ErZtt?fgy 1 CONDITION REPORT CR-PNP-2006-03677

~

Originator: Ford,Bryan Seth Originator Phone: 8403 Originator Group: Regulatory & Industry Affairs Mgmt Operability Required: Y Reportability Required: Y Supervisor Name: Bethay,Stephen J Discovered Date: 10/04/2006 10:10 Initiated Date: 10/04/2006 10:12 Condition

Description:

The controls to prevent and monitor for corrosion of the drywell shell need to be assessed and strengthened. As a minimum, the following items require review: I ) collection of leakage from drains that would indicate leakage past the refueling bellows such that the leakage can be identified/quantified, 2) documentation of surveillance of drains on the 74 ft and -17 ft elevations, 3) controls to assure that the refueling bellows leakage detection line flow switch is tested and repaired as necessary prior to refueling outages, 4) controls to ensure that the need for additional inspections under the containment IWE program addressed if leakage into the air pocket is identified, and 5 ) modifications to the aging management program for the drywell shell considering the service life of the sealing compound (currently the compound used is not known) used above the sand cushion region.

Immediate Action

Description:

Suggested Action

Description: