R N P E H6.02 PILGRIM NUCLEAR POWER STATION Procedure No. 2.1.8.7 ASME CODE VISUAL EXAMINATION OF PRIMARY CONTAINMENT A
stop Think Act Review REFERENCE USE QUALITY RELATED 021 234 2.1.8.7 Rev. 4
REVISION 4 Paqes Affected 4-1 9 REVISION 3 Paqes Affected 9
REVISION 2 Pages Affected 3,7-9,19 REVISION LOG Date Originated 11/05 Description Revise Procedure to allow for use in conjunction with ENN-EP-S-001.
Date Originated 3/02 DescriDtion Add "When identified by Engineering" to Step 7.2[4].
Date Originated 2/00 Description Add Attachment 10 (Drywell Exterior).
2.1.8.7 Rev. 4 Page 2 of 19
1. 0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 TABLE OF CONTENTS Paqe PURPOSE AND SCOPE...................................................................................
4 REFERENCES..................................................................................................
5 DEFINITIONS....................................................................................................
5 DISCUSSION.....................................................................................................
6 P RE CAUT I 0 N S AN D L I M ITAT I 0 N S.................................................................
6 PREREQUISITES..............................................................................................
6 PROCEDURE....................................................................................................
7 ATTACHMENTS................................................................................................
9 ATTACHMENT 1.
DRYWELL 9'..................................................................................
10 ATTACHMENT 2 - DRYWELL 23'................................................................................
11 ATTACHMENT 3 - DRWELL 41'..................................................................................
12 ATTACHMENT 4 - DRYWELL 74'................................................................................
13 ATTACHMENT 5 - DRYWELL 83' AND 93'3-3/4"........................................................
14 ATTACHMENT 6 - DRYWELL HEAD...........................................................................
15 ATTACHMENT 7 - TORUS INTERIOR BAY................................................................
16 ATTACHMENT 8 - TORUS EXTERIOR (LOWER HALF) BAY.................................... 17 ATTACHMENT 9 - TORUS EXTERIOR (UPPER HALF) BAY.....................................
18 ATTACHMENT 10 - DRYWELL EXTERIOR...............................................................
19 2.1.8.7 Rev. 4 Page 3 of 19
1.0 PURPOSE AND SCOPE 1.1 PURPOSE This Procedure is to be used in conjunction with ENN-EP-S-001.
This Procedure provides the method for performing the General Visual Examination of Primary Containment pressure-retaining surfaces in accordance with the requirements of 1 OCFR50.55a(b)(2) and subsection IWE of ASME Section XI. The purpose of these examinations is to detect evidence of degradation that may affect either the structural integrity or leak-tightness of Primary Containment.
The General Visual Examination is performed once every 40 months by personnel selected from the Engineering organization. Some Primary Containment components or areas (such as the Torus ring header, vent system, and Torus submerged areas) examined by the General Visual Examination are inspected every I O years. The examination is the successor to the previously performed Appendix J walkdown and does not require the use of Code-certified inspection personnel but must be performed under the direction of an individual identified as the "Responsible Individual".
The scope of the General Visual Examination includes all interior and exterior accessible pressure-retaining surfaces of the Primary Containment structure and its integral attachments (code class MC), excluding insulated surfaces.
1.2 SCOPE This Procedure applies to the following class MC components:
[l]
Drywell and Drywell head
[Z]
Suppression Chamber (Torus) exterior surface 131
[4]
Suppression Chamber vapor phase surface Containment reinforcing structures such as stiffening rings, manhole frames, and reinforcement around openings
[5]
Suppression Chamber submerged surfaces (once every 10 years)
[6]
Drywell vent system including vent piping, vent header, and downcomers (once every 10 years)
[7]
Drywell exterior and penetrations 2.1.8.7 Rev. 4 Page 4 of 19
2.0 REFERENCES
[I]
ASME Boiler and Pressure Vessel Code,Section XI, 1998 edition with 2000 addenda, Subsection IWE, Category E-A ENN-EP-S-001, "/WE General Visual Confainmenf lnspection" ISIlWEl, "IWE Boundary Drawing - Typical Piping Penetration" ISIIWE2, "IWE Boundary Drawing - Typical Piping Penetration" IS1 IWE3, "IWE Boundary Drawing - Typical Piping Penetration" ISIIWE4, "IWE Boundary Drawing - Typical Instrument Penetration" I
[2]
[3]
[4]
[5]
[6]
[7]
ISIIWE5, "IWE Boundary Drawing - Typical Electrical Penetration for Low Voltage Power, Control & Instrumentation Cable"
[8]
[9]
ISIIWE6, "IWE Boundary Typical Electrical Penetration for Coaxial Cable" ISIIWE7, "IWE Boundary Drawing -Typical Electrical Penetration for Medium Voltage Power Cable"
[I 01
[I I]
[I21 ISIlWE8, "IWE Boundary Drawing - Containment Vessel Section" ISIIWE9, "IWE Boundary Drawing - Drywell Seal & Control Rod Inserts" ISIIWEIO, "IWE Boundary Drawing - CRD Hatch Drywell Penetration X-6"
[I31 ISIIWEI 1, "IWE Boundary Drawing - Ten Feet Zero Inch Diameter Equipment Door Assembly"
[I41 ISIIWE12, "IWE Boundary Drawing - Suppression Chamber Access Penetrations X-200A & X-200B"
[I51 ISIIWEl3, "IWE Boundary Drawing - Personnel Air Lock"
[I 61
[I71 NE1 5.03, "Performing, Reporfing, and Controlling IS1 Acfivities" PNPS RPT-05-001, "PNPS Fourth Ten Year Interval lnservice lnspection Program" 3.0 DEFINITIONS
[I] Definitions of ENN-EP-S-001 apply.
2.1.8.7 Rev. 4 Page 5 of 19
4.0 DISCUSSION 4.1 PERSONNEL CERTIFICATIONS Personnel performing the General Visual Examination are not required to be Code certified but shall meet the relevant requirements outlined in Section 6.0.
5.0 VI 121 r31 6.0
[I1 PRECAUTIONS AND LIMITATIONS These inspections are performed in radiation areas. Special care must be exercised to prevent personnel contamination and minimize dose to individuals performing the inspections. Review the appropriate RWP and follow the instructions using ALARA principles.
Some areas inside Primary Containment may not be sufficiently purged of nitrogen to permit entry immediately after containment is de-inerted. The PNPS Nuclear Safety Coordinatorldesignee must determine whether the atmosphere is breathable in all areas inside containment prior to entry, particularly the Drywell-Torus vents and the ring header.
The Torus ring header, vent surfaces internal to the Torus, and submerged surfaces of the Torus are required to be examined as part of the General Visual Examination only once every 10 years.
PREREQUISITES Approved Radiation Work Permits (RWPs) for examinations in the following areas must be in place:
(a)
Drywell - all elevations (b)
(c)
(d)
(e)
Vent System (f)
Refuel Floor (both surfaces of Drywell head)
Torus Room elevation -17 inboard and outboard of Torus Torus Room elevation 16 (top of Torus)
Torus interior (catwalk only for General Visual Examination) 2.1.8.7 Rev. 4 Page 6 of 19
Adequate illumination supplied by hand-held lanterns or supplemental lighting, if required, shall be used. Binoculars, spotting scopes, periscopes, or other optical aids may be used for remote examinations.
The General Visual Examination shall be performed either directly or remotely by an examiner with near-distance acuity of 20/25 or greater Snellen fraction and far-distance acuity of 20/30 or greater Snellen fraction or equivalent. Acuity shall be demonstrated natural or corrected with at least one eye.
Prior to Drywell entry, an ALARA briefing will be conducted with all Inspectors. As a minimum, the following will be discussed:
(a)
Time saving travel (b)
Areas of responsibility - who goes where (c)
Time saving inspection techniques (d)
Dose rates PROCEDURE Ensure that all required RWPs are activated.
General Visual Examinations shall be conducted in accordance with ENN-EP-S-001 to detect conditions that may affect either the containment structural integrity or leak tightness. Inspection personnel shall work in pairs. Reportable areas are identified as those having discoloration, blistering, flaking, peeling or cracking of the coating, corrosion, pitting, mechanical damage, uncoated areas, or arc strikes.
I List all reportable conditions in the table and plot the location of each area using the diagrams on the Inspection Forms (Attachments 1 through IO). Alternatively, the forms contained in ENN-EP-S-001 (Attachments 7.1, 7.5, and 7.6) may be used to document inspection results. Include area location (azimuth, elevation, etc.), approximate size, and significant details. Photographs should be taken, if possible, and logged on the appropriate Inspection Form. Areas determined to be inaccessible shall be shown by hash marks on the Attachments.
Visually examine the Drywell interior pressure-retaining surfaces using Attachments 1, 2, 3,4, and 5.
Visually examine the interior and exterior pressure-retaining surfaces of the Drywell head using Attachment 6.
Visually examine the Torus interior pressure-retaining surfaces (vapor phase) using.
2.1.8.7 Rev. 4 Page 7 of 19
Visually examine the Torus exterior pressure-retaining surfaces using Attachments 8 and 9.
Visually examine the Drywell exterior and penetrations in the Reactor Building using Attachment I O.
Visually examine the Drywell vent system and ring header (once every 10 years) using.1 of ENN-EP-S-001.
Visually examine Torus submerged areas (once every 10 years) using Attachment 7.1 of ENN-EP-S-001.
RECORDING AND REPORTING CRITERIA The criteria of Section 5.0 of ENN-EP-S-001 shall be used for recording and reporting criteria for the General Visual Walkdown.
The Responsible Individual shall complete Attachment 7.2 of ENN-EP-S-001 (IWE General Visual Examination Evaluation Form) for each area or condition requiring further engineering evaluation.
Attachments 7.1, 7.5, and 7.6 of ENN-EP-S-001 may be used as an alternative to the datasheet forms shown in Attachments 1 through I O of this Procedure.
Condition Reports shall be issued to document reportable conditions. One Condition Report should be written to present the consolidated Inspection Team results for each Attachment area, unless there is a safety concern which requires more immediate processing.
EVALUATION PROCESS All reportable conditions shall be evaluated by the Responsible Individual using.2 of ENN-EP-S-001. Conditions that may affect containment structural integrity or leak tightness shall be accepted by engineering evaluation or corrected by repair or replacement prior to proceeding with an Appendix J Type A test (ILRT) or prior to return to service if no ILRT is scheduled. Acceptance criteria for evaluations shall be determined based on licensing and design requirements for PNPS.
When conditions exist in accessible areas that could indicate the presence of degradation or result in degradation to inaccessible areas, the inaccessible areas shall receive an engineering evaluation for acceptability.
2.1.8.7 Rev. 4 Page 8 of 19
For each inaccessible area evaluated, the following information shall be incorporated into the IS1 Summary Report by the IS1 work organization:
(a)
A description of the type and estimated extent of degradation, and the conditions that led to the degradation.
(b)
An evaluation of each area and the results of the evaluation.
(c)
When identified by Design Engineering, reportable conditions accepted for continued service by engineering evaluation shall be added to the IWE augmented examination scope under Code category E-C and re-examined during each successive 40-month period. If after three successive periods the conditions are essentially unchanged, these augmented examinations shall be discontinued.
A description of necessary corrective actions.
REPORTS All Inspection Forms shall be completed, signed, dated, and submitted to the Responsible Individual.
MSTP Rep Task SO02074 shall be signed off upon completion of the General Visual Examination.
ATTACHMENTS ATTACHMENT 1 - DRYWELL 9' ATTACHMENT 2 - DRYWELL 23' ATTACHMENT 3 - DRYWELL 41' ATTACHMENT 4 - DRYWELL 74' ATTACHMENT 5 - DRYWELL 83' AND 93'3-3""
ATTACHMENT 6 - DRYWELL HEAD ATTACHMENT 7 - TORUS INTERIOR BAY ATTACHMENT 8 - TORUS EXTERIOR (LOWER HALF) BAY ATTACHMENT 9 - TORUS EXTERIOR (UPPER HALF) BAY ATTACHMENT I O - DRYWELL EXTERIOR 2.1.8.7 Rev. 4 Page 9 of 19
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Area Approx Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo Indic.
Elev.
Az. dimen.
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
No.
Wear I
1 ATTACHMENT 1 Sheet 1 of I NORTH DRYWELL 9 I El. 23'-
I 0
90 180 270 360 0
Drywell elevation (rollout)
NORTH DRYWELL 9 I El. 23'-
I 0
90 180 270 360 0
Drywell elevation (rollout)
I80 2.1.8.7 Rev. 4 Page 10 of 19
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Disk Photo Area Approx Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Indic.
Elev.
Az.
dimen.
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
No.
Wear I
NORTH 0
I I I
(
El. 41'-
270 90 I
I El. 23' -
180 DRYWELL 23 I 90 180 270 360 Drywell elevation (rollout)
EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 11 of I 9
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Area Approx Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo Indic.
Elev.
Az. dimen.
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
No.
Wear I
NORTH J
t 0
Area -
270 c DRYWELL 41 I 41' -
EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 12 of 19
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Area Approx Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo Indic.
Elev.
Az. dimen.
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
No.
Wear NORTH 0
1 27 El. 74' -
180 DRYWELL 74 0
2 3 3
Drywell elevation (rollout) 0 DATE EXAMINER SIGNATURES 2.1.8.7 Rev. 4 Page 13 of I 9
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials NORTH DRYWELL 83 I D w e l l Flange 93'3-3134" 0
Area Indic.
No.
I I 270 I
El. 83' -
Approx Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo Elev.
Az. dimen.
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
Wear 180 90 I n 270 3
Drywell elevation (rollout)
EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 14 of I 9
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Area Approx Blister Cracking Indic.
Elev.
Az. dimen.
-ing Flaking Peeling Checking No.
~
NORTH 0
Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
Wear
~
~
DRYWELL HEAD 270 90 I
I I
i Drywell Head elevation 180 EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 15 of 19
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials t
i ! Torus Vapor Phase TORUS INTERIOR BAY # -
I.
I 2
\\
Torus Va or Phase Area Approx Indic.
Elev.
Az. dirnen.
No.
,.?
/
a I
f 1
Torus inboard 1
side waterline r
f i
Torus inboard side waterline El. (-)2'7
I 1
Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
Wear Rollout EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 16 of I 9
I ATTACHMENT8 I
Area Approx Blister Indic.
Elev.
Az. dimen.
-ing Flaking Peeling No.
Sheet I of 1 I
Cracking Pitt-Rust-Discolor Mech.
Arc Dents Disk Photo Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
Wear All Prerequisites (base document Section 6.0) met.
Name (print)
Initials TORUS EXTERIOR (LOWER HALF) BAY # -
Torus centerline 3
,.\\
I BAY #
Torus outboard side at El. (-)OJ3 Torus Exterior Lower Half Rollout
\\
/
/
L EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 17 of I 9
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Area Approx Blister Indic.
Elev.
Az. dimen.
-ing Flaking No.
TORUS EXTERIOR (UPPER HALF) BAY ##
Cracking Pit+
Rust-Discolor Mech.
Arc Dents Disk Photo Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
Wear Torus inboard side at El. (-)03 Torus centerline Torus outboard side at El. (-)03 BAY #
i I
I i
Half Rollout I I !
I I
Torus Exterior Upper i i EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 18 of 19
All Prerequisites (base document Section 6.0) met.
Name (print)
Initials Disk Photo Area Approx Blister Cracking Pitt-Rust-Discolor Mech.
Arc Dents Indic.
Elev.
Az. dimen.
-ing Flaking Peeling Checking ing ing
-ation Damage Uncoated Strikes Bulges No.
No.
No.
Wear DRYWELL EXTERIOR I
NOTE Very little of the Drywell exterior and penetrations are accessible from the Reactor Building. This examination is best conducted with the containment System Engineer to locate areas for examination.
EXAMINER SIGNATURES DATE 2.1.8.7 Rev. 4 Page 19 of 19