L-24-199, Discharge Monitoring Report (NPDES) Permit No. PA0025615
| ML24274A084 | |
| Person / Time | |
|---|---|
| Site: | Beaver Valley |
| Issue date: | 08/22/2024 |
| From: | Kristophel R Vistra Operations Company |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| L-24-199 | |
| Download: ML24274A084 (1) | |
Text
August22,2024 L-24-199 eDMR for Electronic Submission Department of Environmental Protection Bureau of Water Quality Management 400 Waterfront Drive Pittsburgh, PA 15222
SUBJECT:
Beaver Valley Power Station 200 State Route 3016 P.O.Box4 Shippingport, PA 15077-0004 Beaver Valley Power Station Discharge Monitoring Report {NPDES) Permit No.
PA0025615 Enclosed are the July 2024 NPDES Discharge Monitoring Report (DMR), Chemical Additives Usage Forms, Daily Effluent Monitoring Forms and Cooling Water Intake Monitoring Forms in accordance with the requirements set forth in the site NPDES permit. Also attached is the Clamicide Application Report for 2024 system dosing completed in July.
A review of the data indicates that no Part A NPDES effluent limits were exceeded during the reporting period.
Should you have any questions regarding the enclosed documents, please direct them to James Harvey, at 724-682-7358.
Sincerely, istophel (Aug 22, 2024 06:48 CDT)
Robert Kristophel General Plant Manager
Beaver Valley Power Station, Unit Nos. 1 and 2 L-24-199 Page2 Enclosure(s):
A.
Monthly Discharge Monitoring Report B.
Chemical Additives Usage Forms
- C.
Daily Effluent Monitoring Forms D.
Cooling Water Intake Monitoring Forms Attachment(s):
- 1.
Clamicide Application Report cc:
Document Control Desk US NRG (NOTE: No new US NRG commitments are contained in this letter.)
L-24-199 ENCLOSURE A
3800-FM-BCW046212/2016 pennsylvania J~ DEPARTMENT Of ENVrnONMENTAL
'6l:!2i!I PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Flnal Effluent PARAMETERS REPORTED VALUES PARAMETER Temperature (deg F) (00011)
Sample Measw,;ment P<<mlt Requlfement pHi00400)
Snmpl:e~mt::nt Permit Requirement
-n(00610)
Sample Measurement Penni!--
Pf'ltmolcs, Total (32730)
Sample Meas.urement Permit Requirement Chromium, Total (01034)
Sampkl, Measurement Permit Requirement Copper, Tota! (01042)
S4lmp{e MMswemfint Permit Requiremem Iron, Total (01045)
Sample Meas.uement Permit Requ!rement Zinc, Tola! {01092)
Ptmnit Requirement
.Aluminum, Total {0110$)
Sample Mtu?Swement Permit Requirement Flow (50050)
Bamplo Measurement PctmltR~ment Tota.t ~esldue.l Chlorine (TRC) (50060)
Sample Measurement Permit Requirement Nelw H150M (51698)
Sample Measurement Permii~irffllent Free Ava~ Ctilodne (50054)
$ampbtMeasurement Permn Requirement Mercury, Total (71900}
Sample Measurement Permit Requirement Hydrazine (81313)
~Moaswement Permlt Re(lu!rement Fiu~Ully Sampllng Point Comment&
COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 001 PERMIT NUMBER MONITORING PERIOD VEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Repolting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTllY OR CONCENTRATION VALUE VAWE UNITS VALUE VALUE VALUE UNITS 92.8
'F 110 Dal>,Max 7.5 s.u.
6.l) s.o lnsl!.tin IMAX m
GG GG mg/I.
Montlor&Rcport Monitor& Report Avg Mo Dal>,Max
< ~1
<,01 mg/I.
Monllor & Report Monllor&Repod A'<9Mo DaitJMax GG GG mg/I.
.2
.2 Avg Mo Dal~Ma,
.0061
.0071 mg/I.
Monl10<&-
Momtof& Report AvgMo
~Max
.42 mg/I.
Monftot&Report -=,:,::Ort AvgMo GG GG mg/L 1.0 1.0 Avg Mo DailyMax
.26
.28 mg/I.
Monlt0<&Report Monlklr&Report Avg Mo Daily Max 43.1 46.3 MGD Mon1tor&Repott MOl"lilor & Report AvgM<>
DaityMax
<.111
.17 mg/I.
~
1.25 Avg Mo IMAX
<,034
< Jl34 mgll
.034 Jl34 Avg Mo Dal~Ma,
<.06
.16 mg/I.
.2
.5 Avg Mo Dal>,Ma,
<.2
<.2 ug/1.
.2
.2 Avg Mo OailyMax GG GG mg/I.
.007
.001 Avg Mo OaityMax Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 D
SAII/IFUNGFREQUENCY SAMPLING TYPE 1/day 1-l!
1/day 1-S 1-k 1-*
Gmb 11w..,
Grab 2/monlh G,.b 2}montn Grab 1-2,4,Htc.,,_,..
GMb 1-24-Hf Composikt 2if1'l0f'11h Grab 2/rnonlh Grab Continuous Measured Contlm*ous Meas.ured 1/woek Grab 1/week GMb 24-Hr(:omposlt&
24-Hrc.mpo.il<
Continuous Recorded ContirlU0\\1$
Roeo"
2/month Grab 2/moolh Grab 1fwook Grab
3800-FM-BCW046212/2016
~
~
DEPARTMENT OF ENVIRONMENTAL f.iii:2, PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, "4308-201" FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
'-'Fl::.:n:::*lc.::E::.:fflc::ucc*:.cnl:__ ____________
PARAMETERS REPORTED VALUES PARAMETER Flow (50050)
Sample Measurement Permit Requ!remen1 Fadlty Samp8ng Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 002 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 202" 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS
.046
.046 MGD Monitor&Report Monitor& Report Avg Mo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/202" 07/31/2024 10/31/2026 05/04/2026 SAMPLING FREQUENCY SAMPLING TYPE 1/week Estimate 1ANeek Estimate
3800-FM-BCW046212/2016
~
~
DEPARTMENT DF ENVIRONMENTAL
'6 PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
'-F"-ln"'a'-'I Eccffl=ue'-'n""t ______________ _
PARAMETERS REPORTED VALUES PARAMETER Ammonia.Nitrogen (00610)
Sample Measurement Permit Requirement Aluminum, Total (01105)
Sample Measurement Permit Requirement Flow (50050)
Sampe Measurement Permit Requirement Nalco H150M (51698)
Sample Measurement Permit Requirement Mercury, Total (71900)
Sample Measurement Permit Requirement Hydrazine (81313)
Sample Measurement Permit R~qt.drement Facility Samping Point Comm*nts COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 003 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Penni! Expires:
Penni! Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS GG GG mg/l.
Monitor & Report Mon!tor&Report Avg Mo Daily Max 26
.35 mg/l.
Monltor&Report Monitor&Report Avg Mo Daily Max
.235 276 MGD Monitor&Report Monitor&Report Avg Mo Daily Max
<.034
<.034 mg/l.
.034
.034 Avg Mo DaltyMax
<2
<2 ug/L 2
2 Avg Mo DallyMax GG GG mg/l.
,007
,007 Avg Mo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2028 05/04/2026 SAMPLING FREQUEt~CY SAMPLING TYPE Grab 2hnonth 24-Hr Composite 2hnonth 24-Hr Composite 2/month Estimate 2/month Estimate 1/week Grab 1/week Grab 2hnonth Grab 2hnonth Grab Grab
3800-FM-BCW046212/2016 pennsylvania J,,;;;tg DEPARTMENT OF ENVJRONMENTAL
'&2'J PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, "4308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
'-F"'lna=I E=cffl=ue"'n'-'t ______________ _
PARAMETERS REPORTED VALUES PARAMETER Temperature (deg F) (00011)
Sample Measurement Permit Requirement pH(00400)
Sample Measurement Permit Requirement Chromium. Total (01034)
Sample Measurement Permit R&quirement Copper, Total (01042)
Sample Measurement Permit Requirement Zinc, Total (01092)
Sample Measurement Permit Requirement Aluminum, Total (01105)
Sample Measurement Perm!! Requirement Flow(50050)
Sample Measurement Permit Requirement Tota! Residua! Chlorine (TRC) (50060)
Sample Measurement Permit Requirement Free Available Chlorine (50064)
Sample Measurement Permit Requlrement Facility Sampling Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 004 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effecfive From:
DMR Effecfive To:
Permit Expires:
Permit Applicafion Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 89.9
'F 110 OaityMax 7.5 7.5 s.u.
6.0 9.0 lnstM'fl IMAX GG GG mg/L 2
.2 Avg Mo DailyMax
.0036
.0036 mg/L Monitor&Report Monltor&Report Avg Mo Daily Max GG GG mg/L
,.o 1.0 Avg Mo Dally Max 24
.24 mg/L Monllor&Report Monitor& Report Avg Mo Daily Max
.435 5.78 MGD Monitor&Report Monitor & Report A,gMo Dally Max
.04
.04 mgil
.5 125 AvgMo IMAX
<.02
<,02 mg/L 2
.5 Avg Mo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 D
SAMPLING FREQUENCY SAMPLING TYPE 1/day 1-S 1/doy 1-S 1/week Grab 1/week Grab 1/week 24-Hr Composite 2/mon1h Grab 2/momh Grab 1/week 2+Hr Composite 2/month Grab 2/month Grab 1tweek Galculation 1tweek calculation 1/week Grab 11.-eek Grab 1/week Grab 1/week Grab
3800-FM-BCW046212/2016 8
pennsylvania J~ DEPARTMENT OF ENVIRONMENTAL
'lli:if!!! PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
_Fl_n_al_E_ffl_u_o_nt ______________
PARAMETERS REPORTEO VALUES PARAMETER Flow (50050)
Sample Measurement Permit Requirement FacUlty SampRng Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 006 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
OMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS
.016
. 016 MGD Monitor&Report Monitor& Report Avg Mo Daily Max Privacy Polley I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 D
SA.~PUNGFREQUENCY SAMPLING TYPE 1/week Estimate 1/week Estimate
3800-FM-BCW046212/2016
~
~
DEPARTMENT OF ENVIRONMENTAL
'ca' PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, "4308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
e-F.c.lna=I E~ffl.c.u.c.e.c.n.c.t ______________ _
PARAMETERS REPORTED VALUES PARAMETER Temperature (degF)(00011)
Sample Measurement Pennit Requirement pH(00400)
Sample Measurement Pennlt Requirement Fbw (50050)
Sample Measurement Permit Requiremenl Total Residual Chlorine (TRC) (50060)
Sample Measurement Permit Requirement Nalco H150M (51698)
Sample Measurement Pennlt Requirement Free Available Chlorine (50064)
Sample Measurement Pennlt Requirement FacDlty Sampling Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 007 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS
'F 110 -
DailyMax s.u.
6.0 9.0 Inst Min IMAX MGD Monitor&Report Monllor&Report Avg Mo DaiJyMax mg/L
.20 Dally Max mg/L
. 034
.034
_Avg Mo Daily Max mg/L 2
.5 Avg Mo Daily Max Privacy Polley I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 0
SAMPLING FREQUENCY SAMPLING TYPE 1/day Grab 1/week Estimate Grab Grab 1/week Grab
3800-FM-BCW046212/2016
~
~
DEPARTMENT Of ENVIRONMENTAi.
,~ PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP AODRESS:
168 E MARl<ET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Final Effluent PARAMETERS REPORTED VALUES PARAMETER Temperarure (deg f) (00011)
SampleM~
Permit Requimmeni pH(00400) 5ample Measurement Permit Requirement
.... (50050)
Sample Measurement P~rt Requirement Total l<esldua!Chb!ne (TRC)(50060)
Sample Mea$Ul'$'ment Pennit Requirement Nako H150M (51698)
Pennit Requirement Free Avallable ctuoMe (50064}
Sample Measurenwnl Permit Requ!mment Me.:ury, Total {71900)
Sample Measurement Permit Requirement FacUltySampSng PolntCommont.
COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 010 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
OMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTlfY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 85.1
'F 110 DaitJMax 7.4 7.9 S,lL 6.0 9,0 lnstM!n IMAX 4.25 U2 MGO m
m MOllllor&l!ep<>tl MonitOr&Report AV!JMo OallyMax m
.13 mg/L
.20 Oall)'Max
<JJ>4
,ngll JJ34
.034 A'IJMo Qa!lyMax.
<JJ7
.12 mg/L
.2
.5 Avr,tl.o Dai~-
<.2
<.2 Ug/L Moni!or&Report -&-
Avg Mo OaltyMax Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 D
SAMPLING FREQUENCY SAMPLING TYPE tlday
~*
1/day
~
1/week Grab Grab 1/weel<
1/weok Grab 1/week
- Greb 24-HTC-1/week 24-11,~
Grab Grob
- >Jmonlh Grab
- lim<>nlh Grab
3800-FM-BCW046212/2016
~
~
OEPAATMEITT OF ENVIRONMENTAl
,a PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
169 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA. 15977 STAGE':
_Fl_na_l_E_ffl_ue_nt _____________ _
PARAMETERS REPORTED VALUES PARAMETER FIOw (50050)
Sam,leM-Pennit Requlrement
-.u,y, total(71900)
$ample Measurement Permit Requirement Facility Sampling PolntComme-nta COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 011 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permtt Appliealion Due:
No Discharge:
QUANTITY OR LOAOING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS
,004
.004 MGD OH
- H Monltor&Report Monitor&Report
- tt Avg Mo DaityMax
<.2
<.2 ug/1.
fl.
.2
.2 AvgM<>
Dally Max Privacy Polley I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/3112024 10/31/2026 05/0412026 SAMPLING FREQUENCY SAMPLING TYPE Estima!<>
E.-
2/mon!h Grab
3800-FM-BCW046212/2016
~
~
DEPARTMENT OF ENVIRONMENTAL
'&a° PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
_F_ln_a_l E_ffl_u~e~n~t ______________ _
PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sample Measurement Pennit Requirement Cadmium, Total (01027)
Sample Measurement Permit Requirement Copper, Total(01042)
Sample Measurement Permit Requirement Zlnc, Total (01092)
Sample Measurement Permit Requirement Fbw(SOOSO)
Sample Measurement Pennit Requirement Facility Sampling Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 012 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 7,7 7,9 s.u.
6,0 9.0 Inst Min IMAX
<.001
<.001 mg/L Monltor&Repoft Monitor & Report Avg Mo Daily Max
.161 27 mg/L Monitor&Report Monitor & Report Avg Mo Dally Max
.578 1.1 mg/L Monltor&Report Monitor&Report Avg Mo Da!lyMax
.001
.001 MGD Monitor & Report
~onltor & Report Avg Mo DaitjMal(
Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 SAMPLING FREQUENCY SAMPLING TYPE 2/month Grab 2hnoo1h Grab 2/monlh Grab 2hnoo1h Grab 2/month Grab 2/month Grab 2hnoo1h Grab 2hnoo1h Grab 2/month Estimate 2hnoo1h Estimate
3800*FM-BCW046212/2016 pennsylvania J~ DEPARTMENT OF ENVIRONMENTAL
'C!f!!J PROTEc:TJON NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 1son STAGE:
Flnal Effluent PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sample Measuremet1t Permit Requ!tument Copper, Totatt01042)
Sampk, Mea.sutement f>erm!tRequ!rement Flow (50050)
Semple Measurement Potmit Requirement f'Klllly Samplng Poln1 Conmlenta COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 013 PERMIT NUMBER OUTFALL NUMBER MONITORJNG PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permtt Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY DR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 6.4 7.3 s,u.
6.0 9.0 mstMin IMAX
.0039 mg/L ow Manltor&Report Monitor & Report A,gMo llalt,Max
.002
.002 MGD Morutor&Reporl Monrtor&ftepot1 AvgMo
!l<!lyMax Privacy Policy ( Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/111/2024 07/31/2024 10/31/2026 05/04/2026 SAMPLING FREQUENCY SAIIIPIJNG TYPE 2/monlh Gr,b 2/rnonlh Grab 2/monlh Grab Grab Estimate 2/momh
3800-FM-BCW046212/2016
~
~
DEPARTMENT OF ENVIRONMENTAL
,.a PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sample Measuramenl Permit Requirament Tolal Suspended So ids (00530)
St\\mpla Measurement PemillRequircment 00 aq:i Grease (00556}
Samiite Measurement
~rmil Requirement
""""°nla,Njjrogen(D0610)
Sample Measurement Permit Requirement fbw(50050)
Sample M&astuement Permit Requirement Hydrazine (81313)
Sample Menurerrumt Pem'llt Requirement Fadltty Sampling Polnt Comm*nU COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 101 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 01 31 Reporling Fraquency:
OMR Etreetive From:
OMR Effective To:
Permit Expires:
Penni! Applieation Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 7.4 s,u, 6.0 9,0 lnStMin IMAX
<4.1 4,4 30.0 100.0 Avg Mo OaifyMall:
<4.9
<5.0 mgll.
15D 20,0 Avg Mo D""1Mw<
GG GG mgll.
Monltor&Report Morifor&Repotl A,gMo DailyMax
,018
,031 MGD Monlb)t&Report Mooitor & Report
. AvgMo*,
Oali;'Mm<
GG 00 mgll.
Monitor&Report Moriitor a Report Avg Mo Dall)/Max Privacy Polley I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07101/2024 07/31/2024 10/31/2026 05/04/2026 D
SAr~PUNGFREQUENCV SAMPLING TYPE Grab 1-Grab 1/week Grab Grab Grab 1/wffk Grab Grab 1/week 1/w<ek Estil1'la!e Grab
3800-FM*BCW0462 12/2016 pennsylvania J...-.&' DEPARTMENT OF ENVIRONMENTAL
'11:!111 PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
lnmmal MonHortng Point PARAMETERS REPORTED VALUES PARAMETER pH (00400)
Sample Measumm&nl Total Suspended So&ds (00530)
Pennl!Requl,._.
Oil and GN:taiw (00556)
Sample Measurement PermilRtiq,.drnrnent ftlw(S0050)
~
Measurement Permit Requirement Factlity Snmping Politt Conunentt COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 102 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VAWE VALUE UNITS 6.9 7.0 s.u.
6.0 9.0 tnstMin IMAX C4,0
<4.0 mgli.
30.0 100.0 Avg Mo DallyMa.a:
<4,8
<4.9 mgll 20.0 A,gMo Dall;'M.,.
.801
.001 MGD Mon!lof&RePQrt Monlior & Report A,gMo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07131/2024 10/31/2026 05/04/2026 SA.ll!IPLING FREQUENCY SAMPLING TYPE Grab
>Jmonth G
2Jm<mth G..t, 2/month Grab Grab 2im<mth Grab Estrmate Emlmata
3800-FM-BCW0462 12/2016 pennsylvania r~ 01:PAATMENT OF ENVIRONMENTAi.
'/1.!!!!!1 Pl!OTECT!ON NAME:
i:NERGY HARBOR NUCLEAR CORP AOORESS:
161 E MARKET ST, AKRON OH, 44308-201, FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sampt& MoaMt(tlment Permit Requlromenl Total SUspi.,nded so,ds (00530}
Swnpto Me~menl Pe:mlt Requirement Oil and Grease (00556)
Sample Measurement Pmnlt Requirement Flow(S0050)
Sample Measurement PermH Requirement Facility Samping Point Commonts COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 103 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO OAY YEAR MO OAY FROM 202, 07 01 TO 2024 07 31 Reporting Frequency:
OMR Effeclive From:
OMR Effective To:
PermH Expires:
Permit Application Oue:
No Oischarge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 6,8 7.6 s.u.
6.0
. mstMin IMAX
<4.0
-<4,0 mglL 30.0 100.0 Avg Mo OailyMax
<5,1
<5.3 m,j/1.
15,0 20,0 A,gMo Or,a!!yMex 235
.269 MGO Monnor & R$por1 Monllor&Rep<<t
- d Avg Mo OailyM!n(
Privacy Polley I Security Polley Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 SAMPLING FREQUENCY SAMPLING TYPE 2/mcntt>
Grab 2/moott>
G,.,,
2/month See Permit 2/month SeePennit Grab 2/month Grab 2/month Estimate 2fmonth Estimate
3800-FM-BCW046212/2016 pennsylvania J,al!!J DEPARTMENT OF ENVIRONMENTAL
'Cf3 PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER Flow (5005D)
Sample Measurement Permit Requirement Tota! Residual Chlorine (TRC) (50060)
Sample Measurement Pennlt Requirement FacUlty Sampling Point Commenta COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 108 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permtt Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS MGD Monitor & Report Monitor& Report Avg Mo Daily Max.
mg/L Monitor& Report Morwtor&Report Avg Mo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 0
SAMPLING FREQUENCY SAMPLING TYPE Weekly when Discharging Estimate Weekly when Discharging Grab
3800-FM-BCW046212/2016
~
~
DEPARTMENT OF ENVIRONMENTAL
,.a.,. PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sample Measurement Pennit Requirement Total Suspended Soids (00530)
Sample Measurement Permit Requirement Oil and Grease (00556)
Sample Measurement Permit Requirement Flow (50050)
Sample Measurement Permit Requirement FacDHy Sampling Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 111 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 6.5 7.2 s.u.
6.0 9.0 Inst Min IMAX
<4.8 6.0 mg/L 30.0 100.0 Avg Mo DailyMax
<4.9
<5.0 mg/L 15,0 20.0 Avg Mo OollyMex
.002
.002 MGO Monitor&Report Monitor & Report Avg Mo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 SA.l\\!PLING FREQUENCY SAMPLING TYPE 1/week Grab 1/week Grab 1/Week Grab 11week Grab 1/Week Grab 1/Week Grab 1/week Estimate 1/Week Estimate
3800*FM-BCW0462 12/2016 pennsylvania J~ DEPARTMENT OF ENV!RONMENTl\\l
'61.a PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308°2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH (00400)
Sample Measumrmmt Permit Requlrnment Total Suspended Soldo (005311)
S&mr>le Measumment Permit Requlromerrt Oil al'ld Grease (00556}
SSntpl& Measurement Perm.ti Requirement Flow (50050)
Sample Measurement Permlt Requirement Fncmty Sampling Pclnt Comment.a COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 211 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Repomng Frequency:
DMR Effective From:
DMR Effective To:
Permlt e.pires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 6,8 3.1 s.u.
6.0 9.0 lns!Mln IMAX
<6.4 11,5 mglL
- JJJ,0 100.0 AvgMo OaiJyMa.:
<4.9
<5,0 mglL 15.0 20.0 Avg Mo Deily-
.002
,002 MGO Monilor&Report AV9Mo OeilyMa><
Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07101/2024 07/31/2024 10/31/2026 05/04/2026 SAMPLING FREQUENCY SAMPLING TYPE 1/week Grab 1M'eek Gmb 11.....
Grab Grab Grab 1/week Grab Estimate 1/week Estimate
3800.fM*BCW046212/2016 pennsylvania NAME:
DEPARTMENT OF ENVIRONMENTAL PROTECTION ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWl!R STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
lnmmal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER Total SU$pended Sotids (00530)
Sample Measurement Poo:nltlwquirement Oil and Grease (00556)
SarrlJ)le Measurement l'etmlt-n1 Flow (50050)
P<,,ml!-
Facmty Sampling Polnt Comtmtnts COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 301 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
OMR Effective FrQm:
OMR Effective To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS mg/I.
3C.O 100.0 Avg Mo DallyMax mg/I.
15,0 21).0 AvgMo Oai!yMax MGO
,,_&_ Monllor&Report
°""'"""
Privacy Policy I Security Polley Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 0S/!14/2026 0
SAMPLING FREQUENCY SAMPLING TYPE 2/month Gmb 2/monttl Grab Estimate
3800-FM-BCW046212/2016
~
~
DEPARTMENT DF ENVIRONMENTAL f..e!;, PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 150n STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sample Measurement Pennlt Requirement Total Suspended Solids (00530)
Sample Measurement Pennlt Requirement Oil and Grease (00556)
Sample Measurement Permit Requirement Fbw(SOOS0)
Sample Measurement Permit Requlremen~
FacDity Sampling Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 303 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
Permil Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS s.u.
6,0 9.0 Inst Min IMAX mg/L 30,0 100.0 Avg Mo DaityMa:x mg/L 15.0 20.0 Avg Mo Dally Max MGD MonilorAReport Monitor& Report A"9Mo Dally Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 0
SA.'!!PLING FREQUENCY SAMPLING TYPE 2/mooth Grab 2/month Grab 2/month Grab 1/week Estimate
3800-FM-BCW046212/2016 pennsylvania J~ DEPARlMENT Of ENVl!lOl'lMENTJ\\L
'.:a PIIOTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, '4308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH (00400)
Sample"'-!
Permit Requirement Total-ed Solos (00530)
Semple Measurement Permtt Requirement Oil end Grease (005$6}
Sam.t;lc M&asufflnenl PermitReql.lWment Fbw(50050)
Measurement Permlt Requirement Facility Samping Point Comm*RU COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 313 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR Effective From:
DMR Effective To:
PermH Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS 6.3 7.4 s.u.
6.0 9,0 IM\\Min
!MA)(
<5.0 6.9 mg/I..
30,0 100.0 Dall)'Max
<~.9
<5,0 mg/I..
15 20 AvjJMo DaltyM;;ix
,002
.ooz MGO Monltor&Report MfflitDf&Report
"""M*
°""""
Privacy Policy ( Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07101/2024 07131/2024 10/3112026 05/0412026 SAMPLING FREQUENCY SAMPLING TYPE 11week Grab 1/week G..,,
1/week Grab 1/week G..,,
1/week G..,,
1/week Grab 1/week Estimate f?stimata,
3800-FM-BCW046212/2016 pennsylvania r,iJ//i/l!J DEPARTMENT OF ENVIRONMENTAL
'11/:S PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, "4308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
lntomal Monitoring Point PARAMETERS REPORTED VALUES PARA.METER pH(00400)
Sample Measurement Permit Requirement Total S11$pended So!ds (00530)
Sample Measurement Penn!! Requirement Oil and Grease (OOSSS)
Sample Measurvment Penn1tRe,qu:itemrurt Fbw(50050)
Sample Measurement
~rmit Requirement Facility &wplng Point ccmtntnta COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 401 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
OMR Effective From:
OMR Effeetlve To:
Perm~ Expires:
Permit Application Due:
No Discha!ge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VAWE UNITS 7.fJ s.u.
e.o m
IIISIMln
<4J)
<4.0 mgJl.
m 30.0 100.l)
Avg Mo l)sllyMax
<4,9
<4.9 mgJl.
15.0 20.0 Avg Mo O,ilyMox
.001
.001 MOD Mooltor & Report Monitor & Report A"!Jl.lo Dally""'
Privacy Polley I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 SAMPLING FREQUENCY SAMPLING TYPE 2/month Grab 2/monlh G..i.
2/month Grab 2/month Grab 2/monlh Glab 2/monlh Grab
- 11wee, Estimate 1/wee<
E&tlmate
3800-FM-BCW0462 12/2016 9
pennsylvania J,.;J![J DEPARTMENT OF ENVIRONMENTAL
'&:a PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
Internal MonHorlng Point PARAMETERS REPORTED VALUES PARAMETER pH (00400)
Sampte Measurement Permit Requirement Total Suspended So5ds (00530)
Sample Measurement Permit Requirement Oil arxt Grease (00556)
Sample Measurement Permit Requirement Ammonia-Nitrogen (00610)
Samp!e Measurement Permit Requirement Chromium, Total (01034)
Samp!e Measurement Permit R~uirement Zinc, Total (01092)
Sample Measurement Pennlt Requirement Flow (50050)
Sample Measurement Permit Requirement Total ResJdual Chlorine (TRC) (50060)
Sample Measurement Permit Requirement Nalco H150M (51698)
Sample Measurement Permit Requirement Hydrazine(81313)
Sample Measuremenl Pennlt Requirement FacUlty Sampling Point Comments COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 403 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
DMR EffecUve From:
DMR EffecUve To:
Permit Expires:
Permit Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS s.u.
6.0 9.0 Inst Min IMAX mg/L 30.0 100.0 Avg Mo DailyMax mg/L 15.0 20.0 Avg Mo Dally Max mg/L Monltor&Report Monitor& Report Avg Mo Daily Max mg/L 2
.2 Avg Mo O211y'Max mg/L 1.0 1.0 Avg Mo DailyMax MGD Monilor&Report Monitor& Report Avg Mo Daily Max mg/L
~
1.25 Avg Mo IMAX mg/L
.034
.034 Avg Mo Dally Max mg/L
.007
.007 Avg Mo Daily Max Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07/01/2024 07/31/2024 10/31/2026 05/04/2026 121 SAMPLING FREQUENCY SAMPLING TYPE Weekly when Discharging Grab Weekly wllen Discharging Grab Weekty when Discharging Grab Weekly when Discharging Grab Weekly when Discharging Grab Weekly when Discharging Grab Weekly when Discharging Estimate Weekly when Discharging Grab Weekly when Discharging Grab Weekly when Discharging Grab
3800-FM-BCW0462 12/2016
~
~
DEPARTMENT OF ENVIRONMENTAL
,a PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGV BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
lntomal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH (00400)
Sarnpkl Measurement PermitRequ~
Total Suspended Sofds (00530)
Sample Measurement Permit Requirement Oil and Grease {00556)
Samptu Measuromenl PennitReqlrir&ment (00610)
Smf4)le Measurament PermltReqt.'ltemenl Fk>w(50050)
PemutRequifM!Ont Hydtazin<,(81313)
&.arnpteMeasuromenl Perm!t Requiromenl FadUty &mplng Point Comm*nts COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 601 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO OA.Y FROM 2024 07 01 TO 2024 07 31 Repol1ing Frequency:
OMR Effective From:
OMR Elleclive To:
Permit Expires:
PermH Application 01.1&:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS s.u.
6.0 9.0 lnstMin IMAX mQ/1.
30.0 100.0 A,gMo OaityMax mQ/1.
15.0 20.0 Avg Mo DallyMax mQ/1.
Monitor& Report
""""""&Report Avg:Mo DallyMax MGD MoMor&Report Monitor & Report A,gMo Dally-mQ/1.
Monltor&Report Monitor & Report Avg Mo Oe!JyMwc Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Month!>>'
07/01/2024 07/31/2024 10/31/2026 05/04/2026 0
SAMPLING FREQUENCY SAMPLING TYPE Grab 1-G,..
1t...k Grab 1/w,ek Grab E-Grab
3800-FM*BCW046212/2016 pennsylvania J~ DEPARTMENT OF ENVJRONMENTAl
'.:::at PROTECTION NAME:
ENERGY HARBOR NUCLEAR CORP ADDRESS:
168 E MARKET ST, AKRON OH, 44308-2014 FACILITY:
FIRSTENERGY BEAVER VALLEY POWER STATION 1 LOCATION:
PA ROUTE 168, SHIPPINGPORT PA, 15077 STAGE:
lnlomal Monitoring Point PARAMETERS REPORTED VALUES PARAMETER pH(00400)
Sample Measurement Permit Requirement Tatar Suspended SOids {00530)
Samptc M<tasumment Permit Requirement 0!1 end Grease- (00556)
Sarnpfo Measurement Permit Requitemenl
--*(00610)
Sample Measurement Permit Requirement Flow (50050)
Sampfe,MeasumlTl9nt Pe:"'" R-rrt Hydrazil"te{81313)
Sample Measw:emeflt Permit Requirement faclnty Sampling Point Comm*nta COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
PA0025615 701 PERMIT NUMBER OUTFALL NUMBER MONITORING PERIOD YEAR MO DAY YEAR MO DAY FROM 2024 07 01 TO 2024 07 31 Reporting Frequency:
OMR Effective From:
OMR Effective To:
Permit Elq)lres:
PermH Application Due:
No Discharge:
QUANTITY OR LOADING QUANTITY OR CONCENTRATION VALUE VALUE UNITS VALUE VALUE VALUE UNITS s.u.
6.0 9.0 lnSIMll"I IMAX mg/L 30.0 100.0 Avg Mo DailyMax mg/L 15.0 20.0 A'igMo
""'lY"""'
mg/L Momlot & Report Monitor & Report AvgMo OailyMa>c MGO Monltor&Report M9nltor&Report
,w Avg Mo llallyMax mg/I.
Monltor & Report Monltor&Repott AvgMo DailyMax Privacy Policy I Security Polley Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved Monthly 07101/20.24 07/31/2024 10/31/2026 05104/2026 0
SAMPLING FREQUENCY SAMPLING TYPE 1/woel<
Grab Grab 1/week Grab Grab I/woe!<
Esti-1/week Grab
3800-FM-BCW046212/2016
~
~
DEPARTMENT OF ENVIRONMENTAL
,a,. PROTECTION ATTACHMENT DETAILS FlloNamo BVPS July 2024 Chemical Additives Usage Forms.pdf BVPS July 2024 Cooling Water Intake Monitoring Forms.pdf
_BVPS July 2024 Cover Letter..pdf BVPS July 202-4 Daily Effl.lent Forrns.pdr BVPS DMR Attachment Cbmlcide Report July 2O24.pdf PERMIT VIOLATIONS Non-Compllance ID E:vont Stut Date Event End Date UNAUTHORIZED DISCHARGES Parameter UnlltT,Pe Non-Compllance ID Event Start Dato Event End Date Dato and Time Discovered OTHER PERMIT VIOLATIONS Non-Compliance ID Non~ompDanco Type COMMENT DETAILS COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF CLEAN WATER DISCHARGE MONITORING REPORT (DMR)
Attactun.nt TJpe Uploaded Time Chemical Additives Usage Fonn 2024-08-22:T14:15:53-04:00 Attachment ColTUMf1tl
- Othe, 2024-08-22T14:16:28-04:00 BVPS July 202-4 Cooing Water intake Monitoring Fonns Cover letter Daily Efh.,ent Monitoring Form
- Olhe, Reported Value Permit Limit Event location 61:mpUng Point 2024-<l8-22T14:14:O3-04:00 2024.08-22T14:15:16-04:00 202<Mm-26T06:22:00-04:00 Clamicide App6cation Report Unit Samplng Point cause Of No~mpUance Volume (gal)
Duration (hrs)
Receiving Water& Impact On Watera Cauu Of Dlschargo Parametor Reporwd Value Correctlv. Action Date and Time DEP Notified Omly Permit Limit Comments Comments Comments Comments Operator Certification Number Operator Contact Number SUBMISSION INFORMATION
- Pursuant lo the Pennsylvania Electronic Transactions Act. Act 69, effective January 15, 2002, you are about 10 engage in an electronic transaction TELEPHONE DATE with the Commonwealth of Pennsylvania. You are submitting official Information. You certify under penally of law that this documenl and all Robert Kristophel (724) 682-7773 2024 08 26 attachments were prepared under your direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on your inquiry of the person or persons who manage the system or those persons directly responsible for SUBMITTED BY gathering the Information, the information submitted Is, to the best of your knowledge and befief, true, accurate and complele. You are aware thal any AREA CODE NUMBER YEAR MO DAY false slalemenl may be subject to substantial civil and criminal penalties, including 18 P.S. section 4904 (relating lo unswom falsification lo authorities).
FULL NAME Privacy Policy I Security Policy Copyright ©2016 Commonwealth of Pennsylvania. All Rights Reserved
L-24-199 ENCLOSURE B
e ~!;!~;2'.!~,!!_
SUPPLEMENTAL REPORT* CHEMICAL ADDITIVES USAGE 3B00-FM-BCW0439 3/2014 Facility Name:
Beaver Valley Power Station - Unit 1 Month:
_J_u_.ly __________ _
Year:
2024 Municipality:
Shippingport Borough County:
Beaver NPDES Permit No.:
PA0025615 Outfall:
001 Watershed:
Ohio River Renewal application due 180 days prior to expiration.
This permit will expire on:
October 31, 2026 Chemical Names _
Control Brom Cts-Surfactant I Dispersant Nalco Act1 Brom l:HOCide Nalco Dechlorination Bleach Liquichlor 70 Nalco 73550 3DT-120 Nalco 1318 H-150M Nalco 7408 Nalco CL-50 Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
632.0 22.0 0.0 25.0 0.0 0.0 39.0 0.0 2
824.0 26.0 0.0 25.0 0.0 0.0 46.0 0.0 3
0.0 0.0 0.0 25.0 0.0 0.0 15.0 0.0 4
0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 5
0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 6
0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 7
0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 8
0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 9
0.0 0.0 0.0 25.0 0.0 69.0 0.0 0.0 10 0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 11 549.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 12 824.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 13 686.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 14 0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 15 0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 16 0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 17 0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 18 696.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 19 698.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 20 663.0 0.0 0.0 25.0 -
0.0 0.0 0.0 0.0 21 679.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 22 729.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 23 0.0 0.0 0.0 25.0 0.0 31.4 0.0 0.0 24 774.0 0.0 0.0 25.0 0.0 0.0 48.0 0.0 25 824.0 0.0 0.0 25.0 0.0 0.0 48.0 0.0 26 784.0 0.0 0.0 25.0 0.0 0.0 47.0 0.0 27 625.0 0.0 0.0 25.0 0.0 0.0 46.0 0.0 28 702.0 0.0 0.0 25.0 0.0 0.0 45.0 0.0 29 0.0 0.0 0.0 25.0 0.0 0.0 9.0 0.0 30 0.0 0.0 0.0 25.0 0.0 0.0 0.0 0.0 31 0.0 0.0 0.0 25.0 0.0 0.0 32.0 0.0 Average 344.8 1.5 25.0 3.2 12.1 Maximum 824.0 26.0 25.0 69.0 48.0 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By: James Harvey License No.: ----------------
Title:
Senior Environmental Specialist Date:
8/12/2024 lbs
~
l 3800-FM-BCW0439 3/2014
,;,- e!!:'!'!~!0~.~!120~rnoN SUPPLEMENTAL REPORT* CHEMICAL ADDITIVES USAGE Facility Name:
Beaver Valley Power Station
- Unit 2 Month:
July Year:
_2_0_24 ___ _
Municipality:
Shippingport Borough County:
Beaver NPDES Permit No.:
PA0025615 Outfall:
001 -----
Watershed:
Ohio River Renewal application due 180 days oriorto expiration.
This permit will expire on:
October 31, 2026 Chemical Names Control Brom Cts-Sunactant Dispersant Nalco tslOCide Nalco Dechlormat1on Bleach Liquichlor 70 Nalco 73550 3DT-120 H150-M Nalco 7408 Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
0.0 0.0 0.0 16.0 0.0 0.0 2
466.0 19.0 27.0 16.0 0.0 0.0 3
0.0 0.0 0.0 16.0 0.0 0.0 4
582.0 23.0 27.0 16.0 0.0 0.0 5
582.0 23.0 27.0 16.0 0.0 0.0 6
582.0 23.0 27.0 16.0 0.0 0.0 7
582.0 23.0 27.0 16.0 0.0 0.0
~
582.0 23.0 27.0 16.0 0.0 0.0 9
0.0 0.0 0.0 16.0 0.0 0.0 10 0.0 0.0 0.0 16.0 0.0 0.0 11 582.0 23.0 27.0 16.0 0.0 0.0 12 582.0 23.0 27.0 16.0 0.0 0.0 13 582.0 23.0 27.0 16.0 0.0 0.0 14 582.0 23.0 27.0 16.0 0.0 0.0 15 932.0 37.0 27.0 16.0 0.0 0.0 16 0.0 0.0 0.0 16.0 87.2..
0.0 17 874.0 35.0 27.0 16.0 0.0 0.0 18 655.0 26.0 27.0 16.0 0.0 0.0 19 582.0 23.0 0.0 16.0 0.0 0.0 20 582.0 23.0 27.0 16.0 0.0 0.0 21 582.0 23.0 27.0 16.0 0.0 0.0 22 0.0 0.0 0.0 16.0 0.0 0.0 23 0.0 0.0 0.0 16.0 0.0 0.0 24 582.0 23.0 27.0 16.0 0.0 0.0 25 582.0 23.0 27.0 16.0 0.0 0.0 26 582.0 23.0 27.0 16.0 0.0 0.0 27 466.0 19.0 27.0 16.0 0.0 0.0 28 349.0 15.0 27.0 16.0 0.0 0.0 29 0.0 0.0 0.0 16.0 0.0 0.0 30 0.0 0.0 0.0 16.0 94.3 0.0 31 0.0 0.0 0.0 16.0 0.0 0.0 Average 402.3 16.0 17.4 16.0 5.9 Maximum 932.0 37.0 27.0 16.0 94.3 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By: James Harvey License No.: ----------------
Title:
Senior Environmental Specialist Date:
8/12/2024 lbs
f)'
e~~!!~!~~~A~JO~CTION 3800-FM-BCW0439 3/2014 SUPPLEMENTAL REPORT - CHEMICAL ADDITIVES USAGE Year:
2024 Facility Name:
Beaver Valley power Station Month: _J_u_.ly"----------
Municipality:
Shippingport Borough NPDES Permit No.:
PA0025615 Outfall:
003 County:
_B_e_a_v_e_r _____ _
Watershed:
Ohio River Renewal application due 180 days prior to expiration.
This permit will expire on:
October 31, 2026 Chemical Names RO Antlscalant Klarald IC1172 Hypersperse Coagulant Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
0.0 1.75 2
0.0 1.6 3
0.0 1.06 4
0.0 0.43 5
0.0 0.95 6
0.0 1.75 7
0.0 0.0 8
0.0 1.75 9
0.0 1.75 10 0.0 0.52 11 0.0 1.06 12 0.0 1.75 13 0.0 1.4 14 0.0 0.29 15 0.0 1.54 16 0.0 1.25 17 0.0 1.75 18 0.0 1.75 19 0.0 0.29 20 0.0 0.95 21 0.0 1.75 22 0.0 1.39 23 0.0 1.25 24 0.0 0.73 25 0.0 1.25 26 0.0 0.95 27 0.0 0.0 28 0.0 1.06 29 0.0 1.54 30 0.0 1.1 31 0.0 1.17 Average 1.2 Maximum 1.8 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By: James Harvey License No.: -----------------
Title:
Senior Environmental Specialist Date:
8/12/2024 lbs
~
L 3800-FM-BCW0439 3/2014 t... e!~~~o~:!!~o~CTioN SUPPLEMENTAL REPORT a CHEMICAL ADDITIVES USAGE Facility Name:
Beaver Valley Power Station - Unit 1 Month:
July Year:
_2_0_2_4 ___ _
Municipality:
Shippingport Borough County:
Beaver NPDES Permit No.:
PA0025615 Outfall:
004 Watershed:
Ohio River Renewal application due 180 days orior to expiration.
This permit will expire on:
October 31, 2026 Chemical Names Dech lormation Nalco 7408 Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
0.0 2
0.0 3
0.0 4
0.0 5
0.0 6
0.0 7
0.0 8
0.0 9
0.0 10 0.0 11 0.0 12 0.0 13 0.0 14 0.0 15 0.0 16 0.0 17 0.0 18 0.0 19 0.0 20 0.0 21 0.0 22 0.0 23 0.0 24 0.0 25 0.0 26 0.0 27 0.0 28 0.0 29 0.0 30 0.0 31 0.0 Average Maximum I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unsworn falsification).
Prepared By: James Harvey License No.: -----------------
Title:
Senior Environmental Specialist Date:
8/12/2024 lbs
3800-FM-BCW0439 3/2014 SUPPLEMENT AL REPORT
- CHEMICAL ADDITIVES USAGE Facility Name:
Beaver Vallley Power Station Month:
_J_ul.... Y _______ _
Year:
2024 Municipality:
Shippingport Borough County:
Beaver NPDES Permit No.:
PA0025615 Outfall:
010 Wate~hed:
Ohio River Renewal application due 180 days prior to expiration.
This permit will expire on:
October 31, 2026 Chemical Names contro1-crom
'-'D 1:11ocIae uecniormat1on Corrosion inmo.
70 Nalco H-150M NALCO7408 NALCOCL-5 Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
0.0 0.0 10.69 0.0 2
0.0 0.0 10.69 0.0 3
0.0 0.0 10.69 0.0 4
0.0 0.0 10.69 0.0 5
0.0 0.0 10.69 0.0 6
0.0 0.0 10.69 0.0 7
0.0 0.0 10.69 0.0 8
0.0 0.0 10.69 0.0 9
0.0 0.0 10.69 0.0 10 0.0 0.0 10.69 0.0 11 0.0 0.066 10.69 0.066 12 0.0 0.0 10.69 0.0 13 0.0 0.0 10.69 0.0 14 0.0 0.0 10.69 0.0 15 o.o 0.0 10.69 0.0 16 0.0 0.0 3.56 0.0 17 0.0 0.0 6.73 0.0 18 0.0 0.0 10.69 0.0 19 0.0 0.0 10.69 0.0 20 0.0 0.0 10.69 0.0 21 0.0 0.0 10.69 0.0 22 0.0 0.0 10.69 0.0 23 0.0 o.o 10.69 0.0 24 0.0 0.0 10.69 0.0 25 0.0 0.0 10.69 0.0 26 0.0 0.0 10.69 0.0 27 0.0 0.0 10.69 0.0 28 0.0 0.0 10.69 0.0 29 0.0 0.0 10.69 0.0 30 0.0 0.0 0.0 0.0 31 0.0 0.0 3.78 0.0 Average o.o 9.8 0.0 Maximum 0.1 10.7 0.1 I certify under penalty of law that this document was prepared under my direction or supervision In accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By: James Harvey License No.:..,..,..,..,,..,.,.-,,...,..-----------
Title:
Senior Environmental Specialist Date:
_8_11_2/:_2_0_2_4 __________ _
lbs
~
L 3800-FM-BCW0439 3/2014
,;- e!~!'!~0~:A~!o~oN SUPPLEMENTAL REPORT* CHEMICAL ADDITIVES USAGE Facility Name:
Beaver Valley Power Station
- Unit 1 Secondary Month:
July Year:
_2_0_24 ___ _
Municipality:
Shippingport Borough County:
Beaver NPDES Permit No.:
PA0025615 Outfall:
No Outfall Watershed:
Ohio River Renewal application due 180 days prior to expiration.
These feedwater additives are noftypically discharged. They are reported to align with DEP guidance.
This permit will expire on:
October 31, 2026 Chemical Names Monoetnanolam1ne Hydrazine PTTOOO Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
5.0 0.0 2
5.0 0.0 3
5.0 0.0 4
5.0 0.0 5
5.5 0.5 6
5.0 0.0 7
5.0 0.0 8
5.0 1.0 9
5.0 0.0 10 6.0 0.0 11 5.0 1.0 12 5.0 1.0 13 5.0 0.0 14 5.0 0.0 15 6.0 0.0 16_
6.0 0.0 17 6.0 1.5 18 6.0 0.0 19 6.0 0.0 20 6.0 0.0 21 0.0 0.0 22 6.0 0.0 23 7.0 1.0 24 7.0 0.0 25 7.0 0.0 26 7.0 0.0 27 7.0 0.0 28 7.0 0.0 29 7.0 1.0 30 7.0 0.0 31 7.0 0.0 Average 5.7 0.2 Maximum 7.0 1.5 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false Information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unsworn falsification).
Prepared By: Jim Harvey
Title:
Senior Environmental Specialist License No.:
Date:
""'s'"'1"'"12""1""'2'"'0'"'2""'4,-,-------------
lbs
p P!_'!,'!~"!!!1~,
SUPPLEMENTAL REPORT* CHEMICAL ADDITNES USAGE 3800-FM-BCW0439 3/2014 Facility Name:
Beaver Valley Power Station - Unit 2 Secondary Month:
_J_u... ly __________ _
Year:
2024 Municipality:,,
Shippingport Borough County:
Beaver NPDES Permit No.:
PA0025615 Outfall:
No Outfall Watershed:
Ohio River Renewal application due 180 days prior to expiration.
These feedwater additives are not typically discharged. They are reported to align with DEP guidance.
This permit will expire on:
October 31, 2026 Chemical Names Monoethanolamme Hydrazine Pnooo Dav gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons lbs gallons 1
5.0 2.0 2
5.5 2.0 3
5.5 2.5 4
6.0 2.5 5
5.5 2.5 6
5.0 5.0 7
5.0 5.0 8
5.0 5.0 9
5.0 4.0 10 5.0 4.0 11 5.0 4.0 12 5.0 4.0 13 5.0 3.0 14 5.0 3.0 15 5.0 4.0 16 5.0 4.0 17 5.0 4.0 18 5.0 4.0 19 5.0 4.0 20 5.0 4.0 21 0.0 0.0 22 5.0 4.0 23 6.0 4.0 24 7.0 4.0 25 7.0 4.0 26 7.0 3.0 27 7.0 3.0 28 7.0 1.0 29 7.0 0.0 30 7.0 0.0 31 7.0 0.0 Average 5.5 3.1 Maximum 7.0 5.0 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:..;.J_im_H_a_rv_e_..Y.,..... _________ _
Title:
Senior Environmental Specialist License No.: ---,--.,----------------
Date:
8/12/2024 lbs
L-24-199 ENCLOSURE C
pennsylvania Jlfliil!rl DEPARTMENT OF ENVIRONMENTAL
'lliJiE5 PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow pH 1
1 MGD Q
s.u.
1 Sun 6/30/24 41.6 7.8 Mon 7/1/24 41.7 Tue 712124 40.1 Wed 7/3/24 39.8 Thu 7/4/24 40.7 Frt 7/5/24 41.3 Sat 7/6/24 40.2 2
Sun 7f7/24 40.3 Mon 7/8/24 43.5 7.9 Tue 7/9/24 45.4 Wed 7/10/24 41.0 Thu 7/11/24 42.3 Frt 7/12/24 41.4 Sat 7/13/24 42.1 3
Sun 7/14/24 43.6 7.6 Mon 7/15/24 43.6 Tua 7/16/24 43.6 Wad 7/17/24 45.3 Thu 7/18/24 44.8 Frt 7/19/24 44.8 Sat 7/20/24 44.2 4
Sun 7/21/24 44.2 8.0 Mon 7/22/24 45.0 Tua 7/23/24 46.3 Wad 7/24/24 43.7 Thu 7/25/24 44.4 Fri 7/26/24 44.1 Sat 7/27/24 43.6 5
Sun 7/28/24 43.2 7.5 Mon 7/29/24 44.1 Tua 7/30/24 44.9 Wed 7/31/24 43.8 Thu 8/1/24 Fri 8/2/24 Sat 8/3/24 Daily Mfnlmum (Cone.):
7.5 Daily Maximum (Cone):
8 Max Avg Weekly (Cone.):
Avg Monthly (Cone.):
Geometric Mean (Cone.):
Max Avg Weekly (Load):
44.5 Avg Monthly (Load):
43.1 Total Monthly (Load):
1337 Daily Minimum (Load):
39.8 Daily Maximum (Load):
46.3 Q
3800-FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
1.__ (select number)
Year:
2024 Permit No.: PA0025615 Outfall:
~0~01~----
Renewal application due 180 days orior to expiration.
This permit will expire on:
..:O:.actaao=.:be=-*=-31,.,-=2=02=.:6=-------
TRC Free Available Temperature NH3-N Total AJumlnum Total Chromium Chlorine 1
1 1
1 1
1 mall.
Q moll.
Q
'F Q
mgA.
Q mgA.
Q mgA.
0.02 D.D2 91.7 0.18 79.9 0.12 80.2 0.15 86.4 0.03 90 0.13 91.9 0.12 88.4 0.14 87.2 0.17 0.09 86.3 0.28 0.1 91.8 92.8 0.24 0.11 86.4 0.07 82.2 0.06 92.2 0.08 0.04 86.9 0.06 87.7 91.8 0.06 89.6 0.12 86 0.18 80.3 0.1 87.7 0.02 0.07 86.4 0.08 84.4 84.7 0.02 86.5 0.06 87.1 0.02 80.9 0.02 82.2 0.02 0.02 82.9 0.02 85.6 0.02 89.7 0.02 89.3 0.02 0.02 79.9 0.24 0.17 0.18 92.8 0.28 0.17 0,11 68 0.26 0.07 0.08 86.6 0.26 62 36 82 26 28 82 816 671 2847 7
7 82 62 67 102 I certify under penalty of law that this document was prepared under my direction or supervision In accordance with a system designed to assure that quafrfied personnel gather and evaluate the Information submitted. Based on my Inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the Information submitted is, to the best of my knowiedge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false Information, including the possibTiity of fine and Imprisonment for knowing \\'lolations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey License No.: _________________ _
Title:
Senior Environmental Specialist Date:
-'8"-/1'-'9"'/2'"'0"'2'-'4 _____________ _
Total Copper Total Iron Total Mercury Total Zinc Hydrazine Nalco H150M Total Phenolics 1
1 1
1 1
1 1
Q -
Q mgA.
Q -
Q
=*
Q -
Q mgA.
Q -
0.0051 0.46 0.0002 0,01 0.0071 0,38 0,0002 0.034 0,01 0.034 0.034 0.034 0.0051 0.38 0.0002 0.034 0.01 0.0071 0.46 0.0002 0.034 0.01 0.0061 0.42 0,0002 0.03 0.01 0.0061 0.42 0.0002 0.034 0.01 2
148 0.07 13 4
2 148 0.07 12 4
66 4601 2
382 109 2
130 0.07 12 3
2 167 0.07 13 4
8 pennsylvania 3800.FM-BCW0'35 312012
~
DEPARTMENT OF EN\\llRONMENTAt SUPPLEMENTAL REPORT PROTECrlON DAILY EFFLUENT MONITORING Facility Name:
Beaver Vall!! Power Station Month:
_7_(~lectm.imber)
Year:
2024 Municipality:
Shil!l!IDl!I!!!!:! Borou11h County:
Beaver PennitNo.: PA0025615 Outfall:
002 Watershed:
20-B Renewal application due~ prior to expirafion.
Laboratories:
T e&tAmerlca BVPS tab This permit will expire on:
October 31 1 2026 Flow 1
MGD Q
Q Q
Q Q
Q Q
Q Q
Q Q
Q Q
Q 1
Sun 6/30/24 Mon 7/1/24 0.046 Tue 7/2/24 Wed 7/3124 Thu 714/24 Fri 715/24 Sal 7/6/24 n
0.046 e
Set 7/13/24 3
Sun 7/14/24 Mon 7/15/24 0.046 Tue 7/16/24 Wed 7/17/24 7/18/24 Frt 7/19/24 Sal 7/20/24 4
Mon 7/22/24 0.046 Tue 7/23124 Wed 7/24/24 Thu 7/25/24 Frt 7/26/24 Sat 7/27/24 5
Sun
,,,~,.
Mon 7/29/24 0.046 Tue 7130124 Wed 7/31124 Thu 811/24
-~
DaHy Minimum (Cone,):
Detty Maximum (Cone):
Mm Avg Weekly (Cone,):
Avg Monthly (CoM,):
Geometric Mimn (Cone,):
Max Avg Weekly (Load):
0.046 Avg Montht;< (Load):
0.046 T Ota! Month!)' (Load):
0.23 OaJy Mln!ml.lm (load):
0.046 Daily Maxirmim {Load):
0.046 f e;ertlfy 1.1nder penf!lty <>f raw !hat !his document was prepared under my cl~ l>t' wpervlslon in secordanoe ~
e systom de!l19ned to 8$Sl.!Te 1hat qua!Wled per$0Mcl galher and evaluate the lnfomWiM eobmittf:d. Based on my Inquiry of th('J pel'$0n or parnoos 'MIO manage ll;e sysiem er those per..ons Ondly l9$j)Q(lsib:O for gathering the lnfcrmalkm. the lnformeticn submitted Is, 10 the be:st of my knowledge and belief, We. accurate end camplate. I am aware thnt the~ m,;i $ign!ficant penallle$ forwbmiffing f.i1$E1 infQtl'M!icn, Including 1he po$,Slbllityof fine and imprisonment fo; knowing \\/lofat!ons. See 18 Pa, C.S. § 4904 (relating to w,swom falsif1C£1tion).
Prepared By: James Harve~
License No.:
Title:
Senior Environmental seecialist Date:
8/13/2024
g pennsylvania DEPARTMENT OF ENVmONMENTAL PROTECTlON Facility Name:
Municipality:
Watershed:
Laboratories:
Flow 1
-Dav Date 11 MOO Q
II
~
1 Sun Mon 0.121 Tue 7/2124 Wed 7/3124 Thu 7/4/24 Fri 7/5124 Set 7/6124 2
Sun 7/7124 Mon 7/8124 Tue 7/9/24 Wed 7/10/24 0.25 Thu 7/11/24 Fri 7/12124 Sat 7/13/24 3
Sun 7/14/24 Mon 7/15124 Tue 7/16124 Wed 7/17/24 0.275 Thu 7118/24 0.22 Fri 7119/24 Set 7/20/24 4
Sun 7121124 Mon 7/22124 Tue 7/23/24 Wed 7/24124 0.276 Thu 7/25/24 0.208 Fri 7126124 Set 7127/24 0.271 5
Sun 7128124 Mon 7129/24 Tue 7130124 Wed 7/31/24 Thu 8/1/24 0.263 Fri 812/24 Set 813124 Ody Minimum (Cone,): ~
Daily Maximom (cone):
MsxAvgW~{Cooo.}: f -
AVli!Monthly(Co!K:,): f -
~!ricMMn(Cnnc.); -
MexA'-'l)Woekly(Load}: Ri=f=
Avg Monthly (Load):
To'.sl Monthly (load}:
Deily Minimum (toed): I 0.121 I
Deity Maximum (load):
0.276 NH3-N 1
s.u.
3!00-FM*BCWMlS 3/2012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
L_(.. hr.lnumbe,)
Year:
2024 PermitNo.: PA0025615 Outfall:
-=0"'0='3~----
Renewal application due 180 daY§ crier to expiration.
This permit will expire on:
_,O:.:cta:o==l>e=-* 3:.1,,_,.:202=6'-------
Total Alurnlnum Total Mareury Hydrazfne NaleoH150M 1
1 1
1 Q
maJL Q
Q Q
m"'-
Q Q
0.034 0,0002 0.35 0.034 0.17 0.0002 0.17 0.0002 0,034 0.35 0.0002 0.034 0.35 0,0002 0.03 0.26 0.0002 0.03 0.6 0,0005 0.08 0,5 0.0005 0.07 16 0.01 2
0.4 0,0004 0.07 0.6 0.0005 0,08 I c>>rtify under penalty cf law that thts document was prepared under 01)' direction or sopenitslon In eccordanoo with a 1;,ys~m designed lo assure l:hal q1.1t1biled pe:-oonno! gather and ev.iloo!e Iha information submitted. Bated' on my lnquhyof the pernon or persons who manage tho cystem or thoee pte!Wlls diredly r&pe.'"lslbt&for qathering I.he inform.Won, the Information submitted is, to the best cf my knt'.l\\Medgeend belief, true, accurate and eomplt!sta. I M1.eware
!.hat there em sfgnifant pena!llM for submittingfuloo lnfomltt!:10", looli.'dlng the possib:lily offioo and lm!;'lll$0l"!ment for knowing,t:.dations. See 18 Pe. C.S. § 4004 (relating to unswom fal~tlon}.
Prepared By: James Harvey Trtle:
Senior Environmental Specialist License No.:
Date:
-=e"'M"'312=024,..,....-------------
Q Q
Q Q
Q Q
Q
G' pennsylvania
,-~ DEPARTMENT OF ENVIRONMENTAL
~
PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmorica, BVPS Lab Flow pH 1
1 Week Day Date MGD Q
s.u.
1 Sun 6/30/24 7.706 7.6 Mon 7/1/24 0.0 Tua 712124 0.0 Wad 7/3/24 0.0 Thu 7/4/24 o.o Fri 7/5/24 5.78 Sat 7/6/24 0.0 2
Sun 7n/24 0.0 Mon 7/8124 0.0 Tua 7/9/24 0.0 Wed 7/10/24 0.0 Thu 7/11/24 0.0 Fri 7/12/24 0.0 Sat 7/13/24 0.0 3
Sun 7/14/24 5.78 7.5 Mon 7/15/24 1.93 Tue 7/16/24 o.o Wed 7/17/24 o.o Thu 7/18/24 0.0 Fri 7/19/24 0.0 Sat 7/20/24 0.0 4
Sun 7/21/24 0.0 Mon 7/22/24 0.0 Tue 7/23/24 o.o Wed 7/24/24 0.0 Thu 7/25/24 o.o Fri 7/26/24 0.0 Sat 7/27/24 o.o 5
Sun 7/28/24 o.o Mon 7/29/24 0.0 Tue 7/30/24 o.o Wed 7/31/24 0.0 Thu 8/1/24 Fri 8/2/24 Sat 8/3/24 Dally Minimum (Cone.):
7.5 Daily Maximum (Cone):
7.5 Max Avg Weekly (Cone.):
Avg Monthly (Cone.):
Geomebic Mean (Cone.):
Max Avg Weekly (Load):
1.927 Avg Monthly (Load):
0.435 Total Monlhly(Load):
13.49 Daily Minimum (Load):
0 Daily Maximum (Load):
5.78 Q
3800-FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
_7_(seleclnumber)
Year:
,2,,o,,2::,4c_ __ _
Permit No.: PA0025615 Outfall:
00::,D::,c4 ____ _
Renewal application due 180 days oner to expiration.
This permit will expire on:
~O.,ct:,;oe,be=.r.:c31,..,_,,2,,02,,s,_ _____ _
TRC Free Available Temperature Total Aluminum Total Chromium Total Copper Chlorine 1
1 1
1 1
1 Q
mg,l Q
'F Q
mg,l Q
m*'
Q mg,l 0,03 0.02 86.3 1.0 0.006 89.9 0.23 0,0035 0.04 0.02 88.2 0.24 0.0036 85.1 0.04 0.02 85.1 0.23 0.0035 0.04 0.02 89.9 0.24 0.0036 0.04 0.02 88 0.62 0.0048 0.04 0.02 87.7 0.24 0.0036 2
1 38 0.3 2
1 11 0.2 60 30 351 5
2 1
11 0.2 2
1 12 0.2 I certify under penalty of law lhat !his document was prepared under my direction or supervision In eceordance with a system designed to assure that qualified personnel gather and evaluate the Information submitted. Based on my inquiry of the peruin or peruins who manage the system or those persons directly responslb!e for gathering the Information, the Information submitted is, to Iha best of my knowledge end belief, In.le, accurate and complete. I am aware that there ere significant penalties for submitting false infofTTISlion, Including the possibRity of fine end imprisonment for knm<.ring violations. See 18 Pa. C.S. § 4904 (relating to unswom fa!siflcafon).
Prepared By:
James Harvey License No.: _________________ _
liHe:
Senior Environmental Specialist Date:
..::B:..:11:::3,:12:::D::;24;:_ ____________ _
1 Q
mg,t Q
Q Q
Q Q
Q 0.0002 0.0002 0.0002 0.0002 0.0002 0,01 0.01 0.3 0.01 0.01
pennsylvania If~ OEPAAiMENf OF ENVIRONMENTAL
&1!f PROTECTION Facility Name:
Beaver VaUey Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow 1
W~k; MGO Q
1 Sun 6130/24 Mon 711124 M16 Tue 712124 Wed 7/3124 Thu 7/4124 Fri 7/5124 Sat 7/6124 2
Sun 7{1/24 Mon 7/8/24 0.016 Tue 7/9/24 Wed Thu 7/1 Fri 7/1 Sat 711 3
Sun Mon 0.016 Tue Wed Thu 7/18124 Fri 7119124 Sat 7120/24 4
Sun 7121124 Mon 7122124 Tue 7/23124 Wed 7124124 Thu 7/25124 Fri 7126124 Sal 7127124 5
Sun 7/28124 Mon 7129/24 0.016
.ID Deily Minimum (Cooc.}:
Daily Mmdmum (Conc:,j; Max Avg Weekly (Concij; Avg Monthly- (CCne.):
GeometriaMean(C<:mo.}:
MaK Avg Weel-Jy (Loedj:
0.016 A..-g Monthly (Load):
0.016 Tota!Monthly(Load);
0.06 Oa:ly Minimum (Load):
0.016 Daily Maid mom (Load):
0.016 Q
3800-FM.:SCW0,435 3/2012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
B&av,ir Monlh:
]__ ("""',.,_)
Year; 2024 Permit No.: PA0025615 Outfall:
~o~os=----
Renewal application due 1!!.!lJ!m prior to expiration.
This permit will expire on:
.;:0:::ctaao:::be,cr:.;3,c;1,_, ::;20::2:::6'-------
Q Q
Q Q
Q I c:ertdy under penalty Of taw that thlt document was Fff!Pared under my direction or super'4!Slon !n <<OCOi'dM with* syitem de$lgned to assum th.at qualified P6fSM001 gilllher and evafl.l$.!O the Information submitted. BaS$d on my
!nquiiy of tt>> J)el'$0n ct persons. who manage the system or those persons diret:Uy ~-sibk'l for gathering the lnfM'l'latlon, tile information submitted ls, to the best of my ~l'I and beUef, true, aeetJrate and coir..pie.o. I am awerc lhatthe.-e en, sigr.ifieenl perwlti'" fur subm!tllngfe\\$e irlf<:t'l'JUt!lon, including the ~tibilrtyof fine and imprisonment fur knowing violations, See t8 Pa, C.S. §: 4904 (relatlng to untw00t fuh;if;cationt Prepared By: James Harvey
Title:
Senior Environmental Specialist License No.:
Date:
""0""11"'312=02""4:--------------
Q Q
Q Q
Q Q
Q
G' pennsylvania r....:t DEPARTMENT OF ENVIRONMENTAL
-=:!I' PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
T estAmerica, BVPS Lab Flow pH 1
1 e
MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 D.O Tue 712124 Wed 713124 Thu 7/4124 Fri 715124 Sat 716124 2
Sun 7lll24 Mon 7/8/24 0.0 Tue 719124 Wed 7/10/24 Thu 7/11/24 Fri 7112124 Sat 7/13/24 3
Sun 7/14124 Mon 7/15/24 0,0 Tue 7/16/24 Wed 7/17124 Thu 7/18/24 Fri 7/19/24 Sat 7/20/24 4
Sun 7/21/24 Mon 7122124 0.0 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7126124 Set 7127124 0,0 5
Sun 7/28/24 Mon 7129124 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 0,0 Fri 8/2/24 Sat 8/3/24 Oa~y Minimum (Cone.):
Deily Maximum (Cone):
Max Avg Weekly (Cone.):
Avg Monthly (Cone.):
Geomebic Mean (Cone.):
Max Avg Weekly (Load):
Avg Monthly (Load):
Total Monthly (Load):
Deily Minimum (Load):
0 Deily Maximum (Load):
0 Q
380o.FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
_7_(selectnumber)
Year:
2024 Permit No.: PA0025615 Outfall:
"0"'07~----
Renewal application due 180 days prior to expiration.
This permit will expire on:
-'O""ct"'o""be""'"r 3=-1"-'-"20""2"'6'--------
TRC Free Available Temperature Nalco H150M Chlorine 1
1 1
1 Q
mg/L Q
"F Q
Q Q
I certify under penalty of law that lhis document was prepared under my direction or supervision in accordance llllith a system designed to assure that qualified personnel gather and evaluate the Information submitted. Based on my inquiry of the person or pemons 'Mlo manage the system or those persons directly responsible for gathering the Information, the information submitted Is, to the best of my knowledge and belief, true, accurate end complete. I am aware that there are significant penalties for submitting false lnformallon, Including the possibility of fine end Imprisonment fer knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey TiHe:
Senior Environmental Specialist License No.:
Date:
-=s"'11"'3"'12"'0"'2-=-4--------------
Q Q
Q Q
Q Q
Q
.. ~
DEPARTMENT OF ENVIRONMENTAL a2!D' PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow pH 1
1 MGD Q
s.u.
1 Sun 6/30/24 7.8 Mon 7/1/24 Tue 712124 4.32 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 Sat 7/6/24 2
Sun 7f7/24 4.32 Mon 7/8/24 4.32 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 Fri 7/12/24 Sat 7/13/24 3
Sun 7/14/24 3.6 Mon 7/15/24 4.32 Tue 7/16/24 4.32 Wed 7/17/24 4.32 Thu 7/18/24 Fri 7/19/24 Sat 7/20/24 4
Sun 7/21/24 4.32 Mon 7122124 Tue 7/23/24 Wad 7/24/24 Thu 7/25/24 Fri 7126124 Sat 7/27/24 5
Sun 7/28/24 4.32 7.4 Mon 7/29/24 4.32 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 8/2/24 Set 8/3/24 Daily Minimum (Cone.):
7.4 Daily Maximum (Cone):
7.8 Max Avg Weekly (Cone.):
Avg Monthly (Cone.);
Geomebie Mean (Cone.):
Max Avg Weekly (load):
4.32
- REF!
Avg Monthly (Load):
4.25
- REF!
Tola! Monthly (Load):
42.48
- REF!
Daily Minimum (Load):
3.6
- REF!
Daily Maximum (Load):
4.32
- REF!
Q 7.5 -
7.9 7.6 380o.FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
1.__ (select number)
Year:
2024 Permit No.: PA0025615 Outfall:
-0~1-0 ____ _
Renewal application due 180 days prior to expiration.
This permit will expire on:
_o_ct_o_be_r_J_1~, 2_0_2_6 ______ _
TRC Free Available Temperature Total Mercury Nalco H150M Chlorine 1
1 1
Q mg,<
Q "F
Q man.
Q mg,<
Q 0.02 0.02 83.3 76.1 -
82.5 f--
82.7 -
83.5 83.8 f--
83.6 -
f--
83.8 f--
0.13 0.12 84.2 0.0002 84.7 f--
84.9 0.0002 f--
71.2 82.2 f--
84.7 f--
f--
0.13 0.07 86.1 0.0002 f--
f--
85.1 85.6 f--
f--
85.4 0.034 85.4 f--
f--
85.4 0.07 f--
0.06 -
85.2 83.3 84.9 84.3 84.2 84.2 82.5 82.9 0.02 0.02 83.3 84.3 84.5 84.5 0,034 0.02 0.02 71.2 0.0002 0.034 0.13 0.12 86.1 0.0002 0.034 0.13 0.12 85 0.0002 0.03 0.09 0.07 83.5 0.0002 0.034
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
I certify under penalty of law that this document was prepared under my direction or supervision In accordance with a system designed to assure that qualified personnel gather and evaluate the Information submitted. Based on my inquiry of the parson or persons ~o manage the system or those persons directly responsible for gathering the Information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I em aware that there are significant penalties for submitting false Information, including the possibility offane and imprisonment for knowing violations. See 18 Pa. C.S. § 4go4 (relating to unsmm fa!sfficalion).
Prepared By:
James Harvey
Title:
Senior Environmental Specialist Q
Q Q
Q Q
Q Q
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
~
~
DEPARTMENT OF ENVIRONMENTAL J'.ci, PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories*
TestAmerica BVPS Lab Flow Total Mercury 1
1 e
MOD Q
mg/L 1
Sun 6/30/24 Mon 7/1/24 0,004 Tue 7/2/24 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 Set 716124 2
Sun 7[7/24 Mon 7/8/24 0.004 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 Fri 7/12/24 Sat 7/13/24 3
Sun 7/14/24 Mon 7/15/24 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 Fri 7/19/24 0.004 0.0002 Sat 7/20/24 4
Sun 7/21/24 Mon 7122124 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 Set 7/27/24 0.004 0.0002 5
Sun 7/28/24 Mon 7/29/24 Tua 7/30/24 Wed 7/31/24 Thu 8/1/24 0.0004 Fri 8/2/24 Sat 8/3/24 Dany Minimum (Cone.):
0.0002 DaUy Maximum (Cone):
0,0002 Max Avg Weekly (Cone.):
0.0002 Avg Monthly (Cone.):
0.0002 Geomebic Mean (Cone.):
Max A\\'g Weekly (Load):
0.004 0.000007 Avg Monthly (Load):
0.004 0.000007 Total Monthly (Load):
0.016 0.0002 Daily Minimum (Load):
0.004 0.000007 Daily Maximum (Load):
0.004 0.000007 Q
3800-FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
_7_(se!eetnumber)
Year:
2024 Permit No.:
PA0025615 Outfall:
~oc.;1.,c1 "-----
Renewal application due 180 days orior to expiration.
This permit will expire on-October 31 2026 Q
Q Q
Q Q
I certify under penalty cf law that this document was prepared under my direction or supervision In a=rdanee with a system designed to assure that qualified personnel gather and evaluate the lnfonnation submitted. Based on my inquiry cf the person or persons 'Mlo manage the system or those persons directly responsible for gathering the Information, the Information submitted is, to the best of my knowledge and benef, true, accurate and complete. I am aware that there are significant penalties for submitting false information, Including the possibility cfflne and lmprlsonmenl for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey TiUe:
Senior Environmental Specialist
~~~;se No.:~s~,1~3~,2~0~2~4---------------
~==~--------------
Q Q
Q Q
Q Q
Q
G' pennsylvania 310o.FM-8CW0435 312012 rE!i' OEPARTMENTOFENVIRONMENTAL SUPPLEMENTAL REPORT PROTECTION DAILY EFFLUENT MONITORING Facility Name:
Station Month:
_7_{Mleclnumber)
Year:
2024 Municipality:
County:
Beaver Perm~No.:
PA0025615 Outfall:
012 Watershed:
Renewal application due.:!.!!!!J!filll prior to expiration.
Laboratories:
Tos!Amorlca, BVPS Lab This permit will expire on:
October 311 2026 Flow pH Total Cadtnfutn Total Copper Total Zinc 1
1 1
1 1
MGD a
s.u.
a Q
a a
Q Q
Q a
Q Q
Q Q
Q II II I 1
Sun Mon Tue Wed Thu 714124 Fri 715124 Sat 7/fJ/24 1m 717124 7/8/24 7/9/24 Wed Thu Fri Sat 3
Sun Mon 7/15124 Tue 71161'24
=ed 7/17/24 Thu 7/181'24 Fri 7/19/24 0.001 7.7 0.001 0.27 1.1 Sat 7/20/24 4
Sun 7/211'24 Mon ii Tue Wed Thu Fri Sat 71271'24 0.001 7.9 0.001 0.051 0.056 5
Sun 7128/24 Mon 7/29/24 Tuo 7/30i24 Wed 7/31/24 Thu 811/24 Fri 8f2124 Sal 813124 Dally Minimum (Coo,;.):
7.7 0.001 0.051 0.056 Daily Maximum (Col)¢}:
7.9 0.001 0.27 1.1 Max:A-.g Weekly (Cone,)'.
0.001 0.27 1.1 Avg' Monthly (COnc.):
0.001 0.161 0.578 Geonwlrie MCM (Cono.):
Max-Avg Wfk'lkly (!..oJAd}'.
0.001 0.000008 0.002 0.000 Avg Month.')' (i.oad):
0.001 0.000006 0.001 0.005 Totol Moothl)' (Loed);
0.002 0.0003 0.04 0.1 OanyMlnimwn{Load);"
0.001 0.000008 0.0004 0.0005 Daily Mioomunt (Load):.
0.001 o.ooooos*
0.002 0.009 I certify under penalty of law ht thia document was prepared under my direclioo or supervision in aecordtmoe wtth a system designed lo 8$S<Jre that qualified peroonnol gather and evaluate tlUI !Mmnation $Ubmlttod. Based on my lnqujry of the person or persons 'M\\o manage the sys:em or those person& cl~ re1:sponsible fer gathering the informoOOt'l, lho info1111Stion submlltecl Is, ID the be$! o1 m)' knowledge and belef, tr\\!$,~ and cemp!eto. l am aware lhet tluire ere significant penalties fotwbmifflng fols.e information, lnclud:ng the possibility off~e and lmprisonmentfotknowin9 'Vlo!aSons. See 18 Pa. C,S, § 4904 {relating to unswom fe!s!flcalion},
Prepared By:
James Harve~
License No.:
Title:
Senior Environmental Seecialist Date:
8/1312024
pennsylvania J'~ DEPARTMENT OF ENVIRONMENTAL
~
PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerica, BVPS Lab Flow pH 1
1 Woek Dav Date MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 Tue 7/2/24 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 Sat 7/6/24 2
Sun 7/7/24 Mon 7/8/24 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 Fri 7/12/24 Set 7/13/24 3
Sun 7/14/24 Mon 7/15/24 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 Frl 7/19/24 0.002 7,3 Sat 7/20/24 4
Sun 7/21/24 Mon 7122124 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 Sat 7/27/24 0.002 6.4 5
Sun 7/28/24 Mon 7/29/24 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 8/2/24 Set 8/3/24 Daily Minimum (Cone.):
6.4 Daily Maximum (Cone):
7,3 Max Avg Weekly (Cone.):
A\\'9 Monthly (Cone.):
Geomebic Mean (Cone,):
Max Avg Weekly (Load):
0.002 Avg Monthly (load):
0.002 Total Monthly (load):
0.004 Daily Minimum (load):
0.002 Daily Maximum (Load):
0.002 Q
3800-FM-BCW0435 3/2012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
L__(se!ec:tnumber)
Year:
2024 Permit No.: PA0025615 Outfall:
~0~1~3-----
Renewal application due 180 days orior to expiration.
This permit will expire on:
..,o"ct"'o"bo""-r 3=-1a:.*.:2.,02"6'--------
Total Copper 1 -*
Q Q
Q Q
Q 0.0041 0.0037 0.0037 0.0041 0.0041 0.0039 0.00007 0.00007 0.002 0.00006 0.00007 I certify under penalty of raw !hat lh!s document was prepared under my direction or supervision in aocordance wilh a system designed lo assure !hat qualified personnel gather and evaluate the information S1Jbmltted. Based on my Inquiry of the person or persons who manage the system or those persons directly responsible for gathering the Information, the Information submitted Is, lo the best of my knowledge and belief, true, accurate and complete. J am aware that there are significant penalties for S1Jbm!tting false Information, Including the possiblllty of fine end Imprisonment for knowing violations. See 18 Pe. C.S. § 4904 (relating lo uns'NOm falsification).
Prepared By:
James Harvey License No.: _________________ _
Title:
Senior Environmental Specialist Date:
_,8"-/1""3"'/2'-'0"'2"'4 _____________ _
Q Q
Q Q
Q Q
Q
Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow pH 1
RI Wook -Dav Date MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 Tue 712124 Wed 7/3/24 Thu 714124 Fri 7/5/24 0.021 6.3 Sal 7/6/24 2
Sun 717124 Mon 7/8/24 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 0.01 6.6 Fri 7/12/24 Sal 7/13/24 3
Sun 7/14/24 Mon 7/15/24 0.031 7.4 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 Fri 7/19/24 Sal 7/20/24 4
Sun 7/21/24 Mon 7/22/24 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 0.008 6.9 Sal 7/27/24 5
Sun 7128/24 0.02 6.5 Mon 7/29/24 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 8/2/24 Sat 8/3/24 Daily Minimum (Cone.):
6.3 Daily Maximum (Conct.
7.4 Max AYQ Weekly (Cone.):
AvgMonthly(Cene.):
Geometric Mean (Cone.):
Max Avg Weekly (Load):
0.031 AYg Monthly (Load):
0.018 Total Monthly (Load):
0.09 Daily Minimum (Load):
0.008 Daily Maximum (Load):
0.031 Q
3800-FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver
~~:{ No.: -!-A-O~;~;;;"mbe,)
6~':!~11:
- ~:i1:
24::::::::=
Renewal application due 180 days prior to expiration.
This permit will expire on:
-=o.,ct.,o.,be=-r 3::.;1:.,., =-20:::2.,6'--------
TSS Oil and Grease NH3-N Hydrazine RI RI RI RI mg/I.
Q mg/I.
Q mg/I.
Q -
Q Q
4.0 4.9 4.0 4.8 4.4 4.9 4.0 5.0 4.0 4.8 4
4.8 4.4 5
4.4 5.0 4.1 4.9 1
1 0.6 0.7 19 23 0.3 0.3 1
1 I certify under penalty of law that !his document was prepared under my direction or supervision In a=rdanoe with a system designed to assure !hat quaHfied personnel gather and evaluate the lnformalion submitted. Based on my Inquiry of the person or persons 'Mio manage the system or those persons directly responsible forgathering the infonnation, the information submitted is, to the best of my knowledge and belief, true, aceurate and complete. 1 am aware that there are significant penalties for submitting false Information, Including the possiblfity of fine end Imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey License No.: _________________ _
Title:
Senior Environmental Specialist Date:
..:Bc../1'-'3"'/2'-'0=24-'---------------
Q Q
Q Q
Q Q
Q
G' pennsylvania J'~ DEPARTMENTOFENVIAONMENTAL
~
PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow pH 1
RI MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 Tue 712124 Wed 7/3/24 Thu 7/4/24 Fri 715124 Set 7/6/24 2
Sun 7rTl24 Mon 7/8/24 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 Fri 7/12/24 Set 7/13/24 3
Sun 7/14/24 Mon 7/15/24 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 0.001 6,9 Fri 7/19/24 Set 7/20/24 4
Sun 7/21/24 Mon 7/22/24 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 Set 7/27/24 0.001 7.0 5
Sun 7/28/24 Mon 7/29/24 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 8/2124 Set 8/3/24 Dally Minimum (Cone.):
6.9 Daily Maximum (Cone):
7 Max Avg Weekly (Cone.):
Avg Monthly (Cone.);
Geometric Mean (Cone.):
Max Avg Weekly (Load);
0.001
- REF!
Avg Monthly (Load):
0.001
- REF!
Total Monthly (load):
0.002
- REF!
Daily Minimum (Load):
0.001
- REF!
Daily Maximum (Load):
0.001
- REF!
Q 3800+FM--BCW0435 3/2012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver
~~:~~ No.: -~-A-ori;~;~;umber) 6~~11:
-=:'-'~=:~
4----
Renewal application due 180 davs crier to expiration.
This permit will expire on:
-'O'-'ct'-"o'-'be=-r :..31,.,_,-=2-"'02"'6'-------
TSS 011 and Grease RI RI moll Q
mg,1.
Q Q
Q Q
4.0 4.7 4.0 4.9 4
4.7 4
4.0 4.0 4.0 4.0 4.8
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REFI
- REFI
- REF!
- REF! -
- REF!
- REF!
- REF!
- REFI
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
I certify under penalty of law that this document was prepared under my direction or supervision In accordance with a system designed to assure that qualfled personnel gather end evaluate the Information submitted. Based on my Inquiry of the person or persons v.ho manage the system or those persons directly responsible for gathering the Information, the lnfonnation submitted ls, lo the best of my knowledge end belief, true, accurate and complete. I em aware that there are significant penalties for submitting false Information, Including the possibility of fine and Imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey
Title:
Senior Environmental Specialist License No.:
Date:
"'s""11"'3"'12"'0-=24-=--------------
Q Q
Q Q
Q Q
Q
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REFI
- REF!
- REF!
- REF!
pennsylvania DEPARTMENT OF ENVIRONMENTAL PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca, BVPS Lab Flow pH 1
RI MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 0.121 Tue 7/2/24 0.121 Wed 7/3/24 0.087 Thu 7/4/24 0.121 Fri 7/5124 0.124 Sat 7/6/24 0.189 2
Sun 7/7/24 0.221 Mon 718124 0.246 Tue 7/9124 0.255 Wed 7/10/24 0.250 Thu 7/11/24 0.253 Fri 7/12/24 0.263 Sat 7/13/24 0.245 3
Sun 7/14124 0.234 Mon 7/15/24 0.247 Tue 7/16124 0.289 Wed 7/17/24 0.275 Thu 7/18/24 0.220 Fri 7/18/24 0.269 6.8 Sat 7/20124 0.277 4
Sun 7/21/24 0.266 7.6 Mon 7/22124 0.273 Tue 7/23/24 0.265 Wed 7/24/24 0.276 Thu 7/25/24 0.268 Fri 7/26/24 0.274 Sa*
7/27/24 0.271 5
Sun 7/28/24 0.268 Mon 7/29/24 0.273 Tue 7/30/24 0.274 Wed 7/31/24 0.273 Thu 8/1/24 Fri 8/2/24 Sat 8/3/24 Deily Minimum (Cone.):
6.8 DallyMaximum (Cone):
7.6 Max Avg Weekly (Cone.):
Avg Monlhly (Cone.):
Geometric Mean (Cone.):
Max Avg Weekly (Load):
0.272066 Avg Monthly (Load):
0.235027 Total Monthly {load):
7.285848 Daily Minimum (load):
0.086588 Daily Maximum (load):
0.288587 Q
3800.FM-BCW0,435 3/2012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
_7_(setectnumber)
Year:
2024 Permit No.: PA0025615 Outfall: 03 ____ _
Renewal application due 180 days prior to expiration.
This permit will expire on:
..,o"'ct"'o"'be=r 3:a;1:z., =20"'2"'6'--------
TSS 011 and Grease Q
Q Q
Q Q
4.0 4.9 4.0 5.3 4
4.9 4
5.3 4.0 5.3 4.0 5.1 9
12 9
11 277 353 9
11 9
12 l certify under penalty of law that this document was prepared under my direction or supervision In accordance with a system designed to assure that qualified per.;onnel gather and evaluate the Information submitted. Based on my Inquiry of the person or persons 'Mlo manage the system or those persons direcfly responsible for gathering the Information, the information submitted Is, to the best of my knowledge end belief, true, accurate and comp!eOO. I am aware that there are significant penellies for submitting false lnformalion, Including the possibility of fine end Imprisonment for knowing violations. See 18 Pe. C.S. § 4904 (relating to unswom fa!sffication).
Prepared By:
James Harvey TiUe:
Senior Environmental Specialist License No.:
Date:
-=s,-,,1:-:3"'12:-:oc=2-=-4--------------
Q Q
Q Q
Q Q
Q
G' pennsylvania F-:111!3 DEPARTMENT OF ENV.IRONMENTAL
-.a9' PROTECTION Facility Name:
Seaver Valley Powar Sbrtion Municipality:
Shippingport Borough Watershed:
20-B Laboratories*
Tes!Amerlca BVPS I.ab Flow TRC 1
RI a
Q 1
Sim Mon Tue Wed Thu Frt Sat 2
Sun Mon 7/8/24 II 0.0 Tue 7/9/24 11 Wed 1110124 11 Thu Fri Sat 3
Sun Mon Tue I
EBEWed n
Sat 7120/24 4
Sun 7/21/24 Mon 7122124 0.0 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 Sat 7/27/24 0,0 5
Sun 7/28/24 Mon 7/29/24 Tue 7/S0/24 Wed 7131/24 Thu 8/t/24 0,0
~~
Deily M!t!lmum {cone.~
Daily Meximum {Cone).
Mal( A>Jg: Weekly (Cone.):
Avg Monthly (Cone.):
Geometric Mean (C<<lc.):
Max Avg Week.ly{toad):
Avg Monl'hly(toed):
Total Monthly(LOffl:I);
Dally Mln!ITl'Jm {Load):
0 Dafly Maximum (Load):
0 Q
38oo-FM-BCW0435 3/%01%
SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
L_ (oo1oc1 """"""'
Year:
2024 Permtt No.: PA0025615 Outfall:
'"1:::oa~----
Renewal application due 180 days prior to expiration.
This permit v.ill expire on*
October 31 2026 Q
Q Q
Q I certify under penalty of law lhal ttils document wtis p~ under my direction ct suporvls.loo In accordam:.:e With a system designed ID asS\\lre !hat qualified persoMc! g,thor and evaluate 610 information submlttod. Based ori my biqUil'y of the person ot ptlf$0flS IMlO manage the system or those persons directly resp::ms!b!efot 9alher'.og the lnf0mmtion, the Information subm!:ted Is, ta lt1e ~
of my knowfed90 and belief, true. accurate and eomp!e!&, I am l\\lW8!'0 thal there are slgnlfieantpenalti(lll for wbmlttlng-fitso Information, including the possibilcy ti!fine and fmptlsoomeritfor Mowfng "1olati£'4'!s. See 18 Pe. C.S. § 4904 (rn!a!ing to unllW:'lm falslflemion).
Prepared By:
James Harvey Tlfie:
Senior Environmental Specialist License No,:
Date:
""'s""11""4"'12"'0.,..24.,...-------------
Q Q
Q Q
Q Q
Q
~
G' pennsylvania
,-__.. DEPARTMENT OF ENVIRONMENTAL
~
PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow pH 1
RI MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 Tue 712/24 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 0.002 6.0 Set 7/6/24 2
Sun 717/24 Mon 7/8/24 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 0.002 6.5 Fri 7/12/24 Set 7/13/24 3
Sun 7/14/24 Mon 7/15/24 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 0.002 7.1 Frl 7/19/24 Set 7/20/24 4
Sun 7/21/24 Mon 7122124 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 0.002 7.2 Set 7/27/24 5
Sun 7/28/24 0.002 6.8 Mon 7/29/24 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 8/2/24 Sal 8/3/24 Deily Minimum (Cone.):
6.5 Deny Maximum (Cone):
7.2 Max Avg Weekly (Cone.):
Avg Monthly (Cone.):
Geomebic Mean (Cone.):
Max Avg Weekly (Load):
0.002 Avg Monthly (load):
0.002 Total Monthly (load):
0.01 Dally Minimum (load):
0,002 Daily Maximum (Load):
0.002 Q
3800-FM-BCWU435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
1._ (select number)
Year:
2024 Permit No.:
PA0025615 Outfall:
-1~11 ____
Renewal application due 180 days prior to expiration.
This permit will expire on:
_,o.,ct.,o:::bo;;:;r:.;3::.;1"-1 :20::.:2:::6'-------
TSS Oil and Grease RI RI Q
mg,1.
Q Q
Q Q
6.0 4.0 4.0 4.8 4.0 4.7 4.0 5.0 5.8 4.0 4
4.7 6
5 6.0 5.0 4.8 4.0 0.1 0.08 0,08 0.08 2
3 0.07 0.08 0.1 0.08 I certify under penalty of law that this document was prepared under my direction or supervision In accordance with a system designed to assure that quaflfied personnel gather and evaluate the lnfom,ation submitted. Based on my Inquiry of the person or persons v.tio manage the system or those persons directly responsible for gathering the information, the information submitted Is, lo the best of my knawtedge and belief, true, eOC1Jrate and complete. I am aware that there are significant penalties for submitting false Information, Including the possibility offme and Imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey License No.: ------------------
Title:
Senior Environmental Specialist Date:
-'8"'-/1"4"'/2'-'0=2-'-4 _____________ _
Q Q
Q Q
Q Q
Q
e pennsylvania 3801).f'M.SCWf.1435 3J20f2 r&!J DEPARTMENT OF ENVIRONMENTAL SUPPLEMENTAL REPORT PAOTECTlON DAILY EFFLUENT MONITORING Facility Name:
Beaver Vall!X: Power Station Month:
J__ (select number}
Year:
2024 Municipality:
ShleEl*&i!!!!! Boroush County:
Beaver PermiNo.: PA0025fi15 Outfall:
211 Watershed:
20-8 Renewal application due 180 davs orior to expiration.
Laboratories:
TostAmorlca BVPS Lab This permit will expire on:
October 31 1 2026 Flow pH TSS Oil and Grease 1
RI RI RI MGD Q
s.u.
Q Q -
Q Q
Q Q
Q Q
Q Q
Q Q
Q 1
Sun 8130/24 Mon 7/1/24 Tue 7/2124 Wed 713124 Thu 714124 Fri 715124 0.002 8.1 8.4 4.9 Sal 710124 2
Sun 7{lf24 Mon 7/8/24 0.002 8,1 Tue 719124 VVGO 7110/24 Thu 7/11124 0.002 8.0 11.6 4.8 Fri 7/12124 Set 7113124 3
Sun 7/14124 Mon 7/15124 Tue 7116124 Wed 7/17124 Thu 7/18/24 0.002 7,5 4.0 4,Q Fri 7/10124 Set 7/20/24 4
Sun 7/21/24 Mon 7/22124 Tue 7123124 Wed 7/24124 Thu 7/25/24 Fri 7126124 0.002 6.9 4.0 5.0 Set 7127124 5
Sun 7128124 0.002 6.8 4.0 5.0 Mon 7/29124 Tue 7/30124 Wod 7/31/24 Thu 6/1124 Fri 8/2124 Set 8/3124 Daily Mtn!mum {Cone.):
6.8 4
4.8 Daily Maximum (Cone):
6.1 11.6 5
Max.Avg Weekly (Cone.):
11.6 5.0 Avg M0t1thly (Cone:,):
6.4 Geomelrk: Mean (Cone.):
Max A"V Weekly (1.oad):
0.002 0.2 0.08 Avg Monthly (toad}:
0.002 0.1 0.08 Tola! Monthly (Load}:
0.012 3
3 Daily Minimum (Load):
0.002 0.07 0.08 Daily Maximum (1.ood):
0.002 0.2 0.08 I certify under penalty of law !bet tti:iS '1001.UTri'fflt was prepared undet my tf1re!Cfkln or supervision in aceordan.ee With a system de,;!gned to asoore Iha! quatdled pornontV}J gather and evaluate the information submitted. Based,on my lnqulry of the peraon or peraoos 'tmO ma.,age ltMt system or tho$e peroons diractly NISpOl"lsiblofor gathering lho l!'lfurmatkm, the Information submitted IS. to thO bMt of my knuwlooge and ber>M. true, aceumw Otid ()Q!Tlpk,!1J. I am aware thetthere are significant pernt!ties for submitting false infoimatlon, including the possibility of fine Md !mprioorummt for knowing 'llblallons. See 18 Pe.. 0$, § 4004 (teieting to u.nswom falsifk:t'ltfon),
Prepared By:
James Harvel License No.:
Trtle:
Senior Environmental seecialist Date:
8/1412024
pennsylvania J',,,;;;/D DEPARTMENT OF ENVIRONMENTAL
~
PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories*
TestAmerica BVPS Lab Flow TSS 1
RI e
MGO Q
mg,1.
1 Sun 6130/24 Mon 711124 0.0 Tue 7/2/24 Wed 713124 Thu 7/4/24 Fri 7/5(24 Set 7/6/24 2
Sun 7n/24 Mon 718124 0.0 Tue 7/9/24 Wed 7110124 Thu 7/11/24 Fri 7/12124 Sal 7/13124 3
Sun 7/14/24 Mon 7115124 0.0 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 Fri 7/19/24 Set 7120124 4
Sun 7/21/24 Mon 7122/24 Tue 7/23/24 0.0 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 Set 7/27/24 5
Sun 7/28/24 Mon 7/29/24 0.0 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 812/24 Sat 813124 Daily Minimum (Cone.):
Da~y Maxlmum {Cone):
Max Avg Weekly (Cone.):
Avg Monthly (Cone.):
Geomebic Mean (Cone.):
Max Avg Weekly (Load):
Avg Monthly (Load):
Total Monthly (Load):
Daily Minimum (Load):
0 Daily Maximum (Load):
0 3800-FM-BCW0435 3/2012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
L c~,oo1 o,mbe,)
Year:
2024 Permit No.: PA0025615 Outfall:
-=3~01~----
Renewal application due 180 days prior to expiration.
This permit 'hill expire on*
October 31 2026 I
Oil and Grease RI Q -
Q Q
Q Q
Q I certify under penalty of law thal this document was prepared under my direction or supervision In acx:ordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the Information, the Information submitted is, to the best of my knowledge and belief, true, aceurate and complete. I am aware that there are sign!frcant penalties for submitting false Information, including the possibility of fine and imprisonment for knowing \\'iolatlons. See 18 Pa. C.S. § 4go4 (relating to unswom falsification).
Prepared By:
James Harvey ntle:
Senior Environmental Specialist License No.:
Date:
""a""11,.,4""12"'0"'24.,.....-------------
Q Q
Q Q
Q Q
Q
pennsylvania 38GG-FM~Sa/2012
~
DEPARTMENT OF ENI/IRONMENTAL SUPPLEMENTAL REPORT PROTECTION DAILY EFFLUENT MONITORING Facility Name:
Beaver Vall!;! Power Station Month:
J__ (seleetnumber)
Year:
2024 Municipality:
Shreetnae2rt Boro*sh County:
Beaver Permit No.: PA0025615 Outfall:
303 Watershed:
20--B Renewal application due 1l!.!!.!!.!oo; prior to expiration.
Laboratories:
TestAmerica, BVPS Lab This permit will expire on:
October 31 1 2026 flow pH TSS Olland Groase 1
RI RI RI MGO Q
s.u.
Q
='
Q Q
Q Q
Q Q
Q Q
Q Q
Q Q
1 SUn~I Mon 0,0 Tue 712124 Wed 7/3/24 Thu 714124 Fri 715124 Set 7/6/24 2
Sun 7[1/24 Mon 718124 0,0 Tue 719124 Wed 7110/24 Thu Fri Set 3
Sun Mon Tue Wed Thu Fri Sal 4
Sun 7121124 Mon 7122124 0.0 Tue 7123124 Wed 7124124 Thu 7125124 Fri 7125124 Sal 7/27/24 0,0 5
Mon 7129124 Tue mo12*
Wed 7131124 Thu 8/i/24 0,0
~-
Daily Minimum (Cone.}:
Daffy Maxlmum {Cone}:
MaxA\\<iJ Weekly{Cone):
AvgMonl.hly{Ccne.):
Geometri: Mean (Ccne.):
MaxA'"t!Weekly{load):
Avg Monthly (Load):
Total Monthly {Load).
Daily Minimum {LQad}:
0 Daily Maximum (Loud):
0 I eert!fy under penalty of low that this document was prepared l.mder my dlreetion or 111JpeMSlon 1n eecordance with a system designed to assurt:i lhat qualified personnel 90ther and evaluate the Information submitted. Based on my Inquiry of the pernon or persons who manage the s}'$fem DI' those persons direcHy respon:;ible for gslhertng the informallon, the information submitted fa, I.GI th~ best of my know!edg9 and belief, true, accurate and ecmplete. I am aware 1hatthereare slgnlficent pe,nelt:es for submitting faJim information, including the pos~bi!ity of fin-o and Imprisonment for knowing \\l!oh':itions. See 18 Pa. C.S. § 4904 (relating to un$WC:m fu1Sif1¢a!Jon).
Prepared By:
James Harvel License No,:
11He:
Senior Environmental Seeclalist Date:
8/14/2023
Facility Name:
Municipality:
Beaver Valley Power Station Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca BVPS Lab Flow pH 1
RI MGD Q
S.U.
1 Sun 6/30/24 Mon 7/1/24 Tue 712124 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 0.002 6.Q Sat 7/6/24 2
Sun 7f7124 Mon 7/8/24 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 0.002 7.4 Fri 7/12124 Sat 7/13/24 3
Sun 7/14/24 Mon 7/15/24 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 0.002 6.8 Fri 7/19/24 Sat 7/20/24 4
Sun 7/21/24 Mon 7122124 Tue 7/23/24 Wed 7/24/24 Thu 7125124 Fri 7126124 0.002 6.5 Sat 7127124 5
Sun 7/28/24 0.002 6.3 Mon 7/29/24 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 Fri 8/2124 Sal 8/3/24 Dally Minimum (Cone.):
6.3 Daily Maximum (Cone):
7.4 Max A-.g Weekly (Cone.):
Avg Monthly (Cone.):
Geomelrio Mean (Cone.):
Max Avg Weekly (Load):
0.002 Avg Monthly (Load):
0.002 Total Monthly (Load):
0.01 Daily Minimum (Load):
0.002 Daily Maximum (Load):
0.002 Q
38oo.FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
L<~Jectnumbe,J Year:
2024 Permit No.:
PA0025615 Outfall: 13 ____ _
Renewal application due 180 days prior to expiration.
This permit will expire on:
..:O.,ct"'o"'be""-'r 3::.;1:.,., =20:::2.,6'-------
TSS Oil and Grease RI RI Q -
Q Q
Q Q
7.0 4.8 4.0 4.8 8.8 4.7 4.0 5.0 4.2 5.0 4
4.7 8.8 5
8.6 5.0 5.6 4.9 0.1 0.08 0.09 0.08 3
3 0.07 0.08 0.1 0.08 I certify under penally of law that this document was prepared under my dlrection or supervision In accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my Inquiry of the person or persons who manage the system or those persons direcUy responsible for gathering the Information, the Information submitted is, to the best of my knov.-1edge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false Information, including the possibility offlne and Imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey
Title:
Senior Environmental Specialist License No.:
Date:
--:8:-:,/1'"'4"'12'"'0:=24-:--------------
Q Q
Q Q
Q Q
Q
~4 DEPARTMENT OF ENVlAONMf:NTAL
- $if PROTECTION Facility Name
Municipality:
Watershed:
Laboratories* -
Flow 1
MGO I
1 Sun Mon 0.001 Tue Wed Thu Fri 7/5/24 Sat 7/6/24 2
Sun 7n/24 Mon 7/8/24 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 0.001 Fri 7/12/24 Sat 7/13/24 3
Sun 7114/24 Mon 7/15/24 Tue 7116/24 Wed 7117/24 Thu 7/18/24 0.001 Fri 7/19/24 Sat 7/20/24 4
Sun 7/21/24 Mon 7/22/24 Tue 7/23/24 Wed 7/24/24 Thu m,r,*
0.001 Fri 7/26/24 Sal 7/27/24 5
Sun 7/28/24 Mon 7/29/24 Tue 7/30/24 Wed 7i31/24 Thu 8/1/24 0.001 Frl 81212.4 3H'@?:.. l1L (Co,,.), I Owly Meximt.tm {CoM):
Ma,c;Avg Weekly (Cone,):
Avg Moothly {Cone.):
Geometrio Mecm {Cone.):
Max Avg WHl,\\ly {l.ofid}:
0.001 AV{JMor,lhly(Losdj:
0.001 Total: Monthly {Load}:
0,004 0.ai!y Mif!irnun, (Load):
0.001 OaltyMli!X!mum{Load):
0.001 Q
pH RI s,u.
Q 7.9 8.0 7.9 8
310l).FM..JJCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
L (w*otr,umbo,)
Year:
2024 Permit No.: PA0025615 Outfall:
-=40"'1=-----
Renewal application due~ prior to expiration.
This permit v.ill expire on*
October 31 2026 I
TSS 011 and Grease RI Rl
~,
Q Q
Q Q
Q 4.0 4.9 4,0 4
4.9 4
4.9 4.0 4.9 4.0 4,9 0.93 0.04 0.03 0.04 1
1 0.03 0,04 0.03 0,04
! certify tmder penalty of few that this dOOl.lment wru: prepared under m; direction or wporvlsion in eec.o:dance w.!h fl $ystem designed to MSUNJ that f:il.lS:ified per$0nnel gal.her and evalue!$ the lnfommtlon submitted. 8esed QI\\ my tnqulry of tha person or~ Who man3Re the system or1hot.(! pen;oos du'ecily rot;pOnsible forgathering the iruorrna",,on, the !nforrrmfun submitted b, to the best af my knO'Yll!-edge and beliof, tru..., eceumte end complete. I am &W&re thnl trn,re are slgnffieantpenn!tie$ lor$Ubmittngfeloo iflfotmalltxl, lm:.:il.kfng the possibili1yoffine and imprisonment forkl'IO'Mn9 \\<lo!ations, See 18 Pa. C.S. § 4904 (relating to unswom fslslfica!IOO),
Prepared By:
James Harvey
Title:
Senior Environmental Specialist License No.:
Date:
"'a"",1'"'4-=12"'02=-4=--------------
Q Q
Q Q
Q Q
Q
pennsylvania 3800-FM-8CWD435 312012 DEPARTMENT OF EN\\llRONMENTAL SUPPLEMENTAL REPORT POOTEC'f!ON DAILY EFFLUENT MONITORING Facility Name:
~r Vallo:r; Power Stati-on Monlh:
J__(seJectnumbet')
Year:
2024 Municipality:
Shleel*~e!!rl Borough County; Beaver PennitNo.: PA0025615 Outfall:
403 Watershed:
20.S Renewal application due 180 days prior to expiration.
Laboratories:
Tes!Amerlca BVPS I.ab This pennit will expire on:
October 31, 2026 Flow pH TRC TSS Oil and Grease NH3-N Total Chromium Total Zinc llydralfno H1SOM 1
RI RI RI RI RI RI RI RI RI MGO Q
s.u.
Q Q
mM.
Q mot.
Q mM.
Q Q
Q Q
Q Q
Q Q
I II
~
I n
0.0 Tue 712124 Wed 713124 Thu 714/24
.Fri 715124 Sat 716124 2
Sun 7f7/24 Mon 718124 0.0 Tue 719124 Wed 7/10124 Thu 7/11124 Fri 7/12124 Sat 7/13124 3
Sun 7/14124 Mon it o.o Tue Wed
-- ~
Fri Sat 4
Sun 7121124 Mon 7122124 0.0 Tua 7123124 Wed 7124124 Thu 7125124 Fri 7/26/24 Sal 0.0 5
Sun
//SOI<< II Mon 7129124 Tue 7/30/24 Wed 7131124 Thu 811/24 0.0 Fri 812124
-~
DailyMil'limum(Conc:,):
OellyMall.imum {Cone);
Max Avg Weekly(Conc.):
A>t; Mon!hly(Com::;,):
Geomelrlc Mean (Cono,);
Max Avg WMl,Jy (Loo::i}:
Avg Monthly (Load):
Tota!Montiily(Load):
Daily Minimum (Load):
0 Daily Maximum (Load):
0 I eortlfy under penalty of law !Ml this document was prepared under my d~on er 1,upervlslon tn accordance w!lh a ;,y$tem designed to assure that qualified peroonnot gathw ond c:ivodu8te N information &1bmitted. Ba$Cld oo ffr/
lnqu!Jy of the per.l01'1 or person\\. who mat11'190 the syi.tem or those pe=s directly responslbte for gatherinq the rnformation, the lnfomiation submitted Is, to the best of rr,y knowledgo Md belief, tue, a:;f.:UfSte and CCN1iplett,. I am ftWllN tha! there are s,;!l'lificant peru:ilties for submitting false !n'frumation, lndt.>ding the pos~l!:"ty of fine and lmprtsonment(ot krlowtng violations. See 18 Pa C.$. § 4904 (rctl'rtl:'lg to UnmNOm falsiflcetlon).
Prepared By:
James Harv~
License No.:
TIiie:
Senior Environmental seecialist Date:
8114/2024
g pennsylvania J~ DEPARTMENT OF ENVIRONMENTAL
-=eJ PROTECTION Facility Name:
Beaver Valley Power Station Municipality:
Shippingport Borough Watershed:
20-B Laboratories:
TestAmerlca, BVPS Lab Flow pH 1
RI Woek ~Dav
r;ate MGD Q
s.u.
1 Sun 6/30/24 Mon 7/1/24 0.0 Tue 7/2/24 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 Sat 7/6/24 2
Sun 717124 Mon 7/8/24 0.0 Tue 7/9/24 Wed 7/10/24 Thu 7/11/24 Fri 7/12/24 Sat 7/13/24 3
Sun 7/14/24 Mon 7/15/24 0.0 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 Fri 7/19/24 Sat 7120124 4
Sun 7/21/24 Mon 7/22/24 0.0 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7126/24 Sat 7/27/24 0
5 Sun 7/28/24 Mon 7/29/24 Tue 7/30/24 Wed 7/31/24 Thu 8/1/24 0.0 Fri 812124 Sat 8/3/24 Daily Minimum (Cone.):
De Uy Maximum (Conct.
Max Avg Weekly (Cone.):
A\\'9 Monthly (Cone.):
Geometric Mean (Cone.):
Max Avg Weekly (Load):
- REFI Avg Monthly (Load):
- REF!
Total Monthly(Load):
- REF!
Daily Minimum (Load):
0
- REF!
Daily Maximum (Load):
0
- REFI Q
3800,.fM-BCWD435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County:
Beaver Month:
.1..._ (select number)
Year:
2024 Permit No.: PA0025615 Outfall: 01 ____ _
Renewal applicafion due 180 days prior to expiration.
This permit will expire on:
_,Oaact:::oaabe=.r 3:c1:i.,.:20::2aa6c_ _____ _
TSS Oil and Grease NH:J..N Hydrazine RI RI RI RI m"'-
Q -
Q Q
mg/L Q
Q
- REFI
- REF!
- REFI
- REF!
- REFI
- REFI
- REFI
- REF!
- REFI
- REFI
- REFI
- REFI
- REFI
- REF!
- REF!
- REF!
- REFI
- REFI
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
I certrfy under penalty of law that this document was prepared under my direction or supervision In accordance with a system des!gned to assure that qualified personnel gather and evaluate the Information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responslble for gathering the Information, the Information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and Imprisonment for knowing vlo!atlons. See 18 Pa. C.S. § 4904 (relating to UnS'NOm falsification).
Prepared By:
James Harvey TiUe:
Senior Environmental Specialist License No.:
Date:
-=s""/1c-:4-::/2c::0-::-24.,----------------
Q Q
Q Q
Q Q
Q
- REF!
- REF!
- REF!
- REF!
- REFI
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REFI
- REFI
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REFI
- REF!
- REF!
- REFI
- REFI
- REFI
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
,..-, DEPARTMENT OF ENVIRONMENTAL
~
PROTECTION Facility Name:
Beaver Valley Power Station Municipality; Watershed:
Shippingport Borough 20-B Laboratories:
TostAmerlca, BVPS Lab Flow 1
MGO Q
1 Sun 6/30/24 Mon 7/1/24 0.0 Tue 7/2/24 Wed 7/3/24 Thu 7/4/24 Fri 7/5/24 Sat 7/6/24 2
Sun 717/24 Mon 7/8/24 0.0 Tue 7/9/24 Wad 7/10/24 Thu 7/11/24 Fri 7/12/24 Sal 7/13/24 3
Sun 7114/24 Mon 7/15/24 0.0 Tue 7/16/24 Wed 7/17/24 Thu 7/18/24 Fri 7/19/24 Sat 7/20/24 4
Sun 7/21/24 Mon 7/22/24 0.0 Tue 7/23/24 Wed 7/24/24 Thu 7/25/24 Fri 7/26/24 Set 7/27/24 0
5 Sun 7/26/24 Mon 7/29/24 Tua 7/30/24 Wad 7/31/24 Thu 8/1/24 0.0 Fri 812/24 Sat 8/3/24 Deity Minimum (Cone.):
Daily Maximum (Cone):
Max Avg Weekly (Cone.);
Avg Monthly (Cone.):
Geomebic Mean (Cone.):
Max Avg Weekly (Load):
Avg Monthly (Load):
Total Monthly (Load):
Daily Minimum (Load):
0 Daily Maximum (Load):
0 pH RI S.U.
- REFI
- REFI
- REF!
- REFI
- REFI Q
3800..FM-BCW0435 312012 SUPPLEMENTAL REPORT DAILY EFFLUENT MONITORING County; Beaver
~~:t: No.: -~-A-O~;~;~;umber) 6~~~11:
s:::i:::c:
4----
Renewal application due 180 davs prior to expiration.
This permit \\I.ill expire on:
.,o,,ct"'o"be=-* 3=-1,,_,.::2D::2::::6c...... _____ _
TSS Oil and Grease NHJ.N Hydrazine RI RI RI RI mg,1_
Q Q
m""-
Q -
Q Q
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
I certify under penalty of law that this document was prepared under my direction or supeNislon in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the Information, the infonnation submitted Is, to the best of my knowledge and belief, true, eccursto and complete. I am aware thet there are significant penalties for submitting false information, including the p,ssibi!ity of fine and Imprisonment for knO'n'lng violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By:
James Harvey License No.: _________________ _
Title:
Senior Environmental Specialist Date:
_,8"-/1'-'4"'/2::0c:2..,_4 _____________ _
Q Q
Q Q
Q Q
Q
- REF!
- REFI
- REF!
- REF!
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REF!
- REFI
- REF!
- REF!
- REFI
- REF!
- REF!
- REFI
- REFI
- REF!
- REF!
L-24-199 ENCLOSURED
380o-FM-BCW0010 212020 SUPPLEMENTAL REPORT* COOLING WATER INTAKE MONITORING Facility Name:
Beaver Valley Power Station - Unit 1 Month:
_J_u_ly ________ _
Year:
2024 Municipality:
Watershed:
Shippingport Borough County:
Beaver 20-B 20-D NPDES Permit No.:
PA0025615 Renewal application due 180 days Prior to expiration.
This permit will expire on:
October 31, 2026 Actual Intake Flow Cooling Water Make-Up Water Slowdown Volume Cycles of Actual Through Withdrawal Concentration Screen Velocity Day MGD MGD Million Gallons MIiiion Gallons fps 1
1.6 2
1.56 3
1.7 4
1.62 5
1;65 6
1.64 7
1.28 8
1.6 9
1.24 10 1.55 11 1.58 12 1.52 13 1.6 14 1.35 15 1.33 16
- 1.24 17 1.35 18 1.28 19 1.39 20 1.53 21 1.57 22 1.53 23 1.49 24 1.51 25 1.47 26 1.48 27 1.38 28 1.39 29 1.39 30 1.55 31 1.54 Average 1.5 Maximum 1.7 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By: James Harvey License No.: --,-,---------------
Title:
Senior Environmental Specialist Date:
8/8/2024
3800-FM-BCW0010 2/2020 SUPPLEMENTAL REPORT - COOLING WATER INTAKE MONITORING Facility Name:
Beaver Valley Power Station - Unit 2 Month:
_J_ul...,Y _______ _
Year:
2024 Municipality:
Shippingport Borough County:
- Beaver NPDES Permit No.:
PA0025615 Watershed:
20-8 20-D Renewal application due 180 days orior to expiration.
This permit will expire on:
October 31, 2026 Actual Intake Flow Cooling Water Make-Up Water Blowdown Volume Cycles of Actual Through Withdrawal Concentration Screen Velocity Day MGD MGD Million Gallons MIiiion Gallons fps 1
2.13 2
2.08 3
2.3 4
2.23 5
2.27 6
2.38 7
2.16 8
2.3 9
2.26 10 2.22 11 2.15 12 2.09 13 2.19 14 2.01 15 2.26 16 2.23 17 2.25 18 2.21 19 2.11 20 2.09 21 2.15 22 2.14 23 2.05 24 2.08 25 1.99 26 2.04 27 2.06 28 2.06 29 2.11 30 2.11 31 2.06 Average 2.2 Maximum 2.4 I certify under penalty of law that this document was prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel gather and evaluate the information submitted. Based on my Inquiry of the person or persons who manage the system or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowl.edge and belief, true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations. See 18 Pa. C.S. § 4904 (relating to unswom falsification).
Prepared By: James Harvey
Title:
Senior Environmental Specialist License No.:
Date:
_8_/1_2/:_2_0_2_4 ___________ _
L-24-199 ATTACHMENT 1
Clamicide Report Attachment for NPDES Permit No. PA0025615 Beaver Valley Power Station August 2024 ATTACHMENT 1 Clamicide Application Report L-24-199 The following summarizes the clamicide treatment for the control of Asian clams and Zebra mussels conducted in July 2024 at Beaver Valley Power Station.
2024 DOSING Parameter Unit 1 B Train Unit 1 A Train Unit 2 A Train Unit 2 B Train Date 7 /23/24 09:54 7/9/24 09:35 7 /30/24 09: 15 7/16/24 12:10 Chemical Used1 248 pounds3 545;1 pounds3 745 pounds3 689 pounds3 Outfall 001 H150M ND ND ND ND Concentration Outfall 003 H150M ND ND N/A4 N/A4 Concentration Outfall 010 H150M N/A4 N/A4 ND ND Concentration Outfall 001 Detox 1,043 pounds 1,043 pounds 1,243 pounds 1,043 pounds Used2 Outfall 001 TSS 2.7 mg/L 2.8 mg/L 3.3 mg/L 2.9 mg/L Concentrations Outfall 003 Detox 150 pounds 150 pounds N/A4 N/A4 Used2 Outfall 003 TSS 35 mg/L 29.3 mg/L N/A4 N/A4 Concentrations Outfall 010 Detox N/A4 N/A4 51.8 pounds 42.9 pounds Used2 Outfall 010 TSS N/A4 N/A4 1.4 mg/L 1.2 mg/L Concentrations
- 1. The chemical used is NALCO H150M; LIMITS: 7,000 pounds per day and No Detectable (ND) amount at Outfalls 001, 003 and 010.
- 2. The Bentonite Based Detoxifying Agent used is NALCO 1315 a slurry mixture and/
or NALCO 36 a dry product; LIMITS:~ 35 mg/I at Outfalls
- 3. Total product weight. Active ingredient is 50% of product by volume.
- 4. Outfall does not receive wastewater from the target system.
- 5. Calculated value
- Attachment 1 END -