L-10-020, Fourteenth Refueling Outage Inservice Inspection Report

From kanterella
(Redirected from L-10-020)
Jump to navigation Jump to search
Fourteenth Refueling Outage Inservice Inspection Report
ML100560196
Person / Time
Site: Beaver Valley
Issue date: 02/22/2010
From: Harden P
FirstEnergy Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-10-020
Download: ML100560196 (239)


Text

FENOC Beaver Valley Power Station FirstEnergyNuclear OperatingCompany P.O. Box 4 Shippingport, PA 15077 Paul A. Harden 724-682-5234 Site Vice President Fax: 724-643-8069 February 22, 2010 L-10-020

'i ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

SUBJECT:

Beaver Valley Power Station, Unit No. 2 Docket No. 50-412, License No. NPF-73 Fourteenth Refuelina Outaae Inservice Inspection Report Enclosed please find the Inservice Inspection (ISI) Summary Report on American Society of Mechanical Engineers (ASME) Class 1, 2, 3, and IWE examinations performed prior to and during the fourteenth refueling outage at Beaver Valley Power Station Unit No. 2 (BVPS-2). The ASME Boiler and Pressure Vessel Code,Section XI, Article IWA-6240 requires an inservice inspection summary report to be submitted to the enforcement and regulatory authorities having jurisdiction at the plant site within ninety calendar days of the completion of each refueling outage. The recent inservice inspection term at BVPS-2 covered the period from August 29, 2008 to November 27, 2009.

The Class 1, 2, 3, and IWE examinations are part of Interval 3, Period 1 of the BVPS-2 ISI schedule, and were performed in accordance with Section XI of the ASME Boiler and Pressure Vessel Code, 2001 Edition, 2003 Addenda.

There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Thomas A. Lentz, Manager -

Fleet Licensing, at 330-761-6071.

Paul A. Harden

Beaver Valley Power Station, Unit No. 2 L-10-020 Page 2

Enclosure:

FirstEnergy Nuclear Operating Company Beaver Valley Power Station, Unit No. 2, Fourteenth Refueling Outage Inservice Inspection Report cc: NRC Region I Administrator NRC Resident Inspector NRR Project Manager Director BRP/DEP Site BRP/DEP Representative

FirstEnergy Nuclear Operating Company Beaver Valley Power Station, Unit No. 2 Fourteenth Refueling Outage Inservice Inspection Report

BEAVER VALLEY POWER STATION UNIT 2 Route 168, Shippingport, PA Inservice Inspection Summary Report Outage 14, Year 2009 Inspection Term: 8/29/2008 to 11/27/2009 Issue date: to9---f0 Owner: FirstEnergy 76 South Main St.

Akron, OH 44308 NRC Docket Number: 50-412 Reactor Supplier: Westinghouse Electric Corporation Commercial Service Date: November 17, 1987 Prepared by: 7

  • Date: ,___-__o RevieweducaPor Date: ,7 0 (t
    • )U Nuclear Program*.
  • Reviewed by: Date: ,z -- ,ý-/ 0 ANII Approved by: cA-- Date: "

Manager, Technical Services Engineering FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 90-DAY REPORT TABLE OF CONTENTS Item Page Number Cover Page 1 Table of Contents 2 Form NIS-l 3-4 Outage Summary 5 ASME XI Vessel, Piping and Support Examinations

1. Class I 5
2. Class 2 5
3. Class 3 6 IWE Examination 6 Pressure Testing 7 Deficiency Resolution 7 Steam Generator Tube Examination 7 NIS-2 Forms 7 Appendix I - Completed Code Examinations 10 pages Appendix II - Repair/Replacement Abstract and NIS-2 Forms 225 pages See Table of Contents (pg 2) for total number of sheets FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisibns of the ASME Code Rules
1. Owner FirstEnergy Nuclear Operating Company, Route 168, Shippingport, PA 15077 (Name and Address of Owner)
2. Plant Beaver Valley Power Station, Route 168, Shippingport, PA 15077 (Name and Address of Plant)
3. Plant Unit 2 4. Owner Certificate of Authorization (if required) N/A
5. Commercial Service Date 11/17/87 ý 6. National Board Number for Unit N/A

.7. Components Inspected Manufacturer or Component or Manufacturer or Installer State or National Appurtenance Installer Serial No. Province No. Board No.

Reactor Coolant Piping Southwest Fabricating N/A N/A N/A Auxiliary Piping Schneider Power N/A N/A N/A 2RCS-REV21 Combustion Engineering CE-9071 160591B 21669 2RCS-SG21A Westinghouse Electric Corp DMGT-1961 485066V W-16599 2RCS-PRE21 Westinghouse Electric Corp 1911 485064V W18695 2RHS-E21A Atlas Industrial 3483 485068V 2853 2R1S-E21B Atlas Industrial 3484 485069V 2854 2RHS-P21A Ingersoll-Dresser 1274-26 N/A N/A 2SIS-P21A Goulds Pumps Inc N235B034 N/A N/A Note: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8/2 in. x 11 in.,

(2) information in items 1 though 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

This form (E0029) may be obtained from the ASME Order Dept., 22 Law Drive, Box 2300, Fa"ield, NJ 07008-2300 See Table of Contents (pg 2) for total number of sheets FORM NIS-1 (Back)

8. Examination Dates 8/29/2008 to 11/27/2009
9. Inspection Period Identification: 8/29/2008 to 12/29/2011
10. Inspection Interval Identification: 8/29/2008 to 8/28/2018
11. Applicable Edition of Section XI 2001 Addenda 2003
12. Date/Revision of Inspection Plan: 1/2-ADM-2039, Revision 10
13. Abstract of Examination and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Appendix I (Code Exams) for examinations performed during Cycle 14 and Refueling Outage 2R14. 2R14 was the first outage in the 1st Period of the 3 rd Ten-Year Interval. Nine examinations were limited in that 90% of the required coverage was not obtained. These examinations will be identified in relief requests for submittal to the NRC.
14. Abstract of Results of Examination and Tests. See text of summary report.
15. Abstract of Corrective Measures. Corrective measures resulting from NDE ISI examinations were necessary in 2R14.

See Deficiency Resolution section (page 7). Visual examinations of bolted connections that found evidence of boric acid leakage resulted in boric acid cleaning and re-examination.

We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date 7-.. 7-110 Signed FirstEnergy Nuclear Operating Co. By \

(Owner)

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 8/29/2008 to 11/27/2009 and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer make any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damageor a loss of any kind arising from or connected with thi inspection.

/9 1.7-J_ )Commissions NB 9428 ANIB, PA 2384 lnspector'OS, nature National Board, State, Province and Endorsements Date 2_ -2_ - 0_

FirstEnergy Nuclear Operating Company, 76 South Main St.,Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 OUTAGE

SUMMARY

During the Fourteenth Refueling Outage (2R14) at the Beaver Valley Power Station, Unit No. 2 (BVPS-2), Inservice Inspection (ISI) examinations were performed on Class 1, 2, 3 and IWE components.

This was the first outage in the first period of the 3 rd Ten-Year Interval. Also included in this report and the counts below, are examinations performed prior to 2R14 during plant operation. The Class 1, 2, 3 and IWE examinations were based on ASME Section XI, 2001 Edition, 2003 Addenda.

ASME XI Class 1, 2, 3 and IWE Credited Examinations (See Appendix I)

1. One-Hundred and thirty-two (132) Class 1 exams were performed and are divided as follows:
a. MRP UT Exams - 11
b. Pressurizer SWOL UT Exams - 12 Nozzle UT Exams - 2 Nozzle IR Section UT Exams - 2
c. Code Case N-722 Bare Metal Exams RV Hot Leg Nozzle (VE) - 3 RV BMI (VE) - 1 RV BMI All Tube Welds (VE) - 1
d. Code Case N-729-1 Exams RV Head All Penetrations (UT) - 1 RV Head Repaired Penetrations (PT) - 6 RV Head Surface (VE) - 1
e. Steam Generator Exams Nozzle IR sections (VT-1) - 2
f. Bolting UT Exams (RV studs) - 19 Visual Exams - 18
g. Piping Weld UT Exams - 14
h. Piping Supports Visual Exams (VT-3) - 33
i. RI-ISI piping VT-2 exams - 6
2. One-hundred and forty-six (146) Class 2 exams were performed and are divided as follows:
a. Vessel Welds UT Exams - 2 VT-2 Exams - 2
b. Pipe Welds Ultrasonic Exams - 22
c. Welded Attachments Penetrant Exams - 12
d. Bolted Connection (VT-2) - 14
e. Piping Supports Visual Exams (VT-3) - 50
f. RI-ISI piping VT-2 exams - 44 FirstEnergy Nuclear Operating Company, 76 South Main, St.,Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87
3. Forty-nine (49) Class 3 exams were performed and are divided as follows:
a. Supports (VT-3) - 35
b. Welded Attachments (VT-1) - 14
4. IWE Examinations (Visual) - 5 Examinations were performed by FirstEnergy Nuclear Operating Company (FENOC) and contracted NDE Technicians. Appendix I compiles the examinations that have been credited toward fulfilling the Ten Year Plan requirements.

Pressurizer Structural Weld Overlay (SWOL) Re-Examinations The six pressurizer nozzle welds where SWOL was applied in 2R12, were re-examined as required during 2R14. All examinations were acceptable.

Code Cases N-722 and N-729-1 Examinations The examinations required by 10CFR50.55a associated with Code Cases N-722 and N-729-1 were completed during 2R14. These examinations included the Reactor Vessel Bottom Mounted Instrumentation (BMI) Nozzles and instrumentation welds per N-722. Volumetric examination was performed on the RV Head penetrations, a bare metal visual exam was completed on the RV Head outside diameter surface, and penetrant examinations were performed on the inside diameter surface of the RV Head for all previously repaired penetrations in accordance with N-729-1.

MRP Examinations MRP-146 was issued in June 2005, requiring that utilities perform an assessment of reactor coolant system normally-stagnant branch lines for the effects of thermal fatigue. MRP-146 was issued with "Needed" requirements, with some implementation; specifically a calculation stating which lines are susceptible to thermal fatigue cracking. Eleven BV2 areas were identified for UT examination in 2R14.

All examinations were acceptable (no indications reported).

IWE Examinations As a result of the through-wall hole reported during the BV 1 1R1 9 IWE visual examination, an additional general visual examination was performed on the BV2 containment liner during 2R14. No indications were reported that impacted the structural or leak tight integrity of the liner. The next scheduled IWE exam at BV2 is 2R15. Included in the 2R14 IWE examinations were the moisture barrier, electrical penetration bolting, equipment hatch bolting and the fuel canal blind flange bolting.

FirstErergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Pressure Testing The Class 1 piping System Leakage Test was performed prior to plant start-up. All Class 1 and 2 bolted connections subject to the examination requirements of IWA-5242, "Insulated Components" were examined during 2R14. Also, Class 2 and 3 system functional and system inservice tests were performed on various systems to fulfill the current 40-month pressure testing requirement.

Deficiency Resolution There were eight examinations that required corrective actions during 2R14 as a result of ISI examinations. They were:

2CCP-E21A-WS-2 Loose nut Nut was retightened to snug tight per Engineering.

2RCS-PSSH077X Loose nut Nut was retightened to specific torque requirement.

2RHS-E-21A-A-1 PT Unsat indications Weld repairs were required.

2RHS-E-21A-A-2 PT Unsat indications Weld repairs were required.

2RHS-E-21B-A-1 PT Unsat indications Weld repairs were required.

2RHS-E-2 1B-A-2 PT Unsat indications Weld repairs were required.

2RCS-REV21 Penetration 49 cracking Weld overlays were required.

2RCS-REV21 Penetration 57 cracking Weld overlays were required.

Steam Generator Tube Examination One hundred percent of the in-service tubes were examined in the three steam generators. Results of the examinations are submitted to regulatory authorities in accordance with Technical Specification requirements.

NIS-2 Forms Included as Appendix II are the NIS-2 Forms associated with ASME XI repairs and replacements.

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Descriotion ClaRR G=fAnnrv Item Method Class Czutenon 015600 2CHS-PSST732X SUPPORT F-A FI.IOT VT-3 019300 2CHS-PSR657X SUPPORT F-A FI.10R VT-3 033500 107425-MJ-04-B-1 TO 4 PIPE BOLTING STUD BOLTS B-G-2 B7.50 VT-1 039800 2CHS-PSA616 SUPPORT F-A F1.10A VT-3 039900 2CHS-PSR615 SUPPORT F-A FI.10R VT-3 040500 2CHS-PSR620 SUPPORT F-A Fl.10R VT-3 043000 2CHS-PSR075X SUPPORT F-A FI.1OR VT-3 043600 2CHS-PSST077 SUPPORT F-A F1.10T VT-3 046900 2CHS-PSA611 SUPPORT F-A F1.10A VT-3 080350 2RCS-002-25-1 LOOP A MANUAL DRAIN LINE MRP 146 UT 082200 2RCS-PSST908 SUPPORT F-A F1.10T VT-3 082800 2RCS-PSR071X SUPPORT F-A FI.10R VT-3 085100 2RCS-PSR037 SUPPORT F-A Fl.10R VT-3 085350 2RCS-002-168-1 LOOP A DRAIN LINE MRP 146 UT 087300 2RCS-PSSH076X SUPPORT F-A F1.10S VT-3 089600 2RCS-PSSH077X SUPPORT F-A F1.10S VT-3 104450 2RCS-002-47-1 LOOP B DRAIN LINE MRP 146 UT 106350 RCS-018 RI-ISI SEGMENT R-A R1.12 VT-2 109150 2RCS-002-45-1 LOOP B MANUAL DRAIN LINE MRP 146 UT 110000 2RCS-PSSH085X SUPPORT F-A FI.10S VT-3 112100 2RCS-PSSH086X SUPPORT F-A FI.10S VT-3 125550 2RCS-002-65-1 LOOP C MANUAL DRAIN LINE MRP 146 UT 131350 2RCS-002-67-1 LOOP C DRAIN LINE MRP 146 UT 131950 RCS-089 RI-ISI SEGMENT R-A R1.12 VT-2 133700 107015-MJ-01-B-1 TO 8 2RCS-FE482 STUD BOLTS B-G-2 B7.50 VT-1 134700 2RCS-PSSH027X SUPPORT F-A F1.10S VT-3 135600 2RCS-003-FO1 PIPE WELD (LIMITED) R-A R1.11 UT 136000 2RCS-003-F02 PIPE WELD (LIMITED) R-A R1.11 UT 141300 2RCS-001-F03 PIPE WELD (LIMITED) R-A R1.11 UT 141600 2RCS-001-F04 NOZZLE TO SAFE-END (LIMITED) R-A R1.11 UT 144500 2RCS-002-F03 PIPE WELD R-A R1.11 UT 148700 2RCS-084-F03 PIPE WELD R-A R1.11 UT 149000 2RCS-PSSH001X SUPPORT F-A F1.10S VT-3 150000 2RCS-021-F503 PIPE WELD R-A R1.11 UT 151000 2RCS-020-2B-2 PIPE WELD R-A R1.11 UT Page Al-1

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Category Item Method 159250 RCS-086 RI-ISI SEGMENT R-A R1.12 VT-2 162400 2RCS-080-F503 PIPE WELD R-A R1.11 UT 164900 2RCS-PSSH001 SUPPORT F-A F1.10S VT-3 168300 2RCS-081 -F503 PIPE WELD R-A R1.11 UT 168400 2RCS-PSST013A SUPPORT F-A FI.10T VT-3 170100 2RCS-PSST015 SUPPORT F-A F1.10T VT-3 172800 2RCS-202-FO1 PIPE WELD R-A R1.11 UT 172900 2RCS-107-FOl PIPE WELD R-A R1.11 UT 178800 2RCS-101-FOl PIPE WELD R-A R1.11 UT 181700 2RCS-103-FOl PIPE WELD R-A R1.11 UT 184600 2RCS-102-FOl PIPE WELD R-A R1.11 UT 187600 2RCS*PRE21-101A NOZZLE-TO-SAFE-END R-A R1.11 UT 187700 2RCS*PRE21-102B NOZZLE-TO-SAFE-END R-A R1.11 UT 187800 2RCS*PRE21-103C NOZZLE-TO-SAFE-END R-A R1.11 UT 187900 2RCS*PRE21-107Z NOZZLE-TO-SAFE-END R-A R1.11 UT 188000 2RCS*PRE21-202Z NOZZLE-TO-SAFE-END R-A R1.11 UT 188100 2RCS*PRE21-84Z NOZZLE-TO-SAFE-END R-A R111 UT 191400 2RCS*PRE21 -N-1 3 NOZZLE-TO-VESSEL WELD (LIMITED) B-D B03.1 10 UT 191500 2RCS*PRE21-N-i31R NOZZLE INSIDE RADIUS B-D B3.120 UT 191600 2RCS*PRE21-N-14 NOZZLE-TO-VESSEL.WELD (LIMITED) B-D B03.110 UT 191700 2RCS*PRE21-N-141R NOZZLE INSIDE RADIUS B-D B3.120 UT 191800 2RCS*PRE21-SS-1 SKIRT SUPPORT F-A F1.40E VT-3 191900 2RCS*PRE21-SS-2 STRUCTURAL SUPPORT F-A Fl.40E VT-3 200003 BC-2CHS-E24 BOLTED CONNECTION BoltCon Bolt2 VT-2 200004 BC-2CHS-HCV137 BOLTED CONNECTION BoltCon Bolt2 VT-2 200006 BC-1 10312-MJ-1 BOLTED CONNECTION BoltCon Bolt2 VT-2 200007 BC-1 10312-MJ-2 BOLTED CONNECTION BoltCon Bolt2 VT-2 200029 BC-2RHS-HCV758A-MJ-1 BOLTED CONNECTION BoltCon Bolt2 VT-2 200034 BC-2RHS-HCV758B-MJ-1 BOLTED CONNECTION BoltCon Bolt2 VT-2 200037 BC-2RHS-FE607B-MJ-2 BOLTED CONNECTION BoltCon Bolt2 VT-2 200038 BC-2RHS-FCV605B-MJ-1 BOLTED CONNECTION BoltCon Bolt2 VT-2 200039 BC-2RHS-FCV605A-MJ-1 BOLTED CONNECTION BoltCon Bolt2 VT-2 200040 BC-2RHS-MOV750A BOLTED CONNECTION BoltCon Bolt2 VT-2 200041 BC-2RHS-MOV750B BOLTED CONNECTION BoltCon Bolt2 VT-2 200042 BC-2RHS-E21A BOLTED CONNECTION BoltCon Bolt2 VT-2 Page AI-2

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Category Item Method 200043 BC-2RHS-E21 B BOLTED CONNECTION 2 BoltCon Bolt2 VT-2 200044 BC-2RCS-FE480-MJ-1 BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200045 BC-2RCS-FE481 -MJ-1 BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200046 BC-2RCS-FE482-MJ-1 BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200047 BC-2RCS-SG21A-MNVVYS BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200048 BC-2RCS-SG21B-MNWYS BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200049 BC-2RCS-SG21C-MNWYS BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200088 - BC-2RCS-REV21-FIg Bolts BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200089 BC-2RCS-PRE21-Manway BOLTED CONNECTION 1 BoltCon Bolt1 VT-2 200091 BC-2RHS-FE607A-MJ-2 BOLTED CONNECTION 2 BoltCon Bolt2 VT-2 200092 PT-2-Leakage Package 2 Leakage during RHS "A" Train 2,3 Press Test VT-2 200093 PT-2-Leakage Package 3 Leakage during RHS "B" Train 2,3 Press Test VT-2 200094 PT-2-Leakage Package 4 DGS pumps dicharge piping 2,3 Press Test VT-2 200095 PT-2-Leakage Package 5 Temporary Dike Drain using Das piping 2 Press Test VT-2 200098 PT-2-Leakage Package 8 Terry Turbine OST 3 Press Test VT-2 200099 PT-2-Leakage Package 9 20ST-11.14B High Head Full Flow 2 Press Test VT-2 200100 PT-2-Leakage Package 10A 2OST-30-13A 3 Press Test VT-2 200101 PT-2-Leakage Package 10B 20ST-30-13B 3 Press Test VT-2 200102 PT-2-Leakage Package 11 2OST-11.14A Low Head SI Full Flow 2 Press Test VT-2 200103 PT-2-Leakage Package 12A Leakage during 20ST-2.43.15A 3 Press Test VT-2 200105 PT-2-Leakage Package 13 20M-20.4H Cavity Drain 2 Press Test VT-2 200106 PT-2-Leakage Package 14 LETDOWN INSERVICE 2 Press Test VT-2 200107 PT-2-Leakage Package 15 RCS Fill and vent through 2CHS-FCV160 2 Press Test VT-2 200109 PT-2-Leakage Package 17 Leakage during 20M-6.4E 2 Press Test VT-2 200110 PT-2-Leakage Package 18 Cavity Fill 20M-1 1.4C 2 Press Test VT-2 200112 PT-2-Leakage Package 20 2BVT-13.5 2RSSP21A Pump run 2 Press Test VT-2 200113 PT-2-Leakage Package 21 2BVT-1 3.5 2RSSP21B Pump run 2 Press Test VT-2 200114 PT-2-Leakage Package 22 2BVT-13.5 2RSSP21C Pump run 2 Press Test VT-2 200115 PT-2-Leakage Package 23 2BVT-1 3.5 2RSSP21D Pump run 2 Press Test VT-2 200120 PT-2-Leakage Package 29 Mode 3 walkdown 123 Press Test VT-2 200122 PT-2-Leakage Package 31 CCP Inservice 3 Press Test VT-2 200124 PT-2-Leakage Package 33 FNC "A" Train Inservice 3 Press Test VT-2 200125 PT-2-Leakage Package 34 FNC "B" Train Inservice 3 Press Test VT-2 200126 PT-2-Leakage Package 35 Stroke 2FWE-1165 3 Press Test VT-2 200127 PT-2-Leakage Package 36 Static Head Pressure exam of 2FWE-TK210(DWST) 3 Press Test VT-2 Page AI-3

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Category Item Method 200128 PT-2-Leakage Package 37 FWS INSERVICE 2 Press Test VT-2 200129 PT-2-Leakage Package 38 MSS INSERVICE 2 Press Test VT-2 200131 PT-2-Leakage Package 40 Leakage during 20ST-13.2 2 Press Test VT-2 200135 PT-2-Leakage Package 44 20ST-13.10B 2 Press Test VT-2 200137 PT-2-Leakage Package 46 Leakage during 20ST-1 1.2 2 Press Test VT-2 200138 PT-2-Leakage Package 47 Leakage during 20ST-30. 1A or 1B 3 Press Test VT-2 200142 PT-2-Leakage Package 51A Leakage during 20ST-36.1- (OUTAGE) 3 Press Test VT-2 206950 2REV-HEAD-OD VESSEL HEAD OD SURFACE 1 N-729 B4.10 VE 206960 2REV-HEAD-PENE-ID VESSEL HEAD PENETRATIONS 1 N-729 B4.20 UT/ET 206970 2REV-HEAD-PENE-16 PENE 16 REPAIR AREA 1 N-729 B4.20 PT 206971 2REV-HEAD-PENE-51 PENE 51 REPAIR AREA 1 N-729 B4.20 PT 206972 2REV-HEAD-PENE-56 PENE 56 REPAIR AREA 1 N-729 B4.20 PT 206973 2REV-HEAD-PENE-61 PENE 61 REPAIR AREA 1 N-729 B4.20 PT 206974 2REV-HEAD-PENE-49 PENE 49 REPAIR AREA 1 N-729 B4.20 PT 206975 2REV-HEAD-PENE-57 PENE 57 REPAIR AREA (RR# 2-TYP-3-RV-03) 1 N-729 B4.20 PT 218000 2RCS*REV21 -N-24 NOZZLE-TO-SAFE-END WELD 1 R-A R1.11 VE 218200 2RCS*REV21 -N-26 NOZZLE-TO-SAFE-END WELD 1 R-A R1.11 VE 218400 2RCS*REV21 -N-28 NOZZLE-TO-SAFE-END WELD 1 R-A R1.11 VE 218540 2RCS*REV21-NUT-1 TO 19 BOLTING 1 B-G-1 B6. 10 VT-i 224340 2RCS*REV21-STUD-1 TO 19 BOLTING 1 B-G-1 B6.20 UT 230140 2RCS*REV21-WASHER-1 TO 19 BOLTING 1 B-G-1 B6.50 VT-1 235845 2REV-BMI-PENE-OD RV Bottom Mounted Inst Nozzles 1 N-722 B15.80 VE 235850 2REV-BMI-TUBE-WELDS BMI NOZZLE TO TUBE WELDS 1 N-722 B15.100 VE 235911 2RCS*SG21A-H-S01 TO S16 PRIMARY MANWAY STUDNUTWASHER 1 B-G-2 B7.30 VT-1 237511 2RCS*SG21A-C-S01 TO S16 PRIMARY MANWAY STUDNUTWASHER 1 B-G-2 B7.30 VT-i 239200 2RCS*SG21A-N-1AIR NOZZLE INSIDE RADIUS 1 B-D B3.140 VT-1 239300 2RCS*SG21A-N-1BIR NOZZLE INSIDE RADIUS 1 B-D B3.140 VT-I 247300 2RHS-001-5D PIPE WELD 1 R-A R1.11 UT 250400 2RHS-MOV701B-B-1 TO 18 2RHS-MOV701 B STUDS AND NUTS 1 B-G-2 B7.70 VT-1 250600 2SIS-142-B-1 TO 18 2SIS-142 STUDS AND NUTS 1 B-G-2 B7.70 VT-1 255500 2SIS-148-B-1 TO 18 2SIS-148 STUDS AND NUTS 1 B-G-2 B7.70 VT-1 258500 2SIS-PRR804 SUPPORT 1 F-A FI.10R VT-3 259400 2SIS-289-1B PIPE WELD 1 R-A R1.11 UT 259800 2SIS-147-B-1 TO 18 2SIS-147 STUDS AND NUTS 1 B-G-2 B7.70 VT-1 266250 SIS-045B RI-ISI SEGMENT 1 R-A R1.12 VT-2 Page AI-4

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Category Item Method 266650 SIS-044B RI-ISI SEGMENT Description 1 R-A R1.12 VT-2 269250 SIS-046B RI-ISI SEGMENT 1 R-A R1.12 VT-2 271000 2SIS-PSR494 SUPPORT 1 F-A Fi.10R VT-3 272150 SIS-090B SRI-ISI SEGMENT 2 R-A R1.12 VT-2 275250 SIS-085B RI-ISI SEGMENT 2 R-A R1.12 VT-2 277250 SIS-087B RI-ISI SEGMENT 2 R-A R1.12 VT-2 277500 2SIS-PSR292 SUPPORT 1 F-A F1.10R VT-3 278400 2SIS-PSR529 SUPPORT 1 F-A FI.10R VT-3 291950 2SIS-006-15-1 LOOP B C/L INJECTION 1 MRP 146 UT 295350 2SIS-006-24-1 LOOP B H/L INJECTION 1 MRP 146 UT 295800 2SIS-PSA080 SUPPORT 1 F-A F1.10A VT-3 296600 2SIS-PSSH081 B SUPPORT 1 F-A Fl.10S VT-3 296800 2SIS-269-F06 PIPE WELD 1 R-A R1.11 UT 296900 2SIS-PSR082 SUPPORT 1 F-A FI.10R VT-3 298650 2SIS-006-12-1 LOOP A C/L INJECTION 1 MRP 146 UT 298700 2SIS-012-1A PIPE WELD 1 R-A R1.11 UT 299500 2SIS-PSST085 SUPPORT 1 F-A F1.10T VT-3 300400 2SIS-PSSH087 SUPPORT 1 F-A FI.10S VT-3 301650 2SIS-006-26-1 LOOP A H/L INJECTION 1 MRP 146 UT 302100 2SIS-026-1D PIPE WELD 1 R-A R1.11 UT 303200 2SIS-PSSP209A SNUBBER 1 F-A FI.10N VT-3 303300 2SIS-PSSP209B SNUBBER 1 F-A F1.10N VT-3 307350 2SIS-006-25-1 LOOP C H/L INJECTION 1 MRP 146 UT 307660 2BDG-01 1-26-1 BUTT WELD 2 R-A R1.11 UT 314050 2CHS-434-F02 SOCKET WELD 2 R-A R1.12 VT-2 314800 2CHS-PSR261Y SUPPORT 2 F-A F1.20R VT-3 315900 2CHS-PSR146 SUPPORT 2 F-A F1.20R VT-3 316400 2CHS-PSR225 SUPPORT 2 F-A F1.20R VT-3 317450 2CHS-433-F02 SOCKET WELD 2 R-A R1.12 VT-2 318300 2CHS-PSR260Y SUPPORT 2 F-A F1.20R VT-3 319700 2CHS-PSR147 SUPPORT 2 F-A F1.20R VT-3 320100 2CHS-PSA148 SUPPORT 2 F-A F1.20A VT-3 321300 2CHS-PSR258Y SUPPORT 2 F-A F1.20R VT-3 322500 2CHS-PSR151 SUPPORT 2 F-A F1.20R VT-3 322900 2CHS-72 -5A1 B BUTT WELD 2 R-A R1.11 UT Page Al-5

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077' Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Cateaorv Item Method 324650 2CHS-291-F403 Class Cateaorv SOCKET WELD R-A R1.12 VT-2 324670 CHS-028A RI-ISI SEGMENT R-A R1.12 VT-2 325800 2CHS-320-F404 SOCKET WELD R-A R1.12 VT-2 325850 CHS-026E RI-ISI SEGMENT R-A R1.12 VT-2 332270 CHS-028D RI-ISI SEGMENT R-A R1.12 VT-2 342500 2CHS-207-F02 SOCKET WELD R-A R1.12 VT-2 353800 2CHS-PSA29OF SUPPORT F-A F1.20A VT-3 354700 2CHS-PSR299F SUPPORT F-A F1.20R VT-3 373850 2CHS-056-F13 SOCKET WELD R-A R1.12 VT-2 384300 2CHS-063-2-A BUTT WELD R-A R1.11 UT 387800 2CHS-069-F518 BUTT WELD R-A R1.11 UT 389400 2CHS-278-F400 SOCKET WELD R-A R1.12 VT-2 389450 CHS-016C RI-ISI SEGMENT R-A R1.12 VT-2 389600 2CHS-278-F401 SOCKET WELD R-A R1.12 VT-2 393550 CHS-018C RI-ISI SEGMENT R-A R1.12 VT-2 393700 2CHS-275-F401 SOCKET WELD R-A R1.12 VT-2 397700 2CHS-272-F400 SOCKET WELD R-A R1.12 VT-2 397900 2CHS-272-F401 SOCKET WELD R-A R1.12 VT-2 402100 2CHS-PSR318 SUPPORT F-A F1.20R VT-3 402200 2CHS-120-F514 WELDED ATTACHMENT FOR 2CHS-PSR318 C-C C3.20 PT 402300 2CHS-120-F515 WELDED ATTACHMENT FOR 2CHS-PSR318 C-C C3.20 PT 402400 2CHS-120-F516 WELDED ATTACHMENT FOR 2CHS-PSR318 C-C C3.20 PT 402500 2CHS-120-F517 WELDED ATTACHMENT FOR 2CHS-PSR318 C-C C3.20 PT 406400 2CHS-PSA327Y SUPPORT F-A F1.20A VT-3 410300 2CHS-PSR217R SUPPORT F-A F1.20R VT-3 434750 CHS-050A RI-ISI SEGMENT R-A R1.12 VT-2 447050 CHS-041 RI-ISI SEGMENT R-A R1.12 VT-2 471650 2FWS-PSST185 SUPPORT F-A F1.20T VT-3 471680 2FWS-022-F-801 WELDED ATTACHMENT FOR 2FWS-PSST185 C-C C3.20 MT 471900 2FWS-PSSPOO6 SNUBBER F-A F1.20N VT-3 472000 2FWS-PSSH007 SUPPORT F-A F1.20S VT-3 474000 2MSS-PSST101 B SUPPORT F-A F1.20T VT-3 474200 2MSS-037-F801 WELDED ATTACHMENT FOR 2MSS-PSST101 B C-C C3.20 MT 483400 2MSS-PSST004 SUPPORT F-A F1.20T VT-3 483600 2MSS-35 -6A BUTT WELD R-A R1.11 UT Page AI-6

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Category Item Method 483700 2MSS-035-L05 LONGITUDINAL WELD R-A R1.11 UT 483900 2MSS-035-L06 LONGITUDINAL WELD R-A R1.11 UT 495750 MSS-056 RI-ISI SEGMENT R-A R1.12 VT-2 495850 MSS-054 RI-ISI SEGMENT R-A R1.12 VT-2 496050 MSS-055 RI-ISI SEGMENT R-A R1.12 VT-2 500770 QSS-016 RI-ISI SEGMENT R-A R1.12 VT-2 502950 2QSS-1 -5C BUTT WELD (LIMITED) R-A R1. 11 UT 505460 QSS-015 RI-ISI SEGMENT R-A R1.12 VT-2 507460 QSS-020 RI-ISI SEGMENT R-A R1.12 VT-2 507900 2QSS-PSSP138Y SNUBBER F-A F1.20N VT-3 510900 2QSS-PSST111Y SUPPORT F-A F1.20T VT-3 511015 QSS-019 RI-ISI SEGMENT R-A R1.12 VT-2 511016 2QSS-PSR 132Y SUPPORT F-A F1.20R VT-3 513060 2QSS-004-F535 BUTT WELD R-A R1.11 UT 524600 2QSS-PSR216X SUPPORT F-A F1.20R VT-3 527400 2RCS*SG21A-WS-1 TRUNNION WELD # 1WS C-C C3. 10 MT 530500 2RCS*SG21C-ESUP-21 UPPER INTERMEDIATE SUPPORT STRUCTURE F-A FI.40E VT-3 531300 2RHS-PSSH037A SUPPORT F-A F1.20S VT-3 531400 2RHS-PSSH037B SUPPORT F-A F1.20S VT-3 561300 2RHS-PSR51OX SUPPORT F-A F1.20R VT-3 573200 2RHS*E21A-WS-1 FOOT SUPPORT # 1 (4 GUSSET PLATES) F-A FI.40E VT-3 573300 2RHS*E21A-WS-2 FOOT SUPPORT # 2 (4 GUSSET PLATES) F-A F1.40E VT-3 573400 2RHS*E21A-C-2 HEAD CIRCUMFERENTIAL WELD # 2 C-A C1.20 UT 573500 2RHS*E21A-A-1 WELDED ATTACHMENT FOR WS-1 C-C C3.10 PT 573600 2RHS*E21A-A-2 WELDED ATTACHMENT FOR WS-2 C-C C3.10 PT 573700 2RHS*E21A-N-3 NOZZLE-TO-SHELL WELD # 3 C-B C2.21 VT-2 573800 2RHS*E21A-N-4 NOZZLE-TO-SHELL WELD # 4 C-B C2.21 VT-2 573900 2RHS*E21A-C-1 SHELL CIRCUMFERENTIAL WELD # 1 C-A C1.10 UT 574300 2RHS*E21 B-A-1 WELDED ATTACHMENT FOR WS-1 C-C C3.10 PT 574400 2RHS*E21 B-A-2 WELDED ATTACHMENT FOR WS-2 C-C C3.10 PT 575400 2RHS*P21A-A-2 WELDED ATTCHMENT FOR WS-2 C-C C3.30 PT 575600 2RHS*P21A-WS-1 PUMP SUPPORT F-A F1.40P VT-3 575700 2RHS*P21A-WS-2 PUMP SUPPORT F-A F1.40P VT-3 575710 2RHS*P21A-WS-3 PUMP SUPPORT F-A F1.40P VT-3 586520 2RSS-017-F500 BUTT WELD R-A R1.11 UT Page AI-7

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Category Item Method 604400 2RSS-10 -4AC BUTT WELD R-A R1.11 UT 636200 2SDS-PSR102R SUPPORT F-A F1.20R VT-3 640634 2SIS-2-3-A BUTT WELD R-A R1.1 1 UT 640682 2SIS-PSR329Y SUPPORT F-A FI.20R VT-3 644000 2SIS-PSR351Y SUPPORT F-A F1.20R VT-3 649950 2SIS-005-F513 BRANCH CONNECTION R-A R1.12 VT-2 650000 2SIS-PSR318Y SUPPORT F-A FI.20R VT-3 653200 2SIS-PSST31 OX SUPPORT F-A FI.20T VT-3 653900 2SIS-10 -4AA BUTT WELD R-A R1.1 1 UT 654000 2SIS-PSSH322X SUPPORT F-A F1.20S VT-3 658000 2SIS-048-1-A BUTT WELD R-A R1. 11 UT 661600 2SIS-PSR338Y SUPPORT F-A FI.20R VT-3 662900 2SIS-006-F-22 BUTT WELD R-A R1.11 UT 662950 SIS-037B RI-ISI SEGMENT R-A R1.12 VT-2 670200 2SIS-PSST607 SUPPORT F-A F1.20T VT-3 670800 2SIS-9 -6A BUTT WELD R-A R1.11 UT 674350 SIS-065B RI-ISI SEGMENT R-A R1.12 VT-2 676650 SIS-064B RI-ISI SEGMENT R-A R1.12 VT-2 679400 2SIS-PSR030 SUPPORT F-A F1.20R VT-3 679800 2SIS-091-FO1 BUTT WELD (LIMITED) R-A R1.1 1 UT 679900 2SIS-091-F511 BUTT WELD (LIMITED) R-A R1.1 1 UT 680600 2SIS-PSR028Y SUPPORT F-A F1.20R VT-3 681370 SIS-062B RI-ISI SEGMENT R-A R1.12 VT-2 705500 2SIS-PSR108 SUPPORT F-A FI.20R VT-3 716100 2SIS-96 -1A BUTT WELD R-A R1.1 1 UT 717070 SIS-060B RI-ISI SEGMENT R-A R1.12 VT-2 727050 SIS-081A RI-ISI SEGMENT R-A R1.12 VT-2 727300 2SIS-PSA58OX SUPPORT F-A F1.20A VT-3 728150 SIS-080A RI-ISI SEGMENT R-A R1.12 VT-2 730100 2SIS-PSA590 SUPPORT F-A FI.20A VT-3 732250 SIS-079A RI-ISI SEGMENT R-A R1.12 VT-2 734250 SIS-057B RI-ISI SEGMENT R-A R1.12 VT-2 749350 SIS-057A RI-ISI SEGMENT R-A R1.12 VT-2 750350 SIS-056A RI-ISI SEGMENT R-A R1.12 VT-2 751470 SIS-056B RI-ISI SEGMENT R-A R1.12 VT-2 Page AI-8

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077' Commerical Service Date: 11/17/87 Summary No. Component Identification Description Class Cateqory Item Method 773850 SIS-070B RI-ISI SEGMENT R-A R1.12 VT-2 775350 SIS-072B RI-ISI SEGMENT R-A R1.12 VT-2 787770 SIS-056C RI-ISI SEGMENT R-A R1.12 VT-2 790800 2SIS-PSR321 S SUPPORT F-A F1.20R VT-3 791400 2SIS-PSR273S SUPPORT F-A F1.20R VT-3 791500 2SIS-PSR282S SUPPORT F-A F1.20R VT-3 791900 2SiS*P21A-MS-1 STRUCT SUPTS, SKIDS, BOLTS, ETC. F-A F1.40P VT-3 791950 2SIS*P21A-MS-2 STRUCT SUPTS, SKIDS, BOLTS, ETC. F-A FI.40P VT-3 792070 21AC-049-F502A BUTT WELD R-A Ri1i UT 792200 2SVS-036-F501 BUTT WELD R-A R1.11 UT 802300 2SVS-12 -7C BUTT WELD R-A R1.11 UT 806550 2SVS-PSST693 SUPPORT F-A F1.20T VT-3 813600 2CCP-PSSH329 SUPPORT F-A F1.30S VT-3 813700 2CCP-471-F-808 WELDED ATTACHMENT FOR 2CCP-PSSH329 D-A D1.20 VT-1 813800 2CCP-471-F-809 WELDED ATTACHMENT FOR 2CCP-PSSH329 D-A D1.20 VT-1 813900 2CCP-471-F-810 WELDED ATTACHMENT FOR 2CCP-PSSH329 D-A D1.20 VT-1 814000 2CCP-471-F-811 WELDED ATTACHMENT FOR 2CCP-PSSH329 D-A D1.20 VT-1 815000 2CCP-PSR070 SUPPORT F-A F1.30R VT-3 815200 2CCP-PSA077 SUPPORT F-A FI.30A VT-3 816900 2CCP-PSR099 SUPPORT F-A FI.30R VT-3 817400 2CCP-PSR071 SUPPORT F-A F1.30R VT-3 817700 2CCP-PSR101 SUPPORT F-A F1.30R VT-3 821600 2CCP-PSA033 SUPPORT F-A F1.30A VT-3 821700 2CCP-332-F-504 WELDED ATTACHMENT FOR 2CCP-PSA033 D-A D1.20 VT-1 821800 2CCP-PSR041 SUPPORT F-A Fl.30R VT-3 832300 2CCP-PSST381 B SUPPORT F-A FI.30T VT-3 832800 2CCP-PSR053 SUPPORT F-A F1.30R VT-3 832900 2CCP-433-F-500 WELDED ATTACHMENT FOR 2CCP-PSR053 D-A D1.20 VT-1 833000 2CCP-433-F-501 WELDED ATTACHMENT FOR 2CCP-PSR053 D-A D1.20 VT-1 833100 2CCP-433-F-502 WELDED ATTACHMENT FOR 2CCP-PSR053 D-A D1.20 VT-1 833200 2CCP-433-F-503 WELDED ATTACHMENT FOR 2CCP-PSR053 D-A D1.20 VT-1 846500 2CCP-PSR302X SUPPORT F-A F1.30R VT-3 856200 2CCP*E21A-WS-1 FIXED SUPPORT F-A F1.40E VT-3 856300 2CCP*E21A-WS-2 SLIDING SUPPORT F-A F1.40E VT-3 856400 2CCP*E21A-A-1 WELDED PAD FOR WS-1 D-A D1.10 VT-1 Page AI-9

APPENDIX I FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 2R14 COMPELETED CODE EXAMS Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 Summary No. ComDonent Identification Descriotion Class Cateqorv Item Method 856500 2CCP*E21A-A-2 WELDED PAD FOR WS-2 3 D-A D1.10 VT-1 856600 2CCP*E21 B-WS-1 FIXED SUPPORT 3 F-A F1.40E VT-3 856700 2CCP*E21 B-WS-2 SLIDING SUPPORT 3 F-A F1.40E VT-3 857400 2CCP*TK21A-WS-1 SKIRT SUPPORT 3 F-A F1.40E VT-3 857500 2CCP*TK21A-A-1 WELDED ATTACHMENT FOR WS-1 3 D-A D1.10 VT-1 860638 2FNC-PSST920 SUPPORT 3 F-A F1.30T VT-3 866600 2FWE-PSR043Y SUPPORT 3 F-A F1.30R VT-3 872100 2FWE-PSR332X SUPPORT 3 F-A F1.30R VT-3 872700 2FWE-PSA357X SUPPORT 3 F-A FI.30A VT-3 874500 2FWE-PSR004R SUPPORT 3 F-A F1.30R VT-3 877100 2MSS-PSR496 SUPPORT 3 F-A F1.30R VT-3 877300 2MSS-PSSP476 SNUBBER 3 F-A F1.30N VT-3 877800 2RHS*E21A-A-3 WELDED ATTACHMENT FOR WS-3 3 D-A D1.10 VT-1 877900 2RHS*E21A-WS-3 UPPER SUPPORT RESTRAINT ASSEMBLY 3 F-A F1.40E VT-3 878200 2RHS*E22A-WS-1 SADDLE STRUCT SUPPORT 3 F-A F1.40E VT-3 878300 2RHS*E22A-A-1 WELDED ATTACHMENT FOR WS-1 3 D-A D1.10 VT-1 879972 2SWS*P21 B-MS-1 PUMP SUPPORT 3 F-A F1.40P VT-3 881700 2SWS-PSR025 SUPPORT 3 F-A F1.30R VT-3 883500 2SWS-PSST007 SUPPORT 3 F-A F1.30T VT-3 898350 2SWS-PSST373 SUPPORT 3 F-A F1.30T VT-3 900100 2SWS-PSSP773A SNUBBER 3 F-A F1.30N VT-3 900200 2SWS-PSSP773B SNUBBER 3 F-A F1.30N VT-3 902000 2SWS-PSR136Y SUPPORT 3 F-A FI.30R VT-3 903200 2SWS-PS R823Y SUPPORT 3 F-A F1.30R VT-3 904700 2SWS-PSR306 SUPPORT 3 F-A FI.30R VT-3 932450 2SWE-PSR652T SUPPORT 3 F-A FI.30R VT-3 999980 2CNMT-LINER CONTAINMENT LINER MC E-A E1.11 GV 999983 2CNMT-MOISTBARR MOISTURE BARRIER MC E-A E1.11 GV 999985 2CNMT-BLDFLG FUEL CANAL BLIND FLANGE BOLTING MC E-A E1.11 VT-3 999986 2CNMT-EQUHATCH EQUIPMENT HATCH BOLTING MC E-A E1.11 VT-3 999987 2CNMT-ELEC-PENE-BLTG ELEC PENETRATION BOLTING MC E-A E1.11 VT-3 Page Al-10

FirstEnergy Nuclear Operating Company, 76 South Main St,, Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: 11/17/87 APPENDIX II REPAIR / REPLACEMENT ABSTRACT AND NIS-2 FORMS A11-1

FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Senrice Date: 1/17/87 NIS-2 ABSTRACT FORM NO. ASSET NUMBER ORDER NO. COMMENTS 1986 2CHS-488 200087075 Installed 2020 2SWS-737 200157397 Installed 2029 2RCS-PCV455C 200147710 Installed If 11 200196994 Co 2040 2SWS-P21A 55104476 Corrected 2053 2MSS-AOV101B 200089238 Corrected 2083 2RHS-E21 B 200252925 Corrected 2098 2SWS-P21C 200109377 Installed 3025 2CHS-153 200283896 Corrected 3045 2FWE-HCV100A 200318973 Corrected 3072 2SVS-81 200333986 Corrected 3078 2FWE-RV101 200106774 Installed 3085 2SWS-106 200334927 Installed 3087 2MSS-196 200335041 Installed 3089 2SWS-P21 B 200023701 Corrected 3095 2CHS-181 200335124 Corrected 11 11 200393491 It 3104 2CCO-259 200335121 Installed 3105 2RCS-RV551 B 200336058 Installed 3106 2RCS-PCV456 200331527 Corrected 3116 2RCS-45 200328341 Installed 3117 2RCS-46 200337513 Installed 3118 2CHS-184 200147365 Installed 3119 2RCS-44 200322713 Installed 3120 2RCS-53 200349704 Removed 3121 2RCS-26 200349700 Removed 3122 2RCS-12 200349701 Removed 3123 2RCS-58 200349705 Removed 3124 2RCS-66 200349703 Removed 3125 2RCS-38 200349702 Removed 3127 2MSS-165 200023408 Removed 3130 2RCS-27 200356255 Removed 3131 2RCS-13 200356254 Removed 3132 2RCS-39 200356256 Removed 3133 2RCS-54 200356258 Removed 3134 2RCS-67 200356257 Removed 3137 2-QSS-002-236-2 200338916 Corrected 3138 2-QSS-002-217-2 200338915 Corrected if if II 2-QSS-002-234-2 2QSS-303 Removed 2QSS-267 AII-2

FirstEnergy Nuclear Operating Company, 76 South Main St., Akron, OH 44308 Beaver Valley Power Station Unit 2, Route 168, Shippingport, PA 15077 Commerical Service Date: i 1/17/87 NIS-2 ABSTRACT FORM NO. ASSET NUMBER ORDER NO. COMMENTS 3167 2SWS-MOV107A 200148982 Installed 3168 2SWS-MOV107B 200148983 Installed 3170 2RCS-633 200326364 Removed 3171 2RCS-634 200326360 Removed 3173 2FPW-382 200339308 Removed 1I 2-FPW-002-007-2 Corrected 2-FPW-025-005-2 Removed X-117 Corrected 3174 2-SWS-012-085-3 200370411 Corrected 3175 2FPW-388 200339309 Removed 2-FPW-002-002-2 Corrected 2-FPW-025-004-2 Removed X-1 16 Corrected 3185 2RCS-59 200359393 Installed 3188 2-SWS-006-064-3 200382345 Corrected 3192 2RHS-E21 B 200336968 Corrected 3194 2FWE-MOV1 16B 200331068 Corrected 3195 2CHS-RV382B 200336052 Corrected 3198 2CHS-579 200352079 Corrected 3199 2SWS-MOV103B 200335450 Installed 3204 2RCS-REV21 200378010 Corrected 200361987 200392534 200334948 3205 2RHS-E21A 200392332 Corrected 3206 2RCS-SG21 A 7024829 Corrected 3207 2RCS-SG21 B 7024829 Corrected 3208 2RCS-SG21C 7024829 Corrected 3209 2RHS-E21 B 200392524 Corrected 3217 2MSS-PSSPO1 1A 200338887 Installed 3218 2MSS-PSSP011B 200338887 Installed 3219 2CHS-PSSPOO6 200338887 Installed 3220 2CHS-PSSP015X 200338887 Installed 3221 2CHS-PSSP017X 200338887 Installed 3222 2CHS-PSSP025X 200338887. Installed 3223 2CHS-PSSP66OX 200338887 Installed 3224 2RCS-PSSP001X 200338887 Installed 3225 2RCS-PSSP035 200338887 Installed 3226 2DGS-PSSP879 200338887 Installed 3227 2FWE-PSSP354A 200338888 Installed 3228 2FWE-PSSP354B 200338888 Installed 3229 2RHS-PSSP521X 200344402 Installed A11-3

FORM 1/2-ADM-OO1.F02 RER#V--3 RTL # A4.4I4*A Form No. 1986 FORM NIS-2 OWNER'S REPORT FOR REPAIi/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.ENO.C Date 01/18/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200087075 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

ShiDpinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 2)
5. (a) Applicable Construction Code Section 1II 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest KP110-1 6164 2CHS-488 1975 Removed Yes Valve Enertech 11803 N/A 2CHS-488 2009 Installed Yes

7. Description of Work Replaced valve & pipe, installed coupling.
8. Tests Conducted: Hydrostatic* E] Pneumatic* E] Nominal Operating Pressure M Exempt E]

Other [] Pressure - psi Test Temp. _°IF lst pressure and temperature tRecord

FORM 1/2-ADM-0801:F02 REV 3 RTL # A4:,414-A

.... ORM NIS-2 (Back)

9. Remarks Code Data Report attached. Installed 2" Couplingq: P0 45313563 / Ht. #247689.

Applicable Manufacturer's Data Reports to be attached Reolaced 2" PiDe: PO 47244224 / Ht. #38884.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization o. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 19 20 10 Ownel or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period f-Jd- ,2- - 87 to //- ') 0?* , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

___L Commissions - , '

Inspector's nature Natlonal'-oard, State, Province, and Endorsements Date ,/- 0 ,, 20 ./Q

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. 1 of 2

1. Manufactured and certified by Enertech, A Div. of Curtiss-Wright Flow Control Corp.; 2950 Birch St.; Brea, CA 92821 (name and address of N Certificate Holder)
2. Manufactured for First Energy Corp.; P.O. Box 6100; Johnstown, PA 15907-6100 (name and address of Purchaser)
3. Location of installation Beaver Valley Power Station; Route 168; Shippingport, PA 15077 (name and address) cLAMsEA BELLOWS MD22791 C None
4. Model No., Series No., or Type SEL Drawing Rev. C CRN
5. ASME Code, Section 1II, Division 1: 1989 NO 1 N-62-7 & N-452 (edition) (addenda date) (class) (Code Case no.)
6. Pump or valve Globe Valve Nominal inlet size 2 outlet size 2 SA479 (in.) SA479 (in.)
7. Material: Body SA182 F316 Bonnet UNS-S20910 Disk UNS-S21800 Bolting N/A (a) (b) (c) (d) (e)

Cart. Nat'l Body Bonnet Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

11803 None 09-50-2 09-78-1 09-80-9 11805 None 09-50-4 09-78-3 09-80-5 11806 None 09-50-5 09-78-9 09-80-4 11807 None 09-50-7 09-78-7 09-80-2 11808 None 09-50-8 09-78-8 09-80-3 Supplemental information in form of lists, sketches, or drawings may be used provided (1) size is 8 x 11, (2) information in items 1 through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this form, (12/88) This form (E00037) may be obtained from the Order Dept., ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300. REPRINT 6/93

FORM NPV-1 (Back - Pg. 2 of 2 11803, 118D5 Certificate Holder's Serial No. thru 11808

8. Design conditions 2500 psi 650 OF or valve pressure class 1700 (1)

(pressure) (temperature)

9. Cold working pressure 4080 psi at 1O0°F
10. Hydrostatic test 6125 psi. Disk differential test pressure N/A psi
11. Remarks: Qty. 5, Enertech Project Number 520118 Yoke Material - SA182 F316, S/Ns: 09-176-1, 09-176-3, 09-176-4, 09-176-6, 09-176-7 CERTIFICATION OF DESIGN Design Specification certified by . Francis W. Gardner P.E. State .------ PA Reg. no. 036614-E.

Design Report certified by Ira J, Silverman P.E. State CA Reg. no. 23241 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.

N Certificate of Authorization No. N-2826 Ex October 11, 2011 Date Enertech, A Div. of Curtiss-Wright Flow 11f Date -Name Control Corp. Signed IN Certificate Holder) (authorized representativel CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of California and employed by HSB CT of Connecticut have inspected the pump, or valve, described in this Data Report on

  • _, and state that to the best of my knowledge and belief, the Certificate Holder has con-structed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. FurtheA9 6?p, neither the inspector nor his employer shall be liable in any manner for any personal injury or property daryage or a I/ ary kind arising from or connected with this inspection.

Date IAJ040e Signed In\or Commissions I 09t t (Authorized lnýpActorl [Nat'l. Bd. (mdc.endorsements) and state or prov. and no.]

(1) For manually operated valves only.

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 2020 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 02/02/2009 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShiNDinoOrt. PA 15077 Work Order #200157397 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date ".

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III
  • Edition, 1971 Addenda, S'73 Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity_ 1989 (c) Applicable Section XI Code Case(s): N-416-2
6. Identification of Components Corrnoced, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Gate Valve Dresser N/A N/A 2SWS-737 N/A Removed Yes Gate Valve Velan 011008-10 N/A 2SWS-737 2001 Installed Yes

7. Description of Work Replaced valve and pipe with spare.
8. Tests Conducted: Hydrostatic* E] Pneumatic* LI Nominal Operating Pressure E Exempt LI Other El Pressure psi Test Temp. _ OF

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Replacement 2" NPS Pipe: P.O. 7071315, Ht. #40007.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Au horiza o. N/A Expiration Date N/A Signed ..Jt.Zj Senior Specialist Date February 02 , 20 09 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period /[ -- ý to Is- - ,-,..'- -)0 'Y , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

-Ie inspect/p( Signature Cmis Ns at ,ioaCo, Stai r ea National Board, State, Province, and Endorsements

. Date ,2 -7 - , 20 0 7

,Page' 16, of 42)

DATA PACKAGE NO. 011008 FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES

  • As Required by the Provisions of the ASME Code, Section III, Division 1 Pg. 1 of 2
1. Manufactured and certified by _VLAN INC. 2125 WARD W-E#MONTRRAL.0ULMEC.A. A H4MlT6 (name and address of N Certificate Holder)
2. Manufactured for FRAMATOME TCECHNOLOGIES 3315-A OLD FOREST RD.LYNCHBURG.VA.USA 24501 (name and addres of purchasr)
3. Location of installionz N/A (name and address)
4. Model No., Series No., or Type: GATE Drawing" Pl-76800-NOI Rev H CRY N/AL.
5. ASME Code, Section III, Division 1: __ 1989 NONE 1 (edIeon) (addends date) (cda&) (Code Case no.)
6. Pump or valve VALV-. Nominal inlet size 2 Outlet size .
7. Material: .Body, SA-105.,CS onnatSA-105,CS Disk SA-351.CF8I "Biting SA-194,2H SA-193, B7 (a) (b) (c) (d) (e)

Cert. Nat'1 Body Bonnet Disk

  • Holder's Boaxd Serial Serial Serial Serial No. NO. No. NO. No.

011008-1 fl/A .H/C:, XCX ,H/C; V-C R/C: 16N 011008-3 KCX V-c 16H 011008-3 V-C 16H

. 011008-4 Xci v-c-011008-5 V-c. 16M XcZ Nag

  • 011008-6 V-C 16R 011008-7 --- KCX V-c 169 Xci 86Z 011008-9 xci* V-c 86Z

" 011008-10 V-c B Z~z non Supplemental Information in form of UsIa, sketches, or drawings may be used provided (1) site Is S 1/2 x lI, (2) information In Items. I througb 4 oanthis Data Report is Included on each sheet, (3) each sheet is numbered and the number of sheets Is recorded at the top of this form.

(12/88) This form (E00637) may be obtained from the Order Dept., ASME, 22 LAW DRIVE< BOX 2300 Fairfield, NJ 07007-2300. S-n m PBG

(Page 19 of 42)

S-1 .

FORM NPV-I-(Back - Pg. 2 of z2 )

Certificate Holder's Serial No. 011008

8. Design conditions 1975 psi 100 F or valve pressure class 80o (1)

(preimre) (tumiperatuxe)

9. Cold working pressure 1975 psi at 100*F
10. Hydrostatic test 3000 psi. Disk differential test pressure 2200 psi
11. Remarks: MATERIALS -ERT ASME SECTION 1I EDITION: 1989 ADDENDAt NONMR CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASKM Code,Section III, Division 1.

N Certificate of Authorization No. N-2797-1 Y2.2001 X

Date 1ame VELAN ICC'r Sig-e)

K(N Certificate Holder) (authorized rep= ['.t~v)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of OUNBEC and employed by REgIPDU AAT.MXNT of o OUBEC have inspected the pump, or valve, described in this Data Report on 04 , and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with the ASKS Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warrenty, expressed or implied, concerning the component described in thin Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss any Xipd arising from or connected with this spection.

Date signed Iso usc. "L Au ori'zedInspector) state or proy. 2nd oo.)

(N42'L Bd. (aida cadornients) and

['J i~7 (1) For manually operated valves only.

rPA7GýF QpZZl

FORM I/2-ADM-0801.F02 REV 3 RTL # A4.414-A

-. Form No. 2029 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 11/06/09 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order Nos: 200147710, 200196994 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Reactor Coolant (Class 1)'
5. (a) Applicable Construction Code Section Ill 1977 Edition, S'79 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Power Relief Valve Garrett Pneumatic P-121 N/A 2RCS-PCV455C 1983 Corrected Yes Fitting/Tubing Assy Anderson N/A N/A N/A 2008 Installed No Greenwood Crosby Plug . Crosby Valve N96012-39-0036 N/A N/A 1987 Installed Yes 4- 4 F -4 4 + 4

7. Description of Work Replaced fitting/tubing assembly, plug, bonnet stud & nut.
8. Tests Conducted: Hydrostatic* El Pneumatic* 0 Nominal Operating Pressure 0 Exempt E]

Other L] Pressure psi Test Temp. o_F

  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Code Data Reports available. Previous NIS-2 Data Report No: 1440, 1332, 1043, Applicable Manufacturer's Data Reports to be attached 800 (NPV-1 attached), 553, 361, 088. Replacement 1-3/8" Stud: PO 7116467 / Ht. #HC04 F742, Nut: PO 7086198 / Ht. #532326 E473.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 14 , 2010 Owne)-or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period , "-o -0 to 1)- s-'" - 0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

2 Commissions a. Y, 5,'/

inspýtorjýý ature National Board, State, Province, and Endorsements Date /- ;lO 0 ,, 20 /0)

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 2040 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 01/15/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of _ 4 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 Purchase Order 55104476 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Flowserve-Charlotte Nuclear Type Code Symbol Stamp NR (NAME) 2801 T Hutchinson McDonald Rd, Charlotte NC 28269 Authorization No. NR-88 (ADDRESS)

Expiration Date Feb. 18, 2009

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 1989E (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pump Byron Jackson 731-N-0027 N/A 2SWS-P21A 1982 Corrected Yes Bowl Assy BW/IP Intl. 901W0204 N/A 2SWS-P21A 1991 Corrected Yes

7. Description of Work Vendor overhauled pump by weld repairing suction bells & columns, and replacing bolting.
8. Tests Conducted: Hydrostatic* E] Pneumatic* [] Nominal Operating Pressure [] Exempt LI Other LI Pressure 225 psi Test Temp. 72 OF
  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Rebort attached. Previous NIS-2 Data Reoort Nos: 1823. 397. and 141.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White .4 __i2 Staff Specialist Date January 15 , 20 10 d-owner's Desi-gn-e" Title t'wer CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period S--_-Za,-L -O Y to / / - 2 .- 0 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this

ý11 Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

J -,-ý -J, )""ýZ Inspector' ature Commissions - '/ A'1 'tY National Board, State, Province, and Endorsements Date /- 1-' 0 , 20 _/ 0

(Page 26 of 529)

FORM NR-I REPORT OF REPAIR 0 OR REPLACEMNT [

TO NUCLEAR COMPONENTS AND SYSTEMS IWNUCLEAR-POWER PLANTS

1. work perrmed by: Fowsw4e - Charotte Nucear Serwce-Ce .. " CC064146,-

2801-T Htuchlson McDonald Rd, Charlott., NC 28269

2. Owner First.6_y Route 16B, Shippjngpot, PA 15077 *
3. Name, address and Identification of nuudear powerplant Ed~lon*

Beaver Valley ucudearPlant Route 168, ShtppingporM, N~isane PA 15077" Yeai

4. System: Jurs Servce Water NatlO.

Sa. Items that required Repair or Repacenent Actviies No.

Mfg. IdentoFication -"Const*i"lon Code Activity Type of Mfg. ~ Name/ Ewn Code Code Repair!I 0 Them Name Seral No. No. - Built SectonI Addenda Case(s) Class Replace ov-

"yron 731-N- 2SWS ASMHEUh/

Pump 3ad . 0027 -- -P21A 1982 1 197 ,, N146-l1 3 Repair.

ov-Bowl BWIDP 2SW ASE/W 2: Assem hi-,I 901WO204 - - -P2tA- 1991 1 1971/W77 - 3 Repair E3 . , ______

5 6

17

.9 In 112 SIdentift ation .Consm truton Code, In ~ dor Na rne/ Edto Co e o e Type Cif Peplacd MN, Mfg. Nat'l Bd. Jurts. Other Year Secdok I d oC de o e i[tern Sa Item No. Name' Sertia No. No. No. Buil Divisbon Addenda Case(s) Class

" t ASME_ I A SM E,"Mt

..... 1 l86ne n -I Nuts .2 Noa .. rt I

"g Nov

~...

L

6. ASME Code Sectio* X appffcable for inservloe Msecin: lg89 None-
7. ASME Code SectionX used Ibr- repair or repk-ements: See Item 12 See Ite 12 -

S. Cbnsftructoi Code used fo repa~rs ar repý " ":  : 1971 "V1972- U146-1 jO. Tests condu mtS : tr i CK p meuiatc [3 design pressure [I prssw 225 psl Code Case(s) N -146-1 05

(Page 27 of 529)

11. Description of work: RgradRefriibsh Chmyponnts Pump Mode # 32KXHl-2 §Nq Servic Water Ptimp' per repahr plan for Customer PO 55101476, 0iai9ge Or 5

, General Repairs Included pressure bountf/ weld repairs and KDE wbft MHyd-Test Repabs were pelbmied to riestore-imn dafitiess and mechanial fitae condilons a of os udnsand bonls to arg-hia OEM desbyo renif.ements.

'All studs an-d nuts replaced hinbowl assEmbl. Studs and nuts suppLied by azstmer.

12. Rnamks: 1. Repar scope appled toitem Sa,WNo. I and 2 of this dociment pote that the bowl assemb,,*s replaced

.m in 1991

2. Continued Item #7, Matbf- and Fabricaton per ASME SeiUnm UT, Div 1,1995 Ed, 96 Add.

Pressure Testing in acrordance with ASME Section 1i1,Div 1 1989 Ed, no Add.

3. Code NR-1 Nameplate atltdhed In bowl assembly CERTIFICATE OF COMPLIANCE 0 I, Dennis WHey ,certifythat to the best of my knowledge and belief the statements made in this report are correct and the repair or replacement acivities described above conform to T"t-c)WheA-SE-Code and the Natknal WoardIBziwcb Code*Nlr rules.

National Board Cirficateof AuthoriaiornNo. NR.-88 " to use the ýNR" stamp expires Feb, 18 2009 NR Certificate Holder Ftowserve - Charlotte Nuclear Repair Center

(-3 Date 10hfL]V7 Signed Z2~1 Q%-X rv-ý

-~ Quariy Assurance Representative 0

CERTIFICATE OF INSPECTION I,' Charles F. Toegel, Jr. ,holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and certificate of competency Issued by theJurisdiction of North Carolina and employed by Hartford Steam Boiler of Cr of Hartford, Cr have Inspected the repair or replacement described in this report on I.odt2 *.stand-tia-thatto the best of my knowledge and belief, this repair or replacement activity has been completed in accordance with Section X) of the ASME Code and the Nal'onalBoardInspectin Code"NR" rules.

By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or Implied, concerning The work described in this report Furthermore, neither the undersigned nor my -employershall be liable in any manner for any personal injury, property damage or a lossfan is, fro nnected with this Inspection.-

Date /V 1 0 A Signed Cm ssons NS#8462 NC# 1073 t fd.~~

06

_I,_o-f

  • e c3o

.4' Page -J-of RePor 0 FORM NPV-1 N CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code. Section Iil. Div. 1

1. Manufactured by 8yWS V T~gts Amp~fON~,6(), ti.

(Name and Address of J4 Certificate Hold )

3L0 Ji 1I"1'N01V 4iY e,2ivUi7X r/'AA !ý5 I

2. Manulacturedior STor Aq I tNAT* -,o Ea*.P P 6',s-M n S< in //.17 p O .4 tq 3. Location of Installation am. anO Address of PUrch'S or Owner)

M e- le 1.H]Lt K 5 -Y.r.r 5 3pl

4. Pump or Valve PUM 12 Nominal Iniet Siz 1W.4 outiet size (inch) (inch)

Is) Model No.. (b N Certificate Holder's Ic) Canadian Series No. Serial Registration (d) Drawing IfI Nat'l. (g) Year or Type No. No.

  • No. WetClass 8d. No. suilt (1) .( ,X 361

.1 (n 7 1-N 72-. MI-TO 7

-7 ty/ 1,

/. F o7 ,7-1S / 6 , /,

13)

(41.

(si 17)

IS)

(9)

(101

-.eelt- e.,.,

5. te",e rnof.S ('nnP A eai "NTAy6Th*,n _Lf w(7G (gie de~paaibon of soewvce fmr'.hich eQuipmern fwas 06q~nedl to i
6. Design Conditions /3.0 .si T or Valve Pressure Class ,//i (1) f4rmiuret ( W aertuiul
7. Cold Working Pressure NPsi, at i0"F.
8. Pressure Retaining Pieces Mark No. Materw Spec. No. Manufacturer Remarks

[a) Coatings

-'FOP L.',A1e. .S- .,/i( #;gowe4 _______ /'* /I(,2ALg*

I-Oe4a -A-216 g 9, Wani!8 9_____5

  • gz*,;

_*R-2/l.,1s.d~q* 4_R1, 9/A23..

(b) Fo~rings 1-: 4 _ _ _

III For manually operated valves only.

SUp9pIrfIt&al sheats in form of lists. sketches or drawings may be used provided (1) size is 8-1S2 x 11. (2) Information in Items 1. 2 and 5 on this Date Report Is Included on tech sheet, and (3) each shoat Is numbered and number of cheat1 is recordod at top this form.

Item) "trihslform (11000371 atey beebtain from the Order DePt.. ASMIU, 345 1. 47th St.. New YoQANVy. 10017

Page FORM NP`V-1 (Back) a Mark No. Material Spec. No. Manufactuu'er Remarks (c)Boning .

JYeXffA0IP-SCA- <;19-j3 61Z. (31 05______

1 15 -37 ReKiiz Nut__ _ _ __II '97731, (d) Othw er Pua_____________ _____ ______

C-04, ArAdvee- 5, -57/ 5 GR 70 Vs___7_?4__

9/&X plle u~t~

- O- ,5,/5 15R, 70 _ _ _ _ _ _ __ _ _ _ _ _

Ii a~ ,P-S

~ A-LO & C2 8 . _ _ _ _ a s,__

uA'ime ggiwne- S14-s'5i CA. -7o ___________ /1 qAI

,E~ sA-g5ICR.7o 'U's____

colipe, SA-515 6A-70 i1~ 5'8 70 9____6_

____I __/_Pa-5 54___1______ 0 /5783 6!?

9.. Hyd~mrtic ta 1 .A2L 60 psi. Visk Oltforential testp r W1 Psd.

CERTIFCATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pu p. or valve, conforms to the rules of construction of the ASME Code for Nuclear Power Plant Components. Secti Ill. Div. I. Edition ,1 Z Z.

A WI/-N-t/C197,.

'Lnda Code Case No. -i./ a I 1 2 6

00 Signed y1?ON -AT&'sAfn ah 19hMY, b &.,ý W3Certn1caw. 14lder)

-q Our ASME Certificate of Authorization No. to use the symbol expires-1YAWY-W 00 CERTIFICATION OF DESIGN Design information on file at &yRQAJ 1Pdek!5aVIN fi DV Stress analy&s report (Camss 1 only) on file at 1N/A -

iF P4 Design specifications cartified by (1) A4. S119U MA N Oati PEStat. & Aeg. -.eTc*PHie-N 3-"2.-

Stress anasscried Uyt n y.-

(1) Signature not~required. Ust name only.- -

CERTIFICATE OF SHOP INSPECTION

1. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of M2L/FRNZ'V4 and employed byA19 & n6F4*,117VJ4& IN/A.5, '..

of WA)ALTRAIi A 55 -.- have inspected the pump. or valve, described in this Data Report on c_-. _ 19 -. `Lrend state that to the best of my knowledge and belief. the N Certificate Holder has con-structed this pump. or valve. in accordance with the ASME Code. Section IlL By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described in this Data Report. Furtherniora. neither the Inspector nor his employer shall be liable in any manner for any pwrsonal injury o property damage or a loss of any kind arising from or connected with this inspection.

I ale *)ot-!e-. f ýF' 1- *---

I*" -td ý -- All Ilnspec*bor

=ý - -!=- Commissions IN 8d, Stole sl P!Pe Da ,-

, and N.J Pr I, i"ý-.ý:-...'

.4 P-2ge.3 of 3 FORM NPV-1 N CXR-FItCATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALUES (SUPP.)

1. Xanufactured 37: Sa/o fr.nhILL/ 2 CO LVee*'vc

. AVC. fNON cAOl vEoALA 2.

Manufactured For: *5-"Ne 4N*i te85Teg *Nr.oRP. OP 1-Y"-MASSP-2107

3. Lacition of installation: Ae,'vek vglie~j PAweA s-r4Tvaý !fo~r Pevra.U.i/v'N
4. Pump S/11: 3N1 I- 400.07 5.

(Brief description of secvice for which equipumet was designed)

8. Pressure Retaining Pieces Mark N'o. Material Spec. No. Xanufacturer Remarks Lacjef 0,1vc SA-5-J* 68, 70 596~J2

!~

C04. P/PC s,"5- /1- 70 5__

toe. *6A-515 .P-70 _______ .85?

C

-- 5- 5-__

  • 1 (A-
  • N r~i~

Our ASME Certificate of Authorization No. 1130 to use Verifica no/gZatures

" s"ymbol expirs 16 June 1984 A -4 Manufacturer. C',.b.. ..

Authorized Suclear Inspector:Z J ,

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 2053 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/06/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 4 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippincport, PA 15077 Work Order #200089238 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippincport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Main Steam (Class 2)
5. (a) Applicable Construction Code Section III 1977 Edition, S'79 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No- Identification Built Installed (Yes or No)

Valve Atwood & Morrill 2-15579-03 N/A 2MSS-AOV1IOB 1987 Corrected Yes Poppet Weir Valve G8923-1 N/A Ht. #N1892 2008 Installed Yes Pilot Poppet Weir Valve I N/A Ht. #415388 2008 Installed Yes

7. Description of Work Replaced both main poppet and pilot poppet/stem assembly. Weld restored #6 guide rib base material & stellite, and area above seat in body bore radius.
8. Tests Conducted: Hydrostatic* E] Pneumatic* E] Nominal Operating Pressure EL Exempt Z Other LI Pressure psi Test Temp. _ OF
  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Reports attached. Body gasket seating area was restored by machining &

Applicable Manufacturer's Data Reports to be attached NDE'd. and several areas of the bodv castino were around & NDE'd to remove rounded indications_

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 15 2010 Own Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period .. f- - * -O T to - 0Z. 7 - 0 9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions , ,J /14 -L.. ? TV tnspector~~s tr Natioral Board, State, Province, and Endorsements Date , 20 Z"0 Date 20 (~

9787409668  ; Nov-21-06 12:02PM; Page 8/9

ent By. ATWOOD&MORRILL CO.;

FORM NPV-1 N CERTI ICA HOLDERS' DATA REPORT FOR .NUCL I PUMIPS OR VALVES*

'(Corrected Copy As Requ ed the Provisions -f-Owe ASME Code, Section ill, Div. 1

1. M a n u f a c t u r e d b y A(wn h n 28 a l Str e e t ,

C . ,an Sal li , MA 01 9 7 0_

(Na *and Addressof N Certificate Holder)

2. Manufactured for DugQesne Liizh_ Qomp.pny*,. Pittsburgh., PA (Nam rid Address of Purchaser or Owner)
3. Location of Installation 33e ver Valley ,Station 2, SZhipinzport, PA.

(Nam rnd Addreia)

4. Pump or Valve V Lve Nominal Inlet Size 28 Outlet Size 28 jinch) (inch)

(a) Model No., (b) N Ce icate Holder's (c) Canadian Series No. rial Registration (d) Drawing (f) Nat'l. (0) Year or Type I No. No. No. (a) Class Bd.

No. Sujit (1) 28" Main Steam 2-ISS79-03 ,N/A 15979-03 2 N/A N 'q87 (2) Valve R 0_5olain a_'02 (4) *Sold Lto $ ne & Webster Enzineering Corp.. . ..

(5)

(6) **PRilor poo .t mater$al -pocured to ASME Section II, 1974 Edition. with (7) Winter 19 Addenda. Reference A&M NCR# 32446.

(8) " ___________

(9)

5. ~Main Stea*

(8(iaf deacription of servire for which equipment wax disuigned)

(Pressu

6. Design Conditions _ ill i psi 560 (Te 1trperat ur )" 'F or Valve Pressura Class N/A (1)
7. Cold Working Pressure 150 psi at 100"F.
8. Pressure Retaining Pieces Mark No. Material Spec. No, Manufacturer Remarks (a) Casirirgs Body S 1216 Gr .

WCC NewP ort New, 4235B-1 (b) Forgings

?opoet .A 0O5 0 & T C.nn & Saul Steel1 _X{V4191-1 05 0 & T Cann & Saul e 068460-4 Cover SA

    • Pilot Poppet ~ ~ ~ZSAI ill. .82 Gr. 'F6a Cann & Saul Steel 30611-2 j1) for manvally operatea valves onIV1 osuipi,ornmttat inforrnallotn (n lttte form ýt Uists, sketches, or drawings may no L4ssd providod (1) size is SK x " , (2) Itformation In 'tam% 1 tJhrouch 4 on this Data9 Report Is Inclue i on each shest, (3) each sheet is numbered and the number of sh"eTi s recorded at the top of this fOrM, And (4) *ach additional xhaet shall e signed by the Ceri*ticatt Hodaer a-d the ANI, (61f4)Th I* f^.

Sent By; ATWOOD&MORRILL CO.; 9787409668  ; Nov-21-06 12:02PM; Page 9/9,-

Mark No.

I FORM NPV-1 (Backj Material Spec. Noý Manufacturer Remarks (c) 8otting _

Stud *540 Gr. B23 C1. 5 Jos. Dyson & Son Trace F1776 Nuts 540 Gr. B23 CI.1 5 Jos. Dyson & Son Trace F1773 1d) Other Parts N/A__ _ _ _ _ _ _ _ ___ _ _ _ _ _ _

19. Hydro4tartip wst 2250 psi Disk Differential test pressure 1650 psi.

CERTIFICATE OF COMPLIANCE We certify that the state.mentt made in this report are correct and that this pump, or valve, conforms to the rules of iconstruction of the ASME Cou for Nuclear Power Plant Components. Section iII, Div. L. Editior) 1977.

  • Addenda Suimsner 1979** _, Code Case No. N/A Date " 4Zi--Z*iIoII7 Signed Atwood .6 Morr 1 Co., Inc.

(N Certificate Hob r)

(Our ASME Certificate of Autho ation No. N2606 to use the N Isymbol expires 6--13-89 (NJ Lu CERTIFICATION OF DESIGN pasign information on file at ;tone & Webster Engineering Stress analysis report (Class ly) on file at N/A

ýDesign specifications certified (1) ... D eisl Pati L essard I.E State PA .No. 34173-E

,'Strem analysis certified by (1) NIA__

E State N/A . No. N/A I]) Signature not required. List ame only.

I, i,?*

CERITIFICATE OF SHOP INSPECTION IL the undersigned, holding a lid commission issued by the National Board of Boiler and 'reasure Vessel Inspectors And the State or Province of-- s and employed by H_.S.B.I. & 1. Co.

mf Hartford. CT have inspected the pump, or valve. described in this Data Report on ill 46& 1 LZ_.. and state that to the best of my knowledge and belief, tho N Cartificate Holder has con-

£rkructed this pump. or valve, ir ,ccordance with the ASME Code, Section Ill.

a*B*y signing this certificate, neit ýr the Inspector nor his employer makes any warranty, expressed or implied. concerning the equipment described in th Data Report, Furthermore, neither the Inspector nor his empoyer shall be liable in any

.fnranner for any personal injurv >r property damage or a loss of any kind arising from or connected with this inspection.

~Date Commissions Nat'r'd,. aZownd .

(Not' Bd,, State, Prov. and No.1

-*NF its

(Paige .9 0f 60)

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section III Not to Exceed One Day's Production .11 of 2

1. Manufactured and certified by Weir Valves & Controls USA, Inc. 29 Old Right Rd., Ipswich, MA 01938-1119 (name and address of NPT Certificate HOIdorj
2. Manufactured for First Enerqy, P.O. Box 6100, Johnstown, PA 15907-6100 (name and address of Purchaser)
3. Location of installation Beaver Valley Nuclear Power Plant, Route 16B, Shippingport PA -15077 (name and address)
4. Type: *32467-614-D Rev 0 SA 105 84.500 N/A 2008 2008 (drawing no.) SA 105 (malt. spec. no.) (iensde strengthl) NIA (CRN) (year built)
5. ASME Code,Section III, Division 1: 1977 S'11979 2 N/A (editon) (aiddenda date) (class) (Code case no.)
6. Fabricated in accordance with Const. Spec. (Div. 2 only) N/A N/A N/A Date N/A (no.)
7. Remarks: Cust. Item 00001 WVC Item 10 Qty. 1 Poppet A&M PIN 32467-614-2974-121 QLA (WVC S.O. 78595) *Dwq. Prepared by WVC. This certification meets required information of ASME Section Ill 1977 Edition S'1979 Addenda.
8. Nom. Thickness (in.) N/A Min. design thickness (in.) N/A Dla. ID (ft & in.) N/A Length overall (ft& in.) N/A
9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:

Part or Appurtenance National Part or Appurtenance National Serial Number Board No. Serial Number Board No.

In Numerical Order In Numerical Order (1) HT: N1892 S/N: G8923-1 N/A (26)

(2)

(3)

(4)

(27)

(28)

(29)

(5) (30)

(6) (31)

(7) (32)

(8) (33)

(9) (34) 4-(10) (35)

+

(11) (36) 4.

(12) (37)

(13) (38)

(14) (39)

(15) ___________ _________ (40)

(16) (41) 4.

(17) (42)

(18) (43) i (19) (44)

(20) (45)

(21) (46)

(22) (47)

(23) (48)

(24) (49)

(25) (50)

10. Design pressure N/A psi. Temp. N/A *F. Hydro. test pressure N/A At temp. 'F (when applicable)

'Supplemental information in the form of lists, sketches, or drawings may be used provided (I) size Is 11%x 11, (2) Information In Items 2 and 3 on this Data Report is Included on each sheet is numbered and the number of sheets is recorded at the top of this form.

(12./88) This form (E00040) may be obtained from the Order Dept, ASME, 22 Law Drive. Box 2300. Fairfield. NJ 07007-2300.

Reprint (7/91)

(Page 10 -of 60)

FORM N-2 (Back - Pg. 2 of 2)

Certificate Holders' Serial Nos. HT: N1892 SIN: G8923-1 through N/A CERTIFICATION OF DESIGN Design specifications certified by N/A P.E. State N/A Reg. no. N/A (when applicatde)

Design report

  • certified by N/A P.E. State N/A Reg. no. N/A (when applicable)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this (these) Poppet conforms to the rules of construction of the ASME Code, Section II1,Division 1.

NPT Certificate of Authorization No N2607 Expires 6-13-2010 Date Name Weir Valves & Controls USA, Inc. Signed (NPT Ceflificale Holder)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of MA. And employed by HSBCT of Hartford, CT have inspected these Items described in this Data Report on -?, and state that to the Best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code, Section Ill, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, conceming the equipment described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.

Date 7- Ik - k Signed /, Commissions -Y4 /4 S-4 (authorized inspector) IeNal Bd. (Ind. Endorsements) and state or pwov.and no.1

(Page 36 of 71)

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section III Not to Exceed One Day's Production Pq. 1 of 2

1. Manufactured and certified by Weir Valves & Controls USA, Inc. 285 Canal Street Salem, MA 01970 (name and address of NPT Certificate Holder)
2. Manufactured for First Enerqy, P.O. Box 6100, Johnstown, PA 15907-6100 (name and address of Purchaser)
3. Location of installation Beaver Valley Nuclear Power Plant, Route 16B, Shippinqport PA 15077 (name and address)
4. Type: *32446-303-C Rev. 02 SA 479, S30400 86,500 N/A 2008 (drawing no.) (mall. spec. no.) (lensile strength) (CRN) (year buill)
5. ASME Code,Section III, Division 1: 1977 S'1 979 2 N/A (edition) (addenda date) (class) (Code Case no.)
6. Fabricated in accordance with Const. Spec. (Div. 2 only) N/A N/A N/A Date N/A

,(no.)

7. Remarks: Cust. Item 00001 WVC Item 20-3 Qty. 2 Pilot Poppet A&M PIN 32446-303-4226-000 QLA (WVC S.O. 78595) *Dwg. Prepared by WVC. This certification meets required information of ASME Section ii 1977 Edition S'1979 Addenda.
8. Nom. Thickness (in.) N/A ' Min. design thickness (in.) N/A Dia. ID (ft & in.) N/A Length overall (ft& in.) N/A
9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:

Part or Appurtenance National Part or Appurtenance National Serial Number Board No. Serial Number Board No.

In Numerical Order In Numerical Order (1) HT:415388 S/N: 1 & 2 N/A (26)

(2) (27)

(3) (28)

(4) (29)

(5) (30)

(6) (31)

(7) (32)

(8) (33)

(9) (34)

(10) (35)

(11) (36)

(12) (37)

(13) (38)

(14) (39)

(15) (40)

(16) (41)

(17) (42)

(18) (43)

(19) (44)

(20) (45)

(21) (46)

(22) (47)

(23) (48)

(24) -' (49)

(25) (50)

10. Design pressure - N/A psi. Temp. N/A 'F. Hydro. test pressure N/A At temp. 'F (when applicable)

".5upplemental Information In the form of fhis, sketches, or drawings may be used provided (1) size Is 8 AI x 11. (2) Information In Items 2 and 3 on this Data Report Is includod on each sheet Is numbered and the number of sheets It recorded at the top of this form.

(121Ss) (Thisform (E00040) may be obtained from the Order Dept.. ASMF, 22 Law Drive. Box 2300. Fairfield, NJ 07007-2300.

Reprint [7191)

(Page 37 of 71)

FORM N-2 (Back - Pg. 2 of 2)

Certificate Holders' Serial Nos. HT: 415388 S/N 1 through 2 CERTIFICATION OF DESIGN Design specifications certified by N/A P.E. State N/A Reg. no. N/A (when avpkcstbe)

Design report certified by N/A P.E. State N/A Reg. no. N/A twhen applicabtal)

CERTIFICATE OF COMPUANCE We certify that the statements made in this report are correct and that this (these) Pilot Poppet conforms to the rules of construction of the ASME Code.Section III, Division 1.

NPT Certificate of Authorization No N2607 Expires 6-13-2010 1 -72 Date Name Weir Valves & Controls USA. Inc. Signed (NPT Certificate Hoider) (authized reresentatve)

CERTIFICATE OF INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of MA. And employed by HSBCT / /

of Hartford, CT have Inspected these items described In this Data Report on . and state that to the Best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordan ASME Code, Section I11,Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Reporc Furthermore, neither the' spec r nor his employer s I be liable in any manner for any personal injury or property damage or loss of any kdndyfisin,,ror or =th IM* sp ioS Date Yj/ < ge(Commissions W /~ 1 4 Ai

-lauhon-ed~npectr) Nall ed- (id. Endlorsements) and state of prov. and no.1

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 2083 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 02/02/2009 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShippinQport, PA 15077 Work Order #200252925 (ADDRESS) RepairlReplacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Ship pinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Residual Heat Removal (Class 2)
5. (a) Applicable Construction Code Section III 1974 Edition, S'74 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity. 1989 (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer , National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Heat Exchanger Atlas Industrial 3484 2854 2RHS-E21B 1978 Corrected Yes

7. Description of Work Replaced stud and nut.
8. Tests Conducted: Hydrostatic* El Pneumatic* [] Nominal Operating Pressure LI Exempt [Z Other [:] Pressure psi Test Temp. o_F
  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Replacement 1-1/8" Stud: P.O. 47037233 / Ht. #M584: Nut: P.O 47043141 / Ht. #J858.

Applicable Manufacturer's Data Reports to be attached Code Data Report attached to previous NIS-2 Data Report No. 1132.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorizatio.*o* - N/A Expiration Date N/A Signed - Senior Specialist Date March 05 20 09

% Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during 'the period * '- -. ' to - ,and I state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/* -I* Iector's SgNational Commissions J/zA* Y')4 ,/".

Board, State, Province, and Endorsements Date 3- (ý -

, 20

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 2098 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 01/15/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 3 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order 200109377 (ADDRESS) Repair(Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shioninonort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date N/A

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda' N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 1989E (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pump Byron Jackson 731-N-0020 N/A 2SWS-P21C 1982 Removed Yes Pump Byron Jackson 731-N-0027 N/A 2SWS-P21C 1982 Installed Yes Column Penn Iron Works 5236N-l " 473 N/A 2006 Installed Yes Stuffing Box Flowserve/IDP RLSA06662 N/A N/A 2005 Installed Yes

7. Description of Work Replaced pump with rebuilt spare, replaced pump column and boltinq.

Replaced seismic supports.

8. Tests Conducted: . Hydrostatic* LI Pneumatic* L-I Nominal4Operating Pressure 0 Exempt []

Other L] Pressure psi Test Temp. _F

  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Previous NIS-2 Data Report Nos: 576 (NPV-1 attached). The spare pump was Applicable Manufacturer's Data Reports to be attached rebuilt per NIS-2 Data Report No 2040. Replacement 7/8" Studs: PO 45172981 / Ht. #x374, 47134616 / Ht. #Z660: 7/8" Nuts: PO 45246143/ Ht. #Q.JR; 1" Studs: PO 45246235 / Ht, #1C69, PO 45168676 / Ht. #255: 1-1/4" Studs: PO 47082958 Ht. #P918: %" Bolts: PO 45257251 / Ht. # GA 139335: %/"Plate: PO 7037275 / Ht. #7468224: Channel: PO 45258306 / Ht.
  1. 6706558 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Justin Sciulli A/

  • Nuclear Specialist Date January 25 , 2010 Ownertwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period ."'--, - 0 F to /1- ). 7 - , and state that to the best of my knowiedge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions /, ,  !-!9d-? ?V Inspector'>inature National Board, State, Province, and Endorsements Date t -- 20 , 20 /`0

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section III 2 Not to Exceed One Day's Production Pg..1 of __

Flowserve Corp.,Pump Division, 2300 E. Vernon Ave., Vernon, CA 90.058

1. Manufactured and certified by (name aud address ofNPT Certiqcate Ijolder)

First Energy Corp., P.O. Box 6100, Johnstown, Pennsylvama

2. Manufactured for Me daddCess of purcaser)

Beaver Valley Station, Route 8, ippmgport, vennsylvana

3. Location of installation InambakpfjW 2005 DWG313206 ASME SA 216 GR.WCB
4. T y p e (drawing no.) (marl. sem. no.) ( e sl 5trmer tC 1972 ce N1 ~

4 rbttltt

5. ASME Code, Section III, Division 1:

(edition) VtAnda dale) (e~)/Case no.)

6. Fabricated in accordance with Const. Spec. (Div. 2 only) Revision Date (no.)
7. Remarks: Flowserve Job No.: RLCA02520 Nomenclature: Stuffing Box.

Nameplate attached with drive pins.

1.12l .UU Iu.uu LJ.uu

8. Nom. thickness (in.) . Min. design thickness (in.) - Dia. ID (ft & in.) Length overall (ft & in.)
9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:

National National Part or Appurtenance Board No. Part or Appurtenance Board No.

Serial Number in Numerical Order Serial Number in Numerical Order RLSA06662 N/A (1) (26)

(2) (27)

(3_) (28)

(4) (29).

(5) (30)

(6) (31)

(7) _______________________________~~I__ ________________ (32)

(8) (33)

(9) -4 (34)

(10) (35)

(11) (36)

(12) + (37)

(13) + (38)

(14)i (39)

(i 6) (40)

(16) (41)

(17) (42) +

(43)

(19) (44)

(45)

(46)

(22) (47)

(23) (48) i (24) (49)

(25) Irni 150 100 235 @70F 10 "ign pressure psi. Temp. °F. Hydro. test pressure at temp. 'F lwhen applicablel

  • Supplemental information in the form of lists, sketches, or drawings may be used provided (1) size is 81/2 x 11, (2) information in items 2 and 3 on this Data Report is included on each sheet, (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(7/98) This form (E00040) may be obtained from the Order Dept., ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.

E00040

2 FORM N-2 (Back - Pg 2."of RLSA06662 RLSA06662 Certificate Holder's Serial Nos. through CERTIFICATION OF DESIGN Rodger E.Martin PA 2808-E Design specifications certified by P.E. State Reg. no.

Douglas B. NM&gdfJcable) CA 1314 Design report* certified by P.E. State Reg. no.

(when applicable)

CERTIFICATE OF COMPLIANCE Stuffing Box.

We certify that the statements made in this report are correct and that this (these) conforms to the rules of construction of the ASME Code,Section III, Division 1.

N-1 131 June 10, 2005 NPT Certificate of Authorization No. Expires 2/25/2005 Flowserve Corp., Pump Division , Z - /

Date Name (NPT Certificate Holder) Signed ,Lthorized representativd)

CERTIFICATE OF INSPECTION I, the undrigned, holding a valid commission issued bpg&-._.tional.Board of Boiler and Pressure Vessel Inspectors and the State or Province of Htodae1a ermployed by of have inspected these items described in this Data Report on , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code,Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage oss of any kind arising from or connected with this ins 3/29/2005 ',-jsction. C  :

Date ýJ om- 55 -

(Authorized Nuckar Inspector) [Nat'l. 8d. (incl. endorsements) and state or prov. and no.)

FORM N-2 CERIIFICATE HO.ERS' DATA REPORT FOR IDEWHCAL NUCLEAR PARTS AND APPURTENANCES' As Reqtired by the Provisions of the ASME Code, Section 101 Not to Exceed One Day's Production Pg. 1. of 2

-- 17Manufa*-ured end certiied by Penn Iron Works, Inc,. 700. Old Fritztown Road, Sinking Spring, PA 19608

[name and address of NPT CerlifIcate Holder)

2. Manufactured for Flowserve Pump Cprp*, 2300 East Vernon Avenue, Vernon. CA 90058

{(nane and a*drerz of purcrh } 1

3. Lozation of installation Unknown (nama and addransi 313207i Rev. E SA-l05, 106, 515 &516 70 ksi Min. NA 2006 00
4. Type. 4(drarngno.) (mail. -pe. na.= (a. aa t h (CaN) " Wear builtl

. Ce S - ......

'-v. ... See Remarks See Remarks " 3 NA

5. ASME Code, 5ection II), Division 1 (edition) (addenda date) (class) (CodeCase no.)

NA- NA NA

6. Fabricated in accordance with Const Spec. (Div. 2 only) N Revision Date
7. Remads-
  • Penn Iron Works. Inc. not responsible for design
1. Design -.1971 Edition, Winter 1972 Addenda; 2. Materials - ASME Section-.l, Parts A &G-. 1995 Edition;. 1996 Addenda Z Fabrication and Examination- 0ASME 500"Section III; 1995 0 43"Edition, 1996 Addenda___2__O" OD____
8. Nomd. tl*ne [in. 0. Soo" Min. design tticlcness [In.) 0.435" Dia. ID (ft & In.) 2' - 0"OD Lengrn overall (1r & in.) 9' - 6"
9. When applicable, Certificate Holders' Data Reports are attached for each item of this report:

National Part o- App.rton..on Borrd Nq.

Serial Number in Numerical Order (26) ....

(27)

(28)

(29)

(30)

(31)

(32)

(33)

(34)

(35)

(36)

(37)

(38]

  • (39)

(40) 141)

(42)

(43)

(44)

(45)

(46)

(47)

(48)

(49)

(50)

10. Design pressure 150' ps Temp. 100 F. Hydro. test pressure 225(when psigapplkcablel

@71 at temp. IF Supplemental information in the form of [ists. sfetcihes. or drawings may be used provided (1) size is 9% x 11. (2j information in itermn 2 2nd.3 on this Datz Renort is inclu de d on ea;:h sheet, ()

3 eah: sheet nm bered ;=zd the numubarof Shrats is raodd nis at' the to p of ths form'.

(7/381 -This form (T00040) may be obtained from the Order Dept.. ASME. 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.

LOT NO.: 02-005299 SALE ORDER NO.: RLCJ00040 ITEM NAME: COLUMN ITEM NO.: 10051634 CUSTOMER P.O.: 55i03921

FORM Nod-2(ak - pg 2 2 53N CetiiatHlersSerial Nos. 5236N-1 truh5236N-1 CERTIFICATION O- NDESIGN Design specifications certified by' PE State NA Reg. no NA

'.(whenappiicahle)

Design report* certified by NA PE. State NA Reg. no. NA I.hen applicable)

(w CERTIFICATE iOF COMPLIAN~CE'-

-We certify that the statements made in this report are correct and that this (these) Column conforms to the rules of construction of the ASME Code,Section III,* Division 1.

NPT Certificate of Authorization No. N-2927 Exp__ires June 28, 2008 N-2927 Axie ZZ*LName Name Penn Iron  : Works; Inc.Signe n 81 ..

" iCERT"FICATE OF INSPECGTION 1, the urndrsigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of . and emrpoydby ed of ._I____

__e____ ._ _ have in-spected these items described in this Data Report on 12/,l 6 . and staIte that to the best of rny knowledge and belief, ne Certlrcate.tiolder has tabriCatedl these parts or appurtenances in accordance with the ASMI- Code, Section Ili, Divislon 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described In this Data Report. Purthermore. neither the inspector nor his employer shall, be liable in any manner for any personal injury or property damage or loss of any kindarising from or connected V&ýs inspeti...

Date 7 6 Signed' Commissions i1 S + > )/2W 253;2 Z t - .- 1 lAuttuoriz celaarlnapec IKat'L Bd. lind. anciotemmena) .nd Istt cr pou. and m]-

LOT No.: 02-005299 SALE-ORDERý NO.: RLCJ00040 ITEM NAME: COLUMN T0mEM NO.:.0051032

CUSTOMER P.O.: 55103921

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3025 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 02/02/2009 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 3 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Thinninnorwt PA 15077 PA 15077 Work Order #200283896 Shinningnort (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shic *pingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical & Volume Control (Class 2)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Check Valve Kerotest LA2-1 9437 2CHS-153 1976 Corrected Yes Disc Flowserve --- N/A Ht. #724770 2002 Installed Yes

7. Description of Work Replaced valve disc.
8. Tests Conducted: Hydrostatic* E] Pneumatic* E] Nominal Operating Pressure 0' Exempt Z Other EL Pressure _ psi Test Temp. OF Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Serial number of replacement disc was not recorded.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate ofAuthori n No. N/A Expiration Date _ N/A Signe_ Date March 13 , 20 09 Owner or Owner's Designee, Title Senior Specialist CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT - of Hartford CT have inspected the components described in this Owner's Report during the period , '2 - o 9 to 3 -/ "? - 0 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations. and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions '-J,17/L 7 , P4 a-  ?"i Insp:pr Signature National Board, State, Province, and Endorsements Date

,20 ___

Date 1 20 iý 7

t roaM= ?mr m"TaCz.7 0w R DATA X KT FmO mNL.EA. rPxxr Amo A.*VrZ=EmDm As gcquawd by the Ftwwi~Q of die ASME*Codc R1dku Setion in. Div. I L W Midcmlkr- Fpowserve Coeporatio1, 701 First trteet,. WiIJAnspo-rt, PA 17701 First Energy Corp., P.O. Box 3611, Akron, OH 44309-3611 0ma dqng 1&2 _ /A_

(a) C*-a~s'aIxtd la ri~ "7572609118 R/J DemkIpspare jglowserve Corp.

"m ,,, t,=t*! Disc w/Steilite Heatt#724770 SA479-316

  • .a t.Sc- e. - 1971 -A - t Winter72,.m N/A I1

-- a,.-Spare Part(s) for 2"-1500# Check Valve *Disc Assembly Dwg. #7572609084 R/E FlowIerve ._ Item Nofk F.R23w*R-3 *o"nd tmNo RI-I

=. wsrv S 0 n NOTE:No H~drotesting Perfort~d Long Term Storaze Facility we cgaify dactie ammftow ma~e io &Ui StpoSc st *ad &"i vessd parO SPPtM = AS Aasdclc am&C CO&e to*

too"a* dith Mrs of vommouuclomi &Etc ASWE Code Seed..n RL (The a~*D~ sc~ca AW o Swam Repwt am~ aoa Ibe Iimuibtluty at the xWi Ce"Ieafe ROWelIa- aUU.An Xrr CaUf.

kite Ha~dc fqe ttaS~le tor SdiaaSCPa Ias itau~s Dcimu Syedficu~ou sd S=Au Yxon-if the e~apaccme is o Winaded Ia the c~~amD=~ SeC~d~csdt s 3ww Sax plevalt.

U/it... ~O~~p now erve corporFaiijo Cemrl~come a M m 4115104 ....

-1713 L CEMlFi CATMON OF DM I FOR APPURTENCE (.h= *pplcx*e)

S., a washm" astp@as Mle S" De..

' s-'L-i-sa-ST -- ce-

- ed . . . ' -- P aL Reg......

a

&44YsI ceu1Eifi naisswPurg t P=.L Em tc - e.11.

CERanFIC OF SUOP tWSECTIMt

&C, watheagsweedaed kbig a Valid e luod Vy &Ce adomal Baudl of Boner ond pzsewmv Vesiel upecwv imas modlosth SUMC ~ Pe =SY, van iA -~.. Oni~cBeA!ý icai5nsiuiancr

.- f Wn, !b L216c ra 91pft- vc ss &..Maed 7^his aid beflef. wh T~rCtE=6&%* K*4jr ms cudctd Us panInE accodance wtth me As)0 Code SectkaSlL ~ iweg ft a=gmoi d.as Catilkaae alfatem tAe JauPe-a - Us asP.Zoyt e 00 --- Y.~ asPfei*ae 0C jpliC4, eaoso. -

Iwoi tepart fetbedbCb Is hi Paroal ta4 Repais yvfhtmwge. %either thet lusuectwor'so his ""tomr SbHal be liable ilk &ormUaw fot soy Ot Pel- domage OrI os any orl~i0 of .u. kin H" lamisor~

m-se widh %bis jV Ca~eis than E'5 YOIMfl"~' ~

7~-~~ ~5~-.~7

-7

~Pennsylvania 2392 INSa ,ECOAO4awv beO*'u-rd lvaii If Orftr DeSm- W 345 E. "m q_ m*w~rf.rX Mi

FOP.%1N \ ~V.M I(1!iI~I 1I)ATA lKIOI01 F FORl NItA PU~\i

'MP~S OR1 \AL%'Es p1 2525 Liberty'Ave.

1. Manulactured byKrUdt~eSt _trf~trf~p.2~~

bL)XhJA rerN. Jkf_

Z.,,.Acddas of U-.focz.rer)

P. 0. Box 355 I al Anu acture 4r Of Westinghouse.Electric.Corp. Pittsburgh, PA "'.A r., er I*.l , ML.

oa, 5L46-CCF-78252]BN (Urme *nd Add-e-,)

3. 0,'e Duquesne LightCompazy_______________________

A-. Location 0r Plant Beave r Valley No.. 2

~. X~~lv Ienifiat ~2" hek alv s1~LA2~-1: L.A2-8, LA2-1O, LA2-46, LA2-18, LA12-15 LAL-21, LA2-23, LA2-25 (Sri,?( de~cription of service for whichs equiptntnt waa dezigned) service: radioactive WF1 .fluid (z) Drm-inpg oW-D--9911-(2) Rev .D H.pr~

,>__Dratfinsky S0 1 of 1 Mb National Board No...9i+/-.Uthri.) q~45

6. Design Condi:ionS 2580 - 650 or Prcssxire Cla-ss ~ 500 ~

(Tcmp. ralure) 2

7. The material, design. cons~tuc IEof, and wo~rkman~ship complies with ASME Code Section 1114 Class__________

1971 winter 1972 N /A Edition -. *Addenda Date Case No.

Markc 111. -l~oeriaI Spec. No.) Manufactur R avt (a) Cnasin~a

_._ _ _ _I _ _. _ _ _,

____________________________________ I__________________ _________________ I. ________________

(b) Forging.%

body P-.9911-1-(1)Z SA182,F316 McWilliams Forge Mat'l Code LA cover P-9911-2-(l)Z "_" _"_FA & EA cover UP- ()Z . " . .

(1) For, manually spcr.,tcrd '.lvc- only.

'Supplemental shee ts J. form of l s.i. skischea or dI....ng. masy b.- used prorsd~d (I). lss i. a,/,** a W', (2) irifvrm.otio in .* 3sa 2. S.s -d Sbott tkis data report is inc.,xled on each shest, and (3) each she as nusat~cred anid n~brs of .hct& L. .- cordrd at tvp of thim form.

- ^**- G--~~9 Crdcr Dept..

rm'c t.,1..tflel ASMAE, 345 E. 47 St., New York. N.Y. 10017.

FI,' Z.N,NI'V-1 1(lýzck}

M~*e k N., ,orit- cl Sptc. N.,. i (c) r-oling

- _______ ____ 7K~7L__.11L_ __ _ ___1~

I-... ___

I -... -----

(d) Qr~t~rPa+/-is '1-disc assv. UP~-99ll-59~-(1)Z I SA'479~TYP~Z6fcar~enter

-_____ _____ _- -~ ____

_____ I..________

If L_____________________

_____ ___ _______-t . -- ____

1

,.0 V. SA..

C -IR, C'AT') ON()F 't)ESIGN Dczim mia rm-atin ont file at I~riI~i~ c u~a na . -__

aaz~s v'~ is repozrt vyn Mie as ~ A ________ ___________

]~y ip- ,or cir...ific by (1) iF-r (e

- ()

nm~r~not u~d Lin't c. aieoy.

fri. g. ESt z ce ', N.o.,

W7Vc certiy tht- the &ca,-mn--t nzdt in his5 7 co*cecs . /,7'

..!{/ /2 Rc ,-'2N*

April 9 76er-Lotest

~. d 0 vUaroIeo Cecflcacc of Authorizacion No-- __8_10/28 CERTIFICATE OF *tiOP iNSPECT!ON 1, the uutderesigned, ho!ding a vaid cco-,issicsn i..fiucd by th- Nhaeinarl Bofrd of." Boiler PrcsI:,5rt Vessel 1n.vIeczO7'I &nd and/,I0 t6e Sace of Proirnce of-l ,,'a-:. a.rid .ployed- by-he t f-*.r:d 5 c a.- i e U i If{rart ford Q -- ctj u t - have inspecctd dte cquipment descriibcd in this.l Dlt Repo r.- c-ii 39- 7-6----, and siate thac to the be of .my kno*ledge end belief, "he M2snuincturez hasl co t*c*;:-,ced rýs eq pornre't in zcc~ordanc- wiih the 2pplicable Subsectjoas of ASME Code, Scction Ill.

By s*itain -his certificafe, nt'itiher the Inspectoy nor his employer ma .ies any z-arranty, cxpcessc-d ..r i,,,ird. concern-ingthe equipment describ-ed in this Daza Report. Fu thersmore, n*either thc lnspcctor nor his ernployer .iNalleý.c,le in any mr-nner for any pe.sonal injury .sr property damage or a loss of any kind Zisiing from or connected with this inpection.

April 9 1976 Ad . 41/263/

.- - - Cot'tei !-: 0.!~S zt,,t.. Prtp..nr C And ?' a.)

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3045 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/11/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 3 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shiooinaoort. PA 15077 Work Order #200318973 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

ShiooinaDort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Auxiliary Feedwater (Class 2)
5. (a) Applicable Construction Code Section III 1980 Edition, S'81 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Globe Valve Copes-Vulcan 8320-95453-6-1 2475 2FWE-HCV1OOA 1984 Corrected Yes Plug Copes-Vulcan 8721-96246-1-6 N/A N/A 1988 Installed Yes (87-5)

7. Description of Work Replaced plug.
8. Tests Conducted: Hydrostatic* E] Pneumatic* L1 Nominal Operating Pressure Dj Exempt [

Other F1 Pressure psi Test Temp. OF Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Reports attached.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 26 20 10 OwnertrOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford. CT have inspected the components described in this Owner's Report during the period -- ,2 - 0 K to /(- 2 7 - G 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any Kind arising from or connected with this inspection.

2' tnspEefr's signature Commissions Boar7 dStte, //, g 7d3eny National Board, State, Province, and Endorsements Date /2- 7 - ,200 /'o0

- *>~"

FORM N-2 N OR NPT CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL

- - - :NUCLEAR PARTS AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section I If, Division 1 Not To Exceed One Day's Production P g.IOf 1 1.Manufacturedand certloledby Copes-Vulcan, Lake City, PA 16423 (no"and o~~at Wadrs ci* afcaii hlOldO'

2. Manufactured tor Duiesnuene Light Co.. Pittsburvh. PA 15279 (r d address of purchap anne )
3. Location of installation neaver valley unlt i+/- Snippingport, EAt J.jU//

Rev. 0 If.me aend dd,.)

4. Type E-266684MKD SA-182 Tp. 304 89,410 psi --- 1988 (drawing no.) Imet*I. Spec. no.) 4onail. mransth? (CRNJ (yIar built!
5. ASME Code, Section 111: 1980 Summer 1981 2 ....

ledrrion) (addend.) icluas) ICode Con. no.)

N/A Revision N/A Date N/A

6. Fabricated in accordance with Const. Spec. (Div. 2 only)

MNo.)

7. Remarks: Plug for 3" Class 600# Valve Ass'v per DwR. E-266212 Rev. 5 Cn~t. P.O. D039416 CV-Job 8721-96246 cust. P-0. D039416 CV Ref. Job 8320-95453
8. Nom. thickness (in.) N/A Min. design thickness (in.) N/A Die. ID (ft. & in.) N/A Length overall (ft. & in.) N/A
9. When applicable, Certificate Holders' data reports are attached for each item of this report-Part or Appurtenance National Part or Appurtenance National Serial Number Board No. Serial Number Board Number In Numerical Order In Numerical Order R791 _qr,9Lft-1 _A (R749)l M/A (26) 1(21 (27)

(3). (28)

(4) (29) . .. .

(5) ... . (30) , .. *

(6) .. (31)

(~7) .... .. .. . .. _ __ _ __ __ _ __ __ _ __ _ (32) _

(8)

(33)

(9) (34)

(10) (35)

(11) .. (36) 1(12) (37)

(13) . .. (38)

(14) (39)

(15) (40)

(16) (41)

(17) (42)

(1 B).. .. . .

(43)

(19), (44).

(20) (45)

(21) (46)

(22) (47)

(23)- (48)

(24)-

(49)

I') Et (50)

I!&ut- , .. - 0 10 einpesr e .Hdo emrsp ep eetpesr eaks Se Reak ttm F

10. Design pressure_ See Kemarkspsi Temp.. See Remarks OF. Hydro. test pressure .See eak (whn 5lpphcabts) at temp- °F.

aSupplemental Information In the form of [lite,sketches, or drawingS may be used erovldod (I) size In BY. X 1. (2) Information In Items 2 and 3 on this dote report Is Included on-each shoot. (3) each shoot Is numbered and the number of shears Is recorded at the top of this form. T (6*/85)-I This form (E00040) may be obtalned from the Order Dept., ASME, 345 E, 47th St., New York, N.Y. 10017.

--.* -. ... . -- * "" "" -'* 7 ". ... . 7-FORM N-2 (back) .. . . . . . . *

... .e.~ "" .... ~r.s---si~i I No*" .'.8721-96246 o._--

CERTIFICATE OF DESIGN ' ..

Louis C. Wilmot. P. E. state N Reg. no. 49480 Design specifications certified by (when applicable)

Design report' certified by N/A P. E. state______Rag, no._

(whtln Spplicable)

CERTIFICATE OF SHOP COMPLIANCE We certify that the statements made In this report are correct and that this (these)

Conform to the rules of construction of the ASME Code, Section Iit.

NPT Certificate of Authorization no. N-1843 Plugs Expires 8/19/89 I

Date-l-WO-U- Name Copes-Vulcan Signed INPT Certificate Holder) i .t ri(.dp r$' nhoi"ve) rae~nt CERTIFICATE OF SHOP INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or pro-ince of Penna and employed by Protection Mutual Ins.Co.*

of Park Ridge, IL have inspected these Items described In this data report on / -_.D/ - , and state that to the best of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances In accordance with the ASME Code,Section III. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the equipment described In this data report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal Injury or property damage or loss of any kind arsi from or connected with this Inspection. *Factory Mutual Systems Date WLQJ-99 n Commissions Axas6? -2:

4Authorized Inspector) (1,151.Il8. (incl. anrjomrnomet) stat,3 or prov. and no.)

I

'-I

As Required by 'the'Povisions of te ASME Cod"@, Seao* "H,Div. 1 I. L rnufaiurcd by Cote2.-Vulcan, Lake City*.-

Wanre and Address Ofn# Cor.,Ia Holder)

PA -16423 ote L 16antufacured for Stone & Webster Eng- Corp., Boston', Mass Mn& eVal_

A_*l of PUniw e Owio) - 2W m 15eavel: Val q 1Pow*er Station Unit #2. Shippin2-oorr. PA

.*a4 or Valve Valve Nominal Inlet Size 3 Ouit't Si~ _3 (inch)

(a) Model No.. ( I3 N Crtlficate Moideres I ~L IdgiCradioan or No. (d) Drawing M Natt W yev, at Type No. M Class 24L f4c. 80A Globe 8320-95453-6-I - . E-266212-Rev. 4 2 24 75 zI QSU.

oRaj 2475 I.

-.t. *,

/ -411 ri Ann& TAav-P,&I rr% s- Aivv r W t,ý Z+--- r- ITY It -

(3-isf dea~ion of sc fot whid' OqApm&Mt was 8eSi0nitJI Cust. P.O. 2BV-209A Valve I.D-. 2FWE*ECV100A 1415 12"

& S .- 1415 pjal 10 - or Vaive Precaure Claes '

ColdW noPTesure Psi pt1*. .. . - - '-

Preawr Mn* P - -.

Marttii* M, Sp .. Metiufa:uer . Remarks Wa caznsdv to SI lSN 425 ISME SA 216 Quaker Q _ _

_-WCB_ _ _

Bcna-et SIN E3091-2 ASME SA 216 Quaker GR-WCB I

I ____________________

______________________________ I___________________________

I

11) Foginss r Valley Foyer znit Station - No. 2 C.OIo.6289 -Ei/H Actuated Vilv-es J.0. INo. 12241 -O.F.F,. No. 10)80JL P.0. iNo. 2BV-209A .

Valv4 S/N" 83 - 395 6`/ 1. .,....-; - _L

p. . .

-ay operated vavWS only. .Fr sta-ftn in form. o~f 135.ar'e tc d ewinoa ,nav be used nravidc~d (11 .;7,,3  ; 2MID" 11V ft%.J.i

Manufacturer Remert~s Mar~g No.N~. M.te~.l Sp.c~ No.

MatcrAl Spec. No.

Mark Manufacw'mri I I .1 ----------------

1c) Boltinq I I I I- L Studl Lo.n C,6 ASME SA 193 V4 1 I I -- ~-.. I Nuts*  !.t XIZ A 5 A 19J4 I~--- '- -' -- - - %WV-I (d) OWer Part Pliul S/N 83--5 ASME SA _82 McInnes Tp. 304

9. Iydrntm c _2225 , V.
1. , 1628 i.

CV S/N 8320-95453-6-1 CER a CATE OF COMPUANCE -

We Otrtif thet sttatenmet rmad* an this rop~or ame wrrfec and that this pump, or vaive, conformns to the rukea of conotructmon of the ASMVE Cad9 for NUC14W PowerW f~tW Components. Secfian III i. L Ed-"n J398o .,

Sind Copes-Vulcan b ij QuSECertflGat of Authortzatn No N-1842 N8/19/861

_________________________________OF_______DESIGN____________

Desigr informiation on fite at ,Stone & Webster Eng. Corp., Boston Mass Sta ntysis fogort (Ciass I nM on fil a NIA Dgoneerfcatifn cemid by (1) LoUifi X Wilmot PE Sae NYReg. No. 44 Svren analysis cortified bV ( 1) N/A PE State Reg. No. _______

I1 Q~nature not required- List name only.

CERTIRCATE OF SHOP INSPECTION

1. i'e undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Ptla and employed by 'Protection Mutual Ins.ro.

of Park R.id , L hve inspectedtme pump, or valve, described in this Date Report on d"- 19 .A---.and Ststathat to the best of my knowledge and belief, th. N-Certificate Holder has con-sUmct" vi$s purYp, or valve, in accordace with the ASME Coda, Section IlI.

BY Sigftit t*'is certificate. neither the i.spedtat no: his employer makes any warranty, expressed cr implied, covncern*ng Ve:eQui0&&ent descrilod in this Data Report. Fiurthermore., neither the Inspector nor his emp!oyer shal! be fiabie in any manner for any erso&nal injury or Prop-rty damoge or a loss of any 5kind arisirng from or onnecyed with this inspa<:ion.

  • Factory .Auta Systems I,

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3072 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 10/31/09 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200333986 (ADDRESS) Repair/Replacement Organization P.O. No., Job No-, etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippincport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date __

4. Identification of System Steam Vent (Class 2)
5. (a) Applicable Construction Code Section III 1974 Edition, S'74 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Check Valve Enertech 11355 N/A 2SVS-81 2005 Corrected Yes

7. Description of Work Replace four flange studs & nuts.
8. Tests Conducted; Hyduostatic* LI Pneumatic* LI Nominal Operating Pressure [i Exempt Z Otherli-] Pressure psi Test Temp. OF_"_,

Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL #A4.414-A FORM'NIS-2 (Back)

9. Remarks NPV-1 Data Report attached to Previous NIS-2 Data Report No. 1783. Replacement 1" Applicable Manufacturer's Data Reports to be attached Studs: PO 45168676 I Ht. #255: Nuts: PO 47048563 / Ht. #M795.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the _ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 13 20 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S-a2-.-L 0 T to -// 7 - 07 , and state that to the best of my knowledge and belief, the Owner-has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor.his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions f 7-- *1W, Inspecto I nature National Board, State, Province, and Endorsements Date 20 / 0

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3078 FORM.NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 10/27/09 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippincport, PA 15077 Work Order #200106774 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol'Stamp N/A (NAME)

ShiDDinooort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Auxiliary Feedwater (Class 3)
5. (a) Applicable Construction Code Section III 1974 Edition, S'74 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corected, ASM[E Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Relief Valve Dresser Ind. TN-39769 N/A 2FWE-RV10 2003 Removed Yes Relief Valve Farris Eng. NC-2658-A14 N/A 2FWE-RV101 2009 Installed Yes

7. Description of Work Replaced relief valve.
8. Tests Conducted: Hydrostatic' E] Pneumatic* L1 Nominal Operating Pressure [ Exempt LI Other L] Pressure psi Test Temp. °_F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Previous NIS-2 Data Report Nb: 1650. Replacement valve Applicable Manufacturer's Data Reports to be attached provided to Section III 1989E-1991A ner ECP 03-010-'063.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White "* ', n Staff Specialist Date January 13 2010 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period s- " to 1- If - '2 7 O , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A-~J,- Inspector's Siýýre L omisin Commissions National Board, State, Province, and Endorsements Date d- 1 250 20 (" 0

Corrected Copy FORM NV-1 CERTIFICATE HOLDER'S DATA REPORT FOR PRESSURE OR VACUUM RELIEF VALVES*

As Required by the Provisions of the ASME Code.Section III, Division 1 Pg. 1 of 2

1. Manufactured and certified by Farris Engineering Division of Curtiss-Wright Flow Control Corporation 15 Shaver Street Brantford, Ontario Canada N3T 5T3 (name and address of NV Cortificate Holder)
2. Manufactured for First Energy Beaver V'alley NPP Route PO Box 6100 Shippingport PA USA 15907 (name and address of Purchaser)
3. Location of installation Beaver Valley Power Station (name and address) 26KA13L-141/S4/SP K Nom. inlet size 3 Outlet size 4
4. Valve Orifice size (modal no. series no.

1989 1991 3 N/A 1989 1991 3 N/A 5- ASME Code,Section III, Division 1 (edition) (addenda date) Mclass) (Code Case no.)

Spring 1430 PSIG N/S PSI 400 *F 2150 PSIG Min. 50 'F

6. Type at (spring, pilot, or power operated) (set pressure) (blowdo- n) (rated temp.) thydro. test, inlet)

NC-2658-A14 27986 REV - N/A 2009

7. Identification (Cert. Holder's serial no)J CRN) Idreii-ng no.) (National Bd. no.) (year built)

S. Control ring settings 8 Notches

9. Pressure retaining items Serial No. or Identification Material Spec., Including Type or Grade Tensile Strength (KSI) ruiNiA SA-216 GRADE WCB Body 70 Bonnet or Yoke M0356 SA-351 GRADE CF8M 70 Support Rods N/A N/A N/A Nozzle G2195-4 SA-351 GRADE CF8M 70 Disk J9t20 51-2-r SA-479 TYPE 316 75 Spring Washers 56352-1-6 56 352-1-7 N/A 75 Adjusting Screws 3730H-gA-32 SA-479 TYPE 316 75 Spindle 728853-1-14 SA-479 TYPE 316 75 Spring 1 9598 A 313 Type 316 STAINLESS STEEL I RFi Bolting 723541 SA-564 GR 630 COND H1100 140 Other Items See Pg. 2
10. Relieving capacity 2004 USGPM WATER C 10% overpressure as certified by the National Board 10/8/2003 (steam or fluid) (datel
11. Remarks L'O~e,,e96YoA) WkAs 7- A02i Aft-iz A~LIJ z;xrI 6C.~OJ PA46; 2 CERTIFICATION OF DESIGN Design Specification certified by Francis W. Gardner R.E. State Pennsylvania Reg. no. 036614-E Design Report certified by Johnson Madukavil R.E.State Ontario Reg. no. 100058089 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this valve conforms to the rules for construction of the ASME Code,Section III, Division 1.

NV Certificate of Authorization No.

N-3061 11/2/2010 D/it ,/ . / Farrs Engineering, A Business Unit Of Curtiss-Wight Flow Control Co.

Date Name (NVCtficte Holder)Signed eauthorizetion representativel

  • Supplemental information in the form of lists, sketches, or drawings may be used provided: (1) size is 811h x 112) information in items 1 through 4 on this Data Report is included on each sheet: and 13)each sheet is numbered and the number of sheets is recorded at the top of this form.

(09/06)

ANQ3.2.5 Rev 3

Corrected Copy FORM NV-1 (Back - Pg. 2. of 2 Certificate Holder's Serial No.,__________ NC-2658-A14 CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of ONTARIO and employed by TECHNICAL STANDARDS AND SAFETY AUTHORITY (TSSA) of ONTARIO have inspected the valve described in this Data Report on ., 240 and state that to the best of my knowledge and belief, the Certificate Holder has constructed this valve in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the cormiponent described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Date A '-0 09 Signed __"_ Commissions DA/3 " A/"/2/ 72 A v

lAuthorized Iy clear Inspector) [Nat'l. Bd. (incl. endorsements) and state or prov. and no.]

9. Pressure retaining items continued:

Soria] No, tf Itteoalcmfiiol )AatlI Som-., ttrchidijng TYO!e Or Grade Hex Nut G8520 SA-194 GRADE 8M FINISHED PART 98 Disc Holder 150307-1-49 SA-479 TYPE 316 BAR 75 Stem Retainer 7396H-2-64 SA-564 GR 630 COND H1100 BAR 140 ANQ3.2.5 Rev 3

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3085 FORM NIS-2 OWNER'S REPORT. FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 12/29/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 -of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinciport, PA 15077 Work Order #200334927 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1974 Edition, S'74 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed. Code Name of Name of Manufacturer National Board Other Year or . Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Duo-Chek Valve Crane Nuclear D2226 N/A 2SWS-106 2003 Removed Yes Duo-Chek Valve Crane Nuclear D3375 N/A 2SWS-106 2004 Installed Yes

7. Description of Work Replaced valve with spare.
8. -Tests Conducted: Hydrostatic* LI Pneumatic* LI Nominal Operating Pressure Z Exempt [IT Other -I Pressure psi Test Temp. _F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Previous NIS-2 Data Report No. 1456.

- . Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF 'COMPLIANCE-I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 18 2010 Onrsesgnee. Titte CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this 2

Owner's Report during the period "-) -, - 0 ? to f- ,5 0  ? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/

i2~;

Inspector's SignaX Commissions J A National Board, State, Province, and Endorsements Date a 20 / 0

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. 1 of 2

1. Manufactured and certified by CRANE Nuclear, Inc., 860 Remington Boulevard, Bolingbrook. IL 60440 (name and address of NPT Certificate Holder)
2. Manufactured for First Energy Corporation, PO Box 345 Shippingport, PA 15077 (name and address of purchiaser)
3. Location of installation Beaver Valley Nuclear Power Plant, Route 168, Shippingport, PA 15077 (name and address)
4. Model No., Series No., or Type 15-SEF-X04 Drawing CB02839 Rev. C CRN N/A
5. ASME Code,Section III, Division 1: 1974 Summer 1974 3 N/A (edition) (addenda date) (class) (Code Case no.)
6. Pump or valve Duo-Chek Valve Nominal inlet size 30 Outlet size 30 (in.) (in.)
7. Material:

(a) valve Body SA216 WCB Bonnet N/A Disk SA216 WCB Bolting SA479 TP 316 (b) pump Casting N/A Cover N/A Bolting N/A (a) (b) (c) (d) (e)

Cert. Nat'l Body/Casing Bonnet/Cover Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

D3375 N/A D3376 N/A D3377 & D3378 Supplemental information in the form of lists, sketches, or drawings may be used provided (1) size is 8 Y2Ax11, (2) information in items 1 through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

This form (EO0037) may be obtained from the Order Dept. ASME. 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.

FORM NPV-1. (Back) --- Pg- 2 of 2 Certificate Holder's Serial No. D3375 8 . Design conditions 200 Psi 300 'F or valve pressure class (1)

(pressure (temperature)

9. Cold working pressure 285 Psi at 100"F
10. Hydrostatic test 450 Psi. Disk differential test pressure 315 Psi
11. Remarks: SO No. 24795-01 Replacement Valve for Tag No.: VCI-01 5-C-3 CERTIFICATION OF DESIGN Design Specifications certified by Walter Joseph Parker, Jr. P.E. State PA Reg. No. 29003-E Design Report certified by N/A P.E. State N/A Reg. No. N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.

N Certificate of Authorization No. N-2899 Expires September 24, 2005 Date 12128/04 Name CRANE Nuclear, Inc. Signed ,

(N Certficate Holder) a i e.s tat Jerome A. Kurowski, PE.

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Illinois and employed by HSBCT of Hartford, CT Have inspected the pump, or valve, described in this Data Report on 12128/04 and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the Component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in anymanner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.

Date 12/28/04 Signed 62)" ommissions IL 1005 (Authoized Nudear inspecor) (Natl. led. Ond. endorsernents) and state or prov. And no.)

Fred Ouvana (1) For manually operated valves only.

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3087 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/05/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS1 Unit No. 2 (NAME)

Shippincport, PA 15077 Work Order #200335041 (ADDRESS) Repair/Replacement Organization P.O. No.. Job No-, etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippincrport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Main Steam (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, S'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Check Valve Enertech 10551 N/A 2MSS-196 1997 Removed Yes Check Valve Enertech 11076 N/A 2MSS-196 2001 Installed Yes

7. Description of Work Replaced valve with spare.
8. Tests Conducted: Hydrostatic* E] Pneumatic* El Nominal Operating Pressure.ZN Exempt L]

Other EL Pressure psi Test Temp. °_F lost tRecord pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks NPV-1 Data Report attached. Previous NIS-2 Data Report No. 1030.

Applicable Manufacturer's Data Reports to be attaihed CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorizatio r.No. EL Expiration Date N/A Signed T. White . Staff Specialist Date January 27 20 10 Ow r or Owner's De*ignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period j- 7d-d- -O0 to /(- * - d F ,and stateth-at to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_nspector__National__oar__Commissions St,,Pvin-' En t inspector's 9! ature National Board, State. Province, and Endorsements Date / - "?, 7 - / 6' 1 20 Date .20 ___

FORM NPV-1 CERTIFICATE HOLDERS" DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code. Section IMI. Division 1 Pg. 1 of 2 I. Manufactured and certified by Enerteh, A Div. of Curtiss-Wright Flow Contcol Corp., 2950 8ir.cd-St. Brea, CA 92821 (name and address of N Cerctlicate Holder)

2. Manufactured for First Energy Corp.; PO. Box.361 1; Akron. OH 44309-3611 (name and address of Purchaser)
3. Location of installation Beaver Valley Power Station; Route 168; Shippingport, PA 15077 (name and address)
4. Model No., Series No., or Type DRV-Z Drawing PD98401 Rev. E CRN None 5: ASME Code, Section Ill, Division 1: 1971 S72 3 None fedition) (addenda date) Idass) (Code Case no.?

Nominal inlet size _ Outlet size 3

6. Pump or. valve Nozzle Check Valve fin.) fin.)

7- Material: Body SA-105 Bonnet N/A Disk SA-479 Type 316 Bolting NIA (a) (b) (cl (dl (el Cert_ Nat'l .Bonnet Disk Body Holders Board Serial Serial Serial Serial No. No. No. No. No.

11075 None KEI-001 None JKT-023 11076 None KEI-002 None JKT-024 C

"Supplemental information in form of lists. sketches, or. drawings may be used provided (1) size is 8 , x 11. 121 information in items 1 through 4 on this Data Report is inciuded on each sheet. (31 each sheetis numbered and the numbec of sheets is recorded at the top of this form.

(121881 This form (E000371 may be obtained from the Order Dept.. ASME. 22 Law Drive. Box 2300. Fairfield. N-1-07007-2300-. - RFtPNT 6/93 C

FORM NPV-1 (B.ck -Pg. 2of j Certificate Holder's Serial.No_ 11075 & 11076 8- Design conditions 1100 psi 560 'F or valve pressure class -.. _ _____ (t Ipressre) lItemperature) 9- Cold working pressure 1440 psi at 100F

10. Hydrostatic test 2175 psi. Disk differential test pressure 1600 psi
11. Remarks: Oty. 2. Enertech Job Number 24628V CERTIFICATION OF DESIGN Design Specification certified by Francis W. Gardne P-E. State PA Reg. no. 036614-E Design Report cerified by Ira J. Silverman P_E. State CA Reg. no- 2324" CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code. Section Ill. Division 1.

N Certificate of Authorization 'No. ExN12s Date - Etech (N CeZ.Naame Signed aut.r 22eestte

-IN Certificate H-older) (authorized representative)

CERTIFICATE OF INSPECTION I, the undersigned, holding, a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of California and employed by Hartford Steam Bailer Insp. & Insur. Go-of ~Coon necticut have inspected the pump. or valve, described in this. Data Report on 4t, and state that to the best of my knowledge and belief. the Certificate Holder has con-sttucted this pump, or valve, in accordance with the ASME Code, Section Iil, Division 1.

By signinrg this certificate, neither the inspector nor his employer makes any-warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable,in any manner for any personal injury or property damage or a loss of any kind arising from or Connected with this inspection.

Date2:,L Signed *Z.ommissions tAuttiorized Inspector) [Nafl_ Bd. f-ind endorse**nts) and state or pr:ov and no.l J1I For manually operated valves only.

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 4G98 30!67 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner FENOC Date 01/25/10 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 3 (ADDRESS)
2. Plant Beaver Vallev Power Station Unit No. 2 (NAME)

Shinninanort. PA 15077 Order # 200023701 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS- Maintenance Type Code Symbol Stamp N/A (NAME)

Shippincport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date N/A

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code ASME Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity: 2001-2003 (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pump Byron Jackson 731-N-0028 N/A 2SWS-P21B 1982 Corrected Yes Bowl Assembly BW/IP 901-W-20046 N/A N/A 1991 Corrected Yes Stuffing Box Flowserve RLSA07407 N/A N/A 2006 Installed Yes

7. Description of Work Repair bowl assembly/pump and install a new stuffing box and bolting
8. Tests Conducted: Hydrostatic* El Pneumatic* [] Nominal Operating Pressure a Exempt [

Other L-- Pressure __ psi Test Temp. °F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV .RTL R # A4.414-A FORM NIS-2 (1Back)

9. -Remarks Previous NIS-2 #402. Rod PO/HT#'s: 45265407/1R76, 452654, Bolting PO/HT#

45246143/8994826, 45254219/251919.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Justin Sciulli Owner of Owne6^*esignee, Title Nuclear Specialist Date January 25 ' 2010 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford. CT have inspected the components described in this Owner's Report during the period J- _,-- .4- - 0 R, to /I - - 0 9 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

. 4ýZa-, ý/- L'y Commissions J-7 /, "1 */

Inspector's Signature National Board, State, Province, and Endorsements 7.

Date- , 2010 2010 Date

FORM NR-1 REPORT OF REPAIR M MODIFICATION [] OR REPLACEMENT Z TO NUCLEAR COMPONENTS AND SYSTEMS IN NUCLEAR POWER PLANTS P.O. 55108299 Vork performed by: Flowserve - Charlotte Nuclear Service Center Job No. CC0084734 (namneof NR certificate holder) (PO No., Job No., etc..)

2801-T Hutchison McDonald Rd., Charlotte, NC 28269 (addresS)

2. Owner: First Energy (namne)

Route 168, Shippingport, PA 15077 (address) -

3. Name, address and identification of nuclear power plant Beaver Valley Nuclear Power Plant Route 168, Shippingport, PA 15077
4. System: Service Water 5a. Items which required Repair, Modification, or Replacement Activities Identification Construction Code Activity Type of Mfg. Mfg. Natl Jurisd Name / Repair /

No Te Itemof Name Serial No. Bd. Other Year Built Section Devtion Edition Addenda Code Case(s) Code Class Rodac No. No. Division ____Replace Byron 731-N- ASME/III/

1 Pump Jackson 0027,28,29 - - 1982 1 1971/W72 N 146-1 3 Repair Bowl 901-W- ASME/II!/

2 Assy BW/IP 0204,5,6,7 - - 1991 1 1971/W72 - 3 Repair 3

4 5

6 9

10 5b. Items installed during Replacement Activities Identification Construction Code Type of Installed or Replaced 3Mfg. Mfg. Nat'l Bd. Jurisd. _____ _________ Yther _________

N m Seton/ Adition Codes Class Item 5a Item No. Name Serial No. No. No. Ohr Built Dieision Adea Cse) Cls ASME/III/

Studs 2. Nova I 1986/none -1 ASME/III/

Nuts 2 Nova -. 1 1986/none- -

6&ASME Code Section XI applicable for inservice inspection: 1989 None (edition) (addenda) (Code Case(s))

7. ASME Code Section XI used for repairs, modifications, or replacements: See Item 12 See Item 12 N-496-2 (edition) (addenda) (CodeCase(s))

-onstruction Code used for repairs, modifications, or replacements: 1971 W1972 N-146-1 (edition) (addenda) (Code Case(s))

9. Design Responsibilities: First Enerqy/Beaver Valley See
10. Tests conducted: hydrostatic 0 pneumatic ED design pressure D pressure -tem12 psi Code Case(s) N-146-1
11. Description of work: Repair and Refurbish COMPDnents Pe2 mp Sof in aaco bdnc wth ore pai Paf 1O tabn Cutm)

Pump Model 32KXH-2 Stage Service Water pump in accordance with Repair Plan for Customer P.O. # 55108299, Change Order 3.

General repairs included pressure boundary weld repairs and NDE with hydrotest. Repairs were performed to restore wall thickness and mechanical fit-up conditions to oriqinal OEM desion requirements.

12. Remarks:
1. Repair scope applies to Item 5a, No.'s 1 and 2 of this document. Note that bowl assembly was replaced in 1991.
2. Item 7 continued: Material and Fabrication per ASME Section III, div.1 1989 Edition, 1996 Addenda.

Pressure testing in accordance with ASME Section III, 1971 Edition, Winter 1972 Addenda.

3. Bowls pressure tested at 225 psi and columns pressure tested at 200 psi.
4. Code NR-1 nameplate attached to Top Case.

CERTIFICATE OF COMPLIANCE I, Jennifer L. McCarthy , certify that to the best of my knowledge and belief the statements in this report are correct and the repairý modification or replacement activities described above conform to Section XI of the ASME Code and the National Board Inspection Code "NR" rules.

National Board-"R" Certificate of Authorization No. NR-88 to use the "NR" stamp expires Feb 18 , 2009 NR Certificate Holder _____ ,__ Flowserve - Charlotte Nuclear Service Center (flame)

Date 10/16/08 Signed . ... '.. Supervisor, QA CERTIFICATE OF INSPECTION I, Charles F. Toegel, Jr. , holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and certificate of competency issued by the jurisdiction of North Carolina and employed by Hartford Steam Boiler of CT of Hartford, CT have inspected the repair, modification or replacement described in this report on 10/16/08 and state that to the best of my knowledge and belief, this repair, modification or replacement activity has been completed in accordance with

'Section XI of the ASME Code and the National Board Inspection Code "NR" rules.

By signing this certificate, neither the undersigned nor my employer makes any warranty, expressed or implied, concerning The work described in this report. Furthermore, neither the undersigned nor my employer shall be liable in any manner for any personal injury, property damage orp losý of any k)nd arig-rm or connected with this inspection.

Date 10/16/08 Signed Commissions NB#8462, NC#1073 (NatimoaI Board (min.endcfsmerents),

3uriscrition anrd No.)

Page 9 of *28)

FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS'AND APPURTENANCES*

As Required by the Provisions of the ASME Code,Section III Not to Exceed One Day's Production Pg= 1 of 2

1. Manufactured and certifiecFitwserve Pump DiVision, Nuclear Products Operation, 2300 E. Vernon Ave., Vernon, CA 90058

. ... (name and address of NPT Certificate Holder)

2. Manufactured for First Energy Corp., P.O. Box 6100, Johnstown, Pennsylvania (name and address of purchaser)
3. Location of installation Beaver Valley Station, Route 168, Shippingport, Pennsylvania (name and address)

.4. Type DWG313206 ASME SA 216 GR. WCB 70 KSI Min. N/A 2006 (drawing no.) - (marl. spec. no.) (tensile strength) (CRN) (year built)

5. ASME Code,Section III, Division 1: 1971 Winter 1972 N146-1 (edi6on) (addenda date) (class) (Code Case no.)
6. Fabricated in accordance with Const. Spec. (Oiv. 2 only) N/A Revision N/A Date N/A (no.)
7. Remarks: " Flnwgerve pfo n " RI'.CAfflO73 Nomenclahire- Stuffing n nx Namenlate attached by tack weld.
8. Nom. thickness (in.) 1.12 Min. design thickness (in.) 1.00 Dia. ID (ft & in.) 10.00 Length overall (ft & in.)" 15.00
9. When applicable, Certific*ate Holders' Data Reports are attached for each item of this report:

National .. National Part or.Appurtenarice Board No. PartSerial or Appurtenance Number Board No.

in . Numerical Order Serial'Number "."-"."........in Nunmerical Order (1) RLSA07407 N/A (26)

(2) (27)

(3) (28)

(4)

(29),,.

(5). (30)

(6) (31)

(7) (32)

(8) (33)

(34)

(10) (35)

(11)

(36)

(12) (37)

(13) (38)

(14) (39)

(15) (40)

(16) (41)

(17) (42)

(18) (43)

(19) (44)

(20) (45)

(21) (46)

(22) (47)

(23), (48)

(24) (491 (25) (50) t.,oj~esign pressure 5"1' psi. Temp. .100 °F. Hydro: test pressure 235 .R 70F at temp. °F (when applic*bte)

Supplemental inforrmation in the form of lists, sketches, or drawings may be used provided (1) size is 81/2 x 11, (2) information in items 2 and 3 on this Data Report is included on each sheet, (3) each sheet is numbered and the number of sheets is recorded at the top of this-form.

(7198) This form (E00040) may be obtained from the Order Dept.. ASME. 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300.

E00040

(Page 10 of 28)

FORM N-2 (Back - Pg.. 2 of 2_

Certificate Holder's Serial Nos. RLSA07407 through* RLSA07407 CERTIFICATION OF DESIGN Roge E. Mati PA 288-Design specifications certified by Rodger E. Marin P.E. State PA Reg. no. 208-E (when applicable)

Design report* certified by Douglas B. Nickerson P.E. State CA Reg. no. 1314 (when applicable)

CERTIFICATE OF COMPLIANCE

.We certify that the statements made in this report are correct and that this (these) Stuffing Boxý

conforms, to .the ules of construction, of the ASME Code, .Section Ill, Division 1.

NPT Certificate of Authorization No.. N-I 131 Expires June 10, 2008 Date 1/25/06 NamCrloiseate Pump Division, OperationSigned (NPIT Cerrtifcata Holder) (5-u~ofked representative.)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the.State or Province of Californ.ia -and employed by .. . HSB-CT " "

of .... Hantford, CT e o have inspected these items described in this Data Report on 1/25/06 .and state that to the of mykowledge mbest and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code,Section III, Division 1. Each part listed has been authorized for stamping on the date shown above.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage loss of any kind arising from or connected with thisi n.

fc 1/25/06 C -A43 CA

. Authorized Nucieaki~ipector) (Nat'l. ad. finci.e ndorsernentsl and state or proe. and no.]

0

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3095 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 10/28/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 3

.(ADDRESS)

2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShiDDninanort. PA 15077 Work Order Nos: 200335124, 200393491 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shio pincqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
6. Identification of Components Corrected, ASMIE Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No., Identification Built Installed (Yes or No)

Check Valve Kerotest EGS-15 7574 2CHS-181 1975 Corrected Yes Disc Flowserve 40 N/A Ht. #143275 1998 Installed Yes

7. Description of Work Replaced disc and seal welded cap to body.
8. Tests Conducted: Hydrostatic* DI Pneumatic* LI Nominal Operating Pressure El Exempt N Other E] Pressure psi Test Temp. OF_.
  • Recr1 test pressure and temperature

FORM-1/2-ADM-0801.02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Reports attached.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE 'OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White 6 *O~ror wne's D~sineeTitle Staff Specialist Date January 18 20 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period _---,2',X -6 W to - - L , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions ,JA' X"ýr F-y, Inspector gnature National Board, State, Province, and Endorsements Date - ' ,20 /'

Foam N-2 NfT CEETIFICATE HOLDER DATA REPORT FOR NuCLEAR PART AND APURTENANCES:

As required by the Provision of the ASME Code Rules. Section IllI. Div. I L (a) Maitscrwedby Flowserve Corp., 701 FirSt Street, Williamsport, PA" 17701 (Manza ow eta= of M" COUR Ha~eiti"~

(b) M,,aulacure.d First Energy Corp. P.O. Box 345 Shipping Port, PA 15077 tun=, an" addrvn of if Cergante Neibr ar eM006d ancaw rie., Csm S/N 40 _ Natl Bd. No. N/A

2. IdentUfiation-Cat~flcalt Holder's Serial No. a rpart NIA (a)Csrcted Accoding to Drawing No. 72609084,Dra pa b Flowserve Corp.

Disc Heat No. 43275 SA479-316 (b) Description of Part Inspected (c) Applicble,AECode.Sectinm, Editio* 1971 ._.. A*d . . CaseNo. Clan 1 I. Roemar2:

B:

mm*zJ*{

2"-1500# Check Ka, (Diri- descr"tKsWQ of eates let whicbh empenet or. de.kmod)

Shop Order No. E031R-2 See BW/IP N-2 Form supplied for Disc Ref. R/S No. 332459 S/N - 40 Ve certify that the statements made in this report ae correct and this vessel part or appurtenance as defined in the Code con-forms to the rules of consruction of the ASME Code Section Ill.

(The applicable Design Specification and Shem Rep*rt are not the responslbllty of the NPT Certificate Holder for parts. An Niqp Certif-icate Holder for apprtemnaces is responsible for furnishing a separate Design Specification and Stress Report if the appurtenanc: is not Included in the component Design Specification and Stres Report.)

Date o E Sires Flowserve Corp. By a mi (NOl' Catdfilewt Holder)

Certificate of Authorization Ezoires 4/15/01 Certificate of. Authorization No. N1713 CERTIFICATION OF DESIGN FOR APPURTENANCE (w"en applicable)

Design informamio oan file at Streas analysia report an file a__

Design specifications certified by Prof. Eng. State_ Reg. No._

Stress analysis report certified by Prof. Eng. *ate, Reg. No.____

CERTIFICATE OF SHOP INSPECTION

1. the undersigned, holding a valid commission issued by the National Board of Boiler and Presstre Vessel Inspectors and/orthe State qriM~gx0of Pennsylvania ande.ployjedby Commercial Union Insurance Compan3 of-. BQst Mash. ahve inspected the part of a pressure vessel described in this Partial Date Report an -) 12 and state that to the best of my knowledge
  • ý19_

.and belief, the NP? Certificate Holder has conswructed this Part In accordance with the ASME Code Section Mi.

By signing this certificate, neither the Inspector nor his employer makes ay warranty, expressed or implied, concern-ing the part described In this Partial Data Report. Furthermore. neither the Inspector nor his emlployer shall be liable in my manner for any peral

'with this inspection,. Kil,"* uinry" or property damage or a loss of any kind arising from or connected Date JUN 3 02000

-w-

--- / Nattmmat Beard. sotat. P'wftar .evd Mo.

1a -n..an

- n tote rh~.M. <st.,

Ii nf Akqt.

.V/' .,nsm so"- -.

.o ...

,ro..d.. 11I) i.at

.. an nc L v1OW s'*.

I 1". (2) L. UnitoII*t.cq . - tt..

7 This form tEO004O) may be obtained from tle Order Dem.. ASME._345 E. 4 t1 St.. New York. N.Y. 10017

FOItM N PV. I hIANU"ACTURIlIYS DA llATA II-AT FOR NII(.II.I-\ II 011 VALV1?5n OI'ItS

~ A* Re,-quired Ly the Provi.sions of ihr ASN" (Code Itule.

2525 Liberty Avenue I. Manu(actured by Kerotest Manufacturing Corp. Pittsburh,_h,. -order jMk& e 6. Addte. or Mlut-civ.er)

P.O. Box 355 No. 5U-O 3 56 7- Manufactured for Westinhopuse Felctric CQrD- Pjttshurr.h. Pa. o,de, (Nme, and Addrrwas)

3. Owner 7D-iip~np .LirW (Lomany 4- Locationto Plat Beaver Valley No. 2 5.XA ,ValveIdentification serial #'s EG5-12. EG5-13. EG5-4, 'Er,51-1c m5--*

(Brief dCh Uck ave. l ra.diioact-F iqip-%

e udli) 2" Check Valve radioactive W1F fluid (a) Drawing No. W-D-9911.-(1) Prepared by H. Dratfinsky Sh. 1 of 1 (b) National Bonrd No. 7571 thru 7575

  • e;sn Cod;j.,a 2580 Pit; 65c. F ' Pressure Class 15 00lh (
7. The iate*wm;I. de1-i&. ,coasruction, and %wrhma*mship complies w*,t A-.ME Code Section I1I. Class Edition 1Q1 *Addenda Date-W-i.nter 9127 Case No.__________________

f tliriN 4t U* . tlS ll* .]4. tlnlllWu Itlmtk (a) cast;n Il

  • /*

I I I I (A) Fo*r",A Lokd UP-2211 I) .... -36 iUns ...r . "

Yoke -UP-9911.-.2-.()-21L..

.A:+* j":if,," fMiA *yl uoperated valIc-%ohlfy:

  • + '.+1#[ n1 n;"... .. ts"La

' o aI ham .hte w 4 w .g a. I ,.c p 'i d(N "

in i 8 Il. (7 1.nIp, i ~

,*++j,,.+.:i...l ,ail #*mii .1Rp#1 . nl nnelmndedli~oem e.ahJ* .himet* and ES .. rck .)aI a.i in '*mland .,.4 n.embt~.- m.f aIel ... tnI.m.~od -1 tel, 4 i.E .r

+ l~.t.

i.ii

FORMW NI'V-1 (back)

)4.k 140. I K.-im sp-c ?a*. IRw.f I- I I (c) Boluinz

4. I I (d) Ot*er Paxts DJISC UVý9911-55--'I (.7 ¶'n :6CrpftEl ~ t1 oe'.

4S Hydt'cuazijc tet .5400 C.ERTI7FICATION OF DESIGN Kerotest Manufacturing Corp.

Desigaf iintanation outiic at Stress sztatysis CePOrt wei file at- Kerotest Manufacturing CorD-1~.z-~n~o.+h T~1uc~p - (1) Prof.Eng. State Pl - Reg. No. 37T28E Stress analysis report ccr.iiied by-, S. J- CaroDeo, (J) Prof. Eng&. State Pa WRrg.*40. O1 I ~E (1)Sipaazrcr -O- sew~d List name We- r-eqtiy thalt idt~ statemuents, msna in &hiswepoct ace coerce c.

Kerotest Date Aupms& 25 - 97 sis.,

Caoeo Ceert~icate o( Aftdioriza~~aao. 90 xpares I0f28fTT CER31IFICATE OF 4.4IOP INSPECTION A. the swAveeipbed. hat.Wg a vadid commuixsiom issued by the NmKeuoaaJ Deard of "Iier man Prigr cs~ juecr

&*o h stote a swva~ of fenosIyjanis ~ facolydb 4 ~ TheWir 17ard ' 1clb r~nncitct of--mm-traa ,ba6&e inspected i).e ejuipme~ae deac*;bed in gihis Dais mae n- sI~

t- 5- j,5

. &"stag ze that to dec beat of my kn ledae Wa4 belief, tue "AnVIsfaetre baa te abls eq, ijb a!4c4rdms~cv wiars the &"icmsheSubm-"ieots of ASMdE Code. Section 1ig.

Ix hiis~ ertit rCAL.-, litxpv"Oe wor 16;s vaployeI mksi2t any wwranr~ty. vxa-cxe4se ow i;npjCd conceern-Al qswpwaval deseiribed ift ths Dus ftqros. F"unhernmoer "edithr the Ulapec~ot nor kit rinploycg "Ial be to~lsag.y mamaci-10 any. PevSO"s imajry or gWOPrety 4-msC erf Ao 109Of 2* &r;nd (SO

0. orf tfcnnctd W.ll.thiks inspeclion.

Dat Auzust 25 .19 7~5 I

I

/I4*1*~~IJ4.A.S. . PIeriftcr a

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3104 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/06/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shi)Dwinaoort. PA 15077 Work Order #200335121 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. N/A-(ADDRESS)

Expiration Date "

4. Identification of System Primary Component Cooling
5. (a) Applicable Construction Code Section III 1974 Edition,- S'74 Addenda, N/A Code Case (b) -Applicable Edition of Section X1 Utilized for Repair/Replacement Activity. 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected. ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve TRW Mission B5666 N/A 2CCP-259 1976 Removed Yes Valve Crane Nuclear D0835 N/A 2CCP-259 2002 Installed Yes

7. Description of Work Replace valve and flange studs & nuts.
8. Tests Conducted: Hydrostatic* E] Pneumatic* LI Nominal Operating Pressure Z Exempt LI Other LI Pressure _ psi Test Temp. o_F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTIL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Reports attached. Replacement 3 /" Studs: PO 45312663 / Ht. #3K21: Nuts:

Applicable Manufacturer's Data Reports to be attached PO 45297098 / Ht. #2X79.

CERTIFICATE OF COMPLIANCE I certify that the statements~rhaide in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. -- J*/A Expiration Date N/A Signed T. White 4n Staff Specialist Date "February 01 ,20 10 Own'eror One' 0 ne, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report duringthe period .5- - d.-.) 01rT to /1 -----'"2- 0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

.z~-~- I ccU~- nspector'1tur Commissions J--- /t/. A, .

National Board. State, Province, and Endorsements Date I -/ -- ,20 /, _

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT*FORNUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. I of 2

1. Manufactured andcertified by CRANE Nuclear, Inc., 860 Remington Boulevard. Bolingbrook, IL 60440 (name and address of NPT Certificate Holder)
2. Manufactured for First Energy Corporation, PO Box 345 Shippingport, PA 15077 (name and address of purdcaser)
3. Location of installation Long Term Storage Facility, Shippingport Hill Road, Shippingport, PA 15077 (name and address)
4. Model No., Series No., or Type K1 5 SEF-X04 Drawing CB02840 Rev. A CRN N/A
5. ASME Code,Section III. Division 1: 1974 Sumrmer 1974 3 N/A (edition) (addenda date) (classl (Code Case no.)
6. Pump or valve Duo-Chek Valve Nominal inlet size 6 Outlet size 6 lin.I (in.)
7. Material:

(a) valve Body SA216 WCB Bonnet N/A Disk SA216 WC8 Bolting SA479 TP 316A (b) pump Casting N/A Cover N/A Bolting N/A (a) (b) (c) (d) (e)

Cert. Nat'l Body/Casing Bonnet/Cover Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

D0835 N/A D0836 N/A D0837 & D0838-Supplemental information in the form of lists, sketches, or drawings may be used provided (1) size is 8 'A x 11, (2) information in items 1 through 4 on

-this Data Report is included on each sheet. (3) each sheet is numbered and tlhe number of sheets is recorded at (the lop of this form.

This form (E00037) may be obtained from the Order Dept. ASME. 22 Law Drive..Box 2300, Fairfield, NJ 07007-2300.

FORM NPV-1 (Back) --- Pg. 2 of 2 Certificate Holder's Serial No. D0835 8 Design conditions 200 Psi 300 °F or valve pressure class ANSI 150 (1)

(pressure (temperature)

9. Cold working pressure 285 Psi at 100"F
10. Hydrostatic test 450* psi. Disk differential test pressure 315 Psi
11. Remarks: P0 No. 7083942, Rev. 0, Item No.#2 S No. 14362-02 Valve ID: VC1 -01 5-A-3 Retaining Pin Retainer Ht. #G4570 CERTIFICATION OF DESIGN Design Specifications certified by Walter Joseph Parker, Jr. P.E. State PA Reg. no. 24003-E Design Report certified by N/A P.E. State N/A Reg. no. N/A

-CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction" of the ASME Code,Section III, Division 1.

N Certificate of Authorization No. N-2899 Expires September 24, 2002 Date 08/29/02 Name CRANE Nuclear, Inc. Signep . :2tK IN Certificate Holder) (authorized representative)

Garrett Petrovich CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of .  : Illinois and employed by Factory Mutual Insurance Company of . Johnston, RI .. have inspected the pump, or valve, described in this Data Report on 08/29/02 and state that to the best of my knowledge and belief, the Certificate Holder has constructed this pump, or valve, in accordance with the ASME Code, Section II1,Division 1.

By signing this certificate,. neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data ReporL Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of any kind arising from or connected with this inspection.

Commissions Date 08/29/02 Signed IL 1077 (Au orized Nuclear Inspector) (Nat'l. d. (incd. endorsements) and stale or pray. andrno.)

) James Bush (1) For manually operated valves only.

FORM 1/2-ADM-0801 .F02 REV 3 RTL # A4.414-A Form No. . . 3105 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 01/14/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shinninnnort PA 15077 Work Order #200336058 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shioninoaort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System - Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Relief Valve Crosby Valve N56963-01-0010 N/A 2RCS-RV551B 1980 Removed Yes Relief Valve Crosby Valve N56963-00-0007 N/A 2RCS-RV551B 1976 Installed Yes

7. Description of Work Replaced valve with spare.

.8. Tests Conducted: Hydrostatic* El Pneumatic* nI Nominal Operating Pressure E Exempt EL Other L1 Pressure psi Test Temp. OF

'Reco'd test pressure and temperature

FORM 112-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Previous NIS-2 Data Report Nos: 1947, 1659, 1204, 1197, Applicable Manufacturer's Data Reports to be attached 1157, 847, 686, 247, 054, 045, 015, and 009. NPV-1 Data Report attached to NIS-2 Report #202.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the.ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed . T. White Staff Specialist Date January 28 20 10 Owner o" Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period d- - a to // -* "? - a ,Y , and state that to the best of my knowledge and belief, the Owner has performed-examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

e9J.2I ,-tur!

Inspector's i Commissions -,1 7/ 4,j-., ry National Board, State, Province, and Endorsements ure Date / - 1 2200 / G

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3106 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShiDDinaoort. PA 15077 Work Order #200331527 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shipping port, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Reactor Coolant (Class 1)
5. (a). Applicable Construction Code Section III 1977 Edition, S'79 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Power Relief Valve Garrett Pneumatic P-1 19 N/A 2RCS-PCV456 1983 Corrected Yes Plug Anderson N96012-82-0159 N/A N/A 2007 Installed Yes Greenwood Crosby

7. Description of Work Replaced plug.
8. Tests Conducted: Hydrostatic* E] Pneumatic* El Nominal Operating Pressure LI Exempt [

Other EL Pressure psi Test Temp. __ o_F Re*deo test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL R # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Previous NIS-2 Data Report No: 1995, 1660, 1441, 1195, Applicable Manufacturer's Data Reports to be attached 1042 (NPV-1 attached), 802, 539. 360. 090.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Ow*'

or *e~ signee, Title Staff Specialist Date January 14 20 10 I

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period d-- T to / ( - 2;2 06, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

'-C, - ý I,/ Commissions L 4, /"-,3 -

Inspector's , tre National Board, State, Province, and Endorsements Date , 20 /0 Date .20 70

Page 3 of 19)

Q.C.-392 Sheet I of 2 FORM N-2 CERTIFICATE HOLDERS' DATA REPORT FOR IDENTICAL NUCLEAR PARTS AND APPURTENANCES*

As required by the Provisions of the ASME Code, Section IMl, Division I - Not to Exceed One Day's Production

1. Manufactured and certified by Anderson Greeiiwood Crosby, 43 Kendrick St., Wrentham, MA 02093 (Name and Address of N Certificate Holder)
2. Manufactured for FIRST ENERGY CORP._________

(Name and Address of Purchaser or Owner)

3. Location of Installation BEAVER VALLEY NUCLEAR POWER PLANT
  • .(Name and Address)
4. Type DS-C-67970-13 REV.] ASME SA479 TYPE 316 75,000 -_20W7 (drawing no.) (mat'l. spec. no.) (tensile strength) (CRN) (year built)
5. ASME Code, Section UT, Division 1! 1977 S79 I N/A (edition) (addenda date) (class) (Code Case No.)
6. Fabricated in accordance with Const. Spec. (Div. 2 only) - Revision - Date --
7. Re k(no.)
7. Remarks . . ...
8. Norm. thickness (in.) - Min. design thickness (in.),:.. `- - Dia. ID (ft & in-) - Length overall (ft & in.)

9- When aDDlicable. Certificate Holders' data reports are attachd for each item of this report.

Part or Appurtenance National Partaor Appurtenance 'National Serial Number Board No. Serial Number Board No.

in Numerical Order in Numerical Order (1) N96012-82-0159 (26)1 (2) (*7).

(3) (28)

(4)

_ _....._ ." (2 91).

(5) (30)

(6) "(31)

(7) "_:. (32) '

(8) .- (33).

(9) *;-?.(-34.)-.

(10)

(11)

(12) (38) ..

(13)

(14) (39)

(15) _ .(40)

(16) (41)

(17) .- .__ (42) .

(18) .__ .__

_ ._ (43)

(19) ,. (44) .

(20) __  :.(4 (21) ___._._.(47)

(22)

(23) ____________ (49)..

(24) (...)

(25)

10. Design pressure - psi. - Temp. - F Hydro. test pressure 6125 PSIG at temp. 70 (when applicable)

Supplemantal4nirrmaton in the form of lists, sktdwa, or drawings may be used pmovidd (1) size is 8-1/2 xI1, (2) oformalonin i ns 2 and3 tis Data Is IIEZ-deWon car.h sheet, (3) eada s.*ee is mnmbered and td nmber of sheetnis recorded at di. topof dais form.

"htis form (.)0040) may be obtained fr'o th; OrrDept, ASME. 22 Law Drive, Box 2300, Fairfield, NJ U7ID-2300

(Page 4 of 19)

Q.C.-392 Form N-2 (Back) Sheet 2 of 2 Certificate Holder' k [o N o12-82-0159 CERTIFICATE OFDESIGN Design specifications certified by L. IKE EZEKOYE P.E. State PA Reg. no- 18379-E (when applicable)

Design report* certified by W. D. GREENLAW P.E. State MA Reg. no. 14784 (when applicable)

CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct an*d- that "this (these) Plug conforms to the rules of construction of the ASME Code,Section II,"Division I.

NPT Certificate of Authorization No. N-1877 Expis9 . SSept. 30,2007 Anderson -Greenwood Crosby Date 14- 1569 -o.p7 Signed Wrentham,..MA by T ,> fta -

(NPT Certificate Holder) (Authorize-Representative)

CER77FICATE OF.NSPECTION I, the undersigned, holding a valid commission issued.by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of MA and emplbyed by "

-" B-CT of Hartford-CT have inspected these items described in this Data Report on

_____/___ ,_200.)7 and state that to the best'of my knowledge and belief, the Certificate Holder has fabricated these parts or appurtenances in accordance with the ASME Code,Section III, Division 1. Each part listed has been authorized for stamping on the date shown above. -

By signing this certificate, neither the-Impector nor his employer makes any warranty, expressed or implied, concerning the equipment described in this Data Report. Furtliermore., ieither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or loss of. any kind arising from or connected with this inspection.

Date I ,200~

Signed Commissions MA - 1420 A. N. I.

a..- -.CN4t'l. Bd. (ind. endorsemients) and state or prov. and no.)

[/Authorized Inspector)

FORM 1/2-ADM-0801LF02 REV 3 RTL # A4.414-A Form No. 3116 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/03/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 2

,(ADDRESS)

2. Plant Beaver V6l*v6VF Station (BVPS) Unit No. 2 (NAME)

Shirminaoort. PA 15077 Work Order #200328341 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section 1II 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected,. ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped C6mponent Manufacturer Serial No. No- Identification Built Installed (Yes or No)

Valve Kerotest Mfg. QAP4-18 N/A 2RCS-45 1982 Removed Yes Valve Enertech 11808 N/A 2RCS-45 2009 . Installed Yes

7. Description of Work Replaced valve and pipe.
8. Tests Conducted: Hydrostatic* L] Pneumatic*'[ Nominat Operating Pressure M Exempt []

Other LI Pressure psi Test Temp. oF Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks NPV-1 Data Report attached. Previous NIS-2 Data Report Nos: 086, and 022.

Applicable Manufacturer's Data Reports to be attached Replacement 2" Pipe: PO 45213729 / Ht. #037046.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed- T. White Staff Specialist Date January 11, 20 10

,gnee,Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period ,'- d.,A -0 - to // -,*. 7 - (0 7 , and state that to the best.of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector hor his employer.

shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

xjý J - Commissions * ' ,

Inspector's :ýMure National Board, State, Province, and Endorsements Date /- f,?- 20 2 /0)

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code, Section 111, Division 1 Pg. 1 of 2

1. Manufactured and certified by Enertech, A Div. of Curtiss-Wright Flow Control Corp.; 2950 Birch St.; Brea, CA 92821 (name and address of N Certificate Holder)
2. Manufactured for First Energy Corp.; P.O. Box 6100; Johnstown, PA 15907-6100 (name and address of Purchaser)
3. Location of installation Beaver Valley Power Station; Route'168; Shippingport, PA 15077

- (Anameand address)

CLAMPSEA BELLOWS .. e . C

4. Model No., Series No., or Type SEAL Drawing MD22791 Rev. CRN None
5. ASME Code,Section III, Division 1: 1989 NO 1 N-62-7 & N-452 (edition) (addenda date) (class) (Code Case no.)
6. Pump or valve Globe Valve Nominal inlet size 2 Outlet size 2

... SA479 .. Jin.) SA479 (in.)

7. Material: Body SA182 F316 Bonnet UNS-S20910 Disk UNS-S21800 Bolting N/A (a) (b) (c) (d) (e)

Cert. Nat'l Body Bonnet Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

11803 None 09_50-2 09-78-1 09-80-9 11805 None 09-50-4 09-78-3 09-80-5 11806 None 09ý50-5 09-78-9 09-80-4 11807 None 09-50-7 09-78-7 09-80-2,'

11808 None 09-50-8 09-78-8 09-80-3 "I .-.

Supplemental information in form of lists, sketches, or drawings may be used provided (1) size is 8Y X 11, (2) information in items I through 4 on this Data Report is included on each sheet, (3) each sheet Is numbered and the numbmeeoftsh',t1'ls recorded at the top of this formn.

(12/88) This form (E00037) may be obtained from the Order Dept., ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300. REPRINT 6/93

NPV-1 (Back - Pg. 2 of 2 1

  • ~~~1FORM* ..... 180.3, ý11805 Certificate Holder's Serial No. thru 11808
8. Design conditions p2500 si .650 F orvalve pressure class 1700 (1)

(pressure) (temperature) 4080

9. Cold working pressure 4080 psi at 100 0 F
10. Hydrostatic test p6125 si Disk differential test pressure N/A
11. Remarks: Qty. 5, Enertech Project Number 520118..

Yoke Material - SA182 F316, SINs: 09-176-1, 09-176-3, 09-176-4, 09-176-6, 09-176-7 CERTIFICATION OIF DESIGN

-Design--Specification-certified-by -. . Francis W . Gardiner ...-- P;E.-State ---. - ---.--........ Re--no. .... 03.6_6__4-E ...

Design Report certified by Ira J, Silverman P.E. State CA Reg. no. 23241 S. : CERTIFICATE.OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.

N Authorization Certificate of -

No.. ~~N-2826 - xOctober1,21 Ex 2011 Date i - " Enertech, A Div. of Curtiss-Wright Flow Date "Name Control Holder)

IN Certificate Corp. Signed (authorized representative)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of _and California employed by HSB CT of " . Connecticut have inspected-the pump, or valve, described in this Data Report on

. 1!(31c!(-*n- , and state that to the best of my knowledge and belief, the Certificate Holder has con-structed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthe r)6?, neither the inspector norhis employer shall be liable in any manner for any personal injury or property darage or a I a yakind arising from or connected With this inspection. ""

Date t Signed Commissions r aog . (Authorized In~lactor) * [Nat'l. Bd. (incl. endorsements) and state or prov. and no.]

(1) For manually operated valves only.

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3117 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/05/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 *of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShiopinQcort, PA 15077 Work Order #200337513 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System . Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section X1 Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
6. Identification of Components Corrected, ASME Rtemoved, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest Mfg. QAP4-23 N/A 2RCS-46 1982 Removed Yes Valve Enertech 11806 N/A 2RCS-46 2009 Installed Yes

7. Description of Work Replaced valve and pipe.
8. Tests Conducted: Hydrostatic* El Pneumatic* E] Nominal Operating Pressure [ Exempt []

Other E] Pressure psi Test Temp. °F

'ecord test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks NPV-1 Data Report attached. -Previous NIS-2 Data Report Nos: 087, and 041

-Applicable Manufacturer's Data Reports to be attached Renlacement 2" Pipe: 10 47244224 / Ht_ #38884.

Replacement 2" Pipe: PO 47244224 / Ht #38884.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A 'Expiration Date . N/A Signed T. White Date January 11, 20 10 Ownbr or Owner's ifesignee, Title Staff Snecialist CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this

-Owner's Report during the period j*"-Z. 0 2., -0 7 to -,7-. 7 - 0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described. in this Owner's:Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

r Commissions ZI-7 'J, / Z3 -Y' Inspector's Si:gf National Board, State, Province, and Endorsements Date 1 20 _/10

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME- Code,Section III. Division I

...Pg. of. 2

1. Manufactured and certified by Enertech, A Div. of Curtiss-Wright Flow Control Corp.; 2950 Birch St.; Brea, CA 92821 (name and address of N Certificate Holder) "
2. Manufactured for First Energy Corp.; P.O. Box 6100; Johnstown, PA 15907-6100 7 (name and addressof Purchaser)
3. Location of installation Beaver Valley Power Station; Route 168; Shippingport, PA 15077 (name and address)

CLAMPSEALBELLOWS

4. Model No., Series No., or Type -SEAL Drawing MD22791 Rev. C CRN None
5. ASME Code,Section III, Division 1: 1989 NO 1 N-62-7 & N-452 (edition) (addenda date) (class) (Code Case no.)

6'. Pump or valve Globe Valve Nominal inlet size 2 Outlet size 2 SA479 (in.) SA479 (in.)

7

7. Material: Body ~SA182 F316F316 Bonnet UNS-S20910 Disk UNS-S21800 Bolting N/A N/A______

(a) (b) (c) (d) (e)

Cert. Nat'l Body Bonnet Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

11803 None 09-50-2 09-78-A 09-80-9 11805 None 09-50-4 09-78-3 09-80-5 11806 None 09-50-5 09-78-9 09-80-4 11807 None 09-50-7 09-78-7 09-80-2 11808 None 09-50-8 09-78-8 09-80-3 Supplernrantal information in form of lists, sketches, or drawings may be used provided (1) size is a8Y.x 11, 12) infoirmation in items I through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this forkn.

(12/88) This form (E0D0037) may be obtained from the Order Dept.. ASME. 22 Law Drive. Box 2300. Fairfield, NJ 07007-2300. REPRINT 6193

FORM NPV-1 (Back -. Pg.'2of 2 0 11803, 11805.,

Certificate Holder's Serial No.ý thru 11808

8. Design conditions 2500 psi 650 OF or valve pressure class 1700 )

.(pressure) (temperature)

9. Cold working pressure 4080 psi at 100 0 F
10. Hydrostatic test 6125. psi. Disk differential test pressure N/A psi
11. Remarks: Qty._5, Enertech Project Number 520118 __

Yoke Material - SA182 F316, SINs: 09-176-1, 09-176-3, 09-176-4, 09-176-6, 09-176-7 CERTIFICATION OF DESIGN Design:Specification certified by FrancJs .W..Gardner ':P.E. State -..... PA Reg. no- .03661+/-4:E....

Design Report certified by Ira J, Silverman P.E. State CA Beg. no. 23241 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division-1. -

N Certificate of Authorization No. N-2826 Ex October 11, 2011 Enertech, A Div. of Curtiss-Wright Flow Date Name Control Corp. Signed IN Certificate Holder) (authorized representative)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of California and employed by HSB CT of Connecticut have inspected the pump, or valve, described in this Data Report on

.* and state that to the best of my knowledge and belief, the Certificate Holder has con-structed this pump, or valve, in accordance with the ASME Code, Section IlIl, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthe/6, neither the inspector nor his employer shall be liable in any manner for any personal injury or property dargaoe ora fary kind arising from or connected with this inspection.

Date S "gned i Zu ntor)I Commissions CA 0n.5n.

(Autoie Bd. (inc. endorsements) end state or prov. and no.)

[npctrNat'l.

(1) For manually operate'd valves only.

FORM 1/2-ADM-0801 .F02 REV 3 RTL # A4.414-A Form No. 3118 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant . Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200147365 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shin pinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest HWI-25 6472 2CHS-184 1975 Removed Yes Valve Enertech 11807 N/A 2CHS-184 2009 Installed Yes

7. Description of Work Replaced valve & pipe.
8. Tests Conducted: Hydrostatic* D Pneumatic* E] Nominal Operating Pressure M Exempt E]

Other 0]... Pressure psi Test Temp. oF

  • Record test pressure and temperature

FORM 1/2-ADM-0801F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Replacement 2" Pipe: PO 45213729 / Ht. #037046.

Applicable Manufacturer's Data Reports to be attached -

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 25 20 10 S&Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission-issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period .5-- _-Z-L - 0 Z' to / / -- , 7 - 0 ? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

lnspector':rure Commissions /-

,A/i K X'3 9-,(r National Beard, State. Province, and Endorsements Date -/- , 20 /0O

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code, Section 111,Division 1 Pg. I of 2

1. Manufactured and certified by Enertech, A Div. of Curtiss-Wright Flow Control Corp.; 2950 Birch St.; Brea, CA 92821 (name and address of N Certificate Holder)
2. Manufactured for First Energy Corp.; P.O. Box 6100; Johnstown, PA 15907-6100 (name and address of Purchaser)
3. Location of installation Beaver Valley Power Station; Route 168; Shippingport, PA 15077 (name and address) cLMPSEA BELLOWS MD22791 C None
4. Model No., Series No., or Type SEAL Drawing Rev. CRN
5. ASME Code,Section III, Division 1: 1989 NO 1 N-62-7 & N-452 (edition) (addenda datel (class) (Code Case no.)
6. Pump or valve Globe Valve Nominal inlet size 2 Outlet size 2 SA479 (in.) SA479 (in.)
7. Material: Body SA182 F316 Bonnet UNS-S20910 Disk UNS-S21800 Bolting N/A (a) (b) (c) (d) (e)

Cert. Nat'l Body Bonnet Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

1.1803 None 09-50-2 09-78-1 09-80-9 11805 None 09-50-4 09-78-3 09-80-5 11806 None 09-50-5 09-78-9 09-80-4 11807 None 09-50-7 09-78-7 09-80-2 11808 None 09-50-8 09-78-8 09-80-3 Supplemental information in form of lists, sketches, or drawings may be used provided (1) size is 8 % x 11, (2) information in items 1 through 4 on this Data Report is included on each sheet. (3) each sheet is numbered and the number of sheets is recorded at the top of this forkn.

(12/88) This form (EO0037) may be obtained from the Order Dept.. ASME, 22 Law Drive, Box 2300, Fairfield" NJ 07007-2300. REPRINT 6/93

FORM NPV-1 (Back - Pa. 2 of_2__

11803, 11805 Certificate Holder's Serial No. thru 11808

8. Design conditions 2500 psi 650 *F or valve preiii~wda&iass. -A*..Q:

(pressure) (temperature)

9. Cold working pressure 4080 psi at 1009 F
10. Hydrostatic test 6125 psi. Disk differential test pressure N(A psi
11. Remarks: Qty. 5, Enertech Project Number 520118 Yoke Material - SA182 F316, S/Ns: 09-176-1, 09-176-3. 09-176-4, 09-176-6,-09-176-7 CERTIFICATION OF DESIGN

- Design Specification certified by Francis W. Gardner P.E. State ....... A . Reg. no. 03661_4-E.

Design Report certified by Ira J, Silverman P.E. State CA Reg. no. 23241 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division-1.

N Certificate of Authorization No. N-2826 _October'11, 2011 Date DateNameEnertech,

.-Name A Div. of Curtiss-Wright Control Corp-. Flow Signed IN Certificate Holder) (authorized representative)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or'Province of California and employed by HSB CT of Connecticut have inspected the pump, or valve, described in this Data Report on

  • 119!U92%\ . and state that to the best of my knowledge and belief, the Certificate Holder has con-structed this pump, or valve, in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Date Report. Furthe4K-?, neither the inspector nor his employer shall be liable in any manner for any personal injury or property da rage ora ?/ ,farfy kind arising from or connected with this inspection.

Date - / Signed Commissions a 0

£5* I lAuthorized In(ctor (Nat'l. Bd. (incl. endorsements) and state or prov. and no.]

(1) For manually operated valves only.

FORM 1/2-ADM-0801LF02 REV 3 RTL 4 A4.414-A Form No. 3119

.-FORM NIS-2 OWNER'S -REPORT FOR REPAIRS/REPLACEMENT-ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 11/03/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPSI Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200322713 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3 . Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippincqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. Noo Identification Built Installed (Yes or No)

Valve Kerotest Mfg. QAP4-8 N/A 2RCS-44 1982 Removed Yes Valve Enertech 11805 N/A 2RCS-44 2009 Installed Yes

7. Description of Work Replaced valve and pipe.
8. Tests-Conducted.-,-.; Hydrostatic* LI Prreumatic* LI Nominal Operating Pressure [ Exempt LI Other 0 . Pressure - psi Test Temp. F Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 .RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks NPV-1 Data Report attached. Previous NIS-2 Data Report Nos: 3042, 085. and 040.

"ApplicableManufacturer's Data Reports to be attached Reolacement 2" Pioe: PO 47244224 / Ht. #038884.

CERTIFICATE OF COMPLIANCE I certify.that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White -gnee, Staff Specialist 'Date January 11, 20 10 4 0=rOwnr' Dsiignee, Title

,l CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the 'National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period "-f- .L - a 7 to 7 * , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions ,'-4

/,,,J ý-,3 (7 lnspectýZgrrature National Board. State, Province, and Endbirserents Date , 20 /-

FORM NPV-1 CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code, Section iIl, Division 1

- .2

1. Manufactured and certified by Enertech, A Div. of Curtiss-Wright Flow Control Corp.; 2950 Birch St.; Brea, CA 92821 (name and address of N Certificate Holder)
2. Manufactured for First Energy Corp.; P.O. Box 6100; Johnstown, PA .15907-6100 (name and address of Purchaser)
3. Location of installation Beaver Valley Power Station; Route 168; Shippingport, PA 15077 (name and address)
4. Model No., Series No., or Type CLAMPSEA BELOWSMD29

-SEAL Drawing MD22791 Rev. CNn C CRN None

5. ASME Code,Section III, Division 1: 1989 NO 1 N-62-7 & N-452 (edition) (addenda date) (class) (Code Case no.)
6. Pump orvalve Globe Valve Nominal inlet size 2 Outlet size 2 SA479 (in.) SA479 (in.)
7. Material: Body SA182 F316 Bonnet UNS-S20910 Disk UNS-S21800 Bolting N/A (a). (b) (c) (dl (e)

Cert. Nat'l Body Bonnet Disk Holder's Board Serial Serial Serial Serial No.: No. No. No. No.

11803 None 09-50-2 09-78-- 09-80-9 11-805 None 09-50-4 09-78-3 09-80-5.

11806 None 09-50-5 09-78-9 09-80-4 11807 None 09-50-7 09-78-7 09-80-2 11808 None 09-50-8 09-78-8 09-80-3 Supplemental information in form of lists. sketches, or drawings may be used provided (I) size is BY. x 11, 12) information-in items 1 through 4 on this Data Report is included on each sheet, (3) each sheet Is numbered and the number of sheets is recorded at the top of this forTh.

(12/88) This form (E00037) may be obtained from the Order Dept.. ASME, 22 Law Drive, Box 2300, Fairfield, NJ 07007-2300. REPRINT 6/93

FORM NPV-I ,(Back - Pg. 2 of 2 11803, 11805

  • " .'* " ..... .:," ' " ... *":- ':..... .*;:-thru"11808 Certificate Holder's Serial No.

-8. De'sign conditions 2500 psi 650 'F or valve pressure class 1700 (1)

  • (pressurei {temperature)
9. Cold working pressure 4080 psi at 100F
10. Hydrostatic test 6125 psi. Disk differential test pressure psi
11. Remarks: Qty. 5, Enertech Project Number 520118 Yoke Material - SA182 F316, SINs: 09-176-1, 09-176-3, 09-176-4, 09-176-6, 09-176-7 CERTIFICATION OF DESIGN

-Design-Specification.certified by .- P. E.-rancis.WGardner State -- PA .- Reg: no. 3 Design Report certified-by Ira J, Silverman P.E. State CA Reg. no. 23241 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for 'construction of the.ASMEICode,Section III,--Division--I. - .-.

NCertificateof Authorization No. N-2826 Ex October 11, 2011 D Ene:tech, A Div. of Curtiss-Wright Flow pale Name Control Corp. Signed (N Certificate Holder) (authoriled representative)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of California and employed by HSB CT of Connecticut have inspected the pump, or valve, described in this Data Report on

-"andstate that to the best of my knowledge and belief, the Certificate Holder has con-structed this.pump, or valve, in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. FurtheA9 6?*, neither the inspector nor his employer shall be liable in any manner for any personal injury or property da age or a I ary kind arising from or connected with this inspection.

Date Signed . W,=

L. 1Y I"Commissions CA ?_ O5 (

(Authorized Inspectorl [Nat'l. Bd. (incl. endorsements) and state or prov. and no.]

(1) For manually operated valves only.

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3120 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/09/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippinciport, PA 15077 Work Order #200349704 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc,

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

ShiDDinaoDort. PA 15077 Authorization No. N/A.

(ADDRESS)

Expiration -Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity. 2001 E-2003A (c) Applicable Section XI Code Case(s):
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-53 1978" Removed Yes

7. Description of Work Removed valve and capped pipe nipple.
8. Tests Conducted: Hydrostatic-* D Pneumatic* E] Nominal Operating Pressure Z Exempt L]

Other L] Pressure psi Test Temp. o_F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 .RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement /" pipe Cap: PO 45310710 Ht. # 4213888; 3/4 Applicable Manufacturers Data Reports to be attached Pipe: PO 7116897 / Ht. 448980. Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White -*

  • Staff Specialist Date January 19 20 10 rorOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J-,7. - 0 7" to / - 7 - 0 ? ', and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions /.-J, A /, d- 9' Inspec r ignature .Natidnal Board, Stat6, Province, and Endorsements Date 20 /()

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3121 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 11/09/09 (NAME) 76 South Main Street-Akron. OH 44308 Sheet 1 of .1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shiooinaoort, PA 15077 Work Order #200349700 (ADDRESS) Repair/Replacernent Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section 1l1 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s):
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-26 1978" Removed . Yes

7. Description of Work Removed valve and installed pipe and cap.
8. Tests Conducted: Hydrostatic* LI Pneumatic* E] Nominal Ope~ating Pressure M Exempt []

Other E] Pressure .. _psi Test Temp. OF

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement 3/." pipe Cap: PO 45310710 I Ht. # 421388; 1/."

Applicable Manufacturer's Data Reports to be attached Pipe: PO 7116897 / Ht. 448980. Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. -W Expiration Date N/A Signed T. White Staff Specialist Date January19 2010 Ownrf'~or One-r's Dlt nee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of -

Hartford, CT have inspected the components described in this Owner's Report during the period ,--2Z_ - 0_ to / / - "D and state that to the best of my-knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

__CCommissions d,, A4

/ d,& r*

Inspetor's i~ture National Board. State, Province, and Endorsements Date 20 /

1 20/0 C)

Date

FORM 1/2-ADM-0801.F02 REV 3 RTL 4 A4.414-A Form No. 3122 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/09/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shiocinooort. PA 15077 Work Order #200349701 (ADDRESS) Repair/Replacement Organization P.O. No., Job No-, etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shipninoport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s):
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year . or Stamped Component Mh'eoThaier"*' Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest --- 2RCS-12 1978" Removed Yes

7. Description of Work Removed valve and installed new pipe and cap.
8. Tests Conducted: Hydrostatic* LI Pneumatic* LI Nominal Operating Pressure M Exempt E]

Oiher EL Pressure psi Test Temp. _ OF "Remrd test pressure afndiem'erature

FORM I/2-ADM-080I.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement /" pipe Cap: PO 45310710 / Ht. # 421388; 3/4" Applicable Manufacturer's Data Reports to be attached Pipe: PG 7116897 / Ht. 448980. Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. 4 Expiration Date N/A Signed T. White Staff Specialist Date January 19 , 2010 Ownar"or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the-period -f L--- 0 - to 1//- 1 7 - ( Y-, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions i'-/ ,

lnspectoýýgSfnature National.Board, State, Province, and Endorsements Date 1 20 /' '3 Date 20 7 0

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3123 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/09/09 (NAME).

76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)

2. Plant Beaver Valley Power Station (BVPS) Unit No. .2 (NAME)

Shippingport, PA 15077 Work Order #200349705 (ADDRESS) RepairlReplacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section 1II 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xi Code Case(s):
6. Identification of Components Corrected. ASMAE Removed, Code.

Name of Name-of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-58 1978" Removed Yes

7. Description of Work Removed valve and installed pipe and cap.
8. Tests (Conducted: Hydrostatic* ] Pneumatic* ] Nominal Operating Pressure []. Exempt [

Other [i Pressure psi Test Temp. _ OF

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement /4"pipe Cap: PO 45310710 / Ht. # 421388: 3/4" Applicable Manufacturer's Data Reports to be attached Pine: P0 71 16897 / Htf 448980. Serial number of removed valve was not recorded. *Year "in ePe..d. . . . . . . . . . ... . . ... .. . ..... .. ..... . . . . ..... . . . . . .. . .. . .. . . . . . .. . . .. ...

-installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. Expiration Date N/A Sinnend T White Staff Snrp.niali.ft Date January 19 , 2010

- Own'ýr O~wner's Designee, Titte I

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period - to - " 7 - 0  ? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Boar4St. Pro c,aE r/

Inspector's 5ign1* National Board State, Province, and Endorsements Date S,20 //'

-FORM 1/2-ADM-0801.F02 RErV3 .....

RTL # A4.414-A Form No. 3124 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 11109/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of .1.

(ADDRESS)

.2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200349703 (ADDRESS) RepairlReplacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stanmped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest --- 2RCS-66 1978" Removed Yes

7. Description of Work Removed valve and installed pipe and cap.
8. Tests Conducted: Hydrostatic* LI Pneumatic* L] Nominal Operating Pressure [ Exempt El Other [i Pressure _ psi Test Temp. oF R lost pressure and temperature ecord

FORM -1/2-ADM-0801 :F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. .Remarks No Data Report available. Replacement Y" pipe Cap: PO 45310710 / Ht. # 421388: 3/4 Applicable Manufacturer's Data Reports to be attached Pipe: PO 7116897 / Ht. 448980 Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the-National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 3-2.7 * -O r to // -,,2- 2 - 0 F, and state that to.the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, exp.ressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions ,J ,6 -)---- -/

,-,).

Inspector's Si76re Nationil Board, State, Province, and Endorsements Date ' 1 20 / ()

Date ,20 /0

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3125 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/09/09 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinciport, PA 15077 Work Order #200349702 (ADDRESS) Repair/Replacement Organization P.O. No. Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shinninonort PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section Il1 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed. Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-38 19780 Removed Yes

7. Description of Work Removed valve and installed pipe and cap.
8. Tests Conducted: Hydrostatic* [ Pneumatic* LI Nominal Operating Pressure Z Exempt L]

Other L1 Pressure psi Test Temp. OF

'Record test pressure and temperature

FORM i/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement Y" pipe Cap: PO 45310710 / Ht. # 421388; M/"

Applicable Manufacturer's Data Reports to be attached PiDe: PO 7116897 / Ht. 448980_ Serial number of removed valve was not recorded_ *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. -W Expiration Date N/A Sinne~d T White' 5Thaff g npci~tli.t Date January 22 , 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period . - 0 to // - - 0 F , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the inspector nor~his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

In__o__S___raoaor___tPovnen__dreetCommissions a, ,oar- //t - ors Inspector's 5ý atr National Board, State, Province, and Endorsements Date 1 20 /0 Date ,20 /0

FORM 1/2-ADM-0801.F02 REM 3 RTL # A4.414-A Form No. 3127 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.NO.C Date 10/30/2009 (NAME) 76 South Main Street -Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS'I Unit No. 2 (NAME)

Shippinciport, PA 15077 Work Order #200023408 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shinninonort PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Main Steam (Class 2)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Seriat No. No. Identification Built Installed (Yes or No)

Valve Kerotest FAH13-24 N/A RMSS-165 1981 Removed Yes

7. Description of Work Removed valve, pipe and elbow and installed cap.
8. Tests Conducted: Hydrostatic*D-] Pneumatic* LI Nominal Operating Pressure Z Exempt F1 Other F-1 Pressure psi Test Temp. OF Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL #A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Replacement 1-1/2.' pipe Cap: PO 45186379 / Ht. # 9122.

Applicable Manufacturers Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. LA Expiration Date N/A Signed T. White Staff Specialist Date January 26 20 10 Owvner ol*)wner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J,'- 2_-) -0 T to I/'- 2 7 -  ? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

J,_ý J. Zky" lnspector1'ýýfature Commissions -4 ,-. z*-V National Board, State, Province, and Endorsements Date S,20 /0

FORM4 NPV-1 -N CERTIFICATE- HOLDERS' DATA. REPORT FOR NUJCLEAR PUMPS OR VALVES-As Rtequired by the Provisionas of the ASME Code.-Seclion fit. Div. 1 *1 of 1, Mw-wf~vactured by ICEQ CEI 't-b1r-Rfnci nu Con .I 6t6 ¶5 1 ter 12 (Name and AddreSS 01 N Cer ifliCate Holder)

&. 0Asifaclured1 for Stn ký WL\(.t'OP I Bxmnaoston, NkissiwhLISCttS (210)7 Wanme and Address. of Pu-crwaser wownta,~,

3- toalo ofis allo lic-nvc~r V~d11_V. Fowcer Stzitioi 12idt 2.Shippirntu-xort, PA fName aftd Addresvl A. Purnmt or Va~ valve .Nominal Inlet Size 1 /2Outlet Size______

fintb) (inch)

(a) Mode: No., (b) N Certificate Holder's WcCanadian serits No~. Serial Registration (dj Drawing Mf Nat'l. (gI Year So! Typ~e No. No. No. (e) Class Bd. No. built

-43) mT OR FAID 3-144 n/ '--~fl(4NA i G)fjTfE'-- AH3-4 N/A Sit- -9q70-(2) /

(7).

PUFING SYSTENIE (RADIOACTIVE FLUIDS)

,. 4 Srie.1 description of service for _hich wa oesiged-ru~m..

2580 '650 'F or Valve Prewure Class i

-pesua iTemperamurej Ca W r.; Pressure - ii &t 100F.Mn~cirr I Rmr~

Mark No.Mateca ju Spec. No.

_________ IN _ MauatrrR mr-4-.

11;i rfaf valves oniv.

  • ,spp~Irrn&..dt;0 sl;m Ir. falm at list. ssk mches or ctrawtrul rn-;%wb

. us"'r f'"?vmdet 1 ie Sl) is a- 142 x 11'. (21 informatioll Ir

FORM NPV-1 iec MarL No.Material 3VW NO. Manulacturer emr

___F" 1-K 1-.

idi Other Pont; rene

~-~'

~ A.S 479- W 16 1C SA479 TP 31 -i nter

!4. Hydrrstz~tlc tus* 4 psi Disk DlfferaritW~ tot pfgcsu?* 3600 p~

CERTIFICATE OF COM;PUANCE W D ciertify ihat the statements made in this report are correct and that this pump. or valve, conforms to- the rules of iozgsJuCtiOn of the ASME Code for Nuclear Power Plant Components.Section III, Div. L. Edition 1977 Ad s uldrrmer 1977 . Code Case No. 1539. Dte April 28, 1981 Moatel Kerotest N4arcufa=cturing

{.c*,li;.,*., . Coro.

1902 4-25-83

-jrASME Certificate cf Authorization No. to us t symbol expires CERTIFICA11ON OF DESIGN oe;n"1C~rzj~ i.21 _~l Ktlertest Manufacturingr Corr , Fittsburph, PA*

Sit&ws analws-is'report lClass I only) on r-l0 at -NIA peifcuot enfedby(

C-siir Faruk A. Gopalani PE Sims& PA Reg. No 21966-E Stra-%s analysis ceftfitd by 4 NIA______ ______________

~E Stt / No.

1431)

_ _Reg. _ _ _ _ _ _

Signature ;c.z fecuired. List "ame only.

CERTIFICATE OF SHOP INSPEC0ION I, !hs i-:oersigned. holding a valid commissien issued by the National Board of.Boiier and Pressure Vessel Insiector9 a..5 the-STate or Province of _ ______l___ - _ and employed by ]lLI3 [ Cr.i.* AN,____"

.... if)- CO.. .. CTIC. T have inspected the pump. or valve, described in this Oata Roepti act fllýM 19-r and state that to the bect of my knowledge and belief. the N Cenificate Holder has Con-i

!n~c+/-P fns - Or va;va. in aceoroance with the ASME Code. Section Ill.

8y oginr.;r m:s neitlsr the Inspector nor hot employcr .nake% any warrtnty. exrpressed or imptlied, co"ncartwlg,

"-he tcu-:)me,-"z dtscrtl.,ed sr. i*s Dz*3 Peport Funiwcmore. neither the. Irspeclo rinot his employer shall be liable in any ma nnerrn for zny ;.cricnal ;pury or properly dierria of aloss of assy kitid ar.sarnI from or connected wt- this? nSp.c-ton.

- ~!'

--ItL~1-tr...~ ______Cnaswis-sions-

FORM 1/2-ADM-0801_F02 REV 3 RTL # A4.414-A Form No. 3130 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinlport, PA 15077 Work Order #200356255 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shioninooort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c). Applicable Section Xl Code Case(s):
6. Identification of Components Corrected, ASME Remeved, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest --- 2RCS-27 1978" Removed Yes

7. Description of Work Removed valve and installed cap.
8. Tests Conducted: Hydrostatic* Li Pneumatic* Li Nominal Operating Pressure Z Exempt Li Other Li Pressure psi Test Temp. __ o_F lest pressure and temperature tRecord

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM-NIS-2 (Back)

9. Remarks No Data Report available. Replacement 3/" pipeCap: PO 45310710 / Ht. # 421388.

Applicable Manufacturer's Data Reports to be attached Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No. _

  • Expiration Date N/A Signed T. White Staff Specialist Date January 21 , 20 10 Oner'er Owner-sOesýgnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period - - 0 7, to //- -, 7 -93 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

NatioCommissions Board, S e a Inspector's Si rture Nationat Board, State, Province, and:Endorsements Date ,.2070 20 //0 Date

FORM 1/2-ADM-0801.F02 REV 3 . RTL # A4.414-A Form No. 3131 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street-Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShioDinooort. PA 15077 Work Order #200356254 (ADDRESS) Repair/Reptacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shippinwport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section I1l 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized forRepair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s):
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-13 1978* Removed Yes

7. Description of Work Removed valve and capped pipe.
8. Tests Conducted: Hydrostatic* [I Pneumatic" E] Nominal Operating Pressure [ Exempt E]

Other F] Pressure psi Test Temp. _ OF

-Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement 3/4" pipe Cap: PO 45310710 / Ht. # 421388.

Applicable Manufacturer's Data Reports to be attached Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME

.Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 19 2010 Ower'sDesignee, Title CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford. CT have inspected the components described in this Owner's Report during the period s'"-,--- - 0 - to // --2, ; - 0 F and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions -I-,'-'(

/ 3 lnspector'srture National Board, State, Province, and Endorsements Date ,20 r'0 I

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3132 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200356256 (ADDRESS) Repair/Replacement Organization P.O. No., Job No.. etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

ShirminoDort PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity. 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-39 19780 Removed Yes

7. Description of Work Removed valve and installed cap.
8. Tests Conducted: Hydrostatic* El Pneumatic* LI Nominal Operating Pressure M Exempt EL Other n" Pressure psi Test Temp. °F Record test pressure and temperature

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement '/A" pipe Cap: P0 45310710 / Ht # 421388.

Applicable Manufacturer's Data Reports to be attached Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White j Staff Specialist Date January 22 , 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period .5-- ,K2,-0 ' to / /--_- 0 ', and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing. this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or'a loss of any kind arising from or connected with this inspection.

_____________~ Commissions -x )/?~

Inspector's Signat National Board, State, Province, and Endorsements Date.2 /6 Date , 20 /0*

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A

- Form No. 3133 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street-Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShiDoinoDort, PA 15077 Work Order #200356258 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shiooinoort- PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s):
6. Identification of Components Corrcted, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest --- 2RCS-54 19780 Removed Yes

7. Description of Work Removed valve and capped pipe.
8. Tests Conducted: Hydrostatic* 0L_ Pneumatic* [] Nominal Operating Pressure [ Exempt
  • Other E] Pressure psi Test Temp. °F Record test pressure and temperature

FORM I/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement 3/" pipe Cap: PO 45310710 / Ht. # 421388.

Applicable Manufacturer's Data Reports to be attached Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization o. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 19 2010 Owner or Owner's Desgnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period .-. J- - 17' to ]//-, L,? - 07 , and state that to-the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions -E, /, /$ý 3 -V trrspector';?nature National Board, State, Province, and Endorsements Date 120

,20 ' ()

(C)

Date

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3134 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/04/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200356257 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

ShiDDincwort, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or NO)

Valve Kerotest 2RCS-67 1978" Removed Yes

7. Description of Work Removed valve and installed cap.
8. Tests Conducted: Hydrostatic* El Pneumatic* LI Nominal Operating Pressure [ Exempt LI
  • Oter F1 Pressure psi Test Temp. _ F

FORM 1/2-ADM-0801.F02 REV 3 .... RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Data Report available. Replacement 3/4/4" pipe Cap: PO 45310710 / Ht. # 421388.

Applicable Manufacturer's Data Reports to be attached Serial number of removed valve was not recorded. *Year installed.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 22 20 10 ow'ftf or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford. CT have inspected the components described in this Owner's Report during the period 0 r to / I ,- 7 - 0 Z, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions .2ý /tý / 9Z, 3 '-7 Inspector's ~ure National Board, State, Province, and Endorsements Date 20 /'3

.FORM 1/2-ADM-0801.F02 REV 3 Form No. 3137 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E..N.l.C Date 11/11/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shiboinwport, PA 15077 Work Order #200338916 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Containment Depressurization (Class 2).
5. (a) Applicable Construction Code Section If] 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Co-rected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pipe Schneider Power 2-SR-13-03-QSS N/A 2-QSS-002-236-2 1987 Corrected Yes

7. Description of Work Installed a plate to blank off system.
8. Tests Conducted: Hydrostatic* fl' Pneumatic* El Nominal Operating Pressure Exempt E]

Other LI Pressure psi Test Temp. oF

  • Rec'r4Wf pressure and tempeeature I-..,.

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414'-A FORM NIS-2 (atachk

9. Remarks N-5 Code Data RepocLnQt attached. Blank plate '!t4": P0 45317573 / Ht. #46Y3.

Applicable Manufacturer's Data Report4e be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 29 2010 0 ,wner wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J - -) - ) Y to //- 2, - 0 7 - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XL.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

KQ~e~~~J Inspector's

)~ 6ure Commissions Commissions ~~/-i J,~ i1/2 eoa./ State r a Edrmn National Board, State, Province, and Endorsements Date . /" ,20 /0

FORM 1/2-ADM-0801:F02 REV 3 RTL .# A4.414-A Form No. 3138 Rev. 1 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/10/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 3 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS'l Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200338915 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

- Ship pingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Containment Depressurization (Class 2)
5. (a) Applicable Construction Code Section 1II 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity. 2001E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pipe Schneider Power 2-SR-13-03-QSS N/A 2-QSS-002-217-2 1987 Corrected Yes Pipe Schneider Power 2-SR-13-03-QSS N/A 2-QSS-002-234-2 1987 Corrected Yes Check Valve Velan 830167-4 N/A 2QSS-303 1983 Removed Yes Check Valve Atwood & Morrill 1-13540-19 N/A 2QSS-267 1983 Removed _ Yes

7. Description of Work Removed valves, sections of pipe, and installed oiDe cads.
8. Tests Conducted: Hydrostatic* n Pneumatic* M Nominal Operating Pressure [ Exempt LI Other LI Pressure 49 psi Test Temp. Amb -F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Reports attached. Replacement 2" pipe Caps: PO 4530224 / Ht. #245216 Applicable Manufacturer's Data Reports to be attached Pineline 2-OSS-002-234-2 received the Nominal Oneratina Pressure System I eakaae Test while 2-QSS-002-217-2 received the Pneumatic Test.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 29 20 10 C'ne r O'wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT - have inspected the components described in this Owner's Report during the period )-- - 3 9' to // - a2 2 - 0 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/&- v"- j 2 InspectorýSignature L/"Commissions A,. "1"- v/

National Board, State, Province, and Endorsements Date , 20 / 0

-FORM. NPV-1 MANUFACTURERS' DATA *FEPORT FOR NUCLEAR PUMPS OR VALVESo -

(As Required by the Provisions of the ASME Code.Section III, Div. 4.)

Vmaiufacturec vy NP-AN *nr., 212 5 wLRD AVý2, 1,rimE LQ .1LCI

. 6anwfacturec to. r ~4,45 -6flA~,PGH, PA 1Z219 (Nom~e oneC Aaarm of fPurchotor ori-nr XUZ~!

o?1s~~~~a~sa~~~ior~~ ~P GP~ JkV3~T 7~~SkIN Mamai arnc "O@rem:

49. Fumnp or Valve MR!S- i:~ 9i150MASS Nominal Inlin Size 2 Outlet Size _L Y:

finch) CiFW%~)

VALJV+/-

is) Model No., (b) Momnfacturers' Wc)Canadian Series No. Registration (d) Drawing (f) N4*I. 4g) Year or Tfpe , No. No. No. (Cias" Bd. No. Built I/ /

ou 316- M7O3B-3 O N/~?-79NJ 2 LNWA 1283 (2) 8064RV (3)

(71 (a)

7. ~Cow wsarkivf owmps a W2 L- pmWW Rewli A~

mmk No.L SWVu merov Nowj Remwk

__ _ _ _ _ _ _ _ _ _ _ L __ .__ _ __._ _T _ _ _ __ _ _ _

I

__ __ _ _ _L_ _

(a) r

-Z*

_ _ _ _ _ _ _ _ _ _ _ _ _ 1 _ _ _

N/A_______I______

_____I _

.4___________________

BODY ___ SA-122 5F 16 FOV Iý Z'§

___ __ _ _ SA-132 316 /r ___ __JE __ __ EEA M COVER SA-122 F 316 FORMJE kaT co: E~A-V, ;a- manually 000rated vavts only.

-S,ýi:*mental shmes in~ form~ of sewc-m :r orawings may be used orov.ided .11) size in 8-7 11-. I:ý infom-rattom -n

FW~M NPV-1 fleck)

%0.'~ Material Soo~c. No. Manufacturer. Rmat SF,-479 c/5 316 ME V________55_S__74 t" 4235 V -s CEPRTIICATE OF COMPLIANCE 1-o -4ri~J t-" Pamfnnts -node ink this report are correct and that this pump. or va".e conforms to the rules of i= na ~cn , h AME CodeO for Nuclear Power Plant Components. Seciaion 311. Div. I.. Ed~itin 1971 .

A= ___________N___ Code Casn No.

by - - Z*4 FEB 185n3 x~~SlAl Zonifcmi of A4zhornzatiofl No. 178 t . ympoo expfif" - 3,19p3 CERTIFICATIoN OF DESIGN S-ram ra.-vs-s evonr (Ciaus i or.iy; on file at a -. Ange. No. -- 196-n!-.;*ror.

reouived. Us&name onty.

- CERTFICATE OF SHOP INSPECTIoN n*e un~ersignee o Olding a a. 9 mrnnssion issued by the National Board of "folr Pepure Vssel Insoectrs pn

&-a~ ti S:a~e ar civince of a ari rnaloyeG by I

  • r~ L f Lhave inspected the ountp. or valve. descsbed itt this Dam Report on

_T751- . L.  % 9 - and swi atet to rho Dows r- mv knoviledge and beiof. :it Mainufaocrurer has con-r-~.?~ ::.or va:*e. in aecordanca wirt no ASME Code. $*rter. 3t, s; ; s':e~1cate. neither 'he Inspectro n~or his employ.-, mrnts tnv warranty. exoressed or imolied. concerning Tf oz.-:=9* coscribec in t-is Do Repor. Furtmeriore. neirc -r 1-t iý'Zctor nor his emoloyor shall be liabie in any

~.:-s.a.

r' -~ rv~'eor a loss of .~ m rising from or connected with this inspection.

~~ Commissc' tNal' IBd.. Stale. Freiv. 'art No.j

_.1 IV CEflTIMDATIE HOLDER~S' DATA FO 7EdR NUCM PW cmvALvgEs-O-

a.d by --

Mn*n Address of N Certificate Holder)

i* a;red for _Slone. L.Wb5trF

-a&tm of bnoHatton _Bav.r a1LI S~hiangQorx,__PA..

(Herme anid Adetepal I& ______Vale_____p_ Nom.inal iniet Size .iLI .. Ou~tru Size _2_112 ma" N~o. Wb" Certificate Holder's (c) Canadian WeNo serial Registration (d) Drawing I0) Nat'l ) .~

we Type No. No. No le) Class ld. No F

() 2 1/711 Chec~k 1-1.3510-19 W1A -H- 3 A.42J2 2/~I (7)

S______C heir;i-a 1L.1.Va.1u-e.Cn:*ro1 . .___ ~

6.Design Conditsans ..- .. -2V .- F or Valve' Pressure Class __"U _

7. Co*s Workisi Pressure 27A at 100 F IL Promwue Ratiwir~.r Paeces marb No ma"8 SpeC No Manufacturer -ear-151.. CF8 _odY Lebanon Steel FJ 5. 5 _-
    • ... .F3. Quaker Alp Ht.t -6*61-2

____ --- V____

W140C mwatwfy Operei..TV21vws only

~ ~A~

  • ~ 'I-AA. ~ ~ ~ ~ 7 "'7~*~-,i-

.~vV

-- .~' No I - I

- .. Wr r I -

W4Wsp"t. No.

I I'* .-

fI4sa, ctirer 1-~-~---

Cq3_LyJd~d. SA 193~c~ 0. I.AL1LJ 1...~.

1.~.

- ____ 1

$Uff.SOX Sktuds SA.32C C1.2 .2 Rono Mfcq n TirageLW24F- .-..

SA 194 gr, 8 511!_A1O' SI vf f . Bxj 1:Lut

14) Othet Parts 4 SA .Z_4Q r. 304 Stuff.Box Cover SA 240o Gr. 104 w- ......

+

1'

9. l"V*onatic tM25..

iii- ___________________________

D;sk Differential trit Prrsr- 2 Pv.;

CERTIFICATE OF~ COMPUANCE We Certify that I"e stateernrts m'ade in th~s report are correct sfbd mhat this purrrv. or valve. conforms to the rules of Consatruction of the ASIVE Code for Nuclejgr Power P~znt Components. Secir;on :%Dr.. I.. Eduitnn .12' - -

Addenof r._.

,3~re- . Code Cmw N~o toLA 41A 1-qe~ _____

Sg~ Att ~d__ LMQr r U. I1~____

uwr ASME1 Coortficuie of Aih&1Ionizz~oli No. 260 to th _N symbol exp~raires z 6 in) Vi.

CERTIFICATION OF DESIGN Dsigninformation or file at-.. S t _ -.. W ebs t .__. ... . .. ...

Stre, aii*t report IClAs, I only) on file A* NIA .... ......

Design specificatons cet-food by (II Walter J. Parker, Jr.

PE Stew .f .Rg o 2 900O-F Stress analysis cern,-ed by 1 ... N/A ......

P( SiguatureA ..........Li.s Noame'.NoAnl (1) Signature usot required. L,$! name only.

CERTIFICATE OF SHOP INSPECTION I: the unctirsigrnod. t-o..lnr) a v.sld comm,.twon issued by the National Bo0ard M?Bo~ler and Pressure Vessel :np-ýctv.,r and the State or rovevnee f )~Ž~jCttand -. employed by KS. B..L A... C....

Of~~ f rhawr inspecte the pump, or valve. de~scribevd in this Data Re&:c-t or.

-qIf.Z. and itat, that to the be~t of rny rneiowte~ge &no e,.f the N Certificate PMotdcr t-OS Cop-.

strtjcted thus pump~. or wia've *n accordsnice w.u' ithe ASME Colla Section III-SY signing this Carl-f-cautc. n:.t!itr me' !'sspecitor nor hi.; emaoloVer m.atel any wartrjnty. e-cpressed or Implied. concern.r.q.

Ow eq vit)foft described *- !has Data Aeport Furthermore. neither the InSpeCtor nor Ili$ , nirl'yer shall be Iiab!.ý -un any Nwww flew o anly erOrs130 in,tuvy o,r 5)5 PerTV 'igsu . of a loss :if any k~rnd syssrsg frcr' -or crutjt,.,cud wtlh this uVVi:o Dore Y15I '/1 p -lpVCommisv..ons_____

rtIeow (Noots bit. Sinto. Prov and N& I

-j

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3167 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASMECode Section Xl

1. Owner F.E.NO.C Date 01/13/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet .1i of 2 (ADDRESS)
2. Plant Beaver Va 11ev Power Station (BVPS'I Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200148982 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Constnuction Service Type Code Symbol Stamp N/A (NAME)

ShioDincwort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1974 Edition, S'76 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Butterfly Valve Fisher Controls 59204-IA N/A 2SWS-MOV107A 1992 Removed Yes Butterfly Valve Fisher Controls 19029363 7578 2SWS-MOV107A 2009 Installed Yes

7. Description of Work Replaced valve and flanqe screws
8. Tests Conducted: Hydrostatic* El Pneumatic* E] Nominal Operating Pressure 0 Exempt Ej OtherU Pfessure _ psi Test Temp. o_F
  • Record tMst [pren*aie and temperature

FORM I/2-ADM-080I.F02 REV 3 - RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks NPV-1 Code Data Report attached. Previous NIS-2 Data Report No: 380. Replacement Applicable Manufacturer's Data Reports to be attached 1-1/4" Screws: PO 45311238 / Ht. #3G84.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 13 ,2010 "wrir-or vOwner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period '- -;"-L- a - to /( -*-- - 0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the

. examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer

,shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's iture

/~7A~-2 1,92/#AI.T.z/'

~Commissions 7d?

National Board, State, Province, and Endorsements F~(/

Date D 20 / 0

FORM NPV - CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR.VALVES*

As Required by the Provisions of the ASME Code, Section [II,Division I Pg. I of 2

1. Manufactured and certified by FISHER CONTROLS INT'L LLC. VALVE DIVISION, 205 S. CENTER STREET, MARSHALLTOWN, IA. 50158 (name and address of N Cerificate Holder)
2. Manufactured for FIRSTENERGYCORPPO BOX 6100, JOHNSTOWN. PA 15907 (name and address of Purchaser)
3. Location of installation BEAVER VALLEY NUCLEAR PLANT, ROUTE 168, SHIPPINGPORT, PA 15077 (name and address)
4. Model No-, Series No., or Type All Drawing GE43888 Rev. A CRN N/A
5. ASME Code, Section I1I, Division 1: 1974 S 1976 3 N/A (edition) (addenda date) (class) (Code Case no.)
6. Pump or valve VALVE Nominal inlet 24 Outlet size 24 size (in.) (in-)

7: Mateial: Body SA516-70 Gasket SA240-S31600 Disk SA351-CF8M Gasket SA193-B7 Retainer Retainer

_________________Bolt (a) (b) (c) (d) Wc Cert. Nat'l Body Gasket Retainer Disk Holder's Board Serial Serial Serial

  • Serial No. No. No. 'No. No.

19029363 7578 AB6608-1 654225-1 AB6607-1 (f)

Gasket Retainer Bolt Serial No.

654226-1 thru -3 813007-1

  • Supplemental information in form of lists, sketches, or drawings may be used provided (1) size is 8 1/2 x 1"1,(2) information in items I through 4 on this Data Report is included on each sheet, (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

FORM NPV-1 (Back - Pg. 2 of 2 )

Ccrtificzitc Holder's Serial No. 19029363

8. Design conditio 150 psi 120 IF or valve pressure class MA_)

(pressure) ' (tempera-tur) 0

9. Cold working p ressure 275 psi al IOU F
10. Hydrostatic test 450 psL Disk differential test pressure N/A psi
11. Remarks: DESIGN: ASME BPVC SECT. UILDIV. 1. 1974 EDITION, S 1976 ADDENDA, CLASS: 3 OTHER: ASME BPVC SECT. IULDIV. 1. 1989 EDITION, NO ADDENDA, CLASS: 3 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME code,Section II, Division I.

N Certificate of Authorization 1929 Expires 10-27-2010 No.

Date qt Name FISHER CONTROLS INt'L Signed riC (N Certificate Holder) (authorized rpee ie CERTIFICATE OF [NSPECTION I. the undersignedholding a validecommission-issued by-the National Board of Boiler-and Pressure Vessel Inspectors and the State or Iowa Province of and employed by Hartford Steam Boiler of CT of Hartford, CT have inspected the pump, or valve, described in this Data Report and state that to the best of my knowledge and On~ -I/

bcliet the Certificate Holder has constructed this pump, or valve, inaccordance with the ASME Code, Section [II. Division I.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report.

Furthermore, neither the inspector not his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Da- 0 Signed / ti InpNa (Authorized Inspector),

Commissions NS .i lde e d't o ro .

(Nat'l. Bd. (include, endorsements) and-statc or prov. and no.)

(1) For manually operated valves only.

FORM 1/2-ADM-0801.F02 REV 3 RTL # MA414-A Form No, 3168 FORM NIS-2 OWNER'S. REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 01/13/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippincqport, PA 15077 Work Order #200148983 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

ShiDrinaDort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section Ill 1974 Edition, S'76.Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Butterfly Valve Fisher Controls 59204-IB N/A 2SWS-MOV107B 1992 Removed Yes Butterfly Valve Fisher Controls 19029600 7577 2SWS-MOV107B 2009 Installed Yes

7. Description of Work Replaced valve and flange screws
8. Tests Conducted: Hydrostatic* LI Pneumatic* LI Nominal Operating Pressure [ Exempt Lii Other LI Pressure psi Test Temp. oF

'Record test pressure and temperature

FORM-I/2-ADM-0801.F02 REV 3 RTL 4 A4.414-A FORM NIS-2 (Back)

9. Remarks NPV-1 Code Data Report attached. Previous NIS-2 Data Report No: 382. Replacement Applicable Manufacturer's Data Reports to be attached 1-1/4" Screws: PO 45318681 / Ht..#3P79. Ht. #E123. Ht. #3P80.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White OYAWr orr s~es'gnee, iOwner'Title Staff Specialist Date January 13 2010 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period - - 0 W to /' / - 2 - 6 9 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied; concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 7-1'2/VL'q AAdýý )-a 6cý

-F Inspecto ature National Board, State, Province, and Endorsements Date S,20 L/Ž

FORM NPV-I CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES*

As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. I of 2

. Manufactured and cetificd by FISHER CONTROLS INTL LLC, VALVE DIVISION, 205 S. CENTER STREET, MARSHALLTOWN, IA. 50158 (name and address ofN Certificate Holder)

2. Manufactured for FIRST ENERGY CORP, PO BOX 6100, JOHNSTOWN, PA 15907 (name and address of Purchase)
3. Location of installation BEAVER VALLEY NUCLEAR PLANT. ROUTE 168, SHIPPINGPORT, PA 15077 (name and address)
4. Model No., Series No., or Type All Drawing GE43898 Rev. A CRN N/A S. ASME Code,Section III, Division 1: 1974 S 1976 3 N/A (edition) (addenda date) (class) (Code Case no.)
6. Pump or valve VALVE Nominal inlet 24 Outlet size 24 size (in.) (in.)
7. Material: Body SAS 16-70 Gasket SA240-S31600 Disk SA35I-CF8M Gaskct.- SA193-B7 Retainer Retainer Bolt (a) (b) (d) We Nat*] Body Gasket Retainer Disk Holder's Board Serial Serial Serial Serial No. No. No. No. No.

19029600 7577 AB661 1-1 654246-1 A.B6610-1 Gasket Retainer Bolt Serial No.

654247-1 thru -4

  • Supplemental information in form'of lists, sketches, or drawings may be used provided (I) size is 8 1/2 x 11, (2) information in items I through 4 on this Data Report is included on each sheet, (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

FORM-NPV-1 (Back - Pg. 2 of 2 )

Certificate Holder's Scriil No. 19029600

8. Design conditioIns ISO psi 120 'F or valve prcssur c class N/A (1)

(pressure) (temperature)

9. Cold working p ressure 275 psi at 100F
10. Hydrostatic test 450 psi. Disk differential test pressure N/A psi If. Remarks: DESIGN: ASME BPVC SECT. aI, DIV. 1, 1974 EDMON, S 1976 ADDENDA, CLASS: 3 OTHER- ASME BPVC SECT. II, DIV. 1, 1989 EDMON, NO ADDENDA, CLASS: 3 CERTIFICATION OF DESIGN Design Specification certified by FRANCIS W. GARDNER P.E. State PA Reg. no. 036614-E Design Report certificd by NIA P.E. State' N/A Reg. no. N/A CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for enoamtnction of the ASME code. Section Ill, Division I.

N Certificate of Authorization 1929 Expires 10-27-2010 No.

Date ql- Name -FISHER CONTROLS INrL LLC Signed 4EA A (N Certificate Holder) (authorized represen4,aive)

CERTIFICATE OF INSPECTION 1, the undersigned, holding.a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors.and the State or Iowa Province of and employed by Hartford Steam Boiler of CT of Hartford, CT have inspected the pump. or valve, described in this Data Report- a-/ 0 7 and state that to the best of my knowledge and on 7-7 belief, the Certificate Holder has constnrcted this pump, or valve, inaccordancc with the ASME Code, Section II1, Division I.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report.

Furthermore. neither the inspector not his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

D ate 7 < H tD 7 Signed _ _ " _ _ _ _ _ Com m issions ,( 7 P1 / II/ ' , , -I (Authorized SOP-6or) (Nat'l. Bd. (include. endorsements) and state or prov. and no.)

(I) For manually operated valves only.

FORM I/2-ADM-0801.F02 REV 3 RTL # A-4.414-A Form No. 3170 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/11/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippincqport, PA 15077 Work Order #200326364 (ADDRESS) Repair/Replacement Organization P-0. No., Job No., etc.

3. Work Performed By BVPS-Construction Service Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)

.5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity. 2001-2003 (c) Applicable Section XI Code Case(s): N/A

6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Globe Valve BW/IP 95EP0225 N/A 2RCS-633 1995 Removed Yes International

7. Description of Work Removed valve and installed pipe & couplings.
8. Tests Conducted: Hydrostatic* LI Pneumatic* .] 'Nominal Operating Pressure M Exempt El Other [] Pressure psi Test Temp. _ OF lst tRecord pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL #.A4.414-A FORM NIS-2 (Back)

9. Remarks- Code Data Report attached to previous NIS-2 Data Report #753. Replacement 2" Pipe:

Applicable Manufacturer's Data Reports to be attached PO 45213729 / Ht. #037046: 2" CouDlinas: PO 45313563 / Ht #247689.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 11 20 10 Owner or Owner'?"esignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period ,-- d- ot_ - (3 9 to //- gL 2 - 6?

  • and state that to the best of my knowledge and belief, the Owner has performed examinations .and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Z,.- f AI,I d,.s rvýt National Board, State, Province, and Endorsements Date S,20 /C

FORM 1/2-ADM-080 1 C02 REV 3 RTL # A4.414-A Form No. 3171 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 12/28/09 (NAME) 76 South Main Street- Akron. OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shiroinooort. PA 15077 Work Order #200326360 (ADDRESS) Repair/Replacement Organization P-.0 No., Job No., etc.

3. Work Performed By BVPS-Construction Service Type Code Symbol Stamp N/A (NAME)

ShibDinaport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section 11 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity. 2001-2003 (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Nameof Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Seriat No. No. Identification Built Initalled (Yes or No)

Globe Valve Kerotest HWI-21 6471 2RCS-634 1975 Removed- Yes

7. Description of Work Removed valve and installed pipe & couplings.
8. Tests Conducted: Hydrostatic* L] Pneumatic* L] Nominal Operating Pressure [ Exempt Li Other n . Pressure psi Test Temp. oF
  • Record test pressure and temperature

FORM 1/2-ADM-080I.F02 REV 3 .RTL # A4.4.14-A FORM NIS-2 (Back)

9. Remarks Replacement 2" Pipe: PO 45213729 / Ht. #037046, 2" Couplings: PO 45313563 / Ht.

Applicable Manufacturer's Data Reports to be attached

  1. 247689.PO 7086304 /Ht. #XAN TR #17847.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 27 20 10 0"

  • or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period . -- d-- G T to 1 -  ? -? 02 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

2*. (*

Inspector's>Z" nature

/ Commissions / 7,- -,-- *,.y National Board, State. Province, and Endorsements Date D 20 /b

F"ORM NPV-I MIAMINU'AL11US 01U '1ti-s 'I' FUVI N'IT: XII lIT.'MPS oil VAL!VUSIO Aft llhquised 6y the PbvkisonA at £Iu, VA{IF Cofir U41c.4 2525 Liberty Avenue M"Viwt"Cd by.

Keroteat M4anufacturing Corp. Pittsburgh, Pa. Order No

?4U-W~816 (W4ex~& AOdrocia 9( Monaciurao)

P.O. Box 355 Westinghouse Electric Corp. Pittsburgh, Pa. 5I46-CCF-17a.?':52:-.'

NMQSf6CteiA fOF Oodef No.

Duquesne Light Company ofPlat 116oli eaver Valley #2 faftValv~e IetIgios~ erial #f s~ -9 HW1-20, W.1-21, M~-.-25 (3.1.1 aao~I utleltrh ". 0eqdpaozd won oloif)

~ Ci) Rev.E Sh. 2 of 2

(b) Koado"I Dowd~ No.140 M5T 2580 ~ 650 0 "gsI d:o, c*1dIfuc~i4fic and Wdkaasip Cdaplies widb AS E Code Sectiao III. Clanss

. 191 Addeoda Dam. ýWinter 1972 ,Cose Me. W/A Aa) Cas~~n~a

~alet, fee. f a Mato l S~pec. H.Mnfgt~rR a~

4. 4.

___It- *. . _

... I_ '_ __

- '4-

  • 0 - __________________________ 4.

Body UP-90 9-) S__18 16:"ý'.'ý*

-- kJe.Up-91-1T I A105 f I 2 9 1-

. ) W. .N' *Uiw\-I ,,L)

I 41 I Itp.o. N." I 3.4 1 A(t' Z.. i,,.- I

.i.-

_________________________________ I __________

I -

I - I.-- -~--- ________

~~~1 I -f _________ I ______________

r Other p .~ ~ _________________________ -~

Z~

Ii

- '.--fl-~'S..... -~ .*

- - ~ ~-.----------- -

T. T-11E]

.1....

I. _____________

I _____________

________________________________________ __________LI-U. ?tyduiiijt;ic sit pai.

CERTIFiCATION OF DESIGN Des~~~~jrefsh fi~siilii'*! '--.on 0' )0 cf:! (,r A t S .

17Y.,b1 Carp Eng. c. fa4c- ?a

1) plor.  :- -

totes~~el~i.n ccftiturd by. I Cn~-'i1~ -

(1) Peof. Eng. St-tv - FA P.cr- No-S.~~~sLi ~ y Anty~

'We tell;NA th the 1451eaents wmade ifl this reor se Correct.

.5 Date y 16 Kerot est Ba

l.iii*
.* i.;*
  • 908. .. jP** :.:.12817"T S. C~ro~1~

CERTIFICATE OF SHOP INSPETI'ON IaIdjn1A Ll;ng it COISS0 l S'Ws4*-by tke National Boar?~ of Baohr' .^,d PflrLestu*rSS Vese n%;-*CCTor 4foesbi.tiith c*~fc -CHoPp ace________ _ IAM employed Ly The' -!Itrtfcr.. Se.z 3ofie 1' Co -

ii rtf 6.rd .ik, coinec1`6 ave inspectird the e-suwr-mai Jescr~be.J in this Dots t . 1k-i i: t " anc* :a"te dc -a1o tih b-,st of Our knowlirdIe ,nd 6elief, ihe Mootufacturc."

hSl conaaaed tS iI ;ft aceordance. with ithe6'tIcblile

.ncnin Subseetio a AS.,.E Cod-, Irccion Ill.

  • By i iVii .. e lfr, sit- Int n cees n or-hisca*o*pijer o'akes say wibrramly Vxpreli!ad C.?; itspleJi colaceri-

- ar, CcaiirC4 ind Civiu bitas RtoII.t. Fdicirm*oir'n-ieher the Inspreio: Aar hi* rý,,,.Iwycr shul bc Nae-Ic in any utsnegt't an~.!ly:petsol. injury or poacra Jsuamgc or A.4os,5 a.ny kind atising frogs or ii..- cr-8 ýw',h dthis iinslection.

If%...,

.. _..D . .6 7g5 Pu)q, *

- :, (l~li-III-I*,%i~~opr-t-vi -- d N*.)

FORM l/2-ADM-0801.F02 REV 3 RTL # A4.414-A .

Form No. 3173 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 01/22/201.0 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 3 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinclport, PA 15077 Work Order #200339308 (ADDRESS) Repair/Replacement Organization P.O. No.. Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Fire Protection (Class 2)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code C

Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Check Valve Atwood-Morrill 20-13540 N/A 2FPW-382 1980 Removed Yes Pipe Schneider Power 2-SR-33-02-FPW-l N/A 2-FPW-002-007-2 1986 Corrected Yes Pipe Schneider Power 2-SR-33-02-FPW-1 N/A 2-FPW-025-005-2 1986 Removed Yes Penetration Pittsburgh-Des 13691-117 979 X-117 1978 Corrected Yes Moines Steel

7. Description of Work Cut/cap pipe and remove portions including valve.
8. Tests Conductecd; . HydrO -.Pneumatic* ] Nsminal Operating Pressure LI Exempt LI Other E] Pressure 46 psi Test Temp. Amb oF
  • Record test pressure andlemperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Replacement 2" Caps:_P0 7077508 / Ht. #AY7W1.

Applicable Manufacturer's Data Reports to be attacthed CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

TypeCode Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date NIA Signed T. White  :ý Staff Soecialist Date Januar 25 , 20 10 Owneror Owner's Designee, Titte CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S"- - 6 F to /I - .) ID , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described i~nthis Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions -.- , /'*k,?  ?'

Inspector's ~~(re National Board, State, Province, and Endorsements Date 20 20 /t0 70 Date

(PORM N-5 DATA-REPORT FOR INSTALLATION OR SHOP ASSEMB~LY Or-Nt'CLEAk POWER PLANT COMPONENTS. COMPONENT SUPPORTIS, AND A',F-ATENANCES*

As Required bythe Fvo;isiiom of the AW~ECo& Ruls. f1, ivusionI

¶$fityPittsburgh-Des Moines Corporia týittsbur h Tp.

1homfe and orvae o ce.88 .Component.

of compor;;t NO, Or Puncn10011ICM for wDw~w Light Com anv Pit

-ANa6"Me 8"eae Of putChaasiv til ~*ftv I~

N*Cmtifi$jt Ha wvHaing Oywrs Pkmnsibility Stone 4 Webste-xi j ~ ing- Cor~..L

4. Loctionof n~sla~aon __&Myq Valley Unit No. 2.__ Shitp,-4 OKI.,

S. syrmm Idmfctwcin 1:3091-17 Z36 Nat'l 9d. No -. 9__yvOrtinz~jd

- 18 G. Nuclear Components and Appurtenancer. installed in the Fi*1d by WQelding (List eachs item and atacki~

copp~s of N0Carltificato Hclders* Data Reaorts and MPT Certificate Holders' Partial, Data Rtr)orts)

(b) Name Of W)l Cantedien (S) Nations!

gal ~ ~

p-fqw~wS Cartificate HoIl1sr (0i serial No. Reg. No. 8d. No. if) Y&&Y Suift (ae~pipitq (bi Naew of (di Canadian ie) Natio~nal 14C)Sarial Nco Rag. No. ad. No. WI Yexr BuAilt (d) Design Rqport.

(a cwnaam 4bNom fLoad C&pW. (9) Cansclin (!) National SpotNo. c'tiftcate Holdew t0 seuial No. Data Shoot Reg. No. Od. No. (9) Year Built go) Nanw of. 1b) Material NA._____ _ _

%qnkWn1ghequ in aorn ofl im,~ sketacis, or drawings may bo used providG-d 01) size iz 8-% In. x I1I in.. (2,1 inforars-tiop 1 fptems I thrwgih 6 an thts D,%ta Rvport s l8 includd an atach stheat. and (3) each shset is numberpld r. th~e mimber of dMj.fwscode az the top of whs horm,

Ri*--oý-  %

FORM N-5 (Back)

7. Ua) installation in Accordance with:

Proceoure Or Or(wing No, Prrtdrew *y Drawing E36 _A_ jPCc_'i.-',.

Drawina 78 ____~: L. g (b) DescritNion of tnstalation Perfrm-ed.

Pipe field hydroteale In RCgx&L&.e with_.ZVR -o__c N-32-3 aniPd . proc eure CKT-5, Rev. B. See NPo'r sbCop fbri-cathion cert iflic't ion.

1c) Hydrostalic Teom 240 psi. System Working Pressure paii and Temrp. - - F.

C*RTICATION OF DESIGN FOR PMIIUG SYSTEMIKST&LLATION sig.n oni~on on te at stone & Webster Enginteerý_in, Co.. Boston, MA Design Report on file at Design 54o9cificatiofl5 certified by f1)* Owen WI Lowe,. Jr, PE State . flasl~v1Thfl neg.N o. 258g2-E Design Report certified by I1) PE Sttet_

Poo. No. __

I1) Signature not r*uireqw d. List on)y.

__a___ "r Design Contlitions of Piping PrmmesTsurrer psi 34-88 F.

CERTW*CATE OF COMPLIANCE I We certify ttat -tht statemets madfe in this reporl are correct and that thiz installation conforms to the ru* cft cof -

struct*rn of the ASME Code for Nucear Power Plant Componm3rnts,Section III, Divoicm 1, Addenda W~Z .Code accordanca with the documents lited in 64s1. above.

Came Wf. -Classa___

1971 - Ediion, andi was p*.r1orrneti ir.

Palo Signed b Our ASME Certificate of Authorization No. N-14937 to isa the A syw eyrx*cres]-L-1918 j

CERTIFICATE OF INSPECTION 1.the undrsigned holding a valid commitsqtpn issued by the National Soard of un¢1 Pressure Vessel tnsp.~orsaoilar and tti Simw or Province 0 _______________ancl employed by andi stt that to the best of my knowledge and belief. the Cartificate of Autewelzation "Older has const.ructed this I* n~l~l.latio in accordance with the AS*ME Code for Nuclear Power Plant Component%~.

By signing this certificae, naither the Inspector nor his employer make sow wzrranty, sipress or implied. con-

!rrýng the piping described in this Data Report. Furthermore, neither the inspector nor emplayer

" shalt b* i4ble in any mnner for any Personal injury or property damage or a loss of any kind rising from cw Connected wITh Ifht rA".,0,ion, sign" ~~~Commissionw ~--S' r Following completion of the above. the Certificate of Authorization holder accepting overall responsibility for ?N-2 S'stem shall complete the following *Matement.

We con,tv the statements made by this report are corroct and that ther system co. rms to the rule of constroclir, of the ASME Code Suctro itions i.

Date fe Suhrio Stone rigned f1 "bster Ener. Corp. e Certificate qf Authoriza~iaon Eprs 6 Cqn ificate of Au~horirWtin oN1 3Z

ý9 h Ltalled byPittaburthD I-I Wone Cporation, Pittsburgh., PA 2.lzala o Du~queene-Lisht Co&ape! L~ýPittvburgb. PA

3. ffCertificat~e Rolder Having jOverall Benponsibility StneWebsterniercop 4,. Loeimof Ic t alla tic=?--") -Seaver Val.eZ Unit N.2 bkinrP Syte dentifieeton'C169l-l7 Ya~T 1 R as lter ofcriia - iUPPIeet,-to the 14-5 Data Report for Peaetration li~petration was intau~~rt.e nacrdanc thCeCae1-23 Weery

~frhrcertify that thi a!AWd& tai keot,: performed in accordance with P1)1 Procedure 5,also ccxaplieg wih od 'ase' N W32-4' eh-cthe Wn approved.

4 41 "w,.k, 7-U-~4 e 1~'~:,. Sheet z of ?.

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3174 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/06/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shim)inaport, PA 15077 Work Order #200370411 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shiopinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pipe Power Piping N-1141-3564 N/A 2-SWS-012-185-3 1979 Corrected Yes

7. Description of Work Cut out portion of pipe and replaced.
8. Tests Conducted: Hydrostatic* El Pneumatic* E] Nominal Operating Pressure [ Exempt LI Other F] Pressure psi Test Temp. o_F

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Replacement 12" Pipe: PO 45205163 / Ht. #A81517.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date _ N/A Signed T. White . Staff Specialist Date January 25 , 20 10 Owriet' or Owner's Designe-e, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period ,5- ,o- - 0 Z to /'f - - C Y , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

L'Qlnsp.1t. Commissions -.- */ 7%- ,L-- e nspec nt u National Board. State, Province, and Endorsements Date - , 20 el' 0 Date 2060

0M NPP I DATA REPORT FOR FABRICATED NUCLEA eiINl vl Ai-6 As~ Required by the Pravisio&ns Of -he ASME Code Rules, Section 1I1, Div. I N-1l35I Power Piping Company, Donors, PA 15033 Order No. N-1141

. :ýrl,(*co Beaver Valley Power Station, Unit 412 Oidr; No. 2BV-58, J.C I. No. 12241

. wnrr Duqucsne tight Company, Pittsburgh, PA .1 of Plao SI iippingport Borough, PA

1. Pipin.g dv*.- cai,;-, Service WO.ter ,MKSWS-185-14/lo99-185--va iso-loqgih fflr..I dr'. t ...ddp .

Stone Fi Webster Engineering Corp.

) rJ..:ragNo. ..- 9A.. ~ Prepared by Ri"AN' N/A _____ Boston. Massachusetts 1071' DiI W~nter 1972 C5c~ No.. -- ý iRcnarks: ManuEf. ucr'ý D~ili PK'pcifo pr..petly idirntfird 2nd signed by~ Commis ioned Inspcto~rs htvr ltcn iumrashed fot the follow.ing items5 ef this report
7. Shop Hydrostatit Tem - By FieldPs s~. Lk'd4qiptioO ofp'pnep'fci~rtpcrd

- -a,. -. ... a....l.p~. - ~as-.... - a,~...ab..&nt-,' kap.-. Ia,.nj~' --. 0.1.5. Ca I 1 Pc. - 12" Std. Wt. Smis. C.S. Pipe, SA-106, Gr. B; Item klo. 3, L.C. No.

P-958, nt. ID L-62hO6, Dev. Lgth. = 15;-1 3/4!" Ig.,

NOMVE: Welding Electrodes L.C. No. E--16, E-57, E-68 We certify %hotth, st*r*,,mts made in this reporz ar correct and that the fabrication of the dcre.d Piping co-rif" W. t)( requirements of SECTION O of the ASME BOILER AND PRESSURE VESSEL CODE. /1 NoveF,*,*mbe~r 979 sigr Power Piping Company B ooi

' o) N-2 cerxfAW~tc oAuzorilkarion Exprcs Jaur-,~Ccrtific~tc of Auilhoriz~zion No. N1Z CERTIFICATE OF SHOP INSPECTION .N-1141-3564f I.1 ~he uar"ire "h4ng a ";slid commiassion issued by the National- Board of Boiler 2nd Pressurc V-ssel Inspectors and/or the Statc or Pwovince of PENN* YViAi- ;-d'" , ", . HARTFORD STEAM BOIL:.INSPFCTIONfi-!%,SU RANCE COMPANY 0_ HARTFORD, CONN. b,.

'p -.. .... i.,.r o r. this Dy a Repoft On / _ . 19 . nd statc that to the best of.. nowk.dg. and,-

bcie*- nlli'JPCcn i;ar Holder has conszruc'ed this piping in accordance 4ihh the s/pplicabte Subsections of ASME Code.Section III.

BT pi.wng ibis ce.ifmene, neithef'the Inspcctor nor his employer makes ,nywarra,.y. eaprcssed or implied. omerning the piping in this Date Report.

Furthcrmon.re. ncth.r the Inspector nor his employer shall bI liable in any manner (or any'perunal injury or propcrty damage or a loss of any kind arising from or ioinneetd with this iLpLt PiAn.

I, r.-.I %.Id $'-.a.N n itd .

"J.Eti-rt ýmJ p.t.11 f I*Ft-.. . MY'.* 0)W.ni.M~A'n .;-.-m,* 1.,a. -1 I 1" t' a.. t-61tt c.. h tmiw. mnl111 ,ah aw-a a mnvoeofwd

.a 1...,.~ iied

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A rm -No.

S".. 3175 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 12/28/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 3 (ADDRESS).
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200339309 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shippincport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Fire Protection (Class 2)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Check Valve Atwood-Morrill 22-13540 N/A 2FPW-388 1980 Removed Yes Pipe Schneider Power 2-SR-33-02-FPW-2 N/A 2-FPW-002-002-2 1987 Corrected Yes Pipe Schneider Power 2-SR-33-02-FPW-2 N/A 2-FPW-025-004-2 1987 Removed Yes Penetraition Pittsburgh-Des 13691-116 978 X-1 16 1977 Corrected Yes Moines Steel

7. Description of Work. Cut/cap pipe and remove portions including valve.
8. Tests Conducted: Hydrostatic* [] Pneumatic* [ Nominal Operating Pressure [l Exempt LI Other l Pressure 46 psi Test Temp. Amb °F lst pressure andti tRecord .J ..

FORM i/2-ADM-0801.F02 REV 3 RTL.-# A4.414-A "

FORM NIS-2 (Back)

9. Remarks Previous NIS-2 Data Report No: 532. Replacement 2" CaD: PO 7077508 / Ht. #AY7W1, Applicable Manufacturer's Data Reports to be attached and PO D166317 / Ht. #9182_

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. Whit2t1 ;taff Specialist Date January 25 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J- '-' .-- - - O it to /(- Z 7 - 0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions ,"4 r g Inspectr 5 gnatureN National Board, State, Province, and Endorsements Date

  • FORM N-5 DATA REPORT FOR INSTALLATION OR SHOP ASSEMBLY OF NUCLEAR POWER PLANT CONPONENTS. COMPONENT SUPPORTS, AND APPURTENANCES-As Regeirtd by the Provisi-ont of the AVAAE Cod* Rulos, Secti on III, Diwvioin I
3. N Cartificate Holder Ha.,inq Oycral Rosponsibility _ýtn ese ngneiyrip

.4. Locaton of In.jiJafln _jvmt Y 1al YU t L .2. St1pin ___

6. Nucittor Comporonens and ApunlenoCes Installed inl the feiod by Aftidig iLiv each item card rut vcb copieso1 N Ca flIlate Holders' Data Pooorls and UPT Cwtificate Noldarzý Pairtlip. Data Raporws

()COnMPOnen'i or (b) Name of (4-9 Cariedo~n Na"onat Ap~rtnw*%~e cenrvct*s Holder (0~ Serial No, F102. He. Sd. No. (1)Yeisr Sul, Piping SystemitMeio (a) Piping (b) Nam* of. (d) Canadisn (a) National (c) Serial No. Mfg. No. Bd. No.

5

~n~i~a~on(8)

C~r~nat~ 44fJ05 D,*69n Reoo-'t.

(2ý Comonmwww (h) Name0 of Load Capac. (g)Canadian 0f) National supooni No. coniticato Hcodm ici sarioe No. Data Sh'aI Reg. No. Edi. N4. (q) yos,?.

Additicnai Matevial FWiudijq Wa4digr~ Material (a) ftaxw of jb). Mafed8

-Mwiftazurm 502clft~ian (IV Dimensions "Suproementot OuetM in formt of 11M. %kev-.he, or drawings-may be used provided (1) site is 8-% in. x I t in., 42) Informa-tion in Iteinm I ihrtno Faon IhlS Date Raport iz included on each sheet, and (3) sach ý_hest is numbe~red -and the number of Owtts is cewrtid at tfe ftp of ~thi fm~'ni.

ThIA f=m framls? finaw k- oft2faMPEA F.- ah- 9-5.w- r-.&A Actem.n.Aa a A- W. _- - - .-

FORM N-5 (Back)

7. (a) instalstion in Accordance with:

Pocedure of rawing; No .Prepared by

__ Drawing E36 - J.

L___ McCormick-Drawing 78 C. -J. Homxich

'bl Descr'pti.-n of Inhtallation Pprforrmedc Pipe field hvdrcteste 14"ni a*p4nCe with and_~iMproedure 'CfT-5, Rev. B. See NPP-1 form for sl.,ýp abr"-

cation certff-U at on. _____ __________

'ctvdjxatxc Test 245 2 psi. Sys~errn Working Piessure ps15%n Temp. -i4-R r F.

F CEERTiIMICATICOM OF ESIGN POR PIPING SYSTEM MNSTALLATION Ofivtgn information on fil le Stone &Webster Eagineertxxg Co., Bo~tnmA Detiig Repcr~t an file o~-

Delign Spec-fic-Atiorts cenified iLiy 0t 1_ PE s~tst Pennsig~yyania Reg. No, I Desi,n Report -zrtifidc-1 t-Y ) _________________ _PE State________________

[C~esign P eg.I'No.

0 1 Sgi9#1tiure not reqi;ired. Uzt'a'ne ontly.

Contdstions of Fpaq;n pr-sc0 Psi 3 4-88 .

CERTIMIATE OF COMPLIANCE We ciprufy azat Itw gutaeiemri maed in this repoti arg correct and thipt this installation confo'rns to the ruiss of con.-

strwctios of -he ASME Cod* for Nucisar Powe.r Psrnt Components, Sictioon Ill, Division -4 1971 Edition, Aded Code Carse NO. _______ Class 2 and was performed ~n AIaccordanceg with tho itocurnart;isieVd in F~a). abqve.

Dause thez~2-~leN'%9YZ,~ Syn xie 4N, MA) (as

1. "I-r-Va tie ndwsgne vlid omrI)T#"Ue byIhQ atinslBoard of Soilor arid Preasurn Vessel Isetr LC th*Si*!4rPoirc -ademployed byt ______

ofhv Ixcdteppn described in this DaiB Report on ~22 9~

q) thatto sate estof ir kowlcla andbelef.theCtritifcate of Authorization Holder- !ias conkstructed thiz a-o !ha Installation in accrt1ance with teASME Code for Nuclevir ftwer Plant Components.

By eniemeneiher" sgnig tis ispetor ey is mplvermake any warrarty, express or implied, can-cenn rtppn ecioi hs0&aRpr.Frhroe ete tho Inaspector ner Jim omrpftoyer 0.0l be liablo io any mnrir fr ay 0 prjosilinj~y r ropirr danig ofa Isi;of nykind vtising from of connectiod with this; inrpaction.

a Following completion of-the above, the Cenitifiato of Authorization hle cetn vr,1rsosblt o h

  • system shall completethe following staterens. teOea)rs~sblt o h Wecetiyth ae saerensy hs epnar crrc ad ht hesytm onomstoteCtorgo cnsrctono the ASE Cod Seltomion'1,Dvson ______________._ ___________
1. Installed by Pittsburgh-Des Moinee Corporation. Pittsburgh,_PA
2. Installed for Duuesne Liht CoPittsburgh, PA 3ý 9 Certificate Holder Having Overall Responsibility Stone & Webster Engineering Corv.
4. Location of installation Beaver Valley Unit No. 2, Shipin ort PA
5. System Identification 1369-i116 Dwg. E36 Nat'l Board No. 978 Year !ais i i.9&t rhis letter of certification serves a* a supplement to the N-5 Data Report for cuiration go. 116, National Board No. 978.

rhis penetration vas initially hydrotested in accordance with Code Cave X-32-3. We hereky further certify that this hydrostatic temt, performed in accordance with PDIr1 P eru MrT-5, *Iso complies with Code Case N-32-4 which the owner approved.

M'O~Pr*oje6ct Engineer A jAx e,

-i/'~ /~Ž'

FORM 1/2-ADM-0801.F02 REV 3 PRTL # A4.414-A Form No. 3185 Rev. 1 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/05/09 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 2 (ADDRESS) 2.. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shipninqport, PA 15077 Work Order #200359393 (ADDRESS) Repair/Replacement Organization P-0. No-, Job No., etc.

3. Work Performed By BVPS Construction Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Re-actor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Kerotest 2RCS-59 1978' Removed Yes Valve Velan 051049-1 N/A 2RCS-59 2006 Installed Yes

7. Description of Work Replaced valve with spare.
8. Tests Conducted: Hydrostatic* E] Pneumatic* E] Nominal Operating Pressure N Exempt El Other i Pressure psi Test Temp. OF Pwword test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Serial number of removed valve was not recorded. *Year Applicable Manufacturer's Data Reports to be attached

-installed.

I CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date . N/A Signed T. White Date January 27 , 20 10 Owner-or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period 5 , - cI F to / / - 2 - 0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions -Z7-, .*J /1041i--,? 9"C/

Inspector's 2r ture National Board, State, Province, and Endorsements Date /- 2 V- ,20 /6

DATA PACKAGE NO. 1. 1049 FORM NPV- I CERTIFICATE HOLDERS' DATA REPORT FOR NUCLEAR PUMPS OR VALVES As Required by the Provisions of the ASME Code,Section III, Division 1 Pg. I of 2

1. Manufactured and certified by VELAN INC. 2125 WARD AVE,MONTREAL.QUEBEC CANADA H4MIT6 (name and address ofN Certificate Holder)
2. Manufactured for FRAMATOME ANP - 3315-A OLD FOREST ROAD, LYNCHBURG, VA 24501 (name and address ofpurchas-r)
3. Location of installation NOT AVAILABLE (name and addmzs)
4. Model No., Series No., or Type: B.S.GLOBE Drawing P011-451830-N12 Rev 0 CRN N/A
5. ASME Code, Section III, Division 1: 1995 1996 1 N/A (edition) (addenda date) (class) (Code Case no-)
6. Pump or valve VALVE Nominal inlet size x Outlet size x (ine) (iuS).
7. Material: Body SA-182,F316 Bonnet SA-182,F316 Disk tINS 99644, _Bolting N/

ALLOY 40 (a) (b) (c) (d) (a)

Cert. Nat'l Body Bonnet Disk Holder'Is Board Ser-ial Serial Serial Ser-ial'No. No/ No. No. No -

-- 051049-1 N/A H/C: tMMOIR4 H/C: IDUK H/C: 69K 051049-2 N/A H/C: MMOIR4 H/C: lDUK H/C: 69K 051049-3 N/A H/C: MMOIR4 H/C: 1DUK H/C: 69K 051049-4 N/A H/C: M'MOIR4 H/C: IDUK . i/C- 69K 051049-5 N/A H/C: H~MOIR4 H/C: IDUK H/C: 69K Supplementalirfomson in form oflists, sketches, or drawings may be used provided(]) size is 8 1/2 x'l 1, (2) information in items I through 4 on this Data Report is included on each sheet, (3) each shect is numbered and the number of sheets is recorded at the top of this form.

(12/88) This form (E00037) may be obtained from the Order Dept. ASME_ 22 LAW DR1VZ Ifbx1 2O I 77-3O A.REVA NP Inc.

6P SUP PAGE OF

i FORM NPV-1 (Back - Pg. 2 of 2 Certificate Holder's Serial No. 051049

8. Design conditions 4152 psi 100 o F or valve pressure class 1730 (1)

(preasure) (temperature)

9. Cold working pressure 4152 psi at 100'F
10. Hydrostatic test 6250 psi. Disk differential test pressure 4575 psi
11. Remarks: MATERIALS MEET ASME SECTION II EDITION: 1995 ADDENDA: 1996 CERTIFICATE OF DESIGN Design Specification certified by Francis Gardner P.E. State PA Reg. no. 036614-E Design report certified by S. ISBITSKY P.E. State QUE Reg. no. 22115 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and that this pump or valve conforms to the rules for construction of the ASME Code,Section III, Division 1.

N Certificate of Authorization No. N-2797-1 Expires APR 20,2007 Date FEB 2 1 2OD6 Name VELAN INC. Signed (N Cetifcate Holder) (auth-iz-d rq-p etativc)

CERTIFICATE OF INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of QUEBEC and employed by REGIE DU BATENT of, /QeBeC= have inspected the pump, or valve, described in this Data Report on /Ac4 $/*!d2, , and state that to the best of my knowledge and belief, the Certificate Holder,"has constructed- this pump, or valve, in accordance with the ASME Code,Section III, Division 1.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the component described in this Data Report. Furthermore, neither the inspector nor his 'employer shall be liable in any .mannerfor any personal injury or propert d ge or a loss of any kind arising from or connected wiP.1 tzti 8 7 14 1, Z Date nro.)

signe

( utuozed finspector)

Commissions QUEBEC L OE 0;os -- m (Nat' Bd. (iacL mdrm ents) and state or prnv. and (1) For manually operated valves only.

AREVA NP Inc-OP SUP REG II PGE>~OF 19 I

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A Form No. 3188 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 10/26/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200382345 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Construction Service Type Code Symbol Stamp N/A (NAME)

Shirrinaoort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date , _ "

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity. 2001E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Pipe Schneider Power 2-SWS-120799-1 N/A 2-SWS-006-064-3 1984 Corrected Yes

7. Description of Work Replaced section of pipe.

&:..Tests Conducted: Hydrostatic* [I Pneumatic* L] Nominal Operating Pressure E] Exempt o Other L1 Pressure psi Test Temp. o_F

'Record test pressure.and temperature

FORM 1/2-ADMý0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Oriqinal Code Data Report attached. Replacement 6" NPS Pipe: PO 45312493 1 Ht. #

Applicable Manufacturer's Data Reports to be attached C68250.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section-XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 11 , 2010 Owlaw* or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S'- r2.A_ - 0 Z' to //  ;; - 0 2 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/

Commissions I .J inspector's ýýature National Board, State, Province, and Endorsements AV Date- ,,2020 //

/0

FORM l/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3192 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/06/2009 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shirninrcrtctrt OA 1r[)77 Work Order #200336968 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

. Work Performed By BVPS- Maintenance Type Code Symbol Stamp N/A (NAME)

Shippingnport PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System. Residual Heat Removal (Class 2)
5. (a) Applicable Construction Code Section III 1974 Edition, S'74 Addenda, 1567 Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001-2003 (c) Applicable Section Xi Code Case(s):
6. Identification of Components Corrected, ASME Removed, Code.

Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Heat Exchanger Atlas Industrial 3484 2854 2RHS-E21B 1978 Corrected Yes Mfg.

7. Description of Work Replaced one stud and two nuts.
8. Tests Conducted: Hydrostatic* E] Pneumatic* [] Nominal Operating Pressure [E Exempt 0 Other I] Pressure - psi.-. -Test Temp. oF

'Record test pressure and temperature

FORM i/2-ADM-0801.F02 REV 3, RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached to NIS-2 #1132. Replaced 1-1/8" Stud: PO 45243289, Ht. #

Applicable Manufacturer's Data Reports to be attached 59412 / TRC #0Z84: Nut: PO 47043141, Ht. #223469 / TRC #J858.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. Whith-S. ;taff Specialist Date January 5 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board-of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period -0 o' to J/ - 9r2 - 0 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions /J1 Y'46, / 12,6 d--3 FV Inspec Signature National Board, State, Province, and Endorsements Date

FORM 1/2,ADM.80t1.F02 REV 3 RTL # A4.414-A Form No. 3194 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C .Date 01/14/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 Work Order #200331068 (ADDRESS) Repair/Replacement Organization P-0. No., Job No., etc.

3. Work Performed By BVPS Maintenance Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section XI Code Case(s):
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Henry Pratt D-0014-4-2 N/A 2SWE-MOV116B 1978 Corrected Yes

7. Description of Work Replaced flange screws, taper pins and nuts.
8. Tests Conducte&d' Hydrostatic* Pneumatic*

PI LI Nominal Operating Pressure [] Exempt [

Other El Pressure _ psi Test Temp. °_F "Record test pressure and temperature

FORM'I/2-ADM-080I.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached. Replacement 1-1/4" Screws: P047181824/Ht. #1C34, Applicable Manufacturer's Data Reports to be attached Po 45211642 / Ht. #7CV. PO 47250471 / Ht. #3M26. PO 47167866 / Ht. #QQT. PO 7083355 / Ht.
  1. QQX, PO 47084840 / Ht. #QQT. Replacement Taper Pins: PO 7066665 /-Ht. #52872/08352.

Replacement Taper Pin Nuts: P0 45204136 / Ht. #BJT.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp , N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date February 01 20 10 SO e 'sDesinee, Title CERTIFICATE .OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period d- d -- 0 9- to ,// - 7 - 0 2 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_J, I Inspectors 'r if i /-,-

re Commissions 27> 'J, ,J, 01- Y-Y National Board, State, Province, and Endorsements Date ,20 /0

FORM NPV-1 N CERTflnCATE t5OLDERS' DATA REPOflT FOR NUCLEAR PUMPS OR VAILVES0 Ki equirod by th~e Provision s ol the A WE Cod*, Sect'og Itl. Div' 1 CORITECTED -FORKE

1. mnqW910 1o yPiatt C'o. 900 DOr ot Ave. Dixon, IL 61021 COMEZCTE.D COPY"~

t nd Aaldress of N C rt.ilcate 11lol er)5

&nw F Z

-- f'#~b1~4WJ Beaver .Valley Powor St _______ uquesnec Light Company Ont9 * -1t42 Imam @#Piach~i,4 odtt I Shippingport, Penn Zhul b3

3. Loato of Intllation Pittsburgh, Penn Valve Nomial nle Sie u~ll Sze 0 ,Hext Nut A.P~mporVa"v (a) Modal No.. (6) H Cori~flcaft6o1olierk series No.L Serial (c)C Reog istatitotn

~ ~ 30

~nndion (d) Drawinig Oulei SizeB8 (f) Na( g) Year Should be em

ý&

E or Type . No. No. (a) Class Od. No. Suitt 1100 Series 0-0014 2 N/A C-4485-Rev-2 3 -/A 011 LDu uesne I jhiCivellay (21 jkavýer V-611 3'O abru y T 1 '

Ilumbaci Bnqnce iTbU-p 561 M~antif rtured b~y H~enry I'raltt .03 Atli RhidAVe.

Auruir, I.,. fl Fresh Water Systezm 30" 1100 Selesz W/S1402 5 / 114gcv

0. Dos Canditions 153** -pi 88 / T or Valve Pro* sure 0so /

(1)

7. Catd Working Pressure 275 -psi .0 IW'F.

O. Presture RxleinirC Pieces NS Mark NO. - ,sf*riaif Sec*r.- No.  ! Manuia&urer - Remarks A)cafstim , --

I I

w. SA 216 GR. WC1 Ouaker A11oy IHT! F-1973 v'

.1 K _

Ib) Forging$

I - 4*~'**~

q;_,,t - CU r4, 0% CAA 412 tj'~i* 1~~Z W tý, V*?rýr-*l U're I Aqrl 1 1 ~AGP CrWlA -

j ~ 4 - I Ba*ttf

-- w. .Sha~t 9A qA4 Tvr- ~Al I I

(1) For mrnsn;Iy omerated vetvee only.

Supotemential zs'ers in formv of Sists. sketches os Orrawincjs mey too used pfovided Il I %ize is 4-~' lltz x'.I 7 inrdO 00

.ziýl Oemsu 1. 2 armd 5 on this Date fRe-oort iszincluded on echti hee%. anda (Nir each shett is numbercd end flumbef 0~ tects is fccoltd~ as' lop0 thu folm.

FORtM WPV.-1 .19001)

Mark Nog. fral spr No. M nufacturer eual I Bolting t ---- --

9. - ----- 4 e"'trov- U^14- cz l r-T R7 Fri^ -Aliý ryvý-n J1 Taper Pin Coat CC SA E64 Typ, 630 -

Hex iut SA 194 G.. B8 . Jos.[yson t Son !nc (dl.Other Pants Body Shell S/N 1125138 Po- 5 SA 516-GR. 70 Becth. Steel [TT&2;56055 Bottom Cover Plate s/N -n'4gx:4To.- -

SA 516 CR. T0 Beth. Steel

_____ -- li'T* fOi1M;J-U0 Dot*on Cover S/N 1124937 PO- 5 SA 51 GR. 70 eth. Steel HT_ 1Y.21230,

9. HydruszItlc test 425 psi- Disk {*iff tis! zr pressure N/1_AI psi.

CERTIFICATE OF COMUPLIANCE WV canitVf ths: the stattments mde in this repof wre conrect and that thit puimp. or vv-,, he fulez C4

'f~tat roflstructiofl P1 thje ASYM. Code lor NuhClear Power Plant Componenis. Sect:on liil. Oiv. L** Ed~tion I_____

1171 Acdenda

'0Lntar 1912 ~C~et~.1702 CoeCs N.Dt 0 51516.2 a- z________

Sigid HenrV Pratt Con'any JNN CERTIFICATION OF DESIGN

.ign information on file at *Henry Pratt Co. 401 S. Highland Ave. Aurora, TL 60507 Stress analysis report tClzss , only) on file at N/A IDeni;n speciicaions "-nifed b*- (1) Carl Otto R1i-hardson PE 5tal- PA Reg. No.--61E ktress anIyals certified by V! i, pE Slage ___/A Reg. No.

11) Siotature not required. Lis$ namo only.

CERlTIFICATE OF SHiOP II'SPECTION

1. the wderzigne,d holding a vatid commnission issued by the National board of Boiler erid Pteesufa Vesselh 1

nd the State *- Province of Illinois &.PA - and emp~ovedbyWt &. 1. CO.

of Aartford

  • Connecticut have inspected itc ewmp. of valve. descrttsed in 1hi Dal;: lc--,A ont

__________and s~tate that 0 Ithe be-st of my bnowfege an;, lkelncf, the k I_~tfCj~f.s i;ol "_t-.a~i rton-alfixt~ad this pulrp. ort valve. in accofedance with thte AWME Code. Sctison Ill.

ny i'OfirbR !his Certiicae. no-ther lthe linspector nor hfý employer rnakes any wosiantsy. Cezzfirsld or r-p~r~a~ decriedon this Data flrpomi Fuflhermar.

ll~C netimov 11%e Iri'givcctr nof tits e sli;il li31  ; Ar'-r flrCy

  • tPnrsfonal injury wr propeety d.arniaqv of a l4ois of any ktnd arising fromn of ccignc.;;zd vtti slus in&tetrm.

FORM 1/2-ADM-0801.F02 REV 3 RTL #.A4.414-A Form No. 3195 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/09/09 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit.No. 2 (NAME)

ShitDinaDort. PA 15077 Work Order #200336052 (ADDRESS) Repair/Replacement Organization P.O. No.. Job No., etc.

3. Work Performed By BVPS-Maintenance Type Code Symbol Stamp N/A (NAME)

ShiD*pingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 2)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001-2003 (c) Applicable Section Xl Code Case(s): N/A
6. Identification of Components Colected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Relief Valve Crosby Valve N56900-00-0034 NB-209 2CHS-RV382B 1976 Corrected Yes Spindle Assy. Crosby Valve N88669-38-0071 N/A N/A 1976 Removed No Spindle Assy. Anderson N88669-69-0246 N/A Ht. #528255 2003 Installed No Greenwood Crosby

7. Description of Work Replaced valve spindle assembly.
8. Tests Conducted: Hydrostatic* LI Pneumatic* LI Nominal Operating Pressueg Exempt L]

Other E] Pressure psi Test Temp. oF

'Record test pressure and temperature

FORM- 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Previous NIS-2 Data Report Nos: 1786. 1528. and 513. Oriqinal Data Report attached to

'-- A -"-

.r's,

...... t, pata Reports to be attached -

No. 1528T**,-

  • NIS-2 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 13 2010 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE 'INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owners Report during the period S)'- 4 0Y . to /5 -- 2 - , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions __-_2 ___" ______

Inspe O~s Si ure National Board, State, Province, and Endorsements Date /2-,.0 43 - , 20 / 0

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3198 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner FENOC Date 01/25/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Vallev Power Station Unit No. 2 (NAME)

ShiooinaDort. PA 15077 Order # 200352079 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS- Valve Team Type Code Symbol Stamp N/A (NAME)

Shippinacport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System
5. (a) Applicable Construction Code ASME Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity: 2001-2003 (c) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASMIE Removed, Code Name of Nam. of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve )TT Grinnell 74-10817-9-3 WR1881 2CHS-579 1976 Corrected Installed

7. Description of Work Rebuilt diaphragm valve.

I 8. Tests Conducted: Hydrostatic* LI Pneumatic* E] Nominal Operating Pressure LI Exempt U Other L1 Pressure-.__ psi Test Temp. _F

  • Record test pressure and temperature

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks No Previous NIS-2. Bolting PO/HT#"s Stud: 45310196/3G26 Nut* 7118859/500822 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Justin Sciulli Date January 25 , 2010 Owner or Owner's De46nee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid-commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period . .- -( r to  ! 77 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions ),g 21 / 95?-'-

Inspector's Signature National Board, State, Province, and Endorsements Date a-d 1 201-2010

F'11N1.1jVI \\L !.A. DIE ATA RIEPORT FOP -NUCLEARI P01['S 0H, NVMVFS*

L I2 ITT Gri-neiell Cot?). 'AWr,1ihtsville., Pa ~ 74 1;-~7-9 1)8rcN Westirgio(Noe .Ei~ r.Ph

.ianUfa CtUI d fori CK~t

______ H0 .5 6 ~CCA 19.iOi-

~,~

dAm9 I

3. G ?o~r____ .. V tpny._____

4-' L:,>caio of Pl;ý. Beaver Z. h.SJ :hingp~r Sai Pa.

5- FUME orvulve Idcntficain ITGiel Val-ve 'RWQ WI!TS

~a) ~ SDC-102875- keV.A p J1v W. Bail~ 1 Jr __

()Nton Boird N~o. WR17 tht Ri3 6&nCoridi--o-h 30 .: 1F

7. triatral drxigr., con~zu+icttun, and wo:k-mvi-sitip complics with ASME Code -ction HLtCIe'ss + __

F-~ 1971 D-972 Summera .C~N cik 1540-1 ___ __

74_087_ ___1.- 5_ ___u hL) Forrin-ý i-:-

7-F IZZO---~-

V_ 11, V_ _ .y ~ u

__Jrl.10 4a____ .0 h 1 d ____A t., ________1.___Sj~dw tj s o"clt~3 ý

_ _ K. __ ___I o __

x; FORM N P (-back) - ',

p I..

(c)*

UO1 n+/- 0m

' "7

- 9_

J.. '"_____

p .

f".

I___,i.

  • ~~~ lainvi-l

. r~~fVIL 1.71.L

-7A-1l0317-9 1 -thru 5

~~uts-J ME ýS I9:31 Victo~rProd_______

- I__ ý ..... ,1 , *.. ,.

(d, -O therPart-s. _ _

___L_ _____

RogersGom.N~W V. T1 .. 1 a- Hydrostatic cc. 450 S CIr F.CATION 01 DES1G Dclgi iaxormuo on 51c atj~ 7U 1 Prpvidencý: J ____

C~cfi- bý.- loui-is J. MaiAndra.. (1) PrfE-18O ýt. ~!tz zaA-R.-.N 0llilS Dezignrpi.fca-in I) rrt. Eaii. c Rt Suessl~ Imna3)lsl11 re-pulor cettified bri - -

(1) Slew bturc not reqitired- Lug -narbe onEr.

1/ 1) Stxe Il Wrnei ~ ~ 1KF.K (,

Certificate of Aucmzharion  : ioe0N!",N865 exp9/77 CE 'FICATE OF 0BF I NýFCTI ().

k? ld isy-tica fbY. i~onrd of-Ba~z sic ~d i- re s u r.:e~o

1. the undc~zrer d balding A c ar.ýxSion  %!r~a-.

and/or the Smit- of Prsoviracc Of -P-a. - .t H a,1/2*kord'S tmBri SHartford

  • Cortnt;- hiv____l-cI r~ei! -Ie e~ulr~rnta described in cIhi3 D 19 7 4? a StuicI re :h~ t-om tie: tesc ef nyI . j ri~li belicf, C!ýc 1r'r. 3LCr J Subscrroans 6r AS-.i Cade, Secticu '-If.

has conittracreJi this eq.iipm.ent in accordmncc with the Applicoble cci-By zirning tMs certiiicucci nc'rhec the Jnsspcc~cr nsr hi.v cenp.!;vr n zrry -whrri~ry, cxp.ýsscd or Itnpi:4-iihte r~ze lnspciztor ri r h73 cro~~' e-fl iI .

th cqur~rr in dczc~ibrJ in Alis D -a Report. TFurherniore manier fo,- any pcison~l injury or. properry dair,:tIe o: a x~of~yl~Iriiglo~a oncc ~ twz ~ctn

. rS 3'In)
  • hlU,~v;.,= h~ ,d,Sw . 471In.. ý Nt.~ ~

FORM 1/2-ADM-0801.F02 REV 3 RTL. # A4.414-A Form No. 3199 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 01/13/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) - Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200335450 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS Constrt uction Service Type Code Symbol Stamp N/A (NAME)

Shippinqport, PA 15077 Authorization No. . N/A (ADDRESS)

Expiration Date ".

4. Identification of System Service Water (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section X1 Utilized for Repair/Replacement Activity 2001 E-2003A (c) Applicable Section X1 Code Case(s): N/A
6. Identification of Components Correctds, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Valve Henry Pratt A-0027-8-2 N/A 2SWS-MOV103B 1978 Removed Yes Valve Henry Pratt D-0152-10-1 N/A 2SWS-MOV103B 1980 Installed Yes 7.- Description of Work Replaced valve and 1-1/4" screws.-

8. Tests Conducted: Hydrostatic* E] Pneumatic* El Nominal Operating Pressure Z Exempt E]

Other LI Pressutre psi Test Temp. oF Record test pressure and temperature

FORM 1/2-ADM-080IF02 REV 3 RTL # A4.414-A FORM-NIS-2 4Back)

9. Remarks NPV-1 Data Report attached. Replacement 1-1/4" Screws: PO 4531128 / Ht. #3G84 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorizatio No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 14 2010 Owner or Owner's D;signee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this.

Owner's Report during the period o 2 ..7- 4 0 Z. to 1(-2-? -O " , and statethattothe best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions - ,/ / XJ 3 -'/

Inspector's SiKture ' National Board, State, Province, and Endorsements Date I- -

,20 /__

It-010/0 043 10/16/2009 11:39 FAX FORM NPV-1 N CERTIFICATE HOLDERS' DATA "REPORT FOR NUCLEARl PUMPS OR VALVES-As Required by the Provisions of the AS*IE Code. Section 9W.aiv. 1

1. Ma*ufactured byIle-ar-.. PLa aL-Co*90QfDcpu Atve-._fjxa.u1_I._J_6 Z1 (Name and Adaress of N Certiticate Holder)
2. Manufactured for Tennessee Va c Authority _.y 77K25-820750-1, Har-k # PS0-F-OOIA (Name and Add-rs% of Purchaser or Owrner) 41
3. Locationoflnstallationlart:sv* Ile NucPlants A & B & Phipp~s Bend Nde.Plant. HartsvilleT nn.

(N0.- .a. Address)

4. Pump or Valve Valve . Nominal Inlet Size 24" Outlet Size 24" (inch) (inch)

(a) Model No.. (b) N Certificate Holder's (cl Canadialn A Series No. serial Registiation (d) Drawing IfI Nat'l. Ig) Year or Type No. No. No. (a) Class 8d. No. Built 111 1100 Ser-jes D-0152-10-1 N/A C-S516 Rev-2 2 N/A 1980 (2)

(3)

(4)

(7)

(1)

(910

5. Water Service Systerm (Bref dtacripu of servc fa EmWtNd equipment WASGlesignedl

'24" 1100 Ses W/SMBOO15/43BC G. Design Conditions 100 psi 150 "F or Valve Pressure Class 150

7. Cold Woking Pressure 275 L psi at 100"F.

I. Pressure Retaining Pieces Mark No. Material Spec. No. Manufacturer Remarks 4A)Castings ... .

tb) Fdzgings

  • op Shaft SA 564 Typ. 630 Cartech HT# 22481 Cond. 1150 F _

Bottom Shaft SA 56h Tyn 610 _ _rt__h __ 9T# 22481 Cond 1150 F III For manually operated valves only.

Supplarontal sheets in form of lists, sketches or drawings may be used provided (1) size is SA1W2x 11, ('2) information in Item* 1, 2 And S on this Data flepout is included on each sheet, and 13) each sheet Is numbered and number of sheets Is recorded at lap of this form.

(to/7l ThIs form (E000371 mwy be obtained from the Order Dept.. ASME. 345 E. 47th St- New York. N.Y. 10017 ji

10/16/2009 11:40 FAX  ! 0011/0043 FORM NPV-1 (Back)

Mark No. Material Spec. No. Manufacturer flemarks I - t - 4 (c) Bolling I

  • I

-$ I Z

kr.ltn.e Cnver Rnlt SA lq't cit it Rltm oerBlt SA__93___B7_________E__0

_lq,,rcze Pin, rde CR SA 320 GR. 18M Cartech HT# 842749 1d) Other Parts Body Shell s/N 1331563 NO-i SA 516 GR. 70 Rerh - 51pp HT# 803H87090 Disc Plate S/N 1263464 1,-7 SA 240 GR. 304 Eastern S.S- Co. WTC4 F-40RIR Disc HFh

'-I S1 1149913 gO-7T . 0 CA dC U"

CD ~ifl

. jaftjj - arpej

  • n-v1RO1*O710 I 'U-A 8OIE20710 Cod le BD =/ 'qM SA 516 GR- 70 B.~etJ' st-el FIO~IrNwORn0.

-9. Hydosmttic 425 psi: Disk Differentil rest pros-u._*SO.D,.

CERTIFICATE OF COMPLIANCE psi.

A We certify that the statements made in this report are correct and that this pump, of valve, conforms to the rules of construction of the ASME Code (or Nuclear Power Plant Componentsr Section Ill. Div I Eition .77 Addends / Code Case No. NIA N/J* Date Dae 7/10/8 /810o Signed "Henry Pratt Cn. by (iN Cerliilcate Nfolderi Our ASME Certificate of Authorization No. N_1. 13 ta use the NL/ symbol expires HayF.- 6 19*L.

CERTIFICATION OF DESIGN Design information on file at Henry Pratt CO.401 S.Highland Ave. Aurora.IL' 60507 Stress analysis report (Class I only) on file at N/A Design specirfcations certified by(i) Alex1 Wa s~enkrn PE State Cal Rag. No. C 22109'

  • Stress analysis certified by (1 NI/A PE State -NI Reg. No. N/A (1) Signature not required. List name only.

CERTIFICATE OF SHOP INSPECTION IL the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel InspectolC and the State or Province of I I I i-nois and employed by H S .8.1 & 1 CO.

of .-. prtrOtr .Connecticut - have inspected the pump, or valve, described in this Data Report on JRL 1 0 19 ,ands.,tethat to thebestof my knowledge end belief. theN CertificatenHolderhaaco-r-stcted this pump. or valve. in accordance with the ASME Code, Section Ill-By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied. concerning the equipment described in this Data Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arisinC Ironaor connected with this.inspection.1

. & C. CCTEN7 . JR OILUNOIS- 104-7 Date 19 R KL WCZJB3 OHIO12-8-78 lIns.sa6e.i ) omm S ons INert Rd.. Stata. Pro-, aod t~e-I

__ -' ---..--- _~.....

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A Form No. 3204 Rev. 1 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xl

1. Owner F.E.N.O.C Date 01/27/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShioDinaDort. PA 15077 Work Orders 200378010, 200361987, 200392534, 200334948 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Westingqhouse/PCI Enerqy Type Code Symbol Stamp N/A (NAME)

Lake Bluff, IL 60044 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W'72 Addenda, N/A Code Case (b) Applicable Edition of Section X1 Utilized for Repair/Replacement Activity. 2001E-2003A (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corre'ed, ASME Removed, Code Name of Nam. of Manufacturer National Board Other Year Mr Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Reactor Vessel Combustion Engr. CE-9071 21669 2RCS-REV21 1975 Corrected Yes

7. Description of Work Performed embedded flaw repairs on J-weld and tube OD on penetrations 49

& 57. Removed unacceptable indications on penetration 51.

8. Tests Conducted: Hydrostatic* El Pneumatic* L] Nominal Operating Pressure Z Exempt L]

Other E] Pressure psi Test Temp. _ OF "Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 R.TL # A4.414-A FORM NIS-2 (Back)

9. Remarks Previous NIS-2 Data Report Nos: 3043, 1973, 1656, and 1128. Weld overlays on Applicable Manufacturer's Data Reports to be attached Penetrations 49 & 57 were performed in accordance with BV Relief Recuest 2-TYP-3-RV-03.

Penetration 51 was corrected in accordance with ASME Construction Code acceptance criteria.

Work was performed by Westinqhouse/PCI under the FENOC ASME Section XI prowram.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Wes Williams Staff Enqineer Date February 10 20 10 Owner or Owyes Designee, Ti le CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period ..5--- .7_- - K to J/ -,2 ( 7, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section -Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions )(1,6 9 F ins s Signature National Board, State, Province, and Endorsements Date 20 /0

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3205 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section Xd

1. Owner F.E.N.O.C Date 11/12/2009 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShinDinaoort. PA 15077 Work Order #200392332 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS-Construction Service Type Code Symbol Stamp N/A (NAME)

ShiDpinciport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Residual Heat Removal (Class 2)
5. (a) Applicable Construction Code Section Ill 1974 Edition, S'74 Addenda, 1567 Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001-2003 (c) Applicable Section XI Code Case(s): N/A
6. Identification of Components Corrected; ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Instatled (Yes or No)

Heat Exchanger Atlas Industrial 3483 2853 2R.HS-E21A 1978 Corrected Yes Mfg.

Support Atlas Industrial N/A N/A 2RHS-E21A-A-1 1978 Corrected Yes Mfg.

Support Atlas Industrial N/A N/A 2RHS-E21A-A-2 1978 Corrected Yes Mfg.

7. Description of Work Replaced three support gusset plates and repaired other.
8. Tests Conducted: Hydrostatic* E] Pneumatic* LI Nominal Operating Pressure LI Exempt 0 Other LI Pressure psi Test Temp. OF

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached to previous NIS-2 #1133. Supports are NF per W spec.

Applicable Manufacturer's Data Reports to be attached Replaced 1/2z" qusset support plates: PO 7124481, Ht. #D60685. Note: on R/R Plan and weld travelers - support 2RHS-E21A-A-1 is "A-1-1" and "A-1-2", and support 2RHS-E21A-A-2 is "A-2-1" and "A-2-2".

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorizatioji No. N/A Expiration Date N/A Signed T. Whit44ý? Staff Specialist Date January 5 20 10 O er or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period J- ,-.- 0 Y to //-- 1, 9 -O ", and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions ,-8 - -,"*".' ,A ?y Inspecto ' ature National Board, State, Province, and Endorsements Date , 20 / 0 Date - -. 20 /0

FORM 1/2-ADM-0801.F02 REV 3 RTL 4 A4.414-A Form No. 3206' FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY

__As Required by the Provisions of the ASME Code Section XI

1. Owner First Energy Nuclear Operating Company Date 12/14/09 (NAME) 76 South Main Street - Akron OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station Unit No. 2 (NAME)

Route 168 - ShioDinaoort. PA 15077 Westinohouse P.O.# 7024829 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS/ITech. Services Eng. Type Code Symbol Stamp N/A (NAME)

Route 168 - ShiooingDort, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date N/A

4. Identification of System Reactor coolant
5. (a) Applicable Construction Code ASME Section 111 19 71 Edition, S'72 Addenda, See N-1 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs/Replacement Activity: 2001 Edition. 2003 Addenda (c). Applicable Section X1 Code Case(s) N/A
6. Identification of Components Corrected, ASME Removed. Code Name of Name or Manufacturer National Board Other Year 'or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or NO)

Steam Westinghouse DMGT-1961 W-16598 2RCS-SG21A 1977 Corrected Yes Generator

7. Description of Work Installed 76 Inconel 690 plugs (38 tubes). Installed stabilizers in 35 of those tube locations. Installed helicoil in bolt hole #5 of secondary side hand hole #1.
8. Tests Conducted: Hydrostatic* D Pneumatic* E] Nominal Operating Pressure [] Exempt [

Other Ei Pressure N/A psi Test Temp. N/A °F

'Record test pressure and temperature

FORM I/2-ADM-0801.F02 REV 3 RTiL # A4.414-A FORM NIS-2 (Back)

9. Remarks Primary side order 200334182, secondary side orders 200334182 & 200334183.

Applicable Manufacturer's Data Reports to be attached Installed new aaskets on primary manwavs secondarv side hand holes & inspention norts

~iI* ~

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Gary Alberti, SG Proiect Manaqer L = aN.,-A-*t Date January 4 , 2010 Owner or Owner's Designee, Title Q CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of PA and employed by HSB CT of Hartford. CT have inspected the components described in this Owner's Report during the period -- - - (3 9W to /( - ) ? -1 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By-signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury orproperty damage or a loss of any kind arising from or connected with this inspection.

Commissions 1-13 /7/*

Inspector'>ature National Board, State, Province, and Endorsements Date Date , /0/0

FORM ]/2-ADM-0801.F02 REV 3 RTL # A4,414-A Form No. 3207 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner First Enerov Nuclear ODeratina ComDanv Date 12/14/09 (NAME) 76 South Main Street - Akron OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station Unit No. 2 (NAME)

Route 168 - Shippinqport, PA 15077 Westinahouse P.O.# 7024829 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS/Tech. Services Eng. Type Code Symbol Stamp N/A (NAME)

Route 168 - Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date N/A

4. Identification of System Reactor coolant
5. (a) Applicable Construction Code ASME Section III 19 71 Edition, S72 Addenda, See N-1 Code Case (d) Applicable Edition of Section XI Utilized for Repairs/Replacement Activity: 2001 Edition. 2003 Addenda (e) Applicable Section XI Code Cai'-s(iy -N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identifiection Built Istalled (Yes or No)

Steam Westinghouse DMGT-1962 W-16599 2RCS-SG21B 1977 Corrected Yes Generator

7. Description of Work Installed 46 Inconel 690 plugs (23 tubes). Installedstabilizers in 13 of those tube locations.
8. Tests. Condulcted: Hydrostatic* FD Pneumatic* D] Nominal Operating Pressure [] Exempt Dl Other F-1 Pressure N/A psi Test Temp. N/A °F

'Record test pressure and temperature

,FORM 1/2-ADM-080].F02 REV 3 RTL 4 A4.414-A FORM NIS-2 (Back)

9. Remarks Primary side order 200334184, secondary side order 200334185.

Applicable Manufacturer's Data Reports to be attached lnstalled new Gaskets on the orimarv manwavs, secondarv side hand holes & inspection nodts Installed new'oaskets on the Drimary manways secondary side hand holes & inspection norts CERTIFICATE OF COMPLIANCE..

I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Gary Alberti, SG Proiect Manager )-=s ,)V-.-*-* Date January 4 , 2010 Owner or Owners Designee, Title (*)

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of PA and employed by HSB CT of Hartford, CT have inspected the components described in this 2

Owner's Report during the period .j-- )- - F to // - A 7 - 0 ? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning-the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

A&os.-e- to Inspector's nature, Commissions ,Jd4,Z- /L-National Board, State. Province, and Endorsements Date /- (,, - /o

FORM 1/2-ADM-080 .F02 REV 3 RTL 4 A4.414-A Form No. 3208 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner First Enerav Nuclear Ooeratina Companv Date 12/14/09 (NAME) 76 South Main Street - Akron OH 44308 Sheet 1 of 2 (ADDRESS)
2. Plant Beaver Valley Power Station Unit No. 2 (NAME)

Route 168 - ShiDDinaDort, PA 15077 Westinahouse P.O.# 7024829 (ADDRESS) RepaidReplacement Organization P.O. No., Job No., etc.

3. Work Performed By BVPS/Tech. Services Eng. Type Code Symbol Stamp N/A (NAME)

Route 168 - Shippinqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date N/A

4. Identification of System Reactor coolant
5. (a) Applicable Construction Code ASME Section III 19 71 Edition, S'72 Addenda, See N-1 Code Case (f) Applicable Edition of Section Xl Utilized for Repairs/Replacement Activity: 2001 Edition. 2003 Addenda (g) Applicable Section Xl Code Case(s) N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Steam Westinghouse DMGT-1963 W-16600 2RCS-SG21C 1977 Corrected Yes Generator

7. Description of Work Installed 62 Inconel 690 plugs (31 tubes). Installed stabilizers in 26 of those tube locations. Re-established Dhonoaraohic finish on four (4) insoection Dorts (vessel Dad.l
8. Tests Conducted: Hydrostatic* ED Pneumatic*[I Nominal Operating Pressure ZI Exempt E]

Other D Pressure N/A psi Test Temp. N/A °F

'Record test pressure and temperature Page 2 of 2

FORM 1/2-ADM-0801 .F02 REV:3 RTL #,A4.414-A FORM NIS-2 (Back)

9. Remarks PrimaryVside order 200334198, secondary side orders 200334199 & 200334200.

Applicable Manufacturer's Data Reports to be attached Installed new oaskets on the Drimarv manwavs, secondary side hand holes & insDection Dorts.

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI."

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Gary Alberti, SG Proiect Manager A , Date January 4 , 2010 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of PA and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period -'I--L' - 0 F to /(- 2- ? - G , and state that to the -

best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 10e ) ,4'.

1 J?-t-/ Y A 3 Inspector' ature National Board, State, Province, and Endorsements Date ,/0 Page 2 ofl2

FORM 1/2-ADM-0801.F02 REV 3 RTL # A:4.414-A Form No. 3209 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 11/12/2009 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 Work Order #200392524 (ADDRESS) Repair/Replacement Organization P.O. No.. Job No., etc.

3. Work Performed By BVPS-Construction Service Type Code Symbol Stamp N/A (NAME)

Shippincqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Residual Heat Removal (Class 2)
5. (a) Applicable Construction Code Section I11 1974 Edition, S'74 Addenda, 1567 Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity. 2001-2003 (c) Applicable Section X1 Code Case(s): N/A
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Heat Exchanger Atlas Industrial 3484 2854 2RHS-E21B 1978 Corrected Yes Mfg.

Support Atlas Industrial N/A N/A 2RtHS-E21 B-B-l 1978 Corrected Yes Mfg.

Support Atlas Industrial N/A N/A 2RHS-E21B-B-2 1978 Corrected Yes Mfg.

4.* -*, .. -

7. Description of Work Replaced two support qusset plates and repaired two others.

8.- Tests Conducted: Hydrostatic* E] Pneumatic* E] Nominal Operating Pressure FI Exempt [

Other LI Pressure psi Test Temp. oF Recofd test pressure and temperature

FORM 1/2-ADM-080LF02 REV 3 IPTL # A4.414-A FORM NIS-2 (Back)

9. Remarks Code Data Report attached to NIS-2 #1132. Previous NIS-2 Data Report Nos: 3192, Applicable Manufacturer's Data Reports to be attacded 2083, and 1132. Supports are NF per W spec. Replaced 1/2" qusset support plates: PO 7124481, Ht. #D60685. Note: on R/R Plan and weld travelers - support 2RHS-E21 B-B-1 is "A-1-1" and "A-1-2", and support 2RHS-E21 B-B-2 is "A-2-1" and "A-2-2".

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed T. White Staff Specialist Date January 9 , 20 10 OwnAr or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period "- ,. - Y to / (- - 7 - 13 I , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

J,- 24ý ý1ý Inspector's -Siq re ACommissions (-'I8 /? Ih'WZý, A4 ý ý'

National Board, State, Province, and Endorsements Date i-f D (- 1 20 / P

FORM 1/2-ADM-0801 .F02 REV 3 RTL # A4.414-A -

Form No. 39a417 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By technical Services Enqr Type Code Symbol Stamp N/A (NAME)

Shippincqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Main Steam (Class 2)
5. (a) Applicable Construction Code Section Ill 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61265/11 N/A 2MSS-PSSPOI IA Removed No Snubber Lisega 30900139/023 N/A 2MSS-PSSPO I1A IInstalled No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* El Pneumatic* Ej Nominal Operating Pressure El Exempt M Other Ml Pressure psi Test Temp. _ OF
  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed 4 , Date j--i. ,/j, 20 10 Owner or Owner-s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period 7,-ok--.- ( 7 to .// J- '7 - () , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions --- '- /d'¢... >7 National Board, State. Province, and Endorsements lnspectoý

ýnature 9

Date Dat

.2 20 10 1

FORM 1/2-ADM-0801.F02 REV 3 RTL WA4.414-A Form No. 3_

FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippingport, PA 15077 200338887 (ADDRESS) RepairlReplacement Organization P.O. No.. Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

ShioDinaDort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Main Steam (Class 2)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (d) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (e) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61265/12 N/A 2MSS-PSSPOI lB --- Removed No Snubber Lisega 30900139/022 N/A 2MSS-PSSPO1 IB --- Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* [ Pneumatic* E] Nominal Operating Pressure LI Exempt 1K Other R Pressure psi Test Temp. oF

'Record test pressure and temperature

FORM 1/2-ADM-080L F02 REV 3 RTL # A4.414i-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Date 20 20 10 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period - 0

  • to (- 2 2 - 0? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Ac29~2J2 Inspector's Sn e Commissions *"-LA*3 National Board, State, Province, and Endorsements Date D 20 10

FORM I/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3ai  ?

FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShippinqIport, PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Enqr Type Code Symbol Stamp N/A (NAME)

Shippinclport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (f) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (g) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61195/130 . N/A 2CHS-PSSP0O6 Removed No Snubber Lisega 30900222/006 N/A 2CHS-PSSP0O6 Installed No

7. Description of Work Replaced snubber with a spare for testinq/refurbishment purposes
8. Tests Conducted: Hydrostatic* LI Pneumatic* E] Nominal Operating Pressure [] Exempt [

Other EL Pressure psi Test Temp o_F I--

-.. 'Redord iest pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Date U-v Z 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period -"1 - 0 to //- - ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage.or a loss of any kind arising from or connected with this inspection.

Inspect 2

'L(

~'gnature Y Commissions /

National Board, State, Province, and Endorsements Date / -z- 7 , 20 10

FORM 1/2-ADM-080I.F02 REV 3 RTL # A4.414-A Form No. 3;L.-O FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shinninnnort PA 150l77 200338887 Shinninnnort (ADDRESS)

PA 15077 RepairlReplacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services-Enqr Type Code Symbol Stamp N/A (NAME)

Ship pingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (h) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 - 2003 Edition (i) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61211/20 N/A 2CHS-PSSP015X Removed No Snubber Lisega 30800392/096 N/A 2CHS-PSSP015X Installed No

7. Description of Work Replaced snubber with a spare for testinq/refurbishment purposes
8. Tests Conducted: Hydrostatic* El Pneumatic* E] Nominal Operating Pressure L] Exempt ['

Other LI Pressure. psi Test Temp. oF Record test pressure and temperature

FORM I/2-ADM-0801.F02 REV 3 *RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed . Date _ o__L_ _ _ _ , 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period , dJ-".-0 Y- to /1 - aL- ; - 0 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions - /tK /'t4,,. .

Inspector' %;'nature National Board, State, Province, and Endorsements Date /- 01 201 20 10

FORM 1/2-ADM-0801 .F02 REV 3 RTL # A4.414-A FormNo. 3.a FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 11 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinciport, PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

Ship pingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (C) Applicable Section Xl Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61211/38 N/A 2CHS-PSSP017X Removed No Snubber Lisega 30800392/094 N/A 2CHS-PSSP017X --- Installed No

7. Description of Work Redplceds-rr-uNer with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* El Pneumatic* E] Nominal Operating Pressure El Exempt M Other FI Pressure psi Test Temp. _ OF Record test pressure and temperature

FORM 1/2-ADM-080].F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF. COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed - e.

Owner or Owner's gesignee, Title Date 20 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel' Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period . -- ,' - 0 ' to /1 * . 0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

________________ Commissions - //.,

Inspecto r National Board, State, Province, and Endorsements Dae-2r1 Date , 20 10

FORM l/2-ADM-0801.F02 REV 3 RTL # A4.414-A Form No. 3222 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shippinwport, PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No.. Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section Xl Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No.-d*t i -. *.

2 ". Built Installed (Yes or No)

Snubber Lisega 61211/70 N/A 2CHS-PSSP025X Removed No Snubber Lisega 30800392/092 N/A 2CHS-PSSP025X Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes,
8. Tests Conducted: Hydrostatic* El Pneumatic* E] Nominal Operating Pressure LI Exempt [

Other LI Pressure psi Test Temp. _ OF

  • Record test pressure and temperature

FORM I/2-ADM-080I.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _ e, Date -"l £6 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period JoLc 9 to //- cL 2 - 7 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

J, 27-ý Y, tnspector~'sgnature Commissions *-"-, ,d /0,+,.-3,. (/

National Board, State, Province. and Endorsements Date a 20 10

FORM 1/2-ADM-080).F02 REV 3 RTL # A4.414-A Form No. 3223 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 200338887 (ADDRESS) Repair/Replacement OrganizationP-.0 No., Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

Ship pincqport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Chemical and Volume Control (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name or Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61211/15 N/A 2CHS-PSSP66OX Removed No Snubber Lisega 30800392/091 N/A 2CHS-PSSP66OX __. Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* D Pneumatic* LII Nominal Operating Pressure [] Exempt Z Other F] Pressure psi Test Temp. - °OF

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was reDlaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xt.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed orL/e 1,6 - $ i. Date a7ro-r"I. 20 10

- Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period .)-d- - ) 9- to /1 2 ' - 0? , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this..

Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions -7 /1J, -- 7,3 Inspector's 0 tureNainlBad ttroncndEosens National Board, State, Province, and Endorsements Date , 20 10 Date 20 10

FORM 1/2-ADM-0801 .F02 REV 3 RTL # A4.414-A Form No. 3224 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShinninaoDort. PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

Shinoinaoort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section XI Code Case(s): None
6. Identification of Components-~-

Corrected, ASME Removed, Code Name of Name of Manufacturer National Board . Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61211/52 N/A 2RCS-PSSP0OIX Removed No Snubber Lisega 30800392/095 N/A 2RCS-PSSPOOIX --- Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* nI Pneumatic* E] Nominal Operating Pressure [: Exempt Z Other E] Pressure psi Test Temp. _ OF ......
  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.4 14-A FORM NIS-2 (Back)-

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed -ed c-- Date _ "__:;_, __20 10 OwAer or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period .'-d- - 0 Y to / / 2 - () , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions _"

  • g Inspector's Sg National Board, State, Province, and Endorsements Date , 20 10 Date 20 10

FORM 1/2-ADM-080I.F02 REV 3 RTL,4.A4.414-A Form No. 3225 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of,the ASME Code Section Xl

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

ShiDoinaDort. PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

ShioDinaDort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Coolant (Class 1)
5. (a) Applicable Construction Code Section Ill 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section XI Code Case(s): None 6: Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No Identification Built Installed (Yes or No)

Snubber Lisega 61211/06 N/A 2RCS-PSSP035 Removed No Snubber Lisega 30800392/093 N/A 2RCS-PSSP035 Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic*ElI Pneumatic* LI Nominal Operating Pressure [: Exempt [

Other LI Pressure psi Test Temp. o_F

  • Record test pressure and temperature

FORM 1/2-ADM-0801 .F02 REV 3 'RTC* # A4.4t4-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Oat6 Reports to be attached CERTIFICATE OF COMPLIANCE I certify that-the statements made in the report are correct and that this conforms to the requirements of the ASME Code,Section XI.

Type Code Symbol Stamp N/A.

Certificate of Authorization No. N/A Expiration Date N/A Signed A e Owner or Owner's Designee, Title Date 20 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period ' .)_ ' - 0 - to //9 -- ' - , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions -', /J " .

tnspec~~tflature National Board, State, Province, and Endorsements Date S,20 10

FORM 1/2-ADM-080] .F02 REV 3 RTL # A4:414-A Form No. 3226 FORM NIS-2 OWNER'S REPORT FOR REPAIRS/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E N. O.C Date 1/26/10 (NAME) 76 South Main Street- Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 200338887 (ADDRESS) Repair/Replacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Reactor Plant Drains (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section XI Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber . Lisega 61211/35 N/A 2DGS-PSSP879 --- Removed No Snubber Lisega 30900222/005 N/A 2DGS-PSSP879 Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* E] Pneumatic* El Nominal Operating Pressure [] Exempt [

Other Li Pressure psi Test Temp. OF

'Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2D (Back)

9. Remarks The snubber-was reiplaced with a new sn~are.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A

.Signed*

Ownel'or Owner's Designee, Title Date Sign.ed Dt2 20 1 10 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period - - ý - 6 T to // - -- ? - 0 ' , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section X1.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4po inspector's Sjfijafture -National CommissioNs ti oar, ateoieo e Board, State. Province, and Endorsemen-ts Date /- a-- -1 , 20 10

FORM 1/2-ADM-0801.F02 REV 3 RTL #4 A4.414-A Form No. 3227 FORM NIS-2 OWNER'S REPORT FOR REPAIRS!REPLACEMENT ACTIVITY As R5equired by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Valiev Power Station (BVPS) Unit No. 2 (NAME)

Shippinqport, PA 15077 200338888 (ADDRESS) RepairlReplacement Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Enqr Type Code Symbol Stamp N/A (NAME)

ShinDinonort, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "_

4. Identification of System Auxiliary Feedwater (Class 3)
5. (a) Applicable Construction Code Section 111 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c). Applicable Section Xl Code Case(s): None
6. Identification of Components Corrected, ASME Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 61211/80 N/A 2FWE-PSSP354A Removed No Snubber Lisega 30800392/087 N/A 2FWE-PSSP354A Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* E] Pneumatic* [] Nominal Operating Pressure L1 Exempt [

Other EL Pressure psi Test Temp. o_F tRecord est pressure and lemperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new snare Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Date C -I. 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period S oz d- - -I to //-,1- -/ 0 t , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4sze ý Commissions 1,/ " /A z-, F-/

National Board, State, Province, and Endorsements Inspector's Signa*

Date 20 1 Date , 20 10

FORM -/2-ADM-0801.F02 REV 3 RTL # A4.:414-A.

Form No. 3228 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron, OH 44308 Sheet 1 of 1 (ADDRESS)
2. Plant Beaver Vallev Power Station (BVPS) Unit No. 2 (NAME)

ShiDoinaoort. PA 15077 200338888 (ADDRESS) Repair/Replacement Organization P.O. No.. Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

ShiDDinaDort. PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date

4. Identification of System Auxiliary Feedwater (Class 3)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section Xl Code Case(s): None - -
6. Identification of Components Corrected, ASM11E Removed, Code Name of Name of Manufacturer National Board Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber . Lisega 61211/88 N/A 2FWE-PSSP354B Removed No Snubber Lisega 30800392/090 N/A 2FWE-PSSP354B Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* E] Pneumatic* ] Nominal Operating. Pressure [I Exempt [

Other F] Pressure psi Test Temp. oF

  • Record test pressure and temperature

FORM 1/2-ADM-080.F02 REV 3 RTL # A4.4]4-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a new spare.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE -OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A SignedOwner r Date Jc-,-, 20 110 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford, CT have inspected the components described in this Owner's Report during the period 2- d - 0 ? to /t-- 2 - 0 7 , and state that tothe best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

1_ý J Z"'I .

Inspect:ature Commissions ._- , ,,/ /,- 7,. -

National Board, State, Province, and Endorsements Date at,20 10

FORM 1/2-ADM-080] .F02 REV 3 RTL # A4.414-A Form No. 3229 FORM NIS-2 OWNER'S REPORT FOR REPAIRSIREPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code Section XI

1. Owner F.E.N.O.C Date 1/26/10 (NAME) 76 South Main Street - Akron. OH 44308 Sheet 1 of 1

. (ADDRESS)

2. Plant Beaver Valley Power Station (BVPS) Unit No. 2 (NAME)

Shiooinooort, PA 15077 200344402 (ADDRESS) Repair/Replacemenl Organization P.O. No., Job No., etc.

3. Work Performed By Technical Services Engr Type Code Symbol Stamp N/A (NAME)

Shippingport, PA 15077 Authorization No. N/A (ADDRESS)

Expiration Date "

4. Identification of System Residual Heat Removal (Class 1)
5. (a) Applicable Construction Code Section III 1971 Edition, W72 Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 2001 - 2003 Edition (c) Applicable Section X1 Code Case(s): None
6. Identification of Components Corrected, ASIvME Removed, Code Name of Name of Manufacturer National Board , Other Year or Stamped Component Manufacturer Serial No. No. Identification Built Installed (Yes or No)

Snubber Lisega 6885 N/A 2RBS-PSSP521X --- Removed No Snubber Lisega 5048 N/A 2RHS-PSSP52LX Installed No

7. Description of Work Replaced snubber with a spare for testing/refurbishment purposes
8. Tests Conducted: Hydrostatic* LI Pneumatic* El Nominal Operating Pressure LI Exempt [

Other F] Pressure psi Test Temp. oF

  • Record test pressure and temperature

FORM 1/2-ADM-0801.F02 REV 3 RTL # A4.414-A FORM NIS-2 (Back)

9. Remarks The snubber was replaced with a used spare rotated from stock, but the removed.

Applicable Manufacturer's Data Reports to be attached Snubber was not tested - IWA-4132(h)

CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section X1.

Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed _ je e Date .  ; .2, , 20 10 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Pennsylvania and employed by HSB CT of Hartford CT have inspected the components described in this Owner's Report during the period o--,--

7 to / . -(7' O? and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions - ' /64.*f; "" .

Inspectors nature National Board, State, Province, and Endorsements Date a 20 10