Masters, Anthony From:

Lake, Louis (0ý Sent:

Wednesday, January 27, 2010 4:06 PM To:

Masters, Anthony Cc:

Dan naus; Farzam, Farhad; Thomas, George; Carrion, Robert

Subject:

RE: New NCR Categories:

Perform Review Anthony; Some of your question has been asked before and, although not asked by the SIT, some has been addressed by the Progress Energy De-lamination project team. My conversation with Paul produced the following info.

You are correct that initially (during hydro lazing) the crack (de-lamination) got more pronounced. The de-lamination has been monitored since November using strain gages which are monitored on a weekly basis, IR scans and core bores.

There has been no indication of growth since that time. Also there plans call for monitoring by strain gages and acoustic monitoring during the de-tensioning process plus they will inspect the core bores to check for any changes. In addition they plan to perform IR scans at various times during de-tensioning.

I think this addresses your concerns presented below. Let me know if you have any additional questions.

Lou From: Masters, Anthony VU*

Sent: Tuesday, January 26, 2010 6:19 AM To: Lake, Louis Cc: Dan naus; Carrion, Robert; Thomas, George

Subject:

RE: New NCR Ok. Thanks. Please let me know ASAP as to my on-site needs.

Lou - I have a question you may be able to pose (if someone hasn't already asked previously) while you are there.

The NDE and borings were completed some time ago. Since one possible idea is that this delamination and crack has propagated and gotten more pronounced from the first couple of days the opening was made, are there any plans to do any additional NDE or borings to re-confirm the condition is still the same as shown previously during the past NDE/borings? It seems to me that if it is believed that the delamination widened and is shown from pictures taken immediately after the cut until the current condition, that there may also be changes made since the NDE/borings were completed as to the width of the delam and possibly even the total size or area affected. Do their detensioning plans include any monitoring or verification of the delaminated condition and size?

Thanks, Anthony D. Masters, PE Senior Construction Inspector Division of Construction Inspections U.S. Nuclear Regulatory Commission Region II - Atlanta

(404) 562 - 0612 (office phone)

(404) 562 - 0559 (fax)

Anthony.Masters@nrc.gov From: Lake, Louis t

  • Sent: Monday, January 25, 2010 1:53 PM To: Dan naus; Lake, Louis; Masters, Anthony; Carrion, Robert; Thomas, George

Subject:

FW: New NCR All-FYI Bob and Anthony; Unless you have other reasons to be on site during the week of Feb. 1, and based on updates to the info below, I will let you know Wednsday if you are needed for tendon on site activities next week.

Lou From: Chou, Rich IL

  • Sent: Monday, January 25, 2010 1:29 PM To: Powell, Sid Cc: Herrin, Dennis W.; Franke, Mark; Lake, Louis; Sykes, Marvin; Ninh, Son; Morrissey, Thomas; Reyes, Rogerio; Chou, Rich

Subject:

RE: New NCR Sid:

Thanks for information. In this case, I probably will go down Crystal River on 2/8 or 2/9 - 2/12 or 2/13/2010 instead of the original chedule of 2/1 - 2/5/2010.

From: Powell, Sid [mailto: Sid.Powell@pgnmail.com]

Sent: Monday, January 25, 2010 12:35 PM To: Chou, Rich

Subject:

RE: New NCR The following starting dates are from Progress Reporter:

Remove Tendon Caps - 2/2/2010 Implement Detensioning Work Package - 2/8/2010 Start Detensioning - 2/10/2010 Sid Powell SGR/Containment Repair Licensing 352 464-1244 From: Chou, Rich [1]

Sent: Monday, January 25, 2010 10:28 AM To: Powell, Sid

Subject:

RE: New NCR Sid:

Thanks.

2

From: Powell, Sid [2]

Sent: Monday, January 25, 2010 10:23 AM To: Chou, Rich; Rich Chou (richchou5@yahoo.com)

Subject:

New NCR See attached.

Sid Powell SGR/Containment Repair Licensing 352 464-1244 3