Insp Repts 50-413/87-37 & 50-414/87-37 on 871102-06. Violation Identified.Major Areas Inspected:Fire Protection/ Prevention & Followup on Previously Identified Open Items
ML20236Y477
Person / Time
Site: Catawba  Duke Energy icon.png
Issue date: 11/30/1987
From: Conlon T, Wiseman G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20236Y459 List:
References
50-413-87-37, 50-414-87-37, NUDOCS 8712140020
Download: ML20236Y477 (12)


Text

--__ - _ - _ _ -

/ja aro ug UNITED STAT 6S D

NUCLEAR REGULATORY COMMISSION o

["-

E FiEGloN H n

' y

,, j 101 MAR ETTA STREET, N.W.

  • y.

-

ATLANTA. GloRGI A 30323

[

+,

+..+

'

lieport Nos.:

50-413/87-37 and 50-414/87-37 l

Licensee: Duke Power Company 422 South Church Street Charlotte, NC 28242 Docket Nos.

50-413 and 50-414 License Nos.:

NPF-35 and NPF-52 Facility Name:

Catawba 1 and 2 Inspection Conducted:

November 2-6, 1987 Inspector:

8 /. ace

///M/D G. R. Wiseman Dhte Signed Accompanying Personnel-D.

C., Ward h// f T E l Cbnl on, CTi'i e f

-

6/ D

/ /- Ef O m9

' '

Approved by Date Signed Plant Systems Section Division of Reactor Salety SUNMARY Scope:

This routine, unannounced inspection was in the areas of Fi re Protection / Prevention and followup on previously identified cpen items.

Results:

One violation was identified, Violation Item - 413, 414/87-37-01 - Unqualified Personnel Assigned to Fire Brigade Duty.

l l

G

_-m.__._._.m_

. _ _ _ _

- _ ___

I l

-

.

I

REPORT DETAILS 1.

Persons Contacted i

Licensee Employees

  • W. Anfin, Jr., CNS/NPD/MM
  • J. Barbour, QA Manager, Operations -DPC
  • M. Brady, NPD/0PS l
  • B. Caldwell, CNS/ Station Service Support

"

  • W. Carrol, NPD/CNS/ Security
  • J.

Cherry, QA Specialist - ISI

  • T. Crawford, CNS/IS
  • J. Cox, Training Manager i
  • J. Glenn, NPD/TS Compliance
  • T. Hilderbrand, QA Supervisor

'

  • D.

Miller, QA, Catawba

  • S. Mode, CNS/ Safety
  • J. Roach, CNS/ Security
  • J. Starkley, NPD/CNS/MNT/IAE
  • D. Tower, NPD/0PS Other licensee employees contacted included construction craftsmen, engineers, ter hnicians, operators, mechanics, security force members, and j

office personnel, j

NRC Resident Inspectors K. VanDoorn I

M. Lesser

]

  • Attended exit interview

.

i 2.

Exit Interview The inspection scope and findings were summarized on November 5, 1987, with those persons indicated in paragr.aph I above.

The inspector described the areas inspected and discussed in detail the inspection findings.

No dissenting coinn:ents were received from the licensee.

The following new item was identified during this inspection:

Violation Item (413, 414/87-37-01). Unqualified Personnel Assigned to Fire j

Brigade Duty paragraph 5.e(1).

'

The licensee did not identify as proprietary any of the materials provided

{

to or reviewed by the inspector during this inspection.

!

s l

w

. -

_ _ _ _ _ - _

- _ - - - _ - _ -

.

$

}

3.

Licensee Action on Previous Enforcement Matters This subject was not addressed in the inspection.

4.

Unresolved Items Unresolved items were not identified during this inspection.

5.

Fire Protection / Prevention Program (64704)

a.

Fire Prevention / Administrative Control Procedures

!

The inspector reviewed the following Fire Prevention / Administrative Procedures:

Procedure No.

Title-l CNS Station Directive 2.12.1 Fire Protection Program and (Revision 6)

Fire Reporting Procedure CNS Station Directive 2.12.2 Fire Brigade Organization, (Revision 6)

Training, and Responsibilities CNS Station Directive 2.12.5 Control of Combustibe Material (Revision 6)

CNS Station Directive 3.3.9 Hot Work Procedure (Revision 3)

CNS Station Directive 3.11.1 Housekeeping and Cleanliness (Revision 12)

Levels in Safety-Related Areas Based on this review, it appears that the above procedures meet the NRC guidelines of NUREG-0800, Section 9.5.1,

" Standard Review Plan Fire

-

Protection Program."

b.

Fire Protection Surveillance Procedures The inspector reviewed the following Fire Protection System Surveillance Procedures:

Procedure No.

Title j

IP/0/0/3540/02 DC Emergency Lighting (ELD) System Periodic Maintenance and Testing MP/0/A/7650/66 Auxiliary Feedwater Pumps - CO 2 Cylinder Weight PT/0/A/4400/01A Exterior Fire Protection Functional i

Capacity Tests - Fire Pumps A, B, and 18 Months PT/0/A/4400/01H Fire Door Inspection j

PT/0/A/4400/01M Monthly Visual Inspection of Fire Hose PT/0/A/4400/015 RY Fire Protection Flow Periodic Test

- _ _ -__ -_ __-

--

_.

.

'

Procedure No.

Title (cont'd)

PT/1/A/4450/012 Auxiliary Feedwater Pump Room High Pressure CO Cylinder Weig'nt

Determination PT/2/A/4450/13A Unit

Auxiliary Turbine Driven Feedwater Pump Room CO System Annual

Test PT/2/A/4450/13B Unit 2 Auxiliary Feedwater Pump Room j

CO Weekly Test

2 PT/2/A/4450/130 Unit 2 Auxiliary Feedwater Pump CO2 System Semi Annual Test The above surveillance procedures were reviewed to determine if the various test outlines and inspection instructions adequately implement the surveillance requirements of the plant's Fi re Protection Technical Specifications.

In addition, these procedures were reviewed to determine if the inspection and test instructions followed general industry fire protection practices, NRC fire-protection program guidelines and the guidelines of the National Fire Protection Association (NFPA) Fire Codes.

Based on this review, it appears that the above procedures are satisfactory, c.

Fire Protection System Surveillance Inspections and Tests The inspector reviewed the following surveillance inspection and test records for the dates indicated:

i Procedure No.

Test Records PT/0/A/4400/01A 5/84 to 7/86 PT/0/A/4400/d14 Daily Records 5/1/87 to 7/31/07 Monthly Records 7/87 to 11/87 PT/0/A/4400/01M 1/87 to 11/87 PT/0/A/4400/015 7/7/84 PT/0/A/4450/13B 5/86 to 10/87 PT/2/A/4450/13D 8/86 to 9/87

,

The surveillance test record data and testing frequency associated with the above fire protection system surveillance test / inspections I

were found to be satisfactory with regard to meeting the requirements j

of the plant's Fire Protection Technical Specifications.

d.

Fire Protection Audit The most recent audit reports of the Catawba Nuclear Station Fire Protection Program were reviewed.

These audits were:

Annual QA Audit NP-86-25 (CN) March 10 - April 7,1986 Triennial QA Audit NP-87-26 (CN) March 6 - June 1, 1987

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

_-

- -

-

.__-_ _____ _ _ __ _ __ _ _ -

-

.

-

.

I

'

l l

These audits identified several fire protection program discrepancies

'

and unresolved items, and recommended several program improvements.

l The licensee has either implemented the corrective actions associated with these audit findings or a scheduled date for completion of the carrection actions had been established. The licensee appears to be taking the appropriate corrective actions on these audit findings.

e.

Fire Brigade

(1) Organization i

.

'

The total s+.ation fire brigade is composed of approximately 85 personnel from the Operation and Security staff.

The on duty shift fire captain is normally an Assistant Shift Supervisor and the remaining four fire brigade members are composed of security personnel.

The licensee is presently - recognizing the fire brigade membership to eliminate security personnel participation, j

The fire brigade will be made up completely of personnel from

'(

the operations staff. This transition is scheduled to occur in December 1987.

The inspector reviewed the on duty shifts for the months of September and October 1987, to verify that sufficient qualified fire brigade personnel were on duty to meet the provisions of the plant's Fire Protection Program. The inspectors identified that on several occasions during the months reviewed unqualified personnel were assigned fire brigade duty.

Two security personnel who were removed from fire brigade duty when security reduced it's participation in the fire brigade and did not participate in the required training and one security member was removed for health reasons; however, these personnel were assigned brigade duty in the recurity journal.

This is identified as Violation Item (413, 414/87-37-01), Unqualified

Personnel Assigned to Fire Brigade Duty.

I l

(2) The inspector reviewed the training and drill records for five

'

brigade leaders and thirteen brigade members for 1986 and 1987.

The records reviewed indicated thr.t each of these leaders and members had received an annual medical review, attended the required training and participated into the required number of drills.

The inspector also veriiied that a fire brigade drill had been conducted quarterly for each shift for 1986 and 1987.

The fire brigade training records which were inspected were found satisfactory, i

..

_ -. _ _ - - - - _ -

..

,

.

,

  • t l

(3)

Fire Brigade Fire Fighting Strategies

The inspector reviewed the following plant fire fighting

-

strategies:

Strategy No.

Title 1.17 Unit 1 Cable Room 1.31 Unit 1 Interior Doghouse

!

1.32 Unit 1 Exterhor Doghouse l

1.60 Unit 1 Auxiliary Feedwater Pump Panel

'

2.12 Unit 2 Essential Switchgear Room 2.17 Unit 2 Switchgear Room i

2.60 2A Diesel generator Room Based on this review, the inspector determined that the above

fire fighting strategies adequately addressed the fire hazards I

in the area, the type of fire extinguishants to be utilized, the

,

,

direction of attack, systems in the room / area to be managed in l

order to reduce fire damage, heat sensitive equipment in the room / area, and specific fire brigade duties with regard to smoke control and salvage. The inspector recommended that in a future

!

'

revision of the fire fighting strategies, they be upgraded to include a description of redundant safe shutdown equipment located within the area.

The description should include precautions to be taken to ensure fire fighting activities do

,

not inadvertently disable this equipment.

l I

(4)

Fire Reports

'

The inspectors reviewed the station fire reports for 1985, 1986 and 1987.

These reports are designated in Station Directive 2.12.1, Enclosure 6.1.

These reports indicated that there were seven incidents of fire in 1985, two fire events in 1986, and three events so far in 1987.

Of the fire events reviewed, approximately one-half of the events involved equipment failures and the remainder involved welding cr cutting activities.

None of the fire events reviewed appeared to be of major safety significance.

,

l-( 5 ) Fire Brigade Drill During this inspection, the inspector witnessed an unannounced I

fire brigade drill.

The drill fire scenario was a fire in the l

Unit 1 Exterior Doghouse which was apparently caused by a welding operation which ignited the trash in a 55 gallon drum in the area.

I

,

.

1

)

i Five fire brigade members and two technical assistants responded

to the pending fire emergency.

The brigade assembled outside the exterior doghouse in full protective firefighting turnout clothing and self contained breathing apparatus.

An initial j

size-up of the fire condition was made by the fire brigade

'

captain and one lh inch fire attack hose lines were advanced.

into the area.

The fire attack hose lines were placed in service on the fire and the fire was placed under control in twelve minutes.

In addition, the fire brigade initiated five victim search and rescue, smoke control, and water control operations.

The fire brigade utilized proper manual firefighting methods and reacted to the fire drill scenario in an effective and efficient manner.

f.

Plant Tour and Inspection of Fire Protection Equipment (1)

Inspection of Fire Brigade Manual Fire Fighting Equipment The inspector performed an inspection of the fire brigade equipment, consisting of fire hose, nozzles, tools, and miscellaneous equipment, stored at the fire brigade equipment response location located in the Turbine Building.

A total of 12 sets of turnout gear (coats, boots, helmets, etc.),12 sets of self contained breathing apparatus, and 12 spare air cylinders are stored at the fire brigade equipment response location.

Based on this inspection, the designated fire brigade equipment appeared to be properly maintained and stored in a ready condition.

(2) Outside Fire Protection Walkdown The inspoctor verified that the fire pump suction intake structure from the Wyle lake was in service and met the requirements of the Technical Specifications. The three fire pumps were inspected and found to be in service.

The following sectional control valves in the outside fire protection water supply system and CO system were

inspected and verified to be properly aligned and locked in position:

Valve No.

Function 1RYO2 Fire Pump A Discharge Valve IRYO9 Fire Pump C Discharge Valve IRY14 Fire Pump B Discharge Valve

,

IRYl8 North Loop Tie In Sectional Valve

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _

- - _ _ _ _

_ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ - _ _ _ _ _ __

_-

.

  • Valve No.

Function (cont'd)

1RY103 South Loor Tie In Section Valve IRY138 North Auxiliary Building Lead In IRY139 South Auxiliary Building Lead In 1RY199 West Lead In to SSS 1RY200 East Lead In to SSS 1RY65 West Lead In to Unit 1 Turbine Bldg.

1RY67 East Lead In to Unit 1 Turbine Bldg.

1RF819 Unit 1 Diesel Generator CO Isolation

2RF817 Unit 2 Diesel Generator CO Is lation

P.RF819 Unit 2 Diesel Generator CO Isolation

The following fi re hydrants and fire hydrant equipment i

houses were inspected:

Hydrant 12 Hose House 20-0HC Hydrant 25 Hose House 33-OHC Hydrant 26 Hydrant 30 Hose House 9-OHH Hydrant 32 Hose House 7-OHCH The equipment houses contained the minimum equipment requirement. of that specified by NFPA-24, Private Fi re Service Mains and Their Appurtenances, and/or the FSAR commitments.

The equipment appeared to be adequately maintained.

A tour of the exterior of the plant indicated that sufficient clearance was provided between permanent safety-related buildings and structures and temporary buildings, trailers, and other transient combustible materials. The general housekeeping of the areas adjacent

,

to the permanent plant structures were satisfactory.

l (M Permanent Plant Fire Protection Features A plant tour was made by the inspector. During the plant tour, the following safe shutdown related plant area and their related fire protection features were inspected:

l Fire Area Description j

k

Unit 2 Motor Driven Auxiliary

)

Feedwater Pump Area J

Unit 1 Motor Driven Auxiliary

,

l Feedwater Pump Area i

l

Unit 2 Battary Rooms l

Unit 1 Battary Rooms l

Unit 2 KCW Pump Area l

l

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _ _

... _ _ _ _ _ _ _..

.__

. _ _ _ _. _. _ _ _. _

_. _ _ _

_ _ _

_._.

._

j

.

Fire Area Description (cont'd)

Unit 2 Essential Switchgear Room

,

Unit 1 Essential Switchgear Room

32 Unit 1 Train A Shutdown Panel Room

Unit 1 Train B Shutdown Panel Room

Unit 1 Turbine Driven Auxiliary Feedwater Pu:ap Panel The fire / smoke detection system, manual fire fighting equipment (i.e.,

portable extinguishers, hose stations, j

etc.) and the fire area boundary walls, floors and ceiling I

associated for the above plant areas were inspected and verified to be in service or functional.

The automatic sprinkler systems installed in for Unit 2 KCW Pumps and the CO system installed in Unit 1 and Unit 2

Motor Driven Auxillary Feedwater Pump Pits were inspected and found to be in service.

Based on this inspection, it appears that the fire protection features associated with the above plant area are satisfactorily maintained.

The plant tour also verified the licensee's implementation of the fire prevention administrative procedures.

The control of combustibles and flammable materials, liquids and gases, and the general housekeeping were found to satisfactory in the areas inspected.

Two welding operations were observed on 594' elevation of Turbine building. An approved " Hot Work" permit had been issued for each of the welding operations and the work practices met the licensee's fire prevention control procedures.

(4) Appendix R Fire Protection Features j

)

The inspector visually inspected the fire rated raceway fire barriers required for compliance with Appendix R.

Section III.G.2 in the following plant areas:

Fire Area Description.

Unit 2 Motor Driven Auxiliary Feedwater Pump Room

Unit 1 Motor Driven Auxiliary Feedwater Pump Room

)

_ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ - _ _ _ _ _

_ _ _ _

. _ _ _ _ _

_ _ _ _ _ _ _ _ - _

!

l

'

.

g l'

l Based on the inspector. observations of the above raceway

]

fire barrier enclosures, it appears that the one hour fire barrier integrity associated with the above fire barrier assemblies was being properly maintained in a satisfactory condition.

The inspector made a _ walkdown of the Appendix R related sprinkler and CO protection in the following plant areas:

Fire Area D_escription

Unit 2 Motor Driven Auxiliary i

Feedwater Pumps I

Unit 1 Motor Driven Auxiliary Feedwater Pumps

Unit 2 KCW Pumps Based on this walkdown, the inspector determined that the sprinkler protection provided for the areas identified i

)

above provided sufficient protection with respect to controlling an exposure fire.

"

The following eight-hour emergency lighting units were inspected:

Unit Column Line Unit / Elevation 88-49 Unit 1 Auxiliary Building 560 BB-51 Unit 1 Auxiliary Building 560 88-54 Unit 1 Auxiliary Building 560 BB-60 Unit 2 Auxiliary Building 560 BB-62 Unit 2 Auxiliary Building 560 88-63 Unit 2 Auxiliary Building 560

]

EE-46 Unit 1 Auxiliary Building 577

']

BB-51 Unit 1 Auxiliary Building 577 These units were in service, lamps properly aligned and appeared to be properly maintained.

l Except as noted above, within the areas inspected, no additional violations or deviations were identified.

6.

Inspector Followup Items j

i a.

(Closed) Inspector Followup Item (414'85-50-06), Procedures Required

!

for Functional Test of Hydrogen Gas Excess Flow Valve:

A review was made of the hydrogen gas piping systems to the drain i

tank for the reactor coolant pumps.

This piping extends from two cylinders in the bulk gas storage building located outside the plant I

l i

i

-- - - - - _ _ _ _ _ - _ - _ _ _ - - _ _

I

.

'

structures through underground piping in the yard and exposed piping in the auxiliary and reactor buildings to the drain tank. An excess flow valve has been installed in the distribution piping at the cylinders to limit the maximum hydrogen concentration in the event of a line break to less than 2? in the effected area. The inspectors verified that the excess flow valves (Dragon Model 15600-15SW) were installed.

The licensee provided the ir,spectors with manufacturers documentation of performance tests for each of the two excess flow check valves

)

installed on the Hydrogen blank supply headers. The test results are below the shut-off flow requiremcats for the system. Also, the valve

drawing No.15600 indicates that the valves are of all corrosive i

resistant stainlets steel construction and that, as such, need not be otherwise tested.

Based on the above licensee information and evaluation, this item is considered closed.

b.

(Closed) Inspector Followup Item (414/85-66-01, No Fire Detection System or Interior Fire Hose System and No Fire Hazards Analysis Provided for D6ghouses - Fire Areas 48 and 50:

By letter dated March 19, 1986, the licensee transmitted to NRC Region II a Fi re Hazards Analysis for Fire Areas 48 through 51.

Because the Fire Hazards Analysis contained deviations from NRC staff guidelines, the analyses were forwarded by the Region to the Office of Nuclear Reactor Regulation for further review.

By letter dated September 28, 1987, NRR provided Region II with a Supplemental Safety Evaluation Report (SSER) which concludes that the level of fire protection in the above fire area represents an acceptable deviation from Branch Technical Position CMEB 9.5.1 and, therefare, this item is considered closed.

c.

(0 pen) Inspector Followup Item (413/86-39-02 and 414/86-42-02),

Conduct 18-Month Capacity Test of Fire Pump at 100?J and 150% of Rated Volume:

During this inspection PT/0/A/4400/01A, change No.14 was revies d.

This test had not been revised since it was last performed on March 14, 1986.

The licensee stated that test procedure PT/0/A/4400/01A

,

will be revised in the near future to incorporate the inspectors suggestions for fire pump testing prior to it being performed for the

'[

next required Technical Specification period (by February 5,1988).

This ittm will remain open and will be reviewed during a future i

inspection.

d.

(Closed) Inspector Followup Item (413/80-39-01 and 414/86-42-01),

Revise Procedure for Control of Combustible Materiils to Permit Improved Implementation:

The inspectors reviewed Procedure Station Directive 2.12.5,

,

i Revision 6, Control of Combustible Materisi.

Tne procedure was revised to include details for implementat'.an of a ggod program for

,

____m_.

_ _. _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _ _ _ - _ _ _ _ _ _ _ _ _ _

- - _ _ - _ - - _ _

_

__ _

..

control of combustibles in the plant. The inspectors walkthrough of the plant indicated that housekeeping within safety related areas of the plant to be satisfactory. Based upon the procedure review and plant walkthrough, this item is considered closed.

i l

J

_ _ _

,