ML070790115

From kanterella
Jump to navigation Jump to search
CR-PNP-2006-03677, Controls to Prevent and Monitor for Corrosion of the Drywell Shell Need to Be Assessed and Strengthened
ML070790115
Person / Time
Site: Pilgrim
Issue date: 10/04/2006
From: Ford B
Entergy Corp
To:
Office of Nuclear Reactor Regulation
References
CR-PNP-2006-03677
Download: ML070790115 (1)


Text

ErZtt?fgy 1 CONDITION REPORT

~

Originator: Ford,Bryan Seth Originator Group: Regulatory & Industry Affairs Mgmt Supervisor Name: Bethay,Stephen J Discovered Date: 10/04/2006 10: 10 CR-PNP-2006-03677 Originator Phone: 8403 Operability Required: Y Reportability Required: Y Initiated Date: 10/04/2006 10: 12 Condition

Description:

The controls to prevent and monitor for corrosion of the drywell shell need to be assessed and strengthened. As a minimum, the following items require review: I) collection of leakage from drains that would indicate leakage past the refueling bellows such that the leakage can be identified/quantified, 2) documentation of surveillance of drains on the 74 ft and -17 ft elevations, 3) controls to assure that the refueling bellows leakage detection line flow switch is tested and repaired as necessary prior to refueling outages, 4) controls to ensure that the need for additional inspections under the containment IWE program addressed if leakage into the air pocket is identified, and 5) modifications to the aging management program for the drywell shell considering the service life of the sealing compound (currently the compound used is not known) used above the sand cushion region.

Immediate Action

Description:

Suggested Action

Description: