Fuel integrity is demonstrated by ensuring that peak cladding temperature is below the IOCFR50.46 limit of 2200'F and fuel local cladding oxidation is below the IOCFR50.46 limit of 17 % total clad thickness. The peak cladding temperature for ATWS has been confirmed to be less than 16007F for GNF2 and GE14. Because the cladding temperature increase for ATWS is of short duration and limited magnitude, cladding oxidation is not explicitly calculated in the ATWS analysis.

Table 3-11: Peak Pressures for Other System Evaluations Parameter Value Comments Lower Plenum 1212 psig The lower plenum pressure for all Pressure transients was reviewed and compared to the initiation time of the SLCS pumps.

1212 psig is the highest lower plenum pressure that occurs after the initiation of the SLCS pumps.

3-16

NEDO-33532 Revision 2 Figure 3-1a: MSIVC BOC - GEl4 and GNF2 Fuel 3-17

NEDO-33532 Revision 2 Figure 3-1b: MSIVC BOC - GE14 and GNF2 Fuel 11 3-18

NEDO-33532 Revision 2 Figure 3-1c: MSIVC BOC - GE14 and GNF2 Fuel

((

3-19

NEDO-33532 Revision 2 Figure 3-2a: PRFO BOC - GE14 and GNF2 Fuel

[I 3-20

NEDO-33532 Revision 2 Figure 3-2b: PRFO BOC - GE14 and GNF2 Fuel 3-21

NEDO-33532 Revision 2 Figure 3-2c: PRFO BOC - GE14 and GNF2 Fuel 3-22

NEDO-33532 Revision 2 Figure 3-3a: MSIVC EOC - GE14 and GNF2 Fuel 3-23

NEDO-33532 Revision 2 Figure 3-3b: MSIVC EOC - GE14 and GNF2 Fuel 3-24

NEDO-33532 Revision 2 Figure 3-3c: MSIVC EOC - GE14 and GNF2 Fuel

[1 3-25

NEDO-33532 Revision 2 Figure 3-4a: PRFO EOC - GE14 and GNF2 Fuel 1]

3-26

NEDO-33532 Revision 2 Figure 3-4b: PRFO EOC - GE14 and GNF2 Fuel 3-27

NEDO-33532 Revision 2 Figure 3-4c: PRFO EOC - GE14 and GNF2 Fuel 3-28

NEDO-33532 Revision 2 Figure 3-5: Containment Response MSIVC BOC Er Figure 3-6: Containment Response PRFO BOC Er 3-29

NEDO-33532 Revision 2 Figure 3-7: Containment Response MSIVC EOC Figure 3-8: Containment Response PRFO EOC

((

3-30

NEDO-33532 Revision 2 Figure 3-9: Lower Plenum Pressure PRFO BOC

3.6 CONCLUSION

S The ATWS evaluation incorporating the SSV capacity increase, SRV/SSV setpoint increase, setpoint tolerance increase to 3% and the increase in the ATWS recirculation pump trip setpoint confirms that all ATWS acceptance criteria are met. Therefore, the implementation of these increases in SRV/SSV setpoints, setpoint tolerance and ATWS pump trip setpoint at the PNPS is acceptable. The ATWS evaluations are based on a 39 gallon per minute Standby Liquid Control System injection rate with a 8.42% weight concentration of Sodium Pentaborate solution containing 54.5% enriched Boron-I0. The peak lower plenum pressure during the operation of the Standby Liquid Control System is 1212 psig. The Standby Liquid Control system is required to attain an equivalent Boron injection rate with a lower plenum pressure up to 1212 psig in order for these analyses to remain valid. The Standby Liquid Control System performance is addressed in Section 5.3. The high pressure feedwater pump trip setpoint is reduced and is a required function for ATWS mitigation.

3-31

NEDO-33532 Revision 2 4

ECCS/LOCA EVALUATION 4.1 ECCS/LOCA PERFORMANCE EVALUATION The most recent SAFER/GESTR-LOCA analysis for PNPS is reported in References 4 and 5.

The analysis was performed using the SAFER/GESTR-LOCA application methodology approved by the NRC.

The impact of safety valve setpoint relaxation on the ECCS-LOCA performance for Boiling Water Reactor (BWR) 2-6 plants has been evaluated on a generic basis in the Boiling Water Reactor Owners Group (BWROG) report approved by the NRC (Reference 1).

The ECCS conclusions contained in Reference 1 apply to Reference 4.

)). As such, plant-specific evaluations of ECCS performance and the impact of safety valve set point relaxation on LOCA Licensing Basis PCT are not required.

It is also noted that SSV actuation is not predicted for the LOCA analysis and therefore, the SSV modifications do not impact the ECCS SAFER/GESTR-LOCA Analyses.

4-1

NEDO-33532 Revision 2 5

CONTAINMENT RESPONSE AND LOADS ANALYSIS This section presents the results of the various containment related evaluations in support of the SRV and SSV 40 psi setpoint increase and a setpoint tolerance increase from 1% to 3%. This evaluation also addresses an increase in the capacity of the SSVs from 644,501 lbm/hr to 1,126,200 lbmlhr @ 1240 psig +3% overpressure accumulation.

5.1 CONTAINMENT PRESSURE AND TEMPERATURE FOR DBA LOCA The Design Basis Accident (DBA)-LOCA short-term containment analyses includes the large Recirculation Suction Line Break (RSLB) which is used to establish the peak drywell pressure and also used to establish the containment conditions used to evaluate the DBA-LOCA hydrodynamic loads. The DBA-LOCA analysis does not predict actuation of SSVs or SRVs because the break size is large enough to cause reactor vessel depressurization without actuation of the SRVs.

Therefore, the current short-term containment analysis for PNPS remains unaffected for the SRV and SSV changes. The effects on the peak suppression pool temperature and wetwell pressure for the long-term DBA-LOCA were considered. Changes to the SSV and SRV safety valve setpoints, tolerance and SSV capacity have no effect on the DBA-LOCA event because the vessel depressurizes without any SRV or SSV actuations. Therefore, there is no effect on the DBA-LOCA containment pressure and temperature and on the DBA-LOCA suppression pool temperature and wetwell pressure. The DBA-LOCA containment pressure and suppression pool temperature used to demonstrate available Net Positive Suction Head (NPSH) margins are also unaffected.

5.2 SMALL STEAM LINE BREAKS Small steam line break spectrum established in Reference 6 (0.05, 0.10, 0.35, 0.50 and 1.0 ft2 breaks) and Reference 7 (0.01 and 0.02 ft2 breaks) was evaluated to determine the impact on the drywell temperature for generating the Environmental Qualification (EQ) curve. The SLBs that generally produce the most limiting peak drywell temperature are large enough to maintain the initial vessel pressure below the SRV setpoints and also large enough to depressurize through the break without requiring SRV actuation. Therefore, an increase in SRV opening setpoint and tolerance has no effect on the larger SLBs that do not have SRV actuation. The drywell temperature response for smaller SLBs that require SRV actuation may be slightly affected. For these breaks, the peak drywell temperature is well below that of the larger limiting SLB.

Furthermore, the peak drywell temperature for the smaller SLBs occurs later in the event at the time the drywell sprays are actuated. Since this time occurs after many SRV actuations the peak temperature is controlled by the integrated steam flow to the drywell which is not affected by the change in the SRV setpoint and tolerance increase. The long-term drywell temperature, after the 5-1

NEDO-33532 Revision 2 sprays are initiated, is controlled by the break steam mass flow to the drywell and the spray temperature. The drywell spray temperature is controlled by the suppression pool temperature that is mainly governed by energy transferred to the suppression pool through the SRVs. The rate of SRV energy transfer to the suppression pool is controlled by the defined vessel depressurization rate, the initial vessel liquid inventory, and decay heat. These factors are not affected by the changes to the SRV's. The break steam flow to the drywell is controlled by the vessel pressure response, which is determined by the assumed vessel depressurization rate. This parameter is also unaffected by the change in the SRV setpoint and tolerance. Since the steam break flow and drywell spray temperature response for the smaller SLBs are not impacted by the SRV changes, the drywell temperature response for the smaller SLBs is also not impacted. The SRV's maintain the vessel pressure below the SSV setpoint for even the smallest break analyzed so there is no SSV actuation. Therefore, the subject SRV and SSV changes have no impact on the bounding drywell temperature response and the EQ curve remains valid.

SLB's from 1.0 ft2 to as small as 0.01 ft2 were also evaluated in the NPSH assessment where the impact of the setpoint tolerance increase was determined to have negligible impact on the long term suppression pool temperature.

5.3 IBA AND SBA The effect on Intermediate and Small Break Accidents (i.e., IBA and SBA) was also evaluated.

The containment pressure and temperature response for the IBA and the SBA, were originally evaluated as part of the Mark I Containment Program and documented in the Plant Unique Load Definition report (PULD - Reference 8).

PNPS profiles from Reference 8 are calculated in accordance with the generic Mark I Load Definition Report (Reference 9) and are based on endpoint type calculations, which are controlled by the amount of initial stored energy in the primary system and decay heat. There is no increase in the initial primary system stored energy or decay heat due to an increase in the SRV safety valve setpoint and tolerance. Therefore, there is no effect on the IBA and SBA event results presented in Reference 8. Additionally, for the SBA the drywell temperature response is taken to be bounding, constant value of 340'F. This bounding drywell temperature value would not change due to an increase in SRV setpoint tolerance.

5.4 NUREG-0783 LOCAL SUPPRESSION POOL TEMPERATURE The Reference 10 plant drawings identified that the PNPS SRV quencher elevation is above the Emergency Core Cooling System (ECCS) pump suction elevation and therefore, per the NRC conditional acceptance of NEDC-30832 (Reference 11), PNPS is no longer required to meet NUREG-0783 local suppression pool temperature limits for events with SRV discharge.

5-2

NEDO-33532 Revision 2 5.5 DBA LOCA HYDRODYNAMIC LOADS The DBA LOCA hydrodynamic loads, such as pool swell, vent thrust, condensation oscillation and chugging are dependent on the containment pressure and temperature response during the DBA LOCA. Because the containment DBA LOCA pressure and temperature response are not affected by the SSV and SRV safety valve setpoint changes, the DBA LOCA hydrodynamic loads defined for PNPS are also unaffected.

5.6 SRV AND SSV DYNAMIC LOADS The SRV discharge loads are defined by parameters which include:

" SRV discharge line and containment geometry

" Water leg length in the SRV discharge line at the time of SRV opening

" SRV flow capacity and SRV opening pressure Since an SRV setpoint increase and the setpoint tolerance relaxation will increase the SRV safety valve opening pressure, the SRV discharge dynamic loads are expected to increase. Entergy will need to evaluate the factors affecting the SRV dynamic loads.

The SSV discharge loads are affected by parameters which include the SSV flow capacity and SSV opening pressure.

Since an SSV setpoint increase and setpoint tolerance relaxation will increase the SSV safety valve opening pressure and an increase in the SSV throat size will increase the SSV flow capacity, the SSV dynamic loads are expected to increase. Entergy will need to evaluate the factors affecting the SSV dynamic loads..

5.7 RIPD EVALUATION During normal operation, there is no SRV or SSV actuation. Therefore, the SRV setpoint and tolerance change or SSV modification have no effect on the Reactor Internal Pressure Differences (RIPDs) at normal conditions.

For upset conditions, any event in which SRVs will actuate would have a faster depressurization due to increased SRV flow as a result of SRV setpoint and tolerance change, causing higher RIPDs. ((

)) In addition, SSV does not actuate due to higher setpoint than SRV and SRV actuation to maintain pressure below SSV setpoint.

Therefore, the RIPD results at upset conditions remain valid for the SRV setpoint and tolerance change.

5-3

NEDO-33532 Revision 2 The limiting emergency event used for RIPD is an inadvertent actuation of all ADS valves.

Increased SRV flow as a result of SRV setpoint and tolerance change would have a faster depressurization and thus would result in higher RIPDs. ((

)) In addition, SSV is not part of ADS. Thus, the RIPD results at emergency conditions are still applicable for the SRV setpoint and tolerance increase or SSV modification.

The limiting faulted event for RIPD is an instantaneous circumferential break of one main steam line, for which SRV or SSV does not actuate. Therefore, the SRV setpoint and tolerance change or SSV modification has no effect on the RIPD results at faulted conditions.

As part of RIPD, the analyses for acoustic and flow-induced loads on jet pump, core shroud and shroud support due to recirculation line break are not affected by SRV setpoint and tolerance change because the SRVs will not actuate during the event. Therefore, the SRV setpoint and tolerance increase or SSV modification does not impact the acoustic and flow induced load analyses.

5.8 ATWS Suppression Pool temperatures during an ATWS are provided as reported in section 3 of this report.

The increase in SSV capacity with its discharge directly to the Drywell (DW) has the potential to increase the DW temperature and challenge the DW temperature for qualification of the Neutron Monitoring System equipment. This was evaluated as a BWROG activity in response to RG 1.97 and is addressed in GE-NE-C5100121-01 (Reference 12).

GE-NE-C5100121-01 (Reference 12) documents a BWROG activity to evaluate the drywell temperature response during an ATWS for those few Mark I plants that have SSV which discharge directly to the drywell atmosphere, including PNPS. That report identified Dresden as a bounding plant and an analysis was performed, based on the Dresden reactor system and containment configuration which could be applied to all affected plants in this group.

The Dresden plant was identified as the bounding plant based upon a comparison of selected ratios of critical parameters for each plant identified. The bounding plant selection criteria was based upon the following ratios:

  • SSV capacity to rated thermal power

" SSV capacity to DW volume 5-4

NEDO-33532 Revision 2

  • SRV capacity to rated thermal power The resulting drywell atmosphere temperature and pressure response was provided in Reference 12 to the participating BWROG members, for their use in qualifying the Neutron Monitoring System (NMS) instrumentation for ATWS drywell atmosphere conditions.

The change to the PNPS SSV capacity was reviewed to assure that PNPS remains bounded by the Dresden analysis results in Reference 12. The proposed changes included an increase in the SSV capacity from 644,501 Ibm/hr to 1,126,200 lbm/hr @ 1240 psig +3% overpressure accumulation which with 2 SSVs would increase the total SSV capacity from the previously assumed 1290000 lb/hr to 2252400 lb/hr @ 1240 psig +3% accumulation.

Based upon the minimum DW volume of 132000 ft3 as identified in Table 5.2-1 of the PNPS FSAR, the resulting SSV capacity to DW volume ratio is increased from the value of 8.8 lbm/hr/ft3 in Table 1 of Reference 12 to a new value of 17.1 lbm/hr/ft3. However, this value remains substantially below the Dresden value of 31.3 lbm/hr/ft3 reported in Table I of Reference 12 and therefore still bounded by the Dresden value defined as the bounding plant.

The SRV capacity is not impacted by the proposed changes and therefore the previous PNPS ratio of SRV capacity to rated thermal power of 1606 lbm/hr/MWt will remain well bounded by the Dresden value of 1088 lbm/hr/MWt as reported in Table 1 of Reference 12.

Based upon the above parametric evaluation, the PNPS ATWS drywell temperature response with the proposed changes to the SRV and SSV setpoints, tolerances and capacities is still expected to be bounded by the ATWS drywell temperature profile defined in Reference 12 for qualification of the Neutron Monitoring System.

5-5

NEDO-33532 Revision 2 6

HIGH PRESSURE SYSTEMS PERFORMANCE 6.1 HPCI & RCIC - SYSTEM DESCRIPTION AND FUNCTIONS The HPCI system, an ECCS, is designed to provide sufficient core cooling to prevent excessive fuel cladding temperature in the event of a small break loss of coolant accident that does not depressurize the reactor quickly enough to permit timely operation of the low pressure ECCS.

The HPCI system accomplishes this function by injecting coolant makeup water into the pressure vessel, with a turbine driven pump. HPCI was designed to pump water at the rate of 4250 gpm into the reactor vessel over a wide range of pressures, from 165 psia to 1135 psia. PNPS requirements are for HPCI to deliver 4250 gpm to the reactor vessel over the range of 150 psig to 1000 psig, and 3000 gpm to a peak reactor pressure of 1126 psig. The HPCI system also serves as a backup to the RCIC system to maintain the nuclear boiler in the standby condition in the event the vessel becomes isolated from the main condenser and feedwater makeup flow.

The RCIC system provides makeup water to the reactor vessel whenever the vessel is isolated from the main condenser and feedwater makeup. The RCIC system can also provide makeup water during shutdown whenever the normal water supply is unavailable. RCIC uses a turbine driven pump to maintain adequate reactor vessel water level. RCIC was designed to supply makeup water to the reactor at a capacity of 400 gpm over a dome pressure range of 165 psia to 1135 psia. In 1982 an SRV setpoint increase to 1115 psig resulted in an increased pressure range of 165 psia to 1141 psia for the RCIC system (Reference 13). The most significant effect of increasing the SRV setpoint and relaxing the SRV tolerance on the HPCI and RCIC systems operation is the maximum dome pressure at which they are required to deliver water to the reactor. Both systems are required to provide injection into the reactor pressure vessel at the lowest group of SRVs setpoints (including drift). Increasing the allowable setpoint tolerance to 3% while increasing the current setpoint of 1115 psig to 1155 psig increases the maximum vessel pressure for HPCI and RCIC injection by 64 psi to 1205 psia.

6.1.1 Pump Flow and Head Increasing the SRV setpoint and tolerance while increasing the required maximum discharge pressure of the pumps does not change the flow requirement. Because there is no increase in flow or maximum operational temperature, the NPSH required, or available, does not change.

Because there is no increase in flow, the pressure losses due to pipe friction remain unchanged.

If the original conservatism in the assumed head losses for RCIC is maintained, then the Total Dynamic Head (TDH) is increased to 2962 feet.

The RCIC pump speed is required to be increased to at least 4628 rpm to meet the new TDH (with no allowance for pump degradation).

6-1

NEDO-33532 Revision 2 The original design for the HPCI system made conservative, bounding assumptions for dynamic and static head losses to determine the pump's TDH requirements.

PNPS has performed a detailed analysis (Reference 17) of the piping configuration for the HPCI system to determine both dynamic and static head losses.

Utilizing the more accurate result from the analysis demonstrates HPCI performance remains acceptable with a TDH required of2913 feet. HPCI has a TDH of 2920 feet available.

6.1.2 System Boundary Components An assessment of pressure integrity for the HPCI and RCIC system was made by comparing the design conditions for the piping and components at the higher system operating conditions. The maximum reactor pressure and temperature design conditions do not change. There is no change to the design requirements of the piping and components attached to the reactor vessel 6.1.3 Pump and Turbine The pump and turbine speed required to meet the TDH requirement for the HPCI and RCIC systems is bounded by the current system design. There is no change in the HPCI turbine or pump power requirements, steam flow to the turbine, or system reliability.

To meet the new TDH requirements, the RCIC turbine and pump speed, power, and steam flow requirements require an increase to meet the discharge pressure requirements.

6.1.4 Instrumentation Instrument specifications, according to the instrument data sheet, have been reviewed for application to the HPCI and RCIC required pressure increase. Because the maximum reactor pressure and temperature design conditions exceed the conditions required for the SRV setpoint and setpoint tolerance increase, there is no change to the design pressure requirements of the instrumentation. Because there is no increase in makeup flow to the vessel, for either HPCI or RCIC, no change is required for flow instrumentation. Exhaust trip setpoints and rupture disks do not need to be changed because changes in exhaust pressure, for either turbine, are negligible.

There is no increase in steam flow for HPCI. Therefore, there is no change in leak detection setpoints. RCIC steam flow will increase, due to an increase in turbine horsepower, and the leak detection setpoint for high steam flow will require revision.

Because there is no increase in maximum containment pressure during an accident, the high exhaust pressure trip remains unaffected.

6-2

NEDO-33532 Revision 2 6.1.5 Motor Operated Valves The system valves that are impacted by reactor pressure will require re-evaluation by the PNPS Generic Letter 89-10 program for operability at the increased operating pressures expected at the required maximum vessel pressure conditions. The specified full differential pressure values for the steam supply and pump discharge valves shall be revised to reflect the increased SRV tolerances and the higher system operating pressures.

6.1.6 Start Up Transient Because for HPCI there is no change in steam flow or maximum turbine speed, the slight increase in reactor pressure will not affect the start up transient. The effect of the increased steam flow to RCIC has been separately evaluated and will not affect the startup transient.

Therefore, the time to reach the higher turbine speed required to inject at the higher pressure will remain within existing design requirements.

6.1.7 Key Assumptions None Design values for input parameters are the same for both units unless specifically noted.

6.1.8 Key Input for RCIC Item Parameter Unit Value,..

1 Maximum design value for system start time to seconds 75 rated flow (system in standby line up) 2 Maximum design value for reactor pressure for psia 1141 system operation 3

Maximum design value for system injection gpm 400 flow rate 5

Rated turbine speed rpm 4500 6

Maximum design value for turbine exhaust psia 25 pressure 7

Turbine exhaust high pressure trip psig 46 8

Maximum design pressure value for turbine psig 1250 9

Maximum design pressure value for pump psig 1500 6-3

NEDO-33532 Revision 2 6.1.9 Key Input for HPCI Item Parameter Unit" a lue. ",,7 1

Maximum design value for system start time to seconds 90 rated flow (system in standby line up) 2 Maximum design value for reactor pressure for psia 1141 system operation 3

Maximum design value for system injection gpm 4250 flow rate to 1000 psig 4

Maximum design value for system injection gpm 3000 flow rate to peak vessel pressure (item 2) 5 Rated turbine speed rpm 4000 6

Maximum design value for turbine exhaust psia 65 pressure 7

Turbine exhaust high pressure trip psig 150 8

Maximum design pressure value for turbine psig 1250 9

Maximum design pressure value for pump psig 1500 6.1.10 Key Results The RCIC and HPCI systems are designed to provide rated flow to the reactor up to maximum reactor dome pressure of 1141 psia. The maximum reactor dome pressure required for injection is the setpoint of the lowest group of SRVs, including setpoint drift. For a setpoint increase to 1155 psig and tolerance increase from 1% to 3%, the maximum dome pressure that the high pressure systems are required to inject rated flow, increases by 64 psi to 1205 psia (Tables 6-1 and 6-2).

The original system design specifications require a pump pressure rise (TDH) of 2800 feet in order for the systems to deliver water from the suppression pool to the reactor at the high pressure condition. The 2800 feet of head was a bounding conservative design specification for piping losses and elevation changes. Using actual plant analysis the new required TDH of 2913 feet is still met for HPCI because the rated flow of 4250 gpm is not required above 1000 psig. An increase in RCIC turbine speed (4628 rpm versus the original 4500 rpm design specification) is required to provide a TDH of 2962 feet. The RCIC turbine has been evaluated up to a speed of 4700 rpm.

6-4

NEDO-33532 Revision 2 Because the turbine steam supply pressure increase is less than 65 psi, there is no effect on the systems' startup time, or the severity of the startup transient.

The NPSH available for the HPCI and RCIC pumps does not change because there is no change in required flow or allowable suction temperature. Pressure losses from the pump to the vessel, due to piping friction or elevation differences, do not change.

The SRV setpoint increase requires a corresponding change to the pump discharge pressure and TDH. Surveillance test procedures, that verify pump performance, will require revision to demonstrate pump performance. The steam supply and pump discharge MOVs will require re-evaluation for operability at the increased differential pressures.

No changes are required to the SLB detection instrumentation setpoints for the HPCI system, because there is no increase in the maximum steam flow.

The RCIC SLB detection instrumentation setpoint will require a revision to maintain the analytical limit of 300% above the maximum required steam flow.

Table 6-1 Key Results for RCIC Ite PaameerUnits Current.

Proposed Change ItemDeig Parameter D

n Design 1

Setpoint for lowest group SRV psig 1115 1155

+40 2

Vessel pressure at setpoint for lowest psia 1141 1205

+64 group of SRVs with drift 3

Required flow with vessel pressure at gpm 400 400 0

setpoint for lowest group SRV with drift 4

Required TDH feet 2800 2962

+162 5

Rated pump speed (allowance for rpm 4500 4700

+200 pump degradation included)

I I

_I 6-5

NEDO-33532 Revision 2 Table 6-2 Key Results for HPCI Item Parameter Units Current Proposed Change Design Design.

1 Setpoint for lowest group SRV psig 1115 1155

+40 2

Vessel pressure at setpoint for lowest psia 1141 1205

+64 group of SRVs with drift 3

Required flow with vessel pressure at gpm 3000 3000 0

setpoint for lowest group SRV with drift 4

TDH required feet 2751 2913

+162 5

Rated pump speed rpm 4000 4000 0

6.1.11 Recommendations and Observations The HPCI and RCIC systems' steam supply and pump discharge re-evaluation for operability at the new, higher pressures.

MOVs will require The RCIC system requires modification to increase the maximum turbine speed.

The RCIC SLB detection setpoint will require revision for increased steam.

6.2 SETPOINT CALCULATIONS 6.2.1 Description The purpose of this section is to evaluate the impact of the proposed main steam SRV opening setpoint tolerance relaxation and Tech Specs change to increase the set point tolerance of the SRVs from 1% to 3% on the following setpoint functions at PNPS Nuclear Power Station.

" Anticipated Transient Without Scram (ATWS) High Pressure Recirculation Pump Trip (RPT)

" Reactor Core Isolation Cooling (RCIC) High Steam Flow Isolation The ATWS High Pressure RPT setpoint function initiates RPT and Alternate Rod Insertion (ARI) when the reactor pressure exceeds the switch setpoint, to provide a back-up method for controlling reactivity in the unlikely event that the Reactor fails to scram when required.

6-6

NEDO-33532 Revision 2 The RCIC High Steam Flow Isolation setpoint function limits the uncontrolled release of radiation to the environment for a RCIC SLB, by isolating (closure) of the RCIC Steam Supply Isolation Valves, tripping the RCIC Turbine, and isolating the Minimum Flow Bypass Valve.

6.2.2 Inputs and Assumptions The RCIC High Steam Flow Isolation analytical limit has historically been set at 300% of rated flow as described in SIL-475 (Reference 15). The RCIC High Steam Flow setpoint calculation inputs are summarized in a setpoint calculation summary document (Reference 14). The ATWS analysis inputs and assumptions are provided in Section 3. Entergy will establish the ATWS high pressure RPT AV and NTSP based on the new transient analysis setpoint established in Section 3.

6.2.3 Evaluation The ATWS high pressure RPT AV and NTSP will be determined by Entergy. The transient analysis setpoints are summarized below:

.... Current Transient New. Transient

  • "".Function Analysis Setpoint:

Analysis Setpoint 1180 psig ATWS High Pressure RPT Upper AV 1220 psig (Reference 3)

The RCIC Steam Supply Isolation AV and NTSP were calculated in Reference 14 using GEH Instrument Setpoint Methodology (Reference 16). The ALs are summarized below.

Function Current AL New AL RCIC Turbine 219.9 Inch H20 262.373 Inch H20 Steam Line High Flow 300% Rated 300 % Rated RCIC RCIC Flow Steam 6.2.4 Conclusion This evaluation concludes that the setpoints for the ATWS High Pressure Recirc Pump Trip and the RCIC High Steam Flow Isolation functions are affected by the Main Steam Safety Valve (MSSV) setpoint tolerance relaxation.

6-7

NEDO-33532 Revision 2 6.3 STANDBY LIQUID CONTROL SYSTEM The Standby Liquid Control System (SLCS) is designed to shut down the reactor from rated power condition to cold shutdown in a postulated event in which all or some of the control rods cannot be inserted or during a postulated ATWS event. The SLCS accomplishes this function by pumping a sodium pentaborate solution into the vessel at a prescribed boron injection rate in order to provide neutron absorption and achieve a subcritical reactor condition.

The original performance design basis for the SLCS was that it must be capable of injecting the system design rated flow into the reactor vessel using a single SLCS pump at all reactor operating pressures up to the reactor design pressure of 1250 psig. This method has been superseded by the use of the maximum reactor vessel pressure occurring during the limiting ATWS event when the SLCS is in operation in consideration of NRC Information Notice 200-13.

Entergy will ensure that the ATWS analyses performed in Section 3 are based on the SLC system delivering 39 gpm of 8.42% sodium pentaborate solution with a minimum B10 enrichment of 54.5%. These SLC system equipment parameters are the minimum required by PNPS Technical Specifications and provide a hot shutdown capability equivalent to 10CFR50.62 requirements to inject 86 gpm of 13% sodium pentaborate solution with a B10 enrichment of 19.8% (natural enrichment). No changes to the SLC performance are necessary because of the proposed changes to the SRV and SSV configuration to comply with 10CFR50.62 requirements for a SLC system.

ATWS specific injection requirements stated in Section 3 of this report are met provided that the SLC system relief valve remains closed against the maximum lower plenum pressure of 1212 psig, which occurs during SLC system operation. Entergy will evaluate the SLC system relief valve setpoint to ensure the relief valve remains closed when the SLC system is in operation so that the system performance assumed in Section 3 is valid.

6-8

NEDO-33532 Revision 2 7

APPENDIX R ANALYSIS Reference 6 for PNPS demonstrates that no SSV actuation is predicted so the SSV modifications will have no impact on the Appendix R analysis.

The proposed increased SRV setpoint and tolerance will cause SRV actuation at higher pressure and thus result in a slight delay in the SRV actuation. Consequently, the instantaneous flow rates out of the SRVs are increased due to the higher critical flow rates in comparison to the case with SRVs at currently analyzed setpoint and tolerance. However, the change in the total inventory lost from the vessel due to SRV setpoint tolerance relaxation is negligible. This is because the inventory loss is primarily dependent on the decay heat, which remains unaffected by SRV setpoint tolerance relaxation. Therefore, the vessel water level responses and conclusions in the existing evaluations are still applicable for SRV safety valve setpoint tolerance change.

The suppression pool temperature is mainly governed by energy transferred to the suppression pool through the SRVs. Before depressurization, there is negligible change to the energy transferred to the suppression pool because the increased SRV flow which can occur with the SRV safety valve setpoint tolerance increase, is balanced by reduced periods of SRV flow during SRV cycles. After depressurization, the rate of SRV energy transfer to the suppression pool and total energy transfer to the suppression pool are controlled by the vessel depressurization rate, the initial vessel liquid inventory, and decay heat which are unaffected by the SRV changes.

Thus, the SRV setpoint tolerance change has no adverse impact on the suppression pool temperature, as well as containment temperature and pressure for an Appendix R fire event.

Therefore, the containment response not impacted by the subject changes.

7-1

NEDO-33532 Revision 2 8

REFERENCES

1. GE Nuclear Energy, "BWROG In-Service Pressure Relief Technical Specification Revision Licensing Topical Report," NEDC-31753P, February 1990.
2. GE Nuclear Energy, "General Electric Standard Application for Reactor Fuel (GESTAR),

NEDE-2401 1-P-A-16, October, 2007.

3. GE Nuclear Energy, "Safety Analysis Report for Pilgrim Nuclear Power Station Thermal Power Optimization," NEDO-33050, Rev. 1, October 2002.
4. GE Nuclear Energy, "SAFER/GESTR-LOCA Loss of Coolant Accident Analysis for Pilgrim Nuclear Power Station," NEDC-31852P, Rev. 4, January 2008.
5. GE Nuclear Energy, 0000-0095-407 1-RO, Pilgrim Nuclear Power Station GNF2 ECCS-LOCA Evaluation, February 2009.
6. GE Nuclear Energy, "Pilgrim Nuclear Power Station Containment Heatup Analysis with ANS 5.1 +2 sigma Decay Heat," GE-NE-T23-00749-01, December 1997
7. GE Nuclear Energy, "Pilgrim Nuclear Power Station Containment Heat Removal Analysis,"

GE-NE-T23-00732-01, March 1996.

8. GE Nuclear Energy, "Mark I Containment Program Plant Unique Load Definition, Pilgrim Nuclear Power Station: Unit 1," NEDO-24565 Rev 2, May, 1982
9. GE Nuclear Energy, "Mark I Containment Program Load Definition Report," NEDO-21888, November 1981
10. Pilgrim Drawings: C1A198, Rev 0, C1A363, Rev 0, C1A365 Rev 0 and C1A301 Rev 0.
11. GE Nuclear Energy, "Elimination of Limit on BWR Suppression Pool Temperature for SRV Discharge with Quenchers," NEDO-30832-A, May 1995.
12. GE Nuclear Energy, "Drywell Temperature Response for Neutron Monitoring Equipment System Assessment During ATWS," GE-NE-C5100121-01, November 1995.
13. GE Nuclear Energy, "General Electric Boiling Water Reactor Increased Safety/Relief Valve Simmer Margin Analysis for Pilgrim Nuclear Power Station Unit 1," NEDO-22159, June 1982.

8-1

NEDO-33532 Revision 2

14. GE Hitachi Nuclear Energy, "Instrument Limits Calculation Entergy Operations Inc. Pilgrim Nuclear Power Station RCIC High Steam Flow Isolation," 0000-0112-0077 Revision 2, March 2010.
15. SIL-475, "RCIC and HPCI High Steam Flow Analytical Limit," Revision 2, November 1988.
16. GE Nuclear Energy, "General Electric Instrument Setpoint Methodology,"

NEDC-31336P-A, September 1996, and NEDO-31336-A, September 1996.

8-2